SUMMARY FAN DATA SHEET

Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

NALTRF-B2G - Roof Mounted Ducted Inlet Twinfan,


Direct Drive, Single Phase
Roof Mounted Ducted Inlet Twinfan
Fan Code:
NALTRF4-B2G
Installation Manual Links:
671268
Required Duty:
168 l/s @ 150 Pa
Actual Duty:
177 l/s @ 166 Pa
Actual at Required Flow:
168 l/s @ 178 Pa
Nominal Fan Speed:
Electrical Supply:
Nominal Motor Rating:
Motor Current:
Motor Current:

1,260 RPM
1 Phase
0.328 kW
flc: 1.3 A
sc: 5.5 A

Max. Operating Temp.:

60C

Project Details

ALUDEIED BASE 7851 A


Location: EF-A1 -

Specification
External roof mounted twin fan unit manufactured from aluzinc. Outlet
grilles are positioned on opposite sides of the fan casing to prevent
wind pressures effecting fan performance. Fan assemblies
incorporate forward curved centrifugal impellers directly driven by
BS5000 motors fitted with airflow fail monitors. Fans are suitable for
operation in ambient temperatures up to 60C. All units are suitable
for internal and external use and may be installed up to a maximum
angle of 5. (Care must be taken to ensure the back draught dampers
operate correctly).

Fan Dimensions

Sound Data

kg

1,165
980
575
250
31
The drawing is for dimensional purposes only. Dimensions in mm.

Performance Curve
350

300

250

200

150
Static Pressure (Pa)

Acoustic perfomance to BS848 Part 2.2 and AMCA 300.


Inlet Noise (dBA): 43 dBA @ 3m (90% of Max Pa)
Outlet Noise (dBA): 52 dBA @ 3m (90% of Max Pa)
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Induct Inlet
73 68 63 60 56 55 52 50
Open Outlet
81 76 70 63 66 62 59 56
Values shown are for inlet Lw and outlet Lw sound power levels for:
Installation Type C: ducted inlet, free outlet. Ratings include the effects
of duct end correction.
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

100

50

0
50
100
Volume Flow Rate (l/s)

150

200

250

300

SUMMARY FAN DATA SHEET


Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

Project Details

Wall Mounted Axial - Supply or Extract


Fan Code:
XS12WA
Installation Manual Links:
671051
Required Duty:
282 l/s @ 0 Pa
Actual Duty:
530 l/s @ 0 Pa
Actual at Required Flow:
282 l/s @ 55 Pa
Motor Input Power:
0.105 kW
Specific Fan Power:
0.2 W/(l/s)
Nominal Fan Speed:
4 Pole 1,370 RPM
Electrical Supply:
1 Phase
Nominal Motor Rating:
0.1 kW
Motor Current:
flc: 0.44 A
Motor Current:
sc: 1.32 A

Location: EF-A2 -

XS - Wall Mounted Extract Fan

Max. Operating Temp.:

ALUDEIED BASE 7851 A

Specification
Wall mounted extract fan, manufactured from ABS material. The fan is
to have an externally weather louvre and a thermally actuated antibackdraught shutter at the rear of the fan and the impeller at the front.
The fans are controlled via a full range of integral sensors matched to
an external remote controller providing on/off, extract, variable / fixed
economy speed, auto / manual functions.

Fan Dimensions

60C

Sound Data

kg

370
420
420
46
9.4
The drawing is for dimensional purposes only. Dimensions in mm.

Performance Curve
125

100

75

50
Static Pressure (Pa)

Inlet Noise (dBA): 47 dBA @ 3m


Outlet Noise (dBA): 46 dBA @ 3m
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Open Inlet
57 63 65 62 64 61 55 48
Open Outlet
63 67 68 61 62 60 55 46
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

25

0
100
200
Volume Flow Rate (l/s)

300

400

500

600

SUMMARY FAN DATA SHEET


Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

Project Details

NALTF - Duct Mounted Twin Fan,


Direct Drive, Single Phase
Duct Mounted Twinfan
Fan Code:
Installation Manual Links:
Required Duty:
Actual Duty:
Actual at Required Flow:

ALUDEIED BASE 7851 A


Location: EF-A3 -

NALTF5

Specification

671267
335 l/s @ 175 Pa
335 l/s @ 175 Pa
335 l/s @ 175 Pa

Nominal Fan Speed:


Electrical Supply:
Nominal Motor Rating:
Motor Current:
Motor Current:

1,140 RPM
1 Phase
0.375 kW
flc: 1.3 A
sc: 5.5 A

Max. Operating Temp.:

50C

Sound Data
Breakout Noise (dBA): 37 dBA @ 3m (90% of Max Pa)
Breakout level is spherical. For hemi-spherical add 3 dBA.
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Induct Inlet
77 72 66 60 57 54 51 47
Induct Outlet
83 78 71 65 63 59 58 54
Values shown are for inlet Lw and outlet Lw sound power levels for:
Installation Type D: ducted inlet, ducted outlet. Ratings include the
effects of duct end correction.
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

Performance Curve

kg

700
970
476
250
57.5
The drawing is for dimensional purposes only. Dimensions in mm.

300

250

200

150
Static Pressure (Pa)

Fan Dimensions

350

100

50

Duct mounted twinfan unit for internal use, with a high efficiency
forward curved centrifugal impeller, sensors fitted in each scroll
monitor air flow, detect and signal flow failure. Direct drive motors
fitted with thermal protection and manufactured to BS5000. Class B
insulation and sealed for life bearings. Air is discharged into a
common outlet plenum chamber through separate shutter system
which prevents blow back through the standby fan. The casing is
manufactured from galvanised steel, internal faces of the case are
lined with flame retardant acoustic material. The fan unit incorporates
an integral auto-changeover controller which provides 6 hour duty
shared operation and automatic selection of the standby fan should
the duty fan fail. Fault indication to a remote fail indicator (supplied) is
provided via volt free contacts of a relay. The integral run-on timer
allows the fan to run-on for a pre-determined time after the initial
source (eg. coupled light switch) has been switched off. The run-on
period is adjustable between 1 and 60 minutes.

0
100
Volume Flow Rate (l/s)

200

300

400

SUMMARY FAN DATA SHEET


Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

Axus Long Case with Access Door. Class F ambient, 240V


1ph 50Hz TEFC IP55, with a PTC. Aluminium impeller.
Galvanised steel case.
Fan Code:
AX40F-41A1Z-02/T
Installation Manual Links:
Required Duty:
Actual Duty:
Actual at Required Flow:
Fan Input Power:
Maximum Fan Input Power:
Motor Input Power:
Specific Fan Power:
Nominal Fan Speed:
Electrical Supply:
Nominal Motor Rating:
Motor Current:
Motor Current:
Overload Setting:
Motor Frame Size:
Blade Angle:
Max. Operating Temp.:

671220
325 l/s @ 150 Pa
336 l/s @ 160 Pa
325 l/s @ 162 Pa
0.137 kW
0.137 kW
0.253 kW
0.8 W/(l/s)
4 Pole 1,370 RPM
240 V 1 Phase 50 Hz
0.18 kW
flc: 1.5 A
sc: 4 A
1.65 A
63
25
60C

Project Details

ALUDEIED BASE 7851 A


Location: EF-A4 -

Selected Ancillaries
1 x CMB40

Mounting bracket (pair)

Specification
Axus 400mm diameter long cased circular axial flow fan with access
door manufactured from pre-galvanised mild steel. Fan incorporates
inlet and outlet flanges with pre-drilled bolt holes and an external
standard safe area terminal box Wiring provided to case.. Impeller
blades manufactured from aluminium mounted in an aluminium hub as
standard. The motor is 240V single phase, single speed, totally
enclosed fan-cooled, protected to IP55, foot mounted, class F
insulated and has sealed for life bearings. The motor is fitted with a
PTC. NOTE: This unit cannot be inverter
speed controlled.

Fan Dimensions

Sound Data

400

490

kg

440

270

370

12

450

290

340
23
The drawing is for dimensional purposes only. Dimensions in mm.

Performance Curve
175

150

125

100

75
Static Pressure (Pa)

Acoustic perfomance to BS848 Part 2.2 and AMCA 300.


Breakout Noise (dBA): 37 dBA @ 3m
Breakout level is spherical. For hemi-spherical add 3 dBA.
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Induct Inlet
70 69 74 70 68 66 61 53
Induct Outlet
80 71 76 68 67 66 61 54
Open Inlet
58 62 70 69 67 66 61 53
Open Outlet
69 63 72 67 67 65 61 54
Breakout
58 51 63 48 44 52 50 38
Noise calculated at actual duty of fan.
Values shown are for inlet Lw and outlet Lw sound power levels for:
Installation Type D: ducted inlet, ducted outlet. Ratings include the
effects of duct end correction.
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

50

25

0
200
Volume Flow Rate (l/s)

400

600

800

SUMMARY FAN DATA SHEET


Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

NALTRF-B2G - Roof Mounted Ducted Inlet Twinfan,


Direct Drive, Single Phase
Roof Mounted Ducted Inlet Twinfan
Fan Code:
NALTRF8-B2G
Installation Manual Links:
671268
Required Duty:
630 l/s @ 175 Pa
Actual Duty:
742 l/s @ 243 Pa
Actual at Required Flow:
630 l/s @ 261 Pa
Nominal Fan Speed:
Electrical Supply:
Nominal Motor Rating:
Motor Current:
Motor Current:

960 RPM
1 Phase
1.406 kW
flc: 6.3 A
sc: 50 A

Max. Operating Temp.:

60C

Project Details

ALUDEIED BASE 7851 A


Location: EF-A5 -

Specification
External roof mounted twin fan unit manufactured from aluzinc. Outlet
grilles are positioned on opposite sides of the fan casing to prevent
wind pressures effecting fan performance. Fan assemblies
incorporate forward curved centrifugal impellers directly driven by
BS5000 motors fitted with airflow fail monitors. Fans are suitable for
operation in ambient temperatures up to 60C. All units are suitable
for internal and external use and may be installed up to a maximum
angle of 5. (Care must be taken to ensure the back draught dampers
operate correctly).

Fan Dimensions

Sound Data

kg

1,495
1,125
710
500
162
The drawing is for dimensional purposes only. Dimensions in mm.

Performance Curve
450
400
350
300
250
200

Static Pressure (Pa)

Acoustic perfomance to BS848 Part 2.2 and AMCA 300.


Inlet Noise (dBA): 61 dBA @ 3m (90% of Max Pa)
Outlet Noise (dBA): 68 dBA @ 3m (90% of Max Pa)
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Induct Inlet
78 73 70 71 73 73 71 66
Open Outlet
91 86 82 81 80 78 77 74
Values shown are for inlet Lw and outlet Lw sound power levels for:
Installation Type C: ducted inlet, free outlet. Ratings include the effects
of duct end correction.
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

150
100
50
0

0
400
Volume Flow Rate (l/s)

800

1200

1600

SUMMARY FAN DATA SHEET


Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:info@nuaire.co.uk
UK Commercial Enquiries T:029 2085 8200 UK Residential Enquiries T:029 2085 8500 International Enquiries T:+44.29 2085 8497
Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.
This data sheet produced on 13 Nov 2016 12:54 using software version 3.2.00.0351 - 20-October-2015

Technical Data

Project Details

NALTF - Duct Mounted Twin Fan,


Direct Drive, Single Phase
Duct Mounted Twinfan
Fan Code:
Installation Manual Links:
Required Duty:
Actual Duty:

ALUDEIED BASE 7851 A


Location: EF-A6 -

NALTF6

Specification

671267
340 l/s @ 200 Pa
404 l/s @ 282 Pa

Nominal Fan Speed:


Electrical Supply:
Nominal Motor Rating:
Motor Current:
Motor Current:

1,104 RPM
1 Phase
0.65 kW
flc: 3.63 A
sc: 8 A

Max. Operating Temp.:

50C

Sound Data
Breakout Noise (dBA): 39 dBA @ 3m (90% of Max Pa)
Breakout level is spherical. For hemi-spherical add 3 dBA.
Sound Power Levels re 1 pWatts (Hz):
Hz
63 125 250 500 1k
2k
4k
8k
Induct Inlet
76 71 65 59 63 62 60 54
Open Outlet
79 74 66 67 72 71 67 61
Values shown are for inlet Lw and outlet Lw sound power levels for:
Installation Type C: ducted inlet, free outlet. Ratings include the effects
of duct end correction.
Please note that the noise data stated on this data sheet for the unit
and/or silencer is tested in accordance with UK, European and
International industry laboratory standards. However onsite conditions
may vary and we would recommend that this information is verified by
an acoustic specialist in order to ensure its suitability for the intended
application.

Duct mounted twinfan unit for internal use, with a high efficiency
forward curved centrifugal impeller, sensors fitted in each scroll
monitor air flow, detect and signal flow failure. Direct drive motors
fitted with thermal protection and manufactured to BS5000. Class B
insulation and sealed for life bearings. Air is discharged into a
common outlet plenum chamber through separate shutter system
which prevents blow back through the standby fan. The casing is
manufactured from galvanised steel, internal faces of the case are
lined with flame retardant acoustic material. The fan unit incorporates
an integral auto-changeover controller which provides 6 hour duty
shared operation and automatic selection of the standby fan should
the duty fan fail. Fault indication to a remote fail indicator (supplied) is
provided via volt free contacts of a relay. The integral run-on timer
allows the fan to run-on for a pre-determined time after the initial
source (eg. coupled light switch) has been switched off. The run-on
period is adjustable between 1 and 60 minutes.

Fan Dimensions

Performance Curve
A

350

300

250

200

Static Pressure (Pa)

150

100

50

kg

700
970
476
400
62.5
The drawing is for dimensional purposes only. Dimensions in mm.

0
100
200
Volume Flow Rate (l/s)

300

400

500

600

700