Sei sulla pagina 1di 36

ACS 1000

Medium voltage AC drives


315 to 5000 kW
400 to 6700 hp

Engineering guidelines
Input circuit breaker control

Document No.:

3BHS104785 ZAB E01, Rev. G

Issued

ABB Switzerland Ltd. All Rights Reserved.

08.08.2014

The information in this document is subject to change without notice.


This document and parts thereof must not be reproduced or copied, or disclosed to third parties, nor
used for any unauthorized purpose without written permission from ABB Switzerland Ltd, Medium
Voltage Drives.

2/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


Table of contents
Table of contents ................................................................................................................. 3
Table of figures .................................................................................................................... 5
Notice of changes................................................................................................................ 6
1 General .............................................................................................................................. 7
1.1
1.2
1.3

Scope of the document ................................................................................................... 7


References ..................................................................................................................... 7
Standards ....................................................................................................................... 7

2 System components overview ........................................................................................ 8


3 ICB requirements............................................................................................................ 10
3.1
3.2

MCB requirements .........................................................................................................10


Protection relay requirements ........................................................................................11

4 MCB control .................................................................................................................... 12


4.1
4.2
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.5
4.4
4.4.1
4.4.2
4.4.3
4.5
4.6
4.6.1
4.6.2
4.6.3

Closing the MCB ............................................................................................................12


Opening / tripping the MCB............................................................................................12
MCB control signal.........................................................................................................13
MCB logic terminology ...............................................................................................13
Control signals ...........................................................................................................13
Signal settings for control signals ...............................................................................14
MCB tripping loop.......................................................................................................15
Fast MCB trip by the converter ...................................................................................16
MCB control interface rating ..........................................................................................17
Standard MCB control interface .................................................................................17
Optional MCB control interface with relays .................................................................17
Optional MCB control interface with relays and open circuit monitoring......................19
Fused input contactor option..........................................................................................21
Local and remote MCB control ......................................................................................22
Remote control via digital inputs.................................................................................22
Remote control via serial interface .............................................................................23
Diagram local and remote control...............................................................................24

5 Fault and alarm messages............................................................................................. 25


5.1
Fault messages .............................................................................................................25
5.1.1
MCB disturbed ...........................................................................................................25
5.1.2
MCB control ...............................................................................................................26
5.1.3
Tripping loop ..............................................................................................................26
5.2
Alarm messages ............................................................................................................27
5.2.1
MCB not available ......................................................................................................27
5.2.2
MCB discrepancy .......................................................................................................27

ACS 1000

3BHS104785 ZAB E01, Rev. G

3/36


6 Connection diagrams .................................................................................................... 28
6.1
Safety function category ............................................................................................... 28
6.2
Control configurations ................................................................................................... 28
6.2.1
One high active coil to close, open and trip the MCB ................................................ 30
6.2.2
One high active coil to close and one low active coil to open / trip the MCB .............. 31
6.2.3
One high active coil to close and one high active coil to open / trip the MCB............. 33
6.2.4
Two high active coils to close and open and one low active coil to trip the MCB ....... 34
6.3
Special cases ............................................................................................................... 35
6.3.1
MCB functions as a grounding isolator switch ........................................................... 35
6.3.2
Reoccurring emergency off caused by open circuit monitoring .................................. 36

4/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


Table of figures
Figure 1: System components overview ........................................................................................... 8
Figure 2: Overview ICB timing .........................................................................................................10
Figure 3: Contact wiring of the control interface relays ....................................................................18
Figure 4: Wiring with optional interface relays .................................................................................19
Figure 5: Wiring of the interface monitoring relays ...........................................................................20
Figure 6: Wiring of the fused input contactor ...................................................................................21
Figure 7: Local and remote control ..................................................................................................24
Figure 8 Wiring with one High Active Coil to Close, Open and Trip the MCB, Standard MCB
Interface ..........................................................................................................................................30
Figure 9: Wiring with one high active coil to close, open and trip the MCB, MCB interface relays....31
Figure 10: Wiring with one high active coil to close and one low active coil to open / trip the MCB,
standard MCB interface ...................................................................................................................32
Figure 11: Wiring with one high active coil to close and one low active coil to open / trip the MCB,
MCB interface relays .......................................................................................................................32
Figure 12: Wiring with one high active coil to close and one high active coil to open / trip the MCB,
MCB interface relays .......................................................................................................................33
Figure 13: Wiring with one low active coil to trip the MCB, standard MCB interface.........................34
Figure 14: Wiring with one low active coil to trip the MCB, MCB interface relays .............................35
Figure 15: MCB and GND isolator feedback wiring..........................................................................36

ACS 1000

3BHS104785 ZAB E01, Rev. G

5/36


Notice of changes
Rev.
index

Page / chapter

Description

Date
Dept. / name

General revision
(Revision C replaces all former versions of
this document)

09-01-19
ATD1-M / Rees

20 / 4.4.2
21 / 4.4.3

Correction to Figures 3 and 4

10-04-23
ATD1-M /
Muehlberg

39 - 41 / Chapter 6
21 / 4.4.2
General

Addition of wiring examples


Addition of internal MCB control voltage
General corrections/improvements

11-05-30
ATD1-M /
Muehlberg

17 - 20 / Chapter 4

Removal of externally supplied U R

13-07-10
ATD1-M /
Muehlberg

14 / 4.3.1
14-15 / 4.3.2
16 / 4.3.4
19-20 / 4.4.3
36 / 6.3.2

Addition of section
Small corrections
Small corrections
Update to option functionality added
Addition of section

14-08-07
DMDR-P /
Muehlberg

ACS 1000

3BHS104785 ZAB E01, Rev. G

6/36


1 General
1.1

Scope of the document


This document is a guideline for engineering and design of the ICB (Input
Circuit Breaker) and the control of it.
The ICB combines the switching device MCB (Main Circuit Breaker) and
the protection relay.
The ICB is a major protection device of the drive system and connects /
disconnects the main power supply to the drive.
This engineering guideline provides information about the interface
between the ACS 1000 and ICB as well as information on the
requirements for the MCB or fused contactor from a hardware
performance and a control point of view,
This document replaces the following ACS 1000 documents:

1.2

3BHS197846, Specification for MCB

3BHS104785, Application Note Tripping loop

References
[1]

3BHS213402 ACS 1000A Technical Data Sheet


3BHS213403 ACS 1000W Technical Data Sheet
3BHS213404 ACS 1000i Technical Data Sheet

[2]

3BHS112321 E44 ACS 1000 Signal& Signal Table for MSOH 4xxx
3BHS112321 E50 ACS 1000 Signal& Signal Table for MSOI 5xxx

1.3

3BHS103412 ACS 1000 Type Code

[4]

3BHS125149 E81 Technical Specification MCB Protection Design


Requirements

[5]

3BHS230517 Main Circuit Breaker Design for VSD

Standards

IEC 60204-1
IEC 60204-11
ISO13849-1 / EN-954-1

ACS 1000

[3]

Safety of machinery - Electrical equipment of machines - Part 1:


General requirements
Refers to IEC 60204-1 for control circuit requirements
Safety of machinery - Safety-related parts of control systems Part 1: General principles for design

3BHS104785 ZAB E01, Rev. G

7/36


2 System components overview
The Variable Speed Drive (VSD) system consists of:

ICB (Input Circuit Breaker)

Converter power transformer

Frequency converter

Motor

MCB

Feeder

MCB control
interface

Protection

ICB
CT

Converter
power
transformer

Frequency
converter
Local MCB
control

Motor

VSD system control


interface (remote
MCB control)

Figure 1: System components overview


The ICB consists of:

Switch gear enclosure

MCB (Breaker or fused contactor)

CTs (Current transformers)

Protection relay

The MCB is controlled by the frequency converter. The closing command


is given exclusively by the frequency converter, since the MCB has to be
interlocked with the VSD system.

ACS 1000

3BHS104785 ZAB E01, Rev. G

8/36


The protection relay of the ICB is used for:

Transformer primary cable protection

Transformer protection

Transformer secondary cable protection

Backing up the frequency converter protection

In some cases a thermal motor protection relay can also trip the MCB.
This feature is required by certain standards.
For more information about requirements and functionality of the MCB,
please see the following document:
3BHS230517 Main Circuit Breaker Design for VSD [5]

ACS 1000

3BHS104785 ZAB E01, Rev. G

9/36


3 ICB requirements
In case of a failure (e.g. short circuit) on the cabling on the transformer
primary winding, the ICB must detect the fault instantaneously and clear
it.
Short circuit occurs
Open and / or trip command is set at the
frequency converter control output

No further damage of frequency converter

No hazard to personnel

Max. protection trip time


Max. safety trip time

Figure 2: Overview ICB timing


The time required to open the MCB is limited due to the fuseless design
of the ACS 1000. In order to prevent any hazard to personnel, the ICB
must detect and break a transformer secondary side 3-phase short-circuit
within:
Max. safety trip time = 250 ms (1)
In order to prevent further damage to the frequency converter, e.g. diode
failures, the MCB must break after the open / trip command has been
initiated (including opening and arcing time) within:
Max. protection trip time = 120 ms
For more information about requirements and functionality of the MCB,
please see the following document:

3.1

3BHS230517 Main Circuit Breaker Design for VSD [5]

MCB requirements
Based on IEC, NEMA and local standards, which define the major
characteristics and requirements, the MCB has to be specified and
selected according to:

The rated primary voltage of the converter transformer

The primary current of the converter transformer

If the fault clearing time of the MCB is longer the mains network data (max. short circuit capacity, voltage)
and the transformer data of the drive (power, impedance) have to be checked with the ACS 1000 feeder
factory, whether a longer clearing time (Max protection trip time) can be tolerated.

ACS 1000

3BHS104785 ZAB E01, Rev. G

10/36

The line short-circuit current

The MCB must be able to:

Make and carry nominal load currents

Clear short-circuit currents.

The MCB shall be opened within Max. protection trip time (see Figure 2)
in response to an open / trip command of the ACS 1000 control.
The control interface has to be specified in accordance with the selected
control scheme. The common control schemes are described in 6
Connection diagrams.
As a minimum, a MCB feedback signal indicating MCB status closed is
required.
Optional MCB feedback signals are:

Relay output indicating MCB status open

Relay output indicating MCB status available


i.e.: main circuit breaker not in test position, not drawn out or not
faulty.

See section 4.3.3 Signal settings for control signals for more details about
MCB signals.

3.2

Protection relay requirements


The protection relay must be able to:

Detect a short-circuit in the transformer primary cable *

Detect a short-circuit on the transformer primary side *

Detect a ground fault on the transformer primary side

Tolerate the transformer inrush current without tripping

* not required when the MCB is a fused contactor


The setting of the protection relay has to be determined based on the
project specific transformer data.
The ACS 1000i is always equipped with a transformer protection relay
and CTs for transformer protection. The line side cabling between the
feeder and the ACS 1000i input terminals is not covered by the
ACS 1000i protection relay.
For more information about protection relay requirements and a typical
protection scheme, please see the following document:
3BHS125149 E81 Technical Specification MCB Protection Design
Requirements [4]

ACS 1000

3BHS104785 ZAB E01, Rev. G

11/36


4 MCB control
4.1

Closing the MCB


All the following conditions have to be fulfilled in order to close the MCB:

No trip (initiated by hardware or software) is active.

The ACS 1000 internal grounding switch must be open.

The input disconnector (optional) must be closed.

The MCB must be in operating position (i.e. racked in and available


for closing).

The MCB must have been open for at least 5 seconds before it can
be closed again.

The closing command will be released by the frequency converter upon


request if all the above conditions are fulfilled. Additional project specific
conditions may be required.
The closing command for the MCB must be given exclusively from the
frequency converter. The closing command will be given upon a closing
request to the ACS 1000 control. The closing request or command can be
initiated from a local or a remote control location (see section 4.6 Local
and remote MCB control).
The time delay for closing the MCB is monitored. See section 4.3.3 Signal
settings for control signals for more details about MCB signals.

4.2

Opening / tripping the MCB


The following signals open / trip the MCB:

A signal from the tripping loop (see 4.3.4 MCB tripping loop)

A signal from the ACS 1000 application control software initiated by


the control door pushbutton, a digital input signal, or fieldbus system,
depending on the ACS 1000 Signal settings
o

An external MCB open command request is not accepted while


the ACS 1000 is running and will be ignored until the motor is
stopped.

A signal from the ACS 1000 interface board (hardware or software


protection)

A signal from a trip-circuit directly wired to the MCB

The MCB shall be opened within Max. protection trip time (see Figure 2)
in response to an open / trip command. See chapter 3 ICB requirements.

ACS 1000

3BHS104785 ZAB E01, Rev. G

12/36


4.3

MCB control signal

4.3.1

MCB logic terminology


In this document, when referencing MCB coil control logic, the terms high
active and low active are used. These terms can also be written as
energize to activate and de-energize to activate, respectively.
As an example, a low active trip command or coil refers to a trip circuit
which is energized under normal operation. Removal of power causes a
trip action.
A high active close command or coil refers to a close circuit which is deenergized under normal operation. Application of power causes a close
action.

NOTICE
A slash / before the signal name indicates an inverted signal. For
example MCB ORD CLOSE indicates that the logic is high active or
energize to close, whereas /MCB ORD OPEN indicates that the logic
is low active or de-energize to open. This indication can also be found in
standard and project specific wiring diagrams.

4.3.2

Control signals
The following table shows the ACS 1000 digital inputs (DI) and outputs
(DO) on the standard I/O boards IOEC1 (-A5191) and IOEC2 (-A5201)
provided for the control of the MCB.

ACS 1000

3BHS104785 ZAB E01, Rev. G

13/36

4 MCB control

Table 1: MCB control I/Os


Type

Terminal
Standard

Signal name

Remarks

Optional**

IOEC2, DI 10
(DI 2.10)

X12 / 9
X12 / 10

MCB STATUS CLOSED

status feedback from MCB

IOEC2 DI 9
(DI 2.9)

X12 / 7
X12 / 8

MCB STATUS OPEN

status feedback from MCB

IOEC2 DI 11
(DI 2.11)

X13 / 1
X13 / 2

MCB STATUS AVAILABLE

status feedback, indicating that the MCB is


not faulty, drawn-out or in test position

IOEC2 DO 6
(DO 2.6)

X26 / 1
X26 / 2
X26 / 3

X310 / 3
X310 / 4
X310 / 5

Inversed signal
Common
MCB ORD CLOSE

drive command to close the MCB (pulse or


steady state signal, see Signal 21.06 MCB
Control Mode*)

IOEC2 DO 5
(DO 2.5)

X25 / 1
X25 / 2
X25 / 3

X310 / 6
X310 / 7
X310 / 8

Inversed signal (high active)


Common
/MCB ORD OPEN (low active)

drive command to open the MCB (pulse or


steady state signal, see Signal 21.06 MCB
Control Mode*)

Inversed signal (high active)


Common
/MCB ORD TRIP (low active)

wired to the tripping loop

X300 / 3
X300 / 11

X310 / 9
X310 / 10
X310 / 11

IOEC1, DO6
(DO 1.6)

* see section 4.3.3 Signal settings for control signals

4.3.3

Signal settings for control signals


The Signals of Signal group 21 (see ACS 1000 Signal & Signal Table [2])
listed in Table 2 have to be selected depending on the signals required by
the MCB.

14/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


Table 2: MCB control Signal
Parameter and
Signal

Setting

Meaning of the setting

Remarks

21.06
MCB
OnControlMode
(O)

0 = ONE
SIGNAL

one output used for opening and closing


(continuous signal)

IOEC2 DO6 (DO 2.6) = 1 MCB is


closed
IOEC2 DO6 (DO 2.6) = 0 MCB is
opened

1 = TWO
SIGNALS

21.07
MCB
FeedbackSig
(O)

0 = ONE
SIGNAL

one output for opening is used

IOEC2 DO5 (DO 2.5) = 0 MCB is


opened
(This signal can also be inverted using
optional relays, see 4.4.2 and chapter
6 for info.)

one output for closing used


(pulse signal*)

IOEC2 DO6 (DO 2.6) = 1 MCB is


closed

Only feedback MCB closed is monitored

IOEC2 DI10 (DI 2.10) = 0 MCB


status open
IOEC2 DI10 (DI 2.10) = 1 MCB
status closed

1 = TWO
SIGNALS

Feedback MCB open and MCB closed


are monitored

IOEC2 DI9 (DI 2.9) = 1 MCB status


open
IOEC2 DI10 (DI 2.10) = 1 MCB
status closed

21.08
MCB
AvailableSig (O)

1 = NO

Feedback MCB available not used

2 = LOW
ACTIVE

Feedback MCB available is used

IOEC2 DI11 (DI 2.11) = 0 MCB is


available

3 = HIGH
ACTIVE

Feedback MCB available is used

IOEC2 DI11 (DI 2.11) = 1 MCB is


available

21.09
MCB
CloseTimeLim

1 to 30 sec

Time allowed for the MCB to close

default setting is 3s

21.10
MCB
OpenTimeLim

1 to 30 sec

Time delay after which the signal MCB


ORD TRIP is initiated if the MCB does not
open upon an opening command

default setting is 3s

*The pulse signal will remain high until either the MCB Closed feedback
is given (IOEC2 DI10) or the MCB Close time limit runs out (Signal group
21.09, default 3s, max 30s).
For further details see ACS 1000 Signal & Signal Table [2].

4.3.4

MCB tripping loop


The tripping loop is a hard-wired circuit, tripping the MCB if the loop is
interrupted. The tripping loop is wired from terminals X300:3 to X300:11
(See chapter 6 Connection diagrams).
The signals wired to the tripping loop are monitored. Table 3 shows the
digital inputs and the corresponding tripping loop terminals.

ACS 1000

3BHS104785 ZAB E01, Rev. G

15/36

4 MCB control

Table 3: Tripping loop monitoring


Signals

IOEC board
input

Tripping loop
terminals

CDP control panel fault


message

Emergency off**

IOEC 1 DI05

X300 / 5
X300 / 6

EmergOff

Transformer protection trip

IOEC 1 DI13

X300 / 7
X300 / 8

ExtTrafProt

Motor protection trip*

IOEC 3 DI10

X300 / 9
X300 / 10

ExtMotProt

Tripping loop monitoring:


If one of the above listed signals is low or
if one of the digital inputs is defective

IOEC 1 DI14

TrippLoop

*IOEC 3 (-A5211) required


**The Emergency Off signal may also be wired via safety relay. See
project specific wiring diagram for connection details.

4.3.5

Fast MCB trip by the converter


The digital outputs DO5 and DO6 of IOEC 1 (-A5191) and IOEC 2
(-A5201) are controlled by:

the ACS 1000 control software

the hardware protection of the ACS 1000

The hardware protection (realized on the ACS 1000 INT-board) is


enabled by a soldering joint on the IOEC boards. The hard-coded
protection comprises internal HW and SW supervision and triggers the
following digital outputs:

DO1.6 /MCB ORD TRIP

DO2.5 /MCB ORD OPEN

DO2.6 MCB ORD CLOSE

Remark:
DO1.5 (MOTOR HEATER ORDER ON) is also controlled by the HW
protection circuit. This is not relevant for the MCB control. It is also not
required from a functional point of view, but it allows the same board
configuration to be used for IOEC 1 and IOEC 2.
The fiber optic link between INT board and IOEC board uses failsafe low
active logic.

NOTICE
Each of the IOEC boards 1 and 2 has the above mentioned soldering
joint when the drive leaves the factory. The soldering joint must be
conducting on the new board if a board is replaced.

16/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


4.4

MCB control interface rating

4.4.1

Standard MCB control interface


The standard ACS 1000 MCB control interface is designed for the
following voltage range:
U MCB = 22..250 Vac
U MCB = 22..150 Vdc
Table 4 gives an overview of the switching capacity of the digital output of
the standard ACS 1000 MCB control interface.
Table 4: IOEC digital output switching capacity
MCB control voltage
(U MCB )

Switching current

Continuous current

24 Vdc

8A

6A

24 Vac

8A

6A

48 Vdc

1A

1A

48 Vac

8A

6A

120 Vdc

0.4 A

0.4 A

120 Vac

8A

6A

230 Vac

8A

6A

The limitation is given by the IOEC board. Refer to the ACS 1000
Technical data sheet [1] for more information.
The ACS 1000 can be equipped with additional relays if a higher
switching capacity is required. Refer to the following section for more
information.

4.4.2

Optional MCB control interface with relays


The interface relays -K5321, -K5322, and -K5323 are controlled by the
standard MCB control DOs (see section 4.4.1 Standard MCB control
interface) using the internally supplied relay control voltage (U R ) supplied
with the internal 27 Vdc bus via an internal isolated DC to DC power
supply to the standard tripping loop input terminals -X300:3/4. See Figure
4 for wiring details. U R can be selected as either 24 Vdc or 48 Vdc. Refer
to position 202, MCB Interface in the ACS 1000 Type Code [3], Revision
L or higher for ordering information.
The switching capacity for the interface relays is given in Table 5.
Connection examples for the interface relays are given in 6 Connection
diagrams.

ACS 1000

3BHS104785 ZAB E01, Rev. G

17/36

4 MCB control

Table 5: Switching capacity of interface relay


MCB control voltages (U MCB )

Switching current*

Up to 240 Vac

16 A

Up to 48 Vdc

16 A

110 Vdc

10 A

125 Vdc

8A

220 Vdc

4A

*The relays used are:

ABB AL9-22 (1SBL143501R8x00, x depends on whether 24 Vdc or


48 Vdc is selected.),

The contacts 1/2 with 7/8 and R5/R6 with R3/R4, respectively, are
connected in series.
X310:3/6/9
X310:4/7/10

R5

R6

R4

R3

X310:5/8/11

Figure 3: Contact wiring of the control interface relays


The project specific switching capacity depends on the inductance of the
MCB coils.

18/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


-X300

-X310
internal tripping loop
wiring (24 or 48 Vdc)

internal wiring

internal wiring
X27_P3

3
emergency off

UR

-S5151
(on front door)

DC
24V or
48V

DC
X27_N3

5
emergency off
6
7

MCB order close


3

(one or more emergency off


connected in series)

R3

-K5321

4
R5

5
8

transformer
protection trip

/ MCB order open

/ MCB order trip

R3

motor protection trip

X26:1

-A5191
(IOEC1 / DO06)

-K5322

10

7
R5

X26:2

11

external wiring, for


MCB command coil
connection details,
see Chapter 6
Conntection Diagrams

X26:3

/ MCB order trip


-K5323

9
R3

10
R5

11
7

Figure 4: Wiring with optional interface relays

4.4.3

Optional MCB control interface with relays and open circuit monitoring
Open circuit monitoring for the open and trip circuit between the ACS
1000 and the MCB can be added if the MCB is equipped with high active
open / trip coils. This option is only available when 48 Vdc tripping loop
voltage is selected for the character MCB Interface in the ACS 1000
Type Code [3], Revision L or greater.

NOTICE
This option is only functional with a U MCB voltage range of 40-220 Vdc.
The relays will not function with 24Vdc or any AC voltage leve.
Protection category 3 (ISO 13849-1) can be achieved, depending on the
MCB control wiring (see 6 Connection diagrams).
The ABB SPER 1B1 C4 monitoring relay is used for this function. See the
respective Data Sheet (www.abb.com) for more information.
The relays K5322 and K5323 are energized during normal operation,
meaning their contacts R5/R6 and R3/R4 are open and will close,
energizing the MCB coils upon an open / trip command. Because of this
high active logic, the ACS 1000 is not able to open / trip the MCB if the
wire between the ACS 1000 and the MCB is disconnected or severed.

ACS 1000

3BHS104785 ZAB E01, Rev. G

19/36

4 MCB control

The monitoring relays induces a small current (< 5 mA) through the open /
trip circuit of the MCB. An alarm / trip will be generated after
approximately 3 seconds at terminal X314 (see Table 3) if this current
cannot maintained in either of the respective circuits, enabling the
operator to initiate corrective measures.
A second pair of contacts from monitoring relays F5331 and F5332 are
wired together in parallel to the tripping loop. When an open circuit fault is
detected in both the MCB order open and trip circuits, the tripping loop
voltage is removed and an Emergency Off fault is generated.
The SPER relays themselves cannot detect the difference between an
open circuit because of a line break or because of a real MCB open / trip
command. In order to avoid false open circuit alarms or faults, auxiliary
contacts from relays K5322 and K5323 are wired directly to time delay
relays K5331 and K5332, respectively. Contacts from these time delay
relays are wired into both the open circuit monitoring alarm and trip
circuits to bypass the signals when an MCB open / trip command is
active.

NOTICE
Time delay relays K5331 and K5332 should be set to an off delay of 1s
in order to verify that the Tripping Loop digital inputs correctly register
the open circuit trip.

-F5331 /
-F5332

Trip contacts of -F5331


and -F5332 wired in
parallel to Tripping Loop

Open/Trip
Alarm

-R5322 /
-R5323

X314:1/2
X314:3/4

SPER

MCB
X310:6/9
X310:7/10

UMCB

R5

R6

R4

R3

X310:8/11

-K5322 / -K5323

Figure 5: Wiring of the interface monitoring relays


Table 6: Interface monitoring relay signals
Terminal

Signal

Remark

X311:1
X311:2

common
MCB ORD open circuit Alarm

MCB Order open circuit monitoring alarm

X311:7
X311:8

common
MCB ORD trip circuit Alarm

MCB Trip circuit monitoring alarm

20/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


4.5

Fused input contactor option


A fused input contactor can be optionally mounted into the ACS1000i
cabinet. With this configuration, the entire ICB (see Figure 1) is internally
wired.
This option is only available for ACS 1000i and only up to either 6.6 kV or
6.9 kV input voltages, depending on the type of contactor chosen. For
more information refer to position 25, Input Contactor, fused in the ACS
1000 Type Code [3]. For wiring details see Figure 6.
Relays -K5311 and -K5312 are controlled by the standard MCB order trip
and MCB order close DOs (see section 4.3.2 Control signalsControl
signals) with the internal 27 Vdc bus via an internal isolated DC to DC
power supply. These relay contacts provide the commands for the fused
input contactor -Q1011, which serves as an internal MCB.
An auxiliary contact from fused input contactor -Q1011 is also internally
wired directly to the MCB Closed feedback IOEC 2 (-A5201) DI10.

internal wiring

internal wiring

-X300
3

emergency off

DC

DC
24 Vdc

-S5151
(on front door)

X27_P3
X27_N3

110/230 Vac

emergency off

(one or more emergency off


connected in series)

6
7
transformer
protection trip

external tripping
loop wiring

/ MCB order trip


-K5311

MCB order close


-K5312

medium voltage
feeder

24 Vdc

9
/ MCB order trip
X26:1

-A5191
(IOEC1 / DO06)

motor protection trip


10

fused input contactor


(Internal MCB)
-Q1011

X26:2
X26:3

MCB order close


X26:1

-A5201
(IOEC1 / DO06)

X26:2

N
-K5311

-K5311

integrated transformer
-T1101

X300:4

X26:3

IOEC2 DI10

MCB CLOSED

Figure 6: Wiring of the fused input contactor

ACS 1000

3BHS104785 ZAB E01, Rev. G

21/36

4 MCB control

4.6

Local and remote MCB control


The close and open command for the MCB can be given to the ACS 1000
from a local or remote control location.

Local:
The MCB can be closed or opened by using the pushbuttons on the
control section door of the drive when local is selected on the control
panel CDP 312.
Exception: The MCB can also be opened and closed via the pushbuttons
on the control section door when the drive is in remote control, provided
that Signal 11.04 (11.05) in the ACS 1000 Signal and Signal Table [2] is
set to 1 = NOT SEL.
Remote:
The MCB can be closed or opened via the digital inputs on IOEC 2 or via
a serial interface (i.e. Modbus) when remote is selected on the control
panel CDP 312.

NOTICE
Local operation can be disabled by digital input IOEC2 DI 14 (DI2.14)
(high active).

4.6.1

Remote control via digital inputs


The ACS 1000 software offers the possibility to close / open the MCB
from one or two remote control locations.
Commands from these two stations cannot be given simultaneously in
case the MCB is controlled by two remote control locations. The active
remote control has to be selected first.
Signal groups 12.02, 11.04 and 11.05 in the ACS 1000 Signal and Signal
Table [2] are provided to make the necessary selections according to the
signal interface (digital inputs and / or fieldbus).

4.6.1.1 Selection of control location


The following control locations can be selected with Signal group 12.02 Ext1/Ext2 Select (O):

Digital input on IOEC 2


o

22/36

This selection is used to switch from control location 1 to


control location 2 and vice versa. In the Signal & Signal
Table the expression EXT1 is used for control location 1
and the expression EXT2 for control location 2.

Control location 1 or control location 2

Control location 1 or 2 via a serial interface

Signal 12.02 is 7 = EXT1 (control location 1)

3BHS104785 ZAB E01, Rev. G

ACS 1000

This is the default selection

4.6.1.2 Selection of digital inputs for the control location


The digital inputs which are to be used to close or open the MCB are
selected with Signal groups 11.04 - Ext1 MCB Control (for control location
1) and 11.05 - Ext2 MCB Control (for control location 2).
The default setting of 11.04 is 9 = DI7P,13P, which means that the digital
inputs DI 2.7 (REM ORD ON-LINE) and DI2.13 (REM ORD OFF-LINE)
are used to close / open the MCB.
In addition to the setting for the selection of the control location it is also
possible to choose whether only one signal is used for opening / closing
or two separate signals with Signal group 11.04.

4.6.2

Remote control via serial interface


The MCB can also be operated via a serial interface. The necessary
setting for Signal 11.04 and 11.05 in the ACS 1000 Signal and Signal
Table [2] is 10 = COMM.MODULE.

ACS 1000

3BHS104785 ZAB E01, Rev. G

23/36

24/36

3BHS104785 ZAB E01, Rev. G

CH0
AMC3-board
Comm. Module

IOEC 2: DI 1...6
DI 7, 13

remote ctrl. location


1&2

IOEC 1: DI 6 OffLine
DI 7 OnLine

push buttons on
control section door

REM

Parameter >

10

Comm.Module
10

Default: DI 7, 13 2...9

Not selected

selection of digital inputs for


control location

11.04
11.05
EXT 2
EXT 1
MCB CONTROL MCB CONTROL

Comm.Module

Default: DI 7, 13 2...9

Not selected

REMOTE

LOCAL

21.06
21.05
MCB
MCB
ON CTRL MODE OPEN SIGNAL

EXT2

EXT1

12.02
EXT 1 / EXT 2
SELECT

21.07
MCB
AVAILABLE

MCB LOGIC

Open/Close

MCB Command

21.08
21.09
MCB CLOSING MCB OPENING
TIME LIM
TIME LIM

IOEC2-DI11
Feedback MCB Status available

Feedback MCB Status closed

IOEC2-DI10

IOEC2-DI9
Feedback MCB Status open

4.6.3

LOC

control panel
CDP 312

4 MCB control

Diagram local and remote control

Figure 7: Local and remote control

ACS 1000


5 Fault and alarm messages
The following fault and alarm messages on the CDP 312 control panel
indicate when there is something wrong in connection with the control of
the MCB.
Fault messages:

MCB disturbed

MCB control

Tripping Loop

Alarm messages:

MCB not available

MCB discrepancy

The fault or alarm word and the signal group and bit are given for the
software version MSOI5000 or later as well as the software version
MSOH 4200 or later. See ACS 1000 Signal & Signal Table [2].

5.1

Fault messages

5.1.1

MCB disturbed

Panel message:

MCB Disturb

Software

MSOI5xxx

MSOH4xxx

Fault word:

3 FC1

Signal group and bit:

9.11 bit 0

9.04 bit 1

Meaning:

Fault message comes up when the MCB opens without receiving a


command from the ACS 1000.

ACS 1000

3BHS104785 ZAB E01, Rev. G

25/36

5 Fault and alarm messages

5.1.2

MCB control

Panel message:

MCB Control

Software

MSOI5xxx

MSOH4xxx

Fault word:

1 FC1

Signal group and bit:

9.09 bit 2

9.04 bit 2

Meaning:

Fault message is displayed under the following circumstances:

5.1.3

When an alarm MCB Discrep occurs while a closing command is


given

When an alarm MCB Discrep occurs while an opening command is


given

In case the ACS 1000 gives the command to close the MCB and the
MCB is not closed within the programmable time frame

In case the ACS 1000 gives the command to open the MCB and the
MCB is not opened within the programmable time frame.

Tripping loop

Panel message:

TrippLoop

Software

MSOI5xxx

MSOH4xxx

Fault word:

1 FC1

Signal group and bit:

9.09 bit 0

9.02 bit 5

Meaning:

The display of the fault message is initiated by the control software which
monitors the tripping loop.
The fault message indicates that:

26/36

The tripping loop is not wired up

At least one of the contacts wired into the loop is open.

3BHS104785 ZAB E01, Rev. G

ACS 1000


5.2

Alarm messages

5.2.1

MCB not available

Panel message:

MCB NotAvl

Software

MSOI5xxx

MSOH4xxx

Alarm word:

Signal group and bit:

9.54 bit 0

9.12 bit 5

Meaning:

The alarm message is enabled by setting Signal 21.08 to low active


or high active.
The alarm message comes up when the MCB signal MCB NOT
AVAILABLE is high and the signal is set to low active.
The alarm message is displayed when the MCB signal MCB NOT
AVAILABLE is low and the signal is set to high active.

Control action

5.2.2

The command to close the MCB is blocked when Signal 21.08 is set
to low active or high active and a corresponding feedback signal is
not available.

MCB discrepancy

Panel message:

MCB Discrep

Software

MSOI5xxx

MSOH4xxx

Alarm word:

Signal group and bit:

9.54 bit 1

9.12 bit 6

Meaning:

The alarm message is displayed when the status of the MCB


feedback signals is not in accordance with the ACS 1000 control
software.
The alarm message comes up under the following conditions:

Control action

Both feedback signals MCB IS OPEN and MCB IS CLOSED


are high

Both feedback signals MCB IS OPEN and MCB IS CLOSED


are low.

The MCB is not opened but the alarm message MCB Discrep is
displayed in case the MCB is closed already and the status of both
feedback signals MCB IS OPEN and MCB IS CLOSED changes to
high or low.
The fault message MCB Control comes up when the alarm MCB
Discrep is pending and the command to close the MCB is released.
The fault message MCB Control comes up and the drive is tripped
via digital output MCB Ord Trip when the alarm MCB Discrep is
pending and the command to open the MCB is given.

ACS 1000

3BHS104785 ZAB E01, Rev. G

27/36


6 Connection diagrams
There are various possibilities for the MCB control wiring, depending on
the number of signals used to close, open and trip the MCB and on the
required safety function category.
The shown connection diagrams are typical for this type of application.
Please read section 4.1 Closing the MCB before reading the following
paragraphs for better understanding.

6.1

Safety function category


The achieved safety function category (ISO 13849-1) of the MCB control
depends on the selected MCB control configuration, the quality of the
used contacts in the tripping loop and the kind of monitoring of the MCB
control circuit.
All proposed MCB control configurations have at least safety function
category 1.
The safety function category achieved depends on the selected
configuration, see section 6.2.1 One high active coil to close, open and
trip the MCB to 6.2.4 Two high active coils to close and open and one low
active coil to trip the MCB.
To achieve safety function category 3 (ISO 13849-1) all contacts in the
tripping loop have to be redundant or the contacts must be designed
according to this category.

6.2

Control configurations
There are four different most common control configurations:
1

One high active coil to close, open and trip the MCB
This is the typical configuration to control a fused contactor. The
control signal is a continuous signal (Signal 21.06 set to one signal).
For connection diagrams refer to section 6.2.1 One high active coil to
close, open and trip the MCB.

One high active coil to close and one low active coil to open / trip
the MCB
This configuration requires a pulsed signal to close the MCB (Signal
21.06 set to two signals).
For connection diagrams refer to section 6.2.2 One high active coil to
close and one low active coil to open / trip the MCB.

ACS 1000

One high active coil to close and one high active coil to open / trip
the MCB

3BHS104785 ZAB E01, Rev. G

28/36


The use of the MCB open circuit monitoring as described in section
4.4.3 Optional MCB control interface with relays and open circuit
monitoring is recommended.
This configuration requires a pulse signal to close the MCB (Signal
21.06 set to two signals).
For connection diagrams refer to section 6.2.3 One high active coil to
close and one high active coil to open / trip the MCB.
4

Two high active coils to close and open and one low active coil to
trip the MCB
This configuration offers the highest safety level and is recommended
in case a new breaker is used.
This configuration requires a pulse signal to close the MCB (Signal
21.06 set to two signals).
For connection diagrams refer to section 6.2.4 Two high active coils
to close and open and one low active coil to trip the MCB.

The selection of one or two signals (continuous or pulse) to be used for


opening and closing the MCB depends on the setting of Signal 21.06 as
shown in Table 2: MCB control Signal.

ACS 1000

3BHS104785 ZAB E01, Rev. G

29/36

6 Connection diagrams

6.2.1

One high active coil to close, open and trip the MCB
In this configuration, the close / open and the trip signal of the ACS 1000
control (see section 4.3.2 Control signals) are connected in series to
achieve redundancy.
The safety function category 3 is achieved if all contacts in the tripping
loop are redundant (refer to section 6.1 Safety function category.
-X300
internal wiring
external wiring
3
emergency off

P/+

-S5151
(on front door)

N/-

U MCB

5
emergency off
6

(one or more emergency off


connected in series)

7
transformer protection trip
8
9
/ MCB order trip
motor protection trip

X26:1

-A5191
(IOEC1 / DO06)

10
X26:2

11
X26:3

MCB order close


X26:1

-A5201
(IOEC2 / DO06)

X26:2
X26:3

MCB closing coil


(High active)
N/-

Figure 8 Wiring with one High Active Coil to Close, Open and Trip the MCB, Standard MCB
Interface

30/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


external wiring

internal wiring
-X310
MCB order close
3
R3

-K5321

U MCB /
Control Voltage

4
R5

5
7

/ MCB order open


6
R3

-K5322

7
R5

8
7

/ MCB order trip


9
R3

-K5323

10
R5

11
7

MCB closing coil


(High active)

N/-

Figure 9: Wiring with one high active coil to close, open and trip the MCB, MCB interface relays

6.2.2

One high active coil to close and one low active coil to open / trip the MCB
In this configuration the open and the trip signal of the ACS 1000 control
(see section 4.3.2 Control signals) are connected in series to achieve
redundancy. The closing command is interlocked with the trip command.
The safety function category 3 is achieved if all contacts in the tripping
loop are redundant (refer to section 6.1 Safety function category.

ACS 1000

3BHS104785 ZAB E01, Rev. G

31/36

6 Connection diagrams
-X300
internal wiring
external wiring
3

P/+

emergency off
4

-S5151
(on front door)

N/-

U MCB

5
emergency off
(one or more emergency off
connected in series)

6
7

transformer protection trip


8
9
/ MCB order trip
motor protection trip

X26:1

-A5191
(IOEC1 / DO06)

10
X26:2

11
X26:3

/ MCB order open

MCB order close


X25:1

-A5201
(IOEC2 / DO05)

X26:1

-A5201
(IOEC2 / DO06)

X25:2
X25:3

X26:2
X26:3

MCB opening coil


(Low active,
undervoltage coil)

N/-

MCB closing coil


(high active)

N/-

U MCB

U MCB

Figure 10: Wiring with one high active coil to close and one low active coil
to open / trip the MCB, standard MCB interface
-X310
internal wiring

external wiring

MCB order close


3
R3

-K5321

R5

MCB closing coil


(High active)

/ MCB order open


6
R3

N/-

-K5322

R5

8
7

MCB opening coil


(Low active,
undervoltage coil)

/ MCB order trip


9
R3

-K5323

10
R5

11
7

N/-

U MCB /
Control Voltage

Figure 11: Wiring with one high active coil to close and one low active coil
to open / trip the MCB, MCB interface relays

32/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


6.2.3

One high active coil to close and one high active coil to open / trip the MCB
In this configuration the open and the trip signal of the ACS 1000 control
(see section 4.3.2 Control signals) are connected in parallel to achieve
redundancy. The closing command is interlocked with the trip command.
This configuration requires the option MCB interface relay (see sections
4.4.2 Optional MCB control interface with relays and 4.4.3 Optional MCB
control interface with relays and open circuit monitoring).

NOTICE
Opening / tripping the MCB by the ACS 1000 is not possible anymore if
a wire supplying the open / trip coil of the MCB with energy is
interrupted.
The safety function category 3 is achieved if all contacts in the tripping
loop are redundant (refer to section 6.1 Safety function category) and if
the MCB circuit monitoring as described in section 4.4.3 Optional MCB
control interface with relays and open circuit monitoring is used.
-X310
internal wiring

external wiring

MCB order close


3
R3

-K5321

R5
7

4
5

/ MCB order open


6

MCB closing coil


(High active)
N/-

R3

-K5322

R5
7

U MCB /
Control Voltage

/ MCB order trip


9
R3

-K5323

R5
7

10
11
MCB opening coil
(High active)

N/-

Figure 12: Wiring with one high active coil to close and one high active
coil to open / trip the MCB, MCB interface relays

ACS 1000

3BHS104785 ZAB E01, Rev. G

33/36

6 Connection diagrams

6.2.4

Two high active coils to close and open and one low active coil to trip the
MCB
The MCB is equipped with separate opening, tripping and closing coils.
Typically the closing and opening coil are high active coils, while the
tripping coil is a low active undervoltage coil.
The closing command is interlocked with the trip command.
The safety function category 3 is achieved if all contacts in the tripping
loop are redundant (refer to section 6.1 Safety function category.
-X300
internal wiring
external wiring
3

P/+

emergency off
4

-S5151
(on front door)

N/-

U MCB

5
emergency off
(one or more emergency off
connected in series)

6
7

transformer protection trip


8
9
/ MCB order trip
motor protection trip

X26:1

-A5191
(IOEC1 / DO06)

10
X26:2

11
X26:3

MCB order close

/ MCB order open


X26:1

-A5201
(IOEC2 / DO06)

-A5201
(IOEC2 / DO05)

X26:2
X26:3

U MCB

U MCB

X25:2

P/+

X25:3

MCB trip coil


(Low active,
undervoltage coil)

N/-

X25:1

MCB closing coil


(high active)

N/-

U MCB

MCB opening coil


(high active)

N/-

U MCB

Figure 13: Wiring with one low active coil to trip the MCB, standard MCB
interface

34/36

3BHS104785 ZAB E01, Rev. G

ACS 1000


-X310
internal wiring

external wiring

MCB order close


3
R3

-K5321

R5
7

4
5

/ MCB order open


6

MCB closing coil


(High active)
N/-

R3

-K5322

R5
7

MCB opening coil


(High active)

/ MCB order trip

N/9
R3

-K5323

R5
7

10

U MCB /
Control Voltage

11

MCB tripping coil


(low active)

N/-

Figure 14: Wiring with one low active coil to trip the MCB, MCB interface
relays

6.3

Special cases

6.3.1

MCB functions as a grounding isolator switch


In certain cases, the MCB can also function as a grounding isolator switch
in order to ground the primary side of the transformer. In this case, an
unwanted MCB Discrep alarm (see Section 5.2.2 - MCB discrepancy)
may come in when the MCB is in the grounded position. This is because
when the MCB is in this position, it sends a MCB IS CLOSED feedback
and removes the MCB IS OPEN feedback. See Figure 15 for wiring
details.
This alarm can be avoided by wiring an additional normally closed MCB
IS GROUNDED contact in series with the MCB IS CLOSED feedback
signal to maintain a closed status when the MCB is grounded. If the MCB
IS OPEN feedback signal is also being used, an additional normally open
MCB IS GROUNDED contact must be wired in parallel.

ACS 1000

3BHS104785 ZAB E01, Rev. G

35/36

6 Connection diagrams

Control Voltage

MCB
CLOSED
feedback
contact

MCB
GROUNDED
feedback
contact

IOEC2
DI10

IOEC2
DI09

MCB CLOSED

MCB OPEN

MCB
OPEN
feedback
contact

Figure 15: MCB and GND isolator feedback wiring


This type of grounding switch functionality often exists in breakers rated
for 33 kV and higher.

6.3.2

Reoccurring emergency off caused by open circuit monitoring


When an emergency off fault is present on the drive but no emergency off
has been pushed, it could be an indication that the open circuit monitoring
is active (see section 4.4.3 Optional MCB control interface with relays and
open circuit monitoring). When an emergency off fault message reoccurs
immediately (within 2-5 seconds) after resetting, check monitoring relays
F5331 and F5332 for fault indication which will be indicated by an LED on
the face of the relays themselves.
If a fault condition exists, check the MCB order open / trip logic circuit for
possible wire disconnection or severed wires.

36/36

3BHS104785 ZAB E01, Rev. G

ACS 1000

Potrebbero piacerti anche