Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
X4.1 Determine the value of the coefficient of coupling ( k) for the transformer of Example
4.7 of the text.
The turns ratio is
a
V1 240
2
V2 120
Based on [4.27],
M
Xm
400
0.5305 H
a 2 60 2
X1
0.18
aM
2 0.5305 1.0615 H
2 60
L2
X2 M
0.045 0.5305
0.2654 H
a 2 60
2
L1 L2
0.5305
1.0615 0.2654
0.999
X4.2 For the ideal transformer circuit of Fig. X4.1, R p 18 , RL 6 , and X l 0.5 . If
V2 1200 V and PS 5600 W , (a) determine the turns ratio a, (b) the source voltage
VS , and (c) the input power factor PFS .
(a)
V 2 120
PRL 2
2400 W
RL
6
2
3200 18
V1 PR p R p
a
240 V
V1 240
2
V2 120
(b)
I2
V2 1200
200 A
RL
6
I1
1
1
I 2 200 100 A
a
2
I S I1
V1
2400
100
23.330 A
Rp
18
(c)
PFS
PS
5600
0.999 lagging
VS I S 240.28 23.33
2400 24
240 V
I 2 PL / RL 2400 / 24 10 A
1
1
I 2 100 10 A
a
10
I S I1
V1
24000
10
1.6670 A
Rp
3600
(b)
X4.4 For the circuit of Fig. X4.1, a 2 , R p 20 , and RL 10 . Determine the percentage of input power PS that is dissipated by R p regardless of the voltage values.
% PS
% PS
V12 / R p 100
V12 / R p V22 / RL
a 2 RL 100
a 2 RL R p
a 2V22 / R p 100
a 2V22 / R p V22 / RL
2 2 10 100
2 2 10 20
66.7%
X4.5 For the circuit of Fig. X4.1, let RL 0 , R p 10 , X l 1 , and a 2 . Determine the
power factor PS .
With RL 0 , V2 0 and V1 aV2 0 ; thus R p is shorted and the input
impedance is j X l . Since I S must lag VS by 90,
PFS cos 90 0 lagging
X4.6 The non-ideal transformer of Fig. X4.2 has three coils each with identical number of
turns N. Terminal pair e-f is open circuit. If terminals b and c are connected together
and Vad 240 V (60 Hz), the input current is 1 A. If terminal pairs a-b and e-f are open
circuit and Vcd 120 V (60 Hz), predict the value of input current. Leakage flux and
coil resistance are to be neglected.
Based on [4.7], the maximum value of mutual flux for the two cases, respectively, is
m
Vad
240
2
Vcd
120
2
Or, the mutual flux has the same value for both cases. Thus, the magnetizing current
and core losses have identical values for both cases. Consequently, the input current
for the second case must also be 1 A.
X4.7 The non-ideal transformer of Fig. X4.2 has three coils each with identical number of
turns. Terminal pair e-f is open circuit. Leakage flux, coil resistance, and core losses
can be neglected. When the two left-hand coils are additively connected in parallel and
Vab 120 V (60 Hz), the input current is 2 A. If the lower coil (terminal pair c-d) is
disconnected (open circuit) and Vab remains 120 V (60 Hz), predict the value of input
current to the single coil.
Based on [4.7], the maximum value of mutual flux for both cases is given by
m
Vab
120
2
Hence, the mmf established for both cases must be identical. For the first case of
parallel-connected coils, the 2 A input current divides equally between the two coils to
produce an exciting mmf of 1 N 1 N 2 N . When one of the two coils is disconnected, the current through the remaining coil must increase to 2 A to produce the
required mmf of 2N. Thus, input current remains 2 A.
X4.8 For the ideal residential distribution transformer of Fig. X4.3, (a) determine current I1 .
(b) Assume that the two series-connected secondary windings are identical and determine the minimum kVA rating of a 2400:240/120 V transformer required to sustain this
load without risk of winding over-temperature.
(a)
I2
2400
120 A
20
I3
1200
I 2 120 120 240 A
10
I1
120
120
120
I2
I3
360 1.80 A
2400
2400
2400
(b) Since I3 is the larger secondary current, the rating is dictated by the lower secondary winding; thus,
S R 2V3 I 3 2 120 24 5.76 kVA
(a) Conclude from the voltage rating that three coils have identical number of turns.
VX 1 VH 3 VH 1 120 V
IX1
VX 1 120
20 A
R2
6
IH 3
VH 3 120
12 A
Z1
10
SR
3000
12.5 A
VH 1H 4 R
240
S R 3000
25 A
VXR 120
From the results of part (a), it is seen that the X 1 -X 2 coil and the H 3 -H 4 coil are
operating within rated current.
1
1
I H1 I H 3
I X 1 12 20 32 A
1
1
Thus, the current of the H1 -H 2 coil significantly exceeds the rated value of 12 A.
X4.10 Determine the value of Ceq for the ideal transformer of Fig. X4.5.
a
X eq
1
1
2
Ceq 1
XC
2
1
4
C C
or
Ceq
1
4
X4.11 The three-winding ideal transformer of Fig. X4.6 has N1 N 2 2 N3 and identical
load resistors (R ) connected across coils 2 and 3. Determine the input impedance Z1
as indicated on Fig. X4.6.
N1 I1 N1 I 2 N1I 3
2
or
1
I1 I 2 I3
(1)
Since the value of flux through all three coils is identical, V1 V2 2V3 . By Ohm's law,
I2
V2 V1
R R
(2)
I3
V3 V1
R 2R
(3)
V1 V1 5V1
R 4R 4R
Hence,
Z1
V1 4
R
I1 5
15,000
125 A
120
(b) The core and copper losses are unchanged from the two-winding transformer.
Po S H PF 315,000 0.8 252 kW
Po 100
Po losses
252,000 100
252,000 280 300
99.77 %
(1)
(2)
I 2 1 20
This described condition can only occur for a leading PF as illustrated by the
phasor diagram of Fig. X4.7. By the Law of Cosines,
cos
V1 2 V2'
I 2' Z eq
'
2V1V2
Then,
240 2 240 2 20.83 0.3795 2
1.887
cos
2 240 240
By application of KVL,
I 2'
20.8219.38
Z eq
0.379571.56
X4.15 Three 100 kVA, 12,470:7200 V, 60 Hz, two-winding transformers are to be connected
to provide 300 kVA, 7200/4160 V service to an industrial customer from the threephase 7200 V distribution mains. (a) Determine the connection arrangement for this
transformer bank. (b) For balanced operation, with an apparent power load of 150
kVA, determine the values of line current on both sides of the transformer bank.
(a) To meet the service agreement of 300 kVA with rated voltages, the transformers
must be connected on the primary side. A wye connection on the secondary side
provides for 7200 V line-to-line and 4157 V (nominal 4160 V) line-to-neutral.
(b) With the transformer bank operating at half rated apparent power capability and
referring to Fig. 4.33d,
I L1
ST
150,000
6.94 A
S VL1
3 12, 470
I L2
ST
150,000
12.03 A
3 VL 2
3 7200
V1
4.44 N1 f
f
60
60 Hz
2000
50
50 Hz
10
is unchanged, the magnetic core will operate at the design level of flux density with
the magnetizing current unchanged. The core losses, being frequency dependent, will
reduce in value, resulting in a cooler operating temperature. Operationally, there is no
problem.
(b) The transformer can still only thermally handle the rated current for the 60 Hz
design case. However, voltage has reduced. Thus,
ST
50
25 kVA 20.83 kVA
60
11