Sei sulla pagina 1di 10

CONTRACTOR

OWNER

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT

F&G CAUSE AND EFFECT MATRIX

DOCUMENT TITLE
DATE:

3/3/2010

DOCUMENT NUMBER

REV: 1

SCH-00-F-0001

CLASS: II

SHEET

01 OF 09

F&G CAUSE AND EFFECT MATRIX

AS-BUILT

3/3/2010

MS

NN

FT

ISSUED FOR CONSTRUCTION

12/12/2007

TS

SN

ShS

ISSUED FOR APPROVAL

11/23/2007

TS

SN

ShS

REV

DESCRIPTION

DATE

PREPARED

CHECKED

APPROVED

CPECC

OWNER

CONTRACTOR

OWNER

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT

DOCUMENT TITLE
DATE:

3/3/2010

DOCUMENT NUMBER

F&G CAUSE AND EFFECT MATRIX


SCH-00-F-0001

REV: 1

CLASS: II

SHEET

01 OF 09

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ1

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 02 OF 09

ESD
2

NOTE

ALARMS

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

TYPE

EFFECT

1.

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

NOTES

TAG

FZ

FZ 1 - Gas Compressor House

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90191

XI-90192

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90101

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90102

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90103

Flammable Gas Detector - Point IR type

GDP-90111

Flammable Gas Detector - Point IR type

GDP-90112

Flammable Gas Detector - Point IR type

GDP-90113

Flammable Gas Detector - Point IR type

GDP-90114

Flammable Gas Detector - Point IR type

GDP-90115

10

Flammable Gas Detector - Point IR type

GDP-90116

X X V X V
X X V X V
X X V X V

X
X
X

X
X
X

X X
X X
X X

V
V
V

V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

V
V
V
V
V
V

V
V
V
V
V
V

V
V
V
V
V
V

11

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

12
Toxic H2S Gas Detector - Electrochemical type

GDX-90121

13

Toxic H2S Gas Detector - Electrochemical type

GDX-90122

14

Toxic H2S Gas Detector - Electrochemical type

GDX-90123

15

Toxic H2S Gas Detector - Electrochemical type

GDX-90124

16

Toxic H2S Gas Detector - Electrochemical type

GDX-90125

17

Toxic H2S Gas Detector - Electrochemical type

GDX-90126

18

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

19
Flame Detector - Triple IR type

FD-90131

20

Flame Detector - Triple IR type

FD-90132

21

Flame Detector - Triple IR type

FD-90133

22

Flame Detector - Triple IR type

FD-90134

23

Flame Detector - Triple IR type

FD-90135

24

Flame Detector - Triple IR type

FD-90136

25

Heat Detector - Rate Compensated

HD-90141

27

Heat Detector - Rate Compensated

HD-90142

28

Heat Detector - Rate Compensated

HD-90143

29

Heat Detector - Rate Compensated

HD-90144

30

Heat Detector - Rate Compensated

HD-90145

31

Heat Detector - Rate Compensated

HD-90146

32

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

V
V
V
V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

V
V
V
V
V
V

X
X
X

X
X
X

X X
X X
X X

X
X
X

X
X
X

X
X
X

X X

26

33
Manual Alarm Callpoint Compressor A

MAC-90151

34

Manual Alarm Callpoint Compressor B

MAC-90152

35

Manual Alarm Callpoint Compressor C

MAC-90153

36
37

Fire Alarm Pushbutton

HS-046

38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ2

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

TYPE

1.

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

NOTES

TAG

FZ

FZ 2 - Compressor Scrubber

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90291

XI-90292

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

EFFECT

CSS Sequence of Events Recorder

Nomenclature
X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

SHEET 03 OF 09

ESD
2

NOTE

ALARMS

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90201

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90202

Flammable Gas Detector - Point IR type

GDP-90211

Flammable Gas Detector - Point IR type

GDP-90212

Flammable Gas Detector - Point IR type

GDP-90213

Flammable Gas Detector - Point IR type

GDP-90214

Flammable Gas Detector - Point IR type

GDP-90215

Flammable Gas Detector - Point IR type

GDP-90216

10

Flammable Gas Detector - Point IR type

GDP-90217

11

Flammable Gas Detector - Point IR type

GDP-90218

12

Flammable Gas Detector - Point IR type

GDP-90219

13

Toxic H2S Gas Detector - Electrochemical type

GDX-90221

15

Toxic H2S Gas Detector - Electrochemical type

GDX-90222

16

Toxic H2S Gas Detector - Electrochemical type

GDX-90223

17

Toxic H2S Gas Detector - Electrochemical type

GDX-90224

18

Toxic H2S Gas Detector - Electrochemical type

GDX-90225

19

Toxic H2S Gas Detector - Electrochemical type

GDX-90226

20

Toxic H2S Gas Detector - Electrochemical type

GDX-90227

21

Toxic H2S Gas Detector - Electrochemical type

GDX-90228

22

Toxic H2S Gas Detector - Electrochemical type

GDX-90229

23

Flame Detector - Triple IR type

FD-90231

25

Flame Detector - Triple IR type

FD-90232

26

Flame Detector - Triple IR type

FD-90233

27

Flame Detector - Triple IR type

FD-90234

28

Flame Detector - Triple IR type

FD-90235

29

Flame Detector - Triple IR type

FD-90236

30

Manual Alarm Callpoint

MAC-90251

32

Manual Alarm Callpoint

MAC-90252

33

Manual Alarm Callpoint

MAC-90253

34

X X V X V
X X V X V

X
X

X
X

X X
X X

V
V

V
V

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

V
V
V
V
V
V
V
V
V

V
V
V
V
V
V
V
V
V

V
V
V
V
V
V
V
V
V

V
V
V
V
V
V
V
V
V

X
X
X
X
X
X
X
X
X

V
V
V
V
V
V
V
V
V

X
X
X
X
X
X
X
X
X

V
V
V
V
V
V
V
V
V

X
X
X
X
X
X
X
X
X

14

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

V
V
V
V
V
V
V
V
V

X
X
X
X
X
X
X
X
X

V
V
V
V
V
V
V
V
V

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

General Notes

24

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

V
V
V
V
V
V

X
X
X

X X
X X
X X

X
X
X

X
X
X

X
X
X

31

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

X
X
X

V
V
V
V
V
V

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ3

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 04 OF 09

ESD
2

NOTE

ALARMS

Notes

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


S

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

S
1

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

2. Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

NOTES

TAG

FZ

FZ 3 - Air Cooled Heat Exchangers

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90391

XI-90392

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET

TYPE

EFFECT

1. Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90301

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90302

Flammable Gas Detector - Point IR type

GDP-90311

Flammable Gas Detector - Point IR type

GDP-90312

Flammable Gas Detector - Point IR type

GDP-90313

Flammable Gas Detector - Point IR type

GDP-90314

Flammable Gas Detector - Point IR type

GDP-90315

X X V X V
X X V X V

X
X

X
X

X X
X X

V
V

V
V

X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

V
V
V
V
V

V
V
V
V
V

V
V
V
V
V

V
V
V
V
V

X
X
X
X
X

V
V
V
V
V

X
X
X
X
X

V
V
V
V
V

X
X
X
X
X

10
Toxic H2S Gas Detector - Electrochemical type

GDX-90321

11

Toxic H2S Gas Detector - Electrochemical type

GDX-90322

12

Toxic H2S Gas Detector - Electrochemical type

GDX-90323

13

Toxic H2S Gas Detector - Electrochemical type

GDX-90324

14

Toxic H2S Gas Detector - Electrochemical type

GDX-90325

15

Flame Detector - Triple IR type

FD-90331

17

Flame Detector - Triple IR type

FD-90332

18

Flame Detector - Triple IR type

FD-90333

19

Manual Alarm Callpoint

MAC-90351

21

Manual Alarm Callpoint

MAC-90352

22

Manual Alarm Callpoint

MAC-90353

23

X
X
X
X
X

X
X
X
X
X

V
V
V
V
V

X
X
X
X
X

V
V
V
V
V

X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

16

X
X
X

X V
X V
X V

X
X
X

X
X
X

X
X
X

V
V
V

X
X
X

X
X
X

X X
X X
X X

X
X
X

X
X
X

X
X
X

20

24

V
V
V

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ4

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 05 OF 09

ESD
2

NOTE

ALARMS

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

Siren for Fire Alarm

Siren for Toxic Gas Alert

Siren for Combustible Gas Alert (High Level)

Siren for Combustible Gas Alert (Low Level)

Beacons for Fire Alarm

Beacons for Toxic Gas Alert

Beacons for Combustible Gas Alert

ESD - Confirmed Fire


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

EFFECT

TYPE

1.

24

25

Energise

23

Energise

Energise
YAS-9XX74

O/O

SS-001

Energise
YAS-9XX73

M ENABLE

SS-002

Energise
YAS-9XX72

M GROUP

Energise

Energise
YAS-9XX71

Energise

Energise
YAB-9XX63

FZ

XI-90492

Energise

TAG

FZ 4 - Filters, Cond Recovery and Flare KO Drum

XI-90491

Energise

YAB-9XX62

NOTES

YAB-9XX61

CAUSE
DESCRIPTION

10 11 12 13 14 15 16 17 18 19 20 21 22

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

26 27 28 29 30 31 32

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

49

50 51 52 53 54 55 56 57 58 59

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90401

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-90402

Flammable Gas Detector - Point IR type

GDP-90411

Flammable Gas Detector - Point IR type

GDP-90412

Flammable Gas Detector - Point IR type

GDP-90413

Flammable Gas Detector - Point IR type

GDP-90414

Toxic H2S Gas Detector - Electrochemical type

GDX-90421

10

Toxic H2S Gas Detector - Electrochemical type

GDX-90422

11

Toxic H2S Gas Detector - Electrochemical type

GDX-90423

12

Toxic H2S Gas Detector - Electrochemical type

GDX-90424

13

Flame Detector - Triple IR type

FD-90431

15

Flame Detector - Triple IR type

FD-90432

16

Manual Alarm Callpoint

MAC-90451

18

Manual Alarm Callpoint

MAC-90452

19

X X V X V
X X V X V

X
X

X
X

X X
X X

V
V

V
V

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

V
V
V
V

V
V
V
V

V
V
V
V

V
V
V
V

X
X
X
X

V
V
V
V

X
X
X
X

V
V
V
V

X
X
X
X

X
X
X
X

X
X
X
X

V
V
V
V

X
X
X
X

V
V
V
V

X
X
X
X

X
X
X
X

X
X
X
X

14

X
X

X V
X V

X
X

X
X

X
X

V
V

X
X

X
X

X X
X X

X
X

X
X

X
X

V
V

17

20
21

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ5

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 06 OF 09

ESD
2

NOTE

ALARMS

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

TYPE

EFFECT

1.

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

NOTES

TAG

FZ

FZ 5 - Gas Compressor Air Intakes


Flammable Gas Detector - Open Path type- Tx, Rx

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90591

XI-90592

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

1
GDT/GDR-90501

X X V X V

X X

X X V X V
X X V X V
X X V X V

X
X
X

X
X
X

X X
X X
X X

V
V
V

V
V
V

3
Flammable Gas Detector - Point IR type

GDP-90511

Flammable Gas Detector - Point IR type

GDP-90512

Flammable Gas Detector - Point IR type

GDP-90513

Manual Alarm Callpoint

MAC-90551

Manual Alarm Callpoint

MAC-90552

X
X

X
X

X X
X X

X
X

X
X

X
X

10
11
12
13
14
15
16
17
18
19
20
21

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ6

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 07 OF 09

ESD
2

NOTE

ALARMS

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

TYPE

EFFECT

1.

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

NOTES

TAG

FZ

FZ 6 - Fuel Gas Skid


Flammable Gas Detector - Open Path type- Tx, Rx

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90691

XI-90692

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

1
GDT/GDR-90601

X X V X V

X X

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

V
V
V
V

V
V
V
V

V
V
V
V

V
V
V
V

3
Flammable Gas Detector - Point IR type

GDP-90611

Flammable Gas Detector - Point IR type

GDP-90612

Flammable Gas Detector - Point IR type

GDP-90613

Flammable Gas Detector - Point IR type

GDP-90614

Toxic H2S Gas Detector - Electrochemical type

GDX-90621

Toxic H2S Gas Detector - Electrochemical type

GDX-90622

10

Toxic H2S Gas Detector - Electrochemical type

GDX-90623

11

Toxic H2S Gas Detector - Electrochemical type

GDX-90624

12

Flame Detector - Triple IR type

FD-90631

14

Flame Detector - Triple IR type

FD-90632

15

X
X
X
X

V
V
V
V

X
X
X
X

V
V
V
V

X
X
X
X

X
X
X
X

X
X
X
X

V
V
V
V

X
X
X
X

V
V
V
V

X
X
X
X

X
X
X
X

X
X
X
X

13

X
X

X V
X V

X
X

X
X

X
X

V
V

X X

V
V

16
Manual Alarm Callpoint

MAC-90651

17
18
19
20
21

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ7

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 08 OF 09

ESD
2

NOTE

ALARMS

Notes

ESD - Confirmed High Gas Detection

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop)

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

EFFECT

TYPE

1.

NOTES

TAG

FZ

FZ 7 - New Slug Catcher


Flammable Gas Detector - Open Path type- Tx, Rx

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-90791

XI-90792

SS-002

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

1
GDT/GDR-90701

X X V X V

X X

X X V X V
X X V X V

X
X

X
X

X X
X X

V
V

V
V

V
V

V
V

3
Flammable Gas Detector - Point IR type

GDP-90711

Flammable Gas Detector - Point IR type

GDP-90712

Toxic H2S Gas Detector - Electrochemical type

GDX-90721

Toxic H2S Gas Detector - Electrochemical type

GDX-90722

Manual Alarm Callpoint

MAC-90751

10

X
X

X V X V
X V X V

X
X

X
X

X
X

X X

11
12
13
14
15
16
17
18
19
20
21

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

OWNER

CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT


F&G CAUSE AND EFFECT MATRIX FZ11

DOCUMENT TITLE:
DOCUMENT NO:

SCH-00-F-0001

REV:

CLASS:

II

SHEET 09 OF 09

ESD
2

NOTE

ALARMS

Notes

2.

Beacons & Sirens tag nos. contains "XX". XX is used


here to identify different fire zones. FZXX includes
following fire Zones:
FZ01 (Gas Compressor House)
FZ04 (Filters Condensate Recovery & Flare KO)
FZ12 (Administration Block)
FZ13 (Workshop).

ESD - Confirmed Fire

ESD - Confirmed High Gas Detection

Gas Detectors bring up a High alarm at 20% LEL


and a High High alarm at 50% LEL. Only Confirmed
High High initiates an executive action.

ESD - Confirmed High Gas Detection

ESD - Confirmed Fire


H

Siren for Fire Alarm


H

Siren for Toxic Gas Alert


H

Siren for Combustible Gas Alert (High Level)


H

Siren for Combustible Gas Alert (Low Level)


H

Beacons for Fire Alarm


H

Beacons for Combustible Gas Alert

Beacons for Toxic Gas Alert


H

S
Energise

PCS Repeat Alarm

S
Energise

CSS Alarm - Manual Callpoint Alarm

S
Energise

CSS Alarm - Confirmed Fire Alarm

S
Energise

CSS Alarm - Single Fire Alarm

S
Energise

CSS Alarm - Confirmed High Toxic Gas Alarm

S
Energise

CSS Alarm - Single High Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Toxic Gas Alarm

S
Energise

CSS Alarm - Single Low Toxic Gas Alarm

S
Energise

CSS Alarm - Confirmed High Flammable Gas Alarm

S
Energise

CSS Alarm - Single High Flammable Gas Alarm

S
Energise

CSS Alarm - Confirmed Low Flammable Gas Alarm

S
Energise

DESCRIPTION

CSS Alarm - Single Low Flammable Gas Alarm

TYPE

EFFECT

1.

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

NOTES

TAG

FZ

FZ 11 - Generator Room

M GROUP

M ENABLE

O/O

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

Energise

YAB-9XX62

YAB-9XX63

YAS-9XX71

YAS-9XX72

YAS-9XX73

YAS-9XX74

XI-91191

XI-91192

SS-002

SS-001

CAUSE
DESCRIPTION

YAB-9XX61

TAG

ACTION

RESET
Log

X - Input initiated causes output action in column(s) shown. Output may not be reset until
Input condition recovers.
T - Input initiated causes output action only after time delay.
& - All '&' inputs in a column must fail together to cause output in that column (unless
paired with a function).
V - Voted Output - 2ooN or 1oo2 as applicable.
FZ - Firezone Location
M - Maintenance Override (MOS)
O/O- Operational or Startup Override

CSS Sequence of Events Recorder

Nomenclature

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-91101

11

Flammable Gas Detector - Open Path type- Tx, Rx

GDT/GDR-91102

11

X X V X V
X X V X V

X
X

X
X

X X
X X

V
V

V
V

4
Flame Detector - Triple IR type

FD-91131

11

Flame Detector - Triple IR type

FD-91132

11

MAC-91151

11

X
X

X V
X V

X
X

X
X

X
X

V
V

X X

V
V

7
Manual Alarm Callpoint

8
9
10
11
12
13
14
15
16
17
18
19

General Notes
A

All trip inputs have PCS alarms not shown


on C&Es. Maintenance and operational
overrides do not affect PCS alarms.

Handswitch backlights and local panel


indicators are not shown on C&Es.

I/O related only to sequence logic is not


shown on C&Es.

All I/O is de-energised to operate unless


otherwise indicated or a reset.

In a 2oo3 voting scheme, if one detector goes into fault


then the voting scheme reduces to 1oo2.

All Maintenance Overrides (MOS) are software


switches on the PCS screen. A MOS may only be
applied if the associated MOS Enable hard wired
Switch is ON. A MOS Enable Switch may be set to
ON only when the Master MOS Enable Keyswitch is
ON. The Master MOS Enable Keyswitch may then be
withdrawn.

20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50