Sei sulla pagina 1di 9

Basler Electric

Spreadsheet for Testing and Analysis of the Basler Current Differential Di

Disclaimer
This spreadsheet presents basic calculations associated with current distribution in electric power transformers, but users s
purported to be complete or comprehensive. In developing this software Basler Electric has attempted to develop accurate
free from bugs, errors, or other program limitations. Users are encouraged to use good judgment with the results, and cons
and results for the specific use or purpose of the user.

By use of this program, the user agrees that Basler Electric disclaims all warranties of noninfringement of third party rights,
user assumes the entire risk as to the quality and performance of the software. In no event will Basler Electric be liable for a
regarding this software, the user agrees that the venue shall be the State of Illinois.

Purpose of this Spreadsheet


This spreadsheet is intended to assist in the analysis of Basler Differential Relays in both commissioning testing and post fa
1) Introduction
2) 87T-Testing == For testing the relay with two single phase current sources.
3) 87T-Diff Calc-Isec == For determining relay response to an arbitrary injected current.
4) CDS Testing == For testing the CDS220 or 240 with two single phase current sources.
5) CDS220-Diff Calcs-Isec == For determining relay response to an arbitrary injected current.
6) CDS220-Diff Calcs-Ipri == For determining relay resonse to an arbitrary primary current. Includes CT connection and ra
7) CDS240-Diff Calcs-Isec == For determining relay response to an arbitrary injected current.
8) User == A blank sheet for the user to keep job notes and calcs on.

Instructions, Notes
=> See each sheet for instructions specific to that sheet.
=> The spreadsheets have data already entered in. This is for information only, so one can see the type of information expe
=> On common 1024x768 screens, most sheets are best viewed at 75% zoom. If one has a higher resolution monitor, one m
=> See papers on the Basler Electric Web site for additioal information and transformer differential theory
=> Send comments on this spreadsheet to "info@basler.com"
Revision Notes:
Rev. D.1; 03/26/03; Request for comments
Rev. D.2; DDAB calc error fixed.
Rev. 0.1; Initial release, including a couple formating updates relative to rev 0 as used at Megger Conference, 06/27/05
Rev. 0.2; Fixed "Iop>MPU?" check, cells G31/G32, 87T-Diff Calcs-Isec sheet; revised disclaimer wording. 11/22/05
Basler Electric Company, P.O. Box 269, Highland, Illinois USA 62249
Phone: 618/654-2341 - Fax: 618/654-2351 - Website: http://www.basler.com

Current Differential Differential Relays, BE1-87T and BE1-CDS2x0

power transformers, but users should be aware the specific applications were intended, so the results cannot
attempted to develop accurate calculation methods, but Basler Electric does not warrant that the software is
ment with the results, and consult with a Basler Electric representative to determine the accuracy of the data

fringement of third party rights, quality, performance, merchantability, or fitness for a particular purpose. The
will Basler Electric be liable for any indirect, special, or consequential damages. In the event of any litigation

ommissioning testing and post fault event analysis. The sheets and their puropose are:

nt.
Includes CT connection and ratio effects.
nt.

see the type of information expected. Update all information and settings appropriately.
higher resolution monitor, one might raise the zoom control to 100% for clearer viewing.
erential theory

egger Conference, 06/27/05


imer wording. 11/22/05

BE1-87T, 3 Phase, Testing With 2 Single Phase Current Sources


This sheet predicts targets on BE1-87T when testing with two single phase test sets, with the relay set at user's final settings.
-- Enter data in yellow fields only. Range cell becomes red if out of range data is entered.
-- Input "1" and "2" are used for reference, but each can refer to any of the relay's 3 phase inputs. There up to three 3 phase inputs on a BE1-87T.
-- This sheet does not support back to back delta compensation (e.g., DAB-DAC and DAC-DAB compensation jumper configurations).
RELAY SETTINGS (Red range cell flags bad data)

Nominal Amp Rating of Inputs


% Slope
Minimum Pick-Up (MPU)
Input 1 Tap
Input 1 Compensation Jumper
Input 2 Tap
Input 2 Compensation Jumper

Range

5
25
0.3
5
d1
4.35
y

5 or 1
15-60, steps of 5
Normally 0.35
2.0-8.9 or 0.4-1.78
Y, D1, D2
2.0-8.9 or 0.4-1.78
Y, D1, D2

MULTIPLES OF TAP (MOT) FOR TEST


0.87
Suggest repeating test at 0, 1, 3, and 5 MOT. Selecting 0 MOT means the spreadsheet gives min. pickup. Higher MOT might
be tested but max. continuous rating of relay is 20A.
INITIAL CURRENT INJECTION VALUE
Initially inject into Input 1 (amps):
4.35 < 0
Initially inject into Input 2 (amps):
3.7845 < 180

TEST SET CONNECTIONS AND EXPECTED TARGETS

Connect polarity/non-polarity of the two test set sources to the indicated phase on relay, or the relay common non-polarity as
indicated by the matrix below. See IM Section 5 for examples..
Relay Ph A Pol
Relay Ph B Pol
Relay Ph C Pol
Relay NonPol
Test # 1 (87PH-A)
Test Set 1 Polarity
N.C.
N.C.
Test Set 1 NonPol.
Relay Input 1:
Test Set 2 Polarity
Test Set 2 NonPol.
N.C.
N.C.
Relay Input 2:
Phases that give targets at trip level:
Phase A
Phase B
Relay Ph A Pol
Relay Ph B Pol
Relay Ph C Pol
Relay NonPol
Test # 2 (87PH-B)
N.C.
Test Set 1 Polarity
N.C.
Test Set 1 NonPol.
Relay Input 1:
N.C.
Test Set 2 Polarity
Test Set 2 NonPol.
N.C.
Relay Input 2:
Phases that give targets at trip level:
Phase B
Phase C
Relay Ph A Pol
Relay Ph B Pol
Relay Ph C Pol
Relay NonPol
Test # 3 (87PH-C)
N.C.
N.C.
Test Set 1 Polarity
Test Set 1 NonPol.
Relay Input 1:
Test Set 2 NonPol.
N.C.
Test Set 2 Polarity
N.C.
Relay Input 2:
Phases that give targets at trip level:
Phase A
Phase C
TRIP OCCURS AT THESE CURRENTS:
Increasing Input 1 current:
Decreasing Input 1 current:
Increasing Input 2 current:
Decreasing Input 2 current:

Nominal
5.85
2.85
5.09
2.48

+/0.451
0.271
0.405
0.249

Intermediate Calculations:
When increasing input 1, % Slope is exceeded at:
When decreasing input 1, % Slope is exceeded at:
When increasing input 2, % Slope is exceeded at:
When decreasing input 2, % Slope is exceeded at:
When increasing input 1, Min Operate is exceeded at:
When decreasing Input 1, Min Operate is exceeded at:
When increasing input 2, Min Operate is exceeded at:
When decreasing Input 2, Min Operate is exceeded at:

Test 1

Range
5.40
2.58
4.68
2.23

6.30
3.12
5.49
2.73

As Found
Test 2

Test 3

5.80
3.26
5.05
2.84
5.85
2.85
5.09
2.48

BE1-87T, 3 Phase, Differential Calculations, Arbitrary Isec.


This sheet predicts tripping of a BE1-87T for a set of two user-defined CT secondary current inputs
-- Enter data in yellow fields only. Blue cells are calculated by the spreadsheet.
-- Input 1 and 2 are used for reference; each can refer to any of the relay's 3-phase inputs. There up to three 3-phase inputs on a BE1-87T.
-- The spreadsheet reproduces the differential calculations of the BE1-87T to assist in determining if a trip should occur for a given test current.
-- Range cells will be green normally, but turn red to flag out-of-range settings.
-- Recall the relay expects current reversal across the xfmr, so balanced currents are shifted by 150, 180, or -150 degrees in most applications. For
instance, for balanced 3 phase current, current at Input 2 should be shifted by 180deg if jumpers are Y-Y, +150deg if jumpers are Y-D1, and -150deg
if jumpers are Y-D2.

RELAY SETTINGS (Red range cell flags bad data)


5
Nominal Amp Rating of Inputs
25
% Slope
0.35
Minimum Pickup (MPU), per unit
2
Input 1 Tap
Y
Input 1 Compensation Jumper
6
Input 2 Tap
d2
Input 2 Compensation Jumper

INJECTED CURRENT AT INPUT 1


(Single phase entry sufficient)
Current @ Input 1, Ph A
Current @ Input 1, Ph B
Current @ Input 1, Ph C
INJECTED CURRENTS AT INPUT 2
Current @ Input 2, Ph A
Current @ Input 2, Ph B
Current @ Input 2, Ph C

Range
5 or 1
15-60, steps of 5
See Cell Comment
2.0-8.9 or 0.4-1.78
Y, D1, D2
2.0-8.9 or 0.4-1.78
Y, D1, D2

Mag.
1.1
1.1
1.1

Angle
0
-120
120

Mag.
3
3
3

Angle
150
30
-90

Current Inputs, Per Unit of Tap:


Mag.
Angle
0.550
0
Input 1, Ph A
0.550
-120
Input 1, Ph B
0.550
120
Input 1, Ph C
0.500
150
Input 2, Ph A
0.500
30
Input 2, Ph B
0.500
-90
Input 2, Ph C
Restraint, with Compensation Jumper Effects
0.550
0
Input 1, A Comparator
0.550
-120
Input 1, B Comparator
0.550
120
Input 1, C Comparator
0.866
180
Input 2, A Comparator
0.866
60
Input 2, B Comparator
0.866
-60
Input 2, C Comparator
Effective Restraint (Largest Restraint x Slope)
0.217
A Comparator
0.217
B Comparator
0.217
C Comparator
Mag. Operate Current (Restraint 1 - Restraint 2)
0.316
A Comparator
0.316
B Comparator
0.316
C Comparator
Trip? (I Op>MPU? & I Op>Restraint?)
A Comparator
No
B Comparator
No
C Comparator
No

Intermediate Calculations
D1, D2 Jumper Compensation Equations:
Input 1, Rectangular format D1, D2 Equations
Real
Imag
Real
A
0.5500
0.0000 D1;1A-1C 0.8250
B
-0.2750 -0.4763 D1;1B-1A -0.8250
C
-0.2750
0.4763 D1;1C-1B 0.0000
D2;1A-1B
0.8250
D2;1B-1C 0.0000
D2;1C-1A -0.8250
Input 2, Rectangular format D1, D2 Equations
A
-0.4330
0.2500 D1;2A-2C -0.4330
B
0.4330
0.2500 D1;2B-2A
0.8660
C
0.0000 -0.5000 D1;2C-2B -0.4330
D2;2A-2B -0.8660
D2;2B-2C 0.4330
D2;2C-2A 0.4330
Convert Restraint to Rectangular format
X
jY
Input 1
A
0.5500
0.0000
B
-0.2750
-0.4763
C
-0.2750
0.4763
Input 2
A
-0.8660
0.0000
B
0.4330
0.7500
C
0.4330
-0.7500
Sum Restraint to find Operate Current
X
jY
Mag
Sum
1A+2A
-0.3160
0.0000 0.3160
1B+2B
0.1580
0.2737 0.3160
1C+2C
0.1580
-0.2737 0.3160

Imag
-0.4763
-0.4763
0.9526
0.4763
-0.9526
0.4763

Mag
0.9526
0.9526
0.9526
0.9526
0.9526
0.9526

Angle
-30.0
-150.0
90.0
30.0
-90.0
150.0

0.7500
0.0000
-0.7500
0.0000
0.7500
-0.7500

0.8660
0.8660
0.8660
0.8660
0.8660
0.8660

120.0
0.0
-120.0
180.0
60.0
-60.0

Angle
180.0
60.0
-60.0

BE1-CDS, Testing With 2 Single Phase Current Sources


This sheet predicts targets on the BE1-CDS2x0 when testing with two single phase test sets, with the relay set at user's final settings.
-- Enter data in yellow fields only. Range cells become red if bad data is entered. Blue cells are calculated by the spreadsheet.
-- While most directly applicable to the CDS220, this spreadsheet can be used to analyze the CDS240 if one mentally compensates for the winding numbers and does not use the advanced compensation schemes in the CDS240.
-- The spreadsheet expects one to understand compensation that the relay is using and enter net compensation, not the Xfmr or CT configuration. See IM chapter 3.
RELAY SETTINGS

Nominal Amp Rating of Inputs


Use Max. or Avg. Restraint?
87Phase Min Pickup (MPU), per unit
Phase % Slope
Input 1 Tap
Input 1 Compensation (see IM Chpt 3)
Input 1 "Ground Source" selected?
Input 2 Tap
Input 2 Compensation (see IM Chpt 3)
Input 2 "Ground Source" selected?
87Gnd Min Pickup (MPU), per unit
87Gnd % Slope
Which input # is Ig is compared to?
Phase CT Ratio for Input 2
Ground CT Ratio
87N Tap, Ig Input side
87N Tap, Phase Input side

Range

5
M
0.35
35
4
y
n
5
dab
n
0.5
20
2
300
100
6.00
2.00

5 or 1
M or A
0.10-1.00
15-60, steps of 1
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
0.10-1.00
15-60, steps of 1
1 or 2
N to 1
N to 1
See cell notes
See cell notes above

MULTIPLES OF TAP (MOT) FOR TEST

Messages appear below if certain


unsupported settings are selected

87PHASE TEST
Suggest repeating test at 0, 1, 3, and 5 MOT. Selecting 0 MOT means the spreadsheet gives min. pickup. Higher MOT
might be tested but max. continuous rating of relay is 20A.
INITIAL CURRENT INJECTION VALUE FOR PHASE TEST
Initially inject into Input 1 (amps):
12.000 < 0
Initially inject into Input 2 (amps):
25.981 < 180

TEST SET CONNECTIONS AND EXPECTED TARGETS


Jumper non-polarities on each relay input together. Connect polarity/non-polarity of the two test set sources to the indicated
polarity or non-polarity of the relay. See IM Sect.13 for example connections.
Relay Ph A Pol.
Relay Ph B Pol.
Relay Ph C Pol.
Relay NonPol.
Test # 1 (87PH-A)
Test Set 1 Pol.
N.C.
Test Set 1 NonPol.
N.C.
Relay Input 1:
Test Set 2 Pol.
N.C.
N.C.
Test Set 2 NonPol.
Relay Input 2:
Phases that give targets at trip level:
Phase A
Phase C
Relay Ph A Pol.
Relay Ph B Pol.
Relay Ph C Pol.
Relay NonPol.
Test # 2 (87PH-B)
Test Set 1 NonPol.
Test Set 1 Pol.
N.C.
N.C.
Relay Input 1:
N.C.
Test Set 2 Pol.
N.C.
Test Set 2 NonPol.
Relay Input 2:
Phases that give targets at trip level:
Phase A
Phase B
Relay Ph A Pol.
Relay Ph B Pol.
Relay Ph C Pol.
Relay NonPol.
Test # 3 (87PH-C)
N.C.
Test Set 1 NonPol.
Test Set 1 Pol.
N.C.
Relay Input 1:
N.C.
N.C.
Test Set 2 Pol.
Test Set 2 NonPol.
Relay Input 2:
Phases that give targets at trip level:
Phase B
Phase C

87N TEST
INITIAL CURRENT INJECTION VALUE AND TEST SET CONNECTION
Initially inject into Input Ig (amps):
Initially inject into Input 2, any phase, but 180 degrees out of phase with Ig:

18.00
6.00

Intermediate Calculations:
87 Phase:
87Phase Effective Tap = Tap setting x sqrt(3) if DAB or DAC compensation is used.
Hence, 3 MOT is (amps):
Input 1 Effective Tap for 87Ph calcs:
4.000
Hence, 3 MOT is (amps):
Input 2 Effective Tap for 87Ph calcs:
8.660
Trip Levels (amps):
Max Restr. Avg. Restr.
When increasing input 1, % Slope is exceeded at:
18.462
17.091
When decreasing input 1, % Slope is exceeded at:
7.800
8.426
When increasing input 2, % Slope is exceeded at:
39.970
37.003
When decreasing input 2, % Slope is exceeded at:
16.887
18.242
When increasing input 1, Min Operate is exceeded at:
13.400
13.400
When decreasing Input 1, Min Operate is exceeded at:
10.600
10.600
When increasing input 2, Min Operate is exceeded at:
29.012
29.012
When decreasing Input 2, Min Operate is exceeded at:
22.950
22.950
87 Neutral:
Phase tap to be used in 87N calculations (= tap setting of selected phase):
Trip Levels (amps):
Max Restr. Avg. Restr.
When increasing input 2, % Slope is exceeded at:
7.500
7.333
When decreasing input 2, % Slope is exceeded at:
4.800
4.909
When increasing input Ig, % Slope is exceeded at:
22.500
22.000
When decreasing input Ig, % Slope is exceeded at:
14.400
14.727
When increasing input 2, Min Operate is exceeded at:
7.000
7.000
When decreasing input 2, Min Operate is exceeded at:
5.000
5.000
When increasing input Ig, Min Operate is exceeded at:
21.000
21.000
When decreasing Input Ig, Min Operate is exceeded at:
15.000
15.000

12.00
25.98
In Use:
18.462
7.800
39.970
16.887
13.400
10.600
29.012
22.950

In Use:
7.500
4.800
22.500
14.400
7.000
5.000
21.000
15.000

PHASE DIFFERENTIAL TESTS


As Found
TRIP OCCURS AT THESE CURRENTS:
Test 1
Test 2
Test 3
Nominal
+/Range
Increasing Input 1 current:
18.46
0.738
17.72
19.20
Decreasing Input 1 current:
7.80
0.312
7.49
8.11
Increasing Input 2 current:
39.97
1.599
38.37
41.57
Decreasing Input 2 current:
16.89
0.675
16.21
17.56
GROUND DIFFERENTIAL TESTS
TRIP OCCURS AT THESE CURRENTS:
As Found
Nominal
+/Range
Increasing Input Ig current:
22.50
0.900
21.60
23.40
Decreasing Input Ig current:
14.40
0.576
13.82
14.98
Increasing Input 2 current:
7.50
0.300
7.20
7.80
Decreasing Input 2 current:
4.80
0.192
4.61
4.99
BE CAREFUL: At least one of the listed test currents is above the maximum continuous rating of the relay (20A).

BE1-CDS220, Differential Calculations for Arbitrary Isec


This sheet predicts tripping of a BE1-CDS220 for a set of arbitrary user-defined CT secondary current inputs
-- Enter data in yellow fields only, entering only data listed in the "Range" cell. Range cells become red if bad data is entered.
-- The spreadsheet expects one to understand compensation that the relay is using and enter net compensation, not the Xfmr configuration. See IM chapter 3.
-- This sheet is for analyzing the effect of CT secondary currents being injected into the relay. This is not analyzing effect of primary current on relay. Note the CT Ratio is not
entered in this spreadsheet (except for the purpose of calculating the 87N Tap).
-- This sheet supports DAC, DAB, and "Ground Source" compensations of the CDS220.
-- Recall the relay expects current reversal across the xfmr, so balanced currents are shifted by 150, 180, or -150 degrees in most applications. For instance, for balanced 3
phase current, current at Input 2 should be shifted by 180deg if xfmr is Y-Y, +150deg for a DAB-Y xfmr, and -150deg for a DAC-Y xfmr.
RELAY SETTINGS
Nominal Amp Rating of Inputs
Restr. = Max. or Avg. Mult. of Tap?
87Phase Min Pickup (MPU), per unit
Phase % Slope
Input 1 Tap
Input 1 Compensation (see IM Chpt 3)
Input 1 "Ground Source" selected?
Input 2 Tap
Input 2 Compensation (see IM Chpt 3)
Input 2 "Ground Source" selected?
87Gnd Min Pickup (MPU), per unit
87Gnd % Slope
Which input # is Ig compared to?
Phase CT Ratio for Input 2
Ground CT Ratio

87N Tap, Ig Input side


87N Tap, Phase Input side

5
M
0.25
35
4
y
n
2.2
dab
n
0.2
20
2
400
200
4.00
2.00

Range
5 or 1
M or A
0.10-1.00
15-60, steps of 1
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
0.10-1.00
15-60, steps of 1
1, 2. 3, 4
N to 1
N to 1
See cell notes
See above

CURRENTS AT RELAY INPUT 1


Mag.
Input 1, Ph A
8
Input 1, Ph B
0
Input 1, Ph C
8
CURRENTS AT RELAY INPUT 2

Mag.
Input 2, Ph A
7.62
Input 2, Ph B
0
Input 2, Ph C
0
CURRENT AT RELAY INPUT IG

Mag.

Angle

0.0
0.0
180.0
Angle
180.0
30.0
0.0
Angle

Current @ Input Ig
15.24
0.0
Input Current/Tap ( = current in MOT)
Mag.
Angle
2.000
0.0
Input 1, Ph A
0.000
0.0
Input 1, Ph B
2.000
180.0
Input 1, Ph C
2.000
180.0
Input 2, Ph A
0.000
0.0
Input 2, Ph B
2.000
0.0
Input 2, Ph C
Input Ig / 87N Ig tap
3.810
0.0
3.810
180.0
3Io, Input 2 / 87N Ph tap
Phase Currents after delta/wye compensation
Mag.
Angle
Input 1, A Comparator
2.000
0.0
Input 1, B Comparator
0.000
0.0
Input 1, C Comparator
2.000
180.0
Input 2, A Comparator
2.000
180.0
Input 2, B Comparator
0.000
0.0
Input 2, C Comparator
2.000
0.0

Effective Restraint (see cell notes)


A Comparator
B Comparator
C Comparator
Gnd Comparator

0.700
0.000
0.700
0.762

Mag. Operate Current (Rest. 1+2)


A Comparator
B Comparator
C Comparator
Gnd Comparator

0.000
0.000
0.000
0.000

Trip? (Op>MPU? & Op>Restraint?)


87Ph-A
87Ph-B
87Ph-C
87N

No
No
No
No

BE1-CDS220, 3 Phase, Differential Calculations for Arbitrary Primary Currents


This sheet predicts tripping of a BE1-CDS220 for a set of arbitrary user-defined primary (i.e., line) current inputs
-- This sheet can also be used for the CDS240 in cases where the CDS240 is configured without ABC Swap, DDAB, or Polarity Reversal compensation.
-- Enter data in yellow fields only, entering only data listed in the "Range" cell. Range cells become red if bad data is entered.
-- The spreadsheet expects one to understand compensation that the relay is using and enter net compensation, not the Xfmr configuration. See IM chapter 3.
-- This sheet is for analyzing primary line currents. This sheet includes the effect of the CT connections.
-- Recall the relay expects current reversal across the xfmr, so balanced currents are shifted by 150, 180, or -150 degrees in most applications. For instance, for balanced 3
phase current, current at Input 2 should be shifted by 180deg if xfmr is Y-Y, +150deg for a DAB-Y xfmr, and -150deg for a DAC-Y xfmr.
RELAY SETTINGS
Nominal Amp Rating of Inputs
Restr. = Max. or Avg. Mult. of Tap?
87Phase Min Pickup (MPU), per unit
Phase % Slope
Input 1 CT Ratio
Input 1 CT Connection
Input 1 Tap
Input 1 Compensation (see IM Chpt 3)
Input 1 "Ground Source" selected?
Input 2 CT Ratio
Input 2 CT Connection
Input 2 Tap
Input 2 Compensation (see IM Chpt 3)
Input 2 "Ground Source" selected?
87Gnd Min Pickup (MPU), per unit
87Gnd % Slope
Which input # is Ig compared to?
Ground CT Ratio

87N Tap, Ig Input side


87N Tap, Phase Input side

5
M
0.25
35
40
y
2.67
Y
n
240
y
4.44
dab
n
0.2
20
2
80
6.00
2.00

Range
5 or 1
M or A
0.10-1.00
15-60, steps of 1
N to 1, Incr. of 1
Y, DAB, DAC
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
N to 1, Incr. of 1
Y, DAB, DAC
2.0-20 or 0.4-4
Y, DAB, DAC
Y, N
0.10-1.00
15-60, steps of 1
1, 2
N to 1, Incr. of 1
See cell notes
See above

PRIMARY CURRENTS AT INPUT 1


Mag.
Input 1, Ph A
120
Input 1, Ph B
120
Input 1, Ph C
120
PRIMARY CURRENTS AT INPUT 2
Input 2, Ph A
1200
Input 2, Ph B
1200
Input 2, Ph C
1200
CURRENT AT IG (GROUND INPUT)
Current @ Input Ig
0
CT Secondary Currents
Input 1, Ph A
3.000
Input 1, Ph B
3.000
Input 1, Ph C
3.000
Input 2, Ph A
5.000
Input 2, Ph B
5.000
Input 2, Ph C
5.000
0
Input Ig
Input Current/Tap ( = current in MOT)
1.124
Input 1, Ph A
1.124
Input 1, Ph B
1.124
Input 1, Ph C
1.126
Input 2, Ph A
1.126
Input 2, Ph B
1.126
Input 2, Ph C
Input Ig / 87N Ig tap
0.000
0.000
3Io, Input 6 / 87N Ph tap
Phase Currents after delta/wye comp.
Input 1, A Comparator
1.124
Input 1, B Comparator
1.124
Input 1, C Comparator
1.124
Input 2, A Comparator
1.126
Input 2, B Comparator
1.126
Input 2, C Comparator
1.126

Angle

0.0
-120.0
120.0
150.0
30.0
-90.0
150.0
0.0
-120.0
120.0
150.0
30.0
-90.0
150.0
0.000
-120.000
120.000
150.000
30.000
-90.000
150.0
0.0
0.000
-120.000
120.000
180.000
60.000
-60.000

Effective Restraint (see cell notes)


A Comparator
B Comparator
C Comparator
Gnd Comparator

0.394
0.394
0.394
0.000

Mag. Operate Current (Rest. 1+2)


A Comparator
B Comparator
C Comparator
Gnd Comparator

0.003
0.003
0.003
0.000

Trip? (Op>MPU? & Op>Restraint?)


87Ph-A
87Ph-B
87Ph-C
87N

No
No
No
No

BE1-CDS240, 3 Phase, Differential Calculations for Arbritrary Isec


This sheet predicts targets on a BE1-CDS240 relay for a set of arbitrary user-defined secondary currents
-- Enter data in yellow fields only. Blue cells are calculated by the spreadsheet.
-- The sheet reproduces the differential calculations of the BE1-CDS240 to assist in determining if a trip should occur for a given current defined by the user.
-- This sheet does not support the analysis of virtual currents at this time.
-- Recall the relay expects current reversal across the xfmr, so balanced currents are shifted by 150, 180, or -150 degrees in most applications. For instance, for balanced 3 phase current, current at Input 2 should be
shifted by 180deg if xfmr is Y-Y, +150deg for a DAB-Y xfmr, and -150deg for a DAC-Y xfmr.
RELAY SETTINGS (Red range cell flags bad data)
Nominal Amp Rating of Inputs
5
Restr. = Max. or Avg. Mult. of Tap?
m
No. of 87Ph inputs (see Range notes)
4
87Phase Min Pickup (MPU), per unit
0.25
Phase % Slope
35
Input 1 Tap
5
Input 1 Delta Comp. (see IM Chpt 3)
y
Input 1 "Ground Source" selected?
n
Input 1 Swap; A = ?
a
Input 1 Polarity Reversal?
n
Input 2 Tap
2.5
Input 2 Delta Comp. (see IM Chpt 3)
y
Input 2 "Ground Source" selected?
n
Input 2 Phase Swap; A = ?
a
Input 2 Polarity Reversal?
n
Input 3 Tap
2.5
Input 3 Delta Comp. (see IM Chpt 3)
y
Input 3 "Ground Source" selected?
n
Input 3 Phase Swap; A = ?
A
Input 4 Polarity Reversal?
N
Input 4 Tap
2.5
Input 4 Delta Comp. (see IM Chpt 3)
y
Input 4 "Ground Source" selected?
n
Input 4 Phase Swap; A = ?
a
Input 4 Polarity Reversal?
n
87Gnd Min Pickup (MPU), per unit
0.2
87Gnd % Slope
20
Which input # is Ig compared to?
4
Phase CT Ratio for Input 4
400
Ground CT Ratio
50

87N Tap, Ig Input side

16.00

Range
5 or 1
M or A
2,3,4
0.10-1.00
15-60, steps of 1
2.0-20 or 0.4-4

CURRENTS AT INPUT 1

Y, DAB, DAC, DDAB

Current @ Input 2, Ph A
Current @ Input 2, Ph B
Current @ Input 2, Ph C
CURRENTS AT INPUT 3

Y, N
A, B, C
Y, N
2.0-20 or 0.4-4
Y, DAB, DAC, DDAB

Y, N
A, B, C
Y, N
2.0-20 or 0.4-4
Y, DAB, DAC, DDAB

Y, N
A, B, C
Y, N
2.0-20 or 0.4-4
Y, DAB, DAC, DDAB

Y, N
A, B, C
Y, N
0.10-1.00
15-60, steps of 1
1, 2. 3, 4
N to 1
N to 1
See cell notes

Angle
180.0
60.0
-60.0

Mag.
1
1
1

Angle
0.0
-120.0
120.0

Mag.
1
1
1

Angle
0.0
-120.0
120.0

Mag.
Current @ Input 4, Ph A
1.5
Current @ Input 4, Ph B
1.5
Current @ Input 4, Ph C
1.5
CURRENT AT IG (GROUND INPUT)
Mag.
Current @ Input Ig
0

Angle
0.0
-120.0
120.0

Current @ Input 1, Ph A
Current @ Input 1, Ph B
Current @ Input 1, Ph C
CURRENTS AT INPUT 2

Current @ Input 3, Ph A
Current @ Input 3, Ph B
Current @ Input 3, Ph C
CURRENTS AT INPUT 4

Mag.
Input 1, Ph A
1.400
Input 1, Ph B
1.400
Input 1, Ph C
1.400
Input 2, Ph A
0.400
Input 2, Ph B
0.400
Input 2, Ph C
0.400
Input 3, Ph A
0.400
Input 3, Ph B
0.400
Input 3, Ph C
0.400
Input 4, Ph A
0.600
Input 4, Ph B
0.600
Input 4, Ph C
0.600
Input Ig / 87N Ig tap
0.000
0.000
3Io, Input / 87N Ph tap
Phase Restraint, after compensation
1.400
Input 1, A Comparator
1.400
Input 1, B Comparator
1.400
Input 1, C Comparator
Input 2, A Comparator
0.400
Input 2, B Comparator
0.400
Input 2, C Comparator
0.400
Input 3, A Comparator
0.400
Input 3, B Comparator
0.400
Input 3, C Comparator
0.400
Input 4, A Comparator
0.600
Input 4, B Comparator
0.600
Input 4, C Comparator
0.600
Current, Per Unit of Tap:

Mag.
7
7
7

Angle
180.0

Angle
180.0
60.0
-60.0
0.0
-120.0
120.0
0.0
-120.0
120.0
0.0
-120.0
120.0
180.0
0.0
180.0
60.0
-60.0
0.0
-120.0
120.0
0.0
-120.0
120.0
0.0
-120.0
120.0

Effective Restraint (see cell


notes)
A Comparator
0.490
B Comparator
0.490
C Comparator
0.490
Gnd Comparator
0.000
Mag. Operate Current
(Rest. 1+2+3+4)
A Comparator
B Comparator
C Comparator
Gnd Comparator
Trip? (Op>MPU? &
Op>Restraint?)
A Comparator
B Comparator
C Comparator
Ground Comparator

0.000
0.000
0.000
0.000

No
No
No
No

Blank Sheet for User Calculations

Potrebbero piacerti anche