Phase TOC

Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

Main 13.2kV
13200
10000000
437.39
3.645
600
5
0.729
IEC B
0.3

% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.243
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1500
2.5

% x phase TOC
Pick-up Setting (x pu)

33%
0.833

F1 13.2kV
13200
3000000
131.22
3.280
200
5
0.656
IEC B
0.3

F2 13.2kV
13200
1500000
65.61
1.640
200
5
0.328
IEC B
0.3

F3 13.2kV
13200
2500000
109.35
2.734
200
5
0.547
IEC B
0.3

33%
0.109
IEC B
0.3

33%
0.182
IEC B
0.3

1200
6

1200
6

33%
2.000

33%
2.000

Load for each Feeder

To be set according to TRANSCO


To be set according to TRANSCO

Neutral TOC
33%
0.219
IEC B
0.3

To be set according to TRANSCO


To be set according to TRANSCO

Phase IOC
1200
6

Neutral IOC
33%
2.000

To be set according to the Substat

oad for each Feeder

be set according to TRANSCO Settings


be set according to TRANSCO Settings

be set according to TRANSCO Settings


be set according to TRANSCO Settings

be set according to the Substation

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

Main 13.2kV F1 13.2kV F2 13.2kV F3 13.2kV F4 13.2kV


13200
13200
13200
13200
13200
10000000
2500000 2500000 2500000 2500000 Load for each Feeder
437.39
109.35
109.35
109.35
109.35
3.645
1.822
1.822
1.822
1.822
600
300
300
300
300
5
5
5
5
5
0.729
0.364
0.364
0.364
0.364
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRANSCO Sett
0.3
0.3
0.3
0.3
0.3
To be set according to TRANSCO Sett

Neutral TOC
% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.243
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1500
2.5

% x phase TOC
Pick-up Setting (x pu)

33%
0.833

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

1200
4

1200
4

1200
4

33%
1.333

33%
1.333

33%
1.333

To be set according to TRANSCO Sett


To be set according to TRANSCO Sett

Phase IOC
1200
4

Neutral IOC
33%
1.333

To be set according to the Substation

according to TRANSCO Settings


according to TRANSCO Settings

according to TRANSCO Settings


according to TRANSCO Settings

according to the Substation

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

Main 13.2kV F1 13.2kV F2 13.2kV F3 13.2kV F4 13.2kV


13200
13200
13200
13200
13200
20000000
5000000 5000000 5000000 5000000 Load for each Feeder
874.77
218.69
218.69
218.69
218.69
4.374
3.645
3.645
3.645
3.645
1000
300
300
300
300
5
5
5
5
5
0.875
0.729
0.729
0.729
0.729
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRANSCO Setti
0.3
0.3
0.3
0.3
0.3
To be set according to TRANSCO Setti

Neutral TOC
% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.292
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1500
1.5

% x phase TOC
Pick-up Setting (x pu)

33%
0.500

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

1200
4

1200
4

1200
4

33%
1.333

33%
1.333

33%
1.333

To be set according to TRANSCO Setti


To be set according to TRANSCO Setti

Phase IOC
1200
4

Neutral IOC
33%
1.333

To be set according to the Substation

according to TRANSCO Settings


according to TRANSCO Settings

according to TRANSCO Settings


according to TRANSCO Settings

according to the Substation

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

F1 13.2kV
13200
5000000
218.69
1.822
600
5
0.364
IEC B
0.3

% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.121
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1200
2

% x phase TOC
Pick-up Setting (x pu)

33%
0.667

F2 13.2kV F3 13.2kV F4 13.2kV F5 13.2kV F6 13.2kV


13200
13200
13200
13200
13200
5000000 5000000 5000000 5000000 5000000 Load for each Feeder
218.69
218.69
218.69
218.69
218.69
1.822
1.822
1.822
1.822
1.822
600
600
600
600
600
5
5
5
5
5
0.364
0.364
0.364
0.364
0.364
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRA
0.3
0.3
0.3
0.3
0.3
To be set according to TRA

Neutral TOC
33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

1200
2

1200
2

1200
2

1200
2

33%
0.667

33%
0.667

33%
0.667

33%
0.667

To be set according to TRA


To be set according to TRA

Phase IOC
1200
2

Neutral IOC
33%
0.667

To be set according to the S

Load for each Feeder

To be set according to TRANSCO Settings


To be set according to TRANSCO Settings

To be set according to TRANSCO Settings


To be set according to TRANSCO Settings

To be set according to the Substation