Sei sulla pagina 1di 59

BTS3801C Installation Guide

Table of Contents

Table of Contents
Chapter 1 About This Guide ............................................................................................... 1-1
1.1 Purpose of This Guide ........................................................................................... 1-1
1.2 Intended Readers ..................................................................................................... 1-1
1.3 Organization of This Guide .................................................................................. 1-1
1.4 References .................................................................................................................. 1-1
Chapter 2 Preparing the Installation................................................................................ 2-1
2.1 About this Chapter ................................................................................................... 2-1
2.2 Preparing Technical Documents ........................................................................ 2-1
2.3 Qualifying Hardware Installers ........................................................................... 2-2
2.4 Preparing Tools and Instruments ...................................................................... 2-2
2.5 Checking Installation Conditions ...................................................................... 2-4
2.6 Unpacking the BTS3801C ..................................................................................... 2-6
2.6.1 Unpacking the Case ..................................................................................... 2-6
2.6.2 Unpacking the Carton.................................................................................. 2-7
Chapter 3 Overview of the BTS3801C ............................................................................ 3-1
3.1 About This Chapter .................................................................................................. 3-1
3.2 BTS3801C Main Components.............................................................................. 3-1
3.3 Space Requirements ............................................................................................... 3-1
3.3.1 Recommended Space Requirements.................................................... 3-1
3.3.2 Minimal Space Requirements................................................................... 3-2
3.4 Introduction Scenarios........................................................................................... 3-3
Chapter 4 Installation Procedure and Guidelines...................................................... 4-1
4.1 About This Chapter .................................................................................................. 4-1
4.2 Flow Chart of Installing the BTS3801C ........................................................... 4-1
4.3 Installation Guidelines............................................................................................ 4-2
Chapter 5 Installing the Rack ............................................................................................. 5-1
5.1 About This Chapter .................................................................................................. 5-1
5.2 Installing the Rack on the Pole ........................................................................... 5-1
5.3 Installing the Rack on the Wall ........................................................................... 5-4
5.4 Installing the Rack on the Stand ........................................................................ 5-9
Chapter 6 Installing the RRU3801C and BBU3806C Modules .............................. 6-1
6.1 About This Chapter .................................................................................................. 6-1
6.2 Locations of the RRU3801C and BBU3806C Modules.............................. 6-1
6.3 Installing the RRU3801C Module: ...................................................................... 6-1
6.4 Installing the BBU3806C Module ....................................................................... 6-4
Huawei Technologies Proprietary
i

BTS3801C Installation Guide

Table of Contents

Chapter 7 Installing the Cables ......................................................................................... 7-1


7.1 About This Chapter .................................................................................................. 7-1
7.2 Connectors and Ports at the BTS3801C Bottom......................................... 7-1
7.3 Ports in the Cabling Cavities ............................................................................... 7-3
7.4 Cables for Field Installation ................................................................................. 7-4
7.5 Installing the PGND Cable .................................................................................... 7-5
7.5.1 Introduction to the BTS3801C PGND Cable ....................................... 7-5
7.5.2 Connecting the PGND Cable .................................................................... 7-6
7.6 Installing the Optical Cable .................................................................................. 7-7
7.6.1 Introduction to the Optical Cable ........................................................... 7-7
7.6.2 Optical Cable Connections between RRU3801C and BBU3806C7-7
7.7 Installing the High Speed CPRI Signal Cable ............................................. 7-12
7.7.1 Introduction to the High Speed CPRI Signal Cable ...................... 7-12
7.7.2 Connecting the High Speed CPRI Signal Cable ............................. 7-13
Chapter 8 Installing the Case ............................................................................................. 8-1
8.1 About This Chapter .................................................................................................. 8-1
8.2 Installing the Case.................................................................................................... 8-1
Chapter 9 Completing the Installation ............................................................................ 9-1
9.1 About This Chapter .................................................................................................. 9-1
9.2 Checking Hardware Installation ......................................................................... 9-1
9.3 Powering on the BTS3801C ................................................................................. 9-3
9.4 Checking Field Sanitation ..................................................................................... 9-3

Huawei Technologies Proprietary


ii

BTS3801C Installation Guide

Chapter 1 About This Guide

Chapter 1 About This Guide


1.1 Purpose of This Guide
This manual describes how to install the BTS3801C and its cables.

1.2 Intended Readers


This manual is intended for the NodeB technicians.

1.3 Organization of This Guide


This manual consists of the following chapters:
z

Chapter 1

"About This Guide": introduces the purpose, intended readers,

organization and references of this guide.


z

Chapter 2 Preparing the Installation": introduces the preparations before the


BTS3801C installation.

Chapter 3 "Overview of the BTS3801C": introduces the space requirements and


installation scenarios of the BTS3801C.

Chapter 4

"Installation Procedure and Guidelines": introduces the general

procedure for installing the BTS3801C.


z

Chapter 5 "Installing the Rack": describes how to install the BTS3801C rack in
different scenarios.

Chapter 6 "Installing the RRU3801C and BBU3806C Modules": describes how to


install the RRU3801C module and BBU3806C module in the BTS3801C rack.

Chapter 7 "Installing the Cables": describes how to install BTS3801C cables on


site.

Chapter 8 "Installing the Case": describes how to install the BTS3801C case on
site.

Chapter 9 "Completing the Installation": describes the check items after the
BTS3801C is installed.

1.4 References
z

DBS3800 System Description

DBS3800 Hardware Reference

BBU3806C Installation Guide

RRU3801C Installation Guide

Huawei Technologies Proprietary


1-1

BTS3801C Installation Guide

Chapter 2 Preparing the Installation

Chapter 2 Preparing the Installation


2.1 About this Chapter
This chapter describes the following preparations before the BTS3801C installation:
z

Preparing Technical Documents

Qualifying Hardware Installers

Preparing Tools and Instruments

Checking Installation Conditions

Unpacking the BTS3801C

2.2 Preparing Technical Documents


Table 2-1 lists the technical documents related to the BTS3801C installation.
Table 2-1 Technical documents related to the BTS3801C installation
Document
type

Document name
z
z

z
z

Network Planning
Equipment
Room
Floor Plan (for indoor
installation)
Construction Drawings
Cabling Diagram

The design company appointed by


the customer must get these
documents ready and provide copies
for Huawei before delivery.

Site Survey Report

The report is completed by Huawei


engineers during site survey.

Engineering Design

Based on the hardware configuration


of a site, the document is prepared
by Huawei Construction Design
Department and delivered to the site
with the equipment.

BTS3801C Installation
Guide

The document is provided by Huawei


during the delivery.

Installation
guide

Product
manual

Description

Huawei Technologies Proprietary


2-1

BTS3801C Installation Guide

Document
type

Chapter 2 Preparing the Installation

Document name

Description

Contract
Other related
documentation

Hardware Configuration
Table

These documents are provided by


Huawei during the delivery.

Delivery List

2.3 Qualifying Hardware Installers


The hardware installers or engineers may come from Huawei, the customer's side, or a
partner company.
z

After receiving training from Huawei and obtaining the qualification certificate, the
partner company's engineers master systematic installation and commissioning
knowledge.

After receiving pre-job training from Huawei, the engineers appointed by the
customer master basic installation and commissioning knowledge.

The number of engineers depends on the project scheduling and installation


conditions. It is recommended to assign three to five engineers.

2.4 Preparing Tools and Instruments


Table 2-2 lists the tools and instruments necessary for the BTS3801C installation.

Huawei Technologies Proprietary


2-2

BTS3801C Installation Guide

Chapter 2 Preparing the Installation

Table 2-2 Tools and instruments


z
z

Measuring tools

z
z
z
z

Marking tools

z
z
z

Drilling tools
z
z
z
z
z

General
tools

Fastening tools
z

z
z
z
z
z
z

Pliers

z
z
z
z
z

Auxiliary tools

Special tools

Marker pen
Ink fountain
Pencil
Percussion drill with matching bits of 6,
8, 10, 12, 14, and 16
Cleaner
Flathead screwdrivers (M3 to M6)
Cross screwdrivers (M3 to M6)
Adjustable wrench
Socket wrenches (M6, M8, M10, M12, M14,
M17, M19)
Double ring spanners (M6, M8, M10, M12,
M14, M17, M19)
Combination wrenches (M17 and M19)
Long arm wrench
A pair of sharp nose pliers
A pair of diagonal pliers
A pair of pincer pliers
Electric hand drill
File
Hacksaw
Crowbar
Rubber hammer
Nail hammer

Hairbrush, a pair of tweezers, paper knife,


bellow, plumb, soldering iron, tin wires, fork,
ladder, heat blower, solder absorber, insulating
tape

An earth resistance tester, ESD wrist strap, a pair of ESD gloves,


wire stripper, a clamping pincers, a feeder cutter, a pair of crimping
pliers for SMB, RJ-45 connector crimping pliers, wire punchdown
tool, wire cutter, a non-conductive screwdriver, safety knife,
stripper for 75-ohm coaxial cables, a pair of connector crimping
pliers for 75-ohm coaxial cables, a pair of multi-purpose crimping
pliers
z

Instruments

Long tape
50 m ribbon tape
5 m measuring tape
400 mm level bar
Level instrument

z
z
z

A multi meter
500 V megaohm meter (for insulation resistance)
BER tester
Optical power meter

Huawei Technologies Proprietary


2-3

BTS3801C Installation Guide

Chapter 2 Preparing the Installation

Note:
z

Huawei provides the tool and instrument list.

Tool providers are selected by Huawei and the customer.

The instruments are checked and qualified.

2.5 Checking Installation Conditions


The project supervisor must do the following at the site:
z

Check the construction conditions.

Complete Installation Environment Checklist, based on field conditions.

Sign Kickoff Agreement with the customer if all conditions are ready.

Make out Project Installation Plan.

If the conditions are not ready for the kickoff, complete Onsite Work Liaison Form to
declare reasons for postponing the kickoff.
If the customer requires immediate kickoff, ask the customer to specify and promise the
exact time. If the project is unable to be improved or does not meet the specified
requirements, you must sign a memorandum with the customer.
Table 2-3 lists the checklist for the installation conditions of the BTS3801C.
Table 2-3 Checklist for the installation conditions of the BTS3801C
No.

Item

Description
z

Site selection
z

Site
construction

The site is not full of dust or harmful gases, or subject to a


high temperature, flammable materials, explosive materials,
electromagnetic interference (large-sized radar station,
radio transmitting station, electric substation), or instable
voltage.
The site is not subject to frequent heavy quakes or strong
noises.
During engineering planning, you must select a site suitable
for the outdoor communications equipment by taking into
such factors as hydrology, geology, earthquake, electric
power, and transportation.
Do not install the BTS3801C in a place close to the seaside.
The distance between the seaside and the cabinet is
greater than 500 m. The air inlets of the cabinet stay
opposite to the wind from the sea.
Do not install the BTS3801C in a location that is prone to
water collection. Mount the BTS3801C on a cement step in
higher places.
If you install the BTS3801C on the pole, ensure that the pole
meet the load-bearing requirements.
If you install the BTS3801C on the wall or the stand, ensure
that the wall or the stand meets the load-bearing
requirement.

Huawei Technologies Proprietary


2-4

BTS3801C Installation Guide

No.

Chapter 2 Preparing the Installation

Item

Description

Environment

The temperature and humidity outside the cabinet meet the


specified requirements.

Grounding
resistance

AC voltage
z

The grounding resistance is smaller than 5 ohms. For


regions where yearly thunderstorm days are less than 20,
the resistance can be smaller than 10 ohms.
The AC voltage in the equipment room stays between 150 V
AC and 300 V AC with the rated frequency at 47 Hz to 63
Hz. The AC distribution switches and the AC power cables
are installed in place.
If the voltage is not stable, you must use voltage-adjusting
or voltage-stabilizing devices to keep the voltage within the
specified range.
If you have installed an upper-level protective part of the
BTS3801C, ensure that the through current of the protective
part is no smaller than that of the MCBs in the SPD or AFB.
The upper-level protective part of the BTS3801C is installed
with leakage current protective devices.
To ensure uninterrupted services, use the UPS system.

Never connect the neutral line of the AC power supply to the


AC grounding protection ground of any communications device in the
equipment room.
z

The DC voltage in the equipment room stays between37 V


DC and 60 V DC. The DC distribution switches and the DC
power cables are installed in place.
If the voltage is not stable, you must use voltage-adjusting
or voltage-stabilizing devices to keep the voltage within the
specified range.

DC voltage

Lightning
protection

The AC power supply system of the equipment room is


equipped with an AC lightning protection box whose grounding
cable is shorter than 30 m with the cross sectional area of no
2
smaller than 25 mm .

Trunk cable

Do not route the trunk cables overhead outdoors. If you have


to, use double-shielded or metal-shielded cables, and connect
the outer shielding layer or the metal shielding of the cable to
the protection grounding bar of the equipment room.

10

Transmission The transmission system is commissioned, and its capacity


system
meets the engineering requirements.

Huawei Technologies Proprietary


2-5

BTS3801C Installation Guide

Chapter 2 Preparing the Installation

2.6 Unpacking the BTS3801C


2.6.1 Unpacking the Case

Caution:
z

To protect the equipment and find out the cause, store the unpacked BTS3801C
inside the equipment room.

Take photos of the storage environment, rusted or corroded devices, and packaging
boxes and materials, and then file the photos.

Store the unpacked boxes and materials for future use.

After the project begins, the project supervisor and the customer must check the
shipping components and ensure that:
z

The total number of components conforms to that in the packing list attached to the
packing case.

The components are shipped to the specified site.

The packing case is in good condition.

The BTS3801C is not placed upside down.

Stop unpacking the BTS3801C and find out the cause in either of the following cases:
z

The outer package is damaged or soaked.

The equipment is soaked and becomes rusty.

Feed back this to your Huawei local representative office.

Caution:
When transporting or moving the equipment, components, or parts, you must:
z

Prevent them against collision with doors, walls, shelves, or other objects.

Avoid touching the uncoated metal surface of the equipment, components, or parts
with sweat soaked or dirty gloves.

If the outer package is in good condition, follow the following steps to unpack and
inspect the BTS3801C:
1)

Unpack the case with Packing List (a label indicating that the packing list is
included in the case), and then take out the Packing List.

2)

Check the shipped components in the case according to the Packing List.

Huawei Technologies Proprietary


2-6

BTS3801C Installation Guide

3)

Chapter 2 Preparing the Installation

Complete the Cargo Shortage and Miscarriage Report upon any short or wrong
shipment.

4)

Complete the Cargo Replacement Application Form upon any equipment


damage.

5)

Sign the Packing List together with the customer.

2.6.2 Unpacking the Carton


Cartons are used to pack cables, circuit boards, or terminal devices. During
transportation, these circuit boards are usually put in antistatic bags.
When unpacking the circuit boards, you must:
z

Take antistatic measures to avoid any damage to these boards.

Note the temperature and humidity of the environment.

To keep the antistatic bags dry, put desiccant in the bags to absorb moisture. After
transporting the equipment to a place with higher temperature and humidity, unpack it
30 minutes later. Otherwise, moisture condenses on the surface of the equipment, and
causes damage to it.
To unpack the carton containing the BTS3801C rack or other devices, perform the
following:
1)

Check the models and the quantity of components inside the carton according to
the carton label.

2)

Cut the straps with a pair of diagonal pliers.

3)

Cut the tapes that cover the seams on top of the carton with a knife.
To avoid damaging the equipment inside, do not apply too much force.

4)

Open the carton, and then remove the foam packing material.
To remove the foam packing material, pull it straight up.

5)

Check the number and type of components against the Packing List, and then
accept them.

Figure 2-1 shows the unpacked carton.

Huawei Technologies Proprietary


2-7

BTS3801C Installation Guide

Chapter 2 Preparing the Installation

2
4
3

(1) ESD plastic bag


(3) Foam packing pad

(2) BTS3801C rack


(4) Carton

Figure 2-1 Unpacked carton


It is required for each person to unpack one carton at a time. Before discarding the
carton, ensure that all components in the carton are taken out.

Huawei Technologies Proprietary


2-8

BTS3801C Installation Guide

Chapter 3 Overview of the BTS3801C

Chapter 3 Overview of the BTS3801C


3.1 About This Chapter
This chapter describes the following information necessary for the BTS3801C
installation:
z

BTS3801C Main Components

Space Requirements

Introduction Scenarios

3.2 BTS3801C Main Components


Figure 3-1 shows the main BTS3801C components.

3
2

(1) Case
(3) RRU3801C module

(2) BBU3806C module


(4) Rack

Figure 3-1 Main components of the BTS3801C

3.3 Space Requirements


3.3.1 Recommended Space Requirements
Figure 3-2 shows the recommended space requirements for the BTS3801C. It is
recommended to keep the following clearances:
z

500 mm under the BTS3801C for cabling.

800 mm in front of the BTS3801C for maintenance.


Huawei Technologies Proprietary
3-1

BTS3801C Installation Guide

Chapter 3 Overview of the BTS3801C

200 mm above the BTS3801C for maintenance.

300 mm on the left of the BTS3801C for maintenance.

300 mm on the right of the BTS3801C for maintenance.

200

390

800

610

300

380

300

500

Figure 3-2 Recommended space requirements for the BTS3801C (unit: mm)

3.3.2 Minimal Space Requirements


Figure 3-3 shows the minimal space requirements for the BTS3801C. You must keep
the following clearances:
z

300 mm under the BTS3801C for cabling.

600 mm in front of the BTS3801C for maintenance.

200 mm above the BTS3801C for maintenance.

100 mm on the left of the BTS3801C for maintenance.

100 mm on the right of the BTS3801C for maintenance.

Huawei Technologies Proprietary


3-2

BTS3801C Installation Guide

Chapter 3 Overview of the BTS3801C

200

390

600

610

100

380

100
300

Figure 3-3 Minimal space requirements for the BTS3801C (unit: mm)

3.4 Introduction Scenarios


As shown in Figure 3-4, the BTS3801C supports the following three installation
scenarios:
z

On a pole

On a wall

On a stand

Huawei Technologies Proprietary


3-3

BTS3801C Installation Guide

Chapter 3 Overview of the BTS3801C

(1) BTS3801C mounted on the pole


(2) BTS3801C mounted on the wall
(3) BTS3801C mounted on the stand

Figure 3-4 Installation scenarios

Huawei Technologies Proprietary


3-4

BTS3801C Installation Guide

Chapter 4 Installation Procedure and Guidelines

Chapter 4 Installation Procedure and Guidelines


4.1 About This Chapter
This chapter describes the following:
z

Flow Chart of Installing the BTS3801C

Installation Guidelines

4.2 Flow Chart of Installing the BTS3801C


Figure 4-1 shows the flow chart of installing the BTS3801C and its cables.
Start

Install rack

Install RRU3801C module

Install BBU3806C module

Install cables

Installation check
passed

Reinstall parts not passing


the check

Y
Install case

End

Figure 4-1 Flow chart of installing the BTS3801C and its cables

Huawei Technologies Proprietary


4-1

BTS3801C Installation Guide

Chapter 4 Installation Procedure and Guidelines

Note:
z

The flow chart in Figure 4-1 is recommended.

Specific installation depends on the field requirements.

4.3 Installation Guidelines


Table 4-1 lists the installation guidelines.
Table 4-1 Installation guidelines
Action

Refer to

Description

Install the rack.

Chapter 5 "Installing
the Rack."

Install the rack, depending on


specific scenarios.

Install the
RRU3801C module.

Chapter 6 "Installing
the RRU3801C and
BBU3806C Modules."

Install the RRU3801C module and


BBU3806C module in the rack.

Chapter 7 "Installing
the Cables."

Install the
BBU3806C module.
Install the cables.

Install the cables between the


BBU3806C module and the
RRU3801C module.
For internal cable connections,
refer to BBU3806C Installation
Guide
and
RRU3801C
Installation Guide.

Install the case.

Chapter 8 "Installing
the Case."

Install the case at your site.

Complete the
installation.

Chapter 9 "Completing
the Installation."

After the installation,


z

Huawei Technologies Proprietary


4-2

Check the BTS3801C, cables,


and field sanitation.
Power on the BTS3801C to
check if all the components
work properly.

BTS3801C Installation Guide

Chapter 5 Installing the Rack

Chapter 5 Installing the Rack


5.1 About This Chapter
This chapter describes the following:
z

Installing the Rack on the Pole

Installing the Rack on the Wall

Installing the Rack on the Stand

5.2 Installing the Rack on the Pole


To install the rack on the pole, perform the following:
1)

Mount the two fixture assemblies on the pole by leveling the two pole fixtures in
each assembly and keeping a distance of 378 mm between both assemblies, as
shown in Figure 5-1.

3 2

1
378

(1) M10 x 180 bolt

(2) Spring washer 10

(3) Flat washer 10

(4) Pole fixture

Figure 5-1 Mounting the fixture assemblies (unit: mm)

Note:
The recommended pole diameter stays between 60 mm and 114 mm.

Huawei Technologies Proprietary


5-1

BTS3801C Installation Guide

2)

Chapter 5 Installing the Rack

Install the rack by fitting the rack tabs into the anchor slots on the pole fixture, as
shown in Figure 5-2.
Ensure that the four washers on the rack back are aligned with the four holes at
the outer side of the two pole fixtures, as shown in Figure 5-3.
1 2

(1) Anchor slots

(2) Tabs

Figure 5-2 Installing the rack

Huawei Technologies Proprietary


5-2

BTS3801C Installation Guide

Chapter 5 Installing the Rack

5
4
3

(1) Rack
(4) Tab

(2) Washer
(5) M10 180 bolt

(3) Pole fixture


(6) Pole

Figure 5-3 Aligning the four washers with the pole fixture holes
3)

Secure the rack by tightening the four M10 x 45 bolts, as shown in Figure 5-4.

Huawei Technologies Proprietary


5-3

BTS3801C Installation Guide

Chapter 5 Installing the Rack

1
2

3
4
5

(1) Pole
(4) Spring washer 10

(2) Rack
(5) M10 x 45 bolt

(3) Flat washer 10

Figure 5-4 Securing the rack


The rack is installed on the pole.

5.3 Installing the Rack on the Wall


To install the rack on the wall, perform the following:
1)

Place the mounting frame against the wall, and then mark the four anchor points
with a marker pen or by referring to the inter-hole distances in Figure 5-5.

Huawei Technologies Proprietary


5-4

BTS3801C Installation Guide

Chapter 5 Installing the Rack

378

228

(1) Mounting frame

(2) Anchor point

Figure 5-5 Determining anchor points (unit: mm)

Caution:
The drilled holes must be 72 mm to 80 mm deep.

2)

Drill four holes at the marked points with a 16 drill bit.


The drill bit is a 16 one. After the holes are available, clear up all dust both
inside and around the holes with a cleaner. If the inter-hole distance is too large or
small, locate and drill holes again.

Caution:
When installing the expansion bolt assembly, ensure that:
z

The guiding ribs on the nut are in full contact with the guiding slots on the tube.

The upper end face of the expansion tube is completely buried into the wall. If not,
the mounting frame cannot be leveled against the wall.

Huawei Technologies Proprietary


5-5

BTS3801C Installation Guide

3)

Chapter 5 Installing the Rack

Remove the M12 x 80 bolt, flat washer 12, and spring washer 12, put the nut and
expansion tube into the hole, and then hammer the tube until it is completely
buried into the wall, as shown in Figure 5-6.

(1) M12 x 80 bolt


(5) Nut

(2) Spring washer 12 (3) Flat washer 12 (4) Expansion tube


(6) Hole
(7) Wall

Figure 5-6 Installing the expansion bolt assembly


4)

Place the mounting frame against the wall, and then align the frame with the four
marked anchor points.

5)

Lead each bolt through the spring washer 12, and flat washer 12 in turn, and then
put each bolt into the expansion tube through the hole on the mounting frame, as
shown in Figure 5-7.

Huawei Technologies Proprietary


5-6

BTS3801C Installation Guide

Chapter 5 Installing the Rack

5
4

3
2
1

(1) M12 x 80 bolt


(2) spring washer 12
(4) Mounting frame (5) Wall

(3) flat washer 12

Figure 5-7 Installing the mounting frame


6)

Fix the mounting frame to the wall by tightening the bolts clockwise with the
wrench.

7)

Install the rack by fitting the tabs on the rack back into the anchor slots on the
frame, as shown in Figure 5-8.
Ensure that the four washers on the rack back are aligned with the four holes on
the frame, as shown in Figure 5-9.

Huawei Technologies Proprietary


5-7

BTS3801C Installation Guide

Chapter 5 Installing the Rack


1

(1) Anchor slots

(2) Tabs

Figure 5-8 Installing the rack (a)

(1) Rack
(4) Hook

(2) Washer
(5) Wall

(3) Mounting frame

Figure 5-9 Installing the rack (b)

Huawei Technologies Proprietary


5-8

BTS3801C Installation Guide

8)

Chapter 5 Installing the Rack

Secure the rack to the mounting frame with four M10 x 45 bolts, as shown in
Figure 5-10.

1
2
3

(1) Flat washer 10

(2) Spring washer 10

(3) M10 x 45 bolt

Figure 5-10 Securing the rack


The rack is installed on the wall.

5.4 Installing the Rack on the Stand


To install the rack on the stand, perform the following:
1)

Place the stand in the determined place, and then mark the four anchor points with
the marker or by referring to the inter-hole distances in Figure 5-11.

Huawei Technologies Proprietary


5-9

BTS3801C Installation Guide

Chapter 5 Installing the Rack


1

388

520

520

388

(1) Anchor point

Figure 5-11 Determining the anchor points (unit: mm)

Caution:
The drilled holes must be 52 mm to 60 mm deep

2)

Drill holes at the marked points with a percussion drill.


The drill bit is a 16 one. After the holes are available, clear up all dust both inside
and around the holes with a cleaner. If the inter-hole distance is too large or small,
locate and drill holes again.

Caution:
When installing the expansion bolt assembly, ensure that:
z

The guiding ribs on the nut are in full contact with the guiding slots on the tube.

The upper end face of the expansion tube is completely buried into the ground.If not,
the stand cannot be leveled on the ground.

Huawei Technologies Proprietary


5-10

BTS3801C Installation Guide

3)

Chapter 5 Installing the Rack

Remove the M12 x 60 bolt, flat washer 12, and spring washer 12, and then put
the nut and expansion tube into the hole, as shown in Figure 5-12.

1
2
3

4
5

(1) M12 x 60 bolt


(2) Spring washer 12
(4) Expansion tube (5) Nut

(3) Flat washer 12

Figure 5-12 Installing the expansion bolt assembly

Caution:
The expansion tube must be hammered into the wall. This secures the stand on the
ground.

4)

Hammer the tube until it is completely buried into the ground.

5)

Lift the stand, and then align the stand with the four marked anchor points.

Huawei Technologies Proprietary


5-11

BTS3801C Installation Guide

Chapter 5 Installing the Rack

1
2
3
4

(1) Stand
(2) M12 x 60 bolt
(3) Flat washer 12
(4) Spring washer 12 (5) Expansion tube (6) Nut

Figure 5-13 Installing the stand


6)

Lead each M12 x 60 bolt through the spring washer 12, and flat washer 12 in turn,
put each bolt into the expansion tube through the hole on the stand, as shown in
Figure 5-13, and then tighten the bolts with the wrench.

7)

Install the mounting bracket on the stand, as shown in Figure 5-14.

Huawei Technologies Proprietary


5-12

BTS3801C Installation Guide

Chapter 5 Installing the Rack

2
1

(1) Rack

(2) Washer

(3) Hook on the rack

(4) Stand

Figure 5-14 Installing the rack


8)

Secure the rack to the stand with four M10 x 50 bolts, as shown in Figure 5-15.

Huawei Technologies Proprietary


5-13

BTS3801C Installation Guide

Chapter 5 Installing the Rack

2
3

(1) Flat washer 10

(2) Spring washer 10

(3) M10 x 50 bolt

Figure 5-15 Securing the rack


The rack is installed on the stand.

Huawei Technologies Proprietary


5-14

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

Chapter 6 Installing the RRU3801C and BBU3806C


Modules
6.1 About This Chapter
This chapter describes the following:
z

Locations of the RRU3801C and BBU3806C Modules

Installing the RRU3801C Module

Installing the BBU3806C Module

6.2 Locations of the RRU3801C and BBU3806C Modules


Figure 6-1 shows the locations of the RRU3801C and BBU3806C modules in the rack.

RRU3801C BBU3806C
Figure 6-1 Locations of the RRU3801C and BBU3806C modules

6.3 Installing the RRU3801C Module:


To install the RRU3801C module in the rack, perform the following:
1)

Remove the locking piece from the RRU3801C module by unfastening the screws,
as shown in Figure 6-2.

Huawei Technologies Proprietary


6-1

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

(1) RRU3801C module (2) Screw (3) Locking piece

Figure 6-2 Removing the locking piece


2)

Push the module into the rack along the guide rails, as shown in Figure 6-3.

2
1

(1) RRU3801C module (2) Guide rail

Figure 6-3 Installing the module in the rack


3)

Remove the two screws from the upper angle piece on the module, and then
remove the bolt from the rack, as shown in part A of Figure 6-4.

Huawei Technologies Proprietary


6-2

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

(1) Screw (2) Upper angle piece (3) Bolt

Figure 6-4 Securing the RRU3801C module (a)


4)

Lift the upper angle piece, and then tighten the screws and the bolt, as shown in
part B of Figure 6-4.

5)

Loosen the two screws from the lower angle piece on the module, and then
remove the two bolts from the rack, as shown in part A of Figure 6-5.

Huawei Technologies Proprietary


6-3

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

3
(1) Lower angle piece (2) Screw (3) Bolt

Figure 6-5 Securing the RRU3801C module (b)


6)

Pull down the lower angle piece, and then tighten the screws and the bolts, as
shown in part B of Figure 6-5.

The RRU3801C module is installed in the rack.

6.4 Installing the BBU3806C Module


To install the BBU3806C module in the rack, perform the following:
1)

Unfasten the two screws from the locking piece, and the remove the locking piece,
as shown in Figure 6-6.

Huawei Technologies Proprietary


6-4

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

(1) BBU3806C module (2) Locking piece

(3) Screw

Figure 6-6 Removing the locking piece


2)

Push the BBU3806C module into the rack along the guide rails, as shown in
Figure 6-7.

1
3

(1) Guide rail

(2) RRU3801C module (3) BBU3806C module

Figure 6-7 Install the BBU3806C module in the rack


3)

Remove the two screws from the upper angle piece on the BBU3806C module,
and then remove the bolt from the rack, as shown in part A of Figure 6-8.
Huawei Technologies Proprietary
6-5

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

2
1

(1) Upper angle piece (2) Screw (3) Bolt

Figure 6-8 Securing the BBU3806C module (a)


4)

Lift the upper angle piece, and then tighten the screws and the bolt, as shown in
part B of Figure 6-8.

5)

Loosen the two screws from the lower angle piece on the BBU3806C module, and
then remove the two bolts from the rack, as shown in part A of Figure 6-9.

Huawei Technologies Proprietary


6-6

BTS3801C Installation Guide

Chapter 6 Installing the RRU3801C and BBU3806C Modules

1
2

A
(1) Lower angle piece

B
(2) Screw (3) Bolt

Figure 6-9 Securing the BBU3806C module


6)

Pull down the lower angle piece, and then tighten the screws and the bolts, as
shown in part B of Figure 6-9.

The BBU3806C module is installed in the rack.

Huawei Technologies Proprietary


6-7

BTS3801C Installation Guide

Chapter 7 Installing the Cables

Chapter 7 Installing the Cables


7.1 About This Chapter
This chapter describes the following:
z

Connectors and Ports at the BTS3801C Bottom

Ports in the Cabling Cavities

Cables for Field Installation

Installing the PGND Cable

Installing the Optical Cable

Installing the High Speed CPRI Signal Cable

Note:
z

This chapter describes how to install the PGND cable and the cables between the
BBU3806C and RRU3801C modules.

For details about how to install the other cables, refer to BBU3806C Installation
Guide and RRU3801C Installation Guide.

7.2 Connectors and Ports at the BTS3801C Bottom


Figure 7-1 shows the labeled connectors and ports at the BTS3801C bottom.

Huawei Technologies Proprietary


7-1

BTS3801C Installation Guide

Chapter 7 Installing the Cables

6
7

8
2
9
10
11

(1) ANT_RXB
(4) PWR (RRU3801C module)
(7) 2*FE
(10) 8*E1/T1/J1

(2) ANT_TX/RXA
(5) RS485&EXT_ALM
(8) OPT
(11) GPS

(3) RX_IN/OUT
(6) PWR (BBU3806C module)
(9) E1 GND

Figure 7-1 Connectors and ports at the BTS3801C bottom


Table 7-1 lists the connectors and ports at the BTS3801C bottom.
Table 7-1 Connectors and ports at the BTS3801C bottom
Location

RRU3801C
module
bottom

BBU3806C
module
bottom

Label

Connector
type

Function

PWR

9-pin round
waterproof

Socket for the 220 V AC or 48 V


DC power

Rx_IN/OUT

DB2W2

Connector for uplink signals from


two RRU3801Cs within the same
sector

ANT_TX/RXA

DIN round
waterproof

Port for main Tx/Rx

ANT_RXB

DIN round
waterproof

Port Rx diversity

PWR

9-pin round
waterproof

Socket for the 220 V AC or 48 V


DC power

OPT

4-pin round
waterproof

Iub optical port

Huawei Technologies Proprietary


7-2

BTS3801C Installation Guide

Location

Chapter 7 Installing the Cables

Connector
type

Label

Function

E1 GND

19-pin round
waterproof

Port for grounding connections of


the E1 coaxial cable

8*E1/T1/J1

32-pin round
waterproof

Port for transmitting 8-channel


E1/T1/J1 signals

RS485&EXT_
ALM

DB15
waterproof

Connector for transmitting alarm


signals

2*FE

8-pin round
waterproof

Port for IP transmission

GPS

N-type female

Port for GPS signal input

7.3 Ports in the Cabling Cavities


Figure 7-2 shows the ports in the BTS3801C cabling cavities.
21

7
6
5

(1) ALD
(4) CPRI_W
(7) CPRI1

(2) EXT_ALM/FAN
(5) EIa
(8) CPRI2

(3) CPRI_E
(6) CPRI0

Figure 7-2 Ports in the BTS3801C cabling cavities


Table 7-2 lists the ports in the BTS3801C cabling cavities.

Huawei Technologies Proprietary


7-3

BTS3801C Installation Guide

Chapter 7 Installing the Cables

Table 7-2 Ports in the BTS3801C cabling cavities


Location

RRU3801C
cabling cavity

Label

Connector type

Function

ALD

DB15

RET antenna connector

EXT_ALM/FAN

DB15

Port for dry node alarms

ESFP socket

To the optical port or


CPRI electrical port of
the lower-level
transmission equipment

ESFP socket

To the optical port or


CPRI electrical port of
the upper-level
transmission equipment

ESFP socket

To the optical port or


CPRI electrical port of
the RRU3801C

CPRI_E

CPRI_W

CPRI2
CPRI1
CPRI0
BBU3806C
cabling cavity

EIa

MDR36

Connector for the


inter-BBU3806C
cable
Reserved
for
BBU3806C capacity
expansion

7.4 Cables for Field Installation


Table 7-3 lists the cables necessary for field installation.
Table 7-3 Cables for field installation
Cable

PGND cable

Connector
type
OT or 2-hole
terminal

Grounding bolt on the BTS3801C

OT or 2-hole
terminal

Protection grounding bar

LC

Port labeled CPRI_W in the


RRU3801C cabling cavity

LC

Port labeled CPRI0 in the


BBU3806C cabling cavity

ESFP

Port labeled CPRI_W in the


RRU3801C cabling cavity

ESFP

Port labeled CPRI0 in the


BBU3806C cabling cavity

Optical cable

High speed
CPRI signal
cable

Connect to

Remarks

Mandatory

Huawei Technologies Proprietary


7-4

Mandatory

Reserved

BTS3801C Installation Guide

Chapter 7 Installing the Cables

Figure 7-3 shows the optical cable connections between the RRU3801C and the

CPRI_W
RX TX

RX TX RX TX RX TX
CPRI2 CPRI1 CPRI0

CPRI_E
RX TX

BBU3806C modules.

BBU3806C
cabling cavity

RRU3801C
cabling cavity

Figure 7-3 Optical cable connections between RRU3801C and BBU3806C modules

7.5 Installing the PGND Cable


7.5.1 Introduction to the BTS3801C PGND Cable
Figure 7-4 shows the yellow green or green PGND cable with the cross sectional area
of 25 mm2. If you prepare the cable by yourself, choose a copper-based cable with the
cross sectional area of no smaller than 25 mm2 and make the OT terminals.
1

(1) OT terminal

Figure 7-4 PGND cable


You may choose the PGND cable color and the 2-hole terminal, depending on local
regulations. Figure 7-5 shows the 2-hole terminal.

Figure 7-5 2-hole terminal

Huawei Technologies Proprietary


7-5

BTS3801C Installation Guide

Chapter 7 Installing the Cables

7.5.2 Connecting the PGND Cable


To connect the PGND cable to the BTS3801C, perform the following:
1)

Connect one end of the PGND cable to the grounding bolt on the BTS3801C, as
shown in Figure 7-6.

1
2

(1) Crimping sleeve

(2) PGND cable

(3) Protection grounding bolt

Figure 7-6 Connecting the PGND cable to the BTS3801C

Note:
z

When installing the OT terminal, ensure that the crimping sleeve is positioned as
shown in part A of Figure 7-6.

The crimping sleeve in part B of Figure 7-6 is not allowed.

2)

Connect the other end of the cable to the protection grounding bar on site.

3)

Label the cable.

The PGND cable is installed.


Huawei Technologies Proprietary
7-6

BTS3801C Installation Guide

Chapter 7 Installing the Cables

7.6 Installing the Optical Cable


7.6.1 Introduction to the Optical Cable
The optical cable connecting the BBU3806C module to the RRU3801C module
contains two wires. Each end of the optical cable has two LC connectors, as shown in
Figure 7-7.
1

1A

2A

1B

2B

50

50

(1) LC connector

(2) Label

(3) Fiber tail

(4) 2-wire optical cable

Figure 7-7 Optical cable (unit: mm)


Table 7-4 Labeled fiber tail connections
Label

Connect to

1A

Tx port labeled CPRI0 on the BBU3806C module

1B

Rx port labeled CPRI0 on the BBU3806C module

2A

Rx port labeled CPRI_W on the RRU3801C module

2B

Tx port labeled CPRI_W on the RRU3801C module

Note:
The connection listed in Table 7-4 is recommended.

7.6.2 Optical Cable Connections between RRU3801C and BBU3806C

Caution:
z

Do not overbend the optical cable or fiber tail.

The bending radius of the optical cable or the fiber tail is no smaller than 150 mm or
40 mm.

Huawei Technologies Proprietary


7-7

BTS3801C Installation Guide

Chapter 7 Installing the Cables

To connect the optical cable between the BBU3806C and the RRU3801C modules,
perform the following:
1)

Remove the BBU3806C module cabling cavity cover, as shown in Figure 7-8.

5
4

3
(1) Cabling cavity
(2) Cover
(3) Waterproof block
(4) Cabling troughs for optical cables or high speed signal cables
(5) Cabling trough for the inter-BBU3806C cable

Figure 7-8 Removing the cover from the BBU3806C module cabling cavity

Caution:
Protect the ESFP optical module with a dustproof cap before installing the optical cable
connector.

2)

Wear a pair of ESD gloves.

3)

Insert the ESFP optical module into the socket in the BBU3806C module cabling
cavity, as shown in Figure 7-9.

Huawei Technologies Proprietary


7-8

BTS3801C Installation Guide

Chapter 7 Installing the Cables

(1) ESFP socket

(2) ESFP optical module

Figure 7-9 Inserting the ESFP optical module into the BBU3806C module socket
4)

Remove the RRU3801C module cabling cavity cover, as shown in Figure 7-10.

6
5

3
(1) Cabling cavity
(2) Cover
(3) Waterproof block
(4) Cabling troughs for optical cables
(5) Cabling trough for the dry node alarm cable
(6) Cabling trough for the RET signal cable

Figure 7-10 Removing the cover from the RRU3801C module cabling cavity

Huawei Technologies Proprietary


7-9

BTS3801C Installation Guide

5)

Chapter 7 Installing the Cables

Insert the ESFP optical module into the socket in the RRU3801C module cabling
cavity, as shown in Figure 7-11.

(1) ESFP socket

(2) ESFP optical module

Figure 7-11 Inserting the ESFP optical module into the RRU3801C module socket

6)

Connect the two LC connectors labeled 1A and 1B to the port labeled CPRI0 in the
BBU3806C module cabling cavity.

7)

Remove the waterproof blocks from the BBU3806C module cabling cavity.

8)

Route the optical cables along troughs 1 and 2 numbered from left to right.

9)

Bind the optical cables to the bundling slot on the lower angle piece with cable ties.

Note:
z

You can bind all the cables to the bundling slots with cable ties after connecting
them in the cabling cavity.

Cables routed in the BBU3806C module cabling cavity include the optical cable (or
high speed CPRI signal cable) and the inter-BBU3806C cable.

Cables routed in the RRU3801C module cabling cavity include the optical cable (or
high speed CPRI signal cable), the dry node alarm cable, and the RET signal cable.

10) Connect the two LC connectors labeled 2A and 2B at the other end of the fiber tails
to the port labeled CPRI_W in the RRU3801C module cabling cavity.
11) Remove the waterproof blocks from the RRU3801C module cabling cavity.
12) Route the optical cables along troughs 1 and 2 numbered from left to right.
13) Bind the optical cables to the bundling slot on the lower angle piece with cable ties.
14) Label the optical cables.

Huawei Technologies Proprietary


7-10

BTS3801C Installation Guide

Chapter 7 Installing the Cables

Caution:

Do not remove the waterproof blocks from reserved cabling troughs.

15) Reinstall the RRU3801C module cabling cavity cover by tightening the screws in
the order, as shown in Figure 7-12.

Figure 7-12 Reinstalling the RRU3801C module cabling cavity cover

16) Reinstall the BBU3806C module cabling cavity cover by tightening the screws in
the order, as shown in Figure 7-13.

Huawei Technologies Proprietary


7-11

BTS3801C Installation Guide

Chapter 7 Installing the Cables

Figure 7-13 Reinstalling the BBU3806C module cabling cavity cover

The optical cable is installed.

7.7 Installing the High Speed CPRI Signal Cable


7.7.1 Introduction to the High Speed CPRI Signal Cable
The high speed CPRI signal cable transmits high speed electrical signals over a short
distance between the BBU3806C and the RRU3801C modules.
Both ends of the cable are ESFP connectors, as shown in Figure 7-14.
1

(1) ESFP connector

Figure 7-14 CPRI high-speed signal cable

This cable is optional.

Huawei Technologies Proprietary


7-12

BTS3801C Installation Guide

Chapter 7 Installing the Cables

7.7.2 Connecting the High Speed CPRI Signal Cable


To connect the high speed CPRI signal cable, perform the following:
1)

Remove the BBU3806C module cabling cavity cover of the, as shown in Figure
7-8.

2)

Wear a pair of ESD gloves.

3)

Insert the ESFP connector at one end of the high speed CPRI signal cable into the
ESFP socket in the BBU3806C module cabling cavity.

4)

Remove the RRU3801C module cabling cavity cover, as shown in Figure 7-10.

5)

Insert the ESFP connector at the other end of the high speed CPRI signal cable
into the ESFP socket in the RRU3801C module cabling cavity.

6)

Remove the waterproof blocks from the BBU3806C module cabling cavity.

7)

Route the high speed CPRI signal cables along troughs 1, 2, and 3 numbered from
left to right.

8)

Bind the high speed CPRI signal cables to the bundling slot on the lower angle
piece with cable ties.

Note:
z

You can bind all the cables to the bundling slots with cable ties after connecting
them in the cabling cavity.

Cables routed in the BBU3806C module cabling cavity include the high speed CPRI
signal cable (or optical cable) and the inter-BBU3806C cable.

Cables routed in the RRU3801C module cabling cavity include the high speed CPRI
signal cable (or optical cable), dry node alarm cable, and RET signal cable.

9)

Remove the waterproof blocks from the RRU3801C module cabling cavity.

10) Route the high speed CPRI signal cables along troughs 1 and 2 numbered from
left to right.
11) Bind the high speed CPRI signal cables to the bundling slot on the lower angle
piece with cable ties.
12) Labels the high speed CPRI signal cables.

Note:

The waterproof blocks not in use must be reserved in the cabling troughs.

13) Reinstall the RRU3801C module cabling cavity cover by tightening the screws in
the order, as shown in Figure 7-12.

Huawei Technologies Proprietary


7-13

BTS3801C Installation Guide

Chapter 7 Installing the Cables

14) Install the BBU3806C module cabling cavity cover by tightening the screws in the
order, as shown in Figure 7-13.
The high speed CPRI signal cable is installed.

Huawei Technologies Proprietary


7-14

BTS3801C Installation Guide

Chapter 8 Installing the Case

Chapter 8 Installing the Case


Note:
z

Install the case after the modules and all the cables are connected and checked.

It is recommended to install the case after system commissioning. When loading the
software and commissioning the BBU3806C and RRU3801C modules, you may
need to check the operating status of the modules through the plastic maintenance
cavity covers.

8.1 About This Chapter


This chapter describes the following:
z

Installing the Case

8.2 Installing the Case


Note:
z

The case is installed on the pole, wall, and stand in the same way.

This section only takes pole installation as an example.

To install the case, perform the following:


1)

Check if the lockhole is positioned as shown in Figure 8-1.

If yes, go to step 2).

If no, turn the bolt at 90 with the key delivered with the BTS3801C.

Huawei Technologies Proprietary


8-1

BTS3801C Installation Guide

Chapter 8 Installing the Case

1
(1) Lockhole

Figure 8-1 Checking the lockhole position

2)

Install the case by fitting the case tabs into the anchor slots on the top of the rack,
as shown in Figure 8-2.

Huawei Technologies Proprietary


8-2

BTS3801C Installation Guide

Chapter 8 Installing the Case

2
1

(1) Case (2) Tab (3) Anchor slot

(4) Rack

Figure 8-2 Installing the case

3)

Hold both sides of the case, and then push the case with caution.
Ensure that the case fits the rack completely.

4)

Secure the case with two M6 x 16 screws, as shown in part A of Figure 8-3.
If it is inconvenient, secure the case from both sides, as shown in part B of Figure
8-3.

Huawei Technologies Proprietary


8-3

BTS3801C Installation Guide

Chapter 8 Installing the Case

1
1

(1) Screw

Figure 8-3 Tightening the screws at the case bottom

5)

Lock the BTS3801C by turning the key clockwise.

The case is installed.

Huawei Technologies Proprietary


8-4

BTS3801C Installation Guide

Chapter 9 Completing the Installation

Chapter 9 Completing the Installation


9.1 About This Chapter
This chapter describes the following:
z

Checking Hardware Installation

Powering on the BTS3801C

Checking Field Sanitation

9.2 Checking Hardware Installation


Table 9-1 gives the checklist for the hardware installation.
Table 9-1 Checklist for the hardware installation
Item

SN

Subitem

The BTS3801C cabinet is in strict compliance with


engineering design.

In the pole installation mode, the fixture assemblies and the


rack are secure and steady.
In the wall installation mode,

Holes on the mounting frame are well aligned with those


for expansion bolts.
The mounting frame is placed against the wall securely
and evenly.

In the stand installation mode,


4
Cabinet
installation

Holes on the rack are well aligned with those for


expansion bolts.
The stand is steady.

In the wall and stand installation modes, the BTS3801C are


secure and steady.

The space reserved in the maintenance cavity is no less than


400 mm.

The covers are fastened to the maintenance cavities of the


BBU3806C and the RRU3801C modules.
z

8
z
z

z
z

The covers are fastened to the cabling cavities of the


BBU3806C and the RRU3801C modules.
The empty cabling troughs are waterproofed.
The BTS3801C cabinet surface is clean.
The external paint is satisfactory.
All labels, tags, and nameplates are correct, legible and
complete.

Huawei Technologies Proprietary


9-1

BTS3801C Installation Guide

Item

Chapter 9 Completing the Installation

SN

Subitem
z

1
z

Cable
connection

The extra part of the power cable or PGND cable are stripped
off rather than coiled.

The lugs at both ends of the power cable or PGND cable are
securely soldered or crimped.

The bare wires and lug at the wiring terminals are tightly
wrapped up with insulating tapes or heat-shrink tubes.

The flat washers and spring washers are well mounted to all
wiring terminals.

All cables are neatly bundled with ties installed at even


intervals, to a proper tightness and in the same direction.

Power cables and the PGND cables are routed separately


from other cables.

Both ends of each cable are legible, that is, both ends are
labeled.

z
z
z

10

11
z

Power
cable

PGND
cable

All self-made PGND cables must be copper-based with


proper core diameter.
No switch, fuse, or short-circuit is allowed on the cable.

Extra cable ties are stripped off.


All cuts are smooth without sharp projection.
The power cable and signal cables must not be crossed.
If these cables are parallel, the space between them is
greater than 3 cm.
When the power cable and transmission cable are routed
on the wall, fix them with cabling clips.
When they are routed on the pole, fix those cables with
cable ties.
Ensure that the transmission cable is fitted with a
protection tube.
In outdoor routing, waterproof the protection tube.

12

All cable connections are secure. Pay special attention to


those at the module bottom.

When the UPS or storage batteries are mounted, the power


cable connections must be correct to ensure that the
BBU3806C and RRU3801C modules can work well even if
the AC mains power fails.

The AC power cable and the DC power cable are separately


routed.

The live wire and neutral wire correctly connect to the


terminal block on the external power supply equipment.

The BTS3801C PGND cable connects to the protection


grounding bar.

The cross sectional area of the PGND cable is no less than


2.
25 mm
Huawei Technologies Proprietary
9-2

BTS3801C Installation Guide

Item

Signal
cables

Chapter 9 Completing the Installation

SN

Subitem

When there is an RET antenna, ensure that the RET signal


cable is correctly connected.

When there is an SPD40R, ensure that the alarm cable is


correctly connected.

The optical cable is correctly connected.

9.3 Powering on the BTS3801C


For details about how to power on the BTS3801C, refer to BBU3806C Installation
Guide and RRU3801C Installation Guide.

9.4 Checking Field Sanitation


After checking the hardware installation and powering on the BBU3806C, check the
field sanitation with the checklist in Table 9-2.
Table 9-2 Checklist for field sanitation
No.

Item

There is no unnecessary stuff either inside the BTS3801C case or on its top.
The BTS3801C looks nice and clear with no fingerprints or other smears on
its surface.

There are no unneeded tapes or ties bound to the cables.

There are no tapes, ties, or stripped cables, wastepaper or packages around


the BTS3801C cabinet.

All the stuff around the BTS3801C is clean, neat and intact.

Huawei Technologies Proprietary


9-3

Potrebbero piacerti anche