Reversible Air Conditioner

Page

1 of 4

Document nr.

G0820158

1.

ACHP350

8.3.5

INTRODUCTION

The compact unit ACHP is a of a typical multipurpose rental design, flexible and easy to operate. The unit
can be used in three main operating modes:
Ventilation
Cooling
Heating
The advanced control system is able to select full automatic operating mode to maintain the required
temperature conditions. The unit can either operate at full outside air or on (partly) return air to save energy.
2.

KEY-DATA

Gross cooling capacity @ Eurovent conditions


Total absorbed power compressors
Air volume
Electrical power supply
Dimensions length x with x height
Weight
Air duct connection in - outlet

3.

IDENTIFICATION

Notes :

cooling
224
73

heating
215
62

34,000
3 ph +E 400V / 50 Hz
5800 x 2232 x 2605
4,900
2 x 800

units
kW
kW
3
m /h
V / Hz
mm
kg
mm

INFORMATION BULLETIN

ACHP350

Page

2 of 4

4.

TECHNICAL SPECIFICATION
ITEM
Performance data: return air operation
Gross cooling capacity
Sensible cooling effect
Moisture removal
Air inlet temperature
Ambient Temperature
Off coil condition
Air flow
Compressor Absorbed power
Gross COP
Maximum Ambient temperature at 27C return air temperature
Minimum Ambient temperature at 20C return air temperature
Performance Data: heating (heat pump mode)
Gross Heating capacity
Air inlet temperature
Ambient temperature
Air outlet temperature
Air Flow
Compressor Absorbed power
Gross COP
Minimum Ambient temperature at 20C return air temperature
Compressor
Compressor Type
Number of Compressors
Loading steps
Evaporator Data
Evaporator fan
Installed fan motor rating
Air volume control
Fan Speed
maximum external pressure at design flow 35,000 m3/h
Maximum air volume free outlet
Surface area / number of rows / fins per inch
Condenser Data
Number of Condenser Fans (circuit 1/2)
Installed kW per Fan
Total Air Volume
Maximum External Static Pressure
Surface area / number of rows / fins per inch
Refrigerant Data
Refrigerant Type
Number of Circuits
Refrigerant Charge Circuit 1 / 2
Electrical Data
Design Electrical Supply Voltage
Design Electrical Rating
Maximum Operating Current
Starting Current
Recommended Generator Set
Required Cable Size per Phase
Electrical Connection
Noise Data (1)
Sound Pressure Level at 10 Metres Lp (A)
Sound Power Level Lw (A)

Notes :

8.3.5

UNITS
kW
kW
kg/h
C / %
C / %
C / %
m3/h
kW
C
C
kW
C / %
C / %
C / %
m3/h
kW
C

n
%

kW
rpm
Pa
m3/h
m2/n/FPI

VALUE
227
155
106
27 / 50
35 / 40
13 / 93
34,000
73
3.1
44
10
214
20 / 50
7 / 87
48 / 14
34,000
62
3.45
-7
Scroll
4
0 -25-50-75-100
Centrifugal belt drive
backward curved
18.5
VSD
502
600
45,000
4.6 / 3 / 16

kW
m/h
Pa
m2/n/FPI

2/2
1.02
60,000
10
8.8 / 3 / 16

kg / kg

R410A
2
22.5 / 22.5

V / Hz
kVA
A
A
kVA
mm2
bobbin

3 ph 400 V / 50 Hz
125
180
340
200
70
M12

dB(A)
dB(A)

61
92

INFORMATION BULLETIN
Page

3 of 4

ACHP350
ITEM
Physical Data
Overall Length
Overall Width
Overall Height
Weight
Air duct connection in / outlet
Air Filter
Number of filter
Filter size
Condensate connection
Movex code
Plant number
Note:
1) Outside condition with supply and return ducting connected

Notes :

8.3.5
UNITS
Metres
Metres
Metres
kg
mm
Eurovent
n
mm x mm
GEKA

VALUE
5.836
2.270
2.605
4,900
2 x 800
80-85% G3
10 +5
500 x 500 + 800 x 500
1
AC0250REVAIC
YAVV

INFORMATION BULLETIN

ACHP350

Page

4 of 4

5.

DIMENSIONS

Notes :

8.3.5