Carrier-Class Router
ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://support.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright 2014 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited.
Revision History
Revision No.
Revision Date
Revision Reason
R1.0
2014-10-20
First edition
SJ-20140731105308-005|2014-10-20 (R1.0)
Contents
About This Manual ......................................................................................... I
Chapter 1 Installation Overview ................................................................ 1-1
1.1 Installation Flow ................................................................................................. 1-1
1.2 Installation Preparations ..................................................................................... 1-2
1.3 Unpacking and Checking Items ........................................................................... 1-6
III
SJ-20140731105308-005|2014-10-20 (R1.0)
IV
SJ-20140731105308-005|2014-10-20 (R1.0)
Intended Audience
This manual is intended for:
l
l
Installation engineers
Installation supervisors
Summary
Describes the installation flow, preparations, and how to unpack
and check items.
2, Cabinet Installation
cedures
I
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter
Summary
cable.
Describes how to remove the central guide rail of the network pro-
Conventions
This manual uses the following typographical conventions.
Typeface
Meaning
Italics
Bold
Constant width
II
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 1
Installation Overview
This chapter describes the ZXR10 M6000-S hardware installation flow and installation
preparations.
The installation personnel should meet the following requirements:
l
l
l
Table of Contents
Installation Flow .........................................................................................................1-1
Installation Preparations .............................................................................................1-2
Unpacking and Checking Items ..................................................................................1-6
1-1
SJ-20140731105308-005|2014-10-20 (R1.0)
SJ-20140731105308-005|2014-10-20 (R1.0)
Other facilities
Check the workbench, power outlet, alarm box, and other peripheral devices.
Caution!
Do not perform any installation operation if the environment check result is unsatisfactory.
Tool Preparation
For the tools and instruments used during the ZXR10 M6000-S installation, refer to Table
1-1.
Table 1-1 Tools and Instruments
Category
Tool
Legend
Tightening tools
1-3
SJ-20140731105308-005|2014-10-20 (R1.0)
Category
Tool
Legend
Claw hammer
Measuring tools
Tape measure
Marker pen
Clamping tools
Flat-nose pliers
Diagonal pliers
Combination pliers
1-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Category
Tool
Legend
Crowbar
Hoisting tools
Pulley blocks
Universal instruments
Multimeter
Special tools
Optical attenuator
Antistatic gloves
1-5
SJ-20140731105308-005|2014-10-20 (R1.0)
Category
Tool
Legend
Crimping pliers
Brush
Tweezers
Paper knife
Vacuum cleaner
Ladder
Documentation Preparations
Installation personnel must prepare at least the following technical documents:
l
l
l
l
This procedure describes how to unpack wooden cases, cartons, and board boxes.
l
l
Prerequisite
A flathead screwdriver, a claw hammer, diagonal pliers, a paper knife, and antistatic gloves
(or an antistatic wrist strap) are available.
Steps
1. Check the total number of items in accordance with the Packing List, and verify that
the outer packing is intact.
2. Remove the wooden case.
a. Move the wooden case with a fork lift to the installation site.
b. Open all tongue pieces with a flathead screwdriver, remove the upper cover of the
case, and then remove the sideboards, see Figure 1-2.
Figure 1-2 Unpacking a Wooden Case
1. Tongue
2. Flathead
screwdriver
c.
Take out the package list, technical documents, and parts for equipment
installation from Package 1.
Open the carton, and take out foam protectors and board boxes.
1-7
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Adhesive tape
2. Carton
3. Foam protector
4. Board label
5. Board box
6. Carton label
7. Packing strap
c.
For the board that is not installed immediately, put it back to its original package,
and then seal the package.
5. Verify that the items are in good condition and the quantity is correct before equipment
handover and storage.
End of Steps
1-8
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 2
Cabinet Installation
For the cabinet installation, refer to Bearer Network Product Cabinet (800 mm-Deep) Quick
Installation Guide.
2-1
SJ-20140731105308-005|2014-10-20 (R1.0)
2-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 3
Prerequisite
l
l
l
Steps
1. In accordance with the engineering design documents, determine the installation
position of the chassis in the cabinet.
In general, for a standard cabinet, 1U equals the height of three installation holes, see
Figure 3-1. The chassis should be at least 1U (1U = 44.45 mm) above the cabinet
bottom.
3-1
SJ-20140731105308-005|2014-10-20 (R1.0)
3-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
Use specified handles only. Do not attempt to lift the chassis with other handles of the
chassis.
Engineers should lift up or put down the chassis at the same time to balance the weight.
3-3
SJ-20140731105308-005|2014-10-20 (R1.0)
3-4
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
The protective grounding cable of the device cabinet to the power distribution cabinet
is installed.
Antistatic gloves, cross screwdriver, and screw and bolt assemblies are available.
Context
The protection ground cable is the grounding cable of the equipment, and it is a 35 mm2
cable in yellow-green. The installation apertures of both the cable terminals are 6 mm.
3-5
SJ-20140731105308-005|2014-10-20 (R1.0)
For the overview of a protective grounding cable, see Figure 3-6. For how to prepare a
protective grounding cable, refer to Appendix B Preparing Power Cables and Protective
Grounding Cables.
Figure 3-6 M6000-18S Grounding Cable
Steps
1. Wear antistatic gloves.
2. Use the cross screwdriver to remove the screw and bolt assembly at the grounding
point of the chassis.
3. Connect one end of the protective grounding cable to the grounding rod of the chassis,
and the other end to the grounding rod inside the cabinet, and use a screw and bolt
assembly to fasten the cable.
For an overview of the protective grounding cable connected to the M6000-18S
chassis, see Figure 3-7.
Figure 3-7 Protective Grounding Cable Connected to the M6000-18S Chassis
End of Steps
Prerequisite
l
l
The cabinet and all devices are properly grounded to avoid electrostatic damage.
The DC power supply modules are unpacked and are in good condition.
3-6
SJ-20140731105308-005|2014-10-20 (R1.0)
Verify the type of power supply for the chassis. For the specific types, refer to 3.1.2
DC Power Supply Module and 3.1.3 AC Power Supply Module in the ZXR10
M6000-S Carrier-Class Router Hardware Description.
Context
The ZXR10 M6000-18S supports DC power supply and AC power supply. Based on the
power supply redundancy solution and the number of used power supply modules, DC
power supply is divided into N + 1 and N + N redundancy modes. AC power supply
implements the N + N redundancy mode. For DC power supply and AC power supply,
power supply modules are installed in power supply boxes, and then power supply boxes
are installed in the chassis. The installation procedure for a DC power supply box is similar
to that for an AC power supply box. This procedure describes how to install a DC power
supply module that implements the N + 1 redundancy mode.
Steps
1. Wear anti-static gloves.
2. Check the power supply type of the chassis. Verify that the power supply boxes and
power supply modules match the chassis.
3. Insert a power supply box into the slot. Grasp the handles of the box, and then push
the box until the front panel of the box is flush with the front of the chassis, see Figure
3-8. Ensure that the power supply box is connected to the backplane of the chassis
securely. Use a crosshead screwdriver to tighten the captive screws and fix the power
supply box into the chassis.
Figure 3-8 Installing a Power Supply Box
4. Repeat step 3 to install the other power supply boxes into the corresponding slots.
5. Install the power supply modules into the first three slots from left in the power switch
box , see Figure 3-9. Align each power supply module with the slot of the power switch
box, and then push the module into the slot until you hear a click, which indicates that
the power supply module is locked.
3-7
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 3-9 Installing a Power Supply Module and a Power Switch Module
6. Install the power switch module into the right-most slot in the power switch box, see
Figure 3-9. Align the power switch module with the corresponding slot of the power
switch box, and then push the module into the slot. Use a crossover screwdriver to
secure the screws to fix the power switch module into the power switch box.
For an external view of the chassis after the power supply modules and power switch
modules are installed, see Figure 3-10.
Figure 3-10 Chassis With Power Supply Modules and Power Switch Modules
Installed
7. Install the mesh guard in front of the power supply boxes, and use a crosshead
screwdriver to tighten the captive screws, see Figure 3-11.
3-8
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
The fan modules are unpacked and are in good condition.
Context
The fan modules are installed in the back of the ZXR10 M6000-18S chassis. There are
12 fan modules in total.
Steps
1. Remove the cover of the slot for a fan module.
2. Insert the fan module into the slot vertically, grasp the handle of the fan module and
push the module until the front cover is flush with the back of the chassis, see Figure
3-12.
3-9
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Push the fan module until you hear a click, which indicates that the fan module is
locked.
4. Repeat steps 1 through 3 to install all fan modules. For an overview of the fan modules
installed in the chassis, see Figure 3-13.
3-10
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
The air filters are unpacked and are in good condition.
Context
The ZXR10 M6000-18S chassis has two horizontally-installed air filters and one
vertically-installed air filter.
3-11
SJ-20140731105308-005|2014-10-20 (R1.0)
Steps
1. Grasp an air filter, and push it into the corresponding slot, see Figure 3-14.
Figure 3-14 Installing Air Filters
2. Push the air filters into position until the panels of the air filters are align with the slot
frame.
End of Steps
3-12
SJ-20140731105308-005|2014-10-20 (R1.0)
Warning!
A matching blank filler panel must be installed in a slot where no board is installed. If a
board cannot be installed back to a slot within eight hours, a blank filler panel must be
installed. If not, heat dissipation is affected, noises are increased, and the device may not
operate properly.
Prerequisite
l
l
Steps
1. Wear an antistatic wrist strap (or antistatic gloves), and insert the grounding end into
the ESD jack of the chassis.
2. Loosen captive screws, and remove the blank filler panel.
Caution!
After the blank filler panel is removed, install a board in the slot immediately to prevent
any foreign matter from dropping into the chassis.
3-13
SJ-20140731105308-005|2014-10-20 (R1.0)
Ensure that the extractors of the board are completely open. Stop pushing the board
when the board is connected to the chassis.
Caution!
Do not touch the internal components of the board when you are installing the board
to prevent electronic components from being damaged.
Being different from the boards at the upper layer, the boards in the lower layer must
be installed in an opposite direction, see Figure 3-15.
5. Close the extractors. Ensure that the board is connected to the backplane of the
chassis securely, see Figure 3-16.
3-14
SJ-20140731105308-005|2014-10-20 (R1.0)
6. Tighten the captive screws by turning them clockwise to fasten the board, see Figure
3-17.
3-15
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
Steps
1. Wear an antistatic wrist strap (or antistatic gloves), and insert the grounding end into
the ESD jack of the chassis.
2. Loosen captive screws, and remove the blank filler panel.
3-16
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
After the blank filler panel is removed, install a board in the slot immediately to prevent
any foreign matter from dropping into the chassis.
a. Hold the lower part of the board horizontally with one hand and grasp the board
panel with the other hand. Then push the board smoothly along the rail in the
chassis slot.
Ensure that the extractors of the board are completely open. Stop pushing the
board when the board is connected to the chassis.
3-17
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
Do not touch the internal components of the board when you are installing the
board to prevent electronic components from being damaged.
b. Close the extractors. Ensure that the board is connected to the backplane of the
chassis securely.
c.
Use a Phillips screwdriver to tighten the captive screws on both sides of the board
clockwise.
Note:
When the full-height interface daughter card (PIU) is installed in the network processing
board, it is necessary to remove the central guide rail from the network processing board.
For more information, see Appendix E Removing Central Guide Rail of Network Processing
Board (PFU).
Prerequisite
l
l
Steps
1. Wear an antistatic wrist strap (or antistatic gloves), and insert the grounding end into
the ESD jack of the chassis.
2. Loosen captive screws, and remove the blank filler panel.
Caution!
After the blank filler panel is removed, install a board in the slot immediately to prevent
any foreign matter from dropping into the chassis.
3-18
SJ-20140731105308-005|2014-10-20 (R1.0)
Ensure that the extractors of the board are completely open. Stop pushing the board
when the board is connected to the chassis.
Caution!
Do not touch the internal components of the board when you are installing the board
to prevent electronic components from being damaged.
Being different from the boards at the upper layer, the boards in the lower layer must
be installed in an opposite direction, see see Figure 3-19.
5. Close the extractors. Ensure that the board is connected to the backplane of the
chassis securely, see Figure 3-20.
3-19
SJ-20140731105308-005|2014-10-20 (R1.0)
6. Tighten the captive screws to fasten the board, see Figure 3-21.
3-20
SJ-20140731105308-005|2014-10-20 (R1.0)
3-21
SJ-20140731105308-005|2014-10-20 (R1.0)
Note:
When the full-height interface daughter card (PIU) is installed in the network processing
board, it is necessary to remove the central guide rail from the network processing board.
For more information, see Appendix E Removing Central Guide Rail of Network Processing
Board (PFU).
Prerequisite
l
l
l
Steps
1. Wear an antistatic wrist strap (or antistatic gloves), and insert the grounding end into
the ESD jack of the chassis.
2. Get the board out from the anti-static package box.
3. Hold the bottom of the card with one hand, and grasp the card panel with the other
hand. Slowly insert the card into the slot along the guide rails. After the card is
connected to the mother board, tighten the captive screws to fasten the card, see
Figure 3-22.
Figure 3-22 Installing PIU Cards
End of Steps
3-22
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
Context
The cable trays are the external components for routing network cables and optical fibers.
There are three cable trays for one ZXR10 M6000-18S chassis: one top cable tray, one
bottom cable tray, and one lateral cable tray.
Steps
1. Position a cable tray (top or bottom) at the proper location.
2. Align the screw holes.
3. Mount the screws (ten in total), see Figure 3-23.
3-23
SJ-20140731105308-005|2014-10-20 (R1.0)
4. Tighten the screws. For an overview of the installed cable tray, see Figure 3-24.
3-24
SJ-20140731105308-005|2014-10-20 (R1.0)
5. The procedure for installing the lateral cable tray is the same, see Figure 3-25.
3-25
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
DC power supply
l
3-26
SJ-20140731105308-005|2014-10-20 (R1.0)
To install DC power cables for the ZXR10 M6000-S, the DC power distribution box, if
not provided by ZTE, must satisfy the following basic requirements:
The discharge current capabilities of the power distribution box must satisfy the
requirements of ZXR10 M6000-S, including that the power of circuit breakers is
derated to satisfy the designed power consumption requirement.
The protective grounding cables of the DC power distribution box and ZXR10
M6000-S must be connected to a common ground properly.
If a ZTE DC power distribution box is used, it is recommended that the fusing current
in each input channel of the PDU of the DC power distribution box is not less than 100
A.
l
AC power supply
l
The protective grounding cables of the AC power distribution box and the ZXR10
M6000-S must be connected to a common ground properly.
Discharge current capabilities such as air circuit can satisfy the requirements of
ZXR10 M6000-S.
Prerequisite
l
l
The chassis grounding cable is installed and contacts the ground properly.
DC power cables are available.
3-27
SJ-20140731105308-005|2014-10-20 (R1.0)
The cables between the DC PDU and the power distribution cabinet in the equipment
room are disconnected. The switch for the power supply box at the bottom of the
chassis is OFF.
Context
Prepare DC power cables. For the details, refer to Preparing Power Cables and Protective
Grounding Cables. Figure 3-26 shows DC power cables.
Figure 3-26 DC Power Cable External View
The following procedure uses a power supply module installed in 8 + 8 mode (full
configuration) as an example to describe how to install DC power cables for the DC power
supply modules installed in N + N mode.
Steps
1. Perform the following steps to connect the power cables to the input and output
terminals of the PDU.
a. Use a marker pen to temporarily mark both ends of the DC power cable.
b. Connect the power cables to the input and output terminals of the PDU, see Figure
3-27.
3-28
SJ-20140731105308-005|2014-10-20 (R1.0)
1. -48 V DC power
cable
2. -48 V RTN DC
power cable
3. PDU
4. -48 V DC power
cable
5. -48 V RTN DC
power cable
6. DC power supply
module
Figure 3-28 shows the mapping relationships between power cables from the PDU
and the DC power supply modules. Red numbers represents the power cables
from the PDU.
Figure 3-28 Mapping Relationships Between Power Cables from the PDU and
the DC Power Supply Modules
For the cable connections from the PDU to the DC power supply modules, refer
to Table 3-1.
3-29
SJ-20140731105308-005|2014-10-20 (R1.0)
PDU
Supply
Modules (Top
to Bottom)
Terminal
Quantity
B0-
-48 V (first
B1-
layer)
A0-
A1-
B0+
B1+
layer)
A0+
A1+
B0-
-48 V (second
B1-
layer)
A0-
A1-
B0+
-48 V RTN
B1+
(second layer)
A0+
A1+
B0-
-48 V (third
B1-
layer)
A0-
A1-
B0+
-48 V RTN
B1+
(third layer)
A0+
A1+
B0-
-48 V (fourth
B1-
layer)
A0-
A1-
Length (m)
0.25
0.25
0.3
0.3
0.38
0.38
0.45
3-30
SJ-20140731105308-005|2014-10-20 (R1.0)
DC Power
PDU
Supply
Modules (Top
to Bottom)
Terminal
Quantity
B0+
-48 V RTN
B1+
(fourth layer)
A0+
A1+
Length (m)
0.45
The layers are from first to fourth top to bottom of the chassis.
For Britain: The -48 V cables are grey, and the -48 V RTN cables are pale blue. Areas not
in Britain: The -48 V cables are blue, and the -48 V RTN cables are black. Cables can be
customized if there are special requirements on cable color.
2. Connect the power cable to the input terminal of a DC power supply module.
a. Remove the mesh guard for the connectors of a DC power supply module.
b. Route the DC power cable to the input terminal of the DC power supply module
along the cable trays.
c.
Connect the DC power cable to the input terminal of the DC power supply module.
3. Use straps to bind the DC power cables at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cables on the cabinet cable trays and the wiring ladder
in the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the DC power cables.
End of Steps
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
DC power cables are available.
The cables between the DC PDU and the power distribution cabinet in the equipment
room are disconnected. The switch for the power supply box at the bottom of the
chassis is OFF.
3-31
SJ-20140731105308-005|2014-10-20 (R1.0)
Context
Prepare DC power cables. For the details, refer to Preparing Power Cables and Protective
Grounding Cables. Figure 3-29 shows DC power cables.
Figure 3-29 DC Power Cable External View
The following procedure uses a power supply module installed in 9+1 mode (full
configuration) as an example to describe how to install DC power cables for the DC power
supply modules installed in N + 1 mode.
Steps
1. Perform the following steps to connect the power cables to the input and output
terminals of the PDU.
a. Use a marker pen to temporarily mark both ends of the DC power cable.
b. Connect the power cables to the input and output terminals of the PDU, see Figure
3-30.
3-32
SJ-20140731105308-005|2014-10-20 (R1.0)
1. -48 V DC power
cable
2. -48 V RTN DC
power cable
3. PDU
4. -48 V DC power
cable
5. -48 V RTN DC
power cable
6. DC power supply
module
Figure 3-31 shows the mapping relationships between power cables from the PDU
and the DC power supply modules. Red numbers represents the power cables
from the PDU.
Figure 3-31 Mapping Relationships Between Power Cables from the PDU and
the DC Power Supply Modules
3-33
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the PDU to the DC power supply modules, refer
to Table 3-2.
Table 3-2 DC Power Cable Connections
DC Power
PDU
Supply
Modules (Top
to Bottom)
Terminal
Quantity
B0-
B1-
-48 V (first
B2-
layer)
A0-
A1-
A2-
B0+
B1+
B2+
layer)
A0+
A1+
A2+
B0-
B1-
-48 V (second
B2-
layer)
A0-
A1-
A2-
B0+
B1+
-48 V RTN
B2+
(second layer)
A0+
A1+
A2+
Length (m)
0.25
0.25
0.3
0.3
3-34
SJ-20140731105308-005|2014-10-20 (R1.0)
DC Power
PDU
Supply
Modules (Top
to Bottom)
Terminal
Quantity
B0-
B1-
-48 V (third
B2-
layer)
A0-
A1-
A2-
B0+
B1+
-48 V RTN
B2+
(third layer)
A0+
A1+
A2+
-48 V (fourth
B0-
layer)
A0-
-48 V RTN
B0+
(fourth layer)
A0+
Length (m)
0.38
0.38
0.48
0.48
The layers are from first to fourth top to bottom of the chassis.
For Britain: The -48 V cables are grey, and the -48 V RTN cables are pale blue. Areas not
in Britain: The -48 V cables are blue, and the -48 V RTN cables are black. Cables can be
customized if there are special requirements on cable color.
2. Connect the power cable to the input terminal of a DC power supply module.
a. Remove the mesh guard for the connectors of a DC power supply module.
b. Route the DC power cable to the input terminal of the DC power supply module
along the cable trays.
c.
Connect the DC power cable to the input terminal of the DC power supply module.
3. Use straps to bind the DC power cables at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cables on the cabinet cable trays and the wiring ladder
in the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the DC power cables.
End of Steps
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
AC power cables are available.
The cables between the AC PDU and the power distribution cabinet in the equipment
room are disconnected. The switch for the power supply box at the bottom of the
chassis is OFF.
Context
If AC power supply is used in the equipment room, AC power supply cabinets should be
used for power supply (recommended).
Figure 3-32 shows an AC power cable that is used between a PDU and an AC power
supply module.
Figure 3-32 AC Power Cable Connections
The following procedure uses a power supply module installed in 8 + 8 mode (full
configuration) as an example to describe how to install AC power cables for the AC power
supply modules installed in N + N mode.
Steps
1. Perform the following steps to connect the power cables to the input and output
terminals of the PDU.
Connect the power cables to the input and output terminals of the PDU, see Figure
3-33.
3-36
SJ-20140731105308-005|2014-10-20 (R1.0)
1.
2.
3.
4.
N (neutral wire)
L (live wire)
PE (protective earth)
PDU
5.
6.
7.
8.
N (neutral wire)
PE (protective earth)
L (live wire)
AC power cable
9. AC power supply
module
Figure 3-34 shows the mapping relationships between power cables from the PDU
and the AC power supply modules. Red numbers represents the power cables from
the PDU.
Figure 3-34 Mapping Relationships Between Power Cables from the PDU and the
AC Power Supply Modules
3-37
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the PDU to the AC power supply modules, refer to
Table 3-3.
Table 3-3 AC Power Cable Connections
AC Power Supply Modules
PDU
(Top to Bottom)
B0 (first layer)
B1 (first layer)
B0 (second
layer)
B1 (second
layer)
B0 (third layer)
B1 (third layer)
B0 (fourth layer)
B1 (fourth layer)
A0 (first layer)
PE
PE
PE
PE
PE
PE
PE
PE
PE
Quantity
Length (m)
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
3-38
SJ-20140731105308-005|2014-10-20 (R1.0)
PDU
(Top to Bottom)
A1 (first layer)
A0 (second
layer)
A1 (second
layer)
A0 (third layer)
A1 (third layer)
A0 (fourth layer)
A1 (fourth layer)
PE
PE
PE
PE
PE
PE
PE
Quantity
Length (m)
0.7
0.7
0.7
0.7
0.7
0.7
0.7
The layers are from first to fourth top to bottom of the chassis.
For AC power cables certificated by CCC and VDE, L: brown, N: blue, PE: yellow-green. For
AC power cables certificated by UL, L-black, N-white, PE-green.
2. Connect the power cable to the input terminal of an AC power supply module.
a. Route the AC power cable to the input terminal of the AC power supply module
along the cable trays.
b. Connect the AC power cable to the input terminal of the AC power supply module.
3. Use straps to bind the AC power cables at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cables on the cabinet cable trays and the wiring ladder
in the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the AC power cables.
End of Steps
3-39
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
The HVDC PDU is installed to the chassis properly.
HVDC power cables are available.
The cables between the HVDC PDU and the power distribution cabinet in the
equipment room are disconnected. The switch for the power supply box at the bottom
of the chassis is OFF.
Context
If the equipment room is supplied with HVDC power, it is recommended that the HVDC
PDU of the cabinet be used to supply power to the chassis.
Figure 3-35 shows an HVDC power cable that is used between a PDU and an AC power
supply module.
Figure 3-35 HVDC Power Cable Connections
The following procedure uses a power supply module installed in 8 + 8 mode (full
configuration) as an example to describe how to install HVDC power cables for the AC
power supply modules installed in N + N mode.
Steps
1. Perform the following steps to connect the power cables to the input and output
terminals of the PDU.
Connect the power cables to the input and output terminals of the PDU, see Figure
3-36.
3-40
SJ-20140731105308-005|2014-10-20 (R1.0)
1.
2.
3.
4.
PE (protective earth)
L (+)
N (-)
PDU
5.
6.
7.
8.
PE (protective earth)
L (+)
N (-)
HVDC power cable
9. AC power supply
module
Figure 3-37 shows the mapping relationships between power cables from the PDU
and the AC power supply modules. Red numbers represents the power cables from
the PDU.
Figure 3-37 Mapping Relationships Between Power Cables from the PDU and the
AC Power Supply Modules
3-41
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the PDU to the AC power supply modules, refer to
Table 3-4.
Table 3-4 HVDC Power Cable Connections
AC Power Supply Modules
PDU
(Top to Bottom)
B0 (first layer)
B1 (first layer)
B0 (second
layer)
B1 (second
layer)
B0 (third layer)
B1 (third layer)
B0 (fourth layer)
B1 (fourth layer)
A0 (first layer)
OUT (B): +: 1
OUT (B): -: 1
PE
OUT (B): +: 2
OUT (B): -: 2
PE
OUT (B): +: 3
OUT (B): -: 3
PE
OUT (B): +: 4
OUT (B): -: 4
PE
OUT (B): +: 5
OUT (B): -: 5
PE
OUT (B): +: 6
OUT (B): -: 6
PE
OUT (B): +: 7
OUT (B): -: 7
PE
OUT (B): +: 8
OUT (B): -: 8
PE
OUT (A): +: 1
OUT (A): -: 1
PE
Quantity
Length (m)
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
3-42
SJ-20140731105308-005|2014-10-20 (R1.0)
PDU
(Top to Bottom)
A1 (first layer)
A0 (second
layer)
A1 (second
layer)
A0 (third layer)
A1 (third layer)
A0 (fourth layer)
A1 (fourth layer)
OUT (A): +: 2
OUT (A): -: 2
PE
OUT (A): +: 3
OUT (A): -: 3
PE
OUT (A): +: 4
OUT (A): -: 4
PE
OUT (A): +: 5
OUT (A): -: 5
PE
OUT (A): +: 6
OUT (A): -: 6
PE
OUT (A): +: 7
OUT (A): -: 7
PE
OUT (A): +: 8
OUT (A): -: 8
PE
Quantity
Length (m)
0.7
0.7
0.7
0.7
0.7
0.7
0.7
The layers are from first to fourth top to bottom of the chassis.
For HVDC power cables certificated by CCC and VDE, L: brown, N: blue, PE: yellow-green. For
HVDC power cables certificated by UL, L-black, N-white, PE-green.
2. Connect the power cable to the input terminal of an AC power supply module.
a. Route the HVDC power cable to the input terminal of the AC power supply module
along the cable trays.
b. Connect the HVDC power cable to the input terminal of the AC power supply
module.
3. Use straps to bind the HVDC power cables at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cables on the cabinet cable trays and the wiring ladder
in the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the HVDC power cables.
End of Steps
3-43
SJ-20140731105308-005|2014-10-20 (R1.0)
3-44
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 4
Prerequisite
l
l
Steps
1. In accordance with the engineering design documents, determine the installation
position of the chassis in the cabinet.
In general, for a standard cabinet, 1U equals the height of three installation holes of
the cabinet, see Figure 4-1. The chassis should be at least 1U (1U = 44.45 mm) above
the cabinet bottom.
4-1
SJ-20140731105308-005|2014-10-20 (R1.0)
4-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
Use the chassis handles only. Do not attempt to lift the chassis with other handles of
the chassis.
Engineers should lift up or put down the chassis at the same time to balance the weight.
4-3
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 4-4 Installing the ZXR10 M6000-8S Chassis into the Cabinet
4-4
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
Context
The cable tray is an external component for routing network cables and optical fibers. For
the structure of the M6000-8S cable tray, see Figure 4-6.
4-5
SJ-20140731105308-005|2014-10-20 (R1.0)
For the installation point of the M6000-8S cable tray, see Figure 4-7.
Figure 4-7 Installation Point of the M6000-8S Cable Tray
Steps
1. Position the cable tray at the proper location. The screw holes should be aligned.
2. Mount the screws (eight in total), see Figure 4-8.
4-6
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Tighten the screws. For an overview of the installed cable tray, see Figure 4-9.
Figure 4-9 M6000-8S Cable Tray Installed
End of Steps
4-7
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
The protective grounding cable of the cabinet to the power distribution cabinet is
installed.
Antistatic gloves, cross screwdriver, and screw and bolt assemblies are available.
Context
The protective grounding cables for the chassis is a yellow-green 16 mm2 cable. The
aperture of both terminals of the cable is 0.32 in. (8 mm).
For the overview of a protective grounding cable, see Figure 4-10. For how to prepare a
protective grounding cable, refer to Appendix B Preparing Power Cables and Protective
Grounding Cables.
Figure 4-10 M6000-8S Grounding Cable
Steps
1. Wear antistatic gloves.
2. Use the cross screwdriver to remove the screw and bolt assembly at the grounding
point of the chassis.
3. Connect one end of the protective grounding cable to the grounding rod of the chassis,
and the other end to the grounding rod inside the cabinet, and use a screw and bolt
assembly to fasten the cable.
For an overview of the protective grounding cable connected to the M6000-8S chassis,
see Figure 4-11.
4-8
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
Steps
1. Wear antistatic gloves.
2. Insert the power supply module into the power slot vertically, see Figure 4-12.
4-9
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Grasp the handles of the power supply module and push the module until the front
cover is flush with the front of the chassis.
4. Tighten the captive screws to fasten the power supply module, see Figure 4-13.
4-10
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
4-11
SJ-20140731105308-005|2014-10-20 (R1.0)
Context
For the overview of the M6000-8S AC power supply module, see Figure 4-14.
Figure 4-14 Front View of the AC Power Supply Module
1. Power subrack
2. Channel A rectifier modules
(PSU13)
Steps
1. Wear antistatic gloves.
2. Install the rectifier module.
a. Pull out the handle of a rectifier module to the "open" position, and push the rectifier
module into the subrack until it contacts the interfaces on the backplane, see
Figure 4-15.
Figure 4-15 Installing a Rectifier Module
b. Press the top of the handle inwards to push the rectifier module into the power
subrack, so that the two plugs on the back of the rectifier are fully inserted into the
sockets on the backplane. Now the handle is aligned with the front panel of the
rectifier module.
c.
Fasten the two screws on the handle to lock the rectifier module in the
corresponding position on the subrack, see Figure 4-16.
Figure 4-16 Fastening Screws of the Rectifier Module
Prerequisite
The fan module is unpacked and is in good condition.
Steps
1. Remove the cover in the slot for the fan module.
2. Insert the fan module into the slot vertically, see Figure 4-17.
4-13
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Grasp the handle of the fan module and push the module until the front cover is flush
with the front of the chassis. Tighten the captive screws to fasten the fan module, see
Figure 4-18.
4-14
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
The air filter is unpacked and is in good condition.
Steps
1. Slide the air filter halfway into the air filter slot, see Figure 4-19.
4-15
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Hold the plastic board of the air filter and push the air filter until its connectors connect
to the chassis, see Figure 4-20.
Figure 4-20 M6000-8S Air Filter Installed
End of Steps
4-16
SJ-20140731105308-005|2014-10-20 (R1.0)
Warning!
A matching blank filler panel must be installed in a slot where no board is installed. If a
board cannot be installed back to a slot within eight hours, a blank filler panel must be
installed. If not, heat dissipation is affected, noises are increased, and the device may not
operate properly.
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-8S board is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or gloves) with the grounding end into the ESD jack of
the chassis.
2. Slowly insert the board vertically into the slot along the guide rails, see Figure 4-21.
Figure 4-21 Installing the M6000-8S Board
4-17
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Grasp the extractors of the board and gently insert it into the chassis, see Figure 4-21.
Keep the extractors completely open until the board is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the board. The
board pins are properly connected to the back side of the chassis. For an overview of
the installed board, see Figure 4-22.
Figure 4-22 M6000-8S Board Installed
End of Steps
4-18
SJ-20140731105308-005|2014-10-20 (R1.0)
Note:
When the full-height interface daughter card (PIU) is installed in the network processing
board, it is necessary to remove the central guide rail from the network processing board.
For more information, see Appendix E Removing Central Guide Rail of Network Processing
Board (PFU).
Warning!
The empty slot must be installed with blank panel. If the mother card or daughter
card cannot be installed again with 8 hours, it is necessary to install blank panel in
the corresponding empty slot, otherwise the equipment heat sinking and noise will be
seriously affected, and the equipment cannot run normally.
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-8S mother-daughter card is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or gloves) with the grounding end into the ESD jack of
the chassis.
2. Slowly insert the mother card vertically into the slot along the guide rails, see Figure
4-23.
4-19
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 4-23 Installing the M6000-8S Mother Card into the Board
3. Grasp the extractors of the mother card and gently insert it into the chassis, see Figure
4-24. Keep the extractors completely open until the mother card is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the mother card.
The card pins are properly connected to the back side of the chassis. For an overview
of the installed mother card, see Figure 4-24.
4-20
SJ-20140731105308-005|2014-10-20 (R1.0)
5. Slowly insert the daughter card vertically into the slot along the guide rails of the
installed mother card, see Figure 4-25. The installation method for the 1/4 daughter
card is similar.
4-21
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 4-25 Installing the M6000-8S Daughter Card into the Mother Card
6. Hold the upper and lower side of the daughter card and gently insert it into the chassis.
7. Tighten the captive screws to fasten the daughter card. The card pins are properly
connected to the mother card. For an overview of the installed mother-daughter card,
see Figure 4-26.
4-22
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
DC power supply
l
The discharge current capabilities of the power distribution box must satisfy the
requirements of ZXR10 M6000-S, including that the power of circuit breakers is
derated to satisfy the designed power consumption requirement.
The protective grounding cables of the DC power distribution box and ZXR10
M6000-S must be connected to a common ground properly.
4-23
SJ-20140731105308-005|2014-10-20 (R1.0)
If a ZTE DC power distribution box is used, it is recommended that the fusing current
in each input channel of the PDU of the DC power distribution box is not less than 100
A.
l
AC power supply
l
The protective grounding cables of the AC power distribution box and the ZXR10
M6000-S must be connected to a common ground properly.
Discharge current capabilities such as air circuit can satisfy the requirements of
ZXR10 M6000-S.
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
A DC power cable is available.
The cables between the DC power distribution box and the power distribution cabinet
in the equipment room are disconnected. The power supply module switch on the
bottom of the chassis is in the OFF position.
Context
The DC power cable is connected from the power distribution cabinet in the equipment
room to the input terminal of the PDU, and then connected from the output terminal of the
PDU to a DC power supply module of the ZXR10 M6000-8S chassis.
The PDU supports a maximum of dual 5 inputs and dual 8 outputs.
Steps
1. Use a marker pen to temporarily mark both ends of the DC power cable.
4-24
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Connect the DC power cables from the input terminals to the output terminals of the
PDU, see Figure 4-27.
Figure 4-27 Power Cable Connections in the DC Power Box
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
4. PDU -48 V DC input
(blue)
5. -48 V RTN DC
output PDU (black)
connected to a DC
power supply module
6. -48 V DC output PDU
(blue) connected to
a DC power supply
module
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
4-25
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
4
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 4-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
4-26
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
4
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 4-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
RTN input
distribution cabinet in
4-27
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
tube, 14
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For connections of 35 mm2 power cables from the power distribution cabinet in the
equipment room to the PDU, refer to Table 4-4, Table 4-5, and Table 4-6 for different
certification standards and requirements.
Table 4-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Quan-
Description
tity
Cabinet in the
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
4-28
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
2
distribution cabinet in
single-strand fire-resistant
cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
4
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 4-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
multi-strand conducting
equipment room
cable
distribution cabinet in
4-29
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
4
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 4-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
Protective ground in
Protective ground on
4-30
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.03 m
tube, 14
0.03 m
tube, 14
0.03 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 50 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 4-7.
Table 4-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
Protective ground in
Protective ground on
0.05 m
tube, 20
4-31
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
6
0.05 m
4
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 70 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 4-8.
Table 4-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
distribution cabinet in
single-strand fire-resistant
cable
Protective ground in
Protective ground on
0.05 m
tube, 20
0.05 m
4
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
4-32
SJ-20140731105308-005|2014-10-20 (R1.0)
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For the power cable connections from the output terminals the PDU to a DC power
supply module of the ZXR10 M6000-8S chassis, refer to Table 4-9.
Table 4-9 Wiring of Power Cables from PDU to Power Supply Module
PDU (Output)
DC Power Supply
Quantity
Length (m)
Description
Subject to
the config-
female connector
Module
NEG A-1
-48 V
uration
RTN A-1
NEG A-2
-48 V RTN
-48 V
Subject to
the config-
cable, female
uration
connector
Subject to
the config-
female connector
uration
RTN A-2
NEG B-1
-48 V RTN
-48 V
Subject to
the config-
cable, female
uration
connector
Subject to
the config-
female connector
uration
RTN B-1
NEG B-2
-48 V RTN
-48 V
Subject to
the config-
cable, female
uration
connector
Subject to
the config-
female connector
uration
RTN B-2
-48 V RTN
Subject to
the config-
cable, female
uration
connector
3. Install the grounding cable of the PDU. Connect one end of the protective grounding
cable to the grounding rod of the PDU (there are two grounding rods on interior sides
of the PDU, and you only need to connect to one of them), and connect the other end
to the grounding point inside the cabinet (at top of the cabinet).
4. Check the input terminals with a multimeter to verify that there is no short circuit
between the -48 V and -48 V RTN terminals and between the -48 V and PGND
terminals.
5. Unplug the DC power supply module from the chassis.
4-33
SJ-20140731105308-005|2014-10-20 (R1.0)
6. Connect the power cables to the input terminal of a DC power supply module.
For the connections, refer to Figure 4-28.
Figure 4-28 Wiring of Power Cables at the Ends on a DC Power Supply Module
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
7. Plug the DC power supply module into the chassis, and fasten the protective cover on
the wiring terminal of the DC power supply module.
8. Use straps to bind the DC power cable at intervals of 100 mm to 150 mm to fasten the
power cable on the cabinet cable tray and the wiring ladder in the equipment room.
4-34
SJ-20140731105308-005|2014-10-20 (R1.0)
9. Paste labels at about 0.79 in. (20 mm) to both ends of the DC power cable.
End of Steps
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
An AC power cable is available.
The cables between the AC power distribution box and the AC power distribution
cabinet in the equipment room are disconnected. The power supply module switch
on the bottom of the chassis is in the OFF position.
Context
The AC power cables are connected from the power supply cabinet in the equipment room
to the input terminals of the PDU, and then connected from the output terminals of the
PDU to the AC/DC converter. Power cables are then connected from the converter to the
DC power supply modules. After being converted from AC power to DC power, power is
supplied to the DC supply modules to power on the chassis.
Steps
1. Connect the power cables at the input and output terminals of the AC PDU.
For the power cable connections at the input and output terminals of the PDU, see
Figure 4-29.
Figure 4-29 Cable Connections for the PDU
4-35
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the power distribution cabinet to the input terminals of
the PDU, refer to Table 4-10.
Table 4-10 Cable Wiring From Power Distribution Cabinet to PDU
No.
Cable
PDU (Input)
Power Dis-
Quantity
tribution
Length
Description
(m)
Cabinet in
the Equipment Room
1
Black fire-
Output of
resistant 3-core
software cable
Subject to
On the power
the power
the config-
distribution
distribution
uration
cabinet
pre-insulated
Yellow-green core: AC
in the
tube terminals
equipment
must be
room
crimped on
Black fire-
Output of
resistant 3-core
the power
the config-
software cable
distribution
uration
cabinet
Yellow-green core: AC
in the
equipment
Subject to
H07Z-K35
Protective
yellow-green
the cabinet
single-core cable
user power
supply side,
connectors are
determined by
engineering
survey.
room
3
site. On the
Subject to
Protective
ground of
the config-
grounding
the power
uration
cable of
distribution
the cabinet,
cabinet or
yellow-green
the copper
ground
bar in the
equipment
room
4-36
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Cable
PDU (Input)
Power Dis-
Quantity
tribution
Length
Description
(m)
Cabinet in
the Equipment Room
5
Copper lug
The aperture
is 0.32 in.
(8 mm), and
the applicable
cable diameter
is in the range
of 26.66 - 42.42
mm2
0.04 m 2
14
1. No. 3 cable is crimped with No.4 OT terminal (M8) on the engineering site. The grounding end in the equipment
room is determined through an engineering survey. In general, a No.4 terminal (M8) and No. 5 tube are used.
For the cable connections from the PDU to the AC/DC converter, refer to Table 4-11.
Table 4-11 Cable Wiring From PDU to AC/DC Converter
No.
Cable
PDU (Output)
AC/DC Converter
Quantity
Length (m)
Description
(Input)
1
PWR-G0507-
Brown core:
Brown core:
Subject to
Cable between
003
AC power
AC-to-DC power
the configu-
the AC power
distribution box
ration
distribution
L OUT 1-1
Blue core:
AC-to-DC
AC power
input
power supply
distribution box
Yellow-green core:
conversion
N OUT 1-1
AC-to-DC power
module
Yellow-green
core: AC power
distribution box
PE OUT 1
2
PWR-G0507-
Brown core:
Brown core:
Subject to
Cable between
003
AC power
AC-to-DC power
the configu-
the AC power
distribution box
ration
distribution
L OUT 2-1
Blue core:
AC-to-DC
AC power
input
power supply
distribution box
Yellow-green core:
conversion
N OUT 2-1
AC-to-DC power
module
Yellow-green
core: AC power
4-37
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Cable
PDU (Output)
AC/DC Converter
Quantity
Length (m)
Description
Subject to
Grounding cable
(Input)
distribution box
PE OUT 5
3
PWR-72017-
AC power
Lower-right
067
distribution box
grounding point of
the configu-
of the AC-to-DC
PE OUT 8
ration
power supply
supply conversion
conversion
module
module
2. Connect power cables to the input and output terminals of the AC/DC converter.
a. Loosen the five captive screws on the rear panel of the AC/DC converter.
b. Remove the rear panel. For an external view of the terminals, see Figure 4-30.
Figure 4-30 AC/DC Converter Terminals
1. Channel A input
terminals
2. Channel A -48V
output negative
terminals
3. Channel B -48V
output negative
terminals
4. Channel B input
terminals
5. Protective
earthing terminals
6. PE terminals
7. Channel B -48V
output RTN
terminals
8. Channel A -48V
output RTN
terminals
For the cable connections at the input and output terminals of the AC/DC converter,
see Figure 4-31.
4-38
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Cable N at the
input terminal
of the AC/DC
converter
2. Cable N at the
input terminal
of the AC/DC
converter
3. Cable PE at the
input terminal
of the AC/DC
converter
4. Grounding cable
of the AC/DC
converter
5. -48 V DC power
cable
6. -48 V RTN DC
power cable
7. Protective
grounding cable
The cable connections from the AC/DC converter to the DC power supply modules
vary with different certifications. For details, refer to Table 4-12, Table 4-13, Table
4-14, and Table 4-15.
Table 4-12 Cable Wiring From AC/DC Converter to DC Power Supply Modules (VDE)
No.
Cable
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
AC-to-DC power
Length (m)
Description
Subject to
of M6000-8S
1
PWR-20982-001
M6000-8S
subrack: power
the configu-
V A-1
ration
(-48V)
2
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit A-1
Subject to
the configu-
cable
V RTN A-1
ration
(-48 V RTN)
3
PWR-20982-001
M6000-8S
AC-to-DC power
subrack: power
the configu-
V A-2
ration
Subject to
(-48 V)
4-39
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Cable
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
M6000-8S
AC-to-DC power
subrack: power
supply unit A-2
Length (m)
Description
Subject to
the configu-
cable
V RTN A-2
ration
of M6000-8S
4
PWR-20982-010
(-48 V RTN)
5
PWR-20982-001
M6000-8S
AC-to-DC power
subrack: power
the configu-
V B-1
ration
Subject to
(-48 V)
6
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit B-1
Subject to
the configu-
cable
V RTN B-1
ration
(-48 V RTN)
7
PWR-20982-001
M6000-8S
AC-to-DC power
subrack: power
the configu-
V B-2
ration
Subject to
(-48 V)
8
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit B-2
Subject to
the configu-
cable
V RTN B-2
ration
(-48 V RTN)
9
PE-20982-005
M6000-8S
AC-to-DC power
Subject to
M6000-8S
grounding point
supply: OUTPUT PE
the configu-
grounding cable
ration
Table 4-13 Cable Wiring From AC/DC Converter to DC Power Supply Modules (VDE Certificated for
British Market)
No.
Cable
DC Power
AC/DC Converter
Quan-
Length (m)
Description
Supply Module
(Input)
tity
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
-48 V A-1
ration
of M6000-8S
1
PWR-G0507-002
(-48 V)
2
PWR-20982-011
M6000-8S
AC-to-DC power
subrack: power
supply unit A-1
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
4-40
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Cable
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V A-2
ration
Length (m)
Description
Subject to
of M6000-8S
3
PWR-G0507-002
(-48 V)
4
PWR-20982-011
M6000-8S
AC-to-DC power
subrack: power
supply unit A-2
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
5
PWR-G0507-002
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V B-1
ration
Subject to
(-48 V)
6
PWR-20982-011
M6000-8S
AC-to-DC power
subrack: power
supply unit B-1
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
7
PWR-G0507-002
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
-48 V B-2
ration
(-48 V)
8
PWR-20982-011
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
9
PE-20982-005
M6000-8S
AC-to-DC power
Subject to
M6000-8S
grounding point
supply: OUTPUT PE
the configu-
grounding cable
ration
Table 4-14 Cable Wiring From AC/DC Converter to DC Power Supply Modules (CCC)
No.
Cable
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V A-1
ration
Length (m)
Description
Subject to
of M6000-8S
1
PWR-20982-004
(-48 V)
4-41
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Cable
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
M6000-8S
AC-to-DC power
subrack: power
supply unit A-1
Length (m)
Description
Subject to
supply: OUTPUT
the configu-
cable
ration
of M6000-8S
2
PWR-20982-009
(-48 V RTN)
3
PWR-20982-004
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V A-2
ration
Subject to
(-48 V)
4
PWR-20982-009
M6000-8S
AC-to-DC power
subrack: power
supply unit A-2
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
5
PWR-20982-004
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V B-1
ration
Subject to
(-48 V)
6
PWR-20982-009
M6000-8S
AC-to-DC power
subrack: power
supply unit B-1
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
7
PWR-20982-004
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
Subject to
the configu-
-48 V B-2
ration
(-48 V)
8
PWR-20982-009
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
9
PE-20982-003
M6000-8S
grounding point
AC-to-DC power
Subject to
M6000-8S
supply: OUTPUT PE
the configu-
grounding cable
ration
4-42
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 4-15 Cable Wiring From AC/DC Converter to DC Power Supply Modules (UL)
No.
Cable
PWR-20982-001
DC Power
AC/DC Converter
Quan-
Supply Module
(Input)
tity
of M6000-8S
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V A-1
ration
Length (m)
Description
Subject to
(-48 V)
2
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit A-1
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
3
PWR-20982-001
M6000-8S
AC-to-DC power
subrack: power
supply: OUTPUT
the configu-
-48 V A-2
ration
Subject to
(-48 V)
4
PWR-20982-010
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
5
PWR-20982-001
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
-48 V B-1
ration
(-48 V)
6
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit B-1
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
7
PWR-20982-001
M6000-8S
AC-to-DC power
Subject to
subrack: power
supply: OUTPUT
the configu-
-48 V B-2
ration
(-48 V)
8
PWR-20982-010
M6000-8S
AC-to-DC power
subrack: power
supply unit B-2
Subject to
supply: OUTPUT
the configu-
cable
ration
(-48 V RTN)
9
PE-20982-004
M6000-8S
AC-to-DC power
grounding point
Subject to
M6000-8S
supply: OUTPUT PE
the configu-
grounding cable
ration
3. Connect the power cables to the input terminals of the DC power supply module of the
M6000-8S chassis, see Figure 4-32.
4-43
SJ-20140731105308-005|2014-10-20 (R1.0)
4. Use straps to bind the AC power cable at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cable on the cabinet cable tray and the wiring ladder in
the equipment room.
5. Paste labels at about 0.79 in. (20 mm) to both ends of the AC power cable.
End of Steps
Result
For the overview of installed M6000-8S AC power cables, see Figure 4-32.
4-44
SJ-20140731105308-005|2014-10-20 (R1.0)
1. AC power distribution
box input (brown, blue,
yellow-green)
2. Grounding cable for the
AC power distribution box
(yellow-green)
3. AC power distribution
box output (brown, blue,
yellow-green)
4. Grounding cable for the
AC power supply module
(yellow-green)
4-45
SJ-20140731105308-005|2014-10-20 (R1.0)
4-46
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 5
Prerequisite
l
l
Steps
1. In accordance with the engineering design documents, determine the installation
position of the chassis in the cabinet.
In general, for a standard cabinet, 1U equals the height of three installation holes, see
Figure 5-1. The chassis should be at least 1U (1U = 44.45 mm) above the cabinet
bottom.
5-1
SJ-20140731105308-005|2014-10-20 (R1.0)
5-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
Use specified handles only. Do not attempt to lift the chassis with other handles of the
chassis.
Engineers should lift up or put down the chassis at the same time to balance the weight.
5-3
SJ-20140731105308-005|2014-10-20 (R1.0)
5-4
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
The protective grounding cable of the device cabinet to the power distribution cabinet
is installed.
Antistatic gloves, cross screwdriver, and screw and bolt assemblies are available.
5-5
SJ-20140731105308-005|2014-10-20 (R1.0)
Context
The protective grounding cables for the chassis is a yellow-green 10 mm2 cable. The
aperture of both terminals of the cable is 0.32 in. (8 mm).
For the overview of a protective grounding cable, see Figure 5-6. For how to prepare a
protective grounding cable, refer to Appendix B Preparing Power Cables and Protective
Grounding Cables.
Figure 5-6 M6000-5S Grounding Cable
Steps
1. Wear antistatic gloves.
2. Use the cross screwdriver to remove the screw and bolt assembly at the grounding
point of the chassis.
3. Connect one end of the protective grounding cable to the grounding rod of the chassis,
and the other end to the grounding rod inside the cabinet, and use a screw and bolt
assembly to fasten the cable.
For an overview of the protective grounding cable connected to the M6000-5S chassis,
see Figure 5-7.
Figure 5-7 Protective Grounding Cable Connected to the M6000-5S Chassis
End of Steps
5-6
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
Steps
1. Wear antistatic gloves.
2. Push a DC power supply module horizontally into the slot, secure the screws to fix the
DC power supply module in the chassis, see Figure 5-8.
Figure 5-8 Installing a DC Power Supply Module into the M6000-5S Chassis
3. Insert a blank panel into a vacancy of power supply module slot, and then secure the
screws to fix the black panel to the chassis, see Figure 5-9.
5-7
SJ-20140731105308-005|2014-10-20 (R1.0)
For the chassis after a blank panel of power supply module is installed, see Figure
5-10.
Figure 5-10 Chassis With Blank Panel Installed
End of Steps
5-8
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
Steps
1. Wear antistatic gloves.
2. Insert the power supply module halfway into the power slot vertically, see Figure 5-11.
Figure 5-11 Installing the M6000-5S AC Power Supply Module
3. Push the module until the front cover is flush with the front of the chassis.
4. Tighten the captive screws to fasten the power supply module, see Figure 5-12.
5-9
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
The fan module is unpacked and is in good condition.
Steps
1. Remove the cover in the slot for the fan module.
2. Insert the fan module into the slot horizontally, see Figure 5-13.
5-10
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Grasp the handle of the fan module and push the module until the front cover is flush
with the front of the chassis. Tighten the captive screws to fasten the fan module, see
Figure 5-14.
5-11
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
The air filter is unpacked and is in good condition.
Steps
1. Slide the air filter into the half position of the air filter slot, see Figure 5-15.
5-12
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Hold the plastic board of the air filter and push the air filter until its connectors connect
to the chassis, see Figure 5-16.
Figure 5-16 M6000-5S Air Filter Installed
End of Steps
Caution!
A matching blank filler panel must be installed in a slot where no board is installed. If a
board cannot be installed back to a slot within eight hours, a blank filler panel must be
installed. If not, heat dissipation is affected, noises are increased, and the device may not
operate properly.
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-5S board is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or antistatic gloves).
2. Slowly insert the board horizontally into the slot along the guide rails, see Figure 5-17.
Figure 5-17 Installing the M6000-5S Board
3. Grasp the extractors of the board and gently insert it into the chassis, see Figure 5-17.
Keep the extractors completely open until the board is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the board. The
board pins are properly connected to the back side of the chassis. For an overview of
the installed board, see Figure 5-18.
5-14
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Note:
When the full-height interface daughter card (PIU) is installed in the network processing
board, it is necessary to remove the central guide rail from the network processing board.
For more information, see Appendix E Removing Central Guide Rail of Network Processing
Board (PFU).
5-15
SJ-20140731105308-005|2014-10-20 (R1.0)
Warning!
The empty slot must be installed with blank panel. If the mother card or daughter
card cannot be installed again with 8 hours, it is necessary to install blank panel in
the corresponding empty slot, otherwise the equipment heat sinking and noise will be
seriously affected, and the equipment cannot run normally.
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-5S mother-daughter card is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or antistatic gloves).
2. Slowly insert the mother card horizontally into the slot along the guide rails, see Figure
5-19.
Figure 5-19 Installing the M6000-5S Mother Card into the Board
3. Grasp the extractors of the mother card and gently insert it into the chassis, see Figure
5-19. Keep the extractors completely open until the mother card is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the board. The
board pins are properly connected to the back side of the chassis. For an overview of
the installed mother card, see Figure 5-20.
5-16
SJ-20140731105308-005|2014-10-20 (R1.0)
5. Slowly insert the daughter card horizontally into the slot along the guide rails of the
mother card, see Figure 5-21.
Figure 5-21 Installing the M6000-5S Daughter Card into the Mother Card
6. Hold the upper and lower side of the daughter card and gently insert it into the chassis.
7. Tighten the captive screws to fasten the daughter card. The card pins are properly
connected to the mother card.
8. Push a blank panel into a slot without mother-card installed, see Figure 5-22. Align the
blank panel with the chassis frame, and then secure the screws on the blank panel.
5-17
SJ-20140731105308-005|2014-10-20 (R1.0)
For the chassis after a blank panel is installed, see Figure 5-23.
Figure 5-23 Chassis With a Blank Panel Installed
9. Push a blank panel into a slot without sub-car installed, see Figure 5-24. Align the
blank panel with the chassis frame, and then secure the screws on the blank panel.
5-18
SJ-20140731105308-005|2014-10-20 (R1.0)
For the chassis after a blank panel is installed, see Figure 5-25.
Figure 5-25 Chassis With a Blank Panle Installed
End of Steps
Prerequisite
l
5-19
SJ-20140731105308-005|2014-10-20 (R1.0)
A 0.2 in. 5.91 in. (5 mm x 150 mm) or 0.24 in. 5.91 in. (6 mm x 150 mm)
screwdriver and screws delivered with the cable tray are available.
Context
The cable tray is the external component for routing network cables and optical fibers. For
the structure of the M6000-5S cable tray, see Figure 5-26.
Figure 5-26 M6000-5S Cable Tray
The M6000-5S cable tray is installed vertically at both sides of the chassis.
Because the AC chassis and the DC chassis of the M6000-5S differ in height, the cable
tray for the AC chassis is 1U higher than that for the DC chassis.
Steps
1. Assemble the cable tray, see Figure 5-27.
5-20
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Tighten the screws. For an overview of the assembled cable tray, see Figure 5-28.
Figure 5-28 Installing the M6000-5S Cable Tray (2)
3. Position the cable tray at the proper location. The screw holes should be aligned.
4. Mount the screws (four in total), see Figure 5-29.
5-21
SJ-20140731105308-005|2014-10-20 (R1.0)
5. Tighten the screws. For an overview of the installed cable tray, see Figure 5-30.
Figure 5-30 M6000-5S Cable Tray Installed
End of Steps
DC power supply
l
SJ-20140731105308-005|2014-10-20 (R1.0)
Connect the power cable from the power distribution box to the DC power unit in the
cabinet, and then connect the power cable from the DC power unit to the input terminal
of the DC power supply module. In case of either single-channel or dual-channel
power supply, the ZXR10 M6000-S always obtains power supply from the DC power
distribution box.
To install DC power cables for the ZXR10 M6000-S, the DC power distribution box, if
not provided by ZTE, must satisfy the following basic requirements:
The discharge current capabilities of the power distribution box must satisfy the
requirements of ZXR10 M6000-S, including that the power of circuit breakers is
derated to satisfy the designed power consumption requirement.
The protective grounding cables of the DC power distribution box and ZXR10
M6000-S must be connected to a common ground properly.
If a ZTE DC power distribution box is used, it is recommended that the fusing current
in each input channel of the PDU of the DC power distribution box is not less than 100
A.
l
AC power supply
l
The protective grounding cables of the AC power distribution box and the ZXR10
M6000-S must be connected to a common ground properly.
Discharge current capabilities such as air circuit can satisfy the requirements of
ZXR10 M6000-S.
Prerequisite
l
l
The chassis grounding cable is installed and contacts the ground properly.
A DC power cable is available.
5-23
SJ-20140731105308-005|2014-10-20 (R1.0)
The cables between the DC power distribution box and the power distribution cabinet
in the equipment room are disconnected. The power supply module switch on the
bottom of the chassis is in the OFF position.
Context
The DC power cable is connected from the power distribution cabinet in the equipment
room to the input terminal of the PDU, and then connected from the output terminal of the
PDU to a DC power supply module of the ZXR10 M6000-5S chassis.
The PDU supports a maximum of dual 5 inputs and dual 8 outputs.
Steps
1. Use a marker pen to temporarily mark both ends of the DC power cable.
2. Connect the DC power cables from the input terminals to the output terminals of the
PDU, see Figure 5-31.
Figure 5-31 Power Cable Connections in the DC Power Box
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
4. PDU -48 V DC input
(blue)
5. -48 V RTN DC
output PDU (black)
connected to a DC
power supply module
6. -48 V DC output PDU
(blue) connected to
a DC power supply
module
5-24
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 5-1 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
fire-resistant cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
2
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
5-25
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 5-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
multi-strand cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
2
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
5-26
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 5-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
RTN input
distribution cabinet in
single-core cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
tube, 14
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For connections of 35 mm2 power cables from the power distribution cabinet in the
equipment room to the PDU, refer to Table 5-4, Table 5-5, and Table 5-6 for different
certification standards and requirements.
5-27
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 5-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
distribution cabinet in
single-strand fire-resistant
cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
2
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 5-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
multi-strand conducting
equipment room
cable
5-28
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
2
distribution cabinet in
conducting cable
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
2
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 5-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
5-29
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.03 m
tube, 14
0.03 m
tube, 14
0.03 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 50 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 5-7.
Table 5-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
Protective ground in
Protective ground on
5-30
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.05 m
tube, 20
0.05 m
2
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 70 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 5-8.
Table 5-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
distribution cabinet in
single-strand fire-resistant
cable
Protective ground in
Protective ground on
0.05 m
tube, 20
0.05 m
5-31
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Quan-
Cabinet in the
Description
tity
Equipment Room
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For the power cable connections from the output terminals the PDU to a DC power
supply module of the ZXR10 M6000-5S chassis, refer to Table 5-9.
Table 5-9 Wiring of Power Cables from PDU to Power Supply Module
PDU (Output)
DC Power Supply
Quantity
Length (m)
Description
Subject to
the config-
female connector
Module
NEG A-1
-48 V
uration
RTN A-1
NEG B-1
-48 V RTN
-48 V
Subject to
the config-
cable, female
uration
connector
Subject to
the config-
female connector
uration
RTN B-1
-48 V RTN
Subject to
the config-
cable, female
uration
connector
3. Install the grounding cable of the PDU. Connect one end of the protective grounding
cable to the grounding rod of the PDU (there are two grounding rods on interior sides
of the PDU, and you only need to connect to one of them), and connect the other end
to the grounding point inside the cabinet (at top of the cabinet).
4. Check the input terminals with a multimeter to verify that there is no short circuit
between the -48 V and -48 V RTN terminals and between the -48 V and PGND
terminals.
5. Unplug the DC power supply module from the chassis.
6. Connect the power cables to the input terminal of a DC power supply module.
For the connections, refer to Figure 5-32.
5-32
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 5-32 Wiring of Power Cables at the Ends on a DC Power Supply Module
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
7. Plug the DC power supply module into the chassis, and fasten the protective cover on
the wiring terminal of the DC power supply module.
8. Use straps to bind the DC power cable at intervals of 100 mm to 150 mm to fasten the
power cable on the cabinet cable tray and the wiring ladder in the equipment room.
9. Paste labels at about 0.79 in. (20 mm) to both ends of the DC power cable.
End of Steps
5-33
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
An AC power cable is available.
The cables between the AC power distribution box and the AC power distribution
cabinet in the equipment room are disconnected. The power supply module switch
on the bottom of the chassis is in the OFF position.
Context
If AC power supply is used in the equipment room, a dual-9 AC PDU should be used for
power supply (recommended). Power cables are connected from the power distribution
cabinet in the equipment room to the PDU and then to the AC power supply modules of
the M6000-5S chassis.
Steps
1. Connect the power cables at the input and output terminals of the AC PDU.
For the power cable connections at the input and output terminals of the PDU, see
Figure 5-33.
Figure 5-33 Cable Connections for the PDU
For the cable connections from the power distribution cabinet to the PDU, refer to Table
5-10.
5-34
SJ-20140731105308-005|2014-10-20 (R1.0)
Cable
PDU (Input)
Power Dis-
Quantity
tribution
Length
Description
(m)
Cabinet in
the Equipment Room
1
Black fire-
Output of
resistant 3-core
software cable
Subject to
On the power
the power
the config-
distribution
distribution
uration
cabinet
pre-insulated
Yellow-green core: AC
in the
tube terminals
equipment
must be
room
crimped on
Black fire-
Output of
resistant 3-core
the power
the config-
software cable
distribution
uration
cabinet
Yellow-green core: AC
in the
equipment
Subject to
H07Z-K35
Protective
yellow-green
the cabinet
single-core cable
user power
supply side,
connectors are
determined by
engineering
survey.
room
3
site. On the
Subject to
Protective
ground of
the config-
grounding
the power
uration
cable of
distribution
the cabinet,
cabinet or
yellow-green
the copper
ground
bar in the
equipment
room
4
Copper lug
The aperture
is 0.32 in.
(8 mm), and
the applicable
cable diameter
is in the range
of 26.66 - 42.42
mm2
0.04 m 2
14
1. Cable No.3 is crimped with OT terminal No.4 (M8) on the engineering site. The grounding end in the equipment
room is determined through an engineering survey. In general, a No.4 (M8) terminal and tube No.5 are used.
5-35
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the PDU to the AC power supply modules in the
M6000-5S chassis, refer to Table 5-11.
Table 5-11 Cable Wiring From PDU to AC Power Supply Modules of M6000-5S
AC Power Supply
PDU (Output)
Quantity
Length (m)
Description
Subject to the
AC power cable
connected to the
device's AC power
supply module
Module of M6000-5S
configuration
2. Connect the power cable to the input terminal of an AC power supply module.
a. Use a marker pen to temporarily mark both ends of the AC power cable.
b. Connect the AC power cables to the sockets on the AC power supply module, and
then close the release latch, see Figure 5-34.
5-36
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 5-34 Cable Wiring on the Terminals of the AC Power Supply Modules
of M6000-5S
1. AC power
distribution
box input
(yellow-green)
2. AC power
distribution box
input (blue)
3. AC power
distribution box
input (brown)
4. AC power cable
(connected to the
AC power supply
module)
5. Cabinet groundin
g cable
6. Grounding cable
of the AC power
distribution box
3. Use straps to bind the AC power cable at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cable on the cabinet cable tray and the wiring ladder in
the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the AC power cable.
End of Steps
5-37
SJ-20140731105308-005|2014-10-20 (R1.0)
5-38
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 6
Prerequisite
l
l
Steps
1. In accordance with the engineering documents, determine the installation position of
the chassis in the cabinet.
In general, for a standard cabinet, 1U equals the height of three installation holes, see
Figure 6-1. The chassis should be at least 1U (1U = 44.45 mm) above the cabinet
bottom.
6-1
SJ-20140731105308-005|2014-10-20 (R1.0)
6-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Note:
Use specified handles only. Do not attempt to lift the chassis with other handles of the
chassis.
Engineers should lift up or put down the chassis at the same time to balance the weight.
6-3
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
The protective grounding cable of the cabinet to the power distribution cabinet is
installed.
Antistatic gloves, cross screwdriver, and screw and bolt assemblies are available.
Context
The protective grounding cable is a yellow-green 6 mm2 cable. The aperture of both
terminals of the cable is 0.32 in. (8 mm).
6-4
SJ-20140731105308-005|2014-10-20 (R1.0)
For the overview of a protective grounding cable, see Figure 6-5. To prepare a protective
grounding cable on site, refer to Appendix B Preparing Power Cables and Protective
Grounding Cables.
Figure 6-5 M6000-3S Grounding Cable
Steps
1. Wear antistatic gloves.
2. Use the cross screwdriver to remove the screw and bolt assembly at the grounding
point of the chassis.
3. Connect one end of the protective grounding cable to the grounding rod of the chassis,
and the other end to the grounding rod inside the cabinet, and use a screw and bolt
assembly to fasten the cable.
For an overview of the protective grounding cable connected to the M6000-3S chassis,
see Figure 6-6.
Figure 6-6 M6000-3S Chassis Protective Grounding Cable Installed
End of Steps
This procedure describes how to install a DC power supply module into the M6000-3S
chassis.
Prerequisite
l
l
Steps
1. Wear antistatic gloves.
2. Insert the power supply module halfway into the power slot vertically, see Figure 6-7.
Figure 6-7 Installing the M6000-3S DC Power Supply Module
3. Push the module until the front cover is flush with the front of the chassis.
4. Tighten the captive screws to fasten the power supply module, see Figure 6-8.
6-6
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Prerequisite
l
l
Steps
1. Wear antistatic gloves.
2. Insert the power supply module halfway into the power slot vertically, see Figure 6-9.
6-7
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Push the module until the front cover is flush with the front of the chassis.
4. Tighten the captive screws to fasten the power supply module, see Figure 6-10.
Figure 6-10 M6000-3S AC Power Supply Module Installed
End of Steps
Prerequisite
The fan module is unpacked and is in good condition.
6-8
SJ-20140731105308-005|2014-10-20 (R1.0)
Steps
1. Remove the cover in the slot for the fan module.
2. Insert the fan module into the slot horizontally, see Figure 6-11.
Figure 6-11 Installing the M6000-3S Fan Module
3. Grasp the handle of the fan module and push the module until the front cover is flush
with the front of the chassis. Tighten the captive screws to fasten the fan module, see
Figure 6-12.
Figure 6-12 M6000-3S Fan Module Installed
End of Steps
6-9
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
The air filter is unpacked and is in good condition.
Steps
1. Slide the air filter into the half position of the air filter slot, see Figure 6-13.
Figure 6-13 Installing the M6000-3S Air Filter
2. Hold the plastic board of the air filter and push the air filter until its connectors connect
to the chassis.
End of Steps
6-10
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
A matching blank filler panel must be installed in a slot where no board is installed. If a
board cannot be installed back to a slot within eight hours, a blank filler panel must be
installed. If not, heat dissipation is affected, noises are increased, and the device may not
operate properly.
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-3S board is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or antistatic gloves).
2. Slowly insert the board horizontally into the slot along the guide rails, see Figure 6-14.
Figure 6-14 Installing the M6000-3S Board
3. Grasp the extractors of the board and gently insert it into the chassis, see Figure 6-14.
Keep the extractors completely open until the board is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the board. The
board pins are properly connected to the back side of the chassis. For an overview of
the installed board, see Figure 6-15.
6-11
SJ-20140731105308-005|2014-10-20 (R1.0)
End of Steps
Note:
When the full-height interface daughter card (PIU) is installed in the network processing
board, it is necessary to remove the central guide rail from the network processing board.
For more information, see Appendix E Removing Central Guide Rail of Network Processing
Board (PFU).
Warning!
The empty slot must be installed with blank panel. If the mother card or daughter
card cannot be installed again with 8 hours, it is necessary to install blank panel in
the corresponding empty slot, otherwise the equipment heat sinking and noise will be
seriously affected, and the equipment cannot run normally.
6-12
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
An antistatic wrist strap (or a pair of antistatic gloves) is available, and its grounding
end is inserted into the ESD jack of the chassis.
The M6000-3S mother-daughter card is unpacked and in good condition.
Steps
1. Wear an antistatic wrist strap (or antistatic gloves).
2. Slowly insert the mother card horizontally into the slot along the guide rails, see Figure
6-16.
Figure 6-16 Installing the M6000-3S Mother Card into the Board
3. Grasp the extractors of the mother card and gently insert it into the chassis, see Figure
6-16. Keep the extractors completely open until the mother card is properly installed.
4. Press the extractors inward and tighten the captive screws to fasten the board. The
board pins are properly connected to the back side of the chassis. For an overview of
the installed mother card, see Figure 6-17.
Figure 6-17 M6000-3S Mother Card Installed In the Board
6-13
SJ-20140731105308-005|2014-10-20 (R1.0)
5. Slowly insert the daughter card horizontally into the slot along the guide rails of the
mother card, see Figure 6-18.
Figure 6-18 Installing the M6000-3S Daughter Card into the Mother Card
6. Hold the upper and lower side of the daughter card and gently insert it into the chassis.
7. Tighten the captive screws to fasten the daughter card. The card pins are properly
connected to the mother card, see Figure 6-19.
Figure 6-19 M6000-3S Daughter Card Installed In the Mother Card
End of Steps
6-14
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
l
l
Context
The cable tray is the external component for routing network cables and optical fibers. For
the structure of the M6000-3S cable tray, see Figure 6-20.
Figure 6-20 M6000-3S Cable Tray
The M6000-3S cable tray is installed vertically at both sides of the chassis.
Because the AC chassis and the DC chassis of the M6000-3S differ in height, the cable
tray for the AC chassis is 1U higher than that for the DC chassis.
Steps
1. Assemble the cable tray, see Figure 6-21.
6-15
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Tighten the screws. For an overview of the assembled cable tray, see Figure 6-22.
Figure 6-22 Installing the M6000-3S Cable Tray (2)
3. Position the cable tray at the proper location. The screw holes should be aligned.
4. Mount the screws (three in total), see Figure 6-23.
6-16
SJ-20140731105308-005|2014-10-20 (R1.0)
DC power supply
l
The discharge current capabilities of the power distribution box must satisfy the
requirements of ZXR10 M6000-S, including that the power of circuit breakers is
derated to satisfy the designed power consumption requirement.
The protective grounding cables of the DC power distribution box and ZXR10
M6000-S must be connected to a common ground properly.
If a ZTE DC power distribution box is used, it is recommended that the fusing current
in each input channel of the PDU of the DC power distribution box is not less than 100
A.
l
6-17
SJ-20140731105308-005|2014-10-20 (R1.0)
AC power supply
l
The protective grounding cables of the AC power distribution box and the ZXR10
M6000-S must be connected to a common ground properly.
Discharge current capabilities such as air circuit can satisfy the requirements of
ZXR10 M6000-S.
Prerequisite
l
l
l
The chassis grounding cable is installed and contacts the ground properly.
A DC power cable is available.
The cables between the DC power distribution box and the power distribution cabinet
in the equipment room are disconnected. The power supply module switch on the
bottom of the chassis is in the OFF position.
Context
The DC power cable is connected from the power distribution cabinet in the equipment
room to the input terminal of the PDU, and then connected from the output terminal of the
PDU to a DC power supply module of the ZXR10 M6000-3S chassis.
The PDU supports a maximum of dual 5 inputs and dual 8 outputs.
Steps
1. Use a marker pen to temporarily mark both ends of the DC power cable.
2. Connect the DC power cables from the input terminals to the output terminals of the
PDU, see Figure 6-24.
6-18
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
4. PDU -48 V DC input
(blue)
5. -48 V RTN DC
output PDU (black)
connected to a DC
power supply module
6. -48 V DC output PDU
(blue) connected to
a DC power supply
module
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
fire-resistant cable
Protective ground in
Protective ground on
6-19
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.05 m
tube, 14
0.05 m
2
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 6-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
cabinet in the
cable
equipment room
2
RTN input
distribution cabinet in
multi-strand cable
Protective ground in
Protective ground on
6-20
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.05 m
tube, 14
0.05 m
2
8
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 6-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
RTN input
distribution cabinet in
single-core cable
Protective ground in
Protective ground on
6-21
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.05 m
tube, 14
0.05 m
tube, 14
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 6 and No. 7 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 5 terminal (M8), select No. 8 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For connections of 35 mm2 power cables from the power distribution cabinet in the
equipment room to the PDU, refer to Table 6-4, Table 6-5, and Table 6-6 for different
certification standards and requirements.
Table 6-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
distribution cabinet in
single-strand fire-resistant
cable
6-22
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
3
Protective ground in
Protective ground on
0.05 m
tube, 14
0.05 m
2
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 6-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
multi-strand conducting
equipment room
cable
distribution cabinet in
conducting cable
Protective ground in
Protective ground on
6-23
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
4
0.05 m
tube, 14
0.05 m
2
7
0.05 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
Table 6-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
Protective ground in
Protective ground on
0.03 m
tube, 14
6-24
SJ-20140731105308-005|2014-10-20 (R1.0)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
6
0.03 m
tube, 14
0.03 m
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 50 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 6-7.
Table 6-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
equipment room
2
distribution cabinet in
Protective ground in
Protective ground on
0.05 m
tube, 20
0.05 m
2
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
6-25
SJ-20140731105308-005|2014-10-20 (R1.0)
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For wiring of 70 mm2 power cables from the power distribution cabinet in the equipment
room to the PDU, refer to Table 6-8.
Table 6-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification)
No.
Power Distribution
PDU (Input)
Cabinet in the
Quan-
Description
tity
Equipment Room
1
the PDU
cabinet in the
single-strand fire-resistant
equipment room
cable
distribution cabinet in
single-strand fire-resistant
cable
Protective ground in
Protective ground on
0.05 m
tube, 20
0.05 m
2
7
0.05 m
Yellow-green fire-resistant
Crimp No. 1 and No. 2 cables to No. 4 terminal (M8), select No. 5 and No. 6 heat shrink tubes
according to the cable color, and connect them to the PDU input terminals. The ends on the
power distribution cabinet in the equipment room are determined according to the site survey.
Crimp No. 3 cable to No. 4 terminal (M8), select No. 7 heat shrink tube, and connect it to
the protective ground on top of the cabinet. The protective ground in the equipment room is
determined according to the site survey.
For the power cable connections from the output terminals the PDU to a DC power
supply module of the ZXR10 M6000-3S chassis, refer to Table 6-9.
6-26
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 6-9 Wiring of Power Cables from PDU to Power Supply Module
PDU (Output)
DC Power Supply
Quantity
Length (m)
Description
Subject to
the config-
female connector
Module
NEG A-1
-48 V
uration
RTN A-1
NEG B-1
-48 V RTN
-48 V
Subject to
the config-
cable, female
uration
connector
Subject to
the config-
female connector
uration
RTN B-1
-48 V RTN
Subject to
the config-
cable, female
uration
connector
3. Install the grounding cable of the PDU. Connect one end of the protective grounding
cable to the grounding rod of the PDU (there are two grounding rods on interior sides
of the PDU, and you only need to connect to one of them), and connect the other end
to the grounding point inside the cabinet (at top of the cabinet).
4. Check the input terminals with a multimeter to verify that there is no short circuit
between the -48 V and -48 V RTN terminals and between the -48 V and PGND
terminals.
5. Unplug the DC power supply module from the chassis.
6. Connect the DC power cables to the input terminals of the DC supply modules of the
ZXR10 M6000-3S chassis.
For the connections, refer to Figure 6-25.
6-27
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 6-25 Wiring of Power Cables at the Ends on a DC Power Supply Module
1. Cabinet grounding
cable
2. PDU grounding cable
3. PDU -48 V RTN DC
input (black)
7. Plug the DC power supply module into the chassis, and fasten the protective cover on
the wiring terminal of the DC power supply module.
8. Use straps to bind the DC power cable at intervals of 100 mm to 150 mm to fasten the
power cable on the cabinet cable tray and the wiring ladder in the equipment room.
9. Paste labels at about 0.79 in. (20 mm) to both ends of the DC power cable.
End of Steps
Prerequisite
l
l
The chassis grounding cable is installed and contacts the ground properly.
An AC power cable is available.
6-28
SJ-20140731105308-005|2014-10-20 (R1.0)
The cables between the AC power distribution box and the AC power distribution
cabinet in the equipment room are disconnected. The power supply module switch
on the bottom of the chassis is in the OFF position.
Context
If AC power supply is used in the equipment room, a dual-9 AC PDU should be used for
power supply (recommended). Power cables are connected from the power distribution
cabinet in the equipment room to the PDU and then to the AC power supply modules of
the M6000-3S chassis.
Steps
1. Connect the power cables at the input and output terminals of the AC PDU.
For the power cable connections at the input and output terminals of the PDU, see
Figure 6-26.
Figure 6-26 Cable Connections for the PDU
For the cable connections from the power distribution cabinet to the PDU, refer to Table
6-10.
6-29
SJ-20140731105308-005|2014-10-20 (R1.0)
Cable
PDU (Input)
Power Dis-
Quantity
tribution
Length
Description
(m)
Cabinet in
the Equipment Room
1
Black fire-
Output of
resistant 3-core
software cable
Subject to
On the power
the power
the config-
distribution
distribution
uration
cabinet
pre-insulated
Yellow-green core: AC
in the
tube terminals
equipment
must be
room
crimped on
Black fire-
Output of
resistant 3-core
the power
the config-
software cable
distribution
uration
cabinet
Yellow-green core: AC
in the
equipment
Subject to
H07Z-K35
Protective
yellow-green
the cabinet
single-core cable
user power
supply side,
connectors are
determined by
engineering
survey.
room
3
site. On the
Subject to
Protective
ground of
the config-
grounding
the power
uration
cable of
distribution
the cabinet,
cabinet or
yellow-green
the copper
ground
bar in the
equipment
room
4
Copper lug
The aperture
is 0.32 in.
(8 mm), and
the applicable
cable diameter
is in the range
of 26.66 - 42.42
mm2
0.04 m 2
14
1. Cable No.3 is crimped with OT terminal No.4 (M8) on the engineering site. The grounding end in the equipment
room is determined through an engineering survey. In general, a No.4 (M8) terminal and tube No.5 are used.
6-30
SJ-20140731105308-005|2014-10-20 (R1.0)
For the cable connections from the PDU to the AC power supply modules in the
M6000-3S chassis, refer to Table 6-11.
Table 6-11 Cable Wiring From PDU to AC Power Supply Modules of M6000-3S
AC Power Supply
PDU (Output)
Quantity
Length (m)
Description
Subject to the
AC power cable
connected to the
device's AC power
supply module
Module of M6000-3S
configuration
2. Connect the power cable to the input terminal of an AC power supply module.
a. Use a marker pen to temporarily mark both ends of the AC power cable.
b. Connect the AC power cables to the sockets on the AC power supply module, and
then close the release latch, see Figure 6-27.
6-31
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure 6-27 Cable Wiring on the Terminals of the AC Power Supply Modules
of M6000-3S
1. AC power
distribution
box input
(yellow-green)
2. AC power
distribution box
input (blue)
3. AC power
distribution box
input (brown)
4. AC power cable
(connected to the
AC power supply
module)
5. Cabinet groundin
g cable
6. Grounding cable
of the AC power
distribution box
3. Use straps to bind the AC power cable at intervals of 3.94 in. (100 mm) to 5.91 in.
(150 mm) to fasten the power cable on the cabinet cable tray and the wiring ladder in
the equipment room.
4. Paste labels at about 0.79 in. (20 mm) to both ends of the AC power cable.
End of Steps
6-32
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 7
Before installation, signal cables must pass the continuity test. Both sides of each
signal cable should be marked or labeled correctly.
Signal cables must be free of damage, breakage, and joint.
Do not route signal cables on ventilation holes because this will negatively affect heat
dissipation and cable durability.
Signal cables must be routed at least 11.82 in. (300 mm) away from power cables.
Cabling in the cabinet must not affect door installation.
Cables must be routed along the horizontal and vertical cable trays in a flat and straight
manner, without crossovers or folds.
Binding Principles
l
l
l
l
Cables should be bound and tightened properly. Cable ties should be arranged in the
same direction.
The excess part of the cable tie should be cut off from the root without any jagged
edge.
Take protective measures when attaching a signal cable to a sharp structural
component.
Optical fibers should be bound with the fiber ties for protection.
Bending Principles
l
l
Cable bends should be identically even and smooth. The bending radius should be
larger than 2.36 in. (60 mm) (not less than 20 times the outer diameter of the cable).
The turning points of cables cannot be bound with cable ties. A extra length should
be reserved for all signal cables, see Figure 7-1.
7-1
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Anti-rodent screen
7-2
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Anti-rodent screen
Prerequisite
l
l
Antistatic gloves, diagonal pliers, cable straps, and a ladder are available.
The route of network cables is planned with consideration of possible capacity
expansion. The specific wiring table is obtained.
7-3
SJ-20140731105308-005|2014-10-20 (R1.0)
Steps
1. Wear antistatic gloves.
2. In accordance with the planned route of network cables, determine the installation
positions of both ends of each cable and the cable length.
3. Use a marker pen to temporarily mark both ends of each network cable to identify the
installation positions.
4. Connect the network cables through the top or bottom to the inside of the cabinet.
5. (Optional) To prepare a network cable, refer to Appendix C Preparing Network Cables.
6. Insert one end of each network cable into the corresponding port, and connect the
other end through the cable tray in the equipment room to the other port.
7. Paste formal labels at both ends of each cable. For how to prepare and paste a label,
refer to Appendix D Preparing and Pasting Labels.
8. Verify that the network cables are connected properly, and bind the network cables.
End of Steps
Prerequisite
l
l
Antistatic gloves, diagonal pliers, cable straps, and a ladder are available.
The route of network cables is planned with consideration of possible capacity
expansion. The specific wiring configuration table is obtained.
Steps
1. Wear antistatic gloves.
2. Verify that the optical fibers are intact, and the optical fiber specifications, lengths, and
connector types satisfy the design and contract requirements.
3. Use a marker pen to temporarily mark both ends of each optical fiber to identify the
installation positions of both ends.
4. Place the optical fibers into protective soft tubes.
7-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Note:
Each protective tube can hold multiple optical fibers, but the recommended upper limit
is 12. Before placing optical fibers into a protective tube, bind the optical fibers with a
nylon sticky strip, and protect the optical connectors from damage.
5. In accordance with the route designed in the construction drawing, connect the optical
fibers from devices such as ODF to the ZXR10 M6000-S.
a. In accordance with the cabling method (upward or downward cabling), push the
optical fibers with protective tubes through the optical fiber inlet on top/bottom of
the cabinet into the inside of the cabinet. It is recommended that the protective
tubes be moved to 5 cm over/below the installation tray.
l For upward cabling, the installation tray refers to the installation tray of the
power distribution box.
l For downward cabling, the installation tray refers to the installation tray
nearest to the cabinet bottom.
b. Lead the optical fibers stripped out of the protective tubes to the cabling area on
one side of the cabinet, and then to the corresponding optical interfaces on the
device.
6. Connect the user end of each optical fiber to the corresponding optical interface on
the ODF.
7. Prepare labels for the optical fiber and paste them firmly at both ends of each fiber.
For how to prepare and paste a label, refer to Appendix D Preparing and Pasting
Labels.
8. Along the installation route of the optical fibers, use nylon sticky strips to bind the
optical fibers, and fix bundles of optical fibers in the cabling area.
9. Wind excessive optical fibers and bind them on the top or bottom of the cabinet so that
they cannot be reached easily.
End of Steps
7-5
SJ-20140731105308-005|2014-10-20 (R1.0)
Caution!
During optical module installation, push the module evenly in place in accordance with the
marks on the module and interface board slot. Do not plug or unplug an optical module
with excessive force.
To verify that the optical module is installed properly, try to pull the module after the
installation. Failure to pull out the module indicates that the module is installed properly.
Context
ZXR10 M6000-S interface boards use the following types of pluggable optical modules:
l
l
l
Prerequisite
An antistatic wrist strap is available with the grounding end being inserted into the ESD
hole of the chassis.
Steps
l
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Gently push the XFP optical module to the farthest end. Lift the handle ring on the
module to clasp the module to the slot.
End of Steps
Caution!
After the protective cap of an optical fiber connector is removed, do not touch the optical
fiber connector, and prevent it from other types of pollution (such as dust).
During optical fiber connector installation, push the connector evenly into the slot in
accordance with the marks on the connector and slot. Do not plug or unplug a connector
with excessive force to avoid damage.
To check whether the connector is installed properly, try to pull the connector after the
installation. Failure to pull out the connector indicates that the connector is installed
properly.
Prerequisite
An antistatic wrist strap is available with the grounding end being inserted into the ESD
hole of the chassis.
Steps
l
SJ-20140731105308-005|2014-10-20 (R1.0)
clip locks the SC connector). When you hear a "click" sound and the connector
cannot be pushed any further, the SC connector is moved to the right position.
l
7-8
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 8
8-1
SJ-20140731105308-005|2014-10-20 (R1.0)
8-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 9
Warning!
Before checking hardware installation, ensure that the power distribution cabinet
connected to the cabinet is powered off, and the switches of the cabinet power distribution
box and the chassis power supply module are in OFF state.
Requirement
The cabinet position complies with the actual engineering design documents.
The expansion bolt fastening a cabinet or base to the ground is firm and all the screws
are fastened tightly.
The horizontal and vertical deviations of a cabinet are less than 0.12 in. (3 mm). The
front sides of the cabinets in the same row are on the same plane with a deviation of
less than 0.2 in. (5 mm).
The resistance of each insulated point between a bracket and a cabinet measured by the
M switch of a multimeter is greater than 5 M.
The accessories of the front and back doors of a cabinet are intact, and connecting plates
are installed between combined cabinets.
The front and back doors of a cabinet can be opened and closed smoothly.
Cabinets in the same column are aligned closely and neatly. Rows of cabinets along the
main aisle are aligned with a deviation of less than 5 mm.
Cabinets are clean. There are no excessive bands, threads, or other unrequired items
inside the cabinets. No damage or fingerprints are seen inside or outside the cabinets.
All the entrance and exit holes of a cabinet are sealed, such as cover plates and
mouse-proof bags.
10
Use a multimeter to test the leading-in ends of the power distribution box of a cabinet. No
short circuit exists.
9-1
SJ-20140731105308-005|2014-10-20 (R1.0)
Requirement
The device positions comply with the actual engineering design documents.
The screws of all the devices are fastened, and the clasp of each board is in position.
The fan inlet and outlet for devices are not blocked.
Requirement
The position of a power supply device (such as a power distribution cabinet) complies with
the actual engineering design documents.
Power cables and protective grounding cables are connected reliably and contact properly,
and their polarity is correct.
Naked wires of connecting terminals and OT terminals are not exposed. They are bound
with insulated tape or covered by heat shrink tubes.
Labels are made and pasted on power cables and protective grounding cables. The labels
are pasted neatly and facing the same direction (including power distribution switch labels).
It is recommended that a label be pasted 0.79 in. (20 mm) to the corresponding connector.
External power cables and grounding cables of a cabinet are straight and bound separately
from other cables.
Excessive parts of a power cable or grounding cable are cut off, not being coiled.
The distance between an external power cable or grounding cable of a cabinet and a
signal cable is greater than 1.18 in. (30 mm).
Requirement
The two ends of a cable are connected correctly, and cable connectors are tightened.
Cables are installed along a horizontal or vertical cable tray, and bound in cable clip holes.
Signal cables are not routed over the heat dissipation holes of the cabinet.
Cables are straight and smooth. No cable crossing exists inside a cabinet, and cables
outside a cabinet are bound in bundles.
Cable clips do not overlap. Cable connectors are cut evenly without protruding parts.
Both ends of each signal cable are pasted with labels, and the labels are facing the
same direction.
9-3
SJ-20140731105308-005|2014-10-20 (R1.0)
9-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 10
Prerequisite
An antistatic wrist strap and a multimeter are available.
Steps
1. Perform the following checks before power-on:
a. Verify that the power distribution cabinet connected to the ZXR10 M6000-S cabinet
is powered off, and the switches of the power distribution box and the power supply
module in the chassis are in the OFF position.
b. Verify that the board is installed in the chassis, and the board clasp is in position.
2. To supply power to a cabinet, perform the following steps:
a. Switch on the power supply to the cabinet or set the power control switch on the
power distribution cabinet to the "ON" position.
Caution!
The cabinet power-on operation can be completed by professional power
engineers only.
b. Use a multimeter to verify that the input voltage of the cabinet power distribution
box is within the voltage tolerance range.
l DC power supply: Verify that no short circuit exists between the -48 V power
supply and the -48 V RTN working ground, or between the -48 V power supply
10-1
SJ-20140731105308-005|2014-10-20 (R1.0)
l
c.
and the PGND protective ground, and that the voltage range is from -60 V to
-38 V.
AC power supply: Verify that no short circuit exists between an AC neutral
wire and an AC live wire, and that the voltage range is from 200 V to 240 V.
Set the power control switch on the cabinet power distribution box connected to
the chassis to the "ON" position.
Set the power control switch on the cabinet power distribution box connected to
the chassis to the "ON" position.
d. Use a multimeter to verify that the input voltage of the chassis power supply
module is within the voltage tolerance range.
l DC power supply: Verify that no short circuit exists between the -48 V power
supply and the -48 V RTN working ground, or between the -48 V power supply
and the PGND protective ground, and that the voltage range is from -60 V to
-38 V.
l AC power supply: Verify that no short circuit exists between an AC neutral
wire and an AC live wire, and that the voltage range is from 200 V to 240 V.
e. Set the power control switch of the chassis power supply module to the "ON"
position.
Note:
When the power supply module is switched on, power is supplied to the primary
area first and then to the secondary area.
f.
Verify that power supply modules and fan modules are in normal status.
Verify that:
l
l
The RUN indicator (green) of each power supply module is on, and the FAULT
indicator is off.
The RUN indicator (green) on each fan module is on.
After the board is supplied with power, the RUN indicator (green) on the board is
on.
End of Steps
Steps
1. To stop supplying power to a chassis, perform the following steps:
a. Set the power control switch of the chassis power supply module to the "OFF"
position.
b. Set the power control switch on the cabinet power distribution box connected to
the chassis to the "OFF" position.
2. (Optional) To stop supplying power to a cabinet, perform the following steps:
Switch off the power supply to the cabinet or set the power control switch on the power
distribution cabinet to the "OFF" position.
Caution!
To cut off the power supply from the power distribution cabinet to the cabinet, you
must remove the fuse from the power distribution cabinet or set the switch of the
power distribution cabinet to the OFF position. Do not perform this operation without
permission.
End of Steps
10-3
SJ-20140731105308-005|2014-10-20 (R1.0)
10-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Chapter 11
Site Clean-Up
After completing all the installations, perform the following operations before leaving the
installation site:
l
Remove leftovers
Clear up the installation site, remove all the leftovers.
Dispose of leftovers in accordance with local laws and regulations.
11-1
SJ-20140731105308-005|2014-10-20 (R1.0)
11-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Appendix A
Steps
1. Open the rear panel of the PDU, see Figure A-1.
Figure A-1 Opening the Rear Panel
2. Remove the two copper ground bars RTN(+), see Figure A-2. Save the screws,
insulating washers, copper ground bars, insulating plates, and OT terminals of the
output protective grounding cable.
A-1
SJ-20140731105308-005|2014-10-20 (R1.0)
3. Install the jumper chip and -48 V DC input cables (with OT terminals), and fix them
with M6X16 combination screws, see Figure A-3.
Figure A-3 Installing the Jumper Chip and DC Input Cables
For the DC PDU after the jumper chip and -48 V DC input cables are installed, see
Figure A-4.
Figure A-4 DC PDU After the Jumper Chip and DC Input Cables Are Installed
4. Install two copper ground bars RTN(+) and OT terminals of input and output protective
grounding cables, see Figure A-5.
A-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure A-5 Installing Copper Ground Bars and OT Terminals of Input and Output
Protective Grounding Cables
For the DC PDU after the rear panel is installed, see Figure A-7.
Figure A-7 DC PDU After the Rear Panel is Installed
End of Steps
A-3
SJ-20140731105308-005|2014-10-20 (R1.0)
A-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Appendix B
Prerequisite
l
l
Steps
1. Depending on the actual length, use the cutting pliers to cut off a section of the cable
and retain the remaining part, see Figure B-1.
Figure B-1 Cutting the Cable
2. Push a heat shrink tube along one end of the stripping head to cover the cable, see
Figure B-2.
The color of the heat shrink tube should be the same as that of the cable.
B-1
SJ-20140731105308-005|2014-10-20 (R1.0)
1. Cable
3. Use the wire stripper to peel a section of the insulating layer on one end of the cable.
The length of the peeled section is equal to that of the copper lug, see Figure B-3.
Note:
When peeling the cable, do not scratch the metallic conductor of the cable.
1. Cable
2. Copper lug
4. Insert the core of the cable into the hole of the copper lug until it cannot be pushed
any further, see Figure B-4.
The copper lug and the copper cable contact properly, and no copper is exposed.
Figure B-4 Inserting the Cable into the Copper Lug
1. Copper lug
B-2
SJ-20140731105308-005|2014-10-20 (R1.0)
5. Use the hydraulic clamp to press the copper lug, see Figure B-5. Ensure that the
copper lug is firmly attached to the cable.
Note:
The press mould of the hydraulic clamp should be of the same size as the cable
diameter.
1. Press mould
6. Cover the junction of the copper lug and the cable with a heat shrink tube.
7. Use the heat gun to heat the heat shrink tube until it is tightly wrapped around the
connector, see Figure B-6.
Figure B-6 Blowing the Heat Shrink Tube to Let It Shrink
8. Check the cable and ensure that there is no oxidation on the terminal and the outer
layer of the cable is intact.
End of Steps
B-3
SJ-20140731105308-005|2014-10-20 (R1.0)
B-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Appendix C
By connection type, network cables can be divided into straight-through cables and
crossover cables.
A straight-through cable is used between a network card and a switch (or a hub). A
crossover cable is used between switches (or hubs) or between network cards.
By physical property, network cables can be divided into shielded cables and
non-shielded cables.
Note:
The method for preparing a shielded cable is similar to that for preparing a
non-shielded cable. This procedure uses non-shielded cable as an example to
describe how to prepare a network cable.
1. Connector
3. Cable jacket
C-1
SJ-20140731105308-005|2014-10-20 (R1.0)
For a straight-through cable, wires at one end have the same corresponding colors at
the other end. The sequence of wires complies with the EIA/TIA 568B standard. For
wire relationships of a straight-through cable, refer to Table C-1.
Table C-1 Wire Relationships of a Straight-Through Cable
RJ45 Connector A
RJ45 Connector B
Pin
Pin
Core Color
Core Color
White-Orange
White-Orange
Orange
Orange
White-Green
White-Green
Blue
Blue
White-Blue
White-Blue
Green
Green
White-Brown
White-Brown
Brown
Brown
For a crossover cable, wires at one end may have different colors at the other end.
The wire sequence at end A complies with the EIA/TIA 568B standard, and the wire
sequence at end B complies with the EIA/TIA 568A standard. For wire relationships
of a crossover cable, refer to Table C-2.
Table C-2 Wire Relationships of a Crossover Cable
RJ45 Connector A
RJ45 Connector B
Pin
Pin
Core Color
Core Color
White-Orange
White-Green
Orange
Green
White-Green
White-Orange
Blue
Blue
White-Blue
White-Blue
Green
Orange
White-Brown
White-Brown
Brown
Brown
C-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Prerequisite
A pair of diagonal pliers, a wire stripper, a pair of crimping pliers, a network cable tester, a
multimeter, and a pair of gloves are prepared.
Steps
1. Peel the cable jacket (shield) of the twisted pair wires, and cut off the nylon rip cords
within the cable jacket. The peeled length is 16 mm, see Figure C-3.
Note:
When peeling the cable jacket, do not scratch the insulating layer of the twisted pair
wires.
2. Place the peeled twisted pair wires in order, and use diagonal pliers to trim the end of
the wires neatly, see Figure C-4.
For the wire sequence of a straight-through cable, refer to Table C-1. For the wire
sequence of a crossover cable, refer to Table C-2.
Figure C-4 Arranging the Order of Twisted Pair Wires
1 mm = 0.0394 in.
3. Insert the four pairs of ordered twisted pair wires into the pins of the connector, see
Figure C-5. For example, insert the "white-orange" wire into the first pin.
Note:
When inserting the wires, observe the position of the wires from the side or joint side of
the connector and ensure that the wires completely touch the bottom of the connector.
C-3
SJ-20140731105308-005|2014-10-20 (R1.0)
4. Use the crimping pliers to press the connector, see Figure C-6.
Figure C-6 Pressing the Connector
1. Crimping pliers
5. Insert the connectors on both ends of the network cable respectively into the female
RJ45 socket of the network cable tester, see Figure C-7.
Note:
If no network cable tester is available on site, set the multimeter to the ohms position
instead. Perform simple continuity tests in accordance with the wiring relations.
C-4
SJ-20140731105308-005|2014-10-20 (R1.0)
6. Set the switch of the tester to the ON position and test the continuity of the network
cable.
The sequence of indicator lighting for a straight-through cable is different from that for
a crossover cable.
l
l
For a straight-through cable: If indicators 1 to 8 are lit one by one, it indicates that
the continuity of the cable is normal and the connections are correct.
For a crossover cable: If the indicators at the primary end are lit in order of
1-2-3-4-5-6-7-8-G, and the indicators at the secondary end are lit in order of
3-6-1-4-5-2-7-8-G, the network cable is acceptable.
Note:
Setting the switch of the tester to the "S" position can reduce the flashing rate of
indicators, so that you can observe more accurately.
End of Steps
C-5
SJ-20140731105308-005|2014-10-20 (R1.0)
C-6
SJ-20140731105308-005|2014-10-20 (R1.0)
Appendix D
Note:
The style and content of a label can be customized. This chapter only describes ZTE
dedicated labels.
Table of Contents
Common Labels Description................................................................................... D-1
Pasting Labels........................................................................................................ D-7
D-1
SJ-20140731105308-005|2014-10-20 (R1.0)
1 mm = 0.0394 in.
A label is tagged on each end of a power cable. For the pasting position, see Figure D-2.
Figure D-2 Pasting Position of Power Cable Labels (Unit: mm)
1 mm = 0.0394 in.
Label Contents
A power cable label is divided into two types, L and R. Their meanings are as follows:
l
l
L: specifies the location of the power cable connector on ZTE equipment side (ZXR10
M6000-S).
R: specifies the location of the power cable connector on user equipment side.
For L label format descriptions for power cables , refer to Table D-1.
Table D-1 L Label Format Descriptions for Power Cables
Format
Description
Example
XA-B-D
X: system name
SM01
A: equipment number
B: power cable type
D: port number
For R label format descriptions for power cables, refer to Table D-2.
D-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Description
Example
XA-B-C-D
X: system name
PW03
A: device number
B: power cable type
2R and 2L
15
Label Example
For the power cable label to identify a -48 V power cable that is connected from port A-1
on cabinet IPTN01 to port 15 in line 2 on cabinet PW03 at the user equipment side, see
Figure D-3.
Figure D-3 Example of a Power Cable Label
Label Contents
In the upper area of a signal cable label, "TYPE (Fr:) + local end connector number" is
printed. In the lower area of the signal cable label, "TYPE (To:) + remote end connector
number" is printed. "TYPE" refers to the data type of the cable, for example, 75 or 120
. For format descriptions for signal cable labels at the ZTE equipment side, refer to Table
D-3.
D-3
SJ-20140731105308-005|2014-10-20 (R1.0)
Table D-3 Format Descriptions for Signal Cable Labels at the ZTE Equipment Side
Format
Description
Remarks
Example
XA-B-C-D
X: system name
IPTN01
A: device number
contract number.
A: is a unique ZTE cabinet number at a site.
B: subrack
number
(numeral)
0155
(numeral)
subrack.
D: port number
The order of
(numeral and
electric ports is
letter)
as follows: 1R > 1T
For format descriptions for signal cable labels at the DDF side, refer to Table D-4. For
labels at the side of other types of devices, the format is similar.
Table D-4 Format Descriptions for Signal Cable Labels at the DDF Side
Format
Description
Remarks
Example
XA-B-C-D
X: system name
X: DDF
DDF03
A: system number
B: unit module
number
port is located
C: row or line
number
shortened as "L".
D: port number
2R (2L)
7T
relation
Label Example
For the label to identify a 75 clock cable that is connected from port Tx on board 1 of
subrack 1# on cabinet IPTN01 to port 7# in line 2 in module 3# of DDF03, see Figure D-4.
D-4
SJ-20140731105308-005|2014-10-20 (R1.0)
Label Contents
In the upper area of a fiber pigtail label, "(Fr:) OPTICAL + local end connector number" is
printed. In the lower area of the label, "(To:) OPTICAL + remote end connector number"
is printed. For format descriptions for fiber pigtail labels at the ZTE equipment side, refer
to Table D-5.
Table D-5 Format Descriptions for Fiber Pigtail Labels at the ZTE Equipment Side
Format
Description
Remarks
Example
XA-B-C-D
X: system name
IPTN01
A: device number
B: subrack number
(numeral)
(numeral)
D: port number
0155
D-5
SJ-20140731105308-005|2014-10-20 (R1.0)
Format
Description
Remarks
Example
For format descriptions for fiber pigtail labels at the ODF side, refer to Table D-6.
Table D-6 Format Descriptions for Fiber Pigtail Labels at the ODF Side
Format
Description
Remarks
Example
XA-B-C-D
X: system name
X: ODF
ODF 03
A: system number
2R (or 2L)
7R
transmitting/receiving relation
Label Example
For the label to identify a fiber pigtail that is connected from transmitting optical port 9#
in slot 03 on subrack 1# on cabinet IPTN01 to receiving port 7# in line 3 in module 3# of
3#ODF, see Figure D-5.
Figure D-5 Example of a Fiber Pigtail Label
stickers. For the overview of a ZTE dedicated sticker, see Figure D-6. The pasting
position should be apparent on cables and easy for holding labels firmly.
Figure D-6 Wire Length Label (Unit: mm)
1 mm = 0.0394 in.
Label Contents
Wire length is printed on the label.
Label Example
For the length label of a 15m-long cable, see Figure D-7.
Figure D-7 Example of a Cable Length Label
ODF ID
In accordance with the size of an ODF ID board, prepare ODF ID labels and paste
them on ODF ID boards.
Label contents should include ODF number, module number, ODF port number, peer
device number, local device number, subrack number, slot number in an optical line
board, port number, and transmitting/receiving relation.
DDF ID
In accordance with the size of an DDF ID board, prepare DDF ID labels and paste
them on DDF ID boards.
Label contents should include DDF device number, module number, DDF port number,
peer device number, local device number, subrack number, slot number, port number,
and transmitting/receiving relation.
Prerequisite
Before pasting a label, write or print correct information on the label.
Context
When pasting labels, pay attention to the following points:
l
l
l
l
Before pasting a label, clean the pasting position and ensure that there is no dust or
foreign matter.
During the pasting process, do not touch the sticky side of the label. Otherwise, the
label may be not attached firmly.
The label should not be pasted on cable bends or other positions that affect cable
installation.
Labels should face the same direction. The side indicating where a cable goes to is
upward or towards the operation and maintenance side so that the label can be easily
read.
Steps
1. Place the label about 20 mm to the wire connector, fold the label tail towards the left
side, so that the label is stuck to the cable, see Figure D-8.
Figure D-8 Pasting a Label (1)
1 mm = 0.0394 in.
1. Label head
2. Label tail
Note:
For a vertical cable, the label head is towards the left side. For a horizontal wire, the
label head is downwards.
D-8
SJ-20140731105308-005|2014-10-20 (R1.0)
2. Fold the lower part of the label head inwards, so that the upper part and lower part of
the label head are stuck together, see Figure D-9.
Figure D-9 Pasting a Label (2)
1 mm = 0.0394 in.
For the overview of a pasted label, see Figure D-10.
Figure D-10 Pasted Label
End of Steps
D-9
SJ-20140731105308-005|2014-10-20 (R1.0)
D-10
SJ-20140731105308-005|2014-10-20 (R1.0)
Appendix E
Steps
1. Loosen the screws on the central guide rail, see Figure E-1.
Figure E-1 Loosening Screws on the Central Guide Rail
2. Loosen the screws under the central guide rail, see Figure E-2.
E-1
SJ-20140731105308-005|2014-10-20 (R1.0)
Figure E-4 shows the board after the central guide rail is removed.
Figure E-4 Board after Rail is Removed
End of Steps
E-2
SJ-20140731105308-005|2014-10-20 (R1.0)
Figures
Figure 1-1 ZXR10 M6000-S Installation Flow ............................................................ 1-2
Figure 1-2 Unpacking a Wooden Case...................................................................... 1-7
Figure 1-3 Removing a Carton .................................................................................. 1-8
Figure 1-4 Removing the Outer Packing of a Board .................................................. 1-8
Figure 3-1 Standard Cabinet..................................................................................... 3-2
Figure 3-2 Installing a Mounting Bracket ................................................................... 3-2
Figure 3-3 Floating Nut Installed ............................................................................... 3-3
Figure 3-4 Installing the M6000-18S Chassis In the Cabinet ..................................... 3-4
Figure 3-5 M6000-18S Chassis Installed In the Cabinet............................................ 3-5
Figure 3-6 M6000-18S Grounding Cable................................................................... 3-6
Figure 3-7 Protective Grounding Cable Connected to the M6000-18S
Chassis................................................................................................... 3-6
Figure 3-8 Installing a Power Supply Box.................................................................. 3-7
Figure 3-9 Installing a Power Supply Module and a Power Switch Module ................ 3-8
Figure 3-10 Chassis With Power Supply Modules and Power Switch Modules
Installed .................................................................................................. 3-8
Figure 3-11 Installing a Mesh Guard ......................................................................... 3-9
Figure 3-12 Installing Fan Modules ......................................................................... 3-10
Figure 3-13 Chassis After Fan Modules Are Installed.............................................. 3-11
Figure 3-14 Installing Air Filters............................................................................... 3-12
Figure 3-15 Installing MPU Boards (1) .................................................................... 3-14
Figure 3-16 Installing MPU Boards (2) .................................................................... 3-15
Figure 3-17 Installing MPU Boards (3) .................................................................... 3-16
Figure 3-18 Installing an SFU Board ....................................................................... 3-17
Figure 3-19 Installing Network Processing Boards (1) ............................................. 3-19
Figure 3-20 Installing Network Processing Boards (2) ............................................. 3-20
Figure 3-21 Installing Network Processing Boards (3) ............................................. 3-21
Figure 3-22 Installing PIU Cards ............................................................................. 3-22
Figure 3-23 Installing Front Cable Trays ................................................................. 3-24
Figure 3-24 Chassis After Front Cable Trays Are Installed ...................................... 3-25
Figure 3-25 Installing the Lateral Cable Tray........................................................... 3-26
Figure 3-26 DC Power Cable External View............................................................ 3-28
I
SJ-20140731105308-005|2014-10-20 (R1.0)
II
SJ-20140731105308-005|2014-10-20 (R1.0)
Figures
Installing the M6000-3S Mother Card into the Board ........................... 6-13
Figure 6-17 M6000-3S Mother Card Installed In the Board ..................................... 6-13
Figure 6-18 Installing the M6000-3S Daughter Card into the Mother Card............... 6-14
Figure 6-19 M6000-3S Daughter Card Installed In the Mother Card ........................ 6-14
Figure 6-20 M6000-3S Cable Tray .......................................................................... 6-15
Figure 6-21 Installing the M6000-3S Cable Tray (1) ................................................ 6-16
Figure 6-22 Installing the M6000-3S Cable Tray (2) ................................................ 6-16
Figure 6-23 Installing the M6000-3S Cable Tray (3) ................................................ 6-17
Figure 6-24 Power Cable Connections in the DC Power Box .................................. 6-19
IV
SJ-20140731105308-005|2014-10-20 (R1.0)
Figures
Figure 6-25 Wiring of Power Cables at the Ends on a DC Power Supply Module
............................................................................................................. 6-28
Figure 6-26 Cable Connections for the PDU ........................................................... 6-29
Figure 6-27 Cable Wiring on the Terminals of the AC Power Supply Modules of
M6000-3S ............................................................................................. 6-32
Figure 7-1 Binding Cables......................................................................................... 7-2
Figure 7-2 Cable Outlets on Cabinet Top .................................................................. 7-2
Figure 7-3 Cable Outlets at the Cabinet Bottom ........................................................ 7-3
Figure A-1 Opening the Rear Panel ..........................................................................A-1
Figure A-2 Removing Copper Ground Bars...............................................................A-2
Figure A-3 Installing the Jumper Chip and DC Input Cables......................................A-2
Figure A-4 DC PDU After the Jumper Chip and DC Input Cables Are Installed ...........A-2
Figure A-5 Installing Copper Ground Bars and OT Terminals of Input and Output
Protective Grounding Cables ..................................................................A-3
Figure A-6 Installing the Rear Panel..........................................................................A-3
Figure A-7 DC PDU After the Rear Panel is Installed ................................................A-3
Figure B-1 Cutting the Cable.....................................................................................B-1
Figure B-2 Covering the Cable with a Heat Shrink Tube............................................B-2
Figure B-3 Peeling the Insulating Layer ....................................................................B-2
Figure B-4 Inserting the Cable into the Copper Lug...................................................B-2
Figure B-5 Pressing the Copper Lug .........................................................................B-3
Figure B-6 Blowing the Heat Shrink Tube to Let It Shrink ..........................................B-3
Figure C-1 Composition of a Non-shielded Network Cable....................................... C-1
Figure C-2 Pins........................................................................................................ C-2
Figure C-3 Peeling the Cable Jacket........................................................................ C-3
Figure C-4 Arranging the Order of Twisted Pair Wires.............................................. C-3
Figure C-5 Inserting the Twisted Pair Wires ............................................................. C-4
Figure C-6 Pressing the Connector .......................................................................... C-4
Figure C-7 Testing the Network Cable...................................................................... C-5
Figure D-1 Power Cable Label (Unit: mm) ............................................................... D-2
Figure D-2 Pasting Position of Power Cable Labels (Unit: mm)................................ D-2
Figure D-3 Example of a Power Cable Label............................................................ D-3
Figure D-4 Example of a Signal Cable Label............................................................ D-5
Figure D-5 Example of a Fiber Pigtail Label ............................................................. D-6
Figure D-6 Wire Length Label (Unit: mm) ................................................................ D-7
Figure D-7 Example of a Cable Length Label........................................................... D-7
V
SJ-20140731105308-005|2014-10-20 (R1.0)
VI
SJ-20140731105308-005|2014-10-20 (R1.0)
Tables
Table 1-1 Tools and Instruments ............................................................................... 1-3
Table 3-1 DC Power Cable Connections ................................................................. 3-30
Table 3-2 DC Power Cable Connections ................................................................. 3-34
Table 3-3 AC Power Cable Connections ................................................................. 3-38
Table 3-4 HVDC Power Cable Connections ............................................................ 3-42
Table 4-1 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 4-25
Table 4-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 4-26
Table 4-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 4-27
Table 4-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 4-28
Table 4-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 4-29
Table 4-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 4-30
Table 4-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 4-31
Table 4-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 4-32
Table 4-9
Table 4-10 Cable Wiring From Power Distribution Cabinet to PDU.......................... 4-36
Table 4-11 Cable Wiring From PDU to AC/DC Converter ........................................ 4-37
Table 4-12 Cable Wiring From AC/DC Converter to DC Power Supply Modules
(VDE)..................................................................................................... 4-39
Table 4-13 Cable Wiring From AC/DC Converter to DC Power Supply Modules
(VDE Certificated for British Market)....................................................... 4-40
Table 4-14 Cable Wiring From AC/DC Converter to DC Power Supply Modules
(CCC) .................................................................................................... 4-41
Table 4-15 Cable Wiring From AC/DC Converter to DC Power Supply Modules
(UL) ....................................................................................................... 4-43
Table 5-1 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 5-25
VII
SJ-20140731105308-005|2014-10-20 (R1.0)
Table 5-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 5-26
Table 5-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 5-27
Table 5-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 5-28
Table 5-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 5-28
Table 5-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 5-29
Table 5-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 5-30
Table 5-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 5-31
Table 5-9
Table 5-10 Cable Wiring From Power Distribution Cabinet to PDU ......................... 5-35
Table 5-11 Cable Wiring From PDU to AC Power Supply Modules of M6000-5S
.............................................................................................................. 5-36
Table 6-1 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 6-19
Table 6-2 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 6-20
Table 6-3 Wiring of 25 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 6-21
Table 6-4 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 6-22
Table 6-5 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (UL, VDE for Non-British Markets) ................. 6-23
Table 6-6 Wiring of 35 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (VDE for British Market) ................................. 6-24
Table 6-7 Wiring of 50 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 6-25
Table 6-8 Wiring of 70 mm2 Power Cables from Power Distribution Cabinet in
Equipment Room to PDU (Chinese Certification) ................................... 6-26
Table 6-9
Table 6-10 Cable Wiring From Power Distribution Cabinet to PDU ......................... 6-30
Table 6-11 Cable Wiring From PDU to AC Power Supply Modules of M6000-3S
.............................................................................................................. 6-31
Table 9-1 Cabinet Installation Checklist..................................................................... 9-1
VIII
SJ-20140731105308-005|2014-10-20 (R1.0)
Tables
Table 9-2 Checklist of Device Installations Inside the Cabinet ................................... 9-2
Table 9-3 Checklist of the Installation of Power Cables and Protective Grounding
Cables ..................................................................................................... 9-2
Table 9-4 Signal Cable Installation Checklist ............................................................. 9-3
Table C-1 Wire Relationships of a Straight-Through Cable....................................... C-2
Table C-2 Wire Relationships of a Crossover Cable ................................................. C-2
Table D-1 L Label Format Descriptions for Power Cables ........................................ D-2
Table D-2 R Label Format Descriptions for Power Cables ........................................ D-3
Table D-3 Format Descriptions for Signal Cable Labels at the ZTE Equipment
Side ........................................................................................................ D-4
Table D-4 Format Descriptions for Signal Cable Labels at the DDF Side.................. D-4
Table D-5 Format Descriptions for Fiber Pigtail Labels at the ZTE Equipment
Side ........................................................................................................ D-5
Table D-6 Format Descriptions for Fiber Pigtail Labels at the ODF Side ................... D-6
IX
SJ-20140731105308-005|2014-10-20 (R1.0)
Tables
X
SJ-20140731105308-005|2014-10-20 (R1.0)
Glossary
DDF
- Digital Distribution Frame
ESD
- Electrostatic Discharge
ODF
- Optical Distribution Frame
PDU
- Power Distribution Unit
PE
- Protective Earth
SFP
- Small Form-Factor Pluggable
SFP+
- Small Form-factor Pluggable Plus
XFP
- 10-Gigabit Small Form-Factor Pluggable
XI
SJ-20140731105308-005|2014-10-20 (R1.0)