ELECTRICAL INSTALLATION
CONDITION REPORT
IPN4/0345428
Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor or
Conforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX
Address:
SC House
Vanwall Road
Maidenhead
Berkshire
Original
Client:
This report must be used only for reporting on the condition of an existing installation.
Address
SC House
Vanwall Road
Maidenhead
Berkshire
of premises:
Evidence of alterations
years Description
35
Commercial
domestic, commercial,
or additions
industrial, other
(Please state)
Electrical Installation Certificate No or previous
04/04/2011
Periodic Inspection or Condition Report No:
If yes,
estimated
age
35
years
IPN2/0097869
Matthew Sloane
Agreed limitations (including the reasons), if any, on the inspection and testing:
Limitation of full insulation resistance tests to lighting circuits due to control gear etc. being connected. Limitation of testing main supply as the whole supply was unable to be switch off.
None
The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduits
concealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unless
specifically agreed between the client and inspector prior to the inspection.
SATISFACTORY / UNSATISFACTORY
No
Yes
This report should have been reviewed and confirmed by the registered Qualified Supervisor
of the Approved Contractor responsible for issuing it. (See declaration on page 2)
This report is based on the model forms shown in Appendix 6 of BS7671
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)
Page 1 of
15
ELECTRICAL INSTALLATION
CONDITION REPORT
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety.
or
The following observations and recommendations for
N/A
are made
Code
C3
C3
C3
C3
Unit 3, 2nd floor - CPC's order in DB does not match MCB order
C3
C3
Unit 3, 1st floor - small trunking lid missing from column dado trunking
C3
Unit 3, 1st floor - socket outlet incorrectly installed into column dado trunking
C3
C3
10
C3
11
C3
12
C3
13
C3
14
C3
15
DB1 circuit 24 - sockets x 2 on right in comms room pulling out of plasterboard wall
C3
16
C3
17
C3
18
C3
19
C3
20
C3
21
C3
Additional Pages?
No
Yes
Specify page
9
Immediate remedial action
required for items:
One of the following codes, as appropriate, has been allocated to each of the
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action:
Code C1
Code C2
Code C3
Code FI
Original
Item No
Please see the notes for recipient for guidance regarding the Classification codes.
G. DECLARATION
I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of which
are described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information
in this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electrical
ins t a llat io n t ak in g int o a c c o u nt t he s t at e d e x t e n t o f t he ins t a lla tio n an d t h e lim it a t io n s o f t he ins p e c t ion an d t e s t in g ( s e e D ).
I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is
SATISFACTORY / UNSATISFACTORY*
(see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).
*An Unsatisfactory assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigation
without delay (FI) is required.
INSPECTION, TESTING AND ASSESSMENT BY:
REPORT REVIEWED AND CONFIRMED BY:
Signature
Name
(CAPITALS)
Signature
DAVID PATERSON
Position
Approved Electrician
Date:
04/12/2015
Name
(CAPITALS)
ANDY COLLINS
(Registered Qualified Supervisor for the Approved Contractor at J)
Date:
04/12/2015
Page 2 of
IPN4/0345428
15
ELECTRICAL INSTALLATION
CONDITION REPORT
H. SCHEDULES AND ADDITIONAL PAGES
7, 9, 11, 13
Page No(s)
Original
The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.
I. NEXT INSPECTION
I/We recommend that this installation is further
inspected and tested after an interval of not more than
5 years
provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any items
which have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigated
respectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon as
practicable (see F).
Address:
70 St Marks Road
Maidenhead
Berkshire
Telephone number:
01628 633998
Email Address:
alp@alpelectrical.com
Enrolment number:
(Essential information)
Postcode:SL6 6DW
9514
Branch number:
(if applicable)
d.c.
Nominal U
Voltage(s):
400
2 pole
Nominal
frequency, f
50
3 pole
Prospective fault
current, I
7.8
a.c.
TN-S
1-phase
(2 wire)
TN-C-S
1-phase
(3 wire)
2-phase
(3 wire)
TN-C
3-phase
(3 wire)
TT
3-phase
(4 wire)
other
Number of
sources
Other
IT
0.03
230
Hz
Notes:
(1) by enquiry
kA
(2) by enquiry or by
measurement
BS(EN) 88
Type
(4) by measurement
gG
Rated current
LIM
Short-circuit
80
capacity
Confirmation of
supply polarity
kA
()
Distributor's
facility:
Type:
(eg rod(s),tape(s))
Location:
Electrode
resistance, R:
Installation
earth electrode:
()
Method of
measurement:
Main Switch/Switch-Fuse/Circuit-Breaker/RCD
Type:
BS(EN)
60947-3
No of
Poles
Primary supply
conductors
material
Primary supply
conductors
csa
4
Copper
LIM
Voltage
rating
600
Rated
current,I
LIM
RCD operating
current, I *
N/A
mA
Rated time
delay*
N/A
ms
RCD operating
time (at I )*
N/A
ms
mm
Conductor
material
Conductor
csa
Copper
Connection/
continuity
verified
70
mm
()
Bonding of extraneous-conductive-parts ()
Conductor
material
Conductor
csa
Copper
Water
installation pipes
70
Oil
installation pipes
Connection/
continuity
verified
mm
()
Lightning
protection
Structural
steel
Gas
installation pipes
Other
Page 3 of
IPN4/0345428
15
Outcome*
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.0
2.1
2.2
N/A
N/A
3.0
3.1
3.2
3.3
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
Other methods of protection (where the methods of protection listed below are employed, details should be
provided on separate sheets)
Double insulation
Reinforced insulation
Use of obstacles
Placing out of reach
Non-conducting location
Earth-free local equipotential bonding
Electrical separation for more than one item of equipment
5.0
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
Distribution equipment
Adequacy of working space/accessibility of equipment
Security of fixing
Condition of insulation of live parts
Adequacy/security of barriers
Condition of enclosure(s) in terms of IP rating
Condition of enclosure(s) in terms of fire rating
Enclosure not damaged/deteriorated so as to impair safety
Presence of main switch(es), linked where required
Operation of main switch(es) (functional check)
Correct identification of circuit protective devices
Adequacy of protective devices for prospective fault current
RCD(s) provided for fault protection - includes RCBOs
RCD(s) provided for additional protection - includes RCBOs
Location reference
Original
Item
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
C3
N/A
C3
Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.
IPN4/0345428
Page 4 of
15
Description
Outcome*
Distribution/final circuits
Identification of conductors
Cables correctly supported throughout their length
Condition of insulation of live parts
Non-sheathed cables protected by enclosure in conduit, ducting or trunking
Suitability of containment systems for continued use (including flexible conduit)
Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report)
Confirmation of indication that SPD(s) are functional
Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and
are tight and secure
Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration
Adequacy of cables for current-carrying capacity with regard to the type and nature of installation
Adequacy of protective devices; type and rated current for fault protection
Presence and adequacy of circuit protective conductors
Co-ordination between conductors and overload protective devices
Cable installation methods/practices appropriate to the type and nature of installation and external influences
Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.
Location reference
N/A
C3
Original
Item
IPN4/0345428
N/A
N/A
C3
C3
C3
N/A
N/A
C3
C3
C3
N/A
C3
N/A
Page 5 of
15
7.2
7.3
7.4
8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.7
9.0
9.1
9.2
9.3
9.4
9.5
9.6
9.7
9.8
Description
Outcome*
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.
Location reference
Original
Item
IPN4/0345428
N/A
N/A
N/A
N/A
N/A
N/A
Page 6 of
15
CIRCUIT DETAILS
Location of
distribution board:
Distribution
board designation:
DB1
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Type: 88
BS(EN)
N/A
mA
Operating
current, I
(mm)
(mm)
(s)
(A)
(kA)
(mA)
B/D
10
1.5
COND
0.4
60898
10
10
N/A
3.49
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - kitchen/row 1
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - row 2
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - row 3
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - row 4
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - row 5
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
Lights - row 6
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
10
Lights - boardroom
B/D
1.5
COND
0.4
60898
10
10
N/A
3.49
11
Sockets
B/D
2.5
COND
0.4
60898
32
10
N/A
1.10
12
B/D
2.5
COND
0.4
60898
32
10
N/A
1.10
13
B/D
36
2.5
COND
0.4
60898
32
10
N/A
1.10
14
Column sockets
B/D
2.5
COND
0.4
60898
32
10
N/A
1.10
15
B/D
26
2.5
COND
0.4
60898
32
10
N/A
1.10
16
B/D
2.5
2.5
0.4
60898
32
10
N/A
1.10
17
B/D
2.5
2.5
0.4
60898
16
10
N/A
2.18
18
A/E
B/C
27
2.5
1.5
0.4
60898
32
10
N/A
1.10
19
Sockets - floor
A/E
B/C
2.5
1.5
0.4
60898
32
10
N/A
1.10
20
A/D
B/C
14
2.5
1.5
0.4
60898
32
10
N/A
1.10
21
A/D
B/C
11
2.5
1.5
0.4
61009
32
30
1.10
22
A/D
B/C
2.5
60898
40
10
N/A
0.81
23
Uplighters
A/D
B/C
1.5
0.4
60898
10
10
N/A
3.49
24
A/D
B/C
2.5
1.5
0.4
60898
32
10
N/A
1.10
25
AC wall unit
A/D
B/C
2.5
1.5
0.4
60898
10
N/A
5.82
26
AC condenser - roof
G/D
B/C
0.4
60898
16
10
N/A
2.18
27
A/D
B/A
2.5
1.5
0.4
60898
32
10
N/A
1.10
28
A/D
B/C
2.5
1.5
0.4
60898
29
Spare
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Reference
method
Short-circuit
capacity
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 100
Nominal 230
voltage:
Maximum
permitted by BS 7671
()
32
10
N/A
1.10
N/A
N/A
N/A
N/A
N/A
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit
Thermoplastic/
SWA cables
Thermosetting/
SWA cables
Mineralinsulated
cables
Page 7 of
15
Original
IPN4/0345428
Yes
At I
N/A
ms
At 5I
N/A
ms
N/A
Circuit number
and line
I 5.7
*
Operating times
of associated
RCD (if any)
kA
RCD
Insulation
resistance
Multi P138
function
Continuity
Other
Circuit impedances
()
Ring final circuits only
(measured end to end)
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
Original
RCD operating
times
at I
(if applicable)
Test
button
operation
()
at 5I
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
(ms)
(ms)
N/A
N/A
N/A
0.36
N/A
N/A
LIM
>299
LIM
0.38
N/A
N/A
N/A
N/A
N/A
0.91
N/A
N/A
LIM
>299
LIM
0.94
N/A
N/A
N/A
N/A
N/A
0.58
N/A
N/A
LIM
>299
LIM
0.76
N/A
N/A
2
3
4
5
6
7
8
9
10
N/A
N/A
N/A
0.94
N/A
N/A
LIM
>299
LIM
0.89
N/A
N/A
11
0.58
0.57
LIM
0.05
N/A
N/A
>299
>299
>299
0.09
N/A
N/A
1.86
1.88
LIM
0.98
N/A
N/A
>299
>299
>299
1.01
N/A
N/A
16
0.29
0.28
0.26
0.05
N/A
N/A
>299
>299
>299
0.09
N/A
N/A
17
N/A
N/A
N/A
0.06
N/A
N/A
>299
>299
>299
0.11
N/A
N/A
0.72
0.72
1.04
0.48
N/A
N/A
>299
>299
>299
0.54
N/A
N/A
N/A
N/A
N/A
0.08
N/A
N/A
>299
>299
>299
0.13
N/A
N/A
1.07
1.08
1.17
0.26
N/A
N/A
>199
>199
>199
0.30
N/A
N/A
27
0.97
0.97
1.10
0.18
N/A
N/A
>199
>199
>199
0.22
N/A
N/A
28
0.98
0.98
1.10
0.20
N/A
N/A
>199
>199
>199
0.24
N/A
N/A
12
13
14
15
18
19
20
21
22
23
24
25
26
29
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
04/12/2015
Page 8 of
Name:
(CAPITALS)
DAVID PATERSON
IPN4/0345428
15
CIRCUIT DETAILS
Location of
distribution board:
Distribution
board designation:
DB1
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Type: 88
BS(EN)
N/A
mA
Short-circuit
capacity
Operating
current, I
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Reference
method
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 100
Nominal 230
voltage:
Maximum
permitted by BS 7671
(A)
(kA)
(mA)
16
10
N/A
2.18
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(mm)
(mm)
(s)
30
A/D
B/C
2.5
0.4
60898
31
Spare
N/A
N/A
N/A
N/A
N/A
N/A
32
Spare
N/A
N/A
N/A
N/A
N/A
33
Spare
N/A
N/A
N/A
N/A
34
Spare
N/A
N/A
N/A
N/A
35
Spare
N/A
N/A
N/A
36
Spare
N/A
N/A
N/A
()
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit
Thermoplastic/
SWA cables
Thermosetting/
SWA cables
Mineralinsulated
cables
Page 9 of
15
Original
IPN4/0345428
Yes
At I
N/A
ms
At 5I
N/A
ms
N/A
I 5.7
*
Circuit number
and line
Operating times
of associated
RCD (if any)
kA
RCD
Insulation
resistance
Multi P138
function
Continuity
Other
Circuit impedances
()
Ring final circuits only
(measured end to end)
r
(Line)
r
(Neutral)
r
(cpc)
Insulation resistance
All circuits
(At least one column
to be completed)
R + R
Line/Line
Polarity
(M)
(M)
(M)
(M)
()
Maximum
measured earth
fault loop
impedance,
()
Original
RCD operating
times
at I
(ms)
(if applicable)
Test
button
operation
(ms)
()
at 5I
30
31
32
33
34
35
36
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
04/12/2015
Page 10 of
Name:
(CAPITALS)
DAVID PATERSON
IPN4/0345428
15
CIRCUIT DETAILS
Location of
distribution board:
Distribution
board designation:
LP3/2
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Type: 88
BS(EN)
N/A
mA
Operating
current, I
(mm)
(mm)
(s)
(A)
(kA)
(mA)
Lights - row 1
B/D
1.5
COND
0.4
3871
10
N/A
1.75
Lights - row 2
B/D
1.5
COND
0.4
3871
10
N/A
1.75
Lights - row 3
B/D
1.5
COND
0.4
3871
10
N/A
1.75
Lights - row 4
B/D
1.5
COND
0.4
3871
10
N/A
1.75
Lights - toilets
B/D
1.5
COND
0.4
3871
10
N/A
1.75
A/D
13
2.5
2.5
0.4
3871
32
N/A
0.55
A/D
16
2.5
2.5
0.4
3871
32
N/A
0.55
Hand driers
A/D
2.5
2.5
0.4
3871
32
N/A
0.55
A/D
2.5
0.4
3871
16
N/A
1.09
10
A/D
B/C
2.5
1.5
0.4
3871
32
N/A
0.55
11
B/C
2.5
1.5
0.4
3871
16
N/A
1.09
12
2.5
1.5
0.4
3871
32
N/A
0.55
13
B/D
2.5
1.5
0.4
3871
32
N/A
0.55
14
Kitchen power
A/D
B/C
2.5
2.5
0.4
3871
32
N/A
0.55
15
A/D
B/C
2.5
1.5
0.4
3871
20
N/A
0.87
16
ADT supply
A/D
B/C
1.5
0.4
3871
10
N/A
1.75
17
Spare
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
18
Spare
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Reference
method
Short-circuit
capacity
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 63
Nominal 230
voltage:
Maximum
permitted by BS 7671
()
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit
Thermoplastic/
SWA cables
Thermosetting/
SWA cables
Mineralinsulated
cables
Page 11 of
15
Original
IPN4/0345428
Yes
At I
N/A
ms
At 5I
N/A
ms
N/A
Circuit number
and line
I 4.1
*
Operating times
of associated
RCD (if any)
kA
RCD
Insulation
resistance
Multi P138
function
Continuity
Other
Circuit impedances
()
Ring final circuits only
(measured end to end)
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
Original
RCD operating
times
at I
(if applicable)
Test
button
operation
()
at 5I
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
(ms)
(ms)
N/A
N/A
N/A
0.21
N/A
N/A
LIM
>299
>299
0.68
N/A
N/A
N/A
N/A
N/A
0.30
N/A
N/A
LIM
>299
>299
0.35
N/A
N/A
0.59
0.60
0.16
0.18
N/A
N/A
>299
>299
>299
0.21
N/A
N/A
0.48
0.49
0.76
0.36
N/A
N/A
>299
>299
>299
0.43
N/A
N/A
N/A
N/A
N/A
0.13
N/A
N/A
>299
>299
>299
0.18
N/A
N/A
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
04/12/2015
Page 12 of
Name:
(CAPITALS)
DAVID PATERSON
IPN4/0345428
15
CIRCUIT DETAILS
Location of
distribution board:
Distribution
board designation:
LP4/2
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
MCC4/second floor LP
Type: 88
BS(EN)
N/A
mA
Operating
current, I
(mm)
(mm)
(s)
(A)
(kA)
(mA)
Lighting Row 1
B/D
1.5
cond
0.4
3871 MCB
10
N/A
1.75
B/D
1.5
cond
0.4
3871 MCB
10
N/A
1.75
B/D
1.5
cond
0.4
3871 MCB
10
N/A
1.75
Lighting Row 4
B/D
1.5
cond
0.4
3871 MCB
10
N/A
1.75
Lighting Toilets
B/D
1.5
cond
0.4
3871 MCB
10
N/A
1.75
Power (windows)
B/D
2.5
2.5
0.4
3871 MCB
32
N/A
0.55
Power Wall
B/D
15
2.5
2.5
0.4
3871 MCB
32
N/A
0.55
Power Handryers
B/D
2.5
2.5
0.4
3871 MCB
32
N/A
0.55
B/D
2.5
2.5
0.4
3871 MCB
16
N/A
1.09
10
B/D
2.5
2.5
0.4
3871 MCB
16
N/A
1.09
11
B/D
cond
0.4
3871 MCB
32
N/A
0.55
12
A/D
B/C
2.5
1.5
0.4
3871 MCB
32
N/A
0.55
13
A/D
B/C
2.5
1.5
0.4
3871 MCB
16
N/A
1.09
14
3 x handryers/bell
A/D
B/C
2.5
1.5
0.4
3871 MCB
32
N/A
0.55
15
Spare
16
Spare
17
Spare
18
Spare
19
Spare
20
Spare
21
Spare
22
Spare
23
Spare
24
Spare
Page 13 of
15
Reference
method
Short-circuit
capacity
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 100
Nominal 230
voltage:
Maximum
permitted by BS 7671
()
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit
Thermoplastic/
SWA cables
Thermosetting/
SWA cables
Mineralinsulated
cables
Original
IPN4/0345428
Yes
At I
N/A
ms
At 5I
N/A
ms
N/A
Circuit number
and line
I 2.7
*
Operating times
of associated
RCD (if any)
kA
RCD
Insulation
resistance
Multi P138
function
Continuity
Other
Circuit impedances
()
Ring final circuits only
(measured end to end)
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
Original
RCD operating
times
at I
(if applicable)
Test
button
operation
()
at 5I
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
(ms)
(ms)
N/A
N/A
N/A
0.94
N/A
N/A
LIM
>299
LIM
0.90
N/A
N/A
N/A
N/A
N/A
0.38
N/A
N/A
LIM
>299
LIM
0.42
N/A
N/A
0.76
0.75
0.41
0.30
N/A
N/A
>299
>299
>299
0.33
N/A
N/A
0.50
0.51
0.85
0.34
N/A
N/A
>299
>299
>299
0.35
N/A
N/A
0.36
0.36
0.58
0.25
N/A
N/A
>299
>299
>299
0.29
N/A
N/A
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
04/12/2015
Page 14 of
Name:
(CAPITALS)
DAVID PATERSON
IPN4/0345428
15
Item No
Code
22
Unit 3 second floor - LP3/2 iCPCs order in Dbs do not correlate with MCBs
C3
23
Unit 3 first floor - some small trunking covers missing on column dados
C3
24
Unit 3 first floor - socket outlet incorrectly installed into column dado trunking
C3
Additional Pages?
No
Yes
Specify page
One of the following codes, as appropriate, has been allocated to each of the
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action:
Code C1
Code C2
Code C3
Code FI
22,23,24,
Please see the notes for recipient for guidance regarding the Classification codes.