ELECTRICAL INSTALLATION
CONDITION REPORT

Contractor's Reference Number

(To the person ordering the work)

IPN4/0345428

Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor or
Conforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX

A. DETAILS OF THE CLIENT


Seiko (UK) Ltd

Address:

SC House
Vanwall Road
Maidenhead
Berkshire

Original

Client:

Postcode: SL6 4UW

B. PURPOSE OF THE REPORT


Purpose for which
this report is required:

This report must be used only for reporting on the condition of an existing installation.

Health & Safety/Insurance purposes


04.12.2015

Date(s) on which inspection and testing were carried out:

C. DETAILS OF THE INSTALLATION


Occupier

Seiko (UK) Ltd

Estimated age of the


electrical installation:
Date of previous
inspection:

Address

SC House
Vanwall Road
Maidenhead
Berkshire

of premises:
Evidence of alterations
years Description
35
Commercial
domestic, commercial,
or additions
industrial, other
(Please state)
Electrical Installation Certificate No or previous
04/04/2011
Periodic Inspection or Condition Report No:

Records of installation available:

Postcode: SL6 4UW

If yes,
estimated
age

35

years

IPN2/0097869

Matthew Sloane

Records held by:

D. EXTENT OF THE INSTALLATION AND LIMITATIONS ON THE INSPECTION AND TESTING


Extent of the electrical installation covered by this report:
100% visual inspection, 30% testing of submain/final circuits of Unit no. 3, 1st and 2nd floors.

Agreed limitations (including the reasons), if any, on the inspection and testing:
Limitation of full insulation resistance tests to lighting circuits due to control gear etc. being connected. Limitation of testing main supply as the whole supply was unable to be switch off.

Agreed with: Matthew Sloane


Operational limitations including the reasons (see page No.

None

The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduits
concealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unless
specifically agreed between the client and inspector prior to the inspection.

E. SUMMARY OF THE CONDITION OF THE INSTALLATION


General condition of the installation (in terms of electrical safety):
General condition of the installation is good apart from observations noted.

Summary of the condition of the installation continued on additional pages?


Overall assessment
of the installation:

SATISFACTORY / UNSATISFACTORY

No

Yes

Specify page No(s):

An Unsatisfactory assessment indicates that dangerous (CODE C1) and/or potentially


dangerous (CODE C2) conditions have been identified, or that Further investigation without
delay (FI) is required

This report should have been reviewed and confirmed by the registered Qualified Supervisor
of the Approved Contractor responsible for issuing it. (See declaration on page 2)
This report is based on the model forms shown in Appendix 6 of BS7671
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

Page 1 of

Please see the 'Notes for Recipients'

15

This certificate is not valid if the serial


number has been defaced or altered

ELECTRICAL INSTALLATION
CONDITION REPORT
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety.
or
The following observations and recommendations for
N/A
are made

Code

Unit 3, 2nd floor - kitchen socket outlets - no RCD

C3

Unit 3, 2nd floor - office socket outlets - no RCD

C3

Unit 3, 2nd floor - multiple circuits in ways 1 and 4 LP3/2

C3

Unit 3, 2nd floor - ladies toilet FCU - carrier missing

C3

Unit 3, 2nd floor - CPC's order in DB does not match MCB order

C3

Unit 3, 2nd floor - DB LP3/2 - schedule inaccurate

C3

Unit 3, 1st floor - small trunking lid missing from column dado trunking

C3

Unit 3, 1st floor - socket outlet incorrectly installed into column dado trunking

C3

Unit 3, 1st floor - office socket outlets - no RCD

C3

10

Unit 3, 1st floor - DB1 - schedule inaccurate

C3

11

Unit 4, 2nd floor - multiple circuits in way 10 LP4/2

C3

12

Unit 4, 2nd floor - office socket outlets - no RCD

C3

13

Unit 4, 2nd floor - DB LP4/2 - schedule inaccurate

C3

14

Unit 4, 2nd floor - kitchen socket outlets - no RCD

C3

15

DB1 circuit 24 - sockets x 2 on right in comms room pulling out of plasterboard wall

C3

16

Trunking end caps missing in comms room. Singles accessible

C3

17

Earth cable not connected and left on floor in comms room

C3

18

Unit 3 second floor socket outlets - no RCD protection

C3

19

Unit 3 second floor multiple circuits in CPPS - LP3/2 ways 1 & 4

C3

20

Unit 3 second floor ladies toilet - FCU carrier missing

C3

21

Unit 3 second floor - LP3/2 - board schedule incomplete/incorrect

C3

Additional Pages?

No

Yes

Specify page

9
Immediate remedial action
required for items:

One of the following codes, as appropriate, has been allocated to each of the
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action:
Code C1
Code C2
Code C3
Code FI

Original

Item No

Urgent remedial action


required for items:

"Danger Present". Risk of injury. Immediate remedial action required.


"Potentially dangerous". Urgent remedial action required.
"Improvement recommended".
"Further investigation required without delay".

Further investigation required


without delay for items:
Improvement
recommended for items:

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16,

Please see the notes for recipient for guidance regarding the Classification codes.

G. DECLARATION
I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of which
are described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information
in this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electrical
ins t a llat io n t ak in g int o a c c o u nt t he s t at e d e x t e n t o f t he ins t a lla tio n an d t h e lim it a t io n s o f t he ins p e c t ion an d t e s t in g ( s e e D ).
I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is
SATISFACTORY / UNSATISFACTORY*

(see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).

*An Unsatisfactory assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigation
without delay (FI) is required.
INSPECTION, TESTING AND ASSESSMENT BY:
REPORT REVIEWED AND CONFIRMED BY:
Signature
Name
(CAPITALS)

Signature
DAVID PATERSON

Position

Approved Electrician

Date:

04/12/2015

Name
(CAPITALS)

ANDY COLLINS
(Registered Qualified Supervisor for the Approved Contractor at J)

Date:

04/12/2015
Page 2 of

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

15

Please see the 'Guidance for Recipients on the


classification codes' in the 'Notes for Recipients'

This certificate is not valid if the serial


number has been defaced or altered

ELECTRICAL INSTALLATION
CONDITION REPORT
H. SCHEDULES AND ADDITIONAL PAGES

Schedule of Circuit Details for the Installation: Page No(s)

7, 9, 11, 13

Additional pages, including additional


source(s) data sheets:

Page No(s)

Schedule of Test Results for the Installation:

Page No(s) 8, 10, 12, 14

Original

Inspection Schedule: Page(s) No 4,5,6

The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.

I. NEXT INSPECTION
I/We recommend that this installation is further
inspected and tested after an interval of not more than

(Enter interval in terms of


years, months or weeks, as appropriate)

5 years

provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any items
which have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigated
respectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon as
practicable (see F).

J. DETAILS OF NICEIC APPROVED CONTRACTOR


Trading Title:

ALP Electrical (Maidenhead) Ltd

Address:

70 St Marks Road
Maidenhead
Berkshire

Telephone number:

01628 633998

Email Address:

alp@alpelectrical.com

Enrolment number:
(Essential information)

Postcode:SL6 6DW

9514

Branch number:
(if applicable)

K. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS


System Type(s)

Nature of Supply Parameters

d.c.

Nominal U
Voltage(s):

400

2 pole

Nominal
frequency, f

50

3 pole

Prospective fault
current, I

7.8

a.c.

TN-S

1-phase
(2 wire)

TN-C-S

Characteristics of Primary Supply


Overcurrent Protective Device(s)

Number and Type of Live Conductors

1-phase
(3 wire)

2-phase
(3 wire)

TN-C

3-phase
(3 wire)

TT

3-phase
(4 wire)

External earth fault


loop impendance,

other

Number of
sources

Other

IT

0.03

230

Hz

Notes:
(1) by enquiry

kA

(2) by enquiry or by
measurement

BS(EN) 88
Type

(3) where more than


one supply, record
the higher or highest
values

(4) by measurement

gG

Rated current

LIM

Short-circuit
80
capacity
Confirmation of
supply polarity

kA
()

L. PARTICULARS OF INSTALLATION AT THE ORIGIN


Means of Earthing

Details of Installation Earth Electrode (where applicable)

Distributor's
facility:

Type:
(eg rod(s),tape(s))

Location:

Electrode
resistance, R:

Installation
earth electrode:

()

Method of
measurement:

Main Switch/Switch-Fuse/Circuit-Breaker/RCD

Earthing and protective bonding conductors


Earthing conductor

Type:
BS(EN)

60947-3

No of
Poles
Primary supply
conductors
material
Primary supply
conductors
csa

4
Copper
LIM

Voltage
rating

600

Rated
current,I

LIM

RCD operating
current, I *

N/A

mA

Rated time
delay*

N/A

ms

RCD operating
time (at I )*

N/A

ms

mm

Conductor
material
Conductor
csa

Copper

Connection/
continuity
verified

70

Main protective bonding conductors

mm
()

Bonding of extraneous-conductive-parts ()

Conductor
material
Conductor
csa

Copper

Water
installation pipes

70

Oil
installation pipes

Connection/
continuity
verified

mm
()

Lightning
protection

Structural
steel

Gas
installation pipes
Other

* (applicable only where an RCD is suitable and is used as a main circuit-breaker)

Page 3 of

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

Please see the 'Notes for Recipients'

15

This certificate is not valid if the serial


number has been defaced or altered

ELECTRICAL INSTALLATION CONDITION REPORT


INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Description

Outcome*

1.0
1.1
1.2
1.3
1.4
1.5
1.6

Condition/adequacy of distributor's/supply intake equipment


Service cable
Service head
Distributor's earthing arrangement(s)
Meter tails - Distributor/ Consumer
Metering equipment
Means of main isolation (where present)

2.0
2.1
2.2

Presence of adequate arrangements for parallel or switched alternative sources


Adequate arrangements where a generating set operates as a switched alternative to the public supply
Adequate arrangements where a generating set operates in parallel with the public supply

N/A
N/A

3.0
3.1

Automatic disconnection of supply


Main earthing and bonding arrangements
Presence and condition of distributor's earthing arrangement
Presence and condition of earth electrode arrangement
Adequacy of earthing conductor size
Adequacy of earthing conductor connections
Accessibility of earthing conductor connections
Adequacy of main protective bonding conductor size(s)
Adequacy of main protective bonding conductor connections
Accessibility of main protective bonding connections
Accessibility and condition of other protective bonding connections
Provision of earthing/bonding labels at all appropriate locations
FELV
Source providing at least simple separation
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises
Reduced low voltage
Adequacy of source
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises

3.2

3.3

4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7

Other methods of protection (where the methods of protection listed below are employed, details should be
provided on separate sheets)
Double insulation
Reinforced insulation
Use of obstacles
Placing out of reach
Non-conducting location
Earth-free local equipotential bonding
Electrical separation for more than one item of equipment

5.0
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13

Distribution equipment
Adequacy of working space/accessibility of equipment
Security of fixing
Condition of insulation of live parts
Adequacy/security of barriers
Condition of enclosure(s) in terms of IP rating
Condition of enclosure(s) in terms of fire rating
Enclosure not damaged/deteriorated so as to impair safety
Presence of main switch(es), linked where required
Operation of main switch(es) (functional check)
Correct identification of circuit protective devices
Adequacy of protective devices for prospective fault current
RCD(s) provided for fault protection - includes RCBOs
RCD(s) provided for additional protection - includes RCBOs

* All Outcome boxes must be completed


''
indicates Acceptable condition
'LIM' indicates a Limitation
'N/A' indicates Not applicable

Unacceptable condition state C1 or C2


Improvement recommended state C3
Further investigation required without delay
state FI
(to determine whether danger or potential danger exists)

Location reference

Original

Item

N/A

N/A
N/A
N/A
N/A

N/A
N/A
N/A
N/A
N/A
N/A
N/A

C3

N/A
C3

Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

Page 4 of

15

This certificate is not valid if the serial


number has been defaced or altered

ELECTRICAL INSTALLATION CONDITION REPORT


INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
5.14
5.15
5.16
5.17
5.18
5.19

Description

Outcome*

RCD(s) provided for protection against fire - includes RCBOs


Manual operation of circuit-breakers and RCDs to prove disconnection
Presence of RCD retest notice at or near equipment where required
Presence of diagrams, charts or schedules at or near equipment, where required
Presence of non-standard (mixed) cable colour warning notice at or near equipment where required
Presence of alternative/additional supply arrangement warning notice(s) at or near equipment where required

5.20 Presence of replacement next inspection recommendation label


5.21 Presence of other required labelling (specify)
5.22 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable thermal damage,
arcing or overheating)
5.23 Single-pole switching or protective devices in line conductors only
5.24 Protection against mechanical damage where cables enter equipment
5.25 Protection against electromagnetic effects where cables enter metallic enclosures
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
6.13
6.14

Distribution/final circuits
Identification of conductors
Cables correctly supported throughout their length
Condition of insulation of live parts
Non-sheathed cables protected by enclosure in conduit, ducting or trunking
Suitability of containment systems for continued use (including flexible conduit)
Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report)
Confirmation of indication that SPD(s) are functional
Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and
are tight and secure
Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration
Adequacy of cables for current-carrying capacity with regard to the type and nature of installation
Adequacy of protective devices; type and rated current for fault protection
Presence and adequacy of circuit protective conductors
Co-ordination between conductors and overload protective devices
Cable installation methods/practices appropriate to the type and nature of installation and external influences

6.15 Cables where exposed to direct sunlight, of a suitable type


6.16 Cables installed under floors, above ceilings, in walls / partitions, adequately protected against damage
installed in prescribed zones (see Section D. Extent and limitations)
incorporating earthed armour or sheath, or installed within earthed wiring system, or otherwise protected against
mechanical damage by nails, screws and the like (see Section D. Extent and limitations)
6.17 Provision of additional protection by 30 mA RCD
for mobile equipment not exceeding a rating of 32 A for use outdoors
for all socket-outlets of rating 20 A or less, unless exempt
for cables installed in walls / partitions at a depth of less than 50 mm
for cables installed in walls / partitions containing metal parts regardless of depth
6.18 Provision of fire barriers, sealing arrangements and protection against thermal effects
6.19 Band II cables segregated/separated from Band I cables
6.20 Cables segregated/separated from non-electrical services
6.21 Termination of cables at enclosures (identify numbers and locations of items inspected in Section D)
Connections under no undue strain
No basic insulation of a conductor visible outside an enclosure
Connections of live conductors adequately enclosed
Adequacy of connection at point of entry to enclosure (gland, bush or similar)
6.22 General condition of wiring systems
6.23 Temperature rating of cable insulation
6.24 Condition of accessories including socket-outlets, switches and joint boxes
6.25 Suitability of accessories for external influences
6.26 Single-pole switching or protective devices in line conductors only
6.27 Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify /record
numbers and locations of items inspected

* All Outcome boxes must be completed


''
indicates Acceptable condition
'LIM' indicates a Limitation
'N/A' indicates Not applicable

Unacceptable condition state C1 or C2


Improvement recommended state C3
Further investigation required without delay
state FI
(to determine whether danger or potential danger exists)

Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

Location reference

N/A

C3

Original

Item

(To the person ordering the work)

IPN4/0345428

N/A

N/A

C3
C3

C3

N/A

N/A
C3
C3
C3

N/A

C3
N/A

Page 5 of

15

This certificate is not valid if the serial


number has been defaced or altered

ELECTRICAL INSTALLATION CONDITION REPORT


INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
7.0
7.1

7.2

7.3

7.4

8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.7

9.0
9.1

9.2
9.3
9.4
9.5
9.6
9.7
9.8

Description

Outcome*

Isolation and switching


Isolators
presence and condition of appropriate devices
acceptable location (state if local or remote)
capable of being secured in the OFF position
correct operation verified
clearly identified by position and/or durable marking(s)
Warning label posted in situations where live parts cannot be isolated by the operation of a single device
Switching off for mechanical maintenance
presence and condition of appropriate devices
acceptable location
capable of being secured in the OFF position
correct operation verified
clearly identified by position and/or durable marking(s)
Emergency switching/stopping
presence and condition of appropriate devices
readily accessible for operation where danger might occur
correct operation verified
clearly identified by position and/or durable marking(s)
Functional switching
presence and condition of appropriate devices
correct operation verified

N/A
N/A
N/A
N/A

Current-using equipment (permanently connected)


Condition of equipment in terms of IP rating
Equipment does not constitute a fire hazard
Enclosure not damaged/deteriorated so as to impair safety
Suitability for the environment and external influences
Security of fixing
Cable entry holes in ceiling above luminaires, sized or sealed so as to restrict the spread of fire (indicate extent of
sampling in Section D of report)
Recessed luminaires (e.g. downlighters)
correct type of lamps fitted
installed to minimise build-up of heat by use of "fire rated" fittings, insulation displacement box or similar
no signs of overheating to surrounding building fabric
no signs of overheating to conductors/terminations

N/A
N/A
N/A
N/A

Location(s) containing a bath or shower


Additional protection by RCD not exceeding 30 mA
for low voltage circuits serving the location
for low voltage circuits passing through Zone 1 and Zone 2 not serving the location
Where used as a protective measure, requirements for SELV or PELV are met
Shaver sockets comply with BS EN 61558-2-5 or BS 3535
Presence of supplementary bonding conductors unless not required by BS 7671: 2008
Low voltage (e.g. 230 volts) socket-outlets sited at least 3 m from zone 1
Suitability of equipment for external influences for installed location in terms of IP rating
Suitability of equipment for installation in a particular zone
Suitability of current-using equipment for a particular position within the location

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

10.0 Other special installations or locations


List special locations present, if any. List the results of particular inspections applied (a separate page is required for
each location).

* All Outcome boxes must be completed


''
indicates Acceptable condition
'LIM' indicates a Limitation
'N/A' indicates Not applicable

Unacceptable condition state C1 or C2


Improvement recommended state C3
Further investigation required without delay
state FI
(to determine whether danger or potential danger exists)

Outcome
Provide additional comment where appropriate on
attached numbered sheets. C1, C2, C3 and FI coded
items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

Location reference

Original

Item

(To the person ordering the work)

IPN4/0345428

N/A
N/A
N/A
N/A
N/A
N/A
Page 6 of

15

This certificate is not valid if the serial


number has been defaced or altered

CIRCUIT DETAILS

Location of
distribution board:

Unit 3, 1st floor offices

Distribution
board designation:

DB1

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Supply to distribution
board is from:

No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:

Unit 3/MCC LP first floor

Overcurrent protective device for the distribution circuit:

Type: 88
BS(EN)

Overcurrent protective devices

N/A

mA

Operating
current, I

(mm)

(mm)

(s)

(A)

(kA)

(mA)

Lights - toilets/meeting room

B/D

10

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - comms room

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - meeting room

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - kitchen/row 1

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - row 2

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - row 3

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - row 4

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - row 5

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

Lights - row 6

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

10

Lights - boardroom

B/D

1.5

COND

0.4

60898

10

10

N/A

3.49

11

Sockets

B/D

2.5

COND

0.4

60898

32

10

N/A

1.10

12

Sockets - office dado

B/D

2.5

COND

0.4

60898

32

10

N/A

1.10

13

Columns + 8 floor boxes

B/D

36

2.5

COND

0.4

60898

32

10

N/A

1.10

14

Column sockets

B/D

2.5

COND

0.4

60898

32

10

N/A

1.10

15

Sockets under windows

B/D

26

2.5

COND

0.4

60898

32

10

N/A

1.10

16

Toilet hand driers

B/D

2.5

2.5

0.4

60898

32

10

N/A

1.10

17

Toilet - water heater

B/D

2.5

2.5

0.4

60898

16

10

N/A

2.18

18

Sockets - dado + floor

A/E

B/C

27

2.5

1.5

0.4

60898

32

10

N/A

1.10

19

Sockets - floor

A/E

B/C

2.5

1.5

0.4

60898

32

10

N/A

1.10

20

Sockets - meeting room 1

A/D

B/C

14

2.5

1.5

0.4

60898

32

10

N/A

1.10

21

S/O - kitchen + security panel

A/D

B/C

11

2.5

1.5

0.4

61009

32

30

1.10

22

Kitchen - water heater

A/D

B/C

2.5

60898

40

10

N/A

0.81

23

Uplighters

A/D

B/C

1.5

0.4

60898

10

10

N/A

3.49

24

Comms room sockets

A/D

B/C

2.5

1.5

0.4

60898

32

10

N/A

1.10

25

AC wall unit

A/D

B/C

2.5

1.5

0.4

60898

10

N/A

5.82

26

AC condenser - roof

G/D

B/C

0.4

60898

16

10

N/A

2.18

27

Commando sockets - comms room

A/D

B/A

2.5

1.5

0.4

60898

32

10

N/A

1.10

28

New sockets - phone switch

A/D

B/C

2.5

1.5

0.4

60898

29

Spare

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Reference
method

Short-circuit
capacity

RCD

Rating

BS (EN)

Type

Circuit
conductors: csa
Live
cpc

Max. disconnection
time permitted
by BS 7671

Number of
points served

Circuit number
and line

Type of wiring
(see code below)

Circuit designation

Rating: 100

Nominal 230
voltage:

Maximum
permitted by BS 7671

TO BE COMPLETED IN EVERY CASE

()

32

10

N/A

1.10

N/A

N/A

N/A

N/A

N/A

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See Table 4A2 of Appendix 4 of BS 7671

Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit

CODES FOR TYPE OF WIRING


F
G

Thermoplastic Thermoplastic Thermoplastic


cables in non
cables in
cables in non
metallic conduit metallic trunking metallic trunking

Thermoplastic/
SWA cables

Thermosetting/
SWA cables

O (Other - please state)

Mineralinsulated
cables

Page 7 of

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

See next page for


Schedule of Test Results

15

Original

SCHEDULE OF CIRCUIT DETAILS


FOR THE PRIMARY DISTRIBUTION BOARD

(To the person ordering the work)

IPN4/0345428

This certificate is not valid if the serial


number has been defaced or altered

SCHEDULE OF TEST RESULTS


FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION

Test instruments (serial numbers) used:

Yes

Confirmation of supply polarity

* See note below


*0.04

At I

N/A

ms

At 5I

N/A

ms

Phase sequence confirmed (where appropriate)

N/A

Circuit number
and line

I 5.7
*

Operating times
of associated
RCD (if any)

kA

Earth fault loop


impedance

RCD

Insulation
resistance

Multi P138
function

Continuity

Other

Circuit impedances
()
Ring final circuits only
(measured end to end)

Insulation resistance
All circuits
(At least one column
to be completed)

Line/Line

Polarity

Line/Neutral Line/Earth Neutral/Earth

Maximum
measured earth
fault loop
impedance,

Original

Characteristics at this distribution board

RCD operating
times
at I

(if applicable)

Test
button
operation

()

at 5I

r
(Line)

r
(Neutral)

r
(cpc)

R + R

(M)

(M)

(M)

(M)

()

()

(ms)

(ms)

N/A

N/A

N/A

0.36

N/A

N/A

LIM

>299

LIM

0.38

N/A

N/A

N/A

N/A

N/A

0.91

N/A

N/A

LIM

>299

LIM

0.94

N/A

N/A

N/A

N/A

N/A

0.58

N/A

N/A

LIM

>299

LIM

0.76

N/A

N/A

2
3
4
5
6
7
8
9
10

N/A

N/A

N/A

0.94

N/A

N/A

LIM

>299

LIM

0.89

N/A

N/A

11

0.58

0.57

LIM

0.05

N/A

N/A

>299

>299

>299

0.09

N/A

N/A

1.86

1.88

LIM

0.98

N/A

N/A

>299

>299

>299

1.01

N/A

N/A

16

0.29

0.28

0.26

0.05

N/A

N/A

>299

>299

>299

0.09

N/A

N/A

17

N/A

N/A

N/A

0.06

N/A

N/A

>299

>299

>299

0.11

N/A

N/A

0.72

0.72

1.04

0.48

N/A

N/A

>299

>299

>299

0.54

N/A

N/A

N/A

N/A

N/A

0.08

N/A

N/A

>299

>299

>299

0.13

N/A

N/A

1.07

1.08

1.17

0.26

N/A

N/A

>199

>199

>199

0.30

N/A

N/A

27

0.97

0.97

1.10

0.18

N/A

N/A

>199

>199

>199

0.22

N/A

N/A

28

0.98

0.98

1.10

0.20

N/A

N/A

>199

>199

>199

0.24

N/A

N/A

12
13
14
15

18
19
20
21
22
23
24
25
26

29

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY

Signature:

Position:

Approved Electrician

Date of
testing:

04/12/2015

Page 8 of
Name:
(CAPITALS)

DAVID PATERSON

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

15

See previous page for


Schedule of Circuit Details

This certificate is not valid if the serial


number has been defaced or altered

CIRCUIT DETAILS

Location of
distribution board:

Unit 3, 1st floor offices

Distribution
board designation:

DB1

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Supply to distribution
board is from:

No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:

Unit 3/MCC LP first floor

Overcurrent protective device for the distribution circuit:

Type: 88
BS(EN)

Overcurrent protective devices

N/A

mA

Short-circuit
capacity

Operating
current, I

RCD

Rating

BS (EN)

Type

Circuit
conductors: csa
Live
cpc

Max. disconnection
time permitted
by BS 7671

Number of
points served

Reference
method

Circuit number
and line

Type of wiring
(see code below)

Circuit designation

Rating: 100

Nominal 230
voltage:

Maximum
permitted by BS 7671

TO BE COMPLETED IN EVERY CASE

(A)

(kA)

(mA)

16

10

N/A

2.18

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

(mm)

(mm)

(s)

30

Aqua leak/high temperature alarm

A/D

B/C

2.5

0.4

60898

31

Spare

N/A

N/A

N/A

N/A

N/A

N/A

32

Spare

N/A

N/A

N/A

N/A

N/A

33

Spare

N/A

N/A

N/A

N/A

34

Spare

N/A

N/A

N/A

N/A

35

Spare

N/A

N/A

N/A

36

Spare

N/A

N/A

N/A

()

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See Table 4A2 of Appendix 4 of BS 7671

Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit

CODES FOR TYPE OF WIRING


F
G

Thermoplastic Thermoplastic Thermoplastic


cables in non
cables in
cables in non
metallic conduit metallic trunking metallic trunking

Thermoplastic/
SWA cables

Thermosetting/
SWA cables

O (Other - please state)

Mineralinsulated
cables

Page 9 of

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

See next page for


Schedule of Test Results

15

Original

SCHEDULE OF CIRCUIT DETAILS


FOR THE PRIMARY DISTRIBUTION BOARD

(To the person ordering the work)

IPN4/0345428

This certificate is not valid if the serial


number has been defaced or altered

SCHEDULE OF TEST RESULTS


FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION

Test instruments (serial numbers) used:

Yes

Confirmation of supply polarity

* See note below


*0.04

At I

N/A

ms

At 5I

N/A

ms

Phase sequence confirmed (where appropriate)

N/A

I 5.7
*

Circuit number
and line

Operating times
of associated
RCD (if any)

kA

Earth fault loop


impedance

RCD

Insulation
resistance

Multi P138
function

Continuity

Other

Circuit impedances
()
Ring final circuits only
(measured end to end)
r
(Line)

r
(Neutral)

r
(cpc)

Insulation resistance
All circuits
(At least one column
to be completed)

R + R

Line/Line

Polarity

Line/Neutral Line/Earth Neutral/Earth

(M)

(M)

(M)

(M)

()

Maximum
measured earth
fault loop
impedance,

()

Original

Characteristics at this distribution board

RCD operating
times
at I

(ms)

(if applicable)

Test
button
operation

(ms)

()

at 5I

30
31
32
33
34
35
36

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY

Signature:

Position:

Approved Electrician

Date of
testing:

04/12/2015

Page 10 of
Name:
(CAPITALS)

DAVID PATERSON

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

15

See previous page for


Schedule of Circuit Details

This certificate is not valid if the serial


number has been defaced or altered

CIRCUIT DETAILS

Location of
distribution board:

Unit 3 - 2nd floor kitchen

Distribution
board designation:

LP3/2

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Supply to distribution
board is from:

No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:

Unit 3/MCC LP Second Floor

Overcurrent protective device for the distribution circuit:

Type: 88
BS(EN)

Overcurrent protective devices

N/A

mA

Operating
current, I

(mm)

(mm)

(s)

(A)

(kA)

(mA)

Lights - row 1

B/D

1.5

COND

0.4

3871

10

N/A

1.75

Lights - row 2

B/D

1.5

COND

0.4

3871

10

N/A

1.75

Lights - row 3

B/D

1.5

COND

0.4

3871

10

N/A

1.75

Lights - row 4

B/D

1.5

COND

0.4

3871

10

N/A

1.75

Lights - toilets

B/D

1.5

COND

0.4

3871

10

N/A

1.75

Ring main by window

A/D

13

2.5

2.5

0.4

3871

32

N/A

0.55

Ring main by back wall

A/D

16

2.5

2.5

0.4

3871

32

N/A

0.55

Hand driers

A/D

2.5

2.5

0.4

3871

32

N/A

0.55

Water heater - toilets

A/D

2.5

0.4

3871

16

N/A

1.09

10

Ring - columns and partitions

A/D

B/C

2.5

1.5

0.4

3871

32

N/A

0.55

11

Vending machine S/O

B/C

2.5

1.5

0.4

3871

16

N/A

1.09

12

Demo room - floor box

2.5

1.5

0.4

3871

32

N/A

0.55

13

Comm room sockets

B/D

2.5

1.5

0.4

3871

32

N/A

0.55

14

Kitchen power

A/D

B/C

2.5

2.5

0.4

3871

32

N/A

0.55

15

Kitchen water heater

A/D

B/C

2.5

1.5

0.4

3871

20

N/A

0.87

16

ADT supply

A/D

B/C

1.5

0.4

3871

10

N/A

1.75

17

Spare

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

18

Spare

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Reference
method

Short-circuit
capacity

RCD

Rating

BS (EN)

Type

Circuit
conductors: csa
Live
cpc

Max. disconnection
time permitted
by BS 7671

Number of
points served

Circuit number
and line

Type of wiring
(see code below)

Circuit designation

Rating: 63

Nominal 230
voltage:

Maximum
permitted by BS 7671

TO BE COMPLETED IN EVERY CASE

()

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See Table 4A2 of Appendix 4 of BS 7671

Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit

CODES FOR TYPE OF WIRING


F
G

Thermoplastic Thermoplastic Thermoplastic


cables in non
cables in
cables in non
metallic conduit metallic trunking metallic trunking

Thermoplastic/
SWA cables

Thermosetting/
SWA cables

O (Other - please state)

Mineralinsulated
cables

Page 11 of

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

See next page for


Schedule of Test Results

15

Original

SCHEDULE OF CIRCUIT DETAILS


FOR THE PRIMARY DISTRIBUTION BOARD

(To the person ordering the work)

IPN4/0345428

This certificate is not valid if the serial


number has been defaced or altered

SCHEDULE OF TEST RESULTS


FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION

Test instruments (serial numbers) used:

Yes

Confirmation of supply polarity

* See note below


*0.06

At I

N/A

ms

At 5I

N/A

ms

Phase sequence confirmed (where appropriate)

N/A

Circuit number
and line

I 4.1
*

Operating times
of associated
RCD (if any)

kA

Earth fault loop


impedance

RCD

Insulation
resistance

Multi P138
function

Continuity

Other

Circuit impedances
()
Ring final circuits only
(measured end to end)

Insulation resistance
All circuits
(At least one column
to be completed)

Line/Line

Polarity

Line/Neutral Line/Earth Neutral/Earth

Maximum
measured earth
fault loop
impedance,

Original

Characteristics at this distribution board

RCD operating
times
at I

(if applicable)

Test
button
operation

()

at 5I

r
(Line)

r
(Neutral)

r
(cpc)

R + R

(M)

(M)

(M)

(M)

()

()

(ms)

(ms)

N/A

N/A

N/A

0.21

N/A

N/A

LIM

>299

>299

0.68

N/A

N/A

N/A

N/A

N/A

0.30

N/A

N/A

LIM

>299

>299

0.35

N/A

N/A

0.59

0.60

0.16

0.18

N/A

N/A

>299

>299

>299

0.21

N/A

N/A

0.48

0.49

0.76

0.36

N/A

N/A

>299

>299

>299

0.43

N/A

N/A

N/A

N/A

N/A

0.13

N/A

N/A

>299

>299

>299

0.18

N/A

N/A

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY

Signature:

Position:

Approved Electrician

Date of
testing:

04/12/2015

Page 12 of
Name:
(CAPITALS)

DAVID PATERSON

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

15

See previous page for


Schedule of Circuit Details

This certificate is not valid if the serial


number has been defaced or altered

CIRCUIT DETAILS

Location of
distribution board:

Unit 4, 2nd floor offices

Distribution
board designation:

LP4/2

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Supply to distribution
board is from:

No of
phases: 1
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:

MCC4/second floor LP

Overcurrent protective device for the distribution circuit:

Type: 88
BS(EN)

Overcurrent protective devices

N/A

mA

Operating
current, I

(mm)

(mm)

(s)

(A)

(kA)

(mA)

Lighting Row 1

B/D

1.5

cond

0.4

3871 MCB

10

N/A

1.75

Lighting Row 2 (EM10)

B/D

1.5

cond

0.4

3871 MCB

10

N/A

1.75

Lighting Row 3 (EM 8 & 9)

B/D

1.5

cond

0.4

3871 MCB

10

N/A

1.75

Lighting Row 4

B/D

1.5

cond

0.4

3871 MCB

10

N/A

1.75

Lighting Toilets

B/D

1.5

cond

0.4

3871 MCB

10

N/A

1.75

Power (windows)

B/D

2.5

2.5

0.4

3871 MCB

32

N/A

0.55

Power Wall

B/D

15

2.5

2.5

0.4

3871 MCB

32

N/A

0.55

Power Handryers

B/D

2.5

2.5

0.4

3871 MCB

32

N/A

0.55

Water Heater (Males)

B/D

2.5

2.5

0.4

3871 MCB

16

N/A

1.09

10

H/L Sockets & Water Heater

B/D

2.5

2.5

0.4

3871 MCB

16

N/A

1.09

11

Aircon -Plant room

B/D

cond

0.4

3871 MCB

32

N/A

0.55

12

Sockets in columns & partitions

A/D

B/C

2.5

1.5

0.4

3871 MCB

32

N/A

0.55

13

Aircon - L/H offices

A/D

B/C

2.5

1.5

0.4

3871 MCB

16

N/A

1.09

14

3 x handryers/bell

A/D

B/C

2.5

1.5

0.4

3871 MCB

32

N/A

0.55

15

Spare

16

Spare

17

Spare

18

Spare

19

Spare

20

Spare

21

Spare

22

Spare

23

Spare

24

Spare

Page 13 of

15

Reference
method

Short-circuit
capacity

RCD

Rating

BS (EN)

Type

Circuit
conductors: csa
Live
cpc

Max. disconnection
time permitted
by BS 7671

Number of
points served

Circuit number
and line

Type of wiring
(see code below)

Circuit designation

Rating: 100

Nominal 230
voltage:

Maximum
permitted by BS 7671

TO BE COMPLETED IN EVERY CASE

()

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See Table 4A2 of Appendix 4 of BS 7671

Thermoplastic Thermoplastic
insulated/
cables in
sheathed cables metallic conduit

CODES FOR TYPE OF WIRING


F
G

Thermoplastic Thermoplastic Thermoplastic


cables in non
cables in
cables in non
metallic conduit metallic trunking metallic trunking

Thermoplastic/
SWA cables

Thermosetting/
SWA cables

O (Other - please state)

Mineralinsulated
cables

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

See next page for


Schedule of Test Results

Original

SCHEDULE OF CIRCUIT DETAILS


FOR THE PRIMARY DISTRIBUTION BOARD

(To the person ordering the work)

IPN4/0345428

This certificate is not valid if the serial


number has been defaced or altered

SCHEDULE OF TEST RESULTS


FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION

Test instruments (serial numbers) used:

Yes

Confirmation of supply polarity

* See note below


*0.09

At I

N/A

ms

At 5I

N/A

ms

Phase sequence confirmed (where appropriate)

N/A

Circuit number
and line

I 2.7
*

Operating times
of associated
RCD (if any)

kA

Earth fault loop


impedance

RCD

Insulation
resistance

Multi P138
function

Continuity

Other

Circuit impedances
()
Ring final circuits only
(measured end to end)

Insulation resistance
All circuits
(At least one column
to be completed)

Line/Line

Polarity

Line/Neutral Line/Earth Neutral/Earth

Maximum
measured earth
fault loop
impedance,

Original

Characteristics at this distribution board

RCD operating
times
at I

(if applicable)

Test
button
operation

()

at 5I

r
(Line)

r
(Neutral)

r
(cpc)

R + R

(M)

(M)

(M)

(M)

()

()

(ms)

(ms)

N/A

N/A

N/A

0.94

N/A

N/A

LIM

>299

LIM

0.90

N/A

N/A

N/A

N/A

N/A

0.38

N/A

N/A

LIM

>299

LIM

0.42

N/A

N/A

0.76

0.75

0.41

0.30

N/A

N/A

>299

>299

>299

0.33

N/A

N/A

0.50

0.51

0.85

0.34

N/A

N/A

>299

>299

>299

0.35

N/A

N/A

0.36

0.36

0.58

0.25

N/A

N/A

>299

>299

>299

0.29

N/A

N/A

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY

Signature:

Position:

Approved Electrician

Date of
testing:

04/12/2015

Page 14 of
Name:
(CAPITALS)

DAVID PATERSON

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)

(To the person ordering the work)

IPN4/0345428

15

See previous page for


Schedule of Circuit Details

F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN


Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety.
or
The following observations and recommendations for
N/A
are made

Item No

Code

22

Unit 3 second floor - LP3/2 iCPCs order in Dbs do not correlate with MCBs

C3

23

Unit 3 first floor - some small trunking covers missing on column dados

C3

24

Unit 3 first floor - socket outlet incorrectly installed into column dado trunking

C3

Additional Pages?

No

Yes

Specify page

One of the following codes, as appropriate, has been allocated to each of the
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action:
Code C1
Code C2
Code C3
Code FI

"Danger Present". Risk of injury. Immediate remedial action required.


"Potentially dangerous". Urgent remedial action required.
"Improvement recommended".
"Further investigation required without delay".

Immediate remedial action


required for items:
Urgent remedial action
required for items:
Further investigation
required for items:
Improvement
recommended for items:

22,23,24,

Please see the notes for recipient for guidance regarding the Classification codes.

Please see the 'Guidance for Recipients on the


classification codes' in the 'Notes for Recipients'