QUANTITATIVE
RISK ASSESSMENT
4%
5%
18%
July 2011
2.4

Abo Homos-Nubaria Pipeline QRA

TABLE OF CONTENTS
1
2
3
4

Executive Summary.....................................................................................................3
Introduction..................................................................................................................7
Technical Definitions....................................................................................................8
Project Description.....................................................................................................10
Pipeline Route.................................................................................................................................... 10
Pipeline Design Criteria...................................................................................................................... 10
Valve Room Locations........................................................................................................................ 11
Major Crossings.................................................................................................................................. 11

Design Gas Composition and Flow Rate................................................................................12

5
6
7
8
9
10
11
12
13

Assessment of Risks.................................................................................................13
Methodology..............................................................................................................14
Plan of Work..............................................................................................................16
Operation of the Pipeline...........................................................................................17
Emergency Plan.........................................................................................................18
Weather Data..........................................................................................................19
Release Scenarios..................................................................................................25
Impairment Criteria.................................................................................................28
Flammability Assessment.......................................................................................29

13.1
13.2

14
15
16

Consequence Modelling Input Data.......................................................................31


Sensitivity Analysis.................................................................................................34
Ignited Release Scenario........................................................................................37

16.1
16.2

17

17.1.1
17.1.2
17.1.3

17.2
17.2.1
17.2.2
17.2.3

Hydrocarbon Releases..............................................................................................39
Gaseous Release................................................................................................................. 39
Liquid Release...................................................................................................................... 40
Toxic Gas release................................................................................................................. 41

Fire............................................................................................................................ 41
Flash Fire............................................................................................................................. 43
Unobstructed Jet Fires......................................................................................................... 44
Obstructed Jet Fires............................................................................................................. 45

Release Scenarios..................................................................................................47
Consequence Modelling Results............................................................................49

19.1
19.2
19.3
19.4
19.5
19.6
19.7
19.8

20

Generic Causes of Release.......................................................................................37


Generic Causes of Ignition.........................................................................................37

Typical Fire Consequence Analysis........................................................................39

17.1

18
19

General...................................................................................................................... 29
Process Hydrocarbons...............................................................................................30

70Bar - Full Bore Rupture [32 Inch] - Vertical Release - Gas Dispersion...................51
70Bar - Full Bore Rupture [32 Inch] - Vertical Release - Jet Fire................................52
70Bar - Major Leak [16 Inch] - Vertical Release - Gas Dispersion.............................63
70Bar - Major Leak [16 Inch] - Vertical Release - Jet Fire..........................................64
70Bar - Minor Leak [1 Inch] - Vertical Release - Gas Dispersion...............................65
70Bar - Minor Leak [1 Inch] - Vertical Release - Jet Fire............................................66
70Bar - Depressurization Case [10 Inch Vent at 10 Meter Height].............................67
Explosion Case.......................................................................................................... 68

Likelihood Data.......................................................................................................59

20.1

Process Release........................................................................................................59

Abo Homos-Nubaria Pipeline QRA

20.2

21

21.1
21.2
21.3

22
23
24
25
26

Ignition Probability.....................................................................................................59

Risk Assessment.....................................................................................................60
Risk Assessment Basis..............................................................................................60
Risk Assessment for Buried Underground Pipeline....................................................60
Risk Assessment for Aboveground Pipeline...............................................................60

Risk Evaluation.......................................................................................................61
Risk Reduction Measures (Recommendations).....................................................62
Uncertainty Analysis...............................................................................................63
References..............................................................................................................64
Appendix-1 FRED Simulation Cases for PRS........................................................65

26.2
26.3
26.3.1
26.3.2
26.3.3
26.3.4
26.3.5

26.4
67.4.1
67.4.2
67.4.3
67.4.4
67.4.5

26.5
26.5.1
26.5.2
26.5.3
26.5.4
26.5.5

26.6
26.6.1
26.6.2
26.6.3
26.6.4
26.6.5

26.7
26.7.1
26.7.2
26.7.3

Table of Contents.......................................................................................................65
70Bar - Full Bore Rupture [32 Inch] - Vertical Release...............................................65
Scenario Summary............................................................................................................... 65
Jet Fire................................................................................................................................. 67
Pool Chart............................................................................................................................ 69
Dispersion............................................................................................................................ 70
Warnings.............................................................................................................................. 71

70Bar - Half Bore Rupture [16 Inch] - Vertical Release..............................................72


Scenario Summary............................................................................................................... 72
Jet Fire................................................................................................................................. 74
Pool Chart............................................................................................................................ 76
Dispersion............................................................................................................................ 77
Warnings.............................................................................................................................. 78

70Bar - Minor Leak [1 Inch] - Vertical Release...........................................................79


Scenario Summary............................................................................................................... 79
Jet Fire................................................................................................................................. 81
Pool Chart............................................................................................................................ 83
Dispersion............................................................................................................................ 84
Warnings.............................................................................................................................. 85

70Bar - Depressurization [10 Inch] - Vertical Release................................................86


Scenario Summary............................................................................................................... 86
Jet Fire................................................................................................................................. 88
Pool Chart............................................................................................................................ 90
Dispersion............................................................................................................................ 92
Warnings.............................................................................................................................. 93

Explosion [Confined space].......................................................................................93


Scenario Summary............................................................................................................... 93
Pressure Decay with Distance Chart....................................................................................94
Warnings.............................................................................................................................. 94

Abo Homos-Nubaria Pipeline QRA

1 Executive Summary
Quantitative risk assessment study (QRA) has been performed for the Abo Homos-Nubaria Gas
Pipeline 32" Gas Pipeline for the Egyptian natural Gas Company (GASCO).
The scope of this quantitative risk assessment (QRA) study is to perform consequence
modelling analysis and risk assessment of the overall pipeline, while the pipeline inlet and outlet
facilities are outside the scope of this study.
In order to perform consequence modelling analysis of the potential hazardous scenarios
resulting from loss of containment of the pipeline, some assumptions and design basis have
been proposed.
the pipeline release orientation have been proposed to be a vertical release, which is
considered for buried underground pipeline releasing the entrapped materials in the vertical
direction upwards (represents the actual release scenario). Other release orientations represent
the exaggerated release scenario.
For the pipeline leak scenario, the release rate has been simulated based on 3-hole sizes as
follows:

Full bore rupture (32-inchs);


Half bore rupture (16-inches);
Pin hole leak (1-inch).

The first leak size is a full bore rupture of the pipeline (32 inch leak), which presents a hole
diameter equivalent to the pipeline diameter. This scenario presents the worst case scenario for
maximum release rate in order to represent a catastrophic release scenario.
The second leak size is a half bore rupture of the pipeline (16 inch leak), which presents a hole
diameter equivalent to half the pipeline diameter. This scenario presents the severe case
scenario for a reduced release rate in order to represent a major release scenario.
The third leak size is a one inch hole in the pipeline (1 inch leak), which presents a pin hole in
the pipeline wall or small deformation equivalent to the one inch hole in diameter. This scenario
presents the mild case scenario for a reduced release rate in order to represent a minor release
scenario.
FRED has been selected for the consequence modeling of different types of hazardous
consequences modeling presented as follows:

Jet fires (resulting from immediate ignition).


Gas clouds and Flash fires (resulting from delayed ignition),

Weather conditions have been selected based on wind speed and stability class for the greater
Cairo area detailed weather statistics.

Abo Homos-Nubaria Pipeline QRA

The worst case weather conditions have been selected for consequence modelling represented
by wind speed of 10 m/s and stability class "D" representing prevailing weather conditions, in
order to obtain conservative results.
The gas dispersion distances have been calculated in meters in concentration terms of Lower
Flammability Limits (LFL) and Upper Flammability Limits (UFL) presented by Part Per Million
(PPM) concentrations in order to represent the flammability range of the released gas cloud;
however the extent of damage is presented by LFL only.
The heat radiation from flash fires will not significantly affect humans, equipment or structures
outside the 12.5 (Kw/m2) heat radiation envelopes due to the short duration of flash fires [in
terms of milliseconds].
Since the jet fire is originally a high momentum directed jet release, hence the effects of wind
direction, wind speed or atmospheric stability on the jet flame are minimal.
The jet fire (flame length) and heat radiation distances are measured in meters.
The extent of harmful effects on humans is presented by the distance to the heat radiation
contour of 12.5 (Kw/m2) and the extent of damage for equipment is presented by the flame
length (frustum).
Fire consequence analysis has been described in details in fire consequence effects section,
which details the hazardous effects from different types of fires.
For the purposes of the hazard analysis and consequence modelling, a number of
representative release scenarios and physical impact cases are defined in as per Table below.
Release
Orientation

1.0
Vertical Release
Orientation

Hole Size /
Leak Type
Full Bore
Rupture
(Catastrophic
Failure)
Half Bore
Rupture
(Major Leak)

Pin Hole
(Minor Leak)
2.0
Depressurizatio
n
3.0
Explosion

Table 1.1: Representative Release Cases


Hole Size Press. Hazardous
Case Identification
(Inch)
(Bar)
Scenario
Gas
70Bar - Full Bore Rupture [12 Inch] Dispersion
Vertical Release - Gas Dispersion
32 Inch
70
70Bar - Full Bore Rupture [12 Inch] Jet Fire
Vertical Release - Jet Fire
Gas
70Bar - Half Bore Rupture [6 Inch] Dispersion
Vertical Release - Gas Dispersion
16 Inch
70
70Bar - Half Bore Rupture [6 Inch] Jet Fire
Vertical Release - Jet Fire
Gas
70Bar - Pin Hole leak [1 Inch] Dispersion
Vertical Release - Gas Dispersion
70Bar - Pin Hole leak [1 Inch] 1 Inch
70
Jet Fire
Vertical Release - Jet Fire
70Bar - Pin Hole leak [1 Inch] Jet Fire
Horizontal Release - Jet Fire

Planned
Depressurizatio
n

10 Inch

70

Gas
Dispersion

70Bar - Depressurization [10 Inch] Vertical Release - Gas Dispersion

N/A

N/A

N/A

Explosion

Explosion scenario

Abo Homos-Nubaria Pipeline QRA

Pipeline release generic failure frequencies and ignition probabilities have then been identified
for the detailed quantitative risk assessment (QRA) purposes from E&P Forum, UKOPA and
EGIG.
The failure rate of buried underground pipelines is lower than aboveground pipelines due to the
protection from third parties impacts and adverse atmospheric conditions.
On the other hand, the probability of occurrence of a pipeline full bore leak (catastrophic failure)
is deemed to be much lower than a half bore leak.
Quantitative risk assessment (QRA) has been performed to all types of the modelled hazardous
events (flash fires and jet fires).
The risks have been assessed for the industrial workers and general public representing the two
types of risk namely the "Individual Risk" and "Societal Risk".
From the risk assessment and the international risk acceptance criteria the risk evaluation for
individual and societal risk presented in the following table.
No
1.0
2.0

Table 1.2 Buried Underground Pipeline Orientation Risk Evaluation Summary Table
Risk Type
Calculated Risk
ALARP Limits
Risk Acceptance
Individual Risk
6.60E-08
1.0E-03 to 1.0E-05
Acceptable ()
Societal Risk
6.60E-07
1.0E-04 to 1.0E-06
Acceptable ()

It has been concluded that the risk falls within the Acceptable limits for the individual risk to
workers and public for the pipeline. However, the following measures (recommendations) should
be adhered:

Ensure pipeline design, commissioning, start-up, construction and operation is


complying with code requirements (ASME B31.8 Gas Transmission and Distribution
Piping Systems).

Ensure Signs or markers shall be installed where it is considered necessary to indicate


the presence of a pipeline at road, highway, railroad, and stream crossings. Additional
signs and markers shall be installed along the remainder of the pipeline at locations
where there is a probability of damage or interference (ASME B31.8 requirement).

Signs or markers and the surrounding right-of way shall be maintained so markers can
be easily read and are not obscured (ASME B31.8 requirement).

The signs or markers shall include the words Gas" (or name of gas transported)
Pipeline, the name of the operating company, and the telephone number (including area
code) where the operating company can be contacted (ASME B31.8 requirement).

Ensure Overpressure protection is provided by a device or equipment installed in a gas


piping system that prevents the pressure in the system or part of the system from
exceeding a predetermined value (ASME B31.8 requirement).

Emergency Response plan (ERP) to include means for detection pipeline leak or rupture
also, means for safe and quick isolation of the damaged section of the pipeline.

Abo Homos-Nubaria Pipeline QRA

Finally, uncertainty analysis has been performed in order to verify and ensure that certainty of
the results obtained from the consequence modelling analysis and quantitative risk assessment
are certain and none of the scenarios or input factors have been neglected or underestimated.
Hence, the risk shall be within the acceptable and tolerable limits, if the pipeline is buried
underground and all safe design precautions have been considered and strictly followed in the
design, construction and operation of the Pipeline.

Abo Homos-Nubaria Pipeline QRA

2 Introduction
This report represents the Quantitative risk assessment study (QRA) performed for the Abo
Homos-Nubaria Gas Pipeline 32" Gas Pipeline for the Egyptian natural Gas Company
(GASCO).
The scope of this quantitative risk assessment (QRA) study is to perform consequence
modelling analysis and risk assessment of the overall pipeline, while the pipeline inlet and outlet
facilities are outside the scope of this study.
Objectives:
The primary objective is to perform a quantitative risk assessment to identify the major risk
issues and contributors with a best estimate of the associated levels of risk for the pipeline and
its boundaries and crossings.
In general the work will cover, but not necessarily be limited to, the following:
o

Define data to be provided,

Review key project data,

Perform physical survey of the pipeline route to identify possible hot spots,

Define possible accident scenarios and events,

Conduct a full consequence analysis in relation to gas leaks and fire scenarios,

Perform quantitative risk assessment,

Conduct ALARP risk reduction/mitigation review,

Define possible risk elimination/reduction measures,

Propose residual risk control measures.

Abo Homos-Nubaria Pipeline QRA

3 Technical Definitions
Confinement

A qualitative or quantitative measure of the enclosure or partial enclosure areas


where vapors cloud may be contained.

Congestion

A qualitative or quantitative measure of the physical layout, spacing, and


obstructions within a facility that promote development of a vapor cloud explosion.

EERA

Escape, Evacuation and Rescue Assessment

ESD

Emergency Shut Down

FRA

Fire Risk Assessment

Gas cloud
dispersion

Gas cloud air dilution naturally reduces the concentration to below the LEL or no
longer considered ignitable (typically defined as 50% of the LEL).

Hazard

An inherent physical or chemical characteristic (flammability, toxicity, corrosivity,


stored chemical or mechanical energy) or set of conditions that has the potential for
causing harm to people, property, or the environment.

Individual risk

The risk to a single person inside a particular building. Maximum individual risk is
the risk to the most-exposed person and assumes that the person is exposed.

QRA

Quantitative Risk Assessment

Risk

Relates to the probability of exposure to a hazard, which could result in harm to


personnel, the environment or general public. Risk is a measure of potential for
human injury or economic loss in terms of both the incident likelihood and the
magnitude of the injury or loss.

Risk
assessment

The identification and analysis, either qualitative or quantitative, of the likelihood and
outcome of specific events or scenarios with judgments of probability and
consequences.

Vapor cloud
explosion

An explosion in air of a flammable material cloud

Abo Homos-Nubaria Pipeline QRA

(VCE)

Abo Homos-Nubaria Pipeline QRA

4 Project Description
Pipeline Route
The Abo Homos-Nubaria gas pipeline starts from the outlet of a gas collection unit at Abo Homos, and
extends to the southwest for 400 m. It then turns to the southeast and runs parallel to the ring road to
Basnatawy for 2.5 km, and then extends toward the south, intersecting El-Mahmoudiya canal, CairoAlexandria railway, and Cairo-Alexandria road near the El-Azmaly estate. It follows the eastern side of ElKhadra canal, and then follows the Damanhour canal eastward for 2.5 km until turning south for 1 km to
cross the Abdel Hamid canal and continue along it briefly for 500 m. The pipeline turns southeast and
again follows the Damanhour canal at the east side of the Sharawa estate. The pipeline crosses the road
to Hosh Issa, and then runs parallel to the Khairy drain along the western side for about 15 km, until it
nears a transformer station at El-Nagareen estate. The path crosses the Ferhash canal and continues
eastward alongside it, then turns south with the Abo Shousha canal. It crosses El-Hagar canal and runs
along its southern side for 11.5 km, and then crosses back to the northern side before El-Haddayn estate.
The pipeline passes north of El-Ashraf, then turns south to cross the Nubaria canal and continue along it
for 3 km, then once again turns south, crossing the Alexandria-Embaba railway, and finally reaching the
Nubaria power station.

Pipeline Design Criteria


At the minimum, the pipeline will be built, operated, and maintained to the standards of ASME B31.8,
which dictates the use of good engineering practices for public safety in all conditions and local
regulations as a minimum, along with any additional local regulations. as well as other relevant high
standards for pipeline routing with consideration for nearby settlements.
Settled areas along the pipeline are classified by population density, which is used to determine the
Location Class, as defined in Table 4-1. Location Classes are used to determine the design criteria
appropriate for different sections of the pipeline. They are also used in determining the amount of
surveillance activity to be conducted.

Table 4-1: Determination of Location Class

Generally a zone 200m wide is considered on either side of the route of the pipeline. To include a
maximum number of buildings for human occupancy, the pipeline route is also divided lengthwise into
sections of 1 mile. Within a multiple dwelling unit, each separate dwelling unit is counted as a separate

10

Abo Homos-Nubaria Pipeline QRA


building. However, ASME B31.8 does not provide restrictions on the proximity of a pipeline to a building or
group of buildings, which can lead to pipelines being constructed close to buildings (and vice versa).
The following proximity limits should be applied to all pipeline design and to new buildings developed
close to existing pipelines.

No pipeline operating at a pressure greater than 7 bar must can be within 3m of a


building in residential areas, and 6m desert areas.
Any pipeline closer than 25 m to a normally occupied building should operate at a
pressure that is 40% of the material yield strength or less, and have a wall
thickness of at least 0.375".
Any pipeline closer than 12.5m to a normally occupied building should operate at
a pressure that is 40% of the material yield strength or less, and be laid with
greater than or equal to 0.5" wall thickness.

Wall thickness is also increased at road crossings, and impact protection measures (cast in site or pre cast concrete slab) shall be provided on all pipeline crossings. Warning tape is placed above and below
such impact protection.

Valve Room Locations


Eight (8) valve rooms will be constructed along the pipeline, in the following locations:

valve room (1) at zero km (Abo Homos collection station)


valve room (2) at 7 km
valve room (3) at 10 km
valve room (4) at 24 km
valve room (5) at 43 km
valve room (6) at 54.5 km
valve room (7) at 59.5 km
valve room (8) at 65 km (Nubaria power station)

Major Crossings
There are many crossing that the proposed pipeline route encounters. Some of them will be crossed
using an open trench, but major crossings and waterways will be crossed using the Horizontal Directional
Drilling (HDD) technique. The following crossings will be encountered:

Mahmoudiya Canal 5.3 km


Cairo-Alexandria Agricultural Road and Railway 8.5 km
El-Khadra Canal 9.2 km
Hosh Issa Road 15.8 km
El-Zamarana Canal 23.1 km
Ferhash Road 39.3 km
El-Hagar Canal 43.9 km
Zohor El-omra Canal 54 km
Nubaria Canal 63 km

11

Abo Homos-Nubaria Pipeline QRA

Design Gas Composition and Flow Rate


The main stream of natural gas will come from the national network once the pipeline has been filtered.
The pipeline is designed to transport the gas at a maximum inlet pressure of 70 bar. The compositions of
the gas coming from the national network are indicated in the table below.
Table 4-2: National Network Gas Composition [Reference: GASCO]

Lean Gas

Contaminants
Carbon Dioxide
Nitrogen
Oxygen
Hydrogen
Methane
Ethane
Propane
iso-Butane
n-Butane
iso-Pentane
n-Pentane
n-Hexane
n-Heptane
n-Octane
n-Nonane
Total

Composition
0.150
0.760
0.000
0.000
97.313
1.710
0.040
0.020
0.000
0.000
0.000
0.000
0.000
0.000
0.000
100.000

CO2
N2
O2
H2
CH4
C2H6
C3H8
i-C4.
n-C4.
i-C5
n-C5
n-C6
n-C7
n-C8
n-C9

Rich Gas Composition


3.990
0.050
0.000
0.000
80.224
10.069
3.880
0.570
0.6899
0.2100
0.1200
0.1200
0.0700
0.00
0.000
100.000

Gas delivered will be commercially free of materials and dust or other solid or liquid matter
which may interfere with the operation of lines.

12

Abo Homos-Nubaria Pipeline QRA

5 Assessment of Risks
This part of the study would address the identification, analysis and subsequent assessment of
major hazards associated with the relevant onshore pipeline.
They are categorised, and makes judgement on the tolerability of risks to personnel associated
with these hazards. The international criteria for risk tolerability are used to base such
judgements.
Scenarios that could result in major hazards will be identified and evaluated using Quantified
Risk Assessment QRA. This technique is used to establish the expected frequency of such
incidents occurring on each facility and their consequences.
This section will be linked to the rest of the proposed study in order to tie together the logic of
the arguments and bring the findings into better context. It will encompass:
o

Policy, Standards and Criteria,

The sources of hazards,

Hazardous substances, and their inventories,

Events which are capable to cause major accidents,

Analysis of the consequences and their effects on employees, third parties and the
public,

Evaluation of individual and societal risks, using International Risk Tolerability Criterion,

Measures to prevent, control or minimise likely consequences,

Emergency procedures and emergency systems, derived from consideration of the


above issues.

From these studies, risk reduction measures are identified, and improvements to the hardware
and the management systems are considered.

13

Abo Homos-Nubaria Pipeline QRA

6 Methodology
The proposed QRA methodology is shown in Figure 6.1.

FIGURE 6.1 QRA Risk Assessment Frame-work

14

Abo Homos-Nubaria Pipeline QRA

The QRA Criteria for risk tolerability is shown in Figure 6.2.

FIGURE 6.2 International Gas Criteria for the QRA Risk Tolerability

15

Abo Homos-Nubaria Pipeline QRA

7 Plan of Work
The plan of work includes the following:
o

Review the relevant facilities documentation.

Carry out a physical survey of the pipeline route in order to identify the potential hot spot.

Identify the prevailing weather conditions.

Set the QRA methodology.

Investigate generic and specific release scenarios.

Define the impairment criteria.

Perform flammability assessment.

Select the appropriate consequence modelling software to be used.

Perform sensitivity analysis.

Define ignited release scenarios.

Define the consequence modelling analysis input data.

Perform consequence modelling analysis using the selected modelling software.

Define failure frequencies (frequency assessment).

Perform risk assessment.

Risk evaluation with respect to international risk acceptance criterion.

Investigate risk reduction measures and corrective actions (as applicable).

16

Abo Homos-Nubaria Pipeline QRA

8 Operation of the Pipeline


The pipeline is provided with an automatic shutdown valve (ESDV) at the pipeline start. This
ESDV is included within the inlet station facilities at the pipeline start.
Also, another automatic shutdown valve (ESDV) shall be installed at the pipeline end. This
ESDV shall be included within the receiving station facilities at the pipeline end.
Other inline sectionalizing valves are manual isolation valves installed on different intervals on
the pipeline route in order to minimize leaks and potential failures.
Flow measurements are provided for the pipeline to facilitate flow measurement and leakage
indication.

17

Abo Homos-Nubaria Pipeline QRA

9 Emergency Plan
Emergencies in Stations:
There is an emergency plan for the existing pipelines.
Actions in response to the emergency cases are generally restricted to the isolation of valves,
reporting the incident and follow up with relevant authorities.
Gas Pipeline:
The Company has an emergency booklet that covers the main gas transmission line and
customers.
There is also an emergency room dedicated for such emergencies. Emergencies are prioritised
at different levels, and include the following:
o

Gas leaks (instrumentation and equipment),

Gas explosion,

Natural events to include earthquakes, heavy rain and external events.

Response to these emergencies focus on isolation and reporting for actions.

18

Abo Homos-Nubaria Pipeline QRA

10 Weather Data
The Weather Data relevant to this study consists of a list of weather conditions in the form of
different combinations of wind-speed, temperature, humidity and atmospheric stability. The
weather conditions are an important input into the dispersion calculations and results for a
single set of conditions could give a misleading picture of the hazard potential.
Mete oceanographic data gathered for Greater Cairo over a period of 5 years. This data
included wind speed and direction; air temperature and pressure, as well as current speed,
direction and wave height.
The general climatic conditions at North Cairo are summarised below:
Air Temperature oC:
o Minimum recorded
o Maximum recorded
o Yearly average

- 1.1
52.2
28

Relative humidity %:
o Average daily minimum
o Average daily minimum
o Annual average

82
54
78

The recorded annual wind speeds at Cairo are shown in Table 10.1.
Table 10.1 Wind speeds at Cairo (Knots)
Month

Jan.

Feb.

Mar.

Apr.

May

June

July

Aug.

Sep.

Oct.

Nov.

Dec

Wind
speed

4.7

5.6

6.3

6.2

5.6

5.2

4.4

3.4

3.6

4.0

3.8

4.4

In wind Rose figures the radius = 10%


Average wind speed =

2.44 m/sec.

Wind Direction:
Three permanent high-pressure belts control the wind circulation over Egypt: the Azores, the
Indian subtropical and the South Atlantic subtropical. In addition, there is a permanent lowpressure belt the doldrums which crosses Africa near the equator. Seasonal high and low
pressure systems also alternate over the continental mass, the red sea, the Mediterranean and
the Arabian Peninsula.

19

Abo Homos-Nubaria Pipeline QRA

Table 10.2 Wind Rose for North Cairo

Jan
Feb
Mar
Apr
May
June
July
Aug
Sep
Oct
Nov
Dec

345/
014
5.4
9.9
15.8
15.8
21.3
24.4
26.3
29.1
22.8
19.4
16.6
10.6

015/
044
8.5
14.4
16.3
21.4
24.9
22.2
16.4
16.2
23.9
23.2
17.2
10.8

045/
074
7.4
8.7
9.3
13.3
13.3
8.3
4.8
3.8
8.1
11.4
6.6
6.8

075/
104
3.0
3.6
3.6
4.3
3.0
1.3
0.8
0.8
1.4
2.9
1.9
2.4

105/
134
1.3
1.2
1.4
0.7
0.6
0.1
0.2
0.4
0.2
0.4
0.5
0.8

135/
164
2.7
1.3
1.6
0.6
0.3
0.1
0.0
0.0
0.2
0.4
0.8
1.9

165/
194
13.5
8.0
5.0
1.7
0.7
0.2
0.1
0.0
0.7
1.5
3.3
8.8

195/
224
14.8
12.0
7.5
3.0
1.3
0.7
0.2
0.2
1.2
1.8
5.7
12.0

225/
254
12.6
10.1
6.4
5.0
2.0
1.2
1.2
0.9
0.8
3.0
6.6
8.3

255/
284
8.5
7.1
7.9
7.0
4.3
2.9
3.1
2.6
1.3
3.7
6.3
8.2

285/
314
6.3
6.1
8.2
8.6
7.7
9.3
7.7
6.8
6.3
7.6
7.2
5.9

315/
344
5.8
8.9
10.1
12.5
14.4
20.1
23.4
21.6
15.4
10.5
9.7
8.8

The prevailing winds are quite parallel to or heading towards the Northwest, mostly from west to
north all year, except December and January, when they are from SE. When atmospheric low
pressure is passing quite frequently and fast, the wind direction will change anti-clockwise,
normally during a short period of one to two days. After a low pressure has passed, the wind
returns to the prevailing direction (W-NW). The mean wind speed at Cairo is 2.44 m/sec.
Data on the direction of wind at North Cairo was obtained from the Egyptian Meteorological
Office. Table 10.2 shows the analysis of the 12-months wind distribution data over a period of 10
years. FIGURE 10.1 gives the average wind directions at Cairo throughout the year.

20

Abo Homos-Nubaria Pipeline QRA

Jan

May

Feb

March

June

Sept

July

Oct

April

August

Nov

Dec

FIGURE 10.1 Average wind directions at Cairo


The overall analysis of the wind data at Cairo is given in what is known as the wind rose.
FIGURE 10.2 shows Cairo wind rose, based on data collected during 1992- 2000. Note that
winds blow towards the centre of the rose.

18%

> 22.5 m/sec

20%

20- 22.5

15%

17.5 - 20
15- 17.5

7%

12.5 - 15
10- 12.5

5%

6%
5%
8%

4%
3%
5% 4%

7.5-10

2.4

5- 7.5

2.5- 5
0- 2.5

FIGURE 10.2 the Wind Rose at Cairo

21

Abo Homos-Nubaria Pipeline QRA

Stability Categories:
The two most significant variables, which would affect the dispersion calculations, are: Windspeed and atmospheric stability. The stability class is a measure of the atmospheric turbulence
caused by thermal gradients. Pasquill Stability identifies six main categories, which are shown in
the Table 10.3.
Table 10.3 Pasquill Stability Categories
A
B
C
Very Unstable
Unstable Moderately Unstable

D
Neutral

E
Moderately Stable

F
Stable

Neutral conditions correspond to a vertical temperature gradient of about 1(oC) per 100m.
Cairo weather data for the Geographical area is somewhat limited and do not show seasonal
variations over a long time.
Therefore, the calculations included in this study have considered alternative stabilities for the
average wind speed of 2.4 m/sec.
This was done with reasonable accuracy, since the stability is related to the wind speed, and the
range of stabilities that is observed for a given wind speed is generally small, as shown in the
Table 10.4.
As the range is large for a given wind speed, the calculations have initially considered four
different combinations of wind speeds and stability classes to include the worst possible
conditions.
The calculations have also considered atmospheric temperature (30oC), relative humidity 70%
and surface roughness parameter of 0.1.
Table 10.4 The Relationship between Wind speed and Stability
Wind speed
(m/s)
<2
2-3
3-5
5-6
>6

Day-time
Solar Radiation
strong
medium
slight
A
A-B
B
C
C

A-B
B
B-C
C-D
D

thin
<3/8
E
D
D
D

B
C
C
D
D

Night-time
Cloud Cover
medium
overcast
>3/8
>4/5
D
F
D
E
D
D
D
D
D

At night, the ground is often cooler than the air if the sky is clear, and this gives rise to the most
stable conditions and potentially the greatest effect distances.
FIGURE 10.3 shows the criteria used for the selection of weather parameters used for the
consequences modelling for this study.

22

Abo Homos-Nubaria Pipeline QRA

Is the ground covered


in frost or snow?

Yes

m/s

Check category
against wind speed

0- 6
>7

No
Is it night-time?

Yes

No
Inland
sites

Yes

Is sky overcast?

m/s
<2
2
>3

No
Sky more than half covered

Coastal
sites

Check category
against wind speed

No
Check category
against wind speed

Sky clear?
Wind mainly from
from the sea?

Yes

m/s
<2
2-4
>5

No
Time within 1 hr
before sunset?

Yes

No
Time within 1 hr
after sunrise?

Yes

Sky clear and


wind calm/light?

Yes

No

No
Is sky overcast?

Yes

Check category
against wind speed

No
Summer only

m/s
<3
3- 4
5- 8
>8

A
B
C

0- 4
>5

Select weather type from


Hot

Check category
against wind speed

m/s

Warm

Cool

Check category
against wind speed
m/s

<1
1- 3
4- 7
>7

B
C

23

Check category
against wind speed
m/s
0- 4
>5

C
D

F
E
D
F
E
D

Abo Homos-Nubaria Pipeline QRA

FIGURE 10.3 Determinations of Modified Pasquill Stability Categories


Category D (neutral) is the most probable at inland sites, and appears to occur for up to 80% of
the time at Cairo. To overcome the uncertainty of the accuracy of Cairo weather data results, the
following cases were selected in this analysis to study the effects of normal and extreme
weather conditions at Cairo.
Table 10.5 Sets of weather conditions initially selected for this study:
Set 1
Wind speed
Stability
Wind speed
2 m/s
F
10 m/s

Set 2
Stability
D

The wind speed range between 1 to 5 m/s was considered to be reasonable representation of
typical conditions at Cairo. This would overcome some of the uncertainty of the meteorological
data provided by the meteorological office. Wind speeds in excess of 8 m/s are likely to disperse
the cloud over long distances to well below LFL.
The weather set 2 was eventually selected to represent the most likely conditions; however the
worst case conditions shall be defined by a sensitivity analysis study.

24

Abo Homos-Nubaria Pipeline QRA

11 Release Scenarios
Events associated with release, dispersion and ignition of flammable releases considered in this
study can be summarized in the following figure.

Release

Yes

Ignites?

No

Dispersing cloud

Yes

Ignites?

No

More obstacles
Greater confinement
Flame acceleration

Jet fire

Pool fire

Cloud fire

Fast flame

Internal

Safe

explosion

dispersion

Impinge?

Yes
Structural
Failure

BLEVE

Figure 11.1 Hazardous events


These events can be more detailed as follows:
Jet fires

A jet fire will result from an ignited pressurized hydrocarbon gas release. The
consequence of jet fires is directional depending on the on release orientation. Jet
fires typically have flame temperature of about 2,200 oF and can produce high
intensity thermal radiation. The high temperature poses a hazard from direct effects
of heat on humans and also from possibility of escalation. If a jet flame impinges
upon a target such as a vessel, pipe or structural member, it can cause failure of the
item to fail within several minutes.
Jet (spray) fire will also result from ignited continuous releases of pressurized
flammable liquid. The momentum of the release carries the material forwards in a

25

Abo Homos-Nubaria Pipeline QRA

plume entraining air to give a flammable mixture as gas is released from the plume.
Flash fires

If flammable gas accumulates in an unconfined area and is ignited, then the result
will be a flash fire within the flammable limits of the vapour cloud.

Explosions

Ignition of accumulated gas in semi-confined areas may also be accompanied by an


explosion; the overpressure generated will depend on the degree of congestion and
confinement of the process area, and the gas cloud size.

Pool fires

If a liquid release is ignited after it has time to form a pool, a pool fire results.
Because they are less well aerated, pool fires tend to have lower flame
temperatures and produce lower levels of thermal radiation than jet fires. They also
produce more smoke. Although a pool fire can still lead to structure failure of items
within the flame, this would take longer than in a jet fire.
An additional hazard of pool fires is their ability to flow. A burning liquid pool can
spread along horizontal surface or run down a vertical surface to give a running fire.

BLEVE
(Fire Ball)

BLEVE stands for Boiling Liquid Expanding Vapour Explosion.


A fire ball can occur if a vessel containing fuel ruptures in the presence of an ignition
source (usually a jet or pool fire). A fraction of the liquefied fuel subsequently
released will evaporate immediately and take part in a huge fireball, which has the
shape of a hemispherical burning cloud or ball of fire. High degree of turbulent
mixing and rapid air entrainment allows large quantities of fuel to be consumed in a
short period of time.

Structural
failure

Loss of structure integrity due to overheating of structure members. The structure


shall collapse under much lower load than the designed due to increased
temperature.

Safe
dispersion

Dilution of the released gases beyond the lower flammability limits (LFL) leading to
safe dispersion situation.

26

Abo Homos-Nubaria Pipeline QRA

12 Impairment Criteria
This section defines the human injury and asset impairment criteria in caring out the
consequence analysis of the identified hazardous events scenarios on the proposed facilities.
Table 12.1 represents standard human impact criteria as applied in consequence modelling.
Table 12.1: Criteria for Assessment of Fire Effects on Humans
Distance to
Effect
2
4.7kW/m
Will cause pain in 15-20 seconds and injury after 30
seconds exposure.
12.5 kW/m2
Significant chance of fatality for extended exposure and
high chance of injury.
2
37.5 kW/m
Significant chance of fatality for people exposed
instantaneously.
Flash fire
LFL
Fatal for people in the flammable cloud path
Explosion overpressure 0.05 Bar
Will cause injuries from flying debris
0.2 Bar
20% chance of fatality to a person in a protected
enclosure
0.3 Bar
Threshold for eardrum damage,
50% chance of fatality for a person within enclosure,
15% chance of fatality for a person in the open.
0.50 Bar
Will cause 100 % fatality for a person within enclosure
or in the open.
Event Effect
Jet fire / Pool fire

The criteria applied for assessment of the effects of fire on assets are summarised in Table
12.2.
Table 12.2: Criteria for Assessment of Fire Effects on Assets
Impairment Mechanism
Level
Effect
2
Thermal Radiation
4.7kW/m
Impairment of evacuation/embarkation areas
6.3 kW/m2
Impairment of escape routes
Thermal Radiation or Flame
500 deg.C
Structural Failure.
Impingement on Load Bearing
Structural Steel
Both jet fires and explosions can lead to structure failure of items, though this will take several
times longer for jet fires than for explosions. Table 13.3 presents indicative failure times under
hydrocarbon fire impact conditions, where times to failure refer to burn through or loss of load
bearing capacity.
Table 12.3: Structure Failure times in Fires (Indicative)
Time to Failure (Min)
Component
Jet Fire
Pool Fire
Unprotected structural steel beam
10
10
Unprotected steel plate
5
10
A-60 firewall
15
60
H-120 firewall
60
120

27

Abo Homos-Nubaria Pipeline QRA

Table 12.4 reports published information on the explosion overpressure effects.


Table 12.4: Explosion Overpressure Effects
Explosion
Overpressure - Bar(g)
0.02
0.07
0.07-0.14
0.08-0.1
0.15-0.2
0.2
0.3
0.34
1.0
2.0

Damage
50% windows shattering
Collapse of tank roof
Connection failure of corrugated panelling
Minor damage to steel framework
Wall of concrete blocks shattered
Collapse of steel framework
"Reparable damage" cladding blown off. Offshore bridjes and lifeboats
impaired
Steel walls blown off. Process plant within offshore module rupture, in
neighbouring modules damaged. 50% chance for ESD valve closure
failing
Columns and buoyant deck of semi-sub ruptured
Riser wall rupture

28

Abo Homos-Nubaria Pipeline QRA

13 Flammability Assessment
2

General

An assessment of all flammable and combustible materials present on the facilities is required
to determine those materials that can be excluded from further assessment in the QRA due to
low flammability and hence the low probability of ignition.
In order for a fire to start there must be an ignition source of sufficient heat intensity to cause
ignition. However, after a fire has started, the heat necessary to sustain combustion is typically
supplied by the combustion process.
A flammable gas or vapour burns in air only over a limited concentration range. Below a certain
concentration in air, the Lower Flammability Limit (LFL), the mixture is too lean, and above a
certain concentration in air, the Upper Flammability limit (UFL), the mixture is too rich to sustain
combustion.
The concentrations between these limits constitute the flammable range.
Flammability limits vary between hydrocarbon gases. For example, propane is flammable
between 2.1 and 9.5% v/v. Process streams consist of a mixture of hydrocarbons and on loss
of containment the flammability limits depend on the composition of the gas or vapour that is
released to air.
The flash point of a flammable liquid is the temperature at which the vapour pressure is
sufficient to result in a concentration of vapour in air above the liquid corresponding to the lower
flammable limit.
On loss of containment or where open to the atmosphere, a hydrocarbon liquid that has a flash
point below ambient temperature is readily ignitable. A liquid with a high flash point, could also
ignite if raised in temperature above its flash point by an external heat source, if released as a
high pressure spray that promotes vaporisation, or if soaked into lagging (insulating materials).
Flash point is the main parameter in the hazard classification of flammable liquids.
The flammability of materials has been assessed using the Flammability Hazard Ranking from
NFPA 325M under the categories summarised in Table 13.1. Flammable liquid classes referred
to in Table 13.1 are explained in IP15.
In general, materials with a flammability rating of 3 and 4 are readily ignited and present a
greater fire hazard than materials with flammability rating of 1 or 2 that require pre-heating (e.g.
by an existing fire) before ignition can occur.

29

Abo Homos-Nubaria Pipeline QRA

Flammability
Rating
4

Table 13.1: NFPA 325M Flammability Rating


Description
This degree includes flammable gases, liquids and class IA flammable
liquids. The preferred method of fire attack is to stop the flow of material
or to protect exposures while allowing the fire to burn itself out.
This degree includes class IB and IIC flammable liquids and materials
that can be easily ignited under almost all normal temperature conditions.
Water may be ineffective in controlling or extinguishing fires in such
materials.
This degree includes materials that must be moderately heated before
ignition will occur and includes class II and IIIA combustible liquids and
solids and semi-solids that readily give off ignitable vapours. Water spray
may be used to extinguish fires in these materials because the materials
can be cooled below their flash points.
This degree includes materials that must be pre-heated before ignition
will occur, such as class IIIB combustible liquids and solids and semisolids whose flash point exceeds 93.4C, as well as most ordinary
combustible materials. Water may cause frothing if it sinks below the
surface of the burning liquid and turns to steam. However, a water fog
that is gently applied to the surface of the liquid will cause frothing that
will extinguish the fire.
This degree includes any material that will not burn.

The properties of the various flammable materials present on the facilities are summarised in
Table 13.2. The flammability of the various inventories is discussed in further detail in the
following sections.
Table 13.2 physical properties of Selected Flammable / Combustible materials

13.2 Process Hydrocarbons


NFPA Flammability Index = 4
As a result the process hydrocarbon inventories are classified as highly flammable,
corresponding to an NFPA Flammability Index rating of 4. Based on this rating the fire and
explosion hazards associated with the inventories are further assessed in the QRA.

30

Abo Homos-Nubaria Pipeline QRA

14 Consequence Modelling Input Data


Consequence modelling will be used to simulate the Major Accident Events (MAE) raised from
the scenario identification.
FRED determines the heat radiation contours from different fire scenarios depending on the
amount of fuel burning, type of fuel and wind direction. It calculates a fluid release flow rate
depending on the fluid pressure, the size and location of the hole. Also, It calculates the
explosion overpressure contours resulting from the ignition of released gas inside confined
space depending on the type of the fuel exploding and the degree of confinement. Finally it
performs gas dispersion calculation and calculates the gas concentration contours in fraction of
the lower explosive limits depending on the type of gas released, release rate, wind stability,
wind speed and surface roughness.
The following simulation modules are included (detailed list):

Tank Top Fire


Pool Fire
Trench Fire
Gas Jet Flame (known reservoir pressure)
Gas Jet Flame (Known mass flow rate)
Shell BLEVE
BLEVE (TNO)
Temperature Rise
Pressurised release (known reservoir pressure)
Pressurised release (known mass flow rate)
Pressure relief valve
Blowdown
Two-Phase Blowdown
LPG two-phase
Explosion CAM
Explosion TNO
Explosion TNT
Dense gas dispersion
Gaussian dispersion (instantaneous)
Gaussian dispersion (Continuous)
Gaussian dispersion (Non boiling liquid pool)
Heat Up
Vessel Burst
Bubble Plume

This hazardous consequence simulation is normally carried out in order to optimize the design,
while on the other hand it will be used in this study to estimate the degree of danger raised from
the hazardous events on the facilities under study in order to assess the associated risks.

31

Abo Homos-Nubaria Pipeline QRA

The input file is detailed as follows:


Contaminants
Carbon Dioxide
Nitrogen
Oxygen
Hydrogen
Methane
Ethane
Propane
iso-Butane
n-Butane
iso-Pentane
n-Pentane
n-Hexane
n-Heptane
n-Octane
n-Nonane
Total

CO2
N2
O2
H2
CH4
C2H6
C3H8
i-C4.
n-C4.
i-C5
n-C5
n-C6
n-C7
n-C8
n-C9

Process conditions:
Process conditions:

Temperature = 50 C
Pressure = 70 bara
Pressure downstream of release = 1.013 bara
Use standard atmospheric pressure = yes
Release source = Vapor space

Hole & release geometry:


Hole geometry:

Failure type = Custom


Hole diameter = 0.8 / 0.4 / 0.025 m
Discharge coefficient = 0.8

Pipe:

Pipe length = 10000 m


Pipe diameter = 0.813 m
Pipe surface roughness = 4.6e-005 m
Sum loss coefficient = 0

Release:

32

Rich Gas Composition


3.990
0.050
0.000
0.000
80.224
10.069
3.880
0.570
0.6899
0.2100
0.1200
0.1200
0.0700
0.00
0.000
100.000

Abo Homos-Nubaria Pipeline QRA

Release height = 0 m
Release angle from vertical = 0 / 90 deg
Release angle, clockwise from North = 0 deg

Weather:

Temperature = 40 C
Relative humidity = 75 %
Wind speed = 2 & 10 m/s
Direction wind is going to = 180 deg (measured clockwise from North)
Atmospheric stability conditions define by = Pasquill class
Pasquill class = "F" stable & "D" Unstable

Thermal radiation:

Radiation contours = 1.5, 2.5, 6.3, 12.5, 32 kW/m


Height at which plan view contours to be plotted = 0 m
Cross flame distance at which side view contours to be plotted = 0 m

Dispersion:

Surface roughness = 0.01 m


Contours to plot:
Plot type = LFL/UFL
Sampling time = Instantaneous

Technical Notes:

Fred includes two methods of inputs to the discharge modelling, one is known
reservoir pressure and the second is known release mass flow rate. The scenario was
selected as known reservoir pressure in order to represent the maximum desired flow rate
through the hole.

Pipe surface roughness was selected as 4.6e-005, which represents the steel
material.

Different wind speeds were selected for the gas dispersion and heat radiation
modelling, basically 2 m/s and 10 m/s.

Dispersion sampling time was selected to be Instantaneous, which represents the


worst-case scenario (stricter than 10 minutes sampling).

33

Abo Homos-Nubaria Pipeline QRA

15 Sensitivity Analysis
The sensitivity analysis shall be performed in order to determine the worst case parameters (or
the combination of the worst case parameters), which shall be utilized in the consequence
modelling.
The sensitivity analysis shall include the following parameters:
1.0

Release flow rate:

The release flow rate depends on the size of the hole assumed to leak, which can be
summarized as follows:

Catastrophic leak or full bore rupture (presents maximum release rate).

Major leak or half bore rupture (presents minimum release rate).

2.0

Release pressure:

The release pressure depends on the process design and operating pressure of the released
materials, which can be summarized as follows:

The proposed maximum pipeline design pressure.

The proposed minimum pipeline design pressure.

3.0

Release temperature:

The release temperature depends on the process design and operating temperature of the
released materials, which can be summarized as follows:

The proposed maximum pipeline design temperature.

The proposed minimum pipeline design temperature.

4.0

Ambient temperature:

Ambient temperature varies from high ambient temperatures in the summer to low ambient
temperatures in the winter, which can be summarized as follows:

The proposed maximum ambient temperature in the summer is 40 (oC)

The proposed minimum ambient temperature in the winter is 5 (oC)

34

Abo Homos-Nubaria Pipeline QRA

5.0

Relative humidity:

Relative humidity varies from high relative humidity in the summer to low relative humidity in the
winter, which can be summarized as follows:

The proposed maximum relative humidity is 90 %.

The proposed minimum relative humidity is 50 %.

6.0

Wind speed:

Wind speed varies from high wind speed to low wind speed depending on the weather
conditions, which can be summarized as follows:

The proposed maximum wind speed is 10 m/s (presents very unstable weather
conditions).

The proposed minimum wind speed is 2 m/s (presents very stable weather conditions).

7.0

Wind stability:

Wind stability presented as Pasquill stability classes varies from very unstable weather to very
stable weather depending on the weather conditions, which can be summarized as follows:

The proposed very unstable weather is (A).

The proposed very stable weather is (F).

Different Pasquill stability classes are represented in the following table:


Number
1.
2.
3.
4.
5.
6.

Class
A
B
C
D
E
F

Description
Very Unstable
Unstable
Slightly Unstable
Neutral
Stable
Very Stable

Each of the previously mentioned parameters shall be checked with all other parameters are
constant. (I.e. these parameters shall be checked one by one, and for each case all other
parameters shall remain unchanged in order to determine the worst case scenario for each
parameter).
From the sensitivity analysis for the gas dispersion, it can be concluded that:
1. The gas dispersion distances shall be increased by higher release flow rate.
2. The gas dispersion distances shall be increased by higher release pressures.
35

Abo Homos-Nubaria Pipeline QRA

3. The gas dispersion distances shall be increased by lower release temperatures.


4. The gas dispersion distances shall be increased by higher ambient temperatures.
5. The gas dispersion distances shall be increased by lower relative humidity.
6. The gas dispersion distances shall be increased by lower wind speeds.
7. The gas dispersion distances shall be increased by higher weather stability.
From the sensitivity analysis for the heat radiation, it can be concluded that:
1. The jet flame heat radiation distances shall be increased by higher release flow rate.
2. The jet flame heat radiation distances shall be increased by higher release pressures.
3. The jet flame heat radiation distances shall be increased by higher release
temperatures.
4. The jet flame heat radiation distances shall not be affected by ambient temperatures.
5. The jet flame heat radiation distances shall not be affected by relative humidity.
6. The jet flame heat radiation distances shall be increased by higher wind speeds.
7. The jet flame heat radiation distances shall not be affected by weather stability.
From the sensitivity analysis performed, it has been concluded that there is a combination of set
of parameters that gives the worst case scenarios for the gas dispersion and heat radiation,
while on the opposite side; there is a combination of set of parameters that gives the mild case
scenarios for the gas dispersion and heat radiation.
Both cases (the worst cases and mild cases) can be simulated using consequence modelling,
however only the worst case scenarios for gas dispersion and heat radiation shall be governing
in this report in order to present a conservative approach leading to conservative QRA results.
From the sensitivity analysis, the following parameters have been selected to represent the
worst case scenario parameters and shall be utilized in the consequence modelling analysis:

The proposed maximum ambient temperature in the summer is 40 (oC),

The proposed minimum relative humidity in the winter is 50 %,

The proposed minimum wind speed is 2 m/s (presents very stable weather conditions),

The proposed very stable weather stability class is (F).

36

Abo Homos-Nubaria Pipeline QRA

16 Ignited Release Scenario


2

Generic Causes of Release

Historically, incidents involving the loss of containment of flammable/combustible material in the


oil and gas facilities have occurred due to causes including:

Human error associated with operations and maintenance activities;


Corrosion
Erosion
Fatigue/vibration/vortex shedding;
Brittle fracture (e.g. due to low temperatures embrittlement);
Impact (e.g. due to dropped object, projectile, impactsetc.);
Creep;
Natural causes (e.g. storm, earthquakeetc);
Operation beyond design envelope;
Inappropriate choice of materials; and
Inadequate design.

In relation to the new facilities, thorough design and the implementation by Company of an
appropriate Safety Management System will ensure many of the causes listed above are either
avoided or significantly reduced in potential.

16.2 Generic Causes of Ignition


Historically, the causes of ignition of released flammable/combustible material in the oil and gas
facilities have included:

Flames/direct heat;
Hot surfaces;
Hot work (e.g. welding, flame cutting, grinding);
Mechanical sparks;
Electrical equipment not classified for hazardous areas;
Faulty electrical equipment;
Lightning;
Engines;
Distressed equipment (e.g. overheated bearings);
Impact energy (e.g. tools, dropped objects, projectiles);
Chemical energy;
Static electricity;
Illicit smoking; and
Hot soot particles.

37

Abo Homos-Nubaria Pipeline QRA

Similar to causes of release, the above listed causes of ignition on the new facilities will be
either avoided or significantly reduced in potential through thorough design and the
implementation by Company of an appropriate Safety Management System.

38

Abo Homos-Nubaria Pipeline QRA

17 Typical Fire Consequence Analysis


2

Hydrocarbon Releases

Hydrocarbon releases in the industry are either gaseous, mists or liquids and are either
atmospheric releases or pressurized. Gas and mist releases are considered more significant
since they are readily ignitable since they are in the gas state and due to the generation of
vapour clouds which if ignited are instantly destructive in a widespread nature versus liquid fires
that may be less prone to ignition, generally localized and relatively controllable.
The cause of a release can be external or internal corrosion, internal erosion, equipment wear,
metallurgical defects, operator errors third party damage or for operational requirements.
Generally releases are categorized as:
1

Catastrophic Failure: A vessel or tank opens completely immediately releasing its


contents.

The amount of release is dependent of the size of the container.

Long Rupture: A section of pipe is removed leading to two sources of gas. Each
section being vented in an opening whose cross sectional areas are equal to the
cross sectional area of the pipe (e.g., pipeline external impact and a section is
removed).

Open Pipe: The end of a pipe is fully opened exposing the cross sectional area of the
pipe.

Short Rupture: A split occurs on the side of the pipe or hose. The cross sectional
area of the opening will typically be equal to the cross sectional area of the pipe or
hose (e.g., pipe seam split).

Leak: Leaks are typically developed from valve or pump seal packing failures,
localized corrosion or erosion effects and are typically "small" to "pin-hole" sized
(e.g., corrosion or erosion leakages).

Vents, Drains, Sample Ports Failures: Small diameter piping or valves may be
opened or fail which release vapours or liquids to the environment unexpectedly.

Normal Operational Releases: Process storage or sewer vents, relief valve outlets,
tank seals, which are considered normal and acceptable practices that release to the
atmosphere.

17.2.1 Gaseous Release

39

Abo Homos-Nubaria Pipeline QRA

There are a number of factors that determine the release rate and initial geometry of a
hydrocarbon gas release. The most significant is whether the gas is under pressure or released
at atmospheric conditions.
Depending on the release source the escaping gas can last from several minutes or hours, until
the supply is isolated, depleted or fully depressurized. Common long duration sources are
massive storage equipment, or long pipelines without intermediate isolation capabilities.
If released under atmospheric conditions the gas will either rise or fall depending on its vapour
density and will be directed in the path of the prevailing wind. In the absence of a wind, heavier
gases will collect in low points in the terrain. Normally atmospheric gas releases are dispersed
within relatively close distances to their point source, usually about 3 meters (10 ft.) These
atmospheric releases, if ignited, will burn relatively close to the source point, normally in a
vertical position with flames of short length.
For gases released under pressure, there are a number of determining factors that influence the
release rates and initial geometry of the escaping gases. The pressurized gas is released as
gas jet and depending on the nature of the failure may be directed at any direction. All or part of
a gas jet may be deflected by surrounding structures or equipment.
If adequate isolation capabilities are available and employed, the initial release will be
characterized by high flow and momentum which decreases as isolation is applied or supplied
are exhausted. Within a few pipe diameters of the release point, the pressure of released gases
decreases. Escaping gases are normally very turbulent and air will immediately be drawn into
the mixture. The mixing of air will also reduce the velocity of the escaping gas jet. Obstacles
such overhead platforms or structures will disrupt momentum forces of any pressurized release.
These releases will generally produce a vapour cloud, which if not ignited will eventually
disperse in the atmosphere. Where turbulent dispersion processes are prevalent (e.g., high
pressure flow, winds, congestion, etc.), the gas will spread in both horizontal and vertical
dimensions while continuing mixing with available oxygen in the air. Initially escaping gases are
above the UEL but with dispersion and turbulence effects they rapidly pass into the flammable
limits. If not ignited and given an adequate distance they will eventually disperse below the LEL.
Various computer software programs are currently available that can calculate the turbulent jet
dispersion, downwind explosive atmospheric locations, and volumes for any given flammable
commodity, release rates and atmospheric data input.
Generally most gases have a low vapour density and will rise. In any event, the height of a gas
plume will mostly be limited by the ambient atmospheric stability and wind speed. If the gases
are ignited, the height of the plume will rise due to the increased buoyancy of the high
temperature gases from the combustion process.

17.2.2 Liquid Release


When a liquid is released from process equipment, several things may happen, as shown in the
Figure. If the liquid is stored under pressure at a temperature above its normal boiling point
(superheated), it will flash partially to vapour when released to atmospheric pressure. The
vapour produced may entrain a significant quantity of liquid as droplets. Some of this liquid may
rainout onto the ground, and some may remain suspended as an aerosol with subsequent
possible evaporation. The liquid remaining behind is likely to form a boiling pool which will
continue to evaporate, resulting in additional vapour loading into the air. An example of a

40

Abo Homos-Nubaria Pipeline QRA

superheated release is a release of liquid ammonia from a pressurized container stored at


ambient temperature.

17.2.3 Toxic Gas release


The inhalation of toxic gases can give rise to effects, which range in severity from mild irritation
of the respiratory system to death. Lethal effects of inhalation depend on the concentration of
the gas to which people are exposed and on the duration of exposure. Mostly this dependence
is non linear; as the concentration increases, the time required to produce a specific injury
decreases rapidly.
Immediately dangerous to life and health (IDLH) is defined as a condition that poses immediate
danger to life or health, or a condition that poses a threat of severe exposure.
Two factors are considered when establishing the IDHL limits:

Personnel must be able to escape such an environment without suffering permanent


health damage,

Personnel must be able to escape without severe eye or respiratory tract irritation or
other condition that might impair their escape.

Immediately Dangerous to Life and Health: (IDLH) is an atmospheric concentration of any toxic,
corrosive, or asphyxiate substance that poses an immediate threat to life or would cause
irreversible or delayed adverse health effects or would interfere with an individuals ability to
escape from a dangerous atmosphere.

17.3 Fire
The combustion process:
Fire, or combustion, is a chemical reaction in which a substance combines with oxygen and
heat is released.
Usually fire occurs when a source of heat comes into contact with a combustible material. If a
combustible liquid or solid is heated it evolves vapour, and if the concentration of vapour is high
enough it forms a flammable mixture with the oxygen of the air. If this flammable mixture is then
heated further to its ignition point, combustion starts. Similarly, a combustible gas or vapour
mixture burns if it is heated to a sufficiently high temperature.
Thus there are three conditions essential for a fire: (1) fuel, (2) oxygen, and (3) heat. These
three conditions are often represented as the fire triangle.
If one of the conditions is missing, fire does not occur and if one of them is removed, fire is
extinguished.

41

Abo Homos-Nubaria Pipeline QRA

Normally the heat required is initially supplied by an external source and then provided by the
combustion process itself. The amount of heat needed to cause ignition depends on the form of
the substance. A gas or vapour may be ignited by a spark or small flame.
Ignition of a combustible gas or vapour mixture may occur in two ways. In the first the energy for
ignition is supplied by a local source such as a spark or small flame at a point within the mixture.
In the second the bulk gas mixture is heated up to its ignition temperature.
The three conditions of the fire triangle indicate how fires may be fought. The first method is to
cut off the fuel. This is particularly relevant for fires caused by leaks on process plant. The
second method is to remove heat. This is usually done by putting water on the fire. The third
method is to stop the supply of oxygen. This may be affected in various ways, including the use
of foam or inert gas.
Fire is sustained only if there is a net release of heat.
The heat comes from the combustion of fuel. If this fuel is liquid or solid, it must first be
vaporized. With liquids or solids fire usually involves a process of positive feedback. The heat
evolved by the fire causes the vaporization of an increasing amount of fuel and the fire spreads.
Fire growth and spread:
Fire normally grows and spreads by direct burning, which results from impingement of the flame
on combustible materials, by heat transfer or by travel of the burning material.
The three main modes of heat transfer are (1) conduction, (2) convection and (3) radiation. All
these modes are significant in heat transfer from fires.
Conduction is important particularly in allowing heat to pass through a solid barrier and ignite
material on the other side.
Most of the heat transfer from fires, however, is by convection and radiation. It is estimated that
in most fires some 75% of the heat emanates by convection. On open plant much of the heat is
dissipated into the atmosphere, but in steel structures it is transferred to the steel supports.
Radiation is the other main mode of heat transfer. Although it usually accounts for a smaller
proportion of the heat issuing from the fire, radiated heat is transferred directly to nearby
objects, does not go preferentially upwards and crosses open spaces. For these reasons it is
generally the most significant mode of transfer on open plant.
Combustion of a flammable gas/air mixture occurs if the composition of the mixture lies in the
flammable range and if the conditions exist for ignition. As already mentioned, ignition may
result from either (1) bulk gas temperature rise or (2) local ignition.
The combustion of the mixture occurs if the bulk gas is heated up to its auto-ignition
temperature.
Alternatively, combustion occurs if there is applied to the mixture a source of ignition which has
sufficient energy to ignite it.
Flammability limits:

42

Abo Homos-Nubaria Pipeline QRA

A flammable gas burns in air only over a limited range of composition. Below a certain
concentration of the flammable gas, the lower flammability limit, the mixture is too `lean', while
above a certain concentration, the upper flammability limit; it is too `rich'.
The concentrations between these limits constitute the flammable range. The lower and upper
flammability limits (LFL and UFL) are also sometimes called, respectively, the lower and upper
explosive limits (LEL and UEL). They are distinct from the detonability limits.
Flammability limits are affected by pressure, temperature, direction of flame propagation and
surroundings.

Flash Fire

A flash fire would result if a flammable vapour cloud builds up and engulfs a source of ignition,
or an ignition source is introduced. The volume of the combustion products are approximately 8
times the volume of the vapour cloud, hence a flash fire would be much larger than the initial unignited vapour cloud. Although a flash fire can cause fatalities by flame impingement, it would
be of insufficient duration to cause escalation unless it develops significant overpressure. It
would then be termed a vapour cloud explosion.
Due to the short duration of a flash fire, fatalities are considered to occur only within the flame
itself.
The size of the vapour cloud depends on:

Release rate;
Composition;
Wind conditions.

Dispersion calculations should be performed to estimate the maximum gas cloud sizes within
the LFL. These have been based upon horizontal releases into open air in the same direction
as the wind for various wind speeds.
The results of the gas dispersion calculations shall be represented graphically. These results
will be used to assess the potential for an ignition source to be engulfed in a vapour cloud, the
extent of potential flash fires and the potential for explosion.
The dispersion calculations are valid for open area releases. Releases in congested areas will
not disperse so readily and this will be taken into account in the assessment of effects on
personnel and asset.
The conclusions from the dispersion calculations are:

the heavier gases, propane and butane, produce similar size gas clouds for the same
releases rate;
methane gas tends to rise more rapidly due to buoyancy, particularly in light wind
conditions;

43

Abo Homos-Nubaria Pipeline QRA

The larger the gas cloud, the greater the size of the flash fire and potential explosion
overpressure upon ignition.

Unobstructed Jet Fires

Gas or vapour releases from holes in high-pressure hydrocarbon inventories give rise to
turbulent jet fires if ignited. With this fire type pure fuel is released through an orifice and the air
required for combustion is entrained from the surrounding atmosphere. At high release rates,
the jet becomes highly turbulent, entrains more air and burns hotter.
The jet lengths have been modelled using SHELL FRED (4.0). FRED uses the Chamberlain
model developed by the Shell Oil Company to derive gas jet flame lengths.
Releases from the liquid phase of a process vessel (e.g. separator) will typically be driven by
the vapour pressure of the liquid. Once the gas/liquid interface falls below the level of the leak a
gas jet fire release will ensue driven by the pressure of the gas in the system.
High-pressure condensate releases will atomise due to the momentum of release and vaporise
due to the heat from the fire and burn as a self sustaining jet, some heavier fractions can drop
out when the pressure drops to below approximately 5 bar(a), resulting in surface pool fire
forming below the jet fire.
Thermal radiation isopleths are proportional to the size of the jet fire. The dimensions of 1.5,
4.7, 6.3, 12.5 and 37.5 kW/m2 isopleths shall be calculated and included on the graph to
facilitate assessment of effects on personnel and impairment of safety critical systems. The jet
flame length (metres) for methane releases may be approximated from the mass release rate,
m (kg/s) using a power law curve as follows:
Jet Length = 13.5 m0.45 (based on BP Cirrus modelling results)
Jet flame lengths for propane, butane and condensate are approximately 15% longer than for
methane.
The unobstructed jet fires will only occur from ignited releases originating from inventories at the
edge of the process area and orientated outboard. These are less likely to cause damage or
fatalities.
Due to the congestion presented by the equipment and pipe work, the majority of potential
process fires on the process area will be obstructed. These obstructed jet fires will result in a
fireball type of fire, instead of a jet fire.
For jet fires, the fire fighting systems (firewater or other fire fighting agents) are not efficient to
fight such types of fires due to the high momentum release initiating such jet fires. Hence, the
only way to control jet fires is to limit the isolatable inventory feeding the jet flame.
The jet fire will deplete by time due to the decrease in driving force across the release point "the
hole", consequently the jet flame is expected to be reduced by time.

44

Abo Homos-Nubaria Pipeline QRA

For jet fires, it is essential to predict the approximate jet fire time duration in order to assess the
extent of the hazardous consequences. Based on the isolatable section inventory within the
system and the assumption that all operators are aware and trained to deal with such
emergency situations, the approximate jet fire duration can be estimated as short duration fires.
If the ESD system shall operate effectively in such cases; hence the approximate jet fire
durations can be estimated as too short to cause fatality, injury or massive damage to
equipment.

Obstructed Jet Fires

Most jet fires will be obstructed due to the relatively congested layouts. These will burn as a
continuous fireball. The diameter of these fireballs and the associated thermal radiation
isopleths are calculated by considering the thermal radiation levels surrounding the fire.
For fires above single grade level, the radiation isopleths are in the shape of a hemisphere. The
heat radiated through the hemispherical skin is assumed to be equal to the heat generated by
the burning as follows:
Surface area of a hemisphere, A = 2r2
Hence Q.(2..r2) = m.H.p
And

r = (m.H.p/2..Q)

Where Q = Heat flux (kW/m2)


p = Proportion of heat radiated (typically 20%)
H = Heat of Combustion (kJ/kg)
m = Burning Rate (kg/s) (equivalent to release rate)
r = Radius (m)
The actual fireball radius is estimated based on setting Q at 150 kW/m2, which gives a
conservative fire size. Curves are also calculated for the 1.5, 4.7, 6.3, 12.5 and 37.5 kW/m2
isopleths.
For fires between multiple levels structure, the radiation isopleth is assumed to be in the shape
of a cylinder, the height of which is the distance between decks.
The equilibrium equation for this case is calculated as follows:
Surface area of a cylinder (excluding ends), A = 2..r
Hence Q.(2..h.r) = m.H.p
And

r = (m.H.p/2..h.Q)

Where h = Height (or length) of cylinder (m)

45

Abo Homos-Nubaria Pipeline QRA

For instance, a fireball in the centre of the deck level associated with a release rate greater than
approximately 5 kg/s would produce fatal radiation levels to a distance about 20m from the fire
source. In reality, the fire would soon become ventilation limited and would tend to fill the area
with flames lapping out around the perimeter.

46

Abo Homos-Nubaria Pipeline QRA

18 Release Scenarios
For the purposes of the hazard analysis and consequence modelling, a number of
representative release scenarios and physical impact cases are defined in as per Table 19.1.

Release
Orientation

Table 19.1: Representative Release Cases


Hole
Hole Size /
Press. Hazardous
Size
Leak Type
(Bar)
Scenario
(Inch)
Full Bore
Rupture
(Catastrophic
Failure)

1.0
Vertical Release
Orientation

Half Bore
Rupture
(Major Leak)

Gas
Dispersion
32 Inch

70
Jet Fire

Gas
Dispersion
16 Inch

70
Jet Fire

Gas
Dispersion
Pin Hole
(Minor Leak)

1 Inch

70

Jet Fire
Jet Fire

3.0
Depressurizatio
n

Planned
Depressurizatio
n

10 Inch

70

Gas
Dispersion

4.0
Explosion

N/A

N/A

N/A

Explosion

47

Case Identification
70Bar - Full Bore
Rupture [12 Inch] Vertical Release - Gas
Dispersion
70Bar - Full Bore
Rupture [12 Inch] Vertical Release - Jet
Fire
70Bar - Half Bore
Rupture [6 Inch] Vertical Release - Gas
Dispersion
70Bar - Half Bore
Rupture [6 Inch] Vertical Release - Jet
Fire
70Bar - Pin Hole leak
[1 Inch] - Vertical
Release - Gas
Dispersion
70Bar - Pin Hole leak
[1 Inch] - Vertical
Release - Jet Fire
70Bar - Pin Hole leak
[1 Inch] - Horizontal
Release - Jet Fire
70Bar Depressurization [10
Inch] - Vertical
Release - Gas
Dispersion
Explosion scenario

Abo Homos-Nubaria Pipeline QRA

The full details of the cases / runs are presented in Appendix-1 including the following data:

Process stream composition:

Process conditions:

Hole & release geometry:

Hole geometry:

Pipeline details:

Release details:

Weather details:

Thermal radiation contours:

Dispersion calculations.

Also, the full details of all cases / runs presented in Appendix-1 including the following figures:

Jet fire side view;

Jet fire top view;

Impingement flame probability of occurrence side view;

Flammable pollutant dispersal side view;

Flammable pollutant dispersal side view;

Actual plan top view (scenario actual plan view).

48

Abo Homos-Nubaria Pipeline QRA

19 Consequence Modelling Results


In order to perform consequence modelling analysis of the potential hazardous scenarios
resulting from loss of containment, some assumptions and design basis have been proposed.
the pipeline release orientation have been proposed to be a vertical release, which is
considered for buried underground pipeline releasing the entrapped materials in the vertical
direction upwards (represents the actual release scenario). Other release orientations represent
the exaggerated release scenario.
For the pipeline leak scenario, the release rate has been simulated based on 3-hole sizes as
follows:

Full bore rupture (32-inchs);


Half bore rupture (16-inches);
Pin hole leak (1-inch).

The first leak size is a full bore rupture of the pipeline (32 inch leak), which presents a hole
diameter equivalent to the pipeline diameter. This scenario presents the worst case scenario for
maximum release rate in order to represent a catastrophic release scenario.
The second leak size is a half bore rupture of the pipeline (16 inch leak), which presents a hole
diameter equivalent to half the pipeline diameter. This scenario presents the severe case
scenario for a reduced release rate in order to represent a major release scenario.
The third leak size is a one inch hole in the pipeline (1 inch leak), which presents a pin hole in
the pipeline wall or small deformation equivalent to the one inch hole in diameter. This scenario
presents the mild case scenario for a reduced release rate in order to represent a minor release
scenario.
FRED has been selected for the consequence modeling of different types of hazardous
consequences modeling presented as follows:

Jet fires (resulting from immediate ignition).


Gas clouds and Flash fires (resulting from delayed ignition),

Weather conditions have been selected based on wind speed and stability class for the greater
Cairo area detailed weather statistics.
The worst case weather conditions for gas dispersion is the stable weather conditions,
represented by wind speed of 2 m/s and stability class "F" representing "Very Stable" weather
conditions, in order to obtain conservative results.
The gas dispersion distances have been calculated in meters in concentration terms of Lower
Flammability Limits (LFL) and Upper Flammability Limits (UFL) presented by Part Per Million
(PPM) concentrations in order to represent the flammability range of the released gas cloud;
however the extent of damage is presented by LFL only.

49

Abo Homos-Nubaria Pipeline QRA

The heat radiation from flash fires will not significantly affect humans, equipment or structures
outside the 12.5 (Kw/m2) heat radiation envelopes due to the short duration of flash fires [in
terms of milliseconds].
Since the jet fire is originally a high momentum directed jet release, hence the effects of wind
direction, wind speed or atmospheric stability on the jet flame are minimal.
The jet fire (flame length) and heat radiation distances are measured in meters.
The extent of harmful effects on humans is presented by the distance to the heat radiation
contour of 12.5 (Kw/m2) and the extent of damage for equipment is presented by the flame
length (frustum).
The following figures present the gas cloud distances in meters which consequently represent
the extent of damage distances to the LFL for different pressure profiles, different release
orientations and different leak sizes (release rates), as a result from the consequence modelling
simulation analysis performed.
Since the gas is heavier than air, the released plume tends to disperse on the ground level
depending on the weather conditions of the area, which in general is more likely to meet an
ignition source leading to flash fire.

50

Abo Homos-Nubaria Pipeline QRA

2 Rupture [32 Inch] - Vertical Release - Gas Dispersion

51

Abo Homos-Nubaria Pipeline QRA

19.2 70Bar - Full Bore Rupture [32 Inch] - Vertical Release - Jet Fire

52

Abo Homos-Nubaria Pipeline QRA

19.3 70Bar - Major Leak [16 Inch] - Vertical Release - Gas Dispersion

53

Abo Homos-Nubaria Pipeline QRA

19.4 70Bar - Major Leak [16 Inch] - Vertical Release - Jet Fire

54

Abo Homos-Nubaria Pipeline QRA

19.5 70Bar - Minor Leak [1 Inch] - Vertical Release - Gas Dispersion

55

Abo Homos-Nubaria Pipeline QRA

19.6 70Bar - Minor Leak [1 Inch] - Vertical Release - Jet Fire

56

Abo Homos-Nubaria Pipeline QRA

19.7 70Bar - Depressurization Case [10 Inch Vent at 10 Meter Height]

57

Abo Homos-Nubaria Pipeline QRA

19.8 Explosion Case

58

Abo Homos-Nubaria Pipeline QRA

20 Likelihood Data
2

Process Release

A summary of historical pipeline failure data from some of the best sources of data for landbased pipelines are summarized in the following table (based on E&P Forum, CONCAWE,
PARLOC and EGIG):
No.
1
2
3
4

Table 21.1 Comparison of Pipeline Failure Rate Data


Source
Failure rate / year / Km
US Gas Pipelines (1985 1994)
1.66 X 10-4
US hazardous liquid pipelines (1986 1998)
8.05 X 10-4
CONCAWE European Oil Pipelines (1990 1998)
3.25 X 10-4
European Gas Pipeline Incident Data group (1970 1997)
4.77 X 10-4

The pipeline leak frequency shall be extracted to be (2.2 X 10-4).

20.2 Ignition Probability


The probability of ignition depends on the availability of a flammable mixture, the flammable
mixture reaching an ignition source and the type of ignition source (energy etc.).
The ignition sources may include:

Hot work
Faults in electrical equipment
Faults in rotating equipment
Ignition caused by combustion engines or hot surfaces
Automatic ignition in the event of a fracture or rupture
Static electricity
Open flame

Generic ignition probabilities have been taken from Lees.


Ignition probability data are provided for gas release based on mass release rate.
Typical ignition probability data are given in Table 21.2.
Table 21.2 Ignition Probability Data
Mass Release Category
Minor
Major
Massive

Mass Release Rate (Kg / Sec)


<1
1 50
> 50

59

Ignition Probability
Gas
Oil
0.01
0.01
0.07
0.03
0.3
0.08

Abo Homos-Nubaria Pipeline QRA

21 Risk Assessment
2

Risk Assessment Basis

Risk shall be determined for both workers and public using international risk management
guidelines as a reference. The risk will be compared with international risk acceptance criteria.
Risk assessment will comprise the following items:

Failure rate,
Ignition probability,
Occupancy,
Vulnerability.

Where:
Failure rate: is the failure frequency.
Ignition Probability: is the likelihood of a release to become a fire or explosion.
Occupancy: is the personnel presence in the area. [10 workers assumed to be present
outdoors].
Vulnerability: is the likelihood that the specific person will be fatally injured by the effect of the
event (determined from the consequence modelling software).

21.2 Risk Assessment for Buried Underground Pipeline


Individual risk for buried underground pipeline
IR = 6.6 X 10-8 per year
Societal risk for buried underground pipeline
SR = 6.6 X 10-7 per year

60

Abo Homos-Nubaria Pipeline QRA

22 Risk Evaluation
Risk assessment shall be evaluated based on the international risk acceptance criteria (Figure
22.1).
The ALARP principle has been adopted for risk evaluation. The ALARP region is that point at
which the time, effort difficulty and cost of further risk reduction become out of proportion
compared with the amount of risk reduction achieved.
The international risk acceptance criteria are presented in the following figure.

Workers

UNACCEPTABLE REGION

Public

Maximum tolerable limit

1 in 1000 per year

ALARP Benchmark existing installations


1 in 5,000 per year
ALARP OR TOLERABILITY REGION

Maximum tolerable limit

1 in 10,000 per year


ALARP OR TOLERABILITY
REGION

ALARP Benchmark new installations


1 in 50,000 per year
Minimum tolerable limit

(Risk must be demonstrated to have


been reduced to a level which is
practicable with a view to cost/benefit)

1 in 100,000 per year

Minimum tolerable limit

ACCEPTABLE REGION

1 in 1 million per year


ACCEPTABLE REGION

INDIVIDUAL RISK TO WORKERS


(including contractor employees)

INDIVIDUAL RISK TO THE PUBLIC


(all those not directly involved with company
activities)

Figure 22.1 International Risk Acceptance Criteria


From the risk assessment and the international risk acceptance criteria the risk evaluation for
individual and societal risks for both pipeline orientations are presented in the following tables.
No
1.0
2.0

Table 22.1 Buried Underground Pipeline Orientation Risk Evaluation Summary Table
Risk Type
Calculated Risk
ALARP Limits
Risk Acceptance
Individual Risk
6.60E-08
1.0E-03 to 1.0E-05
Acceptable ()
Societal Risk
6.60E-07
1.0E-04 to 1.0E-06
Acceptable ()

61

Abo Homos-Nubaria Pipeline QRA

23 Risk Reduction Measures (Recommendations)


Risk reduction measures (Recommendations) may include reducing the risk by several
technically feasible methods, generally are as follows:

Measures to eliminate the risk.

Measures to reduce the exposure of personnel to the hazards.

Measures to reduce the frequency of occurrence.

Measures to mitigate the consequences if the event does occur.

Measures to improve evacuation in case of emergency (event occurs).

It has been concluded that the risk falls within the Acceptable limits for the individual risk to
workers and public for the pipeline. However, the following measures (recommendations) should
be adhered:

Ensure pipeline design, commissioning, start-up, construction and operation is


complying with code requirements (ASME B31.8 Gas Transmission and Distribution
Piping Systems).

Ensure Signs or markers shall be installed where it is considered necessary to indicate


the presence of a pipeline at road, highway, railroad, and stream crossings. Additional
signs and markers shall be installed along the remainder of the pipeline at locations
where there is a probability of damage or interference (ASME B31.8 requirement).

Signs or markers and the surrounding right-of way shall be maintained so markers can
be easily read and are not obscured (ASME B31.8 requirement).

The signs or markers shall include the words Gas" (or name of gas transported)
Pipeline, the name of the operating company, and the telephone number (including area
code) where the operating company can be contacted (ASME B31.8 requirement).

Ensure Overpressure protection is provided by a device or equipment installed in a gas


piping system that prevents the pressure in the system or part of the system from
exceeding a predetermined value (ASME B31.8 requirement).

Emergency Response plan (ERP) to include means for detection pipeline leak or rupture
also, means for safe and quick isolation of the damaged section of the pipeline.

62

Abo Homos-Nubaria Pipeline QRA

24 Uncertainty Analysis
Uncertainty analysis is performed to define the uncertainty data in the input model,
underestimation of consequences, neglected items, assumed points, exaggeration points or
overestimation.
In this QRA study all input data have been selected based on the worst case scenarios. The
selection of the worst case scenarios shall result in conservative design leading to conservative
results.
A list of worst case scenarios and conservative assumptions include the following:

Selection of the minimum wind speed of 2 m/s with stability class "F" in order to
represent a "Very Stable" weather conditions in the consequence modelling calculations.

Selection of the maximum ambient temperature of 40 C in the consequence modelling


calculations.

Selection of the minimum relative humidity of 50% in the consequence modelling


calculations.

The maximum operating pressure has been selected as the simulation pressure.

Simulation sampling time has been selected as "Instantaneous" in stead of 10-minutes


sampling to investigate the maximum plume length in order to achieve conservative
results.

Selection of the maximum hole size to be the controlling case. The selected 2-hole sizes
are 32-inch, representing catastrophic failure as a full bore rupture and 16-inche
representing major leak as a half bore rupture.

The release direction (release orientation) has been selected in the direction towards the
populated area under study representing the worst case directional orientation.

The prevailing wind direction has been selected in the direction towards the populated
area under study representing the worst case wind direction.

The highest failure rate has been selected as the basis for failure data.

The highest ignition probability has been selected for all ignition probability data.

The vulnerability of all hazardous events has been selected on the worst case scenario.

Hence, there is no uncertainty in the QRA calculations and all the calculated risks are certain.

63

Abo Homos-Nubaria Pipeline QRA

25 References
1. NFPA 325M,
2. FRED Version (4.0) documentation,
3. Frank P. Lees, Loss Prevention in the Process Industries, 2001,
4. API-581, Risk Based Inspection recommended practice,
5. E&P Forum,
6. Project Documents.

64

Abo Homos-Nubaria Pipeline QRA

26 Appendix-1 FRED Simulation Cases for PRS


Author
Company
Department
Revision
Notes
Revision date

EcoConServ
EcoConServ
HSE
0
QRA - Consequence Modelling
24 July 2011

26.2 Table of Contents


70Bar - Full Bore Rupture [32 Inch] - Vertical Release
70Bar - Half Bore Rupture [16 Inch] - Vertical Release
70Bar - Minor Leak [1 Inch] - Vertical Release
70Bar - Depressurization [10 Inch] - Vertical Release
Explosion [Confined space]

26.3 70Bar - Full Bore Rupture [32 Inch] - Vertical Release


26.3.1 Scenario Summary
26.3.1.1 Scenario
Scenario = 70Bar - Full Bore Rupture [32 Inch] - Vertical Release
Fluid = Natural gas

26.3.1.2 Process conditions


Calculate at = User input pressure
Temperature = 40 C
Pressure = 70 bara

26.3.1.2.1

Pressure downstream of release

Pressure = 1.013 bara


Use standard atmospheric pressure = yes

26.3.1.2.2

Release from

Release source = Vapour space

26.3.1.3 Hole & release geometry


26.3.1.3.1

Hole geometry

65

Abo Homos-Nubaria Pipeline QRA


Failure type = Custom
Hole diameter = 0.799 m
Discharge coefficient = 0.8

26.3.1.3.2

Pipe

Pipe length = 0 m

26.3.1.3.3

Release

Release height = 0 m
Release angle from vertical = 0 deg
Release angle, clockwise from North = 0 deg

26.3.1.4 Weather
26.3.1.4.1

Ambient conditions

Temperature = 40 C
Relative humidity = 75 %
Wind speed = 10 m/s
Direction wind is going to = 0 deg
(measured clockwise from North)

26.3.1.4.2

Atmospheric stability conditions

Define by = Pasquill class


Pasquill class = D Neutral

26.3.1.5 Thermal radiation


Radiation contours = 1.58, 4.73, 6.31, 9.46, 37.5 kW/m
Height at which plan view contours to be plotted = 0 m
Cross flame distance at which side view contours to be plotted = 0 m

26.3.1.6 Dispersion
Surface roughness = 0.1 m
Contours to plot:
47226.4 ppm 148597.8 ppm
Plot type = LFL/UFL
Sampling time = Instantaneous

26.3.1.7 Release summary


Mass flow rate = 5571.0 kg/s
Flux = 11110.9 kg/m/s
Static exit pressure = 35.59 bara
Exit temperature = -55.14 C
Exit density = 35.6 kg/m
Exit velocity = 312.1 m/s
Residence time = 0 s
Vapour fraction at exit = 1 mol/mol
Expanded exit velocity = 623.4 m/s
Air equivalent source diameter = 3.079 m

26.3.1.8 Release Composition


Molecular Weight of Release = 18.13 kg/kmol

66

Abo Homos-Nubaria Pipeline QRA

Component

Weight
Fraction
norm

Mole
Fraction
norm

Critical
Temp C

Critical
Pressure
bara

Molecular
Weight
kg/kmol

n-Butane

0.0321

0.0100

152.1

37.41

Propane

0.0487

0.0200

96.7

41.91

44.1

Ethane

0.0829

0.0500

32.18

48.08

Methane

0.7966

0.9000

-82.6

Nitrogen

0.0155

0.0100

Carbon
dioxide

0.0243

0.0100

Atmos
BP C

58.12 -0.5001

Freeze
Pt C

Heat of
Comb
kJ/kg

-138.4

45742.7

-42.1

-187.7

46383.8

30.07

-88.6

-182.8

47514.8

45.35

16.04

-161.5

-182.5

50043.9

-146.9

33.56

28.01

-195.8

-210

31.06

72.86

44.01

-86.9

-56.6

26.3.1.9 Reservoir summary (at reservoir pressure)


Bubble point temperature = n/a
Dew point temperature = n/a
Vapour fraction = 1

26.3.1.9.1 Properties of phases


Vapour

Liquid

Molecular weight (kg/kmol)

18.13

Density (kg/m)

55.5

Enthalpy (kJ/kmol)

193.3

Entropy (kJ/kmol*K)

-29.46

Cv (kJ/kg*K)

1.725

Cp (kJ/kg*K)

2.627

Sound velocity (m/s)

414.8

Viscosity (e-3 kg/m*s)

0.01354

Surface tension (e-3 N/m)

26.3.2 Jet Fire


26.3.2.1 Jet Fire Summary
Flame length (of frustum) = 233.6 m
Cone width of flame base = 34.82 m
Cone width of flame end = 103.3 m
Flame lift-off = 121.9 m
Flame angle from vertical = 24.55 deg
Flame angle, clockwise from North = 0 deg
Surface emissive power = 258.1 kW/m
Fraction of heat radiated = 0.05906
Total combustion power = 264788.1 MW
Heat of combustion = 47529.6 kJ/kg

67

Abo Homos-Nubaria Pipeline QRA

26.3.2.2 Side view

Raw plot data


26.3.2.3 Top view

Raw plot data

68

Abo Homos-Nubaria Pipeline QRA

26.3.2.4 Impingement

Raw plot data


26.3.3 Pool Chart
26.3.3.1 No pool can form

69

Abo Homos-Nubaria Pipeline QRA

26.3.4 Dispersion
26.3.4.1 Dispersion Summary
Contour value (ppm)

47226.4

148597.8

Downwind distance (m)

72.92

19.03

Height above ground (m)

161.7

91.96

Mass in plume between specified limits = 241723.0 kg


Volume of plume containing this mass = 225706.0 m
Pollutant-only mass in this volume = 13477.4 kg
Specified minimum = 4.723 vol%
Specified maximum = 100 vol%

26.3.4.2 Jet - side

Raw plot data

70

Abo Homos-Nubaria Pipeline QRA

26.3.4.3 Jet - top

Raw plot data


26.3.5 Warnings
1 - Temperature outside experimental range -5 to 15 C
2 - Pressure outside experimental range 0 to 20 bara
3 - Pressure downstream parameter has not been experimentally determined
4 - Warning: some vapour condenses - assume metastable flow
5 - Dew point calculation not possible at requested pressure
6 - Ambient temperature outside extrapolated range -5 to 30 C
7 - Mass flow rate outside extrapolated range 0 to 100 kg/s
8 - Ambient temperature outside experimental range 0 to 15 C
9 - Release height outside experimental range 0.5 to 100 m
10 - Mass flow rate outside experimental range 0 to 30 kg/s
11 - Contour value outside experimental range 0 to 35 kW/m2
12 - Ambient pressure parameter has not been experimentally determined
13 - Release height increased above surface roughness

71

Abo Homos-Nubaria Pipeline QRA

top

26.4 70Bar - Half Bore Rupture [16 Inch] - Vertical Release


26.4.1 Scenario Summary
26.4.1.1 Scenario
Scenario = 70Bar - Half Bore Rupture [16 Inch] - Vertical Release
Fluid = Natural gas

26.4.1.2 Process conditions


Calculate at = User input pressure
Temperature = 40 C
Pressure = 70 bara

26.4.1.2.1

Pressure downstream of release

Pressure = 1.013 bara


Use standard atmospheric pressure = yes

26.4.1.2.2

Release from

Release source = Vapour space

26.4.1.3 Hole & release geometry


26.4.1.3.1

Hole geometry

Failure type = Custom


Hole diameter = 0.4 m
Discharge coefficient = 0.8

26.4.1.3.2

Pipe

Pipe length = 0 m

26.4.1.3.3

Release

Release height = 0 m
Release angle from vertical = 0 deg
Release angle, clockwise from North = 0 deg

26.4.1.4 Weather
26.4.1.4.1

Ambient conditions

Temperature = 40 C
Relative humidity = 75 %
Wind speed = 10 m/s
Direction wind is going to = 0 deg
(measured clockwise from North)

26.4.1.4.2

Atmospheric stability conditions

72

Abo Homos-Nubaria Pipeline QRA


Define by = Pasquill class
Pasquill class = D Neutral

26.4.1.5 Thermal radiation


Radiation contours = 1.58, 4.73, 6.31, 9.46, 37.5 kW/m
Height at which plan view contours to be plotted = 0 m
Cross flame distance at which side view contours to be plotted = 0 m

26.4.1.6 Dispersion
Surface roughness = 0.1 m
Contours to plot:
47226.4 ppm 148597.8 ppm
Plot type = LFL/UFL
Sampling time = Instantaneous

26.4.1.7 Release summary


Mass flow rate = 1396.2 kg/s
Flux = 11110.9 kg/m/s
Static exit pressure = 35.59 bara
Exit temperature = -55.14 C
Exit density = 35.6 kg/m
Exit velocity = 312.1 m/s
Residence time = 0 s
Vapour fraction at exit = 1 mol/mol
Expanded exit velocity = 623.4 m/s
Air equivalent source diameter = 1.542 m

26.4.1.8 Release Composition


Molecular Weight of Release = 18.13 kg/kmol
Component

Weight
Fraction
norm

Mole
Fraction
norm

Critical
Temp C

Critical
Pressure
bara

Molecular
Weight
kg/kmol

n-Butane

0.0321

0.0100

152.1

37.41

Propane

0.0487

0.0200

96.7

41.91

44.1

Ethane

0.0829

0.0500

32.18

48.08

Methane

0.7966

0.9000

-82.6

Nitrogen

0.0155

0.0100

Carbon
dioxide

0.0243

0.0100

Atmos
BP C

58.12 -0.5001

Freeze
Pt C

Heat of
Comb
kJ/kg

-138.4

45742.7

-42.1

-187.7

46383.8

30.07

-88.6

-182.8

47514.8

45.35

16.04

-161.5

-182.5

50043.9

-146.9

33.56

28.01

-195.8

-210

31.06

72.86

44.01

-86.9

-56.6

26.4.1.9 Reservoir summary (at reservoir pressure)


Bubble point temperature = n/a
Dew point temperature = n/a
Vapour fraction = 1

26.4.1.9.1 Properties of phases


Vapour

73

Liquid

Abo Homos-Nubaria Pipeline QRA

Molecular weight (kg/kmol)

18.13

Density (kg/m)

55.5

Enthalpy (kJ/kmol)

193.3

Entropy (kJ/kmol*K)

-29.46

Cv (kJ/kg*K)

1.725

Cp (kJ/kg*K)

2.627

Sound velocity (m/s)

414.8

Viscosity (e-3 kg/m*s)

0.01354

Surface tension (e-3 N/m)

26.4.2 Jet Fire


26.4.2.1 Jet Fire Summary
Flame length (of frustum) = 134.5 m
Cone width of flame base = 20.02 m
Cone width of flame end = 51.73 m
Flame lift-off = 70.07 m
Flame angle from vertical = 25.13 deg
Flame angle, clockwise from North = 0 deg
Surface emissive power = 254.5 kW/m
Fraction of heat radiated = 0.06782
Total combustion power = 66362.8 MW
Heat of combustion = 47529.6 kJ/kg

74

Abo Homos-Nubaria Pipeline QRA

26.4.2.2 Side view

Raw plot data


26.4.2.3 Top view

Raw plot data

75

Abo Homos-Nubaria Pipeline QRA

26.4.2.4 Impingement

Raw plot data


26.4.3 Pool Chart
26.4.3.1 No pool can form

76

Abo Homos-Nubaria Pipeline QRA

26.4.4 Dispersion
26.4.4.1 Dispersion Summary
Contour value (ppm)

47226.4

148597.8

Downwind distance (m)

35.66

9.302

Height above ground (m)

87.76

48.9

Mass in plume between specified limits = 32911.3 kg


Volume of plume containing this mass = 30607.4 m
Pollutant-only mass in this volume = 1815.5 kg
Specified minimum = 4.723 vol%
Specified maximum = 100 vol%

26.4.4.2 Jet - side

Raw plot data

77

Abo Homos-Nubaria Pipeline QRA

26.4.4.3 Jet - top

Raw plot data


26.4.5 Warnings
1 - Temperature outside experimental range -5 to 15 C
2 - Pressure outside experimental range 0 to 20 bara
3 - Pressure downstream parameter has not been experimentally determined
4 - Warning: some vapour condenses - assume metastable flow
5 - Dew point calculation not possible at requested pressure
6 - Ambient temperature outside extrapolated range -5 to 30 C
7 - Mass flow rate outside extrapolated range 0 to 100 kg/s
8 - Ambient temperature outside experimental range 0 to 15 C
9 - Release height outside experimental range 0.5 to 100 m
10 - Mass flow rate outside experimental range 0 to 30 kg/s
11 - Contour value outside experimental range 0 to 35 kW/m2
12 - Ambient pressure parameter has not been experimentally determined
13 - Release height increased above surface roughness

78

Abo Homos-Nubaria Pipeline QRA

top

26.5 70Bar - Minor Leak [1 Inch] - Vertical Release


26.5.1 Scenario Summary
26.5.1.1 Scenario
Scenario = 70Bar - Minor Leak [1 Inch] - Vertical Release
Fluid = Natural gas

26.5.1.2 Process conditions


Calculate at = User input pressure
Temperature = 40 C
Pressure = 70 bara

26.5.1.2.1

Pressure downstream of release

Pressure = 1.013 bara


Use standard atmospheric pressure = yes

26.5.1.2.2

Release from

Release source = Vapour space

26.5.1.3 Hole & release geometry


26.5.1.3.1

Hole geometry

Failure type = Custom


Hole diameter = 0.0254 m
Discharge coefficient = 0.8

26.5.1.3.2

Pipe

Pipe length = 0 m

26.5.1.3.3

Release

Release height = 0 m
Release angle from vertical = 0 deg
Release angle, clockwise from North = 0 deg

26.5.1.4 Weather
26.5.1.4.1

Ambient conditions

Temperature = 40 C
Relative humidity = 75 %
Wind speed = 10 m/s
Direction wind is going to = 0 deg
(measured clockwise from North)

26.5.1.4.2

Atmospheric stability conditions

79

Abo Homos-Nubaria Pipeline QRA


Define by = Pasquill class
Pasquill class = D Neutral

26.5.1.5 Thermal radiation


Radiation contours = 1.58, 4.73, 6.31, 9.46, 37.5 kW/m
Height at which plan view contours to be plotted = 0 m
Cross flame distance at which side view contours to be plotted = 0 m

26.5.1.6 Dispersion
Surface roughness = 0.1 m
Contours to plot:
47226.4 ppm 148597.8 ppm
Plot type = LFL/UFL
Sampling time = Instantaneous

26.5.1.7 Release summary


Mass flow rate = 5.63 kg/s
Flux = 11110.9 kg/m/s
Static exit pressure = 35.59 bara
Exit temperature = -55.14 C
Exit density = 35.6 kg/m
Exit velocity = 312.1 m/s
Residence time = 0 s
Vapour fraction at exit = 1 mol/mol
Expanded exit velocity = 623.4 m/s
Air equivalent source diameter = 0.09789 m

26.5.1.8 Release Composition


Molecular Weight of Release = 18.13 kg/kmol
Component

Weight
Fraction
norm

Mole
Fraction
norm

Critical
Temp C

Critical
Pressure
bara

Molecular
Weight
kg/kmol

n-Butane

0.0321

0.0100

152.1

37.41

Propane

0.0487

0.0200

96.7

41.91

44.1

Ethane

0.0829

0.0500

32.18

48.08

Methane

0.7966

0.9000

-82.6

Nitrogen

0.0155

0.0100

Carbon
dioxide

0.0243

0.0100

Atmos
BP C

58.12 -0.5001

Freeze
Pt C

Heat of
Comb
kJ/kg

-138.4

45742.7

-42.1

-187.7

46383.8

30.07

-88.6

-182.8

47514.8

45.35

16.04

-161.5

-182.5

50043.9

-146.9

33.56

28.01

-195.8

-210

31.06

72.86

44.01

-86.9

-56.6

26.5.1.9 Reservoir summary (at reservoir pressure)


Bubble point temperature = n/a
Dew point temperature = n/a
Vapour fraction = 1

26.5.1.9.1 Properties of phases


Vapour

80

Liquid

Abo Homos-Nubaria Pipeline QRA

Molecular weight (kg/kmol)

18.13

Density (kg/m)

55.5

Enthalpy (kJ/kmol)

193.3

Entropy (kJ/kmol*K)

-29.46

Cv (kJ/kg*K)

1.725

Cp (kJ/kg*K)

2.627

Sound velocity (m/s)

414.8

Viscosity (e-3 kg/m*s)

0.01354

Surface tension (e-3 N/m)

26.5.2 Jet Fire


26.5.2.1 Jet Fire Summary
Flame length (of frustum) = 14.9 m
Cone width of flame base = 2.206 m
Cone width of flame end = 3.285 m
Flame lift-off = 7.722 m
Flame angle from vertical = 26.95 deg
Flame angle, clockwise from North = 0 deg
Surface emissive power = 223.5 kW/m
Fraction of heat radiated = 0.1177
Total combustion power = 267.6 MW
Heat of combustion = 47529.6 kJ/kg

81

Abo Homos-Nubaria Pipeline QRA

26.5.2.2 Side view

Raw plot data


26.5.2.3 Top view

Raw plot data

82

Abo Homos-Nubaria Pipeline QRA

26.5.2.4 Impingement

Raw plot data


26.5.3 Pool Chart
26.5.3.1 No pool can form

83

Abo Homos-Nubaria Pipeline QRA

26.5.4 Dispersion
26.5.4.1 Dispersion Summary
Contour value (ppm)

47226.4

148597.8

Downwind distance (m)

2.132

0.501

Height above ground (m)

7.314

3.946

Mass in plume between specified limits = 11.89 kg


Volume of plume containing this mass = 11.01 m
Pollutant-only mass in this volume = 0.633 kg
Specified minimum = 4.723 vol%
Specified maximum = 100 vol%

26.5.4.2 Jet - side

Raw plot data

84

Abo Homos-Nubaria Pipeline QRA

26.5.4.3 Jet - top

Raw plot data


26.5.5 Warnings
1 - Temperature outside experimental range -5 to 15 C
2 - Pressure outside experimental range 0 to 20 bara
3 - Pressure downstream parameter has not been experimentally determined
4 - Warning: some vapour condenses - assume metastable flow
5 - Dew point calculation not possible at requested pressure
6 - Ambient temperature outside extrapolated range -5 to 30 C
7 - Ambient temperature outside experimental range 0 to 15 C
8 - Release height outside experimental range 0.5 to 100 m
9 - Contour value outside experimental range 0 to 35 kW/m2
10 - Ambient pressure parameter has not been experimentally determined
11 - Release height increased above surface roughness

85

Abo Homos-Nubaria Pipeline QRA

top

26.6 70Bar - Depressurization [10 Inch] - Vertical Release


26.6.1 Scenario Summary
26.6.1.1 Scenario
Scenario = 70Bar - Depressurization [10 Inch] - Vertical Release
Fluid = Natural gas

26.6.1.2 Process conditions


Calculate at = User input pressure
Temperature = 40 C
Pressure = 70 bara

26.6.1.2.1

Pressure downstream of release

Pressure = 1.013 bara


Use standard atmospheric pressure = yes

26.6.1.2.2

Release from

Release source = Vapour space

26.6.1.3 Hole & release geometry


26.6.1.3.1

Hole geometry

Failure type = Custom


Hole diameter = 0.254 m
Discharge coefficient = 0.8

26.6.1.3.2

Pipe

Pipe length = 0 m

26.6.1.3.3

Release

Release height = 0 m
Release angle from vertical = 0 deg
Release angle, clockwise from North = 0 deg

26.6.1.4 Weather
26.6.1.4.1

Ambient conditions

Temperature = 40 C
Relative humidity = 75 %
Wind speed = 10 m/s
Direction wind is going to = 0 deg
(measured clockwise from North)

26.6.1.4.2

Atmospheric stability conditions

86

Abo Homos-Nubaria Pipeline QRA


Define by = Pasquill class
Pasquill class = D Neutral

26.6.1.5 Thermal radiation


Radiation contours = 1.58, 4.73, 6.31, 9.46, 37.5 kW/m
Height at which plan view contours to be plotted = 0 m
Cross flame distance at which side view contours to be plotted = 0 m

26.6.1.6 Dispersion
Surface roughness = 0.1 m
Contours to plot:
47226.4 ppm 148597.8 ppm
Plot type = LFL/UFL
Sampling time = Instantaneous

26.6.1.7 Release summary


Mass flow rate = 563 kg/s
Flux = 11110.9 kg/m/s
Static exit pressure = 35.59 bara
Exit temperature = -55.14 C
Exit density = 35.6 kg/m
Exit velocity = 312.1 m/s
Residence time = 0 s
Vapour fraction at exit = 1 mol/mol
Expanded exit velocity = 623.4 m/s
Air equivalent source diameter = 0.9789 m

26.6.1.8 Release Composition


Molecular Weight of Release = 18.13 kg/kmol
Component

Weight
Fraction
norm

Mole
Fraction
norm

Critical
Temp C

Critical
Pressure
bara

Molecular
Weight
kg/kmol

n-Butane

0.0321

0.0100

152.1

37.41

Propane

0.0487

0.0200

96.7

41.91

44.1

Ethane

0.0829

0.0500

32.18

48.08

Methane

0.7966

0.9000

-82.6

Nitrogen

0.0155

0.0100

Carbon
dioxide

0.0243

0.0100

Atmos
BP C

58.12 -0.5001

Freeze
Pt C

Heat of
Comb
kJ/kg

-138.4

45742.7

-42.1

-187.7

46383.8

30.07

-88.6

-182.8

47514.8

45.35

16.04

-161.5

-182.5

50043.9

-146.9

33.56

28.01

-195.8

-210

31.06

72.86

44.01

-86.9

-56.6

26.6.1.9 Reservoir summary (at reservoir pressure)


Bubble point temperature = n/a
Dew point temperature = n/a
Vapour fraction = 1

26.6.1.9.1 Properties of phases


Vapour

87

Liquid

Abo Homos-Nubaria Pipeline QRA

Molecular weight (kg/kmol)

18.13

Density (kg/m)

55.5

Enthalpy (kJ/kmol)

193.3

Entropy (kJ/kmol*K)

-29.46

Cv (kJ/kg*K)

1.725

Cp (kJ/kg*K)

2.627

Sound velocity (m/s)

414.8

Viscosity (e-3 kg/m*s)

0.01354

Surface tension (e-3 N/m)

26.6.2 Jet Fire


26.6.2.1 Jet Fire Summary
Flame length (of frustum) = 93.64 m
Cone width of flame base = 13.92 m
Cone width of flame end = 32.85 m
Flame lift-off = 48.72 m
Flame angle from vertical = 25.48 deg
Flame angle, clockwise from North = 0 deg
Surface emissive power = 251.1 kW/m
Fraction of heat radiated = 0.07427
Total combustion power = 26759.2 MW
Heat of combustion = 47529.6 kJ/kg

88

Abo Homos-Nubaria Pipeline QRA

26.6.2.2 Side view

Raw plot data


26.6.2.3 Top view

Raw plot data

89

Abo Homos-Nubaria Pipeline QRA

26.6.2.4 Impingement

Raw plot data


26.6.3 Pool Chart
26.6.3.1 No pool can form

90

Abo Homos-Nubaria Pipeline QRA

26.6.4 Dispersion
26.6.4.1 Dispersion Summary
Contour value (ppm)

47226.4

148597.8

Downwind distance (m)

22.47

5.786

Height above ground (m)

57.4

32.56

Mass in plume between specified limits = 9022.8 kg


Volume of plume containing this mass = 8377.5 m
Pollutant-only mass in this volume = 492.5 kg
Specified minimum = 4.723 vol%
Specified maximum = 100 vol%

26.6.4.2 Jet - side

Raw plot data

91

Abo Homos-Nubaria Pipeline QRA

26.6.4.3 Jet - top

Raw plot data


26.6.5 Warnings
1 - Temperature outside experimental range -5 to 15 C
2 - Pressure outside experimental range 0 to 20 bara
3 - Pressure downstream parameter has not been experimentally determined
4 - Warning: some vapour condenses - assume metastable flow
5 - Dew point calculation not possible at requested pressure
6 - Ambient temperature outside extrapolated range -5 to 30 C
7 - Mass flow rate outside extrapolated range 0 to 100 kg/s
8 - Ambient temperature outside experimental range 0 to 15 C
9 - Release height outside experimental range 0.5 to 100 m
10 - Mass flow rate outside experimental range 0 to 30 kg/s
11 - Contour value outside experimental range 0 to 35 kW/m2
12 - Ambient pressure parameter has not been experimentally determined
13 - Release height increased above surface roughness

92

Abo Homos-Nubaria Pipeline QRA

top

26.7 Explosion [Confined space]


26.7.1 Scenario Summary
26.7.1.1 Scenario
Scenario = Explosion [Confined space]
Fluid = Methane

26.7.1.2 Congested region


Region size, m

Number of grids

Blockage ratio

Length

10

0.3

Width

10

0.3

Height

Complexity level = 3
With roof = yes
Partially filled = no
Angle of congested region length = 0 deg
(measured clockwise from North)
26.7.1.3 Pulse at a distance from edge of congested region
Distance = 10 m
Overpressure = 0.038 bar
Duration = 62.9 ms
Rise time = 40.3 ms

26.7.1.4 Source properties


Overpressure = 0.07719 bar
Radius = 7.763 m

26.7.1.5 Response at distances from edge of congested region


Distance to 50% window breaking (0.020 bar) = 24.2 m
Distance to glass damage causing injury (0.050 bar) = 6.2 m
Distance to repairable damage to buildings (0.100 bar) = 0.0 m
Distance to heavy damage buildings/plant (0.340 bar) = 0.0 m

26.7.1.6 Custom Contour Values


Overpressure (mbar)

Distance (m)

25

18.21

50

6.222

100

93

Abo Homos-Nubaria Pipeline QRA

300

500

26.7.1.7 Exceedance Fuel


Equivalant exceedance fuel = Methane
Fuel Factor = 0.6034

26.7.2 Pressure Decay with Distance Chart


26.7.2.1 Overpressure

Raw plot data


26.7.3 Warnings
1 - Congested region length outside experimental range 1 to 8 m
2 - Congested region width outside experimental range 1 to 8 m
3 - Congested region height outside experimental range 1 to 4 m
4 - Number of grids for length outside experimental range 4 to 30
5 - Number of grids for width outside experimental range 4 to 30
6 - Requested contour is greater than source pressure

94