Sei sulla pagina 1di 4

F6TesT

Impedance Relay Timing Test Report

13-Aug-16

132KV LINE \ GE MULTILIN D60


Location Path

132KV LINE

Test and Test Definition Information

Test Plan Name

Relay Testing

Test Name

SHOT TEST

Test Type

Z-Time

Test Definition Name

test

Tested Date

8/13/2016

Tested By

User

Evaluation

Pass

Test Definition Description


Relay Under Test General Parameters

Relay Name

GE MULTILIN D60

Serial Number

D60-J03-HKH-F8L-H6D

Manufacturer

GE

Nominal Ratings:

fn

Model
50.000 Hz
110.00 V (Ph-Ph)
1.000 A

Vn
In
VTR

1200 : 1

Station Name

Pedawaltiar

D60

Max Test Current

2000.000% In
1000.00% Vn

Max Test Voltage

A-B-C

Phase Names And Rotation


CTR

300 : 1

Protected Object Parameters

Protected Object Name

132KV Line

Protected Object Parameters


Relay Functions

Function Name

SHOT TEST

Function Type

Display values in

Secondary

Inherent Op Time

Impedance
1.0ms

General Tolerances

Absolute Minimum

3.000 Ohm

Absolute Minimum Time

20.0 ms

Zone Elements
Zone Name

Char Type

Fault
Type

Characteristic
Angle

t nom
[ms]

Residual Compensation

Z tol

t tol

-%

+%

-%

+%

Zone1

General

Ph-N

60.00

40 Z0/Z1

1.25 -17.00

10.00

10.00

10.00 10.00

Zone2

General

Ph-N

60.00

340 Z0/Z1

1.25 -17.00

10.00

10.00

10.00 10.00

Zone3

General

Ph-N

60.00

640 Z0/Z1

1.25 -17.00

10.00

10.00

10.00 10.00

Zone4

General

Ph-N

60.00

1240 Z0/Z1

1.25 -17.00

10.00

10.00

10.00 10.00

Relay Triggers
Signal Name

Inp 1

F6
Input
No
LN1

Inp 2

LN2

Sense
Condition

Relay OutPut
Name

Terminal

Impedance Relay Timing Test Report


132KV LINE \ GE MULTILIN D60
F6000 Instrument HW and SW Information

F6TesT Software Version

3.10.2 Build 1234

F6000 Model Number

F6150

F6000 CPU ID

67193873

F6000 Firmware Version

4.29.4

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2
F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support

13-Aug-16

Impedance Relay Timing Test Report

13-Aug-16

132KV LINE \ GE MULTILIN D60


Test Configuration

Prefault Voltage

110.00

Prefault Current

0.000

Test Method

Angle

0 Deg

Constant Current

Desired Test Current

Max Acceptable Voltage

90 % of rating

dc transient, fault inception angle


Minimum Offset
Time constant L/R
Values are in

0.00 ms

CT direction

Towards Line

Secondary
Trigger Selection

Test Timing

Prefault Duration
Max. Fault Duration
Max Fault Duration For Faster Zones
CBTripTime
Time between shots

700.0 ms

Fault Type

1300.0 ms

AN

LN1 0->1

BN

LN1 0->1

CN

LN1 0->1

x Tmax
0.0 ms
100.0 ms

AB
BC
CA
ABC

Trigger

Impedance Relay Timing Test Report

13-Aug-16

132KV LINE \ GE MULTILIN D60


Fault Type

AN

Angle

[]

[]

%Zone

Zone

t exp

t act

[ms]

[ms]

Eval

t min

t max

Err

[ms]

[ms]

[%]

V
Test

I
Test

[V]

[A]

0.173

77.65

49.70

Zone1

40.0

45.1

Pass

20.0

60.0

12.75

0.93

5.000

0.494

76.64

76.00

Zone2

340.0

348.0

Pass

306.0

382.1

2.35

2.65

5.000

2.731

76.43

37.50

Zone4

1240.0

1231.2

Pass

1116.0

1364.0

-0.71

14.64

5.000

1.286

339.70

88.20

Zone1

40.0

38.9

Pass

20.0

269.0

-2.75

6.89

5.000

2.536

340.40

92.60

Zone2

340.0

337.2

Pass

306.0

704.0

-0.82

13.59

5.000

1.264

319.60

86.50

Zone1

40.0

40.0

Pass

20.0

212.5

0.00

6.78

5.000

2.535

318.40

92.20

Zone2

340.0

333.3

Pass

306.0

704.0

-1.97

13.59

5.000

3.644

317.00

89.90

Zone3

640.0

633.9

Pass

576.0

1000.4

-0.95

19.53

5.000

0.591

346.50

53.90

Zone1

40.0

36.8

Pass

20.0

60.0

-8.00

3.17

5.000

1.822

76.52

25.00

Zone4

1240.0

1230.7

Pass

1116.0

1364.0

-0.75

9.77

5.000

6.358

76.17

87.40

Zone4

1241.0

1244.9

Pass

1054.9

1442.5

0.31

34.08

5.000

1.729

110.20

63.10

Zone4

1241.0

1234.0

Pass

1054.9

1427.2

-0.56

9.27

5.000

4.611

53.43

66.00

Zone4

1241.0

1232.4

Pass

1116.9

1365.1

-0.69

24.72

5.000

4.046

15.82

42.50

Zone4

1241.0

1233.5

Pass

1116.9

1365.1

-0.60

21.69

5.000

5.687

106.60

0.00

NoOp

NoOp

Pass

NoOp

NoOp

30.48

5.000

13.267

33.70

0.00

NoOp

NoOp

Pass

NoOp

NoOp

57.16

4.019

5.163

248.20

0.00

NoOp

NoOp

Pass

NoOp

NoOp

27.67

5.000

13.374

339.50

0.00

NoOp

NoOp

Pass

NoOp

NoOp

57.16

3.987

Fault Type