Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
No.
MANUFACTURER
TYPE OF EQUIPMENT
EQUIPMENT DESIGNATION
SERIAL NUMBER
CALIBRATION DUE DATE.
USING FOR TEST
No.
MANUFACTURER
TYPE OF EQUIPMENT
EQUIPMENT DESIGNATION
SERIAL NUMBER
CALIBRATION DUE DATE.
USING FOR TEST
Reyrolle
Designation
Serial No.
Model No.
Aux. Voltage
No. of Contacts
Description
Inspect for any physical damage or defects.
Verify connections as per approved drawings.
Check that serial no. of relay matching with serial no. of case.
RelayCT shorting function checked.
Test switch checked for correct function.
Tested:
Witnessed
KAHRAMAA
Name
Name
Signature
Signature
Date
Date
Page 1 of 3
Checked
3. ELECTRICAL TESTS:
3.1 PICK UP TEST:
In = 5A
Mode: Solkor R
Calculat
ed Value
(A)
Pick-up (A)
DC Current
At Test point
(mA dc)
Reset (A)
Pilot Voltage
At terminal
17 and 18
(V ac)
RN
0.721 A
YN
0.923 A
BN
1.212 A
R-Y
3.608 A
Y-B
3.608 A
B-R
1.789 A
3.2. PILOT TERMINAL VOLTAGE TEST @ 5A
Fault
Injected
Current
R-N
5A
Y-N
5A
B-N
5A
R-Y
5A
Y-B
5A
B-R
5A
DC Current
At Test point
(mA dc)
Pilot Voltage
At terminal 17
and 18 (V ac)
Flag operation
Current = 2 x
Pick-up(A)
R-N
1.442
Typical Time
(mS)
60
Y-N
1.846
60
B-N
2.424
60
R-Y
7.216
60
Y-B
7.216
60
B-R
3.578
60
Measured Time
(mS)
Tested:
Witnessed
KAHRAMAA
Name
Name
Signature
Signature
Date
Date
Page 2 of 3
RelayTerminal no.
1and 3
Output-RL
2 and 4
6 and 8
5. FUNCTIONAL TEST:
Item
Description
Checked
1
2
3
Tested:
Witnessed
KAHRAMAA
Name
Name
Signature
Signature
Date
Date
Page 3 of 3