Question
HowdoIconfigureorsetupaPowerFlex753orPowerFlex755driveonacentrifugalfanorpumpmotorapplication?
Arethererecommendedsettingsforthisapplication?
Whydoesthemotorsometimesfirststartinthereversedirectiononalargeinertiaload?

Environment
20FPowerFlex753
20GPowerFlex755

Answer
Pumpsarenotusuallyheavydutyapplications.Experienceshowsthatdrivesleftinthefactorydefaultcontrolmode(sensorlessvectorcontrol)
sometimesdonotwanttoacceleratefansorpumpsabove2to3Hz.

Thiscanbecausedbyseveralthings,autotuningnotexecutedordonesoincorrectly,wrongmotordataetc.Aquickandeasyfixistosetthe
driveinaV/Hzregulationmethod.Thisisanidealcontrolmethodforcentrifugaltypeloads.

Findbelowatablewithsomebestpracticesettings.Othercommonparameterslikemotornameplatedataarenotmentionedbutneedtobe
enteredaspartofthestartup.

Parameter
Definition
#

Bestpracticesetting Comment

35

MotorControl
Mode

0=InductionVHz

65

VHzCurve

Custom

orFanpump(inthiscaseP6263notneeded)

62

BreakVoltage

140V

Assuming400VmotorDependingonfanorpumpcurve

63

BreakFrequency 25Hz

306

Dutyrating

NormalDuty

356

FlyingStart

Enhanced

422

Currentlimit1

setto130%ofmotor
FLA

Assuming50Hzmotordependingonfanorpumpcurvenormallykeepbelowminimum
runningspeed

DefaultSetting
Ifstartingintorotatingfan,mustbeset

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982

1/3

13/11/2015

486982PowerFlex750Series:CentrifugalFan/PumpSetupGuide

535

AccelTime1

setsubjecttoinertia

537

DecelTime1

setsubjecttoinertia

621

SlipRPMatFLA 0

setsonocurrentlimitappears

SetParameter70toReadyinordertochange.

DISCLAIMER
Thisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjectorsubjectsandisnotanexhaustive
treatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteisnotintendedtoconstituteapplication,design,softwareorother
professionalengineeringadviceorservices.Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshould
consultaqualifiedprofessionaladvisor.
ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACYOFANYOFTHEDATACONTAINED
INTHISWEBSITEANDMAYMAKECHANGESTHERETOATANYTIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALL
INFORMATIONCONVEYEDHEREBYISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGES
OFANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,EVENIFROCKWELL
AUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.
ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDINRESPECTOFTHEINFORMATION
(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHEIMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,
MERCHANTABILITY,ANDNONINFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,
thisdisclaimermaynotapplytoyou.

ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982

2/3

13/11/2015

486982PowerFlex750Series:CentrifugalFan/PumpSetupGuide

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982

3/3

Potrebbero piacerti anche