Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
com
I N T R O D U C T IO N
An
na
ni
pd
at
es
UNIT I
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
An
na
ni
pd
at
es
www.annaunivupdates.com
Magnetic Circuits
H.dl = J.da
Amperes law
www.annaunivupdates.com
magnetic flux density is conserved
B.da = 0
J : current density.
B = mH
pd
at
es
m r : relative permeability
Ni F
f = B.da
H. dl = J.da =
ni
(Weber, Wb)
fc : flux in core,
fc @ Bc Ac
@ Hc lc
An
H.dl
na
f
=
Bc
lc = Ni = F
m
lc
m Ac
: reluctance
f
lc = F
m Ac
www.annaunivupdates.com
Bc =
f
Ac
Bg =
f
Ag
mmf
H.dl
= Hc lc + H g g = Ni = F
F=
F = f(c + g )
f=
m0 Ag
Bg
Bc
lc +
g=f
l
g
m c m0
m Ac
ni
pd
at
es
F
+
c : reluctance of core, g : reluctac nce og f air-gap.
An
na
Example 1.1 The magnetic circuit shown in Fig.1.2 has dimensions Ac = Ag = 9 cm2, g = 0.050
cm, lc = 30 cm, and N = 500 tums. Assume the value mr = 70,000 for core material. (a) Find the
reluctances c and g . For the condition that the magnetic circuit is operating with Bc = 1.0 T,
find (b) the flux f and (c) the current i.
Solution:
(a)
(b)
(c)
c =
lc
0.3
=
= 3.79 103 A.turns/Wb
mr m0 Ac 70000 4p 10-7 9 10-4
g =
g
5 10-4
=
= 4.42 105 A.turns/Wb
m0 Ac 4p 10-7 9 10-4
f = Bc Ac = 1.0(910-4) = 910-4 Wb
i=
www.annaunivupdates.com
at
es
Example 1.2 The magnetic structure of a synchronous machine is shown schematically in Fig.
1.5. Assuming that rotor and stator iron have infinite permeability (m ), find the air-gap flux
f and flux density Bg. For this example I = 10 A, N = 1000 turns, g = 1 cm, and Ag = 2000 cm2.
Nim0 Ag
F
f=
=
m0 Ag =
Rg
2g
f
0.13
Bg =
=
= 0. 65 T
Ag
0. 2
2g
1000 10 4p
= 0.13 Wb
2 0.01
10-7 0.2
An
na
ni
Rg =
pd
Solution: total air-gap length = 2g. Reluctance of iron core is negligible ((m ).
E. ds
Faradays law.
dl
df
e=
=N
dt
dt
= - d B.da
dt
S
e : induced voltage,
L=
l
i
NF
l = Nf =
Rtot
=
N 2i
Rtot
L=
N2
Rtot
N2
g
m0 Ag
www.annaunivupdates.com
(Henry, Weber-turn /A)
N 2 m0 Ag
Example 1.3
The magnetic circuit of Fig. 1.6a consists of an N-turn winding on a magnetic core of infinite
permeability with two parallel air gaps of lengths g1 and g2 and areas A1 and A2, respectively.
Find
(a) The inductance of the winding and
(b)The flux density Bl in gap 1 when the winding is carrying a current i. Neglect fringing effects
at the air gap.
R1 R2
g2
m0 A2
A A
= m0 N 2 1 + 2
g1 g 2
B1 =
f1 m0 Ni
=
A1
g1
ni
Ni m0 A1 Ni
=
R1
g1
R2 =
f1 =
N 2 (R1 + R2 )
g1
m0 A1
na
(b)
R1 =
pd
L=
R1R2
R1 + R2
Req =
An
(a)
at
es
Solution:
www.annaunivupdates.com
at
es
F = N1i1 + N 2i2
Neglect the reluctance of the core, and assume Ac = Ag, the resultant core flux produced by the
total mmf is
F
N i + N 2i2
m A
= 11
=g( N 1i1 + N 2i2 ) 0 c
Rg
m0 Ac
pd
f=
m0 Ac
+ N1 N 2
g
m0 Ac
i1
i2
ni
l1 = N1f = N12
l1 = L11i1 + L12i2
na
m0 Ac
L11 = N1 2
g
An
L12 = N1 N 2
m0 Ac
g
: self-inductance of coil 1
l2 = N 2f = N1 N 2
m0 Ac
g
i1
m0 Ac
+ N2
g
i2
l2 = L21i1 + L22i2
L21 = L12 = N1 N 2
m0 Ac
g
: mutual-inductance,
m A
L22 2= N 20 c
g
: self-inductance of coil 1
www.annaunivupdates.com
An
na
ni
pd
at
es
e=
dl d
di
dL
= (Li) = L + i
dt
dt
dt
dt
www.annaunivupdates.com
dl
dt
Change in magnetic stored energy DW in the magnetic circuit in the time interval tl to t2
DW =
t2
l2
t1
l1
p dt = i dl
l2
l2
DW = i dl =
=
l
l
1
1
l2
1
(l 2 - l12 ) W (l ) =
or W (i) = Li 2
2L 2
2L
2
dl
pd
at
es
Single- winding s ystem of constant inductance, the change in magnetic stored energy as the flux
level is changed from l1 to l2
Example 1.6
L=
l Nf
=
i
i
Bc = 1.0 T
F = Ni L =
i = 0. 8 A
N2
5002
=
= 0 .5 6 H
c + g 4.46 105
1
2
1
2
W = Li 2 = (0.56)(0.82 ) = 0.18 J
dl
df
= 500 9 10-4 (377 1.0 cos(377t) )
= N dB = NAc
c
dt
= 170 cos(3d7t 7t) V dt
e=
An
(c)
F
c + g
na
f=
(a)
ni
For the magnetic circuit of Example 1.1 (Fig. 1.2), find (a) the inductance L, (b) the magnetic
stored energy W for Bc = 1.0 T, and (c) the induced voltage e for a 60-Hz time-varying core flux
of the form Bc = 1.0 sin(t) T where = 2f = 2(60) = 377 rad/sec.
Magnetic materials are used to constrain and direct magnetic fields in well-defined paths.
In a transformer they are used to maximize the coupling between the windings, and to
lower the excitation current required for transformer operation.
In electric machinery, they are used to shape the magnetic fields to obtain desired
electrical and mechanical characteristics.
Ferromagnetic materials are composed of iron and alloys of iron with cobalt, tungsten, nickel,
aluminum, and other metals, are the most common magnetic materials.
Relationship between B and H for a ferromagnetic material is nonlinear and multivalued: B-H
curve or hysteresis loop.
pd
at
es
www.annaunivupdates.com
An
na
ni
B-H loops for M-5 grain-oriented electrical steel 0.012 in thick. Only the top halves of the
loops are shown here.
AC EXCITATION
Sinusoidal core flux:
www.annaunivupdates.com
Emax = wNfmax = 2p fNAcBmax
Erms =
Emax
2
1
T
(t)dt
= wNfmax = 2p fNAcBmax
Exciting current: current required to produce magnetic flux in the core; nonsinusoidal because
of the nonlinear magnetic properties of the core.
at
es
pd
1-) Eddy currents: currents induced by the time-varying flux in the core due to nonzero
conductivity of the material. These currents cause ohmic I2R loss.
To reduce the effects of eddy currents, magnetic structures are built of thin sheets of
laminations of the magnetic material. These laminations are aligned in the direction of the field
lines, and are insulated from each other by an oxide layer.
ni
2-) Hysteresis loop: The time-varying excitation causes the magnetic material to undergo a cyclic
variation described by a hysteresis loop.
Energy input W to the magnetic core of Fig. 1.1 as the material undergoes a single cycle
An
na
H c lc ( A
i dl
NdBc ) = Aclc H dBc
W=
j
N c
=
Aclc : volume of the core.
H dBc : area of the ac hysteresis loop.
c
www.annaunivupdates.com
An
na
ni
pd
at
es
Excitation phenomena. (a) Voltage, flux, and exciting current; (b) corresponding
hysteresis loop.
at
es
www.annaunivupdates.com
An
na
ni
pd
Core loss at 60 Hz in watts per kilogram for M-5 grain-oriented electrical steel 0.012 in thick.
Voltage induced
dj
dB
1 m2
= NAc c = 200 4 in2 0.94
1.5 377 cos(377t)
2
dt
dt
39.4 in
= 274 cos(377t) V
e=N
b.
Bmax = 1.5 T
H max = 36 A-turns/m
lc = 0.71 m.
peak current I =
Bmax = 1.5 T
Pa = 1.5 VA/kg
H max lc 36 0.71
= 0.13 A.
=
N
200
www.annaunivupdates.com
Ij,rms =
Pa
20
= 0.10 A
=
Erms 275 / 2
1.1 A magnetic circuit with a single air gap is shown in Fig. 1.24. The core dimensions are:
Cross-sectional area Ac = 1.8 10-3 m2
Mean core length lc = 0.6 m
at
es
ni
pd
N = 83 turns
Assume that the core is of infinite permeability ( m ) and neglect the effects of fringing fields
na
at the air gap and leakage flux. (a) Calculate the reluctance of the core Rc and that of the gap R g .
An
For a current of i = 1.5 A, calculate (b) the total flux f, (c) the flux linkages of the coil, and (d)
the coil inductance L.
Solution:
(a)
Rc = 0 since m
(b)
f=
(c)
l = Nf = 1.016 10-2 Wb
(d)
L=
Rg =
g
2.3 10-3
=
= 1.017 106 A/Wb
m0 Ac 4p 10-7 1.8 10-3
Ni
83 1.5
=
= 1.224 10-4 Wb
Rc + Rg 1.017 106
l 1.016 10-2
=
= 6.773 mH
i
1.5
1.3 Consider the magnetic circuit of Fig. 1.24 with the dimensions of Problem 1.1. Assuming
infinite core permeability, calculate (a) the number of turns required to achieve an inductance of
12 mH and (b) the inductor current which will result in a core flux density of 1.0 T.
Solution:
(a)
www.annaunivupdates.com
L=
N2
= 12 10-3 mH
Rg
N = 110 turns
(b)
Bc = Bg = 1.0 T
i=
f = Bg Ac = 1.8 10 -3 Wb
l Nf 110 1.8 10 -3
=
= 16.5 A
=
L
L
12 10 -3
at
es
lc = 15 cm
g = 0.8 mm
pd
N = 480 turns
An
na
ni
Neglecting leakage and fringing and assuming mr = 1000 , calculate the inductance.
Solution:
L=
l
i
l = Nf = NBc Ac
mmf equation:
Bc = Bg
H clc + H g lg = Ni
Bc =
m0 Ni
g + ( lc / m r )
Bc
Bg lc +
g = Ni
m r m0
m0
L=
m 0 N 2 Ac
4p 10 -7 480 2 10 -4
=
= 30.477 mH
g + ( lc / m r ) [ 0.08 + (15 / 1000) ] 10 -2
1.14 The inductor of Problem 1.13 is to be operated from a 60-Hz voltage source. (a) Assuming
negligible coil resistance, calculate the rms inductor voltage corresponding to a peak core flux
density of 1.5 T. (b) Under this operating condition, calculate the rms current and the peak stored
energy.
www.annaunivupdates.com
Solution:
(a)
dl
dB
= NAc c Bc = Bmax sinwt v(t) = wNAcBmax coswt
dt
dt
1
1
(2p 60) 480 10-4 1.5 = 19.2 V
Vrms =
wNAcBmax =
2
2
(b)
Vrms
= 1.67 A
wL
Wpeak =
1 2
1
LI peak = 30.477 10-3 ( 2 1.67)2 = 85.0 mJ
2
2
pd
I rm s =
at
es
v(t) =
ni
1.16 A square voltage wave having a fundamental frequency of 60 Hz and equal positive and
negative half cycles of amplitude E is applied to a 1000-turn winding surrounding a closed
iron core of 1.25 x 10-3m2 cross section. Neglect both the winding resistance and any effects
of leakage flux.
(a) Sketch the voltage, the winding flux linkage, and the core flux as a function of time.
(a)
An
na
(b) Find the maximum permissible value of E if the maximum flux density is not to
exceed 1.15 T.
E
m ax
voltage
t
max
www.annaunivupdates.com
(b)
dl
l - (-lmax )
l e(t).dt E = max
= 4 f lmax = 4 fNfmax = 4 fNAcBmax
dt =
T /2
E = 4 60 1000 1.2510-3 1.15 = 345 V
e(t) =
at
es
1.24 The reciprocating generator of Fig. 1.34 has a movable plunger (position x) which is
supported so that it can slide in and out of the magnetic yoke while maintaining a constant air
gap of length g on each side adjacent to the yoke. Both the yoke and the plunger can be
considered to be of infinite permeabilit y. The motion of the plunger is constrained such that its
position is limited to 0 x w .
pd
There are two windings on this magnetic circuit. The first has N1 turns and carries a constant
dc current I0. The second, which has N2 turns, is open-circuited and can be connected to a load.
An
na
this motion.
ni
where
generated as a result of
x(t) =
(a) Neglecting any fringing effects, find the mutual inductance between windings 1
and 2 as a function of the plunger position x.
(b) The plunger is driven by an external source so that its motion is given by
(a)
L21 = N1 N 2
(b)
v2 =
dl2
dt
m0 Ac( x)
2g
Ac(x) = D(w - x)
l2 = L21i1 v2 = I 0
dL21
dL21 dx
m N N D dx
= I0
. = -I 0 0 1 2 .
dt
dx dt
2g
dt
m N N Dwe w cosw t
dx 1
= we wcosw t v2 = -I 0 0 1 2
dt 2
4g
An
na
ni
pd
at
es
www.annaunivupdates.com
UNIT II
www.annaunivupdates.com
TRANSFORMERS
An
na
ni
pd
at
es
Working Principle
N1
df
dt
E2
-N2
df
dt
Therefore
E2 N2
=
= K where K is known as voltage transformation ratio.
E1 N1
www.annaunivupdates.com
Ideal Transformer
at
es
pd
1. no winding resistance
2. no leakage flux
3. no iron loss.
EMF Equation of a Transformer
ni
df
df
= -N1 m sinwt
dt
dt
= - N1 m Cost
An
na
e1= -N1
=-2 f N1 m Cost
= 2 f N1 m sin(t-90)
It is clear from the above equation that maximum value of induced emf in the primary is
Em1=2 f N1 m
the rms value E1=Em1/ 2
= 4.44 f N1 m
E2=4.44 f N2 m
Transformer Construction
The main elements of a transformer are two windings and a core. The two coils are
insulated from each other as well as from the core. The core is constructed from laminations of
sheet steel or silicon steel assembled to provide a continuous magnetic path. Silicon steel offers
low hysteresis loss and the laminations minimizes eddy current loss. The laminations are
insulated from each other by a light coating of varnish. According to the core construction and
the manner in which the primary and secondary are placed around it, transformers are classified
as
www.annaunivupdates.com
at
es
1. core type
An
na
ni
pd
2. Shell type
LOSSES IN TRANSFORMER
Since iron core is subjected to alternating flux, there occurs eddy current and hysteresis loss in it.
These two losses together known as iron losses and core losses. Both hysteresis and eddy current
losses depends on maximum flux density Bm in the core and supply frequency f.
www.annaunivupdates.com
Iron loss
Copper Losses
`
The primary and secondary of the transformer have winding resistances of R1 and R2
respectively.
I12 R1 + I22 R2
at
es
Pi
+ Pc
ni
EFFICIENCY OF A TRANSFORMER
pd
=output power
na
Transformer Efficiency
An
Input power
= Pi
= Pc
= Pi + Pc
www.annaunivupdates.com
Power Transformer
Power Transformers are used in generating stations or sub stations for transforming
voltage at each end of transmission line. They are put in operation during load hours and thrown
off during light load hours. These transformers are designed to have maximum efficiency at or
near full load. Normally the power transformers are rated in MVA.
at
es
Distribution Transformer
pd
Distribution Transformers are used for stepping down the voltage to a standard voltage
and kept near or at the consumers premises.They are continuously in circuit whether they are
carrying any load or not. He core losses would occur for all tha time where copper losses occur
only when they are loaded. So they are designed to reduce the core losses compared to copper
losses. They must be designed for good all day efficiency and not for efficiency at full load.
ni
Instrument Transformer
na
Instrument transformers are used to extend the range of instruments for the measuring
purposes. They are of two types
An
pd
at
es
www.annaunivupdates.com
An
No-Load Conditions
na
ni
Figure 2.2 Cutaway view of self-protected distribution transformer t ypical of sizes 2 to 25 kVA,
7200:240/120 V. Only one high-voltage insulator and lightning arrester is needed because one
side of the 7200-V line and one side of the primary are grounded. (General Electric Company.)
Exciting current
winding
ij
e1 =
dl1
dj
= N1
dt
dt
Resistance drop is very small induced voltage e1 is very nearly equal to the applied voltage.
Hence, it is almost sinusoidal. Therefore, the flux is also sinusoidal.
dj
= wN1j max coswt
dt
V1
E1 @ V1 jmax =
2p
fN1
j = jmax sinwt e1 = N1
Rms value: E1 =
1
2p fN1j max = 2p fN1j max
2
The core flux is fixed by the applied voltage. The required exciting current is determined by the
magnetic properties of the core.
www.annaunivupdates.com
at
es
pd
Ic
Pc = E1 Ij cosq c
magnetizing component;
ni
Im :
An
na
dj
dt
v2 = e2 = N 2
dj
dt
www.annaunivupdates.com
v1 N1
=
v2 N 2
When a current in the secondary winding flows, the total mmf should be zero since the
reluctance of the core is very large.
N1i1 - N 2i2 = 0
Instantaneous power:
i1 N 2
=
i2 N1
pd
at
es
v1i1 = v2i2
ni
Figure 2.7 Three circuits which are identical at terminals ab when the transformer is ideal.
Example 2.2
An
na
The equivalent circuit of Fig. 2.8a shows an ideal transformer with an impedance R2 + j X2 = 1 +
j4 connected in series with the secondary. The tums ratio N1/N2 = 5:1. (a) Draw an equivalent
circuit with the series impedance referred to the primary side. (b) For a primary voltage of 120 V
rms and a short connected across the terminals A-B, calculate the primary current and the current
flowing in the short.
Figure 2.8 Equivalent circuits for Example 2.2. (a) Impedance in series with the secondary.
(b) Impedance referred to the primary.
www.annaunivupdates.com
ni
pd
at
es
I2 is the component of the primary current which exactly counteracts the mmf of the secondary
na
An
N1I j = N1I1 - N 2 I2
= N1(I j + I2 ) - N 2 I2
I2 =
N1I2 = N 2 I2
N2
I2
N1
The equivalent sinusoidal current Ij that represents the exciting current can be resolved into a
core-loss component Ic in phase with the emf 1 , and a magnetizing component Im lagging 1
by 90.
Rc : core-loss resistance
Lm : magnetizing inductance
magnetizing reactance: X m = 2p f Lm
Rc
excitation branch
www.annaunivupdates.com
na
ni
pd
at
es
1 N 1
=
2 N 2
X l2 =
N1
N2
Xl 2
An
N1
R2 =
R2
N2
N
V2 = 1 V2
N2
Example 2.3
A 50-kVA 2400:240-V 60-Hz distribution transformer has a leakage impedance of 0.72 + j0.92
in the high-voltage winding and 0.0070 + j0.0090 in the low-voltage winding. At rated
voltage and frequency, the impedance Zj of the shunt branch (equal to the impedance of Rc and
jXm in parallel) accounting for the exciting current is 6.32 + j43.7 when viewed from the lowvoltage side. Draw the equivalent circuit referred to (a) the high-voltage side and (b) the lowvoltage side, and label the impedances numerically.
www.annaunivupdates.com
ni
pd
at
es
An
Example 2.4
na
Consider the equivalent-T circuit of Fig. 2.11a of the 50-kVA 2400:240 V distribution
transformer of Example 2.3 in which the impedances are referred to the high-voltage side. (a)
Draw the cantilever equivalent circuit with the shunt branch at the high-voltage terminal.
Calculate and label Req and Xeq. (b) With the low-voltage terminal open-circuit and 2400 V
applied to the high-voltage terminal, calculate the voltage at the low-voltage terminal as
predicted by each equivalent circuit.
Req = 0.72 + 0.70 = 1.42
Xeq = 0.92 + 0.90 = 1.82
www.annaunivupdates.com
Zj
Vcd = 2400
Zj + Z l1
632 + j 4 3 7 0
2400
6
3
2
.7 2 + j 4 3 7 0 . 9 2
= 2399.4 + j0.315 V
Example 2.5
ni
pd
at
es
The 50-kVA 2400:240-V transformer whose parameters are given in Example 2.3 is used to step
down the voltage at the load end of a feeder whose impedance is 0.30 + j 1.60 . The voltage Vs
at the sending end of the feeder is 2400 V. Find the voltage at the secondary terminals of the
transformer when the load connected to its secondary draws rated current from the transformer
and the power factor of the load is 0.80 lagging. Neglect the voltage drops in the transformer and
feeder caused by the exciting current.
50000
= 20.83 A
2400
q = cos-1(0.8) = 36.87
na
I =
An
V = 2 3 2 8 .3 V
V2 + (R + jX )I = Vs = 2400d
N
V = 2 V =
V
N1
232.83
Short-Circuit Test
Z sc = R1 + jX l1 +
Zj (R2 + jX l 2 )
Zj + R2 + jX l 2
Zj R2 + jX l 2
Z sc R1 + jX l1 + R2 + jX l 2 = R eq + jX eq
V = V2
V
= sc
I sc
P
, Req = sc2
I sc
X eq =
www.annaunivupdates.com
Z eq - Req2
pd
at
es
Open-Circuit Test
Voc2
Poc
Zj =
ni
Rc =
Voc
I oc
Rc ( jX m )
Rc + jX m
Xm =
(1 / Z )
j
- (1 / Rc )
na
Zoc = Zj =
Figure 2.16 Equivalent circuit with open-circuited secondary. (a) Complete equivalent circuit.
(b) Cantilever equivalent circuit with the exciting branch at the transformer primary.
An
Example 2.6
With the instruments located on the high-voltage side and the low-voltage side short-circuited,
the short-circuit test readings for the 50-kVA 2400:240-V transformer of Example 2.3 are 48 V,
20.8 A, and 617 W. An open-circuit test with the low-voltage side energized gives instrument
readings on that side of 240 V, 5.41 A, and 186 W. Determine the efficiency and the voltage
regulation at full load, 0.80 power factor lagging.
From the short-circuit test,
Z eq,H =
48
617
= 2.31 W , R e q,H =
= 1. 42 W ,
20. 8
2 0 .8 2
IH =
50000
= 20. 8 A
2400
www.annaunivupdates.com
Total power supplied from high-voltage winding, Pin = Pout + Ploss = 40803 W
Efficiency =
Pout 40000
=
100 % = 98 %
Pin 40803
Voltage Regulation:
At full load, V2 = 24000 V,
at
es
2446 - 2400
100% = 1.92%
2400
na
ni
pd
Regulation =
An
Figure 2.19 Common three-phase transformer connections; the transformer windings are
indicated by the heavy lines. ( N1 / N 2 = a )
www.annaunivupdates.com
Example 2.8
Three single-phase, 50-kVA 2400:240-V transformers, each identical with that of Example 2.6,
are connected Y-D in a three-phase 150-kVA bank to step down the voltage at the load end of a
feeder whose impedance is 0.15 + j 1.00 /phase. The voltage at the sending end of the feeder is
4160 V line-to-line. On their secondary sides, the transformers supply a balanced three-phase
load through a feeder whose impedance is 0.0005 + j0.0020 D/phase. Find the line-to-line
voltage at the load when the load draws rated current from the transformers at a power factor of
0.80 lagging.
at
es
Threephase
load
LV feeder
pd
HV feeder
0.15+ j 1.0
1.42 + j 1.82
VH
0.15+ j 0.6
ni
Load
na
4160
3
= 2400 V line-to-neutral
An
4160
Zlv,H =
(0.0005 + j 0.0020) = 0.15 + j 0.60 W
240
Combined series impedance of the high- and low-voltage feeders referred to the high-voltage
side,
Z feeder, H = 0.30 + j1.6 W/phase-Y
The equivalent single-phase series impedance of the transformer is equal to the single-phase
series impedance of each single-phase transformer as referred to its high-voltage side
Z eq,H = 1.42 + j1.82 W/phase-Y
Therefore, the single-phase equivalent circuit for this system is identical to that in Example 2.5.
4160
www.annaunivupdates.com
V = 134 V line-to-neutral.
Actual quantity
Base value of quantity
Vbase
I base
VA base 1
(P,Q,VA) pu on base 2 = (P,Q,VA) pu on base 1
VA base 2
2
pd
Example 2.12
at
es
Vbase 1 VA base 2
(R, X , Z ) pu on base 2 = (R, X , Z ) pu on base 1
Vbase 2 VA base 1
X H = 3.75 W,
X m = 114 W,
X L = 0.040 W,
The equivalent circuit for a 100-MVA, 7.97-kV:79.7-kV transformer is shown in Fig. 2.22a. The
equivalent-circuit parameters are:
na
Base quantities:
ni
Note that the magnetizing inductance has been referred to the low-voltage side of the equivalent
circuit. Convert the equivalent circuit parameters to per unit using the transformer rating as base.
Rbase = X base =
Vb2ase
= 0.635 W
VAbase
HV side:
Rbase = X base =
An
LV side:
Vb2ase
= 6 3 .5 W
VAbase
XL =
XH =
0 .0 4 0
7.6 10-4
114
= 0.063 p.u., RL =
= 0.0012 p.u., X m =
= 180 p.u.
0 .6 3 5
0.635
0.635
3 .7 5
0.085
= 0.0591 p.u., RH =
= 0.0013 p.u.
6 3 .5
6 3 .5
pd
at
es
www.annaunivupdates.com
Example 2.13
na
Base values:
ni
The exciting current measured on the low-voltage side of a 50-kVA, 2400:240-V transformer is
5.41 A. Its equivalent impedance referred to the high-voltage side is 1.42 + j 1.82 . Using the
transformer rating as the base, express in per unit on the low- and high-voltage sides (a) the
exciting current and (b) the equivalent impedance.
(a)
(b)
2400
240
= 115.2 W, Z base,L =
= 1.152 W
20.8
208
An
Z base,H =
5 .4 1
= 0.026 p.u.
208
0.541
=
= 0.026 p.u.
20.8
Ij ,L =
Ij ,H
Z eq,H =
1.42 + j1.82
= 0.0123 + j 0.0158 p.u.
115.2
1
Z eq,L = 10 (1.42 + j1.82) = 0.0142 + j 0.0182 W
0.0142 + j0.0182
= 0.0123 + j0.0158 p.u.
Per-unit value Z eq,L =
1.152
Rc1 and X m )
E1 @ V1 . If this is true
www.annaunivupdates.com
connected across the supply voltage. Besides, the winding resistances and leakage reactances can
be lumped together. This equivalent circuit (Fig.3.12a) is frequently used to determine the
performance characteristics of a practical transformer.
Io
transformer (less than 5%). A further approximation of the equivalent circuit can be made b y
removing the excitation branch, as shown in Fig.3.12b. The equivalent circuit referred to side 2 is
An
na
ni
pd
at
es
www.annaunivupdates.com
example, a typical transformer may carry the following information on the nameplate: 10 kVA,
1100/ 110 volts. What are he meanings of these ratings? The voltage ratings in dicate that the
transformer has two windings, one rated for 1100 volts and the other for 110 volts. These
voltages are proportional to their respective numbers of turns, and therefore the voltage ratio also
represents the turns ratio (a = 1100/ 110 = 10). The 10 kVA rating means that each winding is
designed for 10 kVA. Therefore the current rating for the high-voltage winding is 10,000/ 1100 =
9.09 A and for the lower-voltage winding is 10,000/110 = 90.9 A. It may be noted that when the
rated current of 90.9 A flows through the lowvoltage winding, the rated current of 9.09 A will
flow through the highvoltage winding. In an actual case, however, the winding that is connected
at
es
to the supply (called the primary winding) will carry an additional component of current
pd
(excitation current), which is very small compared to the rated current of the winding.
The equivalent circuit model (Fig.3.12(a)) for the actual transformer can be used to predict the
and a = N1 / N 2
ni
If the complete design data of a transformer are available, these parameters can be calculated
(R1, R2 )
na
from the dimensions and properties of the materials used. For example, the winding resistances
can be calculated from the resistivity of copper wires, the total length, and the
An
number of turns of the winding and the reluctance of the magnetic path. The calculation of the
leakage inductance
(Ll )
complicated. However, formulas are available from which a reliable determination of these
quantities can be made.
These parameters can be directly and more easily determined by performing tests that involve
little power consumption. Two tests, a no-load test (or open-circuit test) and a short-circuit test,
will provide information for determining the parameters of the equivalent circuit of a transformer.
3.9.1 No-Load Test (Or Open-Circuit Test)
This test is performed by appl ying a voltage to either the high-voltage side or low-voltage
side, whichever is convenient. Thus, if a 1100/ 110 volt transformer were to be tested, the voltage
would be applied to the low-voltage winding, because a power supply of 110 volts is more
readily available than a supply of 1100 volts.
www.annaunivupdates.com
A wiring diagram for open circuit test of a transformer is shown in Fig.3.13a. Note that the
secondary winding is kept open. Therefore, from the transformer equivalent circuit of Fig.3.12a
the equivalent circuit under open-circuit conditions is as shown in Fig.3.12b. The primary current
is the exciting current and the losses measured by the wattmeter are essentially the core losses.
The equivalent circuit of Fig.3.13b shows that the parameters Rc1 and Xm1 can be determined
from the voltmeter, ammeter, and wattmeter readings.
Note that the core losses will be the same whether 110 volts are applied to the low-voltage
winding having the smaller number of turns or 1100 volts are applied to the high-voltage winding
at
es
having the larger number of turns. The core loss depends on the maximum value of flux in the
ni
pd
core.
An
na
(a)
(b)
Fig.3.13 No-load (or open-circuit) test. (a) Wiring diagram for open-circuit test. (b)
Equivalent circuit under open circuit
3.9.2 Short-Circuit Test.
This test is performed by short-circuiting one winding and applying rated current to the other
winding, as shown in Fig.3.14a. In the equivalent circuit of Fig.3.12a for the transformer, the
impedance of the excitation branch (shunt branch composed of Rc1 and X m1) is much larger than
www.annaunivupdates.com
the high impedance of the shunt branch can be neglected. The equivalent circuit with the
secondary short-circuited can thus be represented by the circuit shown in Fig.3.14b. Note that
since Zeq1 =
2
Req1
+ X eq21
through the windings. It is convenient to perform this test by applying a voltage to the
high-voltage winding.
As can be seen from Fig.3.14b, the parameters Req1 and Xeq1 can be determined from the
2
at
es
and X l1 = a X l 2 = X l 2 .
Note that because the voltage applied under the short-circuit condition is small, the core losses
are neglected and the wattmeter reading can be taken entirely to represent the copper losses in the
2
An
na
ni
pd
Fig.3.14 Short-circuit test. (a) Wiring diagram for short-circuit test. (b). Equivalent circuit at
short-circuit condition.
www.annaunivupdates.com
The following example illustrates the computation of the parameters of the equivalent circuit
of a transformer
Example 3.4 Tests are performed on a 1 f , 10 kVA, 2200/220 V, 60 Hz transformer and the
at
es
pd
(a) Derive the parameters for the approximate equivalent circuits referred to the low-voltage
side and the high-voltage side.
ni
(c) Determine the power factor for the no-load and short-circuit tests.
Solution:
Note that for the no-load test the supply voltage (full-rated voltage of 220V) is applied to the
na
low-voltage winding, and for the short-circuit test the supply voltage is applied to the
high-voltage winding with the low-voltage Equivale winding shorted. The ratings of the
An
V1(rated ) = 2200 V
V2(rated ) = 220 V
I1(rated ) =
100 00
= 4.55 A
2200
I 2(rated ) =
10000
= 45.5 A
220
The equivalent circuit and the phasor diagram for the open-circuit test are shown in Fig.3.15a.
V22
Power, Poc =
Rc2
Then
220 2
Rc2 =
= 484 W
100
I c2 =
www.annaunivupdates.com
220
= 0.45 A
484
I m2 =
X m2 =
V2
22
=
= 89.4 W
I m2 2.46
The corresponding parameters for the high-voltage side are obtained as follows:
a=
2200
= 10
220
at
es
Turns ratio
pd
The equivalent circuit with the low-voltage winding shorted is shown in Fig.3.15b.
= I12 Req1
Z eq 1 =
Then,
215
= 1 0 .4 W
4.55 2
na
Req1 =
Vsc1 150
= 32.97 W
=
I sc1 4.55
An
Then,
ni
Power Psc
X eq1 =
2
2
Zeq1
- Req1
= 31.3 W
at
es
www.annaunivupdates.com
pd
Fig.3.15
X eq1
a2
10 2
= 0.104 W
10.4
ni
a2
31.3
10 2
X eq2 =
Req1
= 0.313 W
na
Req2 =
An
The approximate equivalent circuits referred to the low-voltage side and the high-voltage
side are shown in Fig.3.15c. Note that the impedance of the shunt branch is much larger than
that of the series branch.
(b) From the no-load test the excitation current, with rated voltage applied to the low-voltage
winding, is:
I o = 2.5A
T hi s i s
2 .5
*100% = 5.5%
45.5
Power
volt ampere
100
= 0. 18 2
220 * 2.5
www.annaunivupdates.com
215
= 0.315
150 * 4.55
Example 3.5 Obtain the equivalent circuit of a 200/400-V, 50 Hz, 1 phase transformer
from the following test a :-O.C. test : 200 V, 0.7 A, 70W-on LV side
S.C. test : 15 V, 10 A, 85 W-on HV side
at
es
Calculate the secondary voltage when delivering 5 kW at 0.8 power factor lagging, the primary
voltage being 200 V.
pd
Solution:
Po = Vo I o * cosj o
ni
An
Then I c1
na
Then j o
Po
70
= 0.5
=
Vo I o 200 * 0.7
\ cosj o =
Rc1 =
Vo1 200
=
= 571.4 W
I c1 0.35
And
X m1 =
Vo1
200
= 330 W
=
I m1 0.606
Z eq2 =
V2sc 15
= = 1.5W
I 2sc 10
1
= *1.5 = 0.375W
www.annaunivupdates.com
2
Z eq1 = a * Z eq2
Also,
Then,
Req2 =
Req1 = a * Req2
1
= * 0.85 = 0.21 W
2
2
2
Zeq1
- Req1
= 0.3752 - 0.212 = 0.31 W
Xeq1 =
na
ni
pd
Then,
at
es
Then,
85
= 0.85 W
100
An
Fig.3.16
Output KVA =
real power
5
=
= 6.3 kVA
Power factor 0.8
Output current I 2
Now,
from
the
5000
= 15.6 A
0 .8 * 4 0 0
aproximate
V2 0 o = V1 d o - I 2 j
Then, V2
equivalent
circuit
refeared
* Z eq 2
to
secondery
V2 0o = 400d o - 23.418.17o
www.annaunivupdates.com
V2 and do
it need two
equations to get both of them. The above equation is a complex one so we can get two equations
out of it. If we equate the real parts together and the equate the imaginary parts:
So from the Imaginary parts:
( )
( )
Then, d
at
es
= 7.4o
pd
V2 = 374.5 V
ni
Then,
Example 3.6 A 50 Hz, 1 - f transformer has a turns ratio of 6. The resistances are 0.9 W,
na
0.03 W and reactances are 5W and 0.13 W for high-voltage and low-voltage, windings
respectively. Find (a) the voltage to be applied to the HV side to obtain full-load current of 200
An
Solution:
The turns ratio is
a=
N1
=6
N2
I1 =
I 2 200
=
= 33.33A
a
6
www.annaunivupdates.com
(a)
(b)
cosj =
Req1
Z eq 1
1.98
9. 88
= 0 .2
Example 3.7 A 1 phase, 10 kVA, ,500/250-V, 50 Hz transformer has the following constants:
at
es
pd
X m1 = 750
W.
Rc1 =
na
ni
What would be the readings of the instruments when the transformer is connected for the
O.C. Test:
I m1 =
I c1 =
An
Solution:
V1
500 2
=
= A
X m 750 3
V1
500 1
=
= A
Rc1 1500 3
2
1 2
Io = + = 0.745 A
3 3
No load primary input V1 * I c1
1
= 500 * = 167W
3
Instruments used in primary circuit are: voltmeter, ammeter and wattmeter, their readings
being 500 V, 0745 A and 167 W respectively.
S.C. Test
www.annaunivupdates.com
Suppose S.C. test is performed by short-circuiting the LV, winding i.e. the secondary so that
all instruments are in primary.
Zeq1 =
2
Req1
+ Xe2q1 = 2.22 + 0.82 = 2.341 W
Then Vsc
Power absorbed
at
es
Rated kVA
10000
=
= 20 A
Rated Pr imaryvoltage
500
pd
I1 =
An
3.10 Efficiency
na
ni
h=
h=
Pout
Pout
=
Pout + Losses Pout + Pc + Pcu
(3.14)
The copper loss can be determined if the winding currents and their resistances are known:
(3.16)
www.annaunivupdates.com
= I1 Req1 = I 2 Req2
at
es
Pout = V2 I 2 cosj 2
Therefore,
V2 I 2 cosj 2
V2 I 2 cosj 2 + Pc + I 22 Req2
h=
V2 * I 2 * cosj 2
*100
V2 * I 2 * cosj 2 + Pc + I 22 Req1
(3.17)
(3.18)
na
ni
* 10 0
pd
h=
An
dh
=0
dI 2
(3.19)
If this condition is applied to Eqn. (3.17) the condition for maximum efficiency is:
Pc = I 22 Req 2
(3.20)
That is, core loss = copper loss. For full load condition,
2
Pcu, FL = I 2,FL
Req 2
(3.21)
Let
x=
I2
I 2, FL
(3.22)
www.annaunivupdates.com
Pc = x 2 Pcu, FL
Then,
(3.23)
Pc
x=
Pcu, FL
(3.24)
at
es
dh
=0
dj 2
An
na
ni
pd
(3.25)
j 2 = 0 Then, cosj 2 = 1
www.annaunivupdates.com
Therefore, maximum efficiency in a transformer occurs when the load power factor is unity
(i.e., resistive load) and load current is such that copper loss equals core loss. The variation of
efficiency with load current and load power factor is shown in Fig.3.17.
Example 3.8 For the transformer in Example 3.4, determine
(a)
(b) Power output at maximum efficiency and the value of maximum efficiency. At what percent
at
es
Pout = V2 I 2 cosj 2 .
= 0.75 *10 000 * 0.6 = 4500W
(a )
pd
Solution:
Pcu = I12Req1
2
ni
Pc = 100W ,
na
An
h=
100
Then, I 2 =
0.104
P out
hmax
= 31 A
Pout hmax
hmax =
6820
* 100
6820 + 100 + 100
www.annaunivupdates.com
= 97. 15 %
output kVA=6.82 and Rated kVA=10
Then, h max occurs at 68.2% full load.
Anther Method
From Example 3.4
at
es
Pc
100
X = =
= 0.68
P
2
1
5
c
u
,
F
L
pd
Then
Pcu,FL = 215W
ni
20 A, 100 W
Example 3.9 Obtain the equivalent circuit of a 8kVA 200/400 V, 50 Hz, 1 phase
S.C. test : 20 V,
Calculate the secondary voltage when delivering 6 kW at 0.7 power factor laggi ng, the primary
na
An
Po = Vo I o * cosj o
Po
\ cosj o
=
Then j o
Vo I o
80
= 0.5
2 0 0 * 0 .8
Then I c1
Rc1 =
Vo1 200
=
= 500 W
Ic1 0.4
And
X m1 =
Vo1
I c1
200
= 288.675 W
0.69282
www.annaunivupdates.com
Also,
2
Psc = I 2sc
Req 2
Then,
Req 2 =
pd
= 0.25 W
20
2
Z eq2 2 - Req2
= 12 - 0.252 = 0.968246 W
X eq 2 =
I2 =
6000
= 21. 428 6 A
0.7 * 400
na
Output current
ni
Then,
100
at
es
V2sc 20
=
= 1W
I 2sc 20
Z eq2 =
An
V2 0 o = V1d o - I 2 j
Then,
* Z eq 2
V2 and do
it need two
equations to get both of them. The above equation is a complex one so we can get two equations
out of it. If we equate the real parts together and the equate the imaginary parts:
( )
( )
www.annaunivupdates.com
= 1.533
at
es
Then,
short-circuite
pd
ni
II. calculate applied voltage, voltage regulation and efficiency when the output is 10 A at 500
III. Maximum efficiency, at what percent of full load does this maximum efficiency occur? (At
An
na
IV. At what percent of full load does the effeciency is 95% at 0.8 power factor lagging.
Solution:
Po = Vo I o * cosj o
\ cosj o =
Then j o
Po
80
=
= 0.32
Vo I o 250 *1.0
Then Ic1
Rc1 =
Vo1 250
=
= 781.25W
Ic1 0.32
And
X m1 =
Vo1
250
= 314.35W
=
Im1 0.7953
www.annaunivupdates.com
I2 =
6000
= 12 A
500
It is clear that in this test instruments have been placed in the secondary i.e. high voltage
at
es
winding and the low-voltage winding i.e. primary has been short-circuited.
Now,
Then,
Req2 =
Then,
Then,
na
Also,
Zeq1 = a * Z eq2
1
= *1.667 = 0.4167W
2
ni
pd
V2 sc 20
=
= 1.667W
I 2sc 12
Z eq 2 =
An
100
= 0.694 W
12 2
2
Req1 = a * Req2
1
= * 0.694 = 0.174 W
2
2
X eq1 = Ze2q1 - Req1
= 0.41672 - 0.1742 = 0.3786 W
As shown in the following figure, these values refer to primary i.e. low-voltage side
j0.3786 0.174
I0
www.annaunivupdates.com
V2
V1
314.35
781.25
The parameters of series branch can be obtained directly by modifying the short circuit test data
to be referred to the primary side as following:
SC test 20 V ; 12 A, 100 W (refered to secondery)
2
Psc = I1sc
Req1
Then,
Req1 =
ni
X eq 1 =
100
= 0.174 W
24 2
2
Ze2q1 - Req1
= 0.41672 - 0.1742 = 0.3786 W
na
Then,
Also,
pd
V1sc 10
=
= 0.4167W
I1sc 24
Zeq1 =
S o,
at
es
An
= 4 kVA
V1 d o = V2 0 o + I 2 j
Then,
* Z eq1
VR =
= 257.3580.89o
V2
250
www.annaunivupdates.com
I
Pcu = Psc * 2
I 2SC
2
10
= 100 *
12
or
= 69.4 W
at
es
Pout
4000
=
*100 = 96.4%
Pout + Pi + Pcu 4000 + 80 + 69.4
h=
Pc = Pcu = 80W
pd
the
ni
Pc
80
X = =
= 0.8945%
Pcu, FL
1
0
0
An
h=
na
(IV)
h=
=
Pout
Pout
= 0 .9 5
+ Pi + Pcu
6000 * 0.8 * x
= 0 .9 5
2
6000 * 0.8 * x + 80 + 100 * x
Then,
95 x 2 - 240 x + 76 = 0
Then,
Or
x = 2.155
(Unacceptable)
www.annaunivupdates.com
x = 0.3712
Then to get 95% efficiency at 0.8 power factor the transformer must work at 37.12% of full
load.
at
es
usually designed for maximum efficiency occurring near the rated out put. A transformer
connected to the utility that supplies power to your house and the locality is called a distribution
transformer. Such transformers are connected to the power s ystem for 24 hours a day and operate
pd
well below the rated power output for most of the time. It is therefore desirable to design a
distribution transformer for maximum efficiency occurring at the average output power.
A figure of merit that will be more appropriate to represent the efficiency performance of a
distribution transformer is the "all-day" or "energy" efficiency of the transformer. This is defined
(3.26)
An
h ad =
na
h ad =
ni
as follows:
If the load cycle of the transformer is known, the all day effeciency can be deteremined.
Example 3.11 A 50 kVA, 2400/240 V transformer has a core loss P, = 200 W at rated voltage
and a copper loss Pcu = 500 W at full load. It has the following load cycle.
% L oa d
0 .0 %
Power Factor
H o u rs
50 %
75%
100 %
11 0 %
0.8Lag
0.9L ag
Solution
Energy output 24 hours is
www.annaunivupdates.com
0.5*50*6+0.75*50*0.8*6+1*50*0.9*3+1.1*50*1*3=630 kWh
Energy losses over 24 hours:
Core loss =0.2*24=4.8 kWh
Copper losses = 0.52 *0.5*6 + 0.752 *0.5*6 +12 * 0.5* 3+ 1.12 *0.5*3
=5.76 kWh
630
* 1 0 0 = 9 8 .3 5 %
630 +10.56
pd
Then, h AD
at
es
(1) When a transformer is loaded with a constant primary voltage, then the secondary terminal
Let. V2o
ni
na
= E2 = E1 / a = V1 / a
An
V2 = Secondary terminal
voltage on full-load.
V20
%reg =
Vno-load -Vload
*100
Vload
V2o -V2 .
(3.27)
(3.28)
(3.29)
V2
This
i.e.
As the transformer is loaded, the secondary terminal voltage falls (for a lagging power factor).
Hence, to keep the output voltage constant, the primary voltage must be increased. The rise in
www.annaunivupdates.com
primary voltage required to maintain rated output voltage from no-load to full-load at a given
power factor expressed as percentage of rated primary voltage gives the regulation of the
transformer.
Vector diagram for the voltage drop in the transformer for different load power factor is
shown in Fig.3.18. It is clear that the only way to get V1 less than V2 is when the power factor is
leading which means the load has capacitive reactance (i.e. the drop on
Zeq1
will be negative,
V1
I 2 X eq1
I 2 Zeq1
V2
pd
ni
V1
I 2 Req1
I 2
at
es
I 2 X eq1
I 2 Zeq1
(a)
na
V1
I 2
I 2 Req1
V2
An
I 2
(b)
I 2 X eq1
I 2 Z eq1
I 2 Req1
j
V2
(c)
Fig.3.18 Vector diagram for transformer for different power factor (a) lagging PF (b) Unit y
PF (c) Leading PF.
www.annaunivupdates.com
20 V ; 12 A, 100 W
at
es
Solution
Open circuit test
pd
80
= 0.32
250 *1
P
cosj o = oc
Voc Ioc
=
X m1 =
na
V1oc 250
=
= 781.3 W
Ic
0.32
V1oc 250
=
= 263.8 W
I m 0.95
An
Rc1 =
ni
in Example 3.5 or we can modify the short circuit data to the primary and then we can calculate
Req1 and X eq1 directly. Here will use the two method to compare the results.
First method
R eq 2 =
Psc 100
= 2 = 0.694 W
2
I 2sc
12
Z eq2 =
Vsc 20
=
= 1.667 W
I 2sc 12
Then,
As
X eq2 =
2
2
Zeq2
- Req2
= 1.6672 - 0.6942 = 1.518 W
Rc a n d X m
www.annaunivupdates.com
refer
to
primary,
hence
we
will
transfer
these
values
pd
at
es
Then
ni
Second method
Zeq1 =
Then,
Psc 100
= 2 = 0.174 W
2
I1sc
24
na
An
Then Req1
V1sc 10
=
= 0.417 W
I1sc 24
Xeq1 =
2
2
Zeq1
- Req1
= 04172 - 0.1742 = 0.38 W
Applied voltage
V1 d o = V2 0o + I 2 j o * Zeq1
Then, V1
www.annaunivupdates.com
at
es
= 253.7 0.47 o V
Voltage regulation
pd
(V2)load = 250 00
253.7 - 250
* 1 0 0 = 1 .4 8 %
250
ni
% reg =
%reg =
Effeciency
V2 * I 2 * cosj
*100
V2 * I 2 * cos j + Pcu + Piron
h=
An
na
h=
Example 3.13 A 1f, 10 kVA, 2400/240 V, 60 Hz distribution transformer has the following
characteristics: Core loss at full voltage =100 W and Copper loss at half load =60 W (a)
Determine the efficiency of the transformer when it delivers full load at 0.8 power factor lagging.
(b) Determine the rating at which the transformer efficiency is a maximum. Determine the
efficiency if the load power factor is 0.9. (c) The transformer has the following load cycle:
No load for 6 hours, 70% full load for 10 hours at 0.8 PF and 90% full load for 8 hours at 0.9
PF
Solution:
www.annaunivupdates.com
Pout = 10*0.8 = 8 kW
(a)
x=
hmax
100
= 0.6455`` \
240
at
es
(b)
8000
*100 = 95.92%
8000 +100 + 240
pd
ni
na
An
1 2 0 .8
*100 = 95.93%
120.8 + 2.4 + 2.7312
I1*Req1
%R =
V1
*10 0 =
I12 Req1
V1I1
* 10 0
www.annaunivupdates.com
(3.30)
I 2 Req2
V2 I 2
%Z =
I1 * X eq1
V1
I 1 Z eq 1
V1
*100 =
* 10 0 =
I 2 X eq2
V2
I 2 Z eq2
V2
*100
(3.31)
* 1 00
(3.32)
at
es
%X =
(3.33)
pd
%Z = %R 2 + % X
3.15 Autotransformer
ni
This is a special connection of the transformer from which a variable AC voltage can be
obtained at the secondary. A common winding as shown in Fig.3.19 is mounted on core and the
secondary is taken from a tap on the winding. In contrast to the two-winding transformer
na
discussed earlier, the primary and secondary of an autotransformer are physically connected.
An
However, the basic principle of operation is the same as that of the two-winding transformer.
pd
at
es
www.annaunivupdates.com
ni
Since all the turns link the same flux in the transformer core,
(3.34)
na
V1 N1
=
=a
V2 N 2
If the secondary tapping is replaced by a slider, the output voltage can be varied over the
< V2 < V1 .
An
range 0
The ampere-turns provided by the upper half (i.e., by turns between points a and b) are:
(N1 - N 2 )* I1 = 1 - 1 N 1I1
(3.35)
The ampere-turns provided by the lower half (i.e., by turns between points b and c) are:
N 2 ( I 2 - I1 ) =
N1
( I 2 - I1 )
a
(3.36)
1
1 - N
a
(3.37)
Then,
I1 1
=
I2 a
(3.38)
I =
N1
(I 2 - I1 )
a
Equations (3.34) and (3.37) indicate that, viewed from the terminals of the autotransformer,
the voltages and currents are related by the same turns ratio as in a two-winding transformer.
www.annaunivupdates.com
The advantages of an autotransformer connection are lower leakage reactances, lower losses,
lower exciting current, increased kVA rating (see Example 3.11), and variable output voltage
when a sliding contact is used for the secondary. The disadvantage is the direct connection
between the primary and secondary sides.
Example 3.14 A 1
autotransformer as shown in Fig.E2.6 such that more than 2000 V is obtained at the secondary.
at
es
The portion ab is the 200 V winding, and the portion be is the 2000 V winding. Compute the
An
na
ni
pd
Fig.3.20
Solution:
The current ratings of the windings are
www.annaunivupdates.com
pd
at
es
Therefore, for full-load operation of the autotransformer, the terminal currents are:
ni
conductive connection. Not all of the 1100 kVA is transformed by electromagnetic induction.
An
V to ground.
na
Also note that the 200 V winding must have sufficient insulation to withstand a voltage of 2200
www.annaunivupdates.com
460
2860
pd
U
ni
Then,
= 108.7
(b)
50 *103
I s,2w =
2460
at
es
2400
Pi + Pcu,FL = 2368.42 W
h Auto =
An
Then,
na
(c) h2w
50 *103 * 0.9
=
= 0 .9 5
3
50 *10 * 0.9 + Pi + Pcu, FL
310870 * 0.9
= 9 9 .6 1 %
310870* 0.9 + 2368.42
voltages from one level to another. The transformers may be inherently 3-phase, having three
primary windings and three secondary windings mounted on a 3-legged core. However, the same
www.annaunivupdates.com
result can be achieved by using three single-phase transformers connected together to form a
3-phase transformer bank.
3.16.2 Basic Properties Of 3-Phase Transformer Banks
When three single-phase transformers are used to transform a 3-phase voltage, the windings
can be connected in several ways. Thus, the primaries may be connected in delta and the
secondaries in wye, or vice versa. As a result, the ratio of the 3-phase input voltage to the 3-phase
output voltage depends not only upon the turns ratio of the transformers, but also upon how they
are connected.
A 3-phase transformer bank can also produce a phase shift between the 3-phase input voltage
at
es
and the 3-phase output voltage. The amount of phase shift depends again upon the turns ratio of
the transformers, and on how the primaries and secondaries are interconnected. Furthermore, the
phaseshift feature enables us to change the number of phases. Thus, a 3-phase s ystem can be
pd
converted into a 2-phase, a 6-phase, or a 12-phase system. Indeed, if there were a practical
application for it, we could even convert a 3-phase s ystem into a 5-phase s ystem by an
appropriate choice of single-phase transformers and interconnections.
ni
in polarity may produce a short-circuit or unbalance the line voltages and currents.
The basic behavior of balanced 3-phase transformer banks can be understood by making the
na
An
2.The transformer impedances, due to the resistance and leakage reactance of the windings,
3.The total apparent input power to the transformer bank is equal to the total apparent output
power.
Furthermore, when single-phase transformers are connected into a 3-phase system, they retain
all their basic single-phase properties, such as current ratio, voltage ratio, and flux in the core.
Given the polarity marks
X 1, X 2 and H1 , H 2 ,
secondary is zero.
3.16.3 Delta-Delta Connection
The three single-phase transformers P, Q, and R of Fig.3.21 transform the voltage of the
incoming transmission line A, B, C to a level appropriate for the outgoing transmission line 1, 2,
3. The incoming line is connected to the source, and the outgoing line is connected to the load.
H2
www.annaunivupdates.com
X 1 and X 2 of successive
transformers are connected together. The actual physical layout of the transformers is shown in
Fig.3.21. The corresponding schematic diagram is given in Fig.3.22. The schematic diagram is
drawn in such a way to show not only the connections, but also the phasor relationship between
the primary and secondary voltages. Thus, each secondary winding is drawn parallel to the
corresponding primary winding to which it is coupled. Furthermore, if source G produces
voltages
E AB , EBC , ECA according to the indicated phasor diagram, the primary windings are
oriented the same way, phase by phase. For example, the primary of transformer P between lines
E AB .
ni
pd
at
es
na
An
In such a delta-delta connection, the voltages between the respective incoming and outgoing
transmission lines are in phase. If a balanced load is connected to lines 1-2-3, the resulting line
www.annaunivupdates.com
currents are equal in magnitude. This produces balanced line currents in the incoming lines
A-B-C. As in any delta connection, the line currents are 43 times greater than the respective
currents
IP
and
IS
rating of the transformer bank is three times the rating of a single transformer.
Note that although the transformer bank constitutes a 3-phase arrangement, each transformer,
considered alone, acts as if it were placed in a singlephase circuit. Thus, a current
from
IP
flowing
at
es
in the secondary.
Example 3.16 Three single-phase transformers are connected in delta-delta to step down a
pd
line voltage of 138 kV to 4160 V to su-pply power to a manufacturing plant. The plant draws 21
MW at a lagging power factor of 86 percent.
Calculate a. The apparent power drawn by the plant b. The apparent power furnished by the
HV line
ni
c.The current in the HV lines d. The current in the LV lines e. The currents in the primary and
Solution:
na
An
S = P / cosj
b. The transformer bank itself absorbs a negligible amount of active and reactive power
because the
I2 R
losses and the reactive power associated with the mutual flux and the leakage
fluxes are small. It follows that the apparent power furnished by the HV line is also 24.4 MVA.
c.The current in each HV line is:-
I1 =
24.4 *106
S
=
= 102 A
3 *V1
3 * 13800
I2 =
S
24. 4 * 10 6
=
= 3386 A
3V2
3 * 4 1 60
102
= 58.9 A
3
www.annaunivupdates.com
Ip =
IS =
3386
= 1955 A
3
f. Because the plant load is balanced, each transformer carries one-third of the total load, or
24.4/3 = 8.13 MVA.
The individual transformer load can also be obtained by multiplying the primary voltage times
the primary current:
at
es
Note that we can calculate the line currents and the currents in the transformer windings even
though we do not know how the 3-phase load is connected. In effect, the plant load (shown as a
pd
box in Fig.3.22) is composed of hundreds of individual loads, some of which are connected in
delta, others in wye. Furthermore, some are single-phase loads operating at much lower voltages
than 4160 V, powered by smaller transformers located inside the plant. The sum total of these
ni
loads usually results in a reasonably well-balanced 3-phase load, represented by the box.
3.16.4 Delta-wye connection
When the transformers are connected in delta-wye, the three primary windings are connected
na
the same way as in Fig.3.21. However, the secondary windings are connected so that all the
X2
An
terminals are joined together, creating a common neutral N (Fig.3.23). In such a delta-wye
connection, the voltage across each primary winding is equal to the incoming line voltage.
However, the outgoing line voltage is 3 times the secondary voltage across each transformer.
The relative values of the currents in the transformer windings and transmission lines are
given in Fig.3.24. Thus, the line currents in phases A, B, and C are
primary windings. The line currents in phases 1, 2, 3 are the same as the currents in the
secondary windings. A delta-wye connection produces a 30 phase shift between the line voltages
of the incoming and outgoing transmission lines. Thus, outgoing line voltage E12 is 30 degrees
ahead of incoming line voltage EAB, as can be seen from the phasor diagram. If the outgoing line
feeds an isolated group of loads, the phase shift creates no problem. But, if the outgoing line has
to be connected in parallel with a line coming from another source, the 30 degrees shift ma y
make such a parallel connection impossible, even if the line voltages are otherwise identical.
One of the important advantages of the wye connection is that it reduces the amount of
insulation needed inside the transformer. The HV winding has to be insulated for only 1/
3 , or
www.annaunivupdates.com
pd
at
es
An
na
ni
Fig.3.24 Schematic diagram of a delta-wye connection and associated phasor diagram. (The
phasor diagrams on the primary and secondary sides are not drawn to the same scale.)
Example3.17 Three single-phase step-up transformers rated at 90 MVA, 13.2 kV/80 kV are
connected in delta-wye on a 13.2 kV transmission line (Fig.3.25). If they feed a 90 MVA load,
calculate the following:
www.annaunivupdates.com
Fig.3.25.
at
es
Solution
The easiest way to solve this problem is to consider the windings of onl y one transformer, say,
transformer P.
pd
V2 = 80 * 3 = 139 kV
An
na
S = 90 / 3 = 30MVA
ni
The currents and voltages in a wye-delta connection are identical to those in the delta-wye
connection. The primary and secondary connections are simply interchanged. In other words, the
H2
www.annaunivupdates.com
X 1, X 2
terminals are
connected in delta. Again, there results a 30 degrees phase shift between the voltages of the
incoming and outgoing lines.
3.16.6 Wye-wye connection
When transformers are connected in wye-wye, special precautions have to be taken to prevent
severe distortion of the line-to-neutral voltages. One way to prevent the distortion is to connect
the neutral of the primary to the neutral of the source, usually by way of the ground (Fig.3.26).
at
es
Another way is to provide each transformer with a third winding, called tertiary winding. The
tertiary windings of the three transformers are connected in delta (Fig.3.27). They often provide
the substation service voltage where the transformers are installed.
pd
Note that there is no phase shift between the incoming and outgoing transmission line
na
ni
source.
An
Fig.3.26 Wye-wye connection with neutral of the primary connected to the neutral of the
to the high voltage side is 1.5+j2 S2. The transformer delivers 60 kW at 0.75 power fa ctor
(leading).
www.annaunivupdates.com
60
= 80kVA
0.75
A
240 0
= 10
240
I1 ph =
An
a=
na
80 *103 = 111.029
Is =
3 *416
kVA =
ni
(b)
pd
at
es
(a )
111.029
= 11.103A
10
( )
V1 = V2 + I 2 * Z eq1
2397.96 - 2400
*100 = -0.0875%
2400
Problems:
1
A 1 0, 100 kVA, 1000/ 100 V transformer gave the following test results: open-circuit
www.annaunivupdates.com
(a) Determine the rated voltage and rated current for the HV and LV sides.
(b) Derive an approximate equivalent circuit referred to the HV side.
(c) Determine the voltage regulation at full load, 0.6 PF leading.
(d) Draw the phasor diagram for condition (c).
2
: 37.5 V, 55 A, 950 W
(a) Derive the approximate equivalent circuit in per-unit values. (b) Determine the voltage
at
es
regulation at full load, 0.8 PF lagging. (c) Draw the phasor diagram for condition (b).
parameters:
pd
A1
4-
Po c
ni
parameters. RHV= 1.3 W XHV=4.5W, RLV = 0.05 W, XLV = 0.16, Rc2= 2.4 kW Xm2 = 0.8 kW
na
(a) Draw the approximate equivalent circuit (i.e., magnetizing branch, with Rc1 and Xm
An
connected to the supply terminals) referred to the HV side and show the parameter values.
(b) Determine the no load current in amperes (HV side) as well as in per unit.
(c) If the low-voltage winding terminals are shorted, determine
(d)
(i)
The supply voltage required to pass rated current through the shorted winding.
(ii)
characteristics: Core loss at full voltage = 100 W Copper loss at half load = 60 W
(a)
Determine the efficiency of the transformer when it delivers full load at 0.8 power factor
lagging . (b)
Determine the per unit rating at which the transformer efficiency is a maximum.
Determine this efficiency if the load power factor is 0.9. The transformer has the following load
cycle: No load for 6 hours 70% full load for 10 hours at 0.8 PF 90% full load for 8 hours at 0.9
www.annaunivupdates.com
S ho w
the
A 1
at
es
(b)
Determine the maximum kVA the autotransformer can supply to the 460 V circuit.
(c)
Determine the efficiency of the autotransformer for full load at 0.9 power factor.
pd
(a)
ni
supply a load at 330 V from a 110 V supply. (a) Show the connection.
9
(b) Determine the maximum kVA the reconnected transformer can deliver.
Three 1, 10 kVA, 460/120 V, 60 Hz transformers are connected to form a 3 f 460/208
na
V transformer bank. The equivalent impedance of each transformer referred to the high-voltage
An
side is 1.0 + j2.0 W. The transformer delivers 20 kW at 0.8 power factor (leading).
(a) Draw a schematic diagram showing the transformer connection. (b) Determine the
transformer winding current. (c) Determine the primary voltage. (d) Determine the voltage
regulation.
10
A 1f
impedance of the high-voltage winding is 0.25 + j 1.5 W with the lowvoltage winding
short-circuited. The admittance (i.e., inverse of impedance) of the low-voltage winding is 0.025
- j O.075 mhos with the high-voltage winding open-circuited.
(a)
Taking the transformer rating as base, determine the base values of power, voltage,
current, and impedance for both the high-voltage and low-voltage sides of the transformer.
(b)
Determine the per-unit value of the equivalent resistance and leakage reactance of the
transformer. (c)
(d)
Determine the per-unit value of the total power loss in the transformer at full-load output
condition.
UNIT III
www.annaunivupdates.com
Introduction
Electromechanical energy conversions use a magnetic field as the medium of energy
conversion.Electromechanical energy conversion device:
Converts electrical energy into mechanical energy
or
at
es
Transform the signals of different forms. Examples: microphones, sensors and speakers.
Force producing devices (translational force)- limited mechanical motion.
pd
Produce forces mostly for linear motion drives, Example Actuators - relays, solenoids
and electromagnets.
Continuous energy conversion equipment.
ni
na
An
Energy can neither be created nor destroyed. It can only be changed from one form to
another. Therefore total energy in a system is constant .
An electromechanical converter system has three essential parts:
An electrical system (electric circuits such as windings)
A magnetic system (magnetic field in the magnetic cores and air gaps)
Energy
energy in
=
+
+ losses
www.annaunivupdates.com
at
es
+ stored field
- resis tan celoss and windageloss energy +coreloss
dWe = dWm + dW f
pd
ni
na
An
The mechanical force fm is defined as acting from the relay upon the external mechanical system
and the differential mechanical energy output of the relay is
dWm = fm dx
www.annaunivupdates.com
dWf = id l fm dx
Value of Wf is uniquely specified by the values of l and x, since the magnetic energy storage
system is lossless.
at
es
W f = idl
pd
The l-i characteristics of an electromagnetic system depends on the air-gap length and B-H
characteristics of the magnetic material.
ni
For a larger air-gap length the characteristic is essentially linear. The characteristic becomes non
linear as the air-gap length decreases.
l
na
An
l-i
Wf
Increased
air-gap
lengt h
Wf
i
For a particular value of air-gap length, the field energy is represented by the red area between l
axis and l-i characteristic. The blue area between i axis and l- i characteristic is known as the
coenergy
Wf' =
di
From the figure of l - i characteristic,
Wf + Wf = l i
www.annaunivupdates.com
The quantity of coenergy has no physical significance. However, it can be used to derive
expressions for force (torque) developed in an electromagnetic system
Determination of Force from Energy
The magnetic stored energy Wf is a state function, determined uniquely by the independent state
variables and x. This is shown explicitly by
dWf (, x) = id l fm dx
F ( x1, x2 )
x1
dx1 +
x2
F(x1, x2 )
dx2
x2
x
1
dx
Wf (l,
x)
x
Wf (l, x)
dl
l
+
ni
dWf (l, x)
=
pd
dF(x1, x2 ) =
at
es
For any function of two independent variables F(x1,x2), the total differential equation of F with
respect to the two state variables x1 and x2 can be written
na
i=
Wf (l, x)
l
x
An
where the partial derivative is taken while holding x constant and the mechanical force:
fm = -
Wf (l, x)
x
l
l
Wf (l, x) = i(l, x)dl = l2 dl
L(x) =
0
0
1
2 L(x)
fm = -
Wf (l, x)
1 l2
l2 dL(x)
= -
=
x
x 2 L(x) l 2L(x) 2 dx
l
www.annaunivupdates.com
Wf (l,q )
q
l
at
es
pd
na
By expanding d(i):
ni
An
Wf' (i, x)
Wf' (i, x)
di +
dx
i
x
x
i
Wf' (i, x)
l=
i
www.annaunivupdates.com
x
where the partial derivative is taken while holding x constant and the mechanical force:
Wf' (i, x)
fm =
x
at
es
Wf' (i, x)
i 2 i 2 dL(x)
Wf' (i, x)
= L(x) =
x
x
2 i 2 dx
i
fm =
pd
U
na
Wf' (i,q )
T=
q i
ni
For a system with a rotating mechanical terminal, the mechanical terminal variables become the
angular displacement and the torque T. Therefore, equation for the torque:
An
Wf' (i, x)
x
www.annaunivupdates.com
The positive sign emphasizes that the force acts in a direction to increase the coenergy at
i
constant current.
3. By using inductance function:
i 2 dL(x)
2 dx i
fm = +
The positive sign emphasizes that the force acts in a direction to increase the inductance at
constant current.
at
es
pd
In a magnetic circuit having a substantial air gap g, and high permeability of the iron core, nearly
all the stored energy resides in the gap. Therefore, in most of the cases we just need to consider
the energy stored in the gap. The magnetic stored energy,
l
W f = idl
Therefore, W f =
ni
Hg
and
N
B
Hg
NAdB = Ag H dB
0
N
in which i =
wf =
Wf
Ag
An
na
However, Ag is volume of the air gap. Dividing both sides of the above equation by the volume
Ag results in
H dB
w'f =
www.annaunivupdates.com
The area between the B-H curve and H axis represents the
coenergy density in the air gap.
H dB =
B
B2
dB =
m
2m
at
es
wf =
mH 2
B
d
H
=
m
H
d
H
=
=
0
2
0
w'f
pd
ni
Doubly-excited Systems
na
Rotating Machines
An
Most of the energy converters, particularly the higher-power ones, produce rotational
motion.
The essential part of a rotating electromagnetic system is shown in the figure.
The fixed part is called the stator,
The rotor is mounted on a shaft and is free to rotate between the poles of the stator
Let consider general case where both stator & rotor have windings carrying current ( is
and ir )
www.annaunivupdates.com
Assume general case, both stator and rotor have winding carrying currents (non-uniform
air gap silent pole rotor)
at
es
The system stored field energy, Wf can be evaluated by establishing the stator current is
and rotor current ir and let system static, i.e. no mechanical output
An
na
ni
pd
Stator and rotor flux linkage l is expressed in terms of inductances L (which depends on
position rotor angle q, L(q)
Torque
www.annaunivupdates.com
First two terms represents reluctance torque; variation of self inductance (exist in both
salient stator and rotor, or in either stator or rotor is salient)
The third term represents alignment torque; variation of mutual inductance.
Reluctance Torque It is caused by the tendency of the induced pole to align with
excited pole such that the minimum reluctance is produced. At least one or both of the
winding must be excited.
Alignment Torque It is caused by a tendency of the excited rotor to align with excited
stator so as to maximize the mutual inductance. Both winding must be excited.
Forces and Torques
F = q(E + v B)
at
es
F: N, q: Coulombs, E : V/m,
Fv = r (E + v B)
A/m2
J = rv
An
na
ni
Current density,
pd
B : T or Wb/m2
Right-hand rule for determining the direction magnetic-field component of the Lorentz force F = q(v B).
Example 3.1
A nonmagnetic rotor containing a single-turn coil is placed in a uniform magnetic field of magnitude B0,
as shown in Fig. 3.2. The coil sides are at radius R and the wire carries current I as indicated. Find the directed torque as a function of rotor position when I = 10 A, B0 = 0.02 T and R = 0.05 m. Assume that
the rotor is of length l = 0.3 m.
www.annaunivupdates.com
F1q = - I B0 l sina
F2q = - I B0 l sina
at
es
ni
pd
na
An
dt
dW fld
dt
dt
( f fld x)
dWfld
lossless system
dl
dt
= i dl - f fld dx
e=
Energy Balance
energy input mechanical increase in energy energy
from electric = energy +
+ converted
stored in
sources output magnetic field into heat
Conversion of energy into heat: ohmic heating due to current flow in windings + mechanical friction
Lossless magnetic energy storage system:
dWelec = dWmech + dWfld
www.annaunivupdates.com
An electromagnetic relay
e=
dWmech = f fld dx
dl
dt
dWelec = i dl
dW fld = i dl - f fld dx
at
es
dWelec = ei dt
An
na
ni
pd
Lossless magnetic energy storage system: conservative system: value of Wfld is uniquely specified by the
values of and x (, x are called the state variables)
W f ld =
path 2a
dW fld +
dW fld
path 2b
l
dW fld = 0
W fld (l0, x0 ) = i(l, x0 ) dl
0
0
1 l2
2 L( x)
l d l
L( x)
www.annaunivupdates.com
Example 3.2
The relay shown in Fig.3.6a is made from infinitely-permeable magnetic material with a movable
plunger, also of infinitely-permeable material. The height of the plunger is much greater than the air-gap
length (h >> g). Calculate the magnetic stored energy Wfld as a function of plunger position (0 < x < d) for
N = 1000 turns, g = 2.0 mm, d = 0.15 m, l = 0.1 m, and i = 10 A.
W f ld =
1
L(x)i 2
2
L(x) =
x
Agap = l(d - x) = ld 1 -
d
2g
L(x) =
m0 N 2ld (1 - x / d )
2g
at
es
- x
102 1
= 236 1- J
d
d
2
2(0.002)
na
ni
pd
W fl d =
m0 N 2Agap
An
F
F
dx1 +
dx2
x1
x2
W fld (l, x)
l
dW fld =
f fld = -
W fld
l
dl +
W fld
x
dx
W fld (l, x)
x
Example 3.3
1 l2
l2
dL( x)
=
2
x 2 L( x) 2 [ L( x) ] dx
l = L( x)i
f fld =
1 2 dL( x)
i
2
dx
Table 3.1 contains data from an experiment in which the inductance of a solenoid was measured as a
function of position x, where x = 0 corresponds to the solenoid being fully retracted.
www.annaunivupdates.com
x (cm)
L(mH)
0
2. 8
0.2
2.26
0. 4
1.78
0.6
1.52
Table 3.1
0. 8
1. 0
1.34
1.26
1 .2
1.20
1.4
1.16
1. 6
1.13
1.8
1.11
2. 0
1.10
Plot the solenoid force as a function of position for a current of 0.75 A over the range 0.2 < x < 1.8 cm.
Using the MATLAB function polyfit, a fourth-order polynomial fit of the inductance as a function of x is
obtained:
pd
at
es
f fld = i 2
= i 4a(1)x
+ 3a(2) x 2 + 2a (3)x + a(4)
2
dx
2
ni
MATLAB script:
An
na
clc
clear
% Here is the data: x in cm, L in mH
xdata = [0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0];
Ldata = [2.8 2.26 1.78 1.52 1.34 1.26 1.20 1.16 1.13 1.11 1.10];
%Convert to SI units
x = xdata*1.e-2 ;
L = Ldata*1.e-3;
len = length(x) ;
xmax = x(len) ;
% Use polyfit to perform a 4'th order fit of L to x. Store
% the polynomial coefficients in vector a. The fit will be
% of the form:
%
% Lfit : a(1)*x^4 + a(2)*x^3 + a(3)*x^2 + a(4)*x + a(5) ;
%
a = polyfit(x,L,4) ;
% Let's check the fit
for n = 1:101
xfit(n) = xmax*(n-1)/100;
Lfit(n) = a(1)*xfit(n)^4 + a(2)*xfit(n)^3 + a(3)*xfit(n)^2 ...
+ a(4)*xfit(n) + a(5);
end
% Plot the data and then the fit to compare (convert xfit to cm and Lfit to mH)
figure(1)
plot (xdata, Ldata, ' * ' )
hold
plot (xfit*100, Lfit*1000)
xlabel('x [cm] ')
ylabel('L [mH] ')
% Now plot the force. The force will be given by
%
% (1/2)i^2 dL/dx =(1/2) i^2 ( 4*a(1)*x^3 + 3*a(2)*x^2 + 2*a(3)*x + a(4))
%
%Set current to 0.75 A
I = 0.75;
for n = 1:101
www.annaunivupdates.com
end
figure(2)
plot (xfit*100,F)
xlabel('x [cm] ')
ylabel('Force [N]')
T fld = -
1 l2 1 l2
=
[ L(q
2 L(q )
2
)
Wfld (l,q )
q
1 l2
2 L(q
)
dL(q
)
dq
l = L(q )i
T fld =
1 2 dL(q
i
2 )
dq
at
es
W fl d =
T fl d = -
Example 3.4
L0 = 10.6 mH
L2 = 2.7 mH
L(q ) = L0 + L2 cos(2q )
pd
The magnetic circuit of Fig. 3.9 consists of a single-coil stator and an oval rotor. Because the air-gap is
nonuniform, the coil inductance varies with rotor angular position, measured between the magnetic axis
of the stator coil and the major axis of the rotor, as
An
na
ni
Solution:
2
T fld =
1 2 dL(q ) 1 2
i
= i
2
dq
N. m
dWfld (i, x) =
Wfld
di +
Wfld
i
x
Wfld (i, x)
l=
i
dx
f fld =
www.annaunivupdates.com
Wfld (i, x)
x
l(i, x) di
W fld (i, x) =
0
For linear magnetic systems, l = L(x)i
W fld (i, x) =
1
L(x)i 2
2
fld
W fld (i, x)
x
1 dL(x)
= i2
2
dx
at
es
W fld (i,q ) =
1
2
pd
L(q )i 2
T fl d =
W fld (i,q )
q
1 dL(q
= i2 )
2
dq
ni
Example 3.5
W fld (i,q )
T fld =
na
For the relay of Example 3.2, find the force on the plunger as a function of x when the coil is driven by a
controller which produces a current as a function of x of the form
x
i(x) = I 0 A
d
An
L( x) =
f fld
m0 N ld (1 - x / d )
2g
2
1 dL(x)
1 m N 2l
= i2
= - i2 0
2
dx
2 2g
I 02m0 N 2l x
=
4g d
2
2
2
1
1 m0 N ld (1 - x / d ) m0 N ld (1 - x / d ) x
L( x)i 2 = i 2
=
2
2
2g
4g
d
The force cannot be found by taking the partial derivative of this expression for W fld (i, x) with
respect to x, because in the expression for f fld the current must be kept constant while
differentiating with respect to x.
1 2
1
l / L = Li 2 . For a
2
2
nonlinear system in which x and i or B and H are not linearly proportional, the two functions are not
equal.
For a magnetically-linear system, the energy and coenergy are numerically equal:
at
es
www.annaunivupdates.com
pd
Energy = i d Co-energy = di
sum of the energy and coenergy, W fld (i, l) + W fld (i,l ) = il
Example 3.6
An
na
ni
The magnetic circuit shown in Fig. 3.12 is made of high-permeability electrical steel. The rotor is free to
turn about a vertical axis. The dimensions are shown in the figure.
(a) Derive an expression for the torque acting on the rotor in terms of the dimensions and the
magnetic field in the two air gaps. Assume the reluctance of the steel to be negligible (i.e.
) and neglect the effects of fringing.
(b) The maximum flux density in the overlapping portions of the air gaps is to be limited to
approximately 1.65 T to avoid excessive saturation of the steel. Compute the maximum torque
for r1 = 2.5 cm, h = 1.8 cm, and g = 3 mm.
H ag =
( a)
Ni
2g
L=
m0 N 2Aag
2
Ni m0 N Aag
=
i
2g
2g
www.annaunivupdates.com
1
m N2
1 h.
Aag = r1 + g q . h L(q ) = 0
r1 + g q
2
2g
2
2g
1 dL(q ) m0 N 2 i 2
1 h
T fld = i 2
=
r1 + g
2
dq
4g
2
(b)
Bmax = 1.65 T
Ni = 2g
H max =
Bmax
Ni
=
2g
m0
Maximum torque,
T fld
at
es
1 h 4p 10-7 (7878.2)2
m0 N 2i 2
=
(0.025 + 0.0015)0.018 = 3.1 N-m
r1 + g =
4g
2
4 0.003
na
ni
pd
An
Differential energy
T fld = -
Wfld (l1,l2 ,q )
q
i2 =
T fld = -
l2
l1 0
pd
l2 = L21i1 + L22i2
ni
na
l20
An
.dl1
1
i1 = (L22l1 - L12 l2 )
L12 -1 l1
D
L22 l2
1
i2 = (-L21l1 + L11l2 )
D
D = L11 L22 - L12 L21
where
at
es
www.annaunivupdates.com
L11(q 0 )
l2 .dl2 +
D(q 0 )
l10
i1 d l1 + i2 dl2 - T fld dq
= l1di1 + l2 di2 + T fld dq
l2 =
di1 +
Wfld (i1 ,i2 ,q )
i
2
di2 +
Wfld (i1 ,i2 ,q )
q
T fld =
dq
i2 0
i10
www.annaunivupdates.com
1
1
W fld (i1,i2 ,q ) = L11(q )i1 2 + L22(q )i22 + L12 (q )i1i2
2
2
Torque,
T fld =
Wfld (i1,i2 ,q )
q
1 dL (q ) 1 dL (q )
dL (q )
= i12 11 + i22 22
+ i1i2 12
2
dq
2
dq
dq
Example 3.7
ni
pd
at
es
In the system shown in Fig. 3.15, the inductances in henrys are given as L11 = (3 + cos 2) 10-3;
L12 =0.3cos; L22 = 30 + 10cos2. Find and plot the torque Tfld() for current il =0.8 A and i2 = 0.01 A.
1 2 dL11(q ) 1 2 dL22 (q )
dL12 (q )
i1
+ i2
+ i1i2
2
dq
2
dq
dq
1 2
1
= i1 (-2 10-3 sin 2q ) + i22(-20sin 2q ) + i1i2 (-0.3 sin q )
2
2
= -(1.64sin 2q + 2.4 sin q ) 10-3 N-m
An
na
T fld =
Dynamic Equations
di
dL(x)
dl
l = L( x)i v0 = Ri + L(x) + i
dt
dt
dt
dL( x) dL( x) dx
di
dL( x) dx
=
v0 = Ri + L( x) + i
dt
dx d t
dt
dx dt
v0 = Ri +
di
:
self-inductance voltage term
dt
dL( x) dx
dx
i
: speed voltage ( : mechanical speed)
dx dt
dt
L( x)
www.annaunivupdates.com
Forces in the mechanical system in terms of mechanical position (and its derivatives):
f K = - K(x - x0 )
Spring:
Damper :
Acceleration of mass :
K : spring constant
dx
dt
d2x
= -M 2
dt
f D = -B
B: damping constant
fM
f 0 (t) = -M
at
es
f f ld = f 0 - ( f K + f D + f M )
d2x
dx
- K ( x - x0) + f fld(x,i)
2 - B
dt
dt
d 2x
dx
-B
- K(x - x0) + f fld (x,i)
2
dt
dt
f 0 (t) = -M
di
dL(x) dx
+i
dt
dx dt
ni
v0 (t) = Ri + L(x)
pd
Note: If x > x0 and increasing (with positive second derivative: M accelerating), then the forces fK , fD ,
and fM all oppose ffld.
An
Example 3.10
na
Given the inputs (excitations) v0 (t ) and f 0 (t ) these equations can be solved to find x(t) and i(t).
Figure 3.24 shows in cross section a cylindrical solenoid magnet in which the cylindrical plunger of mass
M moves vertically in brass guide rings of thickness g and mean diameter d. The permeability of brass is
the same as that of free space and is 0 = 4 10-7 H/m in SI units. The plunger is supported by a spring
whose spring constant is K. Its unstretched length is l0. A mechanical load force ft is applied to the plunger
from the mechanical system connected to it, as shown in Fig. 3.24. Assume that frictional force is linearly
proportional to the velocity and that the coefficient of friction is B. The coil has N turns and resistance R.
Its terminal voltage is vt and its current is i. The effects of magnetic leakage and reluctance of the steel are
negligible.
Derive the dynamic equations of motion of the electromechanical system, i.e., the differential equations
expressing the dependent variables i and x in terms of vt, ft, and the given constants and dimensions.
at
es
www.annaunivupdates.com
g
m0p xd
R2 =
Total reluctance,
g
g 1 1
=
+
m0p ad m0p x a
d
N 2 m0 p adN 2 x
x
=
= L
R
g
a+x
a+x
L(x) =
ni
Inductance,
g
m0p
xd
R = R1 + R2 =
g
m0p ad
R1 =
pd
W fld (i, x)
x
An
f fld =
na
The magnetic force acting upward on the plunger in the positive x direction is
1 dL(x) 1 2 aL
= i
= i2
2
dx
2 (a + x)2
d
di
dL
di dL dx
(Li) = L + i
= L +i
dt
dt
dt
dt
dx dt
ai dx
x
di
= L
+L
a
+
x
dt
(a
+
x)2 dt
f (t) = -M
d2x
dx
1
ai 2
B
K(x
l
)
+
L
0
dt 2
dt
2 (a + x)2
ai dx
x
di
v(t) = Ri + L
+L
(a + x)2 dt
a + x dt
An
na
ni
pd
at
es
www.annaunivupdates.com