Aisle clearances

Cold aisle clearance


The maximum protrusion of any installed IT component directly impacts the available cold aisle clearance
for removal and replacement of other IT components. Maximum component depth must follow the clear
aisle distance calculations. The following figure shows how to calculate this distance.

The maximum rack face-to-cold aisle wall distance is 100.33 cm (39.5 inches). In the figure, X represents
any protrusion into the cold aisle starting from the rack face of the installed IT component (for example,
the bezel). Y represents cold aisle clearance. The cold aisle clearance dictates the maximum depth (D) of
any installed IT component. D cannot exceed 100.33 cm (39.5 inches).
To find the maximum cold aisle clearance, calculate 100.33 cm (39.5 inches) - X = Y.
IMPORTANT: As the value for X increases, the value for Y decreases, which also decreases
the maximum depth allowed for an installed component.

Replaceable components
The component parts in the following table can be replaced by qualified facilities personnel.
Spare part
number

Description

536900-001
588787-001
595103-001
595107-001
595108-001
616616-001
637120-001
637135-001
637136-001
637137-001
637369-001

SPS-BUSWAY,DROP BOX,400A,3PH
SPS-FRAME w/FILTER
SPS-BLOWER FAN
SPS-FILTER SCREENS FRAME w/FILTER
SPS-MAINT KIT FILTERS
SPS-POD VENT FAN
SPS-SENSOR TEMP POD
SPS-SENSOR TEMP INSERTION
SPS-SENSOR PRESSURE ABS 10 BAR
SPS-SENSOR TEMP ROOM
SPS-SENSOR HUMIDITY

Illustrated parts catalog

12

Spare part
number

Description

637373-001
641859-001
660821-001
660823-001
671756-001
718588-001

SPS-SENSOR LEAKAGE
SPS-FILTER REPLACEMENT VESDA
SPS-Sensor RAF/A-1-I
SPS-Flow Meter 3030000ZH41 4AM4200C1
SPS-HUMIDISTAT GEN M3
SPS-Humidifier CHF03V2001

The component parts in the following table are electrical components that must be replaced by a qualified
electrician.
IMPORTANT: These parts must be replaced by an authorized fire safety technician
according to all local and regional fire codes, and in compliance with manufacturer
specifications.
Spare part
number

Description

536619-001
536621-001
536901-001
571709-001
571710-001
571711-001
595104-001
612295-001
612296-001
612297-001
612299-001
612968-001
612969-001
612970-001
612971-001
612972-001
612973-001
612974-001
612975-001
612976-001
612977-001
612978-001
612979-001
612980-001
612981-001
612982-001
612983-001

SPS-POD,3PH,C19,OPTIMIZED MASTER,NA
SPS-POD,3PH,C19,OPTIMIZED MASTER,INTL
SPS-POD,225A,3PH,NA,PDU
SPS-BUSWAY,DROP BOX,225A,3PH,NA
SPS-BUSWAY,DROP BOX,225A,3PH,INTL
SPS-POD,225A,3PH,INTL,PDU
SPS-WIRE HARNESS FAN
SPS-CPU MOD w/SINEAX PWR METER SPT
SPS-CPU MOD w/KL3403 PWR METER SPT
SPS-CPU MOD w/PAC3200 PWR METER SPT
SPS-HEAT EXCHANGER w/MOD's
PS-COUPLING RELAYS
SPS-CONTACTOR AUX 4NC4NO
SPS-CONTACTOR
SPS-CONTACTOR INSTA
SPS-TRANSDUCER MEASURING
SPS-PRESSURE TERMINAL DIFFERENTIAL
SPS-MEASURE TERMINAL PT100
SPS-ANALOG INPUT TERMINAL
SPS-DIGITAL INPUT TERMINAL
SPS-DIGITAL OUTPUT TERMINAL KL2622
SPS-DIGITAL OUTPUT TERMINAL KL2408
SPS-TRANSFORMER DY 480/400V 225KVA
SPS-BUS BAR 5 POLE 3M
SPS-END CAP
SPS-HOUSING COUPLER
SPS-MOUNTING STUD M10

The component part in the following table must be replaced by an authorized fire safety contractor.
IMPORTANT: These parts must be replaced by a licensed fire safety contractor according to
all local and regional fire codes, and in compliance with manufacturer specifications.

Illustrated parts catalog

13

Spare part
number

Description

637133-001

Smoke detector

Installation considerations
CAUTION: All plumbing to and from the POD 20c must be completed by a licensed plumber.
All wiring in and around the POD 20cmust be completed by a licensed electrician. Failure to
comply with these instructions can impact your warranty and/or result in equipment damage.

Safety and NEC compliance


The POD 20c is certified to UL 69050-1/IEC 60950-22 as an Information Technology Product and
classified according to the National Electric Code NFPA 70. For more information, see "POD 20c
regulatory compliance (on page 76)."
The POD 20c is not suitable for long-term human occupancy. The POD 20c is Listed as a Product that
provides service access areas for periodic maintenance and service. These areas must be used only by
owner-authorized and qualified personnel who are trained in the maintenance and service of the POD 20c
components.
IMPORTANT: Before installing the POD 20c, consult your local AHJ for applicable
regulations and to review site-specific location guidelines. If needed, obtain any necessary
permits.
Additional considerations for safety and NEC compliance are as follows:
The POD 20c is listed as an Information Technology Product to UL 60950.
The POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for
customer-authorized, qualified, and trained service personnel.
The electrical connections of the POD 20c are evaluated as feeder connections for connection to an
existing facility, and are not suitable as "service entrance" for connection to the utility.
The POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, in
restricted access locations, with field wiring terminals provided for permanent supply connections.
The POD 20c meets the following ratings.
Feature

Specification

Category
Protection
Class
Ambient temperature
Relative humidity

Rated Overvoltage Category III


Surge protection device
Class1
2C to 54C (35.6F to 129.2F)
0% to 100% humidity

As part of the overall certification, relevant sections of the International Building Code have been
applied as part of the design and evaluation. The current design supports wind loads up to 90 mph.

Fire detection and suppression


The fire suppression system, supplied as an optional component for the POD 20c, is a "Manufacturer
Designed" system specifically designed for this product, in compliance with national standards.

Illustrated parts catalog

14