Sei sulla pagina 1di 6

KK MAYA LIKAS

ATTACHMENT D1

D1-1

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED CO2 & FM200 SYSTEM
DATE: 10 NOVEMBER 2014
REVISION: REV 00
FIXED CO2 SYSTEM
No

1
2
3
4
5

Level

UG
UG
UG
UG
UG

FM200 SYSTEM
No
Level

Location

Generator Room
Consumer HV Switch Room
Consumer TX Room
Consumer LV Room 1
Consumer LV Room 2

Location

Area

Height

Volume

Volume Factor

(m2)
65
70
89.5
93
77.5

(m)
5.4
5.4
5.4
5.4
5.4

(m3)
351
378
483
502
419

1.33
1.33
1.33
1.33
1.33

Area

Height

Volume

(m3)
421.2

(m2)
(m)
1
UG
SESB Room
78
5.4
Note: Capacity for FM200/cylinder refer to Brand " Chemetron - Sigma 600".

Basic
Quantity of
CO2 Gas

Safety Factor

(kg)
467
503
643
668
557

10%
10%
10%
10%
10%

Maximum
Concentration

Minimum
Agent
Required

Adjusted
Agent
Required

%
8.0

(kg)
261.8

(kg)
276.00

Quantity of
CO2 Gas
Required

Nos of
45kg CO2
Cylinders

(kg)
540
553
707
735
612

12
13
16
17
14

Number of
Nozzles

Nos of
138kg CO2
Cylinders

KK MAYA LIKAS

ATTACHMENT D2

D2-2

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED CO2
DATE: 10 NOVEMBER 2014
REVISION: REV 00
1.0

Automatic Fixed Carbon Dioxide Fire Extinguishing System

1.1

Design Data

a)

Reference

= NFPA 12

b)

Design Concentration

= 50

c)

Design Temperature

= 30

d)

Cylinder Capacity

= 45

kg CO2

2.0

Rooms to be Protected

2.1

Generator Room (Upper Ground Floor)

a)

Volume of Space

=
=

65
351

m2 x 5.4
m3

m (H)

b)

Total CO2 Required For Total Flooding

351

kg CO2/m3

467

m3 x 1.33
kg CO2

467

kg CO2 x

1.1

514

kg CO2

c)

Total CO2 Required For Total Flooding (10% S.F.)

d)

Total CO2 Cylinders Provided

12

@ 45 kg / cylinder

e)

Total Quantity of CO2 Provided

540

kg CO2

2.2

Consumer HV Switch Room (Upper Ground Floor)

a)

Volume of Space

=
=

70
378

m2 x 5.4
m3

m (H)

b)

Total CO2 Required For Total Flooding

378

kg CO2/m3

503

m3 x 1.33
kg CO2

503

kg CO2 x

1.1

553

kg CO2

c)

Total CO2 Required For Total Flooding (10% S.F.)

d)

Total CO2 Cylinders Provided

13

@ 45 kg / cylinder

e)

Total Quantity of CO2 Provided

585

kg CO2

KK MAYA LIKAS

ATTACHMENT D2

D2-2

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED CO2
DATE: 10 NOVEMBER 2014
REVISION: REV 00

2.3

Consumer TX Room (Upper Ground Floor)

a)

Volume of Space

=
=

89.5
483

m2 x 5.4
m3

m (H)

b)

Total CO2 Required For Total Flooding

483

kg CO2/m3

643

m3 x 1.33
kg CO2

643

kg CO2 x

1.1

707

kg CO2

c)

Total CO2 Required For Total Flooding (10% S.F.)

d)

Total CO2 Cylinders Provided

16

@ 45 kg / cylinder

e)

Total Quantity of CO2 Provided

720

kg CO2

2.4

Consumer LV Room 1 (Upper Ground Floor)

a)

Volume of Space

=
=

93
502

m2 x 5.4
m3

m (H)

b)

Total CO2 Required For Total Flooding

502

kg CO2/m3

668

m3 x 1.33
kg CO2

668

kg CO2 x

1.1

735

kg CO2

c)

Total CO2 Required For Total Flooding (10% S.F.)

d)

Total CO2 Cylinders Provided

17

@ 45 kg / cylinder

e)

Total Quantity of CO2 Provided

765

kg CO2

2.5

Consumer LV Room 2 (Upper Ground Floor)

a)

Volume of Space

=
=

77.5
419

m2 x 5.4
m3

m (H)

b)

Total CO2 Required For Total Flooding

419

kg CO2/m3

557

m3 x 1.33
kg CO2

557

kg CO2 x

1.1

612

kg CO2

14

@ 45 kg / cylinder

c)

d)

Total CO2 Required For Total Flooding (10% S.F.)

Total CO2 Cylinders Provided

KK MAYA LIKAS

ATTACHMENT D2

D2-2

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED CO2
DATE: 10 NOVEMBER 2014
REVISION: REV 00

e)

Total Quantity of CO2 Provided

630

kg CO2

KK MAYA LIKAS

ATTACHMENT D3

D3-1

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED FM200
DATE: 10 NOVEMBER 2014
REVISION: REV 00
1.0

FM200 Fire Extinguishing System

1.1

Design Data

a)

Reference

NFPA 2001:2008

b)

Design Concentration

c)

Flooding Factor

0.4985

d)

Design Temperature

25

e)

Cylinder Capacity

138

kg

2.0

Rooms to be Protected

2.1

SESB Room (Upper Ground Floor)

a)

Volume of Space

b)

Total FM200 Required For Total Flooding=

=
=

m2 x
78
3
421.2 m
421.2
/
### kg

c)

Total FM200 Cylinders Provided

d)

Total Quantity of FM200 Provided

276

Total FM200 Required For Total Flooding,


W = (V/S) x ( C/100 C)
Where,
W = weight of Agent required
V = volume of protected area
C = design concentration
S = specific vapor volume
S = 0.1269 + 0.00052 T
T = Design temperature in protected area (C)

5.4

m (H)

0.1399

@ 138 kg / cylinder
kg

8.00

/ 100

8.00

KK MAYA LIKAS
PROJECT: MAYA LIKAS
SERVICES: FIRE PROTECTION SERVICES
CLEAN AGENT SYSTEM: FIXED FM200

ATTACHMENT D3

D3-1