Sei sulla pagina 1di 33

Power Meters Catalog

V4.1

Power metering & energy efficiency management

Zhuhai Pilot Technology Co. Ltd.

Established in 2000, Zhuhai Pilot Technology Co., Ltd. occupies an area of 20,000 square meters
plant with nearly 400 staffs.
PILOT headquarter in Zhuhai of China, and equipped with a R&D center in Shenzhen Nanshan
Technology Park.

Our business is throughout the world with over 20 branch offices in China, and distribution
network in Germany, Romania, Iran, Saudi Arabia, UAE, Pakistan, India, Indonesia, Malaysia,
New Zealand, Australia, Canada, Mexico, Colombia, Chile, Brazil etc.
Our products and services:
--Digital panel meters
--Multifunction power meters
--Energy meters
--Power Quality Analyzer
--Branch circuit monitor
--LV motor protection and control devices
--Leakage current detectors
--Energy efficiency solution

Additional, our R&D team design customized products to satisfy your special requirements.

CONTENTS
Page

Certificate

Projects References

Product Selection Guide

Products
PST700 Multifunction Power Meter

PMAC615 Single Phase Digital Panel Meter


PMAC625 Three Phase Digital Panel Meter

8
9

PMAC720 Multifunction Power Meter


PMAC727 Multifunction Power Meter
PMAC735 Multifunction Power Meter
PMAC760 Multifunction Power Quality Analyzer

11
14
17
20

PMAC901 Single Phase Din-rail Energy Meter


PMAC903 Three Phase Din-rail Energy Meter
PMAC905 Multifunction Energy Meter
PMAC915 Three Phase Multi-tariff kWh Meter
PMAC921 Single Phase Multi-tariff kWh Meter

23
23
25
27
29

Certificate

Projects References
Projects Abroad
Hindustan Zinc Limited, the Lead Plant and Silver Plant ( India)
IKEA Mega Bangna - IKEA Asias Largest Complex (Thailand)
Trekkpje Uranium Plant (South Africa)
D.G Khan Cement Plant (Pakistan)
Bandung Hydropower Plant (Indonesia)
Scotts Feeds Factory Project ( U.K.)
Iranian Petrochemical Project ( Iran)

Olympic Venues
Beijing Olympic Hockey Center
Beijing Olympic Beach Volleyball Center
Beijing Olympic Shooting Range
Qingdao International Sailing Center
Beijing Olympic Basketball Gymnasium

Municipal Projects
Shanghai F1 International Circuit
Shanghai Pudong Government Processing Center
Shanghai World Expo - World Expo Axis
Shanghai World Expo Village, Block B/ Block D/E plot
Shanghai World Expo-China Pavilion
Bank of China Shanghai Information Center
Chengdu Commodity Inspection Bureau
Guangzhou Baiyun International Convention and Exhibition Centre, Phase I, II, III
Guangzhou International Financial Center (also known as Guangzhou West Tower)
Handan Wastewater Treatment Plant
Hangzhou Nanxing Water Plant
Industrial and Commercial Bank of China Head Office Building, Xinjiang
Nanjing Jiuhuashan Tunnel
New Museum of Nanjing Massacre Memorial Hall
Sichuan Cangxi Wastewater Treatment Plant
Sichuan Wenjiang Water Plant
Urumqi Inspection Centre
Xingjiang Radio and Television Building
Xinjiang Television Station Building

Power Plants / Hydropower Plants


Yunfu Power Plant of Guangdong Electric
Xuangxin Power Plant in Inner Mongolia
Xinjiang Manasi Power Plant, Phase III
Daihai Power Generation Co. Ltd. 4 600MW project, in Inner Mongolia
"Shandong Binzhou Weiqiao Thermoelectric Co., Ltd. Zouping 3rd Thermoelectric Plant: 8 135KW Project"
Inner Mongolia Yuanbaoshan Power Plant:2 600MW project
Inner Mongolia JingLong (Fengzhen) Power Plant: 2 600MW project
Xinjiang Hami Power Plant
Xinjiang Qiapuqihai Hydropower Station
Xinjiang Turk Yamaguchi Hydropower Station
Xinjiang Karasuk Hydropower Station
Jilintai Hydropower Station II
Expansion Project of Qinshan Nuclear Power Station Phase II

Airports / Metro
Guangzhou New Baiyun International Airport
Shanghai Pudong International Airport, Phase II
Shanghai Hongqiao Airport Reconstruction Project
Qingdao Luiting International Airport
Wuxi Airport
Urumqi Airport Overnight Floor
Xinjiang Kanas Airport Terminal
Beijing Metro Line 4#, 5#
Shanghai Metro Line 6#, 7#
Dalian Light Rail Line 3#
Shenzhen Metro Line 1#
Guangzhou Metro Line 2#/ 3#, 4#

Projects References
Telecommunication Porjects
Shenzhen King Tin Telecommunications Room
Shenzhen Fu Yong Telecommunications Room, Phase I,II,& III
China Netcom Building in Shanghai
China Mobile Building in Henan
China Mobile Building in Wangjing
China Unicom Building in Zhuhai

Tobacco Industry
Hongyun Group, Kunming Cigarette Factory Moving Project
Longyan Cigarette Factory
Guiyang Cigarette Factory
Hongta Group, Yuxi Cigarette Factory
Hongyun Group, Honghe Cigarette Factory
Shijiazhuang Cigarette Factory

Hospital / Gym/ School


Tsinhua University Environmental Building
Palais Omnisports of Guangzhou Asian Games City
Dongguan Changping Chang An Hospital
Shanghai Nanhui Central Hospital
Shanghai Red House Hospital
Shanghai Donghua University, Songjiang Campus
Guangzhou University City Complex Building, Phase I, II & III
The New Campus of Sichuan Normal University
Shanghai Stadium
Foshan Century Lotus Stadium
Foshan Swimming Pool
Foshan Pearl Stadium
Beijing Chaoyang Hospital

Commercial/ Complex Buildings


TPL National Support Center / Shanghai
Guangzhou Science Meseum
Guangdong GSM Building
Shenzhen Ho Shing Commercial Centre
Shenzhen Hong Long Century Plaza
Guangxi TV Station/ Guangxi Science Museum
Chongqing Grand Theatre
Beijing Yanjing Hotel
Beijing Big Bell Temple Commercial Plaza
Beijing Chang An Grand Mall
Shanghai Gubei Fortune Centre
Shanghai Tongji Union Square
Shangri-La Hotel, Qingdao
Hanzhong IMC Times Square in Shaanxi

Oil/ Chemical/ Light Industry


China Heavy Truck ZF Steering Project
Daqing Petrochemical 1.2 million / N delayed coking
Daya Bay CNOOC Phase II and petrochemical supporting project
Henan Zhongzhou Aluminum
Inner Mongolia Yitai Coal Chemical Project
New paper mill project in Myanmar
Rene Sola project in Sichuan, 3,000 tons of polysilicon
Shanghai Chlor-Alkali Chemical PVC project
Shanghai Huayi Group, 6500 tons / year synthetic camphor agent project
Shanghai No. 5 Iron and Steel Plant
Shanxi Coking Group, 1 million tons of coking
Shihezi Tianye Chemical, 500,000 tons of calcium carbide project
Sinopec (GZ) 1 million t catalytic cracker
Sinopec East Gas Transmission - Puguang gas field project
Sinopec Fujian Petrochemical integration project
Sinopec Refining & Chemical Project in Shijiazhuang
Xinjiang Tianshan Cement, 2000 tons / D
Xinjiang Yili Steel, 300,000 tons of calcium carbide project in Nilka
3

Product Selection Guide


PST700

PMAC615

PMAC625

PMAC720

PMAC735

PMAC727

PMAC760

PMAC901

PMAC903

PMAC905

PMAC915

PMAC921

Display

LCD

LED

LED

LCD

LCD

LCD

LCD

LCD

LCD

LCD

LCD

LCD

Single or 3 phase

single

single

single

U, I, P, Q, kWh

PF, F

kvarh

kVAh

Demand

Max./ min. value

Multi-tariff energy

Model
Features

Photo

Real-time measurement

Phase angle

Temperature
Power quality analysis
Harmonic

Voltage crest factor

Current K factor

Unbalance rate

Load rate

U or F deviation

DI/ DO
Status input

Relay output

Analog input

Analog output

Pulse output

Communication
RS485 / Modbus

The 2nd RS485

Profibus

Ethernet or USB
Infrared COM
Memory card

Other functions
SOE event log

Setpoint alarm

Data record

standard feature

optional feature

PST700 Multifunction Power Meter


Feature

Suit for LV/ HV voltage system


For low voltage system, PST700 direct connect up to 600VAC
For high voltage system, PTS700 need to connect with PTs, PT ratio
programmable

New appearance and design


Large LCD display and button, replace AI capacitor by Tam capacitor

Self-testing phase sequence error


In case of error phase sequence input, PST700 will display on LCD

Real-time measurement
True-RMS measuring parameters includes:
U, I, P, Q, S, PF, F, kWh, kvarh, kVAh, demand, max./min. value

Demand calculation mode is programmable


2 kinds of demand modes: fixed mode and slip mode
Demand cycle programmable: 5/ 10/ 15/ 30/ 60mins
Slip window programmable: 1/ 2/ 3/ 5mins

Multi-tariff billing, historical data of 31 days and 12 months


2 kinds of setting modes: time zone mode and holiday mode
Time zone mode: 2 time zones in one year

Basic unit

Holiday mode: working days ( Mon.- Fri.) and holidays ( Sat.- Sun.)
Optional module

There are 2 lists of tariff rate, each list can setup 8 periods of time in 24 hours, 4
tariff rates.

Power quality analysis


Harmonic analysis, crest and K factor, unbalance etc.

Optional module and upgradeable


Pluggable in option module, support online upgrade

Setpoint alarm
Under/ over limit alarm, monitoring objects include: U, I, PF, F, THD, unbalance
If any parameters is over or under limit and persists over the specified time,
PST700 will record the event, and trip relay output signal.

High accuracy
Active energy: according to IEC62053-22, class 0.5s
Reactive energy: according to IEC62053-23, class 2

Small size and thin style


Panel: 96x96x13.5mm

Cut-out: 90x90mm,

Depth: 45.1mm (basic unit) + 21.5mm (optional module)

Standard

IEC62053-22/ 23, CE. KEMA


5

PST700 Multifunction Power Meter


Basic Function

Real time metering

Voltage

Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg

Current

Ia, Ib, Ic, In, Iavg

Power

Pa, Pb, Pc, P, Qa, Qb, Qc, Q, Sa, Sb,Sc, S

Power factor

PFa, PFb, PFc, PF

Energy

kWh and kvarh (4 quadrant), kVAh

Frequency

Demand & Max. demand

Dmd_I, Dmd_P, Dmd_Q ,Dmd_S

Max./ min. value

Max./ min. (U, I, P, Q)

Multi-tariff energy

Power quality analysis

Unbalance

U_unbl, I_unbl

Harmonic (31st )

THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi, HRU, RHI

Harmonic RMS (0-31st )

Harmonic RMS-U, Harmonic RMS-I

Harmonic energy (1st -31st )


Voltage crest factor, current K factor, Load rate, Voltage deviation, Frequency deviation
Setpoint alarm

Over/ under limit alarm

3DI +2 DO

3 status input + 2 relay output

RS485

Modbus-RTU protocol
SOE (event log), Real-time clock ( yyyy-mm-dd hh:mm:ss)

Record function
Voltage/ frequency deviation, Voltage unbalance record

Optional Module
S

2 status input

Profibus communication

2 relay output

AI

2 analog input (4-20mA)

The 2 RS485

AO

2 analog output (4-20mA)

Ep

2 pulse output

BA

BACnet protocol

nd

Parameter

Accuracy

Resolution

1GB memory

Measuring Range
Direct: 600Vph-ph

Voltage

0.2%

0.01V

Current

0.2%

0.001A

Power

0.5%

0.1W/var/ VA

PT primary: 0~999.9kV
PT secondary: 100Vph-ph or 110V
CT primary: 0~49,999A
CT secondary: 1 A or 5A
each phase: 0~49994MW/ Mvar/ MVA
Total: 0~149982MW/ Mvar/ MVA

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

45~ 65 Hz

Active energy

0.5%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kvarh

THD

1.0%

0.001

0~100.0%

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

PST700 Multifunction Power Meter


Technical Specification
Metering

True RMS, 1 sec refresh time

Power supply

86 ~265VAC99~374VDC

Input

Rate current: 1A or 5A
Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary: 100Vph-ph or 110V, (optional)
Frequency: 50/ 60Hz

Power loss

2VA

Communication

RS485 serial, support Modbus-RTU


Baud rate: 2400, 4800, 9600, 19200,
38400bps
Address: 1~247

Dimension
(L x W x H)

Panel: 96 x 96 x 13.5 mm
Cut-out: 90 x 90 x 45.1 mm (basic)
90 x 90 x 66.6 mm (optional module)

Overload

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Status input

Wet contact, external power supply

Relay output

Node capacity: 250VAC/5A

IP index

IP52 (front panel) and IP30 (case)

Pulse output

Pulse output value: 1000~9999imp/ kWh


Pulse width: 60~100ms programmable

Weight

Basic unit: approx 400gr.

Environment

Operating temperature: -10~ +55


Storage temperature: -40~ +70
Humidity: 5%~95% non-condensing

Power frequency withstand voltage

AC 2KV/minute

Insulation resistance

50M

Impulse withstand voltage

4kV (peak), 1.2/50uS


Standard (EMC)

Electrostatic discharge immunity test


IEC 61000-4-2,Level 4
Radiated immunity test
IEC 61000-4-3,Level 3
Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B

Dimension & Installation


Unit: mm

Order Information
Basic unit: PST700
Note: 1: Current input 5A (optional 1A)
2: Voltage input: 0~600V.
3. Default PT secondary 100Vph-ph. (optional 110V)

Optional module
S
R
C
Ep

2 status input,
2 relay output
The 2nd RS485
2 pulse output

P
AI
AO
BA
M

Profibus communication (under development)


2 analog input (under development)
2 analog output (under development)
BACnet protocol (under development)
1GB memory (under development)

Note: 1. Max. 3 modules for 1 meter.


2. Module A can be repeatedly chosen for 1 meter, others can not be repeatedly chosen.
7

PMAC615 Single Phase Digital Panel Meter


Feature

Suit for 220V or 240V low voltage system.

Simultaneous sampling of Volts and Amps

Compact design with all real-time measurement

10 years back-up of integrated energy data

LED display, high brightness, auto-scrolling

CT ratio programmable

Pluggable terminals, easy to install and maintain

Panel size: 110 x 65mm

Standard: IEC62053-21, CE

Basic Function

Real time
metering

Optional Function

Parameter

Accuracy

Resolution

Measuring Range

DI

Two status input (wet contact)

Voltage

0.2%

0.01V

0 ~ 500Vph-ph

DO

One relay output

Current

0.2%

0.001A

0 ~ 50,000A

Power

0.5%

0.1 MW/ var

0 ~30MW/ Var

Power factor

0.5%

0.001

-1.000 ~ +1.000

Frequency

0.01

0.01Hz

45 ~ 65Hz

Active energy

1.0%

0.1kWh

0-99,999,999.9 kWh

COM

One RS485

Note: Reactive power and power factor


can be read via RS485 COM only

Technical Specification
Metering

True RMS, 1 sec refresh time

Power frequency withstand voltage

AC 2KV/minute

Input

Rate current: 5A (optional 1A)


Rate voltage: 220V (optional 240V)
Frequency: 50 or 60Hz

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS

Overload

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Dimension
(L x W x H)

Panel: 110 x 65 x 18 mm
Cut-out: 90 x 44.5 x 55 mm (+0.5mm)

Status input

2 channels, external power supply

IP index

IP54 (front panel) and IP20 (case)

Relay output

1 channel,
Node capacity: 220VAC/5A, 30VDC/5A

Weight

Approx 220gr.

Power supply

85~265VAC, 80~300VDC

Environment

Power loss

3VA

Operating temperature: -20~ +60

Communication

RS485 serial, support Modbus-RTU


Baud rate: 4800 or 9600bps
Address: 1~247

Storage temperature: -30~ +70


Humidity: 5%~95% non-condensing
Standard (EMC)

Electrostatic discharge immunity test


IEC 61000-4-2,Level 4
Radiated immunity test
IEC 61000-4-3,Level 3
Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B

Order Information
PMAC615----
W

Voltage + Current + Active Energy

Voltage + Current + Active Power + Reactive Power + Power Factor + Frequency + Active Energy

S
RC
C

Two External Status Input ( wet contact)


One Relay Output + One RS485 COM
One RS485 COM

PMAC625 Three-phase Digital Panel Meter


Feature

Suit for 220V, or 240V (ph-N) low voltage system

Simultaneous sampling of Volts and Amps

Compact design with all real-time measurement

10 years back-up of integrated energy data

LED display, high brightness, auto-scrolling

CT primary is programmable

Pluggable terminals, easy to install

Panel size: 96 x 96mm

Password protect

Standard: IEC62053-21, CE

Basic Function

Optional Function

PMAC625 measures and display one or more parameters listed below:

Two status input ( wet contact)

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

Two relay alarm output

CurrentIa, Ib, Ic, In

One RS485 communication

Active power Pa, Pb, Pc, P

Reactive power Qa, Qb, Qc, Q

Power factorPFa, PFb, PFc, PF

Frequency--F

Active energykWh

Reactive energy-- kvarh

Technical Specification
Metering

True RMS, 1 sec refresh time

Power frequency withstand voltage

AC 2KV/minute

Input

Rate current: 5A (optional 1A)


Rate voltage: 220Vph-N (optional 240V)
Frequency: 50/ 60Hz

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS

Overload

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Dimension
(L x W x H)

Panel: 96 x 96 x 18 mm
Cut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

Status input

2 channels, external power supply

IP index

IP54 (front panel) and IP20 (case)

Relay output

2 channels,
Node capacity: 220VAC/5A, 30VDC/5A

Weight

Approx. 350gr.

Environment

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

Power supply

85~265VAC, 80~300VDC

Power loss

2VA

Communication

RS485 serial, support Modbus-RTU


Baud rate: 4800 or 9600bps
Address: 1~247
Standard (EMC)

Electrostatic discharge immunity test


Radiated immunity test
Electrical fast transient/burst immunity test

IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B

PMAC625 Three-phase Digital Power Meter


Parameter

Accuracy

Resolution

Measuring Range

Voltage

0.2%

0.01V

264V(ph-N), 500V (ph-ph)

Current

0.2%

0.001

CT primary: 0~9,999A
CT secondary: 1 A or 5A

Power

0.5%

0.1W/ var

9,999 kW/ kvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

35-65Hz

Active energy

1.0%

0.1kWh

0-99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0-99,999,999.9 kvarh

Dimension & Installation


Unit: mm

Order Information
PMAC625---
W

Voltage + Current + Active Power + Reactive Power + Power Factor + Active Energy

Voltage + Current + Active Power + Reactive Power + Power Factor + Frequency + Active Energy
+ Reactive Energy

S
R
C

Two External Status Input ( wet contact)


Two Relay Alarm Output
One RS485 COM

Note: PMAC625 default rated voltage/ current is 220V/ 5A. Other customized input such as 240V or 1A is available, please mention the
requirement before place order.
Example: Model No. PMAC625-W-C, which indicates the device measures voltage, current, active power, reactive power, power factor,
active energy, and provide RS485 communication

10

PMAC720 Multifunction Power Meter


Feature

Suit for LV/ HV voltage system

Compact design with all real-time measurement

Consist of basic unit and optional modules

10 years back-up of integrated energy data

Large LCD, high brightness

High accuracy, V or I is 0.2%, kWh is class 1

CT and PT programmable

Panel size: 96 x 96mm

Password protect

Standard: IEC62053-21/ 23, CE

Basic Function
PMAC720 provides one RS485 communication,
measures and display real-time parameters:

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

CurrentIa, Ib, Ic, In

Active power Pa, Pb, Pc, P

Reactive power Qa, Qb, Qc, Q

Power factorPFa, PFb, PFc, PF

Frequency--F

Active energykWh

Reactive energy kvarh

Optional Function

Up to 31st harmonic analysis

Clock and SOE (event log)

TOU (multi-tariff)

Two RS485 communication port

One 4~20mA analog input

One 4~20mA analog output

Basic unit

Optional module

Optional Module

4 status input (dry contact) + 4 relay output

8 status input (dry contact) + 2 relay output

4 status input (wet contact) + 4 relay output

8 status input (wet contact) + 2 pulse output

2 pulse output + 2 analog output

Status input apply to monitoring various kinds of switch status


Relay output apply to monitoring over limit alarm with setpoint system
Pulse output apply to exporting pulse signal for active/ reactive energy

Technical Specification
Metering

True RMS, 1 sec refresh time

Power supply

85~265VAC, 80~300VDC

Input

Rate current: 5A (optional 1A)


Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary 57.7V/ 100V
Frequency: 50/ 60Hz

Power loss

2VA

Communication

RS485 serial, support Modbus-RTU


Baud rate: 2400, 4800, 9600, 19200bps
Address: 1~247

Dimension
(L x W x H)

Panel: 96 x 96 x 16 mm
Cut-out: 89.5 x 89.5 x 55 mm (+0.5mm)

IP index

IP54 (front panel) and IP20 (case)

Weight

Approx. 500gr.

Overload

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Status input
(optional)

8 channels,
provides 30VDC power if it is dry contact

Relay output
(optional)

4 channels,
Node capacity: 220VAC/5A, 30VDC/5A

Analog output
(optional)

2 channels,
4~20mA, load resistance: 400

Pulse output
(optional)

2 channels,
48~50VDC for external connection

Power frequency withstand voltage

AC 2KV/minute

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS

11

PMAC720 Multifunction Power Meter


Standard (EMC)

Environment

Electrostatic discharge immunity test


RF immunity test
Electrical fast transient/burst immunity test
Surge immunity test (1, 2/50s8/20s)
Conducted emissions
Radiated emissions

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

IEC 61000-4-2 Edition 2.0 (2008)


IEC 61000-4-3 Edition 3.0 (2007)
IEC 61000-4-4 Edition 2.0 (2004)
IEC 61000-4-5 Edition 2.0 (2005)
EN 61326-1:2006, CISPR 11:2004
EN 61326-1:2006, CISPR 11:2004

Parameter

Accuracy

Resolution

Voltage

0.2%

0.01V

Current

0.2%

0.001A

Power

0.5%

0.1W/ var

Measuring Range
Directly: 300Vph-N, 520Vph-ph
PT primary: 0~599,999V
PT secondary: 57.7Vph-N, 100Vph-ph
CT primary: 0~49,999A
CT secondary: 1 A or 5A
each phase: 0~100 MW/ Mvar
Total: 0~300 MW/ Mvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

45~ 65 Hz

Active energy

1.0%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kVarh

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

PMAC-

720N

720A

720B

720C

720D

720E

Feature
U-LL, U-LN, 3I, In, 3P, P, 3Q, Q,
F, 3PF, PF, kWh, kvarh,
RS485 communication

4 status input (dry contact) + 4 relay output

8 status input (dry contact) + 2 relay output

4 status input (wet contact) + 4 relay output

8 status input (wet contact) + 2 relay output

2 pulse output + 2 analog output (4~20mA)


H

Up to 31st harmonic analysis

Clock and SOE (event log) function

TOU ( time-of-use)

Two RS485 communication ports

AI

One 4~20mA analog input

AO

One 4~20mA analog output

Apparent power

Demand function

Remark: = standard feature, =optional function = conditional function


1. If select -F, -T should be selected also.
2. Analog port-AI and AO are incompatible feature, can not be selected together
3. For module PMAC720N-, PMAC720E- , the SOE function is invalid.

12

PMAC720 Multifunction Power Meter


Dimension & Installation
unit: mm

Order Information
PMAC720---- ----
N
A
B
C
D
E

Basic Module
Basic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs
Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs
Basic Module + 4 Status Inputs (Wet Contact) + 4 Relay Outputs
Basic Module + 8 Status Inputs (Wet Contact) + 2 Relay Outputs
Basic Module + 2 Pulse Outputs + 2 Analog Outputs (4-20mA)

H
T
F
M

Up to 31st Harmonic Analysis


Clock and SOE (Event Log) Function
TOU (Time- of- Use)
Two RS485 Communication Ports

AI
AO

One 4-20mA Analog Input


One 4-20mA Analog Output

V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Example: Model No. PMAC720-A-H-AO-V1, which indicates the device provides basic function + 4 status input + 4 relay
output + harmonic analysis + one analog output, rated input 57.7/ 100V, 5A

13

PMAC727 Multifunction Power Meter


Feature

Suit for LV/ HV voltage system

Compact design with all real-time measurement

Build-in clock and event logging

Phase failure alarm

10 years back-up of integrated energy data

Large LCD, high brightness

High accuracy, V or I is 0.2%, kWh is class 1

CT and PT programmable

Pluggable terminals, easy to install

Panel size: 96 x 96mm

Password protect

Standard: IEC62053-21/ 23, CE

Basic Function

Basic Data Recording Function

PMAC727 provides one RS485 communication,


measures and display real-time parameters:

Record data once per hour ( last 24 hours)

Record the Avg/ Max./ Min. data of every day (last 31 days)

Record energy consumption hourly ( last 24 hours), daily


(last 31 days), and monthly (last 12 months)

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

Voltage unbalance rate UL-L unbal, UL-N unbal

CurrentIa, Ib, Ic, In

Record phase failure event, max. 30 events

Current unbalance rate I unbal

Record over-limit event, max. 200 events

Active power Pa, Pb, Pc, P, power load rate

Reactive power Qa, Qb, Qc, Q

Power factorPFa, PFb, PFc, PF

Frequency--F

Active energykWh

Reactive energy kvarh

31st harmonic & THD

Temperature of switch box/ cable

Technical Specification
Metering

True RMS, 1 sec refresh time

Power supply

85~265VAC, 80~300VDC

Input

Rate current: 1A or 5A
Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary 57.7V/ 100V
Frequency: 50/ 60Hz

Power loss

2VA

Communication

RS485 serial, support Modbus-RTU


Baud rate: 4800,9600, 19200, 38400bps
Address: 1~247

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Dimension
(L x W x H)

Panel: 96 x 96 x 18 mm
Cut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

IP index

IP54 (front panel) and IP20 (case)

Weight

Approx. 500gr.

Environment

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

Overload

Power frequency withstand voltage

AC 2KV/minute

Insulation resistance

50M

Impulse withstand voltage

4kV (peak), 1.2/50uS

Standard (EMC)
Electrostatic discharge immunity test
IEC 61000-4-2,Level 4
Radiated immunity test
IEC 61000-4-3,Level 3
Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B
14

PMAC727 Multifunction Power Meter


Parameter

Accuracy

Resolution

Measuring Range
Directly: 300Vph-N, 520Vph-ph

Voltage

0.2%

0.01V

Current

0.2%

0.001A

CT primary: 0~49,999A
CT secondary: 1 A or 5A

Power

0.5%

0.1W/ var

each phase: 0~100 MW/ Mvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

35~ 65 Hz

Active energy

1.0%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kVarh

THD

1.0%

0.001

0~100.0%

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

Temperature

0~150

PT primary: 0~499,999V
PT secondary: 57.7Vph-N, 100Vph-ph

Model PMAC727

Data Record Function


Record data per hour
(last 24 hours)

Record Avg./ Max./ Min.


data of every day (last
31 days)

Over-limit record

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

UL-L unbal, UL-N unbal

CurrentIa, Ib, Ic, In

I unbal

Active power Pa, Pb, Pc, P

Load rate

Reactive power Qa, Qb, Qc, Q

Power factorPFa, PFb, PFc, PF

Frequency

and daily (last 31 days),


monthly (last 12 months)

Fundamental RMS current

Harmonic Ratio for Current (3-31st)

Total Harmonic Distortion for Current (THDi)

Fundamental RMS voltage

Harmonic Ratio for Voltage (3-31st)

Total Harmonic Distortion for Voltage (THDu)

Measuring Parameters

Active energy kWh (present & total)


Reactive energy kvarh (present & total)

15

PMAC727 Multifunction Power Meter

Dimension & Installation


unit: mm

Order Information
PMAC727--
V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Example: Model No. PMAC727-V1, which indicates the device provides all basic function, rated input 57.7/ 100V, 5A

16

PMAC735 Multifunction Power Meter


Feature

Suit for LV/ HV voltage system

Compact design with all real-time measurement

Consist of basic unit and optional modules

10 years back-up of integrated energy data

Large LCD, high brightness

High accuracy, V or I is 0.2%, kWh is class 1

CT and PT programmable

Pluggable terminals, easy to install

Panel size: 96 x 96mm

Password protect

Standard: IEC62053-21/23, CE

Basic Function

Optional Module

4 status input + 4 relay output

PMAC735 provide one RS485 communication,

8 status input + 2 relay output

measures and display real-time parameters:

8 status input + 2 pulse output

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

Profibus communication module

Voltage unbalance rate UL-L unbal, UL-N unbal

Status input apply to monitoring various kinds of switch status

CurrentIa, Ib, Ic, In

Relay output apply to monitoring over limit alarm with setpoint system

Current unbalance rate I unbal

Pulse output apply to exporting pulse signal for active/ reactive energy

Active power Pa, Pb, Pc, P

Profibus supports high speed bus communication up to 1.5M, and

Reactive power Qa, Qb, Qc, Q

Compatible with SIEMENS Profibus communication system.

Apparent powerSa, Sb,Sc, S

Power factorPFa, PFb, PFc, PF

Frequency--F

Active energykWh (4 quadrant)

Optional Function

Reactive energy kvarh (4 quadrant)

Up to 31st harmonic analysis, K factor, THD

Demand and Max. record for I, P, Q, S

SOE (event log)

Max./ Min. value

One 4~20mA analog output

Technical Specification
Metering

True RMS, 1 sec refresh time

Power frequency withstand voltage

AC 2KV/minute

Input

Rate current: 1A or 5A
Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary 57.7/ 100V
Frequency: 50/ 60Hz

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Power supply

85~265VAC, 80~300VDC

Power loss

2VA

Status input
(optional)

8 channels,
provides 30VDC power if it is dry contact

Communication

Relay output
(optional)

4 channels,
Node capacity: 220VAC/5A, 30VDC/5A

RS485 serial, support Modbus-RTU


Baudrate: 4800, 9600, 19200, 38400bps
Address: 1~247

Analog
output
(optional)

1 channel,
4~20mA, load resistance: 400

Dimension
(L x W x H)

Panel: 96 x 96 x 18 mm
Cut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

IP index

IP54 (front panel) and IP20 (case)

Pulse output
(optional)

2 channels,
48~50VDC for external connection

Weight

Approx. 500gr.

Overload

17

PMAC735 Multifunction Power Meter

Standard (EMC)

Environment

Electrostatic discharge immunity test


Radiated immunity test
Electrical fast transient/burst immunity test
Surge immunity test (1, 2/50s8/20s)
Conducted emissions
Radiated emissions

Parameter

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4
IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B

Accuracy

Resolution

Measuring Range
Directly: 300Vph-N, 520Vph-ph

Voltage

0.2%

PT primary: 0~499,999V
PT secondary: 57.7Vph-N, 100Vph-ph

0.01V

(Note: when PT ratio is non-integer, voltage range is 0~ 49,999V)


Current

0.2%

0.001A

CT primary: 0~49,999A
CT secondary: 1 A or 5A

Power

0.5%

0.1W/ var

each phase: 0~100 MW/ Mvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

35~ 65 Hz

Active energy

1.0%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kVarh

THD

1.0%

0.001

0~100.0%

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

Model PMAC

735N

735A

735B

735E

735P

Feature
U-LL, U-LN, 3I, In, 3P, P, 3Q, Q, 3S, S, F,
3PF, PF, kWh, kvarh,
Demand& maximum recording,
Unbalance rate,
Build-in clock,
Max./min. recording,
RS485 communication

4 status input + 4 relay output

8 status input + 2 relay output

8 status input + 2 pulse output

Profibus communication
Harmonic analysis, K factor

SOE
One 4-20mA analog output

Remark: = standard, =optional

18

PMAC735 Multifunction Power Meter


Dimension & Installation
unit: mm

PMAC735

Auxiliary
Module

Order Information
PMAC735---- ------
N
A
B
E
P

Basic Module
Basic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs
Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs
Basic Module + 8 Status Inputs (Dry Contact) + 2 Pulse Outputs
Basic Module + Profibus Module

Up to 31st Harmonic Analysis, THD, K Factor

SOE (Event Log) Function

AO

One 4-20mA Analog Output

V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Example: Model No. PMAC735-A-H-V1, which indicates the device provides basic function + 4 status input + 4 relay output +
harmonic analysis, rated input 57.7/ 100V, 5A

19

PMAC760 Intelligent Power Quality Analyzer


Feature

Suit for LV/ HV voltage system

True-RMS measuring parameters

Power quality analysis, over limit alarm

Integrated measure, analyze, control and protect function

Use DSP chip to process voltage and current signal

Graphical data, easy and clearly for reading

Large and color LCD, high brightness

10 years back-up of integrated energy data

High accuracy, V or I is 0.2%, kWh is class 1

Panel size: 126.7 x 126.7mm

Password protect

Standard: IEC62053-21/ 23, CE

Basic Function

Real time metering

Voltage

Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg

Current

Ia, Ib, Ic, In, Iavg

Power

Pa, Pb, Pc, P, Qa, Qb, Qc, Q, Sa, Sb,Sc, S

Power factor

PFa, PFb, PFc, PF

Energy

kWh and kvarh (4 quadrant), kVAh

Max./ Min. value

Max._U, Max._I, Max._P, Max._Q


Min._U, Min._I, Min._P, Min._Q

Demand

Dmd_I, Dmd_P, Dmd_Q ,Dmd_S

Phase angle
Frequency

Voltage fluctuate
Voltage deviation
Power quality analysis

Frequency deviation
Unbalance

U_unbl, I_unbl

Harmonic

THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi


2nd-31st harmonic (display), 32nd -63rd harmonic (COM)

Setpoint alarm

Over/ under limit alarm

DI/ DO

4 status input + 4 relay output

RS485

Modbus-RTU protocol

SOE and Clock

Event log and real time clock

Optional Function
Ethernet

Ethernet communication port, 10M, UDP/ TCP Server/ TCP Client

USB

USB 2.0 communication port

20

PMAC760 Intelligent Power Quality Analyzer


LCD display graphical data
Voltage wave

SOE event log

Harmonic

Phase vector

Multi-communication

Technical Specification
Metering

True RMS, 1 sec refresh time

Power frequency withstand voltage

AC 2KV/minute

Input

Rate current: 1A or 5A
Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary 57.7/ 100V
Frequency: 50/ 60Hz

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Power supply

85~265VAC, 80~300VDC

Power loss

10VA

Dimension
(L x W x H)

Panel: 126.7 x 112.7 x 13 mm


Cut-out: 119 x 105 x 91 mm (+0.5mm)

IP index

IP54 (front panel) and IP20 (case)

Weight

Approx. 760gr.

Overload

Status input

4 channels
Dry contact (internal 30VDC power supply)

Relay output

4 channels,
Node capacity: 250VAC/5A, 30VDC/5A

Standard (EMC)
Electrostatic discharge immunity test
Radiated immunity test
Electrical fast transient/burst immunity test
Surge immunity test (1, 2/50s8/20s)
Conducted emissions
Radiated emissions

Environment
IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4
IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

21

PMAC760 Intelligent Power Quality Analyzer


Parameter

Accuracy

Resolution

Measuring Range

Voltage

0.2%

0.01V

Current

0.2%

0.001A

CT primary: 0~49,999A
CT secondary: 1 A or 5A

Power

0.5%

0.1W/ var

each phase: 0~100 MW/ Mvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

45~ 65 Hz

Active energy

1.0%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kVarh

THD

1.0%

0.001

0~100.0%

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

Directly: 300Vph-N, 520Vph-ph


PT primary: 0~999,999V
PT secondary: 57.7Vph-N, 100Vph-ph

Dimension & Installation


Unit: mm

COM
SHLD

SHLD

Order Information
PMAC760----

Ethernet port

USB port

V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Example: Model No. PMAC760-N-V3, which indicates the device provides basic function + Ethernet communication port, rated
input 220/ 380V, 5A

22

PMAC901 Single Phase Din-rail Energy Meter


PMAC903 Three Phase Din-rail Energy Meter

Feature

Suit for 220V AC low voltage system

6 +1 digits LCD display (999999.9 kWh)

kWh accuracy class 0.5S

LED indicates pulse, reverse energy

3 keys for programming

CT programmable, pulse output

35mm DIN rail installing, standard DIN ED5002

High temperature resistant materials

Spring type buckle, easy to install

Standard: IEC62053-21/ 22/23, CE, KEMA

Basic Function

Measure and display kWh value

One RS485 communication

Support Modbus-RTU

Other real time data via RS485: V, I, P, Q, S, PF, F

Optional Function

Multi-tariff

Reactive energy measuring

Demand analysis

Technical Specification
Rated current

10(40)A, 10(60)A, 20(100)A or 5A/ CT

Rated voltage

AC 220Vph-N, 50Hz (optional 120V, 60Hz)

Input
consumption

2VA

Overload

115% of rated

Pulse output

1 or 2 channels

Pulse output value

PMAC901:1000imp/kWh
PMAC903: 400imp/ kWh (40A or 60A)
200imp/ kWh (100A)
3600imp/ kWh (5A/ CT)

Connection mode

PMAC901: 1-phase 2-wire


PMAC903: 3-phase 4-wire

Impulse duration

80 ms

Power supply

Self supply, 220VAC, 50-60Hz

Communication

RS485 serial, Modbus-RTU


Baud rate: 4800 or 9600bps
Address: 1~247

Environment

Operating temperature: -20~ +55


Storage temperature: -20~ +55
Humidity: 5%~95% non-condensing

Standard (EMC)
Electrostatic discharge immunity test
Radiated immunity test
Electrical fast transient/burst immunity test

IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 4
EN 55022,Class B
EN 55022,Class B

Accuracy

Display
data

Communication data

Parameter

Resolution

Measuring Range

0.2%

0.01V

198V~242V (L-N)

0.2%

0.2%

0.001A

0.5~4995A

Active power

0.5%

0.5%

0.1W

0~1MW

Reactive power

No

1.0%

0.1Var

0~1Mvar

Apparent power

0.5%

0.5%

0.1VA

0~1MvA

Power factor

No

0.5%

0.001

-1.000~+1.000

Frequency

No

0.01

0.01Hz

45Hz~65Hz

Active energy

Class 0.5S

Class 0.5S

0.1kWh

0~999999.9 kWh

Reactive energy

No

Class 2

0.1kVarh

0~999999.9 kvarh

PMAC901

PMAC903

Voltage

0.2%

Current

23

PMAC901 Single Phase Din-rail Energy Meter


PMAC903 Three Phase Din-rail Energy Meter

Dimension
PMAC901

PMAC903
65.0mm

125.5mm

65.0mm
50.0mm

PMAC903

45.0mm

94.0mm

45.0mm

35.7mm

94.0mm

50.0mm

35.7mm

75.0mm

Order Information
PMAC901---- ----
PMAC903---- ----
C

One RS485 communication

1
0.5S

Active energy accuracy: Class 1


Active energy accuracy: Class 0.5S

40
60
100
5

Rated current: 10 (40)A


Rated current: 10 (60)A
Rated current: 20 (100)A
Rated current: 5A / CT (when In>100A, connect via CT)

F
Q
D

TOU (Multi-tariff)
Reactive energy measuring (only available for PMAC903)
Demand analysis (only available for PMAC903)

Note: PMAC901, 903 default rated voltage 220V, frequency 50Hz. Other customized input such as120V or 60Hz is available, please
mention the requirement before place order.
Example 1: Model No. PMAC901-C-1-40-F, which indicates the device provides basic function, rated current is 40A (direct), accuracy class 1,
and measure multi-tariff
Example 2: Model No. PMAC903-C-1-5-Q, which indicates the device provides basic function, rated current is 5A/ CT, accuracy class 1, and
measure reactive energy

24

PMAC905 Multifunction Energy Meter


Feature

Suit for LV/ HV voltage system

CT and PT programmable

kWh accuracy class 0.5S

Password protect

Panel size: 96 x 96mm

Pluggable terminals, easy to install

Large high-contrast LCD

Two pulse output

Standard: IEC62053-22/ 23, CE, KEMA

Basic Function

Optional Function

PMAC905 measure and display real-time parameters:

Statistics of multi-tariff energy: 8 periods of time, 4 different tariff

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

CurrentIa, Ib, Ic, In

Record historical energy value: (kWh & kvarh) data of last 31 days/ 12
months

Active power Pa, Pb, Pc, P

One RS485 communication (Modbus)

Reactive power Qa, Qb, Qc, Q

Apparent powerSa, Sb,Sc, S

Power factorPFa, PFb, PFc, PF

Frequency--F

EnergykWh, kvarh (4 quadrant)

Technical Specification
Connection mode

3-phase 3-wire, 3-phase 4-wire

Pulse output

2 channels

Rated current

1A or 5A

Pulse output value

1000~9900 imp/kWh programmable

Rated voltage

direct 120 ~277Vph-N, (optional)


PT secondary 57.7/ 100V

Impulse duration (width)

50ms

Power supply

85 to 265VAC or 100 to 300VDC

Frequency

50/ 60Hz

Communication

CT earth connection
(secondary)

yes

RS485 serial, Modbus-RTU


Baud rate: 4800 or 9600bps
Address: 1~247

Power consumption

3VA

Environment

Overload

120% of rated

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

Standard (EMC)
Electrostatic discharge immunity test
Radiated immunity test
Electrical fast transient/burst immunity test
Parameter

Accuracy

IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4
Resolution

Surge immunity test (1, 2/50s8/20s)


Conducted emissions
Radiated emissions

IEC 61000-4-5,Level 4
EN 55022,Class B
EN 55022,Class B

Measuring Range
Directly: 300Vph-N, 520Vph-ph

Voltage

0.2%

0.01V

Current

0.2%

0.001A

CT primary: 0~49,999A
CT secondary: 1 A or 5A

Power

0.5%

0.1W/ Var/ VA

0~100 MW/ MVar/ MVA

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

35Hz~65Hz

Active energy

Class 0.5S

0.1kWh

0~999999.9 kWh

Reactive energy

Class 2

0.1kVarh

0~999999.9 kvarh

PT primary: 0~499,999V
PT secondary: 57.7Vph-N, 100Vph-ph

25

PMAC905 Multifunction Energy Meter


Dimension & Installation
Unit: mm

96mm

9.0

46.7

18.3
90mm

96mm

56.5
89.5

90mm

Order Information
PMAC905---- ----
F

Statistics of multi-tariff energy

Record historical energy value

One RS485 communication

V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Note: Other customized input such as 110V or 1A is available, please mention the requirement before place order.
Example: Model No. PMAC905-F-D-V3 , which indicates the device provides basic function, auxiliary statistics and record function.
Rated input is 220V/380V, 5A.

26

PMAC915 Three Phase Multi-tariff kWh Meter


Feature

LCD display

With the DSP technology and the real-time high speed calculation, it guarantees the
measuring accuracy in the case of big load wave and harmonic waves.

2MB large data storage, can be extended to 4MB

Keep high accuracy from 1% In to 600% In

Three phase power source supply, but even there is only one phase work, the meter
will keep running.

Read the meter at power failure, can still read the meter by the button or with
infrared function

Function

Energy measurement: measure kWh or kvarh (reverse/ forward) of 4 quadrants in different tariffs

Max. demand measurement: measure Max. demand kWh or kvarh (reverse/ forward) of 4 quadrants in different tariffs

Real-time measurement: measure voltage, current, active power, reactive power, power factor, frequency, 2nd -31st harmonic (U and I)

Multi-tariff: settable 10 tariffs, 14 time zones, 12 sets of time period list, 14 time periods, 13 holidays, holiday and weekend can be
preset in different time periods.

No-voltage record: record no-voltage of each phase and total no-voltage time of four months, record no-voltage occurs time, end time
and the energy in the time of no-voltage of the last 10 times.

Event log: record last 10 demand resetting, program, no phase, over-voltage, no voltage, unti-phase, overload, current unbalance,
calibrate time, power off and power on.

Load monitor: set voice-optical alarm or relay output when load is beyond a certain value

Harmonic monitor: monitor the 2nd 16th harmonic (U and I), when the value is beyond the setting point, the meter alarm and record the
event.

Energy freeze: freeze the energy by broadcast, also can freeze the energy at hour

Load curve: select different data groups with different or same time terminal (1 to 1440 mins optional) to record the data scrolling with
time remark. Storage space is not less than 2MKb.

Communication port: RS485 and infrared

Relay output: two routes programmable relay output

Pulse output and LED indicator: two pulse output for active and reactive energy.

Technical Specification
Model
Accuracy

PMAC915
Active energy

Class 0.5s

Reactive energy

Class 2

Display

LCD

Rated voltage

PT connect:

357.7/100V

Direct connect

3220/380V

CT connect

31(2)A, 35(6)A

Direct connect

310(40)A, 320(80)A, 330(100)A

Voltage circuit

<2W/ 10VA (external power 0.5VA)

Current circuit

<1VA

Rated (Max.) current

Power loss

Operating temperature

-20C to +60C

Storage

-40C to +70C

27

PMAC915 Three Phase Multi-tariff kWh Meter


Relative humidity

85%

Voltage range

0.7Un ~1.3Un

Reference frequency

50Hz 5%

Start current

0.001 In

MTBF

5104 h

Service life

15 Years

Clock error

0.5s /d (23C)

Dimension

290mm x 170mm x85mm

Net weight

Approx. 1.8 kg

Standard

IEC62052-11/21
IEC62053-21/22/23
IEC62056-21/ 42/ 53/ 61/ 62

Dimension & Installation


Unit: mm

28

PMAC921 Single Phase Multi-tariff kWh Meter


Feature

LCD display

Measure active energy, no need to calibrate for a long working time

LSI design, less spare part, low power consumption, simple structure.

Keep a good linear error within the range 1%Ib~Imax.

Use quality component with long service life, reliable accuracy, cannot be affected by
the frequency, temperature, voltage, harmonic.

Function

Measure reverse and forward energy, and reverse energy is measured as forward energy

Timely single phase power consumption measurement with 3 tariffs and 12 time periods

Automatically read and store the energy, it can store 12 months data

Real time Clock

RS485 communication port realize remote meter concentrative reading.

Infrared communication port to realize point to point communication.

Waking up the meter by pressing the key and meter reading function during power off.

Technical Specification
Model

PMAC921

Relative humidity

85%

Accuracy

Active energy: Class 1.0

Voltage range

0.7Un ~1.3Un

Display

LCD

Reference frequency

50Hz/ 60Hz

Rated voltage

220~240V

Start current

0.004Ib

Rated (Max.) current

2.5(10)A, 5(20)A, 5(30)A,


10(40)A, 20(80)A

Clock error

0.5s /d (23C)

Dimension

182mm x 129mm x 49mm

Power
loss

Voltage circuit

<1W/ 6VA
Net weight

Approx. 700g

Current circuit

<1VA
Standard

IEC62052-11/21
IEC62053-21/22/23
IEC62056-21

Operating temperature

-25C to +55C

Storage

-40C to +70C

Dimension & Installation


Unit: mm

29

Zhuhai Pilot Technology Co., Ltd.

Your representative

Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone,
Zhuhai, Guangdong, China
Post Code: 519085
Tel: +86 756 3629687/ 3629673
Fax: +86 756 3629600/ 3629700
Email: overseamarket@pmac.com.cn
http://www.pmac.com.cn

PILOT reserves the right to modify features without prior notice in view of continued improvement

Potrebbero piacerti anche