Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
OBJECTIVES
1. Explain:
(a) how a generators equivalent circuit is obtained.
(b) why the simplified equivalent circuit will, for most purposes, provide acceptable
results.
2. Explain the operation of a generator when it supplies power at:
(a) 1.0 pf.
(b) lagging pf.
(c) leading pf.
INTRODUCTION
It is possible to explain the operation of a generator by using magnetic flux
diagrams as shown in the previous lesson. However, it is often easier to represent the
operation of a generator by considering its equivalent circuit.
In this lesson, the generators magnetic behavior and equivalent circuits are considered
for the following conditions:
(a) 1.0 pf load. This type of load occurs when a generator load is purely resistive.
(b) lagging pf load. This type of load occurs when a generator supplies, for example,
induction motors.
(c) leading pf load. This type of load occurs when a generator has a resistive and
capacitive load. The capacitance could be due to lightly load transmission lines.
Figure1 can be simplified to the diagram shown in Figure 2. Xa and XL, because
they are both reactances, can be summed forming Xd which is known as the generator
synchronous reactance. The term synchronous is used because this is the reactance of
the generator at its synchronous speed as distinct from standstill or any other speed. Ra,
because it is small compared to Xd, is neglected in this lesson.
1.0 pf load
Figure 4: Equivalent circuit of a generator supplying a 1.0 pf Load.
Figure 8: Phasor diagram showing a generator on full load at 0.9 pf lagging. The
MW load is the same as in Figure 5.
Note the following:
(a) As the generator is operating at 0.9 pf lag, the Ia phasor lags the VT phasor by .
(b) The laXd phasor is at 90 degrees to the Ia phasor.
(c) As the generator is being loaded from 0 load to the same MW load in Figure 5 but
with pf = 0.9 lag, to keep the terminal voltage VT constant, the generated voltage E has to
be increased. This is done by increasing the rotor current. Note E load 0.9 pf lag is greater
than E load at 1.0 pf, and the load angle is smaller. A opposes the rotor flux and
decreases VT. Rotor current has to be increased to increase F to maintain VT at the set
point. The increased excitation causes the load angle to decrease.
10
Figure 11: Phasor diagram showing a generator on full load at 0.9 pf leading. The
MW load is the same as in Figure 5.
Note the following:
(a) As the generator is operating at 0.9 pf lead, the Ia phasor leads the VT phasor by .
(b) The IaXd phasor is at 90 to the Ia phasor.
(c) As the generator is being loaded from 0 load to the same MW load as Figure 5 but pf
= 0.9 leading, to keep the terminal voltage VT constant, the generated voltage E has to be
decreased relative to the 0.9 pf lag and 1.0 pf conditions, this is done by reducing the
rotor current. Note E load 0.9 pf lead is less than E load pf =1.
11