Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
High-speed train traction power supply system causes serious negative current problem.
Railway power conditioner (RPC) is efficient in negative sequence compensation. A novel
power quality collaboration compensation system and strategy based on RPC is proposed in
this paper. The minimum capacity conducted is 1/3 smaller than traditional single station
compensation. Simulation results have confirmed that the collaboration compensation system
proposed can achieve a good performance at the negative sequence compensation with
capacity and cost efficient.
CONTENTS
1. INTODUCTION
2. RAILWAY ELECRIFICATION DESIGN SYSTEM
2.1 CHARACTERISTICS OF ELECTIC TRACTION
2.2 ADVANTAGES & DIS-ADVANTAGES
2.2.1 SUMMARY
3. HARMONICS
3.1 HARMONICS
3.2 WHY WORRY ABOUT THEM
3.3 WHER THEY COME FROM
3.4 WHERE TO LOOK FOR THEM
3.5 HOW DO YOU FIND THEM
3.6 WHEN ARE THEY A PROBLEM
3.7 HOW DO YOU GET RID THEM
3.8 TOTAL HARMONIC DISTROTION
CHAPTER 1
INTRODUCTION
With the rapid development of high-speed railway in China, power quality has
become a major concern for traction supply system. Compared with normal electrification
railway locomotive load, high-speed locomotive load has some characteristics, such as big
instantaneous power, high power factor, low harmonic components and high negative
sequence component. A large amount of negative current is injected into grid, which causes
serious adverse impact on power system, such as increasing motor vibration and additional
loss, reducing output ability of transformers and causing relay protection misoperation. These
adverse impacts threaten the safety of high-speed railway traction supply system and power
system. Therefore, its necessary to take measures to suppress negative current.
Many methods and power quality compensators are studied in order to solve the issue
of power quality. The traditional methods adopted to suppress negative current are as follows:
(1) Connect unbalanced load to different supply terminals;(2) Adopt phase sequence rotation
to make unbalanced load distributed to each sequence reasonably;(3) Connect unbalanced
load to higher voltage level supply terminals; (4) Use balanced transformers such as Scott
transformer and impedance balance transformer. These methods have some effects on
reducing unbalance degree, but they are lack of flexibility and can't adjust dynamically.
Recent years, high-voltage, large-capacity Static Var Compensator (SVC), Active
Power *Filter (APF) and Static Compensator (STATCOM) have become focus on power
quality compensation of electrified railway. However, these methods all need high-voltage
transformers which increase cost. APF is effective in suppressing harmonic currents in
electrified railway but rarely used in negative sequence compensation. An active power
quality compensator (APQC) with a impedance-matching balance transformer or a Scott
transformer is proposed to compensate negative-sequence current, harmonics and reactive
current. Reference put forward a proposal of Railway Power Conditioner (RPC), RPC can
make comprehensive compensation of negative sequence components, harmonics and
reactive power. Reference carries a dual-loop control strategy in order to improve the control
effect and performance of RPC. Taken into account the disturbance and variation of
electrified railway environment, a recursive proportional-integral control based on
fuzzyalgorithm is adopted to realize a fast and smooth tracking to reference current.
Reference raises a method of setting up two groups of thyristor control reactors (TCR) and
two groups of thyristor control 3rd harmonic wave filter besides RPC. The RPC is used to
transfer active power; the reactive power is supplied by the TCR and the filter. These works
prove that RPC is a effective way to solve the power quality problems in railway system. But
the compensator capacity is still too big to make RPC into practice.
To reduce the high compensator capacity, this paper puts forward a new railway
negative unbalance compensation system based on the thought of multiple RPC collaboration
compensation. This method realizes a minimum compensation capacity which is strictly
proved, which reduces 1/3 capacity compared with traditional single station RPC
compensation method. The simulation results have verified the correctness of the method
proposed in this paper.
CHAPTER 2
RAILWAY ELECTRIFICATION SYSTEM
A railway electrification system supplies electrical energy to railway locomotives and
multiple units so that they can operate without having an on-board prime mover. There are
several different electrification systems in use throughout the world. Railway electrification
has many advantages but requires significant capital expenditure for installation.
Fig: 2(b) Overhead wire and centenary in Bridgeport, Connecticut, United states
Voltage
Current
Frequency
Contact System
Disadvantages
Disadvantages include:
mostly an issue for long distance trips, but many lines come to be dominated by
through traffic from long-haul freight trains (usually running coal, ore, or containers
to or from ports). In theory, these trains could enjoy dramatic savings through
electrification, but it can be too costly to extend electrification to isolated areas, and
unless an entire network is electrified, companies often find that they need to continue
use of diesel trains even if sections are electrified. The increasing demand for
container traffic which is more efficient when utilizing the double-stack car also has
network effect issues with existing electrifications due to insufficient clearance of
overhead electrical lines for these trains, but electrification can be built or modified to
have sufficient clearance, at additional cost.
Additionally, there are issues of connections between different electrical services,
particularly connecting intercity lines with sections electrified for commuter traffic,
but also between commuter lines built to different standards. This can cause
electrification of certain connections to be very expensive simply because of the
implications on the sections it is connecting. Many lines have come to be overlaid
with multiple electrification standards for different trains to avoid having to replace
the existing rolling stock on those lines. Obviously, this requires that the economics of
a particular connection must be more compelling and this has prevented complete
electrification of many lines. In a few cases, there are diesel trains running along
completely electrified routes and this can be due to incompatibility of electrification
standards along the route.
2.2.1Summary
Summary of advantages and disadvantages:
Lines with low frequency of traffic may not be feasible for electrification (especially
using regenerative braking), because lower running cost of trains may be overcome by
the higher costs of maintenance. Therefore most long-distance lines in North America
and many developing countries are not electrified due to relatively low frequency of
trains.
Electric locomotives may easily be constructed with greater power output than most
diesel locomotives. For passenger operation it is possible to provide enough power
with diesel engines (see e.g. 'ICE TD') but, at higher speeds, this proves costly and
impractical. Therefore, almost all high speed trains are electric.
The high power of electric locomotives gives them the ability to pull freight at higher
speed over gradients; in mixed traffic conditions this increases capacity when the time
between trains can be decreased. The higher power of electric locomotives and an
electrification can also be a cheaper alternative to a new and less steep railway if
trains weights are to be increased on a system.
2.3 Energy efficiency
There is a significant amount of published material that concludes that electric trains are more
energy efficient than diesel-powered trains and, with suitable energy production, can have a
smaller carbon dioxide footprint. Some of the reasons include:
electric trains are generally lighter than self powered versions (e.g. diesel traction);
they do not have to carry the weight of prime movers, transmission and fuel.
this is partially offset, however, by the weight of electrical control equipment, and in
the case with high-voltage AC by the weight of traction transformers, which may be
particularly heavy with low frequency AC (e.g. 16.7 Hz.).
the electricity may be generated from various energy sources which are more efficient
than a diesel engine, as well as lessening reliance on petroleum products and reducing
carbon dioxide emissions, including;
nuclear power,
renewable resources (e.g. hydroelectricity, wind generation, etc.),
large fossil fuel using power stations with greater efficiency (although they may still
have a relatively large carbon footprint).
under certain conditions, some suitably equipped electric trains can use regenerative
braking to return power to the electrification system so that it may be used elsewhere;
by other vehicles within the network section;
often implemented in tram networks, where there is a high density of vehicles in each
fairly short powered section,
on high voltage mainlines where there may be several trains within each long section,
on mountainous lines where trains may be scheduled such that one is ascending whilst
another descends;
in some form of energy storage, such as flywheel energy storage so that it may be
used later (e.g. to accelerate a train from a station at which it has recently stopped)
The external cost of railway is lower than other modes of transport but the electrification
brings it down further if it is sustainable.
Also, the lower cost of energy from well to wheel and the ability to reduce pollution and
greenhouse gas in the atmosphere according to the Kyoto Protocol is an advantage.
CHAPTER 3
HARMONICS
3.1 HARMONICS
The typical definition for a harmonic is a sinusoidal component of a periodic wave
or\ quantity having a frequency that is an integral multiple of the fundamental frequency.
[1]. Some references refer to clean or pure power as those without any harmonics. But
such clean waveforms typically only exist in a laboratory. Harmonics have been around for a
long time and will continue to do so. In fact, musicians have been aware of such since the
invention of the first string or woodwind instrument. Harmonics (called overtones in
music) are responsible for what makes a trumpet sound like a trumpet, and a clarinet like a
clarinet.
Electrical generators try to produce electric power where the voltage waveform has
only one frequency associated with it, the fundamental frequency. In the North America, this
frequency is 60 Hz, or cycles per second. In European countries and other parts of the world,
this frequency is usually 50 Hz. Aircraft often uses 400 Hz as the fundamental frequency. At
60 Hz, this means that sixty times a second, the voltage waveform increases to a maximum
positive value, then decreases to zero, further decreasing to a maximum negative value, and
then back to zero. The rate at which these changes occur is the trigometric function called a
sine wave, as shown in figure 1. This function occurs in many natural phenomena, such as the
speed of a pendulum as it swings back and forth, or the way a string on a voilin vibrates when
plucked.
sub harmonic frequencies being drawn from the electric power grid. These levels can be quite
high during the melt-down phase, and usually effect the voltage waveform.
3.2 Why Worry About Them
The presence of harmonics does not mean that the factory or office cannot run
properly. Like other power quality phenomena, it depends on the stiffness of the power
distribution system and the susceptibility of the equipment. As shown below, there are a
number of different types of equipment that can have mis operations or failures due to high
harmonic voltage and/or current levels. In addition, one factory may be the source of high
harmonics but able to run properly. This harmonic pollution is often carried back onto the
electric utility distribution system, and may effect facilities on the same system which are
more susceptible.
Some typical types of equipment susceptible to harmonic pollution include: Excessive neutral current, resulting in overheated neutrals. The odd triplen harmonics in three
phase wye circuits are actually additive in the neutral. This is because the harmonic number
multiplied by the 120 degree phase shift between phases is a integer multiple of 360 degrees.
This puts the harmonics from each of the three phase legs in-phase with each other in the
neutral, as shown in Figure 3.
that determines how and when current is conducted. One major variation is the phase angle at
which conduction begins and ends.
A typical such converter is the switching-type power supplies found in most personal
computers and peripheral equipment, such as printers. While they offer many benefits in size,
weight and cost, the large increase of this type of equipment over the past fifteen years is
largely responsible for the increased attention to harmonics.
Figure shows below how a switching-type power supply works. The AC voltage is
converted into a DC voltage, which is further converted into other voltages that the
equipment needs to run. The rectifier consists of semi-conductor devices (such as diodes) that
only conduct current in one direction. In order to do so, the voltage on the one end must be
greater than the other end. These devices feed current into a capacitor, where the voltage
value on the cap at any time depends on how much energy is being taken out by the rest of
the power supply.
When the input voltage value is higher than voltage on the capacitor, the diode will conduct
current through it. This results in a current waveform as shown in Figure 5, and harmonic
spectrum in Figure 6. Obviously, this is not a pure sinusoidal waveform with only a 60 Hz
frequency component.
When transformers are first energized, the current drawn is different from the steady
state condition. This is caused by the inrush of the magnetizing current. The harmonics
during this period varies over time. Some harmonics have zero value for part of the time, and
then increase for a while before returning to zero. An unbalanced transformer (where either
the output current, winding impedance or input voltage on each leg are not equal) will cause
harmonics, as will overvoltage saturation of a transformer.
3.4 Where to look for them
Wherever the aforementioned equipment is used, one can suspect that harmonics are
present. The amount of voltage harmonics will often depend on the amount of harmonic
currents being drawn by the load, and the source impedance, which includes all of the wiring
and transformers back to the source of the electricity. Ohms Law says that Voltage equals
Current multipled by Impedance. This is true for harmonic values as well. If the source
harmonic impedance is very low (often referred to as a stiff system) then the harmonic
currents will result in lower harmonic voltages than if the source impedance were high (such
as found with some types of isolation transformers).
Like any power quality investigation, the search can begin at the equipment effected
by the problem or at the point-of-common-coupling (PCC), where the utility service meets
the building distribution system. If only one piece of equipment is effected (or suspected), it
is often easier to start the monitoring process there. If the source is suspected to be from the
utility service side (such is the case when there is a neighboring factory that is known to
generate high harmonics), then monitoring usually begins at the PCC.
The phase voltages and currents, as well as the neutral-to-ground voltage and neutral
current should be monitored, where possible. This will aid in pinpointing problems, or
detecting marginal systems. Monitoring the neutral will often show a high 3rd harmonic
value, indicating the presence of non-linear loads in the facility.
3.5 How do you find them
Hand-held harmonic meters can be useful tools for making spot checks for known
harmonic problems. However, harmonic values will often change during the day, as different
loads are turned on and off within the facility or in other facilities on the same electric utility
distribution system. This requires the use of a harmonic monitor or power quality monitor
with harmonic capabilities (such as shown in Figure 8), which can record the harmonic
values over a period of time.
(or how stiff it is) to average Load Current of maximum demand over 1 year, as illustrated in
Table 5. Note how the limit decreases at the higher harmonic values, and increases with larger
ratios.
multiplies of the fundamental ie: 3rd harmonic is 3x the fundamental frequency / 150Hz.
Total harmonic distortion is a easurement of the sum value of the waveform that is distorted.
Power Measurement
Despite the use of good quality test meter instrumentation, high current flow can often remain
undetected or under estimated by as much 40%. This severe underestimation causes overly
high running temperatures of equipment and nuisance tripping. This is simply because the
average reading test meters commonly used by maintenance technicians, are not designed to
accurately measure distorted currents, and can only provide indication of the condition of the
supply at the time of checking. Power quality conditions change continuously, and only
instruments offering true RMS measurement of distorted waveforms and neutral currents can
provide the correct measurements to accurately determine the ratings of cables, bus bars and
circuit breakers.
Neutral Currents
High harmonic environments can produce unexpected and dangerous neutral currents. In a
balanced system, the fundamental currents will cancel out, but, triple- Ns will add, so
harmonic currents at the 3rd, 9th, 15th etc. will flow in the neutral. Traditional 3 phase system
meters are only able to calculate the vector of line to neutral current measurements, which
may not register the true reading. Integra 1530, 1560 and 1580 offer a 3 phase 4 wire version
with a neutral 4th CT allowing true neutral current measurement and protection in high
harmonic environments.
Harmonic Profiles
There is much discussion over the practical harmonic range of a measurement instrument,
however study of the harmonic profiles of typically installed equipment can guide the system
designer to the practical solution. A typical harmonic profile graph will show a logarithmic
decay as the harmonic frequency increases. It is necessary to establish the upper level at
which the harmonic content is negligible.
For Example:
A laptop switch mode power supply causes approximately 25% of 3rd harmonic, 19% of 5th
harmonic, 10% of 7th harmonic and 5% of 9th harmonic etc. Therefore it can be seen that
almost all the harmonic content in an IT dominated load will be below the 15th harmonic. In
a 3 phase load incorporating 6 pulse bridge technology as is common in many variable speed
drives, UPS systems and DC converters, similar profiles will be observed but extending to the
25th and 27th harmonic. It can therefore be deduced
that in the majority of industrial and commercial applications an instrument measuring up to
the 31st harmonic is ideal.
CHAPTER 4
RAILWAY POWER QUALITY CONDITIONER
4.1 INTRODUCTION
The AC electrified railway systems have the power quality problems such as the
reactive power consumption and the load imbalance due to their inherent electrical
characteristics of single-phase and nonlinear moving loads. Also the power electronics
equipments in the AC electrified railway systems produce the large amount of harmonic
currents. These power quality problems in the AC electrified railway systems have a bad
effect on themselves as well as other electric systems connected together. Therefore a power
quality compensator is required to maintain the proper power quality in the AC electrified
railway systems. There are many researches on the power quality compensator for improving
power quality in the AC electrified railway applications. Especially, a single-phase active
power filter and a single-phase hybrid active power filter, being composed of a passive power
filter and an active power filter, have been studied [1]. Most of the active power filters are
connected in parallel with M-phase and T-phase secondary outputs of Scott transformer
respectively. Although they can compensate the harmonic currents and the reactive power, the
load imbalance cannot be compensated. A three-phase active power filter for power quality
compensation has been proposed [2]. However, the three-phase active power filter installed at
the three-phase mains requires the high-voltage rating. Another active power quality
compensator, being composed of a three-phase inverter and a Scott transformer, has been
studied [3]. An active power quality compensator with two single-phase inverters connected
back-to-back (that is called the RPQC in this paper) has been proposed [4]. The RPQC
requires no additional Scott transformer and can be operated at lower voltage level than the
three-phase active power filter. In spite of these merits, there are few researches on the
control of RPQC. A novel control algorithm based on SRF for the RPQC is proposed. The
proposed RPQC control algorithm can properly compensate the harmonic currents, the
reactive power, and the load imbalance. The effectiveness and the validity of the proposed
control algorithm are demonstrated through the simulations.
phase and T-phase feeder of the Scott transformer. The RPQC controller is shown in Fig.
4.2.1 The DC-link voltage for the DC-link voltage regulation, the inverter currents for the
current control, and the load currents for the harmonic extraction are required as the
controller inputs. The RPQC can compensate not only the harmonic currents and reactive
power, but also the load imbalance by exchanging the active power deviation between Mphase and T-phase feeders through the DC-link capacitor.
............. (5)
Therefore, the single-phase instantaneous active power and reactive power can be described
as equations (6) and (7).
.................. (6)
....................... (7)
where, VMLrms and IMLrms denote the RMS value of vML and vML, respectively. It is shown that
the single phase instantaneous active power depends on the d-axis current value, while the
instantaneous reactive power depends on the q-axis current value. The source current, iM s is
made by the load current of M-phase, iM L and the inverter current, iMinv, as in equation (8)
........................................ (8)
If the q-axis value of the source current becomes zero through the compensation of the q-axis
current, the corresponding reactive power can be compensated. Fig. 4 shows the control
blocks of reactive power compensation algorithm.
CHAPTER 5
SEMI CONDUCTOR DEVICES
The existence of another path from collector to emitter, this path is collector, p +, n-, p (nchannel), n+ and emitter. There is, thus, another inherent transistor Q2 as n- pn+ in the
structure of IGBT. The interconnection between two transistors Q1 and Q2.This gives the
complete equivalent circuit of an IGBT. Here R by is the existence offered by p region to flow
of hole current Ih .
The two transistor equivalent circuit illustrates that an IGBT structure has a
parasitic thyristor in it. Parasitic thyristor is shown in line.
5.2.2 Working
When collector is made positive with respect to emitter, IGBT gets forward
biased. With no voltage between gate and emitter, two junctions between n- region and p
region (i.e. junction J2) are reversed biased; so no current flows from collector to emitter
When gate is made positive with respect to emitter by voltage V G, with gateemitter voltage more than the threshold voltage VGET of IGBT, an n-channel or inversion
layer, is formed in the upper part of p region just beneath the gate, as in PMOSFET . This nchannel short circuits the n- region with n+ emitter regions. Electrons from the n+ emitter
begin to flow to n- drift region through n-channel. As IGBT is forward biased with collector
positive and emitter negative, p+ collector region injects holes into n- drift region .In short; ndrift region is flooded with electrons from p-body region and holes from p+ collector region.
With this, the injection carrier density in n- drift region increases considerably and as a result,
conductivity of n- region enhances significantly. Therefore, IGBT gets turned on and begins
to conducts forward current IC.
Current Ic , or Ie of two current components:
Holes current Ih due to injected holes flowing from collector ,p+ n- p transistor Q1, pbody region resistance Rby and emitter .
Electronic current Ie due to injected electrons flowing from collector, or load, current
IC=emitter current Ie=Ih+Ie.
Major component of collector current is electronic current Ie, i.e. main current path for
collector, or load, current is through p+, n -, drift resistance Rd and n-channel resistance Rch.
Therefore, the voltage drop in IGBT in its on-state is
Vc e . o n = I c . R c h + I c . Rd + V j i
=voltage drop [in n - channel] + across drift in n- region + across forward
biased p+ n- junction J1.
Here Vji is usually 0.7 to 1v as in a p-n diode. The voltage drop Ic. Rch is due to n-channel
resistance, almost the same as in a PMOSFET. The voltage drop Vdf = Ic.Rd in UGBT is
much less than that in PMOSFET. It is due to substantial increase in the conductivity caused
by injection of electrons and holes in n- drift region. The conductivity increase is the main
reason for the low on-state voltage drop in IGBT than that it is in PMOSFET.
i.e. toff=tdf+tf1+tf2
The delay time is the time during which gate voltage falls from VGE to threshold voltage
VGET.As VGE falls to VGET during tdf, the collector current falls from Ic to 0.9 Ic. At the
end of the tdf, collector-emitter voltage begins to rise. The first fall time Tf1 is defined as the
time during which collector current falls from 90 to 20 % of its initial value Ic, or the time
during which collector-emitter voltage rises from Vces to 0.1 Vce.
The final fall time tf2 is the time during which collector current falls from 20
to 10% of Ic, or the time during which collector-emitter voltage rises from 0.1 VCE to final
value VCE.
5.5 INVERTER
Types of inverters:
Generally inverters are of Two Types:
1. VOLTAGE SOURCE INVERTER (VSI)
2. CURRENT SOURCE INVERTER (CSI)
Single-phase voltage source inverters (VSIs) can be found as half-bridge and fullbridge topologies. Although the power range they cover is the low one, they are widely used
in power supplies, single-phase UPSs, and currently to form elaborate high-power static
power topologies, such as for instance, the multi cell configurations that are reviewed. The
main features of both approaches are reviewed and presented in the following.
5.6.1TYPES OF VSI:
5.6.2 HALF-BRIDGE VSI:
The power topology of a half-bridge VSI, where two large capacitors are required to
provide a neutral point N, such that each capacitor maintains a constant voltage=2. Because
the current harmonics injected by the operation of the inverter are low-order harmonics, a set
of large capacitors (C. and C) is required. It is clear that both switches S. and S cannot be
on simultaneously because short circuit across the dc link voltage source vi would be
produced. There are two defined (states 1 and 2) and one undefined (state 3) switch state as
shown. In order to avoid the short circuit across the dc bus and the undefined ac output
voltage condition, the modulating technique should always ensure that at any instant either
the top or the bottom switch of the inverter leg is on.
Shows the ideal waveforms associated with the half-bridge inverter shown in Fig.
14.2. The states for the switches S. and S are defined by the modulating technique, which in
this case is a carrier-based PWM.
5.6.3 FULL-BRIDGE VSI:
The power topology of a full-bridge VSI. This inverter is similar to the half-bridge
inverter; however, a second leg provides the neutral point to the load. As expected, both
switches S1. and S1 (or S2. and S2) cannot be on simultaneously because a short circuit
across the dc link voltage source vi would be produced. There are four defined and one
undefined
The undefined condition should be avoided so as to be always capable of defining the
ac output voltage. In order to avoid the short circuit across the dc bus and the undefined ac
output voltage condition, the modulating technique should ensure that either the top or the
bottom switch of each leg is on at any instant. It can be observed that the ac output voltage
can take values up to the dc link value vi , which is twice that obtained with half-bridge VSI
topologies. Several modulating techniques have been developed that are applicable to fullbridge VSIs. Among them are the PWM (bipolar and unipolar) techniques.
Should be closed at any time; the dc bus is of the current-source type and thus it
cannot be opened; therefore, there must be at least one top switch and one bottom switch
(closed at all times. Note that both constraints can be summarized by stating that at any time,
only one top switch and one bottom switch must be closed.
There are nine valid states in three-phase CSIs. produce zero ac line currents. In this
case, the dc link current freewheels through either the switches S1 and S4, switches S3 and
S6, or switches S5 and S2.
The remaining states produce nonzero ac output line currents. In order to generate a
given set of ac line current waveforms, the inverter must move from one state to another.
Thus, the resulting line currents consist of discrete values of current, which are ii , 0, and ii .
The selection of the states in order to generate the given waveforms is done by the
modulating technique that should ensure the use of only the valid states.
b) PWM minimizes the lower order harmonics, while the higher order harmonics can
be eliminated using a filter.
The disadvantage possessed by this scheme is that the switching devices used in the
inverter are expensive as they must possess low turn on and turn off times, nevertheless
PWM operated are very popular in all industrial equipments. PWM techniques are
characterized by constant amplitude pulses with different duty cycles for each period. The
width of these pulses are modulated to obtain inverter output voltage control and to reduce its
harmonic content. There are different PWM techniques which essentially differ in the
harmonic content of their respective output voltages, thus the choice of a particular PWM
technique depends on the permissible harmonic content in the inverter output voltage.
5.8.1 Sinusoidal-Pulse Width Modulation (SPWM)
The sinusoidal PWM (SPWM) method also known as the triangulation, sub harmonic,
or sub oscillation method, is very popular in industrial applications and is extensively
reviewed in the literature [1-2]. The SPWM is explained with reference to Figure 2.2, which
is the half-bridge circuit topology for a single-phase inverter.
some arbitrary frequency and magnitude. In the inverter of Figure 2.2 the switches and are
controlled based on the comparison of control signal and the triangular wave which are mixed
in a comparator. When sinusoidal wave has magnitude higher than the triangular wave the
comparator output is high, otherwise it is low.
................... (5.1)
And
.................... (5.2)
(a)
(b)
Figure 5.8.1.1: SPWM illustration (a) Sine-Triangle Comparison (b) Switching Pulses after
comparison.
The comparator output is processes in a trigger pulse generator in such a manner that
the output voltage wave of the inverter has a pulse width in agreement with the comparator
output pulse width. The magnitude ratio of v r/vc is called the modulation index (mi) and it
controls the harmonic content of the output voltage waveform. The magnitude of fundamental
component of output voltage is proportional to m i. The amplitude vc of the triangular wave is
generally kept constant. The frequencymodulation ratio mf is defined as
................. (5.3)
To satisfy the Kirchoffs Voltage law (KVL) constraint, the switches on the same leg are not
turned on at the same time, which gives the condition
................... (5.4)
for each leg of the inverter. This enables the output voltage to fluctuate between V d/2 and
Vd/2as shown in Figure 2.4 for a dc voltage of 200 V.
CHAPTER 6
MODELLING OF CASE STUDY
RPC STRUCTURE AND ANALYSIS OF COMPENSATION PRINCIPLE:
The structure of RPC is shown in Fig.6.0. Three phase 220kV voltage is stepped down
into two single-phase power supply voltage at the rank of 27.5kV by V/V transformer. RPC is
made of back-to-back voltage source converters and a common dc capacitor, which can
provide stable dc-link voltage. Two converters are connected to secondary arms of V/V
transformer by step down transformer. Two converters can transfer active power from one
power supply arm to another, supply reactive power and suppressing harmonic currents.
Figure: 6.0. Traction power system with a three-phase V/V transformer and a RPC
The right feeder section in Fig.1 is denoted as a-phase power arm, while that the left
side is b-phase power arm. The corresponding phases on the primary side are denoted as
Phase A and Phase B, respectively. Since using four-quadrant pulse rectifiers to feed electrical
locomotives, the power factor of high speed electrical locomotive is close to 1. Set U A as the
reference value. Assume that the fundamental current vector of a-phase power arm isaL and
the fundamental current vector of b-phase power arm is bL . aL and bL are shown as follows :
................. (6.0)
The turns ratio of V/V transformer is K, so the three currents of the high-voltage side are
shown as follows:
.............. (6.1)
Before RPC compensation, a-phase power arm has load current aL and the b-phase power arm
has load current bL. Assume that
.................. (6.3)
Figure: 6.0.2. Three-phase current phase diagram after adjusting active and reactive power by
RPC
After the compensation, the currents IA and IB have the same amplitude, as shown in Fig.3,
and their angle difference is 2/3 . The C phase current IC can be obtained as IC = IA IB .
The primary side of traction transformer has a balance three-phase current after active power
shift and reactive power compensation. It is similar when IaL < IbL. The common expression of
RPC compensation current is:
................. (6.4)
, --the equivalent current of RPC converters of a-phase arm and b-phase arm at the voltage
of 27.5 kV
ca cb
................. (6.1)
B. Three stations collaboration compensation:
The simple model of 3 stations structure is shown in Fig.6.1.1. Since RPC could
transfer a quantity of active power and compensate reactive power, a triangle is applied to
illustrate the principle of collaboration compensation: apexes of the triangle are regarded as
active load in Phase-AC, Phase-BC and Phase- AB, and edges of the triangle are regarded as
three railway power conditioners. The arrows mean the delivery of active power (real part)
and compensation of reactive power (imaginary part) . There are three steps to compensate.
Firstly, transfer a quantity of active power. Secondly, separate the network into two parts: a
balanced network and an unbalanced network. And last, make compensation to the
unbalanced network based on the Steinmetz theory.
, separately. The
installed capacity will be the maximum of the three RPC capacities above. So we can obtain
the minimum installed capacity when
This is a fully compensation but the station where RPC2 installed is capacitive. To avoid this
condition, RPC1 supply inductive reactive power with the value of b, and RPC2 supply
capacitive reactive power with the value of b, too. So the capacitive condition is avoided and
the system keeps balance at the same time.
Working condition of three stations is shown in Fig.6.1.2 The ellipses stand for
different traction feeder arms, the squares stand for RPC which connect to traction feeder
arms. The arrows stand for active power transfer and reactive power compensation.
Figure: 6.1.2. Working condition of three stations which supply active power and reactive
power
Three stations collaboration compensation minimum capacity is:
....................... (6.1.1)
Which is 2/3 of the capacity of single RPC compensation? Tab.1 shows the compensation
capacity
of
the
two
strategies.
CHAPTER 7
MATLAB DESIGN OF CASE STUDY AND RESULTS
CONCLUSION
This paper proposes a new power quality compensation system which is composed of
several railway power conditioners. The proposed system can be used to compensate negative
sequence current in high speed electrified railway. A minimum installed capacity is conducted
which is 2/3 of the traditional single station compensation capacity. A new compensation
strategy is raised Simulation results show that the proposed collaboration compensation of
railway power conditioners is effective. It can reduce compensation capacity and has a good
performance at negative sequence current compensation.