Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
I. INTRODUCTION
emperature control in industrial applications is an old
science, taking off mostly during the industrial
revolution, and coming into its own in the United States early
in the Twentieth Century. This control was very simple,
mechanical control that did not go beyond turning a heater or
cooling device on or off. PID control, however is a fairly new
concept that was immediately accepted into use for
temperature control applications, and gave way to an entire
line of PID temperature controllers, including the entirely
digital units seen at work in most applications today.
FIGURE 1
Time vs. Temperature Graph of ON/OFF Control
This was the first type to arrive into production, and is the
simplest of the three. An ON/OFF output controller simply
turns the power on or off to a heater or cooling device
depending on which side of the setpoint that the temperature
is on. The controllers that use this sort of output are very
economical, however they have many problems, depending on
the system you are controlling with it. The main problem
with this is that the ON/OFF control does not provide a steady
temperature, and can be off on either side of the setpoint by a
certain magnitude depending on the heater or cooling device
that is attached.
One other problem is that this output is usually attached to
a relay or other device to transmit the signal to power the
heater or cooler. A mechanical relay, or even a transistorbased device only has a certain amount of switches until it
needs to be replaced. If the temperature gets around the
setpoint, and stays around there, the device will constantly be
switching back and forth since it is so close to the setpoint.
This puts a lot of stress on the switching device, and shortens
its lifespan enormously.
B. Time Proportioning
The second variety is Time Proportioning Output.
FIGURE 4
Time vs. Power Graph of Time Proportioning Control At 75% Power
FIGURE 2
Time vs. Temperature Graph of Time Proportioning Control
IV. INPUTS
Another area of options available in choosing the correct
PID controller are inputs.
A. Contact Sensors
Contact Sensors are sensors that are actually touching or
immersed in the material whose temperature they are
measuring. This means that their temperature range is
limited because of the degradation of the material that can
occur due to high temperatures. The two most distinct types
of contact sensors commercially available are thermocouples
and RTDs.
1. Thermocouples
The benefit of this kind of controller is that the overshoot
is greatly reduced due to the slowed down operation
approaching the set point. A proportional or full PID
controller must be used for this output.
C. Process Control Output
The final type of output used in controllers today is the
Process Control output. This output gives a steady signal
instead of an on or off command, as shown in figure 5.
FIGURE 5
Proportional Control Output (0-5V)
10
Derivative:
2.01
VIII. APPENDIX
Table 1:
Thermocouple VS. RTD Data
[3]
Figure 1:
Block Diagram of Temperature Control
[2]
Figure 2:
Auto Tuning Graph
Temperature (F)
Time vs Temperature
73
72
71
70
69
68
67
66
0
50
100
150
200
250
Time (min)
Table 2:
Data Set For Auto-Tuning
Time (min) Temperature (F) Time (min) Temperature (F) Time (min) Temperature (F)
0
66.9
80
67.7
160
69.7
5
67.8
85
67.6
165
69.9
10
69.1
90
67.4
170
70.3
15
69.5
95
67.6
175
70.3
20
69.3
100
67.7
180
70.4
25
69.1
105
67.8
185
70.7
30
69
110
67.8
190
70.9
35
69
115
67.9
195
71.1
40
68.9
120
68.6
200
71.2
45
68.8
125
68.6
205
71.5
50
68.6
130
68.8
210
71.4
55
68.7
135
69
215
71.7
60
68.6
140
69
220
72
65
68
145
69
225
72
70
68.1
150
69.3
230
72
75
67.8
155
69.5
235
72
Figure 3:
Watlow Series 935a Specifications
[4]
VIII. REFERENCES
[1]
[2]
9
[3]
[4]
[5]
[6]