Sei sulla pagina 1di 244

18 /10/2015

SER

1
1

.1

1. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

POWER TRANSFORMERS

33KV & 34.5 KV PRIMARY


POWER TRANSFORMERS UP TO 30 MVA

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

53-TMSS-01

Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.


Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including short


circuit test) as per SEC specifications/standards shall be carried
out on the first unit to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

ABB TRANSIT OY

FINLAND

Yes

AREVA

GERMANY

Yes

BEST

TURKEY-Balikesir (ASB Factory)

Yes

Based on TS&SD Letter # 06-789-03032300 dated July 25,


2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
EAI-2301061500 dated January 23, 2006.

Page 1 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Electric Systems Zrt. (previously GANZ
Transelektro Electric Co., Ltd.)

FACTORY LOCATION
HUNGARY-Budapest

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter 11-01981-1-03032301 dated July 11,
2011, it is pre-qualified for Power Transformers rated up to
132kV/100MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 15, 2010.

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

GETRA Power S.P.A

ITALY-Marcianise (CE)

Yes

Based on S&SD Letter # 14-04523-01-03504401 dated 7th July


2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD

All Type, Special & Routine tests as per National Grid SA


Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid, SA in an Approved Independent
Testing Laboratory and/or in the manufacturers Testing
Laboratory in the presence of three (03) National Grid SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # GPJLT/SECNG/SSD/009,
dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
GPJLT/SECNG/SSD/0010 dated 8th June 2014
HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 2 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ILJIN Electric Co. Ltd.

FACTORY LOCATION
SOUTH KOREA-Hongseong

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 12-03077-30504401 dated September
15, 2012 and S&SD letter # 15-02407-02-30504401 dated June
23, 2015. ILJIN ELECTRIC Co. Ltd Hongseong city, Korea is
prequalified for Power Transformers up to 230 kV, 166.7 MVA
as conforming to SEC/National Grid SA Specification #
53-TMSS-01 with the following conditions:
All Type, Routine and Special tests as per SEC/National Grid
SA Specifications shall be conducted on the proposed Power
Transformers in the Manufacturer's Testing Laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # IL2014-11-05-01 dated
November 5, 2014.
Ten (10) years extended Warranty for the proposed Power
Transformers in respect of the defects due to design,
manufacturing, installation and workmanship from the date of
the Provisional Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of delivery for the
direct material supply order as confirmed through the
manufacturer letter # Nil dated November 5, 2014.

JEUMONT SCHNEIDER

FRANCE

Yes

Koncar D&ST Inc.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-03217-1-30504401 dated May 18,


2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be supplied
to National Grid SA in the Approved Independent Testing
Laboratory or in the manufacturers Testing Laboratory in
presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated May 04, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter # Nil
dated May 04, 2014.

Page 3 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar Power Transformers Ltd.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014, it is
pre-qualified for Power Transformer up to 100MVA, 132kV as
confirming to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing Laboratory
in presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated 01-04-2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
2014/02, dated 01-04-2014.

Liaoning - Efacec Electrical Equipment Co., Ltd


(LEEEC)

CHINA-Liaoning Province

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.

The old remark before suspension was:


Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to 30
MVA as conforming to SEC Specification# 53-TMSS-01 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by Liaoning - Efacec Electrical Equipment
Co., Ltd (LEEEC) through their letter # Nil dated April 18, 2012.
MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 4 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Power Transformers rated up to
100 MVA, 132 kV as conforming to National Grid SA specification
# 53-TMSS-01, Rev.01, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
1/115-2266 dated August 15, 2011.

Saudi Power Transformers Company (SPTC)

Saudi Arabia-Dammam

Yes

Based on S&SD Letter # 15-04608-03-30504401 dated August


18, 2015, It is prequalified for Power Transformers up to 132 kV
, 100 MVA, with the following conditions:
As per the manufacturer letter # CEO/2015/009 dated
August 8, 2015, all type tests, routine tests and special tests
(including short circuit test) as per SEC/National Grid SA
standards/specifications shall be conducted on the proposed
power transformers rated up to 132 kV, 100 MVA for the first
project in an approved independent testing laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All cost of which shall be borne by the
manufacturer.
Ten (10) years extended Warranty for the proposed Power
Transformers rated up to 132 kV, 100 MVA in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the project (in case of contract award) and
from the date of delivery for the direct material supply order as
confirmed through the manufacturer letter # CEO/2015/008
dated August 8, 2015.

Page 5 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SC ELECTROPUTERE SA

FACTORY LOCATION
Romania-Craiova

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-002054-1-03032300
dated10/7/2011, it is prequalified for Power Transformer up to
132kV, 100MVA, as conforming to National Grid SA specification
# 53-TMSS-01, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order. This was
confirmed by SC Electroputere SA through letter 27500 dated
14/06/2010.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

Previously "AREVA-Turkey", the name has been changed to


Schneider Electric-Turkey based on Schneider Electric letter #
MKT-18.01.11 dated 18/01/2010 and AREVA T&D letter #
BF/BL 25.11.2010.

Schneider Enerji Endustrisi San VE TIC A.S

TURKEY-Cayirova-Kocaeli

Yes

Based on S&SD letter# 14-02364-1-30504401 dated April 01,


2014, it is pre-qualified for Power Transformers up to 67 MVA,
132 kV conforming to National Grid SA specification
53-TMSS-01, Rev. 01, with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the manufacturer Testing
Laboratory in the presence of three (03) National Grid SA
Engineers & one (01) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall be
borne by the manufacturer. This was confirmed in writing by
the manufacturer through their letter # MKT_132KV Trafo_005,
dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova, Istanbul,
Turkey has confirmed that improvement needs implementation
will be complied during the FAT for the first transformer order
confirmed through letter # MKT_132KV Trafo_010 dated
February 12, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter #
MKT_132KV Trafo_007-1 dated March 19, 2014.

SCHORCH

GERMANY

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 6 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

.2

1. 2. 1

32

69 KV PRIMARY
POWER TRANSFORMERS UP TO 67 MVA

Applicable Standards:
ABB

SWITZERLAND

Yes

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

53-TMSS-01

Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.


Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including short


circuit test) as per SEC specifications/standards shall be carried
out on the first unit to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

ABB TRANSIT OY

FINLAND

Yes

AREVA

GERMANY

Yes

BEST

TURKEY-Balikesir (ASB Factory)

Yes

Pre-Qualification & Participation for current & future SEC's


Projects subjected to the mutual agreement between SEC &
ABB dated 09 March 2009

Based on TS&SD Letter # 06-789-03032300 dated July 25,


2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
EAI-2301061500 dated January 23, 2006.

Page 7 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Electric Systems Zrt. (previously GANZ
Transelektro Electric Co., Ltd.)

FACTORY LOCATION
HUNGARY-Budapest

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter 11-01981-1-03032301 dated July 11,
2011, it is pre-qualified for Power Transformers rated up to
132kV/100MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 15, 2010.

CG POWER SYSTEMS

BELGIUM

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

EFACEC

PORTUGAL

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

GETRA Power S.P.A

ITALY-Marcianise (CE)

Yes

Based on S&SD Letter # 14-04523-01-03504401 dated 7th July


2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in an Approved Independent
Testing Laboratory and/or in the manufacturers Testing
Laboratory in the presence of three (03) National Grid, SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # GPJLT/SECNG/SSD/009,
dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
GPJLT/SECNG/SSD/0010 dated 8th June 2014.

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 8 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ILJIN Electric Co. Ltd.

FACTORY LOCATION
SOUTH KOREA-Hongseong

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 12-03077-30504401 dated September
15, 2012 and S&SD letter # 15-02407-02-30504401 dated June
23, 2015. ILJIN ELECTRIC Co. Ltd Hongseong city, Korea is
prequalified for Power Transformers up to 230 kV, 166.7 MVA
as conforming to SEC/National Grid SA Specification #
53-TMSS-01 with the following conditions:
All Type, Routine and Special tests as per SEC/National Grid
SA Specifications shall be conducted on the proposed Power
Transformers in the Manufacturer's Testing Laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # IL2014-11-05-01 dated
November 5, 2014.
Ten (10) years extended Warranty for the proposed Power
Transformers in respect of the defects due to design,
manufacturing, installation and workmanship from the date of
the Provisional Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of delivery for the
direct material supply order as confirmed through the
manufacturer letter # Nil dated November 5, 2014.

JEUMONT SCHNEIDER

FRANCE

Yes

Koncar D&ST Inc.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-03217-1-30504401 dated May 18,


2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be supplied
to National Grid SA in the Approved Independent Testing
Laboratory or in the manufacturers Testing Laboratory in
presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated May 04, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter # Nil
dated May 04, 2014.

Page 9 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar Power Transformers Ltd.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014, it is
pre-qualified for Power Transformer up to 100MVA, 132kV as
confirming to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing Laboratory
in presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated 01-04-2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # 2014/02,
dated 01-04-2014.

Liaoning - Efacec Electrical Equipment Co., Ltd


(LEEEC)

CHINA-Liaoning Province

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.

The old remark before suspension was:


Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to 67
MVA as conforming to SEC Specification# 53-TMSS-01 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by Liaoning - Efacec Electrical Equipment
Co., Ltd (LEEEC) through their letter # Nil dated April 18, 2012.
MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 10 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Power Transformers rated up
to100 MVA, 132 kV as conforming to National Grid SA
specification # 53-TMSS-01, Rev.01, with the following
conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
1/115-2266 dated August 15, 2011.

Saudi Power Transformers Company (SPTC)

Saudi Arabia-Dammam

Yes

Based on S&SD Letter # 15-04608-03-30504401 dated August


18, 2015, It is prequalified for Power Transformers up to 132 kV
, 100 MVA, with the following conditions:
As per the manufacturer letter # CEO/2015/009 dated
August 8, 2015, all type tests, routine tests and special tests
(including short circuit test) as per SEC/National Grid SA
standards/specifications shall be conducted on the proposed
power transformers rated up to 132 kV, 100 MVA for the first
project in an approved independent testing laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All cost of which shall be borne by the
manufacturer.
Ten (10) years extended Warranty for the proposed Power
Transformers rated up to 132 kV, 100 MVA in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the project (in case of contract award) and
from the date of delivery for the direct material supply order as
confirmed through the manufacturer letter # CEO/2015/008
dated August 8, 2015.

Page 11 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SC ELECTROPUTERE SA

FACTORY LOCATION
Romania-Craiova

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-002054-1-03032300
dated10/7/2011, it is prequalified for Power Transformer up to
132kV, 100MVA, as conforming to National Grid SA specification
# 53-TMSS-01, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order. This was
confirmed by SC Electroputere SA through letter 27500 dated
14/06/2010.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

Previously "AREVA-Turkey", the name has been changed to


Schneider Electric-Turkey based on Schneider Electric letter #
MKT-18.01.11 dated 18/01/2010 and AREVA T&D letter #
BF/BL 25.11.2010.

Schneider Enerji Endustrisi San VE TIC A.S

TURKEY-Cayirova-Kocaeli

Yes

Based on S&SD letter# 14-02364-1-30504401 dated April 01,


2014, it is pre-qualified for Power Transformers up to 67 MVA,
132 kV conforming to National Grid SA specification
53-TMSS-01, Rev. 01, with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the manufacturer Testing
Laboratory in the presence of three (03) National Grid SA
Engineers & one (01) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall be
borne by the manufacturer. This was confirmed in writing by
the manufacturer through their letter # MKT_132KV Trafo_005,
dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova, Istanbul,
Turkey has confirmed that improvement needs implementation
will be complied during the FAT for the first transformer order
confirmed through letter # MKT_132KV Trafo_010 dated
February 12, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter #
MKT_132KV Trafo_007-1 dated March 19, 2014.

Page 12 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Siemens AG (Dresden)

GERMANY-Dresden

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TAMINI

ITALY

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

REMARKS
based on TS&SD letter# 09-01501-03032301 dated 25th May
2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0 with
the following conditions:

All type, special & routine tests for each voltage class as
per SEC specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Total =

.3

1. 3. 1

34

110 KV TO 132 KV PRIMARY


POWER TRANSFORMERS UP TO 100 MVA

Applicable Standards:
ABB

SWITZERLAND

Yes

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

53-TMSS-01

Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.


Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including short


circuit test) as per SEC specifications/standards shall be carried
out on the first unit to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

Page 13 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

ABB TRANSIT OY

FINLAND

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA

GERMANY

Yes

BEST

TURKEY-Balikesir (ASB Factory)

Yes

REMARKS
Pre-Qualification & Participation for current & future SEC's
Projects subjected to the mutual agreement between SEC &
ABB dated 09 March 2009

Previously AREVA T&D-Turkey [The name has been changed


based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

Based on TS&SD Letter # 06-789-03032300 dated July 25,


2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
EAI-2301061500 dated January 23, 2006.

BEST

TURKEY-Balikesir (OSB Factory)

Yes

Based on S&SD Letter # 14-07386/03-030504401 dated


December 21, 2014, it is pre-qualified for Power Transformer up
to 133MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-02, Rev.01 with the following
conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
OV-2013200311525 dated March 26, 2013.

CG Electric Systems Zrt. (previously GANZ


Transelektro Electric Co., Ltd.)

HUNGARY-Budapest

Yes

Based on TS&SD Letter 11-01981-1-03032301 dated July 11,


2011, it is pre-qualified for Power Transformers rated up to
132kV/100MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 15, 2010.

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

EFACEC

PORTUGAL

Yes

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD.

Page 14 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

GETRA Power S.P.A

ITALY-Marcianise (CE)

Yes

Based on S&SD Letter # 14-04523-01-03504401 dated 7th July


2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in an Approved Independent
Testing Laboratory and/or in the manufacturers Testing
Laboratory in the presence of three (03) National Grid SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # GPJLT/SECNG/SSD/009,
dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #
GPJLT/SECNG/SSD/0010 dated 8th June 2014.

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 15 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Hyundai Heavy Industries Co. Bulgaria

FACTORY LOCATION
Bulgaria-Sofia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-00438-03-03032301 dated
15/05/2011, it is prequalified for Power Transformers up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards
for Power Transformers up to 132kV, 100MVA shall be carried
out in case of contract award or SEC direct purchase order at
SEC approved independent laboratory or at manufacturers
testing laboratory in presence of three (3) SEC Engineers and
one (1) SEC approved independent inspection agency. All the
related costs for witnessing of the tests will be borne by the
manufacturer. This was confirmed by HHIBulgaria through
letter # D-0353 dated 20/08/2010.
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by HHIBulgaria through letter # D-0355 dated
20/08/2010.

ILJIN Electric Co. Ltd.

SOUTH KOREA-Hongseong

Yes

Based on S&SD Letter # 12-03077-30504401 dated September


15, 2012 and S&SD letter # 15-02407-02-30504401 dated June
23, 2015. ILJIN ELECTRIC Co. Ltd Hongseong city, Korea is
prequalified for Power Transformers up to 230 kV, 166.7 MVA
as conforming to SEC/National Grid SA Specification #
53-TMSS-01 with the following conditions:
All Type, Routine and Special tests as per SEC/National Grid
SA Specifications shall be conducted on the proposed Power
Transformers in the Manufacturer's Testing Laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # IL2014-11-05-01 dated
November 5, 2014.
Ten (10) years extended Warranty for the proposed Power
Transformers in respect of the defects due to design,
manufacturing, installation and workmanship from the date of
the Provisional Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of delivery for the
direct material supply order as confirmed through the
manufacturer letter # Nil dated November 5, 2014.

JEUMONT SCHNEIDER

FRANCE

Yes

Page 16 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar D&ST Inc.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-03217-1-30504401 dated May 18,
2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be supplied
to National Grid SA in the Approved Independent Testing
Laboratory or in the manufacturers Testing Laboratory in
presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated May 04, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter # Nil
dated May 04, 2014.

Koncar Power Transformers Ltd.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-08041-01-03504401 dated


13/02/2014 & 14-08041-02-03504401 dated 25/03/2014, it is
pre-qualified for Power Transformer up to 100MVA, 132kV as
confirming to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing Laboratory
in presence of three (03) National Grid SA Engineers & one (01)
Approved Independent Inspection Agency (IIA) Inspector. All
the costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated 01-04-2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order, as
confirmed by the manufacturer through their letter # 2014/02,
dated 01-04-2014 dated April 06, 2014.

Page 17 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Liaoning - Efacec Electrical Equipment Co., Ltd
(LEEEC)

FACTORY LOCATION
CHINA-Liaoning Province

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.

The old remark before suspension was:


Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to 100
MVA as conforming to SEC Specification# 53-TMSS-01 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by Liaoning - Efacec Electrical Equipment
Co., Ltd (LEEEC) through their letter # Nil dated April 18, 2012.
MITSUBISHI

JAPAN--

Yes

NISSIN ELECTRIC

JAPAN

Yes

PJSC Zaporozhtransformator (ZTR)

Ukraine-Zaporizhia

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Based on S&SD letter# 13-07568-30504401 dated December


31, 2013, it is pre-qualified for Power Transformers rated up to
100MVA, 132 kV as conforming to National Grid SA specification
# 53-TMSS-01, Rev.01, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
1/115-2266 dated August 15, 2011.

Page 18 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Saudi Power Transformers Company (SPTC)

FACTORY LOCATION
Saudi Arabia-Dammam

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 15-04608-03-30504401 dated August
18, 2015, It is prequalified for Power Transformers up to 132 kV
, 100 MVA, with the following conditions:
As per the manufacturer letter # CEO/2015/009 dated
August 8, 2015, all type tests, routine tests and special tests
(including short circuit test) as per SEC/National Grid SA
standards/specifications shall be conducted on the proposed
power transformers rated up to 132 kV, 100 MVA for the first
project in an approved independent testing laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All cost of which shall be borne by the
manufacturer.
Ten (10) years extended Warranty for the proposed Power
Transformers rated up to 132 kV, 100 MVA in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the project (in case of contract award) and
from the date of delivery for the direct material supply order as
confirmed through the manufacturer letter # CEO/2015/008
dated August 8, 2015.

SC ELECTROPUTERE SA

Romania-Craiova

Yes

Based on TS&SD letter # 11-002054-1-03032300


dated10/7/2011, it is prequalified for Power Transformer up to
132kV, 100MVA, as conforming to National Grid SA specification
# 53-TMSS-01, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order. This was
confirmed by SC Electroputere SA through letter 27500 dated
14/06/2010.

Page 19 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Enerji Endustrisi San VE TIC A.S

FACTORY LOCATION
TURKEY-Cayirova-Kocaeli

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-02364-1-30504401 dated April 01,
2014, it is pre-qualified for Power Transformers up to 67 MVA
and, 132 kV conforming to National Grid SA specification
53-TMSS-01, Rev. 01, with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first unit to
be supplied to National Grid SA in the manufacturer Testing
Laboratory in the presence of three (03) National Grid SA
Engineers & one (01) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall be
borne by the manufacturer. This was confirmed in writing by
the manufacturer through their letter # MKT_132KV Trafo_005,
dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova, Istanbul,
Turkey has confirmed that improvement needs implementation
will be complied during the FAT for the first transformer order
confirmed through letter # MKT_132KV Trafo_010 dated
February 12, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter #
MKT_132KV Trafo_007-1 dated March 19, 2014.

Siemens AG (Dresden)

GERMANY-Dresden

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

based on TS&SD letter# 09-01501-03032301 dated 25th May


2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0 with
the following conditions:

All type, special & routine tests for each voltage class as
per SEC specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Total =

38

Page 20 of 244

SER

.4

1. 4. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

230 KV PRIMARY
POWER TRANSFORMERS UP TO 400 MVA

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Cordoba

SPAIN-Cordoba

Yes

53-TMSS-02

Based on TS&SD letter# 09-F011657/03-03032301 dated


August 16, 2009. It is pre-qualified for Power Transformer up
to 380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
All type, design, special (exclude Short-Circuit Test) & routine
tests as per SEC Specifications/Standards together with
Thermal & Dynamic short-circuit calculations per IEC 60076-5
shall be carried out on the first unit to be supplied to SEC in an
accredited Independent Testing Laboratory or in the
manufacturer's testing laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # PPTR-002.2 dated
February 14, 2009 and the submitted "Confirmation Letter" #
Nil dated November 18, 2008. [this condition has been modified
based on S&SD letter# 12-0395-01-30504001 dated February
12, 2012]
Seven (7) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order. This
was confirmed in writing by the manufacturer through their
submitted "Guarantee/Warranty Certificate" # Nil dated May
25, 2009.

Page 21 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Elektrik Sanayi A.S. [previously ABB ESAS]

FACTORY LOCATION
TURKEY-Istanbul/Kartal

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-02898/03-030504401 dated June
17, 2014, it is pre-qualified for Power Transformer up to 380kV,
250MVA as confirming to National Grid SA specification #
53-TMSS-02, Rev.01 with the following conditions:
All Type, Routine and Special testes as per NG
Specifications/Standards and IEC requirement together with
Thermal & Dynamic short-circuit calculations per IEC 60076-5
shall be carried out on the First unit to be supplied to SEC/NG of
Power Transformers in the Manufacturer's Testing Laboratory in
the presence of three (3) SEC/NG Engineers & one (1) SEC/ NG
approved Independent Inspection Agency (IIA) Inspector. All
costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nill dated February 04, 2013 .
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #Nill
dated May 24, 2013.

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA

GERMANY

Yes

CG POWER SYSTEMS

BELGIUM

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

FUJI Electric Co.

JAPAN--

Yes

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

Previously AREVA T&D-Turkey [The name has been changed


based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 22 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

ILJIN Electric Co. Ltd.

SOUTH KOREA-Hongseong

Yes

REMARKS
Based on TS&SD fax#09-F01255/02-03032301 dated 25th.
July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the presence of
three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

Based on S&SD Letter # 12-03077-30504401 dated September


15, 2012 and S&SD letter # 15-02407-02-30504401 dated June
23, 2015. ILJIN ELECTRIC Co. Ltd Hongseong city, Korea is
prequalified for Power Transformers up to 230 kV, 166.7 MVA
as conforming to SEC/National Grid SA Specification #
53-TMSS-01 with the following conditions:
All Type, Routine and Special tests as per SEC/National Grid
SA Specifications shall be conducted on the proposed Power
Transformers in the Manufacturer's Testing Laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # IL2014-11-05-01 dated
November 5, 2014.
Ten (10) years extended Warranty for the proposed Power
Transformers in respect of the defects due to design,
manufacturing, installation and workmanship from the date of
the Provisional Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of delivery for the
direct material supply order as confirmed through the
manufacturer letter # Nil dated November 5, 2014.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 23 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Siemens AG (Dresden)

GERMANY-Dresden

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

UP TO 100 MVA ONLY

based on TS&SD letter# 09-01501-03032301 dated 25th May


2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0 with
the following conditions:

All type, special & routine tests for each voltage class as
per SEC specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

Total =

.5

1. 5. 1

20

380KV PRIMARY
POWER TRANSFORMERS UP TO 500 MVA

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

53-TMSS-02

Page 24 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Cordoba

FACTORY LOCATION
SPAIN-Cordoba

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter# 09-F011657/03-03032301 dated
August 16, 2009. It is pre-qualified for Power Transformer up
to 380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
All type, design, special (exclude Short-Circuit Test) & routine
tests as per SEC Specifications/Standards together with
Thermal & Dynamic short-circuit calculations per IEC 60076-5
shall be carried out on the first unit to be supplied to SEC in an
accredited Independent Testing Laboratory or in the
manufacturer's testing laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # PPTR-002.2 dated
February 14, 2009 and the submitted "Confirmation Letter" #
Nil dated November 18, 2008. [this condition has been modified
based on S&SD letter# 12-0395-01-30504001 dated February
12, 2012]
Seven (7) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order. This
was confirmed in writing by the manufacturer through their
submitted "Guarantee/Warranty Certificate" # Nil dated May
25, 2009.

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

Based on S&SD letter# 14-02898/03-030504401 dated June


17, 2014, it is pre-qualified for Power Transformer up to 380kV,
250MVA as confirming to National Grid SA specification #
53-TMSS-02, Rev.01 with the following conditions:
All Type, Routine and Special testes as per NG
Specifications/Standards and IEC requirement together with
Thermal & Dynamic short-circuit calculations per IEC 60076-5
shall be carried out on the First unit to be supplied to SEC/NG of
Power Transformers in the Manufacturer's Testing Laboratory in
the presence of three (3) SEC/NG Engineers & one (1) SEC/ NG
approved Independent Inspection Agency (IIA) Inspector. All
costs of which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their letter #
Nill dated February 04, 2013 .
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
as confirmed by the manufacturer through their letter #Nill
dated May 24, 2013.

Page 25 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid

FACTORY LOCATION
TURKEY-Gebze

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
First Unit to be Type Tested in the presence of 3 SEC Engineers
& 1 SEC approved Independent Inspector; Extended Warranty
of Six years.
Previously AREVA T&D-Turkey [The name has been changed
based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

AREVA

GERMANY

Yes

CG POWER SYSTEMS

BELGIUM

Yes

FUJI Electric Co.

JAPAN--

Yes

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

Based on TS&SD fax#09-F01255/02-03032301 dated 25th.


July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the presence of
three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

2
2

.1

16

PAD MOUNTED DISTRIBUTION TRANSFORMERS

13.8 KV, 33KV & 34.5 KV PRIMARY

Page 26 of 244

SER

2. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

DIST. TRANSFORMERS UP TO 2 MVA

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
ABB

Saudi Arabia-RIYADH

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

REMARKS

51-TMSS-01

Based on TS&SD letter # 11-03272-03032301 dated


16/11/2011 and S&SD letter # 14-02494-01-30504401 dated
24/04/2014, it is prequalified for Station Service Transformer up
to 2.5MVA as conforming to SEC/National Grid SA specification
# 51-TMSS-01, Rev.01 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or from the
date of first delivery of direct material supply order. This was
confirmed by ALFANAR Electrical Systems (AES)Riyadh
through letter # Nil dated 09/04/2011.

FEDERAL TRANSFORMERS CO.

United Arab Emirates-ABU DHABI

Yes

UP TO 1.5 MVA

KONCAR D&ST

Croatia/Hrvatska

Yes

UP TO 2.5 MVA. Complete Type, Routine / Sample tests for first


order & 10 Years Warranty from the date of PAC is required.

Saudi Federal Transformers L.L.C.

Saudi Arabia-Riyadh

Yes

Based on S&SD Letters# 12-01572-2-30504401 dated May 27,


2012 & 13-06464-1-30504401 dated December 11, 2013, it is
pre-qualified for Power Transformers rated up to 36KV & 2MVA
as confirming to SEC Specification # 51-TMSS-01, Rev.0, with
the following condition:
Ten (10) years extended warranty in respect of defects due
to design , manufacturing, installation and workmanship from
the date of PAC of the first turnkey project (in case of contract
award) or from the date of first delivery of direct material
supply order as confirmed through Saudi Federal Transformers
L.L.C., Riyadh letter # SFTL/TES/545/2012 dated May 05,
2012.

SAUDI TRANSFORMERS CO.

Saudi Arabia-DAMMAM

Yes

UP TO 13.8 KV ONLY

United Transformers Electric Co. (UTEC)

Saudi Arabia-Riyadh

Yes

Prequalified up to 2.5 MVA

WESCOSA

Saudi Arabia-DAMMAM

Yes

UP TO 13.8 KV ONLY
Total =

3
3

.1

3. 1. 1

PAD MOUNTED GROUNDING TRANSFORMERS UP TO 2 MVA

13.8 KV, 33KV & 34.5 KV PRIMARY


GROUNDING TRANSFORMERS

Applicable Standards:

52-TMSS-01

Page 27 of 244

SER

4
4

.1

4. 1. 0

5
5

.1

5. 1. 1

.2

5. 2. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

---

Yes

ABB

United States

Yes

ABB

Saudi Arabia-RIYADH

Yes

ABB ( T& D)

ITALY

Yes

ABB SECHERON

SWITZERLAND-GENEVA

Yes

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

REMARKS
ALL APPROVED POWER TRANSFOREMER MANUFACTURERS,
EXCEPT DISTRIBUTION TRANSFORMER MANUFACTURERS ARE
ALSO ACCEPTABLE FOR GROUNDING TRANSFORMERS

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD

Total =

Total =

Total =

DRY TYPE TRANSFORMERS

36 KV PRIMARY
36 KV PRIMARY

Applicable Standards:
ABB/AEIL

Saudi Arabia

Yes

SIEMENS

GERMANY

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

COMPACT SUBSTATION

69KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


UNIT SUBSTATION, 69KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY

Applicable Standards:

ABB (BBC SECHERON)

SWITZERLAND-GENEVA

Yes

CG POWER SYSTEMS

BELGIUM

Yes

110-132 KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


UNIT SUBSTATION, 110 - 132 KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY

Applicable Standards:

Page 28 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB ( T& D)

FACTORY LOCATION
United States-N/A

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

6
6

.1

6. 1. 1

REACTOR

OIL IMMERSED REACTORS


33 KV TO 69 KV OIL IMMERSED REACTORS

Applicable Standards:
ABB

SWEDEN

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

CG Power Systems Belgium NV

BELGIUM-Mechelen

Yes

58-TMSS-01

Previously AREVA T&D-Turkey [The name has been changed


based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

Based on S&SD letter# 14-08521-2-30504401 dated December


10, 2014, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.1, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements [excluding Short
circuit test ] shall be carried out on the first unit to be supplied
to SEC/National Grid SA in the manufacturer Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter #Nil dated November 10,
2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through their
letter #Nil dated 25 November 2014.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 29 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC standards
& technical requirements shall be conducted at Manufacturer's
Testing Laboratory in presence of three (3) SEC/National Grid
SA engineers & one (1) company approved independent
inspection agency Inspector, at the sole expenses of
manufacturer on the first unit to be supplied to SEC/National
Grid SA. This was confirmed through their letter #
HS-SR-141027-01 dated October 27, 2014.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer and
subsequently reduced yearly in case of future project award
through their letter# HS-SRPQ-150107-01 dated January 7,
2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or from the
date of first delivery of direct material supply order and
subsequently reduced yearly in case of future project award.
This was confirmed by HHI Korea through letter #
S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 30 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Shunt Reactors rated up to 132
kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.0, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements shall be carried
out on the first/next unit to be supplied to SEC/National Grid SA
in an Accredited Testing Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was confirmed
in writing by the manufacturer through their letter 1/115-3553
dated December 14, 2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
1/115-3552 dated December 14, 2011.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

Based on S&SD Letter 12-03420-30504401 dated October 02,


2012, Schneider Electric from Turkey-Kocaeli is pre-qualified for
Shunt Reactors up to 33kV only.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

6. 1. 2

110 KV TO 132 KV REACTORS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

14

58-TMSS-01

Previously AREVA T&D-Turkey [The name has been changed


based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

Page 31 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Power Systems Belgium NV

FACTORY LOCATION
BELGIUM-Mechelen

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-08521-2-30504401 dated December
10, 2014, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.1, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements [excluding Short
circuit test ] shall be carried out on the first unit to be supplied
to SEC/National Grid SA in the manufacturer Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter #Nil dated November 10,
2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through their
letter #Nil dated 25 November 2014.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 32 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC standards
& technical requirements shall be conducted at Manufacturer's
Testing Laboratory in presence of three (3) SEC/National Grid
SA engineers & one (1) company approved independent
inspection agency Inspector, at the sole expenses of
manufacturer on the first unit to be supplied to SEC/National
Grid SA. This was confirmed through their letter #
HS-SR-141027-01 dated October 27, 2014.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer and
subsequently reduced yearly in case of future project award
through their letter# HS-SRPQ-150107-01 dated January 7,
2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or from the
date of first delivery of direct material supply order and
subsequently reduced yearly in case of future project award.
This was confirmed by HHI Korea through letter #
S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 33 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.0, with the following conditions:
All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements shall be carried
out on the first/next unit to be supplied to SEC/National Grid SA
in an Accredited Testing Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was confirmed
in writing by the manufacturer through their letter 1/115-3553
dated December 14, 2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
1/115-3552 dated December 14, 2011.

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

6. 1. 3

230 KV OIL IMMERSED REACTORS

Applicable Standards:

14

58-TMSS-01

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Previously AREVA T&D-Turkey [The name has been changed


based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].

Page 34 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC standards
& technical requirements shall be conducted at Manufacturer's
Testing Laboratory in presence of three (3) SEC/National Grid
SA engineers & one (1) company approved independent
inspection agency Inspector, at the sole expenses of
manufacturer on the first unit to be supplied to SEC/National
Grid SA. This was confirmed through their letter #
HS-SR-141027-01 dated October 27, 2014.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer and
subsequently reduced yearly in case of future project award
through their letter# HS-SRPQ-150107-01 dated January 7,
2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or from the
date of first delivery of direct material supply order and
subsequently reduced yearly in case of future project award.
This was confirmed by HHI Korea through letter #
S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

6. 1. 4

380 KV OIL IMMERSED REACTORS

Applicable Standards:

12

58-TMSS-01

Page 35 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

REMARKS

Based on S&SD letter# 13-04034-2-30504401 dated


September 12, 2013, it is pre-qualified for 380 kV Oil Immersed
Shunt Reactors as conforming to National Grid SA specification
# 58-TMSS-01, Rev.0, with the following conditions:

All type/special, routine tests for 380 kV Oil Immersed Shunt


Reactors on one unit of each rating supplied to SEC shall be
conducted at Manufacturer's Testing Laboratory in presence of
three (3) SEC/National Grid SA engineers & one (1) SEC
approved independent inspection agency Inspector, all the
related costs for witnessing the tests will be borne by the
manufacturer. This was confirmed by Alstom Grid, Turkey
through their letter # Nil dated July 22, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by Alstom Grid, Turkey through their letter # Nil
dated July 22, 2013.
AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Page 36 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC standards
& technical requirements shall be conducted at Manufacturer's
Testing Laboratory in presence of three (3) SEC/National Grid
SA engineers & one (1) company approved independent
inspection agency Inspector, at the sole expenses of
manufacturer on the first unit to be supplied to SEC/National
Grid SA. This was confirmed through their letter #
HS-SR-141027-01 dated October 27, 2014.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer and
subsequently reduced yearly in case of future project award
through their letter# HS-SRPQ-150107-01 dated January 7,
2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or from the
date of first delivery of direct material supply order and
subsequently reduced yearly in case of future project award.
This was confirmed by HHI Korea through letter #
S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

.2

12

AIR CORE SERIES REACTOR

Page 37 of 244

SER

6. 2. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

AIRCORE REACTORS & NEUTRAL GROUNDING REACTOR

NOKIAN ALSTOM Grid oy Ltd

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
FINLAND-Tampere

Yes

REMARKS

52-TMSS-02,58-TMSS-02
Based on S&SD letter # 14-03642-01-30504401 dated June 11,
2014, NOKIAN ALSTOM Grid oy Ltd. Tampere- Finland is
pre-qualified for Air Core Series Reactors up to 145 kV as
confirming to National Grid SA Specification # 58-TMSS-02,
Rev.01 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by the manufacturer through their letter # Nil, dated
20th June 2012.

Power Economy Middle East Co.

United Arab Emirates-Abu Dhabi

Yes

Limited up to 34.5 kV Only; Ten (10) years of Extended


Warranty/Guarantee from the date of PAC of the turnkey
project in case of contract award and from the date of delivery
in case of direct material supply order as confirmed through the
manufacturer letter # Nil dated 09.10.2006.

TRENCH AUSTRIA GMBH

AUSTRIA-Leonding, Linz

Yes

Based on TS&SD letter 10-01317-1-03032301 dated May 10,


2010. TRENCH AUSTRIA GMBH is pre-qualified for Air Core
Series Reactors as confirming to SEC Specification 58-TMSS-02,
Rev.0 with the following conditions:
Extended Warranty: Seven (7) years Extended Warranty
shall be applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH AUSTRIA GMBH as confirmed
through their letter # NIL dated April 28, 2010.

TRENCH CANADA

CANADA-Scarborough, Ontario

Yes

Based on TS&SD letter 10-01317-1-03032301 dated May 10,


2010. TRENCH CANADA is pre-qualified for Air Core Series
Reactors as confirming to SEC Specification 58-TMSS-02, Rev.0
with the following conditions:
Extended Warranty: Seven (7) years Extended Warranty
shall be applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH CANADA as confirmed through their
letter # NIL dated April 28, 2010.
Total =

7
7

.1

7. 1. 1

SWITCHGEARS

METAL CLAD SWITCHGEARS


13.8 KV UP TO 34.5 KV

Applicable Standards:
ABB ( T& D)

United States-N/A

32-TMSS-01

Yes

Page 38 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB/AEIL

FACTORY LOCATION
Saudi Arabia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
For 33kV AIS:
classic ZS3 type with current rating up to 2500A@ 40C; CB
type VD43620-25(2000A), VD43612-25(1250A & 800A); ES
type EK5, 3007N280.
For 13.8kV AIS:
The remark was modified based on S&SD Letter
13-01329-30504401 dated March 13, 2013.
13.8kV switchgear type UniGear ZS1 (CT on upper & lower
side of CB) with rated current of incomer, Bus Section, Bus
Riser 3003A and 1756A, Out Going Feeder with rated current
924A and 682A @ 40C, 60Hz, 25kA (3s).
Out Going Feeder (CT on lower side of CB) with rated current
991A and 648A @ 40C, 60Hz, 25kA (3s).
CB types (VD4 embedded pole): VD4 17.31-25 (interrupter
VG6), ABB Italy and VD4 17.16-25 (interrupter VG4/S), VD4
17.12-25 (interrupter VG4) & VD4 17.06-25 (interrupter VG4),
ABB, Italy.
Circuit breaker for Capacitor bank back to back switching
(BC2-630A); VD4 17.12-40 (interrupter VG6), HD4 17.12-25
(interrupter SF6), HD4 24.12-25 (interrupter SF6), and (BC2900A); HD4 17.16-25 (interrupter SF6) ABB, Italy.
All VD4 Poles and Interrupters are from ABB Calor Emg,
Germany (DECMS).
EL Operating Mechanism form ABB-SACE Italy (ITABB).
Earthing switch type EK6, ABB-EJF, Czech.
CT & VT: ABB-EJF, Czech or WTW make, Germany
Old version: Classic ZS1.

Based on S&SD Letter 12-03120-01-30504401 dated August


14, 2012, 13.8kV UniGear ZS1 AIS is pre-qualified for current
rating 3600/4000A @ 40C, 60Hz with forced cooling, with the
following dimensions of the panels:
Incomer
(100017802595), VCB-VD4
1731-25,Interrupter-VG6
Bus section
(100017802595), VCB-VD4
1731-25,Interrupter-VG6
Bus riser
(80014002595)
ABB-CALOR EMAG

GERMANY-CALOR EMAG

Yes

Page 39 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

AEL -SIEMENS

Saudi Arabia-JEDDAH

Yes

For 13.8kV AIS:


type 8BK20 with CB type 3AH.
for 33kV AIS:
type 8BT2 is not acceptable, as the VT is situated in a separate
compartment and connected by cable.

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-02613-01-03032301 dated 13th


September 2009, ALFANAR ELECTRICAL SYSTEMS from Saudi
Arabia-Riyadh for 13.8kV Switchgear type NES-H with degree
protection IP4X; vacuum CB (rating 3150A & 1250A) and ES
from LSIS (South Korea) - details of types are mentioned in the
TS&SD letter; as confirming to SEC specification # 32-TMSS-01,
rev.0 with the following condition:
Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.

Based on S&SD Letter 11-01668-03032301 dated June 01,


2011, 13.8kV NES-H AIS is pre-qualified for current rating
4000A @ 40C, 60Hz with forced cooling and 2906A @ 40C,
60Hz with natural cooling with busbar dimension 3x100x10mm
and with the following dimensions of the panels:
Incomer
(100018802793),
VCB-LVB-17M-40D/301E2H, Interrupter-10403
Bus section
(100018802793),
VCB-LVB-17M-40D/301E2H, Interrupter-10403
Bus riser
(100018802793)
AREVA (MACON CEDEX 9)

FRANCE-(MACON CEDEX 9)

Yes

EFACEC

PORTUGAL

Yes

ELEKTROBUDOWA SA

Poland-Konin

Yes

based on TS&SD letter# 09-01092-03032301 dated 18th. April


2009 it is prequalified for for 13.8kV Air Insulated Switchgear
type D-17P with SCC of 25kA/3sec, degree of protection IP4X
and rated current of 3000A @ 40oC, 60Hz; CB type VD4 which
approved by SEC from ABB-Germany (3000A) & ABB-Italy
(2500A); ES type UMR from ELECTROBUDOWA SA-Poland as
confirming to SEC specification # 32-TMSS-01, rev.0 with Ten
(10) years warranty from the date of PAC of the Turnkey
project in case of contract award or date of delivery in case of
direct material supply order.

Page 40 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
EPS LTD. (GROUPE SCHNEIDER)

FACTORY LOCATION
Saudi Arabia-RIYADH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
For 13.8kV AIS:
Pre-qualified since 24/02/1420H for 13.8kV SWG type MC-Set
with CB type LF3-3150-(2500A), LF2- 2500 (2000A), LF2-1250
(800A), LF2-630 (400A) and warranty of (7)years from
commissioning date of the first delivery for any onward project
or order in the first two years and then shall be (3)years from
PAC.
Based on S&SD Letter 12-02860-01-30504401 dated July 24,
2012, 13.8kV MC-Set AIS is pre-qualified for current rating
3600A @ 40C, 60Hz with forced cooling, with the following
dimensions of the panels:
Incomer
(90017002500), CB-LF3,
Interrupter-LF3-3150A
Bus section
(90017002500), CB-LF3,
Interrupter-LF3-3150A
Bus riser
(90017002500)
For 33kV AIS:
Based on TS&SD fax ref. #09-00073-2-03032301 dated
04/02/2009. Pre-Qualified for 34.5 kV SWG type
(F400NL)1250/2500 A @40C &60Hz with IP4X,SF6 CB type
SF2(France),ES type TFCM(France), & (10)years warranty.
Old version:
33kV AIS type F400G with current rating up to 2500A @ 40C
with CB type SF & SF2

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

KONCAR

Croatia/Hrvatska

Yes

LIMITED TO DTA ONLY; FOR CTA PREQUALIFICATION UNDER


PROGRESS

Page 41 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
LSIS

FACTORY LOCATION
KOREA, Republic of-Cheongju

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-03781-2-30504401 dated June 04,
2015, the manufacturer is prequalified to supply MV switchgear
Type Solution Power V17 rated 13.8 kV only, with the
following conditions:
Ten (10) years extended Warranty from the date of the
Provisional Acceptance Certificate (PAC) of the project (in case
of contract award) or from the date of delivery for the direct
material supply order, as confirmed through the manufacturer
letter # 013/LSIS-PQ/2015 dated May 26, 2015.
Incomer, Bus Section and Bus Riser ratings
(W-950xD-2000xH-2620 mm); 3000A @ 40C, 60Hz, 25kAp
(3s) / 65kAp, natural cooled.
Outgoing feeder & Capacitor feeder (630 A / 1250A) (W-750xD-2000xH-2620 mm); 1250A @ 40C, 60 Hz, 25kA (3s)
/ 65kAp, natural cooled.
Circuit Breaker:
Incomer & Bus section: LSIS, Korea Type
(LVB-17M-40D/30-1E2H, Interrupter: LV10403, Opr. Mech:
Motor-spring, LVB Pro-MEC)
Outgoing feeder: LSIS, Korea-Type (LVB-17M-25D/12-1E2H,
Interrupter: LV10252, Opr. Mech: Motor-spring, LVB Pro-MEC)
Capacitor feeder: LSIS, Korea-Type
(LVB-17M-25D/12-1E2H-DB, Interrupter: LV12503, Opr. Mech:
Motor-spring, LVB Pro-MEC), Capacitor Bank back to back
switching current-630A.
Earthing switch Type SEH/MH31SM & SEH/MH31M.
CT: ABB, Czech (CT located in upper & lower side of CB for
I/C, O/G, B/S).
VT: ABB, Czech.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

POWER CON

United States

Yes

SWITCHGEAR NOT YET TYPE TESTED

S&C

United States

Yes

SIEMENS

United States

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

VA TECH

FRANCE

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Total =

20

Page 42 of 244

SER

7. 1. 2

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

110 KV TO 132 KV GIS

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
ABB

GERMANY

Yes

REMARKS

32-TMSS-02
Old Version:
145kV GIS type ELK-04 with CB type ELK-SW04, Hydraulic
spring mechanism; DS type ELK-TE0 (3 POS), MES type ELK-TE0
(3 POS)/ TE03-DR04; HES type ELK-EB03.
New Version:
Based on TS&SD letter # 11-00455-5-03032301 dated April 04,
2011, the new version 145kV GIS type ELK-04 with CB type
ELK-CB0 (Hydraulic Spring Mech. HMB-1), DS type
ELK-DE0-3POS, MES type ELK-DE0, HSES type ELK-ES0 (Motor
Spring Mech.) is pre-qualified as conforming to SEC specification
# 32-TMSS-02, Rev.01 with the following condition:
Ten (10) Years Extended Guarantee/Warranty from the date
of PAC of project (in case of contract award) and from date of
delivery for the direct material supply order. This was confirmed
in writing by ABB Germany via their letter # PTPH/GVS.Nb,
10_year-warranty.doc dated May 14, 2010.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

ABB

SWITZERLAND

Yes

CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 43 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid AG

FACTORY LOCATION
SWITZERLAND-Oberentfelden

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version:
Based on S&SD letter# 13-4433-01-30504401, dated 16
January 2013, it is pre-qualified for 145kV GIS type F35 with
rated current, 3150A @40C, 60Hz, CB type- F35-CB4 / Opr.
Mech: FK3-2 (spring charged), Line & Busbar DS-F35-DES-4/
Opr. Mech: ME1-3, MES-F35-DES-4/ Opr. Mech: ME1-3,
HES-F35-EFZ/Opr. Mech:MF-3 (spring charged), CT-F35-CT4,
against specification # 32-TMSS-02, Rev.1 with the following
condition:
1. Eight (8) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order. This was
confirmed through manufacturer lletter ref: Q1F35_210409
dated 21 April 2009.

CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

Old Version:
145kV GIS type B65 with CB type B65-CB Motor spring
mechanism; DS type B65-DS; ES type B65-ES; HES type
B65-EF.
Previously " Areva T &D AG, SWITZERLAND-Oberentfelden ",
the name has been changed to ALSTOM Grid AG,
Oberentfelden, Switzerland, based on ALSTOM Grid Letter # Nil
dated July 11, 2012.
FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Old version:
145kV GIS type SDA5 (SDA514) with CB type BAK5, Hydraulic
mechanism.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 44 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HITACHI Ltd.

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
New version: 145kV GIS type CFTA with CB type
CFPT-120-40L, FAR3 Motor spring mechanism; DS type
CFL-120; ES type CFL-120.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Old version: 145kV GIS type CFT with CB type CFPT-140-40L,


FAR3,C Pneumatic mechanism; DS type SFL-EA; HES type
SFGM-FA.
HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

New Model approved on 10-04-2007, Model Type HSG-144A


145KV GIS with CB type HCSP-144A
Motor spring mechanism; DS type HDMO-144A; MES type
HDMO-144A, HES type HEMS-144A.
All Type and Design tests have been carried out completely &
accepted as mentioned in TS&SD letter#08-F02926-03032301
dated 22/11/2008.
Provide extended Guarantee/Warranty for Seven(7) Years
from the date of PAC
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

Old version: 145kV GIS type 145HGS40 with CB type


145HCB,145PL40; DS type 145SDSV/SDSH; MES type 145SESM;
HES type 145SESA

Page 45 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYUNDAI

FACTORY LOCATION
KOREA, Republic of-Ulsan

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version: 145kV GIS type 145SP-1 with CB type 145SP-K1
Motor spring mechanism; BDS type 145SP-3PS1; LDS type
145SP-3PS2; MES type 145-3PS2; HES type 145SP-LES2.

CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO
Old version: 145kV GIS type 145SP with CB type 145SP-K
Hydraulic mechanism; DS type 145SP-DS; MES type 145SP-ES;
HES type 145SP-LES
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
KONCAR

Croatia/Hrvatska

Yes

GIS & ADAPTORS; LIMITED TO DTA ONLY; FOR CTA


PREQUALIFICATION UNDER PROGRESS
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

LS Industrial System Co.

SOUTH KOREA-Cheongju

Yes

Based on S&SD letter# 13-07921-2-30504401 dated January


06, 2014,it is pre-qualified for 145kV GIS type GESG-1440NHS
with rated current, 3150A, 60Hz, CB type- GEDB-1440NHS /
Opr. Mech. Type: GGA204155 (spring charged), LDS typeGESG 1440-ACSF/ Opr. Mech: Motor, BDS type-GESG
1440-ACSB / Opr. Mech: Motor, MES type- GESG 1440-ACSB/
Opr. Mech: Motor, HES type- GESG 1440-MSES /Opr. Mech:
Motor spring & CT- JK GIS, against specification # 32-TMSS-02,
Rev.1 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated November 25, 2013.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

Page 46 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
MITSUBISHI

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
New version 145kV GIS type 100GMKD with CB type
120-SFMT-40CJ; DS type 120GRD/GLD; MES type
120GRED/GRE; HES type 120 GRED/GRE-A.
Old version: 145kV GIS 120GMKM with CB type 120-SFMT-40,
Pneumatic mechanism; DS type 120-GR-20,
120-GL-20; MES type 120-GRE, 120-GREC; HES type
120-GREA.
Old version: 145kV GIS 100GMKD with CB type 120-SFMT-40CE
Motor spring mechanism; DS type 120GLD; HES type 120-GREA.

CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO
SIEMENS

FRANCE-GRENOBLE

Yes

New version:
145kV GIS type TH7m with CB type TH7m AF8ER(Motor spring);
BDS type CM002, CM003 (3-position); LDS type CM002, CM003
(2-position); MES type CM002,CM003; HES type CM002,
CM003.
Old version: 145kV GIS type HEXABOLIC-TH7 with CB type
DTH7 Hydraulic mechanism; BDS type SITH7; LDS type ITH7, SI
TH7; ES type ST TH7.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 47 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 15-06390-02-30504401 dated August
13, 2015,it is pre-qualified for 145kV GIS type 8DN8-5 with
rated current, 3150A, 60Hz,
CB type- 8DN8-5 / Opr. Mech. Type: FA2 (spring charged),
LDS type- 8DN8-5-3PS / Opr. Mech: Motor,
BDS type- 8DN8-5-3PS / Opr. Mech: Motor,
MES type- 8DN8-5-ES / Opr. Mech: Motor,
HES type- 8DN8-5-HES / Opr. Mech:Motor spring
As conforming to the specification #32-TMSS-02, Rev.01 with
the following conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order &
subsequently reduced yearly in case of future project. This was
confirmed in writing by the manufacturer through their letter #
Nil dated May 30, 2012.
- CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: No
Short line fault: Minimum 5.2m length bus duct between feeder
Bay and OHL shall be used in case the bay is directly connected
to OHL lines.

Old Remark
New version: 145kV GIS type 8DN8-II with CB type 8DN8 Motor
spring mechanism; DS type 8DN8; ES type 8DN8.
Old version: 145kV GIS type 8DN8 with CB type 8DN6(P1)
Motor spring mechanism; DS type 8DN8; ES type 8DN8.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


145kV GIS type with CB type GSPK-145AP; BDS type
KTM-120PW, DTM-120PW, DLM-120PW; LDS type KTM-120PW,
DTM-120PW; MES type EBM-120W; HES type EAP-120W.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Total =

13

Page 48 of 244

SER

7. 1. 3

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

230 KV -GIS

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
ABB

SWITZERLAND

Yes

REMARKS

32-TMSS-02
Based on S&SD letter # 14-00064-30504101 dated January 26,
2014 and ABB Letter # PPHV-300GIS CH-05 dated February 02,
2014, the designation has been corrected to the following:
230 kV GIS Type: ELK-14/300 (1HC0071250M0040), Rated
current: 4000A, 40C, @ 60Hz, CB Type: ELK-SP14/300
(1HC0071250M0040) / Opr. Mech: HMB4 (1HC0071250M0040),
LDS & BDS Type: ELK-TK14/300 (1HC0071250M0040) / Opr.
Mech: BAC (1HC0071250M0040), MES Type: ELK-TK14/300
(1HC0071250M0040) / Opr. Mech: BAC (1HC0071250M0040),
HES Type: ELK-EB14/300 (1HC0071250M0040) / Opr. Mech:
BAE (1HC0071250M0040), CT Type: ELK-CN14/300
(1HC0071250M0040), Cable compartment Type: ELK-HK 14/300
(1HC0071250M0040).
Capacitor Bank Back to Back switching type test will be
performed when required in the project, confirmed by ABB
letter # PPHV-140120/GIS-1, dated 21-01-2014.
Old Designation:
230kV GIS Type: ELK-1, CB Type: ELK SP2-1.

ALSTOM Grid SAS

FRANCE-AIX-LES BAINS

Yes

230kV GIS type B105 with CB type B105-CB; DS type CLT


Previously "AREVA T&D FRANCE-(AIX-LES BAINS) ", the name
has been changed to ALSTOM Grid SAS-France based on
ALSTOM Grid-France letter # Nil, dated December 07, 2012.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
230kV GIS type MFPT MFPTB-300-63L with CB type
MFPTB-300-63LA, HAR/MFTB-300-563L; BDS type FL-EA, LDS
type FMG-FA/FG.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Page 49 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Old Version

230kV GIS type 8DN40-8DN4 with CB 8DN401-8DN4; BDS


type 8DN4-8DQ1; LDS type 8DP4; MES type 8DN4; HES type
8DP4.

Based on SIEMENS letter# 30179023-A1 dated


02/05/2011, this type is already obsolete/phased out.
New Version
Based on TS&SD letter # 11-00267/01-03032301 dated
02/02/2011, it is pre-qualified for 300kV GIS type 8DN9, rated
current 4000A, short time current rating of 63kA, CB (Single
Break) type 8DN9-300-63-4000 with motor spring mechanism,
Busbar & line DS type 8DN9-300-63-4000 with motor drive
mechanism, MES type 8DN9-300-63-with motor drive
mechanism & HES type 8DN9-300-63-4000 with motor drive
mechanism as confirming to SEC specification #
32-TMSS-02,Rev.01, with the following conditions:

Ten (10) years extended warranty starting from project


"Safaniyah 380/230kV project" as confirmed through SIEMENS
letter # PQ_8DN9_02 dated 26/06/2010.

SIEMENS

GERMANY-Berlin

Yes

This GIS shall only be used for 245kV, 63kA applications.

Based on S&SD letter # 13-05708-1-30504401, dated October


10, 2013, it is pre-qualified for 245kV GIS type 8DN9 with rated
current, 3150A @40C, 60Hz, CB type- 8DN9-245kV-50kA/Opr.
Mech: spring charged, Line & Busbar
DS-8DN9-245kV-50kA/Opr. Mech: Motor,
MES-8DN9-245kV-50kA/Opr. Mech: Motor,
HES-8DN9-245kV-50kA/Opr. Mech: spring charged, as
conforming to National Grid SA specification # 32-TMSS-02,
Rev.01, with the following conditions:
CB capability for Capacitor bank back to back switching
(BC1/BC2) is applicable for 145kV only.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by SIEMENS, Germany-Berlin through their
letter # Nil dated June 19, 2010.

SIEMENS

FRANCE-GRENOBLE

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

7. 1. 4

380 KV - GIS

Applicable Standards:

32-TMSS-02

Page 50 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWITZERLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 13-00748-30504101 dated November
06, 2013, it is pre-qualified for 420 kV GIS type ELK-3/420
(1HC0071250M0070) @ 4000A, 60Hz, CB type ELK-SP3/420,
Operating Mechanism-HMB8, Line & Busbar DS type
ELK-TK3/420, Operating Mechanism-ELK-BAC, MES type
ELK-TK3/420, Operating Mechanism-ELK-BAC, HES type
ELK-EB3 420, Operating Mechanism-ELK-BAE, CT type ELK-CN3,
Cable compartment type ELK-HK3.

HYBRID GIS:
Base on S&SD letter # 14-03182-01-30504401, dated
29-01-2015, Pre-qualified ABB, Switzerland GIS type ELK-3/420
(1HC0071250M0070) with its components are acceptable for
Hybrid GIS up to current rating @ 3150A, 55C, 60Hz.
ALSTOM Grid SAS

FRANCE-AIX-LES BAINS

Yes

420kV GIS type T155 with CB type FB2T (Hydraulic Mech.)


Previously "AREVA T&D FRANCE-(AIX-LES BAINS) ", the name
has been changed to ALSTOM Grid SAS-France based on
ALSTOM Grid-France letter # Nil, dated December 07, 2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
420kV GIS type 1FT

Page 51 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-F-02299/02-03032301 dated
25/10/2010, it is pre-qualified for 420kV GIS type HSG 426A,
63kA, CB (Single Break) type HCHY 426A with Hydraulic
Mechanism, Busbar DS type HDMO 426A, Line DS type HDMO
426B,ES type HEMO 426A&H-ES type HEMS 426A as
confirming to SEC specification # 32-TMSS-02,Rev.01, with the
following conditions:

Supply one complete spare bay" free of charge" (for not


repeating the short circuit test of circuit breaker type HCHY
426A) on the first supply of 420kV GIS type HSG 426A to SEC.
This was confirmed in writing by Hyosung Corp (Korea) through
letter #Nil dated 28th December 2009.

Repeat/carry out the temperature rise test at 55C (it was


carried out before at 50C) of the main circuit on the first
supply of the 420kV GIS type HSG 426A to SEC. This was
confirmed in writing by Hyosung Corp (Korea) through letter
#HS-420GIS-100830-1 dated 30th August 2010.

Back to back switching tests for the capacitor bank shall be


conducted in an independent test laboratory whenever there is
project requirement. This was confirmed in writing by Hyosung
Corp (Korea) through letter #HS-420GIS-100830-1 dated 30th
August 2010.

Ten (10) years extended warranty for the proposed 420kV


GIS type HSG 426A from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This was confirmed in writing by
Hyosung Corp (Korea) through letter #HS-420GIS-100830-1
dated 30th August 2010.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

420 kV; 63kA; TYPE-550 SR; CB-550 SR-K (Single Break);


DS-550 DRM 1&2; ES-550 ERM; HES-550 LES; back to back
capacitor switching test for C.B. shall be done in independent
laboratory iin the presence of SEC Engineers whenever there is
a requirment for this test iin th PTS of forthcoming SEC
projects.
- 10 Years extended warranty.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

SIEMENS

FRANCE-GRENOBLE

Yes

420kV GIS type YGII with CB type SPD; DS ype YGII

SIEMENS

United Kingdom-HEBBUM

Yes

Page 52 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version:
550kV GIS type 8DQ1 with CB type 8DQ1-P2; DS type 8DQ1;
ES type 8DQ1. with the following conditions:
- ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the Turnkey project
(In case of contract award) and from the date of delivery for
the direct material supply order. The guarantee/warranty shall
cover all the cost of materials and labor as per
warranty/guarantee of materials and workmanship and
subsequently reduced yearly in case of future project award,
as confirmed by Siemens letter # Nil, dated 31-03-2009.
- Type test: 1000A capacitor bank back to back switching
current test to be performed in the first order before delivery
of the GIS in the project as per Siemens letter # E T HP
GS/SAR/PQ-GIS 8DQ1-NG 87, dated 06-05-2014.

HYBRID GIS:
Base on S&SD letter # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 550kV GIS type
8DQ1 with its components are acceptable for Hybrid GIS up to
current rating 3150A, 55 C, 60Hz.
Old version:
420kV GIS type 8DQ1 with CB type 8DQ1-T2, DOUBLE BREAK,
Hydraulic mechanism; DS type 8QD1

Page 53 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens AG

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00569-2-30504401 dated February
09, 2014,it is pre-qualified for 420KV GIS, type 8DQ1-6, 63KA,
Single Break with rated current 4000A, 60Hz, CB type-8DQ1
6-P1 (Single break)/ Opr. Mech. Type: Spring type (FA5), LDS
type- 8DQ1 6 DS / Opr. Mech: Motor, BDS type-8DQ1 6 DS /
Opr. Mech: Motor, MES type- 8DQ1 6 ES / Opr. Mech: Motor,
HES type- 8DQ1 6 HSES /Opr. Mech: Motor spring & CT- 8DQ1
6 against specification # 32-TMSS-02, Rev.1 with the following
condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer (Siemens
AG-Germany) through their letter # Nil dated May 30, 2012.

HYBRID GIS:
Base on S&SD letter # # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 420 kV GIS type
8DQ1-6 with its components are acceptable for Hybrid GIS up
to current rating 3150A, 55 C, 60Hz.

Page 54 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TOSHIBA CORPORATION, T&D

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-05807-2-30504401, dated
September 08, 2014, it is pre-qualified for 420 kV GIS type GID,
Rated current 3150A @ 40 C, 60Hz, 63kA (1s).
CB type GSRK-420CHK (Single break) with internal grading
capacitor 860pF, Operating Mechanism: Hydraulic
GSRK-420CHK, Busbar & Line DS type DTM, Operating
Mechanism DTM (motor), MES type EBM, Operating Mechanism
EBM (motor), HES type EYP, Operating Mechanism EAP (motor
spring charged) as confirming to National Grid SA Specification
# 32-TMSS-02, Rev.01, With following condition:
Ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the Turnkey project
(In case of contract award) and from the date of delivery for
the direct material supply order. The guarantee/warranty shall
cover all the cost of materials and labor as per
warranty/guarantee of materials and workmanship and
subsequently reduced yearly in case of future project award.
This was confirmed by the manufacturer through their letter #
TSB/TDS/AK/130206/2145-R1 dated August 12, 2014.
Old version: 420kV GIS type GID with CB type GSR
400R2B/GSRK, DOUBLE BREAK, Hydraulic mechanism.

*TOSHIBA CORPORATION, T&D JAPAN- ORIGINALLY TMT&D


CORP. & DISSOLVED DURING APRIL 2005.
Total =
7. 1. 5

550 KV GIS

11

Applicable Standards:

Page 55 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWITZERLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letters 14-00741-30504101dated December 08,
2014 & 14-00043-30504101, dated January 20, 2015, it is
pre-qualified for 550 kV GIS type ELK-3/550
(1HC0071250M0100) @ 4000A, 40 C, 60Hz, CB type
ELK-SP3/550 (1HC0071250M0100), Operating Mechanism-HMB8
(1HC0071250M0100), Busbar DS type ELKTE3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), Line disconnector type
ELK-TV3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), MES type
ELK-EM3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), HES type
ELK-EB3/550(1HC0071250M0100), Operating
Mechanism-DB(1HC0071250M0100), Cable compartment type
ELK-HK3/550(1HC0071250M0100) as confirming SEC
Specification 32-TMSS-02, Rev.01 with following condition:
- Ten (10) years Extended Warranty from the date of
Provisional Acceptance Certificate (PAC) of the project (in case
of contract award) and from date of delivery for the direct
material supply order. The warranty/ guarantee shall cover all
cost of materials and labor as per warrant/guarantee of
materials and workmanship and subsequently reduced yearly in
case of future project and shall be applicable for all Substations
to be supplied to SEC/National Grid SA as confirmed through
ABB, Switzerland Letter # PPHV-550kV dated 02-05-2014.

Page 56 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letters 14-00743-30504101 dated December
08, 2014 & 14-00783-30504101, dated 23 December, 2014, it
is pre-qualified for 550 kV GIS type 550 HSG @ 4000A, 40 ? C,
60Hz, CB type 550 SPR50, Operating Mechanism-HOM-110,
Busbar and Line DS type 550 SDSV, Operating
Mechanism-Motor/DYA0400134, MES type 550 SESM, Operating
Mechanism-Motor DYA0400134, HES type 550 HESA, Operating
Mechanism-Motor-Spring/DYA0400133, Cable compartment
type as confirming SEC Specification 32-TMSS-02, Rev.01 with
following conditions:
- Ten (10) years Extended Warranty from the date of
Provisional Acceptance Certificate (PAC) of the project (in case
of contract award) and from date of delivery for the direct
material supply order. The warranty/ guarantee shall cover all
cost of materials and labor as per warrant/guarantee of
materials and workmanship and subsequently reduced yearly in
case of future project and shall be applicable for all Substations
to be supplied to SEC/National Grid SA as confirmed by M/s.
HYOSUNG, Korea through Letter # Nil, dated Nil.
- Type test: 1000A capacitor bank back to back switching
current test to be performed in the first order before delivery
of the GIS in the project vide Hyosung, Korea letter #
HS-5GIS-1406-1, dated 11-06-2014.

SIEMENS

GERMANY

Yes

Siemens 550kV GIS type 8DQ1, CB type 8DQ1-P2; DS type


8DQ1; ES type 8DQ1 pre-qualified as per item 7.1.4 is
accepted for capacitor bank back to back switching vide S&SD
letter # 14-00742-30504101, dated December 08, 2014 with
following condition:
- Ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the Turnkey project
(In case of contract award) and from the date of delivery for
the direct material supply order. The guarantee/warranty shall
cover all the cost of materials and labor as per
warranty/guarantee of materials and workmanship and
subsequently reduced yearly in case of future project award as
confirmed by Siemens letter # Nil, dated 31-03-2009.
- Type test: 1000A capacitor bank back to back switching
current test to be performed in the first order before delivery
of the GIS in the project as per Siemens letter # E T HP
GS/SAR/PQ-GIS 8DQ1-NG 87, dated 06-05-2014.
Total =

7. 1. 6

33 KV GIS

Applicable Standards:

Page 57 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-0186-01-30504401, dated January
22, 2015 and TS&SD Letter # 10-02461-02-03032301, dated
August 31, 2010, the manufacturer is prequalified for 36kV GAS
Insulated Medium Voltage SWGR Type 8DA10, rated current
2500A @ 40C, 60Hz and short time current rating of
25kA(3sec),
CB type 3AH49 with vacuum interrupter type VSG 40040 (rated
current up to 2500A, 40C, 60Hz & Capacitor bank back to back
switching current 400A),
CB type 3AH49 with vacuum interrupter type VS 30040 (40kA)
for current rating up to 2375A C, 60Hz,
as conforming to National Grid SA specification # 32-TMSS-03,
Rev.0 with the following condition:
Seven (7) years extended warranty for the proposed 36kV
GIS ,type 8DA10 from the date of PAC of the turnkey project in
case of contract award or date of delivery in case of direct
material supply order. This was confirmed by Siemens trough
letter # 8DA10_PQR_R1 dated 24/08/2010.
Total =

8
8

.1

8. 1. 0

BATTERY EQUIPMENT

BATTERY LEAD ACID


BATTERY LEAD ACID

Applicable Standards:
BAE BERLINER BATTERIE FABRIK- G

GERMANY

Yes

C&D

United States

Yes

CEAC

FRANCE

Yes

ENERSYS S.A.R.L.

FRANCE--

Yes

EXIDE

United States

Yes

FIAMM

ITALY

Yes

GOULD (GNB)

United States

Yes

HOPPECKE

GERMANY

Yes

TOVARNA AKUMULATORSKIH BATERIJ

SLOVENIA

Yes

TUNGSTONE (HAWKER TUNGSTONE)

United Kingdom

Yes

VARTA

GERMANY

Yes

46-TMSS-01

PREVIOUSLY KNOWN AS HAWKER S.A.R.L - FRANCE; FIVE


YEARS OF EXTENDED WARRANTY

Page 58 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
YUASA

.2

8. 2. 0

.3

8. 3. 0

FACTORY LOCATION
JAPAN

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

12

Total =

11

BATTERY LEAD ACID, VALVE REGULATED LEAD ACID (VRLA)


BATTERY LEAD ACID, VALVE REGULATED LEAD ACID (VRLA)

Applicable Standards:

AEG Power Solutions SAS

FRANCE--

Yes

C&D

United States

Yes

CHLORIDE (HAWKER CHLORIDE)

United Kingdom

Yes

FIAMM

ITALY

Yes

GNB

United States

Yes

HAWKER LTD.

United Kingdom

Yes

HOPPECKE

GERMANY

Yes

SAB

GERMANY

Yes

SEC

United States

Yes

VARTA

GERMANY

Yes

YUASA EXIDE

United States

Yes

46-TMSS-04
originally was SAFT Power System SAS-France

BATTERY NICKEL CADMIUM (NiCD)


BATTERY NICKEL CADMIUM (NiCD)

Applicable Standards:

46-TMSS-06

ALCAD

SWEDEN

Yes

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

EMISA

SPAIN

Yes

EXIDE

United States

Yes

FRIWO

GERMANY

Yes

MERGED WITH SAFT NIFE -SWEDEN

GAZ Gerate- und Akkumulatorenwerk Zwickau


GmbH

GERMANY-Zwickau

Yes

Based on TS&SD fax ref.#08-F02675/03-03032301 dated


10/01/2009. Pre-Qualified for Nicd Battery with this conditions:
-First batch shall be type tested in Independent Laboratory iin
presence of (3) SEC engineers & (1) independent inspector.
-(07) years warranty

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based on
Emerson Network Power Industrial Systems letter # nill dated
12/04/2013.

Page 59 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

GNB

United States

Yes

SAFT-NIFE

SWEDEN

Yes

VARTA HAWKER

GERMANY

Yes

REMARKS

370 TO 1390AH

Total =

.4

8. 4. 1

BATTERY CHARGER
BATTERY CHARGER

Applicable Standards:

46-TMSS-02

AEG Power Solutions SAS

FRANCE--

Yes

BENNING

FRANCE

Yes

Benning Elektrotechnik & Elektronik GmbH &


Co.kG.

GERMANY--

Yes

Previously "Theo-Benning-Germany", the name has been


changed to Benning Elektrotechnik & Elektronik GmbH & Co. KG
-Germany based on TS&SD/ESD letter # 11-00334-03032301
dated 30/01/2011.

BORRI S.P.A

ITALY-Arezzo

Yes

Based on S&SD Letter # 14-03226-01-030504401 dated June


4, 2014, it is pre-qualified for Battery Charger (125VDC, Type
RTB.e) as conforming to National Grid SA specification #
46-TMSS-02, Rev.0 with the following conditions:

Originally was SAFT Power System SAS-France

Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This has been confirmed in writing
by the manufacturer through letter # Nil dated May 23, 2011.
BRAGA MORO

ITALY

Yes

Based on S&SD Letter 12-03794-01-30504401 dated November


18, 2012, Braga Moro- Italy is pre-qualified for Battery
Chargers 125V DC as conforming to National Grid SA
Specification # 46-TMSS-02, Rev.0, with the following
conditions:
All Type, Routine and Special testes as per National Grid SA
Specifications/Standards together shall be carried out on the
First unit to be supplied to SEC/National Grid SA of Battery
Chargers 125V DC in an Independent Testing Laboratory in the
presence of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by Braga
Moro-Italy. This was confirmed in writing by Braga Moro-Italy
through their letter # SEC Prequalification dated April 13, 2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order as
confirmed by Braga Moro- Italy through their letter # SEC
Prequalification dated April 13, 2011.

Page 60 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

C&D

United States

Yes

CEG

ITALY-BIBIENA

Yes

REMARKS

Based on TS&SD letter# 09-F001363/02-03032301 dated 2nd


May 2009 & S&SD letter# 14-05308-01-30504401 dated 21st
July 2014 as confirming to National Grid SA specifications #
46-TMSS-02, rev.0 ; with the following conditions:
Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based on
Emerson Network Power Industrial Systems letter # nill dated
12/04/2013.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "AEES ", the name has been changed to Emerson


Network Power Industrial Systems - France based on Emerson
Network Power Industrial Systems letter # nill dated
12/04/2013.

EMISA (ELECTRO MERCANTIL INDUSTRIAL


S.A. SPAIN)

SPAIN

Yes

ERSKINE

United Kingdom

Yes

EXIDE

United States

Yes

GUTOR ELECTRONIC LTD.

SWITZERLAND

Yes

JESUS MARIA AGUIRRE SA (JEMA)

SPAIN-Lasarte-Oria

Yes

Based on S&SD Letter 12-00193-030504001 dated January 17,


2012. It is prequalified for Battery Charger as conforming to
SEC Specification# 46-TMSS-02, Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out on the
first batch of each types of Battery Chargers in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated June 17, 2011.
Ten (10) years extended warranty from the date of PAC of
the FIRST turnkey project in case of contract award or date of
FIRST delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 17, 2011.

Page 61 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Statron AG

FACTORY LOCATION
SWITZERLAND-Maegenwil

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03254-01-30504401 dated August
29, 2012, it is pre-qualified for Battery Chargers 125V DC
(Models BDT) as conforming to SEC Specification #
46-TMSS-02, Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out on
the first batch of each types of Battery Chargers 125V DC in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Ten (10) years extended warranty in respect of defects due
to design, manufacturing, installation and workmanship from
the date of PAC of the first turnkey project (in case of contract
award) or from the date of first delivery of direct material
supply order as confirmed by the manufacturer Statron AG
through their letter # bm dated August 13, 2012.
Total =

8. 4. 2

UPS, 5 THROUGH 100KVA

Applicable Standards:
BORRI S.P.A

ITALY-Arezzo

Yes

15

46-TMSS-03
Based on S&SD Letter # 14-03226-01-030504401 dated June
4, 2014, it is pre-qualified for UPS, 5 THROUGH 100 kVA as
conforming to National Grid SA specification # 46-TMSS-03,
Rev.0 with the following conditions:
Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This has been confirmed in writing
by the manufacturer through letter # Nil dated May 23, 2011.

Page 62 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BRAGA MORO

FACTORY LOCATION
ITALY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03794-01-30504401 dated November
18, 2012, Braga Moro- Italy is pre-qualified for UPS as
conforming to National Grid SA Specification # 46-TMSS-03,
Rev.0, with the following conditions:
All Type, Routine and Special testes as per National Grid SA
Specifications/Standards together shall be carried out on the
First unit to be supplied to SEC/National Grid SA of UPS in an
Independent Testing Laboratory in the presence of three (3)
SEC/National Grid SA Engineers & one (1) SEC/National Grid SA
approved Independent Inspection Agency (IIA) Inspector. All
costs of which shall be borne by Braga Moro-Italy. This was
confirmed in writing by Braga Moro-Italy through their letter #
SEC Prequalification dated April 13, 2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order as
confirmed by Braga Moro- Italy through their letter # SEC
Prequalification dated April 13, 2011.

CEG

ITALY-BIBIENA

Yes

Based on TS&SD letter# 09-F001363/02-03032301 dated 2nd


May 2009 & S&SD letter# 14-05308-01-30504401 dated 21st
July 2014 as confirming to National Grid SA specifications #
46-TMSS-02, rev.0 ; with the following conditions:
Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.

GUTOR ELECTRONIC LTD.

SWITZERLAND

Yes

JESUS MARIA AGUIRRE SA (JEMA)

SPAIN-Lasarte-Oria

Yes

Based on S&SD Letter 12-00193-030504001 dated January 17,


2012. It is prequalified for UPS up to 100kVA as conforming to
SEC Specification# 46-TMSS-03, Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out on the
first batch of each types of UPS up to 100kVA in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated June 17, 2011.
Ten (10) years extended warranty from the date of PAC of
the FIRST turnkey project in case of contract award or date of
FIRST delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 17, 2011.

Page 63 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Statron AG

FACTORY LOCATION
SWITZERLAND-Maegenwil

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03254-01-30504401 dated August
29, 2012, it is pre-qualified for UPS (S2000 series) as
conforming to SEC Specification # 46-TMSS-03, Rev.0 with the
following conditions:
All Type, Routine and Special testes shall be carried out on
the first batch of each types of UPS in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Ten (10) years extended warranty in respect of defects due
to design, manufacturing, installation and workmanship from
the date of PAC of the first turnkey project (in case of contract
award) or from the date of first delivery of direct material
supply order as confirmed by the manufacturer Statron AG
through their letter # bm dated August 13, 2012.
Total =

8. 4. 3

BATTERY CHARGER, 48 VDC

Applicable Standards:
AEG Power Solutions SAS

FRANCE--

Yes

BENNING

FRANCE

Yes

46-TMSS-02,46-TMSS-05
originally was SAFT Power System SAS-France

Page 64 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BRAGA MORO

FACTORY LOCATION
ITALY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
I. Prequalified for BATTERY CHARGER, 48 VDC (For Telecom
Applications).
II. Prequalified for DC-DC Converters, 48 Volts based on S&SD
Letter 12-03794-01-30504401 dated November 18, 2012 as
conforming to National Grid SA Specification # 46-TMSS-07,
Rev.0 with the following conditions:
All Type, Routine and Special testes as per National Grid SA
Specifications/Standards together shall be carried out on the
First unit to be supplied to SEC/National Grid SA of DC-DC
Converters, 48 Volts Output in an Independent Testing
Laboratory in the presence of three (3) SEC/National Grid SA
Engineers & one (1) SEC/National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by Braga Moro-Italy. This was confirmed in
writing by Braga Moro-Italy through their letter # SEC
Prequalification dated April 13, 2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order as
confirmed by Braga Moro-Italy through their letter # SEC
Prequalification dated April 13, 2011.

COM 10 INTERNATIONAL PTY. LTD.

AUSTRALIA-ALPHA

Yes

SWITCH MODE RECTIFIERS / BATTERY CHARGERS ONLY FOR


TELECOM APPLICATION.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based on
Emerson Network Power Industrial Systems letter # nill dated
12/04/2013.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

- Previously "AEES ", the name has been changed to Emerson


Network Power Industrial Systems - France based on Emerson
Network Power Industrial Systems letter # nill dated
12/04/2013.

EMISA (ELECTRO MERCANTIL INDUSTRIAL


S.A. SPAIN)

SPAIN

Yes

- ACCEPTABLE FOR APPLICATIONS OTHER THAN TELECOM

Page 65 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ERSKINE

United Kingdom

Yes

Based on TS&SD letter# 09-F02210/03-03032301 dated 1st .


September 2009, ERSKIN System Ltd. (a division of Dale Power
Solution plc) from United Kingdom-Scarborough for 48V DC
battery Charger as confirming to SEC specification #
46-TMSS-05, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the manufacturer's
laboratory in the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

EXIDE

United States

Yes

SCR TYPE ONLY

HAMMER & SIMMONS

United Kingdom

Yes

Statron AG

SWITZERLAND-Maegenwil

Yes

Based on S&SD Letter 12-03254-01-30504401 dated August


29, 2012, it is pre-qualified for Battery Chargers 48V DC
(Models BDT and MPS) as conforming to SEC Specification #
46-TMSS-02, Rev.0 & 46-TMSS-05, Rev.0, with the following
conditions:
All Type, Routine and Special testes shall be carried out on
the first batch of each types of Battery Chargers 48V DC in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Ten (10) years extended warranty in respect of defects due
to design, manufacturing, installation and workmanship from
the date of PAC of the first turnkey project (in case of contract
award) or from the date of first delivery of direct material
supply order as confirmed by the manufacturer Statron AG
through their letter # bm dated August 13, 2012.

T.D.I

United States

Yes

SWITCH MODE RECTIFIERS ONLY FOR TELECOM


APPLICATIONS
Total =

9
9

.1

9. 1. 0

12

LV DISTRIBUTION PANELS

AC & DC DIST. PANELS


AC & DC DIST. PANELS

Applicable Standards:

31-TMSS-02

Page 66 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ABB/AEIL

Saudi Arabia

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

EAST & WEST FACTORY

Saudi Arabia-DAMMAM

Yes

ELECTRICAL PANEL BOARD FACTORY/HAWA


TRADING

Saudi Arabia-DAMMAM

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

ETA-PCS

United Arab Emirates-DUBAI

Yes

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

META Switchgear Company

Saudi Arabia-Riyadh

Yes

Based on based on S&SD letter # 14-02218-01-30504401


dated March 23, 2014 & TS&SD letter
#11-F03210/01-03032301 dated 29/11/2011, it is pre-qualified
for AC&DC Panels as confirming to SEC specification #
31-TMSS-02, Rev.0 with the following conditions:
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by MEMF-ETA Switchgear Manufacturing Company
through letter # Nil dated 08/12/2010.
Previously MEMF-ETA Switchgear Manufacturing Company,
Riyadh, Saudi Arabia [The name has been changed based on
S&SD letter # 14-02218-01-30504401 dated March 23, 2014].

MOHAMMAD AL OJAIMI FACTORY

Saudi Arabia-RIYADH

Yes

MUSAID SWITCHGEAR

Saudi Arabia-RIYADH

Yes

REMAL

Saudi Arabia-DAMMAM

Yes

SIEMENS

Saudi Arabia-JEDDAH

Yes

Page 67 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Waha Electric Supply Co. of Saudi Arabia(WESCOSA)-Dammam

FACTORY LOCATION
Saudi Arabia-Dammam

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 11-01751/01-03032301 dated
27/06/2011, it is pre-qualified for Auxiliary AC & DC Panels up
to 132kV only as confirming to SEC specification # 31-TMSS-02,
Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards shall be carried out on the first batch
of each type of Auxiliary AC&DC Panels to be supplied to SEC in
case of securing an order in the presence of three (3) SEC
engineers & one (1) approved independent inspection agency
Inspector in an independent testing laboratory. All the related
costs for witnessing the tests will be borne by the
manufacturer. This was confirmed by WESCOSA-Dammam
through letter # Nil dated 18/05/2010.
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by WESCOSA-Dammam through letter # Nil dated
30/08/2010.

10
10

.1

10. 1. 0

10

.2

10. 2. 0

Total =

12

Total =

LOAD BREAK SWITCHES UPTO 34.5 KV & RING MAIN UNITS, 15 KV

LOAD BREAK SWITCHES UPTO 34.5 KV


LOAD BREAK SWITCHES UPTO 34.5 KV

Applicable Standards:
ABB/AEIL

Saudi Arabia

Yes

AREVA

FRANCE

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

FRITZ DRIESCHER

GERMANY

Yes

HITACHI

JAPAN

Yes

KONCAR

Croatia/Hrvatska

Yes

SIEMENS

GERMANY

Yes

RMU, 15 KV
RMU, 15 KV

Applicable Standards:
ABB

Saudi Arabia-RIYADH

32-TMSS-07

Yes

Page 68 of 244

SER

10

.3

10. 3. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

11

.1

11. 1. 0

12
12

.1

Pre-Qualified
Manufacturers
By SEC

AREVA

FRANCE

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

FRITZ DRIESHER KG

GERMANY

Yes

GULF REYROLLE LTD

Saudi Arabia-DAMMAM

Yes

MERLIN GERIN

FRANCE

Yes

SAUDI LUCY

Saudi Arabia-AL KHOBAR

Yes

SIEMENS AG EVM

GERMANY-FRANKFURT

Yes

THE INTERNATIONAL ELECTRICAL PRODUCTS


CO.

Saudi Arabia-DAMMAM

Yes

W. LUCY

United Kingdom

Yes

REMARKS

Total =

10

Total =

Total =

SPARE PARTS FOR RMU & EOS


SPARE PARTS FOR RMU & EOS

Applicable Standards:
CELLMEC

11

FACTORY LOCATION

BAHRAIN

Yes

NEUTRAL EARTHING RESISTORS UP TO 33 KV

NER, UP TO 33 KV
NER, UP TO 33 KV

Applicable Standards:
CRESSAL RESISTOR

United Kingdom

Yes

FURSE

United Kingdom

Yes

M.S.Resistances

FRANCE--

Yes

METAL DEPLOYE

FRANCE

Yes

NATIONAL

INDIA

Yes

57-TMSS-01

EXTENDED GUARANTEE / WARRANTY FOR 10 YEARS

BARE CONDUCTORS

TYPE ACAR / ACSR / AAAC

Page 69 of 244

SER

12. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

BARE CONDUCTOR, ACAR / ACSR / AAAC

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
ALCOA

United States

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

REMARKS

10-TMSS-01

Based on S&SD letter# 13-02020-01-30504401 dated July 30,


2013, it is pre-qualified for ACSR, ACAR and AAAC type Bare
Overhead Line Conductors conforming to National Grid SA
specification # 10-TMSS-01, Rev.01 with the following
conditions:
Only ACSR Condor Conductor 795kcmil (402.83mm) was
successfully type tested in accredited Kinectrics
Laboratory-Canada in the presence of SEC/National Grid SA
Engineers with acceptable results (Kinectrics Report #
K-419415-RC-0001-R01, dated 11th Feb 2013).
The first batch of ACAR and AAAC conductors to be supplied
to SEC/National Grid SA shall be type tested in an independent
accredited test laboratory in the presence of three (3)
SEC/National Grid SA Engineers & one (1) SEC/National Grid SA
approved independent inspection agency Inspector and all
costs pertaining to the tests shall be borne by the
manufacturer.
Ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the first turnkey
project in case of contract award or date of first delivery in
case of direct material supply order. This was confirmed in
writing by the manufacturer through their letter #
C-PRQ-2013-02 dated June 17, 2013.

APAR Industries Ltd-NALAGARH

INDIA-NALAGARH

Yes

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010, it is pre-qualified for Bar Conductors as confirming
to SEC specification # 10-TMSS-01, Rev.01 with the following
conditions:

The first batch of each type of conductors to be supplied


to SEC shall be type tested in an independent accredited test
laboratory in the presence of three (3) SEC engineers & one (1)
SEC approved independent inspection agency Inspector and all
cost pertaining to the tests shall be borne by the manufacturer.
This has been confirmed in writing by the manufacturer,
through letter # AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer; through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.

Page 70 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-SILVASSA

FACTORY LOCATION
INDIA-SILVASSA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010 & Letter # 14-03608/02-030504401 dated 04th
June 2014, it is pre-qualified for Bare Conductors as confirming
to SEC/National Grid SA specification # 10-TMSS-01, Rev.01
with the following conditions:

AAAC Conductor (500 mm) was successfully type tested


in accredited VEIKI-VNL Laboratory-Budapest, Hungary in the
presence of SEC/National Grid SA Engineers with acceptable
results (VEIKI-VNL Ltd. Report # 7765/VNL, dated 3rd Feb
2014).

The first batch of ACAR & ACSR conductors to be supplied


to SEC/National Grid SA shall be type tested in an independent
accredited test laboratory in the presence of three (3)
SEC/National Grid SA Engineers & one (1) SEC/National Grid SA
approved Independent Inspection Agency Inspector and all
costs pertaining to the tests shall be borne by the
manufacturer.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer; through letter #
AIL/BRD/SEC/PQ/19 dated 22nd May 2010.

BAHRA CABLES Co.

Saudi Arabia-Jeddah

Yes

Based on S&SD letter # 15-01562-1-30504401 dated March 18,


2015. the manufacturer is prequalified for OVERHEAD
CONDUCTOR (type ACSR Condor) as conforming to National
Grid SA specification # 10-TMSS-01, Rev.01 with the following
condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # BCC/AQ/GSM/MZ dated August 20, 2011.

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN


INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER INTL.
STANDARDS, IN PRESENCE OF SEC ENGINEERS AND ALL COST
SHALL BE BORNE BY THE MANUFACTURER.10 YEARS
EXTENDED WARRANTY.

Page 71 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
STERLITE (INDIA)

FACTORY LOCATION
INDIA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-F001691/01-03032301 dated
June 19, 2010 and S&SD Letter 12-02686-1-30504401 dated
July 23, 2012, it is pre-qualified for Bare Conductors types
(ACAR, ACSR & AAAC) as confirming to SEC Specification #
10-TMSS-01, Rev.01 with the following condition:
ACAR, ACSR & AAAC conductors were successfully type
tested in accredited laboratory in the presence of SEC
Engineers with acceptable results.
Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.
Total =

12

.2

12. 2. 1

11

TYPE ACSR/AW
BARE CONDUCTOR, ACSR/AW

Applicable Standards:
ALCOA

United States

Yes

APAR Industries Ltd-NALAGARH

INDIA-NALAGARH

Yes

01-TMSS-01,10-TMSS-01

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010, it is pre-qualified for Bar Conductors as confirming
to SEC specification # 10-TMSS-01, Rev.01 with the following
conditions:

The first batch of each type of conductors to be supplied


to SEC shall be type tested in an independent accredited test
laboratory in the presence of three (3) SEC engineers & one (1)
SEC approved independent inspection agency Inspector and all
cost pertaining to the tests shall be borne by the manufacturer.
This has been confirmed in writing by the manufacturer,
through letter # AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer; through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.

Page 72 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-SILVASSA

FACTORY LOCATION
INDIA-SILVASSA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Bar Conductors as confirming
to SEC specification # 10-TMSS-01, Rev.01 with the following
conditions:

The first batch of each type of conductors to be supplied


to SEC shall be type tested in an independent accredited test
laboratory in the presence of three (3) SEC engineers & one (1)
SEC approved independent inspection agency Inspector and all
cost pertaining to the tests shall be borne by the manufacturer.
This has been confirmed in writing by the manufacturer,
through letter # AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer; through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.

BAHRA CABLES Co.

Saudi Arabia-Jeddah

Yes

Based on S&SD letter # 15-01562-1-30504401 dated March 18,


2015, the manufacturer is prequalified for OVERHEAD
CONDUCTOR (type Drake ACSR/AW) as conforming to National
Grid SA specification # 10-TMSS-01, Rev.01 with the following
condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # BCC/AQ/GSM/MZ dated August 20, 2011.

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN


INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER INTL.
STANDARDS, IN PRESENCE OF SEC ENGINEERS AND ALL COST
SHALL BE BORNE BY THE MANUFACTURER.10 YEARS
EXTENDED WARRANTY.

Page 73 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
STERLITE (INDIA)

FACTORY LOCATION
INDIA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-F001691/01-03032301 dated
19/06/2010, it is pre-qualified for Bare Conductors type
(ACSR/AW) as confirming to SEC specification # 10-TMSS-01
Rev.01 with the following condition:

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.
Total =

12

.3

12. 3. 1

11

GROUND WIRE
GROUND WIRE

Applicable Standards:
ALCOA

United States

Yes

APAR Industries Ltd-NALAGARH

INDIA-NALAGARH

Yes

10-TMSS-03

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as confirming to
SEC specification # 10-TMSS-03, Rev.0 with the following
conditions:

The first batch of Aluminum Clad Steel (ACS) type to be


supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall be
borne by the manufacturer. This has been confirmed in writing
by the manufacturer through letter # AIL/BRD/PQ/SEC/19
dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.

Page 74 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-SILVASSA

FACTORY LOCATION
INDIA-SILVASSA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as confirming to
SEC specification # 10-TMSS-03, Rev.0 with the following
conditions:

The first batch of Aluminum Clad Steel (ACS) type to be


supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall be
borne by the manufacturer. This has been confirmed in writing
by the manufacturer through letter # AIL/BRD/PQ/SEC/19
dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order. This has been confirmed in
writing by the manufacturer through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.

ECN CG SA

SPAIN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

TREFILEUROPE

FRANCE

Yes
Total =

12

.4

12. 4. 1

10

COPPER CLAD, STEEL GROUNDING CONDUCTOR & GROUNDING ROD


COPPER CLAD STEEL GROUNDING CONDUCTOR AND GROUNDING ROD

Applicable Standards:

ComScope Bimetals USA

United States-Statesville, NC

Yes

FM Sudafix

United Kingdom-Nottingham

Yes

FURSE

Saudi Arabia

Yes

GANSEC SHENGYUEAN WIRE & CABLE CO.


LTD.

CHINA

Yes

ILJIN CORP./JIWOONG ELECTRIC CO.

SOUTH KOREA

Yes

LTV COPPERWELD

United States

Yes

10-TMSS-05

Including Exothermic Welding and Grounding connectors.

Page 75 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SAUDI ELECTRIC INDUSTRIES CO. LTD.

FACTORY LOCATION
Saudi Arabia-JEDDAH

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

12

.5

12. 5. 1

COMPOSITE OPTICAL OH GROUND WIRE (OPGW)


OPGW

Applicable Standards:

10-TMSS-04

AFL TELECOMMUNICATIONS EUROPE LTD

United Kingdom--

Yes

PREVIOUSLY ALCOA FUJIKURA LTD (AFL).

AFL Telecommunications GmbH

GERMANY-Monchengladbach

Yes

EXTENDED GUARANTEE/WARRANTY FOR A PERIOD OF 10


YEARS.

BRUGG TELECOM AG

SWITZERLAND

Yes

CORNING CABLES (BICC)

United Kingdom-PRESCOT MERSYSIDE

Yes

DRAKA NK

FINLAND

Yes

FUJIKURA

JAPAN

Yes

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Jiangsu Zhongtian Technology Co.Ltd (ZTT)


-China

CHINA-Nantong

Yes

Previously Draka Comteq Germany GmbH & KG.

Based on TS&SD Letter # 10-01654-03032301 dated June 05,


2010 and S&SD Letter 12-05204-1-30504401 dated February
04, 2013. It is prequalified for OPGW as conforming to National
Grid SA specification # 10-TMSS-04, Rev.0, with the following
conditions:
OPGW type ZTT 13.3mm & ZTT 17.3mm 48 fibers is
successfully type tested as per SEC/National Grid SA
requirements as mentioned below:
-KEMA witness report TIC 3170-12 for ZTT 13.3mm OPGW
-SECRI Type Test Report 12-2009-1 for ZTT 13.3mm OPGW
-KEMA witness report TIC 3171-12 for ZTT 17.3mm OPGW
-SECRI Type Test Report 12-2009-2 for ZTT 17.3mm OPGW
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 18, 2009.

Page 76 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
LS CABLES

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-02583-03032301 dated
19/09/2010, it is pre-qualified for OPGW as confirming to SEC
specification # 10-TMSS-04,Rev.0, with the following
conditions:

All type/design; routine/sample and special tests per SEC


material specification # 10-TMSS-04, Rev.0 of first batch of
each types of OPGW to be supplied to SEC shall be conducted
in an independent testing laboratory in the presence of three
(3) SEC engineers & one (1) SEC approved independent
inspection agency Inspector and all cost pertaining to the tests
shall be borne by Manufacturer. This was confirmed in writing
by the manufacturer through letter #Nil dated 24th December
2009.

Ten (10) years extended warranty for each types of


OPGW from the date of PAC of the turnkey project in case of
contract award or date of delivery in case of direct material
supply order. This was confirmed in writing by the manufacturer
through letter #Nil dated 24th December 2009.
PHILLIPS FITEL

CANADA

Yes

PIRELLI

ITALY

Yes

PRYSMIAN TELECOM

SPAIN

Yes

PREVIOUSLY "PIRELLI"

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Based on TS&SD letter# 09-F00730/03-03032301 dated 24th


August 2009, Taihan Electric Wire Co. Ltd. from South
Korea-Anyang for OPGW as confirming to SEC specification #
10-TMSS-04, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the manufacturer's
laboratory in the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.
Total =

12

.6

12. 6. 1

13

HEAT RESISTANT ALUMINUM ALLOY CONDUCTOR


HEAT RESISTANT ALUMINUM ALLOY CONDUCTOR

Applicable Standards:

10-TMSS-06

Page 77 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FUJIKURA VISCAS CORP

JAPAN

Yes

IT IS A CONSORTIUM OF FUJIKURA & FURUKAWA. ONLY


INVAR CONDUCTORS PER CLAUSE 1.3 & 1.4 OF 10-TMSS-06.
FIRST LOT TO BE TYPE TESTED IN THE PRESENCE OF 3 SEC
ENGRS AND IIA INSPECTOR; EXTENDED WARRANTY FOR 10
YEARS.

J-Power System Corporation

JAPAN-Hitachi

Yes

Based on S&SD letter # 15-00017-1-30504401 dated 8th


February 2015, the manufacturer is prequalified for INVAR
Conductor Type ZTACIR/AS (Super-Thermal Resistant Aluminum
Alloy Conductor Aluminum Clad Invar Alloy Steel Reinforced) as
conforming to National Grid SA specification # 10-TMSS-06,
Rev.01 with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing and workmanship from the date
of the Provisional Acceptance Certificate (PAC) of the first
turnkey project (in case of contract award) and from the date
of first delivery in case of direct material supply order shall be
provided as confirmed by the manufacturer through their letter
# JLX80-15-0022 dated March 02nd, 2015.

Old Remark
Based on TS&SD letter# 09-00649-1-03032301 dated 28 March
2009 it is pre-qualified for GTACSR & GZTACSR.

Page 78 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
LS CABLES

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-02584-03032301 dated
19/09/2010, it is pre-qualified for Heat Resistance Aluminum
Alloy Conductors, Gap& Non Gap type as confirming to SEC
specification # 10-TMSS-06,Rev.0, with the following
conditions:

All type/design; routine/sample and special tests per SEC


material specification # 10-TMSS-06, Rev.0 of first batch of
each types of Heat Resistance Aluminum Alloy Conductors to be
supplied to SEC shall be conducted in an independent testing
laboratory in the presence of three (3) SEC engineers & one (1)
SEC approved independent inspection agency Inspector and all
cost pertaining to the tests shall be borne by Manufacturer.
This was confirmed in writing by the manufacturer through
letter #Nil dated 08th January 2010.

Ten (10) years extended warranty for each types of Heat


Resistance Aluminum Alloy Conductors from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through letter #Nil
dated 08th January 2010.

Full time presence of LS-Korea expert during execution of


first order with Gap type conductor for guidance and training of
SEC/Contractor staff about installation of this type of
conductor as confirmed through LS letter # LS/LHJ-100526/00
dated 26th May 2010.

Full technical support will be provided to SEC during


operation of Gap Conductors for minimum five (5) years period
from first project as confirmed through LS letter # LS/LHJ100526/00 dated 26th May 2010.
Total =

13
13

.1

13. 1. 1

INSULATED CONDUCTOR CABLE (XLPE)

13.8 KV
XLPE CABLE 13.8 KV

Applicable Standards:

11-TMSS-04

Page 79 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALFANAR ELECTRICAL SYSTEMS

FACTORY LOCATION
Saudi Arabia-RIYADH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-05014-2-3050440 dated September
08, 2013, it is pre-qualified for Insulated Conductor Cable
(XLPE) as conforming to National Grid SA Specification #
11-TMSS-04, Rev.0 with the following conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery (in case of direct material supply order), as
confirmed through ALFANAR Electrical Systems, Riyadh letter
# nil dated March 10, 2013.
Type Tests have been successfully conducted in
KINETRIC-Canada in the presence of National Grid SA
Engineers on 1x630mm2 CU/XLPE/ATA/PVC 20/35 KV MV Cable
during 9th to 22nd April 2013. However, any MV Power Cable
beyond cable size of 630 mm2 to be supplied to SEC/National
Grid SA shall fully type tested at an accredited laboratory in the
presence of National Grid SA Engineers & third party inspector.

DUBAI CABLE CO.

United Arab Emirates-DUBAI

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Ref# is 08-02531/01-0303230 dated 08/11/2008


no accessories are pre-qualified

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13

.2

13. 2. 1

33 & 34.5 KV
XLPE CABLE 33 & 34.5 KV

Applicable Standards:

11-TMSS-04

Page 80 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALFANAR ELECTRICAL SYSTEMS

FACTORY LOCATION
Saudi Arabia-RIYADH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-05014-2-30504401 dated September
08, 2013, it is pre-qualified for Insulated Conductor Cable
(XLPE) as conforming to National Grid SA Specification #
11-TMSS-04, Rev.0 with the following conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery (in case of direct material supply order), as
confirmed through ALFANAR Electrical Systems, Riyadh letter
# nil dated March 10, 2013.
Type Tests have been successfully conducted in
KINETRIC-Canada in the presence of National Grid SA
Engineers on 1x630mm2 CU/XLPE/ATA/PVC 20/35 KV MV Cable
during 9th to 22 April 2013. However, any MV Power Cable
beyond cable size of 630 mm2 to be supplied to National Grid SA
shall be fully type tested at an accredited laboratory in the
presence of National Grid SA Engineers & third party inspector.

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DUBAI CABLE CO.

United Arab Emirates-DUBAI

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

Including Joints & Terminations

FUJIKURA CABLES

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

MKM

HUNGARY

Yes

Including Joints & Terminations

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Ref# is 08-02531/01-0303230 dated 08/11/2008


no accessories are pre-qualified

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13

.3

13. 3. 1

15

XLPE CABLES 69 KV
XLPE CABLES 69 KV

Applicable Standards:
ALCATEL

FRANCE

Yes

11-TMSS-01
Including Joints & Terminations

Page 81 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DRAKA NK

FINLAND

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE


TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY INSPECTION
AGENCY & THREE ENGINEERS OF SEC FOR FIRST CONTRACT;
10 YEARS OF EXTENDED GUARANTEE/WARRANTY; FOR
JOINTS & TERMINATIONS ALSO;

FUJIKURA CABLES

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Based on TS&SD letter # 10-02784-01-03032301 dated


24/10/2010, it is pre-qualified for 69kV, 1x630mm XLPE Power
Cable as confirming to SEC specification # 11-TMSS-01, Rev.0,
with the following condition:

Ten (10) years extended warranty for the proposed 69kV,


1x630mm XLPE Power Cable from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order. This was confirmed in
writing by Jeddah Cable Co. through letter #Nil dated 26th
June 2006.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

MKM

HUNGARY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations


Total =

13

.4

13. 4. 1

14

110KV TO 132 KV
XLPE CABLES 110 TO 132 KV

Applicable Standards:

11-TMSS-02

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DRAKA NK

FINLAND

Yes

Including Joints & Terminations

Page 82 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE


TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY INSPECTION
AGENCY & THREE ENGINEERS OF SEC FOR FIRST CONTRACT;
10 YEARS OF EXTENDED GUARANTEE/WARRANTY; FOR
JOINTS & TERMINATIONS ALSO;

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Based on TS&SD letter # 10-02784-01-03032301 dated


October 10,2014 and S&SD letter# 14-04876-01-30504401
dated July 16, 2014. it is pre-qualified for 132kV, 1x2500mm
CU/XLPE/CWS/LAT/HDPE Power Cable as confirming to National
Grid specification # 11-TMSS-02, Rev.1, with the following
condition:
Ten (10) years extended warranty for XLPE Power Cable
from the date of PAC of the turnkey project in case of contract
award or date of delivery in case of direct material supply
order. This was confirmed in writing by Jeddah Cable Co.
through letter #Nil dated 26th June 2006.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on S&SD letter # 15-00585-01-30504401 dated


February 10, 2015, the manufacturer is prequalified for
110/115/132KV, 1X1200mm CU/XLPE Power Cable as
conforming to National Grid SA specification # 11-TMSS-02,
Rev.01.
Not approved to supply the power cable 110/115KV, 132KV
with conductor cross section of 1X2500 mm,XLPE, as per
11-TMSS-02, Rev.01 for any SEC/ National Grid SA projects
based on S&SD letter# 13-02128-02-30504401 dated
November 25, 2013.

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13

.5

13. 5. 1

15

230 K V
XLPE CABLE 230 K V

Applicable Standards:

11-TMSS-02

Page 83 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations; COMPLETE TYPE, SPECIAL &


ROUTINE TESTS FOR THE FIRST ORDER , ALSO 10 YEARS
WARRANTY FROM THE DATE OF PAC ARE REQUIRED

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

based on TS&SD letter# 09-01366-03032301 dated 10th. May


2009, it is pre-qualified as conforming to SEC specifications #
11-TMSS-02, rev.0 with the following conditions:

All type/design and routine/sample tests shall be carried


out on the first batch of 230kV XLPE power cable to be supplied
to SEC in securing an order in an independent testing
laboratory as per IEC/AEIC and SEC standards in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations.


Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total =

13

.6

13. 6. 1

11

380 KV
XLPE CABLE -380 KV

Applicable Standards:

11-TMSS-02

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations; COMPLETE TYPE, SPECIAL &


ROUTINE TESTS FOR THE FIRST ORDER , ALSO 10 YEARS
WARRANTY FROM THE DATE OF PAC ARE REQUIRED

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

Page 84 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

No

Based on TS&SD letter 11-01374-03032301 dated April 27,


2011. It is DISQUALIFIED for 380KV XLPE Cable.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Based on S&SD letter # 15-3193-30504401 dated May 03,
2015, the manufacturer is prequalified to supply the following
equipment with the specified designations only:
380 kV cable 1x2500 mm2, CU/XLPE/LEAD/PE type.
Outdoor terminations with porcelain bushing type
UMEMA40Q004 from PPC insulators (Germany).
Outdoor terminations with porcelain bushing type
UMEMA40Q004.
GIS Terminations dry type UEPG40Q001.
Cable joint with screen interruption type UEMK40Q002.
Note: For all future SEC/National Grid SA projects/direct
purchase orders, porcelain bushings for outdoor terminations
shall be procured from our approved list.

NEXANS

BELGIUM-Charleroi

Yes

Based on S&SD letter # 14-07330-030504401, dated


22/10/2014 , it is prequalified for 380kV XLPE Cables as
confirming to National Grid SA Material Specification
11-TMSS-02, Rev.01 with the following conditions: Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order, as confirmed by the manufacturer
through letter # Nil dated 12/02/2013.

NKT

GERMANY

Yes

Including Joints & Terminations

PIRELLI

GERMANY-BERLIN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

Page 85 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TAIHAN ELECTRIC WIRE COMPANY

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-08139-01-30504401 dated January
07, 2015, the manufacturer is prequilified to supply power
cables rated 380 kV with conductor cross section of 1X2500
mm, XLPE, with copper wires metallic shield as per
11-TMSS-02, Rev.01 along with the cable accessories with the
following drawings numbers:
- Power cable: TXCCD-3802500-130501.
- Outdoor termination: CVC-APS-3804605N-BD (Rev. A).
- GIS termination fluid filled type: CVC-GWO-380-BD (Rev. A).
- GIS termination dry type: CVC-GWBS-380-BD (Rev. A).
- Cable joint type: CVC-MIP-380-BD (Rev. A).
- Cable joint (A type) with screen interruption type
CVC-MIP-380-R1-BD (Rev. A).
- Straight joint type CVC-MNP-380-BD (Rev. A).
- Coffin Box (1 hole) CV-C1-380N-BD (Rev. A).
- Coffin Box (1 hole) CV-C1-380N-BD (Rev. A).

In addition to the following condition:


- Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) or from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # Nill dated September 02, 2014.
VISCAS FUJIKURA

JAPAN

Yes

Including Joints & Terminations


Total =

14
14

.1

14. 1. 1

11

LOW-PRESSURE OIL FILLED (LPOF) CABLE

110 TO 132 KV
LPOF CABLE 110 KV TO 132 KV

Applicable Standards:

11-TMSS-03

ALCATEL CABLE

FRANCE

Yes

Including Joints & Terminations

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DATWYLER

United Kingdom

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

Page 86 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

KABEL WERK BRUGG AG

SWITZERLAND

Yes

Including Joints & Terminations

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

NEXAN(CORTALLIOD)

SWITZERLAND

Yes

Including Joints & Terminations

PIRELLI

ITALY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

14

.2

14. 2. 1

230 KV
LPOF CABLE 230 KV

Applicable Standards:

11-TMSS-03

ALCATEL

FRANCE

Yes

Including Joints & Terminations

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations.


Complete Type, Routine / Sample tests for first order.
Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total =

14

.3

14. 3. 1

16

10

380 KV
LPOF CABLE 380 KV

Applicable Standards:
ALCATEL

FRANCE

Yes

11-TMSS-03
Including Joints & Terminations

Page 87 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

HITACHI CABLE LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.

MITSUBISHI CABLE INDUSTRIES LTD

JAPAN

Yes

Including Joints & Terminations

PIRELLI

ITALY

Yes

Including Joints & Terminations

PIRELLI GENERAL

United Kingdom

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

SIEMENS

GERMANY

Yes

Including Joints & Terminations

STANDARD TELEFON OG KABELFABRIK A/S

NORWAY

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations.


Complete Type, Routine / Sample tests for first order.
Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total =

14

.4

14. 4. 1

17

LINK BOX FOR U/G POWER


LINK BOX FOR U/G POWER

Applicable Standards:

12-TMSS-11

---

Yes

LINK BOX SUPPLIED / MANUFACTURED BY APPROVED POWER


CABLE MANUFACTURERS ARE ACCEPTABLE

AARTCO

Saudi Arabia-Al-Khobar

Yes

UP TO 230KV.

ABB

SWEDEN

Yes

Page 88 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

AK POWER SOLUTONS PTY LTD

AUSTRALIA-Huntingwood, NSW

Yes

AL SHAHRANI EST.

Saudi Arabia-RIYADH

Yes

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG

MOHAMMAD AL OJAIMI FACTORY

Saudi Arabia-RIYADH

Yes

PAD MOUNTED STAINLESS STEEL BOXES AND UNDER GROUND


FIBER GLASS BOXES UP TO 132KV ACCEPTABLE. EXTENDED
GUARANTEE FOR 10 YEARS FOR THE FIRST SUPPLY AND IT
WILL BE REDUCED YEARLY IN CASE OF FUTURE PROJECT
AWARDS.

PIRELLI

GERMANY-BERLIN

Yes

Power and Telecommunication Equipments


Factory (P.T.E. Co.) (CEPCO)

Saudi Arabia-Jeddah

Yes

STEINER

GERMANY

Yes

Previously HAYCOLEC SWITCHGEAR PTY Australia-NSW [The


name has been changed to AK POWER SOLUTONS PTY LTDAustralia-Huntingwood, NSW based on S&SD/P&SFD letter #
13-07444-30504401 dated December 11, 2013 and based on
AK POWER SOLUTONS PTY LTD- Australia-NSW-Huntingwood
Letter # NG251113 dated November 25, 2013].

Based on TS&SD fax ref# 09-00396-1-03032301 dated


17/02/2009 P.T.E is prequalified for Link Boxes rated up to
380kV.
* (10) years extended warranty.

Total =

14

.5

14. 5. 0

SHEATH VOLTAGE LIMITERS (SVL)


SHEATH VOLTAGE LIMITERS (SVL)

Applicable Standards:
ABB

SWITZERLAND

Yes

AK POWER SOLUTONS PTY LTD

AUSTRALIA-Huntingwood, NSW

Yes

Previously HAYCOLEC SWITCHGEAR PTY Australia-NSW [The


name has been changed to AK POWER SOLUTONS PTY LTDAustralia- Huntingwood, NSW based on S&SD/P&SFD letter #
13-07444-30504401 dated December 11, 2013 and based on
AK POWER SOLUTONS PTY LTD- Australia-NSW-Huntingwood
Letter # NG251113 dated November 25, 2013].
Total =

14

.6

14. 6. 0

13

EARTHING BONDING CABLE


EARTHING BONDING CABLE

Applicable Standards:

11-TMSS-12

Page 89 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

FUJIKURA VISCAS CORP

JAPAN

Yes

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

REMARKS

Based on S&SD letter # 15-04684-02-30504401 dated June 18,


2015, the manufacturer is prequalified to supply coaxial
bonding/ earthing cable, as conforming to National Grid SA
specification # 11-TMSS-12, Rev.0 with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the project (in case of contract award) and from the date of
delivery in case of direct material supply order shall be provided
as confirmed by the manufacturer through their extended
warranty letter attached with the letter #
JCC-EP-PQ-0105-14-05 dated May 24, 2015.

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

PIRELLI

GERMANY-BERLIN

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SAUDI MODERN CO. (RIYADH CABLES)

Saudi Arabia- RIYADH

Yes

PREVIOUSLY LG

Total =

15
15

.1

15. 1. 0

FIBER OPTIC CABLE

NON-METALLIC FIBER OPTIC (F/O) CABLE & ACCESSORIES


NON-METALLIC FIBER OPTIC (F/O) CABLE & ACCESSORIES

Applicable Standards:

AFL TELECOMMUNICATIONS EUROPE LTD

United Kingdom--

Yes

ALCATEL

SWEDEN

Yes

B.V.TWENTSCHE KABELFABRIEK

NETHERLANDS- NAAKSBERGEN PLANT

Yes

BICC

United Kingdom

Yes

BRUGG TELECOM AG

SWITZERLAND

Yes

CORNING CABLES

United Kingdom-PRESCOT MERSEYSIDE

Yes

DRAKA NK

FINLAND

Yes

ERICSON

SWEDEN

Yes

FUJIKURA LTD.

JAPAN

Yes

FURUKAWA

JAPAN

Yes

HITACHI

JAPAN

Yes

48-TMSS-02
PREVIOUSLY ALCOA FUJIKURA LTD. (AFL)

ACCESSORIES ONLY

Page 90 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

INDUSTRIAS ARRUTI

SPAIN

Yes

ONLY ACCESSORIES

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

MIDDLE EAST OPTIC FIBER & CABLE


MANUFACTURING CO. (MEFC)

Saudi Arabia-RIYADH

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

NKF KABEL B.V.

NETHERLANDS

Yes

NOKIA

FINLAND

Yes

ACCESSORIES ONLY

Oman Fiber Optic Cable Company

Oman-Rusayl

Yes

Based on TS&SD letter# 10-00909-2-03032300 dated April 06,


2010. It is pre-qualified for Non Metallic Fiber Optic Cable per
SEC Specification 48-TMSS-02, Rev.0 with the following
conditions:
Type Test: The first batch of each type of Non Metallic Fiber
Optic Cable to be supplied to SEC shall be type tested per
relevant International and SEC Specifications in presence of
three (3) SEC Engineers and one (1) SEC approved IIA
Inspector and all cost pertaining to the test shall be borne by
the Manufacturer as confirmed through Letter# Nil dated
September 12, 2009.
Extended Warranty: Ten (10) year Extended Warranty shall
be applicable for all supplies made by Oman Fiber Optic Cable
Company to SEC as confirmed through Letter# EU.SEC.PQ.01
dated June17, 2009.

OPTOKON

CZECH REPUBLIC-Jihlava

Yes

PIRELLI

ITALY

Yes

PRYSMIAN TELECOM

SPAIN

Yes

ONLY FOR THE FOLLOWING ACCESSORIES


1 Standard 19 rack (ROV Series) and 23" rack
2 Standard 19" rack Mount Fiber Optic Patch Panel type MCNP
& MFDC consisting of 12/24/36/48 Ports
3 Fiber Optic Wall Mount Box type MPIC consisting of
12/24/36/48 Ports
4 Fiber Storage Shelf type MFSS
5 Optical Pig Tails/Patch Chords equipped with FC/PC & E2000
Connectors

PREVIOUSLY "PIRELLI"

Page 91 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
R & M Reichle & De-Massari AG

FACTORY LOCATION
SWITZERLAND-Wetzikon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-02127-030504401 dated May 19,
2013, R & M Reichle & De-Massari AG, Wetzikon, Switzerland is
pre-qualified for "Accessories only" fiber optic and copper
passive components (Structure Cabling) as conforming to
National Grid SA specification # 01-TMSS-01, Rev.01, with the
following conditions:
Five (5) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order as
confirmed by R & M Reichle & De-Massari AG, Wetzikon,
Switzerland through their letter #Nill dated June 10, 2013.

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

RIYADH TELEPHONE CABLES CO.

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on S&SD Letter 12-03896-30504401 dated November


10, 2012, SAUDI CABLE Co. - Saudi Arabia-Jeddah is
pre-qualified for Non-Metallic Fiber Optic Cable (F/O) Cable &
Accessories as conforming to SEC Specification # 48-TMSS-02,
Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated June 12, 2011.

SIEMENS

GERMANY

Yes

SUMITOMO

JAPAN-YOKOHAMA

Yes

TE Connectivity Ltd.

United States--

Yes

Based on S&SD Letter 12-03688-01-30504401 dated January


03, 2012. The name of the manufacturer has been changed
from ADC- United States to TE Connectivity Ltd.-United States.

TELECT

Poland-Wroclaw

Yes

based on TS&SD letter# 09-01095-03032301 dated 18th. April


2009 for the following accessories:
- Management Rack E-9000 series
- Distribution & Termination Unit LCX.
- Wall mounted unit LanLinxs.
Total =

16
16

29

PILOT WIRE CABLES & ACCESSORIES

.0

16. 0. 0

PILOT WIRE CABLES & ACCESSORIES

Applicable Standards:
DEMIRER KABLO

TURKEY

Yes

48-TMSS-01,48-TMSS-03,48-TMSS-04,48-TMSS-05
CABLE & ACCESSORIES

Page 92 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

GOLDSTAR CABLE

KOREA, Republic of

Yes

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

KERPENWORK

GERMANY

Yes

CABLE & ACCESSORIES

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SIEMENS

GERMANY

Yes

STEINER

GERMANY

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

UP TO 100 PAIRS

CABLE & ACCESSORIES

Total =

17
17

SHIELDED CABLE FOR INSTRUMENTATION

.0

17. 0. 0

SHIELDED CABLE FOR INSTRUMENTATION

Applicable Standards:
ALPHA

United States

Yes

AT & T

United States-NEW YORK

Yes

BELDEN

United States

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on TS&SD fax ref.#08-02969-3-03032301 dated


07/01/2009. Pre-Qualified for Shielded Instrumentation &
Thermocouple Cables with this conditions:
-First batch shall be type, designe, special, acceptance &
routine tests in the factory test laboratory in presence of (3)
SEC engineers & (1) independent inspector.
-(10) years warranty

TEKAB Co. Ltd.

United Arab Emirates-Sharjah

Yes

APPROVED FOR CABLES WITHOUT METALLIC SHEATH; TYPE


TEST CERTIFICATE FROM INDEPENDENT LAB TO BE
SUBMITTED FOR 1ST ORDER; EXTENDED QUARANTEE FOR 10
YEARS.
Total =

18
18

11

POWER /OR CONTROL CABLE (0.6/1KV)

.0

Page 93 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

18. 0. 0

POWER /OR CONTROL CABLE (0.6/1KV)

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

REMARKS

11-TMSS-10

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-01432-03032301 dated 16th. May


2009 is pre-qualified for Low Voltage Power & Control Cables
0.6/1kV as conforming to SEC specifications # 11-TMSS-10,
rev.0 with the following conditions:

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

BAHRA CABLES Co.

Saudi Arabia-Jeddah

Yes

Based on S&SD letter # 15-01562-1-30504401 dated March 18


2015, the manufacturer is prequalified for LV power cables as
conforming to National Grid SA specification # 11-TMSS-10,
Rev.01 with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # BCC/AQ/GSM/MZ dated August 20, 2011.

BELDEN

United States

Yes

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

Middle East Specialized Cable Co. MESC

Jordan--

Yes

Previously JORDAN NEW CABLE COMPANY- JORDAN-AMMAN


[The name has been changed based on S&SD/P&SFD letter #
14-01869-30504401 dated March 24, 2014].

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Based on TS&SD letters # 10-02435-03032301 dated


06/09/2010 & 10-02611-03032301 dated 02/10/2010, it is
pre-qualified for LV Power& Control Cables (0.6/1kV) rating as
confirming to SEC specification # 11-TMSS-10,Rev.0, with the
following condition:

based on TS&SD fax ref# 09-00303/01-03032301 dated


18/02/2009.

Ten (10) years extended warranty for the proposed LV


Power& Control Cables from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This was confirmed by Oman
Cables Industry through letter # Nil dated 21/08/2010.
RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Page 94 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TEKAB Co. Ltd.

FACTORY LOCATION
United Arab Emirates-Sharjah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07588-30504401 dated December
11, 2013, it is pre-qualified for Power and/or Control Cable
Copper 600/1000 V Rating as conforming to National Grid SA
specification # 11-TMSS-10, Rev.01, with the following
conditions:
It is pre-qualified for All LV power & control cables with copper
conductor except clause 4.3.5 point a.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer TEKAB Co. Ltd, UAE
through their letter # 0580/SO/13 dated November 17, 2013.
Total =

19
19

.1

19. 1. 1

12

CONDUCTOR FITTINGS/CABLE ACCESSORIES

CABLE SPLICE & TERMINATION KITS UP TO 132 KV


CABLE SPLICE & TERMINATION KITS UP TO 132 KV

Applicable Standards:

---

Yes

ABB

SWITZERLAND

Yes

BRUGG CABLE

SWITZERLAND

Yes

DAITWEILER

United Kingdom

Yes

ELASTIMOLD

United States

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

G&W

United States

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

NEXAN

SWITZERLAND

Yes

12-TMSS-10
APPROVED POWER CABLE MANUFACTURERS UP TO 132KV ARE
ACCEPTABLE SUPPLIERS FOR SPLICE AND TERMINATION KITS
OF THE SAME RATING

SUSPENDED FOR ALL ONGOING & FUTURE PROJECTS DUE TO


FREQUENT FAILURE & VERY POOR FOLLOWUP RESPONSE
FROM THE MANUFACTURER.

PREVIOUSLY LG

Page 95 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
NKT

FACTORY LOCATION
GERMANY-Cologne

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-05202-01-30504401 dated
September 15, 2015, it is pre-qualified for the following types
of 132 kV cables accessories:
- Switchgear Termination SEV 170 (3.7 0264-01)
- Transformer Termination TEV 170 (3.7 0263-01)
- Porcelain Outdoor Termination FEV 170-P (3.7 5056-04)
- Straight Joint with Screen Separation SME 145-S-P (3.7
8122-01)
Extended Warranty/Guarantee for the proposed 132 kV
cables accessories shall be provided in respect of the defects
due to design, manufacturing, installation and workmanship for
a period of ten (10) years from the date of Provisional
Acceptance Certificate (PAC) of the project (in case of contract
award) and from the date of delivery for the direct material
supply order as confirmed through the manufacturer letter # nil
dated June 04, 2013.

PFISTERER IXOSIL

SWITZERLAND

Yes

PIRELLI

GERMANY-BERLIN

Yes

RAYCHEM

GERMANY

Yes

RAYCHEM

Saudi Arabia-DAMMAM

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

PREVIOUSLY SEFAG IXOSIL

LIMITED TO 69KV ONLY. UNDER THE GROUP OF TYCO

Total =

19

.2

19. 2. 1

CABLE SPLICE & TERMINATION KITS UP TO 230 KV


CABLE SPLICE & TERMINATION KITS UP TO 230 KV

Applicable Standards:

---

Yes

ABB

GERMANY

Yes

12-TMSS-10
APPROVED 230 KV POWER CABLE MANUFACTURERS ARE ALSO
ACCEPTABLE SUPPLIERS FOR SPLICE AND TERMINATION KITS
OF THE SAME RATING

Total =

19

.3

19. 3. 0

16

CABLE SPLICE & TERMINATION KITS UP TO 380 KV


CABLE SPLICE & TERMINATION KITS UP TO 380 KV

Applicable Standards:
---

Yes

12-TMSS-10
APPROVED 380 KV POWER CABLE MANUFACTURERS ARE ALSO
ACCEPTABLE SUPPLIERS FOR SPLICE AND TERMINATION KITS
OF THE SAME RATING

Page 96 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

J-POWER SYSTEM CORP.

JAPAN

Yes

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

NEXANS

SWITZERLAND-Cossonnay

Yes

Based on S&SD letter # 14-07330-030504401, dated


22/10/2014, it is prequalified 380kV XLPE Cable Accessories as
confirming to National Grid SA Material Specification
12-TMSS-10, Rev.0 with the following conditions: Only the following Type/Model of accessories are approved
for 380kV: DTF 1.380 (380kV Dry type GIS Sealing End), SOA
1.380 (380kV Outdoor Sealing End), SFY 1.380 (380kV
Transformer Sealing End), SMP 1.380 (380kV Cross-bonding
joint).
Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order, as confirmed by the manufacturer
through letter #Nil dated 12/02/2013.
Total =

20
20

CONNECTORS, OVERHEAD LINE COMPRESSION TYPE

.0

20. 0. 0

CONNECTORS, OVERHEAD LINE COMPRESSION TYPE

Applicable Standards:

A SALVI & C SPA

ITALY-MILANO

Yes

ALCOA

United States

Yes

BURNDY

United States

Yes

CAROBENI

ITALY

Yes

DALEKOVOD PROIZVODNJA

Croatia/Hrvatska-Zagreb

Yes

12-TMSS-02

Based on TS&SD fax # 10-01179-03032301 dated April 20,


2010, this manufacturer is pre-qualified for Compression Type
Connectors for O/H T/L per 12-TMSS-02, Rev.0 with the
following conditions:
Each new design of Compression Type Connectors for O/H T/L
which has NOT been type tested/supplied to SEC before, shall
be type tested as per 12-TMSS-02.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
Previously DALEKOVOD Croatia.[The name has been changed
based on S&SD/P&SFD letter # 12-01292-30504401 dated April
10, 2012]

ELASTIMOLD

United States

Yes

Page 97 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

HOMAC

United States

Yes

INDUSTRIAS ARRUTI

SPAIN

Yes

ISELFA

ITALY

Yes

On Hold

Lorunser Austria GmbH

SLOVAKIA-ML - Productions, Myjava

Yes

Based on S&SD letter # 13-062982-2-30504401 dated


December 04, 2013, it is pre-qualified for substation connectors
(bolted welded & compression types) up to 380 kV, with the
following condition:
Ten (10) years extended warranty shall be provided from the
date of PAC of the first turnkey project in case of contract
award or date of first delivery in case of direct material supply
order. This was confirmed in writing by the manufacturer
through their letter # Nil dated November 02, 2009.

MOSDORFER

AUSTRIA

Yes

Nuova Elettromeccanica Sud S.p.A

ITALY-Campo Calabro

Yes

Based on S&SD letter # 15-06603-030504401 dated August 13,


2015 it is pre-qualified for Overhead line compression type
Connectors, as conforming to National Grid SA specifications #
12-TMSS-02 with the following conditions:
First batch of Overhead line compression type connectors
shall be type tested, at an independent laboratory in the
presence of three (3) SEC/National Grid SA engineers and one
(1) approved IIA (Independent Inspection Agency) inspector as
confirmed by the manufacturer vide their letter no. nil dated
14/11/2014.
Each new design of Overhead Line Compression type
Connectors which has not been tested, shall be type tested as
per latest revision of 12-TMSS-02.
Ten (10) years Extended Warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order shall be
applicable for the Compression type Connectors, to be supplied
to SEC/National Grid SA as confirmed through letter # Nil dated
14.11.2014.

PFISTERER

SWEDEN

Yes

PREVIOUSLY SEFAG

PFISTERER

SWITZERLAND

Yes

PREVIOUSLY SEFAG AG

Page 98 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SA_RA Energy, Construction, Trade and
Industry Co. Inc.

FACTORY LOCATION
TURKEY-ADANA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-09052-01-30504401 dated 11th
December 2014, this manufacturer is pre-qualified for
compression connectors up to 380kV conforming to 12-TMSS-02
Rev.01 with the following conditions.
Type tests (Corona/RIV, Heat Cycle, Fault Current and
Tensile Strength) with ACAR & ACSR/AW conductors were
performed at VEIKEI VNL Ltd. Budapest, Hungary from Nov.
2012 to June 2013.
Each new design of Compression Connectors which has not
been type tested, shall be type tested as per latest revision of
12-TMSS-02.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.

SBI

SPAIN--

Yes

SICAMEX

FRANCE-FEUGEROLLE & POMPADOUR

Yes

SM-CI

FRANCE--

Yes

Based on S&SD letter # 15-04947-30504401 dated June 09,


2015, it is prequalified for Substation Connectors (Bolted,
Welded & Compression type up to 380kV). Corona/RIV, Heat
Cycle/CCT, Mechanical, Short Circuit and Temperature Rise
Tests were conducted at various laboratories including BAZET,
ZKU, KEMA and L.C.O.E.

PREVIOUSLY AS FCI(SAAE), FRANCE.


Total =

21
21

.1

21. 1. 1

18

INSULATORS

PORCELAIN INSULATORS
STATION POST INSULATOR PORCELAIN, UP TO 132 KV, 230 KV and 380 KV

Applicable Standards:

15-TMSS-01

DIELVE

ITALY

Yes

LAPP

GERMANY-ROSENTHAL

Yes

LAPP

United States

Yes

NGK

JAPAN

Yes

Approved Only Up To 132 KV Only

Page 99 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PPC INSULATORS

FACTORY LOCATION
AUSTRIA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC
Insulators (Austria) Letter # Nil dated 4th July 2010, it is
pre-qualified for Station Post Insulator Porcelain, up to 132kV,
230kV&380kV as confirming to SEC specification # 15-TMSS-01,
Rev.0 with the following conditions:
A)
Type tests conducted in presence of SEC Engineers on
132kV-10.9KN (Drawing # 124-11740-132-101), 230kV-10.3KN
(Drawing # 124-11850-132-101) and 380kV-12KN (Drawing #
124-11860-132-101 & 124-11870-132-801) Insulators.

B)
Any new type of Insulators (other than the types which
are mentioned in A) offered by PPC shall Type Tested in
presence of three (3) SEC Engineers and one (1) Approved
Independent Agency Inspector.
C) Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
SIEMENS

GERMANY

Yes

W.S.I

INDIA

Yes

(On HOLD)

Approved Only Up To 132 KV Only

21. 1. 2

21. 1. 3

OHL PORCELAIN INSULATOR UP TO 380 KV

Applicable Standards:

CERAMTEC

GERMANY-N/A

Yes

DIELVE

ITALY

Yes

LAPP

GERMANY-ROSENTHAL

Yes

NGK

JAPAN

Yes

SIEMENS

GERMANY

Yes

LONG ROD PORCELAIN INSULATORS UP TO 380 KV

Applicable Standards:

LAPP

GERMANY-ROSENTHAL

Yes

NGK

JAPAN

Yes

Total =

Total =

15-TMSS-02,15-TMSS-03

15-TMSS-04

Page 100 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PPC INSULATORS (ELEKTROKERAMIK
SONNEBERG)

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC
Insulators (ELEKTROKERAMIK SONNEBERG, Germany) Letter #
Nil dated 4th July 2010, it is pre-qualified for Long Rod Porcelain
Insulators up to 380kV as confirming to SEC specification #
15-TMSS-04, Rev.01 with the following conditions:
A)
Type tests conducted in presence of SEC Engineers on
160KN:LG75/18+17/1450 (Drawing # 11134-339900-B) and
330KN: LG105/18+17/1545 (Drawing # 11134-621400-A)
Insulators.
B)
Any new type of Insulators (other than the types which
are mentioned in A) offered by PPC shall Type Tested in
presence of three (3) SEC Engineers and one (1) Approved
Independent Agency Inspector.
C)
Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.

SIEMENS

GERMANY

Yes
Total =

21

.2

21. 2. 0

OHL GLASS INSULATOR UP TO 380KV


OHL GLASS INSULATOR UP TO 380KV

Applicable Standards:

15-TMSS-02

SEDIVER

BRAZIL--

Yes

COMPLETE SAMPLE, TYPE & ROUTINE TESTS FOR THE FIRST


ORDER IS REQUIRED.

SEDIVER

ITALY

Yes

Complete Sample, Type & Routine Tests for the first order is
required.

Page 101 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SGD LA GRANJA VIDRIERIA, S.L.

FACTORY LOCATION
SPAIN-Segovia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07206-01-30504401 dated
November 09, 2013, it is pre-qualified for Glass Insulator as
conforming to National Grid SA specification # 15-TMSS-02 ,
Rev.01, with the following conditions:
Fresh type tests shall be conducted on each type of
Insulators per clause 5.1 of 15-TMSS-02 Rve.01 and relevant
international standards in the presence of three (03)
SEC/National Grid SA engineers and one (01) SEC/National Grid
SA approved independent inspection agency (IIA) Inspector in
an Independent laboratory and all cost pertaining to these
tests shall be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nil dated
November 08, 2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated November 08, 2012.
Total =

21

.3

21. 3. 1

OHL COMPOSITE INSULATORS


OHL COMPOSITE INSULATORS UP TO 230KV

Applicable Standards:

E.B.REBOSIO S.r.L

ITALY

Yes

FCI (FURUKAWA COMPOSITE INSULATORS


LTD)

HUNGARY-BUDAPEST

Yes

LAPP

GERMANY-ROSENTHAL

Yes

MACLEAN POWER SYSTEM

United States-ILLINOIS

Yes

NGK LOCKE INC.

United States

Yes

15-TMSS-05
Up To 132 kV only. Complete Type, Routine / Sample tests for
first order & 10 Years Warranty from the date of PAC is
required.

Page 102 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PFISTERER SEFAG AG

FACTORY LOCATION
SWITZERLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
It is pre-qualified for Composite Suspension & Tension insulators
up to 380 kV, Composite Line Post insulators up to 132 kV per
SEC Specification 15-TMSS-05, Rev.0 with the following
conditions based on TS&SD letter# 10-02374-03032301 dated
August 18, 2010:
A) Type Tests have been conducted in presence of SEC
Engineers on:
110KV, 120KN (Drawing # 138 206 -393A) and 160KN
(Drawing # 138 206 -667A) at 40 kA.
380KV, 160KN (Drawing # 138 206 -588BC) at 50kA.
However, the manufacturer shall perform the Power Arc Test
only at 63kA.
B) Any new type of Insulators (other than the types which are
mentioned in A) offered by PFISTERRER SEFAG AG
Switzerland shall be Type Tested in presence of three (3) SEC
Engineers and one (1) Approved Independent Agency
Inspector.
C) Ten (10) years warranty from the date of PAC.

XIANGFAN GUOWANG

CHINA--

Yes

MOLDED DESIGN ONLY; UPTO 132KV ONLY; ALL THE


TYPE/SPECIAL / ROUTINE TESTS TO BE CARRIED OUT FOR
FIRST CONTRACT/PROJECT AT SEC APPROVED INDEPENDENT
LAB IN PRESENCE OF 3 SEC ENGRS & A THIRD PARTY
INSPECTOR APPROVED BY SEC; 10 YEARS EXTENDED
WARRANTY
Total =

21. 3. 2

OHL COMPOSITE INSULATORS UP TO 380KV

Applicable Standards:

15-TMSS-05

LAPP

GERMANY-ROSENTHAL

Yes

FIRST BATCH OF EVERY NEW TYPE OF 380KV INSULATOR TO


BE TYPE TESTED IN PRESENCE OF 3 SEC ENGINEERS AND ONE
SEC APPROVED INDEPENDENT INSPECTOR; EXTENDED
WARRANTY OF 10 YEARS

MACLEAN POWER SYSTEM

United States-ILLINOIS

Yes

*All type/design & special tests were performed for first batch
at Independent lab. in presence of SEC/IIA Inspectorbased on
TS&SD fax#09-F00306-030323001 dated 17/02/2009.
-Extended 10(ten) year guarantee/warranty is required.

Page 103 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
NGK LOCKE

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-F02356/02-03032301 dated
22/11/2010, it is pre-qualified for 380kV Composite Insulators
with the following conditions:

Manufacturer shall conduct/repeat the following tests on


the 380kV Composite Insulators 160kN, Cat.# 402-SL1370-SK95 using test series X (Note: Type tests using test series Y on
the 380kV Composite Insulators,160kN , Cat.# 402-SL1370-SK95 have already been conducted satisfactory by the
manufacturer in the presence of SEC engineers).
1.
Power Arc Test (by using test series X) as per IEC 61467.
2.
High Pressure Water Withstand Test followed by Electrical
Test and Verification of the Specified Mechanical Load (SML) as
per IEC 61109

Any new type of composite insulator (other than type Cat.


# 402-SL1370-SK-95) offered by NGK Locke Polymer Insulators
Inc.(USA) shall be subjected to all type, special ,sample and
routine tests as per SEC standards specifications in the
presence of three (03) SEC engineers & one (01) SEC approved
independent inspection agency(IIA) Inspector.

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

PFISTERER SEFAG AG

SWITZERLAND

Yes

It is pre-qualified for Composite Suspension & Tension insulators


up to 380 kV, Composite Line Post insulators up to 132 kV per
SEC Specification 15-TMSS-05, Rev.0 with the following
conditions based on TS&SD letter# 10-02374-03032301 dated
August 18, 2010:
A) Type Tests have been conducted in presence of SEC
Engineers on:
110KV, 120KN (Drawing # 138 206 -393A) and 160KN
(Drawing # 138 206 -667A) at 40 kA.
380KV, 160KN (Drawing # 138 206 -588BC) at 50kA.
However, the manufacturer shall perform the Power Arc Test
only at 63kA.
B) Any new type of Insulators (other than the types which are
mentioned in A) offered by PFISTERRER SEFAG AG
Switzerland shall be Type Tested in presence of three (3) SEC
Engineers and one (1) Approved Independent Agency
Inspector.
C) Ten (10) years warranty from the date of PAC.
Total =

Page 104 of 244

SER

21

.4

21. 4

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

RTV Silicone Rubber Insulator Coating


RTV Silicone Rubber Insulator Coating

Applicable Standards:
CSL Silicones Inc.

CANADA-Guelph Ontario

Yes

15-TMSS-07
Based on S&SD letter# 15-06643-01-30504401 dated August
26, 2015, it is pre-qualified for RTV Silicone Rubber Insulator
Coating Material Si-Coat 570hs as conforming to National Grid
SA specification # 15-TMSS-07, with the following conditions:
First batch of RTV Silicone Rubber Insulator Coating Material
Si-Coat 570hs to be supplied to SEC/National Grid SA shall be
type / design tested as per National Grid SA Specification #
15-TMSS-07, Rev.0 and relevant International Standards in the
presence of three (3) SEC Engineers & one (1) SEC approved
IIA Inspector as confirmed by the manufacturer through letter
# Nil dated 05-08-2015.
Ten (10) years extended Warranty for the proposed RTV
Silicone Rubber Insulator Coating Material Si-Coat 570hs in
respect of the defects due to design, manufacturing and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the project (in case of contract award) and
from the date of delivery for the direct material supply order
shall be provided as confirmed through the manufacturer letter
# Nil dated 05-08-2015.

Dow Corning Corporation

United States-Auburn

Yes

Based on S&SD letter # 14-04590-02-30504401, dated 16th


September 2014, it is prequalified for RTV Silicone Rubber
Insulator Coating Material Xiameter ECE Sylgard HVIC as
conforming to National Grid SA Material Specification
15-TMSS-07,Rev.0 with the following conditions:
All Fresh type/design & special tests shall be conducted as per
National Grid SA Specification 15-TMSS-07, Rev.0 & relevant
International Standards on the first batch to be supplied to
National Grid SA in the presence of three (3) National Grid SA
engineers & one (1) approved Independent Inspection Agency
(IIA) inspector, as confirmed by the manufacturer through
letter # Nil dated 20-07-2014.
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award and date of
delivery in case of direct material supply order, as confirmed by
the manufacturer through letter # Nil dated March 2014.
Total =

22
22

.1

LINE INSULATOR HARDWARE FITTINGS

HARDWARE FITTINGS

Page 105 of 244

SER

22. 1. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

HARDWARE FITTINGS

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
A SALVI & C SPA

ITALY-MILANO

Yes

ALCOA

United States

Yes

CAROBENI

ITALY

Yes

DALEKOVOD PROIZVODNJA

Croatia/Hrvatska-Zagreb

Yes

REMARKS

12-TMSS-01

Based on TS&SD fax # 10-01179-03032301 dated April 20,


2010, this manufacturer is pre-qualified for Line Hardware
except Spacer Dampers per 12-TMSS-01, Rev.0 with the
following conditions:
Each new design of hardware which has NOT been type
tested/supplied to SEC before, shall be type tested as per
12-TMSS-01.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
Previously DALEKOVOD Croatia.[The name has been changed
based on S&SD/P&SFD letter # 12-01292-30504401 dated April
10, 2012]

DAMP

ITALY

Yes

DERVAUX

FRANCE

Yes

Previously "SM-CI-France", the name has been change to


DERVAUX-France based on DERVAUX-France letter # Nil dated
13/10/2009.

Hubbell Power Systems, Inc.

United States-Columbia

Yes

Previously A B CHANCE [The name has been changed based on


S&SD/P&SFD letter# 14-010193-30504401 dated January 06,
2015 and based on Hubbell Power System Grid Letter # Nil
dated December 18, 2014]

INDUSTRIAS ARRUTI

SPAIN

Yes

ISELFA

ITALY

Yes

JOSLYN

United States

Yes

MOSDORFER GMBH

AUSTRIA-WEIZ

Yes

On Hold

Page 106 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Nuova Elettromeccanica Sud S.p.A

FACTORY LOCATION
ITALY-Campo Calabro

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-06603-030504401 dated August 13,
2015 it is pre-qualified for Hardware Fittings, as conforming to
National Grid SA specifications # 12-TMSS-01 with the following
condition:
Manufacturer through Letter # Nil dated 14.11.2014 has
confirmed in writing to conduct the type test during
prequalification. Accordingly, some of the type tests as
mutually agreed between SEC/National Grid SA and NES were
conducted and witnessed by SEC/National Grid SA Engineers
during plant survey visit. However, all other type tests shall be
conducted on the First batch supply of Hardware Fittings to
SEC/National Grid SA, at an independent laboratory in the
presence of three (3) SEC/National Grid SA engineers and one
(1) approved IIA (Independent Inspection Agency) inspector as
confirmed by the manufacturer vide their letter no. nil dated
14/11/2014.
Each new design of Hardware Fittings which has not been
tested, shall be type tested as per latest revision of
12-TMSS-01.
Ten (10) years Extended Warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order shall be
applicable for the Line Hardware to be supplied to SEC/National
Grid SA, as confirmed through letter # Nil dated 14.11.2014.

PFISTERER

SWITZERLAND

Yes

PREVIOUSLY SEFAG AG

PFISTERER

SWEDEN

Yes

PREVIOUSLY SEFAG

PREFORMED LINE PRODUCTS (PLP)

United States

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-ADANA

Yes

Based on S&SD letter# 14-09052-01-30504401 dated 11th


December 2014, this manufacturer is pre-qualified for Line
Hardware (up to 380kV) and Twin Spacer Dampers (up to
132kV) conforming to Company Specifications 12-TMSS-01
Rev.01 with the following conditions:
Type tests (Corona/RIV, Power Arc & Tensile Strength) were
performed on insulator strings for quad bundle with ACAR
conductor and twin bundle with ACSR/AW conductors at VEIKEI
VNL Ltd. Budapest, Hungary during Dec. 2012 & April 2013.
Each new design of Line Hardware which has not been type
tested, shall be type tested as per latest revision of
12-TMSS-01.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.

Page 107 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SICAMEX

22

.2

22. 2. 0

23
23

.1

23. 1. 0

FACTORY LOCATION
FRANCE-FEUGEROLLE & POMPADOUR

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

17

Total =

OBSTRUCTION MARKERS AND CONDUCTOR LIGHTING


OBSTRUCTION MARKERS AND CONDUCTOR LIGHTING

Applicable Standards:

BP SOLAR ARABIA LTD

Saudi Arabia

Yes

DERVAUX

FRANCE

Yes

OBSTA

FRANCE

Yes

P&R TECHNOLOGIES

United States

Yes

PFISTERER SEFAG

SWITZERLAND

Yes

SHIN SEONG IND CORP.

KOREA, Republic of

Yes

SM-CI

FRANCE--

Yes

TANA WIRE MARKER

United States

Yes

12-TMSS-03

PREVIOUSLY SEFAG AG

PREVIOUSLY AS FCI(SAAE), FRANCE.

LINE SUPPORT STRUCTURE

SUBSTATION STEEL STRUCTURE (LATTICED)


SUBSTATION STEEL STRUCTURE (LATTICED)

AL BABTAIN

Applicable Standards:
Saudi Arabia-RIYADH

20-TMSS-01

Yes

Page 108 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Al Yamamah Electric Powers Factory

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-03472-03032301 dated
09/01/2011, it is pre-qualified for Substation Steel Structure
(Latticed) up to 132kV as confirming to SEC specification #
20-TMSS-01, Rev.0 with the following conditions:

Any Substation Steel Structure (Latticed) of new design


proposed by Al-Yamamah Electric Power Towers Factory,
Jeddah (except for the pervious approved design and
drawings provided by SEC to the manufacturer) shall be
subjected to full-scale loading tests and other type, routine and
special tests as per SEC standards specifications and relevant
International Standards in the presence of three (03) SEC
engineers & one (01) SEC approved independent inspection
agency (IIA) Inspector and all cost pertaining to the tests shall
be borne by the manufacturer.

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed in writing by Al-Yamamah Electric Power Towers
Factory, Jeddah through letter # Nil dated 21st October 2009.

AL ZAMIL STEEL

Saudi Arabia-DAMMAM

Yes

AL-BABTAIN POWER&TELECOM CO.

EGYPT-N/A

Yes

FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE


TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.

Alfanar Steel

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter# 08-1058/1-03032301 dated 25th May


2009 it is pre-qualified for Transmission Towers for projects up
to 132kV, Substation & Gantry Steel Structures up to 380kV and
Communications Tower for transmission sector as confirming to
SEC specification # 20-TMSS-01, rev.0 with the following
conditions:

All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in the manufacturer's testing laboratory in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

Page 109 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Energya Steel Solution (Hesham Helal El
Sewedy & Partners for Steel Industries Co.)

FACTORY LOCATION
Saudi Arabia-Rabigh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter# 09-2179/07-03032301 dated
November 11, 2009, approval of Executive Directive for TS&SD
letter# 09-02179/06-03032301 dated November 11, 2009 &
based on S&SD letter# 13-01978/01-30504401 dated June 10,
2013, it is pre-qualified for Substation Steel Structures up to
380kV as conforming to National Grid SA specification #
20-TMSS-01, Rev.01 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order.

GEYARD FOR COMMERCE AND IMPORT CO.

Saudi Arabia-AL KHOBAR

Yes

HIDADA

Saudi Arabia-JEDDAH

Yes

KEC INTERNATIONAL LTD.

INDIA--

Yes

LARSEN & TOUBRO LTD.

INDIA-CHENNAI

Yes

NAJEM

Saudi Arabia

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Polath/ANKARA & ADANA

Yes

NAGPUR-BUTIPORI, JABALPUR, JAIPUR PLANTS ARE


ACCEPTABLE; ALL THE TESTS SHALL BE CARRIED OUT FOR
FIRST CONTRACT/PROJECT IN PRESENCE OF THREE (3) SEC
ENGINEERS; 10 YEARS OF EXTENDED WARRANTY.

Based on S&SD letter# 14-09052-01-30504401 dated 11th


December 2014, this manufacturer is pre-qualified for
Substation Steel Structures up to 380kV conforming to
Company Specifications 20-TMSS-01 Rev.01 with the following
condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
Total =

23

.2

23. 2. 0

13

T/L STEEL STRUCTURE (LATTICED) UP TO 380 KV


T/L STEEL STRUCTURE (LATTICED) UP TO 380 KV

AL BABTAIN

Applicable Standards:
Saudi Arabia-RIYADH

20-TMSS-01

Yes

Page 110 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Al Yamamah Electric Powers Factory

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 13-05834-30504401-01 dated
September 29, 2013 and letter # 12-0054-30504401 dated
January 10, 2012 Al-Yamamah Electric Power Towers Factory,
Jeddah is prequalified for Transmission Line Structures up to
380 kV as conforming to National Grid SA Specification #
20-TMSS-01, Rev.0 with the following conditions:
Any new transmission Line Structure (Latticed) designed by
Al-Yamamah Electric Power Towers Factory, Jeddah (except
other than previous approved design and drawings provided by
SEC/National Grid SA to the manufacturer) shall be subjected to
full scale loading tests and other type, routine & special tests as
per SEC/National Grid SA Standards Specifications and relevant
International Standards in the presence of three (03)
SEC/National Grid SA engineers and one (01) SEC/National Grid
SA approved independent inspection agency (IIA) Inspector
and all cost pertaining to these tests shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated January 07,
2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated October 21, 2009 and letter # Nil dated January 07,
2012.

AL ZAMIL STEEL

Saudi Arabia-DAMMAM

Yes

AL-BABTAIN POWER&TELECOM CO.

EGYPT-N/A

Yes

FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE


TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.

Alfanar Steel

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter# 08-1058/1-03032301 dated 25th May


2009 it is pre-qualified for Transmission Towers for projects up
to 132kV, Substation & Gantry Steel Structures up to 380kV and
Communications Tower for transmission sector as confirming to
SEC specification # 20-TMSS-01, rev.0 with the following
conditions:

All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in the manufacturer's testing laboratory in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

AL-SALAM INSDUTRIES AND TRADING


EST./ADVANCE TECHNOLOGIES.

Saudi Arabia-JEDDAH

Yes

ONE TRIAL PROJECT FOR 110/132 KV SHORT LINE.

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

Page 111 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Energya Steel Solution (Hesham Helal El
Sewedy & Partners for Steel Industries Co.)

FACTORY LOCATION
Saudi Arabia-Rabigh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter# 09-2179/07-03032301 dated
November 11, 2009 & based on S&SD letter#
13-01978/01-30504401 dated June 10, 2013, it is pre-qualified
for Transmission Line Steel Structures and Communication
Towers as conforming to National Grid SA specification #
20-TMSS-01, Rev.01 with the following conditions:
The approval will be initially restricted to the following items
only:
1. Transmission Towers for projects up to 132kV
2. Communication Towers for Transmission Sector
Any Transmission Line Structure (Latticed) of new design
proposed by ENERGYA Steel Solutions, Rabigh (except for the
pervious approved design and drawings provided by SEC/
National Grid SA to the manufacturer) shall be subjected to
full-scale loading tests and other type, routine and special tests
as per National Grid SA standards specifications and relevant
International Standards in the presence of three (3)
SEC/National Grid SA engineers & one (1) National Grid SA
approved independent inspection agency (IIA) Inspector and all
cost pertaining to the tests shall be borne by the manufacturer.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order.

HIDADA

Saudi Arabia-JEDDAH

Yes

KALPATARU Power Transmission Ltd.

INDIA-Gujarat

Yes

Based on TS&SD letter 09-00665/1-03032301 dated 16th.


March 2009 for Galvanised Transmission line Lattice Steel Tower
up to 380kV as conforming to SEC specifications # 20-TMSS-01,
rev.0; with the following conditions:

Ten (10) years extended warranty.

Improvement needs indicated in the plant survey report.

All the tests shall be carried out for first contract/project in


presence of three (3) sec engineers & independent Inspector.

KEC INTERNATIONAL LTD.

INDIA--

Yes

Only NAGPUR-BUTIPORI, JABALPUR & JAIPUR Plants are


acceptable.
Any new transmission line structure designed by KEC, India
shall be subjected to full-scale loading tests and other
type/routine/sample tests per SEC specifications in the
presence of three (3) SEC engineers and one (1) SEC approved
Independent Inspection Agency (IIA) inspector and all costs
pertaining to tests shall be borne by the manufacturer.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
delivery in case of first direct material supply order.

Page 112 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

LARSEN & TOUBRO LTD.

INDIA-CHENNAI

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Polath/ANKARA & ADANA

Yes

REMARKS

Based on S&SD letter# 14-09052-01-30504401 dated 11th


December 2014, this manufacturer is pre-qualified for T/L Steel
Structures up to 380kV conforming to Company Specifications
20-TMSS-01 Rev.01 with the following conditions:
Each new design of transmission steel structure to be supplied
by SA-RA Energy, Construction, Trade and Industry Co. Inc.
shall be subjected to full scale loading test if specified in the
SOW/TS.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
Total =

23

.3

23. 3. 0

13

STEEL POLES, TUBULAR UP TO 230 KV


STEEL POLES, TUBULAR UP TO 230 KV

Applicable Standards:
AL BABTAIN

Saudi Arabia-RIYADH

Yes

Energya Steel Solution (Hesham Helal El


Sewedy & Partners for Steel Industries Co.)

Saudi Arabia-Rabigh

Yes

20-TMSS-02

Based on TS&SD Letter # 10-0331/06-03032301 dated


28/06/2010, it is pre-qualified for Steel Poles, Tubular up to
230kV as confirming to SEC specification # 20-TMSS-02. Rev.0
with the following conditions:

All Type, Routine and Special Tests including the load test
per SEC specification # 20-TMSS-02 and all relevant
International Standards shall be conducted on the first batch in
presence of three (3) SEC Engineers and one (1) SEC approved
independent inspection agency (IIA) Inspector and related cost
pertaining to the test shall be borne by Hesham Helal EL
Sewedy & Partners for Steel Industries Co.(Energya Steel
Solutions) as confirmed by manufacturer through letter #
SEC/WK/100524 dated 24th May 2010.

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order as confirmed by
Hesham Helal EL Sewedy & Partners for Steel Industries Co.
(Energya Steel Solutions) letter # SEC/WK/100524 dated 24th
May 2010 .
HIDADA

Saudi Arabia-JEDDAH

Yes

PETIT JEAN

FRANCE

Yes

Page 113 of 244

METERIAL / EQUIPMENT
DESCRIPTION

SER

23

.5

23. 5. 1

23. 5. 2

24
24

.0

24. 0. 0

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

SUMMIT MANUFACTURING

United States-PA

Yes

TECHNOPALI

ITALY

Yes

VALMONT

United States

Yes

REMARKS

Total =

Total =

Total =

WOOD POLES
WOOD POLES, ANSI CLASS HI H 3

Applicable Standards:
ATLANTIC WOOD IND.

United States-GEORGIA

Yes

CAHABA PRESSURE TREATED FOREST


PRODUCT (NORTH PACIFIC GROUP)

United States-ALABAMA

Yes

COLFAX CREOSOTING CO

United States-LOUISIANA

Yes

KOPPERS INDUSTRIES

United States-PA

Yes

STALLWORTH TIMBER

United States-ALABAMA

Yes

STELLA JONES INC.

CANADA-NEW WESTMINSTER

Yes

TAYLOR LUMBER (NORTH PACIFIC GROUP)

United States-OREGON

Yes

WOOD POLES, ANSI CLASS I - 4

Applicable Standards:
ATLANTIC WOOD IND.

United States-GEORGIA

Yes

CAHABA PRESSURE TREATED FOREST


PRODUCT (NORTH PACIFIC GROUP)

United States-ALABAMA

Yes

COLFAX CREOSOTING CO

United States-LOUISIANA

Yes

KOPPERS INDUSTRIES

United States-PA

Yes

STALLWORTH TIMBER

United States-ALABAMA

Yes

STELLA JONES INC.

CANADA-NEW WESTMINSTER

Yes

TAYLOR LUMBER (NORTH PACIFIC GROUP)

United States-OREGON

Yes

GALVANIZED GUY WIRE (GROUNDING)

.
GALVANIZED GUY WIRE (GROUNDING)

Applicable Standards:

10-TMSS-02

Page 114 of 244

SER

25
25

.1

25. 1. 0

25

.2

25. 2. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

FLORIDA WIRE & CABLE

United States

Yes

JOSLYN

United States

Yes

SOUTHWIRE

United States

Yes

TREFILEUROPE

FRANCE

Yes

REMARKS

Total =

Total =

RACEWAYS

METAL ENCLOSED BUS DUCT, 4.16 13.8 KV OR 34.5 KV


METAL ENCLOSED BUS DUCT, 4.16 13.8 KV OR 34.5 KV

Applicable Standards:

ABB ( T& D)

United States-N/A

Yes

UNIBUS

United States

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

CABLE TRAY SYSTEMS


CABLE TRAY SYSTEMS

Applicable Standards:
3M

United States-Minnesota

Yes

AB WIRE

SWEDEN-sweden

Yes

ABAHSAIN-COPE

Saudi Arabia- DHAHRAN

Yes

AL-AMAL CO.

Saudi Arabia-RIYADH

Yes

24-TMSS-01

FOR LADDERS & ACCESSORIES ALSO; 10 YEARS OF EXTENDED


WARRANTY;

Page 115 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALASHHOURY INDUSTRY

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-0036/04-03032301 dated
06/06/2011, it's prequalified for Cable Trays & Cable Ladders as
conforming to SEC Specification # 24-TMSS-01, Rev.0 with the
following conditions:

Ten (10) years extended warranty from the date of PAC


of the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by Al-Ashouri Industries through letter # 2010/403/0003 dated 01/08/2010.

For any new design of Cable Trays or Cable Ladders


proposed by Al-Ashouri Industries (other than the test proven
SEC designs), Type, Special, routine and Sample test as per the
SEC standards/Specification shall be conduct on the first batch
to be supplied to SEC in presence of three (03) SEC Engineers
in an SEC approved independent test laboratory.

AL-MISBAH House for Steel Works

Saudi Arabia-Riyadh

Yes

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

EFCOR

United States

Yes

ELECTROLINK Co. Ltd.

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter 09-00509/1-03032301 dated 16th.


March 2009 for Metallic Cable Tray Systems as conforming to
SEC specifications # 24-TMSS-01, rev.0; with the following
conditions:

Ten (10) years extended warranty.

Improvement needs indicated in the plant survey report

based on TS&SD letter 09-00524/1-03032301 dated 16th.


March 2009 for Metallic Cable Tray Systems as conforming to
SEC specifications # 24-TMSS-01, rev.0; with the following
conditions:

Eight (8) years extended warranty.

Improvement needs indicated in the plant survey report.

Page 116 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Fas Al-Jazeera

FACTORY LOCATION
Saudi Arabia-Dammam

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-00242/01-30504401 dated March
19 2015, the manufacturer is prequalified for Cable trays,
Cable Ladders and Accessories as conforming to National Grid
SA specification # 24-TMSS-01, Rev.01 with the following
conditions:
1. For new designs of cable trays or cable ladders proposed by
FAS Al Jazeera (other than the test proven SEC/National Grid
SA designs), All type, special, routine tests shall be conducted
on the first batch to be supplied to SEC/National Grid SA, in the
presence of three (3) SEC/National Grid SA engineers at
SEC/National Grid SA approved independent testing laboratory.
2. Ten (10) years extended warranty shall be provided from
the date of the Provisional Acceptance Certificate (PAC) of the
first turnkey project (in case of contract award) and from the
date of first delivery in case of direct material supply order. This
was confirmed by FAS Al Jazeera United Factory Co. through
their letter# NIL dated: 2nd December, 2012G.

HIDADA

Saudi Arabia-JEDDAH

Yes

MECSS - MID EAST CABLE SUPPORT


SOLUTIONS

Saudi Arabia- AL-KHOBAR

Yes

O-Z GEDNEY

United States

Yes

SAUDI ELECTRIC INDUSTRIES CO. LTD.

Saudi Arabia-JEDDAH

Yes

Specialized Factory for Steel Products (SFSP)

Saudi Arabia-Jeddah

Yes

Based on S&SD Letter # 15-01409-01-30504401, dated 18th


March 2015 the manufacturer is prequalified for Cable trays,
Cable Ladders and Accessories as conforming to National Grid
SA Material Specification 24-TMSS-01, Rev. 01, with the
following conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order, as
confirmed by Specialized Factory for Steel Products (SFSP)
through letter # Nil, dated 15th January 2013.
For any new design of cable trays or cable ladders proposed
by Specialized Factory for Steel Products (SFSP) (other than
the test proven SEC/National Grid SA designs), Type, Special,
routine and Sample test as per the SEC/ National Grid SA
standards/ Specification shall be conducted on the first batch to
be supplied to SEC/ National Grid SA in presence of three (03)
SEC/ National Grid SA Engineers in an SEC National Grid SA
approved independent test laboratory.

TOLARTOIS

FRANCE

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

Page 117 of 244

SER

26
26

.1

26. 1. 0

27
27

.1

27. 1. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

17

Total =

CONDUIT FITTINGS

DUCT SEALING UNITS


DUCT SEALING UNITS

Applicable Standards:
AMIANTIT RUBBER IND. (ARIL)

Saudi Arabia-DAMMAM

Yes

UM- AL QUWAIN RUBBER INDUSTRIES

United Arab Emirates

Yes

23-TMSS-02

SWITCHES

DISCONNECT SWITCH, AIR BREAK, UP TO 380 KV


DISCONNECT SWITCH, AIR BREAK, UP TO 380 KV

Applicable Standards:

ABB ( T& D)

United States-N/A

Yes

ALPHA NIDAU

SWITZERLAND

Yes

Alstom Grid S. p .A

ITALY-Venice - Noventa di Piave

Yes

30-TMSS-01

Based on S&SD letter# 13-04035-02-30504401 dated July 22,


2013, it is pre-qualified for Disconnect Switches 420kV, 4000A
(S3CD, S3CDT & S3CD2T) only and Standalone Grounding
Switches (STB) 420kV, 63kA only as conforming to National Grid
SA specification # 30-TMSS-01, Rev.0, with the following
conditions:

All type/special and routine tests for Disconnect Switches


420kV, 4000A (S3CD, S3CDT & S3CD2T) only and Standalone
Grounding Switches (STB) 420kV, 63kA only shall be conducted
at in an Independent testing laboratory on one switch before
supplied to SEC system in the presence of three (3)
SEC/National Grid SA engineers & one (1) National Grid SA
approved independent inspection agency Inspector, all the
related costs for witnessing the tests will be borne by the
manufacturer. This was confirmed by Alstom Grid S. p .A,
ITALY through their letter # 323/11/C/RP.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by Alstom Grid S. p .A, ITALY through their
letter # 136/11/CO/RP.

Page 118 of 244

SER

27

.2

27. 2. 0

27

.3

27. 3. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

28

.1

28. 1. 0

Pre-Qualified
Manufacturers
By SEC

REMARKS

AREVA

FRANCE

Yes

EFACEC

PORTUGAL

Yes

HAPAM

NETHERLANDS

Yes

SUSPENDED based on TS&SD letter 10-00402-03032301 dated


February 08, 2010

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

MG/EGIC

FRANCE

Yes

S&C

United States

Yes

SDCEM

FRANCE

Yes

SIEMENS

GERMANY

Yes

SOUTHERN STATES

United States

Yes

SOUTHERN STATES/ USA HAS ACQUIRED SIEMENS SWITCH


FACTORY
Total =

12

Total =

Total =

LV AUTO-TRANSFER SWITCH
LV AUTO-TRANSFER SWITCH

Applicable Standards:
ALSTOM

FRANCE

Yes

ASCO

United Arab Emirates

Yes

WESTINGHOUSE

United States

Yes

PAD MOUNTED SF6/OIL SWITCH, 34.5 KV


PAD MOUNTED SF6/OIL SWITCH, 34.5 KV

Applicable Standards:
FRITZ DRIESHER KG

28

FACTORY LOCATION

GERMANY

Yes

LV PANELS & ENCLOSURES

RELAY & CONTROL PANEL


RELAY & CONTROL PANEL

Applicable Standards:
ABB

SWEDEN

31-TMSS-01

Yes

Page 119 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ABB/AEIL

Saudi Arabia

Yes

ACRASTYLE

United Kingdom

Yes

AEL -SIEMENS

Saudi Arabia-JEDDAH

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-01251-03032301 dated 03rd. May


2009 UP TO 380KV as confirming to SEC specification #
31-TMSS-01, rev.0 with Ten (10) years warranty from the date
of PAC of the Turnkey project in case of contract award or
date of delivery in case of direct material supply order.

Alstom Grid Integration & Testing Facility

Saudi Arabia-Alkhobar

Yes

Based on S&SD letter # 14-04579-2-030504401, dated


30/06/2014, it is prequalified for Integration & Testing of Relay
& Control Panels confirming to National Grid SA Material
Specification 31-TMSS-01, Rev.0, with the following conditions: Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order, as
confirmed through Alstom Grid letter No. nil, dated 03/10/2013.

AREVA

United Kingdom

Yes

CRUINKSHANK & PARTNERS LTD.

United Kingdom

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

ETA-PCS

United Arab Emirates-DUBAI

Yes

It is pre-qualified for Relay & Control Panels as conforming to


SEC specification # 31-TMSS-01, Rev.0 with the following
condition:

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

Up to 132kV only.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
delivery in case of first direct material supply order.

Koncar Elektricni Uredaji d.d

CROATIA-Dicmo

Yes

Based on S&SD letter# 14-1456-03-30504401 dated April 15,


2014, it is pre-qualified for Relay & Control Panel up to 380 kV
as conforming to National Grid SA specification # 31-TMSS-01,
Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
nil dated March 09, 2012.

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

Page 120 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
MEMF-ETA Switchgear Manufacturing
Company

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-03789-03-30504401 dated January
28, 2013. It is prequalified for Relay & Control Panel up to
132kV as conforming to National Grid SA specification #
31-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
META/12/AM dated March 23, 2011.

MOHD. AL-OJAIMI LTD.

Saudi Arabia-Riyadh

Yes

Extended warranty for 10 years.

PROTEA/AREVA T&D

FRANCE--

Yes

10 YEAR EXTENDED WARRANTY

REYROLLE LTD.

United Kingdom

Yes

SCHNEIDER H.V FACTORY

FRANCE-GRENOBLE

Yes

SIEMENS

GERMANY

Yes

System House Factory for Electric Panels (SEP)

Saudi Arabia-Riyadh

Yes

TIEPCO

Saudi Arabia-DAMMAM

Yes

VA TECH

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-01500-03032301 dated May 25,


2009, 10-01055/02-03032301 dated May 03, 2010 & S&SD
Letter 12-03596-02-30504401 dated April 29, 2012. It is
prequalified for Relay & Control Panel up to 380kV as
conforming to SEC specification # 31-TMSS-01, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated December 11, 2011.

ASSEMBLING UP TO 132KV ONLY, ENCLOSURES SHALL BE


PROCURED FROM MESCO (RIYADH)

Page 121 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
WESCOSA

FACTORY LOCATION
Saudi Arabia-DAMMAM

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-F02715-03032301 dated
17/09/2011, it is prequalified for Relay & Control Panels, 230kV
and above as confirming to SEC specification # 31-TMSS-01,
Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards shall be carried out on the first batch
of Relay & Control Panels to be supplied to SEC, in case of
securing an order, in the presence of three (3) SEC Engineers &
one (1) approved Independent Inspection Agency Inspector in
an Independent Testing Laboratory. All the related costs for
witnessing the tests will be borne by the manufacturer. This
was confirmed by WESCOSA-Dammam through letter # Nil
dated 16/06/2010.
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by WESCOSA-Dammam through letter # Nil dated
05/10/2010.

28

.2

28. 2. 0

Total =

23

Total =

12

ANNUNCIATOR SYSTEM
ANNUNCIATOR SYSTEM

Applicable Standards:
ABB SUBSTATION AUTOMATION OY

FINLAND

Yes

AMETEK POWER INSTRUMENTS

United States

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS

KOREA, Republic of

Yes

NEXANS

SWITZERLAND

Yes

PAN ALARM

United States

Yes

PIRELLI

GERMANY-BERLIN

Yes

RONAN ENGINEERING

United Kingdom

Yes

RTK ENGINEERING LTD.

United Kingdom

Yes

SIEMENS

GERMANY

Yes

STEINER

JAPAN

Yes

38-TMSS-05
SACO 16D3

PREVIOUSLY LG

Page 122 of 244

SER

28

.3

28. 3

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

PARTIAL DISCHARGE MONITORING SYSTEM


PARTIAL DISCHARGE MONITORING SYSTEM

APM TECHNOLOGIES INC

Applicable Standards:
KOREA, Republic of-Seoul

Yes

Based on S&SD letter # 14-08866-2-30504401 dated December


11, 2014, it is pre-qualified for Partial Discharge Monitoring
System (PDMS) APM5000 & APM2000 (Portable) as conforming
to National Grid SA specification # 38-TMSS-07, Rev.0, with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil, dated May 12, 2014.

QUALITROL DMS

Scotland-GLASGOW

Yes

Based on S&SD letter # 15-02752-1-30504401 dated April 15,


2015, the manufacturer is approved to supply PARTIAL
DISCHARGE MONITORING SYSTEM Type PDMG-RH as per
38-TMSS-07, Rev.0 with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # Nil dated January 14th, 2013.
Total =

29
29

.1

29. 1. 0

ARRESTER, SURGE OR LIGHTNING

SURGE ARRESTERS, STATION CLASS UP TO 380 KV


SURGE ARRESTERS, STATION CLASS UP TO 380 KV

Applicable Standards:

35-TMSS-01

Yes
ABB

SWEDEN

Yes

ABB HV TECHNOLOGIES

SWITZERLAND

Yes

AREVA

FRANCE

Yes

BOWTHORPE

United Kingdom

Yes

Page 123 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Eaton

United States-Greenwood (SC state)

Yes

Previously COOPER (MCGRAW-ED), the name has been


changed to Eaton based on S&SD/P&SFD letter # 15-0410730504401 dated May 19, 2015 and COOPER (MCGRAW-ED)
letter # 01110502015 dated May 11, 2015.

ELPRO INTL. LTD

INDIA

Yes

Upto 132 kV Only - Complete Type, Routine / Acceptance tests


for first order & 10 Years Warranty from the date of PAC is
required.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Hubbell Power Systems, Inc.

United States-Columbia

Yes

Previously OHIO BRASS [The name has been changed based on


S&SD/P&SFD letter# 14-07802-30504401 dated October 22,
2014 and based on Hubbell Power System Grid Letter # Nil
dated October 06, 2014]

JAPAN AE POWER SYSTEMS CORP.

JAPAN

Yes

MITSUBISHI

JAPAN--

Yes

SIEMENS

GERMANY

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

TRIDELTA

GERMANY

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Total =

30
30

.1

30. 1. 1

15

CIRCUIT BREAKER

DEADTANK SF6 BREAKER


DEADTANK SF6 BREAKERS, 69 KV

Applicable Standards:

37-TMSS-01

ABB ( T& D)

United States-N/A

Yes

AREVA

United States-CHARLEROI

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

GE-HITACHI HVB

United States-GEORGIA

Yes

Page 124 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

SIEMENS

GERMANY-Berlin

Yes

Based on S&SD Letter 12-2202-01-30504401 dated July 24,


2012, it is pre-qualified for Dead Tank Circuit Breaker type 3AP1
DT 72.5KV & 145KV as conforming to National Grid SA
Specification # 37-TMSS-01, Rev.0 with the following
conditions:
CB type 3AP1 DT 72.5KV & 145KV is not capable for Reactor
and Capacitor bank back to back switching as confirmed by
Siemens through their letter# E T HP CB B SL/MTH dated April
27, 2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
by Siemens through their letter# E T HP CB B SL/MTH, dated
December 18, 2012.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

30. 1. 2

DEADTANK SF6 BREAKERS,110 - 132 KV

Applicable Standards:
ABB

SWITZERLAND

Yes

ABB ( T& D)

United States-N/A

Yes

AREVA T&D Inc.-USA

United States-Charleroi

Yes

37-TMSS-01

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
The old remark before suspension was:
Based on TS&SD letter # 10-02708-02-03032301 dated
25/10/2010, it is pre-qualified for 145kV Dead Tank Circuit
Breaker type DT1-145FK, 40KA, 2000A as confirming to SEC
specification # 37-TMSS-01, Rev.0, with the following
condition:
Ten (10) years extended warranty for the proposed 145kV
Dead Tank Circuit Breaker type DT1-145FK from the date of
PAC of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed in writing by AREVA T&D, Inc-USA through letter #Nil
dated 6th March 2009.

Page 125 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FUJI Electric Co.

JAPAN--

Yes

GE-HITACHI HVB

United States-GEORGIA

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

SIEMENS

GERMANY-Berlin

Yes

Based on S&SD Letter 12-2202-01-30504401 dated July 24,


2012, it is pre-qualified for Dead Tank Circuit Breaker type 3AP1
DT 72.5KV & 145KV as conforming to National Grid SA
Specification # 37-TMSS-01, Rev.0 with the following
conditions:

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

CB type 3AP1 DT 72.5KV & 145KV is not capable for Reactor


and Capacitor bank back to back switching as confirmed by
Siemens through their letter# E T HP CB B SL/MTH dated April
27, 2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
by Siemens through their letter# E T HP CB B SL/MTH dated
December 18, 2012.
SIEMENS

United States

Yes

CB type 3AP1 DT 72.5KV & 145KV is not capable for Reactor


and Capacitor bank back to back switching as confirmed by
Siemens through their letter# E T HP CB B SL/MTH dated April
27, 2012.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.


Total =

30. 1. 3

DEADTANK SF6 BREAKERS, 230 KV

Applicable Standards:
ABB ( T& D)

United States-N/A

Yes

AREVA

United States-CHARLEROI

Yes

10

37-TMSS-01

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
The old remark before suspension was:
Type DT1-245 F3; 10 years of extended warranty; di-electric
test, riv test, continuous current temperature rise test @ 2500
A, 60Hz is to be carried out in the first batch in the presence of
3 SEC engineers and 1 IIA inspector.

Page 126 of 244

SER

30

.2

30. 2. 1

30. 2. 2

30. 2. 3

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FUJI Electric Co.

JAPAN--

Yes

GE-HITACHI HVB

United States-GEORGIA

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.

Originally JAPAN AE POWER SYSTEM CORP and subsequent


change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.

Total =

Total =

Total =

SF6, LIVE TANK


LIVE TANK, 69 KV SF6 BREAKER

Applicable Standards:
ABB

SWEDEN

Yes

ABB

SWITZERLAND

Yes

ABB SWITCHGEAR AB

SWEDEN-LUDUVIKA

Yes

AREVA

SWITZERLAND-OBERENTFELDEN

Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

SIEMENS

GERMANY

Yes

LIVE TANK, 110 - 132 KV SF6 BREAKER

Applicable Standards:
ABB

SWEDEN

Yes

AREVA

GERMANY

Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

SIEMENS

GERMANY

Yes

LIVE TANK, 230 KV SF6 BREAKER

Applicable Standards:
ABB

SWEDEN

Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

37-TMSS-02

37-TMSS-02

37-TMSS-02

Page 127 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

30. 2. 4

31
31

.1

31. 1. 0

31

.2

31. 2. 0

.3

31. 3. 1

GERMANY

CIRCUIT SWITCHER, 69 230 KV

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

Total =

Total =

Total =

Applicable Standards:
S&C

CANADA

Yes

S&C

United States

Yes

SIEMENS

GERMANY

Yes

SUPERVISING EQUIPMENT, TELEMETERING EQUIPMENT

LINE TRAP
LINE TRAP

Applicable Standards:
HAEFELY-TRENCH ELECTRIC

CANADA

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

38-TMSS-01

LINE TUNER
LINE TUNER

Applicable Standards:
ABB HV TECHNOLOGIES

31

FACTORY LOCATION

SWITZERLAND

38-TMSS-02

Yes

CCVT AND/OR COUPLING CAPACITOR CARRIER


CCPD/CCVT, 69KV UP TO 380 KV

Applicable Standards:
ABB

SWEDEN

Yes

ABB HV TECHNOLOGIES

SWITZERLAND

Yes

38-TMSS-08,50-TMSS-02

Page 128 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for CVT Capacitor Voltage
Transformer up to 132 kV only as confirming to SEC
Specification # 50-TMSS-02 Rev.0 with the following
conditions:

All Type, Routine and Special testes shall be carried out on


the first batch of CVT Capacitor Voltage Transformer up to 132
kV only in an Independent Testing Laboratory in the presence
of three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was confirmed
by the manufacturer through their letter # Nil dated April 28,
2011G and October 07, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.
GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

CANADA

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

PASSONI & VILLA

ITALY

Yes

PFIFFNER

SWITZERLAND

Yes

Based on TS&SD letter# 09-01105-03032301 dated 24th June


2009, it is pre-qualified for CT & CVT rated up to 380kV as
confirming to SEC specification # 50-TMSS-01, rev.0 & #
50-TMSS-02, rev.0 respectively with the following conditions:

All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in an independent testing laboratory in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

RITZ

United States

Yes

TYPE TEST REQUIRED IN FIRST SUPPLY

Limited up to 132kV only. All Type, Special, Routine tests per


SEC Standards and IEC to be performed at KONCAR-Electrical
Institute Inc. as independent and accredited testing laboratory.
Extended guarantee/warrenty for 10 years.

Page 129 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TRENCH ITALIA

FACTORY LOCATION
ITALY-N/A

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO)
Total =

31

.4

31. 4. 0

13

REMOTE TERMINAL UNIT (RTU)


REMOTE TERMINAL UNIT (RTU)

Applicable Standards:
ABB

GERMANY

Yes

AREVA

FRANCE

Yes

EFACEC Sistemas de Elctronica, S.A

PORTUGAL-Maia

Yes

38-TMSS-03
RTU-560, SPIDER 200,232 & 233

Based on TS&SD letter# 09-01819-03032301 dated 23rd June


2009, it is prequalified for for RTU type CLP500 as confirming to
SEC specification # 38-TMSS-03, rev.0 with the following
condition:
Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.

FOXBORO

AUSTRALIA

Yes

GE HARRIS

CANADA

Yes

HARRIS D20

Global Energy Technologies Ltd.

United Arab Emirates-Dubai

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
Earlier Condition was:
Ten (10) years extended warranty. Microsol XCell SCADA RTU
System.

HARRIS CORPORATION

United States-MELBOURNE, FLORIDA

Yes

HARRIS MICROPLEX 5000

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

ASSEMBLING ONLY

LSIS

KOREA, Republic of--

Yes

SEVEN (7) YEARS EXTENDED WARRANTY.

MICROSOL LTD.

Ireland-DUBLIN

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.

SAT

AUSTRIA

Yes

SIEMENS

GERMANY

Yes

SIEMENS (LANDYS) - TELEGYR

United States-SAN JOSE, CA

Yes

VA TECH

AUSTRIA

Yes

TELEGYR 5700

Total =

31

.5

14

SEQUENCE OF EVENTS RECORDER

Page 130 of 244

SER

31. 5. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

SEQUENCE OF EVENTS RECORDER

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

REMARKS

38-TMSS-04

ABB

GERMANY

Yes

RTU 560

GE HARRIS

CANADA

Yes

HARRIS D20

Global Energy Technologies Ltd.

United Arab Emirates-Dubai

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
Earlier Condition was:
Ten (10) years extended warranty. Microsol XCell SCADA RTU
System

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

SOE RECORDING SYSTEM AND INTERFACE & CONTROL


CABINET/MARSHALING PANELS

LSIS

KOREA, Republic of--

Yes

SEVEN (7) YEARS EXTENDED WARRANTY.

MICROSOL LTD.

Ireland-DUBLIN

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.

RONAN ENGINEERING

United States-LOS ANGELES, CA

Yes

X500E/1000
Total =

31

.6

31. 6. 1

31. 6. 2

TRANSDUCERS
FREQUENCY TRANSDUCERS

Applicable Standards:
ALSTOM

United States

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

TAP POSITION TRANSDUCERS

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.
Total =

Total =

Applicable Standards:
AREVA

31. 6. 3

United Kingdom

TRANSDUCERS

Yes

Applicable Standards:
CEWE INSTRUMENTS AB

SWEDEN

Yes

ENERDIS

FRANCE

Yes

Page 131 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

LSIS

KOREA, Republic of--

Yes

TILLQUIST

SWEDEN

Yes

TYCO ELECTRONICS (UK) Ltd - CROMPTON


INSTRUMENTS

United Kingdom--

Yes

REMARKS
SEVEN (7) YEARS EXTENDED WARRANTY.

Based on TS&SD Letters (08-F00975/01-03032301 dated June


04, 2008), (10-F00230/01-03032301 dated February 03, 2010)
& (11-F03017/01-03032301 dated October 16, 2011). Integra
1560 is prequalified for Transducers as confirming to SEC
Specification # 40-TMSS-02, Rev.0 with the following condition:
Five (05) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order. This
was confirmed by TYCO Electronic UK through their letter #
INT-SEC-06 dated January 03, 2008 and its Amendment dated
November 21, 2011.
Total =

31. 6. 4

WATTHOURS/VARHOURS TRANSDUCERS

Applicable Standards:
ISKRA MIS

SLOVENIA-KRANJ

Yes

MITSUBISHI ELECTRIC

JAPAN

Yes

SCIENTIFIC COLUMBUS

United States

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.

Total =
31. 6. 5

VOLTAGE TRANSDUCERS

Applicable Standards:
ABB (ASEA INC.)

CANADA-MONTREAL

Yes

AREVA

United Kingdom

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

TRANSDATA

United States

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.

Total =
31. 6. 6

WATTS/VARS TRANSDUCERS

Applicable Standards:
ABB (ASEA INC.)

CANADA-MONTREAL

Yes

AREVA

United Kingdom

Yes

Page 132 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ISKRA MIS

SLOVENIA-KRANJ

Yes

TRANSDATA

United States

Yes

REMARKS
ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT
EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.

Total =

31

.7

31. 7. 1

PROTECTIVE RELAYS
TRANSMISSION LINE PROTECTIVE RELAYS 380/132/115/110kV

Applicable Standards:

Page 133 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X0-D1
A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIs+12BOs
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X0-D1
A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator

Page 134 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Hardware:
4CT+4VT+12BIs+12BOs
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B6-D1
A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B6-D1
A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N

Page 135 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 136 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom

FACTORY LOCATION
United Kingdom---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P546
Ordering Code:
P54631NH7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIs+12BOs
8CT+4VT+16BIs+16BOs
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS

Relay Type:
MiCOM P546
Ordering Code:
P54631NK7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator

Page 137 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Hardware:
4CT+4VT+12BIs+12BOs
8CT+4VT+16BIs+16BOs
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 138 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE

FACTORY LOCATION
CANADA---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIS+12BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W73(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:

Page 139 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
4CT+4VT+12BIS+12BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W73(*) (*) CH2 to be
attenuated to fit SDH
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision

Page 140 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 141 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P546 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Enclosure Protection per IEC 60259 2001) for MiCOM
P546 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Codes, Built in Functions & Hardware shall be as the
following:
Ordering Code: P54631NA7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking, Under
/ over Frequency 81,open conductor protection, Second
harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2 CB)
controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/ 67N ,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital
Outputs, Protection data interface-1 850, Protection data
interface-2 850, IEC61850, 2 x port(PRP)
Ordering Code: P54631NL7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking, Under
/ over Frequency 81,open conductor protection, Second
harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2 CB)
controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/ 67N ,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital

Page 142 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Outputs, Protection data interface-1 1300, Protection data
interface-2 850, IEC61850, 2 x port(PRP)
Ordering Code: P54631NR7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking, Under
/ over Frequency 81,open conductor protection, Second
harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2 CB)
controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/ 67N ,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital
Outputs, Protection data interface-1 1550, Protection data
interface-2 850, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P543 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P54331NL7M0D08M
Built in Functions: 87L(Dual Combined Slope), 21P&G
(5Zones,Quad+Mho+Bi), 67DEF with comm. Scheme, 79(2CBs
OR 1CB controlled)+25, 50/51PH&GR / SEF/46, 67P/ 67N, 49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator,
Hardware: 4CT+4VT+ 12BI's+12BO's, CH-1 1300nm, CH-2
850nm, IEC61850, 2 x port(PRP)
Ordering Code: P54331NR7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking, Under
/ over Frequency 81,open conductor protection, Second
harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2 CB)

Page 143 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/ 67N ,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 4CT+4VT+ 12BI's+12BO's, CH-1 1550nm, CH-2
850nm, IEC61850, 2 x port(PRP)
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NC7M0468J
Built in Functions: 87L High Impedance, 95 CT bus wire
supervision, 50/51PH&GR / SEF/46, 67P/ 67N , SEF,49 Thermal
Overload, 27/59/59N, 50BF, 74 DC supply supervision, 74 Trip
circuit supervision, CT Supervision, 60 VT Supervision, DFR/SOE
/ Fault Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7Digital
Outputs, IEC61850, 2 x port(PRP)
Ordering Code: P14231NC7M0468J
Built in Functions: 50/51PH&GR / SEF/46, 67P/ 67N , SEF,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply supervision,
74 Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator

Page 144 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7Digital
Outputs, IEC61850, 2 x port(PRP)
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from Uni

Page 145 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL 411L
Ordering code:
0411L1X6X1C7CDXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
SEL 411L
Ordering code:
0411L1X6X1C7CEXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 146 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SD522
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0H+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIS+12BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
7SD522
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0J+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:

Page 147 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
4CT+4VT+12BIS+12BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Total =

31. 7. 2

POWER TRANSFORMER PROTECTION RELAYS 380/132/115/110kV

Applicable Standards:

Page 148 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
RED 670
Ordering code:
RET670*1.2-B30X00-A02D03E01P01-B1X-C-B-KB-B-B3B3-D1AXE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
14xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports

Relay Type:
RET 670
Ordering code:
RET670*1.2-B40X00-A01A02D04E01P01-B1X-C-B-KB-B-B3B3-D
1A-XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O

Page 149 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
14xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 150 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P 643
Ordering code:
P64332NA6M0040K
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT (Ph) + 4xCT (Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Relay Type:
MiCOM P 643
Ordering code:
P64532NA6M0040K
Built in Functions:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24

Page 151 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 152 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE Multilin

FACTORY LOCATION
CANADA-Markham

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
T 60
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-PXX-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
15xCT(Ph)+5xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING:
IEC 61850 2-ports
Relay Type:
T 60
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-P6T-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24

Page 153 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+5xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 154 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P643 + MiCOM P849 as per the following
conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Thermal Withstand per IEC 60255-1
2009, Change of Temperature per IEC 60068-2-14 2009 &
Damp Heat Steady State per IEC 60068-2-78 2002) for MiCOM
P643 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P64332QA6M0B08M + P8490NA6M0A08K
Built in Functions: 87T ( Dual Combined Slope), 87REF (low
Impedance), 87REF (High Impedance), 87/50 Instantaneous
Diff, 50/51PH&GR All Windings, 67P/67N (All Windings),
27/59/25, 81U/O, 50BF, 49T, 24, 74 DC supply supervision, 74
Trip circuit supervision, CT Super. (All Windings), 60 VT
Supervision, DFR/SOE,
Hardware: 15xCT(Ph) + 3xCT(Gnd) + 4xVT, 32+16 Digital
Inputs, 16+16 Digital Outputs, IEC61850, 2 x port (PRP)
Ordering Code: P64332QA6M0B08M + P84930NE6M0A08K
Built in Functions: 87T ( Dual Combined Slope),
50/51PH&GR/SEF/46, 67P/67N, 49Therma l overload,
27/59/81/59N, 50BF74 DC supply supervision, CT Supervision,
60 VT Supervision, DFR/SOE
Hardware: 9xCT(Ph) + 3xCT(G) + 4xVT , 16+64 Digital Inputs,
16+16 Digital Outputs, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is

Page 155 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
prequalified for MiCOM P642 + MiCOM P849 as per the following
conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013..
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Functions: P64232QD6M0B08L + P8490NA6M0A08K
Built in Functions: 87T ( Dual Combined Slope), 87REF (low
Impedance), 87REF (High Impedance), 87/50 Instantaneous
Diff, 50/51PH&GR All Windings, 67P/67N (All Windings),
27/59/25, 81U/O, 50BF, 49T, 24, 74 DC supply supervision, 74
Trip circuit supervision, CT Super. (All Windings), 60 VT
Supervision, DFR/SOE,
Hardware: 9xCT(Ph) + 3xCT(Gnd) + 4xVT, 32+12 Digital
Inputs, 16+12 Digital Outputs, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM 142 + MiCOM P849 as per the following
conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
Ordering Code, Built in Functions & Hardware shall be as the

Page 156 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
following:
Ordering Code: P14231NC7M0468J + P84930NE6M0A08K
Built in Functions: 87 High Impedance Diff Protection, SEF,
50/51+50N/51N / 46, 49 Thermal Overload, 27/59/59N,
Breaker Failure (50BF) 74DC DC SUPPLY SUPERVISION, CT
Supervision, 67P/67N, Under / Over Frequency 81, Under
current 37, 60VT Supervision, DFR/SOE/F Locator
Hardware: 5xCT(Ph) + 3xVT 16+64 Digital Inputs, 7+16 Digital
Outputs, IEC61850, 2 x port (PRP)
Ordering Code: P14231NC7M0468J
Built in Functions: 87 High Impedance Diff Protection, SEF,
50/51+50N/51N / 46, 49 Thermal Overload, 27/59/59N,
Breaker Failure (50BF) 74DC DC SUPPLY SUPERVISION, CT
Supervision, 67P/67N, Under / Over Frequency 81, Under
current 37, 60VT Supervision, DFR/SOE/F Locator
Hardware: 5xCT(Ph) + 3xVT , 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 x port (PRP)

SEL

United States

Yes

Relay Type:
SEL487E
Ordering code:
0487E3X648XXC2X4H624XXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
60
DFR/SOE
Hardware:
2-WINDING:
8xcontact inputs
4xcontact outputs
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
IEC 61850 2 ports

Page 157 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7UT6
Ordering code:
7UT6331-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Relay Type:
7UT6
Ordering code:
7UT6351-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24

Page 158 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
12xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 159 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ZIV

FACTORY LOCATION
SPAIN-Madrid

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
IDV
Ordering code:
8IDVK4F22Z104SKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+2xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING
IEC 61850 2 ports
Relay Type:
IDV
Ordering code:
8IDVD4F22Z904VKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
50 BF
49T
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
DFR/SOE

Page 160 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware:
3-WINDING:
12xCT(Ph)+2xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Total =

31. 7. 3

Double BUS-BAR Single CB 132/115/110 kV Relays

Applicable Standards:

Page 161 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REB500 CU
Ordering code:
REB500-CU03-V76-S30-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 CU
Ordering code:
REB500-CU03-V76-S50-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
48 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 PU
Ordering code:
REB500-BU03-C2-A40-P0-F1-BB2-IO0-R0-OC0-BFP1-EFP1-PD0DR0-L0-T0+1MRB150073R0052
Built in Function:
50BF: stage1
50BF: stage2

Page 162 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
End fault protection with Interntrip or Dead Zone
HMI
DFR/SOE

Hardware:
PU: 4CT+16BIS+12BOS
Alstom

United Kingdom---

Yes

Relay Type:
MICOM P740 PU
Ordering code:
P74137NA6M0510K
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage2
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIS+8BOS
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
MICOM P740
Ordering code:
P74331NA6M0510K
Built in Function:
50BF: stage1
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BIs+12BOS
IEC 61850, 2-PORTS

Page 163 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SS52x CU
Ordering code:
7SS5220-4AB92-1CA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
7SS52x CU
Ordering code:
7SS5220-4AB92-1FA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
48 PU connected to CU
IEC 61850, 2-PORTS

Page 164 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Relay Type:
7SS52x PU
Ordering code:
7SS5231-5CA01-1AA1
*BO=6 with double contact
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
PU: 4CT+16BIs+12BOS
Total =

31. 7. 4

33kV Plain OH Feeder + UG + Incomer Relays

Applicable Standards:

Page 165 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REL 670
Ordering code:
REL670*1.2-A31X00-H07P01-B1X-AX-KB-B-B6X0-D1A-XX-XE
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 166 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P543 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Enclosure Protection per IEC 60259 2001) for MiCOM
P543 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P54331NE7M0D08M
Built in Functions: 21 P&GD / 87 L, 50/51PH&GR, 67P/ 67N, 49
Thermal Overload, Phase Unbalance 46, Under current 37,
27/59, Auto Re-closure 79, 50BF, 74 Trip circuit supervision, In
rush blocking, Under/over Frequency 81, CT Supervision, 60 VT
Supervision, Open conductor protection, second harmonic
detection, sensitive earth fault protection, DFR/SOE / Fault
Locator.
Hardware: 5CT + 4VT, 16BI+14BO, IEC61850, 2 x optical port
(PRP)

Page 167 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL421
Ordering code:
04214611XC2X43224XXXX
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
15BI+23 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 168 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SA6x
Ordering code:
7SA6311-5BB92-2DM4+L0S
*with 20BI+09BO
**ONLY 67N

Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67N
49 Thermal Overload
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total =
31. 7. 5

13.8kV Plain OH Feeder + UG + Incomer Relays

Applicable Standards:

Page 169 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
FINLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REF615
Ordering code:
HBFJAEAGNEA1BAA1XE
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 170 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE Multilin

FACTORY LOCATION
SPAIN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
F650
Ordering code:
F650-NFD-F2G1-HI-6E
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 171 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
NR Electric Co. Ltd

FACTORY LOCATION
CHINA-Nanjing

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07186-1-30504401 dated December
23, 2013, it is pre-qualified for 13.8 kV Plain OH Feeder + UG +
Incomer Relays, with the following condition:
Ten (10) years extended warranty from the date of PAC of the
first turnkey project in case of contract award and
subsequently reduced yearly in case of future project award .
This was confirmed in writing by the manufacturer through their
letter # NR-SEC-20110829-CL2 dated August 29, 2011.
Relay Type:
PCS 9611
Ordering code:
PCS-9611-A1C-1B1B3A3A2A
Built in Function:
Control & Mimic
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase unbalance 46
Under Current 37
27/59
Auto reclosure 79
50BF
Trip Circuit Supervision 74TC
Inrush Blocking
Under / over frequency 81
CT Supervision
60 (VT Fuse Supervision )
Sensitive earth element function
Second harmonic detection
DFR / SOE
Hardware:
16 BI+ 07 BO
3CT(Ph) + 1CT(GD)+3VT
IEC 61850, 2-Optical Ports PRP

Page 172 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SCHNEIDER ELECTRIC (Telemecanique)

FACTORY LOCATION
FRANCE--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
Sepam-80
Ordering code:
SEP888S84J33TNTLA
Along with Ordering Code, following optional modules needs to
be ordered..
1.
MES120 (59715) #2 nos.
2.
ACE850F0 interface module (59659) # 2 no.
3.
ACE850 communication cable (CCA614) # 2 no.
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
14BI+6 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 173 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL-451
Ordering code:
04515611XC2X4H244XXXX
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 174 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SJ64
Ordering code:
7SJ6411-5EB92-1FG1+L0S
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE

Hardware:
15BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total =
31. 7. 6

13.8kV and 33kV Capacitor Bank Relays

Applicable Standards:

Page 175 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REC670
Ordering code:
1MRK 002 814-AC
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BIs+24BOs
IEC 61850,2-PORTS

GE Multilin

CANADA-Markham

Yes

Relay Type:
C70
Ordering code:
C70-K03-HKH-F8N-H6D-M8V-P67-U6D-W67
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BIs+20BOs
IEC 61850,2-PORTS

Page 176 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL487V
Ordering code:
0487V0X6111XC2X4H424XXX
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+15BIs+23BOs
IEC 61850,2-PORTS
Total =

31. 7. 7

Tripping and Lockout Relay

Applicable Standards:

Page 177 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom

FACTORY LOCATION
United Kingdom---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MVAJ
Ordering code:
MVAJ101RA0802A
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case
Relay Type:
MVAJ
Ordering code:
MVAJ105RA0802A
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case

Page 178 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ELECTRO-SWITCH

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
LOR
Ordering code:
LOR/HR-7810F
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Relay Type:
LOR
Ordering code:
LOR/SR-7868FD
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)

Page 179 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10095-030504401 dated 31
December 2014, the manufacturer is prequalified for
Latched Tripping and lockout Relay type BI-16R HB, Ordering
Code: BI-16R HB 125 VDC Standard Specification: High burden,
flag indication, electrical reset, 16 Contacts make and carry (3
sec) AC/DC 7500VA/w with max 30A, 300V. Breaking capacity
DC 125w resistive, 60w inductive (L/R = 40ms).
Latched Tripping and lockout Relay type BI-16RP HB, ordering
code: BI-16RP HB 125 VDC, Standard Specification: High
burden, flag indication, electrical and hand reset, 16 Contacts
make and carry (3 sec) AC/DC 7500VA/w with max 30A, 300V.
Breaking capacity DC 125w resistive, 60w inductive (L/R =
40ms).
Unlatched Tripping Relay type RI-16R HB, ordering code:
BI-16RP HB 125 VDC op: 01000, Standard Specification: High
burden, LED indication, Self-reset, 16 Contacts make and carry
(3 sec) AC/DC 7500VA/w with max 30A, 300V. make and carry
continuous AC/DC 1250 VA/w with max of 5A, 300V. DC 80w
resistive, 40w inductive (L/R = 40ms).

with the following condition:


- Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award and
subsequently reduced yearly (in case of future project award) .
and from the date of first delivery in case of direct material
supply order. This was confirmed in writing by the manufacturer
through their letter SEC030214_Annex dated February 03,
2014.

Page 180 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Relay Monitoring System (RMS)

FACTORY LOCATION
AUSTRALIA-Melbourne

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-02815-2-030504401 dated 30 June
2015, the manufacturer is prequalified for:
High Speed Tripping Relay ,
Type: 6RJ21
Ordering Code: 6RJ21-10-D-8M2B
High Burden Tripping Relay ,
Type: 6RJ25
Ordering Code: 6RJ25-10-D-8M2B
As conforming to National Grid SA specification # 41-TMSS-01,
Rev.0 with the following condition:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award and
subsequently reduced yearly (in case of future project award).
and from the date of first delivery in case of direct material
supply order. This was confirmed in writing by the manufacturer
through their letter# Nil dated November 07, 2013.

Page 181 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
TR
Ordering code:
TR241-7PG1524-1JC60-1AF0
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case

Relay Type:
TR
Ordering code:
TR212-7PG1521-2JC60-1AF0
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case

Page 182 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

31. 7. 8

Short Cable - all voltage levels

Applicable Standards:
ABB

SWEDEN

Yes

Relay Type:
RED670
Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-KB-B-B6X0-D1AX-AAXXX
X
-XE
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT+6VT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 850nm, CH-2 850nm (up to 3km)
IEC 61850 -2 Ports
Relay Type:
RED670
Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-KB-B-B6X0-D1AX-BBXXX
X
-XE
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT+6VT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1310nm, CH-2 1310nm (up to 80km)
IEC 61850 -2 Ports

Page 183 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P543
Ordering code:
P54331NA7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs 16 Inputs
Binary Outputs 14
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
MiCOM P543
Ordering code:
P54331NC7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs 16 Inputs
Binary Outputs 14
CH-1 1300nm, CH-2 1300nm (up to 50km)
IEC 61850 -2 Ports

Page 184 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE

FACTORY LOCATION
CANADA---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W77
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W2B
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports

Page 185 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P543 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Enclosure Protection per IEC 60259 2001) for MiCOM
P543 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P54331NA7M0C08M
Built in Functions: Cable Diff. Protection, Breaker Failure
(50BF), DC supply supervision, 50/51 + 50N/51N, Current
Circuit Supervision,.
Hardware: 5 Analog Inputs CT, 4 Analog input VT, 16 Binary
Inputs-14 outputs, CH-1 820nm, CH-2 820nm (up to 1KM),
IEC61850, 2 x port (PRP),
Ordering Code: P54331NC7M0C08M
Built in Functions: Cable Diff. Protection, Breaker Failure
(50BF), DC supply supervision, 50/51 + 50N/51N, Current
Circuit Supervision.
Hardware: 5 Analog Inputs CT, 4 Analog input VT, 16 Binary
inputs-14 outputs, CH-1 1300nm ,CH-2 1300nm (up to 50KM),
IEC61850, 2 x port (PRP),
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per

Page 186 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NC7M0468J
Built in Functions: High Impedance Diff Protection, Internal CT
Bus-wire Supervision (95) , Breaker Failure (50BF), DC Supply
Supervision, 50/51+50N/51N, Current Circuit Supervision
Hardware: 5CT + 3 VT, 16 BI, 7 BO, IEC61850, (? 300m and
GIB), 2 x port IEC61850 (PRP)

Page 187 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL411L
Ordering code:
0411L1X6X1C7CCXH5C424XX (2KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
SEL411L
Ordering code:
0411L1X6X1C7DDXH5C424XX (24KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports

Page 188 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SD52
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0A+N0A
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1.5km)
IEC 61850 -2 Ports
Relay Type:
7SD52
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0G+N0G
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports
Total =

31. 7. 9

High Impedance BBP for all levels

Applicable Standards:

Page 189 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REC670
Ordering code:
REC670*1.2-A30X00-A02C31P02-B1-AA-KB-B-B6X0-D1A-XXX-X
E
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+6U
24BO
16BI
IEC 61850,2-Optical Ports (PRP)

Relay Type:
REB650
Ordering code:
1MRK006520-AD
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+4U
27BO
18BI
IEC 61850,2-Optical Ports (PRP)

Page 190 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MCAG
Ordering code:
MCAG34VCD*****A
Built in Function:
87 3-Phase High Z Differential (Current Base)
External CT Bus Wire Supervision
External stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
3 CT Inputs
2 Output Contacts

Relay Type:
MCAG
Ordering code:
MCAG14SSD**** *A
Built in Function:
87 3-Phase High Z Differential
(Current Base)
External CT Bus Wire Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 CT Phase Inputs
2 Output Contacts

Relay Type:
MFAC
Ordering code:
MFAC34V1B*0001A
Built in Function:
87 3-Phase High Z Differential
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting

Page 191 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Hardware:
3 elements / phases voltage based
2 Output Contacts

Relay Type:
MFAC
Ordering code:
MFACI4S1B*0001A
Built in Function:
87 3-Phase High Z Differential.
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 elements / phases voltage based
4 Output Contacts

Page 192 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NH7M0468J
Built in Functions: 87 3-Phase High Z Differential, 50/51N, CT
Bus-wire Supervision (95), TCS : Trip Circuit Supervision, 74 DC
supply supervision, External stabilizing resistor, External
Metrosil Resistor, External CT shorting
Hardware: 5CT + 3 VT, 16 BI, 5CT Input+3 VT input, 8 BI, 11
BO, IEC61850, 2 optical ports (PRP)

Page 193 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SJ64
Ordering code:
7SJ6411-5EB92-1FE0+L0S
Built in Function:
87 3-Phase High Z Differential
(based on current)50/51N
Internal CT Bus Wire Supervision
(based on current )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
4 CT Inputs
13BO
15BI
IEC 61850, 2-Optical Ports (PRP)
Total =

31. 7. 10

Auxiliary Relays

Applicable Standards:
ABB

SWEDEN---

Yes

Relay Type:
RXMVB2
Ordering code:
RK 251 204-AP (125V DC)
RK 251 204-AN (110v DC)
Built in Function:
CT Shorting
Hardware:

Alstom

United Kingdom---

Yes

Relay Type:
MVTP31
Ordering code:
MVTP31V1CB0751E
Built in Function:
CT Supervision
Hardware:

Page 194 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10095-030504401 dated 31
December 2014, the manufacturer is prequalified for
Relay type VDF- 10, ordering code VDF- 10 125 VDC, built-in
function: Trip circuit supervision - single phase, LED indication
and two contacts.
Relay type VDJ- 30, ordering code VDJ- 30 125 VDC, built-in
functions: Trip circuit supervision - three phase, LED indication
and two contacts.
Relay type RTU-4, ordering code RTU-4 125 VDC, built-in
functions: Auxiliary supply supervision, Self-Reset, LED
indication and (4) contacts.
Relay type RJ-8, ordering code RJ-8 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (8)
contacts.
Relay type RF-4, ordering code RF-4 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (4)
contacts.
Relay type BJ-8 RP, ordering code BJ-8 RP 125 VDC, built-in
functions: CT shorting application, flag indication, electrical and
hand reset and (8) contacts.
Relay type BF-4 RP, ordering code BF-4 RP 125 VDC, built-in
functions: CT shorting application, flag indication, electrical and
hand reset and (4) contacts.
Relay type TDJ-8, ordering code TDJ-8 125 VDC, built-in
functions: time-lag, LED indication, (8) timed contacts (10
functions,16 timing ranges from 30ms to 99 hours).
Relay type TDF-4, ordering code TDF-4 125 VDC, built-in
functions: time-lag, LED indication, (4) timed contacts (10
functions,16 timing ranges from 30ms to 99 hours).

with the following condition:


- Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award and
subsequently reduced yearly (in case of future project award) .
and from the date of first delivery in case of direct material
supply order. This was confirmed in writing by the manufacturer
through their letter SEC030214_Annex dated February 03,
2014.

Page 195 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
AR 901
Ordering code:
7PG1110-7AE10-0AF0
Built in Function:
CT Shorting
Hardware:
Total =

31. 7. 11

Bus Coupler and Bus Section 110 kV to 380 KV

Applicable Standards:

Page 196 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NC7M0468J
Built in Functions: 67P/67N, 50 N / 51PH&GR, SEF, 49 Thermal
Overload, 27/59/59N, 50BF, 74DC DC\ circuit supervision, 74
Trip circuit supervision, CT Supervision, VT Supervision, Stub
protection, DFR/SOE / Fault Locator
Hardware: 5CT + 3 VT, 16 BI, 7 BO, IEC61850, 2 x port (PRP)
Total =

31. 7. 12

Line 380kV CBF

Applicable Standards:

Page 197 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NC7M0468J
Built in Functions: 2 CB breaker Failure, CBF reset by Under
current, CBF reset by CB status, Pole discrepancy, 50BF, 74
Trip circuit supervision, 50/51/67+50N/51N/67N+46,
27/59/59N, Fuse Fail supervision, DFT/SOE
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 portx (PRP)
Total =

31. 7. 13

380 KV LINE REACTOR

Applicable Standards:

Page 198 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P142 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Damp Heat Cycle per IEC 60068-2-78 2002) for MiCOM
P142 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P14231NC7M0468J
Built in Functions: 87 High Impedance, 50/51PH&GR / SEF/46,
67P/ 67N, 49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT Supervision,
60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 x (PRP)
Total =

31. 7. 14

132-115-110 KV REACTOR BANK AND CAPACITOR BANK

Applicable Standards:

Page 199 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P643 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Thermal Withstand per IEC 60255-1
2009, Change of Temperature per IEC 60068-2-14 2009 &
Damp Heat Steady State per IEC 60068-2-78 2002) for MiCOM
P643 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P64332QA6M0B08M
Built in Functions: 87T ( Dual Combined Slope), 87REF (low
Impedance), 87REF (High Impedance), 87REF , 87/50
Instantaneous Diff, 67P/67N (All Windings), 50/51PH&GR All
Windings, , 27/59, 81U/O, 50BF, 49T, 24, 74 DC supply
supervision, 74 Trip circuit supervision, CT Super. (All
Windings), 60 VT Supervision, DFR/SOE,
Hardware: 9xCT(Ph) + 3xCT(Gnd) + 4xVT, 16 Digital Inputs,
16 Digital Outputs, IEC61850, 2 x port (PRP)
Total =

31. 7. 15

13.8 KV CONSUMER FEEDER

Applicable Standards:

Page 200 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated June 12,
2014, M/s Schneider Electric from United Kingdom stone is
prequalified for MiCOM P543 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays as
per new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed by the manufacturer through their letter # Nil dated
June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC 60068-2-78
2002 & Enclosure Protection per IEC 60259 2001) for MiCOM
P543 shall be conducted in the accredited testing laboratory
witnessing by one (1) Independent Inspection Agency (IIA)
inspector and type test report shall be submitted within July
2014.
Ordering Code, Built in Functions & Hardware shall be as the
following:
Ordering Code: P54331NE7M0C08M
Built in Functions: Open Conductor , Protection for primary
cables, Second harmonic detection, under/ over frequency, In
rush blocking, Under & Over Frequency 81, 87L, 21 P&G,
67DEF, 79 + 25 (1CB), ,50/51 P&G + 46, SEF, 67P/67N, 49
Thermal Overload, 27/59/59N, 50 BF, 74 Trip circuit
supervision, 74DC DC circuit supervision, CT Supervision, 60 VT
Supervision, DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 4xVT, 16 Digital Inputs, 14 Digital
Outputs, Protection data interface-1 1300, Protection data
interface-2 1300, IEC61850, 2 x optical port(fiber) (PRP)
Total =

31

.8

31. 8. 0

TERMINAL BLOCK
TERMINAL BLOCK

Applicable Standards:

31-TMSS-06

Page 201 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Connectwell industries Pvt. Ltd.

FACTORY LOCATION
INDIA-Dombivli

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07512-030504401 dated December
09, 2013, it is pre-qualified for terminal blocks as conforming to
National Grid SA specification # 31-TMSS-06, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer Connectwell industries
Pvt. Ltd., India through their letter # Nil dated November 27,
2012.

ENTRELEC

FRANCE

Yes

PHOENIX

GERMANY

Yes

WEIDMULLER

GERMANY

Yes

Wieland Electric GmbH

GERMANY-Bamberg

Yes

Based on S&SD letter# 13-05908-30504401 dated December


04, 2013, it is pre-qualified for terminal blocks as conforming to
National Grid SA specification # 31-TMSS-06, Rev.0 with the
following condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer Wieland Electric
GmbH, Germany-Bamberg through their letter # Bamberg
dated July 20, 2012.
Total =

31

.9

31. 9. 0

FAULT RECORDERS
FAULT RECORDERS

Applicable Standards:
AMETEK (ROCHESTER)

United States

Yes

Page 202 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ERL Phase Power Technologies Ltd

FACTORY LOCATION
CANADA-Winnipeg/Manitoba state

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-01879/02-030504401 dated April
28, 2015, the manufacturer is prequalified to supply TESLA
4000 Fault Recorder with the following conditions:
- Ten (10) years extended for the TESLA 4000 Fault recorder
from the date of PAC of the turnkey project in case of contract
award or date of delivery in case of direct material supply
order. as confirmed through the manufacturer letter # Nil dated
18.10.2013.
- Type tests shall be conducted on the first order as confirmed
through the manufacturer letter No. Nil dated 9.02.2014 and
letter No. Nil dated 04.03.2015 in presence of three (03)
SEC/National Grid SA Engineers and one (01) SEC/National Grid
SA approved IIA inspector. All the cost pertaining to the type
tests shall be borne by the manufacturer.

QUALITROL HATHAWAY

NORTHERN IRELAND

Yes
Total =

31

. 10

31. 10. 0

DYNAMIC SYSTEM MONITORING EQUIPMENTS


DYNAMIC SYSTEM MONITORING EQUIPMENTS

Applicable Standards:

DIgSILENT GmbH

GERMANY

Yes

POWER TECHNOLOGY INC. (PTI)

United States

Yes

QUALITROL HATHAWAY

NORTHERN IRELAND

Yes

38-TMSS-06

Based on S&SD Letter 12-03055-01-30504401 dated August


26, 2012, it is pre-qualified for Dynamic System Monitoring
(DSM) as conforming to SEC Specification # 38-TMSS-06,
Rev.0 with the following conditions:
All Factory tests shall be carried out on the first batch of
Dynamic System Monitoring (DSM) as per 38-TMSS-06, Rev.0 in
the presence of three (3) SEC Engineers. All costs related to
the tests shall be borne by the manufacturer. This
prequalification requirement was confirmed by
Qualitrol-Hathaway, Belfast North Ireland U.K in writing through
their letter # Nil dated July 27, 2012.
Ten (10) years extended warranty in respect of defects due
to design , manufacturing, installation and workmanship from
the date of PAC of the first turnkey project (in case of contract
award) or from the date of first delivery of direct material
supply order as confirmed by Qualitrol-Hathaway, Belfast North
Ireland U.K through their letter # Nil dated May 18, 2010.
Total =

Page 203 of 244

SER

31

. 11

31. 11. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

SUBSTATION AUTOMATION SYSTEM


SUBSTATION AUTOMATION SYSTEM

Applicable Standards:
ABB Automation Co. Ltd.

Saudi Arabia-Riyadh

Yes

Based on S&SD letter# 14-00953-1-30504401 dated February


27, 2014, ABB Automation Co. Ltd., Riyadh is pre-qualified for
integration and testing of SAS systems for substations rated up
to 230kV against specification # TES-P-107.01, Rev.00 with the
following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850 Edition2,
and latest amendments of IEC in an accredited laboratory in
presence of three (03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer by ABB-Riyadh through their letter #
PSN/SAS/0709/08/2013 dated July 09, 2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by ABB Automation Co. Ltd., Riyadh
through their letter # PSN/SAS/0110 dated January 28, 2012.
Bay Controller Unit (BCU) shall be type
REC670*1.2-B30X00-P02-B1X-BE-KB-B-B6X0-D1AD1D1D1-XXXXE.
All the protection IEDs shall be as per section 31.7 National
Grid SA list of technically acceptable manufacturers.
Station Computer, Gateway, EWS and OWS shall be from
Advantech Taiwan.
SAS network shall be provided with SAS oriented Industrial
type Ethernet Switches per SEC/National Grid SA approved list.
Software shall be Micro SCADA.

Page 204 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Switzerland Ltd.( Global SAS Center)

FACTORY LOCATION
SWITZERLAND-Baden

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00953-1-30504401 dated February
27, 2014, ABB Switzerland Ltd.( Global SAS Center), Baden,
Switzerland is pre-qualified for Engineering, integration and
testing of SAS systems for substations up to 380 kV against
specification # TES-P-107.01, Rev.00 with the following
conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850 Edition2,
and latest amendments of IEC in an accredited laboratory in
presence of three (03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by ABB Switzerland Ltd. ( Global SAS
Center), through their letter # Nil dated April 29, 2012.
Bay Controller Unit (BCU) shall be type
REC670*1.2-B30X00-P02-B1X-BE-KB-B-B6X0-D1AD1D1D1-XXXXE.
All the protection IEDs shall be as per section 31.7 National
Grid SA list of technically acceptable manufacturers.
Station Computer, Gateway, EWS and OWS shall be from
Advantech Taiwan.
SAS network shall be provided with SAS oriented Industrial
Ethernet Switches per SEC/National Grid SA approved list.
Software shall be Micro SCADA.

Page 205 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid AG

FACTORY LOCATION
Saudi Arabia-Al-Khobar

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00832-2-30504401 dated February
27, 2014, ALSTOM Grid AG France Montpelier/ U.K Stafford
with integration and testing facility in Al-Khobar, KSA is
pre-qualified for substations rated up to 380 kV against
specification # TES-P-107.01, Rev.00 with the following
conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850 Edition2,
and latest amendments of IEC in an accredited laboratory in
presence of three (03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer by ALSTOM Grid AG France, U.K through their
letter SAS/TSSD/2014/WR1201-1 dated January 12, 2014.

Ten (10) years extended warranty from the date of PAC of


the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by ALSTOM Grid AG France Montpelier &
U.K Stafford for Substation Automation System through their
letter # RN-2012-03-11SAS dated March 4, 2012 for SAS and
from ALSTOM integration facility through their letter # SAS/
TSSD/2014/2012/WR0202-2 dated March 5, 2012.
Bay Controller Unit (BCU) type MICOM C264 from ALSTOM
U.K Stafford is with ordering code
AGC264MB116910012X-Y-Z-PRP.
All the protection IEDs shall be as per section 31.7 National
Grid SA list of technically acceptable manufacturers.
SAS software - DS Agile,
SAS network shall be provided with SAS oriented Industrial
type Ethernet Switches per SEC/National Grid SA approved list.
SAS OI Server is provided with Advantech IPC (Taiwan),
SCADA gateway and IEC/IEC GTW is provided with Advantech
IPC(Taiwan), Workstation OI Viewer is provided with Advantech
IPC(Taiwan), EW is provided with Advantech IPC(Taiwan).

Page 206 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric- France/Lattes

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on the S & SD letter# 14-00571-1-30504401 dated April
20, 2014, Schneider Electric, Lattes, France is prequalified for
Substation Automation System (SAS) for substations up to 380
kV with Integration and Testing of SAS (to be performed only
by Schneider Electric), at EPS factory Riyadh K.S.A subject to
the following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC 61850 Edition 2,
and latest amendments of IEC in an accredited laboratory in
presence of three (03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by Schneider Electric, through their letter #
Nil dated January 05, 2013.
SAS Equipment:
Bay Controller Unit (BCU)
Type MiCOM C264 with ordering codes as follows:
1- For all bays except for Transformers (HV side):
MiCOM C264M11I69100126030000U1111N10 {96 DI + 30 DO,
4 CT (Ph) + 5 VT}
2- For Transformer Bays (HV side):
MiCOM C264M11I691001260300A0U1111N10 {96 DI + 30 DO,
4CT (Ph) + 5 VT + 8 AI}( 8 Analog Current Inputs selectable
4-20 mA, 0-1 mA, 0-5 mA, 0-10 mA, 0-20 mA )
3- For Common BCU:
MiCOM C264L11I6910002D010000U1111N10 { 208 DI + 10
DO}
4- For ABTS/ ACCS:
MiCOM C264L11I691000250300A0U1111N10 {80 DI + 30 DO +
8 AI}
( 8 Analog Current Inputs selectable 4-20 mA, 0-1 mA, 0-5 mA,
0-10 mA, 0-20 mA )
Station Computers: Advantech (Taiwan).
Gateway: Advantech (Taiwan).
EWS: Advantech (Taiwan).

Page 207 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

OWS: Advantech (Taiwan).


Ruggedized Ethernet Switches: SAS network shall be
provided with ruggedized SAS oriented Industrial type Ethernet
Switches per SEC/National Grid SA approved list
Software: Latest version of PACiS.
Protection IEDS: From Manufacturers listed in section 31.7 of
the data base of Approved Manufacturers.
SEL U.S.A

Saudi Arabia-S.E.P - Riyadh

Yes

Based on the S & SD letter# 14-01257-30504401 dated 23


March 2014, Schweitzer Engineering Laboratory (SEL) -U.S.A is
prequalified for Substation Automation System (SAS) with
Integration and Testing of SAS to be performed only by (SEL),
at System House Factory for Electric Panels (SEP) Riyadh
K.S.A up to 380KV subject to the following:
1. Type Tests: The manufacturer has confirmed to perform the
required type tests in Independent Testing laboratories- KEMA
as per SEC/National Grid SA requirements , IEC 81650 Edition 2
standards in the presence of three (3) SEC/National Grid SA
Engineers and one (1) Independent Inspector through
reference letter # SEL/SAS/08/2013.
2. Guarantee/Warranty: The manufacturer has agreed to give
guarantee/ warranty to SEC/National Grid SA for the proposed
Substation Automation System (SAS) from SEL U.S.A with
Integration & Testing facility at SEP Riyadh K.S.A in respect of
the defects due to design, manufacturing, installation and
workmanship for a period of ten (10) years , This was confirmed
in writing by the manufacturer through their letter ref: nil dated
February 18, 2013.
3. Bay Controller Unit (BCU) type SEL 451 from SEL U.S.A is
with ordering code 04515611XC2X4H64444X1.
4. All the protection IEDs shall be as per section 31.7 National
Grid SA list of technically acceptable manufacturers.
5. Station Computer (FESC) SEL-3355, Gateway SEL -3355,
EWS: SEL-3355, OWS: SEL-3355.
6. Software: Survalent Technology EMEA from U.S.A - the
software shall comprise of Survalent packages (Scada Manager,
Scada Explorer, and Worldview Professional).
7. SAS network shall be provided with SAS oriented Industrial
type Ethernet Switches per SEC/National Grid SA approved list.

Page 208 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens - Germany/Nurnberg

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on the S&SD letter# 14-03345-02-30504401 dated May
20, 2014, SIEMENS -Germany is prequalified for Substation
Automation System (SAS) with Integration and Testing at
SIEMENSJeddah K.S.A up to 380kV projects subject to the
following conditions:
Type tests shall be carried out for SAS components as per
National Grid SA requirements latest revision of IEC 61850
(edition 2) on the approved Independent Testing laboratory
witnessing by three (3) National Grid SA engineers and one (1)
approved Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the Siemens Jeddah
K.S.A as per their confirmation through letter # Nil dated April
21, 2014.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery in case of direct material supply order as
confirmed from SIEMENS -Germany & for Integration & Testing
facility at SIEMENS Jeddah K.S.A the Siemens-Germany &
Siemens Jeddah K.S.A through their letter # Nil dated
November 12, 2012.
SAS Equipment:
Bay Controller Unit (BCU) : type 6MD6 from SIEMENS
Germany is with ordering code (6MD6631-4EB90-0AA4+L0S)
shall be used.
Station Computers: Advantech (Taiwan).
Gateway: Advantech (Taiwan).
EWS: Advantech (Taiwan).
OWS: Advantech (Taiwan).
Ruggedized Ethernet Switches: SAS network shall be
provided with ruggedized SAS oriented Industrial type Ethernet
Switches per National Grid SA approved list
Software: Latest version of SICAM PAS/PAS CC/SCC.
Protection IEDS: From Manufacturers listed in section 31.7 of
the data base of Approved Manufacturers.
Total =

32
32

.1

32. 1. 0

METERS

KILOWATT HOUR METER (ENERGY METER)


KILOWATT HOUR METER (ENERGY METER)

Applicable Standards:

40-TMSS-02

Page 209 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ADVANCE ELECTRONICS CO., LTD.

Saudi Arabia-Riyadh

Yes

Based on the approval of Executive Director through TS&SD


Letter # 08-1105-03032301 dated 20/10/2008, this
Manufacturer is pre-qualified for Energy Meters Type
(ADDAD-4).

ELSTER

United States

Yes

PREVIOUSLY ABB (T &D)


Based on S&SD Letter 12-00932-1-30504401 dated March 25,
2012, it is pre-qualified for A3RAQ, A1860RALC and
A1860RAL meters as confirming to SEC Specification #
40-TMSS-02, Rev.0 with the following condition:
A3RAQ meters with configuration ZD3D44F00LD-16,
ZD3E44F00LD-16, ZD3D46000LD-16.
A1860RALC meters with configuration ZE3KM4CF5LK-EL.
A1860RAL meters with configuration ZE3KM4CF0LH-EL.
Free Supply of Meter Type A3RAQ: Five (5) Revenue Meters
Type A3RAQ shall be supplied free of cost to SEC as confirmed
through ELSTER letter # L1-ST12-001 dated January 21, 2012.
Five (5) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as
confirmed through ELSTER letter # NIL dated 12-01-2012.

GEC MEASUREMENT

United Kingdom

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.

Landis + Gyr AG-Zug

SWITZERLAND-Zug

Yes

Based on S&SD Letter 14-04075-30504401 dated July 01,


2014, it is pre-qualified for Revenue Meters Type E650 (ZXD) &
E850 (ZXQ) conforming to National Grid SA specifications #
40-TMSS-03, Rev.1 and 40-TMSS-02 Rev.0 with the following
conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by the manufacturer through their letter # Nil, dated
January 30, 2014.
Software for both meters [(E650 (ZXD) & E850 (ZXQ)] shall be
MAP120 and MAP110 .

SIEMENS

GERMANY

Yes

Page 210 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TYCO ELECTRONICS (UK) Ltd - CROMPTON
INSTRUMENTS

FACTORY LOCATION
United Kingdom--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letters (08-F00975/01-03032301 dated June
04, 2008), (10-F00230/01-03032301 dated February 03, 2010)
& (11-F03017/01-03032301 dated October 16, 2011). Integra
(1530, 1540, &1630) are prequalified for Digital Metering
Devices (NOT FOR BULK ENERGY METERS) as confirming to SEC
Specification # 40-TMSS-02, Rev.0 with the following condition:
Five (05) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order. This
was confirmed by TYCO Electronic UK through their letter #
INT-SEC-06 dated January 03, 2008 and its Amendment dated
November 21, 2011.
Total =

32

.2

32. 2. 0

AMMETER, VOLTMETER, MW, MVAR


AMMETER, VOLTMETER, MW, MVAR

Applicable Standards:
AREVA

FRANCE

Yes

CELSA

ITALY

Yes

CEWE

SWEDEN--

Yes

ENTES

TURKEY-ISTANBUL

Yes

40-TMSS-02

Based on TS&SD letter # 10-F2298/03-03032301 dated


02/10/2010, it is pre-qualified for Digital Ammeter type
(EPM-34) and Digital Voltmeter type (EVM-35) as conforming to
SEC specification # 40-TMSS-02, Rev.0 with the following
condition:

ENTES (Turkey) has agreed to give SEC a


Guarantee/Warranty on the proposed digital meters for a
period of two (02) years and eight (08) years (for maintenance)
for total of ten (10) years from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.

ISKRA MIS

SLOVENIA-KRANJ

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END USER
DEPARTMENT FOR EACH PURCHASE ORDER / PROJECT
DURING TENDER/BIDDING STAGE.

SCHNEIDER ELECTRIC

CANADA--

Yes

DIGITAL POWER METERS TYPE ION 6200 (0.5% ACCURACY


CLASS); 10 YEARS EXTENDED WARRANTY

Page 211 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TYCO ELECTRONICS (UK) Ltd - CROMPTON
INSTRUMENTS

FACTORY LOCATION
United Kingdom--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letters (08-F00975/01-03032301 dated June
04, 2008), (10-F00230/01-03032301 dated February 03, 2010)
& (11-F03017/01-03032301 dated October 16, 2011). Integra
(1530, 1540, &1630) are prequalified for Digital Metering
Devices as confirming to SEC Specification # 40-TMSS-02,
Rev.0 with the following condition:
Five (05) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order. This
was confirmed by TYCO Electronic UK through their letter #
INT-SEC-06 dated January 03, 2008 and its Amendment dated
November 21, 2011.
Total =

32

.3

32. 3

AUTOMATIC METER READING (AMR) SYSTEM


AUTOMATIC METER READING (AMR) SYSTEM

Applicable Standards:

40-TMSS-03

ADVANCE ELECTRONICS CO., LTD.

Saudi Arabia-Riyadh

Yes

Based on approval of Executive Directive for TS&SD Letter #


08-1105-03032301 dated 20/10/2008, it is pre-qualified for
Energy Meters Type (ADDAD-4) & Quality Meters Type
(SEL-734).

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

(AMI)
Based on S&SD letter # 15-03460-30504401 dated April 22,
2015, The manufacturer is prequalified to supply Advance
Metering Infrastructure (AMI) as conforming to National Grid SA
specification # 40-TMSS-03, Rev.01with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # AES-AMI-PQA-2014/001 dated July 09th, 2014.

ALps Technologies

FRANCE-ANNECY-LE-VIEUX CEDEX

Yes

Based on TS&SD letter# 09-F00181/03-03032301 dated 06th.


April 2009 with (5) years warranty from the date of PAC

Page 212 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electro Industries / GaugeTech

FACTORY LOCATION
United States-New York

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-00862/03-030504401 dated April 20,
2013, Electro Industries/ GaugeTech, New York, USA is
pre-qualified for Power Quality Meters type NEXUS 1500 as
conforming to National Grid SA specification # 40-TMSS-03,
Rev.0, with the following conditions:
Product Support: Continuous supply and product support of
Power Quality Meters type NEXUS 1500 to all SEC/National Grid
SA approved AMR Manufacturers for a minimum period of ten
(10) years shall be ensured as confirmed through their letter #
Nil dated January 01, 2012.
Product Demo: EIG Tech USA in coordination with their Local
Agent (Ideal Technical Solutions, Riyadh) shall demonstrate the
hardware and software capability and the features of NEXUS
1500 Power Quality Meters during the proposed Live Demo of
the AMR system to be conducted on the first order in presence
of SEC/National Grid SA Engineers as already confirmed through
item # 8 of ITS letter # L1-NG01-J13-006 dated February06,
2013.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from the
date of first delivery of direct material supply order as
confirmed by Electro Industries /Gauge Tech -New York, USA
through their letter # L1-NG01-J13-004 dated January 29,
2013.

ELSTER

United States

Yes

Based on S&SD Letter 12-00932-1-30504401 dated March 25,


2012, it is pre-qualified for A1884RALNC meters as confirming
to SEC Specification # 40-TMSS-03, Rev.0 with the following
conditions:
A1884RALNC meters with configuration ZE3KM4C4FLP-01
[ This Meter is approved for Revenue Meter Application only ].
Five (5) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through ELSTER letter # NIL dated 12-01-2012.

Page 213 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Ideal Technical Solutions (ITS)

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
AMI
Based on S&SD Letter 14-00090-1-30504401 dated January
09, 2014, it is pre-qualified for Advance Metering Infrastructure
(AMI) systems as conforming to National Grid SA Specification #
40-TMSS-03, Rev. 01 with the following conditions:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or date of
first delivery in case of direct material supply order as confirmed
through Ideal Technical Solutions (ITS), KSA, Riyadh letter
#W1-NG01-J14-001 dated January 01,2014 and
Letter#L1-NG01-J14-001 dated December 03, 2013.
- System Demo: Live Demo of the AMI System will be conducted
in presence of SEC/National Grid SA Engineers on the first
system to be manufactured in SEP factory already confirmed
through Ideal Technical Solutions (ITS), KSA, Riyadh letter
#L1-NG01-J14-002, dated January 06,2014.

AMR
Based on S&SD Letter 13-00971-1-30504401 dated May 15,
2013, it is pre-qualified for AMR system as conforming to
National Grid SA Specification # 40-TMSS-03, Rev.0 with the
following conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award)or date of
first delivery in case of direct material supply order as confirmed
through Ideal Technical Solutions (ITS), KSA, Riyadh letter #
W1-NG01-J13-001 dated January 08, 2013 and L1-ST12-020
dated December 03, 2012.
ITS Integration & Test Facility: as per item# 3.a of ITS letter#
L1-NG01-J13-003 dated January 26, 2013.

Page 214 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Landis + Gyr AG-Zug

FACTORY LOCATION
SWITZERLAND-Zug

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 14-04075-30504401 dated July 01,
2014, it is pre-qualified for Revenue Meters Type E650 (ZXD) &
E850 (ZXQ) conforming to National Grid SA specifications #
40-TMSS-03, Rev.1 and 40-TMSS-02 Rev.0 with the following
conditions:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by the manufacturer through their letter # Nil, dated
January 30, 2014.
E650 (ZXD) & E850 (ZXQ) [This meters are approved for
Revenue Meter application only].
Software for both meters [(E650 (ZXD) & E850 (ZXQ)] shall be
MAP120 and MAP110 .
Total =

33
33

.1

33. 1. 0

CAPACITOR

SHUNT CAPACITOR
SHUNT CAPACITOR

Applicable Standards:

43-TMSS-01

Yes
ABB

SWEDEN

Yes

Based on TS&SD Letter # 10-00269-03032301 dated


24/01/2010, it is pre-qualified for Shunt Capacitor Banks as
confirming to SEC specification # 43-TMSS-01, rev.0 with the
following condition:
Seven (7) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.

ALSTOM Grid Ltd.

FINLAND-Tampere

Yes

Previously " Nokian Capacitors Ltd. Finland", the name has


been changed to Areva T&D Ltd. Finland based on TS&SD/ESD
Letter # 10-00145-03032301 dated January 16, 2010 and
Areva T&D Ltd.-Finland Letter # Nil dated January 04, 2010,
then the name has been changed again to ALSTOM Grid Ltd.
Finland based on Dept Mgr, S&SD E-mail dated February 26,
2012 and ALSTOM Grid Ltd. letter # RN-2012-02-18 dated
February 18, 2012.

Eaton

United States-Greenwood (SC state)

Yes

Previously COOPER (MCGRAW-ED), the name has been


changed to Eaton based on S&SD/P&SFD letter #
15-04107-30504401 dated May 19, 2015 and COOPER
(MCGRAW-ED) letter # 01110502015 dated May 11, 2015

Page 215 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

General Electric Energy-CPQP

United States-New York

Yes

SAMWAH CAPACITOR CO. Ltd

KOREA, Republic of-Yongin-Si, Kyoungki-DoYes

REMARKS
Based on TS&SD fax ref.#08-F0623/01-03032301 dated
02/12/2008.
Pre-Qualified for Capacitor Bank (13.8kV through 380kV) with
this conditions:
-First batch shall be type test in an independent laboratory in
presence of (3) SEC engineers & (1) independent inspector.
-(10) years warranty
Based on TS&SD Letter # 11-02016/01-03032301 dated
06/07/2011, it is pre-qualified for Substation Type 13.8kV to
36kV Only Shunt Capacitor Banks as confirming to SEC
specification # 43-TMSS-01, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by SAMWAHA through letter # Nil dated 12/03/2010.

Schneider Electric

FRANCE-Pringy

Yes

Based on S&SD letter # 15-07331-07-30504401 dated March


03, 2015, the manufacturer is prequalified to supply MV
capacitor banks Type # CP 229 (13.8 kV) only, with the
following condition:
Ten (10) years extended Warranty for the proposed MV
Capacitor Bank in respect of the defects due to design,
manufacturing, installation and workmanship from the date of
the Provisional Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of delivery for the
direct material supply order as confirmed through the
manufacturer letter # Nil dated 11.09.2011.

VISHAY ELECTRONICS

34
34

.1

34. 1. 0

35

.1

Yes

Suspended for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
14-06522-30504401 dated September 03, 2014.
Total =

Total =

ELECTRONIC COMPONENTS

MODULAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS


MODULAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS

NEST OY/NAPS

35

CZECH REPUBLIC-BLATNA

Applicable Standards:
FINLAND

Yes

INSTRUMENT TRANFORMERS

33 & 34.5 KV CTS

Page 216 of 244

SER

35. 1. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

33 & 34.5 KV CTS

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:
ABB ( T& D)

United States-N/A

Yes

ABB EJF

CZECH REPUBLIC

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

REMARKS

50-TMSS-01

Based on S&SD Letter 12-03192-02-30504001 dated February


19, 2012, it is pre-qualified for 33 kV & 34.5 kV Current
Transformers (CTs) as confirming to SEC Specification #
50-TMSS-01 Rev.0 with the following conditions:

All Type, Routine and Special testes shall be carried out on


the first batch of 33 kV & 34.5 kV Current Transformers (CTs)
kV in an Independent Testing Laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall be
borne by the manufacturer. This was confirmed by the
manufacturer through their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.
GE

United States

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

MEMF

Saudi Arabia-RIYADH

Yes

TS&SD letter# 09-00918-03032301 dated 29 March 2009 it is


prequalified for CT up to 36kV with the following conditions:
TYPE TEST SHALL BE DONE AT AN INTL. TESTING LAB IN
PRESENCE OF 3RD PARTY INSPECTOR;
EXTENDED GUARANTEE/ WARRANTY FOR 10 YEARS FROM
PAC.

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE & BLOCK TYPE CTs UP TO 36kV.

SIEMENS

United States

Yes

STE

ITALY

Yes

RING/SPLIT CORE TYPE


Total =

12

Page 217 of 244

SER

35

.2

35. 2. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

69KV CTS
69KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-01

Type test required in first supply; 10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated February


19, 2012, it is pre-qualified for 69 kV Current Transformers
(CTs) as confirming to SEC Specification # 50-TMSS-01 Rev.0
with the following conditions:

All Type, Routine and Special testes shall be carried out on


the first batch of 69 kV Current Transformers (CTs) in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.
GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

Page 218 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

SIEMENS

United States

Yes

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL


TYPE
Total =

35

.3

35. 3. 0

19

110 - 132 KV CTS


110 - 132 KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-01

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

Page 219 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for 110 132 kV Current
Transformers (CTs) as confirming to SEC Specification #
50-TMSS-01 Rev.0 with the following conditions:

All Type, Routine and Special testes shall be carried out on


the first batch of 110 132 kV Current Transformers (CTs) in
an Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.
HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL


TYPE
Total =

35

.4

35. 4. 0

16

230KV CTS
230KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

50-TMSS-01

Page 220 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

REMARKS

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL


TYPE
Total =

35

.5

35. 5. 0

14

380KV CTS
380KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-01

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

Page 221 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

Based on TS&SD letter# 09-01105-03032301 dated 24th June


2009, it is pre-qualified for CT & CVT rated up to 380kV as
confirming to SEC specification # 50-TMSS-01, rev.0 & #
50-TMSS-02, rev.0 respectively with the following conditions:

All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in an independent testing laboratory in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of delivery in
case of direct material supply order.

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL


TYPE
Total =

36
36

.1

36. 1. 0

14

POTENTIAL TRANSFORMER

33 & 34.5 KV POTENTIAL TRANSFORMERS


33 & 34.5 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB ( T& D)

United States-N/A

Yes

ABB EJF

CZECH REPUBLIC

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

50-TMSS-03

Page 222 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for 33 kV & 34.5 kV Potential
Transformers (PT) as confirming to SEC Specification
#50-TMSS-03 Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 33 kV &
34.5 kV Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.

GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

MEMF

Saudi Arabia-RIYADH

Yes

Based on S&SD Letter 12-00694-030504401 dated March 03,


2012. It is prequalified for Medium Voltage Resin Cast Indoor,
Potential Transformers with the following conditions:
This approval is restricted to Resin Cast, Indoor Potential
Transformers with accuracy class including 0.5/3P (0.5%) rated
up to 36kV. Any other accuracy class including 0.2/3P (0.2%)
will be considered only after submitting Type Test Reports
(acceptable to the Company) from Independent Laboratory as
confirmed by MEMF through Letter # NIL dated February 13,
2012.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated October 24, 2011.

NISSIN

JAPAN

Yes

SADTEM

FRANCE

Yes

SIEMENS

GERMANY

Yes

BLOCK TYPE PTs UP TO 36kV.

Page 223 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

36

.2

36. 2. 0

14

69 KV POTENTIAL TRANSFORMERS
69 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-03

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated February


19, 2012, it is pre-qualified for 69 kV Potential Transformers
(PT) as confirming to SEC Specification #50-TMSS-03 Rev.0
with the following conditions:
All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 69 kV
Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

Page 224 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

36

.3

36. 3. 0

11

110 - 132 KV POTENTIAL TRANSFORMERS


110 - 132 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-02,50-TMSS-03

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated February


19, 2012, it is pre-qualified for 110 132 kV Potential
Transformers (PT) as confirming to SEC Specification #
50-TMSS-03 Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 110 132
kV Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Electrotecnica Arteche letter # NIL dated January 11,
2010 G.

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

Page 225 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PFIFFNER Instrument Transformers Ltd

FACTORY LOCATION
SWITZERLAND-Hirschthal

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-01326-02-03032301 dated
04/12/2011, it is pre-qualified for Inductive Voltage
Transformers from 110kV up to 230kV as confirming to SEC
specification # 50-TMSS-03, Rev.0 with the following
conditions:

All type, special, routine and sample tests as per SEC


specifications/standards shall be carried out on the first unit of
Inductive Voltage Transformers to be supplied to SEC in case of
securing an order in the presence of three (3) SEC Engineers &
one (1) approved independent inspection agency Inspector in
an independent testing laboratory or at the manufacturers
testing laboratory. All the related costs for witnessing the tests
will be borne by the manufacturer. This was confirmed by
PFIFFNER Instrument Transformers Ltd through letter # P/90017052011 dated 17 May 2011.

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by PFIFFNER Instrument Transformers Ltd through
letter # P/900-25112010 dated 22 March 2011.
Total =

36

.4

36. 4. 0

11

230 KV POTENTIAL TRANSFORMERS


230 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-02,50-TMSS-03

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

MESWANDLER

GERMANY

Yes

NISSIN

JAPAN

Yes

Page 226 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PFIFFNER Instrument Transformers Ltd

FACTORY LOCATION
SWITZERLAND-Hirschthal

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-01326-02-03032301 dated
04/12/2011, it is pre-qualified for Inductive Voltage
Transformers from 110kV up to 230kV as confirming to SEC
specification # 50-TMSS-03, Rev.0 with the following
conditions:

All type, special, routine and sample tests as per SEC


specifications/standards shall be carried out on the first unit of
Inductive Voltage Transformers to be supplied to SEC in case of
securing an order in the presence of three (3) SEC Engineers &
one (1) approved independent inspection agency Inspector in
an independent testing laboratory or at the manufacturers
testing laboratory. All the related costs for witnessing the tests
will be borne by the manufacturer. This was confirmed by
PFIFFNER Instrument Transformers Ltd through letter # P/90017052011 dated 17 May 2011.

Ten (10) years extended warranty from the date of PAC


of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by PFIFFNER Instrument Transformers Ltd through
letter # P/900-25112010 dated 22 March 2011.
Total =

36

.5

36. 5. 0

10

380 KV POTENTIAL TRANSFORMERS


380 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

50-TMSS-02,50-TMSS-03

Type test required in first supply;10 Years Warranty from the


date of PAC is required.
Previously RITZ- United States [The name has been changed
based on S&SD/P&SFD letter # 13-06262-30504401 dated
December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

NISSIN

JAPAN

Yes
Total =

Page 227 of 244

SER

37
37

.1

37. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

INSULATING OIL

MINERAL OIL FOR ELECTRICAL APPARATUS


MINERAL OIL FOR ELECTRICAL APPARATUS

Applicable Standards:

54-TMSS-01

---

Yes

CT, PT, POWER TRANSFORMER MANUFACTURERS CAN


PROCURE OIL MEETING ALL THE REQUIREMENTS OF
APPLICABLE STANDARD FROM ANY REPUTED OIL
MANUFACTURERS.

APAR INDUSTRIES LTD

INDIA-RABLE-NEW MUMBAI

Yes

Based on TS&SD letter # 11-00152-1-03032301 dated


22/01/2011, it is pre-qualified for Uninhibited Naphthenic
Mineral Insulating Oil type POWEROIL TO 1020 (60U) as
conforming to SEC specification # 54-TMSS-01, Rev.01 with the
following condition:

Five (5) years extended warranty from the date of PAC of


the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

CHEMTRADE/MOBIL OIL CO. LTD.

Saudi Arabia-YANBU

Yes

NYNAS

SWEDEN

Yes

PETROMIN CORPORATION (Petrolube)

Saudi Arabia-Jeddah

Yes

SAVITA

INDIA

Yes

SHELL

GERMANY-Hamburg

Yes

Previously "PETROLUBE", the name has been change to


PETROMIN CORPORATION (Petrolube) - Saudi Arabia based on
PETROMIN CORPORATION letter # Nil dated 30/06/2010.

- previously Shell (France), The location has been changed to


Hamburg, Germany Based on the manufacturer email dated
19/08/2013.
- The acceptable mineral oil type is Shell Diala Type S2-ZU-I.
Total =

37

.2

37. 2. 0

INSULATING OIL FOR LOW PRESSURE OIL FILLED (LPOF) CABLES


INSULATING OIL FOR LOW PRESSURE OIL FILLED (LPOF) CABLES

Applicable Standards:

ATOFINA CHEMICALS

United States

Yes

DIELECTRIC SYSTEM INC.

United States

Yes

FURAKAWA CABLES

JAPAN-FUJIKURA

Yes

INDOPOL

FRANCE-LAVERA

Yes

SIEMENS

GERMANY

Yes

Page 228 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

39
39

.1

39. 1. 1

TELECOMMUNICATION EQUIPMENT

FIBER OPTIC COMMUNICATION SYSTEM


SYSTEM INTEGRATION AND TESTING OF COMMUNICATION/SCADA EQUIPMENT

ABB Automation Co. Ltd

Applicable Standards:
Saudi Arabia-Riyadh

Yes

48-TMSS-06
Based on S&SD letter # 15-01367-01-30504401 dated 8th
March-2015, the manufacturer is prequalified for Integration
(Assembly) & Testing of Communication Equipment from Original
Equipment Manufacturer (OEM) type tested & approved by
SEC/National Grid SA as conforming to National Grid SA
specification # 48-TMSS-06, Rev.0 with the following condition:
Only for Integration (Assembly) & Testing of Communication
Equipment from Original Equipment Manufacturer (OEM) type
tested & approved by SEC/National Grid SA.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing and workmanship, as confirmed
by the manufacturer through their letter #
PSN/TLE/0517/09/2014,dt: 15/09/2014.

Alstom Grid Automation Unit Cogelex

Saudi Arabia-Jeddah

Yes

Based on S&SD letter # 15-00240-02-30504401 dated March


03, 2015, the manufacturer is prequalified for Integration
(assembly) & Testing of Communication & SCADA equipment as
conforming to National Grid SA specification # 48-TMSS-06,
Rev.0 with the following conditions:
- Only for integration (assembly) & testing of communication &
SCADA equipment from original equipment manufacturer (OEM)
type tested and approved by SEC/National Grid SA.
- Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # RN-2013-12-3 NMS/1 dated December 03, 2013.

Page 229 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
Saudi Arabia-JEDDAH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-08957-02-30504401 dated 17
December 2014, the manufacturer is prequalified for
Integration (Assembly) and Testing of Communication
Equipment from Original Equipment Manufacturer (OEM) type
tested and approved by National Grid SA as conforming to
National Grid SA specification # 48-TMSS-06, Rev.0 with the
following condition:
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case of
direct material supply order shall be provided as confirmed by
the manufacturer through their letter Fe/08/14 dated October
10, 2012.
Total =

39. 1. 2

FIBER OPTIC COMMUNICATION TERMINAL EQUIPMENT

Applicable Standards:

ABB

SWEDEN

Yes

ABB

SWITZERLAND

Yes

ALCATEL

FRANCE

Yes

48-TMSS-06

Based on TADD letter# 09-0576-030225, SCADA letter#


SOCW/DIV/97 and Telecomunication Dep. letter#
09-136-03040001.

Page 230 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alcatel-Lucent-ShangHai Bell Alcatel Co.Ltd(ASB)

FACTORY LOCATION
CHINA-ShangHai

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-07395-30504401, dated
23/10/2014, the test facility of Alcatel Lucent in (Bydgoszcz,
Poland) is allowed to conduct Factory Routine test and
Integration testing of communication equipment manufactured
in Alcatel-Lucent Factory in Shanghai China confirming to
National Grid SA requirements.
Based on TS&SD letter #10-03519/03-03032301 dated
17/04/2011, it is pre-qualified for Fiber Optic Communication
Terminal type Optenix1660SM with the following conditions:

The first batch of each type of Optenix 1660SM to be


supplied to SEC shall be Type/Special & Routine/Sample tested
in an independent testing laboratory in the presence of three
(3) SEC engineers & one (1) SEC approved independent
inspection agency Inspector and all cost pertaining to the tests
shall be borne by Manufacturer. This was confirmed in writing
by the Alcatel-Lucent (ASB)-China through letter #
ALU/172/SI/2010 dated 12/12/2010.

Ten (10) years extended warranty for the offered Optenix


1660SM from the date of PAC of the first turnkey project in
case of contract award or date of first delivery in case of direct
material supply order. This was confirmed in writing by A by the
Alcatel-Lucent (ASB)-China through letter # ALU/170/SI/2010
dated 12/12/2010.

Alcatel-lucent (ASB)-China has confirmed that after the


successful resolution of the prequalification process,
configuration as well as the drawings and details of the Trial
Link to be installed in SEC Network shall be submitted for SEC
review and approval. The places and dates of Trail Link
installation will be sent to the manufacturer.
----------------------------------------------------------------------Based on TS&SD letter # 11-03458/02-03032301 dated
03/12/2011, it's prequalified for Fiber Optics Terminal
Equipment 1511MAX Series conforming to SEC Specification #
48-TMSS-06 Rev.0 with the following conditions:

Type, Special, sample & routine tests shall be conducted


on the first batch of 1511MAX Series to be supplied to SEC, in
the presence of three (3) SEC Engineers & one (1) SEC
approved independent inspection agency Inspector in an
independent testing laboratory. All the related costs for
witnessing the tests will be borne by the manufacturer. This
was confirmed by Alcatel Lucent (ASB) Shanghai China through
response letter # ALU/25/SI/2011 dated 30/01/2011 and letter
# Nil dated 27/04/2011.

Page 231 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Ten (10) years extended warranty from the date of PAC


of the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed by Alcatel Lucent (ASB) Shanghai China through
letter # Nil dated 30/01/2011.

Alcatel-lucent (ASB)-China has confirmed that after the


successful resolution of the prequalification process,
configuration as well as the drawings and details of the Trial
Link to be installed in SEC Network shall be submitted for SEC
review and approval. The places and dates of Trail Link
installation will be sent to the manufacturer.
AT & T (LUCENT TECHNOLOGIES)

United States

Yes

Dedicated Network Partners (DNWP) Oy

FINLAND-Helsinki

Yes

Based on S&SD letter# 15-08552-01-30504401 dated March


18, 2015, Dedicated Network Partners (DNWP) Oy
(Espoo/Helsinki-Finland) is pre-qualified for designing,
marketing, servicing of Connection Master - which is
manufactured and tested under license of DNWP by Sanmina
Corp (Oulu/Haukipudas-Finland) - conforming to National Grid
SA specification # 48-TMSS-06, Rev.0, with the following
condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided, as confirmed by the manufacturer in writing
through their letter # Nil dated June 18, 2014.

FUJITSU

JAPAN

Yes

GE Industrial System

CANADA-Ontario

Yes

Based on TADD letter# 09-0297-030225 dated 28th March


2009; (Note: GE Industrial System, Canada has bought only the
Lentronics business from Nortel, Canada that manufactures
TN1U SHD Fiber Optic Terminal Equipment and MUX)

HUAWEI TECHNOLOGIES CO.LTD.

CHINA-Shenzhen

Yes

Based on TS&SD Letter # 10-F01736/02-03032301 dated


18/08/2010 & S&SD Letter # 14-06894-01-30504401 dated
22/10/2014, it is prequalified for (OSN
Series:1500,2500,3500,7500,9500 and iManager T2000NMS)
with the following conditions:
Ten (10) years extended warranty for the proposed
Communication Transmission Equipment (OSN Series
1500,2500,3500,7500,9500 and iManager T2000NMS) from the
date of PAC of the turnkey project in case of contract award or
from date of delivery in case of direct material supply order, as
already confirmed by the manufacturer Huawei vide letter #
70917174/MRK/SEC dated19/02/2008G.

Page 232 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Loop Telecommunication International

FACTORY LOCATION
Taiwan-Hsinchu

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-08552-01-30504401 dated
December 12, 2014 and S&SD letter # 15-01248-01-30504401
dated February 19, 2015, it is pre-qualified for Access DCS-Mux
Type DXC (from Loop Family-AM3440) and Digital Cross
Connect Equipment type eDXC (from Loop family-O9500), as
conforming to National Grid SA specification # 48-TMSS-06,
Rev.0, with the following condition:
- Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated March 15, 2013.

39. 1. 3

39

.2

39. 2. 0

NIPPON ELECTRIC CO. LTD.

JAPAN-TOKYO

Yes

NORTEL

CANADA

Yes

PHILIPS

HOLLAND

Yes

TELETTRA

FRANCE

Yes

FIBER OPTIC LOW DENSITY EQUIPMENT

Applicable Standards:
ABB INFOCOM LTD.

FRANCE-TURGI

Yes

LICOM

United States

Yes

PRISM

CANADA

Yes

SIEMENS

GERMANY

Yes

Total =

14

Total =

48-TMSS-06

DWDM SYSTEM
DWDM SYSTEM

Applicable Standards:

48-TMSS-08

Page 233 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alcatel Lucent

FACTORY LOCATION
ITALY-Trieste

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-0010-02-30504401 dated 12th
February 2015, the manufacturer is prequalified for DWDM
equipment Type 1830 PSS-32 as conforming to National Grid SA
specification # 48-TMSS-08, Rev.0 with the following condition:
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing and workmanship from the date
of the Provisional Acceptance Certificate (PAC) of the first
turnkey project (in case of contract award) and from the date
of first delivery in case of direct material supply order shall be
provided as confirmed by the manufacturer through their letter
No. (Nil) dated 06th June 2014.

IPG Photonics

United States-Oxford, Massachusetts

Yes

Based on S&SD letter # 15-05564-2-30504401 dated July 05,


2015, it is pre-qualified for supply, installation and configuration
of Optical Service Transport Platform (OSTP-DWDM), Erbium
Amplifier rack Mount (EAR) and Raman Amplifier Rack Mount
(RAR) manufactured by IPG Photonics, Oxford, Massachusetts,
USA plant as conforming to National Grid SA specification #
48-TMSS-08 with the following condition:
Ten (10) years Extended Warranty as confirmed through IPG
Letter # NIL dated 2nd April 2014 shall be applicable for all
supplies made to the Company by IPG Photonics Oxford,
Massachusetts, USA.

IPG Photonics

ITALY-Milan

Yes

Based on S&SD letter # 15-05564-3-30504401 dated July 05,


2015, IPG Photonics is pre-qualified for supply, installation and
configuration of Optical Service Transport Platform
(OSTP-DWDM), Erbium Amplifier rack Mount (EAR) and Raman
Amplifier Rack Mount (RAR)- manufactured by IPG Photonics,
Milano, Italy plant- as conforming to National Grid SA
specification # 48-TMSS-08 with the following condition:
Ten (10) years Extended Warranty as confirmed through IPG
Letter # NIL dated 2nd April 2014 shall be applicable for all
supplies made to the Company by IPG Photonics, Milano, Italy
plant.
Total =

39

.3

39. 3. 1

SYNCHRONOUS DIGITAL HIERARCHY (SDH) EQUIPMENT


SYSTEM INTEGRATION AND TESTING OF SDH EQUIPMENT

Applicable Standards:

48-TMSS-09

Page 234 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Automation Co. Ltd

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-01367-01-30504401 dated 8th
March-2015, the manufacturer is prequalified for Integration
(Assembly) & Testing of Communication Equipment from Original
Equipment Manufacturer (OEM) type tested & approved by
SEC/National Grid SA as conforming to National Grid SA
specification # 48-TMSS-09, Rev.0 with the following condition:
Only for Integration (Assembly) & Testing of Communication
Equipment from Original Equipment Manufacturer (OEM) type
tested & approved by SEC/National Grid SA.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing and workmanship, as confirmed
by the manufacturer through their letter #
PSN/TLE/0517/09/2014,dt: 15/09/2014.

Alstom Grid Automation Unit Cogelex

Saudi Arabia-Jeddah

Yes

Based on S&SD letter # 15-00240-02-30504401 dated March


03 2015, the manufacturer is prequalified for Integration
(assembly) & Testing of Communication & SCADA equipment as
conforming to National Grid SA specification # 48-TMSS-09,
Rev.0 with the following conditions:
Only for integration (assembly) & testing of communication &
SCADA equipment from original equipment manufacturer (OEM)
type tested and approved by SEC/National Grid SA.
Ten (10) years extended warranty in respect of the defects
due to design, manufacturing, installation and workmanship
from the date of the Provisional Acceptance Certificate (PAC)
of the first turnkey project (in case of contract award) and from
the date of first delivery in case of direct material supply order
shall be provided as confirmed by the manufacturer through
their letter # RN-2013-12-3 NMS/1 dated December 03, 2013.
Total =

39. 3. 2

SDH EQUIPENT/SYSTEM

Applicable Standards:
Coriant Gmbh

GERMANY-Berlin

Yes

48-TMSS-09
- Previously Nokia Solutions and Network BV (NSN)
- Approved for SDH equipment (hiT 7080, hiT 7070, hiT 7065,
hiT 7060, hiT 7035 and TNMS)
Total =

39

.6

39. 6. 0

FIBER OPTIC CONNECTING DEVICES & PASSIVE COMPONENTS


FIBER OPTIC CONNECTING DEVICES & PASSIVE COMPONENTS

Applicable Standards:

48-TMSS-12

Page 235 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Amwaj Telecommunication Manufacturing Co.

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-00581-02-30504401 dated April 21,
2015, it is pre-qualified for Telecommunication & Fiber Optic
Passive Products (Frame, Box, Rack, etc.) with the following
condition:
Seven (7) years extended warranty from the date of PAC of
the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by Amwaj Telecom MFG. Co. letter dated
09/06/2010.

39

.8

39. 8. 0

39

.9

39. 9. 1

39. 9. 2

Total =

Total =

Total =

DC POWER SYSTEMS
DC POWER SYSTEMS

Applicable Standards:
EXIDE CORP.

United States-PA

Yes

HARMER & SIMMONS

United Kingdom-ESSEX

Yes

LORAIN PRODUCTS INTERNATIONAL SALES

United States-LOARIN

Yes

SAFT POWER SYSTEMS SAS

FRANCE

Yes

Previously SAFT-NIFE

TELEPHONE EXCHANGE
PAX (TELEPHONE EXCHANGE)

Applicable Standards:
ALCATEL

FRANCE

Yes

NORTEL

CANADA

Yes

SIEMENS

GERMANY

Yes

TELEPHONE EQUIPMENT PABXS AND ACCESSORIES

ERICSON

39. 9. 3

Total =

Applicable Standards:
SWEDEN

PABXS TELEPHONE SETS, KEY SYSTEMS

Yes

Applicable Standards:
MITEL CORP.

CANADA

Yes

Page 236 of 244

SER

39. 9. 4

39. 9. 5

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

PABXS TELEPHONE SETS, COMMUNICATION CABLES AND ACCESSORIES

. 10

39. 10. 0

39

. 11

39. 11. 1

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

Total =

Total =

Total =

Applicable Standards:

ALCATEL NV

FRANCE-PARIS

Yes

AT & T

United States-NEW YORK

Yes

NORTHERN TELECOM

CANADA

Yes

PHILIPS

HOLLAND

Yes

SIEMENS

GERMANY

Yes

CABLING ACCESSORIES

Applicable Standards:
RAYCHEM

39

FACTORY LOCATION

United States-CA

Yes

POWER LINE CARRIER EQPT.


POWER LINE CARRIER EQPT.

Applicable Standards:
ABB

SWEDEN

Yes

ABB INFOCOM LTD.

FRANCE-TURGI

Yes

AREVA

FRANCE

Yes

GENERAL ELECTRIC CO.

United States-LYNCHBURG, VIRGINIA

Yes

NERA

NORWAY

Yes

SIEMENS

GERMANY

Yes

TELE-PROTECTION SYSTEM
TELEPROTECTION SYSTEM

Applicable Standards:
ABB

SWEDEN

Yes

AREVA

FRANCE

Yes

Page 237 of 244

SER

39. 11. 2

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

. 12

39. 12. 0

39

. 13

39. 13. 0

39

. 14

Pre-Qualified
Manufacturers
By SEC

DIMAT

SPAIN-Barcelona

Yes

SIEMENS

GERMANY

Yes

CABLE ISOLATION EQUIPMENT

REMARKS
Based on TS&SD Letters# 09-01439-2-03032301 dated 7th July
2009 & 10-00845-1-03032301 dated April 04, 2010. It is prequalified for Tele-protection Equipment type TPU-1 with the
following conditions:
Five (5) years Extended Warranty.

Total =

Total =

Total =

Total =

Applicable Standards:
POSITRON INDUSTRIES

39

FACTORY LOCATION

CANADA-MONTREAL

Yes

VF INTERFACE EQUIPMENT
VF INTERFACE EQUIPMENT

Applicable Standards:
ABB INFOCOM LTD.

SWITZERLAND-TURGI

Yes

TELLABS INC.

United States-N/A

Yes

RADIO/PAGING EQUIPMENT (MOBILE FIXED)


RADIO/PAGING EQUIPMENT (MOBILE FIXED)

Applicable Standards:

ELECTRONIA

Saudi Arabia-AL-KHOBAR

Yes

GE/ERICSON

United States-N/A

Yes

GLENAYRE

CANADA- BC

Yes

KENWOOD

United States-CALIFORNIA

Yes

MOTOROLA

United States-SCHAMBURG IL

Yes

NEC

United States

Yes

NOKIA

FINLAND

Yes

PHILIPS

United Kingdom-CAMBRIDGE

Yes

TEST EQUIPMENT

Page 238 of 244

SER

39. 14. 0

39

. 15

39. 15. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

TEST EQUIPMENT

. 16

39. 16. 0

39

. 17

39. 17. 0

ACTERNA

United States

Yes

ANDO ELECTRIC CO. LTD

JAPAN-TOKYO

Yes

HEWLETT PACKARD CO.

United States

Yes

IFR

United States-N/A

Yes

PHILIPS

United Kingdom-CAMBRIDGE

Yes

ROHDE & SCHWARZ

GERMANY-N/A

Yes

TREND

SPAIN

Yes

WANDEL & GOLTERMAN GMBH CO.

WEST GERMANY

Yes

. 18

REMARKS

Total =

Total =

Total =

Total =

TEST EQUIPMENT (FIBER OPTIC RELATED)


TEST EQUIPMENT (FIBER OPTIC RELATED)

Applicable Standards:
JAPAN-TOKYO

Yes

TEST EQUIPMENT (RADIO RELATED)


TEST EQUIPMENT (RADIO RELATED)

Applicable Standards:
BIRD

United States-SOLON

Yes

MARCONI

United Kingdom-N/A

Yes

TEST EQUIPMENT (RADIO/PAGING RELATED)


TEST EQUIPMENT (RADIO/PAGING RELATED)

NEC

39

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

ANRITSU CORPORATION

39

FACTORY LOCATION

Applicable Standards:
United States

Yes

RADIO/PAGING EQUIPMENT (ACCESSORIES)

Page 239 of 244

SER

39. 18. 0

39

. 19

39. 19. 0

39

. 20

39. 20. 0

40
40

.1

40. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

RADIO/PAGING EQUIPMENT (ACCESSORIES)

Pre-Qualified
Manufacturers
By SEC

REMARKS

Applicable Standards:

ALLEN

United States-DALLAS TEXAS

Yes

ANDREW

United States- IL

Yes

ANTENNA SPECIALIST (AS)

United States- DALLAS TEXAS

Yes

CELWAVE

United States

Yes

DECIBEL

United States-DALLAS TEXAS

Yes

FLEXWELL

United States-N/A

Yes

JAYBEAM

United Kingdom- NORTHAMPTON

Yes

RADIO SPARES (RS)

United Kingdom-NORTHANTS

Yes
Total =

Total =

Total =

UHF RADIO
UHF RADIO

Applicable Standards:
ALCATEL

FRANCE

Yes

ASCOM

United Kingdom

Yes

SIMOCO

United Kingdom

Yes

HIGH DIGITAL SUBSCRIBER LINE (HDSL)


HIGH DIGITAL SUBSCRIBER LINE (HDSL)

Applicable Standards:
ABB

SWEDEN

Yes

NOKIA

FINLAND

Yes

NORTEL

CANADA

Yes

FIRE PROTECTION SYSTEM

FM 200 SYSTEM
GAS CYLINDERS & ACCCESSORIES

Applicable Standards:

Page 240 of 244

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

DUEPOINT

United States

Yes

GREAT LAKES

United States

Yes

REMARKS

Total =
40. 1. 2

EQUIPMENT

Applicable Standards:
Yes

Based on TS&SD Letter # 10-2425/02-03032301 dated


31/08/2010, it is pre-qualified for HFC227ea system (FM 200)
as confirming to SEC specification # TES-B-106.05.

ANSUL

United States

Yes

LOCAL AGENT AL-BILAD

CHEMETRON

United States

Yes

LOCAL AGENT HEBA

FENWAL

United States

Yes

LOCAL AGENT ENERGY HOUSE

FIGGIE

United States

Yes

FIKE

United States

Yes

FIREATER

United States

Yes

HYGOOD

United States

Yes

KIDDE

United States

Yes

Minimax

GERMANY-Bad Oldesloe

Yes

Based on S&SD Letter 12-02704-02-30504001 dated February


19, 2012. It is pre-qualified for Fire Protective Signaling Panel
as conforming to SEC Specification # 90-TMSS-01 Rev.0 with
the following condition:
All Type, Routine and Special testes shall be carried out on the
first batch of Fire Protective Signaling Panel in an Independent
Testing Laboratory in the presence of three (3) SEC Engineers
& one (1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated January 09,
2011.
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order as confirmed
through Minimax-Germany letter # NIL dated January 09,
2011.

Siemens Building Technologies

United States-Buffalo Grove

Yes

Based on TS&SD Letter # 10-2425/02-03032301 dated


31/08/2010, it is pre-qualified for HFC227ea system (FM 200)
as confirming to SEC specification # TES-B-106.05, Rev.0
Total =

11

Page 241 of 244

SER

40

.2

40. 2. 1

40

.3

40. 3. 1

40

.4

40. 4. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

WATER SPRAY SYSTEM


DELUGE VALVE, SPRAY NOZZLE, ALARM VALVE AND SPRINKLERS

Applicable Standards:

GRINNEL

United States

Yes

RELIABLE

United States

Yes

SPRAYSAFE

United States

Yes

VIKING

United States

Yes

WATTS

United States

Yes

LOCAL AGENT AL-BILAD

LOCAL AGENT AL-BILAD

Total =

Total =

CARBON DIOXIDE (CO2) SYSTEM


GAS CYLINDERS & ACCCESSORIES

Applicable Standards:
CARDOX

United States

Yes

LOCAL AGENT HEBA

CHEMETRON

United States

Yes

LOCAL AGENT HEBA

FIKE

United States

Yes

...

HYGOOD

United States

Yes

KIDDE

United States

Yes

LOCAL AGENT ENERGY HOUSE

FIRE FIGHTING WATER PUMPS


FIRE WATER PUMPS & ACCESSORIES

Applicable Standards:
AURORA

United States

Yes

LOCAL AGENT SAUDI PUMP >= 500 GPM

FAIRBANK MORSE

United States

Yes

LOCAL AGENT SAUDI PUMP >=500GPM

FLOWAY

United States

Yes

ITT

United States

Yes

PEERLESS

United States

Yes

PETTERSON

United States

Yes

REDDY BUFFALOU

United States

Yes

WORTHINGTON

United States

Yes

LOCAL AGENT SAUDI PUMP >=500GPM

LOCAL AGENT SAUDI PUMP >=500GPM

Page 242 of 244

SER

40

.5

40. 5. 1

40

.6

40. 6. 1

40. 6. 2

40. 6. 3

40. 6. 4

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

Total =

Total =

Total =

Total =

Total =

FOAM SYSTEM
FOAM SYSTEM & ACCESSORIES

Applicable Standards:
ANGUS

United Kingdom

Yes

CHEMGUARD

United States

Yes

LOCAL AGENT NAFISCO

NATIONAL FOAM

United States

Yes

LOCAL AGENT HEBA

FIRE EXTINGUISHER
PORTABLE / MOBILE

Applicable Standards:
HEBA

Saudi Arabia

Yes

SFFECO

Saudi Arabia

Yes

PORTABLE FIRE EXTINGUISHER, CO2 TYPE

Applicable Standards:
ANSUL

United States

Yes

LOCAL AGENT AL-BILAD >=5 LBS

KIDDE

United States

Yes

>=5 LBS

SENTRY

United States

Yes

LOCAL AGENT AL-BILAD >=5 LBS

PORTABLE FIRE EXTINGUISHER, DRY CHEMICAL TYPE

Applicable Standards:

ANSUL

United States

Yes

LOCAL AGENT AL-BILAD >=2 LBS

SENTRY

United States

Yes

LOCAL AGENT AL-BILAD >=2 LBS

PORTABLE FIRE EXTINGUISHER, WATER TYPE

SENTRY

Applicable Standards:
United States

Yes

LOCAL AGENT AL-BILAD >=2.5 LBS

Page 243 of 244

SER

40

.7

40. 7. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FIRE DETECTION AND ALARM SYSTEM


EQUIPMENT & ACCESSORIES

Applicable Standards:
AUTOCALL (GRINNEL)

United States

Yes

EDWARDS

CANADA

Yes

MIRETONE

United States

Yes

NOTIFIRE

United States

Yes

LOCAL AGENT -NAFISCO

Siemens Building Technologies Fire Safety

United States-New Jersey

Yes

Originaly was PYROTRONICS from USA.


Local Agents are: Siemens Building Technologies (SBT) &
SASEEQ

SIMPLEX

United States

Yes

LOCAL AGENT NAFISCO

THORN

United Kingdom

Yes

LOCAL AGENT AL-BILAD

Total =

Page 244 of 244