Sei sulla pagina 1di 14

5.3.

4 Time Current Curves

TCC for Phase OC Protection for KM5806

1000
KM5806
CABLE

KM5806
FULL LOAD
CURVE
RUNNING
OL LIMIT

100

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

VCB:52KM5806
OLR:49KM5806

STARTING
OL LIMIT

VCB:52TRM1S
OCR: 51PTRM1S

TIME (S)

10

VCB:52TRM1P
OCR: 51PTRM1P

VCB:52KM5806
OCR: 51PKM5806
OCR: 50PKM5806

CTI=528ms

0.1

KM5806
STARTING
CURVE

0.01
1.00

F8:(DLG) 20.34kA (max)

10.00

100.00
1000.00 10000.00 100000.00
CURRENT (A) AT 6.9kV BASE

Figure 5.5 Time-Current Curve for Phase Protection of KM5806

Chapter 5-Protective Device Coordination

Page 329

TCC for Phase OC Protection for YM7601


KM5806
CABLE

10000
YM7601
FULL LOAD
CURVE

1000

RUNNING
OL LIMIT
VCB:52YM7601
OCR: 51PYM7601
OCR: 50PYM7601

VCB:52TRM1P
OCR: 51PTRM1P
OCR: 50PTRM1P

100

VCB:52TRM1S
OCR: 51PTRM1S
OCR: 50PTRM1S

VCB:52YM7601
OLR:49YM7601

TIME(S)

(240mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

10

STARTING
OL
LIMIT

CTI=623ms

0.1
YM7601
STARTING
CURVE

0.01
1.00

@F9,(DLGFault IB) 17.85kA (MAX)

10.00
100.00
1000.00 10000.00 100000.00
CURRENT (A) AT 6.9kV BASE

Figure 5.6 Time-Current Curve for Phase Protection of YM7601

Chapter 5-Protective Device Coordination

Page 330

TCC for Phase Overcurrent Protection for KM8639


1000

KM8639
CABLE
(185mm2
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

KM8639
FULL LOAD
CURVE
RUNNING
OL LIMIT

100

VCB:52KM8639
OCR: 51PKM8639
OCR: 50PKM8639

VCB:52TRM1P
OCR: 51PTRM1P
OCR: 50PTRM1P

VCB:52KM8639
OLR:49KM8639
STARTING
OL LIMIT

TIME(S)

10

VCB:52TRM1S
OCR: 51PTRM1S
OCR: 50PTRM1S

CTI=500ms

0.1

KM8639
STARTING
CURVE

0.01
1.00

@F10,(DLGFault IB) 21.5kA MAX

10.00
100.00
1000.00 10000.00 100000.00
CURRENT (A) AT 6.9kV BASE

Figure 5.7 Time-Current Curve for Phase Protection of KM8639

Chapter 5-Protective Device Coordination

Page 331

TCC for Phase Overcurrent Protection for KM8601

1000
KM8601
CABLE

RUNNING
OL
LIMIT

100

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

VCB:52KM8601
OCR:51KM8601
OCR:50KM8601
VCB:52KM8601
OLR:49KM8601

VCB:52TRM1P
OCR: 51PTRM1P
OCR: 50PTRM1P

KM8601
OPERATING
CURVE

VCB:52TRM1S
OCR: 51PTRM1S
OCR: 50PTRM1S

TIME (S)

10

CTI=567ms

0.1

0.01
1.00

@F11, (DLGFault IB) 19.2kA (MAX)

10.00

100.00
1000.00 10000.00 100000.00
CURRENT (A) AT 6.9kV BASE

Figure 5.8 Time-Current Curve for Phase Protection of


KM8601

Chapter 5-Protective Device Coordination

Page 332

TCC for Phase Overcurrent Protection for PC01


PC01
CABLE
(185mm2
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

1000
VCB:52PC01
OCR: 51PPC01
OCR: 50PPC01

PC01
OPERATING
CURVE

100

VCB:52TRM1P
OCR: 51PTRM1P
OCR: 50PTRM1P

1800kVAR
CAPACITOR
DAMAGE
CURVE
(10%
Probability)

VCB:52TRM1S
OCR: 51PTRM1S
OCR: 50PTRM1S

TIME (S)

10

CTI=471ms

0.1

@F12,(SLGFault) 22.49 kA (MAX)

0.01
1

10

100
1000
10000
CURRENT (A) AT 6.9kV BASE

100000

Figure 5.9 Time-Current Curve for Phase Protection of PC001

Chapter 5-Protective Device Coordination

Page 333

TCC for Phase Overcurrent Protection for VM5814

1000
MCCB:52KM5814
LTD:290A @T:12s
STD:800% of LTD (6x290A)=2320A
@T:0.3s
INST:800% of 400A =3200A

KM5814
CABLE

MC5814:
OLR:49KM5814
PU:5.25
TD:25

100

(150mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

KM5814
OPERATING
CURVE

10

TIME (S)

VCB:52TRL3AS
OCR: 51PTRL3AS
OCR: 50PTRL3AS

0.1

@F15,(DLGFault IB) 5.256kA

0.01
1

10

100
1000
10000
CURRENT (A) AT 480V BASE

100000

Figure 5.10 Time-Current Curve for Phase Protection of


VM5814
Chapter 5-Protective Device Coordination

Page 334

TCC for Phase Overcurrent Protection for MNDB

1000
MNDB
CABLE

MCCB:52MNDB
LTD:400A @T:12s
STD:200% of LTD (2x400A)=800A
@T:0.3s
INST:300% of 400A =1200A

(240mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

100
MAX 400A

10
TIME (S)

VCB:52TRL3AS
OCR: 51PTRL3AS
OCR: 50PTRL3AS

SHORT CIRCUIT
WITHSTAND
25kA 1 sec

@F18,(DLGFault IB)
29382A (MAX)

0.1

CTI=270ms

0.01
1

10

100
1000
10000
CURRENT (A) AT 480V BASE

100000

Figure 5.11 Time-Current Curve for Phase Protection of


MNDB
Chapter 5-Protective Device Coordination

Page 335

TCC for Phase Overcurrent Protection for TRL3A

1000

TL2

3MVA (OA) FULL LOAD


CURRENT (3,608)

VCB: 52TRL3AP
OCR: 51PTRL3AP
CT Ratio: 630:1
ANSI VI
51Pickup: 0.43
51TD: 5
OCR:50PTRL3AP
50Pickup: 3.8
50TimeDelay:0.35

100

VCB: 52TRL3AP
OCR: 51PTRL3AP
CT Ratio: 630:1
ANSI VI
51Pickup: 0.43
51TD: 5
OCR:50PTRL3AP
50Pickup: 3.8
50TimeDelay:0.35

TIME (s)

10

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

TRL3A (3MVA)
THERMAL
LIMIT

TRL3A
(3MVA)
MECH.
LIMIT

SC WITHSTAND
RATING
480V SWGR

TRM1 INRUSH
CURVE

CTI
=200ms

0.1
CTI
=200ms

CTI
=233ms

0.01
1

@F6,(3PHFault) 43.54 kA

100

10000

1000000

CURRENT (A) AT 480V BASE


Figure 5.12 Time-Current Curve for Phase Protection of
TRL3A
Chapter 5-Protective Device Coordination

Page 336

TCC for Phase Overcurrent Protection for SM8645


1000
KM8645
CABLE

MCCB:52KM8645
LTD:290A @T:12s
STD:800% of LTD (6x290A)=2320A
@T:0.3s
INST:200% of LRA =3124.57A

100

(240mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

MC:
OLR:49KM86445
PU:5.25
TD:25

VCB:52TRL3BS
OCR: 51PTRL3BS
OCR: 50PTRL3BS

TIME (S)

10

KM8645
OPERATING
CURVE

CTI=220ms

0.1

0.01
1.00

@F21,(DLGFault IB) 10.03kA (MAX)

10.00

100.00
1000.00 10000.00 100000.00
CURRENT (A) AT 480V BASE

Figure 5.13 Time-Current Curve for Phase Protection of


SM8645
Chapter 5-Protective Device Coordination

Page 337

TCC for Phase Overcurrent Protection for TRL3B

1000
TL3

3MVA (OA) FULL LOAD


CURRENT (3,608)
VCB: 52TRL3BP
OCR: 51PTRL3BP
CT Ratio: 630:1
ANSI VI
51Pickup: 0.43
51TD: 5

100

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

VCB: 52TRL3BS
OCR: 51PTRL3BS
CT Ratio: 4000:1
ANSI VI
51Pickup: 0.81
51TD: 1

TRL3B
(3MVA)
THERMAL
LIMIT
TRL3B
(3MVA)
MECH.
LIMIT

TIME (s)

10

CTI
=200ms

CTI
=200ms
TRM1 INRUSH
CURVE

0.1

@F7,(3PHFault) 43.5 kA
@F5,(SLGFault) 22 kA (MAX)

0.01
1

100

10000

1000000

CURRENT (A) AT 480V BASE


Figure 5.14 Time-Current Curve for Phase Protection of
TRL3B
Chapter 5-Protective Device Coordination

Page 338

TCC for Phase OC Protection for TRM1 and 6.9kV Bus


1000

TL1
40MVA (OA) FULL LOAD
CURRENT (3,346.95A)

VCB: 52TRM1P
OCR: 51PTRM1P
CT Ratio: 2000:1
ANSI VI
51Pickup: 1
51TD: 3.5
OCR:50PTRM1P
50Pickup:6.42
50TimeDelay:0.65

100

VCB: 52TRM1S
OCR: 51PTRM1S
CT Ratio: 4000:1
ANSI VI
51Pickup: 0.92
51TD: 2
OCR: 50PTRM1S
50Pickup:3.19
50TimeDelay:0.55

TIME (s)

10

(630mm
5per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT
40MVA
THERMAL
LIMIT

40MVA
MECH.
LIMIT

TRM1
INRUSH
CURVE

SC WITHSTAND
RATING
6.9kV SWGR

0.1

@F3,(3PHFault)
16.67 kA

0.01
1

10

100
1000
10000
CURRENT (A) AT 6.9kV BASE

100000

Figure 5.15 Time-Current Curve for Phase Protection of TRM1

Chapter 5-Protective Device Coordination

Page 339

TCC for Ground Overcurrent Protection for TRL3A and MCC8


1000

TL2
GRFT: 50GKM5814
50Pickup: 58A
50TimeDelay:0.1s

GRFT: 50GMNDB
50Pickup: 80A
50TimeDelay:0.1s

100

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

TRL3A (3MVA)
THERMAL
LIMIT

OCGR: 50GTRL3AS
50Pickup: 0.27xIn
50Puckup
current: 1082.5 A
50TimeDelay:0.3s

TRL3A
(3MVA)
MECH.
LIMIT

10

TIME (s)

SC WITHSTAND
RATING
480V SWGR

TRM1
INRUSH
CURVE

CTI=200ms

0.1
@F6,(DLG-N) 48.5 kA
@F6,(SLGFault) 46.kA
@F18 ,(SLG Fault @ MNDB) 25.95kA
@F18,(DLG-N@ MNDB) 24.37kA
@F15,(SLGFault@ VM5814) 3.8kA
@F15,(DLG-N@ VM5814) 2.8kA

0.01

100

10000

1000000

CURRENT (A) AT 480V BASE


Figure 5.16 Time-Current Curve for Ground Protection of
TRL3A and MCC8

Chapter 5-Protective Device Coordination

Page 340

TCC for Ground Overcurrent Protection Coordination for


TRL3B and MCC9 Load
1000
TL3

100
GRFT: 50GYM7607
50Pickup: 68A
50TimeDelay:0.1s

TIME (s)

10

(185mm
1per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

GRFT: 50GSM8645
50Pickup: 58A
50TimeDelay:0.1s

TRL3B (3MVA)
THERMAL
LIMIT

OCGR: 50GTRL3BS
50Pickup: 0.27xIn
50Puckup
current: 1082.5 A
50TimeDelay:0.3s

TRL3B
(3MVA)
MECH.
LIMIT (58%
adjusted)

CTI
=200ms

0.1
@F7,(DLG-N) 48.4 kA
@F6,(SLGFault) 46.kA
@F21 ,(SLG Fault @ SM8645)7.67kA
@F21,(DLG-N@ SM8645) 6.15kA
@F20,(SLGFault@ YM7607) 21.86kA

0.01 @F20,(DLG-N@ YM7607)20.29kA


1
100

10000

1000000

CURRENT (A) AT 480V BASE


Figure 5.17 Time-Current Curve for Ground Protection of
TRL3B and MCC9
Chapter 5-Protective Device Coordination

Page 341

TCC for Ground OC Protection for TRM1 and 6.9kV Bus


1000
TL1

(630mm
5per Ph)
THERMAL
OL
&
SHORT
CIRCUIT
LIMIT

50GKM8601
50GKM8639

100
50GKM5806
40MVA
THERMAL
LIMIT

50GYM7601
and
50GPC001

TIME (s)

10

TRM1
INRUSH
CURVE
SC WITHSTAND
RATING
6.9kV SWGR

50GTRL3A
and
50GTRL3B
OCGR: 50GTRM1
50Pickup: 0.25xIn
50Puckup
current: 1004 A
50TimeDelay:0.25s

0.1

SLG-MAX(PC001) 22.495 kA

SLG-MIN(YM7601) 16.43 kA
DLG-N MAX(PC001) 26 kA
DLG-N MIN(KM8601) 15.68 kA

0.01
1

10

100

1000

10000

100000

CURRENT (A) AT 6.9kV BASE

Figure 5.18 Time-Current Curve for Ground Protection of


TRM1 and 6.9kV Switchgear

Chapter 5-Protective Device Coordination

Page 342

Potrebbero piacerti anche