Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
STUDENTTOPIC
Fig 1
Grouping
Factor
(0.65)
Consumer
unit
Thermal
insulation
Ambient
temperature
Factor
(0.5)
for distances
over 0.5 metres
Factor
(0.94)
(0.725)
BS 3036 fuse
Load
Grouping, Cg
This factor is found by reference to Table 4B1 in
Appendix 4. Table 4B2 is used where mineral
insulated cables are installed on perforated cable tray.
Thermal insulation, Ci
Where a cable is in contact with thermal insulation on
one side only, the current-carrying capacity of the
cable should be calculated using Reference Method
4, which is described in Appendix 4 (Table 4A) of BS
7671.
Where a cable is totally surrounded by thermal
insulation for a distance greater than 0.5 metres, the
current-carrying capacity should be taken, in the
absence of further information, as 0.5 times the
current-carrying capacity for that cable when using
Installation Method 1 (open and clipped direct).
Where a cable is totally surrounded by thermal
insulation for a distance of 0.5 metres or less, Table
52A in BS 7671 gives derating factors which must be
applied.
Rewireable fuse (BS 3036) factor, Cr
Where a rewireable fuse to BS 3036 is used, a further
correction factor of 0.725 is applied, due to the poor
fusing factor of rewireable fuses.
It >
In
Ca x Cg x Ci x Cr
It >
In
Ci x Cr
Worked example
1 A 6kW load is to be supplied at 230 V by a PVC sheathed and
insulated twin and cpc copper cable, 8 metres in length. The cable is
clipped on the surface through an area with an ambient temperature
of 40C and is grouped with three other cables of similar size and
loading. The protection is by means of a BS 3036 fuse. Calculate the
minimum cable size required (it is assumed in this example that all the
correction factors need to be applied).
Answer
Design current,
Ib
Tabulated current, It
>
In
correction factors
Ca = 0.94
It
>
In
Ca x Cg x Cr
>
In
>
67.7 amps
From Table 4D5A (Reference Method 1, column 4), select 16 mm2 cable
which takes 85 amps.
Check volts drop from Table 4D2B (column 3).
volts drop
mV/Am x Ib x L
1000
2.8 x 26 x 8
1000
Conclusion
If you need some practice in calculating the right size
for cables, you might try the examples in the Student
Activities section. In the next issue, well consider this
topic some more. Further information can be obtained
from Appendix 4 of BS 7671, and IEE Guidance Note 6,
Protection Against Overcurrent. For a more simplified
approach, Appendix 6 of the IEE On Site Guide should
be consulted.
W
6000
= = 26 amps
V
230
Volts drop =
mv/a/m x design current, Ib x length of run in metres, L
1000