Sei sulla pagina 1di 56

High Reliable Components for

Power Factor Correction


and Power Quality

It's all about saving your money!

Contents

Power Factor Correction Capacitors

Page 3

Basic Harmonic Filter Reactors

Page 11

Standard Harmonic Filter Reactors

Page 13

Capacitor Switching Contactors

Page 21

Discharge Reactors

Page 27

Power Factor Control Relays

Page 29

Modular Construction System

Page 33

Modules for Power Factor Correction Systems

Page 39

Medium Voltage Capacitors

Page 53

Power Factor Correction Capacitors


Type LKT

Features that matter:


Q Overcurrent up to 2.2 times rated current
Q Inrush current up to 300 times rated current
Q Self-healing type, segmented film technology plus overpressure disconnector
Q Environment-friendly, dry type
Q CO2 emission reduction
Q Safes energy costs
3

Power Factor Correction Capacitors


Type LKT

General Remarks

Life Expectancy

FRAKO Power Factor Correction Capacitors are produced in unique advanced technology and incorporate
a triple safety feature. FRAKO LV WKH UVW FDSDFLWRU
manufacturer who succeeded to combine self-healing
FDSDFLWRU OP ZLWK VHJPHQWHG OP DQG RYHUSUHVVXUH
disconnection. This manufacturing technique guarantees
VLJQLFDQWO\ LPSURYHG RSHUDWLRQDO UHOLDELOLW\ RI FDSDFLtors on power factor correction. We reserve the right to
make alterations which are based on newly acquired
knowledge or which contribute to an improvement in
our products.

Technical Remarks
For the operation of Power Factor Correction Capacitors
three aspects are of utmost importance:
Q High overload capacity
Q Long life expectancy
Q Safe reaction at overload

The use of thoroughly tested material as well as careful


processing ensures quality and a long life expectancy
of the products. FRAKO produces its capacitors accorGLQJ WR RZQ VSHFLFDWLRQV ZKLFK VXUSDVV E\ IDU WKH
requirements of EN 60831-1/2. Quality tests following
each single manufacturing step, verify an outstanding
manufacturing quality. Combined with a unique capacitor
manufacturing technology, FRAKO achieves a worldwide leading durability.
For example, the consistently low power loss over many
\HDUVLVDFKLHYHGE\XVLQJDVSHFLDOPLQHUDOOOHUDQG
stabilizer which can avoid permanent partial discharges
within the dielectric. Vacuum drying and temperature
storage over several days avoid oxygen inclusion, which
would accelerate the aging process of a capacitor. This
means an extra effort in our production which, however,
pays-off with a longer life expectancy.

Safty Features
FRAKO Power Factor Correction Capacitors operate
with triple safety:

Overload Capacity
In networks where the pollution with harmonics is permanently increasing, surplus loads in capacitors have to
be reckoned with. Apart from the higher voltage load it
is especially the higher effective current during network
resonances, that can considerably further stress the
capacitors:

Q Self-healing at over-voltage
Q 5HOLDEOHLQRSHUDWLRQEHFDXVHRIVHJPHQWHGOP
Q An overpressure disconnector disconnects the
capacitors from the mains at the end of their
lifetime or at dangerous overload

Capacitor current

If, for example, the 11th harmonic is present with 8 % of


the rated network voltage, the r.m.s. value of the rated
voltage is only increased by some 0.3 %, but the current
in the capacitors will exceed its rated value by 33 %. It
becomes clear that the ability of a capacitor to withstand
H[FHVVLYHFXUUHQWLVVLJQLFDQWO\JUHDWHUWKDQWKHDELOLW\
to withstand excessive voltage.

6HOIKHDOLQJVHJPHQWHGFDSDFLWRUOP

Therefore FRAKO designs its capacitors as follows:

Patent No. 102005045978

Q Max. overcurrent up to 2.2 times rated current


Q Max. inrush current up to 300 times rated
current
The principle of the overpressure disconnector

To verify the correct functioning of the integrated safety


systems, FRAKO regularly draws sample capacitors
from the production line. A constantly outstanding quality
can be achieved and maintained only this way.
4

Power Factor Correction Capacitors


Type LKT

Voltage Load Capacity

Capacitance and Rating Tolerance

FRAKO Power Factor Correction Capacitors have a load


capacity in accordance with EN 60831-1 and -2 as well
as IEC 831-1 and -2.

+/- 5%

Power Loss

Rated voltage
(in VAC)

300

400

440

480

525

615

Approx. 0.5 Watt / kvar measured at the connecting


terminal including discharge resistors.

8 hours daily

330

440

484

528

578

677

Approx. 0.2 Watt / kvar measured at the capacitor coils.

30 min. daily

345

460

506

552

604

707

5 min.

360

480

528

576

630

738

1 min.

390

520

572

624

683

800

Temperature Class
up to - 40 C; + 65 C

Application
FRAKO manufactures three series of Power Factor
Correction Capacitors: Basic, Standard and Premium.
We recommend Basic Capacitors for networks with low
harmonic content and normal ambient temperature.
Standard Capacitors are recommended for networks with
higher harmonic levels and/or high ambient temperature.
Premium Capacitors should be used for demanding
networks (i. e. networks with very high harmonic levels
and/or very high ambient temperature). All three series
of capacitors are of excellent FRAKO quality. FRAKO
KROGVWKH0DQDJHPHQW6\VWHP&HUWLFDWHISO 9001 and
the Environmental Management System ISO 14001.

Discharging
According to EN 60831, every power capacitor must
have a discharge device which guarantees a discharge
to 75 V within three minutes. FRAKO capacitors have
integrated discharge resistors which guarantee a
discharge to 50 V within one minute.

Accessories for
Power Factor Correction Capacitors
Article-No. Description
Plug-in type connecting terminal for
capacitors with 60 mm and 70 mm,
3-phase

AKD 25/3

31-08002

Plug-in type connecting terminal for


capacitors with 60 mm and 70 mm,
single-phase

AKD 25/2

31-08003

Plug-in type connecting terminal for

Mechanical Construction
Cylindrical aluminium case with mounting stud M12 12,
low loss self-healing dielectric made from segmented
PHWDOOL]HG SRO\SURS\OHQH OP )LOOHG ZLWK D 3&%IUHH
DPH LQKLELWLQJ PLQHUDO OOHU ZLWK DGKHVLYH VWDELOL]HU
and integrated mechanical overpressure disconnector.
Permanently connected external discharge resistors at
the terminals. The connecting terminal, which is available
as an accessory, protects against direct contact of the
fast-on terminals and meets the protection class IP 20.

Type

31-08000

capacitors with 85 mm, 3-phase

AKD 30/3

69-00352

Plastic caps for LKT with 60 mm

LKK 60

69-00350

Plastic caps for LKT with 70 mm

LKK 70

69-00353

Rubber sleeve

LKK

Design
FRAKO Power Factor Correction Capacitors are
available as three-phase capacitors in 3 versions: Basic,
Standard and Premium. The single-phase capacitors are
available as Standard version.

Rating
1.1 - 30 kvar; 300 - 615 V; 50 / 60 Hz (higher voltages on
request!)

Power Factor Correction Capacitors


Type LKT

Technical Data
Technical Data

Basic Capacitor

Standard Capacitor

Premium Capacitor
operated with
operated with
DL-specication
DP-specication

Type

LKT...-DB

LKT...-DP

LKT...-DL

LKT...-DL

Rated reactive power

1.7 - 30 kvar

1.1 - 30 kvar

1.4 - 20 kvar

1.4 - 24.2 kvar

Rated voltage

230 - 525 V

230 - 525 V

400 - 525 V

400 - 615 V

Rated frequency

50 - 60 Hz

50 - 60 Hz

50 - 60 Hz

50 - 60 Hz

Max. overcurrent

1.5 IN
(at rated voltage, 50 Hz)

1.8 IN
(at rated voltage, 50 Hz)

2.2 IN
2.0 IN
(at rated voltage, 50 Hz) (at rated voltage, 50 Hz)

Max. inrush current

200 IN
(at rated voltage, 50 Hz)

250 IN
(at rated voltage, 50 Hz)

300 IN
300 IN
(at rated voltage, 50 Hz) (at rated voltage, 50 Hz)

Temperature class

- 25/D

- 40/+60C continuous

- 40/+65C continuous

- 40/+60C continuous

Max. / min. temperature

+55C / -25C

+60C / -40C

+65C / -40C

+60C / -40C

Max. case temperature

+70C

+75C

+78C

+75C

Test voltage terminal / terminal 2.15 UN for 2 sec.


1.85 UN for 18 sec.

2.15 UN for 2 sec.


1.85 UN for 18 sec.

2.15 UN for 2 sec.


1.85 UN for 18 sec.

2.15 UN for 2 sec.


1.85 UN for 18 sec.

Test voltage terminal / case

3,900 V, 2 sec.

3,900 V, 2 sec.

3,900 V, 2 sec.

3,900 V, 2 sec.

Isolation level

3/8 kV

3/8 kV

3/8 kV

3/8 kV

Mean Life expectancy

100,000 h

130,000 h

170,000 h

130,000 h

Max. humidity

95%

95%

95%

95%

Max. altitude

4,000 m

4,000 m

4,000 m

4,000 m

Number of annual
switching operations

20,000

40,000

60,000

60,000

Discharging level in 60 sec.

50 V

50 V

50 V

50 V

Recommended for

Networks with low


harmonic content and
normal ambient
temperature

Networks with higher


harmonic levels
and / or high ambient
temperature

Demanding networks
Networks with higher
(i. e. very high harmonic harmonic levels
levels and/or very high
and / or high ambient
ambient temperature)
temperature

admissible ambient temperature


mean over 24 h
highest mean over 1 year

maximum

45C
35.0
16

h
M12

M12

M12
50

M12

28.0
h
12

12

Dimensions

35C

17.0

55C
15.0

16

Temperature
class

67 / 77

capacitors with
d = 60 / 70 mm

capacitors with
d = 60 / 70 mm

capacitors with
d = 85 mm

capacitors with
d = 85 mm

for connection with


DWFDEOHSOXJ

spring tension
terminal 2 6 mm2

for connection with


DWFDEOHSOXJ

spring tension
terminal 16 mm2

6.3 0.8 mm

Art.-No. 31-08000

9.5 1.2 mm

Art.-No. 31-08003

plastic cap for capacitors


with d = 60 mm
Art.No. 69-00352
d = 70 mm
Art.No. 69-00350
rubber sleeve
Art.-No. 69-00353
(not available for capacitors
with d = 85 mm)

Power Factor Correction Capacitors


Type LKT...-DB for 50Hz and 60Hz

Basic Capacitors
Capacitor
Type

Dimensions
mm

Article-No.

Rated Reactive Power in kvar at Rated Voltage 50 Hz


230 V

250 V

300 V

400 V

415 V

440 V

2.0
2.4
2.9
3.9
4.9
5.9
7.8
9.8
11.7

2.8
3.5
4.2
5.6
7.0
8.4
11.3
14.1
16.9

5.0
6.25
7.5
10.0
12.5
15.0
20.0
25.0
30.0
5.2
8.3
10.3
12.4
16.5
20.7
24.8

5.6
8.9
11.1
13.3
17.8
22.2
26.7

6.25
10.0
12.5
15.0
20.0
25.0
30.0

3.6
7.3
8.7
11.6
14.5

3.9
7.8
9.4
12.5
15.6

4.4
8.8
10.5
14.1
17.6

460V

480 V

525 V

5.2
10.4
12.5
16.7
20.9

6.25
12.5
15.0
20.0
25.0

Three-phase capacitors
LKT 5.0-400-DB
LKT 6.25-400-DB
LKT 7.5-400-DB
LKT 10.0-400-DB
LKT 12.5-400-DB
LKT 15.0-400-DB
LKT 20.0-400-DB
LKT 25.0-400-DB
LKT 30.0-400-DB

60150
60150
60150
60225
60225
70225
85215
85278
85320

31-10414
31-10400
31-10415
31-10416
31-10401
31-10417
31-10418
31-10402
31-10403

1.7
2.1
2.5
3.3
4.2
5.0
6.7
8.3
9.9

LKT 6.25-440-DB
LKT 10.0-440-DB
LKT 12.5-440-DB
LKT 15.0-440-DB
LKT 20.0-440-DB
LKT 25.0-440-DB
LKT 30.0-440-DB

60150
60225
60225
70225
85278
85278
85278

31-10404
31-10412
31-10405
31-10406
31-10413
31-10407
31-10408

1.7
2.7
3.4
4.1
5.5
6.8
8.2

LKT 6.25-525-DB
LKT 12.5-525-DB
LKT 15.0-525-DB
LKT 20.0-525-DB
LKT 25.0-525-DB

60225
70225
70225
70265
85278

31-10409
31-10410
31-10419
31-10420
31-10411

Capacitor
Type

Dimensions
mm

Article-No.

Rated Reactive Power in kvar at Rated Voltage 60 Hz


230 V

250 V

300 V

400 V

2.3
2.9
3.5
4.7
5.9
7.0
9.4
11.7
14.1

3.4
4.2
5.0
6.8
8.4
10.1
13.5
16.9
20.3

6.0
7.5
9.0
12.0
15.0
18.0
24.0
30.0
36.0

415 V

440 V

6.7
10.7
13.3
16.0
21.4
26.7
32.0

7.5
12.0
15.0
18.0
24.0
30.0
36.0

460V

480 V

525 V

5.8
11.5
13.8
18.4
23.0

6.3
12.5
15.1
20.1
25.1

7.5
15.0
18.0
24.0
30.0

Three-phase capacitors
LKT 5.0-400-DB
LKT 6.25-400-DB
LKT 7.5-400-DB
LKT 10.0-400-DB
LKT 12.5-400-DB
LKT 15.0-400-DB
LKT 20.0-400-DB
LKT 25.0-400-DB
LKT 30.0-400-DB

60150
60150
60150
60225
60225
70225
85215
85278
85320

31-10414
31-10400
31-10415
31-10416
31-10401
31-10417
31-10418
31-10402
31-10403

2.0
2.5
3.0
4.0
5.0
6.0
7.9
9.9
11.9

LKT 6.25-440-DB
LKT 10.0-440-DB
LKT 12.5-440-DB
LKT 15.0-440-DB
LKT 20.0-440-DB
LKT 25.0-440-DB
LKT 30.0-440-DB

60150
60225
60225
70225
85278
85278
85278

31-10404
31-10412
31-10405
31-10406
31-10413
31-10407
31-10408

2.0
3.3
4.1
4.9
6.7
8.2
9.8

LKT 6.25-525-DB
LKT 12.5-525-DB
LKT 15.0-525-DB
LKT 20.0-525-DB
LKT 25.0-525-DB

60225
70225
70225
70265
85278

31-10409
31-10410
31-10419
31-10420
31-10411

6.25
9.9
12.4
14.9
19.8
24.8
29.8
4.4
8.7
10.5
13.9
17.4

5.3
10.5
12.6
16.9
21.1

Power Factor Correction Capacitors


Type LKT...-DP/...-EP for 50Hz

Standard Capacitors
Capacitor
Type

Dimensions Article-No.
mm

Rated Reactive Power in kvar at Rated Voltage 50 Hz


230 V

250 V

300 V

400 V

415 V

440 V

480V

525 V

Three-phase capacitors
LKT 7.1-300-DP
LKT 14.2-300-DP
LKT 21.3-300-DP

60225
70265
85278

31-10523
31-10524
31-10525

4.2
8.3
12.5

4.9
9.9
14.8

7.1
14.2
21.3

LKT 5.0-400-DP
LKT 10.0-400-DP
LKT 12.5-400-DP
LKT 15.0-400-DP
LKT 20.0-400-DP
LKT 25.0-400-DP

60150
60225
70225
70265
85278
85278

31-10500
31-10501
31-10502
31-10503
31-10504
31-10505

1.7
3.3
4.2
5.0
6.7
8.3

2.0
3.9
4.9
5.9
7.8
9.8

2.8
5.6
7.0
8.4
11.3
14.1

LKT 3.8-440-DP
LKT 10.0-440-DP
LKT 12.5-440-DP
LKT 15.0-440-DP
LKT 20.0-440-DP
LKT 25.0-440-DP
LKT 28.2-440-DP
LKT 30.0-440-DP

60150
60225
70225
70225
85278
85278
85320
85320

31-10534
31-10508
31-10507
31-10506
31-10512
31-10510
31-10535
31-10509

1.0
2.7
3.4
4.1
5.5
6.8
7.7
8.2

3.1
8.3
10.3
12.4
16.5
20.7
23.3
24.8

3.4
8.9
11.1
13.3
17.8
22.2
25.0
26.7

3.8
10.0
12.5
15.0
20.0
25.0
28.2
30.0

LKT 15.5-480-DP
LKT 18.0-480-DP

70225
70265

31-10513
31-10522

3.6
4.2

10.8
12.5

11.6
13.5

13.1
15.1

15.5
18.0

LKT 10.0-525-DP
LKT 12.5-525-DP
LKT 15.0-525-DP
LKT 20.0-525-DP
LKT 25.0-525-DP

70225
70225
70265
85278
85278

31-10517
31-10516
31-10520
31-10521
31-10519

5.8
7.3
8.7
11.6
14.5

6.3
7.8
9.4
12.5
15.6

7.0
8.8
10.5
14.1
17.6

8.3
10.4
12.5
16.7
20.9

5.0
10.0
12.5
15.0
20.0
25.0

10.0
12.5
15.0
20.0
25.0

Single-phase capacitors

LKT 3.33-440-EP
LKT 4.17-440-EP
LKT 5.0-440-EP
LKT 9.4-440-EP

6090
60138
60138
70138

31-10526
31-10527
31-10528
31-10511

0.9
1.1
1.4
2.6

2.8
3.4
4.1
7.8

3.0
3.7
4.4
8.4

3.3
4.2
5.0
9.4

LKT 2.4-480-EP
LKT 3.33-480-EP
LKT 3.6-480-EP
LKT 4.8-480-EP
LKT 6.0-480-EP

6090
6090
60138
60138
60138

31-10529
31-10530
31-10531
31-10515
31-10514

0.6
0.8
0.8
1.1
1.4

1.7
2.3
2.5
3.3
4.2

1.8
2.5
2.7
3.6
4.5

2.0
2.8
3.0
4.0
5.0

2.4
3.3
3.6
4.8
6.0

LKT 2.8-525-EP
LKT 3.33-525-EP
LKT 8.33-525-EP

6090
60138
70138

31-10532
31-10533
31-10518

1.6
1.9
4.8

1.8
2.1
5.2

2.0
2.3
5.9

2.3
2.8
7.0

2.8
3.4
8.3

Power Factor Correction Capacitors


Type LKT...-DP/...-EP for 60Hz

Standard Capacitors
Capacitor
Type

Dimensions
mm

Article-No.

Rated Reactive Power in kvar at Rated Voltage 60 Hz


230 V

250 V

300 V

400 V

415 V

440 V

460V

480 V

525 V

Three-phase capacitors
LKT 7.1-300-DP
LKT 14.2-300-DP
LKT 21.3-300-DP

60225
70265
85278

31-10523
31-10524
31-10525

5.0
10.0
15.0

5.9
11.8
17.7

8.5
17.0
25.5

LKT 5.0-400-DP
LKT 10.0-400-DP
LKT 12.5-400-DP
LKT 15.0-400-DP
LKT 20.0-400-DP
LKT 25.0-400-DP

60150
60225
70225
70265
85278
85278

31-10500
31-10501
31-10502
31-10503
31-10504
31-10505

2.0
4.0
5.0
6.0
8.0
9.9

2.3
4.7
5.9
7.0
9.4
11.7

3.3
6.8
8.4
10.1
13.5
16.9

LKT 3.8-440-DP
LKT 10.0-440-DP
LKT 12.5-440-DP
LKT 15.0-440-DP
LKT 20.0-440-DP
LKT 25.0-440-DP
LKT 28.2-440-DP
LKT 30.0-440-DP

60150
60225
70225
70225
85278
85278
85320
85320

31-10534
31-10508
31-10507
31-10506
31-10512
31-10510
31-10535
31-10509

1.3
3.3
4.1
4.9
6.7
8.2
9.2
9.8

3.8
9.9
12.4
14.9
19.8
24.8
27.9
29.8

4.1
10.7
13.3
16.0
21.4
26.7
30.0
32.0

4.6
12.0
15.0
18.0
24.0
30.0
33.8
36.0

LKT 15.5-480-DP
LKT 18.0-480-DP

70225
70265

31-10513
31-10522

4.3
5.0

13.0
15.0

13.9
16.2

15.7
18.2

LKT 10.0-525-DP
LKT 12.5-525-DP
LKT 15.0-525-DP
LKT 20.0-525-DP
LKT 25.0-525-DP

70225
70225
70265
85278
85278

31-10517
31-10516
31-10520
31-10521
31-10519

7.0
8.7
10.4
13.9
17.4

7.5
9.4
11.3
15.0
18.8

8.3
10.5
12.6
16.9
21.1

6.0
12.0
15.0
18.0
24.0
30.0

18.6
21.6
9.2
11.5
13.8
18.4
23.0

10.0
12.5
15.0
20.1
25.1

12.0
15.0
18.0
24.0
30.0

Single-phase capacitors
LKT 3.33-440-EP
LKT 4.17-440-EP
LKT 5.0-440-EP
LKT 9.4-440-EP

6090
60138
60138
70138

31-10526
31-10527
31-10528
31-10511

1.1
1.4
1.6
3.1

3.3
4.1
5.0
9.3

3.6
4.5
5.3
10.0

4.0
5.0
6.0
11.3

LKT 2.4-480-EP
LKT 3.33-480-EP
LKT 3.6-480-EP
LKT 4.8-480-EP
LKT 6.0-480-EP

6090
6090
60138
60138
60138

31-10529
31-10530
31-10531
31-10515
31-10514

0.7
0.9
1.0
1.3
1.7

2.0
2.8
3.0
4.0
5.0

2.2
3.0
3.2
4.3
5.4

2.4
3.4
3.7
4.8
6.0

LKT 2.8-525-EP
LKT 3.33-525-EP
LKT 8.33-525-EP

6090
60138
70138

31-10532
31-10533
31-10518

1.9
2.3
5.8

2.0
2.5
6.3

2.4
2.8
7.0

2.9
4.0
4.3
5.8
7.2
2.6
3.1
7.7

2.8
3.3
8.3

3.4
4.0
10.0

Power Factor Correction Capacitors


Type LKT...-DL for 50 Hz and 60 Hz

Premium Capacitors
Capacitor
Type

Dimensions
mm

Article-No.

Rated Reactive Power in kvar at Rated Voltage 50 Hz


230 V

400 V

415V

440 V

480 V

525 V

615V

Three-phase capacitors
LKT 5.0-400-DL
LKT 6.25-400-DL
LKT 9.3-400-DL
LKT 10.0-400-DL
LKT 11.7-400-DL
LKT 12.5-400-DL
LKT 20.0-400-DL

60225
60225
70225
70225
70225
70225
85278

31-10600
31-10601
31-10602
31-10603
31-10604
31-10605
31-10606

1.7
2.1
3.0
3.3
3.9
4.2
6.7

5.0
6.25
9.3
10.0
11.7
12.5
20.0

5.4*
6.7*
10.0*
10.8*
12.6*
13.5*
21.5*

6.1*
7.6*
11.3*
12.1*
14.2*
15.1*
24.2*

LKT 5.0-440-DL
LKT 7.6-440-DL
LKT 9.1-440-DL
LKT 12.1-440-DL
LKT 17.6-440-DL

60225
60225
60225
70225
85278

31-10607
31-10608
31-10609
31-10610
31-10612

1.4
2.1
2.5
3.3
4.8

4.2
6.25
7.5
10.0
14.5

4.5
6.8
8.1
10.8
15.6

5.0
7.6
9.1
12.1
17.6

6.0*
9.0*
10.8*
14.4*
21.0*

LKT 3.6-480-DL
LKT 4.5-480-DL
LKT 7.2-480-DL
LKT 7.8-480-DL
LKT 10.4-480-DL
LKT 12.5-480-DL

60150
60150
60225
60225
70225
70265

31-10613
31-10614
31-10615
31-10616
31-10617
31-10618

2.5
3.1
5.0
5.4
7.3
8.7

2.7
3.4
5.4
5.8
7.8
9.4

3.0
3.8
6.0
6.5
8.8
10.5

3.6
4.5
7.2
7.8
10.4
12.5

4.3*
5.4*
8.6*
9.3*
12.4*
15.0*

LKT 4.17-525-DL
LKT 5.9-525-DL
LKT 7.7-525-DL
LKT 8.3-525-DL

60225
60225
70225
70225

31-10619
31-10620
31-10621
31-10622

2.9
4.2
5.4
5.8

3.5
5.0
6.5
7.0

4.2
5.9
7.7
8.3

Capacitor
Type

Dimensions
mm

Article-No.

5.7*
8.1*
10.6*
11.4*

Rated Reactive Power in kvar at Rated Voltage 60 Hz


230 V

400 V

415V

440 V

460 V

480 V

525 V

615 V

Three-phase capacitors
LKT 5.0-400-DL
LKT 6.25-400-DL
LKT 9.3-400-DL
LKT 10.0-400-DL
LKT 11.7-400-DL
LKT 12.5-400-DL
LKT 20.0-400-DL

60225
60225
70225
70225
70225
70225
85278

31-10600
31-10601
31-10602
31-10603
31-10604
31-10605
31-10606

2.0
2.5
3.7
4.0
4.6
5.0
7.9

6.0
7.5
11.1
12.0
14.0
15.0
24.0

6.5*
8.1*
12.0*
12.9*
15.1*
16.2*
25.8*

7.3*
9.1*
13.5*
14.5*
17.0*
18.2*
29.0*

LKT 5.0-440-DL
LKT 7.6-440-DL
LKT 9.1-440-DL
LKT 12.1-440-DL
LKT 17.6-440-DL

60225
60225
60225
70225
85278

31-10607
31-10608
31-10609
31-10610
31-10612

1.7
2.5
3.0
4.0
5.8

5.0
7.5
9.0
12.0
17.4

5.4
8.1
9.7
12.9
18.8

6.0
9.1
10.9
14.5
21.1

6.6*
9.9*
11.9*
15.8*
23.1*

7.1*
10.9*
13.0*
17.3*
25.1*

LKT 3.6-480-DL
LKT 4.5-480-DL
LKT 7.2-480-DL
LKT 7.8-480-DL
LKT 10.4-480-DL
LKT 12.5-480-DL

60150
60150
60225
60225
70225
70265

31-10613
31-10614
31-10615
31-10616
31-10617
31-10618

3.6
4.6
7.2
7.9
10.5
12.6

4.0
5.0
7.9
8.6
11.5
13.8

4.3
5.4
8.6
9.3
12.5
15.0

5.2*
6.5*
10.3*
11.2*
14.9*
18.0*

4.2
5.9
7.8
8.3

5.0
7.1
9.3
10.0

3.0
3.8
6.0
6.5
8.7
10.4

LKT 4.17-525-DL 60225


31-10619
3.8
LKT 5.9-525-DL
60225
31-10620
5.5
LKT 7.7-525-DL
70225
31-10621
7.1
LKT 8.3-525-DL
70225
31-10622
7.6
*HQHUDOO\'/W\SHFDSDFLWRUVFDQDOVREHRSHUDWHGDWKLJKHUYROWDJHVZLWKWKH'3W\SHVSHFLFDWLRQ
Please note that the DP values in the chart are marked with *

10

6.9*
9.7*
12.7*
13.7*

Basic Harmonic Filter Reactors


Type FDK

Features that matter:


Q Low losses
Q Complete with mounting brackets and connecting clamps
Q Temperature range up to +60C
Q Temperature switches available as option

11

Basic Harmonic Filter Reactors


Type FDK

Application

Standards

Used in conjunction with LKT type power capacitors, harPRQLFOWHUUHDFWRUV EORFNLQJUHDFWRUV PDNHLWSRVVLEOH
WRLQVWDOOGHWXQHGYHUVLRQVRI[HGFDSDFLWRUEDQNVDQG
power factor correction systems.

IEC 60289, IEC 60076, VDE 0532

This enables users installing distribution boards to construct customized systems themselves.

When installing and connecting power capacitors in Germany, the standards VDE 0100 IEC 60364, VDE 0105
IEC 60050, IEC 60529, VDE 0560 Part 46 IEC 60831
and VDE 0106 Part 100 must be complied with. In
other countries the equivalent local regulations must
be observed.

Design
Low-loss, three-phase assembly complete with mounting
brackets.

Applicable Standards

Technical Data
Series Resonance Frequency
Version

Series
resonance
frequency

Detuning
factor

For networks with


utility company AF
remote control 1)

P7

189 Hz

p=7%

> 228 Hz

Please refer also to the design notes given in our Manual of Power
Factor Correction. (other series resonance frequencies on request)
1)

Tolerance of inductance:
Max. ambient temperature:
Temperature class:
Insulation level:
Winding material:
Color:

+/- 5 %
+ 60 C
H 180 C
3 kVac
Al
red or light brown

8WLOLW\FRPSDQ\VSHFLFDWLRQVLQFRQVLVWHQWZLWKWKHDERYHPXVWEHWDNHQLQWRDFFRXQW

Option
Mounting
The reactor must be mounted in a suitable enclosure
HQVXULQJ DQ DPELHQW WHPSHUDWXUH ZLWKLQ WKH VSHFLHG
range.

Temperature switch 130 C + / - 5 C,


Voltage 250 VAC (type FDKT)

Mechanical Data

Connections
The coil line-side (U, V, W) and load-side (X, Y, Z) can be
connected to the switchgear directly or via terminals.

Available Types

 7HFKQLFDO6SHFLFDWLRQ

We reserve the right to make changes to the dimensions and design of the products in this data sheet.
12

Connection diagram
U

X V

Y W

Standard Harmonic Filter Reactors


Type FDR/FKD

Features that matter:


Q Low losses
Q Complete with mounting brackets and connecting cables
Q Including temperature switches
Q Temperature range up to +60C

13

Harmonic Filter Reactors


Type FDR / FKD

Application

Power Loss

Used in conjunction with LKT type Power Factor CorUHFWLRQ &DSDFLWRUV KDUPRQLF OWHU UHDFWRUV EORFNLQJ
reactors) make it possible to install detuned versions of
[HGFDSDFLWRUEDQNVDQGSRZHUIDFWRUFRUUHFWLRQV\Vtems. This enables users installing distribution boards
to construct customized systems themselves.

Design
Low-loss, three-phase assembly complete with mounting
brackets, connecting cables and thermal trip.

Series Resonance Frequency


Version

Series
resonance
frequency

Detuning
factor

For networks with


utility company AF
remote control1)

P1

134 Hz

p=14 %

> 166 Hz

P7

189 Hz

p= 7 %

> 228 Hz

1)

8WLOLW\FRPSDQ\VSHFLFDWLRQVLQFRQVLVWHQWZLWKWKHDERYHPXVWEHWDNHQLQWRDFFRXQW

Please refer also to the design notes given in our Manual of Power
Factor Correction. (other series resonance frequencies on request)

3.5 6 W / kvar (depending on version and level of


harmonics)

Temperature Range
10 to +60 C

Ingress Protection
IP00 to IEC 60529 for mounting within an enclosure

Important Note
Please use only the correct number of the appropriate
power capacitors as stated in the table for each individual
KDUPRQLFOWHUUHDFWRU,IWKLVUHTXLUHPHQWLVQRWDGKHUHG
to, the resulting series resonance frequency can under
certain circumstances move into a critical range. Apart
from possibly overloading the installed components, the
utility companys remote control systems could also be
adversely affected.

Mounting
The reactor must be mounted in a suitable enclosure
HQVXULQJ DQ DPELHQW WHPSHUDWXUH ZLWKLQ WKH VSHFLHG
range.

Connections
The coil line-side (U1, V1, W1) and load-side (U2, V2,
W2) cables can be connected to the switchgear directly
or via terminals. The temperature switch (contacts open
at 140 C) must be connected to a trip/alarm circuit in
the control system.

Applicable Standards
When installing and connecting power capacitors in
Germany, the standards VDE 0100 IEC 60364, VDE
0105 IEC 60050, IEC 60529, VDE 0560 part 46 IEC
60831 and VDE 0106 part 100 must be complied with.
In other countries the equivalent local regulations must
be observed.

Load Capacity
Version

Power loss
W/kvar

Permissible harmonic voltage


250 Hz
350 Hz

P1

4-6

6%

6%

P7

3.5-6

6%

6%

14

Technical Data
Specimen order 1
P.F. correction stage with 7 % detuning factor 25 kvar at 400 V / 50 Hz
supply voltage
2 power capacitors
Type
LKT 11.7 400 DL
Art.-No. 31-10604
2 terminal blocks
Type
AKD 25/3
Art.-No. 31-08000
ORZORVVKDUPRQLFOWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
Type
FDR 25 400 P7
Art.-No. 88-01768

Specimen order 2
P.F. correction stage with 14 % detuning factor 12.5 kvar at 400 V / 50 Hz
supply voltage
1 power capacitor
Type
LKT 15.5 480 DP
Art.-No. 31-10513
1 terminal block
Type
AKD 25/3
Art.-No. 31-08000
ORZORVVKDUPRQLFOWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
Type
FKD 12.5 400 P1
Art.-No. 88-01168

Specimen order 3
P.F. correction stage with 14 % detuning factor 20 kvar at 400 V / 50 Hz
supply voltage
1 power capacitor
Type
LKT 7.6 440 DL
Art.-No. 31-10608
1 power capacitor
Type
LKT 15.5 480 DP
Art.-No. 31-10513
2 terminal blocks
Type
AKD 25/3
Art.-No. 31-08000
ORZORVVKDUPRQLFOWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
Type
FKD 20 400 P1
Art.-No. 88-01038

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 230 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

LKT 10.0-525-DP
Art.-No.31-10517

LKT 10.0-440-DP
Art.-No.31-10508

LKT 12.5-400-DP
Art.-No.31-10502

LKT 10.0-400-DP
Art.-No.31-10501

Weight

QLC
[kvar]

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

D1

kg

Art.-No.

150

50 132

97

77

88-01980 FDR 5-230-P7

180

60 156

91

71

88-01575 FKD 10-230-P7

180

60 156

101

81

88-01974 FDR 12.5-230-P7

180

60 156

111

91

10

88-01583 FKD 16.7-230-P7

Dimensions in mm
W

W1

Type

In [A]

5.0

12.6

10.0

26.9

12.5

31.3

16.7

44.9

20.0

53.8

204

68 177

121

101

15

88-01576 FKD 20-230-P7

25.0

62.5

204

68 177

121

101

16

88-01943 FDR 25-230-P7

33.0

89.9

240

80 197

125

105

21

88-01568 FKD 33-230-P7

Capacitors and Harmonic Filter Reactors for 230 V/60 Hz mains network
Resonance frequency

fres: 227 Hz, detuning factor p= 7%

In [A]

17.0

43.1

25.0

62.2

Harmonic Filter Reactors

D1

kg

Art.-No.

Dimensions in mm
W

Weight

QLC
[kvar]

LKT 7.1-300-DP
Art.-No.31-10523

LKT 10.0-400-DP
Art.-No.31-10501

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

W1

Type

180

60 156

111

91

10

88-01809 FKD 17-230-60Hz-P7

204

68 177

121

101

21

88-01892 FDR 25-230-60Hz-P7

FDR / FKD dimensions


15

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 400 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

Dimensions in mm
W

QLC
[kvar]

In [A]

6.25

9.0

7.5

10.8

10.0

14.4

12.5

18.0

15.0

21.6

20.0

29.0

25.0

36.0

30.0

43.0

40.0

58.0

50.0

72.0

1
1
1
1
2
2
2
3
3
4

Resonance frequency

W1

D1

Weight

LKT 15.0-440-DP
Art.-No.31-10506

LKT 11.7-400-DL
Art.-No.31-10604

LKT 12,5-440-DP
Art.-No.31-10507

LKT 9.1-440-DL
Art.-No.31-10609

LKT 7.6-440-DL
Art.-No.31-10608

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

kg

Art.-No.

Type

150

50 132

97

77

88-01410 FKD 6.25-400-P7

150

50 132

97

77

88-01482 FKD 7.5-400-P7

180

60 156

111

91

10

88-01479 FKD 10-400-P7

180

60 156

111

91

10

88-01767 FDR 12.5-400-P7

204

68 177

121

101

15

88-01362 FKD 15-400-P7

204

68 177

121

101

19

88-01363 FKD 20-400-P7

204

68 177

121

101

21

88-01768 FDR 25-400-P7

264

88 235

114

94

21

88-01484 FKD 30-400-P7

264

88 235

114

94

21

88-01782 FDR 40-400-P7

264

88 235

140

120

27

88-01769 FDR 50-400-P7

fres: 134 Hz, detuning factor p= 14%

16

In [A]

6.25

9.0

10.0

14.4

12.5

18.0

20.0

28.8

25.0

36.0

40.0

57.6

50.0

72.0

LKT 9.1-440-DL
Art.-No.31-10609

LKT 12.1-440-DL
Art.-No.31-10610

LKT 15.5-480-DP
Art.-No.31-10513

LKT 7.6-440-DL
Art.-No.31-10608

LKT 7.7-525-DL
Art.-No.31-10621

Weight

QLC
[kvar]

LKT 7.8-480-DL
Art.-No.31-10616

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

D1

kg

Art.-No.

180

60 156

111

91

10

88-01505 FKD 6.25-400-P1

180

60 156

111

91

10

88-01695 FKD 10-400-P1

204

68 177

121

101

15

88-01168 FKD 12.5-400-P1

228

76 197

128

108

21

88-01038 FKD 20-400-P1

264

Dimensions in mm
W

1
2
1

2
2
4

W1

Type

88 235

140

120

27

88-01171 FKD 25-400-P1

300 100 265

164

144

33

88-01779 FDR 40-400-P1

300 100 265

164

144

33

88-01780 FDR 50-400-P1

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 415 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

LKT 12.5-525-DP
Art.-No.31-10516

LKT 15.5-480-DP
Art.-No.31-10513

Weight

QLC
[kvar]

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

D1

kg

Art.-No.

Dimensions in mm
W

W1

Type

In [A]

12.5

17.3

16.8

23.4

25.0

34.7

33.6

46.7

50.0

69.3

1
2
2
4
4

180

60 156

111

91

10

88-01937 FDR 12.5-415-P7

180

60 156

111

91

11

88-01977 FDR 16.8-415-P7

204

68 177

121

101

15

88-01938 FDR 25-415-P7

228

76 197

128

108

19

88-01978 FDR 33.6-415-P7

264

88 235

140

120

27

88-01930 FDR 50-415-P7

Capacitors and Harmonic Filter Reactors for 440 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

In [A]

25.0

34.2

50.0

68.4

Weight

QLC
[kvar]

LKT 12.1-440-DL
Art.-No.31-10610

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

D1

kg

Art.-No.

76

197 128

108

21

88-01008 FKD 25-440-P7

88

235

94

28

88-01124 FKD 50-440-P7

Dimensions in mm
W

W1

228

264

114

Type

17

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 440 V/60 Hz mains network
Resonance frequency

fres: 227Hz, detuning factor p= 7%

In [A]

6.25

9.2

7.5

9.9

12.5

16.9

15.0

19.8

25.0

33.1

50.0

66.2

LKT 7.8-480-DL
Art.-No.31-10616

LKT 5.9-525-DL
Art.-No.31-10620

LKT 7.7-525-DL
Art.-No.31-10621

Dimensions in mm
W

1
1
1
1

W1

Weight

QLC
[kvar]

LKT 12.1-440-DL
Art.-No.31-10610

LKT 15.5-480-DP
Art.-No.31-10513

LKT 8.33-525-DL
Art.-No.31-10622

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

kg

Art.-No.

D1

Type

150

50 132

97

77

88-01914 FKD 6.25-440-60Hz-P7

150

50 132

97

77

88-01795 FKD 7.5-440-60Hz-P7

180

60 156

91

71

21

88-01883 FKD 12.5-440-60Hz-P7

180

60 156

111

91

10

88-01796 FKD 15-440-60Hz-P7

204

68 177

121

101

11

88-01884 FKD 25-440-60Hz-P7

264

88 235

114

94

29

88-01875 FDR 50-440-60Hz-P7

Capacitors and Harmonic Filter Reactors for 460 V/60 Hz mains network
Resonance frequency

fres: 227 Hz, detuning factor p= 7%

18

Weight

LKT 12.5-525-DP
Art.-No.31-10516

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

W1

D1

kg

Art.-No.

180

60

156

111

91

10

88-01854 FDR 12.5-460-60Hz-P7

31.1

204

68

177

121

101

21

88-01855 FDR 25-460-60Hz-P7

62.1

264

88

235

132

112

27

88-01856 FDR 50-460-60Hz-P7

QLC
[kvar]

In [A]

12.5

15.5

25.0
50.0

Dimensions in mm

Type

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 480 V/60 Hz mains network
Resonance frequency

fres: 227 Hz, detuning factor p= 7%

In [A]

33.3

43.1

41.6

53.9

50.0

60.5

LKT 8.33-525-DL
Art.-No.31-10622

LKT 4.17-525-DL
Art.-No.31-10619

1
1
6

Dimensions in mm

Weight

QLC
[kvar]

LKT 7.7-525-DL
Art.-No.31-10621

LKT 12.5-525-DP
Art.-No.31-10516

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

kg

Art.-No.

W1

D1

Type

264

88

235

114

94

21

88-01736 FKD 33.3-480-60Hz-P7

264

88

235

114

94

21

88-01737 FKD 41.6-480-60Hz-P7

264

88

235 140

120

27

88-01858 FDR 50-480-60Hz-P7

Capacitors and Harmonic Filter Reactors for 525 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

In [A]

W1

D1

Weight

LKT 8.33-525-DL
Art.-No.31-10622

LKT 7.7-525-DL
Art.-No.31-10621

LKT 5.9-525-DL
Art.-No.31-10620

LKT 4.17-525-DL
Art.-No.31-10619

Dimensions in mm

Harmonic Filter Reactors

kg

Art.-No.

Type

6.25

7.0

150

50 132

97

77

88-01801 FKD 6.25-525-P7

12.5

14.1

180

60 156

111

91

10

88-01802 FKD 12.5-525-P7

20.0

24.7

228

76 197

104

84

19

88-01080 FKD 20-525-P7

25.0

29.6

228

76 197

128

108

21

88-01838 FDR 25-525-P7

30.0

34.6

228

76 197

128

108

21

88-01533 FKD 30-525-P7

50.0

55.0

264

88 235

140

120

29

88-01872 FDR 50-525-P7

Weight

QLC
[kvar]

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

kg

Art.-No.

2
3

3
6

Resonance frequency

fres: 134 Hz, detuning factor p= 14%

QLC
[kvar]

LKT 5.9-525-DL
Art.-No.31-10620

LKT 4.17-525-DL
Art.-No.31-10616

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Dimensions in mm
W

In [A]

W1

D1

Type

25.0

27.9

264

88 235

140

120

25

88-01960 FDR 25-525-P1

50.0

55.8

300 100 265

164

144

52

88-01900 FDR 50-525-P1

19

Harmonic Filter Reactors


Type FDR / FKD

Capacitors and Harmonic Filter Reactors for 690 V/50 Hz mains network
Resonance frequency

fres: 189 Hz, detuning factor p= 7%

In [A]

25.0

22.6

50.0

45.2

Weight

QLC
[kvar]

LKT 9.4-440-EP
Art.-No.31-10511

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

W1

D1

kg

Art.-No.

204

68

177

121

101

19

88-01932 FDR 25-690-P7

264

88

235

140

120

27

88-01933 FDR 50-690-P7

Dimensions in mm

Resonance frequency

Type

fres: 134 Hz, detuning factor p= 14%

20

In [A]

25.0

21.7

50.0

43.4

LKT 8.33-525-EP
Art.-No.31-10518

LKT 6.0-480-EP
Art.-No.31-10514
3

Weight

QLC
[kvar]

LKT 4.8-480-EP
Art.-No.31-10515

Rated current of
Capacitor Reactor
combination

Rated power of
Capacitor Reactor
combination

Type and Quantity of the required capacitors

Harmonic Filter Reactors

D1

kg

Art.-No.

88

235

140

120

27

88-01842 FKD 25-690-P1

300 100

265

164

144

33

88-01843 FKD 50-690-P1

Dimensions in mm
W

W1

264

Type

Capacitor Switching Contactors


Type K3...-A, K3...-K

Features that matter:


Q Patented design with significant damping on inrush-current
Q Long-life contactors tested by FRAKO up to 100,000 switching operations
Q Suitable for unchoked and choked Power Factor Correction Systems
Q Very high operational reliability

21

Capacitor Switching Contactors


for unchoked and choked PFC Systems

Description
Capacitor contactors for
unchoked power factor correction systems

Capacitor contactors for


choked power factor correction systems

During the switching of unchoked power factor correction


capacitors a peak-switching current of 200 times of the
nominal current can occur. This load is stressing the
capacitors and the switching contacts of the contactors
immensely. This can lead to welded main contacts of
contactors.

When choked power factor correction systems are


switched, the peak-switching current is essentially
lower because of the high inductivity of the harmonic
OWHUUHDFWRUDVZLWKXQFKRNHGSRZHUIDFWRUFRUUHFWLRQ
systems.

Therefore modern power factor correction systems are


currently equipped with special capacitor contactors
VZLWFKLQJWKHFDSDFLWRUVUVWZLWKOHDGLQJFRQWDFWVDQG
additionally with resistance wires. The in-rush current will
be damped strongly by the resistors. After approximately
5 ms the main contacts of the contactor are switching
in and taking over the current supply to the capacitors.
Further to this the leading contacts open up and no curUHQWFDQRZGXULQJSHUPDQHQWRSHUDWLRQ7KLVLVDOVR
to avoid an additional power loss.
Capacitor contactors with leading transition contact and
additional resistance wires offer the following advantages to power factor correction system applications:
Q 6LJQLFDQWGDPSLQJRILQUXVKFXUUHQW
Q Improvement of the voltage quality during the
switching process
Q Long life of the contactors
Q High operational reliability of the power factor
correction system
Q Extension of the maintenance periods of the power
factor correction systems
Q Suitable for choked and unchoked power factor
correction systems due to leading transition
contacts opening during permanent operation.

22

By using special wear-resistant contact material for these


applications it is possible to use capacitor contactors
without series resistors.
These special capacitor contactors offer the following
advantages for choked power factor correction systems:
Q Safe switching on and off of choked capacitor
steps
Q Improved voltage quality through chatter-proofed
switching operations
Q Long-life of the contactors (> 100,000 switching
operations)
Q High operational reliability of the power factor
correction system

Capacitor Switching Contactors


for unchoked and choked PFC Systems

Technical Data
Rated operational power at 50/60 Hz
Ambient temperature:
50 C
380 V
400 V
kvar
0-12.5
10-20

415 V
440 V
kvar

660 V
690 V
kvar

0-13

0-20

10.5-22

17-33

Aux. contacts
built-in add.

60 C
380 V
400 V
kvar

Article-No.

Weight

Coil voltage
220240 V 50 Hz

415 V
440 V
kvar

660 V
690 V
kvar

NO

NC

pcs.

0-13

0-20

11)

K3-18K10 230

89-00280

0.34

10.5-22

17-33

32)

K3-24K00 230

89-00279

0.62

2)

0-12.5
10-20

Type

kg/pc.

10-25

10.5-27

17-41

10-25

10.5-27

17-41

K3-32K00 230

89-00278

0.62

20-33.3

23-36

36-55

20-33.3

23-36

36-55

32)

K3-50K00 230

89-00277

1.0

20-50

23-53

36-82

20-50

23-53

36-82

32)

K3-62K00 230

89-00276

1.0

20-753)

23-753)

36-1203)

20-60

23-64

36-100

32)

K3-74K00 230

89-00286

1.0

33-80

36-82

57-120

33-75

36-77

57-120

64)

K3-90K00230

89-00356

2.3

33-1005)

36-1035)

57-1485)

33-905)

36-935)

57-1485)

64)

K3-115K00230

89-00357

2.3

1)
4)

2)

1HN.. or HA.. snap-on


2HB.. on the left or right side and 4 HN.. or HA.. snap-on

5)

2HB.. for side mounting and 1HN.. or HA.. snap-on


Consider the min. cross-section of conductor at max. load

3)

Consider the max. thermal current of the contactor K3-74 A:


Ith 130 A

6SHFLFDWLRQ&RQWDFWRUV..DUHVXLWDEOHIRUVZLWFKLQJORZLQGXFWLYHDQGORZORVVFDSDFLWRUVLQFDSDFLWRUEDQNV ,(&DQG9'( ZLWKRXWDQGZLWKUHDFWRUV


&DSDFLWRUVZLWFKLQJFRQWDFWRUVDUHWWHGZLWKHDUO\PDNHFRQWDFWVDQGGDPSLQJUHVLVWRUVWRUHGXFHWKHYDOXHRIPDNHFXUUHQW[Oe .
Operating Conditions: Capacitor switching contactors are protected against contact welding for a prospective making current of 200 x le.

Technical Data acc. to IEC 947-4-1, IEC 947-5-1, EN 60947-4-1, EN 60947-5-1, VDE 0660
Type

K3-18K

K3-24K

K3-32K

K3-50K

K3-62K

K3-74K

K3-90K

K3-115K

Max. frequency of operations z

1/h

120

120

120

120

120

80

80

80

Contact life: unchoked capacitor banks

S x 103

250

150

150

150

150

120

100

75

Contact life: choked banks

S x 103

400

300

300

300

300

200

200

200

0-18

14-28

14-36

30-48

30-72

30-108

50-115

50-144

30-87

50-108

50-130

Rated operational current le

at 50 C A
at 60 C A

0-18

14-28

14-36

30-48

30-72

Fuses gL (gG)

from/to

35/63

50/80

63/100

80/160

125/160 160/200 160/200 160/250

A
L1 L2

L3

Mounting Instructions
Typical Circuit Diagram

A1

A2

,QWKHDUHDRIFDSDFLWRUVZLWFKLQJFRQWDFWRUVGLIFXOW\
LQDPPDEOH DQG VHOIH[WLQJXLVKLQJ PDWHULDOV PD\ EH
used only, because abnormal temperatures within the
area of the resistor spirals cannot be excluded.

Auxiliary Contact Blocks


Rated operational current
AC15
AC1
230 V
400 V
690 V
A
A
A

Contacts

Type

Article-No.

Weight

For contactors

NO

NC

10

K3-24 to K3-115

HB11

89-00294

0.02

10

HN10

89-00281

0.02

kg/pc.

for side mounting


K3-18 to K3-115

23

Capacitor Switching Contactors


for unchoked and choked PFC Systems

Technical Data
Rated operational power at 50/60 Hz
Ambient temperature:
50 C
60 C
380 V
415 V
660 V
380 V
400 V
440 V
690 V
400 V
kvar
kvar
kvar
kvar

Aux. contacts
built-in add.

Type

Article-No.

415 V
440 V
kvar

660 V
690 V
kvar

NO

NC

pcs.

12.5

13

20

12.5

13

20

41)

K3-18A10 230

89-00288

0.23

20

22

33

20

22

33

62)

K3-24A00 230

89-00289

0.48

25

27

41

25

27

41

62)

K3-32A00 230

89-00290

0.48

33.3

36

55

33.3

36

55

62)

K3-50A00 230

89-00291

0.85

50

53

82

50

53

82

62)

K3-62A00 230

89-00292

0.85

753)

753)

100

60

64

100

62)

K3-74A00 230

89-00293

0.85

4)

Coil voltage
220240 V 50 Hz
_

Weight

kg/pc.

80

82

120

75

77

120

K3-90A00 230

89-00358

2.2

1005)

1035)

1485)

905 )

935)

1485)

94)

K3-115A00 230

89-00359

2.2

1)
4)

2)

4HN.. or HA.. snap-on


2HB.. on the left or right side and 7 HN.. or HA.. snap-on

5)

L1 L2

2HB11 on the left or right side and 4HN.. or HA.. snap-on


Consider the min. cross-section of conductor at max. load

3)

Consider the max. thermal current: Ith 130 A

L3

Mounting Instructions
Typical Circuit Diagram

A1

A2

,QWKHDUHDRIFDSDFLWRUVZLWFKLQJFRQWDFWRUVGLIFXOW\
LQDPPDEOH DQG VHOIH[WLQJXLVKLQJ PDWHULDOV PD\ EH
used only, because abnormal temperatures within the
area of the resistor spirals cannot be excluded.

Dimensions
Capacitor switching contactors, AC-operated

Contactors, AC-operated

K3-18K...

K3-18A10

45

98
94

35-36

65.5

45
35-36

61.5

85

59

59

49-50

49-50

5
5

M3.5

M3.5

6.5

6.5

50

50

K3-24K00
K3-32K00

K3-24A00
K3-32A00
45
35

45

119.5
115.5

87.5

35

83.5

4.5

60

74

M5

M5

6.5

6.5

63

24

65

74
65
60

115

4.5

63

Capacitor Switching Contactors


for unchoked and choked PFC Systems

Dimensions
Capacitor switching contactors, AC-operated

Contactors, AC-operated

K3-50K00
K3-62K00
K3-74K00

K3-50A00
K3-62A00
K3-74A00
60
50

60

128.5
124.5

96

50

92

5.5

95

100

110

145

110
100
95

5.5

M6

M6

7.5

7.5
68

68

K3-90K00
K3-115K00

K3-90A00
K3-115A00
120
115

90

152.5
120
115

90
75

75

6
6

70

137

155

70

155
137

M8

M8
9
31.5

31.5

74

9
31.5

74

31.5

Technical Data
Main Contacts

Type

K3-18K

K3-24K

K3-32K

K3-50K

K3-62K

K3-74K


1436


3048


3072

K3-90K

K3-115K

Switching of
three-phase current pfc-systems
$PELHQWWHPSHUDWXUH&
Rated operational current le


690 V


A


018


1428

301081) 50115

501442)

Rated operational power

220240V
380400 V
415440 V

kvar
kvar
kvar

07
012.5
013

511
514
1220
1228
1020
1025
2033.3 2050
10.522 10.527 2336
2353

1233
20751)
23751)

2045
3380
3682

20552)
331002)
361032)

500 V
525 V
660690 V
1000 V

kvar
kvar
kvar
kvar

015
015
020

1225
1225
1733

1230
1232
1741

2640
2643
3655

2660
2664
3682

2675
2680
36120

43100
45105
57120
85160

431202)
451252)
571482)
852002)

$PELHQWWHPSHUDWXUH&
Rated operational current le


690 V


A


018


1428


1436


3048


3072

3087

50108

501302)

Rated operational power

220240 V
380400 V
415440 V

kvar
kvar
kvar

07
012.5
013

511
514
1220
1228
1020
1025
2033.3 2050
10.522 10.527 2336
2353

1230
2060
2364

2040
3375
3677

20502)
33902)
36932)

500 V
525 V
660690 V
1000 V

kvar
kvar
kvar
kvar

015
015
020

1225
1225
1733

2670
2675
36100

4390
4595
57120
85150

431102)
451152)
571482)
851802)

1)

Consider the max. thermal current: Ith 130 A

2)

1230
1232
1741

2640
2643
3655

2660
2664
3682

Consider the min. cross-section of conductor at max. load

25

Capacitor Switching Contactors


Data according to IEC 947- 4 -1, EN 60947- 4 -1, VDE 0660

Technical Data
Main Contacts

Type

K3-18A

K3-24A

K3-32A

K3-50A

K3-62A

K3-74A

K3-90A

K3-115A

Switching of
three-phase current pfc-systems
$PELHQWWHPSHUDWXUH&
Rated operational current le


690 V


A

Rated operational power

220240V
380400 V
415440 V

18

28

36

48

72

1081)

115

1442)

kvar
kvar
kvar

7
12.5
13

11
20
22

14
25
27

20
33.3
36

28
50
53

33
751)
751)

45
80
82

552)
1002)
1032)

500 V
525 V
660690 V
1000 V

kvar
kvar
kvar
kvar

15
15
20

25
25
33

30
32
41

40
43
55

60
64
82

75
80
120

100
105
120
160

1202)
1252)
1482)
2002)

$PELHQWWHPSHUDWXUH&
Rated operational current le


690 V


A

18

28

36

48

72

87

108

1302)

Rated operational power

220240 V
380400 V
415440 V

kvar
kvar
kvar

7
12.5
13

11
20
22

14
25
27

20
33.3
36

28
50
53

30
60
64

40
75
77

502)
902)
932)

500 V
525 V
660690 V
1000 V

kvar
kvar
kvar
kvar

15
15
20

25
25
33

30
32
41

40
43
55

60
64
82

70
75
100

90
95
120
150

1102)
1152)
1482)
1802)

K3-74

K3-90

K3-115

1)

2)

Consider the max. thermal current: Ith 130 A

Main Contacts

Type

Consider the min. cross-section of conductor at max. load

K3-18

K3-24

K3-32

K3-50

K3-62

Maximum ambient temperature


Operation

open
enclosed

40 to +60 (+90)1)
40 to +40
50 to +90

C
C
C

Storage

Short circuit protection


for contactors without thermal overload relay
Coordination-type 1
according to IEC 947-4-1
Contact welding without
Hazard of persons
Max. fuse size
gL (gG)

100

100

100

160

160

160

200

250

10

10

10

10

10

10

Mechanical life
AC-operated

S x 106

DC-operated

S x 10

10

10

10

10

10

10

Short time current

10s-current

144

184

240

360

504

592

680

880

Power loss per pole

At le/AC3 400 V W

0.5

0.7

1.3

2.2

3.9

5.5

4.3

6.0

1)

With reduced control voltage range 0.9 up to 1.0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3

26

Discharge Reactors
Type FR 3AC

Features that matter:


Q One type for every application in Power Factor Correction Systems
Q Low operating losses
Q Ambient temperature up to +60C
Q Allows very fast re-switching of the same capacitor step

27

Discharge Reactors
Type FR 3AC

Description
Discharge reactors have lower losses than discharging
resistors.
This could be an important fact in modern power factor
correction systems if ambient temperature is a topic to
solve.

Technical Data
Discharge reactor, type:
FR3AC230-690V Article-No. 88-02013
Ordering code

88-02013

Rated operating
voltage:

3AC 230 V 690 V

Frequency:

50 60 Hz

The high AC resistance of the discharge reactors generates very small losses, also when capacitors were
permanently connected to the network.

2SHUDWLQJORVVHV

:

1RORDGFXUUHQW

P$

Inductance:

70 H

In the moment when capacitors are switched off, the low


DC resistance of the discharge reactor is responsible for
a very fast discharging time of the capacitors. It will only
take a few seconds. This fast discharging also allows a
very fast re-switching of the same capacitor.

7LPHRIGLVFKDUJH 9 NYDU VHF NYDU VHF


 

9 NYDU VHF NYDUVHF
 

9 NYDU VHF
Permissible
discharges:

3 / min

Temperature class: T40 / E


Ambient
temperature:

25 ... +60 C

Protection class:

IP 00

Abutting cross
section:

0.75 mm2 2.5 mm2

Fixing torque:

0.5 Nm

Total weight:

0.5 kg

Testing voltage:

4 kVAC

Standards:

EN 61558-2-20

Dimensions in mm:
WxHxD
77 x 96 x 55

28

Power Factor Control Relays


Type EMR1100 / EMR1100S / RM9606 / RM2106 / RM2112

Features that matter:


Q Fully automatic and simple commissioning
Q Patented control characteristic no overcompensation during low load
Q Measurement and monitoring of harmonics
Q Overcurrent trip function protection for capacitors
Q Four-quadrant regulation

29

Power Factor Control Relays


Type EMR 1100S / EMR 1100

Description
Microprocessor-based control relay for intelligent control
of capacitor banks with 12 control contacts.

Simple Commissioning
%\ DXWRPDWLF LGHQWLFDWLRQ RI WKUHVKROG FXUUHQW FN
value), phase angle, connected capacitor stages and
switching sequences.

Operator Overview
Through clear digital display of key momentary values
and operating parameters.
Q
Q
Q
Q

Power factor (cos )


Apparent (RMS), active and reactive currents
5th, 7th, 11th and 13th voltage harmonics
Total capacitive power required to meet target
power factor setting

Monitoring of Harmonic Levels


By continuous monitoring and display of harmonic voltage levels. In the event of harmonic levels exceeding
programmable limits, all capacitors will be switched off
through overcurrent alarm.

Features
Q Potential-free alarm
contact.
Q Programmable overcurrent alarm threshold
limit (from 1.05 to 3.0 x Irms).
Q Continuous monitoring for
defective capacitor stages
through self adjustment of
control program.
Q Zero voltage and zero current tripping with alarm
signal.
Q Patented kinked control curve characteristics
avoid overcompensation under light load.
Q Four-quadrant power control with LED display
when active power is generated into mains.
Q Manual/automatic operation with ability to switch
each individual capacitor stage ON or OFF.
Q Target power factor setting adjustable from 0.80
inductive to 0.90 capacitive in steps of 0.01.
Q 3UHVHWXSWRWKUHH[HGFDSDFLWRUVWDJHVZKLFKZLOO
be excluded from normal automatic operation.
Q Independent setting of capacitor switching time to
match discharge time of capacitor stages.
Q Suitable for current transformers with rated
secondary current of 1 A or 5 A.

Prolongs Switchgear Life


The EMR 1100 counts, stores and displays the number of
switching operations for each individual capacitor stage.
An alarm is triggered if the switching counters exceed
programmable limits.

Additional Protection for Capacitors


The RMS current monitoring function provides excellent
SURWHFWLRQIRUFDSDFLWRUEDQNVZLWKRXWKDUPRQLFOWHUV
especially when resonance causes an increase in harmonic levels.

Intelligent Control for Increased


Equipment Life
Q Cyclic switching for capacitor stages of the same
rating.
Q Accurate switching of capacitor stages prevents
unnecessary switchings for responsive control.
Q Continuous optimisation of switching delay
according to required reactive current.

30

Alarm Signals for


Q
Q
Q
Q
Q
Q
Q

Undercompensation
High harmonic levels
Overcurrent
Switching counters
Fault in voltage circuit (U = 0 alarm)
Fault in current circuit (I = 0 alarm)
Fault in capacitor stages (C = 0 alarm)

Optional extension of the EMR 1100 S to


EMR 1100 full version by means of
software upgrading
Q Potential-free tariff switching contact to select two
independent target power factor settings.
Q Remote indication of the measuring values and
historical data (daily curves, monthly and annual
evaluation).
Q Communication with Building control systems.
Q &RQJXUDWLRQDQGUHPRWHLQGLFDWLRQRIWKH
measuring values with software EMR-SW via the
RS232 interface.

Power Factor Control Relays


Type RM 9606

Description
Microprocessor-based control relay for intelligent control
of capacitor banks with 6 control contacts.

Simple Commissioning
%\ DXWRPDWLF LGHQWLFDWLRQ RI WKUHVKROG FXUUHQW FN
value), phase angle, connected capacitor stages and
switching sequences.

Operator Overview
Through clear digital display of key momentary values
and operating parameters.
Q
Q
Q
Q

Power factor (cos )


Apparent (RMS), active and reactive currents
5th, 7th, 11th and 13th voltage harmonics
Total capacitive power required to meet target
power factor setting

Monitoring of Harmonic Levels


By continuous monitoring and display of harmonic voltage levels. In the event of harmonic levels exceeding
programmable limits, all capacitors will be switched off
through overcurrent alarm.

Prolongs Switchgear Life


The RM 9606 counts, stores and displays the number of
switching operations for each individual capacitor stage.
An alarm is triggered if the switching counters exceed
programmable limits.

Additional Protection for Capacitors


The RMS current monitoring function provides excellent
SURWHFWLRQIRUFDSDFLWRUEDQNVZLWKRXWKDUPRQLFOWHUV
especially when resonance causes an increase in harmonic levels.

Intelligent Control for Increased


Equipment Life
Q Cyclic switching for capacitor stages of the same
rating.
Q Accurate switching of capacitor stages prevents
unnecessary switchings
for responsive control.
Q Continuous optimisation of
switching delay according to required reactive
current.

Features
Q Potential-free alarm contact.
Q Programmable overcurrent alarm threshold limit
(from 1.05 to 3.0 x Irms).
Q Continuous monitoring for defective capacitor
stages through self adjustment of control program.
Q Zero voltage and zero current tripping with alarm
signal.
Q Patented kinked control curve characteristics
avoid overcompensation under light load.
Q Four-quadrant power control with LED display
when active power is generated into mains.
Q Manual/automatic operation with ability to switch
each individual capacitor stage ON or OFF.
Q Target power factor setting adjustable from 0.80
inductive to 0.90 capacitive in steps of 0.01.
Q 3UHVHWXSWRWKUHH[HGFDSDFLWRUVWDJHVZKLFKZLOO
be excluded from normal automatic operation.
Q Independent setting of capacitor switching time to
match discharge time of capacitor stages.
Q Suitable for current transformers with rated
secondary current of 1 A or 5 A.

Alarm Signals for


Q
Q
Q
Q
Q
Q
Q

Undercompensation
High harmonic levels
Overcurrent
Switching counters
Fault in voltage circuit (U = 0 alarm)
Fault in current circuit (I = 0 alarm)
Fault in capacitor stages (C = 0 alarm)

&RQJXUDWLRQDQGUHPRWHLQGLFDWLRQRIWKHPHDVXULQJYDOXHV
via RS232 interface with EMR 1100.
31

Power Factor Control Relays


Type RM 2106 / RM 2112

Description
Microprocessor-based control relay for intelligent control
of capacitor banks with 6 or 12 control contacts.

Simple Commissioning
%\ DXWRPDWLF LGHQWLFDWLRQ RI WKUHVKROG FXUUHQW FN
value), phase angle, connected capacitor stages and
switching sequences.

Operator Overview
Through clear digital display of key momentary values
and operating parameters.
Q Power factor (cos )
Q Total harmonic voltage distortion factor (% THVD)
Q Number of active capacitor steps

Extensive Analysis Record


When in automatic mode, display of:
Q Connection faults
Q Capacity step faults
Q Recognized step sequence

Protection for Capacitors


The optional RMS current monitoring function provides
excellent protection for capacitor banks without harmonic
OWHUVHVSHFLDOO\ZKHQUHVRQDQFHFDXVHVDQLQFUHDVH
in harmonic levels. The threshold can be set between
1.05 to 1.95 x Irms.

Intelligent Control for Increased


Equipment Life
Q Cyclic switching for capacitor stages of the same
rating.
Q Accurate switching of capacitor stages prevents
unnecessary switchings for responsive control.
Q Continuous optimisation of switching delay
according to required reactive current.

32

Features
Q Potential-free alarm contact.
Q Programmable overcurrent
alarm threshold limit.
Q Continuous monitoring for
defective capacitor stages
through self adjustment of
control program.
Q Zero voltage and zero current tripping with alarm
signal.
Q Two control curves characteristics:
to avoid overcompensation under light load.
to avoid inductive reactive power under
regeneration conditions.
Q Four-quadrant power control with LED display
when active power is generated into mains.
Q Manual/automatic operation with ability to switch
each individual capacitor stage ON or OFF.
Q Target power factor setting adjustable from 0.85
inductive to 1.00 capacitive.
Q Independent setting of capacitor switching time to
match discharge time of capacitor stages.
Q Suitable for current transformers with rated
secondary current of 1 A or 5 A.
Q Protection class terminals IP 20, housing IP 54
(when sealing ring is used).

Alarm Signals for


Q Overcurrent
Q Fault in voltage circuit (U = 0 alarm)
Q Fault in capacitor stages

Article-No. Power Factor Control Relay

Type

38-00320

With 6 control contacts

RM 2106

38-00340

With 12 control contacts

RM 2112

38-00103

With 6 control contacts

RM 9606

38-00301

With 12 control contacts

EMR 1100 S

20-50008

With 12 control contacts and bus


interface to FRAKO EnergyManagement-System

EMR 1100

20-50013

Software-Upgrade EMR 1100 S


to full version EMR 1100

EMR-Upgrade

20-10312


EMR-Software for EMR 1100 for


FRQJXUDWRQDQGRQOLQHYLHZ

EMR-Sofware

20-50014

Protection kit for protection


class IP 54

Modular Construction System


MCS System

These components fit together


 Design your own high quality Power Factor Correction System
 Type-tested components
 High operational reliability of Power Factor Correction Systems
 Gain from 80 years experience in Power Factor Correction technologies

33

Modular Construction System


MCS System

Description
The FRAKO MCS System is a modular system, with
which a skilled switchgear manufacturer can design a
technically high-quality power factor correction system.
However, knowing our manual of power factor correction is absolutely important to design such a power
IDFWRUFRUUHFWLRQV\VWHP,QWKLVPDQXDORQHZLOOQGDOO
the necessary planning information as well as all the
important technical data. You can download the manual
free of charge from our website or order it free of charge
from your local FRAKO partner.
The FRAKO MCS System consists of selected and
tested components for the design of power factor correction systems. FRAKO uses these components in its
own production of power factor correction systems in
Teningen. This way the skilled switchgear manufacturer
can gain from an experience and application know-how
of almost 80 years.

The FRAKO MCS System contains the following


components:
Q Power factor control relay
Q Control terminal strip for power factor control relay
and Power Factor Correction Systems
Q Control wires
Q Busbar holders
Q NH-fuse base and NH-isolating switch
Q NH-fuse links
Q Contactors
Q Discharge reactors
Q +DUPRQLFOWHUUHDFWRUV
Q Power factor correction capacitors
Q Thyristor switches (see page 52)
Page 37 Specimen order 1 shows the combination of
all FRAKO components for a power factor correction
V\VWHP ZLWK QR KDUPRQLF OWHU UHDFWRUV ZLWK D WRWDO
power of 350 kvar at 400 V, 50 Hz and a step rating of
25 kvar at a switching sequence of the capacitor steps
of: 1:1:2:2:2:2:2:2.
Page 38 Specimen order 2 shows the combination of
all FRAKO components for a choked power factor correction system with a total power of 375 kvar at 400 V,
50 Hz, a series resonance frequency of 189 Hz (p = 7 %)
and a step rating of 25 kvar at a switching sequence of
the capacitor steps of: 1:2:2:2:2:2:2:2.

34

Modular Construction System


MCS System

Technical Data
Power Factor Control Relays and accessories
For technical details on our power factor control relays
we would like to refer you to our catalogue (page 29 to
32).
For the relays, FRAKO recommend to use the suitable
control terminal strips, the thermal trip contact for the
monitoring of the cabinet temperature as well as the pre-

pared control cables. All items can be ordered as single


components or as a complete control relay package.
The following chart shows the different types of relays
as well as the suitable accessories for the assembly and
the connection of the devices.

Article
number: Description:

Order Code:

Power factor control relay


38-00320 with 6 control contacts

RM 2106

38-00103 with 6 control contacts

RM 9606

38-00340 with 12 control contacts

RM 2112

38-00301 with 12 control contacts

EMR 1100 S

20-50008 with 12 control contacts and bus interface to FRAKO Energy-Management-System

EMR 1100

20-50013 Software-Upgrade EMR 1100 S to full version EMR 1100


Control terminal strip with thermal trip contact, pre-mounted
34-80002 suitable for RM 9606

RKLRM 9606

34-80003 suitable for EMR 1100 / EMR 1100 S

RKLEMR 1100

34-80027 for extension units (only 12 control contacts)

RKLZcabinet

Control cable, prepared


89-20557 for connection of RM 9606 with control terminal strip (length: 1000 mm, 6 control contacts)

RK RM 96061150

89-20558 for connection of RM 9606 with control terminal strip (length: 1500 mm, 6 control contacts)

RK RM 96061500

89-20555 for connection of EMR 1100 / EMR 1100 S with control terminal strip (length: 1150 mm, 12 control contacts) RK EMR 11001150
89-20556 for connection of EMR 1100 / EMR 1100 S with control terminal strip (length: 1500 mm, 12 control contacts) RK EMR 11001500
89-20559 for connection of the basic unit with the extension unit (length: 6 m, 12 control contacts)

SS 126000

Reactive power factor control relay package


Completely assembled and tested units comprising:
Power factor control relay with control terminal strip, thermal trip contact and relay cable, length: 1150 mm
34-72016 RM 9606, control terminal strip with thermal trip contact, cable length: 1150 mm

STRRM 9606

34-72024 EMR 1100 S, control terminal strip with thermal trip contact, cable length: 1150 mm

STREMR 1100 S

34-72002 EMR 1100, control terminal strip with thermal trip contact, cable length: 1150 mm

STREMR 1100

RKL-EMR 1100

RKL-RM 9606

35

Modular Construction System


MCS System

Technical Data
Copper busbar holders, NH-fuses
For the design of power factor correction systems
FRAKO recommend to use the below-mentioned
devices and fuses.
The busbar holders have a centre to centre distance
of 60 mm to the single copper busbars. The copper
busbars have either dimensions of 30 5 mm or 30 10
mm, depending on the total power of the power factor
correction system.
Article-No. Description
90-00046

voltage of 690 VAC, can be used. These NH-fuse holders are also available as bus-mounting fuse holders for
direct mounting on a busbar system with a bar centre to
centre distance of 60 mm, or for mounting on mounting
plates.
Article-No. Description
90-00043

NH-bus-mounting fuse base size 00, 160 A, 690 VAC

34-80280

NH-bus-mounting fuse base size 00, 160 A, 690 VAC

90-00162

NH-fuse base for plate mounting


size 00, 160 A, 690 VAC

34-80283

NH-fuse base for plate mounting


size 00, 160 A, 690 VAC

90-00142

Cover for NH-fuses with nonisolated grip lugs

Busbar holder with a bar centre to centre


distance of 60 mm, Cu 30x10mm

90-00046

34-80283

34-80280

NH-isolating switch size 00. Applicable up to a mains


rated voltage of 690 VAC. Available as NH-bus-mounting
isolating switches for direct mounting on a busbar system
with 60 mm bar centre to centre distance, or for mounting
on mounting plates.
90-00162

90-00043

Article-No. Description

When operating the above mentioned devices,


please note that special attention has to be paid to
the corresponding safety regulations, especially the
regulations concerning accident prevention!

90-00167

NH-isolating switch for plate mounting


size 00, 160 A, 690 VAC

34-80282

NH-isolating switch for plate mounting


size 00, 160 A, 690 VAC

90-00166

NH-bus-mounting isolating switch


size 00, 160 A, 690 VAC

Article-No. Description

34-80281

NH-bus-mounting isolating switch


size 00, 160 A, 690 VAC

90-00041 D0-fuse NEOZED 4A, E14

90-00061 D0-fuse NEOZED 2A, E14


90-00092 D0-fuse NEOZED 6A, E14
90-00229 Fuse link with nonisolated metal grip lugs 25 A, 500 VAC
90-00062 Fuse link with isolated metal grip lugs 25 A, 500 VAC
90-00131 Fuse link with nonisolated metal grip lugs 35 A, 500 VAC
90-00056 Fuse link with isolated metal grip lugs 35 A, 500 VAC
90-00130 Fuse link with nonisolated metal grip lugs 50 A, 500 VAC
90-00055 Fuse link with isolated metal grip lugs 50 A, 500 VAC

34-80281

34-80282

90-00125 Fuse link with nonisolated metal grip lugs 63 A, 500 VAC
90-00054 Fuse link with isolated metal grip lugs 63 A, 500 VAC
90-00124 Fuse link with nonisolated metal grip lugs 80 A, 500 VAC
90-00053 Fuse link with isolated metal grip lugs 80 A, 500 VAC
90-00126 Fuse link with nonisolated metal grip lugs 100 A, 500 VAC
90-00052 Fuse link with isolated metal grip lugs 100 A, 500 VAC
90-00051 Fuse link with isolated metal grip lugs 125 A, 500 VAC
90-00050 Fuse link with isolated metal grip lugs 160 A, 500 VAC
90-00230 Fuse link with isolated metal grip lugs 35 A, 690 VAC

90-00166

90-00167

To assemble reasonably priced power factor correction


systems, NH-fuse holders size 00 up to a mains rated
36

90-00132 Fuse link with isolated metal grip lugs 40 A, 690 VAC
90-00111 Fuse link with isolated metal grip lugs 50 A, 690 VAC
90-00133 Fuse link with isolated metal grip lugs 63 A, 690 VAC

Modular Construction System


MCS System

Description
FRAKO MCS System, Specimen order 1

5. Step:

Example: assembly of an unchoked power factor corUHFWLRQV\VWHPZLWKWKHIROORZLQJVSHFLFDWLRQ

One 25 kvar step has a rated current of 36.1 A at 400 V,


50 Hz. This requires a protection with a 63 A, gl fuse. One
50 kvar step has a rated current of 72.2 A at 400 V, 50
Hz. This requires a protection with a 100 A, gl fuse. For
this system we would need altogether 6 pcs NH-fuses
63 A, 500 V, gl (Article-No. 90-00054) and 18 pcs NHfuses 100 A, 500 V, gl (Article-No. 90-00052). FRAKO
recommend to use NH-fuses with isolated grip lugs.

Total power:
Step rating:

350 kvar, 400 V, 50 Hz


2 25 kvar and 6 50 kvar

12-step power factor control relay with switching times


less than 5 seconds.
1. Step:
The system has 8 switching stages and requires a
12-step power factor control relay. Please select a reactive power control relay package with relay EMR 1100 S,
consisting of the relay, temperature switch for the monitoring of the cabinet temperature, terminal strip with
control system fuse and connecting cables.
2. Step:
The system requires 2 contactors for 25 kvar, 400 V,
50 Hz and 6 contactors for 50 kvar, 400 V, 50 Hz. Please
select contactors with series resistors:
25 kvar steps:
50 kvar steps:

contactors type K3-32K00


Article-No.: 89-00278
contactors type K3-62K00
Article-No.: 89-00276

3. Step:
Choose the power factor correction capacitors: Please
select standard power factor correction capacitors with a
rated voltage of 400 V for a mains rated voltage of 400 V.
For the 25 kvar step rating, depending on the construction and the available space, one can choose between
2 pcs. of LKT 12.5-400-DP, or 1 pc. of LKT 25.0-400-DP.
For the 50 kvar step one can choose between 4 pcs. of
LKT 12.5-400-DP or 2 pcs. of LKT 25.0-400-DP.
For the complete system one requires either 28 pcs.
of capacitor LKT 12.5-400-DP or 14 pcs. LKT 25.0400-DP.

6. Step:
For the fuse links, NH-bus-mounting isolating switches
size 00 (article-no. 90-00166) should be selected. For
the 8 steps, 8 pcs. of bus-mounting isolating switches
will be needed.
7. Step:
For the assembly of the busbar system FRAKO recommend a maximum space of 250 mm for the busbar
holders. So 8 pieces of busbar holders are needed
(article-no. 90-00046) for the busbar system.
Due to the total rated current of the system of 505A,
copper busbars with 30 10 mm are required.
8. Step:
ordering chart:
Qty Article-No. Description:
1

34-72024

complete power factor control relay


package EMR 1100S

89-00278

contactor K3-32K00

89-00276

contactor K3-62K00

28

31-10502

capacitor LKT 12.5-400-DP

88-02013

discharge reactor

90-00054

NH-fuse size 00, 63 A, 500 V, gl

18

90-00052

NH-fuse size 00, 100 A, 500 V, gl

90-00166

NH-bus-mounting isolating switch size: 00, 160 A

90-00046

busbar holder, 60 mm, 30x10 mm

4. Step:
The short switching times given, require a discharge of
the capacitors by means of discharge reactors. For 25
and 50 kvar the same discharge reactor can be selected.
The 8 capacitor steps require 8 discharge reactors.

37

Modular Construction System


MCS System

Description
FRAKO MCS System, Specimen order 2

5. Step:

Example: assembly of a power factor correction system


ZLWKWKHIROORZLQJVSHFLFDWLRQ

One 25 kvar step has a rated current of 36.1 A at 400 V,


50 Hz. This requires a protection with a 63 A, gl fuse. One
50 kvar step has a rated current of 72.2 A at 400 V, 50
Hz. This requires a protection with a 100 A, gl fuse. For
this system we would need altogether 3 pcs NH-fuses
63 A, 500 V, gl (Article-No. 90-00054) and 21 pcs NHfuses 100 A, 500 V, gl (Article-No. 90-00052). FRAKO
recommends to use NH-fuses with isolated grip lugs.

Total power: 375 kvar, 400 V, 50 Hz, series resonance


frequency of 189 Hz (7 %)
Step rating:

1 25 kvar and 7 50 kvar

Power factor control relay with 12 control contacts.


1. Step:
The system has 8 switching stages and requires a
12-step power factor control relay. We select a complete power factor control relay package with a relay
EMR 1100 S, consisting of the relay, temperature switch
for the monitoring of the cabinet temperature, clamp with
control fuse and connecting cables.
2. Step:

6. Step:
For the fuse links, NH-bus-mounting isolating switches
size 00 Article-No. 90-00166 should be selected. For
the 8 steps, 8 pcs. NH-bus-mounting isolating switches
would be needed.
7. Step:

The system requires one contactor for 25 kvar, 400 V,


50 Hz and 7 contactors for 50 kvar, 400 V, 50 Hz. Please
select contactors without series resistors.

For the assembly of a busbar system FRAKO recommend a maximum space of 250 mm for the busbar
holders. So 8 pieces of busbar holders are needed
(Article-No. 90-00046) for the busbar system.

25 kvar step:

contactor type K3-32A00,

8. Step:

Article-No.: 89-00290

ordering chart:

contactors type K3-62A00,

Qty Article-No. Description:

Article-No.: 89-00292

50 kvar steps:

34-72024

power factor control relay


package EMR 1100S

3. Step:

89-00290

contactor K3-32A00

Choose the power factor correction capacitors: Please


select standard power factor correction capacitors with
a rated voltage of 440 V or premium capacitors with
a rated voltage of 400 V for a mains rated voltage of
400 V. For the 25 kvar step rating we need 2 pcs. of
LKT 11.7-400-DL. For the 50 kvar step we need 4 pcs.
of LKT 11.7-400-DL.

89-00292

contactor K3-62A00

30

31-10604

capacitor LKT 11.7-400-DL

11)

88-01768

FDR 25-400-P7

72)

88-01769

FDR 50-400-P7

90-00054

NH-fuse size 00, 63 A, 500 V, gl

21

90-00052

NH-fuse size 00, 100 A, 500 V, gl

90-00166

NH-bus-mounting-isolating switch size 00, 160 A

90-00046

busbar holder, 60 mm, 30x10 mm

4. Step:
The 25 kvar step requires one 25 kvar reactor 1) and the
7 50 kvar steps require 7 50 kvar reactors 2).

38

Modules for Power Factor Correction Systems


Type C...C / C...D / C...D-E

The universal solution for all switchgear systems


Q Power Factor Correction Systems without reactors
Q Power Factor Correction Systems with reactors
Q Power Factor Correction Systems with reactors and thyristor switches
Q Compact design for mounting in all common low voltage switchgear systems

39

Modules for Power Factor Correction Systems


Type C

Decisive Advantages
Q Compact compensation module
Ideal for mounting in all common switchgear
systems
Q High performance in the smallest possible space
Up to 100 kvar for each module, with or without
reactors
Q Up to 5 modules per cabinet
Supplying 500 kvar even with 7 % reactors
Q Easy to service with a common bus bar
Upright bus bar and NH fuse elements. No
special cable required between the individual
modules for systems with two or more units

Design
Mounted and fully-wired galvanized sheet steel chassis
consisting of:
Q Self-healing power capacitors with a low-loss
SRO\SURS\OHQHIRLOGLHOHFWLFDQG3&%IUHHOOHUW\SH
LKT with discharge resistors acc. to DIN VDE 0560
parts 46 and 47, EN 60831-1 and 2 as well as IEC
831-1 and -2.
Q Capacitor contactors with leading resistor contacts
attenuate current peaks
Q Common mounting rail with locking elements
Q Fuse elements, 3-pin, NH00
Q /RZORVVOWHUUHDFWRUVZLWKWHPSHUDWXUHVZLWFKHV
for the following series resonance frequencies:

40

Version

Series
resonance
frequency

Detuning
factor

For mains
with utility
audiofrequency1)

3

+]

S 

+]

3

+]

S 

+]

1)

Please observe any deviation from utility company requirements.

,QDGGLWLRQDOVRQRWHYHUVLRQVSHFLFDWLRQVJLYHQLQRXU
Manual of Power Factor Correction.

Quick Mounting with Multifunctional


Rails
When designing this series, special attention was given
to the simplest way of installing modules in all commonly used switchgear systems. The mounting rails
used (shown in grey in the dimensional sketch) can
be supplied as an optional accessory. These replace
the time-consuming work of installation and drilling.
Only the control unit cutout and ventilation holes are
required. Once the rails are mounted, the modules are
VLPSO\LQVHUWHGDQGUPO\DWWDFKHGE\WZRVFUHZVLW
couldnt be simpler!

Modules for Power Factor Correction Systems


Type C

Connection

Accessories / Options

The cable is connected directly to the busbar. A connecting bracket CU-AW 1 can be supplied as an accessory
for vertical connection.
Ideal for all common switchgear systems, e.g.
MT-C8-...

Cabinet type

ABB

MNS

ELEK

Unistar

Hensel

SAS 2008

Moeller

Modan, IVS, ID, GU

Mona

Mona 5000

Rittal

TS, ES, PS

Siemens

SIKUS, Sivacon, 8MF, 8PU

Striebel & John

XA

Q Complete power factor control relay package STRRM 9606, STR-EMR 1100 S or STR-EMR 1100
Q Control cables from the control terminal strip to the
module are included with delivery together with pin
connections
Q Mounting plate SB-C8
Q Module rails MT-C8-...-cabinet depth (see table)
Q Bus connection bracket set CU AW-1
Q Fan package LP-LSFC
Q NH isolating switch instead of NH fuse elements
for group protection type designation: -SLT

Dimensional sketch
Module Grid Width
e.g. 758 for Rittal TS8804

Module Grid Height


300
25

Control cable, L = 1600

C...4 350
C...5 450
C...6 550

C6... 500
C8... 700

Front view
41

Modules for Power Factor Correction Systems


Type C...C

Technical Data
Design
Rated voltage
Rated power
Ingress
protection
Ambient
temperature
Air humidity

Sheet steel chassis with premounted


capacitors, fuses and contactors
Min. 440 V / 50 Hz (capacitors)
See table (at 400 V mains voltage)
IP 00 acc. to DIN 40 050,
for control cabinet mounting
5 to +60 C acc. to DIN VDE
0660 part 500 Sect. 6.1.1.1
(when assembled)
Max. 90 %, no condensation

Discharge
Power loss
Standards

Rated capacity
determination

With discharge resistors acc. to


VDE 0560, part 46
Capacitors: 0.5 W / kvar
Acc. to VDE 0560 Parts 46 and 47,
EN 60831-1 and -2 together with
IEC 831-1 and -2, VDE 0660 part
500 and EN 60439-1 with type test
TSK
See FRAKO Manual of Power
Factor Correction

Minimum rated voltage of capacitors 440 V / 50 Hz Rated power at 400 V / 50 Hz mains voltage other voltages on request
Article-No.

Rated Power
in kvar
at 400 V

Step Power
in kvar
at 400 V

Switching
sequence

Type and order code

Capacitor Module, type: C64C


34-64167

25.00

3.13

1:1:2:4

C64C 253.13211400/44064

34-64163

25.00

6.25

1:1:2

C64C 256.2521400/44064

34-64164

25.00

12.50

1:1

C64C 2512.52400/44064

34-64165

25.00

25.00

C64C 25251400/44064

34-64170

31.25

6.25

1:2:2

C64C 31.256.2512400/44064

34-64180

34.38

3.13

1:2:4...

C64C 34.383.13112400/44064

34-64172

37.50

6.25

1:1:2...

C64C 37.56.2522400/44064

34-64173

37.50

12.50

34-64177

43.75

34-64181
34-64288

1:2

C64C 37.512.511400/44064

6.25

1:2:4

C64C 43.756.25111400/44064

46.88

3.13

1:2:4:8

C64C 46.883.131111400/44064

50.00

3.13

1:1:2:4:8

C64C 503.132111400/44064

34-64182

50.00

6.25

1:1:2:4

C64C 506.25211400/44064

34-64185

50.00

12.50

1:1:2

C64C 5012.521400/44064

34-64186

50.00

25.00

1:1

C64C 50252400/44064

34-64187

50.00

50.00

C64C 50501400/44064

34-64193

62.50

12.50

1:2:2

C64C 62.512.512400/44064

34-64194

68.75

6.25

1:2:4...

C64C 68.756.25112400/44064

34-64845

75.00

12.50

1:2:3

C64C 7512.511A400/44064

34-64200

75.00

25.00

1:2

C64C 752511400/44064

34-64203

87.50

12.50

1:2:4

C64C 87.512.5111400/44064

34-64205

93.75

6.25

1:2:4:8

C64C 93.756.251111400/44064

34-64206

100.00

12.50

1:1:2:4

C64C 10012.5211400/44064

34-64208

100.00

25.00

1:1:2

C64C 1002521400/44064

34-64188

100.00

50.00

1:1

C64C 100502400/44064

Dimensions C64D: WxHxD 500x300x350 mm (for cabinets with a min. W / D: 600 x 400 mm)

42

Modules for Power Factor Correction Systems


Type C...C

Article-No.

Rated Power
in kvar
at 400 V

Step Power
in kvar
at 400 V

Switching
Sequence

Type and order code

Capacitor-Reactor-Module, type: C84C


34-64289

25.00

3.13

1:1:2:4

C84C 253.13211400/44084

34-64290

25.00

6.25

1:1:2

C84C 256.2521400/44084

34-64213

25.00

12.50

1:1

C84C 2512.52400/44084

34-64214

25.00

25.00

C84C 25251400/44084

34-64291

31.25

6.25

1:2:2

C84C 31.256.2512400/44084

34-64292

34.38

3.13

1:2:4...

C84C 34.383.13112400/44084

34-64293

37.50

6.25

1:1:2...

C84C 37.56.2522400/44084

34-64215

37.50

12.50

1:2

C84C 37.512.511400/44084

34-64294

43.75

6.25

1:2:4

C84C 43.756.25111400/44084

34-64295

46.88

3.13

1:2:4:8

C84C 46.883.131111400/44084

34-64296

50.00

3.13

1:1:2:4:8

C84C 503.132111400/44084

34-64297

50.00

6.25

1:1:2:4

C84C 506.25211400/44084

34-64217

50.00

12.50

1:1:2

C84C 5012.521400/44084

34-64218

50.00

25.00

1:1

C84C 50252400/44084

34-64219

50.00

50.00

C84C 50501400/44084

34-64222

62.50

12.50

1:2:2

C84C 62.512.512400/44084

34-64298

68.75

6.25

34-64846

75.00

34-64224
34-64227

1:2:4...

C84C 68.756.25112400/44084

12.50

1:2:3

C84C 7512.511A400/44084

75.00

25.00

1:2

C84C 752511400/44084

87.50

12.50

1:2:4

C84C 87.512.5111400/44084

34-64229

93.75

6.25

1:2:4:8

C84C 93.756.251111400/44084

34-64126

100.00

12.50

1:1:2:4

C84C 10012.5211400/44084

34-64232

100.00

25.00

1:1:2

C84C 1002521400/44084

34-64127

100.00

50.00

1:1

C84C 100502400/44084

Dimensions C84C: WxHxD 700x300x350 mm (for cabinets with a min. W / D: 800 x 400 mm)

43

Modules for Power Factor Correction Systems


Type C...D

Technical Data
Design

Rated voltage
Rated power
Ingress
protection
Ambient
temperature
Air humidity

Sheet steel chassis with premounted


FDSDFLWRUVOWHUUHDFWRUVIXVHV
and contactors
Min. 440 V / 50 Hz (Capacitors)
See table (at 400 V mains voltage)
IP 00 acc. to DIN 40 050,
for cabinet mounting
5 to +60 C acc. to DIN VDE
0660 part 500 Sect. 6.1.1.1
(when assembled)
Max. 90 %, no condensation

Discharge
Power loss

Standards

Rated capacity
determination

With discharge resistors acc. to


VDE 0560, Part 46
Capacitors: 0.5 W / kvar, reactors:
3.56 W / kvar (depending on version and harmonic distortion)
Acc. to VDE 0560 parts 46 and 47,
EN 60831-1 and -2 as well as IEC
831-1 and -2, VDE 0660 part 500
and EN 60439-1 with type test TSK
See FRAKO Manual of Power
Factor Correction

Minimum rated voltage of capacitors 440 V / 50 Hz Rated power at 400 V / 50 Hz mains voltage other voltages on request
Article-No.

Rated Power
in kvar
at 400 V

Step Power
in kvar
at 400 V

Switching
Sequence

Type and order code

Capacitor-Reactor-Module, type: C64D / C65D


P1: series resonance frequency 134Hz, p = 14%
34-64264

25.00

6.25

1:1:2

C64D 256.2521400/48064P1

34-64242

25.00

12.50

1:1

C64D 2512.52400/48064P1

34-64243

25.00

25.00

C64D 25251400/48064P1

34-64244

50.00

50.00

C64D 50501400/48064P1

P7: series resonance frequency 189Hz, p = 7%


34-64300

25.00

3.13

1:1:2:4

C64D 253.13211400/44064P7

34-64257

25.00

6.25

1:1:2

C64D 256.2521400/44064P7

34-64262

25.00

12.50

1:1

C64D 2512.52400/44064P7

34-64245

25.00

25.00

C64D 25251400/44064P7

34-64301

31.25

6.25

1:2:2

C64D 31.256.2512400/44064P7

34-64389

34.38

3.13

1:2:4

C64D 34.383.13112400/44064P7

34-64246

37.50

12.50

1:2

C64D 37.512.511400/44064P7

34-64247

43.75

6.25

1:2:4

C64D 43.756.25111400/44064P7

34-64248

50.00

12.50

1:1:2

C64D 5012.521400/44064P7

34-64249

50.00

25.00

1:1

C64D 50252400/44064P7

34-64250

50.00

50.00

C64D 50501400/44064P7

34-64261

75.00

25.00

1:2

C65D 752511400/44065P7

Dimensions C64D: WxHxD 500x300x350 mm (for cabinets with a min. W / D: 600 x 400 mm)
Dimensions C65D: WxHxD 500x300x450 mm (for cabinets with a min. W / D: 600 x 500 mm)

44

Modules for Power Factor Correction Systems


Type C...D

Article-No.

Rated Power
in kvar
at 400 V

Step Power
in kvar
at 400 V

Switching
Sequence

Type and order code

Capacitor-Reactor-Module, type: C84D / C85D


P1: series resonance frequency 134Hz, p = 14%
34-64069

25.00

6.25

1:1:2

C84D 256.2521400/48084P1

34-64070

25.00

12.50

1:1

C84D 2512.52400/48084P1

34-64039

25.00

25.00

C84D 25251400/48084P1

34-64271

31.25

6.25

1:2:2

C84D 31.256.2512400/48084P1

34-64374

37.50

6.25

1:1:2...

C84D 37.56.2522400/48084P1

34-64018

37.50

12.50

1:2

C84D 37.512.511400/48084P1

34-64002

43.75

6.25

1:2:4

C84D 43.756.25111400/48084P1

34-64003

50.00

12.50

1:1:2

C84D 5012.521400/48084P1

34-64004

50.00

25.00

1:1

C84D 50252400/48084P1

34-64005

50.00

50.00

C84D 50501400/48084P1

34-64006

75.00

25.00

1:2

C84D 752511400/48084P1

34-64040

100.00

50.00

1:1

C85D 100502400/48085P1

P7: series resonance frequency 189Hz, p = 7 %


34-64071

25.00

6.25

1:1:2

C84D 256.2521400/44084P7

34-64072

25.00

12.50

1:1

C84D 2512.52400/44084P7

34-64015

25.00

25.00

C84D 25251400/44084P7

34-64339

31.25

6.25

1:2:2

C84D 31.256.2512400/44084P7

34-64073

43.75

6.25

1:2:4

C84D 43.756.25111400/44084P7

34-64305

46.88

3.13

1:2:4:8

C84D 46.883.131111400/44084P7

34-64007

50.00

6.25

1:1:2:4

C84D 506.25211400/44084P7

34-64008

50.00

12.50

1:1:2

C84D 5012.521400/44084P7

34-64009

50.00

25.00

1:1

C84D 50252400/44084P7

34-64010

50.00

50.00

C84D 50501400/44084P7

34-64041

62.50

12.50

1:2:2

C84D 62.512.512400/44084P7

34-64074

68.75

6.25

34-64848

75.00

34-64011
34-64012

1:2:4...

C84D 68.756.25112400/44084P7

12.50

1:2:3

C84D 7512.511A400/44084P7

75.00

25.00

1:2

C84D 752511400/44084P7

87.50

12.50

1:2:4

C84D 87.512.5111400/44084P7

34-64648

100.00

12.50

1:1:2...

C85D 10012.5211400/44085P7

34-64013

100.00

25.00

1:1:2

C84D 1002521400/44084P7

34-64014

100.00

50.00

1:1

C84D 100502400/44084P7

Dimensions C84D: WxHxD 700x300x350 mm (for cabinets with a min. W / D: 800 x 400 mm)
Dimensions C85D: WxHxD 700x300x450 mm (for cabinets with a min. W / D: 800 x 500 mm)

45

Modules for Power Factor Correction Systems


Type C

Description
Application / Installation
The Power Factor Correction Module Type C is the ideal
answer for designing power factor correction systems.
It can be choked or unchoked and reach a capacity of
up to 400 kvar per enclosure. The enclosure can be up
to 2.000 mm high and 400 mm deep. When installing
VHYHUDOPRGXOHVWKH\VKRXOGEHPRXQWHGUVWDWWKH
bottom, working upwards. This enables additional modules to be installed at a later date without disconnecting
the cable. If the feed-in is at the top of the enclosure
the modules should be mounted from top to bottom.
Prewired control cabling can be used for connecting the
power factor control relay to the control terminal strip
and the individual modules. The mounting rails of the
module have folding tabs to which a vertical connecting
cable can be attached. To ensure that the system can
be extended at a later date, the cable and its protective
device as well as any audiofrequency rejector circuit
UHTXLUHGVKRXOGEHGHVLJQHGWRPHHWWKHQDOVSHFLcations of the system.

Slot 5:

Example
Design of a power factor correction system with reactors in an enclosure (Rittal TS8804) with dimensions
800 2.000 400 mm (H W D), with a nominal
capacity of 300 kvar, with 6 steps each of 50 kvar,
switching sequence 1:1:2...
Components required:
Q 1 complete power factor control relay package
STR-EMR 1100,consisting of EMR 1100, RKL-EMR
1100 and RK EMR 1100-1150
Q 1 mounting plate SB-C8
Q 3 capacitor choke modules C84D 100-50-2-400-P..
The control cable from the control terminal strip
to the modules together with pin connections are
included in delivery.
Q 8 mounting rails MT-C8-Rittal TS8-400
Q 1 connecting bracket set CU AW-1
Q 1 fan package LP-LSFC
RK EMR 1100-1150

Space for the control unit. The mounting plate SB... has
room for the control terminal strip RKL... with control
transformer and thermostat if required.

Slot 4:

Power Factor
Control Relay
EMR 1100

Space for an additional capacitor/reactor module.

Slot 3:
Space for the third capacitor/reactor module.

Slot 2:
Space for the second capacitor/reactor module.

Slot 1:
6SDFHIRUWKHUVWPRGXOH7KHEXVEDUVHW&8
$:HQDEOHVWKHUVWFDSDFLWRUFKRNHPRGXOHWR
be connected vertically if required.

46

Control cable with


pin connections
are included with
the capacitor/reactor module!
The mounting rails
have folding tabs
for attaching a
vertical connecting
cable.

Modules for Dynamic Power Factor Correction


Systems
Type C...D-E

The SBS dynamic power factor correction unit


from FRAKO features:
Q No delay in switching in capacitance thanks to
FRAKOs fast-acting control system
Q Fastest possible direct compensation by SBS
unit with superposed power factor control loop
Q No additional active power losses through
discharge reactors
Q Continuous rating, no auxiliary contactors in parallel
Q Compact design achieved by new cooling technique
Q Solid-state switches mean no limit on number of
switching cycles and no wear and tear
Q Patented control principle offers excellent
price/performance ratio
7KHEHQHWV
Q Optimum network utilization
Q Improved power quality, hence best product quality
Q Reduced energy costs
Typical Applications
Q Modular design, the same construction as
FRAKO C Modules
7KH 6%6 G\QDPLF SRZHU IDFWRU FRUUHFWLRQ XQLW QGV Q Predictive control with superposed feedback control
application in low voltage networks:
Nothing could be faster!
Q With low short-circuit capacities where disruptions
occur when large consumers are switched on
Q Where a fast-acting power factor correction
Typical low voltage networks are those supplying:
system and a large number of switching cycles are
Q Spot welding machines
necessary
Q Motors with high power ratings
Q Where power factor correction is required for only
Q Rolling mills, kneading machine drives, etc.
a few supply cycles at a time
47

Modules for Dynamic Power Factor Correction


Systems
Type C...D-E
Power Factor Correction
All electrical consumers that make use of a magnetic
HOG LQ RUGHU WR IXQFWLRQ VXFK DV LQGXFWLRQ PRWRUV
chokes and transformers, draw not only active current
from the supply network but also reactive current. This
current is necessary to create and reverse the magnetic
HOGDQGLWRZVEDFNDQGIRUWKEHWZHHQWKHJHQHUDWRU
(at the power station) and the load.
As the electrical supply network must be dimensioned
to carry the total current, the goal is always to keep the
reactive current as low as possible.
cos=0.7

GEN

Active power P

Active power P

Reactive power Q

Reactive power Q

7KHUHDFWLYHSRZHURZLQJEHWZHHQWKHJHQHUDWRUDQG
the load is converted into heat in the supply lines.
This represents an additional load on generators,
transformers, cabling and switchgear. Power losses
and voltage drops also result. With a high proportion
of reactive current, the installed conductor cross sections cannot be fully utilized for power transmission or
need to be overdimensioned to cope. From the point of
view of the power supply company, poor power factors
increase the investment and maintenance costs for the
supply network. These additional costs are charged to
the consumers causing the problem, i.e. those drawing
a high proportion of reactive current.
If suitably sized capacitors are installed in parallel to the
ORDGVWKHUHDFWLYHFXUUHQWRZVEDFNDQGIRUWKEHWZHHQ
the capacitors and the loads. There is then no additional
load on the rest of the supply network. If a power factor
of 1 is achieved by means of these corrective measures,
only active current is carried by the network.

UROOLQJPLOOVLQZKLFKJUHDWORDGXFWXDWLRQVRFFXUDQG
the drives for kneading machines, shredders and large
presses.
The starting inrush currents can cause major upsets,
particularly in production lines with spot welding machines.
The conventional approach has been to design the supply networks for installations of this type with extremely
high short-circuit capacities. Increasing the transformer
capacity or interconnecting several transformers at the
low voltage side is not always economically viable. The
most cost-effective solution is therefore to compensate
for the reactive current with response times in the order
of milliseconds. Conventional power factor correction
systems switch in the capacitor stages by means
of contactors with a service life up to a maximum of
80,000 switching cycles. A reactive power control relay
switches the stages in when the capacitors are in a
discharged condition. This usually results in a delay of
some 60 seconds before the capacitors can be switched
in again.
Even when using a reactive power control relay that
measures reactive power demand within 1 or 2 supply
cycles, it may not be possible to reduce the delay in correcting the inductive reactive power below 100 to 200ms
because of the required stability of the control loop. This
is too slow for those applications in which voltage dips
DQGLFNHUPXVWEHFRUUHFWHG,QRUGHUWRVXSSUHVVWKH
above disruptions to the network effectively, the required corrective capacitance must be switched in within
a few milliseconds. Problems of this type can be solved
optimally with a FRAKO SBS fast-acting power factor
control unit.

cos= 1

Costs saved

Active power P
Costs saved

Reactive power Q

GEN

Active power P

The most cost-effective and easily monitored method for


power factor correction is the central system. With this
variant the entire capacitor bank is installed at a central
location, for example the low voltage main distribution
board. The required capacitance is divided into several
switchable stages, which are switched in and out by
special capacitor contactors controlled by an automatic reactive power control relay to suit load conditions.
When motors are switched on, there is a transient
reactive current peak, which can result in serious voltage dips, depending on the short-circuit capacity of the
network. Modern production lines require machinery of
ever-increasing power and therefore necessitate more
stable low voltage networks. Typical applications include
48

Act or react?
Feedback control means:
Measure switch measure correct measure correct and so on until the difference between the target
and actual power factors is less than the correction
provided by one capacitor stage. At a supply frequency
of 50 Hz, each measurement takes at least one to two
cycles to carry out, i.e. 20 to 40 ms. In order to avoid
instability, a classical control relay always switches
in only a part (40 to 60 %) of the capacitor allocation
FRPSXWHGIURPWKHUVWPHDVXUHPHQW6HYHUDOKXQGUHG
milliseconds or as much as a second can then elapse
until the corrective action is complete.
Predictive control means:
1RWUVWPHDVXULQJEXWLPPHGLDWHO\VZLWFKLQJLQFDSDcitance. The signal to switch on an inductive load is

Modules for Dynamic Power Factor Correction


Systems
Type C...D-E
simultaneously an input signal to the FRAKO SBS,
causing it to compensate directly for the reactive power
demand of that load. The corrective action is effective at
the latest 3 to 24 ms after the switching signal.
Nothing could be faster!
This is the solution for low voltage networks with fastswitching inductive loads to:
Q6XSSUHVVLFNHUDQG
Q Stabilize the supply voltage.

Control Methods

0 kvar
approx. 150 seconds

approx. 150 seconds

25 kvar

Power factor correction as our grandfathers knew it:


the classical reactive power control relay using contactors to switch capacitor stages of different sizes in
and out in a progressive sequence. It requires some
30 seconds per switching step until the target power
factor is achieved.
The contactor serving the smallest capacitor stage has
the shortest working life due to its frequent switching.
b) FRAKO RM 9606 or EMR 1100 reactive power control
relays
Reactive power demand

25 kvar

0 kvar
approx. 50 ms

approx. 50 ms

50 kvar

100 kvar

Reaction of the stages

Reactive power demand

c) Dynamic correction with the FRAKO RM 2012 reactive power control relay

25 kvar

125 kvar

0 kvar
5 - 30 seconds

25 kvar

5 - 30 seconds

Reaction of stages

Reaction of the stages

Reactive power demand

a) The classical reactive power control relay using stepby-step progressive switching

FRAKO reactive power control relays adjust the


switching delay to suit the power demand. Large changes of load are compensated for quickly, minor load
variations more slowly. Capacitor stages of different
sizes are switched in selectively to match the power
demand, the number of switching operations minimized
by computation, and all equally sized capacitor stages
are used in rotation. These control characteristics
combine to give a uniform utilization of the capacitor
contactors and the lowest possible number of switching
cycles, thus reducing wear and tear in the power factor
correction system.
At the same time, critical network constellations are
avoided unlike in the classical step-by-step switching
process by rapidly adjusting the capacitor allocation
to match demand precisely when major load changes
occur.

25 kvar

50 kvar

100 kvar

The FRAKO RM 2012 reactive power control relay has


all the monitoring functions necessary incorporated
in it, since stable control characteristics are a prime
concern. As soon as the control relay detects reactive
power demand, it computes the sequences requiring
WKHOHDVWQXPEHURIVZLWFKLQJRSHUDWLRQVYHULHVWKH
selected setting in an additional measurement operation
and initiates switching. This makes the control characteristics absolutely stable with no hunting. With classical
power factor correction systems this process protects
the contactors. With dynamic correction systems it reduces the number of switching operations in the network.
,W HIIHFWLYHO\ VXSSUHVVHV QHWZRUN XFWXDWLRQV EHWWHU
than switching too quickly and hence overshooting and
undershooting several times. This variant represents the
best solution for power factor correction in installations
such as rolling mills or kneading machines, where a
switching delay of 0.5 1.0 seconds is acceptable.

50 kvar

100 kvar

49

Modules for Dynamic Power Factor Correction


Systems
Type C...D-E

Reaction of the stages

Reactive power demand

d) Dynamic correction with the FRAKO SBS


125 kvar

0 kvar

25 kvar

50 kvar

100 kvar

Just as quick as individual power factor correction


for each load, but considerably less expensive, due
to the intelligent control system, which converts the
reactive power demand from all loads into the capacitor
stage allocation for the power factor correction system.
The fast-acting control system ensures that the required
power factor correction is achieved within 3 24 ms,
depending on the phase angle of the switching signal.
Just as accurate as feedback control, since a superposed reactive power control relay compensates for the
remaining reactive power demand not covered by the
predictive control system.

The Ideal Formula


Q The SBS dynamic power factor correction unit from
FRAKO switches without delay at the next voltage
zero at the thyristor switch and thus avoids any
peak inrush current.
Q Any desired frequency of switching with no contact
wear and tear and no additional loss of active
power. The solid-state switches function without
any problems even when the capacitors are not
discharged and without causing peak inrush
currents.
Q Power circuits are designed for a continuous
rating, i.e. no parallel auxiliary contactor is needed
to reduce the load on the thyristors. The switching
delay of at least 50 ms when using auxiliary
contactors is therefore also not necessary.

Power Factor Correction and


Network Stabilization
Q An innovative cooling technique makes the unit
particularly compact.
Q The service life of capacitor contactors is normally
limited to a maximum of 80,000 switching cycles.
In the case of installations with frequent switching,
such as welding systems, it is necessary to cater
for at least 108 switching cycles. The FRAKO SBS
unit is designed for duties of this type.
Q FRAKOs patented predictive control principle
enables the reactive power to be compensated for
as quickly as possible for as much switched load
capacity as desired. The reactive power demand
from loads of any power rating is converted without
delay into the optimum allocation of capacitor
stages for that load.
Q The greater part of the reactive power is
compensated for without delay. This eliminates
PDMRUYROWDJHGLSVWKDWFRXOGUHVXOWLQLFNHU7KH
superposed reactive power control relay then
compensates for the remaining reactive power
demand. These signals are also processed by
the control unit, which determines the required
capacitor allocation from their sum total.
Q Until now, a comparable response without delay
was only possible when correcting the power factor
for large reactive loads by assigning a rapidly
switched-in capacitor stage to each individual load.
In contrast, the SBS is a variant that cuts costs
and offers the fastest possible switching response.
Numerous inputs with widely differing reactive
power demands are converted into the equivalent
capacitor allocation for the power factor correction
system.

Load
... kvar ON

Load
... kvar ON

Load
... kvar ON

Load
... kvar ON

...etc.

Fast-acting power factor control unit

25 kvar

50

50 kvar

100 kvar

Modules for Dynamic Power Factor Correction


Systems
Type C...D-E
Technical Data
Design

Rated voltage
Rated power
Protection
Ambient
temperature
Air humidity

Discharge

Sheet steel chassis with premounted FDSDFLWRUVOWHUUHDFWRUV


fuses and contactors
Min. 440 V / 50 Hz (capacitors)
See table (at 400 V mains voltage)
IP 00 acc. to DIN 40 050,
for cabinet mounting
5 to +60 C acc. DIN VDE 0660
part 500 sect. 6.1.1.1
(when assembled)
Max. 90 %, no condensation

Power loss

Standards

Rated capacity
determination

With discharge resistors acc.


to VDE 0560, part 46
Capacitors: 0.5 W / kvar
Reactors: 3.5-6 W / kvar
(depending on version and
harmonic distortion)
Acc. VDE 0560 parts 46 and 47,
EN 60831-1 and -2 as well as
IEC 831-1 and -2, VDE 0660 part
500 and EN 60439-1 with type
test TSK
See FRAKO Manual of Power
Factor Correction

Minimum rated voltage of capacitors 440 V / 50 Hz Rated power at 400 V / 50 Hz mains voltage other voltages on request
Article-No.

Rated Power Step Power


in kvar
in kvar
at 400 V
at 400 V

Switching
sequence

Type and order code

Capacitor-Reactor-Module, type: C84D-E / C85D-E, wear-free and fast switching, with thyristors
P1: series resonance frequency 134Hz, p = 14%
-

25.00

25.00

C84D 25251400/48084P1E

37.50

12.50

1:2

C84D 37.512.511400/48084P1E

34-64802

50.00

25.00

1:1

C84D 50252400/48084P1E

50.00

50.00

C84D 50501400/48084P1E

34-64376

75.00

25.00

1:2

C85D 752511400/48085P1E

34-64036

100.00

50.00

1:1

C85D 100502400/48085P1E

P7: series resonance frequency 189 Hz, p = 7%


34-64028

25.00

25.00

C84D 25251400/44084P7E

34-64061

37.50

12.50

1:2

C84D 37.512.511400/44084P7E

34-64029

50.00

25.00

1:1

C84D 50252400/44084P7E

34-64030

50.00

50.00

C84D 50501400/44084P7E

34-64031

75.00

25.00

1:2

C85D 752511400/44085P7E

34-64032

100.00

50.00

1:1

C85D 100502400/44085P7E

Accessories
34-80056

Power supply 24 VDC / 2.5 A - for thyristor switches, built on the


mounting plate and wired up to the control terminal

SBS-PS 24VDC-2.5A

Dimensions C84D: WxHxD 700x300x350 mm (for cabinets with a min. W / D: 800 x 400 mm)
Dimensions C85D: WxHxD 700x300x450 mm (for cabinets with a min. W / D: 800 x 500 mm)

Dimensional Sketch

51

Components for Dynamic Power Factor


Correction Systems
Thyristor switches type DCS
Description
A skilled switchgear manufacturer can easily design
and assemble his own Dynamic PFC System by using
dynamic PFC components from FRAKO.

Article No.

Type

Dimensions (WxHxD):

34-80274

DCS 50 x 1-400/415

430x265x170mm

34-80243

DCS 50 x 2-400/415

430x265x170mm

34-80275

DCS 50 x 1-440/525

430x265x170mm

34-80276

DCS 50 x 2-440/525

430x265x170mm

These dynamic components are also used in


FRAKOs own modules for Dynamic Power Factor
Correction Systems (see technical data, page 51).

Accessories:
39-21010

Power Supply-6-thyristor switches 115/230 VAC - 24 VDC

39-29050

with 12 control contacts, 6 with reaction time between 20/40 ms

RM 2012 6+6D

39-29051

with 12 control contacts, reaction time between 20/40 ms

RM 2012 12D

34-80243 front

52

34-80243 back

Medium Voltage Capacitors


Type MSCD / MSCE

Features that matter:


Q Voltage rating from 3 to 24 kV, 50 Hz or 60 Hz
Q Power rating from 50 to 700 kvar per capacitor casing
Q Single- and three-phase capacitors
Q For indoor or outdoor installation
Q IEC 60871-1, IEC 60871-2 and IEC 60871-4 compliance

53

Medium Voltage Capacitors


Type MSCD / MSCE

Technology

Safety

FRAKO Medium Voltage (MV) Capacitors have been


VXFFHVVIXOO\PDQXIDFWXUHGIRUPDQ\\HDUVXVLQJDOOOP
technology.
The dielectric material consists of high quality polypropyOHQHOPVDQGZLFKHGEHWZHHQDOXPLQLXPIRLOHOHFWURGHV
A large number of capacitor elements are assembled
to form a capacitor unit (see Fig. 1), also known as a
winding pack. If desired by the customer, the elements
can be provided with internal fuses. Each capacitor
unit is permanently connected to a discharge resistor.
The winding packs are housed in a sheet steel casing,
ZKLFKLVOOHGZLWKDKLJKTXDOLW\HQYLURQPHQWDOO\VRXQG
impregnating oil.
Residual moisture and oxygen are removed from the
winding pack in a drying and impregnation process
taking place under vacuum at an increased temperature
and lasting several days. The process is carried out very
carefully by experienced personnel. This is crucial to
producing a quality capacitor that is highly reliable and
offers a long life expectancy.
Following this process, the capacitors are hermetically
sealed by welding and are subjected to a routine test
DFFRUGLQJWR,(&7KH\DUHWKHQJLYHQDQDO
QLVKZLWKDKLJKTXDOLW\SDLQW7KHFDSDFLWRUVFRPSO\
with the requirements of IEC 60871-1, IEC 60871-2
and IEC 60871-4. FRAKOs wide range of manufacturing facilities makes it possible to produce capacitors
in numerous dimensions with a variety of voltage and
power ratings.

Polypropylene film

FRAKO Medium Voltage Capacitors are manufactured in


two different versions: either for use with external fuses
RUDOUHDG\WWHGZLWKLQWHUQDOIXVHV

External Fuses
Fig. 2 illustrates the internal arrangement in a capacitor.
If it is overloaded, or another fault occurs, it is particularly
important to prevent the capacitor casing rupturing. We
therefore recommend the use of current-limiting HV HRC
fuses to IEC 60549. As heavy transient currents and high
voltages can occur when capacitors are switched in and
out, the fuse rating should be at least twice the value
of the capacitor current rating, and the voltage rating of
the HV HRC fuse should be one level higher than the
network nominal voltage (e. g. for a 12 kV network voltage use a fuse with a 24 kV voltage rating). IEC 60549
must be complied with.

Internal Fuses
)LJLOOXVWUDWHVWKHLQWHUQDOFRQJXUDWLRQDQGWKHRSHrating principle. Each capacitor element has its own
internal fuse, which can isolate the element if it breaks
down. The overloaded or damaged element is thus
disconnected from the network. This means that the
capacitor loses some of its capacitance, but is still able
to operate safely. Switching out individual elements in
this way has the consequence, however, that the voltage across the other elements generally rises. If many
individual elements are disconnected, the voltage acting
on the remaining elements can become too high. The
capacitor must then be taken out of service and repaired.
FRAKO internal fuses comply with the requirements of
IEC 60871-4.

Discharge resistor
Aluminium foil

Internal fuse
Fig. 1:
Capacitor unit

54

Fig. 2:
Schematic of an
MV capacitor with
internal fuses

Fig. 3:
Operating principle of
the internal fuses

Medium Voltage Capacitors


Type MSCD/MSCE

Technical Data
Q
Q
Q
Q
Q
Q
Q
Q
Q

Voltage ratings from 3 to 24 kV, 50 or 60 Hz


Power rating 50 to 700 kvar per capacitor casing
Single-phase and three-phase capacitors
Available for indoor or outdoor installation
Overpressure switch available on request
Temperature class - 40C to + 50C
3RZHUORVV:NYDU
'LVFKDUJHWROHVVWKDQ9LQPLQXWHV
IEC 60871-1, IEC 60871-2 and IEC 60871-4
compliance

Operating reliability of
MV Capacitors

200

Voltage
rating kV
(at 50Hz)
6

580

760

160

MSCD 200-6

34

300

670

850

160

MSCD 300-6

46

400

870

1050

160

MSCD 400-6

57

500

810

990

175

MSCD 500-6

68

100

12

410

590

160

MSCD 100-12

22

200

12

580

760

160

MSCD 200-12

34

300

12

670

850

160

MSCD 300-12

46

400

12

870

1050

160

MSCD 400-12

57

500

12

810

990

175

MSCD 500-12

68

Power
kvar

H1
S mm

H2
mm

D
mm

Configuration

Type

Weight
kg

150

12

410

631

160

MSCE 150-12

31

250

12

670

891

160

MSCE 250-12

43

500

12

780

1001

175

MSCE 500-12

70

Other power and voltage ratings on request.


We reserve the right to change the technical data and dimensions.

Dimensions

Single-phase Medium Voltage Capacitors are frequently


FRQQHFWHGLQDGRXEOHVWDUFRQJXUDWLRQLQRUGHUWREH
used at higher network voltages. In these applications the
RSHUDWLQJUHOLDELOLW\RIWKHFDSDFLWRUVFDQEHVLJQLFDQWO\
increased by electronically monitoring the conductor between the star points of two capacitor groups, a current
WUDQVIRUPHUEHLQJXVHGWRPHDVXUHWKHFXUUHQWRZLQJ
between them. If a breakdown occurs in an element in
one of the capacitors, an unbalanced current will start
WR RZ WKURXJK WKH FXUUHQW WUDQVIRUPHU$Q HOHFWURQLF
relay monitors this current and sends an alarm signal to
the appropriate control system if the current reaches an
adjustable set point. The control system then switches
this capacitor bank out.
If the capacitor bank is tripped out in this way, it must be
LVRODWHGDQGWKHQLQVSHFWHGE\DSSURSULDWHO\TXDOLHG
electricians, any necessary repairs being carried out.

Network connection

C1

C2

Current transformer

Unbalance
protection relay

55

High Reliable Components

."!0!%&"$!'!0,!!/' /%'!%&$ +

!!!+$ !*
  
+)  

&&#((($"" +!"$""

FRAKO 95-00262 / 01/10 / 8450 Subject to technical changes

for Power Factor Correction and Power Quality

Potrebbero piacerti anche