Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ZTE
Document
revision no
R 1.0
R 2.0
Revised on
Resion for revision
2015/3/20 first draft
2015/5/6 change channel
ZTE
Content
1.Check EISU flash light ................................................................................................................... 4
2.Check alarm data through EISUconfig software .......................................................................... 4
3.How to debug door sensor and Bell Ring..................................................................................... 5
4.How to check smoke sensor ........................................................................................................ 7
5.How to check temperature sensor .............................................................................................. 9
6.How to check ground cut ........................................................................................................... 11
7.How to check DC Fan ................................................................................................................. 12
8.How to check IIC(infared air-condition controller) .................................................................... 13
9.How to set rectifier .................................................................................................................... 17
1.outdoor site........................................................................................................................ 17
2.Indoor site .......................................................................................................................... 18
10.How to check the comunication from EISU to BBU ................................................................. 19
11.How to check Card Holder ....................................................................................................... 22
12.How to check battery&feeder theft GND cut& AC remove & Phase and arrestor Failure ...... 25
13.Below Is For Add sensor site .................................................................................................... 28
1. you should remove the lid of EISU , and make the below S1-7 to on ........................... 28
2.Before config the channel In the board , you must stop the public module , follow the
next picture.(if no have this module just ignore) ........................................................... 29
3.set add sensor channel ...................................................................................................... 30
14.HOW TO Check add Sensor site sensor................................................................................... 31
1.temperature Sensor ........................................................................................................... 31
2.Smoke sensor ..................................................................................................................... 33
3.Door magnistor .................................................................................................................. 34
4.the battery theft and feeder theft are same ..................................................................... 36
ZTE
Connect LAN cable between host computer and EISU through network port
Set up host computer IP address to get into same network with EISU ( EISU default
server IP address is 10.72.88.80 ), the last two number can be any number, but cant
be same as EISU.
Open configuration program EISUCONFIG, password : 11111111, Click Scan Server IP
and double click the IP to be configured.
ZTE
ZTE
A. Open the door , EISU light ALRM1 flash. Close the door, alarm disappear.
B. Check from EISUconfig, DI50 channel alarm become 0.The chanel DI 50 for door sensor .
ZTE
ZTE
B. Blow the smoke sensor with cigarette smoke, DI13 channel alarm become 1
Select BOARD DO Parameter table , DO number 305 fill in channel field. Control way :
Pulse, Click DO Control button.
ZTE
A. Touch the IIC board with hand ( a black probedetector)or burn a lighter near IIC board
sensor ,the alarm data for AI-49 is dynamic and always change every time
ZTE
Before the IIC sensor is given some heat from lighter or hand touch
After the IIC sensor is given some heat from lighter or hand touch
ZTE
A. Pull out X3 socket from EISU alarm appear, connect it to EISU alarm
disappear.
ZTE
2.4
2.5
ZTE
ZTE
ZTE
0----turn on
1----turn up
2----turn up
3--------turn up
4----turn down
5-----turn down
6-----turn off
d how to test the IIC whether to contro the AC .
ZTE
ZTE
0063
ZTE
2.Indoor site (only ZXDU 58 need set and Rect ZXDU68 S301 no
need)
1.see to display rectifer choose CTR parameter push enter
2.choose pass 0000_ move the flash to right _ and push enter
0063
3.enter setup parameter go to 13 and 15 ; 13 seting 9600 15 seting device addr to 001
4 check the rectifier data from EISUconfig software .
ZTE
ZTE
ZTE
How to check the communication from EISU to BTS whether is ok or not .
1. Only measure the voltage from R(Rx) and Ground is about 4.70 V.
and measure from S(Tx) to Ground is 7.14 V (Look pictures below)
ZTE
ZTE
ZTE
Click softTrans than click read than click set until the display show sensor
ZTE
ZTE
ZTE
ZTE
ZTE
2.Before config the channel In the board , you must stop the
public module , follow the next picture.(if no have this module
just ignore)
The second module in the Read ALL Module Information must be stopped.
ZTE
ZTE
1.temperature Sensor
1) the temperature value is dynamic change ,channle 7 AI -7
ZTE
ZTE
2.Smoke sensor
ZTE
3.Door magnistor
1) open the door , the alarm show
ZTE
ZTE