14314-20160915-EK-PARKING_TYPICAL LVLv1.6.

cpt - 9/15/2016

Calc Log
Calculating All (Everything Out-of-Date)(Considering Previous Warnings)
Active Calculation Options:
The structure is not automatically stabilized in the X and Y directions.
Supports above slab NOT included in self-dead loading.
Tendon vertical component NOT considered in punch check reactions.
Design reinforcement.
6 zero-tension iterations are used to eliminate tension in area springs.
Creep Factor of 2 used in ECR and load history calculations.
Shrinkage strain of 0.0004 used in ECR and load history calculations.
ACI 318-05 is used in design.
Live load reduction not used
Assembling Stiffness Matrix.
148790 Degrees of Freedom
Triangularizing Stiffness Matrix.
Creating Self-Dead Loading.
No Tendons to Generate on Latitude Tendon Parameters layer
No Tendons to Generate on Longitude Tendon Parameters layer
An error has occurred while trying to calculate a profile. A profile point is not on the slab. Click on the Fix button to correct the profile point at (-172.3,-35.19) (Manual Longitude Tendon).
User Continued After Auto-Fixing Error
Creating Balance Loading.
Detailing User Reinforcement.
Determining Concrete Cross Sections
WARNING: Strip 58C-1, section 10 has no shear core.
User Continued After Warning
WARNING: Strip 58C-1, section 11 has no shear core.
User Continued After Warning
WARNING: Strip 58C-1, section 12 has no shear core.
User Continued After Warning
WARNING: Strip 65C-1, section 17 has no shear core.
User Continued After Warning
WARNING: Strip 104C-1, section 8 has a very small shear core.
User Continued After Warning
WARNING: Strip 178C-1, section 7 has a very small shear core.
User Continued After Warning
Determining Tendon Cross Sections
Determining Reinforcing Bar Cross Sections
Solving for Self-Dead Loading.
Solving for Self-Dead Loading - Pattern: Full Pattern.
Total Loads: (0,0,-12500) Kips
Total Reactions: (8.02e-11,-1.45e-10,12500) Kips
Load-Reaction Tolerance: (8.02e-11,-1.45e-10,-7.1e-10) Kips
Solving for Balance Loading.
Solving for Balance Loading - Pattern: Full Pattern.
Total Loads: (-0.000408,-0.00458,-0.000884) Kips
Total Reactions: (0.000408,0.00458,0.000884) Kips
Load-Reaction Tolerance: (6.23e-11,-3.68e-11,6.22e-10) Kips
Solving for Temporary Construction (At Stressing) Loading.
Temporary Construction (At Stressing) Loading has No Loads.
Solving for Other Dead Loading.
Solving for Other Dead Loading - Pattern: Full Pattern.
Total Loads: (0,0,-4030) Kips
Total Reactions: (3.75e-11,-5.15e-11,4030) Kips
Load-Reaction Tolerance: (3.75e-11,-5.15e-11,-9.38e-11) Kips
Solving for Live (Reducible) Loading.
Live (Reducible) Loading has No Loads.
Solving for Live (Unreducible) Loading.
Solving for Live (Unreducible) Loading - Pattern: Full Pattern.
Total Loads: (0,0,-3890) Kips
Total Reactions: (-1.07e-11,-8.74e-11,3890) Kips
Load-Reaction Tolerance: (-1.07e-11,-8.74e-11,-4.35e-10) Kips
Solving for Live (Storage) Loading.
Live (Storage) Loading has No Loads.
Solving for Live (Parking) Loading.
Live (Parking) Loading has No Loads.
Solving for Live (Roof) Loading.
Live (Roof) Loading has No Loads.
Calc Log - 1

14314-20160915-EK-PARKING_TYPICAL LVLv1.6.cpt - 9/15/2016

Calc Log (2)


Solving for Snow Loading.
Snow Loading has No Loads.
Solving for Balcony Trib Loading.
Balcony Trib Loading has No Loads.
Solving for Trib Loading.
Solving for Trib Loading - Pattern: Full Pattern.
Total Loads: (0,0,-97200) Kips
Total Reactions: (-2.56e-10,-2.2e-9,97200) Kips
Load-Reaction Tolerance: (-2.56e-10,-2.2e-9,-1.01e-8) Kips
Solving for Wind Loading.
Solving for Wind Loading - Pattern: Full Pattern.
Total Loads: (0,0,-1940) Kips
Total Reactions: (-5.34e-12,-4.37e-11,1940) Kips
Load-Reaction Tolerance: (-5.34e-12,-4.37e-11,-2.18e-10) Kips
Calculating Precompression in Cross Sections
Solving for Hyperstatic Loading.
Solving for All Dead LC.
Solving for Dead + Balance LC.
Solving for Initial Service LC.
Solving for Service LC: D + L.
Solving for Service LC: D + Lr.
Solving for Service LC: D + S.
Solving for Service LC: D + 0.75L + 0.75Lr.
Solving for Service LC: D + 0.75L + 0.75S.
Solving for Sustained Service LC.
Solving for Factored LC: 1.4D.
Solving for Factored LC: 1.2D + 1.6L + 0.5Lr.
Solving for Factored LC: 1.2D + f1L + 1.6Lr.
Solving for Factored LC: 1.2D + 1.6L + 0.5S.
Solving for Factored LC: 1.2D + f1L + 1.6S.
Solving for LT.
Solving for Factored LC: 1.2D + 1.0L + 1.0W.
Solving for Factored LC: 0.9D + 1.0W .
Calculating Code Minimum Design envelopes.
Calculating User Minimum Design envelopes.
Calculating Initial Service Design envelopes.
Calculating Service Design envelopes.
Calculating Sustained Service Design envelopes.
Calculating Strength Design envelopes.
Calculating Ductility Design envelopes.
Calculating Code Minimum Design - Pass 0
Calculating User Minimum Design - Pass 0
Calculating Initial Service Design - Pass 0
Calculating Service Design - Pass 0
Calculating Sustained Service Design - Pass 0
Calculating Strength Design - Pass 0
Calculating Ductility Design - Pass 0
Calculating Code Minimum Design - Pass 1
Calculating User Minimum Design - Pass 1
Calculating Initial Service Design - Pass 1
Calculating Service Design - Pass 1
Calculating Sustained Service Design - Pass 1
Calculating Strength Design - Pass 1
Calculating Ductility Design - Pass 1
Calculating Code Minimum Design - Pass 2
Calculating User Minimum Design - Pass 2
Calculating Initial Service Design - Pass 2
Calculating Service Design - Pass 2
Calculating Sustained Service Design - Pass 2
Calculating Strength Design - Pass 2
Calculating Ductility Design - Pass 2
Calculating Code Minimum Design - Final Design Check
Calculating User Minimum Design - Final Design Check
Calculating Initial Service Design - Final Design Check
Calculating Service Design - Final Design Check
Calculating Sustained Service Design - Final Design Check
Calc Log - 2

14314-20160915-EK-PARKING_TYPICAL LVLv1.6.cpt - 9/15/2016

Calc Log (3)


Calculating Strength Design - Final Design Check
Calculating Ductility Design - Final Design Check
Laying Out Program Reinforcement
WARNING: A cross section's reinforcement zone is very small at ((135.7,64.4)(135.7,64.4)). The layout manager may not be able to layout the bars properly.
User Continued After Warning
WARNING: A cross section's reinforcement zone is very small at ((133.3,66.8)(133.3,66.8)). The layout manager may not be able to layout the bars properly.
User Continued After Warning
WARNING: A cross section's reinforcement zone is very small at ((130.9,69.21)(130.9,69.21)). The layout manager may not be able to layout the bars properly.
User Continued After Warning
WARNING: A cross section's reinforcement zone is very small at ((54.22,145.9)(54.22,145.9)). The layout manager may not be able to layout the bars properly.
User Continued After Warning
Optimizing Program Reinforcement Layout
Converting SSR Designs
Converting Program Transverse Bar Designs
WARNING: Longitude transverse reinforcement at ((-108.5,-186.8)(-106.1,-186.8)) has a very small spacing (0.937 inches).
User Continued After Warning
WARNING: Longitude transverse reinforcement at ((-85.91,-186.8)(-83.48,-186.8)) has a very small spacing (0.937 inches).
User Continued After Warning
WARNING: Longitude transverse reinforcement at ((-78.79,-186.8)(-76.37,-186.8)) has a very small spacing (0.937 inches).
User Continued After Warning
WARNING: Longitude transverse reinforcement at ((136.5,65.01)(134.8,66.76)) has a very small spacing (1.024 inches).
User Continued After Warning
WARNING: Longitude transverse reinforcement at ((87.78,113.8)(86.02,115.6)) has a very small spacing (1.032 inches).
User Continued After Warning
WARNING: Longitude transverse reinforcement at ((82.54,119)(80.78,120.8)) has a very small spacing (1.032 inches).
User Continued After Warning
Detailing User Transverse Reinforcement
Detailing Program Reinforcement
WARNING: Latitude concentrated program reinforcement at (133.3,67.17) has a very small spacing (0.7382 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Latitude concentrated program reinforcement at (130.9,69.32) has a very small spacing (0.7382 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Latitude concentrated program reinforcement at (-176.2,97.55) has a very small spacing (0.873 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Latitude concentrated program reinforcement at (-177.1,158.5) has a very small spacing (1.433 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-97.08,-150.6) has a very small spacing (2.073 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-7.258,-122.5) has a very small spacing (1.6 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (110.5,-76.84) has a very small spacing (0.7616 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-161.9,-43.57) has a very small spacing (1.865 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-158.7,40.11) has a very small spacing (2.211 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-32.72,40.11) has a very small spacing (2.211 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (111.2,75.08) has a very small spacing (1.648 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (96.14,88.55) has a very small spacing (1.319 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (104.4,88.85) has a very small spacing (1.451 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (54.85,146) has a very small spacing (0.2684 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
WARNING: Longitude concentrated program reinforcement at (-154.7,160.5) has a very small spacing (1.578 inches). You may be able to resolve this problem by converting the bars to user reinforcement and adjusting the width and spacing.
User Continued After Warning
Estimating Costs
This analysis has been completed successfully, check above for any warnings or errors.