1
1.1

Engineering design drawings shall be prepared based on approved /agreed over all equipment layout

Dewa Practice

1.2

Engineering design drawings shall be submitted to DEWA as per priority highlighted in DDCMS list .

Dewa Practice

1.3

Engineering design drawings shall be provided with List of required legends and reference of related drawing.

Dewa Practice

1.4
1.5

DEWA approved title Blocks only to be used for each drawings. Drawing number and drawing title must be same as indicated in
DDCMS.
DEWA approval status of reference drawings to be indicated in reference list respectively.

Dewa Practice
Dewa Practice

1.6

Major references drawings to be provided to Dewa Engineers in time to avoid delay in approval process.

Dewa Practice

1.7

Revision number and date shall be maintained based on revised submission to DEWA only.

Dewa Practice

1.8

Engineering design drawings shall be prepared signed and endorsed by approved consultant prior to submission to DEWA for
approval .

Dewa Practice

Engineering

2
2.1

Introduction about the substation type ,its capacity ,contract number should be mentioned.

All rights reserved TED-2015

Dewa Practice

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description
2.2

Table of contents shall give all the descriptions of the clause.

2.3

Unit of measurement adopted shall be in SI units and code of design BS Code.

2.4

DESIGN STANDARDS AND CODE OF PRACTICES

Category
Dewa Practice
Standard
Dewa Specification

2.4.1 All Designs shall be prepared in accordance with British Standards and code of practices .

Dewa Specification

2.4.2 All British codes referred in the Design ,construction ,steel work ,Drainage ,masonry ,earth work , shall be listed .Any British Code not
listed shall also be considered.

Standard

2.4.3 Seismic Analysis shall be as per UBC 97 ; Seismic zone shall be 2B as per lattest DM regulations.

Standard

2.4.4 Wind calculation shall be based on BS 6399

Standard

2.5

LOAD CONSIDERED IN DESIGN

2.5.1 Breakage of all loads (self weight ,imposed dead weight and live or equipment loads )on the Roof ,First floor ,Ground floor and the
basement shall be given as per the standard design criteria.

Dewa Specification

2.5.2 Dead loads shall comprise of the self weight of the structure multiplied by the density and the self imposed dead loads
of the structures like the walls ,finishes ,services ,pipes etc.

Standard

2.5.3 Live loads shall as per the as per BS 6399 or manufacturers specification ,whichever is stringent.Equipment loads are to be
considered as live loads .

Standard

2.5.4 Surcharge loads due to heavy vehicle load of 33.3 kn/m2 should be used in design of all underground structures should be mentioned.

Standard

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.5.5 Lateral Earth pressure on walls of basement and tanks shall be calculated with coefficient of earth pressure at rest as per the soil
Report.

Standard

2.5.6 Basic wind loads shall be considered and dynamic wind pressure to be calculated as per the building location conditions as per BS
6399

Standard

2.5.7 Seismic loads shall be considered for seismic zone 2A and base shear calculated as per parameters of the structure as per UBC 97

Standard

2.5.8 Blast load of 5 kn/m2 shall be considered in design of Transformer and Reactor internal walls.

Dewa Specification

2.5.9 Crane loads shall be checked for the vertical and horizontal load percentages to be increased for electric overhead crane and hand
operated cranes.

Dewa Specification

2.5.10 The capacity of the electrically operated crane of 5 MT capacity in the 132 kv GIS and monorail load of 2.0 MT capaciy in the fire
pump house roof of switchgear control building offloading area shall be checked as live loads.

Dewa Specification

2.60 UNIT WEIGHT


2.6.1 Unit weight of all materilas used in Construction and Design shall be listed.

Standard

2.6.2 Unit weight of soil under saturated condition and unit weight of water is to be checked.All hydrostaic loads to be considered as dead
loads.

Standard

2.7

METHOD OF DESIGN AND ANALYSIS

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.7.1 Analysis shall be performed using a 3 dimensional structural analysis software that takes care of all aspects of designing like model
development ,analysis,verification and visualization.ETAB'S ,STAAD PRO ,SAFE and SAP are to be mentioned in the calculations.

Dewa Practice

2.80 Input data for the beams and columns are to be defined as frames members ,slabs as membrane ,walls as shells and the connection at
the base level as fixed.Raft will be designed by exporting all reactions from ETABS and defining the subgrade modulus as per soil
report.In STAAD PRO an integrate model can be directly designed.

Standard

2.9

ANALYSIS RESULTS

2.9.1 All computer generated results such as member forces ,support reactions ,displacements and graphical output of analysis such as
bending moment ,shear force diagram,displacement to substantiate the numerical output to be checked.

Dewa Practice

2.10 DESIGN DETAILS


2.10.1 Type of cement for super structure/substructure should be as per the recommendations of soil report.

Dewa Specification

2.10.2 Grade of concrete for design shall be grade C40 with compressive strength of 35 N/mm2 @28days

Dewa Specification

2.10.3 Grade of concrete for construction shall be C40 with compressive strength of 40N/mm2 @ 28 days.

Dewa Specification

2.10.4 Precast concrete -C40 with compressive strength of 40 N/mm2 @ 28 days.

Dewa Specification

2.10.5 Blinding and plain cement concrete -C20 with compressive strength of 15N/mm2 @ 28 days.

Dewa Specification

2.10.6 Reinforcement shall be deformed type 2

Dewa Specification

2.10.7 Grade of Steel considered shall be Grade 420 for Design purpose.

Dewa Specification

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.10.8 Grade of steel considered shall be Grade 460 for Construction.

Dewa Specification

2.10.9 Diameter of various bars shall be 8,10,12,16,20,25 & 32.

Dewa Specification

2.22.10.106.4
Welded wire mesh shall comply with BS 4483

Standard

2.10.11 Material Strengths and allowable stresses shall be as per BS 8110 Part 1 & 2.

Standard

2.10.12 Maximum shear stress at any section shall not exceed 4.73 N/mm2.

Standard

2.10.13 Design Ultimate Bond stress.

Standard

2.10.13.1For bars in tension .5 x sq.root of 35 or 2.96 N/mm2

Standard

2.10.15 For bars in compression .63 x sq.root of 35 or 3.73 N/mm2

Standard

2.10.13.2Bearing stress inside bonds should be checked .

Standard

2.11 LOADS AND LOAD COMBINATIONS

Standard

2.11.1 Loads & load combinations for dead ,imposed ,wind ,seismic ,earth and crane loads ( ultimate and service conditions) shall be given as
per the standard design criteria.

Dewa Specification

2.12 FACTOR OF SAFETY

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.12.1 Check for the minimum safety factors for overturning in SLS condition: 1.5

Standard

2.12.2 Minimum factor of safety for sliding in SLS condition : 1.5

Standard

2.12.3 Minimum factor of safety for flotation in SLS condition: 1.1

Standard

2.13 DESIGN
2.13.1 Design should be done for both servisibility and ultimate conditions for worst combinations of loads.
2.13.2 Design of Structural Elements shall be performed using the latest sofwares.

Standard
Dewa Specification

2.14 CLEAR COVER TO REINFORCEMENT:

Standard

2.14.1 Clear cover to reinforcement for members in contact with soil =75 mm

Standard

2.14.2 External beams ,columns and walls =50 mm

Standard

2.14.3 Internal beams ,columns and walls = 40 mm

Standard

2.14.4 Slab external = 40 mm

Standard

2.14.5 Slab internal = 35 mm

Standard

2.14.6 Internal faces of basement wall = 40 mm

Standard

2.14.7 Slab /precast cover= 40 mm

Standard

2.15 ANCHORAGE LENGTH AND LAP LENGTH:

Standard

2.15.1 Anchorage length and lap length shall as indicated in table 3.27 of BS 8110 Part 1.
2.16 FOUNDATION
All rights reserved TED-2015

Standard
Standard

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.16.1 Raft foundation is proposed for main as well as for all ancilliary buildings.All soil parameters shall be
as per the soil report .Safe bearing capacity ,water table level shall be a per soil report.

Dewa Specification

2.16.2 Allowable Settlement shall be 25 mm as per specification and differentiak settlement 10 mm.

Dewa Specification

2.16.3 Retaining walls shall be designed for worst combination of earth pressure ,hydroststic pressure & surcharge
as applicable.

Dewa Specification

2.17 MASONRY

Dewa Specification

2.17.1 Masonry :the minimum characteristic strength of non-load bearing walls shall be 7 N/mm2.
2.17.2 Internal walls shall be 200 mm thick single leaf hollow block work

Dewa Specification

2.17.3 External wall shall be 250 /350 mm thick thermal block wall

Dewa Specification

2.17.4 Toilet partition shall be 100 mm thick.

Dewa Specification

2.18 DETAILING
2.18.1 Detailing :shall be as per british standards of practice and preparation of bar bending schedules will conform to BS 4466.

Standard

2.19 STRUCTURAL STEEL


2.19.1 Structural steel shall comply with BS 5950 Part 1

Standard

2.19.2 Moment Capacity and deflection of the steel members shall be calculated based on BS 5950

Standard

2.19.3 Loads and load combinations shall comply with BS 5950

Standard

2.19.4 Bolt design shall cpmply with BS 3692 & BS 4190 (Minimum no of bolts at any joint shall be two)

Standard

2.19.5 Minimum size of the weld should 6mm and electrode classification should be based on table 37 of BS 5050

Standard

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

2.20 DRAINAGE & PLUMBING


Drainage & Plumbing should follow the five systems Storm /Surface water Drainage ,Sewage Drainage ,Oillwater Drainage
2.20.1 ,Chemical Discharge and Indoor potable water .

Dewa Specification

Inspection

3
3.1
3.2

Construction & Installation

4
4.1
4.2

Testing & Commissioning

5
5.1
5.2

Maintenance

6
6.1

All rights reserved TED-2015

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category

6.2

Mariam Abdullah Al Suwaidhi


Srinivas Kupuswamy
Zeenat Pasha

Nasreen Mir
Prepared By:

All rights reserved TED-2015

Checked By:

Approv

CL-Rev.1

Document Title

Document Number

Rev.

132/11kV Substation- Design Criteria

KHORDXB/C/15/316

SR. Description

Category
Mariam Abdullah Al Suwaidhi
Srinivas Kupuswamy
Zeenat Pasha

Nasreen Mir
Prepared By:

Checked By:

Approv
Khawla Saleh Aldhebaiei

All rights reserved TED-2015

10

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted

Complied

All rights reserved TED-2015

11

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with
Complied
Complied

Complied

BS 8110

Complied

UBC 97

Zone-2A

BS 6399

Complied

Complied
Complied

BS 8110

Complied

BS 8110

All rights reserved TED-2015

Complied

12

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

BS 8110
Complied

BS 6399
Complied

UBC 97

Complied
Complied
Complied

Complied

BS 8110

Complied

BS 8110
Complied

All rights reserved TED-2015

13

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with
Complied

BS 8110
Complied

Complied

As per DM/approved soil


report
C40
C40
C40
C20
Complied
Grade 460

All rights reserved TED-2015

14

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with
Grade 500
Complied

Bs 4483

Complied

BS 8110

Complied

BS 8110

5 N/mm2

BS 8110

As per compressive
strength of concrete

BS 8110

As per compressive
strength of concrete

BS 8110

As per compressive
strength of concrete

BS 8110

Complied

BS 8110
Complied

All rights reserved TED-2015

15

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

BS 8110

Complied

BS 8110

Complied

BS 8110

Complied

BS 8110
BS 8110

Complied
Complied

BS 8110

Complied

BS 8110

Complied

BS 8110

Complied

BS 8110

Complied

BS 8110

40 mm

BS 8110

Complied

BS 8110

Complied

BS 8110
BS 8110

Complied

BS 8110
All rights reserved TED-2015

16

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with
Complied
Complied
Complied

Complied
Complied
Complied
Complied

All rights reserved TED-2015

BS 4466

Complied

BS 5950 PART 1

Complied

BS 5950

Complied

BS 5950 PART 1

Complied

BS 5950 PART 1

Complied

BS 5950 PART 1

Complied
17

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

Complied

All rights reserved TED-2015

18

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

Approved By:

All rights reserved TED-2015

19

CL-Rev.1

Date

Approval Status

9/23/2016

Applicable Reference

Complied with

Approved By:

All rights reserved TED-2015

20

CL-Rev.1