Sei sulla pagina 1di 58

Operation Manual

Bently Nevada Asset Condition Monitoring

3300/20 Dual Thrust Position Monitor

Part Number 80179-01


Rev. Z (08/07)

3300/20 Dual Thrust Position Monitor Operation Manual

Copyright 1993. Bently Nevada LLC.


All rights reserved.
The information contained in this document is subject to change without notice.
The following are trademarks of General Electric Company in the United States and other
countries:
ACM, Actionable Information, Actionable Information to the Right People at the Right
Time, ADRE, Asset Condition Management, Asset Condition Monitoring, Because Better
Machines Begin With Better Bearings, Bently ALIGN, Bently BALANCE, Bently DOCUVIEW,
Bently LUBE, Bently PERFORMANCE, Bently Nevada, CableLoc, ClickLoc, Data Manager,
Decision Support, DemoNet, Dynamic Data Manager, Engineer Assist, FieldMonitor,
flexiTIM, FluidLoc, Helping You Protect and Manage All Your Machinery, HydroScan,
HydroView, Key , Keyphasor, Machine Condition Manager 2000, MachineLibrary,
Machine Manager, MicroPROX, Move Data, Not People, Move Information, Not Data, NSv,
Prime Spike, PROXPAC, Proximitor, REBAM, RuleDesk, SE, Seismoprobe, ServoFluid, Smart
Monitor, Snapshot, System 1, System Extender, TDXnet, TDIXconnX, TipLoc, TorXimitor,
Transient Data Manager, Trendmaster, TrimLoc, Velomitor

Contact Information
The following ways of contacting Bently Nevada are provided for those times when you
cannot contact your local representative:
Mailing Address

Telephone
Fax
Internet

ii

1631 Bently Parkway South


Minden, Nevada USA 89423
USA
1.775.782.3611
1.800.227.5514
1.775.215.2873
www.ge-energy.com/bently

Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.

3300 System Overview (Part Number 80171-01)


3300 System Installation Instructions (Part Number 80172-01)
3300 System Troubleshooting (Part Number 80173-01)
3300/12 Power Supply (AC supply) (Part Number 89602-01)
3300/14 Power Supply (DC supply) (Part Number 101256 01)
3300/03 System Monitor (Part Number 89604-01)
3300 Internal Barriers, Installation Manual (Part Number 88837-01)
RELATED PARTS
3300/20 Field Wiring Diagram Packet (Part Number 100314-01)
3300/20 Data Sheet (Part Number 141500-01)
3300/20 Meter Scales (Part Number 84113-20)

iii

3300/20 Dual Thrust Position Monitor Operation Manual


Product Disposal Statement
Customers and third parties, who are not member states of the European Union, who are
in control of the product at the end of its life or at the end of its use, are solely
responsible for the proper disposal of the product. No person, firm, corporation,
association or agency that is in control of product shall dispose of it in a manner that is
in violation of any applicable federal, state, local or international law. Bently Nevada LLC
is not responsible for the disposal of the product at the end of its life or at the end of its
use.
In this document procedures are typically given only for channel A. Procedures for
channel B are similar except for the obvious substitutions of corresponding switches,
terminals, and indicators.
NOTE: The information in this manual pertains to monitor main boards with part number
135313-01 and 79482-01.

iv

SYMBOLS
Special symbols are used in the manual to illustrate specifics in the step-by-step
processes.

CAUTION
1. With some combinations of worst case high transducer scale factors
and large full scale ranges, the 3300/20 Monitor may not reach a full
scale reading before going not OK. For example, if the 7200 11mm
transducer option is ordered with a full scale option of 2-0-2 mm or
75-0-75 mil (with or without barriers), worst case conditions could
result in the reduction of full scale by about 10%. Therefore, with this
particular option, we recommend setting alarms at least 10% down
from full scale. In all cases, verify that alarms can be reached with the
actual transducer installation being used.
2.

With the 7200 11mm Transducer option and Internal or External


Barriers, the green OK light will not go out if the transducer
probe/cable opens, regardless of the full scale option.

3300/20 Dual Thrust Position Monitor Operation Manual

Contents
1.
2.
3.

Dual Thrust Monitor System.......................................................................................................................1


Monitor Functions ...........................................................................................................................................2
LED Functionality.............................................................................................................................................5
3.1
OK LEDs ....................................................................................................................................................5
3.2
Bypass LEDs ...........................................................................................................................................6
3.3
Alert LEDs ................................................................................................................................................7
3.4
Danger LEDs ..........................................................................................................................................8
4. Read Channel Values.....................................................................................................................................9
5. Read Gap Voltage ........................................................................................................................................ 10
6. Read Setpoint Levels................................................................................................................................... 11
7. Monitor Removal and Disassembly ..................................................................................................... 12
7.1
Remove Monitor from Rack......................................................................................................... 12
7.2
Remove Front Panel........................................................................................................................ 13
7.3
Signal Input Relay Module Removal........................................................................................ 14
7.4
Signal Input Relay Modules (SIRM)............................................................................................ 15
7.5
No Relay and Dual Relay SIRM................................................................................................... 16
7.6
Quad Relay Signal Input Module Options ............................................................................. 17
7.7
Internal Barrier Options SIRM ..................................................................................................... 18
8. Monitor Options............................................................................................................................................. 19
8.1
Field Programmable Options...................................................................................................... 19
8.2
Monitor Ordering Options--3300/20 ....................................................................................... 20
9. Meter Scale Replacement ........................................................................................................................ 21
10. Alarm Setpoint Adjustment...................................................................................................................... 22
11. Channel Bypass............................................................................................................................................. 23
12. Danger Bypass............................................................................................................................................... 24
13. Test Setup......................................................................................................................................................... 25
14. Test Alarms...................................................................................................................................................... 28
14.1
Test the Alert Setpoint Level........................................................................................................ 28
14.2
Test the Danger Setpoint Level.................................................................................................. 29
15. Test OK Limits................................................................................................................................................. 30
16. Calibrate Channels....................................................................................................................................... 33
16.1
Calibration Procedure .................................................................................................................... 33
16.2
Zero Voltage Adjust ......................................................................................................................... 35
16.3
Prepare to Bring the Monitor On Line..................................................................................... 38
17. Self Test ............................................................................................................................................................. 39
18. Error Codes ...................................................................................................................................................... 42
19. Appendix AMain Board Options .......................................................................................................... 43
19.1
Jumper Locations for PWA 135313-01.................................................................................. 43
19.2
Full Scale Options for PWA 135313-01 .................................................................................. 43
19.3
Main Board Option Settings for PWA 135313-01 ............................................................. 45
19.4
Jumper Locations for PWA 79482-01 .................................................................................... 46
19.5
Full Scale Options for PWA 79482-01..................................................................................... 47
19.6
Main Board Option Settings for PWA 79482-01 ................................................................ 48
19.7
Expander Board Installation/Removal, PWA 79482-01................................................. 49
20. Recommended Spare Parts..................................................................................................................... 50
21. Index ......................................................................................................................................................................1

vi

Section 1 - Dual Thrust Monitor System

1. Dual Thrust Monitor System

Do not use this figure as a wiring diagram. Refer to 3300/20 Field Wiring Packet.

3300/20 Dual Thrust Position Monitor Operation Manual

2. Monitor Functions
DUAL THRUST POSITION - Thrust position is the average position, or change in position,
of a rotor in the axial direction with respect to some fixed reference. The Dual Thrust
Position Monitor provides continuous thrust position monitoring on two channels (A & B)
for redundant protection. Normal thrust direction can be toward or away from the probe
face. AND voting logic ensures that failure of one channel will not give a false Danger
alarm. OR voting logic allows for two independent thrust channels in less critical
applications.
PROBE GAP VOLTAGE - Probe gap is measured as a negative dc voltage that is directly
proportional to the gap distance between the face of a proximity probe and the surface
being monitored. Probe gap voltage for each channel is displayed on the front panel
meter by pressing the GAP switch.
OK - When the proximity output voltage is within its upper/lower limits, the transducer is
defined as OK. The OK detection circuit controls the channel OK LED and the monitor
relay drive to the OK relay. If the monitor has the latching OK option, a System Reset is
required to reset the OK function.
OK RELAY - The OK Relay is located on the Power Input Module. Every channel in the
rack must be OK or bypassed to energize the OK Relay.
ALARM - Pressing the ALERT and DANGER switches on the front panel of the monitor
causes the corresponding Alert (first-level alarm) or Danger (second-level alarm)
setpoints on each channel to be displayed on the front panel meter. ALERT and DANGER
LEDs light when the thrust position signal level exceeds preset levels for the selected
time delay, and appropriate ALERT and DANGER alarm relay contacts are activated.
Voting logic options determine when the Danger relay contacts are activated.
FIRST OUT - Separate First Out circuits exist for Alert and Danger alarms. A monitor with
First out option selected flashes a channel alarm LED if that monitor was the first
channel in the rack to go into alarm. Pressing the RESET switch acknowledges the First
Out.
ALARM RELAYS - Monitor alarms can be programmed for either latching or non-latching
mode. In the non-latching mode, the alarm resets automatically when the alarm
condition no longer exists. In the latching mode, the alarm condition must be reset
manually by pressing the RESET switch on the front panel of the System Monitor (or by
closing external Reset contacts). The alarm will not reset if the alarm condition still exists.
DANGER BYPASS - For maintenance functions, a DANGER BYPASS switch on the monitor
circuit board is set to inhibit the Danger relay drive. This function turns on the BYPASS
2

Section 2 - Monitor Functions


LEDs. Other front panel functions are not affected. This function can be disabled using a
jumper within the monitor.
BUFFERED OUTPUT - The channels A and B coaxial cable connectors on the front panel
of the monitor and the terminals on the Signal Input Relay Module provide buffered
signals from respective channel transducers. These connectors can be used for
connection of external equipment.
RECORDER OUTPUT - A recorder output is provided for each channel. Depending on the
option selected, the recorder output levels, proportional to full scale, are 0 to -10 Vdc, +1
to +5 Vdc, or +4 to +20 mA.
SELF TEST - The monitor has three categories of self test: cyclic, power-up, and userinvoked.
Power-up self test is performed automatically each time the monitor power is turned
on. A series of basic tests and transducer OK tests are performed.
Cyclic self test is performed automatically during monitor operation. Errors
encountered during cyclic test disable the monitor, and flash an LCD bargraph error
code. Should the error be intermittent, the monitor will return to operation, but the
error codes are stored for retrieval during user-invoked self test. Stored error codes
are indicated by the OK LEDs flashing at 5 Hz provided that the channel is OK.
User-invoked test performs power-up self test and allows error messages stored
during cyclic test to be read and cleared. Stored errors are annunciated by the OK
LEDs flashing a 5Hz and the error codes displayed on the front panel LCD bargraph.

SIGNAL RESPONSE TIME


To reduce the chance of alarms caused by axial vibration and shaft runout, the Signal
Conditioning performs a running average of the shaft position. This average causes step
changes in axial vibration to be integrated over time. The time constant changes
according to the alarm time delay as shown in Table 1.
METER RESPONSE
The meter response time can be selected to be fast or slow. With a fast response, the
meter will follow the signal conditioning exactly as seen by the monitor. In installations
where there is a large AC component of the thrust signal, this will cause apparent meter
jitter. Selecting the slow meter response reduces the meter's response to rapidly
changing signals, but does not affect the monitor's Recorder or Alarm circuits.

3300/20 Dual Thrust Position Monitor Operation Manual


TABLE 1, RESPONSE TO STEP CHANGE
Alarm Time
Delay

0.1 second
1 second
3 second
6 second

Signal Conditioning
Response Time
Constant *

Fast

Slow

81 ms
180 ms
639 ms
1294 ms

81 ms
180 ms
639 ms
1294 ms

639 ms
967 ms
1294 ms
1622 ms

Meter Response Option

* The time constant approximates a simple RC response curve where one time constant
= 63% of final value and five time constants = 99% of final value.

Section 3 - LED Functionality

3. LED Functionality
3.1 OK LEDs

z
{

ON
OFF
BLINK

LED DISPLAY
A
B
z
{
z

OK
OK
OK

z
z
{

CONDITION
Channel A and B are in operating range.
If a channel's OK LED goes off, that channel
is not OK, has been latched not OK, or is
bypassed.

OK RELAY
DRIVE*
ON
OFF**

The monitor is in self test, or both channels


are not OK or bypassed.
{

OK

OK

OFF**

{
If an error code is displayed refer to the
Error Code section in this manual.
An LED flashing at 5 Hz indicates that an
error was encountered during Cyclic self
test. Self Test, Section 17, describes how to
read error messages.

ON

* Each channel in the system controls the OK Relay. Therefore any channel can cause
a not OK relay condition (Not OK = OFF = de-energized relay).
**Not OK channel can be bypassed to restore relay OK conditions.

3300/20 Dual Thrust Position Monitor Operation Manual

3.2 Bypass LEDs


z
{

ON
OFF

LED DISPLAY
A
B

BYPASS z

{ BYPASS z
z BYPASS {

CONDITION
The monitor is in the Danger Bypass mode.
The system is in the Power-Up mode.
User invoked Self Test is in progress.
Both channels are bypassed.
Rack Inhibit contacts at the back of the rack
closed.
If a single channel's BYPASS LED comes on, that
channel is bypassed.

Section 3 - LED Functionality

3.3 Alert LEDs

z
{

ON
OFF
BLINK

LED DISPLAY
A
B
z

ALERT

ALERT

ALERT

ALERT RELAY
DRIVE

If a channel ALERT LED comes on, that


channel has exceeded its Alert setpoint
level. Read Setpoint Levels, Section 6,
describes how to read alarm setpoint levels.

ON

A flashing ALERT LED indicates that the


channel was the first in the rack to exceed
its Alert setpoint since the last power up or
reset.

ALERT
ALERT

CONDITION

ON

If two channel alert alarms occur within 50


milliseconds, both LEDs could flash.

NOTE: The monitor will not annunciate an alert condition if the monitor is in the
non-latching mode and an alert condition existed but is no longer present.

3300/20 Dual Thrust Position Monitor Operation Manual

3.4 Danger LEDs


z
{

ON
OFF
BLINK

LED DISPLAY
A

z DANGER {
{ DANGER z
z DANGER z

{ DANGER
DANGER {

CONDITION

If a channel's DANGER LED comes on, that


channel has exceeded its Danger setpoint
level. Section 6 describes how to read
setpoint levels.
A flashing DANGER LED indicates that the
channel was the first in the rack to exceed
its Danger setpoint since the last power up
or reset. Two channels may indicate first
out following self test.

DANGER RELAY
DRIVE
OR
Voting
ON

AND *
Voting
OFF

ON

OFF

ON

ON

ON

OFF

ON

OFF

If two channel danger alarms occur within


50 milliseconds, both LEDs could flash.

* If one channel in the monitor is bypassed or not OK and if the other channel then goes
into Danger, the Danger relay will be activated. AND voting with Quad relays must be
done externally by wiring contacts in series.
NOTE: The monitor will not annunciate a danger condition if the monitor is in the nonlatching mode and a danger condition existed but is no longer present.

Section 4 - Read Channel Values

4. Read Channel Values


The monitor continuously indicates measured Thrust Position values for channel A and
channel B.
Note: The meter scale units must be compatible with the full scale option configured in
Section 19.

3300/20 Dual Thrust Position Monitor Operation Manual

5. Read Gap Voltage


1. Press GAP switch and read gap voltage for both Channel A and Channel B on the
meter using the center scale on the meter.

10

Section 6 - Read Setpoint Levels

6. Read Setpoint Levels


Press the ALERT switch to read the Alert setpoints for both channel A and channel B on
the meter scale.

Press the DANGER switch and read the Danger setpoints for both channel A and channel
B on the meter scale. In both cases, normal and counter setpoints are displayed.

11

3300/20 Dual Thrust Position Monitor Operation Manual

7. Monitor Removal and Disassembly


7.1 Remove Monitor from Rack
1. Loosen two monitor retaining screws on
the front of the monitor.
2. Pull the monitor from the rack.
3. Remove side cover by pinching the
protruding tip on each standoff.

12

Caution
Improper rack operation may occur.
Power down rack or inhibit rack
alarms when installing or removing a
monitor.

Section 7 - Monitor Removal and Disassembly

7.2 Remove Front Panel


1. Disconnect the ribbon cable by pressing the connector latches outward.
2. Unscrew two sliding standoffs

13

3300/20 Dual Thrust Position Monitor Operation Manual

7.3 Signal Input Relay Module Removal

WARNING
High voltage present. Contact
could cause shock, burns, or death.
Do not touch exposed wires or
terminals.

Caution
Machine protection provided by
this monitor will be lost while the
Signal Input Relay Module is
removed from the rack.

The Signal Input Relay Module is on the back of the rack. For relay configuration, see the
System Installation Instructions manual. For field wiring, refer to 3300/20 Field Wiring
Diagram Packet.

Module Removal
Loosen two screws and pull out
the module to remove it.

14

Section 7 - Monitor Removal and Disassembly

7.4 Signal Input Relay Modules (SIRM)


A monitor can be configured with the Signal Input Relay Modules shown below. Refer to
options CC & EE in Monitor Ordering Options, Section 8.2 of this manual.

NO
ALARM
RELAYS

DUAL
ALARM
RELAYS

QUAD
ALARM
RELAYS

INTERNAL
BARRIERS
NO RELAYS

INTERNAL
BARRIERS
DUAL RELAYS

15

3300/20 Dual Thrust Position Monitor Operation Manual

7.5 No Relay and Dual Relay SIRM

WARNING
High voltage present. Contact could
cause shock, burns, or death.
Do not touch exposed wires or
terminals.

NOTE: For relay configuration of monitors


with Internal Safety Barriers, refer to
3300 Internal Barriers, Installation
Manual.

Remove the Signal Input Relay Module from the rack before changing option jumpers.

The entire configuration table applies to the Dual Relay SIRM.

JUMPERS
INSTALL REMOVE
ALERT RELAYS
Normally Energized
Normally De-energized*
DANGER RELAYS
Normally Energized
Normally De-energized*
OR Bus
No Options*
Alert & Danger Bus 1
Alert & Danger Bus 2

W3
W4, W11
W4, W11 W3
W2
W1, W12
W1, W12 W2
----------- W5-W8
W6,W8
W5,W7
W5,W7
W6,W8

NOTE: * Denotes standard configuration.

16

Section 7 - Monitor Removal and Disassembly

7.6 Quad Relay Signal Input Module Options

WARNING
High voltage present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.

Remove the Signal Input Relay Module from


the rack before changing option jumpers.
Note: AND voting logic must be done
externally by wiring the contacts in series.
The OR bus option is not available with
quad relays. See 3300 System Installation
Instructions.

JUMPERS
INSTALL
REMOVE
ALERT RELAYS
W2,W3C,
W3D,W4D

Normally Energized

W3A,W4C

Normally De-energized*

W2,W3C,
W3A,W4C
W3D,W4D

DANGER RELAYS
Normally Energized

W4B,W4F

W1,W3B,
W4A,W4E

Normally De-energized*

W1,W3B,
W4A,W4E

W4B,W4F

NOTE: * Denotes standard configuration.

17

3300/20 Dual Thrust Position Monitor Operation Manual

7.7 Internal Barrier Options SIRM


For relay configuration of monitors with internal safety barriers, refer to the 3300 Internal
Barriers Installation Manual (88837) or the 3300 System Installation Instructions (80172).
The Alert Relays and Danger Relays sections of the table below do not apply to the No
Relay SIRM. Only the OR Bus section of the table below applies to the No Relay SIM.

JUMPER
INSTALL REMOVE
ALERT RELAYS
Normally Energized

W3

W4, W9

Normally De-energized* W4, W9


DANGER RELAYS

W3

Normally Energized
W2
Normally De-energized* W1, W10
OR Bus
----------No Options*
Alert & Danger Bus 1
W6, W8
Alert & Danger Bus 2
W5, W7

W1, W10
W2
W5-W8
W5, W7
W6, W8

NOTE: * Denotes standard


configuration.

W9

18

W10

W8
W7
W6
W5
W4
W3
W2
W1

WARNING
High voltage present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.

Section 8 - Monitor Options

8. Monitor Options
8.1 Field Programmable Options
*

Denotes standard configuration.

First Out

Alert Reset Mode

Meter Response Time

Enabled *

Latching *

Fast *

Alarm Delays

Danger Reset Mode

Danger Relay Voting ++

0.1 Second
1 Second *
d
Not OK Mode

Latching *
Non-latching

AND voting for relay drive *


OR voting for relay drive

Recorder Outputs

Danger Bypass

+4 to +20 mA *
Latching
Non-latching *
+1 to +5 Vdc
Normal Direction

Enabled
Disabled *

Toward Probe *
Away from
Probe
++ With Quad Relays, AND voting logic must be done externally by wiring contacts in
series.
NOTE: See section 19 for jumper locations and settings.

19

3300/20 Dual Thrust Position Monitor Operation Manual

8.2 Monitor Ordering Options--3300/20


AA

BB

CC

FULL SCALE RANGE

TRANSDUCER INPUT

ALARM RELAY

01 = 25 - 0 - 25 mils
02 = 30 - 0 - 30 mils
03 = 40 - 0 - 40 mils

01 = 3300 or 7200,
Proximitor 8MM &
5MM, 200mV/mil*

00 = None

02 = 7200 Proximitor (Not XL)


11mm, 100mV/mil

02 = Hermetically
Sealed

03 = 7200 Proximitor 14mm,


3300 HTPS 100mV/mil

03 = Quad Relays***
Epoxy Sealed

04 = 3000 Proximitor,
200mV/mil**

04 = Spare MonitorNo SIM/SIRM

01 = Epoxy Sealed

05 = 50 - 0 - 50 mils
06 = 75 - 0 - 75 mils
11 =0.5 - 0 - 0.5 millimetres
12 =1.0 - 0 - 1.0 millimetres
13 =2.0 - 0 - 2.0 millimetres

05 = 3300 RAM or XL NSv


Proximitor, 200mV/mil**

DD

EE

AGENCY APPROVAL

BARRIERS USED

00 None

00 None

01 CSA/NRTL/C

01 External

02 BASEEFA

02 Internal

* Only for range options 01,02, 03,11, and 12.


** Only for range options 01 and 11.
*** Quad relays are not available with internal barriers.
NOTE:

20

Verify that the transducer power supply level ( -Vt) is correct for
the type of transducer connected. The 3000 transducer requires 18 Vdc, the 3300 and 7200 transducers require -24 Vdc. Power
converter (part number 89634-01) can be used to convert 24 Vdc
to 18 Vdc for use with the 3000 transducer.

Section 9 - Meter Scale Replacement

9. Meter Scale Replacement


The monitor meter scales can be replaced for operation with different full scale ranges.
The replacement meter scales are located in the back of this manual.
1.

Set the monitor full scale range. (See the Appendix A, Main Board Options.)

2.

Cut the meter scale from the back of this manual. Be sure to cut along the marked
outline so the meter scale will fit properly.

3.

Open the front panel by loosening the two monitor retaining screws and sliding the
front panel to the right.

4.

Remove the old meter scale.

5.

Insert the new meter scale in the front panel.

6.

Close the front panel.

21

3300/20 Dual Thrust Position Monitor Operation Manual

10. Alarm Setpoint Adjustment


1.

Open the front panel by loosening the two monitor retaining screws and sliding the
front panel to the right.

2.

Select the channel to be adjusted by setting either switch AA (Adjust channel A) or


AB (Adjust channel B) to the left (ON). Select Normal or Counter Setpoint by setting
the N/C switch to the desired position, left for Normal or right for Counter. The
selected bargraph will start flashing.

3.

Adjust the Alert or Danger setpoints by pressing and holding the ALERT or DANGER
button on front panel and then press the () or () buttons on the System Monitor to
adjust setpoint value up or down.

4.

Reset the selected channel adjust (AA or AB) switches to the right (OFF).
NOTE: The monitor responds to the previous setpoint until the channel adjust switch
is turned off.

5.

22

Adjust the other channel or close the front panel.

Section 11 - Channel Bypass

11. Channel Bypass


Caution
Machine protection provided by
this monitor will be lost while
Channel Bypass is on.
You can use Channel Bypass to take a Not OK or unconnected channel off line. This will
restore the OK Relay to the OK state. The OK Relay will de-energize (go Not OK) if any
channel in the rack is in a Not OK condition.
1.

Open the front panel by loosening the two retaining screws and sliding the front
panel to the right.

2.

Set BA (Bypass Channel A) or BB (Bypass Channel B) switch to the left (ON). The
corresponding BYPASS LED comes on, the OK LED goes off, and the channel reading
is clamped to zero.

3.

Close the front panel.


NOTE
When Channel Bypass is switched on, channel alarms are cleared.

23

3300/20 Dual Thrust Position Monitor Operation Manual

12. Danger Bypass


Caution
Machine protection provided by
this monitor will be lost while
Danger Bypass is on.

1.

Open the front panel by loosening the two retaining screws and sliding the front
panel to the right.

2.

Set DB (Danger Bypass) switch to the left (ON). Both channel BYPASS LEDs come
on. The DANGER LEDs on the front panel can come on, but the danger relay drive
will not be activated if a Danger setpoint is exceeded. The Danger Bypass switch
can only be turned on if Danger Bypass is enabled. To enable the Danger Bypass
switch refer to Appendix A of this manual.

3.

24

Close the front panel.

Section 13 - Test Setup

13. Test Setup


Use the following setup and procedures to test the alarm setpoints that you set in the
Alarm Setpoint Adjustment Procedure Section, to test the OK Limits and to Calibrate the
monitor. These tests use either a TK3 Calibration instrument or a power supply to vary
the input signal so that you can verify that the appropriate LEDs and relays activate.
Use this procedure to test and calibrate both channels. You will need these instruments
and tools

Multimeter (4 digit display)


Power supply (0 to -50 Vdc) or a Bently Nevada TK3 Calibration Instrument
Screwdriver

Testing involves these main steps:

Connect and adjust the test instruments


Test the Alarms (Alert and Danger in both Normal and Counter directions)
Test the OK Limits

WARNING
High voltage present. Contact could
cause shock, burns, or death.
Do not touch exposed wires or
terminals.

Caution
Tests will exceed alarm setpoint
levels causing alarms to activate.
This could result in relay contacts
changing state. See Danger
Bypass, Section 12.

Calibrate both Channels including Zero Position adjustment


Prepare to bring the monitor on line

25

3300/20 Dual Thrust Position Monitor Operation Manual

13.1 Connect a DC Power Supply

1.

Disconnect all transducer wiring from the channel A terminals on the Signal input
Relay Module.

2.

Connect the power supply and multimeter as shown in the figure above.

3.

Adjust the power supply voltage for 0 mil (0 mm) on the monitor display.

4.

Press the Reset switch on the system monitor and verify the following:
OK LEDs are on
Alert and Danger LEDs are off

26

Section 13 - Test Setup

13.2 Connect a TK3 Calibration Instrument

1.
2.

To use the TK3, disconnect the extension cable from the probe.
Reconnect the extension cable to an identical probe on a TK3 and connect the
multimeter as shown in the figure above.

3.

Adjust the gap voltage for 0 mil (0 mm) on the monitor display.

4.

Press the Reset switch on the system monitor and verify the following:
OK LEDs are on
Alert and Danger LEDs are off

27

3300/20 Dual Thrust Position Monitor Operation Manual

14. Test Alarms


14.1 Test the Alert Setpoint Level

1. Adjust the power supply voltage past the


Alert Setpoint level in the Normal direction
and verify that the ALERT LED comes on
(flashing if the First Out Option is selected).
2. Verify that the Alert Relay changed state.

3. Press the RESET switch on the system monitor and


verify that the ALERT LED remains on steady.

28

Section 14 - Test Alarms

14.2 Test the Danger Setpoint Level


1. Adjust the power supply voltage past the Danger
Setpoint level in the Normal direction and verify that
the DANGER LED comes on (flashing if the First Out
Option is selected).
2. Verify that the Danger Relay changed state. If Danger
AND Voting logic is selected, the relay will not change
state until the other channel exceeds the Danger
Setpoint (unless the other channel is Not OK or
bypassed).
3. Danger AND Voting is not active if the second channel
is bypassed. If one channel is bypassed, a signal level
exceeding the Danger Setpoint level on the nonbypassed channel will cause the Danger Relay to
change state. The Danger Bypass switch being on will
inhibit the relay from changing state.

4. Press the RESET switch on the System Monitor.


5. Verify that the ALERT and DANGER LEDs remain on
and steady.
6. Repeat the Alert and Danger Setpoint Level tests for
the Counter direction.

29

3300/20 Dual Thrust Position Monitor Operation Manual

15. Test OK Limits


WARNING
High voltage present. Contact could
cause shock, burns, or death.
Do not touch exposed wires or
terminals.

Caution
Tests will exceed alarm setpoint
levels causing alarms to activate.
This could result in relay contacts
changing state. See Danger
Bypass, Section 12.

Before bringing the monitor on line, use this procedure to check that the OK Limits for
channels A and B are working properly. You will need equipment as described in the Test
Setup section.
1. Adjust the gap voltage for
approximately -9.0 Vdc with
respect to common and verify the
OK LED is on for the channel being
tested. Press RESET on the system
monitor to turn on the OK LED if the
latching OK mode is installed.
Note: All other channels in the rack
must be OK or bypassed in order
for the relay to change states.

30

Section 15 - Test OK Limits

2. Change the gap voltage to be more positive until the OK LED goes off (lower limit).
Check the probe gap voltage on the multimeter per the following table:

TRANSDUCER TYPE *

ACCEPTABLE GAP VOLTAGE RANGE


(LOWER LIMIT)

3000, 3300 RAM or XL NSv Transducer

-1.15 Vdc to -1.41 Vdc

3300 & 7200, 5 mm/8 mm, without External


Barriers

-1.27 Vdc to -1.43 Vdc

3300 & 7200, 5 mm/8 mm, with External Barriers

-1.30 Vdc to -1.50 Vdc

7200 Transducer, 11 mm probe (not 3300 XL)

-2.96 Vdc to -3.25 Vdc

7200 14 mm probe or 3300 HTPS Transducer

-1.45 Vdc to -1.65 Vdc

* See CAUTION on page v of this manual. See Mod 146300-01 for 3300 XL 11mm
Transducers.
3. Return the gap voltage to 9.0 Vdc and verify that the OK LED lights and the OK Relay

31

3300/20 Dual Thrust Position Monitor Operation Manual


4. Gradually change the gap voltage (more negative) until the OK LED goes off
(upper limit). Verify that the upper OK Limit is per the following table:

TRANSDUCER TYPE *

ACCEPTABLE GAP VOLTAGE RANGE


(UPPER LIMIT)

3000, 3300 RAM or XL NSv Transducer

-12.56 Vdc to -13.07 Vdc

3300 & 7200, 5 mm/8 mm, without External


Barriers

-18.51 Vdc to -18.80 Vdc

3300 & 7200, 5 mm/8 mm, with External Barriers

-17.71 Vdc to -17.91 Vdc

7200 Transducer, 11 mm probe (not 3300 XL)

-19.78 Vdc to -20.14 Vdc

7200 14 mm probe or 3300 HTPS Transducer

-18.17 Vdc to -18.53 Vdc

* See CAUTION on page v of this manual. See Mod 146300-01 for 3300 XL 11mm
Transducers.
5. Return the gap voltage to 9.0 Vdc and verify that the OK LED lights and the OK
Relay energizes.

32

Section 16 - Calibrate Channels

16. Calibrate Channels


WARNING
High voltage present. Contact could
cause shock, burns, or death.
Do not touch exposed wires or
terminals.

16.1 Calibration Procedure


Before you begin Channel Calibration, you must choose the full scale range and set
the appropriate jumpers (See Section 19). You will need equipment as described in
the Test Setup, section 13. (Repeat for channels A and B.)
1. Slide front panel to right and adjust the input signal voltage at the SIRM to obtain a
voltage of +2.5 Vdc at the Channel A test point (BPPLA). Measure and record the
input voltage. This value will be the zero voltage used in step 3.

33

3300/20 Dual Thrust Position Monitor Operation Manual


2. Verify that monitor display indicates 0 mil (0mm).
3. Change the input voltage for full scale value.

1 mil = 200 mV

1 mm = 7.87 Vdc
For systems with external barriers, use:

1 mil = 192 mV
1 mm = 7.56 V

For example: The scale factor is 200 mV/MIL for 40 - 0 - 40 mil range, with 5 mm
probe, and without barriers. Full scale voltage change would be: 40x200 mV/MIL =
8.000 Vdc.

If Normal direction is toward the probe, the full scale value is the zero
voltage minus the full scale voltage. For example, with a zero voltage (from
step 1) of -10.00 Vdc the full scale value is: (-10.000) - (-8.000) = -2.000 Vdc
input.

If Normal direction is away from the probe, the full scale value is the zero
voltage plus the full scale voltage. For example, with a zero voltage (from
step 1) of -10.00 Vdc the full scale value is: (-10.000) + (-8.000) = -18.000
Vdc input.
NOTE: See Section 16.2, Zero Voltage Adjust, for the zeroing voltage
appropriate for your transducer.

4. For Normal direction - Adjust potentiometer (GA) for +5.00 Vdc on Channel A test
point. For Counter direction - Adjust potentiometer (GA) for 0.0 Vdc on Channel A
test point. Verify that the front panel indicates full scale and that the recorder
output matches the option selected.

34

Section 16 - Calibrate Channels

16.2 Zero Voltage Adjust


NOTE:

The monitor expects a specific gap voltage when the rotor is at its zero
position. The type of transducer being used determines this voltage. In
the following procedure, the probe gap is adjusted so that the appropriate
voltage is output by the probe when the rotor is at its zero position.

1.

Ensure that rotor is set to the desired zero position (against active or inactive
bearing, or center of float zone).

2.

Connect a multimeter to IN and COM terminals on the monitor Signal Input Module
as shown below.

2.

Adjust probe gap for zeroing voltage specified below for the transducer type
installed.

TRANSDUCER TYPE *

ZEROING VOLTAGE (PROBE GAP


VOLTAGE)

3000, 3300 RAM or XL NSv Transducer

-7.00 Vdc 0.50 Vdc

3300 & 7200, 5mm/8mm, without External


Barriers

-10.00 Vdc 0.20 Vdc

3300 & 7200, 5mm/8mm, with External Barriers

-9.83 Vdc 0.20 Vdc

7200 Transducer, 11mm probe (not 3300 XL)

-11.60 Vdc 0.20 Vdc

7200 14mm probe or 3300 HTPS Transducer

-10.00 Vdc 0.20 Vdc

* See CAUTION on page v of this manual. See Mod 146300-01 for 3300 XL 11mm
Transducers.

35

3300/20 Dual Thrust Position Monitor Operation Manual


3.

Slide the front panel of the monitor to the right and connect a multimeter to
Channel A test point BPPLA. Adjust Channel A zero potentiometer (ZA) for +2.500
Vdc. The monitor bargraph should display zero.

NOTE:

If the monitor will not zero and re-gapping the probe is not practical, the
zero adjust range can be increased by changing the jumpers listed in the
following tables.
If the zero adjustment range is increased, it is important to verify that the
OK voltage level check recognizes Not OK conditions. After selecting the
new zeroing range and calibrating the monitor, verify that the OK LEDs go
out when the shaft is at either of its extreme limits. If the OK LEDs do not
go out, the system must be recalibrated and the OK limits checked again
until this requirement is met.

36

Section 16 - Calibrate Channels

CAUTION
If you extend the zero adjustment range to 7.5 mils, you
may prevent the monitor from reaching a full scale
reading and your alarm setpoints.
This caution applies to ALL transducers with or without
barriers.
Main Board 135313-01
Zero Adjustment Range*
Transducer

Range

3000 and 3300 RAM or XL NSv


7200 - 5mm/8mm & 3300 5mm/8mm
with and without Barriers

REMOVE

INSTALL

25 - 0 - 25 mils

W23C (2.5 mils)

W23B (7.5 mils)

40 - 0 - 40 mils

W23C (2.5 mils)

W23B (7.5 mils)

1 - 0 - 1 mm

W23C (0.0635 mm)

W23B (0.1905 mm)

7200 with

75 - 0 - 75 mils

W23C (5.0 mils)

W23B (15.0 mils)

11 mm/14 mm probe or 3300 HTPS

2 - 0 - 2 mm

W23D (0.0635 mm)

W23C (0.1270 mm)


or
W23B (0.3810 mm)

Main Board 79482-01


Zero Adjustment Range*
Transducer

Range

3000 and 3300 RAM or XL NSv


7200 - 5mm/8mm & 3300 5mm/8mm
with and without Barriers

REMOVE

INSTALL

25 - 0 - 25 mils

W3D (2.5 mils)

W3B (7.5 mils)

40 - 0 - 40 mils

W3D (2.5 mils)

W3B (7.5 mils)

1 - 0 - 1 mm

W3D (0.0635 mm)

W3B (0.1905 mm)

7200 with

75 - 0 - 75 mils

W3D (5.0 mils)

W3B (15.0 mils)

11 mm/14 mm probe or 3300 HTPS

2 - 0 - 2 mm

W3C (0.0635 mm)

W3D (0.1270 mm)


or
W3B (0.3810 mm)

To increase the zero adjustment range, remove and install the jumpers listed in the table. The corresponding zero
adjustment range is given in parentheses next to the jumper selection.
37

3300/20 Dual Thrust Position Monitor Operation Manual

16.3 Prepare to Bring the Monitor On Line


(Repeat for channels A and B)
1.

Reduce the input amplitude to below the alarm setpoints and observe that the
ALERT and DANGER LEDs go off (if non-latching alarm jumpers are installed).

2.

Press the RESET switch on the System Monitor to reset latching alarms.

3.

Disconnect the test equipment and reconnect the transducers to their respective
channels in accordance with the field wiring diagrams at the end of this manual.
Verify that the OK LEDs come on and the OK Relay energizes (if non-latching OK
mode is selected).

4.

Press the RESET switch on the System Monitor to reset latching not OKs.

5.

If the Channel Bypass or the Danger Bypass functions were activated for this
procedure, deactivate them before monitoring resumes (see Sections 11 & 12 of
this manual).

6.

Close the front panel.

38

Section 17 - Self Test

17. Self Test


The monitor has three levels of self tests:
SELF TEST
PERFORMED
Power-up

When the monitor is turned on.


Continuous during monitoring
Cyclic
operations.
When you initiate the self test by
User-invoked temporarily shorting the self-test
pins.
When the monitor detects an error, it displays an error
condition two ways depending on whether the error is
active or stored. An active error is an error that currently
exists. A stored error condition results from a storable
error momentarily occurring after the last time all errors
were cleared.

Active Error Indication

If the monitor detects an active error, the following events


occur:
Monitoring stops until the problem is resolved
The error code is stored in memory and flashes on
the LCD bargraph
The BYPASS LEDs come on
The OK LEDs flash at 5 Hz
The OK Relay de-energizes
Active errors that do not flash the OK LEDs require userinvoked self test or may require recycling power to clear
them. If either of these actions fails to clear the error refer
to the Error Codes section.
If the monitor no longer detects an active error and a
stored error exists, the following events occur:

Monitoring resumes

If the OK LED would otherwise be on, the OK LEDs flash


at 5 Hz to indicate that an error code has been stored
If all other channels in the rack are OK, the OK relay will
energize if non-latching OK mode is set. Press RESET
on the system monitor to restore the OK relay condition
for the latching mode.

Stored Error Indication

39

3300/20 Dual Thrust Position Monitor Operation Manual


Recall stored error codes by using the User-invoked self test. Use the following steps to
run the User-invoked self test, read error codes, and clear stored error codes:

Caution
Machine protection provided by
this monitor will be lost for the
duration of the self test.
Note: If any error is active, a Userinvoked
self test cannot be initiated. Refer to the
error Codes Section.
1. Initiate the User-invoked self test by
shorting the two self test pins (ST) with a
screwdriver. All the LEDs and LCD
elements will come on for 5 seconds. The
OK relay will de-energize during this
test.
If an active or stored error is present at
the end of the self test, the BYPASS LED
remains on, the OK LEDs flash at 5 Hz,
and the first error code flashes at 2 Hz on
the LCD bargraph.
The error code is given by the number of
flashing segments in one column of the
bargraph. For example, the monitor to the
right is indicating error code number 6

40

Section 17 - Self Test

2.

Read any other stored error codes


by pressing and holding the ALERT
switch for approximately one
second.
For example, the display to the far
right contains a second stored
error code - number 10.

4.

When you reach the end of the


error code list, the LCD bargraph
comes on with all LCD segments lit
and the OK LEDs turned off.
You may read through the list
again by continuing to press the
ALERT switch.

41

3300/20 Dual Thrust Position Monitor Operation Manual

18. Error Codes


Refer to the Monitor Functions, Section 2 and Self Test, Section 17 for more information
about displaying error codes. Refer to the Self Test section for information about
clearing stored errors.
ERROR
CODE
2

DESCRIPTION

EXPLANATION/RECOVERY

ROM checksum failed.

Tested at power up and User-invoked self


test. This error is displayed on the front
panel, but is not stored in memory. Install
your spare monitor or contact your local
Bently Nevada office for service.
Nonrecoverable EEPROM failure. Tested only at Cyclic self test. Install your
spare monitor or contact your local Bently
Nevada office for service.

EEPROM failure.

5
6

+7.5V/-VT node out of tolerance.


+VRH node out of tolerance.

7
8

+5V node out of tolerance.


MVREF node out of tolerance.

9
10
11

+7.5V node out of tolerance.


+VRL node out of tolerance.
MVREF/-6.5V node out of
tolerance.

May be corrected by adjusting alarm


setpoints in the monitor (See section 10).
If setpoint adjustment fails to correct this
error, install your spare monitor or
contact your local Bently Nevada office
for service.

Tested cyclically. If it is a stored error,


recall and clear the error codes as
described in the Self Test, Section 17.

12
13

If it is an active error, replace the monitor


+5V/-7.5V node out of tolerance. with a spare or contact your local Bently
Nevada office for service.
Clock OK voltage out of
tolerance.

14

RAM failure.

Tested only at Power-up or User-invoked


self test. These errors are displayed on
17
COP watchdog not configured.
the front panel but not stored in memory.
Install your spare monitor or contact your
local Bently Nevada office for service.
NOTE: If the monitor experiences recurring stored errors contact your local Bently
Nevada office for service.
42

Section 19 - Appendix AMain Board Options

19. Appendix AMain Board Options


19.1 Jumper Locations for PWA 135313-01
The Thrust Position Monitor has several user-programmable options. Removing and
installing jumpers on the main circuit board can change the options. This section
includes a jumper location diagram and a programmable option table for PWA 13531301 (new) followed by a jumper location diagram and a programmable option table for
PWA 79482-01 (old).
IMPORTANT!
W25, W26, and W31 on PWA 135313-01 are for factory
use only and should not be changed.
For normal operation W25, W26, and W31 should be
removed.

43

3300/20 Dual Thrust Position Monitor Operation Manual

19.2 Full Scale Options for PWA 135313-01


Use these and the tables on the following pages to configure main board options:
FULL SCALE OPTIONS *
Transducers

MILS
25 -0- 25

3000 Series,

30 -0- 30

40 -0- 40

MILLIMETRES
50 -0- 50

75 -0- 75

0.5 -0- 0.5

1- 0 -1

2-0-2

W23B,E,J,L

W23C,J, L

3300 RAM or
XL NSv
Proximitors,
200mV/mil
3300 & 7200

W23A,H,

W23B,H,

W23C,G,

W23A,E,H,

W23C,G,

SERIES

L,M,P

L,M,P

H,L,M,P

L,M,P

H,L,M,P

3300 & 7200

W23A,K,

W23B,K,

W23C,G,

W23A,E,K,

W23C,G,

SERIES WITH

O,R

O,R

K,O,R

O,R

K,O,R

7200 SERIES

W23B,E,

W23B,E,

W23B,E,

W23B,I,

W23C,G,

W23B,F,I,

W23B,E,I,

W23D,G,

11 mm, (Not

F,I,L,N,Q

F,I,L,N,Q

I,L,N,Q

L,N,Q

I,L,N,Q

L,N,Q

L,N,Q

I,L,N,Q

WITHOUT
EXTERNAL
BARRIERS
(200 mV/MIL)

EXTERNAL
BARRIERS
(192 mV/mil)

XL), (100
mV/MIL)
7200 SERIES

W23B,E,

W23B,E,

W23B,E,

W23B,H,

W23C,G,

W23B,F,H,

W23B,E,H,

W23D,G,

14 mm or

F,H,L,N, Q

F,H,L,N, Q

H,L,N,Q

L,N,Q

H,L,N,Q

L,N,Q

L,N,Q

H,L,N,Q

3300 HTPS
Proximitors
(100 mV/MIL)

CAUTION
Changing full scale requires recalibration of both
channels (see "Calibrate Channel", section 16).
* To change to a new full scale and transducer option, remove jumpers from W23A-R then install the jumpers specified in the table.

NOTE: For 3300 XL 11mm transducers, use mod 146300-01.

44

Section 19 - Appendix AMain Board Options

19.3 Main Board Option Settings for PWA 135313-01


Option
First Out

Alert Mode

Danger Mode

Danger Voting

Danger Bypass

Alarm Delays

Not OK Mode

Normal Direction

Meter Response Time

Recorder Output

Jumper

Setting

Install

Remove

Enabled*

----------

W24G

Disabled

W24G

----------

Latching*

----------

W24F

Non-latching

W24F

----------

Latching*

----------

W24H

Non-latching

W24H

----------

AND Relay Drive* ++

----------

W24I

OR Relay Drive

W24I

----------

Enabled

W24B

----------

Disabled*

----------

W24B

0.1 s

W24E

W24D

1 s*

----------

W24D,E

3s

W24D,E

----------

6s

W24D

W24E

Latching

W24A

----------

Non-latching*

----------

W24A

Ch A

----------

W24J

Ch B

----------

W24K

Away From Probe Ch A

W24J

----------

Ch B

W24K

----------

Fast*

----------

W24C

Slow

W24C

----------

+4 to +20 mA*

W28A, W29A

W28B, W29B, W30A,B,C,D

Toward Probe*

W28A, W29A, W30A,B,C,D


+1 to +5 Vdc

W28B, W29B
W28A, W29A

0 to -10 Vdc

W28B, W29B,
W30A,B,C,D

NOTES:
*
Denotes standard configuration.
++
AND voting with Quad Relays must be done externally by wiring contacts in
series.

45

3300/20 Dual Thrust Position Monitor Operation Manual

19.4 Jumper Locations for PWA 79482-01

CAUTION
Changing full scale requires
recalibration of both channels
(see "Calibrate Channel" section).

46

Section 19 - Appendix AMain Board Options

19.5 Full Scale Options for PWA 79482-01


FULL SCALE OPTIONS *
Transducers

MILS
25 -0- 25

30 -0- 30

40 -0- 40

MILLIMETRES
50 -0- 50

75 -0- 75

0.5 -0- 0.5

3000 Series,

W2A,B,

3300 RAM or

W3D,

W3B,

XL NSv

W4C,E,G,W

W4C,E,G,

Proximitors,

6B

W6B

1- 0 -1

2-0-2

W2C,

200mV/mil
3300 & 7200

W2A,B,

W2A, W3E,

W2A,

W2C, W3F,

W2A,

SERIES

W3F,

W4A,F,G,

W3D,

W4A,E,G,

W3D,

WITHOUT

W4A,E,G,

W5A,D,

W4A,E,G,

W5A,D,

W4A,E,G,

EXTERNAL

W5A,D,

W6A

W5A,D,

W6B

W5A,D,

BARRIERS

W6B

W6B

W6B

(200 mV/mil)
3300 & 7200

W2A,B,

W2A, W3E,

W2A,

W2C, W3F,

W2A,

SERIES WITH

W3F,

W4D,F,

W3D,

W4D,E,

W3D,

EXTERNAL

W4D,E,

W5C,F,

W4D,E,

W5C,F,

W4D,E,

BARRIERS

W5C,F,

W6A

W5C,F,

W6B

W5C,F,

(192 mV/mil)

W6B

7200 SERIES

W2C, W3A,

W2C, W3E,

W2C,

W2A,B,

W2B,

W2A,C,

W2C,

W2A, W3C,

11 mm (Not

W4B,G,

W4B,G,F,

W3B,

W3B,

W3D,

W3B,

W3B,

W4B,E,G,W

XL) (100

W5B,E

W5B,E,

W4B,E,G,

W4B,E,G,

W4B,E,G,

W4B,E,G,

W4B,E,G,

5B,E, W6B

W6A

W5B,E,

W5B,E,

W5B,E,

W5B,E,

W5B,E,

W6B

W6B

W6B

W6B

W6B

mV/mil)

W6B

W6B

7200 SERIES

W2C, W3A,

W2C, W3E,

W2C,

W2A,B,

W2B,

W2A,C,

W2C,

W2A, W3C,

14 mm or

W4A,G,

W4A,G,F,

W3B,

W3B,

W3D,

W3B,

W3B,

W4A,E,G,

3300 HTPS

W5B,E

W5B,E,

W4A,E,G,

W4A,E,G,

W4A,E,G,

W4A,E,G,

W4A,E,G,

W5B,E,

W6A

W5B,E,

W5B,E,

W5B,E,

W5B,E,

W5B,E,

W6B

W6B

W6B

W6B

W6B

W6B

Proximitors
(100 mV/MIL)

* To change to a new full scale and transducer option, remove jumpers from W2-A,B,C, W3-A,B,C,D,E,F,W4A,B,C,D,E,F,G, W5A,B,C,D,E,F, and W6-A,B then install the jumpers specified in the table.

NOTE: For 3300 XL 11mm transducers, use mod 146300-01.

47

3300/20 Dual Thrust Position Monitor Operation Manual

19.6 Main Board Option Settings for PWA 79482-01


Option
First Out

Alert Mode

Danger Mode

Danger Voting

Danger Bypass

Alarm Delays

Not OK Mode

Normal Direction

Jumper

Setting

Install

Remove

Enabled*

W16A

----------

Disabled

----------

W16A

Latching*

W15C

----------

Non-latching

----------

W15C

Latching*

W16B

----------

Non-latching

----------

W16B

AND Relay Drive* ++

W16C

----------

OR Relay Drive

----------

W16C

Enabled

W20

----------

Disabled*

----------

W20

0.1 s

----------

W15A,B

1 s*

W15B

W15A

3s

W15A

W15B

6s

W15A,B

----------

Latching

W19

----------

Non-latching*

----------

W19

Ch A

W1

----------

Ch B

W18

----------

Ch A

----------

W1

Ch B

----------

W18

Toward Probe
Away From Probe

Meter Response
Time

Fast*

----------

W21

Slow

W21

----------

Recorder Output

+4 to +20 mA

W7A,C,E,F; W8B,C;
W10A,B; W11B,C;

W7B,D; W8A,D,E,F; W9A,B;


W11A,D,E,F;

W12A,C,E,F

W12B,D

+1 to +5 Vdc

W7B,D; W8A,E; W10A,B;


W11A,E; W12B,D

W7A,C,E,F; W8B,C,D,F;
W9A,B; W11B,C,D,F;
W12A,C,E,F

0 to -10 Vdc

W7B,D; W8D,F; W9A,B;


W11D,F; W12B,D

W7A,C,E,F; W8A,B,C,E;
W10A,B; W11A,B,C,E;
W12A,C,E,F

NOTES:
*
Denotes standard configuration.
++
AND voting with Quad Relays must be done externally by wiring contacts in
48

Section 19 - Appendix AMain Board Options

19.7 Expander Board Installation/Removal,


PWA 79482-01

49

3300/20 Dual Thrust Position Monitor Operation Manual

20. Recommended Spare Parts


To order replacement parts see the Specifications and Ordering Information section at
the end this manual. The complete part number must be specified, as indicated on the
identification decal. The part number is explained on page 19.
If you have a monitor that has been modified, the modification number must be specified
on the parts order. The modification number (if any) will be shown on the identification
decal.
If in doubt about the part number, call your Bently Nevada representative before
ordering the part.
The customer programmable options on replacement parts will be set as shown in
Section 19.

50

Section 21 - Index

21. Index
A

Adjustments.............................................................................................................................22, 25, 26, 33, 34


Alarm..........................................................................................................................2, 3, 22, 25, 37, 38, 45, 48
Alert ............................................................................................................................2, 7, 11, 18, 22, 28, 45, 48
B
Barriers............................................................................................................................... 15, 18, 20, 34, 44, 47
Buffered Output ..................................................................................................................................................... 3
Bypass, Channel...................................................................................................................................... 5, 23, 30
Bypass, Danger ........................................................................................................................... 2, 6, 24, 45, 48
C
Calibration ...............................................................................................................................................25, 33, 43
Configuration ................................................................................................................................. 15, 19, 44, 47
D
Danger .............................................................................................................. 2, 8, 11, 18, 22, 24, 29, 45, 48
Direction, Normal/Counter....................................................................................................... 11, 28, 45, 48
E
Error..........................................................................................................................................................3, 5, 40, 42
Error Reset..............................................................................................................................................................41
F
Field Wiring .......................................................................................................................................................1, 14
First Out ....................................................................................................................................... 2, 28, 29, 45, 48
Flashing LCD............................................................................................................................................. 3, 22, 41
Flashing LED ............................................................................................................................ 2, 3, 5, 28, 29, 41
I
Inhibit .......................................................................................................................................................2, 6, 12, 29
J
Jumper Settings....................................................................................................................... 3, 19, 33, 43, 46
L
Latching/Non-latching......................................................................................................2, 5, 30, 38, 45, 48
M
Meter Scale .................................................................................................................... 3, 9, 20, 21, 34, 44, 47

3300/20 Dual Thrust Position Monitor Operation Manual


O
OK/Not OK ....................................................................................................... 2, 5, 23, 30, 33, 36, 38, 45, 48
Options, Monitor .........................................................................................4, 15, 16, 17, 18, 19, 21, 43, 50
OR Bus .......................................................................................................................................................16, 17, 18
P
Probe Installation ...........................................................................................................................................2, 10
R
Recorder Output ..............................................................................................................................3, 34, 45, 48
Relay...........................................................................................................................................................15, 19, 20
Relay, Alert.................................................................................................................................. 2, 16, 17, 18, 28
Relay, Danger..............................................................................................................2, 16, 17, 18, 24, 45, 48
Relay, OK ........................................................................................................................................ 2, 5, 23, 30, 38
Reset ...................................................................................................................................... 2, 23, 27, 30, 31, 38
Response Time ........................................................................................................................................ 3, 45, 48
S
Scale Factor ................................................................................................................................................... 20, 34
Self Test...............................................................................................................................................................3, 42
Setpoints, Alarm................................................................................................. 2, 11, 22, 24, 25, 28, 29, 37
Spare Parts.............................................................................................................................................................50
T
Test Point.................................................................................................................................................................33
Time Delay.............................................................................................................................................2, 3, 45, 48
Transducers ............................................................................................................................................20, 44, 47
V
Voting, AND ................................................................................................................................... 2, 8, 19, 45, 48
Voting, OR .................................................................................................................................................. 2, 45, 48
Z
Zero Adjust ....................................................................................................................... 25, 33, 34, 35, 36, 37

Potrebbero piacerti anche