(R22/R407C)
03 50 TON
011 175 kW
REVERSE CYCLE/COOLING/HIGH AMBIENT

UNIT NOMENCLATURE ..
INTRODUCTION
PRODUCT FEATURES
General ..
Structure
Electrical And Control ..
SB 125 Single System .
SQ 2.0 Double System
Coils ...
Evaporator Fan And Motor .
Condenser Fan And Motor .
Compressor ..
DESIGN PARAMETER .
CONTROL BOARD
SB 125 Series ..
SLM Series
Sequential PAC Controller (SQ 2.0) .
SQLCD Controller
RATINGS DATA
YRM Standard Ambient ..
YRM High Ambient ..
PHYSICAL DATA
YRM Standard Ambient ..
YRM High Ambient ..
YCS Standard Ambient ...
YCS High Ambient ......
DIMENSIONS
YRM Shopfloor .
YCS Shopfloor ..
SOUND DATA
ELECTRICAL NOTES ..
ELECTRICAL DATA .
YRM Standard Ambient ..
YRM High Ambient ..
YCS Standard Ambient ...
YCS High Ambient ...

PAGE
4
5
6
6
6
6
6
7
7
7
7
8
9 20
21 24
25 43
44 51
52 87
88 100
102 - 110
111 117
118 125
126 133
134 151
152 - 158
160
161
162 163
164 165
166 167
168 169

ELECTRICAL DIAGRAM
YRM (Cooling Only)
YRM (Heat Pump)
YCS (Cooling Only & High Ambient)
YCS (Heat Pump)
YRM Cooling Only (CE)
YRM Heat Pump (CE)
GUIDE SPECIFICATIONS
General ..
Cabinet ..
Indooor Section
Outdoor Section ...
Refrigerant Cirduit
Electrical And Control ..
SB 125 Single System .
SQ 2.0 Double System
Indoor Coil and Outdoor Coil .
Evaporator Fan And Motor .
Condenser Fan And Motor .
Compressor(s) ..
Options ..
Nomenclature

170 177
178 184
185 191
192 198
199 205
206 212
214
214
214
214
214
215
215
215
215
216
216
216
216
217

CHANGEABILITY OF THIS DOCUMENT


In complying with YORKS policy for continuous
product improvement, the information contained
in this document is subject to change without
notice. While YORK makes no commitment to
update
or
provide
current
information
automatically to the manual owner, that
information, if applicable, can be obtained by
contacting the nearest YORK Applied Systems
office.

It is the responsibility of operating/service


personnel to verify the applicability of these
documents to the equipment in question. If there
is any question in the mind of operating/service
personnel as to the applicability of these
documents, then prior to working on the
equipment, they should verify with the owner
whether the equipment has been modified and if
current literature is available.

The model number denotes the following characteristics of the unit :

Y R M

0 2 2

Base
Product
Type

Unit
Size
kWR

Type

Power
Type

Comps

Blower
Drive

Ref
Type

Design
Series

Pin
Code

Base product type

YRM Packaged Unit


YCS Condensing Unit

Unit size kWR

011 to 175 (YCS from 030 onwards)

Type

R
C
H

Reverse cycle
Cooling only
Cooling only ( High Ambient)

Power type

4
X

380-415V / 3ph - 50Hz


Others

Comps

S
D
Q

Single Compressor
Double Compressor
Quadruple Compressor

Blower drive

Belt drive

Refrigerant Type

C
A

Design series

Pin code

X
A
S

R - 22
R - 407C

Standard left hand


Standard right hand
Others

YORK MillenniumTM Commercial Unitary Packaged and Split System units are designed for
cooling/heating filtered air. They are capable of providing cooling in ambients of 15oC DB to
46oC DB, cooling in high ambient 15oC DB to 52oC DB and providing heating in ambients
of -5.0oC DB to 20oC DB. Each system consists of either a single packaged unit (YRM ducted
roof mounted packaged unit) or a split system (YCS ducted split systems) which require
installation of interconnecting piping and controls on site (by others).

GENERAL

The YRM and YCS units are designed to be


located on the roof of a building or at ground
level. However with careful consideration of the
air flow to the condenser coils and the drainage
of the condensate, the units can be located
indoors.

Prior to delivery each unit is pressure tested,


evacuated and charged with refrigerant (YRM
only) or dry nitrogen (YCS) and oil.

STRUCTURE

The cabinet is constructed of galvanized


steel with either fabricated galvanized sheet
metal base with full width supported by
underside gusset.
All surfaces coated with oven baked silk
grey colored coating for lasting finish.
Indoor section comes with SS304L
condensate drain pan or electro galvanized
and insulated with 10mm polyethylene
insulation covered with foil surface.
Compressor
compartment
includes
compressor electrical panel(s), outdoor coil
thermal expansion valve(s), liquid line sight
glass(es), pressure controls and filter drier.
For reverse cycle unit, check and reversing
valve(s) and suction accumulators are also
included pressure controls and filter drier.

ELECTRICAL AND CONTROL

High and low pressure safety, power off


electrical reset.
Compressor overloads, manual reset at
switchboard.
Overloads for three phase condenser and
evaporator fan motors, manual reset at
switchboard.
Anti-coincident timers to prevent multiple
compressors from starting at the same time.
Anti-recycle timers for each compressor.
Defrost control for reverse cycle unit.

Automatic compressor lead lag control, for


multiple compressor units.

SB 125 Single System (YRM/YCS)

Auto/Cool/Fan/Heat/Defrost system control


modes.
Real Time Clock with Real Time On/Off Timer
and delay timer up to 15 hours.
Sleep function for Cool, Heat and Auto mode.
Integrated Cold Start, Hot Start and Hot Keep
functions to rapidly bring room temperature to
selected setting during power on.
LEDs display for Power, Cool, Heat, Sleep
and Timer.
Memory backup for last state settings option.
Compatible with wired and wireless controller.

SQ 2.0 Double System (YRM/YCS)

Sequential control and balance loading up to


4 stage compressors.
Selectable stage differential temperatures.
Single speed indoor fan.
7 days programmable timer.
Cool/Heat/Auto/Fan control, ranging from
16oC to 30oC temperature setting.
Cold blast, Spurt heat, Hot start and Hot keep
to rapidly bring room temperature to selected
setting during power on.
Wired LCD control panel.
Self-diagnostic
feature,
error/warning
indications.
Energy saving function for Cool, Heat and
Auto modes.
Compressor trip/low refrigerant warning.
Compressor high temperature protection.
Indoor antifreeze protection.
Battery back-up. If the power fails, a back-up
battery will maintain the real time clock and
the integrity of the controls data. When
power is resumed / switched on again, the
unit will automatically restart using the
original settings.

COILS

CONDENSER FAN AND MOTOR

Indoor coil fabricated with seamless copper


tubing mechanically expanded into high
efficiency Aluminium fins with working
pressure of 1650kPa.
Outdoor coil fabricated with seamless copper
tubing mechanically expanded into high
efficiency Aluminium fins with working
pressure of 1950kPa.
Hydrophilic fins, Copper fins or Heresite
coated fins are available as options.
Optional coils utilizing differing materials of
construction and or coatings applied to the
coils after production may be specified.

EVAPORATOR FAN AND MOTOR

Double inlet centrifugal type, statically and


dynamically balanced and belt driven by
TEFC IP55, Class F insulated motor.

Axial flow type with multiple glass reinforced


nylon aerofoil impellers. The motor(s) are
three phase with external overloads suitable
for outdoor application.

COMPRESSOR

Fully hermetic scroll suited for R22 or R407C.


Constructed from a welded shell complete
with an integral suction gas cooled electric
motor directly driving a multi-cylinder
compressor.
Includes internal discharge muffling to
minimize gas pulsations.
Motor fitted with internal line break overload.
Crankcase heater is fitted to each
compressor.

VOLTAGE CODE

UNIT POWER

MINIMUM
VOLTAGE

MAXIMUM
VOLTAGE

380/415V-3ph-50Hz

342

440

ENTERING AIR TEMPERATURE oC


DRY BULB

COOLING

HEATING

MINIMUM

MAXIMUM

MINIMUM

MAXIMUM

INDOOR COIL

20.0

33.0

10.0

25.0

OUTDOOR COIL

15.0

46.0

-5.0

20.0

OUTDOOR COIL (HI AMBIENT)

15.0

52.0

REFRIGERANT PIPING SPLIT UNITS


(YCS)

OUTDOOR UNIT ABOVE


INDOOR UNIT

OUTDOOR UNIT BELOW


INDOOR UNIT

MAXIMUM TOTAL LENGTH metres

30.0

25.0

MAXIMUM TOTAL HEIGHT


DIFFERENCE metres

15.0

15.0

For advice on application outside the above limits please contact your local York Office.

The SB 125 Series is a Printed Circuit Board (PCB), which is installed in an air-conditioning unit,
ready instructions from a compatible LCD wireless remote control, an LED wired remote control or
an LCD wired remote control.
The SB 125 Series can be produced to respond to all, or a selection of function as listed in the
features, depending on the requirement of each customer.
The module is designed for ducted split air conditioning unit, with ease in installation and highly
reliable.

FEATURES

Auto / Cool / Fan / Heat / Defrost system control modes.


Single speed indoor fan speed control.
Single speed outdoor fan speed control.
LCD remote control reception.
Wired LCD (N2/N3) control reception.
Real Time Clock with Real Time On/Off Timer and delay timer up to 15 hours.
Sleep Function fool Cool, Heat and Auto mode.
Integrated Cold Start, Hot Start and Hot Keep function to rapidly bring room temperature to
selected setting during power on.
Frost / ice prevention in indoor coil for cooling cycle.
Compressors overload protection for heating cycle & cooling cycle.
Compressors recycle protection (Anti short cycle timer).
Indoor Antifreeze (2 options) for cooling cycle.
Indications for thermostats contact condition.
LEDs display for Power, Cool, Dry, Fan, Heat, Sleep, and Timer.
On-line testing activation (OnTAC).
Heat Mode Offset 2 C.
Memory backup for last state setting option.
Compatible with wired and wireless controller.
Seven segments display for room temperature in C or F options.
DEFROST system control.
Outdoor coil sensor exits detection.

SB 125 Main Board

SYSTEM CONFIGURATION
The wiring diagram for SB 125 Series is shown below:

ELECTRICAL SPECIFICATIONS
Power Supply
Frequency
Power Input
Relay

Transformer
Fuse
Power Connections
Fan Connector
10

230V AC Nominal
50 / 60 Hz
10 VA Maximum
Compressor Relay
250V AC 20 A (steady state)
250V AC 70A (in rush)
Auxiliary Relay
250V AC 5A (steady state)
230 / 10V Nominal 6 VA 50 /60 Hz
3.15A 250 VAC
0.25 Tab Terminal
0.25 Tab Terminal

OPERATING AND RELIABILITY SPECIFICATIONS


Electromagnetic Immunity
The SB 125 Series are subjected to the following tests complying with IEC standards:
Test
Electrical Fast Transient
Surge Immunity Test
Power Quality Test
Radiated Immunity
Conducted and Radiated Emissions
Environmental Stress Test
Storage Test
Vibration Test

Standard
IEC 1000 4 4
IEC 1000 4 5
IEC 1000 4 11
IEC 1000 4 3
FCC Part 15B (1990)
In House
In House
In House

Application and Environment


Temperature
Relative Humidity

0 C 60 C Operating Temperature
-10 C 85 C Storage Temperature
0 95% non condensing

FUNCTIONS
The system has 3 modes selection to be selection via the value of resistor RMODE. The following
notations are used to represent the various modes selected:
UNIT
Split
Split
Multisplit
Multisplit
Split / Multisplit
Split / Multisplit

MODES
AP
AP
AP
AP
AT
EC

AUTO
X
X
X
X
X

COOL
X
X
X
X
X
X

HEAT
X
X
X
X
X

FAN
X
X
X
X
X
X

DEFROST
C2.4 version
C2.3 version
-----

RMODE
3K
7K5
3K
7K5
22K
110K

Where X denotes modes available


1

Power Up Setting
During power up, the system memorizes the setting prior to power down. The settings that
are memorized are:
Mode & On/Off status
Set Temperature
Compressor accumulated run hours
Key Lock (for Wired control)
These data or settings are saving in non-volatile memory.

11

The CPU will save the updated settings into the memory 10 seconds after changes are
confirmed. However it will take 3 seconds to update the memory if the unit changes from on
to off state.
2

Unit ON / OFF
There are 3 ways to turn on or off the system:
a) via ON / OFF triggering.
ON / OFF triggering can be achieved by pressing the emergency ON / OFF button or the
LCD remote controller ON / OFF button. In doing so, the DELAY timer will be reset.
When the emergency ON / OFF button is pressed, the system mode setting will rotate in
the following sequence:MODEL
AP
EC

SEQUENCE
--------> COOL > HEAT > OFF>------------------>COOL > OFF>----------

The corresponding LEDs will also follow suit. Pressing the remote control ON / OFF will
toggle the system status either from ON to OFF or from OFF to ON.
b) via delay timer
This delay timer is to simulate the ON / OFF pressing after the set number of hours and
minutes. After triggering, the delay timer is set to 0 hours. Pressing ON / OFF will also
reset this timer to 0 hours.
c) via real time ON / OFF timer
When the real time ON timer set time matches the internal real time clock, the unit will
be switched on. Similarly, when the OFF time matches the real time clock, the unit is
switched off. The timer settings are retained so that similar switching can occur 24 hours
later. The timer will be reset if the emergency ON / OFF switch is pressed.
3

Temperature Range and Settings


The operating temperature range is 16 C to 30 C (60 F to 86 F), both inclusive.
Temperature setting is allowed in Cool, Dry, Heat and Auto modes.

Indoor Fan Speed


Only one fan speed is available for indoor fan.

Sleep Function
In order to compensate for natural variants in our body temperature during sleep, the SB
125 Series automatically adjusts the air-conditioning temperature for the comfort of the user.

12

Cool Mode Sleep Profile

Heat Mode Sleep Profile


The Sleep function is only available in Cool, Heat and Auto modes. Changing to other
modes will inhibit the Sleep function and the timer will be reset.
Pressing the emergency On / Off will deactivate and clear the Sleep function. This function
is set / reset by the wired / wireless controller.
6

Protections

6.1

3 Minutes Minimum OFF Time for Thermostat


For thermostat cycles, the compressor can only cut in after a minimum period of 3 minutes
from the time it cuts off except during valve changeover sequences.

6.1.1

Hardware Anti short cycle protection


Should the main power cuts out and power resume, there are 2 options whereby will depend
on if memory backup option is selected:a)
If memory backup option is not selected (JP1 opened).
i )
within 2 minutes of outage, the compressor can only cut in 180 seconds after
power up; subject to thermostat cut in mode.
ii )
after 2 minutes of outage, the compressor can cut in immediately after power
up again; subject to thermostat cut in mode.

13

b)

If memory backup option is selected (JP1 shorted).


i )
within 2 minutes of outage, the compressor can only cut in 180 seconds to
210 seconds after power up; subject to thermostat cut in mode.
ii )

after 2 minutes of outage, the compressor can cut in 15 seconds to 75


seconds after power up again; subject to thermostat cut in mode.

6.2

140 seconds Minimum Run Time for Thermostat


For thermostat cycles, the compressor can only cut out after minimum 140 seconds of
running in the current mode. The compressor can be cut out at any time if the system is
switched to other modes or in any other protection sequences.

6.3

Compressor Overload Protection


There are two methods to detect the compressor overload; namely by the coil sensors and
the hardware overload (normally close) switch.
a)

Coil Sensors Detection


In cooling cycle when the outdoor coil temperature exceeds 75C, both the
compressor and outdoor fan will stop operating.
In heating cycle when the indoor coil temperature exceeds 75C, the compressor,
outdoor fan and 4 way valve will stop operating accordingly.
The unit will auto reset if the temperature goes below 50C. This is allowed once
every power on reset. If the temperature goes below the permissible limit, the
overload protection can be reset manually by triggering the ON / OFF key.

b)

Hardware Switch Detection


This is normally close switch. It is connected in series with the power supply to the
controller. Once there is overload, the switch will open and power supply to controller
will be cut off.
During the first cycle of thermostat on since power on reset, a counter is increased
by one and a timer start to run. If the timer exceeds 3 minutes or the unit is turned off,
the counter is reset to 0. During the increment, if the counter is > 5, the unit will
declare compressor overload protection. This fault is manual resettable.
The counter is saved in the non-volatile memory. If memory backup option is not
selected, the counter is always set to 0 during power on reset.

6.4

Outdoor fan speed control


Only 1 outdoor fan speed is available

6.5

Indoor fan speed control


Only 1 indoor fan speed is available

14

Operating Modes
The system mode is set by the wired / wireless control. The actual mode will be shown on
the mode LEDs. Mode changes respond 2 seconds after data reception

7.1

Cool Mode
In Cool mode, the compressor will be cut in if the Tr Ts >0.5C and the compressor will be
cut out if the Tr < Ts 1.0C, this is to timing protections. In this mode, the indoor fan is
always running.
During cold start, the working Set Temperature is set to User Set Temperature -2C (cold
blast). This will remain until the compressor has cut off or has run for at least 20 minutes.
After that, the working Set Temp is reset back to the user Set Temp.

7.1.1

Cold Blast
When the unit restarts 2 hours after it has stopped or during power-on-reset start, it is
considered a cold start. During cold start the working Set Temperature is set to User Set
Temperature -2 C (cold blast). This will remain until the compressor has cut off or has run
for at least 20 minutes. After that, the working Set Temperature is reset back to the User Set
Temperature.

7.2

Heat Pump Mode


The compressor will be cut in if the Tr.< Ts + 1C and will be cut out if Tr Ts > 1.5C,
subject to timing protections.

7.2.1

Hot Start
During the compressor cut in cycle, the indoor fan will modulate according to the indoor coil
temperature:
If the indoor coil temperature > 40C, the indoor fan will run at user set fan.
If the indoor coil temperature < 18C, the indoor fan will stop.

7.2.2

Hot Keep
When the compressor cuts out, the unit is Hot Keep mode. There are 3 option of Hot Keep:a) Fan on option (C2 spec)
This option is selected if a 110k ohm resistor is inserted into RFAN.
The start of heat mode is defined as when:
The unit is just turned on from off with setting in Heat mode OR
The mode changes from non-heat to Heat mode OR
Just after the end of a defrost cycle.
The hot keep cycle at the start of heat mode will be as follow:
If the indoor coil temperature crosses 37C, the indoor fan will run.
If indoor coil temperature < 33C, the indoor fan will stop.

15

For thermostat cycle cut offs, the following hot keep cycle will apply:
If the indoor coil temperature crosses 37C, the indoor fan will run.
If indoor coil temperature < 18C, the indoor fan will stop.
b) Fan off option
This option is selected if a 7k5 ohm resistor is inserted into RFAN.
If the indoor coil temperature crosses 37C, the indoor fan will run.
If indoor coil temperature < 33C, the indoor fan will stop.
c) Fan cycle on & off Option
This option is selected if a 22k ohm resistor is inserted into RFAN.
The low fan will cut in for 30 seconds and subsequently off for 120 seconds. This cycle
of on and off will repeat continuously.
8

4 Way Valve Switching


To run heat pump, the 4-way valve must turn On. Upon return to a non-heat pump mode,
the 4-way must turn Off. The 4-way valve can only be changed 55 seconds after the
compressor has been cut out. Then the compressor may be cut in 4 second later.

Auto Mode
In Auto mode, operating mode will be selected automatically between Heat and Cool mode,
depending on the Room Temperature and Set Temperature. There is no cold start in auto
mode.
If the present Auto mode is Cool, its mode Set Temperature is the same as the user Set
Temperature. This mode will only change to Heat mode if Tr Ts mode 3.5C or the
compressor has cut out for at least 10 minutes.
If the present Auto mode is heat, its mode set temperature is 1.5C below the user Set
Temperature. This mode will only change to Cool mode if Tr > Ts mode + 3.0C or the
compressor has cut out for at least 10 minutes.
Cool and Heat options working under Auto mode are the same as those working under nonAuto mode.

10

Fan Mode
Only one fan speed is allowed. The compressor and the outdoor fan will stop. Similarly, the
4-way valve will turn off.

11

Defrost Mode
A defrost timer will start counting when the outdoor heat exchange thermostat is below +3C.
Upon crossing over +5C to a higher temperature for more than 150 seconds, the timer will
be reset. The temperature sensing could only be done when the compressor run time is

16

more than 2 minutes. The likelihood of ice frosting at the outdoor coil is characterized by 3
gradients of outdoor temperature shown in the chart below:

Defrost mode will be activated if the compressor run time is:


A = 30 minutes to 1 hour below 3C reference point, if the outdoor coil temperature is -8C for
more than 3 minutes (provided the compressor is on), then the defrost mode can be started.
B = 1 hour to 2 hour below +3C reference point, if the outdoor coil temperature is -4C for more
than 3 minutes (provided the compressor is on), then the defrost mode can be started.
C = more than 2 hour below +3C reference point, if the outdoor coil temperature is -2C for more
than 3 minutes (provided the compressor is on), then the defrost mode can be started. If unit
in outdoor fan forced off mode, the defrost will not be allowed to be declared.
11.1

Defrost cycle
In the defrost cycle, the Heat LED will blink with other LEDs off. Mode selection via the LCD
remote control is acknowledged but the defrost cycle is unaffected until it is completed.
There are two option of defrost cycles:
a)

C2.4 option
This option is selected if a 3k ohm resistor into RMODE.
When defrost starts, the indoor fan, outdoor fan and 4-way valve will cut off while the
compressor remains running.

17

The defrost will terminate if the temperature of outdoor exchange coil exceeds +10C
or a minimum 10 minutes compressor run time is achieved.
At the end of the defrost cycle, the compressor cuts out. The 4-way valve switches
on 15 seconds later. The compressor can cut in 20 second after the 4-way valve has
cut in.
b)

C2.3 option
This option is selected if a 7k5 ohm resistor into RMODE.
When defrost starts, the indoor fan, outdoor fan and compressor will cut out. The 4way valve will cut out 55 seconds later before compressor will cut in 4 seconds
subsequently.
The defrost will terminate if the temperature of outdoor exchange coil exceeds +10C
or a minimum of 10 minutes compressor run time is achieved.
At the end of the defrost cycle, the compressor cuts out. The 4-way valve switches
on 55 seconds later. The compressor can cut in 4 seconds after the 4-way valve has
cut in.

12

Off Mode
When the unit is off, no indication will be provided. All relays will be turned off immediately
after the ON/OFF triggering except the 4-way valve which is subjected to the 55 +/- 5
seconds protection where applicable.

PROTECTIONS
1

Thermostat Minimum off Time


The compressor can only cut in after a minimum period of 3 minutes from the time it cuts off.

Compressor Random Restart


Should the main power cuts out and power resume, the air conditioner will on immediately or
0 64 seconds after power up, depending on the memory backup option and the thermostat
cut in mode.

Thermostat Minimum Run Time


The compressor can only cut out after minimum 150 seconds of running in the current mode.
The compressor can be cut out at any time if the system is switched to other modes or in
any other protection sequences.

Compressor Overload Protection


Coil sensors detection method is used to detect the compressor overload, and is available in
Cool, Dry, Heat and Auto modes.

18

Coil Sensors Detection


This protection is only available in COOL, DRY, HEAT and AUTO modes.
In cooling cycle, when the Outdoor Coil temperature exceeds 75oC, both the compressor
and outdoor fan will stop operating. In heating cycle, when the Indoor Coil temperature
exceeds 75oC, the compressor, outdoor fan and 4WV will stop operating accordingly.
The indoor fan will continue operating as per hot keep.
The unit will auto reset if the temperature goes below 50oC. This is allowed once every
power on reset. If the unit is required to auto reset every time the overload occurs, please
refer to the RGL hardware selection.
If the temperature goes below the permissible limit, the overload protection can be reset
manually by triggering the ON/OFF.

Indoor Anti Freeze


This protection is available in cooling cycle. The system will be in the Frost Prevention Mode
(compressor and outdoor fan turn off) if the Indoor Coil Temperature reaches 1C / 3C and
below for at least 1 minute and compressor has been running for at least 10 minutes.
The compressor and the outdoor fan can only be restarted when the Indoor Coil
Temperature reaches 10C and above for at least 1 minute.

19

Self Diagnostics
Event

CDF LED

Timer LED

Other LEDs

Error Code

Room sensor open or


short

Blink
1 times

--

Blink Fan

Blink E1

Indoor coil sensor


open
Outdoor coil sensor
open
Compressor overload
/ Indoor coil sensor
short / outdoor coil
sensor short

Blink
2 times
Blink
3 times

--

Blink Dry & Fan

Blink E2

--

Blink Dry

Blink E3

--

Blink
1 times

Blink Cool

Blink E4

Gas leak

--

Blink
3 times

Blink Cool & Dry

Blink E5

Outdoor defrost

--

--

--

--

EC
Outdoor coil sensor
exist (MS model)

--

Blink
5 times

Hardware error (tact


switch pin short)

--

Blink
6 times

AP

Blink Cool
Blink Cool
& Sleep &
& Heat &
Heat /
Heat /
Sleep
Sleep
Blink Heat, Cool, follow
by Fan, Dry

Blink E7

Blink E8

* CDF LED = Cool / Dry / Fan LED


8

Compressor 9 minutes force on


If the compressor has stopped for maximum of 9 minutes during Cool mode, the compressor
will be forced to cut in for a minimum of 90 seconds.

Gas Leak Detection


The gas leak is declared if indoor coil temperature is > 25C in cooling cycle or < 20C in
heating cycle. The system will check for gas leak mode if compressor run time of 30 minutes
is achieved by reconfirming the indoor coil temperature for another 5 minutes before
declaring the gas leak mode. No gas leak detection during outdoor defrost.

20

SLM SERIES
The SLM SERIES is a wired wall mounted Light Emitting Diode (LED) display remote controller
used to send instructions to the PCB residing in the air-conditioning units. The built-in infra-red
sensor allows the reception of instructions from AC5300 wireless transmitter.

FEATURES
Hear/Cool/Dry /Fan/Auto Heat-Cool.
Temperature setting ranging from 16oC to 30oC.
Programmable On/Off timer with 1 hour interval.
Sleep function for Cool, Heat and AUTO Heat -Cool modes.
Slim profile with 13.00mm thickness.

SLM LED display Wired Controller

21

Mounting

Wall-mounted using screws.


Concealed or exposed wiring
selection.
Display
7-Segment LED
Temperature Setting
16 C to 30 C
On / Off Timer
15 hours at 1 hours interval
Colour
Light Grey
Casing
Silky matt finished
Default Settings Upon Power Up
Mode
COOL
Temperature Setting
24 C

Error
Room Sensor missing / short
Indoor coil sensor missing / short
Outdoor coil sensor missing / short
Compressor overload
Outdoor abnormal compressor overload trip or gas leak

22

Seven Segments
E1 blinking
E2 blinking
E3 blinking
E4 blinking
E5 blinking

23

SB 125 Controllers (Model 022, 027, 030S, 036S)


SB 125 Control For Cooling Operation
The staring sequence for indoor fan, outdoor fan and compressor is shown as below:

Start

2 seconds
15 seconds

Indoor Fan
Outdoor Fan

2 seconds

Compressor

SB 125 Control For Heating Operation


The staring sequence for indoor fan, outdoor fan and compressor is shown as below:

Start

2 seconds
15 seconds

24

Indoor Fan
Outdoor Fan

2 seconds
2 seconds

All 4-way valves


Compressor

SEQUENTIAL PAC CONTROLLER


The Sequential PAC (Package Air Conditional) is a control system for multi compressor package air
conditioner, used in conjunction with a wired remote control panel. It can balance the loading up to
4 compressors to maximize the life cycle of each component. The sophisticated user interface
offers flexibility for the user to customize operating parameters like specific loading patterns, electric
heaters, event timers, etc. The corresponding main control board is equipped with protection
systems and selection options to suit the local operating conditions. It is designed for ease of
installation and low power consumption, suitable for small to medium capacity air-conditioning units.

FEATURES

Sequential control and balance loading up to 4 stage compressors.


Selectable stage differential temperatures.
Single Speed indoor fan.
7 days programmable timer.
Cool / Heat / Auto / Fan control, ranging from 16C to 30C temperature setting.
Cold blast, Spurt Heat, Hot start and Hot keep.
Wired LCD control panel.
Self-diagnostic feature, error / warning indications.
Compressor high pressure protection.
Compressor trip / low refrigerant warning.
Compressor high temperature protection.
Outdoor defrost cycle in Heat mode.
Indoor antifreeze protection.
Battery backup. If the power fails, a back up battery will maintain the real time clock and the
integrity of the controls data. When power is resumed / switched on again, the unit will
automatically restart using the original settings.

SEQUENTIAL MAIN BOARD (SQMB)


25

SYSTEM OVERVIEW
The control consists of Main Board and Wired LCD Panel (Remote Control).
Main Board

Located in indoor unit.

Functions as stated in this functional specification.

Provides all the control signal to compressors, indoor/outdoor fans, valves, timer and
protection.

Compressor relay will be cut off when compressor high trip, mechanically, even when
controller fails (hang).
Wired LCD Panel (Remote Controller)

Located in the office/control room.

Connected to Main Board.

Let user interface with the air-conditional.

LED to display On/Off and blinking to indicate error.

SYSTEM CONFIGURATION
The wiring diagram for Sequential PAC is shown below:

26

MAIN BOARD

WIRED LCD PANEL (SQLCD CONTROLLER)

ELECTRICAL SPECIFICATIONS
Power Supply
Frequency
Power Input
Relay

Transformer
Fuse
Power Connections

230V AC Nominal
50 / 60 Hz
10 VA Maximum
Compressor Relay and Heater Relay 250V AC 3 A (steady state)
Outdoor Fan Relay 250V AC 5A (steady state)
240 / 10V Nominal 6 VA 50 /60 Hz
3.15A 250 VAC
0.25 Tab Terminal

OPERATING AND RELIABILITY SPECIFICATIONS


Electromagnetic Immunity
The Sequential PAC controller is subjected to the following tests complying with IEC standards:
Test
Electronic Discharge Test (ESD)
Electrical Fast Transient Test (EFT)
Surge Immunity Test
Pulse Magnetic Test
Power Magnetic Test
Power Quality Test

Standard
IEC 1000 4 2
IEC 1000 4 4
IEC 1000 4 5
IEC 1000 4 6
IEC 1000 4 8
IEC 1000 4 11

Application and Environment


Temperature
Relative Humidity

0 C 50 C Operating Temperature
-10 C 85 C Storage Temperature
0 95% non condensing
27

MODEL SELECTION
1

Models / Configuration Available


The models available are:
a)
b)
c)
d)
e)
f)

Auto Mode
Auto Mode can be enabled / disabled using SW5
Auto mode off
Auto mode on

SW5
off
on

Factory preset: SW5 off (Auto mode off)

Number of Heater
SW1 and SW2 are used to set number of Heater. For Heatpump model, they are auxiliary
heaters. For heater model, they are heaters that will turn on in heat mode.
i) No heater (0 heater)
ii) 1 heater
iii) 2 heater

R42
20K
47K
open
1K
3.3K
9.1K

Cooling 2 Compressors.
Cooling 3 Compressors.
Cooling 4 Compressors.
Heat pump 2 Compressors.
Heat pump 3 Compressors.
Heat pump 4 Compressors.

SW1
off
on
off

SW2
off
off
on
Factory preset: SW1 off, SW2 off (no heater)

Stage Differential Temperature


Stage Differential Temperature is the temperature difference from 1 stage compressor to
another stage compressor. The stage differential temperature can be selected from the
range shown below:
SW3 SW4
a) Default
off
off
b) 0.5C
on
off
c) 1.0C
off
on
d) 1.5C
on
on
Factory preset: SW3 off, SW4 off (Default)
*1.5C only valid for 2 and 3 compressor model. For 4 compressor model, maximum allowed
is 1.0C
The default differential temperature is base on number of compressor model, the setting is
as below
Model
2 compressor
3 compressor
4 compressor

28

Differential Temperature
1.5C
1.0C
0.5C

Hot Keep Option


When all the compressors cut out, the indoor fan will run according to indoor coil
temperature. Hot keep can be enabled or disabled via a dip switch.
Fan off
Fan on

SW6
off
on

(follow hot keep condition)

Factory preset: SW6 off (fan off)

Defrost Options
a) Derivative Defrost Option
Derivative Defrost off
Derivative Defrost on

SW7
off
on
Factory preset: SW7 off (Derivative Defrost option off)

b) Defrost Cycle Option


Selects whether compressor will turn off or remain on when 4WV changes at beginning
of defrost cycle.
SW8
off
on

Compressor off
Compressor on
7

Factory preset: SW8 off (compressor off)

EEPROM Backup Option


JH1
close (power on follow last state)
open (power on in off mode)

EEPROM Backup off


EEPROM Backup on

Factory preset: JH1 closed (EEPROM Backup on)


8

Operating Modes
The system has 4 operating modes to select with respect to each model selection :
MODEL
SQCn
SQHnh
SQHnh
SQHTnh
SQHTnh

AUTO
X
X

COOL
X
X
X
X
X

HEAT
X
X
X
X

FAN
X
X
X
X
X

(SW5 off)
(SW5 on)
(SW5 off)
(SW5 on)

Where X denotes modes available.

29

FUNCTIONS
1

Power Up Setting

1.1

Power Up On / Off Setting


The system will power up on or off base on last state where the main supply was cut off for
model where backup memory is enabled (JH1 short) and backup data valid.
Where as the system will always power up in off mode when backup memory is disabled or
backup data corrupted (JH1 open)

1.2

Power Up Setting
a)
With backup memory valid, power up settings will follow settings in the memory
b)
Without backup memory (JH1 open) or backup memory data corrupted, the power up
settings will follow last settings on the LCD panel in condition that the battery on the
LCD panel is functioning. In case where the backup battery on the LCD panel is
weak, the power up setting will be 25C (Cool Mode)

Unit On / Off
There are 2 ways to turn on or off the system:
i ) via On / Off triggering on the LCD panel or on the display panel
On / Off triggering can be achieved by pressing On / Off key on the wired controller or on
the display panel. Pressing the On / Off will toggle the system either from On to Off or
from Off to On
ii) via 7 days timer
There are two 7 days programmable timers namely On Timer and Off Timer. This timer
can be overridden by the On / Off pressing.

Off Mode
When the unit is off, the on / off LED on the LCD panel will be off. All relays will be turned off
immediately after the ON/OFF triggering except the 4-way valves, and indoor fan which are
subjected to protection where applicable.

Temperature Range and Setting


The operating temperature range is 61F to 86F (16C to 30C) both inclusive. Temperature
settings are determined by the wired controller setting or default setting during power up.
The temperature setting is only effective under Cool, Heat and Auto modes.

Indoor Fan Speed


There is one indoor fan with single fan speed.

Cold Start
When the unit restart 2 hours after it has stopped or during power-on-reset start, it is
considered a cold start.

30

COOL MODE
a)
Cold Blast
During cold start, the working Set Temperature is set to User Set Temperature -2C
(cold blast). This will remain until the compressor has cut off or has run for at least 20
minutes. After that, the working Set Temp is reset back to the user Set Temp. This
feature is not available if Energy Saving is set or in Auto mode
b)

Sequential Control
The staring sequence for indoor fan, outdoor fan and compressor is shown as below:
For model 030D, 036D, 044, 054, 060, 072, 108, 125, 145

Start

2 seconds
15 seconds
15 seconds

Indoor Fan
Outdoor Fan 1
Outdoor Fan 2

2 seconds
2 seconds

Compressor 1
Compressor 2

For model 088 (Tandem System)

Start

2 seconds
15 seconds
15 seconds

Indoor Fan
Outdoor Fan 1
Outdoor Fan 2

2 seconds
2 seconds

Compressor 1
Compressor 3

30 seconds
30 seconds

Compressor 2
Compressor 4

For model 175 (Tandem System)

Start

2 seconds
15 seconds
15 seconds

Indoor Fan
Outdoor Fan 1&2
Outdoor Fan 3&4

2 seconds
2 seconds

Compressor 1
Compressor 3

30 seconds
30 seconds

Compressor 2
Compressor 4

The compressor will be turned on one by one depending on the on / off conditions shown is figure
below. There is a 15s interval (stage timer) between 2 compressors turn on sequence. When a
compressor is turned on its running time is recorded on its run time counter. When it is off the
counter is stop.

31

Balance Loading
When a compressor needs to be on, the controller will turn on the compressor with the shortest
accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the system
will apply the same principle to the subsequent compressor. Similarly, the compressor with the
longest accumulated run time will be the first one to be cut off. This is to load the entire compressor
evenly over long run period.
i ) 0.5C differential temperature

Troom C
Ts+1.0
Ts+0.5
Ts

2 comp. on
1 comp. on

Ts-0.5
Ts-1.0

1.0C
1 comp. off

All comp. off

ii ) 1.0C differential temperature

Troom C
Ts+2.0
Ts+1.0
Ts
Ts-1.0

2 comp. on
1.0C

1 comp. on
1 comp. off
All comp. off

iii) 1.5C differential temperature

Troom C
2 comp. on

Ts+1.5

1.0C

Ts+1.0
Ts+0.5
Ts

1 comp. on

Ts-0.5
Ts-1.0
32

All comp. off

1 comp. off

HEAT MODE (HEATPUMP MODEL)


a)
Spurt Heat
During cold start, the working Set Temperature is set to User Set Temperature +2C.
This will remain until the compressor has cut off or has run for at least 20 minutes.
After that, the working Set Temp is reset back to the user Set Temp. This feature is
not available if Energy Saving is set or in Auto mode

b)

Sequential Control
The staring sequence for indoor fan, outdoor fan and compressor is shown as below:
For model 030D, 036D, 044, 054, 060, 072, 108, 125, 145

Start

2 seconds
15 seconds
15 seconds

Indoor Fan
Outdoor Fan 1
Outdoor Fan 2

2 seconds

2 seconds
2 seconds

All 4-way valves


Compressor 1
Compressor 2

For model 088 (Tandem System)

Start

2 seconds
15 seconds
15 seconds

Indoor Fan

2 seconds

All 4-way valves

2 seconds

Outdoor Fan 1

2 seconds

Outdoor Fan 2

Compressor 1
Compressor 3

30 seconds
30 seconds

Compressor 2
Compressor 4

For model 175 (Tandem System)

Start

2 seconds
15 seconds
15 seconds

Indoor Fan

2 seconds

Outdoor Fan 1&2


Outdoor Fan 3&4

All 4-way valves

2 seconds
2 seconds

Compressor 1
Compressor 3

30 seconds
30 seconds

Compressor 2
Compressor 4

+ Indoor fan may not turn on due to hot keep, then if condition permits, indoor fan will turn on 2s
after 4WV turns on, or 2s after any compressor turns on.
The compressor will be turned on one by one depending on the on / off conditions shown is figure
below. There is a 15s interval (stage timer) between 2 compressors turn on sequence. When a
compressor is turned on its running time is recorded on its run time counter. When it is off the
counter is stop.

33

Balance Loading
When a compressor needs to be on, the controller will turn on the compressor with the shortest
accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the system
will apply the same principle to the subsequent compressor. Similarly, the compressor with the
longest accumulated run time will be the first one to be cut off. This is to load the entire compressor
evenly over long run period.
i ) 0.5C differential temperature

Troom C

Ts+0.5

2 comp. on
1 comp. on

Ts
Ts-0.5
Ts-1.0

1.0C

1 comp. off
All comp. off

ii ) 1.0C differential temperature

Troom C
Ts+2.0
Ts+1.0
Ts
Ts-1.0

2 comp. on
1 comp. on
1 comp. off

1.0C
All comp. off

iii) 1.5C differential temperature

Troom C
Ts+1.5

2 comp. on

Ts+1.0
Ts+0.5

1 comp. off

1 comp. on

Ts

1.0C

Ts-0.5
34

Ts-1.0

All comp. off

Hot Start
When at least 1 compressor cuts in, the indoor fan will run according to indoor coil
temperature:
i ) if any of the indoor coil temperature 30C, the indoor fan will run.
ii) if all the indoor coil temperature 15C, the indoor fan will stop.

10

Hot Keep
When all the compressors cut out, the indoor fan will run according to indoor coil
temperature:
i ) if any of the indoor coil temperature 40C, the indoor fan will run.
ii) if all the indoor coil temperature 15C, the indoor fan will stop.
Hot keep can be enabled or disabled via a dip switch. When fan off is selected, indoor fan
will stop when all compressor cut off.

11

4 Way Valve Changing


To run heat pump, all the 4 way valve will be ON. Upon return to non-heat pump mode, all
the 4 way valves will be turned off. A 4-way valve can only be changed 555 seconds after
the compressor has been cut out, then the compressor may be cut in 4 second later. When
the 4-way valve has been changed and the compressor has not been cut in, the 4-way valve
may still be changed again immediately.

12

Energy Saving Function


In order to save energy, the set temperature will increase or decrease with time.

Troom C
Ts+2
Ts+1
t (hr)

Ts
1

Energy Saving off

Energy Saving on
Cool Mode Energy Saving profile

35

Energy Saving off

Energy Saving on
Troom C Ts+2

t (hr)

Ts+1
Ts

Heat Mode Energy Saving Profile


The option is only available for Cool, Heat and Auto modes. Changing to other modes will
inhibit the Energy saving option and the timer will reset. A changeover within Cool (or Auto
Cool) and Heat (or Auto Heat) mode will reset the timer.
13

Auto Mode
In Auto Mode, operating mode will be selected automatically between Heat and Cool mode,
depending on the Room Temperature and Set Temperature. There is no cold start and
spurt heat in Auto Mode.
If present Auto mode is Cool, this mode will only change to Heat mode if:
i)
ii)

Tr <= Ts 2.5oC AND


all the compressors have cut out for at least 15 minutes.

If the present Auto mode is heat, this mode will only change to Cool mode if:
i)
ii)

Tr >=Ts + 2.5oC AND


All the compressors (or heaters) have cut out for at least 15 minutes.

Cool and Heat options working under Auto mode are the same as those working under nonAuto mode. Compressor on/off condition (Heatpump Model) is shown in Figure 1.

36

i ) 0.5C differential temperature

Troom C
Ts+2.5
Ts+2.0

2 comp. on

Ts+1.5

1 comp. on

Ts+1.0
Ts+0.5
Ts
Ts-0.5

Cooling

all comp. off

1 comp. off

all comp. off

1 comp. off

Ts-1.0

Heating

1 comp. on

Ts-1.5

2 comp. on

Ts-2.0
Ts-2.5

ii ) 1.0C differential temperature

Troom C
Ts+4.0
Ts+3.0
Ts+2.0
Ts+1.0
Ts
Ts-1.0
Ts-2.0
Ts-3.5

2 comp. on
1 comp. on

Cooling

all comp. off

1 comp. off

all comp. off

1 comp. off

1 comp. off

Heating
2 comp. on

Ts-4.0

37

iii ) 1.5C differential temperature

Troom C
Ts+4.0
Ts+3.0

2 comp. on

Ts+2.5
Ts+1.5
Ts+1.0
Ts
Ts-1.0
Ts-1.5
Ts-2.5
Ts-3.0

Cooling
1 comp. on

1 comp. off

all comp. off


all comp. off
1 comp. on

1 comp. off
Heating
2 comp. on

Ts-4.0

14

Test Run Function


The test run function will enable all the compressors and heaters to turn on irrespective of
the set and room temperatures.

15

Key Lock Function


The key lock function is for preventing unauthorized changing of the units operating settings.

PROTECTION
1

5 minute Minimum Run Time for compressor


For thermostat cycles, a compressor can only cut out after running 5 minutes in the current
mode. The compressor can be cut out at any time if the system is switched to other modes.

3 -Minute Minimum Off Time for Compressor


For thermostat cycles, a compressor can only cut out in after 3 minutes from the time it cuts
off except during 4-way valve changeover sequence where it can cut in 5 seconds after 4way valve changeover.

38

Compressor High Pressure Protection


If any of the compressors has high pressure trip, error code will be indicated on LCD. The
compressor is not allowed to cut in for 3 minutes (error code will be shown for 3 minutes). If
the compressor has high pressure trip for 3 times in 30 minutes, it cannot be restart
automatically. (Only can be reset by triggering the on / off button).

Compressor High Temperature Protection


a)
Cool and Auto Cool modes
When the Outdoor Coil Temperature for a particular compressor exceeds 68C, the
compressor and its outdoor fan will stop operating. Other compressor will perform
thermostat cycle as usual. The indoor fan will still continue to run even if the entire
compressors are cut off due to high temperature protection.
b)

Heat and Auto Heat modes


When the Indoor Coil Temperature for a particular compressor exceeds 59C, the
outdoor fan will stop. When the Indoor Coil Temperature for a particular compressor
exceeds 62C, the compressor and its outdoor fan will stop operating. Other
compressor will perform thermostat cycle as usual. The indoor fan will still continue
to run but subject to hot keep condition, if all the entire compressors are cut off due
to high temperature protection.
When any compressor for a particular model cut off due to high temperature, and
there is at least one compressor is running as usual, the compressor that cut off can
be turned on when its temperature falls below 55C. Outdoor fan can be turned on
when temperature falls below 50C.
If all the compressor were cut off due to high temperature protection, the system can
only be reset manually by triggering the On / Off button. If the system is not reset, the
compressor cannot restart.

Compressor Trip / Low Refrigerant Warning


A compressor is said to be tripped or low refrigerant if the conditions below suspected:
a)
b)

Cool and Auto Cool modes


After minimum run time of 5 minutes.
Tr Tincoil - 3C (i.e. indoor coil not cold enough)
Heat and Auto Heat modes
After minimum run time of 5 minutes.
Tincoil - Tr - 3C (i.e. indoor coil not hot enough)

When a compressor has low refrigerant, the LCD panel will blink, the error code will be
shown. However the compressor is not stopped. Once the error is cleared, the LCD display
resumes as normal.

39

Indoor Antifreeze Protection and Filter Check


This protection is only available in Cool modes. A compressor will enter Antifreeze mode if :

Its Indoor Coil Temp. reaches 1C and below for at least 1 minute.
The compressor has run for at least 10 minutes.

Upon confirmation of indoor freeze up, the compressor and the outdoor fan will cut out.
Other compressor will run as usual. The compressor and its outdoor fan can only be
restated when
After a minimum stop time of 3 minutes
The indoor coil temp reaches 12C and above for at least 1 minute.
Another mode of operation is selected.
7

Outdoor Defrost
Defrost mode can only be entered from heat mode. A defrost timer will start counting when
any of the outdoor coil temperature is below 13C. Upon crossing over 13C to a higher
temperature for more than 150 seconds, the timer will be reset (this timer also reset after the
defrost mode). This temperature sensing could only be done when the compressor run time
is more than 2 minutes (except for defrost termination)

7.1

Conventional Defrost Condition


Defrost condition depends on the accumulated compressor run time and characterized by 3
gradients of outdoor temperature.

Defrost mode will be activated if the compressor run time is:


40

A = 30 minutes to 1 hour below 3C reference point, if the outdoor coil temperature is 8C for more than 3 minutes (provided the compressor is on), then the defrost mode
can be started.
B = 1 hour to 2 hour below +3C reference point, if the outdoor coil temperature is -4C for
more than 3 minutes (provided the compressor is on), then the defrost mode can be
started.
C = more than 2 hour below +3C reference point, if the outdoor coil temperature is -2C
for more than 3 minutes (provided the compressor is on), then the defrost mode can
be started. If unit in outdoor fan forced off mode, the defrost will not be allowed to be
declared.

7.2

Derivative Defrost Condition


Derivative defrost condition is enabled by turning on SW7. When enabled it is added as an
add on condition with conventional defrost condition. Only when this two condition are meet
the compressor can enter defrost mode.
The indoor and room temperature is monitor after 5 minutes compressor running. Then
T-T1-Tincoil is recorded all the time. T maximum is found as Tincoil
The condition of frosting is defined as:
T/ Tmax <= 85%
Tmax for a compressor is reset when a defrost operation terminates.

7.3

Alternative Defrost cycle


Only ONE compressor can enter defrost mode at one time. If more than 2 compressors
fulfill defrost condition, the compressor with maximum accumulated run time will enter
defrost cycle.
Pre Defrost Cycle
When one compressor is confirmed to run defrost cycle, one compressor will turn on for 2
minutes before the specific compressor enters defrost cycle. If no compressor can be
turned on in 2 minute, defrost cycle will still be running. If no other compressor run heat
mode and one compressor running defrost, indoor fan will turn off irrespective of hot keep
and hot start conditions except when heater is on.
Defrost Cycle
After 2 minutes pre defrost cycle, depends on defrost option set by SW8, for compressor on
option, outdoor fan and 4 way valve will cut off and the compressor runs defrost cycle.
For compressor off option, the compressor and its outdoor fan will be cut out, then 55
seconds later its 4-way valve switches OFF. Then 4 seconds later the compressor will turn
on with its outdoor fan off.

41

The other compressors will perform thermostat cycle operation as usual with both indoor
and outdoor fans on.
The compressor that runs defrost cycle is consider running cool cycle, therefore one
compressor will be forced on in heat cycle (if available) to cancel the cooling effect. For
example if current Tr Ts condition requires 1 compressor to run heat mode, then the
situation is : 1 compressor runs defrost cycle (cool). 2 compressor run heat cycle and so on.
Terminate Defrost Cycle
The compressor then runs with its outdoor fan off until temperature of its outdoor coil
exceeds + 10oC or a minimum of 10 minutes compressor run time is achieved (if
compressor that runs defrost trip, its defrost cycle ends), after that the compressor will be
stopped, and the defrost cycle is completed. Then 55 seconds later 4-way valve switches
on where the Heat cycle can continue to run (compressor can cut in 5 seconds)
C2.4 option : At the end of the defrost cycle, the compressor cuts out. Then 4-way valve
switches on 15 +/-5 seconds later. The compressor can cut in 20 seconds time.
The poor contact conditions of the room, indoor coil & outdoor coil thermistors are indicated
via the wired control panel using error code on the I.C.D. For indoor coil and outdoor coil
sensors, the error is indicated if any of the sensors is open or close.
SENSOR

ERROR CONDITIONS

i)

INDOOR COIL

<-44oC FOR > 2 SECS OR


>76oC FOR > 2 SECS OR
OPEN OR CLOSE

ii)

OUTDOOR COIL

<-44oC FOR > 2 SECS OR


>76oC FOR > 2 SECS OR
OPEN OR CLOSE

iii)

ROOM

<-33oC OR
>50oC OR
OPEN OR CLOSE

When either of the above faults is confirmed, the system will run as normal. The
compressor and outdoor fan related to the error means sensor cannot be turned on. If
either of the above faults is confirmed rectified, the respective error code is cleared
8

Compressor Status Display


Compressor on / off / fault
The active compressor number is shown in the LCD. When a compressor is faulty, this
number will blink.

42

Defrost
When a compressor performs defrost cycle, the defrost number is shown in the LCD.
9

Error
Code
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10
E11
E12
E13
E14
E15
E16
E17
E18

Error and Display


Error code is displayed on the LCD panel. When system on and error code is shown, the on
/ off LED on the LCD panel will blink. When system off, error code is still display for
thermistor error but the on / off LED will be off.
Description
Require manual reset
Compressor 1 high temperature (overload)
Compressor 2 high temperature (overload)
Compressor 3 high temperature (overload)
Compressor 4 high temperature (overload)
Compressor 1 high pressure trip (or contact open)
Compressor 2 high pressure trip (or contact open)
Compressor 3 high pressure trip (or contact open)
Compressor 4 high pressure trip (or contact open)
Compressor 1 trip (or low refrigerant)
Compressor 2 trip (or low refrigerant)
Compressor 3 trip (or low refrigerant)
Compressor 4 trip (or low refrigerant)
Room sensor short
Room sensor open
Indoor coil sensor 1 short
Indoor coil sensor 2 short
Indoor coil sensor 3 short

Error
Code
E19
E20
E21
E22
E23
E24
E25
E26
E27
E28
E29
E30
E31
E32
E33
E34
E35

Description
Indoor coil sensor 4 short
Indoor coil sensor 1 open
Indoor coil sensor 2 open
Indoor coil sensor 3 open
Indoor coil sensor 4 open
Outdoor coil sensor 1 short
Outdoor coil sensor 2 short
Outdoor coil sensor 3 short
Outdoor coil sensor 4 short
Outdoor coil sensor 1 open
Outdoor coil sensor 2 open
Outdoor coil sensor 3 open
Outdoor coil sensor 4 open
Compressor 1 deice
Compressor 2 deice
Compressor 3 deice
Compressor 4 deice

43

SQLCD CONTROLLER
This is a wall mounted or unit mounted wired control panel that connected to multi compressor
package air conditioners main board.

FEATURES

Cool/Heat/Fan/Dry/Auto modes.
Single fan speed (High speed).
Set temperature in C or F.
Save function
Test run function for easy installation.7 days programmable timer (option).
Compressors Run/Error status.
Compressors Defrost status.
Heater enable control.
Error indicator.
Keylock function to prevent setting change by unauthorized personnel.
Battery backup. In the event of a power failure a back up battery will maintain the real
time clock and the integrity of the controls data. When power is resumed
(returned/switched on again), the unit will automatically restart using the original settings.

SQLCD CONTROLLER

44

SPECIFICATIONS

* All dimensions are in mm.


OUTLOOK
Mounting
Display
Color

Wall mounted for concealed wiring.


LCD
Milky White

45

DISPLAY & OPERATION

A
B
C
D
E
F
G
H
I
J
K

46

= [Current / Start / Ending Time] Display


= Operation mode Display the status of operation
= [Checking] Display Indication when abnormality occurs in the unit.
= [Set temperature] Display Display the set temperature
= [C or F] Display Display the temperature in C or F.
= [Operation] Lamp Light up: in operation, Light off: unit stops.
= [Fan speed] Display Displays High fan speed.
= [Key lock] Display Display indicates when key lock function is activated.
= [Compressor] Display Display the number of compressor is running.
= [Heater] Display Display the number of heater is running.
= [Defrost] Display Display the number of outdoor defrosts is running.

ON /OFF

ON/OFF button

Operating lamp

Start an operation
Press the [ON/OFF] button. Operation lamp light up and operation starts.
Stop an operation
Press the [ON/OFF] button again. Operation lamp goes off and operation stops.
Once setting has been done, pressing [ON/OFF] button will repeat the same operation
thereafter.
Operation lamp beside the [ON/OFF] button lights up during operation.
Caution:
Even if the operation button is pressed immediately after the operation is once stopped,
operation is not resume-able within 3 minutes.
Operation will automatically starts after lapse of approximately 3 minutes.
This is a protection feature incorporated in the controller.

47

Operation selection and Room temperature adjustment

1 = Mode Button
Consecutive press the [MODE] button to switch operation among FAN, COOL, HEAT,
AUTO. For contents of operation, check the display.

2 = Press the room temperature button and set the room temperature of your choice. By pressing
the

or

once, temperature changes by 1 C.

Indoor temperature can be set within the following range:


Cooling 19 ~ 30 C
Heating 17 ~ 28 C
During fan mode, temperature cannot be set.
Normally the panel will show room temperature
= Press
and vise-versa.

48

and

together, the unit of temperature will change from C to F

Time Setting

= Current time display

= Timer hold / Resume display

Clock key
Press the key once, set clock mode activated.
Press the key again, set clock mode disable.

1
2

to

Under set clock mode, real time clock and present


day setting can be changed by pressing Day key,
Hour key or Minute key.

7-Days timer key

6
2

to

Two keys are available ON Timer and OFF Timer.


ON Timer key pressed, set timer mode activated.
OFF Timer key pressed, set timer mode disabled
Under set timer mode, pressing Day key, Hour key
or Minute key, 7-days timer setting can be changed.

Day key
During set clock mode or set timer mode, press the key will change the Day setting.
Hour key
During set clock mode or set timer mode, press the key will change the Hour setting.
49

Minute key
During set clock mode or set timer mode, press the key will change the Minute setting.

Timer Hold/Resume key


If 7-days timer is set, the word Timer Active will be
displayed.
To clear the entire timer setting, press and hold the key
until the word Timer Active is not displayed. To resume
the timer setting after timers have been held, press and
hold the key until the word Timer Active is displayed.

Other function

2
3
4
50

Key lock
Protection feature. The purpose is to avoid mischief of children
etc.
To activate, press the Minute key three times consecutively,
Key Lock symbol will appear on LCD screen.
At this time, only On-Off key is valid.
To cancel this feature, press the Minute key three times
consecutively again.
Test Run
If the TEST RUN key is pressed twice consecutively, the unit
will run and finished automatically after two hours.
Save
Energy saving function
Heater
Selectable up to 2 heaters

FEATURES
1

Save Function
To activate Save function, press the SAVE key once. To disable Save function, press
the SAVE key once again.

Test Run Function


Test Run function is available in Cool and Heat modes. To activate Test run function,
press the TEST RUN key twice. TEST RUN symbol is turned on with COOL or HEAT
symbol blinking. The function will last for 2 hours and could be manually disabled by
pressing ON/OFF key once.

Real Time Clock


Press the CLOCK key one time will activate set clock mode. Press the CLOCK key
again will disable set clock mode.
Under set clock mode, a word SET CLOCK on LCD will blink at 0.5 seconds interval
and the real time clock and day setting can be changed by pressing DAY key, HOUR
key or MINUTE key.

Seven Days Programmable Timer (On Timer and Off Timer)


Press the timer key once will activate set timer mode. Under set timer mode, a word
SET TIMER on LCD will blink at 0.5 seconds interval and the timer setting can be
changed by pressing the DAY key, HOUR key or MINUTE key.
Whenever there is any timer setting in the program, the LCD displays a word TIMER
ACTIVE. To deactivate the timers setting temporary, press the HOLD key for 2-3
seconds until the word TIMER ACTIVE disappears. To recall back the timer setting,
press the HOLD key again for 2-3 seconds or press once the timer key. The word
TIMER ACTIVE will appear.

Keylock Function
The controller has a keylock function to prevent unauthorized changing of the units
operating settings. Press the MINUTE key 3 times consecutively will activate the keylock
function. KEYLOCK symbol will turn on. Upon keylock, all key pressing except ON/OFF
and FAN keys will be ignored. To cancel the keylock function, press the MINUTE key 3
times consecutively, symbol KEYLOCK will disappear.

51

52

YRM 011 R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1270 CFM 600.4L/S
INDOOR COIL
ENTERING AIR
DB
F
70
72
74
76
78
80
82
84
74
76
78
80
82
84
86
88
80
82
84
86
88
90
92
94

WB
F

60

67

74

75
TC
KW
11.31
11.27
11.22
11.2
11.17
11.25
11.33
11.57
12.82
12.82
12.82
12.82
12.82
12.83
12.85
12.87
14.4
14.4
14.41
14.41
14.41
14.41
14.42
14.42

SC
KW
7.38
8.17
8.99
9.66
10.38
10.85
11.33
11.57
6.87
7.48
8.1
8.72
9.31
9.9
10.49
11.02
6.38
6.99
7.61
8.22
8.84
9.45
10.07
10.69

85
PI
KW
2.16
2.15
2.15
2.15
2.14
2.16
2.17
2.2
2.35
2.35
2.35
2.35
2.35
2.35
2.35
2.36
2.54
2.54
2.54
2.54
2.54
2.54
2.54
2.54

EER
17.88
17.85
17.82
17.8
17.78
17.82
17.85
17.97
18.62
18.62
18.62
18.62
18.62
18.63
18.63
18.63
19.32
19.32
19.32
19.33
19.33
19.33
19.33
19.33

TC
KW
10.85
10.82
10.78
10.78
10.77
10.86
10.95
11.18
12.29
12.29
12.29
12.29
12.3
12.31
12.34
12.37
13.83
13.83
13.84
13.84
13.84
13.84
13.84
13.84

SC
KW
7.3
8.04
8.8
9.41
10.07
10.51
10.95
11.18
6.69
7.32
7.95
8.58
9.17
9.73
10.29
10.79
6.15
6.77
7.38
7.99
8.6
9.21
9.83
10.44

PI
KW
2.66
2.66
2.65
2.65
2.65
2.66
2.68
2.7
2.83
2.83
2.83
2.83
2.83
2.83
2.84
2.84
3.01
3.01
3.01
3.01
3.01
3.01
3.01
3.01

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
115
EER TC
SC
PI
EER TC
SC
PI
EER TC
SC
PI
KW KW KW
KW KW KW
KW KW KW
13.91 10.42 7.21 3.13 11.36 9.96 7.1 3.62 9.38 9.5 6.97 4.13
13.88 10.4 7.9 3.13 11.34 9.95 7.73 3.62 9.38 9.5 7.55 4.13
13.86 10.38 8.61 3.12 11.33 9.95 8.39 3.62 9.37 9.51 8.16 4.13
13.86 10.39 9.17 3.13 11.34 9.97 8.91 3.62 9.39 9.55 8.64 4.13
13.85 10.39 9.78 3.13 11.34 10
9.47 3.63 9.4 9.59 9.14 4.14
13.9 10.49 10.19 3.14 11.41 10.1 9.84 3.64 9.47 9.71 9.49 4.15
13.96 10.59 10.59 3.15 11.47 10.21 10.21 3.65 9.54 9.83 9.83 4.17
14.11 10.82 10.82 3.18 11.62 10.43 10.43 3.68 9.68 10.04 10.04 4.19
14.81 11.79 6.51 3.29 12.23 11.26 6.32 3.77 10.19 10.72 6.12 4.26
14.81 11.79 7.16 3.29 12.23 11.26 6.97 3.77 10.19 10.73 6.77 4.26
14.81 11.79 7.79 3.29 12.23 11.26 7.61 3.77 10.19 10.73 7.42 4.26
14.81 11.79 8.44 3.29 12.23 11.26 8.26 3.77 10.19 10.73 8.07 4.26
14.81 11.8 9.01 3.29 12.23 11.28 8.83 3.77 10.2 10.75 8.62 4.26
14.82 11.82 9.55 3.29 12.25 11.31 9.34 3.78 10.22 10.79 9.11 4.27
14.84 11.85 10.09 3.3 12.27 11.34 9.85 3.78 10.24 10.83 9.6 4.27
14.85 11.89 10.56 3.3 12.29 11.4 10.3 3.79 10.27 10.89 10.02 4.28
15.69 13.28 5.93 3.46 13.11 12.7 5.7 3.93 11.03 12.12 5.47 4.4
15.69 13.28 6.54 3.46 13.1 12.7 6.3 3.93 11.03 12.12 6.06 4.4
15.69 13.28 7.15 3.46 13.11 12.7 6.9 3.93 11.03 12.12 6.65 4.4
15.69 13.29 7.76 3.46 13.11 12.71 7.5 3.93 11.03 12.12 7.24 4.4
15.7 13.29 8.36 3.46 13.11 12.71 8.1 3.93 11.04 12.13 7.83 4.4
15.7 13.29 8.97 3.46 13.11 12.71 8.7 3.93 11.04 12.13 8.42 4.4
15.7 13.29 9.58 3.46 13.11 12.71 9.3 3.93 11.04 12.13 9.01 4.4
15.7 13.29 10.19 3.46 13.11 12.71 9.9 3.93 11.04 12.13 9.61 4.4

125
EER
7.85
7.85
7.85
7.88
7.9
7.98
8.05
8.18
8.59
8.59
8.59
8.59
8.6
8.63
8.65
8.69
9.4
9.39
9.4
9.4
9.4
9.4
9.4
9.4

TC
KW
9.04
9.06
9.08
9.14
9.19
9.32
9.45
9.67
10.21
10.21
10.21
10.21
10.24
10.28
10.33
10.4
11.56
11.56
11.57
11.57
11.57
11.57
11.57
11.57

SC
KW
6.82
7.36
7.92
8.36
8.82
9.14
9.45
9.67
5.91
6.56
7.21
7.86
8.4
8.87
9.34
9.73
5.24
5.82
6.4
6.98
7.56
8.14
8.73
9.31

PI
KW
4.62
4.62
4.63
4.63
4.64
4.65
4.66
4.68
4.73
4.73
4.73
4.73
4.73
4.74
4.74
4.75
4.85
4.85
4.85
4.85
4.85
4.85
4.85
4.85

EER
6.68
6.69
6.7
6.73
6.76
6.84
6.92
7.04
7.36
7.36
7.36
7.37
7.38
7.4
7.43
7.47
8.13
8.13
8.13
8.13
8.14
8.14
8.13
8.13

YRM 011 R407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1270cfm 600.4L/S
INDOOR COIL
ENTERING AIR
DB
F
70
72
74
76
78
80
82
84
74
76
78
80
82
84
86
88
80
82
84
86
88
90
92
94

53

WB
F

60

67

74

75
TC
KW
11.17
11.13
11.08
11.07
11.05
11.14
11.22
11.47
12.75
12.75
12.75
12.75
12.75
12.77
12.78
12.81
14.42
14.42
14.42
14.42
14.43
14.43
14.43
14.43

SC
KW
7.36
8.13
8.94
9.58
10.29
10.75
11.22
11.47
6.84
7.46
8.08
8.7
9.3
9.88
10.46
11
6.38
7
7.61
8.23
8.85
9.46
10.08
10.7

85
PI
KW
2.17
2.17
2.17
2.17
2.16
2.17
2.18
2.2
2.32
2.32
2.32
2.32
2.32
2.32
2.32
2.33
2.47
2.47
2.47
2.47
2.47
2.47
2.47
2.47

EER
17.53
17.49
17.45
17.44
17.42
17.49
17.56
17.76
18.75
18.75
18.75
18.75
18.75
18.76
18.77
18.79
19.89
19.89
19.9
19.9
19.9
19.9
19.9
19.9

TC
KW
10.68
10.65
10.62
10.63
10.62
10.72
10.82
11.06
12.18
12.19
12.19
12.19
12.2
12.22
12.24
12.28
13.81
13.8
13.81
13.81
13.82
13.82
13.82
13.82

SC
KW
7.27
7.98
8.73
9.32
9.96
10.39
10.82
11.06
6.65
7.29
7.92
8.55
9.14
9.69
10.25
10.75
6.14
6.75
7.37
7.98
8.59
9.2
9.82
10.43

PI
KW
2.66
2.66
2.66
2.66
2.66
2.67
2.68
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.81
2.94
2.94
2.94
2.94
2.94
2.94
2.94
2.94

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
EER TC
SC
PI
EER TC
SC
PI
EER TC
KW KW KW
KW KW KW
KW
13.68 10.23 7.17 3.12 11.19 9.75 7.04 3.6 9.25 9.25
13.66 10.21 7.83 3.12 11.18 9.74 7.65 3.6 9.24 9.27
13.63 10.19 8.52 3.11 11.17 9.74 8.29 3.6 9.24 9.28
13.64 10.21 9.06 3.12 11.18 9.78 8.78 3.6 9.27 9.33
13.63 10.23 9.65 3.12 11.19 9.81 9.32 3.6 9.29 9.38
13.71 10.33 10.05 3.13 11.27 9.93 9.69 3.61 9.37 9.51
13.79 10.44 10.44 3.14 11.36 10.05 10.05 3.63 9.46 9.64
13.99 10.68 10.68 3.16 11.53 10.28 10.28 3.65 9.61 9.86
14.86 11.65 6.47 3.25 12.23 11.09 6.26 3.73 10.16 10.52
14.86 11.65 7.11 3.25 12.23 11.09 6.91 3.73 10.16 10.53
14.86 11.65 7.75 3.25 12.23 11.09 7.55 3.73 10.16 10.53
14.86 11.65 8.39 3.25 12.23 11.09 8.21 3.73 10.16 10.53
14.87 11.67 8.97 3.25 12.24 11.11 8.77 3.73 10.17 10.55
14.88 11.69 9.5 3.25 12.26 11.15 9.27 3.73 10.19 10.59
14.9 11.73 10.03 3.26 12.28 11.18 9.78 3.73 10.22 10.64
14.93 11.77 10.5 3.26 12.32 11.24 10.22 3.74 10.26 10.7
16.02 13.21 5.91 3.39 13.29 12.59 5.66 3.87 11.11 11.97
16.01 13.21 6.51 3.39 13.28 12.59 6.26 3.87 11.11 11.97
16.02 13.22 7.12 3.39 13.29 12.6 6.86 3.87 11.11 11.97
16.02 13.22 7.73 3.39 13.29 12.6 7.45 3.87 11.11 11.98
16.02 13.22 8.33 3.39 13.29 12.6 8.05 3.87 11.12 11.98
16.02 13.22 8.94 3.39 13.29 12.6 8.65 3.87 11.12 11.98
16.02 13.22 9.55 3.39 13.29 12.6 9.25 3.87 11.12 11.98
16.02 13.22 10.15 3.39 13.29 12.6 9.85 3.87 11.12 11.98

115
SC
KW
6.89
7.45
8.04
8.49
8.97
9.31
9.64
9.86
6.04
6.69
7.34
7.99
8.54
9.02
9.5
9.91
5.41
5.99
6.58
7.17
7.76
8.35
8.94
9.53

PI
KW
4.09
4.09
4.09
4.09
4.1
4.11
4.12
4.15
4.21
4.21
4.21
4.21
4.21
4.21
4.22
4.22
4.34
4.34
4.34
4.34
4.34
4.34
4.34
4.34

125
EER
7.73
7.73
7.74
7.77
7.81
7.89
7.98
8.12
8.53
8.53
8.54
8.54
8.55
8.57
8.6
8.65
9.41
9.4
9.41
9.41
9.41
9.41
9.41
9.41

TC
KW
8.77
8.8
8.83
8.89
8.96
9.1
9.25
9.46
9.97
9.98
9.98
9.98
10
10.05
10.1
10.19
11.38
11.37
11.38
11.38
11.38
11.39
11.38
11.38

SC
KW
6.72
7.24
7.78
8.19
8.63
8.94
9.25
9.46
5.81
6.46
7.11
7.76
8.3
8.75
9.21
9.6
5.16
5.74
6.32
6.89
7.47
8.05
8.63
9.2

PI
KW
4.57
4.57
4.57
4.58
4.58
4.6
4.61
4.63
4.67
4.67
4.67
4.67
4.68
4.68
4.69
4.69
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

EER
6.56
6.57
6.59
6.63
6.67
6.75
6.84
6.98
7.28
7.28
7.28
7.28
7.3
7.33
7.36
7.4
8.09
8.09
8.09
8.09
8.09
8.09
8.09
8.09

54

YRM 014 R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1670CFM 789.6 l/s
INDOOR COIL
ENTERING AIR
DB
F
70
72
74
76
78
80
82
84
74
76
78
80
82
84
86
88
80
82
84
86
88
90
92
94

WB
F

60

67

74

75
TC
KW
13.56
13.51
13.48
13.48
13.51
13.6
13.89
14.18
15.29
15.3
15.3
15.3
15.32
15.34
15.39
15.44
17.18
17.19
17.2
17.19
17.19
17.2
17.2
17.21

SC
KW
9.39
10.39
11.34
12.19
12.93
13.6
13.89
14.18
8.44
9.28
10.12
10.96
11.71
12.47
13.2
13.85
7.76
8.58
9.4
10.22
11.04
11.86
12.68
13.5

85
PI
KW
2.76
2.76
2.75
2.75
2.76
2.77
2.79
2.82
2.91
2.91
2.91
2.91
2.91
2.91
2.91
2.92
3.06
3.06
3.06
3.06
3.06
3.06
3.06
3.06

EER
16.77
16.74
16.71
16.7
16.71
16.77
16.97
17.18
17.96
17.96
17.97
17.96
17.98
17.99
18.01
18.04
19.16
19.16
19.16
19.16
19.16
19.17
19.17
19.17

TC
KW
13
12.97
12.96
12.97
13.02
13.13
13.42
13.71
14.67
14.68
14.69
14.68
14.71
14.74
14.8
14.86
16.53
16.54
16.55
16.54
16.54
16.55
16.56
16.56

SC
KW
9.25
10.18
11.06
11.84
12.52
13.13
13.42
13.71
8.23
9.09
9.95
10.79
11.52
12.24
12.93
13.54
7.51
8.33
9.14
9.95
10.77
11.58
12.39
13.21

PI
KW
3.28
3.28
3.28
3.28
3.28
3.29
3.31
3.34
3.41
3.41
3.41
3.41
3.41
3.41
3.42
3.42
3.55
3.55
3.55
3.55
3.55
3.55
3.55
3.55

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
EER TC
SC
PI
EER TC
SC
PI
EER TC
KW KW KW
KW KW KW
KW
13.53 12.45 9.1 3.79 11.19 11.88 8.92 4.32 9.38 11.3
13.51 12.44 9.96 3.79 11.19 11.89 9.72 4.32 9.39 11.32
13.5 12.44 10.78 3.79 11.19 11.91 10.47 4.32 9.4 11.36
13.51 12.47 11.48 3.8 11.21 11.96 11.11 4.33 9.43 11.43
13.54 12.54 12.11 3.8 11.26 12.05 11.68 4.33 9.49 11.54
13.62 12.67 12.67 3.81 11.34 12.19 12.19 4.34 9.58 11.7
13.82 12.95 12.95 3.83 11.53 12.47 12.47 4.36 9.75 11.97
14.02 13.24 13.24 3.85 11.72 12.75 12.75 4.38 9.93 12.25
14.69 14.05 8.02 3.91 12.26 13.42 7.79 4.43 10.34 12.76
14.69 14.06 8.89 3.91 12.26 13.42 8.66 4.43 10.34 12.77
14.7 14.07 9.75 3.91 12.26 13.43 9.53 4.43 10.34 12.77
14.7 14.07 10.61 3.91 12.26 13.43 10.39 4.43 10.34 12.77
14.71 14.1 11.3 3.92 12.29 13.48 11.05 4.43 10.37 12.83
14.73 14.14 11.99 3.92 12.31 13.52 11.71 4.44 10.4 12.88
14.77 14.2 12.65 3.92 12.35 13.6 12.33 4.44 10.44 12.97
14.81 14.29 13.21 3.93 12.41 13.69 12.86 4.45 10.5 13.08
15.9 15.88 7.26 4.04 13.41 15.2 6.99 4.55 11.4 14.5
15.9 15.88 8.06 4.04 13.41 15.2 7.79 4.55 11.41 14.5
15.91 15.89 8.87 4.04 13.42 15.21 8.58 4.55 11.41 14.51
15.91 15.89 9.67 4.04 13.42 15.21 9.37 4.55 11.41 14.51
15.91 15.89 10.49 4.04 13.42 15.21 10.18 4.55 11.41 14.51
15.91 15.89 11.29 4.04 13.42 15.22 10.97 4.55 11.41 14.51
15.92 15.9 12.09 4.04 13.43 15.22 11.76 4.55 11.42 14.52
15.92 15.9 12.9 4.04 13.43 15.23 12.56 4.55 11.42 14.53

115
SC
KW
8.71
9.45
10.13
10.72
11.24
11.7
11.97
12.25
7.53
8.41
9.28
10.14
10.77
11.4
11.99
12.47
6.71
7.49
8.28
9.05
9.85
10.62
11.41
12.19

PI
KW
4.87
4.87
4.87
4.88
4.88
4.9
4.91
4.93
4.96
4.97
4.97
4.97
4.97
4.97
4.98
4.99
5.07
5.07
5.07
5.07
5.07
5.07
5.07
5.07

125
EER
7.92
7.93
7.95
8
8.06
8.15
8.31
8.47
8.77
8.77
8.78
8.78
8.81
8.84
8.89
8.95
9.75
9.75
9.76
9.76
9.76
9.76
9.77
9.77

TC
KW
10.72
10.76
10.82
10.91
11.04
11.22
11.49
11.76
12.13
12.13
12.14
12.14
12.2
12.27
12.36
12.49
13.84
13.84
13.85
13.84
13.84
13.85
13.86
13.86

SC
KW
8.49
9.16
9.79
10.33
10.8
11.22
11.49
11.76
7.28
8.15
9.02
9.88
10.47
11.07
11.63
12.08
6.44
7.21
7.98
8.74
9.52
10.28
11.05
11.82

PI
KW
5.4
5.4
5.41
5.41
5.42
5.43
5.45
5.47
5.48
5.48
5.48
5.48
5.49
5.49
5.49
5.5
5.57
5.57
5.57
5.57
5.57
5.57
5.57
5.57

EER
6.77
6.8
6.83
6.88
6.95
7.05
7.19
7.34
7.55
7.55
7.56
7.56
7.59
7.63
7.68
7.75
8.47
8.47
8.48
8.48
8.48
8.48
8.49
8.49

YRM 014 R407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1670CFM 789.6l/s
INDOOR COIL
ENTERING AIR
DB
WB
F
F
70
72
74
76
60
78
80
82
84
74
76
78
80
67
82
84
86
88
80
82
84
86
74
88
90
92
94

55

75
TC
KW
13.17
13.14
13.12
13.13
13.17
13.27
13.55
13.84
14.82
14.83
14.84
14.84
14.86
14.89
14.94
15
16.67
16.67
16.68
16.68
16.68
16.68
16.69
16.69

SC
KW
9.3
10.25
11.15
11.94
12.64
13.27
13.55
13.84
8.29
9.14
9.99
10.84
11.57
12.3
13
13.62
7.56
8.38
9.2
10.01
10.83
11.64
12.45
13.27

85
PI
KW
2.73
2.73
2.72
2.73
2.73
2.74
2.77
2.8
2.91
2.91
2.91
2.91
2.91
2.92
2.92
2.93
3.11
3.11
3.11
3.11
3.11
3.11
3.11
3.11

EER
16.46
16.44
16.43
16.43
16.46
16.53
16.69
16.86
17.39
17.4
17.4
17.4
17.42
17.43
17.46
17.49
18.3
18.3
18.31
18.31
18.31
18.31
18.31
18.31

TC
KW
12.68
12.66
12.66
12.68
12.74
12.86
13.14
13.42
14.28
14.29
14.3
14.3
14.33
14.37
14.42
14.5
16.1
16.11
16.12
16.11
16.11
16.12
16.13
16.13

SC
KW
9.17
10.06
10.9
11.63
12.28
12.86
13.14
13.42
8.1
8.97
9.83
10.68
11.38
12.09
12.76
13.34
7.34
8.16
8.97
9.77
10.59
11.39
12.2
13.01

PI
KW
3.31
3.31
3.31
3.31
3.32
3.33
3.36
3.39
3.48
3.49
3.49
3.49
3.49
3.49
3.5
3.51
3.68
3.68
3.69
3.69
3.69
3.69
3.69
3.69

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
EER TC
SC
PI
EER TC
SC
PI
EER TC
KW KW KW
KW KW KW
KW
13.07 12.19 9.02 3.89 10.7 11.69 8.86 4.47 8.92 11.17
13.06 12.19 9.85 3.89 10.7 11.7 9.63 4.47 8.92 11.2
13.05 12.2 10.64 3.89 10.71 11.73 10.36 4.48 8.94 11.24
13.07 12.24 11.32 3.89 10.73 11.79 10.99 4.48 8.97 11.32
13.11 12.32 11.91 3.9 10.78 11.88 11.54 4.5 9.02 11.43
13.18 12.45 12.45 3.91 10.85 12.03 12.03 4.51 9.09 11.59
13.34 12.72 12.72 3.95
11
12.3 12.3 4.55 9.23 11.86
13.51 13.01 13.01 3.98 11.16 12.58 12.58 4.58 9.37 12.14
13.99 13.74 7.91 4.06 11.55 13.19 7.7 4.65 9.67 12.61
13.99 13.75 8.78 4.06 11.55 13.2 8.57 4.66 9.67 12.62
13.99 13.76 9.65 4.06 11.55 13.2 9.45 4.66 9.67 12.62
13.99 13.76 10.51 4.06 11.55 13.2 10.31 4.66 9.67 12.63
14.01 13.8 11.18 4.07 11.57 13.25 10.95 4.66 9.7 12.68
14.03 13.84 11.86 4.07 11.6 13.3 11.6 4.67 9.72 12.74
14.06 13.91 12.5 4.08 11.63 13.38 12.21 4.68 9.76 12.82
14.1
14 13.04 4.09 11.67 13.48 12.72 4.69 9.81 12.94
14.91 15.54 7.12 4.27 12.42 14.95 6.89 4.87 10.47 14.34
14.92 15.54 7.92 4.27 12.42 14.95 7.68 4.87 10.47 14.34
14.92 15.55 8.73 4.27 12.43 14.96 8.47 4.87 10.48 14.35
14.92 15.54 9.52 4.27 12.43 14.95 9.26 4.87 10.47 14.34
14.92 15.54 10.33 4.27 12.43 14.96 10.06 4.87 10.48 14.35
14.92 15.55 11.13 4.27 12.43 14.96 10.84 4.87 10.48 14.35
14.92 15.56 11.93 4.27 12.43 14.97 11.63 4.87 10.48 14.36
14.93 15.56 12.73 4.27 12.43 14.97 12.43 4.87 10.48 14.36

115
SC
PI
KW KW
8.67 5.08
9.39 5.09
10.06 5.09
10.64 5.1
11.14 5.12
11.59 5.14
11.86 5.17
12.14 5.21
7.47 5.27
8.35 5.27
9.22 5.27
10.08 5.27
10.7 5.28
11.32 5.29
11.9 5.3
12.38 5.31
6.64 5.49
7.42 5.5
8.2
5.5
8.98 5.5
9.77 5.5
10.54 5.5
11.32 5.5
12.1 5.5

EER
7.5
7.51
7.53
7.57
7.62
7.7
7.82
7.95
8.17
8.17
8.17
8.17
8.2
8.22
8.26
8.31
8.9
8.9
8.91
8.91
8.91
8.91
8.91
8.91

TC
KW
10.67
10.71
10.76
10.86
10.99
11.17
11.43
11.7
12.06
12.06
12.07
12.07
12.14
12.2
12.29
12.42
13.76
13.76
13.77
13.77
13.77
13.77
13.78
13.79

125
SC
PI
KW KW
8.46 5.68
9.13 5.69
9.76 5.69
10.29 5.7
10.76 5.72
11.17 5.74
11.43 5.78
11.7 5.81
7.25 5.86
8.12 5.86
8.99 5.86
9.85 5.86
10.44 5.87
11.03 5.88
11.59 5.89
12.04 5.91
6.41 6.09
7.18 6.09
7.94 6.09
8.7 6.09
9.48 6.09
10.24 6.09
11.01 6.09
11.78 6.09

EER
6.41
6.43
6.45
6.49
6.55
6.63
6.75
6.87
7.02
7.02
7.02
7.02
7.05
7.08
7.12
7.17
7.71
7.71
7.72
7.72
7.72
7.72
7.72
7.72

56

YRM 018 R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1907CFM 901.6l/s
INDOOR COIL
ENTERING AIR
DB
WB
F
F
70
72
74
76
60
78
80
82
84
74
76
78
80
67
82
84
86
88
80
82
84
86
74
88
90
92
94

75
TC
KW
17.35
17.32
17.27
17.29
17.29
17.44
17.63
18
19.55
19.55
19.57
19.57
19.6
19.62
19.66
19.74
21.96
21.97
21.98
21.99
21.99
22
22
21.99

SC
KW
11.87
13.07
14.27
15.26
16.28
16.98
17.63
18
10.74
11.79
12.84
13.88
14.84
15.74
16.68
17.45
9.83
10.84
11.84
12.84
13.85
14.85
15.85
16.85

85
PI
KW
3.31
3.3
3.3
3.3
3.3
3.32
3.34
3.38
3.54
3.54
3.55
3.55
3.55
3.55
3.56
3.57
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

EER
17.9
17.88
17.86
17.86
17.85
17.91
17.99
18.15
18.82
18.82
18.83
18.83
18.84
18.85
18.86
18.89
19.73
19.74
19.74
19.74
19.74
19.75
19.74
19.74

TC
KW
16.63
16.62
16.59
16.63
16.65
16.82
17.03
17.39
18.76
18.76
18.77
18.77
18.81
18.84
18.88
18.98
21.12
21.13
21.14
21.15
21.15
21.16
21.15
21.15

SC
KW
11.71
12.82
13.93
14.85
15.78
16.43
17.03
17.39
10.46
11.53
12.58
13.64
14.58
15.44
16.35
17.06
9.5
10.5
11.5
12.49
13.48
14.47
15.47
16.46

PI
KW
3.97
3.97
3.96
3.97
3.97
3.99
4.01
4.05
4.19
4.19
4.19
4.19
4.19
4.2
4.2
4.21
4.42
4.42
4.42
4.42
4.42
4.42
4.42
4.42

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
EER TC
SC
PI
EER TC
SC
PI
EER TC
KW KW KW
KW KW KW
KW
14.3 15.95 11.53 4.6 11.83 15.21 11.3 5.27 9.84 14.48
14.29 15.95 12.56 4.6 11.83 15.23 12.26 5.28 9.85 14.52
14.28 15.94 13.59 4.6 11.83 15.24 13.21 5.28 9.86 14.55
14.29 16 14.44 4.6 11.86 15.33 13.99 5.28 9.9 14.65
14.3 16.05 15.3 4.61 11.88 15.4 14.77 5.29 9.93 14.76
14.38 16.23 15.89 4.63 11.97 15.6 15.32 5.31 10.02 14.97
14.48 16.45 16.45 4.65 12.07 15.84 15.84 5.34 10.13 15.22
14.65 16.81 16.81 4.69 12.23 16.19 16.19 5.37 10.28 15.57
15.29 17.98 10.17 4.81 12.76 17.16 9.86 5.47 10.71 16.35
15.29 17.98 11.25 4.81 12.76 17.17 10.94 5.47 10.71 16.35
15.29 18 12.31 4.81 12.76 17.18 12.01 5.47 10.72 16.37
15.3
18 13.38 4.81 12.76 17.18 13.08 5.47 10.72 16.37
15.31 18.04 14.3 4.82 12.78 17.23 13.97 5.47 10.74 16.42
15.33 18.09 15.12 4.82 12.8 17.28 14.76 5.48 10.76 16.49
15.34 18.13 15.99 4.82 12.82 17.34 15.6 5.49 10.79 16.56
15.39 18.25 16.66 4.84 12.87 17.47 16.22 5.5 10.84 16.7
16.3 20.29 9.17 5.04 13.74 19.41 8.82 5.68 11.65 18.56
16.3 20.29 10.15 5.04 13.74 19.42 9.79 5.69 11.66 18.57
16.31 20.31 11.14 5.04 13.74 19.43 10.76 5.69 11.66 18.58
16.31 20.31 12.12 5.04 13.75 19.44 11.73 5.69 11.66 18.59
16.31 20.32 13.1 5.04 13.75 19.45 12.7 5.69 11.67 18.59
16.32 20.32 14.08 5.04 13.75 19.45 13.66 5.69 11.67 18.6
16.32 20.32 15.07 5.04 13.75 19.45 14.63 5.69 11.67 18.6
16.31 20.32 16.05 5.04 13.75 19.45 15.6 5.69 11.67 18.59

115
SC
PI
KW KW
11.05 5.95
11.94 5.95
12.81 5.96
13.52 5.97
14.23 5.98
14.74
6
15.22 6.02
15.57 6.05
9.53 6.12
10.61 6.12
11.68 6.12
12.75 6.12
13.62 6.13
14.37 6.13
15.17 6.14
15.76 6.15
8.47 6.32
9.42 6.32
10.38 6.32
11.33 6.32
12.29 6.32
13.23 6.32
14.19 6.32
15.14 6.32

EER
8.3
8.32
8.34
8.38
8.43
8.52
8.63
8.78
9.11
9.12
9.12
9.12
9.14
9.17
9.2
9.26
10.03
10.03
10.04
10.04
10.04
10.04
10.04
10.04

TC
KW
13.75
13.81
13.86
13.99
14.12
14.35
14.62
14.96
15.55
15.56
15.57
15.57
15.63
15.71
15.78
15.95
17.72
17.73
17.75
17.75
17.76
17.77
17.76
17.76

125
SC
PI
KW KW
10.77 6.61
11.59 6.62
12.4 6.62
13.05 6.64
13.7 6.65
14.17 6.67
14.62 6.69
14.96 6.72
9.2 6.76
10.27 6.76
11.33 6.76
12.4 6.77
13.25 6.77
13.97 6.78
14.73 6.78
15.28 6.8
8.13 6.94
9.06 6.94
10.01 6.94
10.93 6.94
11.87 6.94
12.8 6.94
13.74 6.94
14.67 6.94

EER
7.09
7.12
7.14
7.19
7.25
7.34
7.45
7.59
7.85
7.85
7.85
7.85
7.88
7.91
7.94
8.01
8.72
8.72
8.73
8.73
8.73
8.74
8.73
8.73

YRM 018 R407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1907CFM 901.6l/s
INDOOR COIL
ENTERING AIR
DB
F
70
72
74
76
78
80
82
84
74
76
78
80
82
84
86
88
80
82
84
86
88
90
92
94

57

WB
F

60

67

74

75
TC
KW
16.87
16.86
16.82
16.86
16.88
17.06
17.27
17.66
19.18
19.18
19.2
19.2
19.23
19.27
19.31
19.41
21.72
21.72
21.74
21.74
21.75
21.75
21.75
21.75

SC
KW
11.76
12.91
14.05
14.99
15.96
16.64
17.27
17.66
10.61
11.67
12.72
13.77
14.72
15.61
16.53
17.28
9.74
10.74
11.74
12.74
13.74
14.74
15.74
16.74

85
PI
KW
3.26
3.26
3.26
3.26
3.26
3.28
3.3
3.33
3.46
3.46
3.46
3.46
3.46
3.46
3.47
3.48
3.67
3.67
3.68
3.68
3.68
3.68
3.68
3.68

EER
17.65
17.64
17.62
17.65
17.66
17.76
17.89
18.11
18.93
18.93
18.94
18.94
18.96
18.97
19
19.05
20.17
20.17
20.18
20.18
20.18
20.19
20.19
20.19

TC
KW
16.18
16.18
16.16
16.22
16.27
16.46
16.68
17.06
18.37
18.38
18.39
18.39
18.43
18.48
18.52
18.64
20.82
20.83
20.84
20.85
20.86
20.86
20.86
20.86

SC
KW
11.59
12.65
13.71
14.58
15.47
16.09
16.68
17.06
10.32
11.39
12.45
13.52
14.45
15.29
16.18
16.88
9.38
10.37
11.37
12.36
13.35
14.33
15.33
16.31

PI
KW
3.91
3.91
3.91
3.92
3.92
3.94
3.96
3.99
4.1
4.1
4.1
4.1
4.1
4.11
4.11
4.12
4.31
4.31
4.31
4.31
4.31
4.31
4.31
4.31

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB F


95
105
EER TC
SC
PI
EER TC
SC
PI
EER TC
KW KW KW
KW KW KW
KW
14.11 15.52 11.4 4.53 11.69 14.81 11.17 5.19 9.73 14.1
14.11 15.53 12.39 4.53 11.7 14.84 12.09 5.19 9.75 14.15
14.1 15.54 13.38 4.53 11.7 14.86 13
5.2 9.76 14.19
14.13 15.61 14.18 4.54 11.74 14.96 13.74 5.21 9.8 14.31
14.16 15.68 15
4.54 11.77 15.05 14.48 5.22 9.85 14.42
14.27 15.88 15.57 4.56 11.87 15.27 15.01 5.24 9.95 14.65
14.39 16.12 16.12 4.59 11.99 15.51 15.51 5.26 10.06 14.91
14.6 16.48 16.48 4.62 12.18 15.87 15.87 5.29 10.23 15.25
15.29 17.59 10.02 4.72 12.71 16.77 9.7 5.38 10.63 15.94
15.29 17.6 11.1 4.72 12.71 16.77 10.78 5.38 10.63 15.95
15.3 17.61 12.17 4.72 12.72 16.78 11.85 5.38 10.64 15.96
15.3 17.61 13.24 4.72 12.72 16.78 12.92 5.38 10.64 15.96
15.32 17.65 14.15 4.73 12.74 16.83 13.81 5.39 10.66 16.01
15.34 17.71 14.96 4.73 12.77 16.9 14.58 5.39 10.69 16.09
15.37 17.76 15.81 4.74 12.79 16.96 15.39 5.4 10.72 16.16
15.42 17.89 16.46 4.75 12.85 17.1
16
5.41 10.78 16.31
16.48 19.94 9.03 4.94 13.78 19.02 8.66 5.6 11.59 18.11
16.49 19.95 10.01 4.94 13.78 19.02 9.62 5.6 11.6 18.12
16.49 19.96 10.99 4.94 13.78 19.04 10.59 5.6 11.6 18.13
16.5 19.97 11.97 4.94 13.79 19.04 11.54 5.6 11.6 18.14
16.5 19.97 12.94 4.94 13.79 19.05 12.51 5.6 11.61 18.15
16.5 19.98 13.92 4.94 13.79 19.06 13.46 5.6 11.61 18.15
16.5 19.98 14.9 4.94 13.79 19.05 14.43 5.6 11.61 18.15
16.5 19.98 15.87 4.94 13.79 19.05 15.39 5.6 11.61 18.15

115
SC
KW
10.91
11.76
12.6
13.28
13.96
14.45
14.91
15.25
9.36
10.44
11.51
12.58
13.43
14.17
14.95
15.52
8.29
9.23
10.18
11.12
12.06
13
13.95
14.89

PI
KW
5.86
5.86
5.87
5.88
5.89
5.91
5.93
5.97
6.03
6.03
6.04
6.04
6.04
6.05
6.05
6.07
6.24
6.24
6.24
6.24
6.25
6.25
6.25
6.25

125
EER
8.21
8.23
8.25
8.31
8.36
8.46
8.57
8.72
9.02
9.02
9.02
9.02
9.05
9.08
9.11
9.17
9.9
9.9
9.91
9.91
9.91
9.92
9.91
9.91

TC
KW
13.4
13.46
13.53
13.66
13.8
14.04
14.31
14.64
15.13
15.14
15.15
15.15
15.21
15.29
15.37
15.54
17.22
17.23
17.25
17.25
17.26
17.27
17.26
17.26

SC
KW
10.62
11.41
12.19
12.81
13.43
13.89
14.31
14.64
9.01
10.08
11.14
12.2
13.04
13.74
14.49
15.02
7.92
8.84
9.77
10.69
11.61
12.53
13.46
14.37

PI
KW
6.51
6.52
6.53
6.54
6.55
6.57
6.6
6.63
6.68
6.68
6.68
6.68
6.68
6.69
6.7
6.72
6.88
6.88
6.88
6.88
6.88
6.88
6.88
6.88

EER
7.02
7.05
7.07
7.13
7.19
7.29
7.4
7.54
7.73
7.73
7.74
7.74
7.76
7.8
7.83
7.9
8.55
8.55
8.56
8.56
8.56
8.56
8.56
8.56

58

YRM 022 R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
20.79
20.91
21.31
22.49
23.48
22.59
22.69
22.79
23.08
24.14
24.60
24.69
24.79
24.88
25.07

24 C
TSH COMP
kW
kWl
16.07 4.48
19.55 4.50
21.31 4.53
22.49 4.61
23.48 4.62
11.41 4.68
13.70 4.67
14.88 4.68
17.36 4.70
20.54 4.77
8.98
4.92
9.85
4.91
11.63 4.91
13.36 4.90
15.22 4.90

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
19.93
20.13
20.72
21.70
22.68
21.69
21.79
21.88
22.27
23.44
23.55
23.65
23.74
23.84
24.13

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
15.41 5.07 13.42 19.30 15.50 5.82 11.32 18.48 15.12 6.54
19.12 5.10 13.46 19.49 18.75 5.86 11.35 18.75 18.32 6.63
20.72 5.20 13.59 20.28 20.28 6.01 11.51 19.53 19.53 6.72
21.70 5.21 14.20 21.16 21.16 6.00 12.03 20.41 20.41 6.76
22.68 5.24 14.76 22.15 22.15 6.05 12.49 21.28 21.28 6.80
11.28 5.28 14.03 21.12 11.30 6.07 11.86 20.18 11.10 6.79
13.49 5.27 14.10 21.31 13.51 6.11 11.91 20.27 13.16 6.80
14.62 5.28 14.13 21.41 14.62 6.10 11.98 20.47 14.28 6.82
17.08 5.31 14.32 21.81 17.05 6.14 12.12 21.27 16.95 6.96
20.30 5.39 14.85 23.00 20.27 6.20 12.66 22.17 19.86 6.94
8.95
5.51 14.58 23.03 9.10
6.37 12.34 21.85 8.96
7.06
9.79
5.50 14.68 23.13 9.92
6.35 12.43 22.05 9.79
7.08
11.49 5.50 14.73 23.23 11.59 6.36 12.47 22.15 11.39 7.08
13.16 5.50 14.78 23.43 13.28 6.35 12.58 22.35 13.01 7.09
15.01 5.50 14.95 23.82 15.18 6.40 12.70 23.05 15.03 7.23

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
17.61
17.86
18.75
19.52
20.29
19.16
19.25
19.45
20.47
21.29
20.68
20.79
20.89
21.20
22.13

46 C
TSH COMP
kW
kWl
14.67 7.16
17.72 7.25
18.75 7.35
19.52 7.38
20.29 7.40
10.83 7.38
12.78 7.41
13.87 7.40
16.63 7.56
19.40 7.55
8.79
7.66
9.59
7.65
11.05 7.65
12.65 7.69
14.76 7.87

GH
kW
28.27
27.50
26.79

15 C
NH COMP EER
kW
kWl
28.27 5.72 16.86
27.50 6.20 15.15
26.69 6.68 13.69

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
15.21
14.72
14.27

-5 C
NH COMP EER
kW
kWl
13.54 3.76 13.79
13.04 4.04 12.43
12.70 4.28 11.36

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
16.40 4.30 14.59 21.92 18.90 4.75 15.76 24.86 24.86 5.20 16.31
15.91 4.55 13.35 21.23 18.29 5.10 14.20 24.14 24.14 5.56 14.81
15.22 4.90 11.91 20.43 5.52
5.46 12.77 23.31 23.31 5.93 13.42
o

GH
kW
18.39
17.79
17.09

YRM 022 R407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
19.34
19.44
19.82
20.92
21.84
21.01
21.10
21.19
21.46
22.45
22.88
22.97
23.05
23.14
23.32

24 C
TSH COMP
kW
kWl
14.95 4.58
18.18 4.59
19.82 4.63
20.92 4.71
21.84 4.72
10.61 4.78
12.74 4.78
13.84 4.78
16.14 4.80
19.10 4.87
8.35
5.03
9.16
5.01
10.81 5.01
12.43 5.01
14.15 5.00

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH
TSH COMP EER GTH TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
14.33 5.18 12.21 17.95 14.41 5.94 10.30 17.19 14.06 6.68
17.78 5.21 12.25 18.12 17.43 5.99 10.33 17.44 17.04 6.77
19.27 5.31 12.37 18.86 18.86 6.14 10.48 18.16 18.16 6.86
20.18 5.33 12.92 19.68 19.68 6.13 10.95 18.98 18.98 6.91
21.09 5.36 13.43 20.60 20.60 6.19 11.36 19.79 19.79 6.95
10.49 5.39 12.77 19.64 10.51 6.21 10.80 18.76 10.32 6.94
12.54 5.39 12.83 19.82 12.57 6.24 10.84 18.85 12.23 6.95
13.60 5.40 12.86 19.91 13.60 6.23 10.90 19.03 13.28 6.97
15.89 5.42 13.03 20.28 15.86 6.27 11.03 19.78 15.76 7.11
18.88 5.51 13.51 21.39 18.85 6.34 11.52 20.62 18.47 7.09
8.32
5.63 13.27 21.42 8.46
6.51 11.23 20.32 8.33
7.22
9.10
5.62 13.36 21.51 9.23
6.49 11.31 20.51 9.11
7.23
10.69 5.62 13.41 21.60 10.78 6.50 11.35 20.60 10.59 7.24
12.24 5.63 13.45 21.79 12.35 6.49 11.45 20.79 12.10 7.24
13.96 5.63 13.61 22.16 14.11 6.54 11.56 21.44 13.98 7.38
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
18.54
18.72
19.27
20.18
21.09
20.17
20.26
20.35
20.71
21.80
21.90
21.99
22.08
22.17
22.44

EER
8.78
8.79
9.03
9.37
9.71
9.23
9.25
9.32
9.49
9.92
9.60
9.67
9.71
9.79
9.91

GTH
kW
16.37
16.61
17.43
18.15
18.87
17.82
17.90
18.09
19.04
19.80
19.24
19.33
19.43
19.71
20.58

46oC
TSH COMP
kW
kWl
13.64 7.32
16.48 7.41
17.43 7.51
18.15 7.54
18.87 7.57
10.07 7.55
11.89 7.57
12.90 7.57
15.46 7.72
18.04 7.72
8.18
7.83
8.87
7.82
10.28 7.81
11.77 7.86
13.72 8.04

GH
kW
26.29
25.58
24.92

15oC
NH COMP EER
kW
kWl
26.29 5.85 15.34
25.58 6.33 13.79
24.92 6.82 12.46

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

59

GH
kW
14.14
13.69
13.27

-5 C
NH COMP EER
kW
kWl
12.59 3.84 12.55
12.18 4.13 11.31
11.81 4.38 10.34

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
15.22 4.39 13.28 20.39 17.53 4.85 14.34 23.12 23.12 5.32 14.84
14.72 4.64 12.15 19.74 16.98 5.21 12.92 22.45 22.45 5.68 13.47
14.15 5.00 10.84 19.00 16.34 5.58 11.62 21.68 21.68 6.06 12.21
o

GH
kW
17.10
16.54
15.90

60

YRM 027 R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
25.82
25.94
26.25
27.15
28.24
27.85
27.95
28.05
28.25
28.93
29.92
30.11
30.20
30.30
30.58

24 C
TSH COMP
kW
kWl
19.96 5.56
24.26 5.58
26.25 5.58
27.15 5.56
28.24 5.56
14.07 5.77
16.88 5.76
18.32 5.76
21.24 5.75
24.62 5.71
10.92 5.98
12.01 5.98
14.17 5.98
16.27 5.97
18.56 5.97

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


o
o
30 C
35 C
40 C
TSH COMP EER GTH
TSH COMP EER GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
19.05 6.27 13.42 23.92 19.21 7.21 11.32 22.98 18.80 8.13
23.60 6.30 13.46 24.11 23.19 7.25 11.35 23.14 22.60 8.18
25.14 6.31 13.59 24.59 24.59 7.29 11.51 23.80 23.80 8.19
26.21 6.30 14.20 25.68 25.68 7.28 12.03 24.88 24.88 8.24
27.29 6.31 14.76 26.86 26.86 7.34 12.49 26.04 26.04 8.32
13.91 6.51 14.03 26.12 13.98 7.51 11.86 25.15 13.83 8.46
16.62 6.49 14.10 26.32 16.69 7.54 11.91 25.24 16.38 8.47
18.06 6.53 14.13 26.51 18.11 7.55 11.98 25.53 17.82 8.51
20.96 6.51 14.32 26.81 20.97 7.55 12.12 26.03 20.74 8.52
24.43 6.48 14.85 27.91 24.59 7.52 12.66 27.23 24.40 8.52
10.97 6.75 14.58 28.51 11.26 7.89 12.34 27.39 11.23 8.86
12.03 6.75 14.68 28.71 12.32 7.88 12.43 27.59 12.25 8.85
14.11 6.75 14.73 28.81 14.38 7.88 12.47 27.79 14.28 8.88
16.20 6.78 14.78 29.01 16.45 7.87 12.58 27.99 16.29 8.88
18.43 6.76 14.95 29.41 18.73 7.90 12.70 28.39 18.51 8.90
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
24.65
24.84
25.14
26.21
27.29
26.75
26.85
27.04
27.33
28.21
28.86
29.05
29.15
29.34
29.63

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
21.90
22.15
23.02
24.09
25.26
24.16
24.35
24.65
25.36
26.59
26.58
26.78
26.89
27.19
27.81

46 C
TSH COMP
kW
kWl
18.24 8.91
21.97 8.99
23.02 9.02
24.09 9.10
25.26 9.22
13.65 9.31
16.17 9.37
17.57 9.38
20.59 9.36
24.22 9.43
11.30 9.84
12.29 9.85
14.22 9.84
16.23 9.87
18.55 9.89

GH
kW
35.13
34.14
33.31

15 C
NH COMP EER
kW
kWl
35.13 7.07 16.95
34.14 7.46 15.63
33.31 7.95 14.29

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
18.86
18.27
17.73

-5 C
NH COMP EER
kW
kWl
16.77 4.55 14.13
16.28 4.75 13.13
15.74 4.79 12.62

GH
kW
22.77
22.08
21.26

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


o
o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
20.27 5.20 14.94 27.14 23.39 5.86 15.81 30.84 30.84 6.43 16.38
19.67 5.35 14.07 26.35 22.68 6.12 14.69 30.01 30.01 6.70 15.30
18.98 5.61 12.93 25.33 21.78 6.39 13.53 28.95 28.95 6.97 14.18

YRM 027 R407C Performance Rating


PERFORMANCE DATAAIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
24.02
24.13
24.42
25.25
26.26
25.90
26.00
26.09
26.27
26.90
27.82
28.00
28.09
28.18
28.44

24 C
TSH COMP
kW
kWl
18.56 5.68
22.56 5.70
24.42 5.71
25.25 5.68
26.26 5.68
13.08 5.90
15.70 5.89
17.04 5.89
19.76 5.88
22.89 5.84
10.16 6.11
11.17 6.11
13.17 6.11
15.13 6.10
17.26 6.10

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
22.92
23.10
23.38
24.38
25.38
24.88
24.97
25.15
25.42
26.23
26.84
27.02
27.11
27.29
27.55

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER GTH TSH COMP EER GTH TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
17.72 6.40 12.21 22.25 17.87 7.37 10.30 21.37 17.48 8.31
21.95 6.44 12.25 22.42 21.57 7.41 10.33 21.52 21.02 8.36
23.38 6.45 12.37 22.87 22.87 7.45 10.48 22.14 22.14 8.37
24.38 6.44 12.92 23.88 23.88 7.44 10.95 23.13 23.13 8.42
25.38 6.45 13.43 24.98 24.98 7.50 11.36 24.22 24.22 8.51
12.94 6.65 12.77 24.29 13.00 7.68 10.80 23.39 12.86 8.64
15.45 6.64 12.83 24.48 15.52 7.70 10.84 23.47 15.23 8.65
16.80 6.67 12.86 24.66 16.84 7.72 10.90 23.74 16.57 8.69
19.50 6.65 13.03 24.93 19.50 7.71 11.03 24.20 19.29 8.71
22.72 6.62 13.51 25.95 22.86 7.69 11.52 25.32 22.69 8.71
10.20 6.90 13.27 26.52 10.47 8.06 11.23 25.47 10.44 9.05
11.19 6.90 13.36 26.70 11.45 8.05 11.31 25.66 11.39 9.05
13.12 6.90 13.41 26.79 13.37 8.06 11.35 25.84 13.28 9.08
15.06 6.92 13.45 26.98 15.30 8.04 11.45 26.03 15.15 9.07
17.14 6.91 13.61 27.35 17.42 8.07 11.56 26.40 17.21 9.09

EER
8.78
8.79
9.03
9.37
9.71
9.23
9.25
9.32
9.49
9.92
9.60
9.67
9.71
9.79
9.91

GTH
kW
20.37
20.60
21.41
22.40
23.49
22.47
22.65
22.92
23.58
24.73
24.72
24.91
25.00
25.29
25.87

46 C
TSH COMP EER
kW
kWl
16.97 9.11 7.63
20.43 9.19 7.65
21.41 9.22 7.92
22.40 9.30 8.22
23.49 9.42 8.51
12.69 9.51 8.06
15.04 9.57 8.07
16.34 9.59 8.16
19.15 9.57 8.41
22.53 9.63 8.76
10.50 10.06 8.39
11.43 10.07 8.44
13.23 10.06 8.48
15.10 10.09 8.55
17.25 10.11 8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

61

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
o
-5 C
0C
5C
10 C
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
17.54 15.61 4.65 12.86 21.18 18.85 5.31 13.60 25.24 21.71 5.99 14.38 28.68 28.68 6.57
16.99 15.12 4.85 11.95 20.53 18.27 5.47 12.81 24.51 21.07 6.25 13.37 27.91 27.91 6.84
16.49 14.67 4.90 11.48 19.77 17.60 5.73 11.77 23.55 20.26 6.53 12.31 26.93 26.93 7.12

15 C
EER
GH
NH COMP
kW
kW
kWl
14.90 32.67 32.67 7.23
13.92 31.75 31.75 7.62
12.90 30.98 30.98 8.12

EER
15.42
14.22
13.01

62

YRM 030S R22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
29.21
29.33
29.74
30.93
32.31
31.68
31.78
31.88
32.27
33.14
34.29
34.48
34.57
34.67
34.95

24 C
TSH COMP
kW
kWl
22.58 6.29
27.42 6.31
29.74 6.33
30.93 6.33
32.31 6.36
16.00 6.56
19.20 6.55
20.82 6.55
24.27 6.57
28.20 6.55
12.52 6.86
13.76 6.85
16.21 6.84
18.62 6.83
21.22 6.82

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH
TSH COMP EER GTH TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
21.56 7.08 13.44 26.94 21.63 8.17 11.26 25.73 21.05 9.41
26.58 7.10 13.45 27.12 26.09 8.25 11.22 25.99 25.39 9.42
28.57 7.18 13.58 27.70 27.70 8.30 11.39 26.75 26.75 9.54
29.85 7.22 14.11 29.09 29.09 8.32 11.93 27.92 27.92 9.60
31.12 7.31 14.53 30.27 30.27 8.35 12.37 29.08 29.08 9.65
15.73 7.36 14.02 29.42 15.74 8.57 11.71 27.98 15.39 9.78
18.85 7.37 14.09 29.52 18.72 8.60 11.71 28.18 18.29 9.81
20.40 7.40 14.08 29.82 20.36 8.64 11.77 28.37 19.80 9.85
23.65 7.41 14.20 30.31 23.70 8.67 11.93 28.96 23.08 9.88
27.80 7.44 14.72 31.51 27.76 8.70 12.36 30.37 27.21 9.92
12.43 7.71 14.48 32.00 12.64 8.87 12.31 30.31 12.43 10.21
13.63 7.72 14.55 32.10 13.77 8.90 12.31 30.51 13.55 10.22
16.02 7.74 14.59 32.30 16.12 8.93 12.34 30.61 15.73 10.23
18.27 7.76 14.56 32.40 18.37 8.97 12.32 30.91 17.99 10.24
20.83 7.78 14.69 32.80 20.89 9.00 12.43 31.41 20.48 10.26
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
27.89
27.98
28.57
29.85
31.12
30.25
30.44
30.54
30.83
32.10
32.72
32.91
33.10
33.10
33.49

EER
9.33
9.41
9.57
9.92
10.28
9.76
9.80
9.82
10.00
10.45
10.13
10.19
10.21
10.30
10.45

GTH
kW
24.31
24.55
25.52
26.68
27.74
26.45
26.64
26.94
27.85
29.08
28.65
28.85
28.95
29.37
30.19

46oC
TSH COMP
kW
kWl
20.25 10.31
24.35 10.36
25.52 10.42
26.68 10.57
27.74 10.66
14.94 10.61
17.69 10.64
19.21 10.70
22.62 10.75
26.49 10.80
12.17 11.03
13.24 11.06
15.32 11.07
17.53 11.11
20.14 11.15

GH
kW
39.45
38.36
37.40

15oC
NH COMP EER
kW
kWl
39.45 8.11 16.59
38.36 8.61 15.20
37.40 9.22 13.84

EER
8.04
8.09
8.36
8.61
8.88
8.51
8.54
8.59
8.84
9.19
8.86
8.90
8.92
9.02
9.24

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
21.15
20.46
19.83

-5 C
NH COMP EER
kW
kWl
18.86 5.25 13.75
18.26 5.45 12.80
17.74 5.71 11.84

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
22.77 59.00 1.48 30.48 26.21 6.57 15.84 34.73 34.73 7.24 16.36
22.08 6.16 13.73 29.59 25.40 7.04 14.35 33.69 33.69 7.73 14.88
21.27 6.53 12.48 28.45 24.49 7.31 13.28 32.51 32.51 8.11 13.67
o

GH
kW
25.59
24.80
23.87

YRM 030S R407C Performance Rating


PERFORMANCE DATAAIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
27.16
27.28
27.66
28.76
30.05
29.46
29.56
29.65
30.01
30.82
31.89
32.06
32.15
32.24
32.51

24 C
TSH COMP
kW
kWl
21.00 6.43
25.50 6.44
27.66 6.46
28.76 6.47
30.05 6.50
14.88 6.71
17.85 6.69
19.36 6.69
22.57 6.71
26.23 6.69
11.64 7.01
12.79 7.00
15.08 6.99
17.31 6.98
19.73 6.97

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
25.93
26.03
26.57
27.76
28.94
28.13
28.31
28.40
28.68
29.85
30.43
30.61
30.79
30.79
31.14

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER GTH TSH COMP EER GTH TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
20.05 7.24 12.23 25.05 20.12 8.35 10.24 23.93 19.58 9.62
24.72 7.26 12.24 25.22 24.26 8.43 10.21 24.17 23.62 9.63
26.57 7.34 12.36 25.76 25.76 8.48 10.36 24.88 24.88 9.75
27.76 7.38 12.84 27.05 27.05 8.50 10.86 25.97 25.97 9.81
28.94 7.47 13.22 28.15 28.15 8.53 11.26 27.05 27.05 9.86
14.63 7.52 12.76 27.37 14.64 8.76 10.65 26.03 14.31 9.99
17.53 7.53 12.83 27.45 17.41 8.79 10.66 26.20 17.01 10.03
18.97 7.56 12.81 27.73 18.94 8.83 10.71 26.38 18.41 10.07
21.99 7.57 12.92 28.19 22.04 8.86 10.86 26.94 21.47 10.10
25.85 7.60 13.40 29.30 25.81 8.89 11.24 28.24 25.31 10.14
11.56 7.88 13.18 29.76 11.76 9.06 11.20 28.19 11.56 10.43
12.67 7.89 13.24 29.85 12.81 9.10 11.20 28.37 12.60 10.44
14.90 7.91 13.28 30.04 14.99 9.13 11.23 28.47 14.63 10.45
16.99 7.93 13.25 30.13 17.08 9.17 11.21 28.75 16.73 10.47
19.37 7.95 13.37 30.50 19.43 9.20 11.31 29.21 19.05 10.49

EER
8.49
8.57
8.71
9.03
9.36
8.88
8.92
8.94
9.10
9.51
9.22
9.27
9.29
9.37
9.51

GTH
kW
22.61
22.83
23.73
24.82
25.80
24.60
24.78
25.05
25.90
27.05
26.64
26.83
26.93
27.31
28.08

46 C
TSH COMP EER
kW
kWl
18.84 10.54 7.32
22.65 10.59 7.36
23.73 10.65 7.60
24.82 10.80 7.84
25.80 10.89 8.08
13.90 10.84 7.74
16.45 10.87 7.77
17.86 10.94 7.82
21.03 10.99 8.05
24.64 11.04 8.36
11.32 11.27 8.06
12.32 11.30 8.10
14.24 11.31 8.12
16.30 11.35 8.21
18.73 11.40 8.41

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

63

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
o
-5 C
0C
5C
10 C
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
19.67 17.50 5.36 12.51 23.80 21.18 60.30 1.35 28.35 24.38 6.71 14.42 32.29 32.29 7.40
19.03 16.93 5.57 11.65 23.06 20.52 6.30 12.50 27.52 23.67 7.19 13.05 31.33 31.33 7.89
18.44 16.41 5.84 10.78 22.20 19.76 6.67 11.35 26.46 22.76 7.47 12.08 30.23 30.23 8.29

15 C
EER
GH
NH COMP
kW
kW
kWl
14.89 36.69 36.69 8.29
13.54 35.67 35.67 8.80
12.44 34.79 34.79 9.42

EER
15.10
13.83
12.59

64

YRM 030D R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
29.45
29.68
30.21
31.56
32.71
32.16
32.26
32.47
32.78
33.99
34.91
35.10
35.20
35.40
35.70

24 C
TSH COMP
kW
kWl
21.68 6.34
26.43 6.38
28.77 6.43
30.06 6.46
31.15 6.44
15.47 6.66
18.56 6.65
20.19 6.67
23.48 6.67
27.55 6.71
12.13 6.98
13.34 6.98
15.72 6.97
18.11 6.98
20.64 6.97

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
20.80 7.18 13.42 27.44 20.99 8.27 11.32 26.38 20.55 9.33
25.65 7.19 13.46 27.74 25.41 8.34 11.35 26.65 24.80 9.42
27.69 7.30 13.59 28.56 27.20 8.46 11.51 27.56 26.25 9.48
29.06 7.33 14.20 29.91 28.49 8.48 12.03 28.89 27.52 9.57
30.34 7.36 14.76 31.26 29.77 8.54 12.49 30.22 28.78 9.66
15.27 7.50 14.03 30.16 15.37 8.67 11.86 28.85 15.11 9.70
18.24 7.49 14.10 30.26 18.27 8.67 11.91 29.05 17.96 9.75
19.75 7.50 14.13 30.57 19.89 8.70 11.98 29.36 19.52 9.78
23.13 7.54 14.32 31.09 23.16 8.75 12.12 40.83 30.99 13.36
27.21 7.58 14.85 32.56 27.32 8.78 12.66 31.57 26.94 9.88
12.14 7.85 14.58 32.87 12.36 9.09 12.34 31.51 12.30 10.19
13.31 7.84 14.68 33.08 13.51 9.08 12.43 31.72 13.41 10.18
15.60 7.84 14.73 33.28 15.82 9.11 12.47 31.82 15.58 10.17
17.85 7.84 14.78 33.49 18.09 9.09 12.58 32.14 17.81 10.19
20.41 7.86 14.95 34.02 20.64 9.14 12.70 32.66 20.28 10.24
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
28.25
28.35
29.07
30.51
31.85
30.84
30.95
31.05
31.66
32.99
33.54
33.75
33.85
33.95
34.45

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
25.09
25.34
26.57
27.80
29.02
27.55
27.65
27.96
29.14
30.43
29.97
30.19
30.29
30.72
31.70

46oC
TSH COMP
kW
kWl
19.90 10.21
23.94 10.29
25.31 10.42
26.48 10.51
27.64 10.59
14.83 10.62
17.48 10.64
18.98 10.64
22.53 10.76
26.40 10.79
12.13 11.10
13.20 11.10
15.26 11.09
17.47 11.15
20.14 11.28

GH
kW
37.34
36.36
35.41

15 C
NH COMP EER
kW
kWl
37.34 8.11 15.71
36.36 8.51 14.59
35.41 8.80 13.73

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
20.11
19.42
18.78

-5 C
NH COMP EER
kW
kWl
17.82 5.15 13.33
17.32 5.56 11.93
16.79 5.61 11.42

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
21.62 5.80 14.26 28.91 24.85 6.46 15.26 32.84 32.84 7.14 15.69
20.93 6.06 13.25 28.02 24.04 6.83 13.99 31.90 31.90 7.52 14.48
20.13 6.22 12.40 26.99 23.24 7.00 13.15 30.73 30.73 7.80 13.44
o

GH
kW
24.24
23.54
22.62

YRM 030D R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
27.39
27.60
28.10
29.35
30.42
29.91
30.01
30.20
30.49
31.61
32.46
32.65
32.74
32.93
33.20

24 C
TSH COMP
kW
kWl
21.17 6.48
25.81 6.52
28.10 6.57
29.35 6.60
30.42 6.58
15.10 6.81
18.12 6.79
19.72 6.82
22.92 6.82
26.90 6.86
11.85 7.13
13.03 7.13
15.35 7.12
17.68 7.13
20.15 7.12

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
20.31 7.34 12.21 25.52 20.49 8.45 10.30 24.53 20.07 9.54 8.78
25.05 7.34 12.25 25.80 24.82 8.52 10.33 24.78 24.21 9.62 8.79
27.04 7.46 12.37 26.56 26.56 8.65 10.48 25.63 25.63 9.69 9.03
28.38 7.49 12.92 27.82 27.82 8.67 10.95 26.87 26.87 9.78 9.37
29.62 7.53 13.43 29.07 29.07 8.73 11.36 28.10 28.10 9.87 9.71
14.92 7.67 12.77 28.05 15.01 8.86 10.80 26.83 14.76 9.92 9.23
17.81 7.65 12.83 28.14 17.84 8.86 10.84 27.02 17.54 9.96 9.25
19.29 7.66 12.86 28.43 19.42 8.90 10.90 27.31 19.06 10.00 9.32
22.58 7.71 13.03 28.92 22.61 8.94 11.03 37.97 30.27 13.66 9.49
26.57 7.75 13.51 30.28 26.67 8.97 11.52 29.36 26.31 10.10 9.92
11.85 8.02 13.27 30.57 12.07 9.29 11.23 29.30 12.01 10.41 9.60
12.99 8.02 13.36 30.76 13.20 9.28 11.31 29.50 13.10 10.40 9.67
15.24 8.01 13.41 30.95 15.45 9.31 11.35 29.59 15.21 10.40 9.71
17.43 8.01 13.45 31.15 17.66 9.29 11.45 29.89 17.39 10.42 9.79
19.93 8.03 13.61 31.64 20.15 9.34 11.56 30.38 19.81 10.46 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
26.27
26.37
27.04
28.38
29.62
28.68
28.78
28.87
29.44
30.68
31.20
31.38
31.48
31.57
32.04

GTH
kW
23.33
23.57
24.71
25.85
26.99
25.62
25.71
26.00
27.10
28.30
27.87
28.07
28.17
28.57
29.48

46oC
TSH COMP EER
kW
kWl
19.44 10.43 7.63
23.38 10.51 7.65
24.71 10.65 7.92
25.85 10.74 8.22
26.99 10.82 8.51
14.48 10.85 8.06
17.07 10.87 8.07
18.54 10.88 8.16
22.00 10.99 8.41
25.78 11.03 8.76
11.85 11.34 8.39
12.89 11.35 8.44
14.90 11.33 8.48
17.06 11.40 8.55
19.66 11.52 8.73

GH
kW
34.73
33.81
32.93

15oC
NH COMP
kW
kWl
34.73 8.29
33.81 8.69
32.93 8.99

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

65

GH
kW
18.70
18.06
17.46

-5 C
NH COMP
kW
kWl
16.64 5.26
16.07 5.68
15.54 5.73

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
20.06 5.93 12.97 26.89 23.13 6.61 13.89 30.54 30.54 7.30
19.49 6.19 12.06 26.06 22.41 6.98 12.73 29.67 29.67 7.68
18.72 6.36 11.29 25.10 21.59 7.16 11.97 28.58 28.58 7.97
o

EER
12.13
10.85
10.39

GH
kW
22.54
21.89
21.03

EER
14.28
13.17
12.23

EER
14.29
13.27
12.50

66

YRM 036S R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
34.92
35.04
35.55
37.23
38.81
37.81
38.00
38.11
38.59
39.94
40.84
41.13
41.22
41.32
41.79

24 C
TSH COMP
kW
kWl
26.99 7.52
32.76 7.53
35.55 7.56
37.23 7.62
38.81 7.64
19.09 7.83
22.95 7.83
24.88 7.83
29.02 7.86
33.99 7.89
14.91 8.17
16.41 8.17
19.33 8.16
22.19 8.14
25.37 8.16

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
25.81 8.49 13.42 32.27 25.91 9.72 11.32 30.84 25.23 10.91
31.90 8.51 13.46 32.55 31.31 9.79 11.35 31.09 30.37 10.98
34.17 8.58 13.59 33.63 33.63 9.97 11.51 32.35 32.35 11.12
35.93 8.63 14.20 35.11 35.11 9.96 12.03 33.81 33.81 11.20
37.50 8.67 14.76 36.58 36.58 10.00 12.49 35.26 35.26 11.27
18.82 8.80 14.03 35.33 18.90 10.16 11.86 33.66 18.51 11.32
22.52 8.80 14.10 35.42 22.46 10.15 11.91 33.85 21.97 11.36
24.43 8.83 14.13 35.72 24.40 10.17 11.98 34.04 23.76 11.34
28.42 8.83 14.32 36.31 28.40 10.22 12.12 35.24 28.09 11.53
33.52 8.90 14.85 38.11 33.57 10.27 12.66 36.75 32.93 11.50
14.89 9.17 14.58 38.38 15.16 10.62 12.34 36.55 14.99 11.82
16.30 9.15 14.68 38.58 16.55 10.59 12.43 36.75 16.32 11.80
19.15 9.16 14.73 38.78 19.35 10.61 12.47 36.95 18.99 11.81
21.95 9.18 14.78 38.98 22.10 10.57 12.58 37.25 21.68 11.82
24.97 9.16 14.95 39.47 25.14 10.60 12.70 37.85 24.68 11.86
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
33.39
33.58
34.17
35.93
37.50
36.18
36.38
36.57
37.06
38.71
39.19
39.38
39.57
39.76
40.15

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
29.13
29.46
30.93
32.29
33.74
31.86
32.05
32.55
33.88
35.42
34.75
34.95
35.05
35.47
36.81

46 C
TSH COMP
kW
kWl
24.27 11.85
29.23 11.96
30.93 12.13
32.29 12.20
33.74 12.31
18.00 12.28
21.28 12.33
23.21 12.39
27.51 12.51
32.27 12.56
14.77 12.87
16.04 12.86
18.54 12.83
21.17 12.87
24.55 13.09

GH
kW
47.26
45.95
44.76

15 C
NH COMP EER
kW
kWl
47.26 9.57 16.85
45.95 10.08 15.55
44.76 10.71 14.26

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
25.42
24.53
23.81

-5 C
NH COMP EER
kW
kWl
22.61 6.34 13.69
21.81 6.67 12.56
21.20 6.83 11.89

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
27.27 7.10 14.76 36.53 31.43 7.98 15.62 41.54 41.54 8.67 16.35
26.48 7.37 13.75 35.45 30.52 8.36 14.46 40.30 40.30 9.17 15.00
25.44 7.75 12.62 34.08 30.43 8.76 13.28 38.89 38.89 9.67 13.72
o

GH
kW
30.71
29.72
28.66

YRM 036S R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Single COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
32.47
32.59
33.06
34.62
36.10
35.16
35.34
35.44
35.89
37.14
37.98
38.25
38.34
38.42
38.86

24 C
TSH COMP
kW
kWl
25.10 7.68
30.47 7.70
33.06 7.73
34.62 7.79
36.10 7.81
17.76 8.00
21.35 8.00
23.14 8.00
26.99 8.03
31.61 8.06
13.86 8.35
15.26 8.35
17.98 8.34
20.63 8.32
23.59 8.34

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
24.00 8.68 12.21 30.01 24.10 9.94 10.30 28.68 23.46 11.15 8.78
29.67 8.70 12.25 30.27 29.12 10.00 10.33 28.91 28.25 11.23 8.79
31.78 8.77 12.37 31.27 31.27 10.18 10.48 30.09 30.09 11.37 9.03
33.42 8.82 12.92 32.65 32.65 10.18 10.95 31.44 31.44 11.44 9.37
34.88 8.86 13.43 34.02 34.02 10.22 11.36 32.80 32.80 11.52 9.71
17.50 8.99 12.77 32.86 17.58 10.38 10.80 31.31 17.22 11.57 9.23
20.94 8.99 12.83 32.94 20.89 10.37 10.84 31.48 20.43 11.61 9.25
22.72 9.02 12.86 33.22 22.69 10.39 10.90 31.66 22.10 11.59 9.32
26.43 9.02 13.03 33.77 26.41 10.44 11.03 32.78 26.12 11.79 9.49
31.18 9.09 13.51 35.44 31.22 10.50 11.52 34.17 30.62 11.75 9.92
13.85 9.37 13.27 35.69 14.10 10.85 11.23 33.99 13.94 12.08 9.60
15.16 9.35 13.36 35.88 15.39 10.82 11.31 34.18 15.18 12.05 9.67
17.81 9.37 13.41 36.06 18.00 10.85 11.35 34.36 17.66 12.07 9.71
20.41 9.38 13.45 36.25 20.55 10.81 11.45 34.64 20.16 12.07 9.79
23.22 9.36 13.61 36.71 23.38 10.83 11.56 35.20 22.95 12.12 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
31.05
31.23
31.78
33.42
34.88
33.65
33.83
34.01
34.46
36.00
36.44
36.62
36.80
36.98
37.34

GTH
kW
27.09
27.40
28.77
30.03
31.38
29.63
29.81
30.27
31.51
32.94
32.32
32.51
32.60
32.98
34.23

46oC
TSH COMP
kW
kWl
22.57 12.12
27.18 12.22
28.77 12.39
30.03 12.47
31.38 12.58
16.74 12.55
19.79 12.60
21.58 12.66
25.59 12.78
30.01 12.83
13.73 13.15
14.92 13.14
17.25 13.11
19.69 13.16
22.83 13.38

GH
kW
43.95
42.73
41.63

15oC
NH COMP EER
kW
kWl
43.95 9.78 15.33
42.73 10.30 14.15
41.63 10.94 12.98

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

67

GH
kW
23.64
22.81
22.15

-5 C
NH COMP
kW
kWl
21.04 6.48
20.30 6.81
19.71 6.98

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
25.42 7.26 13.43 33.98 29.22 8.15 14.22 38.64 38.64 8.86
24.60 7.54 12.51 32.97 28.35 8.55 13.16 37.48 37.48 9.37
23.72 7.92 11.48 31.70 27.26 8.95 12.09 36.16 36.16 9.88
o

EER
12.46
11.43
10.82

GH
kW
28.56
27.64
26.66

EER
14.88
13.65
12.48

68

YRM 036D R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
34.14
34.36
34.78
36.55
38.13
36.94
37.14
37.24
37.73
39.27
39.99
40.27
40.46
40.50
40.94

24 C
TSH COMP
kW
kWl
26.39 7.35
32.13 7.39
34.78 7.40
36.55 7.49
38.13 7.51
18.66 7.65
22.43 7.65
24.32 7.65
28.37 7.68
33.42 7.76
14.60 8.00
16.07 8.00
18.98 8.01
21.42 7.98
24.85 7.99

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
25.35 8.34 13.42 31.97 25.67 9.63 11.32 30.84 25.23 10.91
31.44 8.39 13.46 32.24 31.02 9.70 11.35 31.09 30.37 10.98
33.68 8.45 13.59 33.32 33.32 9.88 11.51 32.45 32.45 11.16
35.44 8.51 14.20 34.90 34.90 9.90 12.03 33.91 33.91 11.23
37.01 8.56 14.76 36.48 36.48 9.97 12.49 35.37 35.37 11.30
18.56 8.68 14.03 35.13 18.79 10.10 11.86 33.87 18.63 11.39
22.22 8.68 14.10 35.22 22.33 10.09 11.91 34.05 22.10 11.43
24.11 8.71 14.13 35.52 24.26 10.11 11.98 34.24 23.90 11.41
28.05 8.71 14.32 36.21 28.32 10.19 12.12 35.44 28.25 11.60
33.10 8.78 14.85 38.01 33.49 10.25 12.66 37.05 33.20 11.60
14.71 9.05 14.58 38.28 15.12 10.59 12.34 36.85 15.11 11.92
16.10 9.02 14.68 38.48 16.51 10.56 12.43 37.15 16.50 11.92
18.92 9.05 14.73 38.68 19.30 10.59 12.47 37.25 19.15 11.91
21.68 9.07 14.78 38.88 22.04 10.55 12.58 37.55 21.86 11.91
24.73 9.07 14.95 39.47 25.14 10.60 12.70 38.26 24.94 11.99
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
32.80
33.09
33.68
35.44
37.01
35.70
35.89
36.09
36.57
38.23
38.70
38.80
39.09
39.28
39.76

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
29.66
29.98
31.45
32.91
34.36
32.59
32.78
33.07
34.61
36.15
35.58
35.88
36.09
36.40
37.63

46 C
TSH COMP
kW
kWl
24.70 12.07
29.74 12.17
31.45 12.33
32.91 12.44
34.36 12.54
18.42 12.56
21.77 12.61
23.58 12.59
28.10 12.78
32.93 12.82
15.12 13.17
16.47 13.20
19.09 13.21
21.73 13.21
25.10 13.39

GH
kW
47.15
45.84
44.65

15 C
NH COMP EER
kW
kWl
47.15 8.84 18.20
45.84 9.35 16.74
44.65 9.86 15.46

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
25.31
24.53
23.71

-5 C
NH COMP EER
kW
kWl
22.50 5.94 14.54
21.81 6.16 13.59
21.10 6.43 12.59

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
27.27 6.70 15.59 36.43 31.33 7.47 16.63 41.44 41.44 8.06 17.55
26.37 6.97 14.50 35.34 30.42 7.85 15.35 40.19 40.19 8.55 16.04
25.44 7.24 13.46 33.98 29.29 8.24 14.07 38.78 38.78 8.94 14.79
o

GH
kW
30.61
29.61
28.56

YRM 036D R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
31.75
31.96
32.34
33.99
35.46
34.36
34.54
34.64
35.09
36.52
37.19
37.45
37.63
37.67
38.07

24 C
TSH COMP
kW
kWl
24.54 7.51
29.88 7.55
32.34 7.56
33.99 7.65
35.46 7.67
17.35 7.82
20.86 7.82
22.62 7.82
26.39 7.85
31.08 7.93
13.57 8.17
14.94 8.18
17.65 8.18
20.23 8.16
23.11 8.17

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
23.58 8.52 12.21 29.73 23.87 9.85 10.30 28.68 23.46 11.15 8.78
29.23 8.57 12.25 29.99 28.85 9.91 10.33 28.91 28.25 11.23 8.79
31.32 8.64 12.37 30.99 30.99 10.09 10.48 30.18 30.18 11.40 9.03
32.96 8.70 12.92 32.46 32.46 10.12 10.95 31.54 31.54 11.48 9.37
34.42 8.75 13.43 33.93 33.93 10.19 11.36 32.89 32.89 11.55 9.71
17.26 8.87 12.77 32.67 17.48 10.32 10.80 31.49 17.32 11.64 9.23
20.66 8.87 12.83 32.76 20.77 10.31 10.84 31.67 20.55 11.68 9.25
22.42 8.90 12.86 33.03 22.56 10.34 10.90 31.85 22.23 11.66 9.32
26.09 8.90 13.03 33.68 26.34 10.42 11.03 32.96 26.27 11.86 9.49
30.79 8.98 13.51 35.35 31.14 10.47 11.52 34.46 30.87 11.85 9.92
13.68 9.25 13.27 35.60 14.06 10.82 11.23 34.27 14.05 12.18 9.60
14.94 9.22 13.36 35.79 15.35 10.79 11.31 34.55 15.34 12.19 9.67
17.59 9.25 13.41 35.97 17.95 10.82 11.35 34.65 17.81 12.17 9.71
20.17 9.27 13.45 36.16 20.50 10.78 11.45 34.92 20.33 12.17 9.79
23.00 9.27 13.61 36.71 23.38 10.83 11.56 35.58 23.20 12.25 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
30.50
30.77
31.32
32.96
34.42
33.20
33.38
33.56
34.01
35.55
35.99
36.08
36.35
36.53
36.98

GTH
kW
27.58
27.89
29.25
30.61
31.96
30.31
30.49
30.76
32.19
33.62
33.09
33.37
33.56
33.85
35.00

46oC
TSH COMP
kW
kWl
22.98 12.33
27.66 12.44
29.25 12.60
30.61 12.71
31.96 12.81
17.13 12.84
20.24 12.89
21.93 12.87
26.14 13.06
30.62 13.10
14.06 13.46
15.32 13.49
17.75 13.50
20.21 13.50
23.35 13.68

GH
kW
43.85
42.63
41.53

15oC
NH COMP EER
kW
kWl
43.85 9.03 16.56
42.63 9.55 15.23
41.53 10.07 14.06

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

69

GH
kW
23.54
22.81
22.05

-5 C
NH COMP
kW
kWl
20.95 6.07
20.30 6.30
19.62 6.57

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
25.34 6.85 14.18 33.88 29.14 7.64 15.13 38.54 38.54 8.24
24.51 7.12 13.19 32.87 28.27 8.03 13.97 37.38 37.38 8.74
23.64 7.40 12.24 31.60 27.18 8.42 12.80 36.07 36.07 9.14
o

EER
13.23
12.36
11.46

GH
kW
28.47
27.54
26.56

EER
15.97
14.60
13.46

70

YRM 044 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
41.59
41.82
42.63
44.99
46.96
45.18
45.37
45.57
46.16
48.27
49.20
49.39
49.58
49.77
50.15

24 C
TSH COMP
kW
kWl
32.15 8.96
39.10 8.99
42.63 9.07
44.99 9.21
46.96 9.25
22.81 9.36
27.41 9.35
29.76 9.36
34.71 9.40
41.08 9.53
17.96 9.84
19.71 9.81
23.25 9.81
26.73 9.81
30.44 9.79

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
30.82 10.14 13.42 38.60 31.00 11.63 11.32 36.97 30.24 13.08
38.24 10.20 13.46 38.97 37.49 11.72 11.35 37.51 36.65 13.25
41.43 10.40 13.59 40.55 40.55 12.02 11.51 39.06 39.06 13.43
43.40 10.42 14.20 42.33 42.33 12.01 12.03 40.82 40.82 13.52
45.36 10.49 14.76 44.30 44.30 12.11 12.49 42.56 42.56 13.60
22.56 10.55 14.03 42.24 22.60 12.15 11.86 40.35 22.20 13.57
26.97 10.54 14.10 42.63 27.03 12.21 11.91 40.54 26.31 13.60
29.24 10.57 14.13 42.82 29.25 12.19 11.98 40.93 28.57 13.64
34.17 10.61 14.32 43.62 34.11 12.27 12.12 42.53 33.90 13.92
40.60 10.77 14.85 46.01 40.53 12.41 12.66 44.34 39.73 13.88
17.90 11.02 14.58 46.06 18.19 12.74 12.34 43.70 17.92 14.13
19.58 10.99 14.68 46.25 19.84 12.70 12.43 44.10 19.58 14.15
22.98 11.00 14.73 46.45 23.18 12.71 12.47 44.30 22.77 14.16
26.32 11.01 14.78 46.85 26.56 12.71 12.58 44.70 26.02 14.18
30.01 11.01 14.95 47.65 30.35 12.80 12.70 46.11 30.06 14.45
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
39.87
40.26
41.43
43.40
45.36
43.38
43.58
43.77
44.55
46.88
47.10
47.29
47.49
47.68
48.26

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
35.21
35.73
37.49
39.04
40.58
38.32
38.50
38.90
40.95
42.59
41.37
41.78
41.78
42.39
44.25

46 C
TSH COMP
kW
kWl
29.33 14.33
35.44 14.51
37.49 14.70
39.04 14.76
40.58 14.80
21.65 14.77
25.57 14.81
27.73 14.81
33.25 15.12
38.80 15.10
17.58 15.32
19.18 15.37
22.10 15.29
25.31 15.39
29.52 15.74

GH
kW
56.54
55.01
53.58

15 C
NH COMP EER
kW
kWl
56.54 11.44 16.86
55.01 12.39 15.15
53.58 13.36 13.69

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
30.42
29.44
28.54

-5 C
NH COMP EER
kW
kWl
27.09 7.52 13.79
26.09 8.08 12.43
25.40 8.57 11.36

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
32.80 8.60 14.59 43.84 37.70 9.49 15.76 49.73 49.73 10.40 16.31
31.81 8.08 15.02 42.45 36.48 10.20 14.20 48.27 48.27 11.12 14.81
30.45 9.79 11.91 40.86 35.12 10.92 12.77 46.62 46.62 11.86 13.42
o

GH
kW
36.77
35.57
34.19

YRM 044 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
38.68
38.89
39.64
41.84
43.68
42.01
42.20
42.38
42.93
44.89
45.76
45.93
46.11
46.29
46.64

24 C
TSH COMP
kW
kWl
29.90 9.15
36.36 9.19
39.64 9.27
41.84 9.41
43.68 9.45
21.22 9.56
25.49 9.55
27.68 9.57
32.28 9.60
38.20 9.74
16.70 10.05
18.33 10.03
21.62 10.03
24.86 10.02
28.31 10.01

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
28.66 10.36 12.21 35.90 28.83 11.89 10.30 34.38 28.12 13.37 8.78
35.57 10.43 12.25 36.25 34.87 11.98 10.33 34.88 34.08 13.55 8.79
38.53 10.63 12.37 37.71 37.71 12.28 10.48 36.33 36.33 13.73 9.03
40.36 10.65 12.92 39.36 39.36 12.27 10.95 37.96 37.96 13.82 9.37
42.18 10.72 13.43 41.20 41.20 12.37 11.36 39.58 39.58 13.90 9.71
20.98 10.78 12.77 39.28 21.01 12.41 10.80 37.53 20.64 13.87 9.23
25.09 10.77 12.83 39.65 25.14 12.48 10.84 37.70 24.47 13.90 9.25
27.19 10.80 12.86 39.83 27.20 12.46 10.90 38.06 26.57 13.94 9.32
31.78 10.85 13.03 40.56 31.72 12.54 11.03 39.56 31.53 14.23 9.49
37.76 11.01 13.51 42.79 37.70 12.68 11.52 41.24 36.95 14.18 9.92
16.65 11.26 13.27 42.83 16.92 13.02 11.23 40.64 16.66 14.44 9.60
18.21 11.23 13.36 43.02 18.45 12.98 11.31 41.01 18.21 14.47 9.67
21.37 11.24 13.41 43.20 21.56 12.99 11.35 41.20 21.18 14.47 9.71
24.48 11.25 13.45 43.57 24.71 12.99 11.45 41.57 24.20 14.49 9.79
27.91 11.25 13.61 44.31 28.23 13.08 11.56 42.88 27.96 14.77 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
37.08
37.44
38.53
40.36
42.18
40.34
40.53
40.71
41.43
43.60
43.80
43.98
44.16
44.34
44.88

GTH
kW
32.75
33.23
34.87
36.31
37.73
35.64
35.81
36.17
38.08
39.60
38.47
38.85
38.85
39.43
41.15

46oC
TSH COMP
kW
kWl
27.28 14.64
32.96 14.82
34.87 15.02
36.31 15.08
37.73 15.13
20.14 15.09
23.78 15.14
25.79 15.13
30.92 15.45
36.08 15.43
16.35 15.65
17.83 15.71
20.55 15.63
23.54 15.72
27.45 16.09

GH
kW
52.58
51.16
49.83

15oC
NH COMP EER
kW
kWl
52.58 11.69 15.34
51.16 12.66 13.79
49.83 13.65 12.46

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

71

GH
kW
28.29
27.38
26.54

-5 C
NH COMP
kW
kWl
25.18 7.69
24.36 8.26
23.62 8.76

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
30.44 8.79 13.28 40.77 35.06 9.70 14.34 46.25 46.25 10.63
29.44 8.26 13.67 39.48 33.95 10.42 12.92 44.90 44.90 11.37
28.30 10.01 10.84 38.00 32.68 11.16 11.62 43.36 43.36 12.12
o

EER
12.55
11.31
10.34

GH
kW
34.20
33.08
31.79

EER
14.84
13.47
12.21

72

YRM 054 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
51.65
51.88
52.51
54.29
56.47
55.70
55.90
56.11
56.50
57.85
59.84
60.22
60.41
60.60
61.17

24 C
TSH COMP
kW
kWl
39.92 11.12
48.51 11.15
52.51 11.17
54.29 11.12
56.47 11.12
28.13 11.54
33.77 11.52
36.64 11.52
42.49 11.50
49.23 11.43
21.84 11.96
24.03 11.96
28.33 11.96
32.54 11.94
37.13 11.94

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
38.10 12.53 13.42 47.85 38.42 14.42 11.32 45.96 37.59 16.26
47.20 12.59 13.46 48.22 46.38 14.50 11.35 46.27 45.21 16.35
50.27 12.62 13.59 49.18 49.18 14.58 11.51 47.61 47.61 16.37
52.43 12.59 14.20 51.35 51.35 14.57 12.03 49.75 49.75 16.48
54.59 12.62 14.76 53.72 53.72 14.68 12.49 52.09 52.09 16.65
27.82 13.01 14.03 52.24 27.95 15.02 11.86 50.29 27.66 16.92
33.23 12.99 14.10 52.64 33.37 15.08 11.91 50.47 32.76 16.94
36.13 13.06 14.13 53.03 36.22 15.10 11.98 51.06 35.64 17.01
41.93 13.02 14.32 53.62 41.93 15.09 12.12 52.05 41.49 17.04
48.85 12.96 14.85 55.81 49.17 15.05 12.66 54.46 48.80 17.05
21.93 13.50 14.58 57.02 22.52 15.77 12.34 54.78 22.46 17.71
24.05 13.50 14.68 57.42 24.63 15.76 12.43 55.18 24.50 17.71
28.21 13.50 14.73 57.62 28.75 15.77 12.47 55.58 28.57 17.77
32.39 13.55 14.78 58.02 32.89 15.74 12.58 55.98 32.58 17.75
36.86 13.52 14.95 58.81 37.46 15.79 12.70 56.78 37.02 17.80
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
49.29
49.68
50.27
52.43
54.59
53.50
53.69
54.08
54.66
56.41
57.72
58.10
58.29
58.68
59.26

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
43.81
44.30
46.03
48.18
50.51
48.32
48.70
49.30
50.72
53.18
53.16
53.57
53.77
54.39
55.63

46 C
TSH COMP
kW
kWl
36.49 17.82
43.94 17.98
46.03 18.04
48.18 18.21
50.51 18.43
27.30 18.62
32.34 18.74
35.15 18.77
41.18 18.72
48.45 18.85
22.59 19.68
24.59 19.71
28.44 19.68
32.47 19.74
37.10 19.79

GH
kW
70.25
68.29
66.61

15 C
NH COMP EER
kW
kWl
70.25 141.44 1.69
68.29 14.91 15.63
66.61 15.90 14.29

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
37.71
36.53
35.46

-5 C
NH COMP EER
kW
kWl
33.55 9.11 14.13
32.56 9.49 13.13
31.49 9.59 12.62

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
40.53 10.40 14.94 54.28 46.78 11.72 15.81 61.69 61.69 12.85 16.38
39.35 10.71 14.07 52.70 45.36 12.24 14.69 60.03 60.03 13.39 15.30
37.85 11.22 12.93 50.65 43.57 12.77 13.53 57.91 57.91 13.94 14.18
o

GH
kW
45.55
44.15
42.53

YRM 054 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
48.03
48.25
48.83
50.49
52.52
51.80
51.99
52.18
52.54
53.80
55.65
56.00
56.18
56.35
56.88

24 C
TSH COMP
kW
kWl
37.13 11.37
45.12 11.40
48.83 11.41
50.49 11.36
52.52 11.36
26.16 11.79
31.40 11.77
34.07 11.78
39.51 11.75
45.79 11.68
20.31 12.23
22.34 12.23
26.35 12.22
30.26 12.20
34.53 12.21

3000 l/s
OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC
30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
35.44 12.81 12.21 44.50 35.73 14.74 10.30 42.74 34.96 16.62 8.78
43.90 12.87 12.25 44.84 43.14 14.82 10.33 43.04 42.05 16.71 8.79
46.75 12.90 12.37 45.74 45.74 14.90 10.48 44.28 44.28 16.73 9.03
48.76 12.87 12.92 47.76 47.76 14.89 10.95 46.27 46.27 16.84 9.37
50.77 12.90 13.43 49.96 49.96 15.00 11.36 48.44 48.44 17.02 9.71
25.87 13.30 12.77 48.59 25.99 15.36 10.80 46.77 25.72 17.29 9.23
30.91 13.27 12.83 48.95 31.04 15.41 10.84 46.94 30.46 17.31 9.25
33.60 13.34 12.86 49.32 33.68 15.43 10.90 47.49 33.15 17.39 9.32
38.99 13.31 13.03 49.87 39.00 15.42 11.03 48.41 38.58 17.41 9.49
45.44 13.25 13.51 51.91 45.73 15.38 11.52 50.65 45.38 17.42 9.92
20.40 13.80 13.27 53.03 20.95 16.12 11.23 50.94 20.89 18.10 9.60
22.37 13.80 13.36 53.40 22.91 16.11 11.31 51.31 22.78 18.10 9.67
26.24 13.80 13.41 53.58 26.74 16.12 11.35 51.69 26.57 18.16 9.71
30.12 13.85 13.45 53.95 30.59 16.08 11.45 52.06 30.30 18.14 9.79
34.28 13.82 13.61 54.70 34.84 16.14 11.56 52.81 34.43 18.19 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
45.84
46.21
46.75
48.76
50.77
49.75
49.93
50.29
50.84
52.47
53.68
54.04
54.21
54.57
55.11

GTH
kW
40.74
41.20
42.81
44.80
46.98
44.94
45.29
45.85
47.17
49.46
49.44
49.82
50.01
50.58
51.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

73

GH
kW
35.07
33.98
32.98

-5 C
NH COMP
kW
kWl
31.21 9.31
30.24 9.70
29.35 9.80

12.86
11.95
11.48

GH
kW
42.36
41.06
39.55

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

3000 l/s
OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC
0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
37.70 10.63 13.60 50.48 43.41 11.97 14.38 57.37 57.37 13.13
36.55 10.94 12.81 49.01 42.15 12.51 13.37 55.83 55.83 13.68
35.20 11.47 11.77 47.11 40.51 13.05 12.31 53.86 53.86 14.24
o

EER

46oC
TSH COMP
kW
kWl
33.94 18.22
40.87 18.38
42.81 18.44
44.80 18.61
46.98 18.84
25.39 19.03
30.08 19.15
32.69 19.18
38.30 19.13
45.06 19.27
21.01 20.11
22.87 20.14
26.45 20.12
30.20 20.17
34.50 20.22

EER
14.90
13.92
12.90

GH
kW
65.33
63.51
61.95

15oC
NH COMP EER
kW
kWl
65.33 144.55 1.54
63.51 15.24 14.22
61.95 16.25 13.01

74

YRM 060 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
58.42
58.66
59.48
61.86
64.62
63.36
63.56
63.77
64.54
66.28
68.58
68.96
69.14
69.33
69.90

24 C
TSH COMP
kW
kWl
45.16 12.58
54.85 12.61
59.48 12.65
61.86 12.67
64.62 12.72
32.00 13.12
38.39 13.10
41.64 13.10
48.54 13.14
56.40 13.09
25.03 13.71
27.51 13.70
32.43 13.69
37.23 13.66
42.43 13.65

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
55.77
55.97
57.14
59.69
62.24
60.50
60.89
61.08
61.67
64.20
65.44
65.82
66.21
66.21
66.98

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
43.11 14.18 13.42 53.88 43.27 16.24 11.32 51.47 42.10 18.21
53.17 14.19 13.46 54.24 52.18 16.31 11.35 51.98 50.79 18.37
57.14 14.34 13.59 55.41 55.41 16.42 11.51 53.51 53.51 18.40
59.69 14.34 14.20 58.17 58.17 16.50 12.03 55.84 55.84 18.50
62.24 14.39 14.76 60.54 60.54 16.54 12.49 58.17 58.17 18.59
31.46 14.71 14.03 58.85 31.48 16.92 11.86 55.97 30.78 18.83
37.69 14.73 14.10 59.04 37.43 16.91 11.91 56.35 36.57 18.91
40.80 14.75 14.13 59.63 40.73 16.98 11.98 56.73 39.60 18.90
47.30 14.69 14.32 60.62 47.41 17.06 12.12 57.93 46.17 18.96
55.59 14.75 14.85 63.01 55.52 16.99 12.66 60.74 54.42 19.01
24.87 15.31 14.58 64.00 25.28 17.70 12.34 60.62 24.85 19.60
27.25 15.30 14.68 64.20 27.54 17.62 12.43 61.02 27.09 19.58
32.05 15.33 14.73 64.60 32.23 17.68 12.47 61.22 31.47 19.57
36.55 15.29 14.78 64.79 36.74 17.58 12.58 61.82 35.98 19.61
41.66 15.28 14.95 65.59 41.78 17.61 12.70 62.82 40.96 19.69

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
48.63
49.10
51.03
53.37
55.48
52.90
53.28
53.87
55.71
58.17
29.16
37.02
44.88
53.15
60.38

46 C
TSH COMP
kW
kWl
40.51 19.79
48.71 19.93
51.03 20.00
53.37 20.17
55.48 20.24
29.89 20.39
35.38 20.50
38.41 20.51
45.24 20.56
52.99 20.62
12.39 10.80
16.99 13.62
23.74 16.43
31.73 19.29
40.27 21.48

GH
kW
78.90
76.72
74.81

15 C
NH COMP EER
kW
kWl
78.90 16.22 16.59
76.72 17.22 15.20
74.81 18.44 13.84

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
42.29
40.92
39.66

-5 C
NH COMP EER
kW
kWl
37.71 10.49 13.75
36.52 10.91 12.80
35.47 11.42 11.84

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
45.55 11.80 14.80 60.96 52.42 13.13 15.84 69.45 69.45 14.48 16.36
44.16 12.32 13.73 59.18 50.80 14.08 14.35 67.38 67.38 15.45 14.88
42.55 13.06 12.48 56.91 48.99 14.63 13.28 65.02 65.02 16.22 13.67
o

GH
kW
51.19
49.59
47.74

YRM 060 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
54.33
54.55
55.32
57.53
60.10
58.92
59.11
59.30
60.03
61.64
63.78
64.13
64.30
64.48
65.01

24 C
TSH COMP
kW
kWl
42.00 12.86
51.01 12.89
55.32 12.93
57.53 12.95
60.10 13.00
29.76 13.41
35.70 13.38
38.72 13.38
45.14 13.43
52.46 13.38
23.28 14.01
25.59 14.00
30.16 13.99
34.63 13.96
39.46 13.95

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
40.10 14.49 12.21 50.11 40.24 16.59 10.30 47.87 39.16 18.61 8.78
49.45 14.50 12.25 50.45 48.53 16.67 10.33 48.34 47.23 18.77 8.79
53.14 14.66 12.37 51.53 51.53 16.78 10.48 49.76 49.76 18.81 9.03
55.52 14.66 12.92 54.10 54.10 16.86 10.95 51.93 51.93 18.90 9.37
57.89 14.71 13.43 56.30 56.30 16.91 11.36 54.10 54.10 19.00 9.71
29.26 15.04 12.77 54.73 29.28 17.30 10.80 52.05 28.63 19.24 9.23
35.05 15.05 12.83 54.91 34.81 17.28 10.84 52.41 34.01 19.32 9.25
37.95 15.07 12.86 55.46 37.88 17.35 10.90 52.76 36.83 19.32 9.32
43.99 15.01 13.03 56.38 44.09 17.44 11.03 53.87 42.94 19.37 9.49
51.70 15.08 13.51 58.60 51.63 17.36 11.52 56.49 50.61 19.43 9.92
23.13 15.65 13.27 59.52 23.51 18.09 11.23 56.37 23.11 20.03 9.60
25.34 15.63 13.36 59.70 25.61 18.01 11.31 56.75 25.20 20.01 9.67
29.80 15.67 13.41 60.07 29.98 18.07 11.35 56.93 29.26 20.00 9.71
33.99 15.63 13.45 60.26 34.17 17.96 11.45 57.49 33.46 20.04 9.79
38.74 15.62 13.61 61.00 38.86 18.00 11.56 58.42 38.09 20.12 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
51.87
52.05
53.14
55.52
57.89
56.27
56.63
56.81
57.35
59.70
60.86
61.22
61.57
61.57
62.29

GTH
kW
45.22
45.67
47.46
49.63
51.60
49.20
49.55
50.10
51.81
54.09
27.12
34.43
41.74
49.43
56.15

46oC
TSH COMP
kW
kWl
37.67 20.22
45.30 20.37
47.46 20.44
49.63 20.61
51.60 20.69
27.80 20.83
32.90 20.95
35.72 20.96
42.07 21.01
49.28 21.08
11.53 11.04
15.80 13.92
22.08 16.79
29.51 19.71
37.46 21.95

GH
kW
73.38
71.35
69.57

15oC
NH COMP EER
kW
kWl
73.38 16.58 15.10
71.35 17.60 13.83
69.57 18.85 12.59

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

75

GH
kW
39.33
38.05
36.88

-5 C
NH COMP
kW
kWl
35.01 10.72
33.87 11.15
32.82 11.68

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
42.37 12.06 13.47 56.69 48.76 13.42 14.42 64.59 64.59 14.80
41.05 12.59 12.50 55.04 47.33 14.39 13.05 62.66 62.66 15.79
39.51 13.34 11.35 52.92 45.51 14.95 12.08 60.47 60.47 16.58
o

EER
12.51
11.65
10.78

GH
kW
47.61
46.12
44.40

EER
14.89
13.54
12.44

76

YRM 072 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
69.83
70.08
71.11
74.46
77.63
75.61
76.01
76.21
77.18
79.88
81.68
82.25
82.44
82.63
83.58

24 C
TSH COMP
kW
kWl
53.98 15.04
65.53 15.07
71.11 15.12
74.46 15.25
77.63 15.28
38.18 15.66
45.91 15.66
49.77 15.65
58.04 15.71
67.98 15.78
29.81 16.33
32.82 16.34
38.67 16.32
44.37 16.28
50.73 16.32

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
51.61 16.98 13.42 64.54 51.82 19.45 11.32 61.68 50.46 21.82
63.80 17.02 13.46 65.09 62.62 19.57 11.35 62.17 60.74 21.97
68.34 17.15 13.59 67.25 67.25 19.93 11.51 64.70 64.70 22.25
71.87 17.26 14.20 70.21 70.21 19.92 12.03 67.62 67.62 22.40
75.01 17.34 14.76 73.17 73.17 19.99 12.49 70.53 70.53 22.54
37.63 17.60 14.03 70.66 37.80 20.32 11.86 67.33 37.03 22.65
45.04 17.60 14.10 70.85 44.92 20.29 11.91 67.70 43.94 22.72
48.86 17.66 14.13 71.44 48.79 20.34 11.98 68.08 47.52 22.69
56.85 17.66 14.32 72.63 56.79 20.44 12.12 70.48 56.18 23.07
67.05 17.79 14.85 76.22 67.15 20.55 12.66 73.49 65.85 23.00
29.78 18.33 14.58 76.76 30.32 21.23 12.34 73.10 29.97 23.64
32.61 18.30 14.68 77.16 33.10 21.18 12.43 73.50 32.64 23.59
38.30 18.33 14.73 77.55 38.70 21.22 12.47 73.90 37.99 23.63
43.90 18.36 14.78 77.95 44.20 21.15 12.58 74.50 43.36 23.63
49.94 18.32 14.95 78.95 50.29 21.20 12.70 75.71 49.36 23.73
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
66.77
67.16
68.34
71.87
75.01
72.37
72.76
73.14
74.12
77.42
78.37
78.76
79.14
79.53
80.30

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
58.27
58.92
61.87
64.58
67.49
63.73
64.10
65.10
67.76
70.84
69.50
69.91
70.11
70.93
73.62

46 C
TSH COMP
kW
kWl
48.54 23.71
58.45 23.92
61.87 24.25
64.58 24.41
67.49 24.62
36.01 24.56
42.57 24.66
46.42 24.78
55.02 25.01
64.53 25.12
29.54 25.73
32.09 25.72
37.09 25.67
42.35 25.74
49.10 26.19

GH
kW
94.51
91.89
89.52

15 C
NH COMP EER
kW
kWl
94.51 19.14 16.85
91.89 20.16 15.55
89.52 21.41 14.26

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
50.84
49.06
47.63

-5 C
NH COMP EER
kW
kWl
45.22 12.67 13.69
43.62 13.33 12.56
42.40 13.67 11.89

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
0C
5C
10 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
54.53 14.20 14.76 73.07 62.86 15.96 15.62 83.09 83.09 17.34 16.35
52.95 14.71 13.79 70.89 61.04 16.73 14.46 80.60 80.60 18.33 15.00
50.89 15.50 12.62 68.16 58.78 17.51 13.28 77.77 19.44 19.34 13.72
o

GH
kW
61.43
59.43
57.33

YRM 072 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
64.94
65.18
66.13
69.25
72.19
70.32
70.69
70.88
71.78
74.29
75.97
76.50
76.67
76.85
77.73

24 C
TSH COMP
kW
kWl
50.20 15.37
60.94 15.40
66.13 15.46
69.25 15.58
72.19 15.62
35.51 16.00
42.70 16.01
46.28 16.00
53.98 16.06
63.22 16.12
27.73 16.69
30.52 16.70
35.96 16.68
41.27 16.64
47.18 16.68

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
48.00 17.35 12.21 60.02 48.19 19.88 10.30 57.36 46.92 22.30 8.78
59.34 17.40 12.25 60.53 58.23 20.00 10.33 57.82 56.49 22.45 8.79
63.55 17.53 12.37 62.54 62.54 20.37 10.48 60.17 60.17 22.74 9.03
66.84 17.64 12.92 65.30 65.30 20.35 10.95 62.89 62.89 22.89 9.37
69.76 17.72 13.43 68.04 68.04 20.43 11.36 65.59 65.59 23.04 9.71
35.00 17.99 12.77 65.71 35.16 20.77 10.80 62.61 34.44 23.14 9.23
41.88 17.99 12.83 65.89 41.77 20.74 10.84 62.96 40.86 23.22 9.25
45.44 18.05 12.86 66.44 45.38 20.79 10.90 63.32 44.19 23.18 9.32
52.87 18.05 13.03 67.54 52.82 20.89 11.03 65.55 52.24 23.58 9.49
62.36 18.18 13.51 70.88 62.45 21.00 11.52 68.35 61.24 23.51 9.92
27.70 18.74 13.27 71.39 28.20 21.70 11.23 67.99 27.87 24.16 9.60
30.32 18.71 13.36 71.76 30.78 21.65 11.31 68.36 30.35 24.11 9.67
35.62 18.73 13.41 72.13 35.99 21.69 11.35 68.73 35.33 24.15 9.71
40.83 18.77 13.45 72.50 41.11 21.61 11.45 69.29 40.33 24.15 9.79
46.45 18.72 13.61 73.42 46.77 21.67 11.56 70.41 45.91 24.25 9.91
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
62.10
62.46
63.55
66.84
69.76
67.30
67.66
68.02
68.93
72.00
72.89
73.24
73.60
73.96
74.68

GTH
kW
54.19
54.80
57.53
60.06
62.76
59.27
59.62
60.55
63.02
65.88
64.63
65.01
65.20
65.97
68.46

46oC
TSH COMP
kW
kWl
45.14 24.23
54.36 24.45
57.53 24.78
60.06 24.95
62.76 25.17
33.49 25.10
39.59 25.20
43.17 25.33
51.17 25.56
60.02 25.67
27.47 26.30
29.84 26.28
34.49 26.23
39.38 26.31
45.66 26.76

GH
kW
87.90
85.46
83.25

15oC
NH COMP EER
kW
kWl
87.90 19.56 15.33
85.46 20.60 14.15
83.25 21.88 12.98

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

77

GH
kW
47.28
45.63
44.29

-5 C
NH COMP
kW
kWl
42.08 12.95
40.61 13.63
39.42 13.97

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
50.84 14.51 13.43 67.95 58.44 16.31 14.22 77.27 77.27 17.72
49.19 15.03 12.55 65.93 56.70 17.10 13.16 74.96 74.96 18.74
47.45 15.84 11.48 63.39 54.52 17.89 12.09 72.33 72.33 19.77
o

EER
12.46
11.43
10.82

GH
kW
57.13
55.27
53.31

EER
14.88
13.65
12.48

78

YRM 088 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
92.58
92.75
93.87
99.19
103.11
101.99
102.56
103.01
104.00
108.69
111.17
112.01
112.54
112.85
114.01

24 C
TSH COMP
kW
kWl
71.57 18.89
86.73 19.02
93.87 19.14
99.19 19.27
103.11 19.40
51.51 19.83
61.94 19.88
67.27 19.93
78.21 19.98
92.50 20.03
40.58 20.83
44.69 20.83
52.78 20.83
60.60 20.83
69.21 20.84

EER
16.72
16.64
16.73
17.56
18.13
17.55
17.60
17.63
17.76
18.51
18.21
18.35
18.43
18.48
18.67

GTH
kW
87.00
87.30
89.07
94.20
98.04
95.69
96.05
96.40
98.35
103.15
104.32
105.06
105.48
105.79
107.06

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
67.25 21.65 13.71 81.93 65.79 25.15 11.12 76.52 62.59 28.70
82.93 21.79 13.67 82.56 79.43 25.31 11.13 77.17 75.39 28.88
89.07 21.93 13.86 85.83 85.83 25.46 11.50 81.09 81.09 29.07
94.20 22.07 14.56 89.60 89.60 25.63 11.93 84.56 84.56 29.26
98.04 22.21 15.06 93.25 93.25 25.79 12.34 88.13 88.13 29.45
49.76 22.57 14.46 90.18 48.25 26.10 11.79 84.00 46.20 29.70
59.45 22.63 14.48 90.54 57.40 26.16 11.81 84.69 54.96 29.77
64.40 22.68 14.50 91.22 62.31 26.22 11.87 85.27 59.52 29.84
75.43 22.73 14.76 92.86 72.61 26.28 12.06 88.92 70.87 29.91
89.33 22.79 15.45 98.19 86.51 26.34 12.72 92.67 83.04 29.98
39.64 23.56 15.11 97.97 38.70 27.14 12.32 91.49 37.51 30.82
43.49 23.56 15.21 98.60 42.30 27.14 12.40 92.01 40.85 30.82
51.05 23.56 15.27 99.24 49.52 27.14 12.48 92.43 47.51 30.82
58.40 23.57 15.32 99.98 56.69 27.14 12.57 93.38 54.35 30.83
66.59 23.57 15.50 101.56 64.70 27.15 12.76 96.66 63.03 30.83

EER
9.10
9.12
9.52
9.86
10.21
9.65
9.71
9.75
10.14
10.55
10.13
10.19
10.23
10.34
10.70

GTH
kW
69.89
70.89
74.72
78.01
81.28
76.40
77.09
77.68
82.07
85.51
83.03
83.56
83.88
84.93
89.06

46 C
TSH COMP
kW
kWl
58.22 31.84
70.32 32.06
74.72 32.28
78.01 32.50
81.28 32.73
43.16 32.91
51.19 32.99
55.39 33.07
66.64 33.15
77.90 33.22
35.29 34.12
38.35 34.12
44.37 34.13
50.71 34.13
59.40 34.14

EER
7.49
7.55
7.90
8.19
8.47
7.92
7.97
8.02
8.45
8.78
8.30
8.36
8.39
8.49
8.90

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
61.25
59.29
57.39

-5 C
NH COMP EER
kW
kWl
54.49 13.56 15.41
52.70 14.24 14.21
51.11 14.89 13.15

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
0C
5C
10 C
15 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
65.92 14.90 16.96 88.10 75.81 16.46 18.26 100.19 100.19 17.75 19.26 114.13 114.13 19.55 19.92
63.94 15.66 15.64 85.53 73.48 17.34 16.83 97.39 97.39 18.95 17.53 110.97 110.97 20.90 18.12
61.52 16.52 14.25 82.34 70.77 18.33 15.32 93.97 93.97 20.07 15.97 108.01 108.01 22.79 16.17
o

GH
kW
74.07
71.78
69.00

YRM 088 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
86.10
86.26
87.30
92.25
95.89
94.85
95.38
95.80
96.72
101.08
103.39
104.17
104.66
104.95
106.03

24 C
TSH COMP
kW
kWl
66.56 19.30
80.65 19.43
87.30 19.57
92.25 19.70
95.89 19.83
47.90 20.27
57.61 20.32
62.56 20.37
72.73 20.42
86.02 20.47
37.74 21.28
41.56 21.29
49.09 21.29
56.36 21.29
64.36 21.29

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH TSH COMP EER GTH TSH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
62.55 22.13 12.48 76.20 61.18 25.70 10.12 71.16 58.21 29.33 8.28
77.13 22.27 12.44 76.78 73.87 25.86 10.13 71.77 70.12 29.52 8.30
82.84 22.41 12.61 79.82 79.82 26.02 10.47 75.41 75.41 29.71 8.66
87.60 22.56 13.25 83.33 83.33 26.19 10.86 78.65 78.65 29.90 8.97
91.17 22.70 13.70 86.72 86.72 26.35 11.23 81.96 81.96 30.09 9.29
46.27 23.07 13.16 83.87 44.87 26.67 10.73 78.12 42.97 30.36 8.78
55.29 23.12 13.18 84.20 53.39 26.73 10.75 78.76 51.12 30.43 8.83
59.89 23.18 13.20 84.84 57.94 26.79 10.80 79.30 55.35 30.50 8.87
70.15 23.23 13.43 86.36 67.53 26.86 10.97 82.70 65.91 30.56 9.23
83.07 23.29 14.06 91.32 80.45 26.92 11.58 86.19 77.22 30.63 9.60
36.87 24.08 13.75 91.11 35.99 27.73 11.21 85.08 34.88 31.49 9.22
40.45 24.08 13.84 91.70 39.34 27.74 11.28 85.57 37.99 31.50 9.27
47.48 24.08 13.90 92.29 46.05 27.74 11.35 85.96 44.19 31.50 9.31
54.31 24.08 13.94 92.98 52.72 27.74 11.44 86.85 50.55 31.50 9.41
61.93 24.09 14.10 94.45 60.17 27.74 11.62 89.90 58.61 31.51 9.74
o

EER
15.22
15.14
15.22
15.98
16.50
15.97
16.02
16.05
16.16
16.85
16.57
16.70
16.77
16.82
16.99

GTH
kW
80.91
81.19
82.84
87.60
91.17
88.99
89.32
89.66
91.47
95.93
97.02
97.70
98.09
98.39
99.57

GTH
kW
65.00
65.92
69.49
72.55
75.59
71.05
71.70
72.24
76.33
79.53
77.22
77.71
78.01
78.99
82.82

46oC
TSH COMP
kW
kWl
54.15 32.53
65.40 32.76
69.49 32.99
72.55 33.21
75.59 33.44
40.14 33.63
47.61 33.71
51.51 33.79
61.98 33.87
72.45 33.95
32.82 34.87
35.67 34.87
41.27 34.88
47.16 34.88
55.24 34.89

EER
6.82
6.87
7.19
7.45
7.71
7.21
7.26
7.29
7.69
7.99
7.56
7.60
7.63
7.73
8.10

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

79

GH
kW
56.97
55.14
53.37

-5 C
NH COMP
kW
kWl
50.70 13.86
49.07 14.55
47.50 15.22

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
61.31 15.23 15.43 81.93 70.46 16.82 16.62 93.18 93.18 18.14
59.41 16.00 14.24 79.54 68.41 17.72 15.32 90.57 90.57 19.37
57.11 16.89 12.97 76.57 65.85 18.74 13.94 87.39 87.39 20.51
o

EER
14.02
12.93
11.96

GH
kW
68.88
66.75
64.17

15oC
EER
GH
NH COMP EER
kW
kW
kWl
17.53 106.14 106.14 19.98 18.12
15.96 103.20 103.20 21.35 16.49
14.54 100.45 100.45 23.29 14.72

80

YRM 108 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
106.50
107.00
108.70
112.70
117.60
117.10
117.80
118.30
119.50
122.00
128.10
128.90
129.50
129.90
131.20

24 C
TSH COMP
kW
kWl
75.10 28.60
88.40 28.60
102.20 28.80
112.70 29.50
117.60 30.10
68.20 29.90
81.30 30.00
94.90 30.10
108.40 30.20
120.50 30.70
60.60 31.50
74.10 31.50
87.40 31.50
100.90 31.60
114.60 31.80

LWB
o
C
10.20
10.20
10.10
9.80
9.40
13.40
13.30
13.30
13.20
13.00
16.60
16.50
16.40
16.40
16.30

GTH
kW
100.30
101.20
102.50
107.20
111.90
65.40
78.00
92.40
105.10
116.70
57.70
71.20
84.10
98.00
111.20

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP LWB GTH
TSH COMP LWB GTH
TSH COMP
o
o
kW
kWl
kW
kW
kWl
kW
kW
kWl
C
C
72.10 30.50 10.60 94.70 69.20 32.40 10.90 88.90 66.60 34.30
85.90 30.60 10.50 95.60 82.70 32.60 10.80 89.80 80.00 34.50
98.30 31.00 10.40 97.70 96.30 32.70 10.70 92.80 92.80 34.80
107.20 31.80 10.10 102.30 102.30 33.80 10.40 97.00 97.00 35.80
111.90 32.50 9.80 106.80 106.80 34.60 10.10 101.30 101.30 36.90
65.40 32.00 13.70 104.00 62.30 34.10 14.10 97.50 59.70 36.10
78.00 32.30 13.70 104.50 75.50 34.20 14.00 98.00 72.80 36.30
92.40 32.20 13.60 105.40 89.10 34.40 13.90 99.00 86.30 36.50
105.10 32.70 13.50 106.90 102.10 34.70 13.80 101.00 99.10 36.90
116.70 33.30 13.30 111.40 111.40 35.50 13.60 105.60 105.60 37.90
57.70 33.80 16.90 113.50 55.20 35.90 17.30 106.30 52.60 38.10
71.20 33.80 16.90 114.20 68.20 36.00 17.20 106.90 65.60 38.20
84.10 34.10 16.80 114.60 81.60 36.20 17.20 107.40 78.90 38.40
98.00 34.20 16.80 115.60 95.30 36.30 17.10 108.40 92.50 38.60
111.20 34.30 16.70 116.90 108.60 36.60 17.00 109.90 105.50 38.90

LWB GTH
o
kW
C
11.30 81.50
11.20 82.80
11.00 86.20
10.70 90.20
10.40 94.10
14.40 89.30
14.30 89.70
14.30 91.20
14.20 94.20
13.90 98.10
17.60 97.10
17.60 97.70
17.50 98.20
17.40 99.50
17.30 102.10

46 C
TSH COMP
kW
kWl
63.20 36.60
76.70 37.00
86.20 37.60
90.20 38.60
94.10 39.70
56.30 38.70
69.50 38.80
83.70 38.90
94.20 39.70
98.10 40.80
49.30 40.80
62.30 41.00
75.60 41.20
89.40 41.50
102.10 42.00

LWB
o
C
11.70
11.60
11.40
11.10
10.90
14.80
14.80
14.70
14.50
14.30
18.00
17.90
17.90
17.80
17.70

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

GH
kW
70.90
68.50
66.10

-5 C
NH COMP LDB
o
kW
kWl
C
63.10 19.70 24.70
61.00 20.20 29.40
58.80 20.90 34.10

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
0C
5C
10 C
15 C
NH COMP LDB
GH
NH COMP LDB
GH
NH COMP LDB
GH
NH COMP LDB
o
o
o
o
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
C
C
C
C
76.10 21.60 26.80 101.90 87.60 23.70 29.00 115.30 115.30 25.50 30.80 130.50 130.50 27.50 32.90
73.70 22.40 31.40 98.70 84.90 24.70 33.60 111.90 111.90 26.70 35.40 127.00 127.00 28.90 37.50
71.10 23.20 36.00 95.30 82.00 25.80 38.10 108.30 108.30 27.90 39.90 124.40 124.40 30.40 42.00
o

GH
kW
85.50
82.80
79.90

YRM 108 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o

16

19

22

C
21
23
25
27
29
23
25
27
29
31
25
27
29
31
33

GTH
kW
99.05
99.51
101.09
104.81
109.37
108.90
109.55
110.02
111.14
113.46
119.13
119.88
120.44
120.81
122.02

24 C
TSH COMP
kW
kWl
76.56 36.41
93.04 36.58
101.09 37.53
104.81 40.10
109.37 43.62
55.00 30.47
66.17 30.88
71.84 31.02
83.57 31.57
96.55 32.72
43.48 26.91
47.83 27.24
56.48 27.53
64.87 27.62
74.06 28.07

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


30 C
35oC
40oC
TSH COMP EER GTH
TSH COMP EER GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
72.10 32.99 9.65 88.07 70.72 30.30 9.92 82.68 67.63 27.43
89.41 33.61 9.56 88.91 85.53 30.87 9.83 83.51 81.59 27.96
95.33 34.37 9.46 90.86 90.86 31.84 9.74 86.30 86.30 29.42
99.70 37.01 9.19 95.14 95.14 34.30 9.46 90.21 90.21 31.61
104.07 39.82 8.92 99.32 99.32 36.87 9.19 94.21 94.21 33.96
31.63 16.65 12.47 96.72 51.75 25.72 12.83 90.68 49.87 23.61
44.90 19.85 12.47 97.19 61.62 26.03 12.74 91.14 59.15 23.90
57.40 23.69 12.38 98.02 66.95 26.44 12.65 92.07 64.26 24.14
74.97 27.15 12.29 99.42 77.74 27.01 12.56 93.93 74.86 24.80
93.99 30.60 12.10 103.60 91.27 28.56 12.38 98.21 87.99 26.49
20.39 11.91 15.38 105.56 41.69 22.88 15.74 98.86 40.53 21.06
27.41 14.69 15.38 106.21 45.56 23.15 15.65 99.42 44.14 21.18
37.86 17.46 15.29 106.58 53.18 23.23 15.65 99.88 51.34 21.40
50.31 20.34 15.29 107.51 60.96 23.57 15.56 100.81 58.67 21.72
64.32 23.22 15.20 108.72 69.25 23.98 15.47 102.21 66.64 22.15
o

EER
9.28
9.28
9.19
8.92
8.55
12.19
12.10
12.10
12.01
11.83
15.11
15.02
14.92
14.92
14.83

GTH
kW
93.28
94.12
95.33
99.70
104.07
60.82
72.54
85.93
97.74
108.53
53.66
66.22
78.21
91.14
103.42

EER
10.28
10.19
10.01
9.74
9.46
13.10
13.01
13.01
12.92
12.65
16.02
16.02
15.93
15.83
15.74

GTH
kW
75.80
77.00
80.17
83.89
87.51
83.05
83.42
84.82
87.61
91.23
90.30
90.86
91.33
92.54
94.95

46oC
TSH COMP
kW
kWl
63.14 24.29
76.39 24.89
80.17 26.37
83.89 28.34
87.51 30.10
46.92 21.04
55.39 21.13
60.47 21.63
71.14 22.65
83.11 23.92
38.38 18.81
41.71 19.03
48.31 19.13
55.24 19.49
63.33 20.11

EER
10.65
10.56
10.37
10.10
9.92
13.47
13.47
13.38
13.20
13.01
16.38
16.29
16.29
16.20
16.11

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

81

GH
kW
65.94
63.71
61.47

-5 C
NH COMP EER
kW
kWl
58.68 20.13 11.17
56.70 20.64 10.53
54.71 21.36 9.82

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


0C
5oC
15oC
10oC
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
70.77 22.07 12.29 94.77 81.50 24.22 13.35 107.23 107.23 26.06 14.04 121.37 121.37 28.10 14.73
68.53 22.89 11.48 91.79 78.94 25.24 12.41 104.07 104.07 27.29 13.01 118.11 118.11 29.54 13.64
66.13 23.71 10.69 88.63 76.22 26.37 11.47 100.72 100.72 28.51 12.05 115.69 115.69 31.07 12.71
o

GH
kW
79.52
77.00
74.31

82

YRM 125 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
122.76
123.40
125.01
129.90
135.67
133.41
134.09
134.67
135.83
138.60
144.66
145.50
146.25
146.62
147.74

24 C
TSH COMP
kW
kWl
94.89 26.43
115.38 26.53
125.01 26.59
129.90 26.60
135.67 26.71
67.37 27.63
80.99 27.63
87.94 27.66
102.14 27.65
117.95 27.37
52.80 28.92
58.05 28.91
68.59 28.95
78.73 28.89
89.68 28.85

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
91.03 29.95 13.42 113.76 91.35 34.28 11.32 109.61 89.66 38.78
112.59 30.04 13.46 114.53 110.17 34.44 11.35 110.29 107.75 38.97
120.14 30.16 13.59 116.38 116.38 34.49 11.51 113.39 113.39 38.99
125.58 30.17 14.20 122.09 122.09 34.63 12.03 118.40 118.40 39.22
131.11 30.31 14.76 127.40 127.40 34.82 12.49 123.48 123.48 39.47
66.58 31.14 14.03 123.66 66.16 35.56 11.86 119.34 65.64 40.14
79.73 31.16 14.10 124.42 78.88 35.64 11.91 119.79 77.75 40.19
86.42 31.24 14.13 125.28 85.56 35.67 11.98 120.75 84.28 40.23
100.41 31.19 14.32 126.82 99.17 35.69 12.12 122.50 97.63 40.09
117.04 31.06 14.85 131.79 116.11 35.53 12.66 128.35 115.00 40.17
52.71 32.45 14.58 134.01 52.93 37.07 12.34 129.16 52.96 41.76
57.82 32.46 14.68 134.88 57.86 37.02 12.43 130.15 57.79 41.77
67.92 32.50 14.73 135.55 67.64 37.10 12.47 130.54 67.10 41.73
77.72 32.51 14.78 136.32 77.30 36.98 12.58 131.52 76.55 41.72
88.23 32.36 14.95 137.77 87.76 37.00 12.70 133.10 86.78 41.71
o

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
117.77
118.51
120.14
125.58
131.11
128.04
128.80
129.38
130.91
135.15
138.71
139.66
140.33
140.80
141.84

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
103.81
104.62
108.62
113.32
118.08
112.96
113.41
114.78
118.29
123.35
122.25
123.06
123.46
124.57
127.10

46 C
TSH COMP
kW
kWl
86.48 42.24
103.79 42.48
108.62 42.58
113.32 42.83
118.08 43.08
63.83 43.53
75.30 43.63
81.84 43.69
96.06 43.66
112.37 43.73
51.96 45.27
56.48 45.27
65.31 45.19
74.37 45.21
84.77 45.21

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
0C
5C
10 C
15 C
-5 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
81.47 24.55 12.73 110.74 98.51 27.10 13.94 131.83 113.40 29.80 15.10 149.81 149.81 32.33 15.81 170.56 170.56 35.46 16.41
78.89 25.76 11.74 107.35 95.54 28.28 12.95 127.88 109.96 31.31 13.93 145.56 145.56 34.20 14.52 165.87 165.87 37.70 15.01
76.51 26.72 10.97 103.29 91.97 29.48 11.96 123.09 105.90 32.75 12.82 140.28 140.28 35.98 13.30 161.49 161.49 40.49 13.61
o

GH
kW
91.57
88.62
85.92

YRM 125 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
114.16
114.76
116.26
120.81
126.18
124.07
124.70
125.25
126.32
128.90
134.53
135.31
136.01
136.36
137.40

24 C
TSH COMP
kW
kWl
88.25 27.01
107.30 27.11
116.26 27.17
120.81 27.19
126.18 27.30
62.66 28.24
75.32 28.24
81.79 28.27
94.99 28.25
109.69 27.97
49.10 29.56
53.99 29.54
63.79 29.58
73.22 29.52
83.40 29.48

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
84.66 30.60 12.21 105.80 84.95 35.04 10.30 101.93 83.38 39.63
104.71 30.70 12.25 106.51 102.46 35.20 10.33 102.57 100.21 39.83
111.73 30.82 12.37 108.23 108.23 35.25 10.48 105.46 105.46 39.85
116.79 30.83 12.92 113.55 113.55 35.39 10.95 110.11 110.11 40.08
121.93 30.98 13.43 118.48 118.48 35.58 11.36 114.83 114.83 40.34
61.92 31.83 12.77 115.01 61.53 36.35 10.80 110.99 61.04 41.02
74.15 31.84 12.83 115.71 73.36 36.42 10.84 111.41 72.30 41.08
80.37 31.92 12.86 116.51 79.57 36.45 10.90 112.29 78.38 41.12
93.38 31.87 13.03 117.94 92.23 36.47 11.03 113.92 90.80 40.97
108.84 31.74 13.51 122.56 107.98 36.31 11.52 119.37 106.95 41.06
49.02 33.16 13.27 124.63 49.23 37.88 11.23 120.12 49.25 42.68
53.77 33.17 13.36 125.44 53.81 37.84 11.31 121.04 53.74 42.69
63.16 33.21 13.41 126.06 62.91 37.91 11.35 121.40 62.40 42.65
72.28 33.23 13.45 126.78 71.88 37.79 11.45 122.32 71.19 42.63
82.05 33.07 13.61 128.13 81.62 37.81 11.56 123.78 80.71 42.63
o

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
109.52
110.22
111.73
116.79
121.93
119.08
119.79
120.32
121.75
125.69
129.00
129.89
130.50
130.94
131.91

EER
8.78
8.79
9.03
9.37
9.71
9.23
9.25
9.32
9.49
9.92
9.60
9.67
9.71
9.79
9.91

GTH
kW
96.55
97.30
101.02
105.38
109.82
105.06
105.47
106.74
110.01
114.71
113.69
114.44
114.81
115.85
118.20

46 C
TSH COMP
kW
kWl
80.42 43.17
96.52 43.41
101.02 43.51
105.38 43.77
109.82 44.03
59.36 44.49
70.03 44.59
76.11 44.65
89.33 44.62
104.50 44.69
48.32 46.26
52.53 46.27
60.74 46.19
69.16 46.20
78.84 46.21

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

83

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
-5 C
10 C
0C
5C
15 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
75.79 25.09 11.58 102.99 91.66 27.70 12.69 122.61 105.44 30.45 13.74 139.32 139.32 33.04 14.39 158.62 158.62 36.24 14.93
73.35 26.32 10.68 99.84 88.85 28.90 11.79 118.93 102.28 32.00 12.68 135.37 135.37 34.95 13.22 154.26 154.26 38.52 13.66
71.12 27.31 9.98 96.06 85.50 30.13 10.88 114.47 98.45 33.47 11.67 130.46 130.46 36.77 12.10 150.19 150.19 41.38 12.38
o

GH
kW
85.16
82.42
79.91

84

YRM 145 R 22 Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
134.64
135.56
137.75
143.84
150.43
147.38
148.39
149.10
150.69
155.55
161.04
162.09
162.77
163.54
165.07

24 C
TSH COMP
kW
kWl
104.07 28.99
126.75 29.14
137.75 29.30
143.84 29.46
150.43 29.61
74.43 30.53
89.63 30.57
97.36 30.62
113.32 30.67
132.37 30.72
58.78 32.20
64.67 32.21
76.34 32.21
87.82 32.22
100.20 32.23

EER
15.85
15.87
16.04
16.66
17.33
16.47
16.56
16.61
16.76
17.28
17.06
17.17
17.24
17.32
17.47

GTH
kW
130.02
131.13
133.13
139.87
146.11
142.36
143.35
143.85
146.01
151.61
155.34
156.41
156.99
157.48
159.43

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
100.50 33.06 13.42 126.46 101.55 38.11 11.32 122.82 100.46 43.45
124.57 33.24 13.46 127.47 122.63 38.33 11.35 123.72 120.88 43.72
133.13 33.42 13.59 130.09 130.09 38.55 11.51 127.91 127.91 43.99
139.87 33.60 14.20 136.71 136.71 38.78 12.03 133.62 133.62 44.26
146.11 33.78 14.76 142.72 142.72 39.00 12.49 139.30 139.30 44.53
74.03 34.62 14.03 138.52 74.11 39.84 11.86 134.69 74.08 45.30
88.73 34.68 14.10 139.30 88.31 39.90 11.91 135.26 87.78 45.38
96.09 34.73 14.13 140.37 95.88 39.97 11.98 136.43 95.23 45.46
111.99 34.79 14.32 142.25 111.24 40.03 12.12 139.14 110.90 45.54
131.30 34.84 14.85 148.73 131.03 40.10 12.66 145.75 130.59 45.62
59.03 36.34 14.58 150.93 59.62 41.75 12.34 146.53 60.08 47.38
64.75 36.35 14.68 152.12 65.26 41.76 12.43 147.65 65.56 47.39
75.99 36.36 14.73 152.62 76.16 41.77 12.47 148.26 76.20 47.40
86.93 36.37 14.78 154.01 87.32 41.78 12.58 149.48 87.00 47.41
99.17 36.38 14.95 155.60 99.12 41.79 12.70 151.31 98.66 47.42

EER
9.64
9.66
9.92
10.30
10.67
10.14
10.17
10.24
10.43
10.90
10.55
10.63
10.67
10.76
10.89

GTH
kW
117.43
118.44
123.45
128.84
134.31
128.90
129.34
130.94
135.28
141.09
139.92
140.86
141.59
142.85
145.78

46 C
TSH COMP
kW
kWl
97.82 47.78
117.50 48.09
123.45 48.39
128.84 48.70
134.31 49.01
72.83 49.67
85.88 49.76
93.36 49.85
109.85 49.93
128.53 50.02
59.47 51.81
64.66 51.82
74.90 51.83
85.28 51.85
97.24 51.86

EER
8.39
8.40
8.70
9.03
9.35
8.85
8.87
8.96
9.24
9.62
9.22
9.27
9.32
9.40
9.59

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
0C
5C
10 C
15 C
-5 C
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
101.26 90.12 30.00 11.52 122.54 109.06 33.00 12.67 145.82 125.41 36.26 13.72 165.76 165.76 39.07 14.48 188.71 188.71 42.74 15.06
98.02 87.24 31.11 10.75 118.76 105.69 34.14 11.87 141.47 121.67 37.74 12.79 160.99 160.99 40.79 13.47 183.47 183.47 44.73 13.99
95.05 84.59 32.03 10.13 114.24 101.67 35.19 11.08 136.22 117.15 39.24 11.84 155.23 155.23 42.64 12.42 178.72 178.72 47.06 12.96
o

YRM 145 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
WET BULB
DRY BULB
o
o
C
C
21
23
16
25
27
29
23
25
19
27
29
31
25
27
22
29
31
33

GTH
kW
125.21
126.07
128.11
133.77
139.90
137.07
138.00
138.67
140.14
144.66
149.76
150.75
151.37
152.09
153.52

24 C
TSH COMP
kW
kWl
96.79 29.63
117.88 29.79
128.11 29.94
133.77 30.10
139.90 30.26
69.22 31.20
83.35 31.25
90.55 31.30
105.38 31.35
123.11 31.40
54.66 32.91
60.15 32.91
70.99 32.92
81.67 32.93
93.18 32.94

EER
14.42
14.44
14.60
15.16
15.77
14.99
15.07
15.12
15.25
15.72
15.53
15.63
15.69
15.76
15.90

GTH
kW
120.92
121.95
123.81
130.07
135.88
132.40
133.32
133.78
135.79
141.00
144.46
145.46
146.00
146.46
148.27

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
30 C
35 C
40 C
TSH COMP EER
GTH
TSH COMP EER
GTH
TSH COMP
kW
kWl
kW
kW
kWl
kW
kW
kWl
93.47 33.79 12.21 117.61 94.44 38.95 10.30 114.22 93.43 44.41
115.85 33.97 12.25 118.55 114.04 39.17 10.33 115.06 112.42 44.68
123.81 34.15 12.37 120.98 120.98 39.40 10.48 118.96 118.96 44.95
130.07 34.34 12.92 127.14 127.14 39.63 10.95 124.26 124.26 45.23
135.88 34.52 13.43 132.73 132.73 39.86 11.36 129.55 129.55 45.51
68.85 35.38 12.77 128.82 68.92 40.71 10.80 125.27 68.90 46.30
82.52 35.44 12.83 129.55 82.13 40.78 10.84 125.79 81.64 46.38
89.36 35.50 12.86 130.55 89.16 40.85 10.90 126.88 88.56 46.46
104.15 35.55 13.03 132.30 103.46 40.91 11.03 129.40 103.13 46.54
122.11 35.61 13.51 138.32 121.86 40.98 11.52 135.54 121.45 46.62
54.90 37.14 13.27 140.36 55.44 42.66 11.23 136.27 55.87 48.42
60.22 37.15 13.36 141.47 60.69 42.68 11.31 137.31 60.97 48.43
70.67 37.16 13.41 141.93 70.83 42.69 11.35 137.88 70.87 48.44
80.85 37.17 13.45 143.23 81.21 42.70 11.45 139.02 80.91 48.45
92.23 37.18 13.61 144.71 92.18 42.71 11.56 140.72 91.75 48.46

EER
8.78
8.79
9.03
9.37
9.71
9.23
9.25
9.32
9.49
9.92
9.60
9.67
9.71
9.79
9.91

GTH
kW
109.21
110.15
114.81
119.83
124.91
119.88
120.29
121.78
125.81
131.21
130.13
131.00
131.68
132.85
135.58

46 C
TSH COMP
kW
kWl
90.97 48.83
109.27 49.14
114.81 49.45
119.83 49.77
124.91 50.08
67.73 50.77
79.87 50.85
86.83 50.94
102.16 51.03
119.53 51.12
55.30 52.95
60.13 52.96
69.66 52.97
79.31 52.99
90.43 53.00

EER
7.63
7.65
7.92
8.22
8.51
8.06
8.07
8.16
8.41
8.76
8.39
8.44
8.48
8.55
8.73

HEATING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s


INDOOR COIL
ENTERING AIR
DRY BULB
o
C
15
20
25

85

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB C


o
o
o
-5 C
10 C
0C
5C
15 C
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
GH
NH COMP EER
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
kW
kW
kWl
83.81 30.66 10.48 113.96 101.43 33.73 11.53 135.61 116.63 37.06 12.49 154.15 154.15 39.92 13.17 175.50 175.50 43.68 13.71
81.13 31.79 9.78 110.44 98.29 34.89 10.80 131.57 113.15 38.57 11.64 149.72 149.72 41.68 12.25 170.62 170.62 45.71 12.74
78.67 32.73 9.21 106.24 94.55 35.96 10.08 126.69 108.95 40.11 10.78 144.36 144.36 43.58 11.30 166.21 166.21 48.10 11.79
o

GH
kW
94.17
91.16
88.39

86

YRM 175 R 22 Performance Rating


PERFORMANCE DATAAIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOWOF 8000 l/s
Indoor Coil
Entering Air
24.00
kw
WET BULB DRY BULB GTH SHF SH
o
o
kW
kW
kW
C
C
16.00
21.00
178.1 0.8 137.6 39.3
23.00
179.0 0.9 167.3 39.4
25.00
179.9 1.0 179.9 39.5
27.00
180.8 1.0 180.8 39.6
29.00
181.7 1.0 181.7 39.6
19.00
23.00
191.5 0.5 96.7 41.5
25.00
191.9 0.6 115.9 41.5
27.00
192.3 0.7 125.6 41.5
29.00
192.6 0.8 144.9 41.6
31.00
193.0 0.9 164.2 41.6
22.00
25.00
208.1 0.4 76.0 43.7
27.00
208.3 0.4 83.1 43.7
29.00
208.4 0.5 97.7 43.8
31.00
208.6 0.5 112.0 43.8
33.00
208.7 0.6 126.7 43.8

EER
15.5
15.5
15.5
15.6
15.6
15.8
15.8
15.8
15.8
15.8
16.2
16.2
16.3
16.3
16.3

30.00
GTH SHF SH
kw
kW kW kW
169.3 0.8 130.9 45.2
170.5 1.0 162.0 45.4
171.7 1.0 171.7 45.5
172.9 1.0 172.9 45.6
174.1 1.0 174.1 45.7
182.4 0.5 94.8 47.3
182.8 0.6 113.1 47.4
183.2 0.7 122.4 47.4
183.6 0.8 140.8 47.5
184.1 0.9 159.4 47.5
198.2 0.4 75.3 49.6
198.3 0.4 82.1 49.6
198.5 0.5 96.1 49.6
198.6 0.6 109.6 49.6
198.7 0.6 123.6 49.6

EER
12.8
12.8
12.9
12.9
13.0
13.1
13.2
13.2
13.2
13.2
13.6
13.6
13.7
13.7
13.7

Outdoor Coil Entering Air (ambient), C


35.00
GTH SHF SH
kw EER
kW kW kW
166.0 0.8 133.3 52.6 10.8
167.4 1.0 161.1 52.8 10.8
168.9 1.0 168.9 52.9 10.9
170.4 1.0 170.4 53.1 11.0
171.9 1.0 171.9 53.2 11.0
178.6 0.5 95.5 54.8 11.1
179.0 0.6 113.5 54.9 11.1
179.5 0.7 122.6 54.9 11.2
180.0 0.8 140.8 55.0 11.2
180.5 0.9 159.0 55.0 11.2
194.1 0.4 76.7 57.2 11.6
194.2 0.4 83.3 57.2 11.6
194.3 0.5 97.0 57.2 11.6
194.5 0.6 110.3 57.2 11.6
194.6 0.6 124.0 57.3 11.6

40.00
GTH SHF SH
kw
kW kW kW
161.3 0.8 131.9 60.2
163.0 1.0 159.3 60.4
164.8 1.0 164.8 60.6
166.6 1.0 166.6 60.8
168.4 1.0 168.4 61.0
173.3 0.6 95.3 62.4
173.9 0.6 112.8 62.5
174.4 0.7 121.7 62.5
175.0 0.8 139.4 62.6
175.5 0.9 157.2 62.7
188.4 0.4 77.3 64.9
188.6 0.4 83.7 64.9
188.7 0.5 97.0 64.9
188.9 0.6 109.9 64.9
189.0 0.7 123.2 64.9

EER
9.1
9.2
9.3
9.4
9.4
9.5
9.5
9.5
9.5
9.6
9.9
9.9
9.9
9.9
9.9

46.00
GTH SHF SH
kw
kW kW kW
152.3 0.8 126.8 66.3
154.2 1.0 153.0 66.5
156.3 1.0 156.3 66.7
158.3 1.0 158.3 66.9
160.4 1.0 160.4 67.2
163.5 0.6 92.4 68.5
164.1 0.7 108.9 68.5
164.7 0.7 117.4 68.6
165.2 0.8 134.2 68.7
165.8 0.9 151.1 68.7
177.9 0.4 75.6 70.9
178.0 0.5 81.7 70.9
178.1 0.5 94.2 70.9
178.3 0.6 106.4 70.9
178.4 0.7 119.0 71.0

EER
7.8
7.9
8.0
8.1
8.1
8.1
8.2
8.2
8.2
8.2
8.6
8.6
8.6
8.6
8.6

YRM 175 R 407C Performance Rating


PERFORMANCE DATA AIR COOLED MODELS YRM, Dual COMPRESSOR UNIT (STANDARD AMBIENT)
COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
Indoor Coil
Entering Air

24
WET BULB DRY BULB GTH SHF SH
o
o
kW kW kW
C
C
21
165.6 0.8 128.0
23
166.4 0.9 155.6
16
25
167.3 1.0 167.3
27
168.1 1.0 168.1
29
169.0 1.0 169.0
23
178.1 0.5 90.0
25
178.5 0.6 107.8
19
27
178.8 0.7 116.8
29
179.1 0.8 134.7
31
179.5 0.9 152.7
25
193.6 0.4 70.6
27
193.7 0.4 77.3
22
29
193.8 0.5 90.9
31
194.0 0.5 104.2
33
194.1 0.6 117.8

87

kw
40.2
40.3
40.3
40.4
40.5
42.4
42.4
42.4
42.5
42.5
44.7
44.7
44.7
44.7
44.7

30
EER GTH SHF SH
kW kW kW
14.1 157.5 0.8 121.7
14.1 158.6 1.0 150.6
14.2 159.7 1.0 159.7
14.2 160.8 1.0 160.8
14.2 161.9 1.0 161.9
14.3 169.6 0.5 88.2
14.4 170.0 0.6 105.2
14.4 170.4 0.7 113.8
14.4 170.8 0.8 131.0
14.4 171.2 0.9 148.2
14.8 184.3 0.4 70.0
14.8 184.4 0.4 76.4
14.8 184.6 0.5 89.3
14.8 184.7 0.6 102.0
14.8 184.8 0.6 115.0

kw
46.2
46.4
46.5
46.6
46.7
48.4
48.4
48.5
48.5
48.5
50.7
50.7
50.7
50.7
50.7

Outdoor Coil Entering Air (ambient), C


35
40
EER GTH SHF SH
kw EER GTH SHF SH
kw
kW kW kW
kW kW kW
11.6 154.4 0.8 124.0 53.8 9.8 150.0 0.8 122.7 61.5
11.7 155.7 1.0 149.8 54.0 9.8 151.6 1.0 148.1 61.7
11.7 157.1 1.0 157.1 54.1 9.9 153.3 1.0 153.3 61.9
11.8 158.5 1.0 158.5 54.3 10.0 154.9 1.0 154.9 62.1
11.8 159.9 1.0 159.9 54.4 10.0 156.6 1.0 156.6 62.3
12.0 166.1 0.5 88.8 56.0 10.1 161.2 0.6 88.7 63.8
12.0 166.5 0.6 105.6 56.1 10.1 161.7 0.6 104.9 63.9
12.0 167.0 0.7 114.0 56.1 10.1 162.2 0.7 113.2 63.9
12.0 167.4 0.8 130.9 56.2 10.2 162.7 0.8 129.7 64.0
12.0 167.9 0.9 147.9 56.2 10.2 163.2 0.9 146.2 64.0
12.4 180.5 0.4 71.3 58.4 10.5 175.2 0.4 71.8 66.3
12.4 180.6 0.4 77.5 58.5 10.5 175.4 0.4 77.9 66.3
12.4 180.7 0.5 90.2 58.5 10.5 175.5 0.5 90.2 66.3
12.4 180.9 0.6 102.6 58.5 10.6 175.6 0.6 102.2 66.3
12.4 181.0 0.6 115.3 58.5 10.6 175.8 0.7 114.6 66.4

46
EER GTH SHF SH
kw
kW kW kW
8.3 141.6 0.8 117.9 67.7
8.4 143.4 1.0 142.3 68.0
8.4 145.3 1.0 145.3 68.2
8.5 147.2 1.0 147.2 68.4
8.6 149.2 1.0 149.2 68.7
8.6 152.0 0.6 85.9 70.0
8.6 152.6 0.7 101.3 70.0
8.7 153.1 0.7 109.2 70.1
8.7 153.7 0.8 124.8 70.2
8.7 154.2 0.9 140.5 70.3
9.0 165.4 0.4 70.3 72.5
9.0 165.5 0.5 76.0 72.5
9.0 165.7 0.5 87.6 72.5
9.0 165.8 0.6 99.0 72.5
9.0 165.9 0.7 110.7 72.5

EER
7.1
7.2
7.3
7.3
7.4
7.4
7.4
7.5
7.5
7.5
7.8
7.8
7.8
7.8
7.8

88

YRM022 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
20.14 13.39 3.49 19.41 19.52 13.36 4.09
23
20.28 16.57 3.52 19.55 19.66 16.32 4.12
16
25
20.43 19.51 3.54 19.69 19.80 18.99 4.15
27
20.91 20.91 3.59 19.88 20.30 20.30 4.19
29
21.63 21.63 3.66 20.17 21.02 21.02 4.26
23
23.37 12.70 3.81 20.90 22.58 12.38 4.40
25
23.37 14.53 3.81 20.91 22.59 14.23 4.40
19
27
23.38 16.66 3.81 20.91 22.59 16.38 4.40
29
23.38 18.94 3.82 20.91 22.59 18.65 4.40
31
23.43 21.00 3.82 20.92 22.66 20.67 4.41
25
25.36 11.20 4.00 21.63 24.55 10.87 4.58
27
25.37 13.61 4.00 21.64 24.57 13.27 4.58
22
29
25.38 15.40 4.00 21.64 24.57 15.05 4.58
31
25.38 17.81 4.00 21.64 24.57 17.44 4.58
33
25.38 19.62 4.00 21.64 24.57 19.24 4.58

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.08 18.83 13.29 4.74 13.37 18.12 13.17 5.41 11.27 17.41
16.20 18.96 16.00 4.77 13.47 18.25 15.65 5.45 11.35 17.53
16.31 19.10 18.40 4.81 13.56 18.38 17.80 5.49 11.43 17.66
16.53 19.63 19.63 4.85 13.80 18.94 18.94 5.54 11.67 18.24
16.85 20.34 20.34 4.92 14.12 19.65 19.65 5.60 11.98 18.94
17.52 21.72 12.03 5.04 14.71 20.83 11.66 5.69 12.49 19.94
17.52 21.72 13.88 5.04 14.72 20.84 13.50 5.69 12.49 19.94
17.52 21.73 16.05 5.04 14.72 20.84 15.69 5.69 12.49 19.95
17.53 21.73 18.31 5.04 14.72 20.84 17.92 5.69 12.49 19.95
17.56 21.82 20.27 5.05 14.76 20.96 19.83 5.70 12.53 20.08
18.31 23.67 10.52 5.20 15.52 22.77 10.15 5.85 13.29 21.86
18.31 23.69 12.89 5.21 15.53 22.79 12.49 5.85 13.29 21.88
18.31 23.69 14.65 5.21 15.53 22.80 14.24 5.85 13.30 21.89
18.31 23.69 17.02 5.21 15.53 22.80 16.58 5.85 13.30 21.89
18.31 23.69 18.80 5.21 15.53 22.80 18.34 5.85 13.30 21.89

46oC
TSH COMP
kW
kWl
13.01 6.10
15.27 6.14
17.18 6.19
18.24 6.23
18.94 6.28
11.28 6.36
13.11 6.36
15.29 6.36
17.50 6.36
19.36 6.37
9.78 6.50
12.09 6.50
13.80 6.50
16.11 6.50
17.85 6.50

EER
9.61
9.68
9.75
9.99
10.29
10.70
10.71
10.71
10.71
10.76
11.48
11.49
11.49
11.49
11.49

GTH
kW
16.69
16.81
16.93
17.53
18.24
19.05
19.05
19.05
19.05
19.21
20.95
20.97
20.98
20.98
20.98

52oC
TSH COMP
kW
kWl
12.80 6.78
14.85 6.83
16.55 6.88
17.53 6.92
18.24 6.97
10.88 7.02
12.70 7.02
14.88 7.02
17.05 7.02
18.86 7.03
9.41 7.14
11.67 7.15
13.36 7.15
15.63 7.15
17.34 7.15

GTH
kW
15.85
15.96
16.08
16.73
17.44
18.05
18.06
18.06
18.06
18.24
19.98
20.00
20.01
20.01
20.01

52oC
TSH COMP
kW
kWl
12.50 6.97
14.33 7.02
15.81 7.07
16.73 7.13
17.44 7.19
10.43 7.23
12.22 7.23
14.39 7.23
16.52 7.23
18.20 7.25
9.00 7.39
11.22 7.39
12.88 7.39
15.10 7.39
16.77 7.39

EER
8.28
8.34
8.40
8.65
8.93
9.26
9.26
9.26
9.26
9.32
10.01
10.01
10.02
10.02
10.02

YRM022 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1400 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
19.86 13.38 3.22 20.73 19.14 13.33 3.90
23
20.00 16.46 3.25 20.88 19.27 16.14 3.93
16
25
20.14 19.27 3.27 21.03 19.41 18.67 3.96
27
20.67 20.67 3.31 21.33 19.96 19.96 4.00
29
21.44 21.44 3.36 21.75 20.71 20.71 4.05
23
23.20 12.63 3.49 22.65 22.26 12.25 4.17
25
23.20 14.47 3.50 22.65 22.27 14.10 4.18
19
27
23.21 16.60 3.50 22.65 22.27 16.26 4.18
29
23.21 18.88 3.50 22.65 22.27 18.53 4.18
31
23.27 20.93 3.50 22.69 22.36 20.53 4.18
25
25.32 11.18 3.65 23.67 24.34 10.79 4.33
27
25.33 13.59 3.65 23.68 24.35 13.18 4.34
22
29
25.33 15.38 3.65 23.68 24.36 14.95 4.34
31
25.33 17.79 3.65 23.68 24.36 17.34 4.34
33
25.33 19.60 3.65 23.68 24.36 19.13 4.34
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.52 18.35 13.21 4.64 13.29 17.52 13.04 5.41 10.88 16.68
16.63 18.47 15.76 4.68 13.38 17.65 15.33 5.45 10.96 16.80
16.75 18.61 17.99 4.71 13.48 17.77 17.28 5.49 11.04 16.92
17.05 19.17 19.17 4.75 13.76 18.37 18.37 5.54 11.31 17.55
17.44 19.92 19.92 4.81 14.12 19.10 19.10 5.60 11.64 18.27
18.19 21.24 11.83 4.92 14.73 20.18 11.38 5.69 12.11 19.12
18.20 21.24 13.68 4.92 14.73 20.19 13.22 5.69 12.11 19.12
18.20 21.24 15.85 4.92 14.73 20.19 15.40 5.69 12.11 19.12
18.20 21.25 18.10 4.92 14.73 20.19 17.62 5.69 12.12 19.13
18.24 21.36 20.04 4.93 14.78 20.32 19.49 5.70 12.17 19.28
19.16 23.28 10.36 5.08 15.63 22.18 9.91 5.85 12.95 21.08
19.17 23.29 12.72 5.08 15.64 22.20 12.23 5.85 12.95 21.10
19.17 23.30 14.47 5.08 15.64 22.21 13.96 5.85 12.96 21.11
19.17 23.30 16.83 5.08 15.64 22.21 16.28 5.85 12.96 21.11
19.17 23.30 18.60 5.08 15.64 22.21 18.02 5.85 12.96 21.11

46oC
TSH COMP
kW
kWl
12.80 6.20
14.85 6.24
16.65 6.29
17.55 6.33
18.27 6.39
10.92 6.46
12.73 6.46
14.91 6.46
17.09 6.46
18.90 6.48
9.46 6.62
11.73 6.62
13.43 6.62
15.70 6.62
17.41 6.62

EER
9.06
9.13
9.19
9.45
9.75
10.10
10.10
10.10
10.10
10.16
10.87
10.87
10.88
10.88
10.88

EER
7.65
7.70
7.76
8.01
8.28
8.52
8.52
8.52
8.52
8.59
9.23
9.23
9.24
9.24
9.24

YRM027 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
25.27 16.00 4.34 19.58 24.52 16.03 5.18
23
25.45 20.20 4.37 19.72 24.69 19.92 5.22
16
25
25.63 24.21 4.41 19.86 24.87 23.59 5.26
27
26.16 26.16 4.46 20.04 25.41 25.41 5.31
29
27.10 27.10 4.54 20.36 26.34 26.34 5.39
23
29.48 16.07 4.82 20.93 28.44 15.66 5.51
25
29.69 18.19 4.81 21.08 28.64 17.81 5.55
19
27
29.90 20.74 4.81 21.23 28.84 20.39 5.59
29
30.11 23.28 4.80 21.38 29.05 22.95 5.63
31
30.70 25.03 4.90 21.82 29.62 24.72 5.74
25
32.70 14.37 5.04 22.15 31.57 13.90 5.85
27
32.74 17.20 5.04 22.16 31.60 16.71 5.85
22
29
32.82 19.31 5.05 22.19 31.69 18.81 5.86
31
32.86 22.15 5.05 22.20 31.73 21.64 5.86
33
32.91 24.29 5.05 22.21 31.77 23.77 5.87

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.93 23.70 15.99 6.09 13.09 22.86 15.91 7.02 10.96 22.01
16.04 23.87 19.57 6.13 13.19 23.02 19.20 7.07 11.03 22.17
16.16 24.04 22.91 6.18 13.28 23.19 22.21 7.12 11.11 22.33
16.35 24.60 24.60 6.23 13.49 23.78 23.78 7.17 11.31 22.94
16.68 25.51 25.51 6.31 13.80 24.66 24.66 7.24 11.61 23.80
17.25 27.33 15.21 6.37 14.31 26.19 14.73 7.27 12.04 25.04
17.37 27.52 17.37 6.42 14.42 26.37 16.90 7.32 12.13 25.22
17.49 27.71 19.96 6.46 14.52 26.56 19.51 7.37 12.21 25.40
17.62 27.91 22.56 6.51 14.62 26.75 22.05 7.42 12.30 25.58
17.97 28.46 24.33 6.65 14.92 27.28 23.88 7.58 12.55 26.08
18.41 30.35 13.40 6.72 15.41 29.12 12.88 7.61 13.05 27.87
18.42 30.39 16.19 6.72 15.42 29.15 15.64 7.61 13.06 27.90
18.45 30.47 18.26 6.73 15.44 29.23 17.69 7.62 13.09 27.98
18.46 30.51 21.07 6.74 15.46 29.27 20.47 7..62 13.10 28.02
18.48 30.55 23.19 6.74 15.47 29.31 22.57 7.63 13.11 28.06

46oC
TSH COMP
kW
kWl
15.77 7.96
18.79 8.02
21.49 8.08
22.94 8.12
23.80 8.19
14.24 8.16
16.41 8.21
19.02 8.27
21.62 8.33
23.38 8.50
12.36 8.51
15.08 8.51
17.10 8.52
19.84 8.52
21.91 8.52

EER

9.30
9.36
9.43
9.63
9.91
10.25
10.32
10.40
10.47
10.69
11.18
11.19
11.21
11.22
11.23

GTH
kW
21.16
21.30
21.46
22.10
22.94
23.88
24.05
24.22
24.39
24.89
26.61
26.64
26.73
26.76
26.79

52oC
TSH COMP
kW
kWl
15.58 8.90
18.34 8.97
20.76 9.03
22.10 9.08
22.94 9.15
13.73 9.06
15.89 9.12
18.49 9.19
21.08 9.25
22.83 9.44
11.84 9.41
14.51 9.41
16.49 9.42
19.18 9.42
21.22 9.42

GTH
kW
20.03
20.17
20.32
21.15
22.16
23.27
23.44
23.60
23.77
24.25
26.63
26.68
26.78
26.83
26.87

52oC
TSH COMP
kW
kWl
15.25 8.95
17.69 9.01
19.78 9.08
21.15 9.14
22.16 9.21
13.47 9.33
15.62 9.32
18.19 9.32
20.78 9.31
22.51 9.50
11.87 9.51
14.54 9.51
16.52 9.52
19.20 9.52
21.24 9.52

EER

7.99
8.05
8.11
8.31
8.56
8.81
8.87
8.94
9.00
9.18
9.65
9.66
9.68
9.69
9.70

YRM027 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1500 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
24.19 16.02 4.27 19.03 23.43 15.98 5.13
23
24.36 19.81 4.30 19.16 23.60 19.48 5.16
16
25
24.54 23.32 4.34 19.30 23.77 22.69 5.20
27
25.16 25.16 4.40 19.55 24.43 24.43 5.27
29
26.20 26.20 4.48 19.96 25.46 25.46 5.35
23
28.76 15.79 4.74 20.77 27.75 15.39 5.58
25
28.97 17.93 4.73 20.91 27.94 17.54 5.58
19
27
29.17 20.50 4.73 21.06 28.14 20.13 5.58
29
29.38 23.05 4.73 21.21 28.34 22.71 5.57
31
29.94 24.82 4.82 21.63 28.89 24.47 5.69
25
32.36 14.24 4.96 22.24 31.30 13.81 5.81
27
32.40 17.06 4.97 22.25 31.34 16.61 5.81
22
29
32.50 19.17 4.98 22.28 31.44 18.70 5.82
31
32.55 22.00 4.98 22.30 31.49 21.52 5.82
33
32.61 24.14 4.98 22.32 31.54 23.64 5.83
* Data based on nominal condition without filter(s)

89

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.36 22.60 15.88 6.06 12.54 21.75 15.73 7.02 10.43 20.89
15.47 22.76 19.09 6.11 12.63 21.91 18.66 7.07 10.51 21.04
15.58 22.92 21.99 6.15 12.72 22.06 21.27 7.12 10.58 21.19
15.84 23.63 23.63 6.21 12.99 22.81 22.81 7.18 10.85 21.98
16.25 24.66 24.66 6.29 13.38 23.83 23.83 7.25 11.21 23.00
16.99 26.65 14.94 6.50 14.02 25.53 14.46 7.43 11.74 24.41
17.11 26.84 17.10 6.50 14.12 25.71 16.63 7.43 11.82 24.58
17.23 27.03 19.70 6.49 14.22 25.89 19.24 7.43 11.91 24.75
17.35 27.22 22.30 6.49 14.32 26.08 21.84 7.42 11.99 24.93
17.70 27.75 24.06 6.62 14.60 26.60 23.59 7.58 12.23 25.42
18.38 30.16 13.33 6.71 15.32 28.99 12.85 7.64 12.95 27.82
18.40 30.20 16.11 6.72 15.34 29.03 15.60 7.64 12.97 27.86
18.43 30.30 18.19 6.73 15.37 29.14 17.65 7.65 13.00 27.97
18.45 30.35 20.98 6.73 15.39 29.19 20.41 7..65 13.01 28.02
18.47 30.40 23.09 6.73 15.40 29.23 22.50 7.65 13.03 28.06

46oC
TSH COMP
kW
kWl
15.52 7.99
18.20 8.04
20.53 8.10
21.98 8.15
23.00 8.23
13.97 8.38
16.13 8.38
18.74 8.37
21.33 8.37
23.08 8.53
12.36 8.57
15.08 8.57
17.10 8.58
19.82 8.58
21.89 8.58

EER

8.81
8.87
8.93
9.20
9.54
9.96
10.03
10.10
10.17
10.37
11.08
11.09
11.12
11.14
11.15

EER

7.53
7.58
7.64
7.90
8.21
8.53
8.59
8.65
8.71
8.88
9.56
9.57
9.60
9.62
9.63

90

YRM030 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
28.85 17.61 4..84 20.05 27.88 17.55 6.02
23
29.06 22.65 4.87 20.19 28.08 22.32 6.07
16
25
29.26 27.62 4.91 20.33 28.28 26.82 6.11
27
28.92 29.82 4.98 20.43 28.86 28.86 6.18
29
30.87 30.87 5.10 20.63 29.90 29.90 6.30
23
33.85 18.21 5.35 20.98 32.54 17.72 6.50
25
34.08 20.51 5.39 21.13 32.77 20.06 6.55
19
27
34.32 23.25 5.42 21.28 33.00 22.85 6.59
29
34.57 25.95 5.46 21.43 33.24 25.61 6.64
31
34.48 28.81 5.50 21.40 33.18 28.36 6.64
25
37.48 16.42 5.83 21.93 36.07 15.85 6.93
27
37.54 19.57 5.84 21.94 36.13 18.99 6.94
22
29
37.62 21.94 5.85 21.96 36.25 21.35 6.95
31
37.66 25.08 5.85 21.96 36.26 24.48 6.95
33
37.72 27.45 5.86 21.97 36.27 26.85 6.96

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.56 26.92 17.57 7.21 12.56 25.95 17.54 8.40 10.39 24.98
15.67 27.11 21.95 7.26 12.65 26.13 21.54 8.46 10.47 25.15
15.78 27.30 26.02 7.32 12.74 26.32 25.20 8.52 10.54 25.33
15.93 27.92 27.92 7.38 12.92 26.97 26.97 8.58 10.72 26.01
16.21 28.94 28.94 7.48 13.20 27.97 27.97 8.67 11.00 27.00
16.72 31.25 17.21 7.61 13.73 29.94 16.69 8.72 11.47 28.64
16.84 31.47 19.59 7.66 13.82 30.15 19.09 8.79 11.55 28.84
16.96 31.69 22.42 7.72 13.92 30.36 21.95 8.85 11.63 29.04
17.08 31.92 25.23 7.77 14.02 30.58 24.78 8..91 11.71 29.25
17.06 31.91 27.87 7.77 14.01 30.61 27.32 8.91 11.72 29.33
17.75 34.67 15.28 8.03 14.72 33.26 14.71 9.15 12.42 31.86
17.76 34.73 18.40 8.04 14.74 33.33 17.80 9.15 12.43 31.92
17.79 34.85 20.75 8.05 14.77 33.44 20.13 9.15 12.45 32.00
17.79 34.96 23.87 8.05 14.77 33.44 23.22 9.15 12.46 32.03
17.80 34.91 26.22 8.06 14.78 33.50 25.55 9.16 12.48 32.09

46oC
TSH COMP
kW
kWl
17.43 9.59
21.09 9.66
24.37 9.73
26.01 9.79
27.00 9.86
16.15 9.83
18.56 9.90
21.43 9.97
24.29 10.04
26.72 10.05
14.13 10.24
17.18 10.25
19.49 10.25
22.55 10.25
24.86 10.26

EER

8.76
8.82
8.89
9.07
9.34
9.73
9.80
9.87
9.94
9.96
10.61
10.63
10.65
10.66
10.67

GTH
kW
24.02
24.18
24.36
25.06
26.03
27.34
27.53
27.72
27.92
28.04
30.44
30.51
30.59
30.62
30.68

52oC
TSH COMP
kW
kWl
17.27 10.78
20.59 10.86
23.54 10.94
25.06 10.99
26.03 11.06
15.59 10.95
18.00 11.02
20.87 11.10
23.74 11.18
26.08 11.19
13.54 11.35
16.55 11.35
18.83 11.36
21.84 11.36
24.12 11.36

GTH
kW
22.88
23.04
23.21
23.96
24.92
25.88
26.06
26.24
26.43
26.60
28.88
28.95
29.03
29.05
29.11

52oC
TSH COMP
kW
kWl
17.00 10.69
19.98 10.77
22.55 10.85
23.96 10.90
24.92 10.97
14.95 10.84
17.35 10.92
20.21 10.99
23.07 11.07
25.30 11.09
12.89 11.24
15.84 11.24
18.07 11.25
21.03 11.25
23.26 11.25

EER

7.49
7.54
7.60
7.79
8.03
8.34
8.40
8.46
8.52
8.55
9.15
9.17
9.19
9.20
9.21

YRM030 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 1800 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
27.92 17.54 4.81 19.53 26.91 17.57 5.99
23
28.12 22.34 4.85 19.67 27.10 21.96 6.03
16
25
28.32 26.85 4.88 19.81 27.30 26.01 6.08
27
29.00 29.00 4.96 19.96 27.99 27.99 6.15
29
30.16 30.16 5.09 20.22 29.12 29.12 6.27
23
33.26 18.00 5.36 20.72 31.79 17.43 6.46
25
33.49 20.32 5.40 20.86 32.01 19.79 6.51
19
27
33.73 23.07 5.44 21.01 32.24 22.60 6.55
29
33.97 25.81 5.48 21.16 32.47 25.39 6.60
31
33.90 28.62 5.48 21.12 32.44 28.08 6.60
25
37.22 16.33 5.83 21.80 35.55 15.65 6.91
27
37.29 19.48 5.83 21.81 35.62 18.78 6.92
22
29
37.38 21.84 5.84 21.83 35.71 21.14 6.92
31
37.42 24.97 5.85 21.83 35.75 24.26 6.93
33
37.49 27.34 5.86 21.85 35.82 26.62 6.94
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.13 25.91 17.54 7.15 12.19 24.90 17.43 8.34 10.05 23.89
15.24 26.10 21.53 7.20 12.27 25.08 21.05 8.40 10.12 24.06
15.35 26.28 25.17 7.26 12.36 25.26 24.30 8.46 10.19 24.23
15.54 26.99 26.99 7.33 12.57 25.98 25.98 8.52 10.40 24.97
15.85 28.07 28.07 7.43 12.88 27.02 27.02 8.61 10.70 25.97
16.44 30.32 16.85 7.55 13.41 28.83 16.24 8.65 11.14 27.36
16.55 30.53 19.24 7.60 13.51 29.04 18.64 8.71 11.22 27.55
16.67 30.75 22.09 7..66 13.60 29.24 21.51 8.77 11.30 27.74
16.79 30.97 24.92 7.71 13.70 29.45 24.37 8.83 11.38 27.94
16.78 30.99 27.49 7.71 13.71 29.52 26.82 8.84 11.40 28.07
17.56 33.89 14.97 7.99 14.48 32.22 14.28 9.07 12.12 30.55
17.57 33.96 18.07 7.99 14.50 32.29 17.35 9.08 12.14 30.63
17.60 34.05 20.41 8.00 14.52 32.37 19.66 9.08 12.16 30.71
17.61 34.08 23.52 8.00 14.53 32.40 22.73 9.09 12.17 30.73
17.62 34.15 25.86 8.01 14.55 32.47 25.04 9.09 12.19 30.79

46oC
TSH COMP
kW
kWl
17.25 9.52
20.54 9.58
23.43 9.65
24.97 9.72
25.97 9.79
15.61 9.74
18.01 9.81
20.89 9.88
23.75 9.95
26.09 9.96
13.59 10.15
16.60 10.16
18.88 10.16
21.90 10.16
24.18 10.17

EER

8.45
8.51
8.57
8.77
9.05
9.38
9.45
9.51
9.58
9.62
10.27
10.29
10.31
10.32
10.33

EER

7.19
7.24
7.30
7.50
7.75
7.98
8.04
8.09
8.15
8.19
8.77
8.79
8.81
8.81
8.83

YRM036 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
35.22 22.59 5.84 20.27 33.96 22.58 7.01
23
35.47 28.26 5.88 20.41 34.20 27.78 7.06
16
25
35.72 33.77 5.93 20.56 34.44 32.73 7.11
27
36.32 36.32 6.01 20.62 35.08 35.08 7.19
29
37.61 37.61 6.17 20.81 36.36 36.36 7.33
23
40.09 22.19 6.42 20.86 38.79 21.54 7.51
25
40.38 25.21 6.47 21.00 39.06 24.58 7.56
19
27
40.66 28.64 6.51 21.15 39.34 28.04 7.62
29
40.95 32.45 6.56 21.30 39.61 31.89 7.67
31
41.24 35.83 6.56 21.45 39.63 35.18 7.67
25
44.82 19.61 6.94 21.93 43.12 18.91 8.01
27
44.86 23.55 6.95 21.95 43.16 22.81 8.01
22
29
44.91 26.53 6.95 21.94 43.21 25.77 8.02
31
44.95 30.51 6.96 21.96 43.25 29.72 8.02
33
45.00 33.48 6.96 21.96 43.29 32.66 8.02

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.29 32.59 22.47 8.26 13.27 31.21 22.28 9.53 11.01 29.82
16.41 32.82 27.20 8.32 13.36 31.43 26.55 9.60 11.09 30.03
16.53 33.05 31.59 8.38 13.46 31.65 30.43 9.67 11.17 30.25
16.66 33.75 33.75 8.45 13.62 32.40 32.40 9.73 11.35 31.05
16.92 35.01 35.01 8.58 13.92 33.65 33.65 9.84 11.66 32.29
17.26 37.07 20.82 8.67 14.28 35.33 20.07 9.85 11.98 33.60
17.38 37.33 23.87 8.74 14.38 35.58 23.13 9.92 12.07 33.84
17.50 37.59 27.34 8.80 14.49 35.83 26.60 9.99 12.15 34.08
17.63 37.86 31.22 8.86 14.59 36.09 30.47 10.06 12.24 34.32
17.63 37.93 34.41 8.86 14.60 36.20 33.56 10.07 12.28 34.48
18.26 41.31 18.17 9.16 15.30 39.49 17.41 10.31 12.99 37.68
18.28 41.35 22.02 9.17 15.32 39.53 21.20 10.32 13.01 37.72
18.29 41.39 24.94 9.18 15.34 39.57 24.08 10.32 13.03 37.76
18.29 41.43 28.84 9.18 15.34 39.61 27.92 10.33 13.03 37.79
18.29 41.48 31.76 9.18 15.34 39.65 30.80 10.33 13.03 37.83

46oC
TSH COMP
kW
kWl
21.98 10.80
25.84 10.88
29.25 10.96
31.05 11.01
32.29 11.11
19.31 11.02
22.35 11.09
25.80 11.17
29.66 11.25
32.65 11.27
16.65 11.46
20.37 11.46
23.20 11.47
26.98 11.48
29.81 11.48

EER

9.29
9.36
9.43
9.62
9.92
10.19
10.26
10.34
10.41
10.45
11.15
11.17
11.19
11.19
11.19

GTH
kW
28.46
28.66
28.87
29.73
30.95
31.90
32.12
32.35
32.58
32.77
35.89
35.93
35.96
36.00
36.03

52oC
TSH COMP
kW
kWl
21.60 12.05
25.08 12.14
28.07 12.23
29.73 12.28
30.95 12.35
18.53 12.17
21.55 12.26
24.96 12.34
28.79 12.43
31.68 12.45
15.90 12.59
19.55 12.59
22.31 12.60
26.01 12.61
28.79 12.61

GTH
kW
27.75
27.94
28.14
29.07
30.18
30.83
31.05
31.27
31.49
31.74
34.60
34.63
34.67
34.70
34.74

52oC
TSH COMP
kW
kWl
21.36 12.21
24.65 12.30
27.44 12.39
29.07 12.45
30.18 12.52
18.03 12.34
21.42 12.42
25.02 12.51
28.62 12.60
31.16 12.62
15.36 12.79
18.94 12.79
21.66 12.80
25.31 12.81
28.04 12.81

EER

7.95
8.00
8.06
8.26
8.55
8.75
8.81
8.88
8.94
8.98
9.66
9.68
9.70
9.70
9.70

YRM036 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2100 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
33.78 22.57 5.82 19.51 32.64 22.48 7.02
23
34.02 27.70 5.86 19.65 32.87 27.22 7.07
16
25
34.26 32.58 5.91 19.79 33.11 31.64 7.12
27
35.07 35.07 5.98 20.03 33.95 33.95 7.19
29
36.40 36.40 6.09 20.40 35.23 35.23 7.30
23
39.09 21.68 6.24 20.93 37.53 21.03 7.39
25
39.37 25.11 6.28 21.08 37.80 24.49 7.44
19
27
39.64 28.77 6.33 21.22 38.06 28.15 7.50
29
39.92 32.40 6.37 21.37 38.33 31.81 7.55
31
39.98 35.48 6.38 21.39 38.42 34.78 7.56
25
43.84 19.21 6.67 22.28 42.08 18.49 7.84
27
43.88 23.12 6.68 22.28 42.12 22.36 7.85
22
29
43.93 26.09 6.68 22.29 42.16 25.29 7.85
31
43.97 30.04 6.69 22.30 42.21 29.21 7.86
33
44.02 33.00 6.69 22.31 42.25 32.14 7.86
* Data based on nominal condition without filter(s)

91

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.65 31.43 22.32 8.31 12.72 30.20 22.07 9.61 10.57 28.96
15.76 31.65 26.66 8.37 12.81 30.41 26.04 9.68 10.64 29.16
15.88 31.87 30.61 8.43 12.91 30.63 29.57 9.75 10.72 29.37
16.11 32.73 32.73 8.50 13.14 31.50 31.50 9.82 10.95 30.27
16.48 33.97 33.97 8.60 13.48 32.70 32.70 9.91 11.26 31.43
16.96 35.86 20.31 8.63 13.89 34.18 19.57 9.87 11.57 32.50
17.08 36.11 23.78 8.69 13.99 34.42 23.02 9.94 11.65 32.72
17.20 36.37 27.45 8.75 14.09 34.66 26.68 10.01 11.73 32.96
17.32 36.63 31.12 8.81 14.19 34.91 30.35 10.08 11.82 33.19
17.35 36.76 33.98 8.82 14.22 35.08 33.10 10.09 11.86 33.40
18.22 40.21 17.71 9.07 15.04 38.33 16.93 10.32 12.60 36.45
18.23 40.25 21.53 9.08 15.05 38.37 20.67 10.33 12.62 36.49
18.24 40.29 24.42 9.09 15.05 38.41 23.52 10.33 12.63 36.52
18.25 40.33 28.29 9.09 15.06 38.45 27.32 10.34 12.64 36.56
18.25 40.37 31.18 9.09 15.07 38.48 30.17 10.34 12.64 36.60

46oC
TSH COMP
kW
kWl
21.75 10.93
25.37 11.00
28.50 11.08
30.27 11.15
31.43 11.23
18.81 11.11
22.23 11.19
25.87 11.27
29.51 11.35
32.15 11.37
16.14 11.56
19.81 11.56
22.59 11.57
26.32 11.58
29.12 11.58

EER
8.92
8.98
9.05
9.27
9.55
9.77
9.84
9.91
9.98
10.03
10.69
10.70
10.71
10.72
10.72

EER
7.65
7.70
7.76
7.97
8.22
8.35
8.41
8.47
8.53
8.58
9.18
9.19
9.20
9.21
9.21

92

YRM044 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 /ls
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
40.40 26.80 6.99 19.44 39.15 26.74 8.18
23
40.69 33.10 7.04 19.58 39.42 32.59 8.24
16
25
40.98 38.99 7.09 19.72 39.70 37.95 8.30
27
41.77 41.77 7.18 19.87 40.54 40.54 8.38
29
43.35 43.35 7.32 20.19 42.11 42.11 8.52
23
46.92 25.43 7.64 20.94 45.33 24.80 8.81
25
46.94 29.10 7.65 20.95 45.34 28.48 8.81
19
27
46.93 33.26 7.65 20.94 45.34 32.64 8.81
29
46.95 37.89 7.65 20.95 45.35 37.29 8.81
31
47.06 42.02 7.66 20.96 45.50 41.35 8.83
25
50.87 22.42 8.01 21.66 49.23 21.76 9.16
27
50.92 27.19 8.02 21.67 49.28 26.49 9.17
22
29
50.93 30.78 8.02 21.67 49.29 30.05 9.17
31
50.93 35.54 8.02 21.67 49.29 34.78 9.17
33
50.93 39.14 8.02 21.67 49.29 38.35 9.17

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.11 37.76 26.60 9.49 13.40 36.33 26.36 10.83 11.29 34.88
16.23 38.03 31.96 9.55 13.49 36.58 31.27 10.91 11.39 35.12
16.34 38.30 36.80 9.62 13.59 36.84 35.58 10.99 11.45 35.37
16.52 39.20 39.20 9.70 13.79 37.81 37.81 11.06 11.66 36.40
16.86 40.74 40.74 9.84 14.13 39.34 39.34 11.19 11.99 37.91
17.56 43.58 24.08 10.08 14.74 41.78 23.33 11.40 12.51 39.97
17.56 43.60 27.77 10.09 14.75 41.80 27.00 11.40 12.52 39.99
17.56 43.59 31.93 10.09 14.75 41.80 31.15 11.40 12.51 39.99
17.56 43.61 36.57 10.09 14.75 41.81 35.78 11.40 12.52 40.00
17.59 43.79 40.54 10.10 14.79 42.03 39.66 11.42 12.57 40.25
18.33 47.44 21.03 10.42 15.54 45.61 20.28 11.70 13.30 43.76
18.34 47.49 25.71 10.42 15.55 45.66 24.90 11.70 13.31 43.82
18.34 47.51 29.24 10.42 15.55 45.68 28.38 11.71 13.31 43.84
18.34 47.51 33.91 10.42 15.55 45.68 33.00 11.71 13.31 43.84
18.34 47.51 37.45 10.42 15.55 45.68 36.49 11.71 13.31 43.84

46oC
TSH COMP
kW
kWl
26.02 12.20
30.51 12.28
34.34 12.37
36.40 12.45
37.91 12.57
22.54 12.72
26.19 12.72
30.31 12.72
34.91 12.72
38.71 12.74
19.51 13.00
24.07 13.00
27.49 13.00
32.04 13.00
35.48 13.00

EER

9.62
9.69
9.76
9.98
10.30
10.72
10.73
10.73
10.73
10.78
11.49
11.50
11.50
11.50
11.50

GTH
kW
33.43
33.66
33.90
34.99
36.49
38.16
38.18
38.18
38.19
38.49
41.91
41.97
42.00
42.00
42.00

52oC
TSH COMP
kW
kWl
25.60 13.56
29.69 13.66
33.08 13.76
34.09 13.83
36.49 13.94
21.74 14.04
25.35 14.04
29.43 14.04
33.98 14.04
37.70 14.07
18.75 14.29
23.22 14.29
26.59 14.29
31.06 14.29
34.44 14.29

GTH
kW
31.73
31.95
32.18
33.37
34.89
36.15
36.17
36.17
36.18
36.53
39.94
40.00
40.03
40.03
40.03

52oC
TSH COMP
kW
kWl
24.99 13.95
28.65 14.05
31.59 14.15
33.37 14.24
34.89 14.37
20.83 14.47
24.39 14.47
28.40 14.47
32.89 14.47
36.42 14.50
17.92 14.78
22.30 4.78
25.60 14.79
29.97 14.79
33.27 14.79

EER

8.29
8.35
8.41
8.63
8.94
9.27
9.28
9.28
9.28
9.33
10.01
10.02
10.02
10.02
10.02

YRM044 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 2800 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
39.85 26.79 6.45 20.77 38.39 26.67 7.81
23
40.13 32.87 6.50 20.91 38.66 32.25 7.86
16
25
40.41 38.53 6.55 21.06 38.93 37.32 7.92
27
41.28 41.28 6.61 21.31 39.86 39.86 7.98
29
42.95 42.95 6.73 21.77 41.49 41.49 8.11
23
46.58 25.30 7.00 22.69 44.69 24.54 8.36
25
46.50 28.97 7.01 22.70 44.70 28.22 8.36
19
27
46.60 33.13 7.01 22.70 44.70 32.38 8.36
29
46.61 37.76 7.01 22.70 44.71 37.03 8.36
31
46.75 41.89 7.02 22.74 44.88 41.07 8.38
25
50.78 22.39 7.31 23.70 48.80 21.58 8.68
27
50.83 27.16 7.31 23.71 48.85 26.31 8.68
22
29
50.85 30.74 7.32 23.72 48.87 29.86 8.68
31
50.85 35.50 7.32 23.72 48.87 34.57 8.68
33
50.85 39.10 7.32 23.72 48.87 38.14 8.68
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.55 36.77 26.44 9.29 13.31 35.10 26.08 10.84 10.90 33.42
16.66 37.03 31.49 9.36 13.41 35.35 30.62 10.91 10.98 33.66
16.78 37.29 35.96 9.43 13.50 35.60 34.54 10.99 11.06 33.90
17.03 38.28 38.28 9.50 13.74 36.65 36.65 11.07 11.29 35.01
17.45 39.89 39.89 9.63 14.13 38.23 38.23 11.20 11.65 36.56
18.23 42.61 23.68 9.85 14.76 40.47 22.76 11.38 12.13 38.31
18.24 42.62 27.35 9.85 14.76 40.49 26.42 11.38 12.14 38.33
18.24 42.62 31.51 9.85 14.76 40.48 30.55 11.38 12.14 38.33
18.24 42.64 36.15 9.85 14.77 40.50 35.15 11.38 12.14 38.34
18.29 42.85 40.09 9.87 14.82 40.75 38.99 11.41 12.19 38.64
19.18 46.63 20.70 10.17 15.65 44.41 19.78 11.70 12.95 42.17
19.20 46.69 25.36 10.17 15.66 44.47 24.37 11.70 12.97 42.24
19.20 46.71 28.86 10.17 15.66 44.49 27.81 11.70 12.97 42.26
19.20 46.71 33.52 10.17 15.66 44.49 32.39 11.70 12.97 42.26
19.20 46.71 37.03 10.17 15.66 44.49 35.84 11.70 12.97 42.26

46oC
TSH COMP
kW
kWl
25.60 12.39
29.68 12.48
33.08 12.57
35.01 12.66
36.56 12.79
21.81 12.93
25.42 12.93
29.51 12.93
34.06 12.93
37.80 12.96
18.85 13.24
23.35 13.24
26.72 13.25
31.20 13.25
34.59 13.25

EER

9.07
9.14
9.20
9.44
9.76
10.11
10.12
10.12
10.12
10.17
10.87
10.88
10.89
10.89
10.89

EER

7.66
7.71
7.77
7.99
8.28
8.52
8.53
8.53
8.53
8.59
9.22
9.23
9.24
9.24
9.24

YRM054 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
52.69 33.08 8.87 19.97 51.03 33.09 10.54
23
53.06 40.64 8.94 20.11 51.39 40.14 10.61
16
25
53.44 47.92 9.00 20.25 51.76 46.86 10.69
27
53.57 53.57 9.02 20.26 52.03 52.03 10.71
29
55.50 55.50 9.20 20.58 53.92 53.92 10.89
23
61.46 32.69 9.72 21.57 59.31 31.81 11.36
25
61.51 37.07 9.73 21.58 59.36 36.21 11.37
19
27
61.52 42.29 9.72 21.58 59.36 41.45 11.36
29
61.54 47.52 9.73 21.58 59.39 46.69 11.37
31
61.57 52.73 9.73 21.59 59.42 51.91 11.37
25
66.76 29.04 10.19 22.35 64.45 28.08 11.81
27
66.86 34.79 10.20 22.36 64.55 33.78 11.82
22
29
66.90 39.07 10.21 22.37 64.60 38.03 11.83
31
66.92 44.74 10.21 22.37 64.61 43.64 11.83
33
66.92 48.97 10.21 22.37 64.61 47.83 11.83

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.29 49.24 33.01 12.34 13.43 47.40 32.81 14.18 11.25 45.55
16.41 49.59 39.52 12.43 13.52 47.73 38.83 14.28 11.33 45.87
16.53 49.94 45.67 12.52 13.62 48.07 44.43 14.39 11.41 46.20
16.57 50.36 50.36 12.55 13.69 48.65 48.65 14.43 11.50 46.92
16.90 52.21 52.21 12.71 14.01 50.46 50.46 14.58 11.81 48.69
17.81 56.99 30.84 13.13 14.81 54.62 29.83 14.93 12.48 52.23
17.82 57.04 35.24 13.13 14.82 54.67 34.23 14.93 12.49 52.28
17.82 57.04 40.49 13.13 14.82 54.67 39.45 14.93 12.49 52.28
17.83 57.08 45.74 13.14 14.83 54.72 44.69 14.94 12.50 52.34
17.83 57.10 50.95 13.14 14.83 54.74 49.88 14.94 12.50 52.35
18.61 61.97 27.04 13.55 15.60 59.45 25.98 15.32 13.24 56.90
18.63 62.08 32.68 13.56 15.62 59.56 31.55 15.33 13.26 57.02
18.64 62.12 36.88 13.56 15.63 59.60 35.69 15.33 13.26 57.06
18.64 62.14 42.43 13.56 15.63 59.62 41.16 15.33 13.27 57.08
18.64 62.14 46.57 13.56 15.63 59.62 45.24 15.33 13.27 57.08

46oC
TSH COMP
kW
kWl
32.51 16.05
38.03 16.16
43.13 16.28
46.92 16.33
48.69 16.47
28.78 16.75
33.16 16.75
38.35 16.75
43.56 16.75
48.70 16.76
24.91 17.10
30.39 17.11
34.46 17.11
39.84 17.12
43.86 17.11

EER

9.55
9.62
9.69
9.80
10.09
10.64
10.65
10.65
10.66
10.66
11.35
11.37
11.38
11.38
11.38

GTH
kW
43.68
43.99
44.30
45.18
46.91
49.82
49.88
49.88
49.94
49.95
54.34
54.45
54.50
54.52
54.52

52oC
TSH COMP
kW
kWl
32.09 17.92
37.16 18.04
41.78 18.17
45.18 18.24
46.91 18.37
27.71 18.58
32.04 18.58
37.18 18.58
42.35 18.59
47.43 18.59
23.82 18.90
29.20 18.91
33.20 18.91
38.47 18.91
42.41 18.91

GTH
kW
41.57
41.86
42.16
43.45
45.54
48.87
48.94
48.94
49.02
49.04
54.73
54.88
54.94
54.96
54.96

52oC
TSH COMP
kW
kWl
31.46 18.01
36.05 18.13
40.23 18.26
43.45 18.35
45.54 18.50
27.27 18.72
31.60 18.73
36.71 18.72
41.87 18.73
46.92 18.73
23.98 19.11
29.40 19.12
33.42 19.12
38.71 19.13
42.66 19.12

EER

8.20
8.26
8.32
8.46
8.71
9.15
9.16
9.16
9.17
9.17
9.81
9.83
9.83
9.83
9.83

YRM054 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
50.62 33.09 8.73 19.50 48.96 32.99 10.43
23
50.98 40.02 8.79 19.64 49.31 39.44 10.51
16
25
51.34 46.59 8.86 19.78 49.66 45.49 10.58
27
51.68 51.68 8.89 19.83 50.17 50.17 10.63
29
53.81 53.81 9.07 20.24 52.29 52.29 10.80
23
60.18 32.16 9.56 21.47 58.08 31.30 11.26
25
60.23 36.56 9.57 21.48 58.14 35.71 11.26
19
27
60.24 41.80 9.57 21.47 58.15 40.95 11.26
29
60.27 47.04 9.57 21.48 58.19 46.21 11.27
31
60.30 52.26 9.58 21.49 58.22 51.43 11.27
25
66.30 28.85 10.05 22.50 64.15 27.95 11.74
27
66.42 34.60 10.06 22.52 64.27 33.66 11.75
22
29
66.47 28.88 10.07 22.52 64.32 37.90 11.75
31
66.49 44.53 10.07 22.53 64.35 43.51 11.75
33
66.49 48.76 10.07 22.53 64.35 47.70 11.75
* Data based on nominal condition without filter(s)

93

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.79 47.16 32.79 12.28 12.92 45.31 32.47 14.17 10.76 43.45
15.90 47.49 38.73 12.37 13.01 45.63 37.92 14.27 10.83 43.75
16.02 47.83 44.26 12.46 13.10 45.95 42.96 14.38 10.91 44.06
16.11 48.53 48.53 12.51 13.23 46.85 46.85 14.44 11.07 45.15
16.52 50.64 50.64 12.68 13.63 48.96 48.96 14.60 11.44 47.25
17.60 55.83 30.35 13.08 14.56 53.53 29.35 14.95 12.22 51.21
17.62 55.89 34.76 13.09 14.57 53.60 33.75 14.95 12.23 51.28
17.61 55.90 40.00 13.09 14.57 53.59 38.96 14.95 12.23 51.27
17.62 55.95 45.25 13.09 14.58 53.66 44.20 14.96 12.24 51.35
17.63 55.97 50.45 13.09 14.58 53.68 49.37 14.96 12.24 51.37
18.65 61.84 26.98 13.54 15.58 59.49 26.00 15.38 13.19 57.12
18.67 61.97 32.63 13.55 15.60 59.63 31.58 15.39 13.22 57.26
18.67 62.02 36.84 13.56 15.61 59.68 35.73 15.40 13.22 57.32
18.68 62.05 42.38 13.56 15.61 59.70 41.20 15.40 13.23 57.34
18.68 62.05 46.52 13.56 15.61 59.70 45.29 15.40 13.23 57.34

46oC
TSH COMP
kW
kWl
32.02 16.09
37.03 16.20
41.61 16.32
45.15 16.40
47.25 16.55
28.33 16.83
32.69 16.83
37.87 16.83
43.07 16.84
48.19 16.84
25.00 17.24
30.50 17.25
34.59 17.25
39.98 17.25
44.00 17.25

EER

9.08
9.15
9.21
9.39
9.74
10.38
10.40
10.39
10.41
10.41
11.31
11.33
11.34
11.34
11.34

EER

7.77
7.82
7.88
8.08
8.40
8.91
8.92
8.92
8.93
8.93
9.77
9.79
9.80
9.80
9.80

94

YRM060 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
59.85 35.43 10.13 19.87 57.89 35.62 12.32
23
60.28 44.73 10.20 20.01 58.30 44.24 12.41
16
25
60.70 53.76 10.28 20.16 58.71 52.53 12.50
27
60.53 60.53 10.28 20.10 58.72 58.72 12.51
29
62.65 62.65 10.51 20.34 60.81 60.81 12.72
23
70.24 36.87 11.26 21.28 67.70 35.87 13.39
25
70.29 41.52 11.27 21.29 67.75 40.57 13.39
19
27
70.31 47.10 11.27 21.29 67.77 46.20 13.40
29
70.33 52.70 11.27 21.29 67.79 51.86 13.40
31
70.31 58.24 11.27 21.29 67.79 57.42 13.40
25
76.23 33.12 11.88 21.89 73.55 32.01 13.96
27
76.27 39.33 11.89 21.90 73.59 38.20 13.96
22
29
76.27 44.00 11.89 21.90 73.59 42.83 13.96
31
76.29 50.28 11.89 21.90 73.61 49.08 13.96
33
76.30 54.94 11.89 21.90 73.61 53.71 13.96

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.81 55.91 35.70 14.52 12.95 53.83 35.66 16.84 10.75 51.73
15.92 56.30 43.67 14.63 13.04 54.21 42.98 16.96 10.83 52.09
16.03 56.70 51.26 14.73 13.14 54.59 49.88 17.08 10.91 52.46
16.02 56.89 56.89 14.75 13.16 54.97 54.97 17.11 10.96 53.04
16.31 58.95 58.95 14.95 13.45 57.00 57.00 17.29 11.25 55.02
17.26 65.13 34.83 15.53 14.31 62.46 33.73 17.77 11.99 59.75
17.26 65.18 39.57 15.54 14.31 62.51 38.48 17.78 12.00 59.81
17.27 65.21 45.24 15.54 14.32 62.53 44.18 17.78 12.00 59.83
17.27 65.22 50.94 15.54 14.32 62.55 49.88 17.78 12.00 59.85
17.27 65.24 56.50 15.54 14.32 62.59 55.43 17.78 12.01 59.90
17.98 70.83 30.88 16.06 15.05 68.01 29.71 18.24 12.72 65.16
17.99 70.88 37.02 16.06 15.06 68.06 35.79 18.24 12.73 65.21
17.99 70.88 41.62 16.06 15.06 68.06 40.33 18.24 12.73 65.21
17.99 70.89 47.82 16.06 15.06 68.07 46.47 18.24 12.73 65.22
17.99 70.90 52.41 16.06 15.06 68.08 51.01 18.24 12.73 65.23

46oC
TSH COMP
kW
kWl
35.48 19.18
42.19 19.31
48.44 19.45
53.04 19.50
55.02 19.66
32.58 20.03
37.34 20.04
43.03 20.04
48.73 20.04
54.26 20.04
28.52 20.44
34.52 20.44
39.00 20.44
45.06 20.44
49.54 20.44

EER

9.08
9..14
9.21
9.28
9.55
10.18
10.19
10.19
10.19
10.20
10.88
10.88
10.88
10.89
10.89

GTH
kW
49.57
49.92
50.28
51.05
52.99
56.96
57.01
57.03
57.05
57.12
62.19
62.24
62.24
62.25
62.26

52oC
TSH COMP
kW
kWl
35.16 21.57
41.29 21.73
46.93 21.88
51.05 21.94
52.99 22.09
31.37 22.37
36.10 22.37
41.77 22.38
47.45 22.38
52.92 22.38
27.27 22.73
33.18 22.74
37.58 22.74
43.54 22.74
47.94 22.74

GTH
kW
47.16
47.50
47.83
48.83
50.76
53.99
54.05
54.07
54.09
54.18
59.07
59.12
59.12
59.13
59.13

52oC
TSH COMP
kW
kWl
34.64 21.34
40.17 21.49
45.19 21.65
48.83 21.71
50.76 21.85
30.05 22.07
34.74 22.07
40.36 22.07
45.98 22.07
51.38 22.08
25.95 22.41
31.74 22.41
36.05 22.41
41.88 22.41
46.19 22.41

EER

7.73
7.79
7.84
7.94
8.18
8.69
8.69
8.70
8.70
8.71
9.33
9.34
9.34
9.34
9.34

YRM060 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 3600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
58.03 35.61 10.65 18.34 55.95 35.70 12.70
23
58.44 44.29 10.72 18.46 56.34 43.69 12.78
16
25
58.85 52.62 10.80 18.60 56.74 51.28 12.88
27
58.93 58.93 10.81 18.60 57.00 57.00 12.90
29
61.28 61.28 11.00 19.01 59.27 59.27 13.07
23
69.13 36.43 11.59 20.36 66.23 35.28 13.60
25
69.18 41.11 11.59 20.37 66.28 40.00 13.60
19
27
69.21 46.71 11.59 20.37 66.31 45.66 13.60
29
69.23 52.35 11.59 20.37 66.33 51.35 13.60
31
69.23 57.90 11.60 20.37 66.35 56.91 13.61
25
75.84 32.96 12.10 21.39 72.62 31.63 14.08
27
75.88 39.17 12.10 21.39 72.67 37.80 14.08
22
29
75.88 43.83 12.10 21.39 72.67 42.42 14.08
31
75.91 50.11 12.10 21.40 72.69 48.66 14.08
33
75.91 54.77 12.11 21.40 72.69 53.28 14.08
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
14.83 53.86 35.66 14.76 12.28 51.65 35.47 16.92 10.27 49.43
14.93 54.24 42.99 14.86 12.37 52.02 42.17 17.04 10.34 49.78
15.04 54.62 49.89 14.97 12.46 52.39 48.40 17.16 10.42 50.13
15.08 55.05 55.05 15.00 12.52 53.01 53.01 17.21 10.51 50.93
15.47 57.24 57.24 15.17 12.88 55.11 55.11 17.36 10.83 52.96
16.62 63.30 34.08 15.62 13.83 60.25 32.80 17.73 11.59 57.16
16.63 63.35 38.83 15.63 13.83 60.30 37.55 17.74 11.60 57.22
16.64 63.38 44.52 15.63 13.84 60.33 43.25 17.74 11.60 57.24
16.64 63.40 50.23 15.63 13.84 60.35 48.95 17.74 11.61 57.26
16.64 63.44 55.78 15.63 13.85 60.40 54.49 17.75 11.61 57.33
17.60 69.37 30.28 16.07 14.73 66.00 28.87 18.14 12.41 62.59
17.61 69.42 36.39 16.08 14.73 66.05 34.90 18.15 12.42 62.65
17.61 69.42 40.96 16.07 14.73 66.05 39.40 18.15 12.42 65.65
17.61 69.44 47.13 16.08 14.74 66.07 45.48 18.15 12.42 62.66
17.62 69.44 51.70 16.08 14.74 66.07 49.98 18.15 12.42 62.66

46oC
TSH COMP
kW
kWl
35.13 19.11
41.23 19.24
46.83 19.38
50.93 19.44
52.96 19.58
31.46 19.87
36.19 19.87
41.87 19.88
47.55 19.88
53.03 19.88
27.44 20.24
33.37 20.24
37.78 20.24
43.75 20.24
48.16 20.24

EER

8.70
8.76
8.83
8.94
9.23
9.82
9.82
9.83
9.83
9.84
10.55
10.56
10.56
10.56
10.56

EER

7.43
7.49
7.54
7.68
7.92
8.35
8.36
8.36
8.36
8.37
8.99
9.00
9.00
9.00
9.00

YRM072 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
74.92 45.35 12.07 21.18 71.94 45.43 14.29
23
74.10 56.04 12.00 21.08 71.29 55.29 14.23
16
25
73.28 66.40 11.93 20.95 70.72 64.72 14.19
27
73.65 73.65 12.01 20.93 71.29 71.29 14.27
29
76.09 76.09 12.30 21.12 73.72 73.72 14.53
23
83.21 44.45 13.03 21.79 80.13 43.21 15.18
25
83.26 50.51 13.04 21.79 80.18 49.29 15.19
19
27
83.30 57.77 13.04 21.79 80.22 56.58 15.19
29
83.31 65.04 13.04 21.79 80.23 63.88 15.19
31
83.36 72.21 13.05 21.80 80.29 71.05 15.20
25
90.02 39.33 13.79 22.28 86.86 38.04 15.88
27
90.07 47.28 13.79 22.28 86.91 45.92 15.89
22
29
90.10 53.25 13.80 22.28 86.94 51.85 15.89
31
90.18 61.18 13.81 22.29 87.02 59.71 15.90
33
90.21 67.16 13.81 22.29 87.05 65.65 15.90

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
17.18 68.62 45.34 16.78 13.96 65.30 45.05 19.26 11.57 61.93
17.10 68.16 54.31 16.74 13.90 65.03 53.20 19.23 11.54 61.85
17.01 67.85 62.78 16.71 13.86 64.98 60.78 19.23 11.53 62.07
17.06 68.65 68.65 16.79 13.95 66.01 66.01 19.23 11.66 63.33
17.31 71.06 71.06 17.03 14.24 68.41 68.41 19.53 11.95 65.71
18.01 76.73 41.81 17.56 14.91 73.32 40.36 19.95 12.54 69.87
18.01 76.77 47.88 17.57 14.91 73.36 46.41 19.95 12.55 69.91
18.02 76.82 55.18 17.57 14.92 73.42 53.69 19.95 12.55 69.97
18.02 76.83 62.49 17.57 14.92 73.42 60.98 19.96 12.55 69.97
18.02 76.90 69.63 17.58 14.93 73.51 68.07 19.96 12.56 70.06
18.66 83.39 36.61 18.17 15.65 79.90 35.18 20.48 13.31 76.39
18.67 83.45 44.41 18.18 15.66 79.97 42.87 20.48 13.32 76.46
18.67 83.47 50.27 18.18 15.66 79.99 48.65 20.48 13.32 76.48
18.68 83.56 58.04 18.19 15.67 80.08 56.31 20.49 13.33 76.57
18.68 83.59 63.92 18.19 15.68 80.12 62.12 20.49 13.34 76.61

46oC
TSH COMP
kW
kWl
44.56 21.78
51.93 21.77
58.69 21.79
63.33 21.88
65.71 22.06
38.85 22.36
44.86 22.36
52.09 22.37
59.34 22.37
66.36 22.38
33.72 22.80
41.28 22.81
46.97 22.81
54.50 22.81
60.23 22.82

EER

9.70
9.69
9.72
9.87
10.16
10.66
10.67
10.67
10.67
10.68
11.43
11.44
11.44
11.45
11.46

GTH
kW
58.33
58.44
58.95
60.47
62.83
66.17
66.22
66.28
66.28
66.39
72.63
72.70
72.71
72.81
72.85

52oC
TSH COMP
kW
kWl
43.81 24.48
50.43 24.49
56.39 24.60
60.47 24.94
62.83 24.95
37.20 24.95
43.13 24.95
50.28 25.44
57.43 25.44
64.36 25.44
32.15 25.29
39.55 25.30
45.13 25.30
52.49 25.30
58.11 25.30

GTH
kW
56.58
56.79
57.42
59.01
61.29
64.04
64.08
64.14
64.14
64.25
70.11
70.18
70.19
70.29
70.33

52oC
TSH COMP
kW
kWl
43.37 24.80
49.63 24.81
55.24 24.86
59.01 24.97
61.29 25.12
36.23 25.29
42.10 25.29
49.18 25.30
56.28 25.30
63.13 25.31
31.09 25.68
38.38 25.69
43.87 25.69
51.11 25.69
56.65 25.70

EER

8.13
8.15
8.33
9.05
9.06
9.06
9.06
10.12
10.13
10.13
9.80
9.81
9.81
9.82
9.82

YRM072 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 4200 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
71.53 45.43 11.92 20.48 68.86 45.35 14.22
23
70.89 55.16 11.87 20.38 68.37 54.38 14.18
16
25
70.37 64.49 11.84 20.29 68.06 62.93 14.16
27
71.11 71.11 11.91 20.38 68.95 68.95 14.24
29
73.78 73.78 12.12 20.77 71.55 71.55 14.44
23
80.74 43.46 12.65 21.77 77.73 42.22 14.93
25
80.79 49.53 12.66 21.78 77.78 48.30 14.94
19
27
80.84 56.83 12.66 21.78 77.83 55.60 14.94
29
80.86 64.12 12.66 21.78 77.84 62.92 14.94
31
80.92 71.29 12.67 21.79 77.92 70.07 14.95
25
88.20 38.58 13.24 22.73 84.92 37.24 15.50
27
88.26 46.50 13.25 22.74 84.98 45.08 15.50
22
29
88.29 52.45 13.25 22.74 85.00 50.98 15.51
31
88.38 60.35 13.26 22.75 85.10 58.79 15.51
33
88.41 66.31 13.26 22.75 85.13 64.70 15.52
* Data based on nominal condition without filter(s)

95

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
16.53 65.87 45.11 16.80 13.38 62.87 44.71 19.37 11.07 59.83
16.45 65.55 53.39 16.77 13.34 62.73 52.29 19.36 11.05 59.86
16.40 65.47 61.13 16.77 13.32 62.88 59.28 19.37 11.07 60.24
16.53 66.52 66.52 16.85 13.47 64.11 64.11 19.46 11.24 61.65
16.90 69.05 69.05 17.05 13.82 66.55 66.55 19.65 11.56 64.01
17.76 74.39 40.82 17.46 14.54 71.05 39.37 19.99 12.13 67.66
17.77 74.44 46.88 17.46 14.55 71.09 45.40 19.99 12.14 67.70
17.77 74.50 54.17 17.46 14.55 71.15 52.65 19.99 12.14 67.77
17.78 74.50 61.47 17.47 14.55 71.16 59.91 19.99 12.14 67.77
17.79 74.59 68.59 17.47 14.57 71.24 66.97 20.00 12.15 67.86
18.69 81.31 35.76 17.98 15.43 77.69 34.26 20.47 12.95 74.03
18.70 81.37 43.49 17.99 15.44 77.75 41.87 20.48 12.96 74.09
18.70 81.39 49.31 17.99 15.44 77.77 47.60 20.48 12.96 74.11
18.72 81.48 57.02 18.00 15.45 77.86 55.17 20.49 12.97 74.20
18.72 81.52 62.86 18.00 15.45 77.90 60.94 20.49 12.97 74.25

46oC
TSH COMP
kW
kWl
44.15 22.00
51.07 22.00
57.35 22.03
61.65 22.13
64.01 22.29
37.87 22.55
43.84 22.55
51.02 22.56
58.22 22.56
65.19 22.57
32.73 22.99
40.20 22.99
45.82 23.00
53.24 23.00
58.91 23.01

EER

9.28
9.29
9.33
9.50
9.80
10.24
10.24
10.25
10.25
10.26
10.99
10.99
11.00
11.01
11.01

EER

7.79
7.81
7.89
8.07
8.33
8.64
8.65
8.65
8.65
8.66
9.31
9.32
9.32
9.33
9.34

96

YRM088 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
86.79 53.31 14.83 19.68 84.00 53.55 18.55
23
87.40 68.35 14.93 19.82 84.59 67.43 18.68
16
25
88.02 82.82 15.04 19.96 85.19 80.58 18.81
27
89.64 89.64 15.16 20.17 86.91 86.91 18.94
29
92.98 92.98 15.42 20.58 90.17 90.17 19.19
23
102.96 54.33 16.17 21.73 99.14 52.91 19.86
25
103.00 61.50 16.17 21.73 99.18 60.17 19.87
19
27
102.99 70.10 16.17 21.73 99.18 68.88 19.86
29
103.01 78.67 16.17 21.73 99.19 77.56 19.87
31
103.02 87.35 16.17 21.73 99.29 86.05 19.87
25
111.86 48.89 16.84 22.67 107.80 47.28 20.51
27
111.94 58.58 16.85 22.67 107.88 56.92 20.52
22
29
111.98 65.84 16.85 22.68 107.92 64.16 20.52
31
111.98 75.49 16.85 22.68 107.92 73.78 20.52
33
111.98 82.79 16.84 22.68 107.92 81.05 20.52

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER
kW
kW
kWl
kW
kW
kWl
15.23 81.33 53.62 22.10 12.38 78.52 53.51 25.83 10.23
15.34 81.90 66.44 22.26 12.47 79.08 65.29 26.02 10.30
15.45 82.48 78.40 22.42 12.56 79.64 76.09 26.20 10.38
15.66 84.29 84.29 22.56 12.75 81.55 81.55 26.35 10.56
16.03 87.47 87.47 22.81 13.09 84.64 84.64 26.60 10.86
17.03 95.45 51.50 23.43 13.90 91.60 49.98 27.15 11.51
17.04 95.49 58.82 23.43 13.91 91.64 57.33 27.15 11.52
17.03 95.48 67.59 23.43 13.90 91.64 66.14 27.15 11.51
17.04 95.50 76.34 23.43 13.90 91.65 74.93 27.15 11.52
17.05 95.68 84.67 23.45 13.92 91.92 83.10 27.18 11.54
17.93 103.85 45.69 24.09 14.71 99.75 44.04 27.79 12.25
17.94 103.94 55.28 24.09 14.72 99.84 53.54 27.80 12.25
17.94 103.97 62.48 24.10 14.72 99.88 60.68 27.80 12.26
17.94 103.97 72.04 24.10 14.72 99.88 70.16 27.80 12.26
17.94 103.97 79.27 24.09 14.72 99.88 77.33 27.80 12.26

GTH
kW
75.69
76.22
76.76
78.78
81.78
87.73
87.76
87.76
87.78
88.13
95.61
95.72
95.76
95.76
95.76

46oC
TSH COMP
kW
kWl
53.22 29.60
64.02 29.81
73.73 30.02
78.78 30.18
81.78 30.42
48.40 30.90
55.77 30.90
64.58 30.90
73.37 30.90
81.36 30.93
42.36 31.53
51.75 31..54
58.81 31..54
68.19 31..54
75.28 31..54

GTH
kW
73.54
74.06
74.58
76.78
79.90
85.57
85.61
85.61
85.63
86.06
93.80
93.92
93.96
93.96
93.96

46oC
TSH COMP
kW
kWl
52.89 28.83
62.99 29.03
71.91 29.24
76.78 29.39
79.90 29.60
47.50 29.98
54.86 29.99
63.67 29.99
72.45 29.99
80.35 30.02
41.62 30.54
50.96 30.55
57.98 30.55
67.30 30.55
74.35 30.55

EER
8.60
8.66
8.73
8.91
9.17
9.69
9.69
9.69
9.69
9.73
10.35
10.36
10.36
10.36
10.36

GTH
kW
72.84
73.35
73.87
75.98
78.91
83.83
83.86
83.86
83.88
84.32
91.46
91.57
91.62
91.62
91.62

52oC
TSH COMP
kW
kWl
52.74 33.39
62.62 33.63
71.32 33.87
75.98 34.03
78.91 34.27
46.77 34.67
54.11 34.67
62.90 34.67
71.66 34.67
79.46 34.71
40.66 35.28
49.92 35.29
56.88 35.29
66.13 35.29
73.11 35.29

GTH
kW
70.59
71.09
71.59
73.89
76.91
81.45
81.48
81.49
81.51
82.03
89.36
89.48
89.53
89.53
89.53

52oC
TSH COMP
kW
kWl
52.25 32.03
61.45 32.26
69.40 32.49
73.89 32.65
76.91 32.85
45.75 33.16
53.06 33.16
61.82 33.16
70.56 33.16
78.25 33.20
39.79 33.70
48.98 33.71
55.88 33.71
65.05 33.71
71.98 33.71

EER
7.34
7.39
7.45
7.62
7.86
8.25
8.25
8.25
8.26
8.29
8.85
8.85
8.86
8.86
8.86

YRM088 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
85.02 53.48 16.34 17.50 82.12 53.61 19.49
23
85.62 67.79 16.46 17.63 82.70 66.75 19.63
16
25
86.22 81.39 16.58 17.75 83.29 79.05 19.77
27
88.04 88.04 16.69 18.00 85.21 85.21 19.89
29
91.56 91.56 16.91 18.47 88.63 88.63 20.10
23
101.70 53.86 17.56 19.76 97.65 52.35 20.68
25
101.74 61.07 17.57 19.77 97.69 59.63 20.68
19
27
101.73 69.71 17.56 19.76 97.69 68.37 20.68
29
101.75 78.32 17.57 19.76 97.70 77.08 20.68
31
101.80 86.94 17.57 19.77 97.85 85.52 20.69
25
111.19 48.63 18.17 20.88 106.84 46.89 21.27
27
111.28 58.31 18.17 20.89 106.93 56.63 21.27
22
29
111.31 65.57 18.18 20.90 106.97 63.76 21.27
31
111.31 75.21 18.18 20.90 106.97 73.37 21.27
33
111.31 82.51 18.17 20.90 106.97 80.63 21.27
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER
kW
kW
kWl
kW
kW
kWl
14.18 79.37 53.57 22.49 11.87 76.46 53.33 25.65 10.03
14.28 79.93 65.66 22.65 11.96 77.00 64.39 25.83 10.10
14.38 80.49 76.79 22.81 12.04 77.55 74.37 26.01 10.18
14.62 82.50 82.50 22.94 12.27 79.65 79.65 26.15 10.40
15.04 85.82 85.82 23.16 12.64 82.87 82.87 26.37 10.72
16.11 93.75 50.83 23.69 13.50 89.68 49.20 26.82 11.41
16.12 93.78 58.17 23.69 13.51 89.71 56.57 26.83 11.41
16.11 93.78 66.96 23.69 13.51 89.71 65.38 26.82 11.41
16.12 93.80 75.73 23.69 13.51 89.73 74.17 26.83 11.41
16.14 94.04 84.00 23.71 13.54 90.07 82.26 26.85 11.45
17.14 102.61 45.19 24.28 14.42 98.22 43.42 27.40 12.23
17.15 102.71 54.76 24.28 14.43 98.33 52.89 27.40 12.24
17.16 102.75 61.95 24.28 14.44 98.37 60.00 27.41 12.25
17.16 102.75 71.48 24.28 14.44 98.37 69.45 27.41 12.25
17.16 102.75 78.70 24.28 14.44 98.37 76.59 27.40 12.25

EER
8.58
8.64
8.70
8.91
9.21
9.74
9.74
9.74
9.74
9.79
10.48
10.49
10.49
10.49
10.49

EER
7.41
7.46
7.52
7.73
7.99
8.38
8.38
8.38
8.39
8.43
9.05
9.06
9.06
9.06
9.06

YRM108 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
107.50 66.03 25.63 14.11 102.50 66.19 27.33
23
108.26 81.89 25..81 14.20 103.22 80.44 27.53
16
25
109.02 97.18 26.00 14.31 103.95 94.00 27.72
27
109.02 109.20 25.86 14.41 104.59 104.59 27.71
29
113.69 113.69 26.18 14.82 108.94 108.94 28.13
23
128.79 67.70 27.83 15.79 122.04 65.02 29.72
25
128.88 76.39 27.83 15.80 122.15 73.80 29.73
19
27
128.92 86.74 27.84 15.80 122.17 84.26 29.73
29
128.97 97.11 27.83 15.81 122.24 94.73 29.74
31
129.02 107.45 27.84 15.81 122.29 105.15 29.74
25
141.59 61.44 29.01 16.65 134.26 58.39 31.16
27
141.80 73.05 29.03 16.67 134.49 69.91 31.19
22
29
141.90 81.71 29.04 16.67 134.58 78.49 31.20
31
141.95 93.16 29.04 16.68 134.63 89.93 31.21
33
141.96 101.71 29.04 16.68 134.65 98.31 31.20

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
12.62 97.10 65.91 29.17 11.20 91.59 65.12 31.04 9.93 86.03
12.71 97.78 78.55 29.38 11.28 92.24 76.28 31.26 10.00 86.64
12.80 98.47 90.42 29.59 11.36 92.89 86.60 31.48 10.07 87.25
12.88 99.59 99.59 29.70 11.44 94.51 94.51 31.74 10.16 89.37
13.21 103.81 103.81 30.23 11.72 98.58 98.58 32.37 10.39 93.31
14.01 114.83 62.04 31.74 12.34 107.50 58.90 33.80 10.85 100.12
14.02 114.94 70.86 31.76 12.35 107.62 67.69 33.82 10.86 100.24
14.02 114.96 81.35 31.76 12.35 107.62 78.12 33.82 10.86 100.24
14.03 115.05 91.86 31.77 12.35 107.74 88.61 33.84 10.86 100.38
14.03 115.09 102.27 31.78 12.36 107.78 98.94 33.85 10.86 100.41
14.70 126.47 55.14 33.45 12.90 118.57 51.82 35.77 11.31 110.62
14.71 126.71 66.50 33.49 12.91 118.82 62.96 35.81 11.32 110.89
14.72 126.81 74.96 33.50 12.92 118.92 71.25 35.83 11.32 110.99
14.72 126.85 86.12 33.51 12.92 118.96 82.18 35.84 11.33 111.03
14.72 126.85 94.46 33.50 12.92 118.96 90.34 35.83 11.32 111.04

46oC
TSH COMP
kW
kWl
63.83 32.93
73.65 33.16
82.60 33.40
89.37 33.79
93.31 34.54
55.63 35.87
64.31 35.90
74.61 35.90
84.97 35.93
95.14 35.93
48.46 38.10
59.32 38.16
67.39 38.18
78.02 38.19
85.95 38.18

EER
8.79
8.85
8.92
9.03
9.22
9.52
9.53
9.53
9.53
9.53
9.91
9.92
9.92
9.92
9.92

GTH
kW
80.48
81.05
81.62
84.25
88.05
92.75
92.89
92.87
93.03
93.06
102.70
102.98
103.09
103.12
103.17

52oC
TSH COMP
kW
kWl
62.03 34.81
70.67 35.06
78.43 35.31
84.25 35.85
88.05 36.69
52.25 37.94
60.76 37.97
70.84 37.97
80.99 38.01
90.91 38.01
45.10 40.42
55.61 40.49
63.42 40.52
73.69 40.53
81.35 40.51

GTH
kW
77.51
78.06
78.61
81.51
85.29
89.09
89.24
89.22
89.39
89.41
98.89
99.18
99.29
99.32
99.33

52oC
TSH COMP
kW
kWl
60.87 36.45
68.93 36.71
76.13 36.97
81.51 37.65
85.29 38.62
50.53 39.85
58.92 39.89
68.86 39.88
78.88 39.93
88.66 39.94
43.48 42.70
53.80 42.78
61.46 42.81
71.54 42.82
79.05 42.80

EER
7.78
7.83
7.89
8.02
8.19
8.34
8.35
8.35
8.35
8.35
8.67
8.68
8.68
8.68
8.68

YRM108 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 6000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
107.07 66.06 24.25 14.86 101.61 66.18 26.50
23
107.82 81.77 24.42 14.96 102.33 80.14 26.69
16
25
108.59 96.91 24.59 15.07 103.05 93.42 26.88
27
108.88 108.88 24.39 15.23 103.82 103.82 26.85
29
113.46 113.46 24.72 15.66 108.24 108.24 27.29
23
128.64 67.65 26.51 16.55 121.25 64.69 29.01
25
128.74 76.33 26.52 16.57 121.36 73.48 29.02
19
27
128.78 86.69 26.53 16.56 121.37 83.95 29.02
29
128.83 97.06 26.52 16.57 121.45 94.44 29.03
31
128.88 107.41 26.53 16.58 121.50 104.85 29.03
25
141.73 61.50 27.75 17.42 133.66 58.14 30.57
27
141.95 73.11 27.77 17.44 133.89 69.65 30.60
22
29
142.05 81.77 27.78 17.45 133.99 78.23 30.61
31
142.10 93.22 27.78 17..45 134.04 89.56 30.62
33
142.11 101.78 27.78 17.45 134.04 98.02 30.61
* Data based on nominal condition without filter(s)

97

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
12.90 95.69 65.75 28.94 11.12 89.67 64.73 31.43 9.60 83.59
12.99 96.37 78.00 29.14 11.20 90.30 75.41 31.65 9.67 84.18
13.09 97.05 89.46 29.35 11.28 90.94 85.24 31.88 9.74 84.77
13.20 98.35 98.35 29.49 11.38 92.77 92.77 32.19 9.83 87.14
13.53 102.61 102.61 30.07 11.64 96.87 96.87 32.90 10.04 91.07
14.26 113.33 61.41 31.68 12.21 105.28 57.93 34.39 10.45 97.18
14.27 113.44 70.22 31.70 12.21 105.41 66.70 34.41 10.45 97.31
14.27 113.46 80.71 31.70 12.21 105.41 77.11 34.41 10.45 97.31
14.28 113.56 91.23 31.71 12.22 105.54 87.55 34.40 10.46 97.46
14.28 113.60 101.63 31.72 12.22 105.57 97.84 34.45 10.46 97.48
14.92 125.08 54.55 33.56 12.72 116.38 50.89 36.60 10.85 107.62
14.93 125.32 65.80 33.60 12.73 116.63 61.97 36.65 10.86 107.89
14.94 125.43 74.32 33.62 12.73 116.74 70.20 36.67 10.86 108.00
14.94 125.47 85.45 33.63 12.73 116.78 81.05 36.68 10.86 108.03
14.94 125.47 93.76 33.62 12.73 116.79 89.15 36.67 10.86 108.03

46oC
TSH COMP
kW
kWl
63.10 33.94
72.38 34.18
80.78 34.42
87.14 34.93
91.07 35.76
54.29 37.12
62.92 37.16
73.14 37.15
83.42 37.19
93.50 37.20
47.19 39.65
57.92 39.72
65.90 39.75
76.40 39.76
84.23 39.74

EER
8.28
8.34
8.40
8.51
8.69
8.93
8.94
8.94
8.94
8.94
9.26
9.27
9.27
9.27
9.27

EER
7.16
7.21
7.26
7.39
7.54
7.63
7.64
7.63
7.64
7.64
7.90
7.91
7.91
7.91
7.91

98

YRM125 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH
TSH COMP EER GTH
TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
129.17 82.62 20.65 21.34 124.34 82.68 24.66
23
129.25 102.29 20.66 21.36 124.59 100.82 24.67
16
25
129.76 120.12 20.69 21.40 125.32 117.00 24.71
27
131.21 131.21 20.77 21.56 127.00 127.00 24.81
29
134.24 134.24 20.94 21.87 130.16 130.16 24.99
23
145.15 78.54 21.57 22.96 139.89 76.32 25.56
25
145.21 89.70 21.58 22.97 139.95 87.48 25.56
19
27
145.34 103.18 21.58 22.98 140.08 100.96 25.57
29
145.90 117.49 21.61 23.03 140.71 115.40 25.60
31
146.70 132.13 21.67 23.12 141.65 130.16 25.66
25
158.44 69.48 22.34 24.20 152.98 67.23 26.32
27
158.50 83.98 22.34 24.21 153.04 81.56 26.32
22
29
158.57 94.91 22.34 24.22 153.11 92.38 26.32
31
158.67 109.43 22.35 24.22 153.22 106.74 26.33
33
158.67 120.40 22.35 24.22 153.22 117.60 26.33

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH
TSH COMP EER GTH TSH COMP EER
kW
kW
kWl
kW
kW
kWl
17.21 119.71 82.52 28.49 14.34 114.79 82.09 32.58 12.04
17.23 120.13 99.25 28.51 14.37 115.37 97.41 32.61 12.07
17.31 121.07 113.94 28.58 14.46 116.54 110.61 32.69 12.17
17.47 122.96 122.96 28.69 14.63 118.67 118.67 32.81 12.34
17.77 126.24 126.24 28.88 14.91 122.08 122.08 33.02 12.62
18.68 134.82 74.14 29.40 15.65 129.45 71.78 33.46 13.20
18.68 134.89 85.27 29.40 15.66 129.52 82.85 33.47 13.21
18.69 135.02 98.72 29.41 15.66 129.65 96.23 33.47 13.22
18.75 135.71 113.24 29.45 15.72 130.41 110.79 33.51 13.28
18.84 136.76 128.08 29.52 15.81 131.57 125.69 33.59 13.37
19.84 147.70 65.03 30.17 16.70 142.14 62.71 34.22 14.17
19.84 147.76 79.19 30.17 16.71 142.20 76.65 34.23 14.18
19.85 147.83 89.88 30.18 16.72 142.28 87.20 34.23 14.18
19.86 147.94 104.06 30.18 16.72 142.39 101.16 34.24 14.19
19.86 147.94 114.79 30.18 16.72 142.31 111.74 34.24 14.19

GTH
kW
109.85
110.62
112.00
114.37
117.91
124.07
124.15
124.29
125.11
126.38
136.56
136.53
136.70
136.81
136.73

46oC
TSH COMP
kW
kWl
81.41 36.67
95.40 36.71
107.20 36.80
114.37 36.94
117.91 37.16
69.37 37.53
80.35 37.54
93.62 37.54
108.19 37.59
123.10 37.68
60.38 38.29
74.08 38.30
84.45 38.30
98.18 38.31
108.57 38.31

GTH
kW
107.53
108.41
109.94
112.50
116.21
122.13
122.21
122.35
123.22
124.57
134.96
135.03
135.11
135.22
135.22

46oC
TSH COMP
kW
kWl
81.00 37.30
94.41 37.37
105.64 37.49
112.50 37.68
116.21 37.97
68.49 38.42
79.43 38.43
92.65 38.44
107.22 38.51
122.15 38.61
59.71 39.44
73.33 39.44
83.66 .39.45
97.31 39.46
107.65 39.46

EER
10.22
10.28
10.39
10.56
10.83
11.28
11.29
11.29
11.36
11.45
12.17
12.17
12.18
12.19
12.19

GTH
kW
104.91
105.85
107.45
110.06
113.73
118.70
118.78
118.91
119.80
121.18
130.99
131.06
131.14
131.25
131.25

52oC
TSH COMP
kW
kWl
80.47 40.77
93.21 40.82
103.72 40.92
110.06 41.08
113.73 41.30
66.91 41.60
77.77 41.61
90.89 41.62
105.41 41.67
120.31 41.76
58.04 42..35
71.47 42.36
81.66 42.36
95.12 42.37
105..32 42.37

GTH
kW
101.61
102.69
104.49
107.31
111.16
115.50
115.58
115.73
116.68
118.15
127.94
128.02
128.10
128.21
128.21

52oC
TSH COMP
kW
kWl
79.70 42.02
91.66 42.11
101.40 42.25
107.31 42.48
111..16 42.79
65.42 43.17
76.19 43.17
89.21 43.19
103.70 43.27
117.54 43.38
56.75 44.21
70.03 44.22
80.11 44.23
93.42 44.24
103.50 44.24

EER
8.78
8.85
8.96
9.14
9.40
9.73
9.74
9.75
9.81
9.90
10.55
10.56
10.56
10.57
10.57

YRM125 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 5600 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH
TSH COMP EER GTH
TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
130.67 82.55 18.84 23.67 124.88 82.69 23.45
23
130.74 102.73 18.83 23.69 125.15 101.01 23.47
16
25
131.27 121.16 18.84 23.77 125.94 117.43 23.50
27
132.78 132.78 18.90 23.96 127.71 127.71 23.60
29
135.99 135.99 19.07 24.33 131.05 131.05 23.79
23
148.12 79.77 19.82 25.49 141.63 77.06 24.47
25
148.18 90.92 19.83 25.50 141.70 88.23 24.47
19
27
148.32 104.39 19.83 25.51 141.84 101.72 24.48
29
148.90 118.64 19.86 25.58 142.49 116.14 24.52
31
149.76 133.22 19.91 25.67 143.47 130.89 24.58
25
162.52 71.16 20.65 26.85 155.65 68.33 25.34
27
162.58 85.77 20.65 26.86 155.71 82.75 25.34
22
29
162.65 96.78 20.66 26.87 155.78 93.63 25.34
31
162.76 111.40 20.66 26.88 155.89 108.07 25.35
33
162.76 122.45 20.66 26.88 155.89 118.98 25.35
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH
TSH COMP EER GTH TSH COMP EER
kW
kW
kWl
kW
kW
kWl
18.17 119.34 82.49 27.87 14.61 113.44 81.93 32.58 11.88
18.20 119.81 99.13 27.90 14.65 114.11 96.89 32.63 11.93
18.28 120.83 113.76 27.97 14.74 115.39 109.75 32.73 12.03
18.46 122.85 122.85 28.10 14.92 117.68 117.68 32.89 12.21
18.79 126.31 126.31 28.32 15.22 121.26 121.26 33.14 12.48
19.75 135.38 74.38 28.94 15.96 128.76 71.47 33.68 13.04
19.76 135.45 85.52 28.95 15.97 128.83 82.54 33.68 13.05
19.77 135.59 98.98 28.95 15.98 128.97 95.91 33.69 13.06
19.83 136.31 113.51 29.00 16.04 129.77 110.49 33.75 13.12
19.92 137.41 128.37 29.08 13.13 131.00 125.41 33.84 13.21
20.96 148.99 65.57 29.87 17.02 141.98 62.65 34.65 13.98
20.97 149.05 79.77 29.88 17.02 142.05 76.58 34.65 13.99
20.97 149.13 90.50 29.88 17.03 142.13 87.13 34.66 13.99
20.98 149.24 104.72 29.89 17.04 142.24 101.09 34.67 14.00
20.98 149.24 115.49 29.89 17.04 142.24 111.65 34.67 14.00

EER
9.84
9.90
10.01
10.19
10.44
10.85
10.85
10.86
10.92
11.01
11.68
11.68
11.69
11.69
11.69

EER
8.25
8.32
8.44
8.62
8.86
9.13
9.14
9.14
9.20
9.29
9.87
9.88
9.88
9.89
9.89

YRM145 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
30oC
24oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
138.72 81.50 24.20 19.29 134.49 82.31 28.55
23
139.70 105.24 24.37 19.42 135.44 104.20 28.75
16
25
140.68 127.50 24.55 19.56 136.39 124.65 28.95
27
141.55 141.55 24.58 19.65 137.50 137.50 29.02
29
144.41 144.41 24.76 19.90 140.48 140.48 29.21
23
160.07 84.57 25.78 21.18 154.69 82.44 30.17
25
160.11 95.56 25.78 21.19 154.74 93.52 30.17
19
27
160.24 108.85 25.79 21.20 154.87 106.92 30.18
29
160.63 122.59 25.81 21.23 155.32 120.90 30.21
31
161.16 136.72 25.84 21.28 155.98 135.24 30.25
25
175.11 76.31 26.74 22.34 169.38 73.97 31.15
27
175.15 91.17 26.74 22.35 169.43 88.73 31.15
22
29
175.22 102.32 26.75 22.35 169.50 99.83 31.16
31
175.33 117.18 26.75 22.36 169.60 114.59 31.16
33
175.34 128.39 26.75 22.36 169.61 125.75 31.16

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
15.85 130.41 82.77 32.74 13.40 126.10 82.68 37.18 11.41 121.77
15.96 131.33 103.06 32.97 13.49 126.98 101.69 37.44 11.49 122.63
16.08 132.26 121.84 33.20 13.59 127.88 118.80 37.71 11.57 123.49
16.17 133.59 133.59 33.29 13.69 129.46 129.46 37.82 11.68 125.32
16.41 136.69 136.69 33.51 13.92 132.67 132.67 38.06 11.90 128.65
17.50 149.48 80.33 34.42 14.82 144.00 78.06 38.89 12.63 138.50
17.50 149.53 91.46 34.43 14.82 144.06 89.22 38.90 12.64 138.56
17.51 149.66 104.93 34.43 14.83 144.19 102.71 38.90 12.64 138.70
17.54 150.19 119.10 34.47 14.86 144.79 117.05 38.95 12.68 139.36
17.60 150.95 133.63 34.53 14.92 145.67 131.73 39.02 12.74 140.37
18.55 163.79 71.68 35.45 15.77 157.95 69.28 39.94 13.49 152.09
18.56 163.84 86.32 35.45 15.77 158.01 83.77 39.94 13.50 152.15
18.56 163.92 97.35 35.46 15.77 158.08 94.69 39.95 13.50 152.23
18.57 164.02 111.99 35.47 15.78 158.19 109.19 39.96 13.51 152.34
18.57 164.03 123.07 35.47 15.78 158.20 120.16 39.96 13.51 152.36

46oC
TSH COMP
kW
kWl
82.64 41.62
100.15 41.91
115.69 42.21
125.32 42.36
128.65 42.61
75.73 43.38
86.88 43.38
100.36 43..39
114.83 43.44
129.63 43.53
66.86 44.45
81.17 44.45
91.97 44.46
106.29 44.47
117.13 44.76

EER
9.85
9.92
9.99
10.09
10.30
10.89
10.90
10.90
10.94
11.01
11.67
11.68
11.68
11.69
11.69

GTH
kW
117.44
118.27
119.11
121.18
124.63
133.02
133.09
133.22
133.96
135.09
146.26
146.32
146.40
146.51
146.52

52oC
TSH COMP
kW
kWl
82.36 46.07
98.46 46.40
112.51 46.73
121.18 46.89
124.63 47.17
73.35 47.85
84.47 47.86
97.90 47.87
112.45 47.93
127.34 48.02
64.43 48.94
78.54 48.94
89.20 48.95
103.32 48.96
114.01 48.96

GTH
kW
112.36
113.15
113.95
116.38
120.10
127.33
127.40
127.55
128.40
129.69
140.80
140.88
140.95
141.07
141.08

52oC
TSH COMP
kW
kWl
81.71 48.24
96.24 48.58
108.68 48.92
116.38 49.10
120.10 49.36
70.83 49.87
81.88 49.87
95.22 49.88
109.82 49.95
124.78 50.04
62.16 50.80
76.04 50.81
86.55 50.81
100.47 50.82
110.99 50.82

EER
8.57
8.63
8.70
8.82
9.02
9.48
9.49
9.49
9..53
9.60
10.20
10.20
10.20
10.21
10.21

YRM145 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
138.52 81.43 23.78 19.60 133.31 82.20 28.64
23
139.50 105.18 23.95 19.74 134.25 103.88 28.85
16
25
140.48 127.37 24.12 19.88 135.20 123.85 29.05
27
141.41 141.41 24.21 19.93 136.44 136.44 29.16
29
144.38 144.38 24.48 20.12 139.55 139.55 29.43
23
160.42 84.70 25.81 21.20 153.84 82.10 30.59
25
160.46 95.69 25.82 21.21 153.89 93.19 30.60
19
27
160.59 108.98 25.83 21.21 154.02 106.60 30.61
29
160.99 122.71 25.86 21.23 154.51 120.63 30.65
31
161.55 136.82 25.93 21.27 155.22 135.01 30.72
25
175.94 76.65 27.14 22.12 168.96 73.80 31.84
27
175.99 91.52 27.15 22.12 169.01 88.56 31.85
22
29
176.06 102.68 27.15 22.12 169.09 99.65 31.86
31
176.17 117.55 27.16 22.13 169.20 114.41 31.86
33
176.19 128.77 27.16 22.13 169.21 125.55 31.86
* Data based on nominal condition without filter(s)

99

EER
15.66
15.77
15.89
15.96
16.18
17.16
17.16
17.17
17.20
17.24
18.10
18.11
18.11
18.12
18.12

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
GTH TSH COMP EER GTH TSH COMP EER GTH
kW
kW
kWl
kW
kW
kWl
kW
128.30 82.60 33.32 12.96 122.99 82.67 38.29 10.81 117.68
129.21 102.40 33.56 13.05 123.86 100.59 38.56 10.89 118.51
130.12 120.37 33.80 13.14 124.74 116.58 38.83 10.97 119.35
131.64 131.64 33.93 13.24 126.57 126.57 38.98 11.08 121.48
134.90 134.90 34.20 13.46 129.97 129.97 39.25 11.30 125.04
147.46 79.50 35.23 14.28 140.76 76.69 40.10 11.98 134.03
147.52 90.65 35.24 14.29 140.82 87.86 40.11 11.98 134.11
147.66 104.13 35.24 14.29 140.97 101.35 40.12 11.99 134.25
148.22 118.39 35.29 14.33 141.62 115.78 40.17 12.03 135.00
149.07 132.98 35.37 14.39 142.62 130.55 40.25 12.09 136.14
162.15 71.01 36.43 15.19 155.05 68.08 41.21 12.84 147.91
162.21 85.61 36.43 15.19 155.11 82.48 41.22 12.84 147.98
162.29 96.61 36.44 15.20 155.19 93.35 41.22 12.84 148.05
162.40 111.22 36.45 15.20 155.30 107.77 41.23 12.85 148.17
162.42 122.27 36.45 15.20 155.32 118.68 41.23 12.85 148.18

46oC
TSH COMP
kW
kWl
82.38 43.26
98.54 43.57
112.68 43.88
121.48 44.04
125.04 44.31
73.80 44.99
84.93 45.00
98.37 45.00
112..92 45.06
127.81 45.15
65.12 46.02
79.29 46.02
89.99 46.03
104.18 46.04
114.91 46.04

EER
9.15
9.22
9.28
9.41
9.63
10.17
10.17
10.17
10.22
10.29
10.97
10.97
10.97
10.98
10.98

EER
7.84
7.89
7.95
8.09
8.30
8.71
8.72
8.72
8.77
8.85
9.46
9.46
9.46
9.47
9.47

100

YRM175 R22 High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
SH
EER GTH SHF
SH
WET BULB DRY BULB GTH SHF
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
167.34 75.23 33.08 17.26 161.52 77.45 39.44
23
165.45 108.11 32.95 17.13 159.93 107.87 39.33
16.00
25
163.64 141.60 32.83 17.01 158.49 138.60 39.23
27
162.79 162.79 32.78 16.95 158.01 158.01 39.20
29
164.86 164.86 32.91 17.09 160.27 160.27 39.35
23
190.92 95.83 34.70 18.77 184.16 93.50 40.99
25
190.93 105.71 34.71 18.77 184.18 103.71 40.99
19.00
27
191.03 117.67 34.71 18.78 184.29 116.07 41.00
29
190.83 129.19 34.70 18.77 184.21 128.19 41.00
31
190.43 141.42 34.67 18.74 184.02 140.92 40.98
25
208.34 89.65 35.90 19.80 201.13 86.79 42.16
27
208.36 104.56 35.90 19.80 201.16 101.76 42.16
22.00
29
208.42 115.63 35.91 19.81 201.22 112.90 42.16
31
208.51 130.50 35.91 19.81 201.31 127.85 42.17
33
208.59 141.65 35.92 19.82 201.37 139.08 42.17

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH SHF
SH
EER GTH SHF
SH
EER
kW
kW
kWl
kW
kW
kWl
13.97 155.76 77.87 45.73 11.62 149.94 79.54 52.07 9.82
13.88 154.48 107.40 45.64 11.55 148.97 106.70 52.00 9.77
13.79 153.39 135.54 45.56 11.49 148.25 132.35 51.96 9.74
13.76 153.28 153.28 45.55 11.48 148.52 148.52 51.97 9.75
13.90 155.72 155.72 45.72 11.62 151.13 151.13 52.16 9.89
15.33 177.46 91.12 47.23 12.82 170.69 88.63 53.54 10.88
15.33 177.48 101.60 47.24 12.82 170.72 99.35 53.54 10.88
15.34 177.60 114.30 47.24 12.83 170.84 112.33 53.55 10.89
15.33 177.65 126.95 47.25 12.83 171.02 125.45 53.56 10.89
15.32 177.65 140.13 47.25 12.83 171.20 139.03 53.58 10.90
16.28 193.96 83.92 48.38 13.68 186.72 81.01 54.67 11.65
16.28 193.99 98.92 48.38 13.68 186.75 95.98 54.67 11.66
16.28 194.06 110.11 48.39 13.68 186.82 107.19 54.68 11.66
16.29 194.16 125.08 48.39 13.69 186.92 122.15 54.68 11.66
16.29 194.20 136.35 48.39 13.69 186.94 133.43 54.68 11.66

GTH
kW
144.06
143.39
143.05
143.69
146.49
163.84
163.88
164.01
164.31
164.70
179.39
179.43
179.51
179.61
179.61

46oC
SHF
SH
kW
kWl
81.76 58.49
105.76 58.45
129.04 58.43
143.69 58.47
146.49 58.67
86.03 59.91
96.94 59.91
110.14 59.92
123.68 59.94
137.62 59.97
78.05 61.02
92.96 61.02
104.15 61.03
119.05 61.04
130.30 61.04

GTH
kW
138.77
138.33
138.31
139.32
142.44
159.10
159.15
159.28
159.69
160.24
175.27
175.32
175.39
175.50
175.49

46oC
TSH COMP
kW
kWl
80.87 59.27
104.69 59.24
125.93 59.23
139.32 59.32
142.44 59.58
84.19 60.99
95.20 60.99
108.52 61.00
122.31 61.03
136.48 61.09
76.37 62.35
91.24 62.36
102.39 62.36
117.25 62.37
128.47 62.37

EER
8.40
8.37
8.36
8.39
8.52
9.33
9.33
9.34
9.35
9.37
10.03
10.03
10.04
10.04
10.04

GTH
kW
137.25
136.94
137.02
138.09
141.10
155.86
155.91
156.04
156.48
157.11
170.81
170.86
170.93
171.04
171.01

52oC
SHF
SH
kW
kWl
82.49 65.93
104.36 65.91
125.07 65.92
138.09 65.99
141.10 66.22
82.91 67.34
93.97 67.35
107.35 67.35
121.28 67.39
135.59 67.44
74.56 68.47
89.34 68.48
100.46 68.48
155.25 68.49
126.42 68.49

GTH
kW
131.63
131.58
132.01
133.48
136.80
150.58
150.63
150.78
151.33
152.14
165.98
166.04
166.12
166.23
166.19

52oC
TSH COMP
kW
kWl
81.96 68.01
102.97 68.00
121.67 68.05
133.48 68.18
136.80 68.47
80.78 69.70
91.90 69.71
105.36 69.72
119.52 69.77
134.03 69.85
72.58 71.08
87.28 71.08
98.33 71.09
113.03 71.10
124.14 71.10

EER
7.10
7.09
7.09
7.14
7.27
7.90
7.90
7.90
7.92
7.95
8.51
8.51
8.52
8.52
8.52

YRM175 R407C High Ambient Rooftop Unit Performance Rating


COOLING PERFORMANCE AT NOMINAL INDOOR AIRFLOW OF 8000 l/s
INDOOR COIL
ENTERING AIR
24oC
30oC
WET BULB DRY BULB GTH TSH COMP EER GTH TSH COMP
o
o
kW
kW
kWl
kW
kW
kWl
C
C
21
163.16 73.48 29.39 18.94 157.06 75.88 36.88
23
161.41 107.95 29.24 18.83 155.64 107.52 36.74
16
25
159.82 139.39 29.12 18.73 154.44 136.17 36.65
27
159.28 159.28 29.07 18.70 154.29 154.29 36.63
29
161.67 161.67 29.27 18.85 156.87 156.87 36.84
23
188.04 94.85 31.40 20.43 180.82 92.32 38.79
25
188.06 104.87 31.41 20.43 180.85 102.68 38.79
19
27
188.16 117.02 31.41 20.44 180.96 115.22 38.80
29
188.04 128.79 31.40 20.43 180.97 127.61 38.80
31
187.73 141.25 31.38 20.41 180.87 140.57 38.79
25
206.59 88.95 32.91 21.42 198.79 85.85 40.24
27
206.61 103.88 32.91 21.42 198.81 100.83 40.24
22
29
206.68 114.98 32.91 21.43 198.88 112.00 40.25
31
206.78 129.87 32.92 21.43 198.98 126.96 40.26
33
206.85 141.05 32.93 21.43 199.04 138.21 40.26
* Data based on nominal condition without filter(s)

OUTDOOR COIL ENTERING AIR TEMPERATURE DRY BULB oC


35oC
40oC
EER GTH TSH COMP EER GTH TSH COMP EER
kW
kW
kWl
kW
kW
kWl
14.54 151.02 79.26 44.26 11.64 144.93 80.70 51.72 9.56
14.46 149.92 106.83 44.17 11.58 144.16 105.90 51.65 9.53
14.38 149.11 132.89 44.10 11.54 143.74 129.49 51.62 9.50
14.37 149.34 149.34 44.12 11.55 144.37 144.37 51.67 9.53
14.53 152.11 152.11 44.35 11.70 147.30 147.30 51.92 9.68
15.91 173.66 89.73 46.11 12.85 166.42 87.02 53.51 10.61
19.51 173.69 100.35 46.11 12.85 166.46 97.87 53.51 10.61
15.92 173.81 113.22 46.12 12.86 166.59 110.99 53.52 10.62
15.92 173.94 126.14 46.13 12.86 166.85 124.38 53.54 10.63
15.91 174.07 139.56 46.15 12.87 167.20 138.20 53.57 10.65
16.85 191.03 82.74 47.53 13.71 183.19 79.59 54.90 11.38
16.86 191.06 97.74 47.54 13.71 183.23 94.54 54.91 11.39
16.86 191.14 108.94 47.54 13.72 183.30 105.74 54.91 11.39
16.86 191.24 123.91 47.55 13.72 183.41 120.68 54.92 11.39
16.87 191.27 135.19 47.55 13.72 183.42 131.95 54.92 11.39

EER
7.99
7.97
7.97
8.01
8.16
8.90
8.90
8.91
8.93
8.95
9.59
9.59
9.60
9.60
9.60

EER
6.60
6.60
6.62
6.68
6.82
7.37
7.37
7.38
7.40
7.43
7.97
7.97
7.97
7.98
7.98

THIS PAGE INTENTIONALLY LEFT BLANK

101

YRM 011 036D, R22 Physical Data (Standard Ambient)


MODELS

YRM
011

YRM
014

YRM
018

11.8

14.1

18.0

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

21.4

26.5

29.8

30.6

35.7

35.5

100 - 50 - 0

100 - 0

100 - 50 - 0

ZR
144 KC

ZR
72 KC

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits

Compressors/Circuit
100-0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
48 KC

ZR
57 KS

ZR
72 KC
1

ZR
81 KC

ZR
108 KC

ZR
125 KC

ZR
57 KC
2

4.5

5.3

6.6

6.8

9.0

10.0

4.8

12.0

6.0
10.1

QTY
Hp/Each
Nominal Total Comp. Kw Input (R22)

3.3

3.9

4.8

6.1

7.6

8.6

8.7

10.2

RLA/Each (R22)

5.9

7.2

8.4

10.2

13.1

15.1

7.5

16.8

8.4

Locked Rotor Amps/Each

50

61.8

74.0

101.0

111.0

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
Aluminium

Fin Material

HYDROPHILIC COATED ALUMINIUM

SEAMLESS COPPER, INNER GROVE (SIG)

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

30

32

Number of Rows

Fins Length (inch)

41

Fins Spacing (FPI)

14

41

48

36
2

54

41
16

12

CONDENSER FAN
Impeller

Type
560

Diameter (mm)

710
1

No. of Fan
Total Airflow (CFM)
Designation

2900

3200

3400

CH-560

CH-560

CH-560

7850

6500
APD 710

CONDENSER FAN MOTOR


FLANGE MOUNTING

Type

Foot-mounted
Direct

Drive Method
Hp/Each
Norminal Amp/Each
LRA/each
Fan Motor Specifications
Power Supply (V/P/Hz)

0.3

0.3

0.3

1.13

1.55

2.10

1.11

1.63

2.66

7.56

6 Poles, IP 54, Class B insulation

6 Poles, IP 55, Class F Insulation

220-240/1/50

380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

102

YRM 011 036D, R22 Physical Data (Standard Ambient)


MODELS

YRM
011

YRM
014

YRM
018

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
28

Tube Height (mm)

Fin Spacing (FPI)

22

Fin Length (inch)


13

16

30
12

13
Double Inlet Centrifugal Forward Fan
1

No. of Fan

Available External Static (" WG)


Designation

28

EVAPORATOR FAN
Type

Total Airflow (CFM)

48

36

Number of Rows

1270

1670

1907
AT 10-10S

AT 09-09S

2966

3178

3814

3814

4450

4450

KAT 15-15

KAT 12-12 C

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
0.75

Hp/Each

1.0

1.5

3.60

5.10

21.00

34.00

Norminal Amp/Each (A)

1.6

1.61

1.9

2.80

LRA/Each (A)

8.4

8.4

10.00

16.00

Fan Motor Specifications

4 Pole, IP 54, Class F Insulation

4 Poles, IP 55, Class F Insulation


380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION
Base frame

Base

Panel Feet

Height (mm)

900

Width (mm)

1106

1926

1528
1583

1223

Depth (mm)

1253

Skid Height (mm)

N/A

127

Skid Width (mm)

N/A

1700

Skid Depth (mm)

N/A

2050

WEIGHT
Factory Refrigerant Charge (kg)

2.5

2.0

3.0

5.0

6.5

Shipping Weight

203

225

247

383

430

9.6

7.6
481

503

524

544

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

103

YRM 044V - 175, R22 Physical Data (Standard Ambient)


MODELS

YRM
044V

YRM
054V

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

42.8

53.0

42.8

53.0

59.6

71.4

91.2

105.4

125.3

140.4

179.5

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KC

ZR
108 KC

ZR
81 KC

ZR
108 KC
2

ZR
125 KC

ZR
144 KC

SM
185

ZR
108 KC

6.8

9.0

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SM
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R22)

12.2

15.1

12.2

15.1

17.0

20.3

26.2

7.6

35.7

40.0

54.9

RLA/Each (R22)

10.2

13.1

10.2

13.1

15.1

16.8

23.3

13.1

29.1

37.1

23.3

Locked Rotor Amps/Each

101.0

111.0

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material
SIG

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

72

Number of Rows

36
2

48
3

72

54

Fins Length (inch)

85
12

Fins Spacing (FPI)

14

CONDENSER FAN
Impeller

Type
800

Diameter (mm)

710

No. of Fan
Total Airflow (CFM)

9000

11500

APD800

Designation

800

710

23000

32000

APD 800

APD 710

2
13000

15700
APD710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

Norminal Amp/Each

3.80

5.40

2.10

3.8

2.10

LRA/each

19.00

28.08

7.56

19.00

7.56

Hp/Each

Fan Motor Specifications


Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

104

YRM 044V - 175, R22 Physical Data (Standard Ambient)


MODELS

YRM
044V

YRM
054V

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
72

Tube Height (mm)


Number of Rows

36
4

28

Fin Length (inch)

48
4

54

60

71

54

12

Fin Spacing (FPI)


EVAPORATOR FAN
Type

14

Double Inlet Centrifugal Forward Fan


1

No. of Fan

Available External Static (" WG)


Total Airflow (CFM)

68

72
4

5933

6357

5933

6357

7628

KAT 15-15

Designation

8899

11866

KAT 18-18

12713

FDA 500

14832

16951

17000

FDA 560

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
4

5.5

5.5

10

15

Norminal Amp/Each (A)

6.70

8.80

6.70

8.80

15.50

21.50

LRA/Each (A)

49.00

63.00

49.00

63.00

111.00

153.00

Hp/Each

4 Poles, IP 55, Class F Insulation

Fan Motor Specifications

380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION
Base

Panel Feet

Base Frame

Height (mm)

2181

1205

2182

2147

Width (mm)

1850

2711

3222

3740

Depth (mm)

1756

2009

2013

Skid Height (mm)

127

N/A

Skid Width (mm)

1880

N/A

2159

2311

Skid Depth (mm)

1981

N/A

3429

3937

1510

2300
127

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

835

925

835

925

1013

1064

1280

1420

1650

1680

1800

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

105

YRM 011 036D, R407C Physical Data (Standard Ambient)


MODELS

YRM
011

YRM
014

YRM
018

11.6

13.7

17.6

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

19.9

24.7

27.7

28.4

33.2

33.0

100 - 50 - 0

100 - 0

100 - 50 - 0

ZR
144 KCE

ZR
72 KCE

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits

Compressors/Circuit
100 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
48 KCE

ZR
57 KSE

ZR
72 KCE
1

ZR
81 KCE

ZR
108 KCE

ZR
125 KCE

ZR
57 KCE
2

Hp/Each

4.5

5.3

6.6

6.8

9.0

10.0

4.8

12.0

6.0

Nominal Total Comp. Kw Input (R407C)

10.3

Designation
QTY

3.3

4.1

4.7

6.2

7.7

8.8

8.9

10.4

RLA/Each (R407C)

7.8

8.6

10.5

13.2

15.6

7.8

16.8

8.6

Locked Rotor Amps/Each

50

61.8

74

101.0

111.0

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
Aluminium

Fin Material

HYDROPHILIC COATED ALUMINIUM

SEAMLESS COPPER, INNER GROVE (SIG)

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

30

32

Number of Rows

Fins Length (inch)

41

Fins Spacing (FPI)

14

41

48

36
2

54

41
16

12

CONDENSER FAN
Impeller

Type
560

Diameter (mm)

710
1

No. of Fan
Total Airflow (CFM)
Designation

2900

3200

3400

CH-560

CH-560

CH-560

7850

6500
APD 710

CONDENSER FAN MOTOR


FLANGE MOUNTING

Type

Foot-mounted
Direct

Drive Method
Hp/Each
Norminal Amp/Each
LRA/each
Fan Motor Specifications
Power Supply (V/P/Hz)

0.3

0.3

0.3

1.13

1.55

2.10

1.11

1.63

2.66

7.56

6 Poles,IP 54, Class B insulation

6 Poles, IP 55, Class F Insulation

220-240/1/50

380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

106

YRM 011 036D, R407C Physical Data (Standard Ambient)


MODELS

YRM
011

YRM
014

YRM
018

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
28

Tube Height (mm)

Fin Spacing (FPI)

22

Fin Length (inch)


13

16

30
12

13
Double Inlet Centrifugal Forward Fan
1

No. of Fan

Available External Static (" WG)


Designation

28

EVAPORATOR FAN
Type

Total Airflow (CFM)

48

36

Number of Rows

1270

1670

1907
AT 10-10S

AT 09-09S

2966

3178

3814

3814

4450

4450

KAT 15-15

KAT 12-12 C

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
0.75

Hp/Each

1.0

1.5

3.60

5.10

21.00

34.00

Norminal Amp/Each (A)

1.6

1.61

1.9

2.80

LRA/Each (A)

8.4

8.4

10.00

16.00

Fan Motor Specifications

4 Pole,IP54,Class F Insulation

4 Poles, IP 55, Class F Insulation


380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION
Base frame

Base

Panel Feet

Height (mm)

900

Width (mm)

1106

1926

1528
1583

1223

Depth (mm)

1253

Skid Height (mm)

N/A

127

Skid Width (mm)

N/A

1700

Skid Depth (mm)

N/A

2050

WEIGHT
Factory Refrigerant Charge (kg)

2.5

2.0

3.0

5.0

6.5

Shipping Weight

203

225

247

383

430

9.6

7.6
481

503

524

544

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

107

YRM 044V - 175, R407C Physical Data (Standard Ambient)


MODELS

YRM
044V

YRM
054V

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

39.8

49.3

39.8

49.3

55.5

66.4

84.8

98.0

116.5

130.6

167.0

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR 81
KCE

ZR 108
KCE

ZR 81
KCE

ZR 108
KCE
2

ZR125
KCE

ZR144
KCE

SZ
185

ZR 108
KCE

6.8

9.0

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SZ
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R407C)

12.5

15.4

12.5

15.4

17.4

20.8

26.8

7.7

36.5

40.9

56.1

RLA/Each (R407C)

10.5

13.2

10.5

13.2

15.6

16.8

22.4

13.2

29.0

35.7

22.4

Locked Rotor Amps/Each

101.0

111.0

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material
SIG

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

72

Number of Rows

36
2

48
3

72

54

Fins Length (inch)

85
12

Fins Spacing (FPI)

14

CONDENSER FAN
Impeller

Type
800

Diameter (mm)

710

No. of Fan
Total Airflow (CFM)

9000

11500

APD800

Designation

800

710

23000

32000

APD 800

APD 710

2
13000

15700
APD710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

Norminal Amp/Each

3.80

5.40

2.10

3.8

2.10

LRA/each

19.00

28.08

7.56

19.00

7.56

Hp/Each

Fan Motor Specifications


Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

108

YRM 044V - 175, R407C Physical Data (Standard Ambient)


MODELS

YRM
044V

YRM
054V

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

EVAPORATOR COIL
Fin Material

ALUMINIUM

Tube Material

SEAMLESS COPPER, INNER GROVE

Tube Diameter (mm/inch)

9.53mm (3/8")

Coil Arrangement

VERTICAL

Tube Height (mm)


Number of Rows

72
3

Fin Length (inch)

36
4

28

48
4

54

68

60

Fin Spacing (FPI)


EVAPORATOR FAN

54

71

12

Type

14

Double Inlet Centrifugal Forward Fan

No. of Fan

Available External Static (" WG)


Total Airflow (CFM)

72
4

1
5933

6357
5933
KAT 15-15

Designation

6357

7628

8899

11866

KAT 18-18

12713

14832

FDA 500

16951

17000

FDA 560

EVAPORATOR FAN MOTOR


Type

Foot-mounted

Drive Method

Belt

Qty
Hp/Each

1
4

5.5

5.5

10

15

Norminal Amp/Each (A)

6.70

8.80

6.70

8.80

15.50

21.50

LRA/Each (A)

49.00

63.00

49.00

63.00

111.00

153.00

Fan Motor Specifications

4 Poles, IP 55, Class F Insulation

Power Supply (V/P/Hz)

380-415/3/50

DIMENSION/CONSTRUCTION
Base

Panel Feet

Base Frame

Height (mm)

2181

1205

2182

2147

Width (mm)

1850

2711

3222

3740

Depth (mm)

1756

2009

2013

Skid Height (mm)

127

N/A

Skid Width (mm)

1880

N/A

2159

2311

Skid Depth (mm)

1981

N/A

3429

3937

1510

2300
127

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

835

925

835

925

1013

1064

1280

1420

1650

1680

1800

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

109

YRM 022 036D, R22 Physical Data (High Ambient)


MODELS

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

19.1

24.2

27.7

27.7

32.6

32.6

100 - 50 - 0

100 - 0

100 - 50 - 0

ZR
144 KC

ZR
72 KC

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits

Compressors/Circuit
100 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KC

ZR
108 KC
1

ZR
125 KC

ZR
57 KC
2

6.8

9.0

10.0

4.8

12.0

6.0

QTY
Hp/Each
Nominal Total Comp. Kw Input (R22)

7.0

9.2

11.1

11.1

12.4

12.4

RLA/Each (R22)

11.8

16.2

18.4

9.1

20.8

10.4

Locked Rotor Amps/Each

101.0

111.0

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

48

Number of Rows

48
5

Fins Length (inch)

54

54

54

54

54

54

Fins Spacing (FPI)

12

14

14

14

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800
1

No. of Fan
Total Airflow (CFM)

6500

7850

7000

9000

APD 710

Designation

APD 800

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

1.5

Norminal Amp/Each

3.60

3.00

3.80

LRA/each

16.56

14.40

19.00

Hp/Each

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole
Power Supply (V/P/Hz)

6
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

110

YRM 022 036D, R22 Physical Data (High Ambient)


MODELS

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (mm)
Number of Rows

48

36
3

Fin Length (inch)

30

28
12

Fin Spacing (FPI)


EVAPORATOR FAN
Type

Double Inlet Centrifugal Forward Fan

No. of Fan

Available External Static (" WG)

Total Airflow (CFM)

2966

Designation

3178

3814

3814

4450

4450

KAT 15-15

KAT 12-12 C

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
Hp/Each

1.5

Norminal Amp/Each (A)

2.80

3.60

5.10

LRA/Each (A)

16.00

21.00

34.00

4 Poles, IP 55, Class F Insulation

Fan Motor Specifications

380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION

Panel Feet

Base
Height (mm)

1528

1223

Width (mm)

1926

Depth (mm)

1583

Skid Height (mm)

127

Skid Width (mm)

1700

Skid Depth (mm)

2050

WEIGHT
Factory Refrigerant Charge (kg)

5.0

6.5

Shipping Weight

393

440

9.6

7.6
491

513

534

554

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

111

YRM 044H - 175, R22 Physical Data (High Ambient)


MODELS

YRM
044H

YRM
054H

YRM
060

YRM
072

38.2

49.9

57.0

66.3

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

83.9

92.9

118.9

133.2

156.0

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
81 KC

ZR
108 KC

ZR
125 KC
2

ZR
144 KC

SM
185

ZR
108 KC

Hp/Each

6.8

9.0

10.0

12.0

15.0

9.0

Nominal Total Comp. Kw Input (R22)

14.0

18.6

22.4

25.4

34.7

RLA/Each (R22)

11.8

16.2

18.4

20.8

27.4

Locked Rotor Amps/Each

101.0

111.0

118.0

118.0

175

111.0

Designation
QTY

SY
240 A

SY
300 A

SM
185

20.0

25.0

15.0

9.2

41.6

47.9

67.4

16.2

33.6

42.6

27.4

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

72

72

72

72

Number of Rows

72
5

Fins Length (inch)

54

54

54

54

54

54

85

85

85

Fins Spacing (FPI)

12

14

14

14

12

14

12

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800

No. of Fan

710
4

Total Airflow (CFM)

13000

14000

15700

18000

APD710

Designation

26000

27600

33000

APD 800

35600

45000

APD 710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
Hp/Each

1.5

Norminal Amp/Each

3.60

2.70

3.00

LRA/each

16.56

11.07

14.40

1.5

3.80

6.4

6.4

19.00

33.28

14.40

33.28

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole

Power Supply (V/P/Hz)

4
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

112

YRM 044H - 175, R22 Physical Data (High Ambient)


MODELS

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
36

Tube Height (mm)


Number of Rows

48

Fin Length (inch)

72
4

54

60

54

71

12

Fin Spacing (FPI)


EVAPORATOR FAN
Type

14

Double Inlet Centrifugal Forward Fan


1

No. of Fan

Available External Static (" WG)


Total Airflow (CFM)

68

5933

6357

7628

KAT 15-15

Designation

8899

11866

KAT 18-18

12713

14832

FDA 500

16951

17000

FDA 560

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
4

5.5

10

15

Norminal Amp/Each (A)

6.70

8.80

15.50

21.50

LRA/Each (A)

49.00

63.00

111.00

153.00

Hp/Each

4 Poles, IP 55, Class F Insulation

Fan Motor Specifications

380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION

Base Frame

Base

2182

2147

Width (mm)

2711

3222

3740

2013

Height (mm)

1205

1510

Depth (mm)

2009

Skid Height (mm)

N/A

2300

Skid Width (mm)

N/A

2159

2311

Skid Depth (mm)

N/A

3429

3937

127

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

850

940

1028

1079

1295

1440

1670

1700

1820

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

113

YRM 022 036D, R407C Physical Data (High Ambient)


MODELS

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

18.1

23.6

26.2

26.2

31.5

31.5

100 - 50 - 0

100 - 0

100 - 50 - 0

ZR
144 KCE

ZR
72 KCE

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits

Compressors/Circuit
100 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KCE

ZR
108 KCE
1

ZR
125 KCE

ZR
57 KCE
2

6.8

9.0

10.0

4.8

12.0

6.0

QTY
Hp/Each
Nominal Total Comp. Kw Input (R407C)

7.2

9.3

11.0

11.0

12.6

12.6

RLA/Each (R407C)

13.0

16.2

18.8

8.3

20.8

11.1

Locked Rotor Amps/Each

101.0

111.0

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

48

Number of Rows

48
5

Fins Length (inch)

54

54

54

54

54

54

Fins Spacing (FPI)

12

14

14

14

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800
1

No. of Fan
Total Airflow (CFM)

6500

7850

7000

9000

APD 710

Designation

APD 800

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

1.5

Norminal Amp/Each

3.60

3.00

3.80

LRA/each

16.56

14.40

19.00

Hp/Each

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole
Power Supply (V/P/Hz)

6
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

114

YRM 022 036D, R407C Physical Data (High Ambient)


MODELS

YRM
022

YRM
027

YRM
030S

YRM
030D

YRM
036S

YRM
036D

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (mm)
Number of Rows

48

36
3

Fin Length (inch)

30
12

Fin Spacing (FPI)


EVAPORATOR FAN
Type

Double Inlet Centrifugal Forward Fan

No. of Fan

Available External Static (" WG)

Total Airflow (CFM)

28

2966

Designation

3178

3814

3814

4450

4450

KAT 15-15

KAT 12-12 C

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
Hp/Each

1.5

Norminal Amp/Each (A)

2.80

3.60

5.10

LRA/Each (A)

16.00

21.00

34.00

4 Poles, IP 55, Class F Insulation

Fan Motor Specifications

380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION

Panel Feet

Base
Height (mm)

1528

1223

Width (mm)

1926

Depth (mm)

1583

Skid Height (mm)

127

Skid Width (mm)

1700

Skid Depth (mm)

2050

WEIGHT
Factory Refrigerant Charge (kg)

5.0

6.5

Shipping Weight

393

440

9.6

7.6
491

513

534

554

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

115

YRM 044H - 175, R407C Physical Data (High Ambient)


MODELS

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

36.2

48.9

54.1

64.1

81.5

89.2

115.7

127.6

150.8

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KCE

ZR
108 KCE

ZR
125 KCE
2

ZR
144 KCE

SZ
185

ZR
108 KCE

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SZ
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R407C)

14.5

18.7

22.1

25.3

33.2

9.3

43.2

49.9

69.7

RLA/Each (R407C)

13.0

16.2

18.8

20.8

26.6

16.2

34.4

42.0

26.6

Locked Rotor Amps/Each

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

72

72

72

72

Number of Rows

72
5

Fins Length (inch)

54

54

54

54

54

54

85

85

85

Fins Spacing (FPI)

12

14

14

14

12

14

12

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800

710

No. of Fan
Total Airflow (CFM)

13000

14000

15700

4
18000

APD710

Designation

26000

27600

33000

APD 800

35600

45000

APD 710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method

1.5

Norminal Amp/Each

3.60

2.70

3.00

3.80

6.4

6.4

LRA/each

16.56

11.07

14.40

19.00

33.28

14.40

33.28

Hp/Each

1.5

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole

Power Supply (V/P/Hz)

4
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

116

YRM 044H - 175, R407C Physical Data (High Ambient)


MODELS

YRM
044H

YRM
054H

YRM
060

YRM
072

YRM
088

YRM
108

YRM
125

YRM
145

YRM
175

EVAPORATOR COIL
ALUMINIUM

Fin Material

SEAMLESS COPPER, INNER GROVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
36

Tube Height (mm)


Number of Rows

48

54

Fin Length (inch)

60

71

54
12

Fin Spacing (FPI)


EVAPORATOR FAN
Type

14

Double Inlet Centrifugal Forward Fan


1

No. of Fan

Available External Static (" WG)


Total Airflow (CFM)

68

72

5933

6357

7628

KAT 15-15

Designation

8899

11866

KAT 18-18

12713

14832

16951

17000

FDA 560

FDA 500

EVAPORATOR FAN MOTOR


Foot-mounted

Type

Belt

Drive Method

Qty
4

5.5

10

15

Norminal Amp/Each (A)

6.70

8.80

15.50

21.50

LRA/Each (A)

49.00

63.00

111.00

153.00

Hp/Each

4 Poles, IP 55, Class F Insulation

Fan Motor Specifications

380-415/3/50

Power Supply (V/P/Hz)


DIMENSION/CONSTRUCTION

Base Frame

Base
1205

Height (mm)

1510

2147

2182

Width (mm)

2711

3222

3740

Depth (mm)

2009

2013

2300

Skid Height (mm)

N/A

Skid Width (mm)

N/A

2159

127
2311

Skid Depth (mm)

N/A

3429

3937

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

850

940

1028

1079

1295

1440

1670

1700

1820

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

117

YCS 030 036D, R22 Physical Data (Standard Ambient)


MODELS

YCS 030S

YCS 030D

YCS 036S

YCS 036D

29.8

30.6

35.7

35.5

GENERAL
Nominal Capacity, kW
No. of Refrigerant Circuits

Compressors/Circuit
Capacity Step of Compressor %

100-0

100 - 50 - 0

100 - 0

Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

100 - 50 - 0

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
125 KC

Designation
QTY

ZR
57 KC

ZR
144 KC

ZR
72 KC

10.0

4.8

12.0

6.0

Nominal Total Comp. Kw Input (R22)

8.6

8.7

10.2

10.1

RLA/Each (R22)

15.1

7.5

16.8

8.4

Locked Rotor Amps/Each

118.0

61.8

118.0

74.0

Hp/Each

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)


Protection Device

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH


CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION

CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement

48

Tube Height (inch)


Number of Rows

Fins Length (inch)

54

Fins Spacing (FPI)

12

CONDENSER FAN
Impeller

Type
Diameter (mm)

710
1

No. of Fan
Total Airflow (CFM)

7850
APD 710

Designation
CONDENSER FAN MOTOR

Foot-mounted

Type

Direct

Drive Method

Hp/Each
Norminal Amp/Each

2.10
7.56

LRA/each
Fan Motor Specifications
Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

118

YCS 030 036D, R22 Physical Data (Standard Ambient)


MODELS

YCS 030S

YCS 030D

YCS 036S

YCS 036D

DIMENSION/CONSTRUCTION
Panel Feet

Base
Height (mm)

1462

Width (mm)

1069

Depth (mm)

1580

Skid Height (mm)

127

Skid Width (mm)

1135

Skid Depth (mm)

1700

WEIGHT
Factory Refrigerant Charge (kg)
Shipping Weight

9.6

7.6
280

296

304

330

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

119

YCS 044V - 175, R22 Physical Data (Standard Ambient)


MODELS

YCS
044V

YCS
054V

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

42.8

53.0

42.8

53.0

59.6

71.4

91.2

105.4

125.3

140.4

179.5

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KC

ZR
108 KC

ZR
81 KC

ZR
108 KC
2

ZR
125 KC

ZR
144 KC

SM
185

ZR
108 KC

6.8

9.0

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SM
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R22)

12.2

15.1

12.2

15.1

17.0

20.3

26.2

7.6

35.7

40.0

54.9

RLA/Each (R22)

10.2

13.1

10.2

13.1

15.1

16.8

23.3

13.1

29.1

37.1

23.3

Locked Rotor Amps/Each

101.0

111.0

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material
SIG

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

72

Number of Rows

36
2

48
3

72

54

Fins Length (inch)

85
12

Fins Spacing (FPI)

14

CONDENSER FAN
Impeller

Type
800

Diameter (mm)

710

No. of Fan
Total Airflow (CFM)

9000

11500

APD800

Designation

800

710

23000

32000

APD 800

APD 710

2
13000

15700
APD710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

Norminal Amp/Each

3.80

5.40

2.10

3.8

2.10

LRA/each

19.00

28.08

7.56

19.00

7.56

Hp/Each

Fan Motor Specifications


Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

120

YCS 044V - 175, R22 Physical Data (Standard Ambient)


MODELS

YCS
044V

YCS
054V

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

DIMENSION/CONSTRUCTION
Base

Panel Feet

Base Frame

Height (mm)

2181

1157

1462

Width (mm)

1004

1579

2080
1579

2156
2318

Depth (mm)

1760

2071

2071

2500

Skid Height (mm)

127

N/A

127

Skid Width (mm)

1118

1700

2311

Skid Depth (mm)

1981

2200

2667

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

430

511

430

511

555

589

760

825

1050

1065

1105

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

121

YCS 030 036D, R407C Physical Data (Standard Ambient)


MODELS

YCS
030S

YCS
030D

YCS
036S

YCS
036D

27.7

28.4

33.2

33.0

100 - 0

100 - 50 - 0

GENERAL
Nominal Capacity, kW
No. of Refrigerant Circuits

Compressors/Circuit
Capacity Step of Compressor %

100 - 0

100 - 50 - 0

Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
125 KCE

Designation
QTY
Hp/Each

ZR
57 KCE

ZR
144 KCE

ZR
72 KCE

10.0

4.8

12.0

6.0
10.3

Nominal Total Comp. Kw Input (R407C)

8.8

8.9

10.4

RLA/Each (R407C)

15.6

7.8

16.8

8.6

Locked Rotor Amps/Each

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)


Protection Device

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH


CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION

CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement

48

Tube Height (inch)


Number of Rows

Fins Length (inch)

54

Fins Spacing (FPI)

12

CONDENSER FAN
Impeller

Type
Diameter (mm)

710
1

No. of Fan
Total Airflow (CFM)

7850
APD 710

Designation
CONDENSER FAN MOTOR

Foot-mounted

Type

Direct

Drive Method

Hp/Each
Norminal Amp/Each

2.10
7.56

LRA/each
Fan Motor Specifications
Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

122

YCS 030 036D, R407C Physical Data (Standard Ambient)


MODELS

YCS
030S

YCS
030D

YCS
036S

YCS
036D

DIMENSION/CONSTRUCTION
Panel Feet

Base
Height (mm)

1462

Width (mm)

1069

Depth (mm)

1580

Skid Height (mm)

127

Skid Width (mm)

1135

Skid Depth (mm)

1700

WEIGHT
7.6

Factory Refrigerant Charge (kg)


Shipping Weight

280

9.6
296

304

330

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

123

YCS 044V - 175, R407C Physical Data (Standard Ambient)


MODELS

YCS
044V

YCS
054V

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
240 A

YCS
145

YCS
175

39.8

49.3

39.8

49.3

55.5

66.4

84.8

98.0

116.5

130.6

167.0

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR 81
KCE

ZR 108
KCE

ZR 81
KCE

ZR 108
KCE
2

ZR125
KCE

ZR144
KCE

SZ
185

ZR 108
KCE

6.8

9.0

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SZ
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R407C)

12.5

15.4

12.5

15.4

17.4

20.8

26.8

7.7

36.5

40.9

56.1

RLA/Each (R407C)

10.5

13.2

10.5

13.2

15.6

16.8

22.4

13.2

29.0

35.7

22.4

Locked Rotor Amps/Each

101.0

111.0

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material
SIG

Tube Material

SEAMLESS COPPER
9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

72

Number of Rows

36
2

48
3

72

54

Fins Length (inch)

85
12

Fins Spacing (FPI)

14

CONDENSER FAN
Impeller

Type
800

Diameter (mm)

710

No. of Fan
Total Airflow (CFM)

9000

11500

APD800

Designation

800

710

23000

32000

APD 800

APD 710

2
13000

15700
APD710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
2

Norminal Amp/Each

3.80

5.40

2.10

3.8

2.10

LRA/each

19.00

28.08

7.56

19.00

7.56

Hp/Each

Fan Motor Specifications


Power Supply (V/P/Hz)

6 Poles, IP 55, Class F Insulation


380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

124

YCS 044V - 175, R407C Physical Data (Standard Ambient)


MODELS

YCS
044V

YCS
054V

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

DIMENSION/CONSTRUCTION
Base

Panel Feet

Base Frame

Height (mm)

2181

1157

1462

Width (mm)

1004

1579

2080
1579

2156
2310

Depth (mm)

1760

2071

2071

2500

Skid Height (mm)

127

N/A

127

Skid Width (mm)

1118

1700

2311

Skid Depth (mm)

1981

2200

2667

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

430

511

430

511

555

589

760

825

1050

1065

1105

Note:
1. Nominal info based on Condensing temperature of 125 F, Evaporating temperature of 45 F and ambient temperature of 95 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

125

YCS 030 036D, R22 Physical Data (High Ambient)


MODELS

YCS
030S

YCS
030D

YCS
036S

YCS
036D

27.7

27.7

32.6

32.6

100 - 0

100 - 50 - 0

GENERAL
Nominal Capacity, kW
No. of Refrigerant Circuits

Compressors/Circuit
Capacity Step of Compressor %

100 - 0

100 - 50 - 0

Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
125 KC

Designation
QTY

ZR
57 KC

ZR
144 KC

ZR
72 KC

Hp/Each

10.0

4.8

12.0

6.0

Nominal Total Comp. Kw Input (R22)

11.1

11.1

12.4

12.4

RLA/Each (R22)

18.4

9.1

20.8

10.4

Locked Rotor Amps/Each

118.0

61.8

118.0

74.0

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)


Protection Device

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH


CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION

CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

48

48

Number of Rows

48
5

Fins Length (inch)

54

54

54

54

Fins Spacing (FPI)

14

14

14

14

CONDENSER FAN
Impeller

Type
Diameter (mm)

710

800
1

No. of Fan
Total Airflow (CFM)
Designation

7850

9000

APD 710

APD 800

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
Hp/Each

1.5

Norminal Amp/Each

3.00

3.80

LRA/each

14.40

Fan Motor Specifications

19.00
IP 55, Class F Insulation
6

No of Pole
Power Supply (V/P/Hz)

380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

126

YCS 030 036D, R22 Physical Data (High Ambient)


MODELS

YCS
030S

YCS
030D

YCS
036S

YCS
036D

DIMENSION/CONSTRUCTION
Panel Feet

Base
Height (mm)

1462

Width (mm)

1069

Depth (mm)

1580

Skid Height (mm)

127

Skid Width (mm)

1135

Skid Depth (mm)

1700

WEIGHT
7.6

Factory Refrigerant Charge (kg)


Shipping Weight

290

9.6
306

314

340

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

127

YCS 044H - 175, R22 Physical Data (High Ambient)


MODELS

YCS
044H

YCS
054H

YCS
060

YCS
072

38.2

49.9

57.0

66.3

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

83.9

92.9

118.9

133.2

156.0

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
81 KC

ZR
108 KC

ZR
125 KC
2

ZR
144 KC

SM
185

ZR
108 KC

Hp/Each

6.8

9.0

10.0

12.0

15.0

9.0

Nominal Total Comp. Kw Input (R22)

14.0

18.6

22.4

25.4

34.7

RLA/Each (R22)

11.8

16.2

18.4

20.8

27.4

Locked Rotor Amps/Each

101.0

111.0

118.0

118.0

175

111.0

Designation
QTY

SY
240 A

SY
300 A

SM
185

20.0

25.0

15.0

9.2

41.6

47.9

67.4

16.2

33.6

42.6

27.4

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

72

72

72

72

Number of Rows

72
5

Fins Length (inch)

54

54

54

54

54

54

85

85

85

Fins Spacing (FPI)

12

14

14

14

12

14

12

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800

No. of Fan

710

Total Airflow (CFM)

13000

14000

15700

18000

APD710

Designation

26000

27600

33000

APD 800

35600

45000

APD 710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
Hp/Each

1.5

Norminal Amp/Each

3.60

2.70

3.00

LRA/each

16.56

11.07

14.40

1.5

3.80

6.4

6.4

19.00

33.28

14.40

33.28

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole

Power Supply (V/P/Hz)

4
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

128

YCS 044H - 175, R22 Physical Data (High Ambient)


MODELS

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

DIMENSION/CONSTRUCTION
Base Frame

Base
1157

Height (mm)

1462

2156

2080

Width (mm)

1579

1579

2310

Depth (mm)

2071

2071

2500

Skid Height (mm)

N/A

127

Skid Width (mm)

1700

2311

Skid Depth (mm)

2200

2667

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

445

526

570

604

775

840

1070

1085

1125

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R22, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

129

YCS 030 036D, R407C Physical Data (High Ambient)


YCS
030S

MODELS

YCS

030D

YCS
036S

YCS
036D

GENERAL
Nominal Capacity, kW
No. of Refrigerant Circuits

26.2

26.2

31.5

31.5

100 - 0

100 - 50 - 0

Compressors/Circuit
Capacity Step of Compressor %

100 - 0

100 - 50 - 0

Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


ZR
125 KCE

Designation
QTY

ZR
57 KCE

ZR
144 KCE

ZR
72 KCE

10.0

4.8

12.0

6.0

Nominal Total Comp. Kw Input (R407C)

11.0

11.0

12.6

12.6

RLA/Each (R407C)

18.8

8.3

20.8

11.1

Locked Rotor Amps/Each

118.0

61.8

118.0

74.0

Hp/Each

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)


Protection Device

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH


CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION

CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

48

48

48

Number of Rows

48
5

Fins Length (inch)

54

54

54

54

Fins Spacing (FPI)

14

14

14

14

CONDENSER FAN
Impeller

Type
Diameter (mm)

710

800
1

No. of Fan
Total Airflow (CFM)
Designation

7850

9000

APD 710

APD 800

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method
Hp/Each

1.5

Norminal Amp/Each

3.00

3.80

LRA/each

14.40

Fan Motor Specifications

19.00
IP 55, Class F Insulation
6

No of Pole
Power Supply (V/P/Hz)

380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

130

YCS 030 036D, R407C Physical Data (High Ambient)


MODELS

YCS
030S

YCS
030D

YCS
036S

YCS
036D

DIMENSION/CONSTRUCTION
Panel Feet

Base
Height (mm)

1462

Width (mm)

1069

Depth (mm)

1580

Skid Height (mm)

127

Skid Width (mm)

1135

Skid Depth (mm)

1700

WEIGHT
7.6

Factory Refrigerant Charge (kg)


Shipping Weight

290

9.6
306

314

340

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

131

YCS 044H - 175, R407C Physical Data (High Ambient)


MODELS

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

36.2

48.9

54.1

64.1

81.5

89.2

115.7

127.6

150.8

GENERAL
Nominal Capacity, kW

No. of Refrigerant Circuits


1

Compressors/Circuit

100 - 50 - 0

Capacity Step of Compressor %


Material

ELECTRO-GALVANIZED MILD STEEL

Finishing

EPOXY-POLYESTER POWDER COATED

COMPRESSOR
SCROLL

Welded Hermetic Type


Designation

ZR
81 KCE

ZR
108 KCE

ZR
125 KCE
2

ZR
144 KCE

SZ
185

ZR
108 KCE

6.8

9.0

10.0

12.0

15.0

9.0

QTY
Hp/Each

SY
240 A

SY
300 A

SZ
185

25.0

15.0

4
20.0

Nominal Total Comp. Kw Input (R407C)

14.5

18.7

22.1

25.3

33.2

9.3

43.2

49.9

69.7

RLA/Each (R407C)

13.0

16.2

18.8

20.8

26.6

16.2

34.4

42.0

26.6

Locked Rotor Amps/Each

101.0

111.0

118.0

118.0

175

111.0

215

270

175

2900RPM

Nominal Speed (RPM)

342-462V

Voltage Range (V)

380-415V , 3 PHASE , 50HZ

Power Supply (V/P/Hz)

CURRENT OVERLOAD RELAY, MOTOR PROTECTOR, DUAL PRESSURE SWITCH

Protection Device

CRANKASE HEATER, ANTI-SHORT CYCLE PROTECTION


CONDENSER COIL(S)
HYDROPHILIC COATED ALUMINIUM

Fin Material

SEAMLESS COPPER INNER GROOVE

Tube Material

9.53mm (3/8")

Tube Diameter (mm/inch)

VERTICAL

Coil Arrangement
Tube Height (inch)

36

36

48

48

72

72

72

72

Number of Rows

72
5

Fins Length (inch)

54

54

54

54

54

54

85

85

85

Fins Spacing (FPI)

12

14

14

14

12

14

12

14

14

CONDENSER FAN
Impeller

Type
710

Diameter (mm)

800

710

No. of Fan
Total Airflow (CFM)

13000

14000

15700

4
18000

APD710

Designation

26000

27600

33000

APD 800

35600

45000

APD 710

CONDENSER FAN MOTOR


Foot-mounted

Type

Direct

Drive Method

1.5

Norminal Amp/Each

3.60

2.70

3.00

3.80

6.4

6.4

LRA/each

16.56

11.07

14.40

19.00

33.28

14.40

33.28

Hp/Each

1.5

IP 55, Class F Insulation

Fan Motor Specifications


4

No of Pole

Power Supply (V/P/Hz)

4
380-415/3/50

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

132

YCS 044H - 175, R407C Physical Data (High Ambient)


MODELS

YCS
044H

YCS
054H

YCS
060

YCS
072

YCS
088

YCS
108

YCS
125

YCS
145

YCS
175

DIMENSION/CONSTRUCTION
Base Frame

Base
1157

2080

2156

Width (mm)

1579

1579

2310

Depth (mm)

2071

2071

2500

Height (mm)

1462

Skid Height (mm)

N/A

127

Skid Width (mm)

1700

2311

Skid Depth (mm)

2200

2667

WEIGHT
Factory Refrigerant Charge (kg)

10.0

13.0

13.4

15.0

16.0

21.0

36.0

42.0

51.0

Shipping Weight

445

526

570

604

775

840

1070

1085

1125

Note:
1. Nominal info based on Condensing temperature of 145 F, Evaporating temperature of 45 F and ambient temperature of 125 F
2. Refrigerant R407C, Compressor Power Supply 380-415V/3Ph/50Hz
3. All Specifications are subject to change without prior notice.

133

134

Shopfloor YRM011 (Single Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40 mm DEEP


RETURN AIR SPIGOT : 40 mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

Shopfloor YRM011 (Single Circuit) Pin Code X


1
2
3
4
5
6
7
8
9

135

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

136

Shopfloor YRM014/018 (Single Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

Shopfloor YRM014/018 (Single Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

137

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

138

Shopfloor YRM022/027 (Single Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM022/027 (Single Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

139

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

140

Shopfloor YRM030/036 (S/D Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM030/036 (S/D Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 1.4m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

141

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

142

Shopfloor YRM044/054 VERT (Dual Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

BOTH SIDES
FOOTPRINT
PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM044/054 VERT (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

BOTH SIDES
FOOTPRINT
PLAN VIEW

LEFT SIDE VIEW

143

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

144

Shopfloor YRM044/054 HORIZ (Dual Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

SLOT 25.40 * 50.80, 4 PLACES


SLING PIPE LIFTING POINTS

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM044/054 HORIZ (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

SLOT 25.40 * 50.80, 4 PLACES


SLING PIPE LIFTING POINTS

PLAN VIEW

LEFT SIDE VIEW

145

FOOTPRINT

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

146

Shopfloor YRM060/072 (Dual Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

BOTH SIDES
SLOT 25.40 * 50.80, 4 PLACES
SLING PIPE LIFTING POINTS

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM060/072 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

BOTH SIDES

SLOT 25.40 * 50.80, 4 PLACES


SLING PIPE LIFTING POINTS

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

147

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

148

Shopfloor YRM088/108 (Dual Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

BOTH SIDES

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM088/108 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

BOTH SIDES
FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

149

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

150

Shopfloor YRM125/145/175 (Dual Circuit) Pin Code A


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

BOTH SIDES

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YRM125/145/175 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.
8.
9.

SUPPLY AIR SPIGOT : 40mm DEEP


RETURN AIR SPIGOT : 40mm DEEP
DRAIN : O.D. X 75 long NOM
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
BLOWER ACCESS CLEARANCE REQD : 1.2m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

BOTH SIDES

PLAN VIEW

LEFT SIDE VIEW

151

FOOTPRINT

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

152

152

Shopfloor YCS 030/036S (Single Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 7/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 0.8m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

LEFT SIDE VIEW

PLAN VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YCS 030/036D (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 7/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 0.8m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

PLAN VIEW

FOOTPRINT

LEFT SIDE VIEW

153

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

154

Shopfloor YCS 044/054 VERT (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 1-1/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 1.75m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YCS 044/054 HORIZ (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 1-1/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 1.75m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT
PLAN VIEW

LEFT SIDE VIEW

155

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

156

Shopfloor YCS 060/072 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 1-1/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 1.75m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

Shopfloor YCS 088/108 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 1-1/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

157

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

158

Shopfloor YCS 125/145/175 (Dual Circuit) Pin Code X


1.
2.
3.
4.
5.
6.
7.

SUCTION LINES : 1-1/8 O.D. x 75 long NOM.


LIQUID LINES : O.D. x 75 long NOM.
ELECTRICAL ENTRIES
SERVICE CLEARANCE REQD : 1.2m MINIMUM
AIR-ON CLEARANCE REQD : 1.6m MINIMUM
AIR-OFF CLEARANCE REQD : 3.0m MINIMUM
FORK TYNES FOR LIFTING : 2.0m MINIMUM
NOTE : GENERAL TOLERANCE = PLUS OR MINUS 5mm UNLESS
NOTED OTHERWISE, OVERALL DIMENSION = PLUS OR MINUS 10mm

63 HOLE, 4 PLACES
SLING PIPE LIFTING POINTS

FOOTPRINT

PLAN VIEW

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

159

THIS PAGE INTENTIONALLY LEFT BLANK

159

Standard and High Ambient YRM/YCS


Model

Total sound
pressure

Total sound
power

Total sound
pressure

Total sound
power

YRM/YCS

dBA

dBA

dBA

dBA

Standard ambient YRM/YCS

High ambient YRM/YCS

22

62.5

80.0

68.6

86.0

27

66.0

83.5

69.8

87.0

30D

64.1

81.5

65.0

82.5

30S

66.2

83.5

66.8

84.0

36D

64.5

82.0

67.8

85.0

36S

66.0

83.5

68.5

86.0

44H

65.5

83.0

71.6

89.0

44V

67.8

85.0

54H

69.0

86.5

72.1

90.0

54V

68.6

86.5

60

69.2

86.5

69.8

87.0

72

69.0

86.5

71.5

89.0

88

71.8

89.0

76.5

94.0

108

71.5

89.0

76.4

94.0

125

70.8

88.0

71.6

89.0

145

70.8

88.0

76.0

93.5

175

71.5

89.0

76.2

94.0

All the sound pressure data above is estimated base on 3m distance

160

1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor
plus 100% of the rated load amps for all other loads included in the circuit. Add the following MCA
values to the electrical tables for the system providing power to the transformer: 460V/3ph/60Hz,
add 1.3 amps: 380-415/3ph/50Hz, add 1.75 amps.
2. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due
to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and
stopping of the unit, and/or operation at ambient temperatures in excess of 35oC (95oF) is
anticipated.
3. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit.
4. The minimum recommended disconnect switch is based on 115% of the rated load amps for all
loads included in the circuit.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the
rated load amps for the largest motor plus 100% of the rated load amps for all other loads
included in the circuit.
6. A ground lug is provided for each compressor system to accommodate a field grounding
conductor. A control circuit grounding lug is also supplied.
7. The supplied disconnect is a Disconnecting Means and is intended for isolating the unit for the
available power supply to perform maintenance and troubleshooting. This disconnect is not
intended to be a Load Break Device.
8. Field Wiring by others which complies with the National Electrical Code & Local Codes.

161

162

YRM 011 YRM 175, 380-415V / 3PH / 50Hz (STANDARD AMBIENT) R22
MODEL
YRM011
YRM014
YRM018
MODEL
YRM 022
YRM 027
YRM 030S
YRM 030D
YRM 036S
YRM 036D
YRM 044V
YRM 044H
YRM 054V
YRM 054H
YRM 060
YRM 072
YRM 088
YRM 108
YRM 125
YRM 145
YRM 175
MODEL
YRM 088
YRM 125
YRM 145
YRM 175

MCB(A)
N/A
N/A
N/A

COPELAND COMPRESSOR
RLA(A)
LRA(A)
O/L(A)
5.9
50
7.5
7.2
62
9.0
8.4
74
10.5

COPELAND COMPRESSOR
RLA(A)
LRA(A)
10.2
101
13.1
111
15.1
118
7.5
62
16.8
118
8.4
74
10.2
101
10.2
101
13.1
111
13.1
111
15.1
118
16.8
118
22.7
198
13.1
111
28.3
225
36.3
272
22.7
198
DANFOSS COMPRESSOR
MCB(A)
RLA(A)
LRA(A)
63
23.3
175
80
29.1
215
100
37.1
270
63
23.3
175
MCB(A)
25
32
40
25
50
25
25
25
32
32
40
50
63
32
80
100
63

O/L(A)
12.5
16.0
18.5
9.0
20.5
10.5
12.5
12.5
16.0
16.0
18.5
20.5
27.5
16.0
34.0
44.0
27.5
O/L(A)
28.0
35.0
44.5
28.0

MCB(A)
N/A
N/A
N/A

MCB(A)
6
6
6
6
6
6
10
10
16
10
10
10
16
16
16
16
16
MCB(A)
16
16
16
16

CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
0.3 / 6P
1.00
1.11
0.3 / 6P
1.13
1.63
0.3 / 6P
1.55
2.66
CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
3.0 / 6P
5.4
28
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
2.0 / 6P
3.8
19
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
CONDENSING FAN
HP / POLE RLA(A)
LRA(A)
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6

FUSE(A)
2.00
2.00
2.00

MCB(A)
N/A
N/A
N/A

O/L(A)
2.5
2.5
2.5
2.5
2.5
2.5
4.5
2.5
6.0
2.5
2.5
2.5
4.5
4.5
2.5
2.5
2.5

MCB(A)
6
10
10
10
16
16
16
16
20
20
20
20
40
40
40
50
50

O/L(A)
4.2
2.5
2.5
2.5

MCB(A)
40
40
50
50

EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
0.75 / 4P
1.6
8.4
0.75 / 4P
1.6
8.4
1.0 / 4P
1.9
10.0
EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
1.5 / 4P
2.8
16
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
3.0 / 4P
5.1
34
3.0 / 4P
5.1
34
4.0 / 4P
6.7
49
4.0 / 4P
6.7
49
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153
EVAPORATOR FAN
HP / POLE RLA(A)
LRA(A)
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153

Notes:
1. Nominal info based on Condensing temperature of 125 F, evaporating temperature of 45 F and ambient temperature of 95 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

O/L(A)
2.0
2.0
2.25

O/L(A)
3.1
4.0
4.0
4.0
6.0
6.0
7.5
7.5
10
10
10
10
17.5
17.5
17.5
24.0
24.0
O/L(A)
17.5
17.5
24.0
24.0

TOTAL
RLA(A)
8.50
9.93
11.85
TOTAL
RLA(A)
15.1
18.8
20.8
20.7
24
24.0
30.9
31.3
40.4
39.2
43.2
46.6
68.5
75.5
80.5
102.5
120.7
TOTAL
RLA(A)
69.7
82.1
104.1
123.1

YRM 011 YRM 175, 380-415V / 3PH / 50Hz (STANDARD AMBIENT) R407C
MODEL
YRM011
YRM014
YRM018
MODEL
YRM 022
YRM 027
YRM 030S
YRM 030D
YRM 036S
YRM 036D
YRM 044V
YRM 044H
YRM 054V
YRM 054H
YRM 060
YRM 072
YRM 088
YRM 108
YRM 125
YRM 145
YRM 175
MODEL
YRM 088
YRM 125
YRM 145
YRM 175

MCB(A)
N/A
N/A
N/A

COPELAND COMPRESSOR
RLA(A)
LRA(A)
O/L(A)
6
50
7.5
7.8
62
9.5
8.6
74
10.5

COPELAND COMPRESSOR
MCB(A)
RLA(A)
LRA(A)
25
10.5
101
32
13.2
111
40
15.6
118
25
7.8
62
50
16.8
118
25
8.6
74
25
10.5
101
25
10.5
101
32
13.2
111
32
13.2
111
40
15.6
118
50
16.8
118
63
22.4
198
32
13.2
111
80
28.7
225
100
36.2
272
63
22.4
198
DANFOSS COMPRESSOR
MCB(A)
RLA(A)
LRA(A)
63
22.4
175
80
29.0
215
100
35.7
270
63
22.4
175

MCB(A)
N/A
N/A
N/A

O/L(A)
13.0
16.0
19.0
9.5
20.5
10.5
13.0
13.0
16.0
16.0
19.0
20.5
27.0
16.0
34.5
43.5
27.0

MCB(A)
6
6
6
6
6
6
10
10
16
10
10
10
16
16
16
16
16

O/L(A)
27.0
35.0
43.0
27.0

MCB(A)
16
16
16
16

CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
0.3 / 6P
1.00
1.11
0.3 / 6P
1.13
1.63
0.3 / 6P
1.55
2.66
CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
3.0 / 6P
5.4
28
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
2.0 / 6P
3.8
19
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
CONDENSING FAN
HP / POLE RLA(A)
LRA(A)
2.0 / 6P
3.8
19
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6
1.0 / 6P
2.1
7.6

FUSE(A)
2.00
2.00
2.00

MCB(A)
N/A
N/A
N/A

O/L(A)
2.5
2.5
2.5
2.5
2.5
2.5
4.5
2.5
6.0
2.5
2.5
2.5
4.5
4.5
2.5
2.5
2.5

MCB(A)
6
10
10
10
16
16
16
16
20
20
20
20
40
40
40
50
50

O/L(A)
4.2
2.5
2.5
2.5

MCB(A)
40
40
50
50

EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
0.75 / 4P
1.6
8.4
0.75 / 4P
1.6
8.4
1.0 / 4P
1.9
10.0
EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
1.5 / 4P
2.8
16
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
3.0 / 4P
5.1
34
3.0 / 4P
5.1
34
4.0 / 4P
6.7
49
4.0 / 4P
6.7
49
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153
EVAPORATOR FAN
HP / POLE RLA(A)
LRA(A)
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153

Notes:
1. Nominal info based on Condensing temperature of 125 F, evaporating temperature of 45 F and ambient temperature of 95 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.
163

O/L(A)
2.0
2.0
2.25

O/L(A)
3.1
4.0
4.0
4.0
6.0
6.0
7.5
7.5
10
10
10
10
17.5
17.5
17.5
24.0
24.0
O/L(A)
17.5
17.5
24.0
24.0

TOTAL
RLA(A)
8.60
10.53
12.05
TOTAL
RLA(A)
15.4
18.9
21.3
21.3
24
24.4
31.5
31.9
40.6
39.4
44.2
46.6
67.9
75.9
81.2
102.3
119.5
TOTAL
RLA(A)
67.9
81.9
101.3
119.5

164

YRM 022 YRM 175, 380-415V / 3PH / 50Hz (HIGH AMBIENT) R22
MODEL
YRM 022
YRM 027
YRM 030S
YRM 030D
YRM 036S
YRM 036D
YRM 044H
YRM 054H
YRM 060
YRM 072
YRM 088
YRM 108
YRM 125
YRM 145
YRM 175
MODEL
YRM 088
YRM 125
YRM 145
YRM 175

MCB(A)
32
40
50
20
50
25
30
40
50
50
63
40
80
100
63

COPELAND COMPRESSOR
RLA(A)
LRA(A)
11.8
101
16.20
118
18.40
118
9.10
62
20.80
118
10.40
74
11.80
101
16.20
111
18.40
118
20.80
118
27.20
198
16.20
111
34.55
225
44.10
272
27.20
198

O/L(A)
14.5
19.5
22.5
11.0
25.0
12.5
14.5
19.5
22.5
25.0
33.0
19.5
41.5
53.0
33.0

DANFOSS COMPRESSOR
MCB(A)
RLA(A)
LRA(A)
O/L(A)
63
27.40
175
33.0
80
33.60
215
40.5
100
42.60
270
51.5
63
27.40
175
33.0

MCB(A)
10
10
10
10
10
10
16
10
10
16
25
25
16
40
40

CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
2.0 / 4P
3.60
17.0
2.0 / 4P
3.60
17.0
1.5 / 6P
3.00
15.0
1.5 / 6P
3.00
15.0
2.0 / 6P
3.80
19.0
2.0 / 6P
3.80
19.0
2.0 / 4P
3.60
17.0
1.5 / 4P
2.70
11.0
1.5 / 6P
3.00
15.0
2.0 / 6P
3.80
19.0
4.0 / 4P
6.40
34.0
4.0 / 4P
6.40
34.0
1.5 / 6P
3.00
15.0
4.0 / 4P
6.40
34.0
4.0 / 4P
6.40
34.0

MCB(A)
25
16
40
40

CONDENSING FAN
HP/POLE
RLA(A)
LRA(A)
4.0 / 4P
6.40
34.0
1.5 / 6P
3.00
15.0
4.0 / 4P
6.40
34.0
4.0 / 4P
6.40
34.0

O/L(A)
4.0
4.0
3.5
3.5
4.5
4.5
4.0
3.0
3.5
4.5
7.5
7.5
3.5
7.5
7.5

O/L(A)
7.5
3.5
7.5
7.5

MCB(A)
6
10
10
10
16
16
16
20
20
20
40
40
40
50
50

EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
1.5 / 4P
2.8
16
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
2.0 / 4P
3.6
21
3.0 / 4P
5.1
34
3.0 / 4P
5.1
34
4.0 / 4P
6.7
49
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
5.5 / 4P
8.8
63
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153

MCB(A)
40
40
50
50

EVAPORATOR FAN
HP/POLE
RLA(A)
LRA(A)
10.0 / 4P
15.5
111
10.0 / 4P
15.5
111
15.0 / 4P
21.5
153
15.0 / 4P
21.5
153

Notes:
1. Nominal info based on Condensing temperature of 145 F, evaporating temperature of 45 F and ambient temperature of 125 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

O/L(A)
3.1
4.0
4.0
4.0
6.0
6.0
7.5
10
10
10
17.0
17.0
17.0
24.0
24.0

O/L(A)
17.0
17.0
24.0
24.0

TOTAL
RLA(A)
18.2
23.4
25
24.8
29.7
29.7
37.5
46.6
51.6
58.0
82.7
93.1
96.6
135.3
155.9
TOTAL
RLA(A)
83.1
94.7
132.3
156.7

YRM 022 YRM 175, 380-415V / 3PH / 50Hz (HIGH AMBIENT) R407C
MODEL
YRM 022
YRM 027
YRM 030S
YRM 030D
YRM 036S
YRM 036D
YRM 044H
YRM 054H
YRM 060
YRM 072
YRM 088
YRM 108
YRM 125
YRM 145
YRM 175
MODEL
YRM 088
YRM 125
YRM 145
YRM 175

COPELAND COMPRESSOR
MCB(A) RLA(A) LRA(A)
O/L(A)
32
13.0
101
16.0
40
16.20
118
19.5
50
18.80
118
23.0
20
8.30
62
10.0
50
20.80
118
25.0
25
11.10
74
13.5
30
13.00
101
16.0
40
16.20
111
19.5
50
18.80
118
23.0
50
20.80
118
25.0
63
27.50
198
33.0
40
16.20
111
19.5
80
35.80
225
43.0
100
44.65
272
54.0
63
27.50
198
33.0

CONDENSING FAN
MCB(A) HP/POLE RLA(A) LRA(A)
10
2.0 / 4P
3.60
17.0
10
2.0 / 4P
3.60
17.0
10
1.5 / 6P
3.00
15.0
10
1.5 / 6P
3.00
15.0
10
2.0 / 6P
3.80
19.0
10
2.0 / 6P
3.80
19.0
16
2.0 / 4P
3.60
17.0
10
1.5 / 4P
2.70
11.0
10
1.5 / 6P
3.00
15.0
16
2.0 / 6P
3.80
19.0
25
4.0 / 4P
6.40
34.0
25
4.0 / 4P
6.40
34.0
16
1.5 / 6P
3.00
15.0
40
4.0 / 4P
6.40
34.0
40
4.0 / 4P
6.40
34.0

O/L(A)
4.0
4.0
3.5
3.5
4.5
4.5
4.0
3.0
3.5
4.5
7.5
7.5
3.5
7.5
7.5

EVAPORATOR FAN
MCB(A) HP/POLE RLA(A) LRA(A)
6
1.5 / 4P
2.8
16
10
2.0 / 4P
3.6
21
10
2.0 / 4P
3.6
21
10
2.0 / 4P
3.6
21
16
3.0 / 4P
5.1
34
16
3.0 / 4P
5.1
34
16
4.0 / 4P
6.7
49
20
5.5 / 4P
8.8
63
20
5.5 / 4P
8.8
63
20
5.5 / 4P
8.8
63
40
10.0 / 4P
15.5
111
40
10.0 / 4P
15.5
111
40
10.0 / 4P
15.5
111
50
15.0 / 4P
21.5
153
50
15.0 / 4P
21.5
153

O/L(A)
3.1
4.0
4.0
4.0
6.0
6.0
7.5
10
10
10
17.0
17.0
17.0
24.0
24.0

TOTAL
RLA(A)
19.4
23.4
25.4
23.2
29.7
31.1
39.9
46.6
52.4
58.0
83.3
93.1
99.1
136.4
157.1

DANFOSS COMPRESSOR
MCB(A) RLA(A) LRA(A)
O/L(A)
63
26.60
175
32.0
80
34.40
215
41.5
100
42.00
270
50.5
63
26.60
175
32.0

CONDENSING FAN
MCB(A) HP/POLE RLA(A) LRA(A)
25
4.0 / 4P
6.40
34.0
16
1.5 / 6P
3.00
15.0
40
4.0 / 4P
6.40
34.0
40
4.0 / 4P
6.40
34.0

O/L(A)
7.5
3.5
7.5
7.5

EVAPORATOR FAN
MCB(A) HP/POLE RLA(A) LRA(A)
40
10.0 / 4P
15.5
111
40
10.0 / 4P
15.5
111
50
15.0 / 4P
21.5
153
50
15.0 / 4P
21.5
153

O/L(A)
17.0
17.0
24.0
24.0

TOTAL
RLA(A)
81.5
96.3
131.1
153.5

Notes:
1. Nominal info based on Condensing temperature of 145 F, evaporating temperature of 45 F and ambient temperature of 125 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

165

166

YCS 030 YCS 175, 380-415V / 3PH / 50Hz (STD AMBIENT) R22
MODEL
YCS 030S
YCS 030D
YCS 036S
YCS 036D
YCS 044V
YCS 044H
YCS 054V
YCS 054H
YCS 060
YCS 072
YCS 088
YCS 108
YCS 125
YCS 145
YCS 175
MODEL
YCS 088
YCS 125
YCS 145
YCS 175

MCB(A)
40
25
50
25
25
25
32
32
40
50
63
32
80
100
63

COPELAND COMPRESSOR
RLA(A)
LRA(A)
15.1
118
7.5
62
16.8
118
8.4
74
10.2
101
10.2
101
13.1
111
13.1
111
15.1
118
16.8
118
22.7
198
13.1
111
28.3
225
36.3
272
22.7
198

O/L(A)
18.5
9.0
20.5
10.5
12.5
12.5
16.0
16.0
18.5
20.5
27.5
16.0
34.0
44.0
27.5

MCB(A)
6
6
6
6
10
10
16
10
10
10
16
16
16
16
16

MCB(A)
63
80
100
63

DANFOSS COMPRESSOR
RLA(A)
LRA(A)
23.3
175
29.1
215
37.1
270
23.3
175

O/L(A)
28.0
35.0
44.5
28.0

MCB(A)
16
16
16
16

HP/POLE
1.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P
2.0 / 6P
1.0 / 6P
3.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P
2.0 / 6P
2.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P

CONDENSING FAN
RLA(A)
2.1
2.1
2.1
2.1
3.8
2.1
5.4
2.1
2.1
2.1
3.8
3.8
2.1
2.1
2.1

LRA(A)
7.6
7.6
7.6
7.6
19
7.6
28
7.6
7.6
7.6
19
19
7.6
7.6
7.6

O/L(A)
2.5
2.5
2.5
2.5
4.5
2.5
6.0
2.5
2.5
2.5
4.5
4.5
2.5
2.5
2.5

HP/POLE
2.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P

CONDENSING FAN
RLA(A)
3.8
2.1
2.1
2.1

LRA(A)
19
7.6
7.6
7.6

O/L(A)
4.5
2.5
2.5
2.5

Notes:
1. Nominal info based on Condensing temperature of 125 F, evaporating temperature of 45 F and ambient temperature of 95 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

TOTAL RLA(A)
17.2
17.1
18.9
18.9
24.2
24.6
31.6
30.4
34.4
37.8
53.0
60.0
65.0
81.0
99.2
TOTAL RLA(A)
54.2
66.6
82.6
101.6

YCS 030 YCS 175, 380-415V / 3PH / 50Hz (STD AMBIENT) R407C
MODEL
YCS 030S
YCS 030D
YCS 036S
YCS 036D
YCS 044V
YCS 044H
YCS 054V
YCS 054H
YCS 060
YCS 072
YCS 088
YCS 108
YCS 125
YCS 145
YCS 175
MODEL
YCS 088
YCS 125
YCS 145
YCS 175

MCB(A)
40
25
50
25
25
25
32
32
40
50
63
32
80
100
63

COPELAND COMPRESSOR
RLA(A)
LRA(A)
15.6
118
7.8
62
16.8
118
8.6
74
10.5
101
10.5
101
13.2
111
13.2
111
15.6
118
16.8
118
22.4
198
13.2
111
28.7
225
36.2
272
22.4
198

O/L(A)
19.0
9.5
20.5
10.5
13.0
13.0
16.0
16.0
19.0
20.5
27.0
16.0
34.5
43.5
27.0

MCB(A)
6
6
6
6
10
10
16
10
10
10
16
16
16
16
16

HP/POLE
1.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P
2.0 / 6P
1.0 / 6P
3.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P
2.0 / 6P
2.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P

CONDENSING FAN
RLA(A)
2.1
2.1
2.1
2.1
3.8
2.1
5.4
2.1
2.1
2.1
3.8
3.8
2.1
2.1
2.1

LRA(A)
7.6
7.6
7.6
7.6
19
7.6
28
7.6
7.6
7.6
19
19
7.6
7.6
7.6

FUSE(A)
2.5
2.5
2.5
2.5
4.5
2.5
6.0
2.5
2.5
2.5
4.5
4.5
2.5
2.5
2.5

MCB(A)
63
80
100
63

DANFOSS COMPRESSOR
RLA(A)
LRA(A)
22.4
175
29.0
215
35.7
270
22.4
175

O/L(A)
27.0
35.0
43.0
27.0

MCB(A)
16
16
16
16

HP/POLE
2.0 / 6P
1.0 / 6P
1.0 / 6P
1.0 / 6P

CONDENSING FAN
RLA(A)
3.8
2.1
2.1
2.1

LRA(A)
19
7.6
7.6
7.6

O/L(A)
4.5
2.5
2.5
2.5

Notes:
1. Nominal info based on Condensing temperature of 125 F, evaporating temperature of 45 F and ambient temperature of 95 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

167

TOTAL RLA(A)
17.7
17.7
18.9
19.3
24.8
25.2
31.8
30.6
35.4
37.8
52.4
60.4
65.7
80.8
98.0
TOTAL RLA(A)
52.4
66.4
79.8
98.0

168

YCS 030 YCS 175, 380-415V / 3PH / 50Hz (HIGH AMBIENT) R22
MODEL
YCS 030S
YCS 030D
YCS 036S
YCS 036D
YCS 044H
YCS 054H
YCS 060
YCS 072
YCS 088
YCS 108
YCS 125
YCS 145
YCS 175
MODEL
YCS 088
YCS 125
YCS 145
YCS 175

MCB(A)
50
20
50
25
30
40
50
50
63
40
80
100
63

COPELAND COMPRESSOR
RLA(A)
LRA(A)
18.40
118
9.10
62
20.80
118
10.40
74
11.80
101
16.20
111
18.40
118
20.80
118
27.20
198
16.20
111
34.55
225
44.10
272
27.20
198

O/L(A)
22.5
11.0
25.0
12.5
14.5
19.5
22.5
25.0
33.0
19.5
41.5
53.0
33.0

MCB(A)
63
80
100
63

DANFOSS COMPRESSOR
RLA(A)
LRA(A)
27.40
175
33.60
215
42.60
270
27.40
175

O/L(A)
33.0
40.5
51.5
33.0

MCB(A)
10
10
10
10
16
10
10
16
25
25
16
40
40

HP/POLE
1.5 / 6P
1.5 / 6P
2.0 / 6P
2.0 / 6P
2.0 / 4P
1.5 / 4P
1.5 / 6P
2.0 / 6P
4.0 / 4P
4.0 / 4P
1.5 / 6P
4.0 / 4P
4.0 / 4P

CONDENSING FAN
RLA(A)
3.00
3.00
3.80
3.80
3.60
2.70
3.00
3.80
6.40
6.40
3.00
6.40
6.40

LRA(A)
15.0
15.0
19.0
19.0
17.0
11.0
15.0
19.0
34.0
34.0
15.0
34.0
34.0

O/L(A)
3.5
3.5
4.5
4.5
4.0
3.0
3.5
4.5
7.5
7.5
3.5
7.5
7.5

MCB(A)
25
16
40
40

HP/POLE
4.0 / 4P
1.5 / 6P
4.0 / 4P
4.0 / 4P

CONDENSING FAN
RLA(A)
6.40
3.00
6.40
6.40

LRA(A)
34.0
15.0
34.0
34.0

O/L(A)
7.5
3.5
7.5
7.5

Notes:
1. Nominal info based on Condensing temperature of 145 F, evaporating temperature of 45 F and ambient temperature of 125 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

TOTAL RLA(A)
21.40
21.2
24.60
24.6
30.8
37.8
42.8
49.2
67.2
77.6
81.1
113.8
134.4
TOTAL RLA(A)
67.6
79.2
110.8
135.2

YCS 030 YCS 175, 380-415V / 3PH / 50Hz (HIGH AMBIENT) R407C
MODEL
YCS 030S
YCS 030D
YCS 036S
YCS 036D
YCS 044H
YCS 054H
YCS 060
YCS 072
YCS 088
YCS 108
YCS 125
YCS 145
YCS 175
MODEL
YCS 088
YCS 125
YCS 145
YCS 175

MCB(A)
50
20
50
25
30
40
50
50
63
40
80
100
63

COPELAND COMPRESSOR
RLA(A)
LRA(A)
18.80
118
8.30
62
20.80
118
11.10
74
13.00
101
16.20
111
18.80
118
20.80
118
27.50
198
16.20
111
35.80
225
44.65
272
27.50
198

MCB(A)
63
80
100
63

DANFOSS COMPRESSOR
RLA(A)
LRA(A)
26.60
175
34.40
215
42.00
270
26.60
175

O/L(A)
23.0
10.0
25.0
13.5
16.0
19.5
23.0
25.0
33.0
19.5
43.0
54.0
33.0

O/L(A)
32.0
41.5
50.5
32.0

MCB(A)
10
10
10
10
16
10
10
16
25
25
16
40
40

MCB(A)
25
16
40
40

HP/POLE
1.5 / 6P
1.5 / 6P
2.0 / 6P
2.0 / 6P
2.0 / 4P
1.5 / 4P
1.5 / 6P
2.0 / 6P
4.0 / 4P
4.0 / 4P
1.5 / 6P
4.0 / 4P
4.0 / 4P

CONDENSING FAN
RLA(A)
3.00
3.00
3.80
3.80
3.60
2.70
3.00
3.80
6.40
6.40
3.00
6.40
6.40

LRA(A)
15.0
15.0
19.0
19.0
17.0
11.0
15.0
19.0
34.0
34.0
15.0
34.0
34.0

O/L(A)
3.5
3.5
4.5
4.5
4.0
3.0
3.5
4.5
7.5
7.5
3.5
7.5
7.5

HP/POLE
4.0 / 4P
1.5 / 6P
4.0 / 4P
4.0 / 4P

CONDENSING FAN
RLA(A)
6.40
3.00
6.40
6.40

LRA(A)
34.0
15.0
34.0
34.0

O/L(A)
7.5
3.5
7.5
7.5

Notes:
1. Nominal info based on Condensing temperature of 145 F, evaporating temperature of 45 F and ambient temperature of 125 F.
2. Refrigerant R22 & R407C, Compressor and Fans Power Supply at 380-415V / 3Ph / 50Hz.
3. All Specifications are subject to change without prior notice.

169

TOTAL RLA(A)
21.8
19.6
24.6
26.0
33.2
37.8
43.6
49.2
67.8
77.6
83.6
114.9
135.6
TOTAL RLA(A)
66.0
80.8
109.6
132.0

YRM 011/014/018 (Cooling Only)

170

Drawing No. 362A14100A011

YRM 022/027/030S/036S (Cooling Only)

Drawing No. 362A12100A022

171

YRM 030D/036D/044V/054V (Cooling Only)

172

Drawing No. 362A11100A030

YRM 044H/054H/060/072 (Cooling Only)

Drawing No. 362A11100A044

173

YRM 088 (Cooling Only)

174

Drawing No. 362A11100A088

YRM 108 (Cooling Only)

Drawing No. 362A11100A108

175

YRM 125/145 (Cooling Only)

176

Drawing No. 362A11100A125

YRM 175 (Cooling Only)

Drawing No. 362A11100A175

177

YRM 022/027/030S/036S (Heat Pump)

178

Drawing No. 362A22100A022

YRM 030D/036D/044V/054V (Heat Pump)

Drawing No. 362A21100A030

179

YRM 044H/054H/060/072 (Heat Pump)

180

Drawing No. 362A21100A044

YRM 088 (Heat Pump)

Drawing No. 362A21100A088

181

YRM 108 (Heat Pump)

182

Drawing No. 362A21100A108

YRM 125/145 (Heat Pump)

Drawing No. 362A21100A125

183

YRM 175 (Heat Pump)

184

Drawing No. 362A21100A175

YCS 030D/036D/044V/054V (Cooling Only) and (High Ambient)

Drawing No. 362A11110A030

185

YCS 044H/054H/060/072 (Cooling Only) and (High Ambient)

186

Drawing No. 362A11110A044

YCS 088 (Cooling Only) and (High Ambient)

Drawing No. 362A11110A088

187

YCS 108 (Cooling Only) and (High Ambient)

188

Drawing No. 362A11110A108

YCS 125/145 (Cooling Only) and (High Ambient)

Drawing No. 362A11110A125

189

YCS 175 (Cooling Only) and (High Ambient)

190

Drawing No. 362A11110A175

YCS 030S/036S (Cooling Only) and (High Ambient)

Drawing No. 362A12110A030

191

YCS 030D/036D/044V/054V (Heat Pump)

192

Drawing No. 362A21110A030

YCS 044H/054H/060/072 (Heat Pump)

Drawing No. 362A21110A044

193

YCS 088 (Heat Pump)

194

Drawing No. 362A21110A088

YCS 108 (Heat Pump)

Drawing No. 362A21110A108

195

YCS 125/145 (Heat Pump)

196

Drawing No. 362A21110A125

YCS 175 (Heat Pump)

Drawing No. 362A21110A175

197

YCS 030S/036S (Heat Pump)

198

Drawing No. 362A21110A030

YRM 022/027/030S/036S Cooling Only (CE)

Drawing No. 362A12200A022

199

YRM 030D/036D/044V/054V Cooling Only (CE)

200

Drawing No. 362A11200A022

YRM 044H/054H/060/072 Cooling Only (CE)

Drawing No. 362A11200A044

201

YRM 088 Cooling Only (CE)

202

Drawing No. 362A11200A088

YRM 108 Cooling Only (CE)

Drawing No. 362A11200A108

203

YRM 125/145 Cooling Only (CE)

204

Drawing No. 362A11200A125

YRM 175 Cooling Only (CE)

Drawing No. 362A11200A175

205

YRM 022/027/030S/036S Heat Pump (CE)

206

Drawing No. 362A22200A022

YRM 030D/036D/044V/054V Heat Pump (CE)

Drawing No. 362A21200A030

207

YRM 044H/054H/060/072 Heat Pump (CE)

208

Drawing No. 362A21200A044

YRM 088 Heat Pump (CE)

Drawing No. 362A21200A088

209

YRM 108 Heat Pump (CE)

210

Drawing No. 362A21200A108

YRM 125/145 Heat Pump (CE)

Drawing No. 362A21200A125

211

YRM 175 Heat Pump (CE)

212

Drawing No. 362A21200A175

THIS PAGE INTENTIONALLY LEFT BLANK

213

GENERAL
The YORK MillenniumTM Commercial Unitary
Packaged and Split System units are designed
for cooling/heating filtered air. They are capable
of providing cooling in ambients of 15oC DB to
46oC DB, cooling in high ambient 15oC DB to
52oC DB and providing heating in ambients
of -5.0oC DB to 20oC DB.
Each system consists of either a single packaged
unit (YRM ducted roof mounted packaged unit) or
a split system (YCS ducted split systems) which
require installation of interconnecting piping and
controls on site (by others)
Some units may be combined with other YORK
products such as YCS condensing sets
combined with YORK YDF or air handlers. In
these cases this manual should be read in
conjunction with the appropriate manual for the
product to which the unit is combined.
The YRM and YCS units are designed to be
located outside on the roof of a building or at
ground level, alternatively they can be located
indoors provided sufficient attention is provided
to: ensuring adequate air flow to cool the
condenser coils; and drainage of condensate.
Prior to delivery each unit is pressure tested,
evacuated and charged with refrigerant (YRM
only; YCS units are charged with dry nitrogen)
and oil.

CABINET
The cabinet is constructed of 1.2mm galvanized
sheet steel, units have either a fabricated
galvanized sheet metal base with full width
structural feet supported by an underside gusset,
or a full size C channel structural base frame
depending on the unit size.

214

All exposed external surfaces of the cabinet are


coated with an electrostatic deposition powder
coating of synthetic resin paint to provide a
durable long lasting finish.

INDOOR SECTION
The indoor section includes a 304L stainless
steel drain pan, indoor coil including thermal
expansion valve(s), check valve(s), forward
curved direct or belt driven evaporator fan and is
insulated with 25mm foil faced polyester fibre
thermal/acoustic insulation (0.036 W/mK at 20oC)

OUTDOOR SECTION
The condenser section has a baffle dividing it into
separate compressor and condenser coil
compartments to minimize noise break-out and
facilitate servicing (note unit sizes 125 and 145
do
not
have
a
separate
compressor
compartment). The compressor compartment
includes the compressor(s) electrical panel(s),
outdoor coil thermal expansion valve(s), liquid
line sight glass(es), HP and LP controls.
Reverse cycle unit comes with additional check
and reversing valve(s) (heat pump units) and
suction accumulator(s).

REFRIGERANT CIRCUIT
The unit contains one or more independent
refrigerant circuits of equal capacity. Each
refrigerant circuit is constructed of seamless
copper tubing with brazed joints and includes:
liquid line sight glass(es), thermal expansion
valve(s), liquid line filter drier(s), high and low
pressure safety controls, reversing valve(s) (heat
pump units only) and suction accumulator(s)
(heat pump units only).

ELECTRICAL & CONTROL


The control panel contains suitably rated
contactors, overloads and circuit breakers for
each three phase motor. This board performs all
the control and safety functions as follows:
High and low pressure safety, power off
electrical reset.
Compressor overloads, manual reset at
switchboard.
Overloads for three phase condenser and
evaporator fan motors, manual reset at
switchboard.
Anti-coincident timers to prevent multiple
compressors from starting at the same time.
Anti-recycle timers for each compressor.
Defrost control for reverse cycle unit.
Automatic compressor lead lag control, for
multiple compressor units.

7 days programmable timer.


Cool/Heat/Auto/Fan control, ranging from
16oC to 30oC temperature setting.
Cold blast, Spurt heat, Hot start and Hot
keep.
Wired LCD control panel.
Self-diagnostic
feature,
error/warning
indications.
Energy saving function for Cool, Heat and
Auto modes.
Compressor trip/low refrigerant warning.
Compressor high temperature protection.
Indoor antifreeze protection.
Battery back-up. If the power fails, a back-up
battery will maintain the real time clock and
the integrity of the controls data. When
power is resumed / switched on again, the
unit will automatically restart using the
original settings.

SB 125 Single System (YRM/YCS)

INDOOR & OUTDOOR COIL

The indoor and outdoor coil is of seamless


copper tube arranged in a staggered pattern,
mechanically expanded into Aluminium fins.

Auto/Cool/Fan/Heat/Defrost system control


modes.
Real Time Clock with Real Time On/Off Timer
and delay timer up to 15 hours.
Sleep function fool Cool, Heat and Auto
mode.
Integrated Cold Start, Hot Start and Hot Keep
functions to rapidly bring room temperature to
selected setting during power on.
LEDs display for Power, Cool, Heat, Sleep
and Timer.
Memory backup for last state settings option.
Compatible with wired and wireless controller.

SQ 2.0 Double System (YRM/YCS)

Sequential control and balance loading up to


4 stage compressors.
Selectable stage differential temperatures.
Single speed indoor fan.

Optional coils utilising differing materials of


construction and or coatings applied to the
coils after production may be specified.
Testing
Pressure
Indoor
Evaporating Coil

350 psig

Outdoor
Condensing Coil

450 psig

215

EVAPORATOR FAN & MOTOR


The evaporator fans are double inlet forward
curved centrifugal type, statically and dynamically
balanced and driven by either a direct drive AOM
(air over motor) motor or via a belt drive utilizing
a TEFC (IP55, Class F insulation) motor.
Belt drives are equipped with a suitable number
and size of Vee belt(s) and utilize an adjustable
drive pulley. The pulley can be changed on site
(by others) to match the installed duty. The fan
motor is sized to perform the required duty as
nominated with a 20% allowance for drive losses.

CONDENSER FAN & MOTOR


The condenser fan(s) are axial flow type with
multiple glass reinforced nylon aerofoil impellers
and cast Aluminium hubs. The motor(s) are three
phase with external overloads suitable for
outdoor application.

COMPRESSOR(S)
The compressors are of the fully hermetic type
suitable for refrigerant R-22 (Mineral oil) and
R407C (POE oil).

216

Each compressor is constructed from a welded


shell complete with an integral suction gas
cooled electric motor directly driving a
multicylinder compressor.
The compressor includes internal discharge
muffling to minimize gas pulsations and the
motor is fitted with an internal line break overload
to prevent the motor from experiencing abnormal
running conditions.
A wrap around or insertion crankcase heater is
fitted.

OPTIONS
The units covered by this document have many
possible optional items that could be fitted. Some
information regarding optional items is dealt with
in this document however, it is impractical to
detail information on all possible options.
If an option is fitted to a unit which is not covered
by this document, for which you require
additional information, contact your local York
Service or Sales Office.

PIN Example:
A standard size 22 reverse cycle roof mount package unit would have a PIN as follows
YRM022R4SBCCX
Marketing Field
For explanation of the codes within the first 13 fields of the PIN refer to the following. For details on
the complete PIN contact your local York office.
BASE MODEL NUMBER :
1 2
3
4
5
6
BASE PRODUCT
UNIT SIZE
TYPE
kW R

7
TYPE

8
9
ELECTRICAL
No of
COMPRESSORS

R - Reverse Cycle
C - Cooling Only
H - Cooling only (High
Ambient)

10
EVAPORATOR
FAN DRIVE

13
11
12
REFRIGERANT DESIGN SERIES SPECIAL

C R22
D Direct Drive
B Belt Drive
X No evaporator fan
S
D
Q

Single Compressor Unit


Dual Compressor Unit
Quad Compressor Unit

C
Series C, or third generation

4 380/415V-3ph-50Hz, with 24V control Interface


#
#
#
Unit Size = Capacity at nominal conditions
(Normally rounded up to nearest whole number for units < 40kW R)
(Normally rounded up to nearest even number for units > 40kW R)
X
No special requirements that cannot be described by the standard PIN code
Special Configuration, or option included not described by standard PIN code Z

RM
CS

York
Roof Mount Package Unit, Standard Air Cooled Type
Condensing Set, Standard Air Cooled Type

UNIT NAMEPLATE

Upon receipt of the unit ensure that


the nameplate is fixed to the unit and
that the details noted on the
nameplate are as ordered.

217

Data subject to change without notice due to engineering innovation in the future.
Ref : YRM/121107