Description
Item-1: Civil Works for Data Center and Power Room
Item-2: Construction Work
Item-3: Raised Flooring System
Item-4: Floor Insulation
Item-5 - Air-Conditioner System for Power Room & NOC Room
Item-6: Dehumidifier for power room
Item-7: Fire Suppression & Fire Detection System
Item-8: Environmental Monitoring System
Item-9: Electrical Works
Item-10: Access Control System and Proximity Card
Item-11: Rodent Systems
Item-12: Heavy Duty Fire Resistant Data Safe
Item-13: Aspiration (VESDA) System
Item-14: Substation with AVR
Item-15: DPDC /DESA /DESCO Connection
Item-16: Electro-magnetic Field Protection
Item-17: Installation and Implementation Service
Item-18: One year Service
Item-19: Furniture and Monitor
Item-20: Labeling & Documentation
Item-21: Tier-Ill Certification
(b) Item-22: Local Training (Category D)
Item-23: Foreign Training (Category D)
Item-24: DataCentre Infrastructure Management (DCIM)
Item-25: Bus Bar Trunking (BBT)
Item-26: Surge Protection Device (SPD)
Item 27. Double Conversion Online UPS
Item-28: UTP Connectivity
Item-29: Fiber Connectivity
Item-30: Precision Air Conditioner
Item-31: Static Transfer Switch
Item-32 - Rack & Containment Solution
Item-33: Ladder System for UTP & Fiber
Item-34: IP based Surveillance System
Item-35: Generator

Price BDT

Item-1: Civil Works for Data Center and Power Room


SL. #

Product Names/Items
1 Dismantling Works
2 Brick Works

3 Plaster Works

4 Normal Paint

Brand
Country of Origin
5 Epoxy Paint
Brand
Country of Origin
6 Tiles Work
Brand
Country of Origin
SL. #

Product Names/Items

Description of the Floor Tiles Work

Dry Wall Partition


Brand
Country of Origin

Tempered Glass Partition

Brand
Country of Origin

Tempered Glass Door

10

Metal Door
Brand
Country of Origin

SL. #

Product Names/Items

12 Alcoa sheet Metal


13 Archway Detector System

14 Security film

15 False Ceiling
16 Louver
17 Ducting
18 Ramp
19 Country of Origin
20 Lo
21 Stair

22 Miscellaneous Works

Description of requirements

UoM

QTY

Dismantling of existing items

lot

125 mm brick work with 1st class bricks in cement mortar (1:4), all
complete as per direction. (Approx.)

sft

9000

250 mm brick work with 1st class bricks in cement mortar (1:4), all
complete as per direction. (Approx.)

sft

10000

1" plaster to wall (1:6) inner surface of the building, finishing the corner and
edges in/c removing the existing damp plaster (if necessary). All complete as
per direction. (Approx.)

sft

25000

Plastic emulsion paint of approved color of reputed brand to wall/column of


inside wall of the Branch of two coats over a coat of brand specified
primer / scalar collapsing specified time for drying/recoating including
cleaning, drying, making free from dirt grease, wax, removing all chalked
sft
and scald materials like fungus, mending grid for the surface defects, sand
papering the surface and necessary scaffolding by roller/ spray etc. and
printing with two coats of synthetic enamel paint approved color over a coat
of priming etc. all complete as per direction (Approx.)

30000

Berger or other globally reputed brand


To be mentioned by the bidder
Epoxy Industrial Paint for protect thermal proof and wall damp proof

sft

12000

sft

7000

Berger or other reputed brand


To be mentioned by bidder
Floor Tiles Work
To be mentioned by the bidder
To be mentioned by the bidder
Description of requirements

UoM

QTY

Gypsum Partition for drop ceiling with necessary structure

Sft

10000

Gypsum board partition for outside wall with necessary structure and
inside glass wool

Sft

5000

sft

8000

Supply, fitting and fixing of mirror polish Wall Tiles size 600 x600mm
placing over existing floor with required cement mortar (proportion 1:3
and average thickness 3/4"), racking out the joint & filling with same
color pudding including cutting and leveling of the wall etc. all complete
as per direction of the purchaser

Elephant or other reputed brand


To be mentioned by the bidder
Supplying, fitting and fixing of Protector Bit Glass Partition work made
with anodized 'Silver' color Aluminum Protector Bit section, silicon gum
& 10mm Tempered glass included edge polish, original bronze anodized
star geed matching, screw, etc. Complete in all respect as per design,
drawing and direction. (10 mm , consider the glass as 8 feet height)
Approx.
(Glass partition will be double for outside due to thermal protection)
Nasir/Euro or other reputed brand
To be mentioned by the bidder

Supply and installation of 10mm thick tempered glass swing door in/c1
fitted with concealed best quality door closer, key locks, handle etc. all
complete as per direction.
a) Tempered glass door (size: 3'-6"X 7'-0")

Pcs

16

b) Sliding Door

Pcs

Fire Rated Metal Door, Size: 3'-6"X8'-0"

Nos

To be mentioned by the bidder, must be a reputed brand


To be mentioned by the bidder
NFPA 251 Standard
Test standard: Fire Door must be tested according to Bangladesh or
international standard
Shutter materials: Steel
Two hours fire resistivity
Jamb:2 vertical Fire Resisting jamb and 1 Fire Resisting horizontal jamb

Description of requirements

UoM

QTY

Fabrication of Alcoa sheet metal inside the RCC column all complete as per
direction (Approx.)

Sft

700

Supply, Installation and commissioning of archway detector system of a


reputed brand

Job

sft

3000

Gypsum board false ceiling

sft

3000

Aluminum louver '

Sft

400

Duct making and fitting by 22 SWG MS Sheet with PU Insulation as per the
purchaser's direction in the mouth of Precision Air-Conditioner

sft

3000

RCC ramp as per design ( Size:- 7'X12')

Pcs

Lot

2 step Movable metal Stair by MS checker plate

Nos.

Supplying Fitting & fixing at site other Miscellaneous Work such as Frosted
paper vertical blinds PVC floor mat, signage, Faade decoration etc. all
complete as per design, drawing and direction.

Job

Door shutter sheet thickness: At least 3mm


Vision panel: Fire Rated glass vision panel
Hinge, bolt and screw :Fire rated
Internal Insulation: Honeycomb core insulation
Lock: Built in mortise lock
Auto Door Closer :Default

Supplying & pasting of best quality Security film paper


after cleaning the glass properly as per approved design

To be mentioned by the bidder


Supply, fitting & fixing of standard signage made by PVC
sticker at Inside & Entry, as per direction of the purchaser

Item-2: Construction Work


Product

SL. #

Names/Items

Two (2) Storied Generator set and


Substation Building

2
_

Two (2) Storied Power Building

SL. #

Product
Names/Items
Page 153 of 363

Page 153 of 363

Description of requirements

UoM

QTY

This building's ground floor will be used for generator and 1st floor will be used for
2 Nos. of substation equipment. Building size ( LXW): 60'X40' and slab to slab
clear height: 13'

N/A

N/A

This building's ground floor will be used for Battery and 1st floor will be used for
UPS. Building size (LXW):40'X12' and slab to slab clear height: 11'

N/A

N/A

The above three building will be developed by the following specification BoQ
(approx)

N/A

N/A

If any others materials required then bidder will mention and quote for the same

N/A

N/A

Earth Excavation (Up to 5 ft from EGL)

Cft

8500

Earth Filling with excavated earth

Cft

7000

Brick Flat Soling

Sft

3500

Mass Concrete

Cft

360

Sand Filling below floor

Cft

4900

Reinforced Cement Concrete Work (1:1.5:3)

N/A

N/A

Footing

Cft

1050

Grade Beam

Cft

960

Floor Slab

Cft

1850

Column

Cft

1280

Roof Beam

Cft

1575

Roof slab

Cft

3550

Stair/Lintel

Cft

1350

Reservoir wall

Cft

650

Cable trench

Cft

480

Deformed Bar

Kg

39500

Polythene sheet Laying

Sft

3000

10" thick brick work in superstructure

Cft

4250

5" thick brick work in superstructure

Sft

3750

1/2" thick plaster

Sft

34500

Cement mortar cove skirting

Rft

1250

Patent Stone floor with NCF

Sft

6950

Weather coat paint

Sft

14000

Plastic paint

Sft

25000

Enamel paint

Sft

6500

Epoxy floor paint

Sft

8650

Hollow Metal Door with metal frame

N/A

N/A

Double Leaf door - 6' x 7'

each

Single Leaf door - 3' - 6" x 7'

each

UoM

QTY

Aluminium Window

Sft

750

Window Grill

Sft

750

Description of requirements

Metal cover for cable trench

Sft

260

Wall and ceiling insulation - 15 mm thick double bubble

Sft

5200

Lime concrete

Cft

1050

4" diameter rain water pipe

Rft

180

6" diameter underground rain water pipe

Rft

200

Inspection Pit

Nos.

Metal fuel Reservoir

N/A

N/A

50000 liter capacity

No.

5000 liter capacity

Nos.

Lot

Electrical works

Item-3: Raised Flooring System


Product

SL. #.

Names/Items

Solid Panel
Brand
Model
.
Country of Origin

Perforated Panel
Brand

Country of Origin

3 Double suction panel lifter


4 Air Grommet

5 Installation

Description of requirements

UoM

QTY

sft

6000

To be mentioned by bidder
To be mentioned by bidder

To be mentioned by bidder
-Calcium Sulphate Panel
Fiber-reinforced Calcium Sulphate Panel only selected raw material
to meet the modern building requirements as well as high graded
ecological aspects.
The mineral binding material is the high alpha
hemihydrates which guarantee the production of constant product
quality depending on permanent high purity. A balanced and constant
density all over the panels must be guaranteed.
Quality Standards: ISO 9001:2008 and KS F 4760
Panel Surface: High Pressure laminate
Panel Dimensions : 600X600 mm
Panel Thickness: Minimum 30 mm
Panel Bottom: Galvanized Steel Plate
Panel Materials: Fiber-Reinforced Calcium Sulphate
Pedestal Material: Galvanized Steel
Finished Floor Height (FFH): 500 mm
Concentrated load: 4500 N per 25mm sq
Ultimate Load: > 11000N
Uniform distributed load: 12.0 kN/m2
Impact load: 780 N
Systematically anti-static
Electrostatic >105 ohm
Thermal conductivity: 0.44 W/mk
Fire resistance Class ace. to DIN 4102
Easy to install, Disassembly and Interchange
* Systematically anti-static
* Fire-proof
* Damp proof
* Support heavy load, easy to install, Disassembly and interchange.
* Difficult to be dirty, easy to clean, decorative,
*Appearance and durable using term.
Pedestal, Stringer, fasteners and other materials will be in accordance
sft
To be mentioned By Bidder

1000

To be mentioned By Bidder
Panel Type: To be mentioned By Bidder
Flammability: A 1
Panel size: 600 x 600 mm
Perforated steel panels designed for static load shall be interchangeab
The panel must be conductive powder coated
Nos

Nos

160

Job

Air grommet Dust proof panel with double brush. Color black.
Divided section.
Overlapping Brushes with double layer facilities. Latch removable bru
Installation facilities at the panel edge or within the panel. High Str
Shape: round or rectangle
Installation should be done in accordance with TIA -942 Standard

Item-4: Floor Insulation


SL. #

Product Names/Items

Description of requirements

1 Floor insulation
Brand

To be mentioned by the Bidder/Must be a globally reputed brand

Country of Origin

To be mentioned by the Bidder

Manufacturing Country

To be mentioned by the Bidder


Supplier should supply and install 19 mm thick closed cell
elastomeric nitrile rubber, class "0" type on Floor and top of that
supply and install Aluminum foil Tap/sheet contained high tempered
Self-adhesive to cover Data Center floor area by solution gum and
necessary silicon gel to prevent floor slab sweatin' from its bottom.

2 Installation

UoM

QTY

sft

7000

sft

7000

Item-5 - Air-Conditioner System for Power Room & NOC Room


SL. #

Product Names/Items
Duct Type Air- Conditioner for Power Room
Quality
Standard
Brand
Country of Origin
Manufacturing Country
1

2 Ducting Accessories
3 Diffuser
4 Return Grill

5 Installation
Split Type Air-Conditioner for NOC
Brand
Country of Origin
Manufacturing Country

7 ACP
8 Installation

Page 158 of 363

m & NOC Room


Description of requirements

UoM

QTY

Nos

22 SWG MS Sheet with PU Insulation as per the purchaser's direction

Sft

1000

Size: 2'X2'

Set

16

Size: 2'X2'

Set

16

ISO 9001/9002 for Manufacturer, FCC Class A/B, Energy Star for quality
assurance
Should be emission tested
To be mentioned by the Bidder
To be mentioned by the Bidder
To be mentioned by the Bidder
Duct Type split Air-Cooler with wireless remote control and clock.
Capacity: 7 TR or 86700 BTU/Hr
SHR should be more than 0.7 and EER should be higher rating
Moisture Removal 7.5 Ltr/hr
Power: 3 Phase/50Hz, 380-415V
Input Power Consumption: less than or equal to 10.5 KW EER: 2.42
Airflow: 9800 CMH

Installation, testing & commissioning of 7 TR AC

Nos.

Nos

Automatic Control Panel for AC rotation for 8 hours interval with DB panel
and necessary timer, magnetic contractor and accessories completed as per
design provided by engineering in charge

Nos

Installation, testing & commissioning of 2 TR AC

EA

To be mentioned by the bidder


To be mentioned by the bidder
To be mentioned by the bidder
Wall Mount type split Air-Cooler with wireless remote control and clock.
Capacity: 2 TR or 23200 BTU/Hr
SHR should be more than 0.7 and EER should be higher rating
Power: Single Phase/50Hz, 220-240V
Input Power Consumption: less than or equal to 2.55 KW EER: 2.67
Airflow: 2590 CMH

Item-6: Dehumidifier for power room


SL. #

Product Names/Items
1 Dehumidifier
Brand
Country of Origin

2 Installation

P
a
g
e
1
5
8
o
f
3
6
3

Description of requirements

UoM

QTY

Nos.

Nos.

To be mentioned By Bidder
To be mentioned By Bidder
Dehumidification: 18 -20 liter /24 Hour
Power: 220/240V 50 Hz
Power Consumption: 500 W or Less
Working Environment: 5-35C
Bucket Volume: 4L/5L
Installation, testing & commissioning

Item-7: Fire Suppression & Fire Detection System


SL. #

Product Names/Items
Suppression Agent for Server Room &

Power Room
Brand
Country of Origin

2 Cylinder for Server & Power Room


Brand
Country of Origin

3 Accessories for suppression system

DETECTION

SYSTEM (Fire Suppression Zone)

Brand
Country of Origin
Control Panel
5

Seal Lead-Acid
Battery, 12V each 7.2 AH

Brand
Country of Origin
6 Low Profile Xenon Beacon (Red Color)
Country of Origin
7 Gas Discharge Sign
Brand
Country of Origin
8 Alarm Bell(Diameter 6")
Brand
Country of Origin
9 Auto Exit Sign
Brand
Country of Origin
10 Manual call point
Brand
Country of Origin

11 Heat Detector
Brand
Country of Origin
12 Optical smoke detector
Brand

Country of Origin
13 Double Flashing Light
Brand
Country of Origin
14 Mechanical fittings
15 Electrical Fittings

16 Installation

Description of requirements

UoM

QTY

Suppression Agent (GAS): NAF S 125

Kg

1090

120 Ltr Cylinder

Set

67.5 Ltr Cylinder

Set

Nos

24

Lot

Safety Hi-tech or other globally reputed brand


To be mentioned by the bidder
Composition: HFC-125 + 0.15% of Limonene Molecular weight : 120
Boiling point @ 1.013 bar: -48.3C
Density of the liquid @ 25C: 1189.7 kg/m3
Critical temperature: 339.45 K Critical pressure: 3595 Kpa
Vapor pressure @ 20C: 12.09 bar
Relative electrical resistance @ 1 atm. 21C (N2=1.0): 0.955
Purity (%): 99.99
Classification Of Fire: A, B, C and Electrical Fire. Global Warming Potential:
NA
Zero ozone depleting potential (ODP)
Safe Human Expose Time: 5 min Discharge Time: +10 sec Storage Pressure:
42 bar
UL Recognized and US EPA SNAP Listed gaseous extinguishing agent

Safety Hi-tech or other globally reputed brand


To be mentioned by the bidder

Working Pressure: 42 bar


Seamless storage containers having a working pressure of 42 bars and a test
pressure from 150 bars to 300 bars. UL Listed

Steel Nozzle 360 "required size" -UL Listed


Cylinder Back Rack
Cylinder Front Strap
Pressure Gauge
Cheek Valve
Manual Actuator
Aluminum Dip Tube
Actuator Block inch TEDEM +SOLENOID
Connection Hose/Pilot Hose
Manifold

To be mentioned By Bidder
To be mentioned By Bidder
Addressable Control Panel with Gas release/ 8 Detection zone with 4
Extinguishing area Control Panel

Nos

Nos

Nos

Nos

10

Nos

Nos

10

Nos

Nos

60

Nos

60

To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
Nos

Lot

Fire resistance cable 1.5 RM

Mtr

3000

PVC Pipe 3/4" conduit, fittings & caution sign

Lot

installation, Testing, Commissioning with line leak test & flow test

Lot

To be mentioned By Bidder
To be mentioned By Bidder
Schedule 40 Pipe, Origin: To be mentioned By Bidder
MS Fittings (Reducer + Clamping + Elbow)

Item-8: Environmental Monitoring System


SL. #

Product Names/Items
1 EMS
Brand
Model
Country of Origin
Form Factor
Features
Protocol

2 Temperature & Humidity Sensor


Brand
Country of Origin

3 Shock & Vibration Sensor


Brand
Country of Origin

4 Water leak detector


Brand
Country of Origin

5 Smoke Detection Sensor


Brand
Country of Origin
6 GSM Modem
Brand

Country of Origin
7 Installation

Description of requirements

UoM QTY

Environment Monitoring Server

Nos.

Nos.

16

NT1/Emerson/Schneider or other reputed brand


To be mentioned By Bidder
To be mentioned by the bidder
IU
Monitor and manage server room environmental and security
conditions over IP.
Create alarm signals with customized input parameters.
Four output relays for control of external devices.

Relays activate upon alarm or via the user interface.

Supports IP network video camera.

Live view of a facility from anywhere, anytime.

Monitor (ping) up to 64 IP network devices.

Alerts are sent if devices are not responding.

Provides power supply for all sensors.

Internal battery backup.

Up to four units can be used together to increase the number


of sensors connected.
Connect the units using CATS expansion cables or via Ethernet
interface by assigning an IP address for each system.

Uses a single Web interface for all systems connected

HTTP, SNMP V IN2C, SMTP, TCP/IP, Syslog, SNIP

Supports local authentication, SSL.

Operates and configures via HTTP/HTTPS web page, Telnet or


RS232 interface.
Alerts are sent using email, SMS messages and/or SNMP traps
when any monitored environmental condition exceeds a userspecified range
Space Temperature and Humidity Sensor
To be mentioned By Bidder
To be mentioned By Bidder
Shock & Vibration Sensor

Nos.

To be mentioned By Bidder

_.

To be mentioned By Bidder
Water Detector with 50 ft Leak Sensor Cable

Nos.

14

To be mentioned By Bidder
To be mentioned By Bidder

Smoke Detection Sensor

Nos

10

Nos.

To be mentioned By Bidder
To be mentioned By Bidder
GSM Modem
To be mentioned By Bidder

To be mentioned By Bidder
Installation, Testing & Commissioning

Job

Item-9: Electrical Works


P
SL. #

Product
Names/Items
1 Cable Trench

a
b
c
2 Cable wiring and Laying:

3 Cables

SL. #

Product Names/Items
4

EARTH
CONTINUITY CONDUCTORS

5 Light Fittings

Emergency Light

6 Switch Board:

SL. #

Products Names/Items
Socket Outlets:

7 DISTRIBUTION BOARD

7.1 MDB

Incoming

SL. # Product Names/Items

Page 167 of 363

Outgoing

SL. #

Product Names/Items

Installation

7.4 AC DB

Incoming:

Outgoing:

protective device(SPD)

SL. #

Product Names/Items

Installation
7.5 Utility & Light DB

Incoming:

Outgoing
Installation

7.6 UPS DB

Incoming

SL. #

Product Names/Items

Outgoing

Installation

8 Isolation Transformer

SL. #

Product Names/Items

Page 171 of 363

9 CABLE LADDER/TRAY

Page 171 of 363

10 Earthing

10.1

10.2
Earthing Bar
Cable

Description of requirements

UoM

QTY

Electrical Cable trench for feeder BBT from substation to cable duct.
Brick cable trench of 3'x 2.5' size with RCC slab of 4"x 48" for covering the
trench. Trench wall will be 5" wall at all side.
3'x2.5' Cable trench

RM

300

4'x48" RCC slab

RM

300

Installation

RM

600

Supply of Water grade PVC pipe and accessories of reputed Manufacturer's


as per routing shown in the drawing, concealed/surface mounted in
columns, ceiling, walls and other various places as required, complete with
bend/elbow, PVC circular boxes, sockets, lock-nuts, male/female
bushes,I8SWG G.I. pull/ wire, necessary taping of joints etc. As per
instruction of the Engineer-in

Job

charge.
20/25/32/40 mm diameter uPVC & flexible Pipe.
Brand: Era or other reputed brand. Country of Origin: To be mentioned by
the bidder
Installation (pipe work)

Job

Supply of PVC insulated single core cable/PVC insulated & PVC sheathed
single/multi core cables (BRB/
BBS/Poly ) having ISO 9002 certified co. of the following sizes in pre-laid
conduits/trench/tray and making good all damages and termination of
connection at both ends as per drawing, specification and instruction of the
Engineer-incharge.
1C -300 mm2 NYY Cable

4000

IC -95 mm NYY Cable

100

1C -35 mm NYY Cable

2400

4C -6 mm NYY Cable

500

3C -10 mm NYY Cable

2400

3C -2.5 mm BYM Cable

1000

1C -2.5 mm2 BYA-FR Cable

1500

1C -1.5 mm2 BYA-FR Cable

5000

Description of requirements

UoM

QTY

Supply of insulated/electrolytic annealed copper earth continuity conductor


(BRB/ Poly/BBS ) of following sizes in pre laid conduit/cable tray along with
cable including connection to various metallic parts as per specification,
drawing and instruction of the Engineer-in-charge:
IC - 300 mm2 BYA Cable(Green)

3000

1C - 95 mm2 BYA Cable(Green)

600

1C - 70 mm2 BYA Cable(Green)

600

400

IC - 35 mm BYA Cable(Green)

900

IC -6.0 mm2 BYA Cable(Green)

3000

IC - 2.5 mm2 BYA Cable(Green)

700

Installation (Cable work)

job

IC - 50 mm BYA Cable(Green)

Supply of imported ceiling surface/concealed mounted light fixture complete


with lx2OW energy saving LED lighting and all other necessary materials as per
drawing, specifications and direction of the Engineer-in-charge. Supply
installation of emergency light with built-in battery backup, all other necessary
materials as per drawing, specification and direction of engineer-in-charge.

Installation (Light fittings work)

set

700

set

60

set

760

Supply and installation of imported gang switches & socket from


Legrand(France)/M.K(Singapore) and wall boxes complete with all other
necessary accessories & connections everything complete as per drawing,
specification and instruction of the Engineer-in-charge. The wall boxes may be
locally made of 18SWG galvanized steel sheet including earthing block.
10A. 250 V., Single Pole Switch 1/2/3/4 Gang

set

Description of requirements

UoM

80
QTY

Supply and installation of imported I3A, 3-pin, 250V, combined switched socket
outlet from Legrand(France) 8.1.K(Singapore) suitable for 3 pin plug including
the box, cover plate with necessary galvanized machine screws, earthing block
complete with necessary connections as per drawings, specifications and
direction of the Engineer-incharge. The box may be locally made of I8SWG

set

40

galvanized sheet steel.

set

320

Supply and installation of imported 63A, 3-pin, 250V, industrial 3pin Plug
outlet from foreign made ABB (Italy) or equivalent as per drawings,
specifications and direction of the Engineer-in-charge.
Supply and installation of imported 32A, 5-pin, 440V, industrial 5pin Plug
outlet from foreign made ABB (Italy) or equivalent as per drawings,
specifications and direction of the Engineer-in-charge.
Installation (Switch & socket work)

set Job

30

Supply, Installation, testing & commissioning of following Distribution Boards


of components from ABB (Italy)/Eaton(EU)/Schneider (France)/Siemens
(Germany) having 1509001 certificate housing the following rated MCB/
MCCB & bus bars and all other accessories as per drawing, specifications and
direction of the Engineer-incharge.
Main Distribution Board at Power Room

Set

Sheet steel enclosed powder coated (I6SWG) , dust & vermin proof, free
standing, floor / Wall mounting,I415V, 50 Hz, indoor type Distribution Board
complete with hard drawn electrolytic copper bus bars of adequate rating, TPN
& E and equipped with:

1 No. 5000A, 100KA, TP full automatic fixed type ACB with stored-energy
motor charged operating mechanism having special features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.
Description of requirements
ii) Electronic trip unit with DIP Switch setting PR121/P which has operation
without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay trip.
I: Protection against instantaneous short circuit with adjustable trip current
threshold
3 Nos. Current Transformer, ratio: 5000/5A with suitable accuracy and
burden
1-No Digital Multi Meter ; brand: Siemens
(Germany)/ABB (Italy)/ Schneider (France) or other reputed brand
3 Nos. Phase Indicating Lamp
1-set Control fuse.
1 No. 100A, 25 kA, 3-pole, MCCB with 250 KA surge protective device(SPD)

1 No. 3200A, 63KA, TP full automatic fixed type ACB with stored-energy
motor charged operating mechanism having special features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.
ii) Electronic trip unit with DIP Switch setting PRI21/P which has operation
without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay tri s.
I: Protection against instantaneous short circuit with ad'ustable tri a current
threshold
I No. 1600A, 63KA, TP full automatic fixed type ACB with stored-energy
motor charged operating mechanism Navin. stecial features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.

_
UoM

QTY

ii) Electronic trip unit with DIP Switch setting PR121/P which has operation
without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay trip.

Description of requirements

UoM

QTY

I: Protection against instantaneous short circuit with adjustable trip current


threshold
1 No 500 A, 36 KA, TP MCCB with adjustable thermal overload and adjustable
magnetic short-circuit releases'
1 No 200 A, 25 KA, TP MCCB with adjustable thermal overload and adjustable
magnetic short-circuit releases'
1 No 100 A, 25 KA, TP MCCB with adjustable thermal overload and adjustable
magnetic short-circuit releases'

Sheet steel enclosed powder coated (16SWG) , dust & vermin proof, free
standing, floor / Wall mounting,'415V, 50 Hz, indoor type Distribution Board
complete with hard drawn electrolytic copper bus bars of adequate rating, TPN
& E and equipped with:

1 No. 1600A, 63KA, TP full automatic fixed type ACB with stored-energy
motor charged operating mechanism having special features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.
ii)
Electronic trip unit with DIP Switch setting PR121/P which has
operation without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay trip.
I: Protection against instantaneous short circuit with adjustable trip current
threshold
3 Nos. Current Transformer, ratio: 1600/5A with suitable accuracy and burden
3 Nos. Phase Indicating lamps, R-Y-B
1-No Digital Multi Meter ; brand: Siemens (Germany)/ABB (Italy)/ Schneider
(France)
I set of Control Fuse
1 No. 100A, 25 kA, 3-pole, MCCB with 200 KA surge
2 No 500 A, 36 KA, TP MCCB with adjustable thermal
overload and adjustable magnetic short-circuit releases'

set

set

Description of requirements

UoM

QTY

8 No 100 A, 25 KA, TP MCCB with adjustable thermal


overload and adjustable magnetic short-circuit releases'
14 No 32 A, 25 KA, TP MCCB with adjustable thermal overload and
adjustable magnetic short-circuit releases'
Set

Set

Set

Set

Sheet steel enclosed powder coated (16SWG) , dust & vermin proof, free
standing, floor / Wall mounting,'415V, 50 Hz, indoor type Distribution Board
complete with hard drawn electrolytic copper bus bars of adequate rating,
TPN & E and equipped with:

1 No 200 A, 25 KA, TP MCCB with adjustable thermal overload and


adjustable magnetic short-circuit releases'
3 Nos. Current Transformer, ratio:250/5A with suitable accuracy and burden
1-No Digital Multi Meter ; brand: Siemens
(Germany)/ABB (Italy)/ Schneider (France)

3 Nos. Phase Indicating lamps, R-Y-B


1 set of Control Fuse
1 No. 32A, 25 kA, 3-pole, MCCB with 100 KA surge protective device(SPD)

30 nos 10/16/20A SP Miniature Circuit breaker

Sheet steel enclosed powder coated (16SWG) , dust & vermin proof, free
standing, floor / Wall mounting,'4I5V, 50 Hz, indoor type Distribution Board
complete with hard drawn electrolytic copper bus bars of adequate rating,
TPN & E and equipped with:

1 No. 2500A, 63KA, TP full automatic fixed type ACB with stored-energy
motor charged operating mechanism having special features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.

Description of requirements
ii) Electronic trip unit with DIP Switch setting PRI21/P which has operation
without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay trip.
I: Protection against instantaneous short circuit with adjustable trip current
threshold
3 Nos. Current Transformer, ratio: 500/5A with suitable accuracy and burden
1-No Digital Multi Meter
3 Nos. Phase Indicating Lamp
1-set Control fuse.
1 No. 100A, 25 kA, 3-pole, MCCB with 200 KA surge protective device(SPD)

UoM

QTY

6 No 500 A, 36 KA, TP MCCB with adjustable thermal


overload and adjustable magnetic short-circuit releases'

1600KVA Galvanic isolation transformer with voltage ratio 415V/415V

Set

Set

The unit shall contain an electro statically shielded TP-I listed K13 or K20 type
isolation transformer. The transformer shall be a dry-type, double-shielded,
three-phase, common-core, convection air-cooled transformer. The transformer
shall conform to UL1561, with 302F (150C) maximum temperature rise. All
transformer windings shall be copper. The transformer shall be energy efficient
and shall meet NEMA standard TP-1 2002. The transformer shall exhibit the
following characteristics: percent impedance, 3.8 to 5.3%; common mode noise
attenuation, 120 dB; harmonic voltage distortion, 0.5% maximum additive; fullload efficiency, 96 to 98.6%.

The isolation transformer shall be provided with six full-capacity compensation


taps at 2-1/2% increments to accommodate field adjustment to match the source
voltage. These compensation taps shall be easily accessible by removal of one
exterior panel. Tap changes include:
two above nominal voltage (upper range limit of +5%), nominal voltage and
four below nominal voltage (lower range limit of -10%).
Description of requirements

The unit shall be provided with additional thermal overload protection for the
transformer. An alarm shall notify personnel if the transformer temperature
reaches 356F (180C). The unit shall automatically shut down if the
transformer temperature reaches 392F (200C). Temperature sensors shall be
located in each coil of the three phase windings.

Transformer neutral shall be sized for at least 200% of full load. The
transformer shall be designed to operate with 100% single-phase, switch-mode
power supplies and associated harmonic phase and neutral currents without
derating.
The Unit should have provision to connect to bus bar trunking system.
The Unit should have feature with soft starting system as it will be connected
with Uninterruptible Power system (UPS) output

UoM

QTY

Supply of required size cable ladder/tray including hangers, clamps, bends, nuts,
bolts & washer etc. complete in all respect as per instruction of the Engineer-incharge:
Size :18"x2" or required size

RM

400

Size :12"x3" or required size

RM

400

Installation (Cable tray/Ladder.)

RM

800

Earthing the electrical installation with 38.10mm (1.5") diameter GI pipe earth
electrode(1 0'-0") having 6.35mm diameter holes across the diameter at 305mm
interval securely bonded with 4 SWG, ; HDBC earth lead with washer, nuts,
bolts etc. sunk up to a depth 150'-0". Resistance should be < 1 Ohm completed
as per direction of the Engineer-in-charge.

set

24

Construction of 300X300X300mm earth inspection pit with R.C.0 cover as per


drawing & instruction of the Engineer-in-charge.

set

24

MGB with support


2

1C - 300 mm BYA Cable(Green)

Nos

15

Mtr

800

Item-10: Access Control System and Proximity Card


SL. #

Product Names/Items
1 Biometric Access Controller
Brand
Model
Country of Origin

Capacity

Interface

Hardware

SL. #

Product Names/Items
2 RFID Access Controller
Brand
Model
Country of Origin

Capacity

Page 173 of 363

Interface

Hardware

3 Push Button
4 U-Channel
5 ZL Bracket
6 Release button
7 UTP Cable
8 Magnetic Door Look
9 Desktop Computer

Brand

10 Power Supply
11 Software
12
13

Description of requirements

UoM QTY
Nos.

To be mentioned by bidder, must be globally reputed brand


To be mentioned by bidder
To be mentioned by bidder
IP Rating: IP 65
RF Option: 125KHz EM
125KHz HID Prox
13.56MHz Mifare/DesF ire/ EV1/Felica/NFC 13.56MHz iClass SE
Multi-Controller: Yes
Max. User (1:1) : 500,000
Max. User (1:N): 20,000
Max. Template ( I:1): 1,000,000
Max. Template (1:N): 40,000
Max. Text Log: 3,000,000
Wi-Fi: Yes
TCP/IP: Yes
RS-485: lch Host or lch Slave (Selectable)
RS-232: Yes
Wigand: lch In lch Out
Input: 2 Inputs
Relay: 1 Relay
USB : Host
CPU: 1.0GHz RISC
Memory: 128MB RAM + 8GB Flash
LCD: 2.8" Color
LED Indicator: Multi-Color
Sound: 16bit Hi-Fi
Operating Temp.: -20 to 50C
Tamper: Yes
Power: 12VDC
PoE: Yes
Certificates: CE, FCC, KC, RoHS, REACH, WEE

Description of requirements

UoM
Nos.

To be mentioned by bidder
To be mentioned by bidder
To be mentioned by bidder
IP Rating: IP 65
13.56MHz Mifare/DESFire/Felica
Multi-Controller: Yes

QTY
12

Max. User (1:1) : 50,000


Max. User (1:N):50,000
Max. Text Log: 100,000
TCP/IP: Yes
RS-485: I& Host or lch Slave (Selectable)
Wigand: lch In, lch Out
Input: 2 Inputs
Relay: 1 Relay
CPU: 533 MHz DSP
Memory: 16MB RAM + 16MB Flash
LED Indicator: Multi-Color
Sound: Multi-tone Buzzer
Operating Temp.: -35 to 65C
Tamper: Yes
Power: 12VDC
Certificates: CE, FCC, KC, RoHS, REACH, WEE
Exit Push Button

Nos.

10

U-Channel breaker for mounting lock

Nos.

12

ZL Bracket for lock mounting accessories

Nos.

12

Emergency Lock release button

Nos.

12

Cat-6 UTP Cable

Box

Electro Magnetic Door Look (600) lbs.

Nos.

12

Desktop Computer

Nos.

Power supply unit c/w battery charging option.

Nos.

12

Windows-Based door Access control Management system software with


Basic attendance facility

Nos.

Front side color & Back side B/W ID Card

Nos.

30

Installation, Testing and commissioning

Lot

HP/DELL /Lenovo or equivalent


Processor Intel 15 or higher, 4GB RAM, 1TB HDD, DVD R & RW,
18.5" LCD/LED monitor

Item-11: Rodent Systems


Product

SL. #

Names/Items
Rodent System
Brand

Model
Country of Origin
Type
Features:
1 Controller

2 Transducer

Wire bundle-600 yards (550m)

4 Installation & Commissioning

Description of requirements

UoM

QTY

To be mentioned by bidder, must be a reputed brand


To be mentioned by bidder
To be mentioned by bidder
Rodent System.
>5000 Sq Feet of Area Coverage
LCD display with on-board controls
Wave Speed: Is an indicator for the number of frequency sweeps per
minute. It can have a maximum value of 130 and a minimum value of 60.
The incremental size is 5 i.e. 65, 70, 75 and so on.
Wave Density: Is an indicator for the number of divisions within a
frequency band. It can have a maximum value of 100 and a minimum
value of 80. The incremental size is 10 i.e.80,90 and 100

Frequency Band Time: Is an indicator of the time for which the controller
would operate in a pre-programmed frequency band. There are 3 bands
available: Band A, Band B, and Band C. This parameter can have
maximum value of 10 minutes and a minimum value of 1 minute per band.
Depending upon the time frame set for each band, the controller will
switch the bands automatically Machine/Controller ID: Is an indicator of
the machine/controller identification number. It can have any value within
the range of 1 to 255.

Password Protection: Every controller is password protected. To change


the
parameters mentioned above you have to key in the password. The
password can be changed if required. The password can be any 5 digit
number.
Inbuilt RS/EIA-485 transmission up to 1.2 kilo meters to protect BMS
Room.
Frequency band of > 20 KHz and <60 KHz is pre tuned for 100 different
frequencies
Each Transducer should cover up to 500 sq. feet of area above false
ceiling, below false ceiling and below false flooring or up to 400 sq. feet of
area above false ceiling, below false ceiling and below false flooring.
UL and CE approved transformers for power supply.

Nos

###

The satellites or Transducers shall be circular ceiling mounted low profile


units that produce high decibel sound waves at very high frequency not
less than 20

Nos

20

KHz. These satellites shall cover an area not less than 400 Sq.Ft for Room
void application, for ceiling Voids & floor void applications
Lot
Installation, Commissioning and tested charges will include appropriate
and quote for the same. If any other Hardware / Software / Internal or
External cables or any component or equipment is required for giving the
solution, mention and quote for the same.

Job

Item-12: Heavy Duty Fire Resistant Data Safe


Product

SL. #
1

Names/Items
Heavy Duty Fire Resistant Data safe
Brand
Model
Country of Origin
Humidity
Capacity
Heating
Fire Rating

Accessories
ISO
Locking System

Description of requirements

Aiko/ Godrej/ or Equivalent reputed brand


To be mentioned by bidder
To be mentioned by bidder
85%
120 Liter / 4 ft3
1010 C
JIS 2 Hours (Japan Industrial Standard)
KIS (Korean Industrial Standard)
SINTEF (Norwegian Fire Research Laboratory): Norway, Europe
UL Certification: USA
SP Certification: Sweden, Europe
5 Shelves (Sliding)
9001:2008
Triple Lock System (2 Key Lock & 1 Combination Lock, Four Side Locking
System) Automatic Re- Locking Device, Duel Locking System.

UoM

QTY

EA

Item-13: Aspiration (VESDA) System


SL. #

Product Names/Items
Aspiration (VESDA) system
Brand
APPROVALS standards

Country of origin
Manufacturing Country
General Features

1 Controller for Server Room

Model
Features:

Controller for Power Room with gas

detector
Model

Features:

3
4
5
6
7
8
9

10 Installation & Commissioning

Description of requirements

UoM

QTY

Nos

Xtralis or other globally reputed brand


LPCB (Loss Prevention Certification Board), UK
FM (Factory Mutual), US
UL (Underwriters Laboratories Inc.), US
ULC (Underwriters Laboratories Canada), Canada
Vds, Germany
To be mentioned by bidder
To be mentioned by bidder

Bidder should supply and install Very Early High Smoke Detection
Aspirating (VESDA) should have the HSSD (High Sensitive Smoke
Detectors) system shall provide an early warning of fire in its incipient
stage, analyze the risk, and provide alarm and actions appropriate to
the risk the system shall include a Display Control Panel, Detector
Assembly, and the properly designed sampling pipe network for the
multiple zones
(Server room, Power room, and PAC room). The system equipment shall
be supplied by the Manufacturer's or by its authorized distributor.
invisible hazards can originate from the release of toxic gases, oxygen
deficiency, or the presence of combustible gases/vapors.

To be mentioned by bidder

Out-of-the-box installation and commissioning.


Ultrasonic Airflow testing.
Laser-based Absolute Smoke Detection.
Programmable Alarm Thresholds.
Clean air barrier optics protection.
Instant Recognition Display.
Multiple Event Logging in separate logs
Determined using ASPIRE2.
Offline/online configuration capability.
Input Power Voltage: 24V DC Nominal (18-30 V DC).

IP Rating IP30.
Tested to: -10C-55C (14-131F)
Page 177 of
Detector Ambient: 0C-39C
(32-103F)
363

Sampled Air: -20-60C (-4-140F)


Humidity: 10%-95% RH, non-condensing
Maximum Area: Please Mention
Alarm Sensitivity Range: 0.0015%-6.25% obs/ft. (0.005% 20% obs/m)
IP Rating IP30
UL Listed
Nos

24V DC, 2 AMP Power Supply Units With Battery

Nos.

Sampling Pipe, Smooth bore PVC Pipe 21mm ID and 25mm OD

Mtr.

300

Hooter

Nos.

2 core x 1.5 sq mm BYA cable for Power -

Mtr.

300

25mm PVC conduit for the above cable

Mtr.

300

End Cap

Mtr.

40

T Joints & L Bends for sampling point network

Mtr.

150

Job

To be mentioned by bidder
Ultrasonic Airflow testing.
Laser-based Absolute Smoke Detection.
Programmable Alarm Thresholds.
Clean air barrier optics protection.
Instant Recognition Display.
Multiple Event Logging in separate logs
Determined using ASPIRE2.
Offline/online configuration capability.
Input Power Voltage: 24V DC Nominal (18-30 V DC).
IP Rating IP30.
Detector Ambient: 0 C to 40 C (32 F to 104 F).
Sampled Air: 0 C to 40 C (32 F to 104 F).
Humidity: 5% to 95% (non-condensing).
Maximum Area: Please Mention
UL Listed

Installation, testing and commissioning

Item-14: Substation with AVR


SL. #.

Product

Names/Items
General
11 KV H.T.

SW1TCHG EAR
(VCB)

SL. #.

Product
Names/Items

SL. #.

3150 KVA TRANSFORMER (DRY TYPE)

Product
Names/Items

Product

SL. #.

Names/Items
LT SWITCH GEAR PANEL

Incoming

Incoming

SL. #.

Product
Names/Items

Page 181 of 363

Outgoing

SL. #.

Product Names/Items

4 1800 KVAR AUTOMATIC PFI PLANT

Incoming

5 SYSTEM EARTHING

6 11KV DROPOUT FUSE (DOF)

11KV LIGHTNING

ARRESTER
7

8 11KV AVR & By- pass Switch

PVC INSULATED & PVC SHEATHED HT


CABLE

10

PVC INSULATED & PVC SHEATHED LT CABLE

10.1

10.2

11

Testing and Commissioning

12

Documentation

13

Warranty

Description of requirements

UoM

QTY

Set

UoM

QTY

Two numbers of 3MVA substations, which are fully redundant


with total required load.
HT PANEL-01& 02 (INCOMMING) WITH ACCESSORIES VCB

Supply of metal enclosed sheet steel clad (12SWG) powder


coated, dust & vermin proof, free-standing, floor mounting
type compartmentalized, withdraw able truck type,
completely local factory assembled with heat proof painting
11KV, 31.5 KA, 50Hz, 3-phase indoor type high tension
switchgear panel having 800Amps hard-drawn electrolytic
copper bus bars and comprising of the following components
in accordance with NEMA/IEC/ VDE/ BS/JIS standards IEC298
or latest version : (The major components of the HT
switchgear shall be from USA or Europe. The work shall be as
per design, drawing, specification & direction of consultant /
Engineer in charge.

1 No. 800A, 11KV, 25KA, 3-Sec. triple pole,


maintenance free Vacuum Circuit Breaker (VCB) withdrawable truck type, with motor operating mechanism, with shunt
trip coil, trip button, auxiliary contacts and 1 No. Emergency
manual charging handle.
I Set Operating mechanism of circuit breaker with
mechanical push buttons "ON" for earthing, electrical push
button "OFF/ON" operation counter, cut out switch, contact for
spring charged mechanical indicators "ON", "OFF", Spring
charged with 1No. Closing coil, 1No. Tripping coil.
I Set: 12 KV, 800 Amp, 25 KA 3-phase bus bars of hard drawn
electrolytic copper for VCB.
1 No. 11 KV, 50Hz, 20 KA (Isec) triple pole earthing
switch to be inter locked with VCB
1 Set HV Termination, 11KV suitable for cable/plug
connection.

Description of requirements
3 Nos. Cast resin insulated dry type single pole Potential
Transformer with ratio 11/n13: 0.110N3KV, class 0.5, burden
50VA.
3 Nos. Cast resin insulated lIKV dry type double core
Current Transformer (CT), ratio 250/5/5A, 1st core for metering
and 2nd core for protection with following accuracy and burden:
Core 1 : 15VA, Class 0.5M5
Core 2 : 15VA, Class 10P10
1 No. TP MCB of adequate rating for PT secondary
protection.

3 nos. digital ammeter range ( 0-250A)


1 no. digital voltmeter of range (0- 15kv) with selector switch

1 set solid state micro-processor based digital IDMT relay for


Over current, short circuit and Earth fault protection with a
provision for setting instantaneous characteristic with a load
monitoring, event and fault memory.

1 No. Multi function meter having KWh/KVA rh meter,


frequency, phase-wise ampere, phase-wise voltage, harmonics,
temperature monitoring MDI in KW with time integration period
30 minutes.
3 Nos. Indicating lamps "ON/OFF/TRIP" spring Charge and DC
available.
3 Nos: ON/OFF/TRIP push buttons
1 No. Panel heater
Panel shall be completed with all accessories as required
Set

UoM

QTY

Supply & installation of 3150 KVA, 3-Phase 50Hz of indoor


type, cast resin insulated power distribution transformer shall be
complying with IEC 60076-11,2004 standard with off-load tap
changer for indoor installation with type tested. The product shall
be standard quality as approved by the consultant/owner. The Xformer shall be suitable for BBT connection as shown in SLD.

Description of
requirements
i) Capacity : 3150 KVA
ii) Voltage Ratio : 11000/4I5V
iii) Cooling : AN
iv) Frequency : 50Hz
v) Phase : 3 (Three)
vi) Vector Group : DYN-11
vii) BIL : 75 KV (HT side), 2.5KV(LT side)
viii) Inter phase connection: Delta
ix)

Ambient Temp : 40 C

x) Maximum Temperature rise in


the HV/LV windings : 100K/100K
xi) Off load manually operated Tap changing: 2.5%, 5%
xii) Impedance % : 6.0 % (app)
xiii) Degree of protection : IP 23
xiv) No-Load Loss : To be quoted by the bidder
xv) Load Loss at 75 C : To be quoted by the bidder
xvi) Environmental class : E2
xvii) Climatic Class :C2

xviii)

Fire behavior Class :F1

xix) Sound Level (LWA) : 81 db


xx) Accessories:
1 Pc. Temperature protection system consisting of:
1 Pc.PTC Temperature sensor-loop winding warning
1 Pc.PTC Temperature sensor-loop winding tripping
1 Pc.PTC resistor rely type MSF 220K AC/DC 24-240V
2 - PTC resistor sets, 2 output relays, 1 change-over contact
(co)/
1 normally open contact (no), K-type housing
1 relay fan, 1 relay FAULT panel cutout:92X92mm,
depth:140mm

Description of
requirements

UoM
Set

L.T. Panels shall be as per design, drawing, specification and


direction of consultant / engineer in charge. The panel shall be of
14 SWG sheet steel clad, dust & vermin proof, floor standing,
indoor type, conforming to IEC 439.1. The panel shall be
equipped with TPNE bus bars of adequate rating of hard drawn
electrolytic Copper, TP/TPN MCCB/ACB with adjustable
thermal overload and magnetic short circuit releases; Ammeter,
Voltmeter, C.T of adequate rating with Phase indication, off, on
and trip lamps at incoming end, over voltage / under voltage trip
coil, and 220V / 4mA shunt trip coil as shown in SLD. All the
panels shall have circuit diagram showing internal wiring
diagram inside of Panel front cover. Size of hard drawn
electrolyte copper bus bar shall be proposed by the bidder. The
panel shall be suitable for BBT connection as shown in SLD. The
supplier shall supply catalogue along with the offer. All ACB
shall be inbuilt DC operation. The product shall be Schneider /
Telemecanique /ABB /Legrand / Dorman Smith or approved
equivalent. Incoming & Outgoing breakers of the Panel Shall be
computerized having communication Port for BMS Integration.
6000A hard drawn bus bars, TP, N&E equipped with:

2 No. 5000A, 100KA, 4P full automatic fixed type ACB with


stored-energy motor charged operating mechanism having
features :
i) Microprocessor controlled adjustable thermal overload,
Adjustable electromagnetic short circuit releases.
ii) Electronic trip unit with DIP Switch setting PRI21/P which
has operation without the need for an external power supply
iii) Protection function :

QTY
1

L: Protection against overload with inverse long time delay trip.


Description of requirements

UoM

QTY

I: Protection against instantaneous short circuit with


adjustable trip current threshold
3 Nos. Current Transformer, ratio: 5000/5A with suitable
accuracy and burden
3 Nos. Ammeter, 0 - 5000 A.
1 No. Voltmeter, 0 - 500 V with selector switch.
3 Nos. Phase Indicating Lamp
2 Nos. 5000A, 100KA, TP full automatic fixed type ACB with
stored-energy motor charged operating mechanism having
special features :
i) Microprocessor controlled adjustable thermal overload,
adjustable electromagnetic short circuit releases.
ii) Electronic trip unit with DIP Switch setting PR121/P which
has operation without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay
trip.
1: Protection against instantaneous short circuit with
adjustable
trip current threshold
1 No. 500 A, 36 KA, TP MCCB with adjustable thermal overload
and adjustable magnetic short-circuit releases
1 No. 200 A, 36 KA, TP MCCB with adjustable thermal overload
and adjustable magnetic short-circuit releases
Bus Coupler:
1 No. 5000A, 100KA, 4P full automatic fixed type ACB with
stored-energy motor charged operating mechanism having
special features :
i) Microprocessor controlled adjustable thermal overload,
adjustable electromagnetic short circuit releases.
ii) Electronic trip unit with DIP Switch setting PRI21/P which
has operation without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay
trip.
I: Protection against instantaneous short circuit with
adjustable trip current threshold.
Switchgear brand: Siemens/ABB/Schneider/Eaton or other
globally reputed brand.
Switchgear Origin: To be mentioned by the bidder

Description of requirements

UoM

QTY

Auto/Manual P.F.I. plants as per drawing, specification and


direction. The panel shall be of 14SWG-sheet steel clad, dust and
vermin proof, freestanding floor mounting type, conforming to
IEC 439.1. PF correction relay with interlocking auxiliary relay
with digital built in P.F meter; selector switch for Auto/Manual
Set
operation; step indicating lamps, TP capacitor bank within built
discharge resistor. Size of hard drawn electrolyte copper bus bar
shall be proposed by the bidder. The P.F.I. plant shall consist of
the following type Automatic Power Factor Improvement Plant,
comprising:

1 No. 3200A, 65KA,TP full automatic fixed type ACB with


stored-energy motor charged operating mechanism having special
features :
i) Microprocessor controlled adjustable thermal overload,
adjustable electromagnetic short circuit releases.
ii)
Electronic trip unit with DIP Switch setting PR121/P ,
which has operation without the need for an external power
supply
iii) Protection function :
L: Protection against overload with inverse long time delay trip.
I: Protection against instantaneous short circuit with adjustable
trip current threshold
Switchgear brand: Siemens/ABB/Schneider/Eaton or equivalent
Switchgear Origin: USA/ EU/ UK/ Japan
1 No. 25 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resister (Direct)
1 No. 25 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resister
1 No. 50 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resistor
1 No. 100 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resister
8 Nos. 200(100+100) KVAR Bank of TP dry type Power
Capacitors with built-in discharge resister
Capacitor Origin : EU/ USA/UK/ Japan
Capacitor Brand: To be mentioned by bidder
1 No. - 415V, 40 Amps. 50 Hz TP magnetic contactor with AC3
duty.
1 Nos. - 415V, 80 Amps. 50 Hz TP magnetic contactor with AC3
duty.
1 Nos. - 415V, 150 Amps. 50 Hz TP magnetic contactor with
AC3 duty.
8 Nos. - 415V, 300 Amps. 50 Hz TP magnetic contactor with
AC3 duty.

Set

1 Nos. - 415V, 40 Amps. TPMCCB with thermal overload &


instantaneous electro-magnetic short circuit release.
1 Nos. - 415V, 80 Amps. TPMCCB with thermal overload &
instantaneous electro-magnetic short circuit release.
1 Nos. - 415V, 160 Amps. TPMCCB with thermal overload &
instantaneous electro-magnetic short circuit release.
8 Nos. - 415V, 320 Amps. TPMCCB with thermal overload &
instantaneous electro-magnetic s t mitrelease.

All MCCB made of ABB/(Italy) r ii /Schneider


(France)/Siemens (Germany) /Equivalent
1 No. Automatic Power Factor Correction Relay 11 Nos. TP Air
Contactors of adequate rating Origin: EU/ UK/ Japan
Brand: To be mentioned by bidder
11 Nos. of Indicating Lamps
1 Set of Control fuses
System Earthing shall be as per design, drawing, Specification &
direction of consultant / Engineer in charge completed with the
followings:
Earth continuity conductor:
Copper earth continuity conductor 2x1/0 SWG from equipment
body to Earthing block through GI pipe. Copper Earthing block:
Copper Earthing block (450mmx50mmx10mm) Earthing Lead:
Supply, Installation & Connection of copper Earthing Lead
(2x1/0 SWG) from main Earthling Block to the Earth Electrode
through GI pipe. Earthing lead shall be run in duplicate down to
the earth electrode.
Earth Electrode:
Earth electrode shall be 40mm dia. 40m long (Variable) G.I. pipe
with 10mm diameter holes @ 1200mm length wise in a zigzag
manner. Including 2 nos. brass clamps (200mmx4Ommx6mm)
with teeth, at the top. The earth electrode shall be driven into the
ground by tube well

sinking method. The top/head of the G.I. pipe after completing all
connections shall be covered with hessian cloth soaked in
bitumen. They have to apply to possible way to get the earth
resistance below 1 ohm.
Earth Inspection Pit:

Set

30

Construction of Earth Inspection Pit (inside:


300mmx300mmx300mm) with 125mm brick side wall in 1:4,
75mm C.0 bed in 1:5:7; inside 12mm plaster in 1:4: and
700mmx700mmx75mm R.C.0 cover at top with lifting hooks.
The item includes earth excavation, back filling, ramming etc

11KV Drop-Out Fuse (250A 3 Nos.) of following specification


including required size galvanized iron angle/channel as per drawing
& direction:
Specifications:

Rated Voltage (Nominal) : 11 KV


Rated Max. Voltage : 15 KV

Set

Set

Rated Frequency : 50 Hz BIL : 75 KV


Rated Current (rms) : 250 A

Interrupting Current (rms) : 10 KA


Withstand Test Voltage: Dry, 1 Min. : 35 KV Wet, 10 Sec : 30KV
11 KV lightning arrester (3 Nos.) of following specification

including required size galvanized iron angle/ channel as


per drawing & direction: Specifications:
Rated Voltage : 11 KV
Rated System Voltage : 12 KV Rated Arrester Voltage: 9KV
Frequency : 50 Hz
Min. Spark Over (rms) : 14 KV Max. Spark Over (rms) : 40 KV
Max. Impulse Spark : 45 KV

BIL (Peak) : 75 KV
Withstand Voltage:
Wet, 10 Sec. : 24 KV
Dry, 1 Min. : 28 KV
Discharge Current : 5 KA
Impulse Current Withstand : 55 KA
Supply of lIKV Automatic Voltage Regulators Siemens type JFR
single phase voltage regulators to provide +/- 10% regulation in
32 steps of 5/8% each. Rated 139 kVA, 6,350 volts, 219 amps, 95
kV BIL, 55/65C, 50 Hz, ANSI

type "B", class "ONAN". Manufactured and tested per ANSI


C57.15. According to NEMA and ANSI C57.12.31 or equivalent
standards and shall meet latest requirements of
DPDC/DESA/DESCO. The Voltage Regulators shall be from
reputed Manufacturer's of USA, Japan or European countries
(1Set=3Nos)

Automatic Voltage Regulators shall be type tested 219A, 11KV,


3-phase/ 6.35KV, Single Phase in sealed tank design with digital
Control panel, Ground clamps & standard accessories and as per
following technical data/
specification:
Output Voltage: 11KV, 50hz, 3-Phase
Rated voltage : lIKV, 3-phase/ 6.35KV,1-phase Rated frequency :
50Hz
Rated current : 219 Amps
Basic Insulation Level (BIL) : 95KV
Rated range of regulation :+/-10% in 32 nos. equal steps Sealed
tank design: Yes
Cooling : Self
Temperature rise: Up to 65deg.0 without increase the oxidation
rate of Oil.

Set

RM

500

Provision for 240VAC, 50Hz test input voltage for testing of the
voltage regulator with external power supply: Yes Microprocessor based control panel : Yes
Non-PCB oil for the voltage regulator : Yes
Accuracy class of regulator control panel: Class-1 Installation:
Outdoor/Indoor
Voltage Regulators shall be supplied with following spares: 6
Nos. Fuses
2 Nos. Position Indicator Glass
2 Nos. Oil Sight Gauge Glass
1 No. Digital control panel
IP Rating: 65
Response to stable in sec: 5 to 10 Sec

Supply of sheet steel clad, powder coated, dust & vermin proof,
free standing, floor mounting, indoor type 11KV Bypass Switch
panel boards having self quenching, single phase, two position
device LBS type with 20KA (lsec) and isolating or de-energizing
of Auto Voltage Regulator as per following technical data/
specification: (ISet= 3Nos.) and Surge Arrester.

Maximum design voltage : 15.5KV


Basic Insulation Level (BIL) : 95KV
Rated Continuous Current : 630A
Momentary ratings : Disconnect blades 40KA
By-pass blade 30KA
IP Rating: 23
Supply, laying and termination of follow PVC bedded
and PVC sheathed 15KV (XLPE t Taritioreable of
Eastern Cable or approved equi kihaliiie

as pet\design,

drawing, specification & direction of consultant / Engineer in


charge, through underground cable trench / G.I. pipe in trench
along/across the road, back filling, road cutting (including
getting permission from concerned authority) & mending
good the damage, brick, sand, heat shrink joint etc. up to the
entire satisfaction of the concerned authority DPDC /DESA/
DESCO.
The work shall be included with cable tray and cable ladder
for indoor installation as per drawing and direction.
The cables shall be made according to VDE 0271/3.69 &
B.D.S901:85 with rated voltage 8.7/15kv.
3c 240 mm2 NYSEYFG by (HT Cable) In Pakka road (Quantity
shall be as per site measurement)

Supply, installation & termination of following PVC insulated


and PVC sheathed cables (NYY type) of Eastern, Super sign,
Poly, BRB or approved quality shall be as per design, drawing,
specification & direction of consultant / Engineer in charge.
Cable work shall be complete with rigid PVC conduit of
approved type, pull box, bend, tees, cable tray, cable ladder
etc. External cable work such as underground lying, earth
cutting up to 900-mm depth, providing cable protection, filling
the excavation with sand etc. shall be done by the contractor.
The cables shall be made according to VDE 0271/3.69 &
B.D.S_901:85 with rated voltage 600/1000v.

lc 300 mm2 NYY for substation panel interconnectivity.


(Quantity shall be as per site measurement)

RM

1000

lc 300 mm2 BYA ECC green for transformer Neutral and


Substation main earthing. (Quantity shall be as per site
measurement)

RM

250

Testing, Commissioning and balancing of the system shall be


done as per recommended practice and as per direction of the
Engineer-in-Charge /Consultant. For this purpose liaison and
arrangements with DPDC/DESA/DESCO for the connection &
power feeding must be done by the Contractor. Measuring of
all equipment, line, conductors, dielectric insulation testing of
transformer oil, earth resistance testing, centrifuging of oil (if
necessary), phase sequence testing, primary and secondary
induction test of all relay, x-former ratio test, tapping test, tap
changing test, voltage compensation test, permanent phase
marking etc. shall be done in presence of consultant and
proper document shall be submitted for approval.

Job

After complete installation, testing, commissioning and


balancing the contractor has to submit 4 copies of as built
drawing and all documents to the owner. Working drawing
shall have to be prepared by the contractor.

Lot

One year full warranty (onsite covering everything with parts


and services) period including all maintenance and support
for the system from the date of commissioning and
acceptance. This warranty coverage document shall include
24 x 7 supports and maintenance services from Principal shall
submit to the customer.

Item-15: DPDC /DESA /DESCO Connection


SL. #

Product
Names/Items

1 DPDC /DESA / DESCO Connection

Description of requirements

The Contractor shall arrange power line connection from


DPDC/DESA/DESCO 11 KV over head line, H.T. meter supply &
installation permission from Electricity Licensing Board etc. All the
expenses including road cutting etc. shall be under this contract at
contractor's cost. Only security money and H.T meter installation
charge against demand note and electricity licensing board fee shall be
deposited by the Customers.

UoM

QTY

Job

Item-16: Electro-magnetic Field Protection


Product

SL. #

Names/Items
1 EM F

2 SRG

3 Installation

Description of requirements

UoM

Electromagnetic Field Protection by 3mm thickness and 25 mm


width copper flat conductor for Server, PAC and Power Room

Lot

Single Grid reference (SRG) of 4 swg crisscross bare copper


grounding conductors under the raised floor, attaching to every
fourth support pedestal via bolt/clamp connection as per ANSI-JSTD-607-A

Mtr

Job

QTY

###

1600

###

Item-17: Installation and Implementation Service


Product

SL. #

Names/Items
1

Description of requirements

UoM

Installation , testing and commission of all data centre item

lot

QTY

###

Item-18: One year Service


SL. #

Product

Names/Items

Description of requirements

1 Network Engineer, Type-1

CCIE Certified network engineer on site

2 Network Engineer, Type-2

CCNP Certified network engineer on site

3 Data Centre Engineer. Type-1

CDCP Certified Data centre engineer on site

4 Data Centre Engineer, Type-2

CDCS Certified Data centre engineer on site

UoM

QTY

Year

###

Year

###

Year

###

Year

###

Item-19: Furniture and Monitor


Product

SL. #

Description of requirements

Names/Items
Monitor

42" LCD/LED Display Monitor

Brand

To be mentioned by bidder

Model

To be mentioned by bidder

2 Furniture

NOC Room Workstation with executive chair

Page 189 of 363

ti

UoM

QTY

Each

Each

Item-20: Labeling & Documentation


UoM

Description of requirements
9mm, 12mm, 18mm, 25mm, 36mm
laminated label tape with standard adhesive
for hot and cold environments for

Nos

the reason of labeling and tagging of all


cable and

Lot

equipment as per TIA-942 standard


UAT, as built design of all major equipment
layout, user
operation manual of intelligent products and
others
necessary
relevant
document
submission as per specified clause

QTY
100
1

Item-21: Tier-Ill Certification


Product
SL. #

Description of requirements

UoIVI

Names/Items
1 Design Validation EPI Design Validation
2

EPI Certification EP1 Tier-Ill Certification for 3


Years

Lot
Lot

(b) Item-22: Local Training (Category D)

Products
Names/Items

Description of requirements

10 Days 15 Person Training on UPS, PAC,


Local Training DCIM, Substation, Generator item in BCC
Premises

UoM

Lot

Item-23: Foreign Training (Category D)


Products
Names/Items
Foreign
Training

Description of requirements

Data Center Facility Operation Management


(CDFOM) Training Abroad for 10 person
(Malaysia/Thailand/Philippines)

UoM

Lot

QTY

QTY

QTY

Item-24: DataCentre Infrastructure Management (DCIM)


Product

SL. #

Names/Items
1

Brand
Model

Country of origin
Manufacturing Country
Type
User Experience Computer User

User Experience Mobile User

Device Library

I__ _

SL. #

Product
Names/Items

Device Data Import

Device Placement

Product

SL. #

Names/Items

Connections Catalog

Page 191 of 363

Inventory Search

Physical Area Capacities

Product

SL. #

Names/Items

Container
Capacities

Group Capacities

SL. #

Product
Names/Items

Threshold Alerting

Capacity Visualization

Capacity Search

Project Management

Business Process Planning

Page 193 of 363

Product

SL. #

Names/Items
Business Process Enforcement

The Solution shall have the ability to configure the


processes per the organization's requirements.
Visualization
The solution shall show the user any device or space
that is affected by a future change
The solution shall allow the user to see a chosen asset
represented multiple times, showing all the changes that are
_planned for that device of time.
Monitor and Manage Workflows

The solution shall show the user all workflows in the


system and track their status, owner, planned
completion date and history.
completed in a chosen day, week, month
Power Chain Inventory

The solution shall provide an ability to collect an


inventory of all the AC power connections between
devices or device ports.

The solution shall provide an ability to build a power chain tree and for any newly connected device to inherit the
attributes and upstream connections of that tree once a connection is made.
Product I

SL. #

Names/Items
Power Chain

Power Chain
Visualization

Thermal Visualization

Facility Monitoring, Site Management

Page 197 of 363

Device Alarm Monitoring

SL. #

Product
Names/Items
Alarm Group Management

Alarm Visualization

Threshold Management

Raise Alarms to Users or Systems

Product

SL. #

Names/Items
Escalate Alarms

Suppress Alarms

Device Discovery

Device Monitoring

Data Aggregation & Visualization

Product

SL. #

Names/Items

Page 199 of

363

Dependency

IT v Facilities

Pre-Configured Dashboards

Pre-Configured Reports

Product

SL. #

Names/Items

Page 200 of 363 11-)

Report Distribution

Application Server

SL. #

Product
Names/Items
Device Monitoring

DOOM Server System


Specification

Page 202 of

DCIM Facility Management Gateway

(L4

SL. #

Product
Names/Items

2 Installation & Commissioning

Item-24: DataCentre Infrastructure Management (DCIM)


Description of
requirements

UoM

QTY

Emerson/Schneider or other equivalent reputed brand


To be mentioned By Bidder
To be mentioned By Bidder
To be mentioned By Bidder
Data centre Infrastructure Management (DCIM) Software and
Hardware with minimum 1000 port licenses

Set

The user interface shall be provided via Web browser without the
need for any additional installation of software on the client
computer.
The user interface shall be provided using textual or graphical
views of data with drag and drop capability for the majority of the
user interaction.

The mobile user interface shall be provided using an app


supported on Apple iPad.
The mobile solution shall provide a full graphical view of the data
center floors, racks, devices and connections.
The mobile solution shall allow the user to modify any of the data
center parameters including position of devices in racks, device
properties and connections. The mobile solution shall allow the user
to conduct an audit of any rack noting any devices that do not
conform to the placement as recorded in the DCIM tool.
The mobile solution shall allow the user to receive; view and
respond to alarms generated by the DCIM system or attached
equipment.

The solution shall support a library of pre-built symbols to include a


graphical representation of the device front, rear and top down
where relevant. The symbol shall also contain all
capacity/consumption data for the device to include, power, heat,
space and weight.

Description of requirements
The solution library symbols shall have at least 10,000 vendor
neutral symbols available for use on installation of the solution.
The solution symbols shall depict an exact replica of the device
power connections, network connections and available slots.
The solution symbols shall contain an ability to monitor real time
from the device automatically once added to the solution library.
The solution user shall have an ability to request additional
symbols be created to match devices at the customer site.
The solution user shall have an ability to download additional
symbols from a central online repository without support from the
Manufacturer's.
The solution symbols library shall contain symbols for IT devices.

UoM

QTY

The solution symbols library shall contain symbols for critical


infrastructure or other non-IT devices.
The solution shall allow a user to import device data from an open
file format e.g. csv, Excel
The solution shall allow a user to import device data into a staging
area for manipulation and verification before applying the data to
the DCIM model
The solution shall provide an ability to verify the staging area data
against the DCIM model including checks for capacity, device
names etc.
The solution shall have an ability to export device details to an
open file format e.g. csv, Excel

The solution shall provide an ability to build a model of the


placement of devices using simple drag and drop methods
The solution shall allow devices to be placed on a floor plan
The solution shall allow devices to be placed in a row
The solution shall allow devices to be placed in a rack
The solution shall allow devices to be placed inside another device
The solution shall allow provide default naming conventions to be
used when a device is placed in the model

The solution shall allow devices to be placed in a zone


The solution shall allow devices to be placed in a generic breaker
panel

The solution shall provide an ability to group devices into logical


groups that can be created and named by the user.

The solution shall provide an ability to make power connections


between power ports of placed devices
The solution shall provide an ability to make data connections between
data ports of placed devices
The solution shall provide an ability to make power connections
between placed devices i.e. without specifying a port connection
The solution shall provide an ability to make data connections between
placed devices i.e. without specifying a port connection
The solution shall provide an ability to make all connections using
drag and drop methods
The solution shall provide an ability to make all connections using
textual selection methods
All connections shall make use of previously created
connections further up the power or data tree e.g. ATS to UPS
connections will be used for all downstream connections and not recreated each time.
,

The solution shall provide an ability to search the inventory on any of


the default fields/properties
The solution shall provide an ability to search the inventory on any of
the user defined properties
The solution shall provide an ability to search the inventory on any
combination of properties
The solution shall provide an ability to manage the following
capacities for physical areas:
Power
Cooling

Description of requirements

UoM

QTY

UoM

QTY

Weight
Space
The solution shall provide an ability to manage the above
capacities for any floor plan that is added to the solution.
The solution shall provide an ability to manage the above
capacities for any space that is added to a floor plan.
The solution shall provide an ability to manage the above
capacities for any zone that is added to a space.

The solution shall provide an ability to manage the following


capacities for containers e.g. racks:
Power
Cooling
Weight
Space
The solution shall provide an ability to manage the above
capacities for any rack that is added to the solution.
The solution shall provide an ability to manage the above
capacities for any breaker panel that is added to a floor plan.
The solution shall provide an ability to manage the above
capacities for any zone that is added to a space.

The solution shall provide an ability to manage the following


capacities for groups:
Power
Cooling
Weight
Description of requirements
Space
The solution shall provide an ability to manage capacities for any
group of devices that is added to the solution.

The solution shall provide an ability to assign thresholds to each of


the capacities mentioned in this document.
The solution shall provide an ability to raise an alert when a
threshold is breached.

The solution shall provide an ability to colorize the floor plan to


show the usage of any of the container capacities specified.

The solution shall provide an ability to search a chosen floor or


space for rack capacity to accommodate a chosen device. The
results of this search shall be provided in both a textual list and a
colorization of the floor plan.

The solution shall allow the users to create projects based at some
date in the future, using drag and drop, where the project will be
comprised on tasks generated for each drag and drop action taken
by the user.
The solution shall allow the user to visualize lists of projects and a
detailed Gannt of each project showing tasks against time.

The solution shall provide a catalog of standard data center


processes
The solution shall allow the user to trigger any of these processes
and provide a set of standard input data to the process.
The solution shall have automated ticketing system that allows
install, decommission, move and rename of equipments

Description of requirements

The solution shall route any instance of a process through a standard


set of notifications, approvals and decision points as outlined in the
process.
The solution shall perform all the routing and associated actions using
an engine that is internal to the solution and shall not be reliant on an
external workflow solution.
The solution shall provide a view of all work orders recorded by the
tool, showing status, owner, planned complete date and history.

l the changes that are

The Solution shall have the ability to configure the


processes per the organization's requirements.
The solution shall show the user any device or space
that is reserved for a future use
The solution shall show the user any device or space
that is affected by a future change
The solution shall allow the user to see a chosen asset

UoM

QTY

The solution shall show the user all workflows in the


system and track their status, owner, planned
completion
date
andshow
history.
The solution
shall
the user all tasks that are due
to be
completed in a chosen day, week, month
The solution shall show the user all tasks that are to be
completed by that user.
The solution shall provide an ability to collect an
inventory of all the AC power connections between
devices or device ports.
to build a power chain tree and for any newly connected device to inherit the
that tree once a connection is made.
Description of requirements
Analysis
The solution shall provide an ability to warn the user if an attempt
is made to connect a device to a power tree that does not have
sufficient capacity
The solution shall provide an ability to build a power chain tree and
for any newly connected device to inherit the attributes and j_._pi
stream connections of that tree once a connection is made.
The solution shall provide an ability to visualize a schematic of all
the power devices in the power chain and the connections between
each device. The schematic shall have the ability to zoom into any
portion to see the details of that area.
The solution shall provide an ability to automatically generate the
schematic using any device connections previously set up by the
user.
The solution shall provide an ability to display an electrical symbol
representation of the power devices on the schematic.
The solution shall provide an ability to display real-time
performance or alarm information for each device on the
schematic, with an ability to hover over to see more details.
The solution shall provide an ability to drill into any device shown
on the schematic, using double click, to see a more detailed view
of the device and its performance.
The solution shall provide an ability to show the status of the
power connections on the schematic to indicate if a connection is
energized, active or dormant. This will be dynamic and will change
as measured data of the power chain changes.

The solution shall provide an ability to visualize a top down view of


the floor with racks colorized to show the various levels of
temperature threshold breach.
The solution shall provide an ability to display temperature values
via hover over on any temperature sensor that is placed on the
floor plan.
The solution shall provide an ability to display alarms via hover
over on any temperature sensor that is placed on the floor plan.

Customizable notification and threshold validation functions allow


users to focus on active alarms that need to be attended to immediately.

UoM
_

QTY

Manage alarm notifications via SNMP, SMS and email via userdefined rules.
Categorize and visualize data via Configure, Control, Support and
Specification tabs.
Gather data from any device in the system once alarm is triggered.
Tracking via Cold Aisle Temperature Sensors and track aisle
temperature or evaluate high room temperature events.
Configure data points for collection and assign data collection
intervals.
Side-by-side alarms through the Timeline View.
Prevent unnecessary tracking of alarms via the creation of a "to-do"
list to be attended.
Prioritize alarms based on a Summary View.

The solution shall provide an ability to monitor device generated


alarms using Modbus/IP protocols.
The solution shall provide an ability to monitor device generated
alarms using Bacnet/IP protocols.
The solution shall provide an ability to monitor device generated
alarms using SNMP protocols.
The solution shall provide an ability to monitor device generated
alarms using Velocity protocols.

The solution shall collect alarms using the protocols outlined above
through the deployment of remote data/alarm collection devices and
shall not depend on a central data/alarm collection server.

Description of requirements

The solution shall allow devices to be added to alarm groups and for
any alarm from this group to be treated as a single instance of alarm

The solution shall allow a user to visualize alarm conditions overlaid


on graphical views e.g. floor plans
The solution shall allow a user to visualize alarm conditions in a list
view or alarm viewer with associated ability filter, sort etc.
The solution shall allow for device or system conditions to be used to
be combined and used to trigger user alarms
The solution shall allow a user to view and interact with alarms from a
mobile device
The solution shall allow a user to navigate to the device using the
device on board web interface

UoM

QTY

The solution shall allow a user to navigate to the device using a DCIM
view of the attributes of the device including properties and
measurements appropriate for that type of device

The solution shall allow up to 4 thresholds to be applied to any


measured data point.
The solution shall allow for alarms to be raised whenever a threshold
is breached for a measured data point.

The solution shall allow alarms to be raised to users via email


The solution shall allow alarms to be raised to users via SMS
The solution shall allow alarms to be raised to users via SNMP trap
Description of requirements

The solution shall automatically escalate alarms to a designated person


if the first responder does not take an appropriate action to clear or
acknowledge the alarm.

The solution shall allow a user to suppress alarms on equipment that is


placed into maintenance using a maintenance mode option

It shall be possible to discover devices on a chosen IP address range or


subnet when selected by the user

It shall be possible to collect real time data from a device using the
network port of the device and supported protocols
It shall be possible to collect real time environmental data from a
device using an embedded service processor
It shall be possible to collect real time data from a device through a
network interface of a BMS or EPMS system
The solution shall provide an ability to monitor device generated
alarms using Modbus/IP protocols.
The solution shall provide an ability to monitor device generated
alarms using Bacnet/IP protocols.
The solution shall provide an ability to monitor device generated
alarms using SNMP protocols.
The solution shall provide an ability to monitor device generated
alarms using Velocity protocols.

UoM

QTY

The solution shall collect alarms using the protocols outlined above
through the deployment of remote data/alarm collection devices and
shall not depend on a central data/alarm collection server.

The solution shall provide an ability to aggregate measured data over


periods of time as specified automatically by the system or adjusted by
the user.
The solution shall allow a user to visualize measured data at a device
level

Description of requirements
The solution shall allow a user to visualize measured data at a floor
level
The solution shall allow a user to visualize measured data at an
electrical schematic level
The solution shall allow a user to view measured data when hovering
their pointer over the chosen device

The solution shall allow a user to select a device and see what other
devices are dependent on the chosen device for power.

The solution shall provide a PUE/DCiE dashboard which is


automatically generated based on the placement of IT or Facilities
devices on the floor plan
The solution shall offer the user an ability to include or exclude
devices from the PUE/DCiE calculation, over riding the automatic
selection carried out above.

The solution shall provide a dashboard showing PUE and energy costs
at a floor or sub-system level

The solution shall provide a report of Device Inventory


The solution shall provide a report of Inventory Metrics
The solution shall provide a report of Rack Inventory
The solution shall provide a report of UDP by Device
The solution shall provide a report of Alarms by Device
The solution shall provide a report of Consumed Capacity by Device
The solution shall provide a report of Data Points by Device

UoM

QTY

The solution shall provide a report of Energy Consumption by Device

Description of requirements
The solution shall provide a report of Time Sensitive Events by
Device

BCC

The solution shall provide a report of Stranded Capacity by Rack


The solution shall provide a report of Unattended Tasks
The solution shall provide a report of Task Priority
The solution shall provide a report of Task Cycle Time
The solution shall provide a report of Task Productivity
The solution shall provide a report of Tasks Time
Distribution
The solution shall provide an ability to automatically distribute
reports at a specified period via email.
The solution shall be installed on a single server cluster of one
back-end and one front end server.
The solution shall be based on a single database housed on a
server
The solution shall be capable of installation on a set of virtual
servers
The application server shall support an interface to a Network Time
Protocol server
The solution shall have a single administration area for all system
administration functions

Description of requirements

It shall be possible to collect real time data from a device using the
network port of the device and supported protocols
It shall be possible to collect real time environmental data from a
device using an embedded service processor

Processor: Quad-Core Intel Xeon, 2.6 GHz, IOM L3 Cache or


Higher
Memory: 24GB, DDR3 ECC SDRAM Memory 1333MHz or Higher
Hard Disk: 2x 1TB 7.2K RPM SATA 3.5" Hot Plug Hard Drive or
higher
Power Supply: Dual Hot Plug Power Supplier 350W
OS: Red Hat Linux Enterprise 5.9/6.4

The solution shall be built around an architecture of centralized


processing and distributed data collection appliances

UoM

QTY

The solution shall provide processing of collected data for aggregation


and alarm generation at the distributed appliances
It shall act as both the data collection engine for the DCIM platform
applications as well as the closed loop control.
Greatly reduce the complexity of deploying various hardware systems
for alerts, telemetry, environmental sensors and device access and
control.
The speed, flow control, parity and data-size are all predefined for
connectivity to standard RS-232 server consoles but can be modified
on a per-port basis.
Supports minimum 8 autosensing ports that can be used for either
service processor (SP) or serial connectivity and management.
It has an additional 32 RJ45 ports which are intended solely for SP
connectivity and management.

Description of
requirements

UoM

QTY

Set

It shall have combined Serial device or embedded console access


through a single port.
It shall support minimum 1000 data points.
It shall be able to support IPMI, SNMP, Modbus, BACnet and
Velocity.
Allow users who are authorized for rack power distribution units
(PDU) and service processor (SP) power management to turn
power on, turn power off and reset servers via their embedded SP
devices plugged into a connected rack PDU.
It shall be able to set up data logging, notifications and alarms to
alert administrators of problems with email and Syslog
messages. It shall provide remote authentication via AD and LDAP
server SSH and Telnet access, Syslog server.
It can create users and administrators that perform most tasks
through Web User Interface accessed with HTTPS via SSL and
supports Microsoft Internet Explorer, Mozil la Firefox and Google
Chrome browsers.
The appliance is supplied with dual power supplies, dual NIC ports.
The front panel LED shall be able to indicate normal operation,
failure, booting.
The rear panel LED shall be able to indicate differences between
serial connection or SP connections.
The rear panel LED shall be able to indicate differences between
serial connection or SP connections.
Installation & Commissioning charges will include appropriate and
quote for the same. If any other components are required
for finishing the raised floor, please, mention and quote for the
same.

One year full warranty (onsite covering everything with parts and
services) period including all maintenance and support for the
system from the date of commissioning and acceptance. This
support coverage document shall include 24 x 7 supports services.

Item-25: Bus Bar Trunking (BBT)


SL. #

Product

Description of requirements

Names/Items

Supply, Installation, Termination and Testing-Commissioning of


Low impedance, Low reactance, factory assembled, type tested,
totally enclosed Sandwich type, insulated Copper bus bar

Trunking System completed with Aluminum enclosure


-minimum earthing 200% of the phase conductor 1P54 for
5000A BBT Indoor & Cast resin IP68 for outdoor Installation, Trafo.
Connection Unit, Straight trunking, feed unit, Junction Unit, Tap
off unit, End Cap, fixing elements etc. all accessories as per
design, drawing, specification & direction of consultant /
Engineer in charge. It shall be made according to Standard: IEC
60439 -1/ -2. IEC 61439-1 to 6, Netform: TN-S (acc. to IEC 364
and DIN VDE 0100), with operating Voltage: < 690V / 50Hz.
The contractor shall submit Working drawing as per site
measurement & quantities in details before LC opening for
approval.

Brand: Siemens/Schneider/ Eaton/ Fujitsu or other reputed


brand
Model: To Be mentioned by bidder
Country Of Origin: To Be mentioned by bidder
Country of manufacture: To Be mentioned by bidder
Capacity: 5000A
Configuration: 3 Phase+ Neutral + grounding
The following technical specification shall be submitted with
offer and indicated in catalogue.
Rated Insulation Voltage: 1000V
Short Circuit Current:150KA for 5000A BBT
Neutral: 100%
Earthing: 200% of the phase conductor ( Enclosure)
Degree of protection-1P: 54 for Indoor and 68 for outdoor
Insulation materials: Myler/ Epoxy for Indoor & Epoxy Cast
resin for Outdoor.
Class of Insulation: B for Indoor & H for Outdoor.
Ambient temperature: 40 5C
Type of Conductor CU:

Standard:

Standard: IEC 60439-1/-2


Degree of protection: IP54 (acc. to IEC 60529)
Netform: TN-S (acc. to IEC 364 and DIN VDE 0100)
Capable to carry the nominal current at an ambient temperature
of 50C not exceeding a temperature rise of 55K on the
enclosure and not exceeding the temperature limits of all

relevant functional components and insulating materials. This


product feature is not defined ace. to the IEC regulation
IEC61439-1/-6 where is defined that the max. temperature of
the enclosure must not exceed 90C

Local materials: Not offered


Housing materials: Aluminum for Indoortyp_e_BEIT

Installation Material

a)

Feeder Bus bar Trunking system

Supplier should consider all installation necessary


accessories / Material, hanger, nut , bolt etc.
This Bus bar trunking (BBT) system will be connected
between Automatic transfer switch (ATS) panel to main
distribution board (MDB) in Data centre power room through
outdoor and indoor ducting.
Outdoor BBT distance:(Quantity shall be as per site
measurement)
Indoor BBT distance: (Quantity shall be as per site
measurement)

b)

LT side Bus bar Trunking system

This Bus bar trunking (BBT) system will connect 1)


Transformer to LT panel 2) LT panel to Automatic Transfer
Switch (ATS) Panel and 3) Generators output panel to ATS
panel
Indoor distance: (Quantity shall be as per site measurement)
Supply, Installation, Termination and Testing-Commissioning
of Low impedance, Low reactance, factory assembled, type
tested, totally enclosed Sandwich type, insulated Copper
bus bar

3200A BBT

3200A BBT

Trunking System completed with Aluminum enclosure


-minimum earthing 200% of the phase conductor 1P54 for
Indoor & Cast resin 1P68 for outdoor Installation, Trafo.
Connection Unit, Straight trunking, feed unit, Junction Unit,
Tap off unit, End Cap, fixing elements etc. all accessories as
per design, drawing, specification & direction of consultant /
Engineer in charge. It shall be made according to Standard:
IEC 60439 -1/ -2. IEC 61439-1 to 6, Netform: TN-S (act. to IEC
364 and DIN VDE 0100), with operating Voltage: < 690V /
50Hz. The contractor shall submit Working drawing as per
site measurement & quantities in details before LC opening
for approval.

Brand: Siemens/Schneider/ Eaton/ Fujitsu or other reputed


brand
Model: To Be mentioned by bidder
Country Of Origin: To be mentioned by bidder
Country of manufacture: To be mentioned by bidder
Capacity: 3200A
Configuration: 3 Phase+ Neutral + grounding
The following technical specification shall be submitted with
offer and indicated in catalogue.
Rated Insulation Voltage: 1000V
Short Circuit Current:100KA for 3200A BBT
Neutral: 100%
Earthing: 200% of the phase conductor ( Enclosure)
Page 205 of 363

Degree of protection-IP: 54 for Indoor and 68 for outdoor


Insulation materials: Myler/ Epoxy for Indoor & Epoxy Cast
resin for Outdoor.
Class of Insulation: B for Indoor & H for Outdoor.
Ambient temperature: 40 5C
Type of Conductor CU:
Standard:
Standard: 1EC 60439-1/-2
Degree of protection: IP54 (act. to IEC 60529)
Netform: TN-S (act. to IEC 364 and DIN VDE 0100)

Capable to carry the nominal current at an ambient temperature


of 50C not exceeding a temperature rise of 55K on the
enclosure and not exceeding the temperature limits of all
relevant functional components and insulating materials. This
product feature is not defined acc. to the IEC regulation
IEC61439-1/-6 where is defined that the max. temperature of
the enclosure must not exceed 90C

Local materials: Not offered


Housing materials: Aluminum for Indoor type BBT
Installation Material

Supplier should consider all installation necessary accessories /


Material, hanger, nut , bolt etc.

UPS output Feeder Bus bar

This Bus bar trunking (BBT) system will connect MDB and
UPS input
Indoor BBT distance: (Quantity shall be as per site
measurement)

2500A BBT

Supply, Installation, Termination and Testing-Commissioning of


Low impedance, Low reactance, factory assembled, type tested,
totally enclosed Sandwich type, insulated Copper bus bar
Trunking System completed with Aluminum enclosure
-minimum earthing 200% of the phase conductor 1P54 for
Indoor & Cast resin IP68 for outdoor Installation, Trafo.
Connection Unit, Straight trunking, feed unit, Junction Unit, Tap
off unit, End Cap, fixing elements etc. all accessories as per
design, drawing, specification & direction of consultant /
Engineer in charge. It shall be made according to Standard: IEC
60439 -1/ -2. IEC 61439-1 to 6, Netform: TN-S (acc. to 1EC
364 and DIN VDE 0100), with operating Voltage: < 690V /
50Hz. The contractor shall submit Working drawing as per site
measurement & quantities in details before LC opening for
approval.

Brand: Siemens/Schneider/ Eaton/ Fujitsu or other reputed


brand
Model: To Be mentioned by bidder
Country Of Origin: To Be mentioned by bidder
Country of manufacture: To Be mentioned by bidder
Capacity: 2500A
Configuration: 3 Phase+ Neutral + grounding

The following technical specification shall be submitted with


offer and indicated in catalogue.
Rated Insulation Voltage: 1000V
Short Circuit Current:100KA for 2500A BBT
Neutral: 100%
Earthing: 200% of the phase conductor ( Enclosure)
Degree of protection-IP: 54 for Indoor and 68 for outdoor
Insulation materials: Myler/ Epoxy for Indoor & Epoxy Cast
resin for Outdoor.
Class of Insulation: B for Indoor & H for Outdoor.
Ambient temperature: 40 5C
Type of Conductor CU:
Standard:
Standard: IEC 60439-1/-2
Degree of protection: IP54 (acc. to IEC 60529)
Netform: TN-S (acc. to IEC 364 and DIN VDE 0100)

capable to carry the nominal current at an ambient temperature


of 50C not exceeding a temperature rise of 55K on the
enclosure and not exceeding the temperature limits of all
relevant functional components and insulating materials. This
product feature is not defined acc. to the IEC regulation
IEC61439-1/-6 where is defined that the max. temperature of
the enclosure must not exceed 90C

Local materials: Not offered


Housing materials: Aluminum for Indoor type BBT
Tap - Off Boxes: Type tested 4 Nos 630A tap off unit with 6
meters of spacing Including 70KA, breaking capacity MCCB.
Installation Material

Supplier should consider all installation necessary accessories /


Material, hanger, nut , bolt etc.

UPS output Feeder Bus bar

This Bus bar trunking (BBT) system will connect to UPS and
will feed to distribution BBT
Indoor BBT distance: (Quantity shall be as per site
measurement)
Supply, Installation, Termination and Testing-Commissioning of
Low impedance, Low reactance, factory assembled, type tested,
totally enclosed Sandwich type, insulated Copper bus bar

4 500A BBT

Trunking System completed with Aluminum enclosure


-minimum earthing 200% of the phase conductor IP54 for
Indoor & Cast resin IP68 for outdoor Installation, Trafo.
Connection Unit, Straight trunking, feed unit, Junction
Unit, Tap off unit, End Cap, fixing elements etc. all accessories
as per design, drawing, specification & direction of consultant /
Engineer in charge. It shall be made according to Standard: IEC
60439 1/ -2. IEC 61439-1 to 6, Netform: TN-S (acc. to IEC
364 and DIN VDE 0100), with operating Voltage: < 690V /
50Hz. The contractor shall submit Working drawing as per site
measurement & quantities in details before LC opening for
approval.
-

Brand: Siemens/Schneider/ Eaton/ Fujitsu or other reputed


brand
Model: To Be mentioned by bidder

Country Of Origin: To be mentioned by the bidder


Country of manufacture: To be mentioned by the bidder
Capacity: 500A
Configuration: 3 Phase+ Neutral + grounding
The following technical specification shall be submitted with

offer and indicated in catalogue.


Rated Insulation Voltage: 1000V

-----------------

Short Circuit Current:50KA for 500A BBT


Neutral: 100%
Earthing: 200% of the phase conductor ( Enclosure)
Degree of protection-IP: 54 for Indoor and 68 for outdoor
Insulation materials: Myler/ Epoxy for Indoor & Epoxy Cast
resin for Outdoor.
Class of Insulation: B for Indoor & H for Outdoor.
Ambient temperature: 40 5C
Type of Conductor CU:
Standard: IEC 60439-1/-2
Degree of protection: 1P54 (ace. to IEC 60529)
Netform: TN-S (acc. to 1EC 364 and DIN VDE 0100)
Capable to carry the nominal current at an ambient
temperature of 50C not exceeding a temperature rise of
55K on the enclosure and not exceeding the temperature
limits of all
relevant functional components and insulating materials.
This product feature is not defined acc. to the IEC regulation

IEC61439-1/-6 where is defined that the max. temperature of


the enclosure must not exceed 90C
Local materials: Not offered
Housing materials: Aluminum for Indoor type BBT
Tap - Off Boxes: Type tested 40 Nos 63A tap off unit with
spacing of 0.6 meter Including 10KA, breaking capacity MCB.
Each tap off unit should consist of minimum 2 nos 63A
single/ 2 nos 32A Three phase CEE socket

Installation Material
Rack level Distribution BBT

Supplier should consider all installation necessary


accessories / Material, hanger, nut , bolt etc.
This BBT will connect to UPS feeder BBT and feed to rack
strip
Indoor distance: (Quantity shall be as per site measurement)

Warranty

One year full warranty (onsite covering everything with parts


and services) period including all maintenance and support
for the system from the date of commissioning and
acceptance. This warranty coverage document shall include
24 x 7 supports and maintenance services.

UoM

QTY

Mtr

180

Mtr

120

Mtr

120

Mtr

80

Nos

Mtr

100

Nos

300

Mtr

200

Item-26: Surge Protection Device (SPD)


SL. #
1

Product Names/Items
Surge Protection Device (SPD) / TVSS
Model
Brand
Country of Origin
Country of manufacture
Capacity
Nominal Operating Voltage / Phase Configuration
Operating Voltage Range
Operating Frequency Range
Fault Current Rating

General

Standards

System Description:

Maximum Continuous Operating Voltage (MCOV)

Life Cycle Testing

Over current Protection:

Surge Current Capacity

Noise Attenuation:

Protection Modes:
ANSI/UL 1449 Nominal Discharge Current:

Quality Assurance
Environmental Requirements

Connections

Internal Connections and Serviceability

Standard Features

Capacity
Enclosure Rating
Weight
Status Indication
Response Time
Operating Humidity

3 Warranty

Description of requirements
TVSS/SPD Type 1
-

To be mentioned by bidder
Must be a globally reputed brand that needs to be mentioned by the bidder
To be mentioned by bidder
To be mentioned by bidder
250KA
277/480VAC, Three Phase Wye, 4 Wire + Gnd
277 VAC +/- 15%
47 - 63 Hz
250kAIC
These specifications describe the electrical and mechanical requirements
for a modular, high-energy surge protective device (SPD). The specified
system shall provide effective, high-energy surge current diversion and be
suitable for use as Type 1, 20kA device per ANSI/UL 1449 Third Edition.
The specified system shall be designed, manufactured, tested and installed
in compliance with the following codes and standards:

Underwriters Laboratories; ANSI/UL 1449 Third Edition Underwriters


Laboratories; UL 1283 (complimentary listing for Type 2 locations);
Canadian Underwriters Laboratories (CUL); American National Standards
Institute and Institute of Electrical and Electronic Engineers (ANSI/IEEE
C62.34, C62.41, C62.45); Institute of Electrical and Electronic Engineers
1100 Emerald Book; Federal Information Processing Standards Publication
94 (FIPS PUB 94); National Fire Protection Association (NFPA 20, 70, 75 and
780); International Standards Organization (ISO) Company certified ISO
9001:2000 for Manufacturer's, design and service. The system shall be UL
listed and labeled under ANSI/UL 1449 Third Edition and the voltage
protection ratings (VPRs) shall be permanently affixed to the SPD. The
product shall also be CE marked and CUL listed. Type 2 units of the product
family shall be listed and labeled to UL1283 Standard for Electromagnetic
Interference Filters.

The system shall be constructed using single or multiple surge current


diversion modules utilizing Metal Oxide Varistor (MOV) computer matched to
a variance of 1 volt and tested for Manufacturer's defects. The modules shall
be designed and constructed in a manner that ensures surge current sharing.
Use of gas tubes, silicon avalanche diodes or selenium cells are unacceptable
unless documentation from a nationally recognized laboratory demonstrates
current sharing of all dissimilar components at all surge current levels.
The SPD and all components in the suppression path (including all current
diversion components) maximum continuous operating voltage (MCOV) shall
be greater than 115% of the nominal system operating voltage to ensure the
ability of the system to withstand temporary RMS over-voltage (swell
conditions).
The SPD shall be duty life cycle tested to withstand l0kA (8x20ms), 20kV
(1.2x50 4s), IEEE C62.41 Category C surge current with less than 5%
degradation of clamping
voltage. The minimum numbers of surges the unit shall be able to protect
against are:

UoM
set

QTY
8

24000 of Cycle Surges Life Cycle Surges per Mode


24000 of Cycle Surges Life Cycle Surges per Phase

Fusing: All suppression components shall be individually fused and rated to


allow maximum specified surge current capacity. Devices that utilize a single
fuse to protect two or more suppression paths are not accepted. Individual
surge components shall be sand packed and shall be UL listed to be capable of
interrupting up to 200 kA symmetrical fault current with 480 VAC applied.
Replaceable fusing is unacceptable. Over current protection that limits
specified surge currents is not acceptable.

250 kA Surge Rating per Mode 250kA Surge Rating per Phase
The filter shall provide an attenuation of 63 db max from 10 kHz to 100MHz,
per 50 Ohm Insertion Loss Methodology from MIL 220A. The system shall
provide up to 120-dB insertion loss from 100 kHz to 100 MHz when used in a
coordinated facility system.
The SPD shall provide protection as follows: All modes, L-N or L-L, L-G and
N-G (where applicable). Note: L = Line, G = Ground, N = Neutral
The ANSI/UL 1449 Nominal Discharge Current Rating shall be a minimum of
20kA.
The Manufacturer's shall be ISO 9001:2000 certified. The Manufacturer's shall
have been engaged in the design and Manufacturer's of such products for a
minimum of 20 years.
Storage Temperature: -55 to +85C (-67 to +I85F)
Operating Temperature: -40 to +60C (-40 to +140F)
Relative Humidity: 0% to 95% (non-condensing)
Audible Noise: less than 45dB at 5 feet (1.5m)
Operating Altitude: 0 to 18,000 feet above sea level
The terminals shall be provided to accommodate wire sizes up to # 2 AWG.

The system shall be designed for simple change out of any or all SPD modules
by a qualified electrician. Designs that require factory service are not
acceptable. All connections, conductors and terminals must be appropriately
sized for specified surge current capacity.

Unit Testing CapabilityThe SPD monitoring circuitry must continually verify


the protection status during operation and display this information on the front
cover status panel. The integrity of all fuses must be indicated on the status
panel.
Unit Status IndicatorsSPD shall be equipped with red and green solid state
indicators for each internal surge module. Indicators must be mounted within
the enclosure but must be externally visible.
Dry Contacts for Remote MonitoringSPD must have electrically isolated
Form C dry contacts, one normally open and one normally closed.
Under voltage DetectionSPD shall bg-ecritipliedzwith 70%

under voltage detection.


Phase Loss MonitoringSPD shall be equipped with phase loss monitoring.
Power Loss MonitoringSPD shall be equipped with power loss monitoring.

Audible alarmThe specified system shall be equipped with an audible alarm


that is activated during a fault condition. In conjunction with alarm, an alarm
on/off switch shall be provided to silence the alarm, and an alarm push-to-test
switch shall be provided to test the alarm's function. A visible LED will
confirm whether alarm is on or disabled. Both switches shall be located on the
unit's hinged front cover.

Continuous (Parallel Connection)


NEMA 12
Specify by the bidder
LEDs, Dry Contacts, Audible Alarm
<0.5 ns
0% to 95% non-condensing
Full five year warranty from date of shipment against any part failure when
installed in compliance with Manufacturer's written instructions, UL listing
requirements, and any applicable national or local electrical codes.
Manufacturer shall make available (local, national) field engineering service
support.

Item 27. Double Conversion Online UPS


L. #

Product
Names/Items

Guideline

Brand
Model
Country of origin
Manufacturing Country

Scope and type of contract

Relevant European Directives and reference


standards

Safety Standard:

Electromagnetic Compatibility Standard


(EMC):

Performance Standard

Description of supply

Design Specifications

Rectifier

Booster /
converter)

Battery

1GBT Inverter

charger

(DC/DC

Symmetrical Power Factor Output Diagram

Power Interface / Static bypass switch

Batteries

Operating modes

Double Conversion operation (VFI)

Digital Interactive mode (VD)

Page 219 of 363

M
Interactive mode (VI)

Maintenance

Controls and diagnostics

Modularity

i)Internal parallel ability

ii) System parallel ability

Controls, measurements,

signals and alarms.

Measurements

_ Signals and alarms

Remote diagnostics

Monitoring and control from service centre

Uninterruptible Power System (UPS) Technical Data


i) Input characteristics
Nominal voltage
Tolerance on voltage
Tolerance on voltage with output de-rated
Nominal frequency (60 Hz selectable)
Tolerance on frequency
Input power factor (u, nominal voltage
Total harmonic distortion (THDi)@ full load
ii)Inverter output characteristics

Nominal voltage (380/415 selectable)


Nominal frequency (60 Hz selectable)
Nominal power @ 40C
Output Power Factor
Automatic adjustment of nominal output
power as a function of temperature

Output voltage
stability in steady-state condition for input
within permitted limits and load variations
from 0 to 100%
Stability in dynamic conditions for 100%
load step variations
Load crest factor without derating
Output voltage distortion with 100% linear
load
Output voltage distortion with nonlinear
load as
specified by IEC/EN 62040-3
Output frequency stability in
synchronization with mains
Output frequency stability with internal
oscillator
Frequency slew rate

Permitted overload: For 10 minutes For 60


seconds
Short circuit current: 3 x In
1.5 x In
Characteristics of electronic static
changeover switch
Nominal voltage (380/415 selectable)

Tolerance on voltage ( 5 , + 15 selectable)


Nominal frequency (60 Hz selectable)
Tolerance on frequency ( 0.2 , 6
Permitted overload: -for 10 minutes -for
1 minute
UPS characteristics
Maximum power module dimensions (W x H
x D)
I/O BOX cabinet dimensions
(1600kVA) (W x H x D)
Noise level measured g 1 meter and g

100% load according to ISO 3746


EMC compatibility as per EN 62040-2
Degree of protection
Color of the frame
Efficiency Data
The overall efficiency (Double Conversion
mode) shall not be
less than the figures shown in below:
100% Load 75% Load 50% Load 25% Load
The overall efficiency (Digital Interactive
Mode) shall not be
less than the figures shown in below:
100% Load 75% Load 50% Load 25% Load

The overall efficiency (Interactive Mode VI)


shall not be less than the figures shown in
below:
100% Load 75% Load 50% Load 25% Load

Page 224 of 363

ENVIRONMENTAL CONDITIONS

Miscellaneous provisions

Documentation

Spare parts

Warranty

Installation & Commissioning

Item 27. Double Conversion Online UPS


Description of requirements

UoM

QTY

Supply, installation, testing & commission of 800KVA


400ACV, 3-phase, 50Hz. UPS (Integrated with Single Mode Set
operation), 30 Minutes battery backup power with output power factor
(PF) 0.9 at full (100 %) load.
Emerson/ Schneider/ ABB or other equivalent globally reputed brand
To be mentioned by the bidder
To be mentioned by the bidder
To be mentioned by the bidder
The present special contract specifications constitute a call for best
offers for the supply of:
no X Uninterruptible Power System (hereinafter referred to as UPS)
rated at 1600 kVA.

This specification describes a continuously rated, solid state


Uninterruptible Power Supply (UPS) with three dimensions of
modularity. The UPS utilizes a double conversion, transformer free
topology combined with Tri mode technology, whereby the output
power supplied is derived directly from the UPS without the need for
an internal step-up output transformer. The UPS will be used to operate
in conjunction with the existing building supplies and shall provide
high quality power distribution for critical loads.

Any deviations or exceptions to the minimum requirements must


appear in the offer. Where no exceptions are shown, the requirements
of the present specifications will be considered as accurate.

The product shall have the CE marking for compliance with the
following European directives:
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
The Manufacturer's shall demonstrate conformity with the UPS
harmonized standards and directives EN 62040-1-2 (Safety) and EN
62040-2 (EMC).

The UPS shall be designed in accordance with the applicable sections


of the current revision of the standards shown in the table below.
Where a conflict arises between these documents and statements made
herein, the statements in this specification shall govern.

EN 62040-1-2:2003
EN 60950-1:2001/A11:2004
EN 62040-2:2005 EN 61000-3-2:2000
EN61000-3-3:1995/A1:2001
EN61000-6-2:2001
EN61000-6-4:2001
EN 62040-3:2001

Regarding the EMC requirements, the UPS Manufacturer's will be able


to provide a copy of the test results certificate for the relevant standard
as released by an independent EMC laboratory (certified by the TUV)
stating the compliance of a sample unit, of the same type and rating as
the UPS specified in this contract. Upon request, the UPS
Manufacturer's will be able to show the complete original EMC test
report, carried out in its on-site R&D department, which will be
archived in the Type Tests File.

The purpose of the following specification is to define minimum


design, construction and testing criteria relating to the supply of
Uninterruptible Power Systems

The UPS system shall consist of a comprehensive modular solution


made up of a single UPS module or the appropriate number of UPS
modules connected in parallel for operation in capacity or N+1
redundancy mode. The UPS modules shall be connected to a central 1/0
Box within a fully enclosed, freestanding system cabinet which shall
contain automatic parallel connection terminals, communication cables,
input/output power terminals and switches and an integral wrap around
maintenance bypass switch.

Parallel configurations shall be designed to allow each UPS module to


work autonomously and incorporate individual active components such
as Power Converters (rectifier, booster, and inverter), Static Bypass
Switches, and CPU's and separate battery sets so as to eliminate single
points of failure in the system. All UPS modules must operate
simultaneously and equally share the load without utilizing a
centralized static bypass switch or system control module.

The UPS must be scalable up to 1600 kW and allow for the addition of
up to eight core modules to be placed side by side and/or around the
I/O Box (input/output power section).
Each power module will consist of the following major
components: PFC Rectifier & Booster with IGBT

IGBT Battery Charger


IGBT Inverter
Dedicated Digital Signal Processor (DSP) control

Embedded controller for I/O interfaces

Power Interface with electronic static switch and bypass


supply
Switches for input mains, UPS output and static
bypass
input.
The full IGBT Rectifier/Battery charger will have an input isolating
switch and a PWM digital vector control system (DSP based) which,
in addition to normal functions (AC/DC conversion), will
automatically correct the input power factor to a value > 0.99 and
limit the harmonic rejection to the mains at a THDi value < 3% at
full output load.
A bidirectional DC/DC converter (booster/battery charger) will
perform the following functions:

To recharge the batteries taking the power


from the DC BUS when the main is present;

To provide the suitable full DC power taken from the batteries


to the IGBT output inverter if the primary mains is not available.
For the battery charger function, this converter will include built-in
fuses and a control circuit for the voltage and battery recharging
current. The ripple current to the batteries will be less than 0.01
C10. A microprocessor control function will perform the following
operations:

Test the battery by automatically performing a partial battery


discharge at weekly intervals or at intervals defined by the user
Adjust battery float voltage as a function of ambient
temperature
Calculate the remaining battery autonomy time during discharge
Automatically compensate battery shutdown voltage as a function
of the time for prolonged discharges

From the DC voltage of the intermediate circuit the inverter will


generate sinusoidal AC voltage for the user load on the basis of
Pulse-Width Modulation (PWM). By means of the Digital Signal
Processor (DSP) of the control unit, the IGBT of the inverter will be
controlled so that DC voltage is divided into pulsed voltage packets.
A low-pass filter pulse-width modulated signal will be converted into
sinusoidal AC voltage. No isolation transformer is needed for the
IGBT inverter, which provides attractive advantages in terms of
energy conservation and efficiency as well as reducing the physical
size and weight of the modules.

The control circuit, in addition to normal functions, will


automatically adjust nominal output power in accordance with
ambient temperature.

The full IGBT inverter is able to supply all types of loads with a Power
Factor up to 1. All types of leading and lagging loads can be supplied
without derating. This is achieved thanks to the perfect dimensioning of
all components of the output stage, which allows for a Power Factor
output diagram perfectly symmetrical respect to zero. This unique
feature allows the UPS to achieve maximum flexibility and
compatibility with each installation and alleviates any foreseen
difficulty relating to future modifications of loads with different Power
Factors

The power interface including the static bypass switch will feature a
separate power input and will consist of the following:

An input choke for sags and transient filtering when working


in direct line
Static switches (SCR type), which can support overloads and short
circuits downstream of the UPS

A back feed detection circuit as specified by IEC/EN 62040-11, clause 5.1.4


A bypass input isolating switch with auxiliary indicator contact
An output load switch
The control logic will be managed by digital algorithms (using vector
control techniques), similar to those used for the rectifier and the
inverter. The static bypass will be equipped with a back feed protection
device compliant with clause 5.1.4 of IEC/EN 62040-1-1; and a relay
signal contact, for the control of the external back feed isolator will
also be made available.

The battery system shall be sized to support a connected load of 800


kVA at load PF of 0.9 lag for a minimum of 15 minutes at an ambient
temperature of 25 C.
The battery system shall consist of gas recombination valve regulated
lead acid cells (VRLA), compliant with BS6290 Part 4 and BS
EN6089-2.

To provide full redundancy, both for the UPS and batteries, the UPS
shall be able to connect batteries to each power module. At the same
time it shall be possible to have centralized battery connection in the
event that redundancy is not required thus simplifying the installation
and reducing costs.

The batteries shall be housed on open or cladding steel racks with an


epoxy powder-coated finish. Racks shall have adjustable feet for
leveling and shall be adequately designed to support the weight of the
batteries, allowing ease of access for maintenance and/or repair of the
batteries. If the battery system is positioned on open stands then all
individual battery cell terminals shall be fully shrouded to prevent
inadvertent contact

The UPS D.0 bus voltage shall be variable whereby the number of cells
can range from 240 to 300 allowing the battery blocks to be adjusted
between 40 and 50 (12 Vdc blocks) or 80 and 100 (6 Vdc blocks) to
enable the battery system to be optimized in
terms of size and cost.

This section describes the different operating modes of the


Uninterruptible Power System The UPS module shall be designed to
incorporate the three industry standard configurations in order to
accomplish the highest efficiency and effectiveness while maintaining
first class performance and power protection to the load. The system
shall

be a Voltage and Frequency Independent (VFI-SS-111) system where


the UPS output is independent of supply
(utility/generator) voltage variations, and by which frequency variations
are controlled within EN 62040-3:2001 limits.

The IGBT inverter will be synchronized with the bypass line so that the
load can be transferred from the inverter (conditioned line) to the
bypass supply (direct line) and vice versa without any break in the
supply to the load. In all operating modes, the battery charger will
provide the power necessary to keep the battery fully charged.

In this operating mode, under normal service conditions, the load will
always be supplied by the inverter, guaranteeing maximum protection.

Upon failure or primary AC source out of tolerance limits, the load will
be supplied by the battery via the inverter. In this phase, power will be
drawn from the battery. Visible and audible signals will alert the user to
this operating state. The remaining autonomy time will be calculated by
a diagnostic algorithm. Upon return of the primary AC source, to within
tolerance limits, the Uninterruptible Power System will recommence
operating in normal double conversion mode.

UPS also should have capability to operate in cyclic mode when


operating in VFI double conversion operation. At lesser loads, it should
ensure automatically switch off of UPS cores in such way that the
running cores are sufficient to feed the loads at that time. This feature
should ensure that UPS is operating at best possible loading condition

In this operating mode, under normal service conditions, the load will
always be supplied by the direct line via the power interface. The
quality of the direct line will be constantly monitored using algorithms
operated in real time by the DSP control system. If the direct line is
outside the permitted tolerances, in the case of small conditioning
required by the load, the UPS will operate in Interactive mode. In the
event of voltages outside the permitted tolerances the UPS will
instantaneously activate the Double Conversion mode. When the
quality and reliability of the direct line returns within permitted limits,
the UPS will automatically start supplying the load via the direct line.

When the quality of the network is within tolerances but there is need
for load conditioning the UPS will operate in Interactive mode. While
working in this operating mode the UPS will compensate only the main
disturbances such as the load THDi, the load Power Factor and main
sags and swells. The energy used will be derived from the use of the
inverter as an active filter giving all the necessary reactive power.

The power module will be equipped with input, output, neutral and
battery switches permitting it, where necessary, to completely isolate a
particular module while the other power modules will continue to
protect the load in normal double conversion mode.

A system bypass switch will be available for adding or removing power


modules and for maintenance of the entire system. In this situation, the
supply to the load will be maintained. However, an external system
bypass is always recommended.

The controls for the electronic power supply modules are distributed in
each power module thus avoiding the possibility of any single point of
failure. Each power module will feature a digital vector control based
on a DSP (Digital Signal Processor). The special DSP algorithm is
designed to ensure the rapid and flexible processing of the detected
data, allowing rapid generation of the controlled variables. The
electronic inverter is driven by these algorithms in real time to:

Improve short-circuit behavior (3x In for 10 ms, 1,5x In up


to 5 s)
Have a synchronized (precise phase) angle between UPS output and
bypass network, in the event of mains voltage distortion
Highly flexible parallel operation and perfect load sharing between all
the power modules in the system

Redundant operation: The UPS unit shall operate in an N+n internal


configuration where N is the number of modules connected in parallel
to support the load and n is the number of modules connected in
parallel to provide the required redundancy. In the event of a
malfunction of one of the UPS modules the particular module affected
will be automatically isolated from the system and the remaining UPS
modules shall continue to support the load. The maximum power that
will be provided in a redundant configuration for one single system will
be 1.4MW.

Full load parallel operation: Capacity (non-redundant) unit. All UPS


modules connected in parallel are required to supply the full rated load.
If a UPS module should malfunction, the load is to be transferred
automatically, and simultaneously, to the bypass line via each of the
UPS internal static bypass switches. The maximum power provided by
one single system will be 1.6MW.

Each UPS system shall operate in system N+n parallel configuration


where N is the number of UPS units connected in parallel to support
the load and n is the number of UPS units connected in parallel to
provide the redundancy required

Up to eight units can be connected in parallel reaching a maximum


power of 9.6MW. The communication of the parallel units shall be set
up via a loop bus connection, hence avoiding any single point of
failure. The parallel UPS units shall be capable of operation with a
separate DC supply for each UPS unit. The batteries should be
configured so that in the event of a failure of one battery set the
specified autonomy at full load is maintained.

In the event of a malfunction of one of the UPS units, the particular


UPS unit affected will be automatically isolated from the entire system
and the remaining UPS units shall continue to support the load.
Replacement or repair of a UPS module shall be achieved on line,
without risk to personnel, and without disturbance or risk to the
connected load

The Uninterruptible Power System will feature an LCD a touch screen


display as part of the central I/O Box , permitting the monitoring of the
status of the entire system and displaying the measurements of each of
the power modules. The touch screen will also provide integrated
SNMP capability.

Simultaneously, this display shall also geographically illustrate the


status of each single internal functional block, the power flow and the
output load percentage, all in real time
The UPS shall provide the measurements (voltage, current and
frequency) for each single internal functional block and this
information will be directly accessible via the display
The UPS must provide signals and alarms for every single functional
block. These signals must be directly accessible via the display
The UPS touch screen display will also:
Clearly display, upon mains failure, the remaining battery autonomy
which will be a function of battery status and charge (discharge curve,
degradation, operating temperature, etc)
Have serial and LAN connection ports for compatibility
and communication with special peripheral units and remote
connections
Be able to support remote graphic measurement and signaling software
Be able to interface with a network monitoring system using SNMP
slot-in cards
Provide remote diagnostics (see description under section 6.0 "Remote
diagnostics")

A voltage-free input will also be provided to disable the static switches


and all power converters (EPO) in case of emergency. Programmable
I/O contacts (at least 6sixvoltage-free outputs and four input).

This section defines the system requirements for remote monitoring,


diagnosis and control from the Service Centre
The system will be capable of analyzing the UPS operation and
electrical supply in order to identify faults and thus prevent the
occurrence of conditions that are likely to damage the equipment that is
being protected by the UPS.

The system will guarantee single or parallel UPS surveillance, 24 hours


a day, 365 days a year, by authorized technical personnel operating
remotely. The system will provide a detailed, preventive analysis of the
connected UPS, without any of the disturbances associated with an onsite visit.

The remote diagnostic system will offer the following main features:
Continuous monitoring and control of the performance of end-user
UPS
Bi-directional communications between end-user UPS, Authorized
Service Centre and its authorized field service engineers
Automatic call out of service engineers in the event of anomalous UPS
functioning (even at night and during public holidays)
Possibility of using graphic software for remote in-depth analysis and
control
Periodic reports on UPS performance with advice from service centre
engineers
(UPS) Technical Data
400V, 30 + N
15%
-30%
50Hz
10%
> 0.99
< 3%

400V, 30 + N
50
1600KVA
Up to unity. All lead / lag loads without de-rating of UPS
@ 25C = 110%
@ 35C = 105%
@ 40C = 100%

1%

Complies with IEC/EN 62040-3, VFI-SS-111


3:01
< 1%
< 3%
6 %(adjustable between 0,2 to 6)
0.1%
< 1 HziSec

125%
150%
10ms 5Sec

400V

10%
50Hz
selectable) +6% (adjustable between 0,2 to +6)
125%
150%

To be mentioned by bidder
To be mentioned by bidder

< 68-75 dBA

< 68-75 dBA

Class C3
IP 20
RAL7021

95.2% 95.5% 95.4% 94%

98.5% 98.5% 98%


97.50%

96-98% 96-98% 96-98% 95-98%

The constructional and functional characteristics of the UPS must


be in line with the state-of-the-art technology in this field. The
supplying company must be able to provide evidence that it is ISO
9001-2000 and ISO 14001 certified for design and Manufacturer's
and for the provision of services.
The UPS will be guaranteed for one year, during which time the
Supplier will provide technical assistance. The supply of spare parts
will however be guaranteed for 10 years.
The offer must include:
a draft maintenance contract providing 24 hour service with
guaranteed minimum service call response time of 4 hours
(references are required)
the addresses of all Service Centres, divided according to
geographical areas, and the number of engineers working for each
centre
indication of the main tele-monitoring installations that are in
operation.
The UPS system shall be designed to operate continuously at full
load without degradation of its reliability, operating characteristics
or service life in the following environmental conditions:

UPS ambient temperature range 0C to 40C,

Battery ambient temperature range 20C to 25C

Humidity 5 to 95% RH non-condensing

The UPS system shall be designed for operation in altitudes up to


1000 meters, without the need for derating or reduction of the
above environmental operating temperatures.

The UPS system shall be designed to limit the injection of current


harmonics in to the incoming utility supply and as such the
maximum total input current harmonic distortion should not exceed
3% THDi when the UPS system is operating at the UPS
Manufacturer's specified rating.
This section defines the details of services, activities and means
necessary to complete the supply of the Uninterruptible Power
System.
All technical documents issued by the Supplier, in particular the
user handbook and the installation, maintenance and
troubleshooting guides, must be in English.
The Supplier should supply one module major item like inverter,
rectifier, static bypass etc at the time of product delivery. That will
keep at customer store room to give prompt support.

One year full warranty (onsite covering everything with parts and
services) period including all maintenance and support for the
system from the date of commissioning and acceptance. This
warranty coverage document shall include 24 x 7 support and
maintenance services from Principal shall be submitted to the
customer.

Commissioning costs will be payable by the Supplier who will be


responsible for the work carried out and the personnel involved.
Technical personnel will be trained to meet the requirements of current
work safety standards.

Set

Item-28: UTP Connectivity


Product

SL. #

Names/Items
l Cat 6A UTP Solid Cable
Brand
Country of Origin
Specifications

2 UTP Patch Panels


Brand
Country of Origin
Specifications

UTP Patch Cord


(2 Meter)
Brand
Country of Origin
Specifications

UTP Patch Cord


(3 Meter)
Brand
Country of Origin
Specifications

Cable Manager

Installation

Description of requirements
LAN Cable Category 6A UTP 4-Pair, 305m Reel Blue Color.

UoM QTY
Box

180

Each

150

Schneider/Systimax/ Panduit or other equivalent globally reputed brand


To be mentioned by the bidder
Unshielded Twisted Pair, Category 6A, TIA / EIA 568-C-2
23 AWG Annealed bare solid copper, CAT-6A U/UTP Cable, Channel optimized
to 500 MHz or more.
Must meet EIA/TIA 568-C.2 Category 6A specifications, UL Listed. Cat 6A
U/UTP Solution Zero bit error rate ETL report need
To submit. Cat 6A 4 Connector Channel Performance ETL Certificate need to be
submit to validate the cable channel performance.
Worst Case Cable Skew : 25 nanosecond/100 meters
Characteristic Impendence : 1006 0@ 1-500 MHz
Conductor Diameter 0.65 mm (nominal)
Insulation High Density polyethylene
Support for Fast Ethernet and Gigabit Ethemet,10G, IEEE 802.3/5/12,Voice,ISDN,
ATM 52 & 622 Mbps,
Broadband, TP=PMD and ITU V.21 and X.11
DC Resistance Max: 75 Ohms/1000m
Solid Cable should be compliance to RoHS.
Sheath Fire retardant PVC Compound (FRPVC) Flame Rating : 60 deg. C As per
UL 1685 CM
PAIRS Color code: Blue / White-Blue, Orange / White-Orange Green / WhiteGreen, Brown / White - Brown
Outer Sheath PVC compound Thickness Diameter 1.45 mm (nominal) Outer
diameter 9 mm (nominal)
Mutual Capacitance : 45pF/Mtr
Standard length: 305 Mtr (1000 ft.)
Loaded Patch Panel, 24-Port, Category 6A UTP, 568A/Bn.
Schneider Electronic /Systimax/ Panduit or other equivalent globally reputed brand
To be mentioned by the bidder
Type - 24-port, Unshielded Twisted Pair, Category 6A, TIA / EIA 568-C.2
Modular, PCB based andoth
Keystone type Unshielded Twisted pair, category 6A,
Page 227 of

EIA/TIA
568-C-2
363

Ern

The keystone modules are fire-retardant, molded plastic modules UL94 VO rated,
consisting of horizontal index strips for ease of re-termination.

110 IDC Termination 180 degree Punch, allowing wires between 22 26 AWG
sizes.
Meets or Exceeds EIA/TIA 568 C-2 Category 6A connecting hardware
specification.
RJ45 (8P8C) T568A/T568B color coding termination.
Cable Guide way to guide the cable on the rear side
1U size for 6/12/24 Ports and 2U for 48 Ports.
UL Listed to "ANSI/TIA/ EIA-568-C-2" specifications
Jack Panel should be RoHS Complaint.
Patch Cord Category 6A LSZH 568A 2.0m

Each

1800

Each

1800

Schneider /Systimax/ Panduit or other equivalent globally reputed brand


To be mentioned by the bidder
Type - Unshielded Twisted Pair, Category 6A, TIA / EIA 568-C.2
Patch cords shall be of multi strand copper cable with UL Listed.
Outer Jacket type: LSZH
With Matching colored snag-less, elastomeric polyolefin boot
Terminals with gold contacts, 50 micron" gold over nickel
Patch cord has a characteristic impedance of 100 +/- 3 Ohms
Patch cord has extra long boot to maintain the bend radius.
Assembled with short body RJ45 50u gold plate to minimize untwisted pair length.
Designed for high speed transmission
Improved PS -NEXT, ELFEXT and Return Loss performance. Back-ward-compatibility with all current Cat.5 products and applications.
Material : ROHS compliant

Patch Cord Category 6A LSZH 568A 3.0m


Schneider Electronic /Systimax/ Panduit or other equivalent globally reputed brand
To be mentioned by the bidder
Type Unshielded Twisted Pair, Category 6A, TIA / EIA 568-C.2
-

Patch cords shall be of multi strand copper cable with UL Listed.


Outer Jacket type: LSZH
With Matching colored snag-less, elastomeric polyolefin boot
Terminals with gold contacts, 50 micron" gold over nickel
Patch cord has a characteristic impedance of 100 +/- 3 Ohms

Patch cord has extra long boot to maintain the bend radius.
Assembled with short body RJ45 50u gold plate to minimize untwisted pair length.

Designed for high speed transmission


Improved PS -NEXT, ELFEXT and Return Loss performance.
Back-ward-compatibility with all current Cat.5 products and

applications.
Material : ROHS compliant
I RU Clipsal Cable Management Panel, Deep

Each

200

Installation, testing & commissioning

Node

2000

Page 229 of 363

IT II

.-

'ICI.r?

(II, '71 C, i .1
t

'-.
."
.-

.4.

.,-.. , HI,
F.,

( C

---- - ' -6-6 .


* - -.../e'
.-,=',
L..:-_______:...,-

Item-29: Fiber Connectivity


Product

SL. #

Names/Items
1 Fiber Cable SM
Brand
Country of Origin
Specifications

2 Fiber Cable MM
Brand
Country of Origin
Specifications

Fiber Patch Panel


3
4

24 Port MM
Fiber Patch Panel
24 Port SM

Fiber Patch Panel


5

12 Port SM

Fiber Pigtail SM

Fiber Pigtail MM

Fiber Patch Cord


SC/SC SM

Fiber Patch Cord SC/LC SM

10

Fiber Patch Cord LC/LC SM

11

Fiber Patch Cord SC/SC MM

12

Fiber Patch Cord SC/LC MM

13

Fiber Patch Cord LC/LC MM

14

Installation

Page 233 of 363

Description of requirements
12 Core Single Mode Fiber Cable Indoor 0S2
Schneider Electronic /Systimax/ Panduit or other equivalent reputed brand
To be mentioned by the bidder
Cable Type: 12- core, Single mode, 0S2, Un-armored Loose Tube (Multi-tube) Cable,
Gel Filled, LSZH
Fiber type: 09/ 125, Telcordia's GR-20 and ITU-T 652.D Compliance (0S2)
No. of cores: 12
Number of Fiber per tube: 4-Feb
Number of Loose Tubes: 1- 6
Cable Construction: BELLCORE GR 20 / IEC 794-1
Loose Tube ID/OD: 1.2/1.9 + 0.1 mm
Loose Tube material: PBT
Central Strength Member: 2.0 0.1 mm
Central Strength Member Material: FRP
Number of Fillers: 0-5
Moisture Barrier: Flooding Gel
Core Wrapping: Polyester Tape
Outer Sheath: 1.8 mm (Nominal)
Outer Sheath Type: LSZH
Number of Ripcords: 1
Rip codes Material: Polyester
Overall Cable Diameter: 9.8 + 0.5 mm
Attenuation
(6)1310nm < = 0.36 dB/Km
@1550nm < = 0.22 dB/Km
Coating / Cladding non-circularity <= 12 microns
Zero Dispersion Wavelength: 1302 - 1322 nm
Zero Dispersion Slope <= 0.092 ps / sqnm-km
Max (chromatic) dispersion:
<5.3 ps/nm-km @1270-1340 nm
<3.5 ps/nm-km Al285-1330 nm
<18 ps/nm-km @1550 nm
Polarization Mode Dispersion < 0.2 ps/ ikm
Cut-off Wavelength < 1260 nm
Mode Field Diameter: 9.2 0.4 gm (a) 1310
Core Cladding Concentricity Error < 0.8 pm
Cladding Diameter: 125 1 gm
Cladding Non-circularity < 1 %
Coating Diameter: 245 10 gm

Li o NI

QTY

Meter

5000

Coating Diameter: 245 10 gm


Tensile rating: Not less than 1000N
Maximum Crush resistance: Not less than 2000N
Operating Temperature: -10 Degree C to +70 Degree C
Storage Temperature: -20C to + 70aC
Micro bending coating CPC coating
Inner jacket: Hi@ density polyethylene
Secondary Buffer Material: Secondary Buffer Material Gel filled Loose Tube.
Min Bend: 20 X Outer Diameter
Weight: 105.0 10 kg/km
Test (Must pass): IEC794-1-E1 , IEC794-1-E2 , IEC794-1-E3 , IEC794-1-E4 , EIA455-104 , IEC794-1-E7 , IEC794-1-E10 , IEC794-1-F1 , IEC794-1-F3 and IEC794-1F5
Marking: Identification marking at regular intervals of 1 meter
Fiber Core: Raw fiber of corning. CORNING marking should be visible on the OFC
SM Fiber type: 28e+
Qualifies:
EIA/TIA 568B and ISO/IEC 11801
ICEA-640
UL-94V-0
Complies: ANS1/TIA 568.C.0
Approval: UL Listed
RoHS: RoHS Compliant
Length of cable drum: (+/-) 4000 Mtr
ISO Certification: Must have ISO 9001 and 14001 certified Manufacturer's units in
India.
Test Report: Factory Test report has to be provided for the products.
24 Core Multimode Fiber Cable Indoor 0M3
Schneider Electronic /Systimwd Panduit or other equivalent globally reputed brand
To be mentioned by the bidder
Cable Type: 24- core, Multimode mode, 0m3, Unarmored Loose Tube (Multi-tube)
Cable, Gel Filled, LSZH
Fiber type: 09/ 125, Telcordia's GR-20 and ITU-T 652.D Compliance (0M3)
No. of cores: 24
Number of Fiber per tube: 4-Feb
Number of Loose Tubes: 1- 6
Cable Construction: BELLCORE GR 20 / IEC 794-1
Loose Tube ID/OD: 1.2/1.9 + 0.1 mm
Loose Tube material: PBT
Central Strength Member: 2.0 0.1 mm

Meter

5000

Central Strength Member Material: FRP


Number of Fillers: 0-5
Moisture Barrier: Flooding Gel
Core Wrapping: Polyester Tape
Outer Sheath: 1.8 mm (Nominal)
Outer Sheath Type: LSZH
Number of Ripcords: 1
Rip codes Material: Polyester
Overall Cable Diameter: 9.8 0.5 mm
Attenuation
(a)850nm < 3.0 dB/Km
41310nm < 1.0 dB/Km
Bandwidth
@850nm >200 (62.5),>500 (50 0M2),> 1500 (50 0M3)
Ot,1310nm C1260> 500 (62.5),>500(50 0M2),> 500 (50 0M3)
Core Diameter: 50 + 2.5 pm
Zero Dispersion Wavelength: 1302 - 1322 nm
Core Cladding Concentricity Error < 1m
Cladding Diameter: 125 1 pm
Cladding Non-circularity < I %
Coating Diameter: 245 10 pm
Tensile rating: Not less than 1000N
Maximum Crush resistance: Not less than 2000N
Operating Temperature: -10 Degree C to +70 Degree C
Storage Temperature: -20C to + 70C
Micro bending coating: CPC coating
Inner jacket: High density polyethylene
Secondary Buffer Material: Secondary Buffer Material Gel filled Loose Tube.
Min Bend: 20 X Outer Diameter
Weight: 105.0 10 kg/km
Test (Must pass): IEC794-1-E1 , IEC794-1-E2 , IEC794-1-E3 , IEC794-1-E4 , EIA455-104 , IEC794-1-E7 , IEC794-1-E10 , IEC794-1-F1 , IEC794-1-F3 and IEC794-1F5
Marking: Identification marking at regular intervals of 1 meter
Fiber Core: Raw fiber of corning. CORNING marking should be visible on the OFC
Qualifies
EIA/TIA 568B and ISO/IEC 11801
ICEA-640
UL-94V-0
Complies: ANSI/TIA 568.C.0 Approval: UL Listed
RoHS: RoHS Compliant
Length of cable drum: (+1-) 4000 Mtr

ISO Certification: Must have ISO 9001 and 14001 certified Manufacturer's units in
India.
Test Report: Factory Test report has to be provided for the products.
.
Fiber Patch Panel 24 Port Loaded with SC MM Adapter Duplex
Fiber Patch Panel 24 Port Loaded with SC SM Adapter Duplex

Each

140

Each

70

.
Fiber Patch Panel 12 Port Loaded with SC SM Adapter Duplex
SC Pigtail Single Mode
SC Pigtail Multimode
.
Fiber Patch Cord SC/SC SM Duplex 3 Meter
.
Fiber Patch Cord SC/LC SM Duplex 3 Meter
.
Fiber Patch Cord LC/LC SM Duplex 3 Meter
.
Fiber Patch Cord SC/SC MM Duplex 3 Meter
.
Fiber Patch Cord SC/LC MM Duplex 3 Meter
.
Fiber Patch Cord LC/LC MM Duplex 3 Meter
Cable Laying & Splicing (10000 Mtr fiber cable and 6000 Nos Splicing)

Each

70

Each

2600

Each

3400

Each

200

Each

1000

Each

100

Each

100

Each

1500

Each

100

Lot

Item-30: Precision Air Conditioner


SL. #

Product Names/Items
1 Precision Air Conditioner
-

2 Quality Certifications

Brand
Country of Origin
Country of Manufacture
Model
3 Design Parameter:
Air flow rate
Refrigerant
Air Inlet Temperature to the PAC unit
Air Inlet Relative Humidity
Electric supply
Required fan static pressure
Ambient Temperature
Unit Configuration Type
Unit Selection Parameter:
Total Cooling Capacity (Gross)
Sensible cooling Capacity (Gross)
Sensible Heat Ratio
Type of Compressor
Compressor must be
No of refrigeration circuits
No of Outdoor Unit
No of indoor fan
Humidifier
Electric Heater
Heat Rejection Capacity of each Outdoor Unit

4 CABINET

4 CABINET

5 COOLING CIRCUITS

6 FAN SECTION

ELECTRICAL PANEL

Page 234 of 363

ELECTRIC HEATING

ELECTRIC HEATING

7 HUMIDIFIER

MICROPROCESSOR CONTROLLER

9 AIR FILTRATION

10 Safety Protections

11 Remote Communication

12 Heat Removal System

13 Warranty

14 Installation & Commissioning

Description of requirements

UoM

Direct Expansion (DX) Precision Air- Conditioner

Each

ISO Certification, CE Certifications to fulfill the requirements of the harmonized EC


Directives and EC Safety Standards (i.e., Showing EC machinery directive, EC
directive for low voltage, EC EMC directive, EC pressure equipment directive, etc.)
Schneider/Emerson/ Stulz/ Uniflare/ Emicon/Air-dale or other equivalent globally
reputed brand
To be mentioned by the bidder
To be mentioned by the bidder
To be mentioned by the bidder
27000 CMH
R410A
24 deg C
50%
3 phase, 50Hz
Minimum 20 Pa or higher
40 deg C
Down flow up Smart Aisle
135 KW
135 KW
1
Tandem Digital Compressor ,./.. /;/;;;X
1

Double
2
2
2
Required
Required
Minimum 80 KW or Higher
The cabinet is manufactured from galvanized steel sheet, externally painted with
Black 7021 color epoxy-polyester powder paint and assembled using stainless steel
screws and high tensile rivets.

The front and rear panels are double-skinned, with 10mm Class '0' (Al EU) fireproof
insulation sandwiched between the skins to reduce noise emission and heat loss. The
side panels are removable and insulated with 10mm Class '0' (Al EU) fireproof
insulation with aluminum foil to form a complete double-skinned cabinet.

QTY
6

The front access panel(s) are hinged and secured by means of a lever catch

Double refrigeration circuit, incorporating high efficiency, fully hermetic tandem


Digital compressor with crankcase heater with outlet service valve, safety valve, filter
drier, moisture indicating sight glass, liquid line solenoid valve and an externally
equalized thermostatic expansion valve. Compressor should be equipped with pre-set
high and low pressure switches for protection against high condensing and low
evaporating temperatures. The low pressure switch features an automatic reset whilst
to avoid compressor cycling at high discharge pressures, the high pressure switch is
equipped with a manual reset.

The inclined evaporator coil is manufactured from copper tubes and aluminum fins,
with a stainless steel condensate drain pan. The large face area/low velocity coil
allows precise control of temperature and humidity during cooling and
dehumidification, and is designed to optimize fluid velocity and minimize pressure
drop. The moisture indicating sight glass, liquid line solenoid valve and thermostatic
expansion valve for the circuit should be mounted in a service compartment, isolated
from the air stream, to allow checking and adjustment while the unit is in operation

The unit should be fitted with two direct-driven, highly efficient, single inlets,
backward curved, centrifugal 'plug' type fan with aluminum nozzle and impeller. The
fan motor is three-phase, 4-pole, IP54, with internal thermal protection. The fan motor
is Electronically Commutated, 1P54, with internal protections, continuous speed
regulation via controller signal. Fan impeller should be statically and dynamically
balanced and equipped with self lubricating bearings.

The electrical panel, located at the front of the unit in a compartment isolated from the
airflow, contains the MCB's, contactors, transformers, controller PCB, overload relays
etc. Each high voltage system component is provided with an MCB over-current
protective device. All high voltage components are touch protected by means of a
plastic cover. Electrical power supply is 400V (10%)/3Ph/50Hz +N +E and are fitted
with a mains isolator, mechanically interlocked with the electrical panel cover.

The heating resistors are of a rigid design for extended operational life and are
normally utilized to maintain room dry-bulb conditions during a system call for
dehumidification. The low Watt-density, electrically enclosed elements are made of
finned aluminum, reducing sheath temperatures and eliminating ionization. Heating
control is of the ON-OFF type. The heaters are phase balanced and are provided with
a

manual reset safety thermostat to disable them in the event of a high temperature. The
heating system also incorporates Miniature Circuit Breaker which protects the heater
from short circuits, should the harness be damaged accidentally.

The unit is fitted with a humidifier suitable for use with water of varying degrees of
hardness, treated or de-mineralized water is also applicable. The humidifier is
complete with a water inlet valve, water outlet valve and a maximum water level
sensor.
Steam from the tray/cylinder is mixed with the discharge air from the evaporating coil
by means of a copper steam distributor. Humidification control may be of the
proportional or of the on-off type, according to the requirements of the installation:
on/off is set as standard.

The Control System is microprocessor based, 32 bit RISC. It can be programmed


to control the function of every device within the unit via I/O.
An external on/off switch is fitted, incorporating a 3-colour LED, indicating the
unit status 'Power on' (Orange), 'Standby' (Flashing green), 'Unit on' (Green) or
'Warning/Alarm activated' (Red)
The controller allows setting and monitoring of the following room parameters via
a 3 button keypad:
Air Temperature
Temperature set-point
Temperature band

Humidity

Humidity set-point

Humidity band

The parameters are indicated using symbols and text on a back-lit, 3 digit Liquid
Crystal Display.
The control provides with the following functions: unit to unit Ethernet connection
to operate with multiple units, run/standby rotation, automatic changeover and
parameter sharing functions, external communications through BMS or other
monitoring solution, sequential auto restart timer, with adjustable time delays to
be applied to unit restart after a power loss.
The following warnings / alarms should be included:
High & low temperature
High & low relative humidity
Humidifier failure
Fan failure
Compressor Low & high Pressure trip

Electrical heater high temperature (When applicable)

Sensor failure

Controller errors

Terminals are provided for remote start/stop control plus Volt-free 'Common
Alarm' and 'Unit Run' indication.
The filter cells should be made of pleated synthetic fiber in a Steel frame and are
designed to minimize the air pressure drop while maintaining maximum filter
efficiency. They are easily accessed /replaced by opening the front panel. The
rated efficiency should be F5, in compliance with EN 779 standards

The unit shall also incorporate the following protections:


Single phasing preventers.
Reverse phasing
Phase misbalancing
Phase failure

Overload tripping (MCB) of all components

High pressure trip Manual reset for each compressor


-

Low pressure trip- Manual reset for each compressor.

Each of the unit should be fitted with SNMP card for remote monitoring.
Additionally it should be capable to connect dry contact output signal in case of
any alarm generation.
The outdoor unit shall comprise of high capacity Condenser fan with variable
speed motor and high size coil designed for 40 deg C ambient and heat rejection
of more than 80 KW per condenser.

One year full warranty (onsite covering everything with parts and services) period
including all maintenance and support for the system from the date of commissioning
and acceptance.
This warranty coverage document shall include 24 x 7 supports and maintenance
services from Principal shall submit to customer.
Installation, testing and commissioning with necessary accessories

Each

Item-31: Static Transfer Switch


SL. #

Product Names/Items
General
1 Static Transfer Switch (STS)
Model
Brand
Country of Origin
Manufacturing Country
Capacity

Input
Input Connectors
1EC309 x 2
Rated Voltage
220 /230VAC
Rated Frequency
50 / 60Hz
Voltage Range
150 to 300VAC
Frequency Range
Voltage Distortion

Output
Output Connectors
Power Factor
Overload Capacity
Efficiency

Transfer
Number of Poles
Automatic Transfer

Environmental Parameters
Operating temperature
0 to 40C
Storage temperature
-40 to 70C
Relative humidity
Elevation

Mechanical Parameters
Dimension H x W x D (mm)
Net weight of standard Equipment
Gross weight with options

Page 238 of 363

Description of requirements UoM


Single phase static transfer switch (STS) for the single feed device like
network switch, router etc. These STS will be mount in the network racks
No
To be mentioned by bidder
Emerson/ Schneider/ Eaton or other equivalent globally reputed brand
To be mentioned by bidder
To be mentioned by bidder
32 A

1
50 / 60Hz 5Hz
5
< 10%

C13 x 4+ C19 x 4
0.8 to 1 lead or lag
125% for 30 minutes
99%

2 poles
Interval < 6ms typical, < 11 ms max

5 to 95%; no condensation
3000 m

85 x 430 x 250; 2U Size


To be mentioned by bidder
To be mentioned by bidder

Item-32 - Rack & Containment Solution


Product

SL. #

Names/Items

Server Rack 600x1000mm

Brand
Country of Origin

3
4
5
6
7
8
10
12
Network Rack 800x1000mm

Brand
Country Of Origin

4
5
6
7
8
10

12

lx contained cold aisle w1200, 24x rack w600 + 6x rack w800; 2x sliding door

Brand
Country Of Origin
1
2
3

4
5

Description of requirements

UoM

QTY

Type: Ri7, Width: 600 mm, Height: 42U (1978 mm), Depth: 1000 mm, Extrusions: L type of extrusions, Front Door: perforated door, perforation rate 86%, Front Door Lock:
swivel handle, universal key EK 333, Rear Door/Panel: perforated door, perforation rate
86% , Rear Door/Panel Lock: swivel handle, universal key EK 333, Side Panels: 2 side
panels, sheet steel, universal key, IP Rating: 1P20, Plates: Standard top and bottom plate
(fixed), Load Rating: 1000 kg

Each

24

Frame for separation of 150mm cold zone in front of 19" profiles, for ROF 42RU, width
600mm

Each

24

Each

24

cable entry, two layers of brushes, suitable for ROF (opening 300x100mm)

Each

24

19" blank panel 1U - Quick assembly

Each

150

19" blank panel 2U - Quick assembly

Each

50

19" blank panel 3U - Quick assembly

Each

50

19" blank panel 5U - Quick assembly

Each

24

Basic PDU, plug IEC 309 3m, Outlet 1 - 20xC13, Outlet 2 - 4xC19, power rating 63A

Each

48

Brackets for mounting of vertical power distribution unit DP-RP-20-xx into ROF frame

Each

48

Each

16

Each

16

Each

16

Emerson/ Schneider/ Rittal/ Conteg or other equivalent globally reputed brand


To be mentioned by the bidder

connecting kit for installing racks SEVEN, OPTIMAL, PREMIUM series in blocks - with

installed side panels

Emerson/ Schneider/ Rittal/ Conteg or other equivalent globally reputed brand


To be mentioned by the bidder
Type: Ri7, Width: 800 mm, Height: 42U (1978 mm), Depth: 1000 mm,
Extrusions: P-profile with up to 3 x1U additional 19" vertical positions per

extrusion, Front Door: perforated door, perforation rate 86% , Front Door Lock: swivel
handle, universal key EK 333, Rear Door/Panel: perforated door, perforation rate 86%,
Rear Door/Panel Lock: swivel handle, universal key EK 333, Side Panels: 2 side panels,
sheet steel, universal key, IP Rating: 1P20, Plates: Standard top and bottom plate (fixed),
Load Rating: 1000 kg
Frame for separation of 150mm cold zone in front of 19" profiles, for ROF/RDF 42RU,
width 800mm
connecting kit for installing racks SEVEN, OPTIMAL, PREMIUM series in blocks - with
installed side panels

cable entry, two layers of brushes, suitable for ROF (opening 300x100mm)

Each

32

19" blank panel 1U - Quick assembly

Each

80

19" blank panel 2U - Quick assembly

Each

32

19" blank panel 3U - Quick assembly

Each

32

19" blank panel 5U - Quick assembly

Each

16

Each

32

Basic PDU, plug IEC 309 3m, Outlet 1 - 20xC13, Outlet 2 - 4xC19, power rating
63A__,._--___

Brackets for mounting of vertical power distribution unit DP-RP-20-xx into ROF frame
Each 1 32

w800; 2x sliding door

Emerson/ Schneider/ Rittal/ Conteg or other equivalent globally reputed brand


To be mentioned by the bidder
Double-wing sliding door width 1200mm, height 42 and 45U (racks without plinth), RAL
Each
7035 or RAL 9005; Mechanical, double door opening system

special top cover + vertical side panels with see-through - 600w/1200d/42U -width
1200mm - without roof panel

Each

24

special top cover + vertical side panels with see-through - 800w/1200d/42U -width
1200mm - without roof panel

Each

roof multiwall polycarbonate panel 600 mm width for 1200 mm aisle

Each

24

roof multiwall polycarbonate panel 800 mm width for 1200 mm aisle

Each

Item-33: Ladder System for UTP & Fiber


SL. #

Product Names/Items

1 Ladder System for UTP & Fiber

Description of requirements

Universal Cable Runway; 12"W x 1.5"H x 9.96'L; Black; Cable


Capacity - 629; Black; Brand: To be mentioned by bidder Origin: To
be mentioned by bidder
Butt-Splice Kit; 0.38"W x 1.5"H x 5"L; Black ; Brand: To

2
be mentioned by bidder Origin: To be mentioned by bidder
3

Cable Runway Radius Drop, Cross Member; 11"W; Black; Brand:


To be mentioned by bidder Origin: To be mentioned by bidder

Protective End Caps for runway ; Brand: To be mentioned by bidder


Origin: To be mentioned by bidder

UoM

QTY

Each

50

Each

120

Each

150

Each

50

Item-34: IP based Surveillance System


SL. #
1

Product
Names/Items
Indoor Camera (PoE)
Brand
Model
Country of origin

Video Management System


Brand
Model
Country of origin

3 Network Attached Storage (NAS)


Brand
4 Network Switch
Brand
Model
Country of Origin
5 UTP Cable
6 RJ45 Connector

7 Installation

Description of requirements

UoM

QTY

Dome Network Camera

Nos

24

To be mentioned by bidder
To be mentioned by bidder
To be mentioned by bidder
Specifications
1/2.7" Full HD progressive megapixel CMOS sensor
10 or above meter IR illumination distance.
Built-in Infrared-Cut Removable (ICR) Filter module
Minimum illumination: 0.12 lux (day mode), 0 lux (night mode) with IR
LED.
Fixed lens, 4 mm F1.5 with 77.4 degree horizontal viewing angle.
256 Mbytes SDRAM
128 Mbytes of flash memory
Digital Zoom 16X
Audio Features
GSM-AMR speech encoding, bit rate: 4.75 kbps to 12.2 kbps
MPEG-4 AAC audio encoding, bit rate: 16 kpbs to 128 kbps
Supports two-way audio and audio mute
Video Compression
H.264/MPEG4/MJPEG dual format compression simultaneously
JPEG for still image
H.264/MPEG-4 multicast streaming
Video Resolution
1920x1080 @ 15 fps, 1280x1024 @ 20 fps, 1280x720 @ 30 fps, 640x480
@ 30 fps, 320x240 @ 30 fps, 176x144 @ 30 fps
Networking protocol
IPv4, IPv6, TCP/IP, UDP, ICMP, DHCP Client, NTP Client , DNS Client,
DDNS Client , SMTP Client, FTP Client, HTTP / HTTPS,
Samba Client, PPPoE, UPnP Port Forwarding, RTP / RTSP/ RTCP, IP
filtering, 3GPP, LLTD, CoS/QoS, SNMP, IGMP, 802.1x, ONVIF Compliant
sikh
Emp1a
241
of A, 50/60 Hz, IEEE 802.3af PoE
Power Input 12Page
V DC
1.25
Eic
c

General Specifications
363

Max. Power Consumption 5.3 W

ionF)
Operating Temperature -0 to 40 C (32DiVis
to 104
Storage Temperature -20 to 70 C (-4 to14y
158 F)
Humidity 90% non-condensing
Weight 472 g (1.04 Ibs)
Certifications CE (Class A), CE LVD (EN60965-1), FCC (Class A), ICES003, C-Tick

Nos.
To be mentioned by bidder
To be mentioned by bidder
To be mentioned by bidder
Specifications
Supports up to 32 cameras Megapixel network camera support
MJPEG/MPEG-4/H.264 compression format support
Dual monitor support
Multilingual support
OSD (On-screen Display) setting Live Monitoring
30 FPS maximum recording per camera (subject to camera and video server
capacity)
Automatic discovery of network cameras
On-the-fly configuration changes Auto reboot function support System
DDNS support
Remote Desktop Viewer SMS alert
Lock system to avoid unauthorized changes
User Account Management User validation
User password restriction User profiling
Access privilege control
Recording
Supports multiple storage locations Record by schedule
Record by event
Digital watermark protection Pre-record/Post-record support
Manual recording of up to 32/64 channels
One-way audio recording of multiple channels
Record and live display at different frame rates and resolutions Data Search
and Playback
Video playback control
Intelligent Search Tool
Histogram quick search method for videos
Video stamp
Extract snapshots from video Extract video to AVI /A SF
Supports remote playback/web playback
Video Mode
Screen division layout support
Monitor display allows for drag and drop of videos
Supports full screen video Multiple channel playback support Information
window support
Enable Move function to control a P/T/Z camera
Digital zoom in/out support
Supports remote live viewing to display video
Map Mode
Multiple map support
Alarm notification

Customized map background support


Camera preview
Camera and I/O indicator I/O & Event Feature
Output port control
Input port trigger on event
Output port relay when an event is detected
Digital Input Trigger SMS Digital Input Trigger CMS E-mail notifications
P/T/Z Control
Manual control
Preset positions (device dependent)
Preset patrolling
Multiple patrol group support Backup database for logs and videos
Import/Export configuration DB tool
Compatible with D-Link NVR Compatible with 3rd Party CMS
No

Each

Cat-6 UTP Cable

Box

Must be of a globally reputed brand

Each

100

Capacity 15TB usable storage after RAIDS


To be mentioned by bidder
24 Port 10/100/1000 PoE switch
To be mentioned by bidder
To be mentioned by bidder
To be mentioned by bidder

Installation, testing & commissioning

Lot

Item-35: Generator
SL

Product Names/Items

General

Generating Set

Diesel Engine

Alternator

Page 245 of 363

Circuit Breaker :
Control Panel:
Manufacturer's name :
Factory Test :
Testing & commissioning at site :

Synchronizing Control Panel:

Room Canopy:

Synchronizing LT Panel:

3 ATS Panel

Incoming

Outgoing

trip.
Cable

5 Installation

6 Warranty

Page 247 of 363

Description of requirements

UoM

QTY

THREE PHASE AUTO START GENERATOR (WITH AUTO TRANSFER


SWITCH)
Supply of 1000 KVA, 400 / 230 V, 3-phase, 50 Hz. air/water cooled,
Set
floor mounted, indoor type as per following technical specification
for Generator sets, Engine, Alternator, Digital Control Panel for
4x1000KVA automatic start Diesel Generator.

Generator Brand: To be mentioned by the bidder


Generating set Model: To be mentioned by the bidder
Manufacturer's Name: To be mentioned by the bidder
Country of origin: To be mentioned by the bidder
Country of Assembled: (Generator set must be assembled, Tested
by the original Manufacturer of the given Country of Origin.)
Net Power Rating: Prime :900KVA, 720KW at 0.8 P.F Standby :
1000KVA, 800KWat 0.8 P.F
Supply System: 3-phase, 4-wire, 400/230V, 0.8P.F., 50Hz
Ambient Temperature: 50C
Maximum load acceptance:100%, 800KWe at 0.5% Voltage
regulation & with 300% short circuit current capacity
Single load step to NFPA110: 100-110% load taken during
emergency power system, meets all requirements
Engine Model : To be mentioned by the bidder
Manufacturer's name : To be mentioned by the bidder
Country of origin : To be mentioned by the bidder
Number of cylinders and arrangement: 6 Cylinder Diesel, 4 Stroke,
in line-built, water cooled, Turbocharged and after cooled.

Governor Type: Isochronous Electronic Governing Controls engine


speed within plus or minus 0.25% for any steady state load from no
load to full load. Frequency drift will not exceed 0.5% for a 69F
(330C) change in ambient temperature over an 8 hour period &
have facilities for droop Governing, Temperature Dynamic, Idle
mode, Isochronous (kw) load sharing control, Droop load sharing
control

Speed : 1500 rpm


Bore ' stroke (mm) : 160mm x 190mm
Piston displacement (cc) : 30.6Litre
Compression ratio : 13.6 : 1
Fuel Consumption : Load % : 100% 75% 50% Fuel Consumption :
194.4 143.2 100.3
( Liter/ Hr)

Maximum engine output according to DIN (Hp/rpm), Temp,


Humidity, Altitude: 1080BHP, 805kWm
(Prime)&1183BHP, 882kWm (Standby) at 1500 RPM,
50C ambient, 30% humidity, 110maltitude
Average piston speed : 9.5m/sec
Starting device : Self-starter Motor with 24V Battery with charging
Dynamo (35A)
Cooling system (Radiator): Circulated by a centrifugal
pump with 50C tropical radiator & blower fan.
Exhaust Silencer : Residential type Silencer, noise level 80dBA (0, 37 meter Lubrication system : Oil pressure at Governed speed 0.34 Mpa
Literature and illustrations : Will be enclosed
Engine Low NOX Emission treatment/Emissions
Certification : The certificate for the mentioned emission treatment will
have to be collected from competent authority & data sheet will be
enclosed
Heavy duty Air Cleaner : Will be fitted with engine for Dust free &
longer life
Design : 4 cycle, in-line, Turbo charged, Air-cooled
Battery Capacity : As per standard
Starting Voltage : 24 volt, negative ground
Standard Cooling : 122F (50C) ambient radiator
Design: Brushless single bearing, revolving field.
Alternator Manufacturer's/Brand: Leroy Somer/Stamford
Stator : 2/3 pitch-6S
Rotor: Single Bearing, flexible disc.
Standard Temperature Rise : 125 - 163C Standby
Exciter Type : AREP
Phase Rotation : A (U), B(V), C(W)
Alternator Cooling : Direct drive centrifugal blower fan
Manufacturer's name : Leroy Somer or Equivalent
Country of origin: EU
Prime Power : 900KVA @ Class H Insulation
RPM : 1500 (Clockwise)
Power Factor : 0.8
Voltage : 400V/230V
Frequency : 50Hz
Voltage Regulation : within +0.5%

Class of Insulation : Class H, IP23 Protection

Automatic Voltage Regulator (AVR) : Microprocessor


based Control Power Command Control system have
integrated automatic voltage regulator, output within 1.0%

Antivibration Mountings: The combine engine /alternator unit is


attached to the bed frame by anti-vibration neoprene rubber mountings.
These efficient vibration isolators are inserted into the machine between
the engine /alternator and the skid. Additional spring isolator (EU
standard) need to be provided for more vibration safety.
1600Amps 3P ACB
Built-in Sync Panel
To be mentioned
0, 25, 50, 75, 100 & 110% load test will be done at factory before
Shipment. Load test report need to be submitted along with documents.
All test will be done at site & recorded with available site load

Controller must be capable to sync not less than 10 generating sets in


case of future extension with RS485 Modbus interface. Protections:
Over/Under Voltage, Over/Under frequency, Overload detection, Dead
bus detection, Reverse power, Time over current, Instantaneous over
current, Inverse time over current, Phase rotation, Unbalanced load,
Power Factor.

Supplier must have experience in synchronizing more than 30 projects


on higher ratings. (Above 500KVA)
- 85-90 dBA@ I m
- High density fiber glass sound absorption materials - Perforated sheet
will be used
- Residential type silencer
- Power coated weather protected louver
- ANSI, ASTM standard materials for piping and fittings

LT Panel for synchronizing need to be provided with a common bus-bar


of 7000Amps. 04 Nos generators will include in the input point of the
common bus-bar from their breaker and 02 Nos ACB will be connected
in the output end of common bus-bar. Each output ACB will be rated
5000 Amps equally.
Capacity : 5000A

Set

Sheet steel enclosed powder coated (16SWG) , dust & vermin proof,
free standing, floor / Wall mounting,'415V, 50 Hz, indoor type
Distribution Board complete with hard drawn electrolytic copper bus
bars of adequate rating, TPN & E and equipped with:

2 No. 5000A, 100KA, TP full automatic fixed type ACB with storedenergy motor charged operating mechanism having special features :
i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.
ii)
Electronic trip unit with DIP Switch setting PR121/P which has
operation without the need for an external power supply
iii) Protection function:
L: Protection against overload with inverse long time delay trip.
I: Protection against instantaneous short circuit with adjustable trip
current threshold
3 Nos. Current Transformer, ratio: 5000/5A with suitable accuracy and
burden
1-unit of Digital Multi Meter
3 Nos. Phase Indicating Lamp
1 set Control fuse.
-

1 No. 5000A, 100KA, TP full automatic fixed type ACB with stored-

energy motor charged operating mechanism having special features :


i) Microprocessor controlled adjustable thermal overload, adjustable
electromagnetic short circuit releases.
ii)
Electronic trip unit with DIP Switch setting PR121/P which has
operation without the need for an external power supply
iii) Protection function :
L: Protection against overload with inverse long time delay
I: Protection against instantaneous short circuit with adjustable trip
current threshold
lc 300 mm2 NYY Cable

RM

1000

lc 300 mm2 BYA ECC green

RM

400

Installation of 1000KVA generator with Exhaust Louver

Set

One year full warranty (onsite covering everything with parts and
services) period including all maintenance and support for the system
from the date of commissioning and acceptance. This warranty coverage
document shall include 24 x 7 supports and maintenance services from
Principal shall be submitted to the customer.