Sei sulla pagina 1di 1

ANEXO N 01

CORRELACION DEL CONDUCTOR ACSR Y CABLE OPGW

DATOS DE CONDUCTOR ACSR

DATOS DEL CABLE DE GUARDA

Seccin :

184.54 mm2

Seccin :

Trotura :

5651 kg

Trotura :

6550 kg

W c.g. :

0.493 kg/m

W cond. :
Tiro EDS :

0.510 kg/m
18.0% Trotura

104 mm2

1017.18

PARA EDS = 18% Trotura


Para la Hiptesis I se debe cumplir:
Si Fc.g. =

0.95 Fcond.
T c.g. = Tc x ( Wc.g. / ( Wcond. x 1.0 ) )
T c.g. =

Si Fc.g. =

1035.0 kg

15.80%

0.90 Fcond.
T c.g. = Tc x ( Wc.g. / ( Wcond. x 0.90 ) )
T c.g. =

Si Fc.g. =

1092.5 kg

16.68%

0.85 Fcond.
T c.g. = Tc x ( Wc.g. / ( Wcond. x 0.90 ) )
T c.g. =

Si Fc.g. =

1156.8 kg

17.66%

0.80 Fcond.
T c.g. = Tc x ( Wc.g. / ( Wcond. x 0.85 ) )

Valor seleccionado para el EDS

T c.g. =

del cabe OPGW es 16.68 %

1235.3 kg

18.86%

1 de 1