Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CIV5002Z
Structuralconcretepropertiesandpractice
LaboratoryReportAssignment
CourseSupervisor:ProfM.Alexander
23April2012
Student:MichaelComninos
StudentNumber:CMNMIC001
Contents
Part1Mixdesigns
1. Introduction
2. Mix1Requiredconcreteproperties
3. Mix1Mixdesignprocess
4. Mix2Requiredconcreteproperties
5. Mix2Mixdesignprocess
Part2Laboratoryreportontrialmixes
1. Laboratoryreportsummary
2. Mixdesign
3. Laboratorydata,resultsandobservations
4. Conclusionsanddiscussions
5. References
2.1
High strength
A high design strength of 45 MPa is required to withstand the high compressive stresses induced by post
tensioning and to ensure that the serviceability limits on the tensile stresses within the concrete are not
exceeded. (Tensile serviceability stress limits are proportional to the compressive strength of the
concrete)
2.2
High workability
The congested secondary reinforcement requires the mix to be highly workable to allow concrete to flow
through and around the reinforcement with minimal vibration (it is difficult to get standard poker vibrators
through congested reinforcement therefore vibrations will be limited)
2.3
To facilitate rapid construction and quick turnaround times of falsework and formwork, it is important that
the casting, stressing and stripping cycle is made as efficient as possible. The concrete needs to reach a
certain strength before stressing is permitted and therefore early strength gain will allow the contractor to
stress relatively early thereby facilitating the overall speed of construction.
2.4
Low permeability
A 130mm deep slab with both top and bottom secondary reinforcement present is likely to have cover in
the region of 30mm. Therefore with limited cover, low permeability (in particular in the cover region) is
important to ensure durability.
2.5
It is important to limit long term creep and shrinkage in a post tensioned slab as high creep and shrinkage
strains will result in high prestress losses and therefore inefficient use of prestressing materials.
2.6
For well documented structural and durability reasons, ASR within the hardened concrete must be
prevented
3.1
A design strength of 45 MPa has been specified in order to withstand the relatively high stresses induced
by prestressing. Assuming the degree of control will be good (which is a reasonable assumption given
that the control on site should be good for post tensioning type construction), from table 16.1 a minimum
margin of 8.2 MPa will be used giving a target strength of 53.2 MPa.
3.2
Specify slump
The mix requires the fresh concrete to be highly workability due to the congested secondary
reinforcement. A slump of 100mm is therefore specified.
3.3
Greywake is a potentially reactive aggregate. An extender will be advantages as both Fly Ash
(FA) and Ground Granulated Blastfurnace Slag (GGBS) retard or prevent ASR by reducing the
active alkali content in the binder in comparison with a pure CEM1 mix with equivalent binder
content.
The cover to the reinforcement is likely to be low (given the thickness of the slab) therefore
decreased permeability of the concrete in the cover zone is important for durability. The use of
extenders (both FA and GGBS) reduces the permeability of the hardened concrete.
Extender Type
A FA extender will be used for the following reasons:
In order to reduce shrinkage the mix requires as low a water content as possible. Water content
is the main influencing factor with regard to shrinkage with an almost linear relationship between
shrinkage and water content. FA blends tend to reduce the quantity of water required for a given
consistency
In order to reduce long-term creep and shrinkage a relatively high aggregate content is required.
Aggregates have a two-fold effect on creep and shrinkage, a) the source of creep and shrinkage
is the hardened cement paste and the greater the aggregate content, the lesser the amount of
paste is available for creep and shrinkage (simple proportional mathematics) and b) the
aggregate actually has a restraining effect on creep and shrinkage movement. FA blends permit
an increase in stone content
The mix requires a high workability. FA improves workability.
3.4
The water:binder (w:b) ratio is the major influencing factor on the strength of the concrete. The
compressive strength is related to the capillary porosity of the hardened cement paste which is a function
of the water:binder ratio and of the degree of hydration of the cement. For this high strength concrete, a
relatively low water:binder ratio will be required.
3
For a target strength of 53 MPa, a w:b ratio of 0.55 is appropriate if CEM I - 52.5 is used (obtained from
PPC data sheets)
3.5
Use of an admixture
The superplasticiser Sika Viscocrete will be used to reduce the water content required (giving the
associated creep, shrinkage, durability and strength benefits as described in 3.3. and 3.4. above) to
achieve the specified slump of 100mm. An initial dosage of 0.5l per 100kg of cementitious material is
prescribed (based on supplier literature). The dosage will be refined and optimised through laboratory and
site trial mixes. Based on suppliers literature, it is assumed that the addition of the superplasticiser will
result in a 15% higher slump than a control mix without plasticiser at the same water content
3.6
The characteristics of sand significantly influence the amount of water required to make a given volume of
concrete workable. The Philippi Dune Sand has a low standard water requirement (SWR) of
approximately 180 l/m3. The Crusher sand has a relatively high SWR in the region of 215 l/m3. It would
therefore be beneficial to use as high a proportion of dune sand as possible to limit the water content
required for the given slump. However the dune sand has a low fines content and a limited range of
grading and these combined factors can lead to segregation and bleeding in concretes. It is therefore
advisable to blend the dune sand with a small portion of crusher sand which will increase the range of
grading and prevent bleeding. The strength of the Interfacial Transition Zone (ITZ) between the cement
paste and the aggregate, which directly affects the strength of the concrete, is improved as bleeding is
reduced; therefore controlling bleeding is a prerequisite to producing the relatively high strength concrete
required.
A blend of 70% dune sand with 30% crusher sand will be used. A SWR of 190 l/m3 is assumed for the
blend. The Fineness Modulus (FM) of the blend is 2.33.
3.7
The SWR of the sand blend is approximately 190 l/m3 as described above. This prescribes the water
content required to achieve a 75mm slump without the use of an admixture. It is assumed that the use of
the superplasticiser will achieve the required slump of 100mm with the same water content. Therefore the
water content specified is 190 l/m3
3.8
Cement content
FA = 64 kg
3.9
Stone Content
Ma = CBD(K-0.1FM)
CBD = 1500 kg/m3
K = 1 (moderate vibration likely for post tensioned slab)
Therefore Ma = 1500 (1 0.1 x 2.33) = 1151 kg.
Stone content can be increased due to use of FA. Using table 11.5, the percentage of additional stone
allowed for a FA content of 20% of total cementitious material is approximately 3.5% therefore stone
content can be increased to 1151 x 1.035 = 1191 kg, say 1190kg.
Sand content, which is calculated by volume remaining after cement, water and stone content have been
calculated, is:
Ms
2.65 x 1000 x [1 345 / 2.93 x 1000 1190 / 2.7 x 1000 190 / 1 x 1000]
667 kg
Mix 1
3
1 m mix
Target
(MPa)
RD
Volumes
(l)
0.015
mix
m3
strength
53.2
75
w/c
0.55
Water (l)
190
190
2.85
276
3.14
88
4.14
FA Extender (kg)
Total binder content
(kg)
69
2.3
30
1.035
345
2.93
Stone (kg)
1190
2.7
441
17.85
467
2.65
176
7.005
200
2.65
75
Superplasticiser (ml)
1725
25.875
Check totals
2392
OK
1000
Table 1 Design Mix 1
OK
4.1
Sulphate-resisting concrete
The concrete will be exposed to high concentrations of sulphates which will attack the concrete and
cause deterioration of the concrete unless the mix is designed to resist the sulphate attack. Various
reactions between the sulphate ion and the hydrated calcium aluminate, the calcium hydroxide and the
hydrated calcium silicates within the hardened cement paste cause expansions and contractions in the
concrete which in turn cause high tensile stresses which can result in severe spalling. Resistance to
sulphate attack is provided by increasing the physical resistance of the concrete to the penetration and
capillary induced migration of the sulphate ions and increasing the chemical resistance of the cement to
the reactions described above.
4.2
High workability
The congested secondary reinforcement requires the mix to be workable to flow through the congested
reinforcement. A moderate degree of compaction is likely to be achievable during construction.
4.3
Early thermal cracking in concrete occurs when the fresh concrete thermally expands due to heat
released during hydration and then later cools and contracts. When the concrete expands, it is still fresh
with very low stiffness and therefore any restraints to the thermal movement do not induce large stresses.
However during the cooling and contraction phase, the concrete has hardened and stiffened and
therefore any restraints to the movement will induce high tensile stresses. The concrete is still in the early
stage of strength development and is unable to withstand the tensile stresses and therefore cracks.
In this specific application restraints to thermal movement will be both external (previously cast pier
foundation will restrain movement in the newly cast pier) and internal (non uniform distributions of
temperature due to the large size of the member will provide restraint between the internal and external
zones of the member)
Reduced total heat of hydration liberated and reduced rate at which the heat is liberated (thereby allowing
the concrete to gain strength before the tensile stresses develop) are properties of the concrete mix that
will reduce early thermal cracking of the concrete.
4.4
For well documented structural and durability reasons, ASR within the hardened concrete must be
prevented
5.1
A design strength of 20 MPa has been specified. This is a relatively low design strength and is unlikely to
be the limiting criterion with regards to minimum cement content and maximum water cement ratio.
7
Assuming the degree of control will be good, from table 16.1 a minimum margin of 8.2 MPa will be used
giving a target strength of 28.2 MPa.
5.2
Specify slump
The mix requires the fresh concrete to be highly workability due to the congested secondary
reinforcement however a moderate degree of vibration is achievable. A slump of 75mm is likely to be
adequate for this application.
5.3
Sulphate resisting portland cement would ideally be used in this mix however it is not available and
therefore the binder will be a blend of CEM1-52.5 with either GGBS or FA.
Use or non-use of a cement extender (FA or GGBS)
A cement extender will be used for the following reasons:
Extenders reduce the risk of thermal cracking in the concrete by reducing the rate that heat of
hydration is produced
Extender Type
A FA extender will be used for the following reasons:
FA will reduce the water content required for a given consistency. This reduces the cementitious
content required and hence the heat liberated which will reduce thermal cracking
5.4
Although the water binder ratio is the major influencing factor on the strength of the concrete, the low
design strength renders this criterion non-critical. The critical criterion with regard to water binder ratio for
this mix will be the requirement for concrete exposed to sulphate attack. From table 8.6 of Fultons
concrete technology, the maximum water:binder ratio for a Class 2 concentration of sulphates (0.3 g/l to
1.2 g/l in ground water) is 0.55.
As predicted, for a target strength of 28.2 MPa, a w:b ratio of 0.55 is more than adequate.
5.5
Use of an admixture
The superplasticiser Sika Viscocrete will be used to reduce the water content required (giving the
associated durability and thermal cracking benefits as described above) to achieve the given slump of
75mm. An initial dosage of 0.5l per 100kg of cementitious material is prescribed. The dosage will be
refined and optimised through laboratory and site trial mixes. Based on suppliers literature, it is assumed
that the addition of the superplasticiser will result in a 15% higher slump than a control mix without
plasticiser at the same water content
5.6
A blend of 70% dune sand with 30% crusher sand will be used for similar reasons as described and
explained for mix 1.
5.7
The SWR of the sand blend is approximately 190 l/m3. This prescribes the water content required to
achieve the specified 75mm slump without the addition of an admixture. Allowing for the use of a
superplasticiser, a water content of 180 l/m3 is specified to achieve the 75mm slump.
5.8
Cement content
Mc = water content / w:b ratio = 180 / 0.55 = 327 kg/m3 say 330 kg/m3 (This cement content meets the
minimum cement content criteria of 310 kg/m3 for concrete exposed to sulphate attack as specified in
table 8.6 of Fultons concrete technology)
CEM 1 -52.5 = 198 kg
FA = 132 kg
9
5.9
Stone Content
Ma = CBD(K-0.1FM)
CBD = 1500 kg/m3
K = 1 (moderate vibration likely for post tensioned slab)
Therefore Ma = 1500 (1 0.1 x 2.33) = 1151 kg.
Stone content can be increased due to use of FA. Using table 11.5, the percentage of additional stone
allowed for a FA content of 40% of total cementitious material is approximately 6% therefore stone
content can be increased to 1151 x 1.06 = 1262 kg, say 1260kg.
Sand content, which is calculated by volume remaining after cement, water and stone content have been
calculated, is:
Ms
2.65 x 1000 x [1 330 / 2.74 x 1000 1260 / 2.7 x 1000 180 / 1 x 1000]
617 kg
10
Mix 2
Target
(MPa)
RD
Volumes
(l)
0.015m3
mix
strength
28.2
75
w/b ratio
0.55
Water (l)
180
180
2.7
198
3.14
63
2.97
FA Extender (kg)
Total binder content
(kg)
132
2.3
57
1.98
330
2.74
Stone (kg)
1260
2.7
467
18.9
432
2.65
163
6.48
185
2.65
70
2.775
Superplasticiser (ml)
1650
24.75
Check totals
2387
1000
OK
OK
Table2Mixdesignformix2
11
Mix 1 failed to achieve its 28-day target strength of 53.2 MPa and only achieved a mean strength of
40.3 MPa. The slump measured was in the target range. The shrinkage strains measured (235
microstrain after 44 days) were within expected values and are not considered excessive. The
durability index tests returned values which classify the concrete in the good durability class.
Mix 2 achieved a mean 28-day strength of 58.3 MPa easily meeting its 28-day target strength of 28.2
MPa. The slump measured was in the target range. The shrinkage strains measured (267.5
microstrain after 44 days) were within expected values and are not considered excessive. The
durability index tests returned values which classify the concrete in the excellent durability class
thereby meeting its sulphate resistance durability requirement
2. Mix designs
The mix design processes were undertaken as a collective group. Water binder ratios were obtained
from a Cement and Concrete Institute Brochure for the strength criterion and from Fultons concrete
technologyforthesulphateexposurecriterion.
A 100% CEM1 52.5 mix was chosen for mix 1 as the concrete application and environment did not
dictateanyspecialdurabilityrequirements(whichwouldnecessitatetheuseofanextender)andearly
strengthgainrequiredforprestressingwasconsideredmoreimportant.The criteriondeterminingthe
w:bratioformix1wasthehighstrengthrequirement.
A50%CEM152.5/50%GGBSextenderwaschosenformix2toincreasethedurabilityoftheconcrete
asnecessitatedbyitsexposureconditiontosulphateattack.Thecriteriondeterminingthew:bratiofor
mix2wastheexposuretosulphateattack.
Targetslumpsof75mmwerespecifiedforbothmixes
12
Summariesofthemixdesignsformix1and2areprovidedintables3and4below.
Mix1
1m3mix
RD
Volumes(l)
0.015m3
mix
Targetstrength(Mpa)
53
Targetslump(mm)
75
w/c
0.6
Water(l)
190
190
2.85
CEM152.5(kg)
320
3.14
102
4.80
FAExtender(kg)
0
Total binder content
(kg)
320
2.3
0.00
2.93
Stone(kg)
1150
2.7
426
17.25
DuneSand(kg)
525
2.65
198
7.88
CrusherSand(kg)
225
2.65
85
3.38
Superplasticiser(ml)
Checktotals
2410
OK
1001
OK
Table3Trialmix1
Mix2
1m3mix
RD
Volumes(l)
0.015m3
mix
Targetstrength(Mpa)
28
Targetslump(mm)
75
w/c
0.5
Water(l)
170
170
2.55
CEM152.5(kg)
170
3.14
54
2.55
GGBSExtender(kg)
170
Total binder content
(kg)
340
2.9
59
2.55
2.74
Stone(kg)
1150
2.7
426
17.25
DuneSand(kg)
540
2.65
204
8.10
CrusherSand(kg)
232
2.65
88
3.48
Superplasticiser(ml)
1000
15
Checktotals
2432
OK
1000
OK
Table4Trialmix2
13
3.1.1
Mix 1
Workability
The trial mix achieved a slump of 95mm. This was within the target range of 75mm +/- 25mm. No
admixture was require to achieve this slump
3.1.2
Strength
The trial mix achieved an average 28-day cube strength of 40.3 MPa with a standard deviation of 0.1
MPa. This is significantly below the target strength of 53.2 MPa
Cube
Mark
Age at Mass
Test
Cube
Dim.
Dens.
Mean
Dens.
Fail.
Load
fcu
Mean
fcu
(Days)
(g)
(mm)
(kg/m3)
(kg/m3)
(kN)
(MPa)
(MPa)
2528
2509
2416
2538
100.0
100.0
100.0
100.0
2528
2509
2416
2538
356.0
364.0
502.0
516.0
35.6
36.4
50.2
51.6
2378
2438
2465
2541
100.0
100.0
100.0
100.0
2378
2438
2465
2541
376.0
380.0
558.0
582.0
37.6
38.0
55.8
58.2
2330
2490
2531
2541
100.0
100.0
100.0
100.0
2330
2490
2531
2541
402.0
404.0
564.0
602.0
40.2
40.4
56.4
60.2
Mix 1
Mix 2
Mix 1
14
Mix 2
14
Mix 1
28
Mix 2
28
2519
2477
2408
2503
2410
2536
Table5Compressivetestresultsformix1and2
14
Strength
gain (%)
36.0
89%
50.9
87%
37.8
94%
57.0
98%
40.3
100%
58.3
100%
70
60
50
40
Mix 1
30
Mix 2
20
10
0
0
10
15
Age (days)
20
25
30
Figure1Compressivestrengthgainsformixes1and2
Further trial mixes with decreased water:binder ratios will be required to achieve the target strength of
53.2 MPa
3.1.3
The average 3-day and 7-day cube strengths were 36.0 MPa and 37.8 MPa respectively giving an 89%
strength gain at 3 days and a 94% strength gain at 7 days. These values indicate that although the
ultimate target strength was not achieved, the required early strength gain property (required for rapid
construction) was achieved
3.1.4
Shrinkage
Shrinkage measurements of 235 microstrain after 44 days of drying were recorded. Typically 50% of
shrinkage has taken place after a drying period of approximately 50 days and therefore the total
shrinkage of the mix could roughly be estimated to be in the region of 470 microstrain.
Large variations in shrinkage strain were detected not only between the different test specimens but also
between the different sides of the same specimen. For example strains of 190 microstrain and 310
microstrain were recorded on specimen C sides 1 and sides 2 respectively. Measurements to determine
shrinkage strain are extremely sensitive and small variations in temperature combined with human
15
handling errors can results in large variations in strains. It is likely that this was the cause of the
anomalous results.
Shrinkage - Comparison
300.00
250.00
Starin ( 10-6)
200.00
150.00
Mix 1
Mix 2
100.00
50.00
0.00
0
10
15
20
25
30
35
40
45
50
Age (days)
Figure2Shrinkagestrainresultsformixes1and2
The shrinkage strains recorded appear consistent with prediction models (which themselves vary greatly)
and are not excessive and therefore it can be concluded that the mix will not cause high prestress losses
due to shrinkage.
3.1.5
3.1.5.1
Oxygen permeability tests were conducted on three disc samples of 70mm nominal diameter and 30mm
nominal thickness (for actual measured diameters and thicknesses refer to detailed results sheets). The
samples were placed in a sealed falling head permeameter apparatus and subjected to an initial pressure
of approximately 100kPa. The pressure decay was monitored from which the coefficient of permeability
(k) was determined. The Oxygen Permeability Index (OPI) is defined as OPI = -log10k
16
The samples achieved a mean co-efficient of permeability (k) of 1.55 x 10-6 m/s which equates to a mean
OPI of 9.8. Good correlation was achieved between the three samples with a standard deviation on the
OPI results tending to zero.
Disk
Number
k (m/s)
OPI
1.6E-10
9.8
1.5E-10
9.8
1.5E-10
9.8
Mean
1.6E-10
9.8
Std dev
0.0
0.0
Table6OPIresultsformix1
An OPI value of 9.8 indicates a concrete of good durability class and low permeability and thus likely to
have a good carbonation resistance.
3.1.5.2
The same specimens that were used for the Oxygen Permeability Test were used for the water sorptivity
test to provide an indication of the porosity of the concrete. The lower the water sorptivity index, the better
is the potential durability of the concrete. The bottom face of a disc sample is exposed to a few
millimetres of water. At regular time intervals, the sample is weighed to determine the mass of water
absorbed, and the sorptivity is determined from the plot of mass of water absorbed versus square root of
time.
The mean sorptivity of the 3 samples was 11.3 mm/hr0.5 with a standard deviation of 1.5 mm/hr0.5. This
equates to a mean porosity of 12%.
Disk
Number
Sorptivity (mm/hr0.5)
Porosity (%)
11.1
11.8
12.9
11.7
9.9
12.6
Mean
11.3
12.0
Std dev
1.5
0.5
Table7Watersorptivityresultsformix1
17
A sorptivity value of 11.3 mm/hr0.5 and a porosity of 12% indicate a concrete of poor durability class
(sorptivity values of between 6 10 mm/hr0.5 are indicative of a good durability class of concrete).
3.1.5.3
Chloride conductivity tests were conducted on 3 core samples. Either side of the core ends were exposed
to a NaCl chloride solution and then accelerated diffusion of the chloride ions was achieved by applying a
10V potential difference across the core. The amperage was measured to determine the chloride
conductivity. The lower the chloride conductivity, the better is the potential durability of the concrete.
Disk
Number
Conductivity (mS/cm)
1.28
1.51
1.45
Average
1.41
Average
0.12
Table8Chlorideconductivityresultformix1
The mean chloride conductivity of the samples was 1.41 mS/cm with a standard deviation of 0.12 mS/cm.
This indicates a concrete of good durability class with good chloride resistance
3.1.5.4
Both the oxygen permeability test results and the chloride conductivity test results indicate a concrete of
good durability class with good carbonation and chloride resistance. The water sorptivity test on the other
hand indicates a poor durability class. Correlations between test result from the oxygen permeability test
and the chloride conductivity tests versus tests carried out on existing concrete exposed to carbonation
and marine conditions respectively have shown to be good and thus both these tests are considered
reliable indicators of the durability of the concrete. The water sorptivity test however only measures the
porosity of the concrete and not the rate of absorption and therefore is not as good an indicator of
durability. For the above reasons, the OPI and chloride conductivity tests results will take precedence
when concluding on the durability of the concrete and therefore the concrete durability can be classed as
good.
18
3.2
3.2.1
Mix 2
Workability
The trial mix achieved a slump of 75mm. This was within the target range of 75mm +/- 25mm. The slump
was achieved with the addition of a superplasticiser.
3.2.2
Strength
The trial mix achieved a mean 28-day cube strength of 58.3 MPa with a standard deviation of 2.7 MPa.
This is far greater than the target strength of 28.2 MPa which is not unexpected given that the governing
criterion for w:b ratio was for sulphate resistance and not strength.
For laboratory results, see section 3.1.2 above.
3.2.3
The mean 3-day and 7-day cube strengths were 50.9 MPa and 57.0 MPa respectively giving an 87%
strength gain at 3 days and a 98% strength gain at 7 days.
These values indicate that early strength gain was achieved although this was not a required property for
this mix.
3.2.4
Shrinkage
Shrinkage measurements of 267.5 microstrain after 44 days of drying were recorded. Typically 50% of
shrinkage has taken place after a drying period of approximately 50 days and therefore the total
shrinkage of the mix could roughly be estimated to be in the region of 330 microstrain.
The correlation of the shrinkage measurements for the various samples and the sides of the samples
appears to be better than that of mix 1 with strains ranging between 220 microstrain and 300 microstrain.
The shrinkage strains recorded appear consistent with prediction models (which themselves vary greatly)
and are not excessive. Reduced shrinkage strains is not a requirement of this mix and thus the shrinkage
results require no further evaluation.
For shrinkage laboratory results for mix 2, see section 3.1.4 above.
19
3.2.5
Durability index tests, as described in 3.1.5, were conducted on samples taken from mix 2. The test
methodologyisnotrepeatedunderthissectionandonlyresultsareprovided.
3.2.5.1
The samples achieved a mean co-efficient of permeability (k) of 1.51 x 10-6 m/s which equates to a mean
OPI of 9.8. Good correlation was achieved between the three samples with a standard deviation on the
OPI results tending to zero.
Disk
Number
k (m/s)
OPI
1.55E-10
9.8
1.46E-10
9.8
1.53E-10
9.8
Mean
1.51E-10
9.8
Std dev
0.0
0.0
Table9OPIresultsformix2
An OPI value of 9.8 indicates a concrete of good durability class and low permeability and thus likely to
have a good carbonation resistance.
3.2.5.2
The mean sorptivity of the 3 samples was 5.4 mm/hr0.5 with a standard deviation of 0.9 mm/hr0.5. This
equates to a mean porosity of 11.2%.
Disk
Number
Sorptivity (mm/hr0.5)
Porosity (%)
6.3
11.2
5.4
10.3
4.4
12.1
Mean
5.4
11.2
Std Dev
0.9
0.9
Table10Watersorptivityresultsformix2
20
A sorptivity value of 5.4 mm/hr0.5 and a porosity of 11.2% indicate a concrete of excellent durability class
(sorptivity values of <6 are considered excellent). It is likely that the use of a GGBS extender (blended
50% / 50% with the CEM 1 52.5) together with the low w:b ratio contributed to the low sorptivity value.
3.2.5.3
The mean chloride conductivity of the samples was 0.5 mS/cm with a standard deviation of 0.07 mS/cm.
This indicates a concrete of excellent durability class with excellent chloride resistance (chloride
conductivity value < 0.75 are considered excellent). It is likely that the use of a GGBS extender (blended
50% / 50% with the CEM 1 52.5) together with the low w:b ratio contributed to the low chloride
conductivity value.
Disk
Number
Conductivity (mS/cm)
0.44
0.50
0.57
Average
0.50
Std Dev
0.07
Table11Chlorideconductivityresultsformix2
3.2.5.4
The durability index test results indicated that the mix achieved good to excellent durability properties.
This was one of the main requirements of the mix as good durability properties were required to combat
sulphate attack. The mix has met these requirements through the use of a GGBS extender and a low w:b
ratio.
21
4.1
Workability
Mix 1 achieved a slump of 95mm without the addition of a superplasticiser admixture whilst mix 2
achieved a slump of 75mm with the addition of 1 l/m3 of superplasticiser. The higher slump was achieved
in mix 1 due to the higher water content (190 l/m3 as oppose to 170 l/m3). The use of an admixture for
mix 1 is advisable as this will lower the water content (which will lower the w:b ratio for the same cement
content) whilst still achieving the same consistency
Mix 2s water content and admixture dosage are deemed correct as the required slump was achieved
with a relatively low water content
4.2
Strength
Mix 1 failed to achieve its target strength of 53.2 MPa. Although not required of the concrete, Mix 2
achieved a 28 day strength of 58.3 MPa. The higher strength of mix 2 was achieved due to the lower w:b
ratio (0.5 vs. 0.6). It is advised that a new trial mix for mix 1 be batched using a w:b ratio in the region of
0.5. This need not be achieved by increasing the cement content and can instead be achieved by
lowering the water content by using an admixture as described in 4.1 above.
4.3
Both mix 1 and mix 2 achieved good early strength gains with 3 day strengths of 89% and 87%
respectively and 7 day strengths of 94% and 98% respectively. It is not surprising that mix 1 achieved
good early strength gain given that it contains 100% CEM 1 - 52.5 however it is slightly surprising that
the 50% component of GGBS in mix 2 did not retard the early strength gain. A conclusion can be drawn
that GGBS does not retard early strength development and it is perhaps only FA extenders, which contain
no free calcium and therefore rely purely on CH from the cement hydration reaction, that retard early
strength development in concrete.
4.4
Shrinkage
The shrinkage strains of mix 1 are less than those of mix 2 (235 microstrain vs. 267 microstrain). On initial
inspection of the mixes, it would be expected that mix 1 would have the higher shrinkage strains given
that both the water content and the w:b ratio of mix 1 is higher than those of mix 2, whilst there is very
little difference in aggregate content. However on closer inspection, this apparent anomalous result can
be explained by previous research results which have shown that the incorporation of GGBS in concretes
at 50% replacement levels has the effect of causing a possible 20% increase in shrinkage at early ages in
small exposed laboratory specimens. This increase in shrinkage of the GGBS blend only occurs in
laboratory specimens and can be ignored for shrinkage calculations of the structural element
22
4.5
Durability
The durability index results achieved for both mix 1 and mix 2 are more than satisfactory for their
respective exposure classes and conditions and therefore mix proportions and materials do not need to
be altered for the durability criterion.
The water sorptivity test and the chloride conductivity tests for mix 2 exceeded those of mix 1 and the mix
2 concrete achieved an excellent durability class. This was one the main requirements of mix 2 due to
the severe sulphate exposure condition. The lower chloride conductivity and water sorptivity values in mix
2 can be explained by the presence of the GGBS extender in mix 2 which lowers the values of these
durability indexes by up to 50%, as is the case with these results. It must be noted however that the OPI
results of the 2 mixes were very similar and this is in line with previous research which shows that OPI is
not significantly improved by the addition of FA or GGBS extenders.
5. References
Website - www.theconcreteportal.com/perf_spec.html
PPC suppliers brochure CEM I 52.5
23
AppendixADetailedLabResult