Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
COPYRIGHT
DISCLAIMER
CONTENTS
PAGE
4
Introduction
11
44
66
71
Acknowledgements
C401
C402
C403
C404
C405
C406
C407
C408
C501
General
Building Envelope Requirements
Building Mechanical Systems
Service Water Heating
Electrical Power and Lighting Systems
Additional Efficiency Package Options
Total Building Performance
System Commissioning
Existing Buildings
R401 General
R402 Building Thermal Envelope
R403 Systems
R404 Electrical Power and Lighting Systems
R405 Simulated Performance Alternative
R406 Energy Rating Index
R501 Existing Buildings
INTRODUCTION
INTRODUCTION
INTRODUCTION
ENERGY CODE
BASICS
IMPROVEMENTS TO BUILDING ENERGY USE SINCE 1975
The first energy efficiency standard for buildings, ASHRAE 90-1975, was originally developed in response to the OPEC
oil embargo energy crisis of the early 70s. Although the priority for most cities has now shifted to carbon emissions,
for the first time, Americans were starting to think about the energy consumption of their infrastructure and what
they could do to reduce it.
Since then, energy codes have improved dramaticallya building approved under todays energy code will use almost
half of the energy of a building constructed in 1975and designers have gained a better understanding of how all
building systems work together to affect energy use as an integrated whole. The 2015 IECC significantly improves
building performance while taking into account the cost of design and construction so that new requirements are
not burdensome to the building industry. The code strengthens energy requirements for insulation, air barriers and
window construction. New and retrofitted buildings will be better sealed and insulated, reducing the energy required
to keep them comfortable and well-lit.
100
90
MEC
1983/86
Std.
90-1975
Std.
90A-1980
MEC
1992/93 MEC
1995
Std. 90.1-1989
80
IECC
1998
Std.
90.1-2004
Std.
90.1-2007
60
40
IECC
2009
Std.
90.1-2001
70
50
IECC
2004/06
Std.
90.1-1999
Std.
90.1-2010
IECC
2012
IECC
2015
Std.
90.1-2013
30
20
10
0
1975
1980
1985
1990
1995
2000
2005
2010
2015
2020
2025
2030
Year
Code Non-Compliant
Residential
Code Non-Compliant
Commercial
$31,659
$480,000
+/-
HIGH PERFORMANCE
BUILDINGS AND
PRODUCTIVITY
+/-
INTRODUCTION
Climate Zone 6
Climate Zone 5
Climate Zone 4
CLIMATE PARAMETERS
AFFECT ENERGY DESIGN
SOLAR RADIATION
MOISTURE
DAYLIGHT/GLARE
HEAT/COLD
WIND
INTRODUCTION
The whole-building approach is the idea that all systems such as lighting, HVAC, plumbing, and envelope are all
interconnected and work together in an efficient building.
Changing one aspect of the building envelope may have unintended consequences elsewhere. For example,
increasing the efficiency of the thermal envelope will lead to a lower demand on the boiler, but If the boiler is
already over-sized, it will short-cycle more and run less efficiently. Conversely, swapping out inefficient, heatproducing incandescent light bulbs with LEDs will lower the amount of heat in the building, and the boiler will have
to work harder to compensate.
Consider all of a buildings systems at once and be aware of how changes in one system may affect other
systems. The ultimate goal is synergy between systems, meaning that each system works in cooperation with the
others, creating a result that is greater than the sum of its parts. For example, upgrading a buildings thermal
envelope while simultaneously installing a smaller, more efficient boiler will have a positive effect on the buildings
performance that would not be possible separately.
A
B
C
D
A
E
C
B
Solar Thermal
Condensing Boiler
I
J
Cogeneration
Occupancy + Daylighting
Controlled Lighting
K
L
H
I
Q
R
Q
R
Meters + Submeters
Recycling
Greywater System
P
POTABLE
WATER
BLACK
WATER
INTRODUCTION
Optimal time
for energy
decisions
Future
Occupants
Product
Suppliers
Engineers
Contractor
Owner
Architects
Trade/Design
Specialists
Project
Manager
Energy
Professional
Building
Staff
Commissioning
Agent
INTRODUCTION
COORDINATION AND
COMMUNICATION
INTRODUCTION
Architect
Engineer
Energy Professional
Commissioning Agent
Construction Manager
Operator
STAKEHOLDER EFFORT
Phase 1: Pre-Design
Ow
Ar
En
Op
STAKEHOLDER EFFORT
Ow
Ar
En
EP
CM
Op
STAKEHOLDER EFFORT
Ar
En
EP
CxA
CM
Op
STAKEHOLDER EFFORT
Ow
Ar
En
EP
CxA
CM
Op
STAKEHOLDER EFFORT
Phase 5: Construction
Ow
Ar
En
EP
CxA
CM
Op
STAKEHOLDER EFFORT
Phase 6: Occupancy
Ow
Ar
En
EP
CxA
CM
Op
PAGE
13
C401 General
15
31
32
38
39
41
43
25
COMMERCIAL
IECC
COMMERCIAL
PROVISIONS
2015 IECC will increase the energy efficiency of both commercial and
residential buildings.
COMMERCIAL
INTRODUCTION
C401.1 SCOPE
All buildings that are not defined as Residential must comply
with the Commercial Energy Conservation Code, including
multifamily buildings more than three stories above grade. The
mechanical systems in multifamily buildings may require the
commercial code if the units are served by the same system.
COMMERCIAL
C401
GENERAL
COMMERCIAL VERSUS
RESIDENTIAL BUILDINGS
Residential buildings include: Detached 1- and
2-family dwellings, Multiple single-family
dwellings (townhouses), and Group R-2, R-3
and R-4 three stories or less above grade.
Any building four stories or moreincluding
multifamily residential buildingsmust comply
with the commercial code.
Residential
Commercial
Commercial
Commercial
Commercial
If filing for a building with both residential and commercial, it would all be included in one application and the designer would include two sets of
data. One would cover the residential portions, and the other would cover the commercial. This is only necessary if the building is three stories or
less and includes commercial and residential dwelling units.
PRESCRIPTIVE PATH
PERFORMANCE PATH
COMMERCIAL
C401.2 APPLICATION
GENERAL
The thermal envelope and the air barrier should be both
continuous and continguous.
Air seal all joints, seams, and penetrations.
ROOFS
R-value and Solar
Reflectance Index (SRI)
affects heat loss / gain.
ABOVE-GRADE
WALLS
R-value and Solar
Reflectance Index
(SRI) affects heat
loss / gain.
WINDOWS
U-factor affects heat
loss/gain.
SHGC affects heat gain.
VT affects daylighting.
Operation affects
natural ventilation.
BELOW-GRADE
WALLS
R-value affects heat
loss / gain.
THERMAL ENVELOPE
The thermal envelope and the air barrier should
be both continuous and continguous.
COMMERCIAL: ENVELOPE
C402
BUILDING ENVELOPE
REQUIREMENTS
High-performing
Typical
Outdoor Temp
Indoor temperatures during a winter blackout. Higher performing buildings have better windows, less air infiltration, and more
insulation than a conventional building.
COMMERCIAL: ENVELOPE
THERMAL BRIDGING
COMMERCIAL: ENVELOPE
Interior sheathing
R-0.45
Cavity insulation
Exterior sheathing
Vapor retarder
Continuous insulation
Metal panel
R-13.60
R-0.45
R-0.06
R-7.50
R-0
Total:
U-value = 1 / 22.06 =
R 22.06
0.045
R-Values can be found by adding the values of each wall component. To find
the U-factor, take the inverse of the total R-value.
R = 1/U
U = 1/R
C402.1 GENERAL
C402.1.3 INSULATION COMPONENT
R-VALUE-BASED METHOD
COMPLIANCE METHOD #1: The R-Value method is the
most straightforward approach. Designers show their
proposed above- and below-grade walls, roofs, floors
and slabs-on-grade meet the required R-values listed
in Table C402.1.3. Note that the R-values vary based on
climate zone and whether or not the buildings use falls
under a Residential Use Group.
OR
C402.1.4 ASSEMBLY U-FACTOR, C-FACTOR,
OR F-FACTOR-BASED METHOD
COMPLIANCE METHOD #2: This method allows
designers to make some envelope tradeoffs by
calculating the U-factor (thermal transmittance),
C-Factor (thermal conductance) and F-Factor
(perimeter heat loss for slab on grade floors) for the
various components and verifying that each complies
independently.
The values for a wide variety of commonly used
materials and construction assemblies can be found
in ASHRAE 90.1 Appendix A. The designer inputs
the required values and the areas/lengths for each
assembly. COMcheck is a useful tool to calculate these
tradeoffs.
OR
C402.1.5 COMPONENT
PERFORMANCE ALTERNATIVE
COMPLIANCE METHOD #3: The Component
Performance Alternative method is similar to the UA
Alternative method in the Residential code. It allows
more substantial envelope tradeoffs.
If an envelope component doesnt comply with the
prescriptive requirement, this method gives even more
wiggle room than the other two methods. Calculate the
differences in thermal resistance between the proposed
design of each component and the values listed in
Tables C402.1.3 and C402.1.4.
The code allows adding up all the differences and if
they net to below zero, the opaque thermal envelope
complies.
COMMERCIAL: ENVELOPE
COMMERCIAL: ENVELOPE
C402.2.4 FLOORS
Cavity
insulation
Sheathing
Air gap
FLASHING
SLAB
PROTECTION
BOARD
SLAB
SLAB
R-10 INSULATION
SLAB
R-10 INSULATION
Thermal break
between slab and
foundation
R-10 INSULATION
Thermal break
between slab and
foundation
SLAB
COMMERCIAL: ENVELOPE
Wood subfloor
SRI 0 (Black):
SRI 78:
C402.4 FENESTRATION
Code-Compliant
Window:
Lower =
more efficient
Lower = less
solar heat gain
Metal-Framed Wall:
R-13 + R-7.5 ci
(CZ4, Table C402.1.3)
Higher = more
light in space
Lower = less
air infiltration
WWR
30%
Complies
prescriptively
>30%, 40%
>40%
COMMERCIAL: ENVELOPE
75%
25%
C402.4.3 MAXIMUM
COMMERCIAL: ENVELOPE
Meets an air
leakage rate of
less than 0.40
cfm/ft2
Fig X.XXX
COMMERCIAL: ENVELOPE
C402.5.7 VESTIBULES
Building vestibules prevent heat loss and gain.
1. All building entrances shall have an enclosed
vestibule
2. Vestibule doors must be equipped with selfclosing devices
3. Interior and exterior doors should not need to be
open at the same time
Exceptions:
Doors not for public use
Doors from a residential unit
Doors opening onto space < 3,000 ft2
Revolving doors (vestibules are still required at
doors adjacent to revolving doors)
If air curtain at door
DOCK SEALS
COMMERCIAL: ENVELOPE
HEATING
COOLING
Envelope (windows,
walls, roof)
Envelope (mostly
windows)
Ventilation
Lights, equipment
(plug loads), people,
and other internal
loads
Ventilation
COMMUNICATION IS KEY
The design and quality of the
building envelope determines
the load of the HVAC system.
Calculate the buildings loads
and then size the equipment
accordingly. A building with
a better designed envelope
will have smaller heating and
cooling loads which will require
smaller systems. In order to
accomplish this, a knowledge
of envelope systems and
mechanical systems is essential
for both the architect and the
engineer.
The building on the left has an inefficient envelope and therefore must have a larger heating/
cooling system to compensate.
COMMERCIAL: SYSTEMS
C403
BUILDING
MECHANICAL SYSTEMS
EQUIPMENT SELECTION:
AVOID WASTE BY IMPROVING
COMMUNICATION
Communication is key! Engineers use code
minimums as defaults until they receive
necessary info (sometimes not until the
Design Development phase)
Better option: Architect and Engineer
communicate early about important
envelope issues
Added benefit: Smaller equipment, ducts,
pipes and fans mean more space for
occupants
Table Name
(1)
(2)
(3)
PTACs / PTHPs
(4)
(5)
Gas-fired boiler
(6)
Standalone DX condensing
A/C equipment
(7)
Chiller
(8)
Cooling towers
(9)
NEW TABLE
(10)
COMMERCIAL: SYSTEMS
EFFICIENCY RATINGS
Various parameters describe the effectiveness of heating and cooling equipment. Using these terms is the only way
to unambiguously ensure that equipment of the highest performance is being used.
ASHRAE
Values in ASHRAE vary slightly
from those in the IECC
NYC
NYCECC requires higher
efficiencies for some tables
C403.2.4.1.2 DEADBAND
When controlling heating and cooling in same
zone, the thermostat must be capable of providing
a deadband of 5 between heating and cooling
set pointsmeaning that neither the heating nor
cooling system will be used when the interior
temperature is within this range.
zzz...
<70
70- 75
(Deadband)
>75
COMMERCIAL: SYSTEMS
C403.2.6 VENTILATION
COMMERCIAL: SYSTEMS
0%
10%
20%
30%
40%
Additional systems
required under 2012 IECC
50%
AND CONTROL
60%
70%
80%
Required an ERV
under 2009 IECC
90%
100%
10
15
20
25
30
COMMERCIAL: SYSTEMS
REFRIGERATION
C403.3 ECONOMIZERS
When the outside temperature is pleasant, economizers
supplement conditioned air with outdoor air. Every
cooling system that has a fan must have either an air or
water economizer.
Separate from C403.2, which are all required measures,
Economizers are not always cost effective for all
systems or climates so the code recognizes exceptions
specifically for very efficient systems and systems that
are run infrequently. Systems with heat recovery are also
exempt.
All economizers must have diagnostic controls to ensure
they are functioning properly. See section C403.2.4.7 for
more information about this requirement. Equipment
specifications and exceptions vary greatly depending on
the size and complexity of the HVAC system.
Outdoor Air
Logic Controller
Temperature
Sensor
Economizers act as a switch to use
more outside air or more return
air, depending on the temperature
outside. In mild weather, the
economizer will limit the amount of
return air that is recirculated and use
more outdoor air. Conversely, during
hot or cold weather, the economizer
will limit the amount of outdoor air
that is used.
Return Air
Filter
Supply Air
Heating/Cooling Elements
COMMERCIAL: SYSTEMS
C404.6 HEATED-WATER
CIRCULATING AND TEMPERATURE
MAINTENANCE SYSTEMS
Hot water circulation systems, as seen in figure XXXX,
avoid waste of water and heating energy by providing
a ready supply of hot water at the fixture, so the
occupant doesnt need to run water until it heats up.
However, these systems must have a circulation pump
with automatic controls that turn off the pump when
water is hot and there is no demand.
COMMERCIAL: SYSTEMS
C404
SERVICE WATER
HEATING
LAMP EFFICACY
Since we are limited in the amount of power we can use
for lighting, it is critical that we use light fixtures that
meet the applications requirements and give the proper
light quality with the best efficacy. Lamp efficacy is the
effectiveness of a lamp measured in output lumens per
input watts.
LUMENS
The lumen is the basic unit of visible light emitted from
a source. There are multiple options to achieve a certain
level of lumens. For example, a 100 W incandescent, a
23 W CFL, or a 16 W LED can each emit 1,500 lumens,
but the LEDs lamp efficacy of 94 Lumens/Watt far
exceeds an incandescent bulbs efficacy of 15 Lumens/
Watt.
Incandenscent
CFL
LED
1,500 Lumens
1,500 Lumens
1,500 Lumens
100W
23W
16W
Low efficacy
High efficacy
10 Lumens
350 Lumens
1,500 Lumens
C405
ELECTRICAL POWER
AND LIGHTING
SYSTEMS
Can be reduced by
lowering lighting
wattage
TIME
Can be reduced by
lusing lighting controls
and sensors
C405.2.3 DAYLIGHT-RESPONSIVE
CONTROLS
Spaces that are daylit and that also have more
than 150 Watts of general lighting must have
daylight responsive controls. This section defines
the size and location of daylight zones adjacent to
windows (vertical fenestration) and below skylights
(toplighting). This section also lays out the dimming
and calibration requirements for the controls that
respond to daylight.
This section is closely connected to the requirements
for window-to-wall ratio (C402.4.1 Maximum
fenestration area)
DAYLIGHTING ZONES
Increasing the size and number of windows increases access to natural light and lowers energy needs for lighting.
However, it can potentially increase the need for heating and cooling energy. Good design balances occupant
comfort as well as the buildings energy consumption.
VERTICAL FENESTRATION
SKYLIGHTS
C405.2.3.2(4) SIDELIGHT
DAYLIGHT ZONE
The distance from the fenestration
to any building or geological
formation which would block
access to daylight must be
greater than the height from the
bottom of the fenestration to the
top of the building or geologic
formation.
C405.2.3.3(2) TOPLIGHT
DAYLIGHT ZONE
A skylight must receive direct
sunlight when the sun is at peak
angle on the summer solstice to
qualify as a daylight zone.
SKYLIGHT NOT
A DAYLIGHT ZONE
Being able to find the area of floor space that qualifies as a daylighting zone is important when considering lighting
controls and window-to-wall ratio (See section C402.4, Fenestration).
+ SL
+ LV
+ LTPB
+ OTHER
Screw-in Lamps)
Low-Voltage lighting)
___________________
(Total Connected Lighting
= TCLP
Power, in Watts)
LPD =
Watts
Area (ft2) of illuminated space
For example:
3,000 ft2
320W
Office
(LPD: 0.82)
AREA
Retail
(LPD: 1.26)
LPD
1,000 ft
1.01
500 ft
0.82
500 ft2
1.26
1,010 W
410 W
+ 630 W
2,050 W
C405.4.1
Total
Connected
Interior
Lighting
Power
SL
+ LV
+ LTPB
+ Other
________
= TCLP
C405.4.2
Total
Allowed
Interior
Lighting
Power
Building Area
Method
OR
Space-by-Space
Method
C405.7 ELECTRICAL
TRANSFORMERS (MANDATORY)
& C405.8 ELECTRICAL MOTORS
(MANDATORY)
Electric motors and transformers are now required
to comply with minimum efficiency requirements
for electric transformers. There are 14 exempted
transformers. Transformers need to meet minimum
efficiency requirements from Table C405.7 and be
tested and rated in accordance with the procedure in
DOE 10 CFR 432.
There are four new tables for electrical motors. The
efficiencies need to be tested and rated in accordance
with DOE 10 CFR 431.
C406
ADDITIONAL EFFICIENCY
PACKAGE OPTIONS
C406.1 REQUIREMENTS
IECC requires the design team to pick one system, and
then comply with a higher level of efficiency for that
chosen system.
Note: 2015 IECC added 3 more options.
1. More Efficient HVAC
2. Reduce LPD by 10%
Fig X.XXX
C407
TOTAL BUILDING
PERFORMANCE
C407.1 SCOPE
This section establishes criteria for compliance using
an energy simulation. This energy model includes
all energy expected to be consumed in the building
including demands from building operation (HVAC
systems, service water heating, fan systems, and lighting
power) as well as energy related to the buildings use
(receptacle and process loads).
The energy used by a building using the performance
path is generally equivalent to the current prescriptive
requirements. The energy used by the building is
compared to the baseline.
It provides additional flexibility as it allows the design
team to use a variety of materials and approaches
that may or may not meet prescriptive requirements.
A whole-building performance model allows tradeoffs
to be made for components that are important to the
design but which exceed the prescriptive requirements.
In total, these tradeoffs must be as efficient as the
standard reference design.
C407.2 MANDATORY
REQUIREMENTS
In addition to providing a compliant energy model, the
building must also comply with all mandatory sections
in C402.5, C403.2, C404 and C405.
C407.3 PERFORMANCE-BASED
COMPLIANCE
Compliance using the performance approach requires a
simulation of annual energy cost that sums the energy
of a building as it varies every hour over the course of a
year. These simulations accounts for climate, occupancy,
and building type.
In the simulation, a model of the proposed building
must have a lower energy cost as compared to an
energy cost index (ECI) of a standard reference design.
Note that ASHRAE 90.1-2013 requires building energy
cost to be even loweronly 85% of the standard
reference design building. The parameters of the
standard reference design are determined by the rules
set forth in this section of the code.
Off-site renewable energy is considered the same as any
other energy source but on-site renewable energy can
be excluded from the simulation.
C407.4 DOCUMENTATION
The design professional must submit a compliance
report that documents that the proposed design has
annual energy costs less than or equal to the standard
reference design.
C407.5 CALCULATION
PROCEDURE
The calculation procedure for the proposed design and
standard reference design must use identical methods
and techniques.
The calculation procedure refers to Table C407.5.1(1).
Table C407.5.1(1): Specifications for the Standard
Reference and Proposed Designs
This table contains most of the building
envelope, lighting, heating, cooling, and
service water heating systems
Table C407.5.1(2): HVAC Systems Map
Table C407.5.1(3): Specifications for the Standard
Reference Design HVAC System Descriptions
Table C407.5.1(4): Number of chillers
Table C407.5.1(5): Water Chiller Types
C408
SYSTEM
COMMISSIONING
Even when equipment is specified and installed correctly, it is still possible that systems will not operate as planned
once the building is occupied. A careful process is needed to ensure that different systems do not interfere with each
other, and that all controls operate correctly. The commissioning process verifies that a facility has been designed,
constructed, and tested to perform as expected.
C408.1 GENERAL
This section specifically covers system commissioning
(Cx) for Building Mechanical Systems (C403) and
Electrical Power and Lighting Systems (C405). Although
not listed in this provision, Section C404.11 Service
Water-Heating System Commissioning and Completion
Requirements requires commissioning for Service
water-heating systems and controls.
COMMERCIAL: CX
Commissioning is the time in the construction process when the systems are tested in a prescribed manner so any
remaining defects are observed and correcteddefects that might otherwise remain hidden well into occupancy.
By highlighting these problems during the construction process, their impact is greatly lessened and correction is
simplified. Any issues discovered can be corrected before the warranties expire and prior to any damage occurring to
connected systems or harm to personnel.
BALANCING
C408.2.5.1 DRAWINGS
Location and performance data for HVAC and
Service Hot Water equipment
C408.2.5.2 MANUALS
O&M manuals
Size and selected options
Calibration information and wiring diagrams
Name and address for at least one service
company for each piece of equipment
C408.2.5.3 SYSTEM BALANCING REPORT
A written report describing the activities and
measurements completed in accordance with Section
C408.2.2.
COMMERCIAL: CX
CHAPTER 5
EXISTING BUILDINGS
Implementing stricter energy codes on new construction will go a long way to reduce energy consumption in buildings
across the state. However, 85% of the buildings that will exist in 2030 already exist and represent a challenge for
reducing energy use. The energy code recognizes the difficulties involved with improving the performance of these
buildings.
Note also that the 50% Rule is no longer in effectthe exemption for commercial renovations, additions, and
alterations from being subject to the current state energy code unless the project affected more than half of the
buildings systems. Now, any work that is not a repair or maintenance and affects energy use must meet the same
requirements as for new construction.
C501 GENERAL
C503 ALTERATIONS
C503.1 GENERAL
C502 ADDITIONS
ALTERATIONS
Unaltered adjacent
elements dont need
to comply
Fig X.XXX
The term existing buildings refers to buildings constructed before the codes provisions took effect. The IECC does
not require a legally-constructed existing building or system to comply with the current energy code provisions, but
does require any new additions and alterations to comply.
IECC
RESIDENTIAL
PROVISIONS
46
R401 General
48
58
R403 Systems
61
62
64
65
RESIDENTIAL
Page
INTRODUCTION
The provisions of the International Energy Conservation Code (IECC) promote the effective use of energy in buildings.
Conquer the Code teaches design professionals the structure and rationale behind the energy code in order to
maximize compliance, as well as the codes effectiveness.
There are several important new provisions in 2015 IECC. As the code strengthens energy requirements for thermal
and air barriers and window construction, any new construction or existing building renovation will be better sealed
and insulated, thus reducing the energy required to heat and cool them. The residential energy code now requires a
blower door test to verify the strict new air infiltration limit of 3ACH50, as well as mechanical ventilation in all new
and renovated homes. Additionally, IECC now includes a compliance path known as the Energy Rating Index (ERI),
which means that a Home Energy Rating System rating (HERS)an industry standard that measures a homes energy
efficiencycan satisfy energy code compliance if the home meets a minimum rating.
RESIDENTIAL
The Residential section of the energy code has three options for compliance. A designer may select either a
straightforward checklist-style prescriptive path with or without envelope tradeoffs, or a building performance path,
which requires an energy model. The flexibility within the codes performance path requirements encourages the
improvement of energy-conserving construction practices, equipment, materials, and techniques. Regardless of which
compliance pathway you choose, every project must meet specific mandatory requirements in accordance with 2015
IECC, which cannot be traded off. This course includes all of the mandatory provisions.
R401
GENERAL
R401.1 SCOPE
All residential buildings must comply with the Residential
provisions of the Energy Code. The mechanical systems in
multifamily buildings may require the commercial code if the
units are served by the same system. Every other type of
building uses the commercial code.
COMMERCIAL VERSUS
RESIDENTIAL BUILDINGS
Residential buildings include: Detached 1- and
2-family dwellings, Multiple single-family
dwellings (townhouses), and Group R-2, R-3
and R-4 three stories or less above grade.
Any building four stories or moreincluding
multifamily residential buildingsmust comply
with the commercial code.
Residential
Commercial
Commercial
Commercial
If filing for a building with both residential and commercial, it would all be included in one application and the designer would include two sets of
data. One would cover the residential portions, and the other would cover the commercial. This is only necessary if the building is three stories or
less and includes commercial and residential dwelling units.
RESIDENTIAL
Commercial
R401.3 CERTIFICATE
In residential buildings, it is a mandatory requirement to
post a permanent certificate on the wall of the furnace
or utility room. This certificate must include:
R-values of insulation installed on the ceiling/roof,
walls, foundation, and ducts outside conditioned
space
U-factors for fenestration and the solar heat gain
coefficient (SHGC) of fenestration
Results of any required duct system and building
envelope air leakage testing done on the building
Types and efficiences of heating, cooling, and
service water heating equipment
If a gas-fired unvented room heater, electric
furnace, or baseboard electric heaters are
installed in the building (These do not need
efficiencies listed.)
An example certificate
RESIDENTIAL
Section R405along with the provisions in R401 R404 that are mandatory for all projectsdetails the
performance path. Design teams that choose this
method must provide an energy model in order to
demonstrate that the buildings energy use will not
exceed the maximum allowed. The performance path
allows greater design flexibility and tradeoffs among
systems. This compliance path may require more
expense and effort if the firm is not used to creating
energy models.
R402
BUILDING THERMAL
ENVELOPE
The building envelope is the physical barrier between
the buildings conditioned interior environment and
the outside. Efficient building envelopes prevent air
leakage and moisture migration, heat gain and loss,
and solar heat gain through windows and skylights.
To create a comfortable indoor environment and
minimize wasted energy, the energy code requires
continuous air barriers, continuous insulation, and
efficient windows. The following sections will explain
the context behind each code provision and provide
examples of how to comply.
RESIDENTIAL: ENVELOPE
Knee Wall
Ceiling
Window
Rim Joist
Above-Grade
Wall
Basement
Wall
Slab-on-Grade
THERMAL BRIDGING
Thermal bridging occurs when a poorly insulating
material allows heat flow across a thermal barrier.
To prevent thermal bridging you must provide a
thermal break, such as with continuous insulation,
seen in the illustration to the right
Gysum Board
Cavity Batt Insulation
Exterior Sheathing
Vapor Retarder
Continuous Insulation
Wood Siding
Total:
U-value = 1 / 25.72 =
R-0.64
R-13.60
R-0.62
R-0.06
R-5.00
R-0.80
R 20.72
0.048
R = 1/U
U = 1/R
RESIDENTIAL: ENVELOPE
FENESTRATION U-FACTOR
Permeability
Rating
MASS WALLS
The R-value column in Table R402.1.2 lists two values
for mass walls. Mass walls relieve you of some insulation
requirements. Use the first number if over 50% of the
insulation is on the outside of the wall, and the second
number if over 50% of the insulation is on the inside.
Note that interior insulation on a mass wall is greater
than exterior insulation.
0.01
0.1
10
100
Polyethylene
Asphalt-Coated Kraft Paper
Plywood
Gypsum Board
+ Primer, Paint
Gypsum Board
+ Primer
Tyvek
Gypsum
Board Alone
RESIDENTIAL: ENVELOPE
RESIDENTIAL: ENVELOPE
An installation marker
Possibility of ice
dam formations
Heat loss
Insulation (R-49)
Insulation (R-38)
Insulation at full
thickness over
exterior walls
Eave baffle with protective chutes to allow ventilation from the soffits
R402.2.8 FLOORS
The code requires that insulation maintain permanent
contact with the underside of the floor. If the ceiling
were removed the insulation would remain intact.
Sheathing
EXCEPTION: If the floor cavity insulation goes from top
to bottom on the perimeter near the walls, the insulation
is permitted to rest on the sheathing.
Air gap
RESIDENTIAL: ENVELOPE
R402.3.1 U-FACTOR
Dont confuse the area weighted U-factor with the Total
UA alternative. They are two different calculations and
this provision is only for fenestration, not the entire
component such as a wall or ceiling. R402.3.1 is more
strict because it requires a fenestration U-factor of 0.35,
while the Total UA alternative allows 0.48 for average
fenestration. This is a useful provision if using a small
amount of inefficient glazing and still want to use the
prescriptive path, as long as the averages meet the
U-factor requirements.
U-factor
Area
U*A
Double Pane
Low-E
0.3
300
90
Single Pane
Stained Glass
1.1
20
22
320
112
Total
Weighted U
0.35
A sunroom
RESIDENTIAL: ENVELOPE
Type of Window
R402.3.3 GLAZED
FENESTRATION EXEMPTION
RIM JOISTS
Air seal at all vertical and horizontal joints along beams
and rim joist.
R402.4.1 BUILDING
THERMAL ENVELOPE
Because materials expand and contract due to changes
in temperature, the code specifies that air sealing
materials need to take into consideration the space that
will open up between dissimilar materials.
GENERAL REQUIREMENTS
SHAFTS, PENETRATIONS
Seal duct shafts, utility penetrations, and flue shafts
opening to exterior or unconditioned space.
RECESSED LIGHTING
Historically, recessed light fixtures have been a source
of significant energy loss because they penetrate the
building thermal envelope. The code specifies that
recessed lighting must be airtight and IC rated. IC-rated:
IC means in contact with insulated ceiling.
RESIDENTIAL: ENVELOPE
R402.4.2 FIREPLACES
New wood-burning fireplaces must have tight fitting
flue dampers or doors and a source of outside
combustion air.
RESIDENTIAL: ENVELOPE
OR
RESIDENTIAL: ENVELOPE
R403
SYSTEMS
Mechanical systems are essential to providing a
comfortable environment for the occupant. Since the
thermal envelope is to be completely sealed, uncontrolled
infiltration can no longer be counted on to circulate fresh
air into the home. Mechanical systems are now required
to provide and distribute the proper amount of fresh air,
heating, and cooling into the building. The code covers
pipes, ductwork, and equipment, and the proper sizing of
the mechanical systems.
To maximize energy efficiency, mechanical systems must
be sized correctly. Before, architects could estimate the
size of heating and cooling equipment, and they usually
fell back on oversizing equipment. The code requires that
systems be designed with the help of two guides from
the Air Conditioning Contractors of America: Manuals J
and S. They cover heating and cooling loads, system size,
and duct design. Systems that are designed with these
calculations in mind will run more efficiently and save
energy.
R403.3 DUCTS
R403.3.1 INSULATION
Insulating ducts prevents heat loss as the air is moved
around the house. Code requires R-8 if duct is greater
than 3 in diameter and R-6 if duct is less than 3 in
diameter. Ducts in a conditioned space do not need to
be insulated. A conditioned space is any room or space
enclosed in the thermal envelope that is directly or
indirectly heated or cooled.
RESIDENTIAL: SYSTEMS
R403.3.2 SEALING
To minimize heat gains and losses, ducts must have
all joints and transitions sealed. Properly sealed duct
systems can save energy, improve occupant comfort, and
increase the life of heating and cooling systems.
Seal
elbows
Seal
boots
Seal plenum
Furnace
Locations for duct sealing
Floor and wall cavities without ductwork are not suitable for air
conduits
R403.4 MECHANICAL
SYSTEM PIPING INSULATION
(MANDATORY)
Insulate the pipes to a minimum R-3 and protect exterior
piping from the weather.
RESIDENTIAL: SYSTEMS
Seal
joints and
connections
COMMUNICATION IS KEY
The building on the left has an inefficient envelope and therefore must have a larger heating/
cooling system to compensate.
RESIDENTIAL: SYSTEMS
R404
ELECTRICAL POWER
AND LIGHTING SYSTEMS
In contrast with the commercial code, lighting systems
in residential buildings have very few requirements.
The code does not specify how much lighting to install,
but simply how much of it needs to meet minimum
efficiency requirements.
LIGHTING EFFICACY
A lamps efficacy is analogous to how efficient it is. A
high-efficacy lamp will use a small amount of power
(Watts) to produce a large amount of light (Lumens).
Lamp efficacy is measured by Lumens/Watt. Therefore,
an incandescent lamp that uses 100W to produce 1,500
Lumens would be considered very low efficacy and an
LED that used 16W to produce the same 1,500 Lumens
would be considered very high efficacy.
10 Lumens
350 Lumens
1,500 Lumens
WATTAGE VS EFFICACY
CODE REQUIREMENTS
All three of these bulbs produce the same amount of light (1,500 lumens).
However, the amount of power they draw is drastically different.
100W
Incandescent
Efficacy
LAMPS OVER 40 WATTS:
15 Lumens/
Watt
LOW
EFFICACY
1500 / 33 =
45 Lumens/
Watt
HIGH
EFFICACY
1500 / 16 =
94 Lumens/
Watt
VERY HIGH
EFFICACY
1500 / 100 =
1,500 Lumens
LAMPS 16 - 40 WATTS:
23W
CFL
1,500 Lumens
16W
LED
60 Lumens / W
50 Lumens / W
LAMPS 15 WATTS OR LESS:
1,500 Lumens
40 Lumens / W
RESIDENTIAL: LIGHTING
Lumens/Watts
R405
SIMULATED
PERFORMANCE
ALTERNATIVE
R405.1 SCOPE
This section establishes criteria for compliance using
an energy simulation. This energy model includes all
energy expected to be consumed by heating, cooling,
and service water heating.
The energy used by a building using the performance
path is generally equivalent to the current prescriptive
requirements. The energy used by the building is
compared to the baseline.
It also provides additional flexibility as it allows
the design team to use a variety of materials and
approaches that may or may not meet prescriptive
requirements. A whole-building performance model
allows tradeoffs to be made for components that
are important to the design but which exceed the
prescriptive requirements. In total, these tradeoffs must
be as efficient as the standard reference design.
R405.3 PERFORMANCE-BASED
COMPLIANCE
Compliance using the performance approach requires
a simulation of annual energy usage. In the simulation,
a model of the proposed building must have a lower
energy cost as compared to an energy cost index (ECI)
of a standard reference design. Alternatively, the code
permits an energy use simulation using the source
energy relative to the conditioned floor area, expressed
in Btu/ft2.
Off-site renewable energy is considered the same as any
other energy source but on-site renewable energy can
be excluded from the simulation.
R405.2 MANDATORY
REQUIREMENTS
R405.4 DOCUMENTATION
The design professional must submit a compliance
report that documents that the proposed design has
annual energy costs less than or equal to the standard
reference design.
R405.4.2.1
R405.4.2.2
A certificate indicating
the building passes the
performance matrix for
code compliance, and
listing the energy-saving
features of the building
R405.5 CALCULATION
PROCEDURE
To calculate the standard reference design, use the
values in Table R405.5.2(1)
Once the standard reference design has been
configured and analyzed, a model of the proposed
design using the same methods must show that it uses
less or equal energy than the standard reference design.
R406
ENERGY RATING
INDEX COMPLIANCE
ALTERNATIVE
160...
150
140
130
120
CZ4
CZ5
CZ6
54
55
54
110
100
90
80
70
60
50
40
30
20
30
29
28
27
26
25
24
23
22
21
20
Each step
between 0 and
100 indicates
a 1% energy
use increase
between a
net-zero home
and the baseline
reference design.
10
DOCUMENTATION AND
COMPLIANCE
The ERI pathway is very similar to the HERS rating index, with 0 being a
net-zero design and 100 being the standard reference design
CHAPTER 5
EXISTING BUILDINGS
Implementing stricter energy codes on new construction will go a long way to reduce energy consumption in buildings
across the state. However, 85% of the buildings that will exist in 2030 already exist and represent a challenge for
reducing energy use. The energy code recognizes the difficulties involved with improving the performance of these
buildings.
The term existing buildings refers to buildings constructed before the codes provisions took effect. The IECC does
not require a legally-constructed existing building or system to comply with the current energy code provisions, but
does require any new additions and alterations to comply.
Note also that the 50% Rule is no longer in effectthe exemption for renovations, additions, and alterations from
being subject to the current state energy code unless the project affected more than half of the buildings systems.
Now, any work that is not a repair or maintenance and affects energy use must meet the same requirements as for
new construction.
R501 GENERAL
R503 ALTERATIONS
R502 ADDITIONS
Roof recover
When less than 50% of the luminaries in a space
are being replaced, assuming the installed lighting
power doesnt increase
ALTERATIONS
Unaltered adjacent
elements dont
need to comply
DOCUMENTATION
& INSPECTIONS
While it is important to understand the specific code provisions, it is equally important to understand how to prove
that the project complies to the enforcement entity.
Lack of proper documentation is often the reason that plans are denied. Projects that are noncompliant will be
delayed or stopped altogether until the designs are compliant and inspections are passed. This chapter includes easyto-follow guides for documentation and progress inspections.
For residential projects, the most common objections include improperly specified or installed insulation. Specifically,
the slab is not properly insulated and the interior foundation walls and ceilings have no insulation at all. Other
reasons include the lack of air sealing and inappropriately sized cooling systems. Interestingly, insulation is not the
main documentation problem for commercial projects, rather the lack of details and documentation for fenestration,
air sealing, duct sealing, HVAC, Service Hot Water, and LPD calculations and controls. Pay particular attention to
documenting these building components when ready to submit the construction documents to the code official.
80%
DOCUMENTATION
C/R103
CONSTRUCTION
DOCUMENTS
The construction documents must be submitted to the
code official with the project filing.
C/R103.2 INFORMATION ON
CONSTRUCTION DOCUMENTS
C103.3 EXAMINATION OF
DOCUMENTS
When the code official decides that the construction
documents meet the requirements of the energy
code, they will stamp them as Reviewed for Code
Compliance, meaning that they are approved. Once the
documents are approved, a copy will be sent back to the
applicant and one will be kept by the code official.
200
41
100
41
lys
is
t
ee
An
a
sh
er
gy
En
ys
is
et
An
al
he
En
er
gy
ks
so
er
Ot
h
70
59
W
or
ftw
ar
e
tiv
e
ip
cr
off
45
Pr
es
51
Tr
ad
e
289
703
ec
Economizer description
800
700
600
500
400
300
200
100
0
ch
RE
S
W
or
k
Ot
he
r
so
ftw
ar
e
ive
cr
ip
t
ff
Pr
es
CO
M
ch
79
50
eo
246
300
Tr
ad
500
400
600
ec
693
DOCUMENTATION
C/R103.1 GENERAL
C/R104
INSPECTIONS
C/R104.1 GENERAL
APPROVAL PROCESS
INSPECTION COMMERCIAL
RESIDENTIAL
Footing and
foundation
inspection
Framing and
rough-in
inspection
Plumbing
rough-in
inspection
Mechanical
rough-in
inspection
Not required
Final inspection
DOCUMENTATION
Drawings must:
q Be drawn to scale
q Indicate the location, nature, and extent of the work proposed
q Detail pertinent data and features of the building, systems and equipment
PROGRESS INSPECTIONS
Progress inspections verify that the construction matches the construction documents. Progress inspectors will
identify if the envelope, systems, service water heating, electrical, and other building components are installed
according to code requirements.
Progress inspectors are registered design professionals with relevant experience. They are hired by the Owner from
an approved Progress Inspection Agency. The registered design professional of record can act as the inspector but
the contractor cannot (NYC rule). Otherwise, the progress inspector must have a minimum of 5 years experience
with energy code-related building systems (for commercial buildings, at least 3 of those years must be related to the
systems being inspected).
Where an inspection or test fails, the construction shall be corrected and must be made available for re-inspection
and/or retesting by the progress inspector until it complies.
Commercial:
q Visually inspect light fixtures to confirm lighting power allowance
q Visually inspect exterior lighting fixtures
q Visually inspect lighting controls and test for functionality and proper operation
q Check exit signs and motors for compliance
OTHER:
q Are maintenance manuals present? Do they match equipment?
q Is Permanent Certificate installed?
70 DRAFT FOR REVIEW: NOT PROOFREAD
DOCUMENTATION
NYSERDA
New York State Energy Research & Development Authority
17 Columbia Circle
Albany, New York 12203
(518) 862-1090
www.nyserda.org