Sei sulla pagina 1di 20

16 CHANNEL SCANNER /

CONTROLLER

ISOSCAN-H
ISOSCAN-V
VER 53.XX

MAN#241R1/P1/22/300908/A

INSTRUCTIONS FOR USE

INDEX

MAN#241R1/P2/20/300908/A

DESCRIPTION

PAGE

1.

IMPORTANT SAFETY INFORMATION ..........................................................................

1.1

Installation ........................................................................................................................

1.2

Warranty ..........................................................................................................................

1.3

Special Instructions..

2.

INTRODUCTION..............................................................................................................

3.

FRONT PANEL ...............................................................................................................

3.1

ISOSCAN-H ..

3.2

ISOSCAN-V..

4.

KEY FUNCTIONS AND PARAMETER PROGRAMMING...............................................

5.

INPUT SPECIFICATIONS................................................................................................

6.

DIAGRAM TO SHOW SCHEME

7.

CONNECTION DIAGRAM ..............................................................................................

7.1

Supply Voltage : 85~265 V AC/DC ..

7.2

Supply Voltage : 24 VDC ...

8.

RUN TIME DISPLAYS ....................................................................................................

9.

PROGRAMMING.

9.1

Level Review

9.2

Level Group ..

10.

RELAY LOGIC ................................................................................................................

10

10.1

Onoff Control

10

10.2

Alarm Output . 10

11.

PROGRAM MODE DUIDE................................................................................................ 10

11.1

Level Review . 10

11.2

Level Initial............................................................................................... 11

11.3

Level Channel................................................................................................. 12

11.4

Level Group............................................................................................. 15

11.5

Level Setpoint................................................................................................. 16

11.6

Level Calibration................................................................................................. 18

11.7

Calibration of CJC.............................................................................................. 19

12.

TROUBE SHOOTING ..................................................................................................... 19

12.1

Error Messages ............................................................................................................... 19

13.

DATA CORRUPTION....................................................................................................... 19

14.

SPECIFICATION ............................................................................................................. 20

IMPORTANT SAFETY INFORMATION

INTRODUCTION

Installation
Check that the supply voltage given to the instrument is as
specified on the terminals of the instrument. To avoid
shock hazard prevent live parts being touched and follow
wiring diagram and specifications.

ISOSCAN is a microcontroller based user programmable


ONOFF scanner / controller with 5 digit LED display for
displaying process variable, 5 digit LED display for
selected setpoint and 2 digit LED display for channel
number. A 2x16 LCD display shows status of relays,
channels, etc.

1.2 Warranty
Radix Electrosystems Pvt. Ltd. warrants this product to be
free of defects in workmanship and materials for one year
from the date of purchase.

ISOSCAN has inputs & 16 relays & 2 current outputs. It is


operated by 3 user friendly keys.

1.

Defects in workmanship and materials will be serviced


free of charge during the warranty period. Labour
required for rectifying the defects is also covered by
this warranty. Any further claims are excluded.

3.1 ISOSCAN-H

2.

Warranty servicing does not extend the period of


warranty for the entire instrument or for the parts that
have been replaced.

3.

4.

From the warranty are excluded :


a) all damage caused by improper handling, e.g. nonobservance of the operating instructions, subjecting
the product to excessive heat, moisture, corrosion,
etc.
b) damage caused by the intervention of the buyer by
unauthorised third parties
c) transport damage from the manufacturer to the
dealer or user or on the way to servicing
d) parts subject to normal wear, e.g. relays.
Any liability for direct or indirect consequential
damages caused by the instrument is excluded, even
if the defect of the instrument is covered by the
warranty.

FRONT PANEL

(1)

PV

(2)

SP

(3)

CH
NO

(4)

(5)

ALM
1

10

11 12 13 14 15 16

RLY

3.2 ISOSCAN-V

Radix liability for any breach of this agreement shall


not exceed the purchase price paid.
ISOSCAN-V

5.

Any further claims, based on any title, are excluded.

6.

In case repair service is required under this factory


warranty, please send the instrument, indicating the
exact address of the sender and defect, carefully
packed, postage paid, to : Radix Microsystems, B-1,
2nd Floor, Ghanshyam Indl Estate, Off Veera Desai
Road, Andheri (West), Mumbai - 400 053.

(1)

PV

(2)

SP

(3)

CH
NO

ALM
1

10 11 12 13 14 15 16

RLY
ALM

Special Instructions
To avoid malfunction, an RC filter should be connected as
shown across the coil of each contactor or inductive load
such as AC solenoid.

RLY

(4)

(5)

MAN#241R1/P3/22/300908/A

CONTACTOR COIL

4. KEY FUNCTIONS AND PARAMETER PROGRAMMING


No. in Figures

Indicator/ Display

Function

(1)

Measured input value (PV)


display

Displays the measured input value (PV)

(2)

Setpoint (SP) display

Displays the setpoint (SP)

(3)

Channel Number
(CH NO) display

Displays the channel No.

(4)

Relay & Alarm status


indicator LEDs

When the relays & alarms get ON or OFF, the respective LEDs becomes
ON & OFF

(5)

Channel status in LCD


display

In run mode, displays the channel status.


Displays a parameter value in program mode or the error message if an
error occurs.
In program mode, allows to change value of parameter. At parameter
VEr if pressed for 6 sec, enters in the hidden level.
In run mode, to view the data of the selected channel.
In program mode, scrolls forward through the programmable parameters.
Increments the value of the selected parameter (
+
)
In run mode, acknowledge the alarm.

(6)

In program mode, scrolls backward through the programmable parameters


in program mode.
Decrements the value of the selected parameter (
+
)
In run mode, holds the current channel in the display.

5. INPUT SPECIFICATIONS

SENSOR / INPUT

MAN#241R1/P4/22/300908/A

Pt - 6% Rh / Pt - 30% RH (B)
Chromel / Constantan (E)
Iron / Constantan (J)
Chromel / Alumel (K)
NiCrosil / NiSil (N)
Pt / Pt - 13% Rh (R)
Pt / Pt - 10% Rh (S)
Copper / Constantan (T)
Pt100, 3 wire
Linear ( 0 - 50 mV, 0 - 20 mA,
4 20 mA)

RANGE LIMITS
( C / EU )

RANGE IN WHICH
ACCURACY
IS SPECIFIED
HIGH
LOW
SCALE
SCALE

TYPICAL
ACCURACY
AT 30C
( C / EU )

WORST CASE
ACCURACY
( C / EU )

LOW
SCALE

HIGH
SCALE

400
-270
-210
-270
-270
0
0
-270
-200

1820
1000
760
1372
1300
1760
1760
400
850

400
0
0
-50
-50
0
0
-200
-200

1820
1000
760
1200
1200
1760
1760
400
850

3
1
1
1
1
2
2
1
0.5

5
3
3
3
3
5
5
3
2.0

-19999

19999

-19999

19999

5 EU

20 EU

MAN#241R1/P5/22/300908/A

6. ISOSCAN VER.53.XX DIAGRAM TO SHOW SCHEME

7.

CONNECTION DIAGRAM

MAN#241R1/P6/22/300908/A

7.1 Supply Voltage : 85~265 V AC/DC

MAN#241R1/P7/22/300908/A

7.2 Supply Voltage : 24 VDC

8. RUN TIME DISPLAYS


8.1 In run mode the default LCD screen appears as
below :
ALARM
<I I
<
CHANNELS I < I < <

SCREEN A
(DEFAULT SCREEN)

: Channel skipped
I : Channel not selected in any group or channel selected
in group but no setpoint is assigned to that
channel or group.
< : Channel PV value has not crossed setpoint value
: Channel PV value has crossed setpoint value
S : Channel input is underrange (REV POL) or
overrange (INPUT OPEN)

8.3 To see details of a given setpoint in the screen B :


1.
2.
3.

Press
Press
Press

The following screens G, H & I will appear :

,<
!! "

8.2 To see which setpoints are selected for a given


channel.
1.
2.
3.

Press
Press
Press

key. Channel no. 1 flashes


or
to select any channel
key to display status of selected channel

key. Setpoint no.1 flashes


or
to select any setpoint
key to display channel and setpoint data

CHXX SPXX :
gr X fshi PV

21.5
52.7

SCREEN G

!!
!

CHXX SPXX NOT FOR


THIS CHNL
CHXX SPXX UNUSED

SCREEN H

SCREEN I

The following screens B, C, D, E & F will appear :

,<

CHXX
<X X
<
STPOINTS X < X < <

SCREEN B

: Setpoint not selected in any group


X : Setpoint not selected with channel selected but with
some other channel in other group
< : CHXX PV value has not crossed setpoint value
: CHXX PV value has crossed setpoint value

CHXX INDICATOR

CHXX SKIP

CHXX INPUT OPEN

CHXX REV POL

8.4 If no key is pressed, the display reverts to the


previous screen as follows :
CHXX SPXX :
gr X fshi PV

21.5
52.7

SCREEN G

After 2 minutes
CHXX
<X X
<
STPOINTS X < X < <

SCREEN B

ALARM
<I I
<
CHANNELS I < I < <

SCREEN A (DEFAULT
SCREEN)

SCREEN C

SCREEN D

SCREEN E

Screens C, D, E & F stay for 1 second, then revert to screen


A.
Screens H & I stay for 1 second, then revert to screen B.

MAN#241R1/P8/22/300908/A

8.5 Hold Mode


SCREEN F

From RUN mode display, to go to HOLD mode, press


The display DIS2 shows HOLD.

To change the channel number being displayed while in


HOLD mode : Press
and
or
to select the
required channel number.

This level is used to select channels & setpoints for a


group.
#

&

''

To select channels for group :

L : REVIEW
P:

L : GRP A NYYNNYYN
P : SELECT CH
1-8

Step 1

N Not selected
Y Selected
Press

+
) * +, +- .
SUMMARY

L : REVIEW CH DATA
SUMMARY

key. Channel 1 starts flashing

/)

Starts flashing
+

+
) * +, +011 2

) * +, +- .
SUMMARY

L : GRP A NYYNNYYN
P : SELECT CH
1-8

# #

Step 2

# *

Press

or

Setpoint value

(
.

Starts flashing

L : GRP A NYYNNYYN
P : SELECT CH 1-8

Step 3

Press
Setpoint in group Control action
(

key to select any channel, say 5

&

or

key to select / deselect channel

Channel 5 selected

Alarm type

L : GRP A NYYNYYYN
P : SELECT CH 1-8

. !! # 5 /# *

Step 4

Flashing stops
.

!
#

. !!

6
6

//+) *

!
/

6
6

After step 5, press

key to select setpoints 1-8

L : Gr A NYYNNYYN
P : SELECT SP 1-8

*
6 *
(

The procedure for setpoint selection is similar to channel


selection, as in steps 1 to 5.

# *
Selected channel

Input Type

6
.

MAN#241R1/P9/22/300908/A

Step 5

To select setpoints for a group :


6

key to select channels 9-16. Repeat steps 1 to 4.

L : GRP A NYYNNYYN
P : SELECT CH 9-16

Selected channel

Press

CH10 is part of
Groups E, M & N

CH to be displayed
or not during scan

'

Unit

For second group, change Gr A to Gr B and repeat step 1


to 5.
Note : User can not change input type & resolution of
grouped channels. If user wants to change, he has to
ungroup that channel.
While grouping any channel, unit and display
resolution of that channel and group level should be
same.

10. RELAY LOGIC

10.2 Alarm Output

10.1 Onoff Control

a) Latch (Ltch)
In latch output, once relay gets ON, it remains ON
until alarm is acknowledged by
key.

ON
OFF
HI ALRM

b) Hold
Alarm is disabled at power ON. After process variable
reaches normal (non alarm) value, the alarm is enabled.

LO ALRM

2 #
2 #

DEV HI
SP = SP1 + DEV *

c) Ltch.Hold
It is combination of latch & Hold logic.

DEV LO
SP = SP1 DEV *

2 #
2 #

IN BAND

OUT BND
2 #

+,7

+,7

+,7

+,7

2 #

2 #

2 #

* - DEV = SP2/SP3 SP16

11. PROGRAM MODE GUIDE

To enter program mode, press & hold


&
keys together, in run mode.
Press
+
keys to increment the value of the selected parameter or increment the level, & press
to decrement the
value of the selected parameter, or decrement the level.
Use
key to go to next parameter.
Use
key to go to previous parameter.
To exit from the program mode & enter run mode, press
&
keys together
If no key press for atleast two minutes instrument exit from program mode & enter run mode.

keys

11.1 Level Review


STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

L : RVIEW
CHDATA
SUMMARY

MAN#241R1/P10/22/300908/A

To select the display


format

L : RVIEW GR CHNLS
SUMMARY
L : RVIEW GR STPTS
SUMMARY
L : RVIEW
SPDATA
SUMMARY

ACTION

CH DATA Channel data (CH NO.,


input type,
display option, unit & max. first 3
groups to which this channel
belongs)
GR CHNLS Group channels
(i.e the channels selected in group)
GR STPTS Group setpoints
(i.e. the setpoints selected in group)
SP DATA Setpoint data (SP NO,
SP value, control action, alarm
type, relay action & the group to
which this setpoint belongs)
Details are explained in 9.1

11.2 Level Initial


STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION

Enter Program Mode

L : INIT
P:

Enter program mode from run


mode.

To enter in initial level

L : INIT
NO
P : LEVEL LOCK

First parameter in initial level is


displayed.

Selection of level lock

L : INIT
NO
P : LEVEL LOCK
L : INIT
YES
P : LEVEL LOCK

Storing of level lock

Selection of slave ID

L : INIT
P : SLAVE ID

L : INIT
P : SLAVE ID

Storing of slave ID

Selection of display scan


rate

Storing of display scan rate

255

L : INIT
1
P : DISSCAN SEC/CH

L : INIT
1
P : DISSCAN SEC/CH

to
L : INIT
99
P : DISSCAN SEC/CH
L : INIT
OFF
P : SETPOINT LOCK
L : INIT
OFF
P : SETPOINT LOCK

10

Selection of Setpoint lock

Storing of Setpoint lock

L : INIT
ON
P : SETPOINT LOCK
L : INIT
RLY OFF
P : SENSOR BREAK

L : INIT
RLY OFF
P : SENSOR BREAK

12

Selection of Sensor break


L : INIT
RLY ON
P : SENSOR BREAK

MAN#241R1/P11/22/300908/A

Level lock parameter is stored and


next parameter is displayed.

Selection of slave ID
1 255 user selectable

to
L : INIT
P : SLAVE ID

Locks the level.


If the level is locked, parameters in
that level can be read but cannot
be changed.
NO - Level is not locked
YES - Level is locked

Program auto exit is stored and next


parameter is displayed.

Display scan rate for scanning the


channels
1 99 user selectable
unit sec

Display scan rate is stored and next


parameter is displayed.

Setpoint Lock
OFF - Setpoints can be changed
ON - Setpoints can not be changed

Setpoint lock is stored and next


parameter is displayed.
Status of o/p when sensor is burnout
RLY OFF - At open condition, Relays
remain OFF & O/P power will be 0%
RLY ON - At open condition, Relays
remain ON & O/P power will be
100%

contd

contd
STEP
NO.
13

14

15

Level Initial
DESCRIPTION

KEY TO BE
PRESSED

Storing of Sensor break

Selection of Reset
parameters

DISPLAY

ACTION

L : INIT
NONE
P : RESET PARAMETS

Sensor break is stored and next


parameter is displayed.

L : INIT
NONE
P : RESET PARAMETS

Resets all functions to factory set


value.
NONE
ALL Press
&
keys
together to reset the instrument
Shows Software Version. Entry to
hidden level is made through this
function by keeping
key
pressed for 6 sec.

L : INIT
ALL
P : RESET PARAMETS
L : INIT
P:

Storing of Reset parameter

11.3 Level Channel


STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION
Selection of channel level from
options :
GROUP, SP, INIT

16

Selection of level channel

L : CHANL
P:

17

To enter in channel level

L : CH ANL
P : LEVEL LOCK

NO

L : CHANL
P : LEVEL LOCK

NO

18

Selection of level lock


L : CHANL
YES
P : LEVEL LOCK

19

20

Storing of level lock

Selection of channel no.

L : CHANL
P : CHANNEL NO.

L : CHANL
P : CHANNEL NO.

to

First parameter in channel level is


displayed.
Locks the level.
If the level is locked, parameters in
that level can be read but cannot be
changed.
NO - Level is not locked
YES - Level is locked
Level lock parameter is stored and
next parameter is displayed.

Select the number of channels

L : CHANL
16
P : CHANNEL NO.

21

Storing of channel no.

L : CH 1
TC K
P : INPUT TYPE

Channel no. is stored and next


parameter is displayed.

MAN#241R1/P12/22/300908/A

contd

contd
STEP
NO.

Level Channel
DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION

L : CH 1
TC B
P : INPUT TYPE
L : CH 1
TC E
P : INPUT TYPE
L : CH 1
TC J
P : INPUT TYPE
L : CH 1
TC K
P : INPUT TYPE
L : CH 1
TC N
P : INPUT TYPE
L : CH 1
TC R
P : INPUT TYPE

22

Selection of input type

L : CH 1
TC S
P : INPUT TYPE

Input sensor selection


TC - B, E, J, K, N, R, S, T
Pt100, 0-20 mA, 4-20 mA
Lin V - (0-50 mV)

L : CH 1
TC T
P : INPUT TYPE
L : CH 1
Pt100
P : INPUT TYPE
L : CH 1
Lin V
P : INPUT TYPE
L : CH 1
0~20 mA
P : INPUT TYPE
L : CH 1
4~20 mA
P : INPUT TYPE

23

Storing of input type

L : CH 1
0.1
P : DIS RESOLUTION

Input type is stored and next


parameter is displayed.

L : CH 1
1
P : DIS RESOLUTION
L : CH 1
0.1
P : DIS RESOLUTION

24

Selection of Display
resolution

L : CH 1
0.01
P : DIS RESOLUTION
L : CH 1
0.001
P : DIS RESOLUTION

Display resolution
1 resolution
0.1 resolution
0.01 resolution
(In case of LINEAR INPUT )
0.001 resolution
(In case of LINEAR INPUT )
0.0001 resolution
(In case of LINEAR INPUT )

MAN#241R1/P13/22/300908/A

L : CH 1
0.0001
P : DIS RESOLUTION

25

Storing of Display
resolution

L : CH 1
850
P : INPUT HI SCALE

Display resolution is stored and next


parameter is displayed.

26

Set high scale value for


selected channel

L : CH 1
850
P : INPUT HI SCALE

Adjust the high scale value for


selected channel

contd

contd

Level Channel

STEP
NO.

DESCRIPTION

27

Storing of high scale value


for selected channel

L : CH 1
0
P : INPUT LO SCALE

High scale value is stored and next


parameter is displayed.

28

Set low scale value for


selected channel

L : CH 1
0
P : INPUT LO SCALE

Adjust the low scale value for


selected channel

29

Storing of low scale value


for selected channel

L : CH 1
P : UNIT

Low scale value is stored and next


parameter is displayed.

L : CH 1
P : UNIT

L : CH 1
P : UNIT

L : CH 1
P : UNIT

L : CH 1
P : UNIT

EU

30

31

32

33

34

Selection of Unit for display

Storing of Unit

Selection of software filter


for selected channel

Storing of digital filter

Selection of Channel skip

KEY TO BE
PRESSED

DISPLAY

ACTION

L : CH 1
A
P : DIGITAL FILTER

Unit is stored and next parameter is


displayed,

L : CH 1
A
P : DIGITAL FILTER

L : CH 1
E
P : DIGITAL FILTER

Software Input Filter


A no filtering of input
B
minimum
C
to
D
maximum
E
filtering

L : CH 1
NO
P : CHANNEL SKIP

Digital filter is stored and next


parameter is displayed.

to

L : CH 1
NO
P : CHANNEL SKIP
L : CH 1
YES
P : CHANNEL SKIP

35

Storing of Channel skip

L : CH 1
0
P : DISPLAY OFFSET

L : CH 1
-125
P : DISPLAY OFFSET

36

Selection of display offset


for selected channel

to

MAN#241R1/P14/22/300908/A

L : CH 1
125
P : DISPLAY OFFSET

37

Storing of display offset

Unit is selected from options :


C, F, K, Engineering unit for
linear input only

L : CHANL
P:

Skip or scan channel


NO channel scanned
YES channel not scanned

Channel skip is stored and next


parameter is displayed.
Offset added to displayed Process
Variable
User selectable range
-125 to 125 (1 resolution)
-12.5 to 12.5 (0.1 resolution)
-1.25 to 1.25 (0.01 resolution)
-0.125 to 0.125 (0.001 resolution)
-0.0125 to 0.0125 (0.0001
resolution)
Display offset is stored and next
parameter is displayed.

11.4 Level Group


STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION
Selection of channel level from
options :
SP, INIT

38

Selection of level group

L : GROUP
P:

To enter in group level

L : GROUP
P : LEVEL LOCK

NO

L : GROUP
P : LEVEL LOCK

NO

Selection of level lock

L : GROUP
YES
P : LEVEL LOCK

Storing of level lock

L : GROUP
A
P : SELECT GROUP

First parameter in group level is


displayed.
Locks the level.
If the level is locked, parameters in
that level can be read but cannot be
changed.
NO Level is not locked
YES Level is locked
Level lock parameter is stored and
next parameter is displayed.

L : GROUP
A
P : SELECT GROUP

Selection of group no.

Select the number of groups

to
L : GROUP
P
P : SELECT GROUP

43

44

45

Storing of group no.

Selection of Unit for display

Storing of unit

L : GRP A
P : UNIT

L : GRP A
P : UNIT

L : GRP A
P : UNIT

L GRP A
P : UNIT

L : GRP A
P : UNIT

EU

L : GRP A
0.1
P : DIS RESOLUTION

Group no. is stored and next


parameter is displayed.

Unit is selected from options :


C, F, K, Engineering unit for
linear input only

Unit type is stored and next


parameter is displayed.

L : GRP A
1
P : DIS RESOLUTION
L : GRP A
0.1
P : DIS RESOLUTION

46

Selection of Display
resolution

L : GRP A
0.01
P : DIS RESOLUTION
L : GRP A
0.001
P : DIS RESOLUTION

Display resolution
1 resolution
0.1 resolution
0.01 resolution
(In case of LINEAR INPUT )
0.001 resolution
(In case of LINEAR INPUT )
0.0001 resolution
(In case of LINEAR INPUT )

MAN#241R1/P15/22/300908/A

L : GRP A
0.0001
P : DIS RESOLUTION

47

Storing of Display
resolution

L : GRP A
850
P : INPUT HI SCALE

Display resolution is stored and


next parameter is displayed.

47

Storing of Display
resolution

L : GRP A
850
P : INPUT HI SCALE

Display resolution is stored and


next parameter is displayed.

contd

contd

Level Group

STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION

48

Set high scale value for


selected channel

L : GRP A
850
P : INPUT HI SCALE

Adjust the high scale value for


selected channel

49

Storing of high scale value


for selected channel

L : GRP A
0
P : INPUT LO SCALE

High scale value is stored and next


parameter is displayed.

50

Set low scale value for


selected channel

L : GRP A
0
P : INPUT LO SCALE

Adjust the low scale value for


selected channel

51

Select channels from 1 8


in a group

L : GRPA NNNNNNNN
P : SELECT CH 1-8

Details are explained in 9.2

52

Select channels from 9


16 in a group

L : GRPA NNNNNNNN
P : SELECT CH 9-16

Details are explained in 9.2

53

Select setpoints from 1 8


in a group

L : GRPA NNNNNNNN
P : SELECT SP 1-8

Details are explained in 9.2

54

Select setpoints from 9


16 in a group

L : GRPA NNNNNNNN
P : SELECT SP 9-16

Details are explained in 9.2

11.5 Level Setpoint


STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION

33

Selection of level setpoint

L : SETPT
P:

Selection of channel level from


options :
INIT, CHANL, GROUP

3;

To enter in setpoint level

L : SETPT
NO
P : LEVEL LOCK

First parameter setpoint level is


displayed.

3<

38

39

Selection of level lock

Storing of level lock

Selection of setpoint no.

L : SETPT
YES
P : LEVEL LOCK

Locks the level.


If the level is locked, parameters in
that level can be read but cannot be
changed.
NO Level is not locked
YES Level is locked

L : SETPT GR A
P : SETPOINT NO.

Level lock parameter is stored and


next parameter is displayed.

L : SETPT GR A
P : SETPOINT NO.

L :SETPT
NO
P : LEVEL LOCK

to

Select the number of setpoints

MAN#241R1/P16/22/300908/A

L : SETPT GR A
16
P : SETPOINT NO.

Storing of setpoint no.

L : SP 1
50.0
P : SETPOINT VALUE

Setpoint no. is stored and next


parameter is displayed.

Setpoint value of selected


setpoint

L : SP 1
70.0
P : SETPOINT VALUE

Setpoint value is adjusted

contd

contd
STEP
NO.
;

Level Setpoint
DESCRIPTION
Storing of setpoint value

KEY TO BE
PRESSED

DISPLAY

ACTION

L : SP 1
0.1
P : HYSTERISIS

Setpoint value is stored and next


parameter is displayed.

Set hysterisis value of


selected setpoint

L : SP 1
1.1
P : HYSTERISIS

Hysteresis
User selectable range
0.1 - 99.9 (1 resolution)
0.01 - 9.99 (0.1 resolution)
0.001 - 0.999 (0.01 resolution)
0.0001 - 0.0999 (0.001 & 0.0001
resolution)

;:

Storing of hysterisis

L : SP 1
HEAT
P : RELAY LOGIC

Hysteresis is stored and next


parameter is displayed.

L : SP 1
NONE
P : RELAY LOGIC
L : SP 1
HI ALRM
P : RELAY LOGIC
L : SP 1
LO ALRM
P : RELAY LOGIC

;3

Selection of relay logic

L : SP 1
DEV HI
P : RELAY LOGIC
L : SP 1
DEV LO
P : RELAY LOGIC

SP operating mode
NONE - Indicator
HI ALRM - Full scale high alarm
LO ALRM - Full scale low alarm
DEV HI - Deviation high alarm
DEV LO - Deviation low alarm
IN BAND - In band alarm
OUT BND - Out band alarm

L : SP 1
IN BAND
P : RELAY LOGIC
L : SP 1
OUT BND
P : RELAY LOGIC

;;

Storing of relay logic

L : SP 1
SELFRST
P : ALARM TYPE

Relay logic is stored and next


parameter is displayed.

L : SP 1
SELFRST
P : ALARM TYPE
L : SP 1
LATCH
P : ALARM TYPE

;<

Selection of Alarm type


L : SP 1
HOLD
P : ALARM TYPE

Types of alarm SP
SELFRST - Autoreset alarm
LATCH - Alarm condition is latched
HOLD - Disable alarm on power
ON
LT+HOLD - Latch & Hold together

L : SP 1
LT+HOLD
P : ALARM TYPE

;8

;9

Storing of Alarm type

L : SP 1
NORMAL
P : RELAY ACTION

Alarm type is stored and next


parameter is displayed.

L : SP 1
NORMAL
P : RELAY ACTION

NORMAL - Relay ON below SP for


HEAT, above SP for HI ALARM, etc
REVERSE Relay OFF instead of
ON in above

Selection of Relay action

MAN#241R1/P17/22/300908/A

L : SP
REVERSE
P : RELAY ACTION

<

Storing of relay action

L : SP 1
ON
P : LED AT RELAY ON

Relay action is stored and next


parameter is displayed.

contd

contd
STEP
NO.

<

<

Level Setpoint
DESCRIPTION

KEY TO BE
PRESSED

DISPLAY
L : SP 1
ON
P : LED AT RELAY ON

Selection of LED at relay


on

L : SP 1
OFF
P : LED AT RELAY ON

Storing of LED at relay on


for selected channel

L : SETPT
P:

ACTION

LED indicator mode


ON - Relay ON, LED ON
OFF - Relay ON, LED OFF

LED at relay on is stored and next


parameter is displayed.

11.6 Level Calibration


Note : Do not proceed through this section unless there is definite need to re-calibrate the instrument. All previous calibration
data will be lost. Do not attempt recalibration unless you have available appropriate calibration equipment. If calibration data is
lost, you will need to return the instrument to your supplier who may charge you a service fee to recalibrate the instrument.

Press
key when Ver 53.XX is displayed in level init.
User calibration should be done for Channel 1
STEP
NO.

DESCRIPTION

KEY TO BE
PRESSED

DISPLAY

ACTION

<

Calibration level

L : CAL
P:

Level cal is selected

<:

To enter in cal level

L : CAL
OFF
P : USER CALIBRATE

Second parameter in cal level is


displayed.

L : CAL
OFF
P : USER CALIBRATE

<3

Calibration of channel1

L : CAL
ON
P : USER CALIBRATE

Select options
OFF Calibration off
ON Calibration on
DO Allows to do calibration

L : CAL
DO
P : USER CALIBRATE

<;

To do calibration of
channel1

L : CAL
DO
P : USER CALIBRATE

Allows to do calibration of channel1

<<

Feed low input from known


standard source (eg
microcal)

L : CAL
0.5
P : USERCAL LO.SCL

Press
key, uncalibrated low
value of input is displayed

<8

Adjust the display

L : CAL
0.0
P : USERCAL LO.SCL

Adjust the display till it corresponds


to the lower limit of input detected

<9

Feed high input from


known standard source (eg
microcal)

L : CAL
999.8
P : USERCAL HI.SCL

Press
key, uncalibrated high
value of input is displayed

Adjust the display

L : CAL
1000.0
P : USERCAL HI.SCL

Adjust the display till it corresponds


to the higher limit of input detected

MAN#241R1/P18/22/300908/A

L : CAL
NO
P : CALIBRATE EXIT

Calibration exit

To save calibration & exit

L : CAL
YES
P : CALIBRATE EXIT
L : CAL
YES
P : CALIBRATE EXIT

Select options
NO - Calibration is not saved
YES - Calibration is saved

Calibration is saved & enters in run


mode

11.7 Calibration of CJC


Note : Do not proceed through this section unless there is definite need to re-calibrate the instrument. All previous calibration
data will be lost. Do not attempt recalibration unless you have available appropriate calibration equipment. If calibration data is
lost, you will need to return the instrument to your supplier who may charge you a service fee to recalibrate the instrument.

Press
key when Ver 53.XX is displayed in level init.
CJC calibration should be done for Channel 1 & T/C K input type.
STEP
NO.

KEY TO BE
PRESSED

DESCRIPTION

DISPLAY

ACTION

Calibration level

L : CAL
P:

Level cal is selected

8:

To enter in cal level

L : CAL
24.7
P : CJC CALIBRATE

First parameter in cal level is


displayed.

83

Adjust the CJC of


instrument to room
temperature as per
standard source

L : CAL
26.0
P : CJC CALIBRATE

Adjust CJC

8;

To save calibration of CJC


& exit

L : CAL
26.0
P : CJC CALIBRATE

Adjusted CJC is stored & program


enters in run mode

12. TROUBLE SHOOTING


12.1 Error Messages
Display Symbol

PARAMETERS BAD
RESET BAD

Cause

Solution

This message can occur while exiting from


program mode. The cause is improper
selection of some parameter
This message occurs if input wires are not
connected or broken
This message occurs in case of negative
over range/ under range at input

13. DATA CORRUPTION

Press
key which will show the wrongly
selected parameter & its value, correct it

Check input signal


Check input wiring

PARAMETERS BAD

RESET BAD
In case of corruption of user programmed data, a message
& ProG Error is displayed on seven segment
display at power on & the instrument does not proceed further until the corrupted data is cleared by user.

If user wants to clear only the corrupted parameter, press

&

keys together to go to corrupted parameter.

If user wants to reset all parameters to their default values, then press & hold
change to reset all.

key & then press

&

key to

PARAMETERS BAD
RESET ALL

If you proceed further, all programmed parameters will be set to their default values. Instrument will require recalibration also.
After pressing

&

keys together, it displays

L : CH 1
NONE
P : INPUT TYPE

Instrument now requires initial selection which include input type.

MAN#241R1/P19/22/300908/A

Press & hold

key & then press

When selection is over, press

&
&

to select input. Select INPUT TYPE for all the channels.

keys together which will enable the instrument to enter run mode.

14. RS485 COMMUNICATION


For RS485 communication refer MODBUS/RTU & RS485 - INSTRUCTIONS FOR USE provided with this manual. The slave
ID of the instrument is set by programming of SLAVE ID parameter as explain in section 10.

15. SPECIFICATION
Specifications & features are subject to change without notice.
INPUTS
Maximum no. of
channels (X)
Input types
Thermocouple
RTD
Linear input

COMMUNICATION
Port

16
B, E, J, K, N, R, S, T
Pt100, 3-wire
0~50 mV, 0~20 mA, 4~20 mA
(each input independently
scaleable and without any DIP
reconfiguration)
< 1.6 seconds for 16 channels
lessSuitable for low (leakage)
voltages
than 3V AC

Channel scan rate


Channel-to-channel
isolation
Input protection
Thermocouple, mV,
RTD inputs
Current inputs
Range limits
Accuracy
Cold junction
compensation
Sensor break protection

10 V DC max
Current limit < 30 mA, 28 VDC max
See Sec 5
See Sec 5
Automatic
User programmable

CONTROL
Control functions
ONOFF control

Heat or Cool or Cool with


compressor time delay
(version 11.XX, 41.XX & 51.XX)
Alarm functions
High alarm
Low alarm
Deviation high alarm
Deviation low alarm
Inband alarm
Outband alarm
Control action
Direct / reverse
Hysteresis
0.1 - 99.9 C / F / EU
Compressor ON time delay 1 - 200 sec
Autoreset, Latch, Hold,
Alarm type
Latch + Hold
Latch (Ltch) Once relay gets ON, it remains
'ON' until alarm is acknowledged
by key.
Hold Alarm is disabled at power ON.
After process variable reaches
normal (non alarm) value, the
alarm is enabled.
Ltch.Hold Combination of Latch & Hold
logic.
OUTPUTS
Maximum no. of outputs
(Y)
Output type
Relay contact type
Relay contact rating

MAN#241R1/P20/22/300908/A

ADJUSTMENTS
Setpoint
Alarm
Unit
Resolution

#
AN ISO 9001:2000 COMPANY

Alarm status
Relay status
CALIBRATION
Zero & span

INDICATION
Display type

16
(8 inbuilt, 8 in external relay unit)
a) Electromagnetic relay
b) SSR drive
NO-C
5A / 230V AC, resistive

0.56 (15 mm), 7 - segment LED


and 2x16 character LCD display
Upper, 4 digit, LED display
Middle, 4 digit, LED display
Lower, 2 digit, LED display
16 LEDs for alarm, 16 LEDs for
relay status & 2x16 LCD

Process variable
Setpoint
Channel no.
Status indication
OTHER
Keypad
Memory for programmed
parameters
Field Connections
Plug-in Terminal Type
Supply voltage
Power consumption
Dimensions (in mm)
ISOSCAN-H
ISOSCAN-V
FLP ISOSCAN

Mounting

Read only
Read & write from the host
computer
Read only
Read only
Through front panel keys &
display
Sensor span and sensor zero
Room temperature

User calibration
CJC calibration

FLP enclosure

Full range adjustable


Full range adjustable
User selectable
User selectable
0.0001,0.001,0.01, 0.1or 1 for
linear input, 0.1 or 1 for
temperature

OTHER MAJOR
PARAMETERS
Setpoint lock
Level lock
Display scan rate
SKIP channel
Display channel

Baud rate
Protocol
Slave ID
Minimum polling interval
Parameters
Process variables
Setpoints

a) RS485, non-isolated
b) RS485, isolated
9600 bps
Modbus RTU
User programmable, 1~255
250 milliseconds

ISOSCAN-H
ISOSCAN-V
FLP ISOSCAN

Protection (FLP enclosure)


Operating ambient
temperature
Relative humidity

Membrane, tactile, 3 keys


Non-volatile, indefinite duration
Screw type connections in plug-in
terminals
a) Standard (Brass nickel plated)
b) Gold plated
a) 85~265 V AC, 50/60 hz
b) 24 V DC supply
5 watts
96(H)x192(W)x220(D)
192(H)x96(W)x220(D)
X8Y8 & below :
420(H)x365(W)x165(D)
X12Y0 & above :
500(H)x365(W)x165(D)
In panel cutout of 92x184 mm
In panel cutout of 184x92 mm
Surface
Certified flameproof for
gas groups I, IIA & IIB
IP55
0 - 50 C
Below 90%, non condensing

EXTERNAL RELAY UNIT


Dimensions
Mounting
PRINTER INTERFACE
Dimensions (in mm)
Mounting
Connection
Printer type
Dot Matrix

75(H)x100(W)x110(D)
Snap on for 35mm DIN rail to
DIN 46277
96(H)x96(W)x120(D)
In panel cutout of 92x92 mm
25 pin male D type connector
EPSON LX-300, LX-300+,
EPSON LX-800

1~99 seconds/channel