Subject :Tender Bulletin No.12

Dear Sirs, With reference to above mentioned tender, please find hereafter response to query raised by tenderers below.

Q1: The Employer is kindly requested to provide FX-VVIP-007_Dining Table detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A1: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF&
E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The Contractor
will be required to complete the Detailed Design while complying with the visual intent indicated on the design
documents and criteria stated in the Performance Specification.

Q2: The Employer is kindly requested to provide FX-VVIP-006_Dining Table detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A2: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q3: The Employer is kindly requested to provide FX-VVIP-004_Coffe Table detailed drawings which are aforementioned
as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A3: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q4: The Employer is kindly requested to provide FX-VVIP-003_Coffe Table detailed drawings which are aforementioned
as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A4: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q5: In PROPOSED LOGISTICS PLAN, except the StadiumSite, please confirm that contractor can use the two places
(areas in redcircle in attached drawing) for construction or not
A5: Yes these areas are identified for use by the Contractor.

Q6: Kindly provide the detailed drawing for Pumpingstation chamber for Storm & Foul water drain systems and as
mentioned inBOQ, Item C in Page 7.4.17_S34 - Page 1 of 3 and Item B, G & K in Page7.4.17_S34 - Page 2 of 3
A6: Tenderer to refer to Tender Bulletin 4 answer to question 2 & Tender Bulletin 5 answer to question 5
regarding Pricing Document Item C in Page 7.4.17_S34 - Page 1 of 3.There is no item G & K in Page 7.4.17_S34 Page 2 of 3 and item B is breaking hard surfaces and does not relate to Pumping Chambers. Tenderer to clarify.

Q7: Kindly provide the detailed drawing for RRFW asmentioned in BOQ, Item D in Page 7.4.17_S34 - Page 2 of 3
A7: There is no item D in 7.4.17_S34 - Page 2 of 3. Tenderer to clarify.

Q8: Kindly provide the detailed drawing for Storm &Foul water drain systems Drain runs indicating the diameter and
depth of thepipes as mentioned in BOQ, Item A in Page 7.4.17_S34 - Page 1 of 3 and Item Ain Page 7.4.17_S34 - Page
2 of 3.
A8: Tenderer to refer to Civils Proposed Storm Drainage Utility Layout Plan - C01-FOS-D- STA-T-CI-AL-AZ-1505
and Civils Proposed Foul Drainage Utility Layout Plan - C01-FOS-D- STA-T-CI-AL-AZ-1506 for Schematic Design
information. The Contractor will be required to complete the Detailed Design while complying design criteria
stated in the Performance Specification.

Q9: Kindly advise the location of "Duct / trench" as mentioned in BOQ Page 7.4.1_S11 Pages 1 of 3, Item A, B & C.
A9: Tenderer to refer to the following: Public Health Below Ground Drainage Services Details Sheet 4 - C01-FOSD- STA-T-DR-AL-AZ-5023 Public Health Level B4 Basement (B4) Zone 1 Below Ground Drainage Plan - C01-FOSD- STA-T-DR-B4-01-1001 Public Health Level B4 Basement (B4) Zone 3 Below Ground Drainage Plan - C01-FOSD- STA-T-DR-B4-03-1001The Contractor will be required to complete the Detailed Design while complying design
criteria stated in the Performance Specification.

Q10: The Employer is kindly requested to provide FX-VVIP-009_Bespoke sofa 2 detailed drawings which are

aforementioned as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.


A10: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q11: The Employer is kindly requested to provide FF& E detailed drawings which are mentioned in
'SCC01CAFFOSSPEAD00002_T1_Project Specification ReportSection 062023'.
A11: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. Tenderer to refer to Annexure 5 FF&
E Schedule and D2.2 Schematic Design Report , Section 4.1.7 Interior design for design intent. The Contractor
will be required to complete the Detailed Design while complying with the visual intent indicated on the design
documents and criteria stated in the Performance Specification.

Q12: The Employer is kindly requested to provide Credenza detailed drawings which are aforementioned as 'CO1-FOSD-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A12: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q13: Kindly provide the BOQ item & the Location of "Type ST-302 Stadium Seating - Easy Access"as mentioned in
Project Specification Report - Section 126000 - Clause 1.3.A.2.
A13: Tenderer to refer to Architectural drawing series Numbers & Seats for example Upper Tier Numbers & Seats
- C01-FOS-D-STA-T-AR-AL-AZ-1710. Tenderer to refer to Pricing Document 7.4.13_S2 and allow for any missing
items in the Tender Adjustment Schedule.

Q14: The FF&E Schedule reference SC-C01-CAF-FOS-REP-AR-00049 Rev T0 dated 03/04/2016, contains references to
various documents in the "Sheet Number" column. Please provide all the documents referenced within the schedule
which commence with "C01-FOS-D-STA-IN-".
A14: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. Tenderer to refer to Annexure 5 FF&
E Schedule for design intent and D2.2 Schematic Design Report , Section 4.1.7 Interior design.The Drawing
References are as follows C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP
Entrance Detailed Plan C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01FOS-D-STA-T-ID-VP-AZ-4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4002
VIP Lounge Entrance Interior Elevations & Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge
& Prayer Room General Details

Q15: The Employer is kindly requested to provide FX-VVIP-008_Bespoke-sofa 1 detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-ID-01-AZ-1003 & CO1-FOS-D-STA-T-ID-01-AZ-4003'.
A15: The drawings referred to in the query are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan
C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5
FF& E Schedule and D2.2 Schematic Design Report , Section 4.1.7 Interior design for design intent. The
Contractor will be required to complete the Detailed Design while complying with the visual intent indicated on
the design documents and criteria stated in the Performance Specification.

Q16: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Lower Plaza West (B3)D-B3-0003, D-B3-0004, D-B3-0005, D-B3-0007, D-B3-0065, D-B3-0066, D-B3-0073,
D-B3-0076, D-B3-0077, D-B3-0078, D-B3-0079, D-B3-0080, D-B3-0089, D-B3-0090, D-B3-0091, D-B3-0092, D-B3-0093,
D-B3-0094, D-B3-0184, D-B3-0247, D-B3-0254, D-B3-0263, D-B3-0264, D-B3-0265, D-B3-0266, D-B3-0267, D-B3-0268,
D-B3-0269, D-B3-0270, D-B3-0272, D-B3-0273, D-B3-0274, D-B3-0275, D-B3-0276, D-B3-0280, D-B3-1021, D-B3-1022
A16: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q17: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Lower Plaza (B2)D-B2-0033, D-B2-0042, D-B2-0127, D-B2-0129, D-B2-0135, D-B2-0199, D-B2-0200, D-B20202, D-B2-0203, D-B2-0206, D-B2-0208, D-B2-1035, D-B2-1055, D-B2-1057, D-B2-1063
A17: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q18: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Lower Plaza Mezzanine (B1)D-B1-0002, D-B1-0007, D-B1-0008, D-B1-1010, D-B1-1011, D-B1-1012
A18: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q19: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Upper Tier (04)D-04-0001, D-04-0002, D-04-0003, D-04-0004, D-04-0005, D-04-0006, D-04-0007, D-04-0008,
D-04-0009, D-04-0010, D-04-0011, D-04-0012, D-04-0013, D-04-0014, D-04-0015, D-04-0016, D-04-0017, D-04-0018,

D-04-0019, D-04-0020, D-04-0021, D-04-0022, D-04-0023, D-04-0024, D-04-0025, D-04-0026, D-04-0027, D-04-0028,
D-04-0029, D-04-0030, D-04-0031, D-04-0037, D-04-0038, D-04-0039, D-04-0040, D-04-0041, D-04-0042, D-04-0043,
D-04-0044, D-04-0045, D-04-0046, D-04-0047, D-04-0048, D-04-0049, D-04-0050, D-04-0051, D-04-0052, D-04-0053,
D-04-0054, D-04-0055, D-04-0056, D-04-0057, D-04-0058, D-04-0059, D-04-0061, D-04-0062, D-04-0063, D-04-0064,
D-04-0068, D-04-0069, D-04-0071, D-04-0072, D-04-0073, D-04-0074, D-04-0075, D-04-0076, D-04-0077, D-04-0078,
D-04-0079, D-04-0080, D-04-0081, D-04-0083, D-04-0084, D-04-0086, D-04-0087, D-04-0088, D-04-0089, D-04-0090,
D-04-0091, D-04-0092, D-04-0093, D-04-0094, D-04-0095, D-04-0096, D-04-0098, D-04-0099, D-04-0101, D-04-0102,
D-04-0103, D-04-0104, D-04-0105, D-04-0106, D-04-0107, D-04-0108, D-04-0109, D-04-0110, D-04-0111, D-04-0113,
D-04-0114, D-04-0126, D-04-0127, D-04-0128, D-04-0129, D-04-0133, D-04-0134, D-04-0135, D-04-0136, D-04-0137,
D-04-0138, D-04-0139, D-04-0140, D-04-0141, D-04-0142, D-04-0161, D-04-0162, D-04-0163, D-04-0164, D-04-0165,
D-04-0166, D-04-0167, D-04-0168, D-04-0169, D-04-0170, D-04-0171
A19: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q20: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL VIP Lounge (VP) MezzanineD-VP-0009, D-VP-0015, D-VP-0016, D-VP-0017, D-VP-0018, D-VP-0019, D-VP0020, D-VP-0021, D-VP-0022, D-VP-0023, D-VP-0024, D-VP-0025, D-VP-0026, D-VP-0027, D-VP-0028, D-VP-0029, DVP-0030, D-VP-0031
A20: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q21: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Emir (EM)D-EM-0025
A21: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q22: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Upper Tier (03)D-03-0001, D-03-0002, D-03-0003, D-03-0004, D-03-0007, D-03-0008, D-03-0009, D-03-0010,
D-03-0011, D-03-0012, D-03-0013, D-03-0014, D-03-0015, D-03-0016, D-03-0017, D-03-0018, D-03-0019, D-03-0020,
D-03-0021, D-03-0022, D-03-0023, D-03-0024, D-03-0025, D-03-0026, D-03-0027, D-03-0028, D-03-0029, D-03-0030,
D-03-0031, D-03-0032, D-03-0033, D-03-0034, D-03-0035, D-03-0036, D-03-0037, D-03-0038, D-03-0039, D-03-0040,
D-03-0041, D-03-0042, D-03-0043, D-03-0044, D-03-0045, D-03-0046, D-03-0047, D-03-0048, D-03-0049, D-03-0050,
D-03-0064, D-03-0065, D-03-0066, D-03-0067, D-03-0068, D-03-0069, D-03-0070, D-03-0071, D-03-0072, D-03-0073,
D-03-0074, D-03-0075, D-03-0076, D-03-0077, D-03-0078, D-03-0079, D-03-0080, D-03-0081, D-03-0082, D-03-0083,
D-03-0084, D-03-0085, D-03-0086, D-03-0087, D-03-0088, D-03-0089, D-03-0090, D-03-0091, D-03-0092, D-03-0093,
D-03-0094, D-03-0096, D-03-0097, D-03-0098, D-03-0099, D-03-0100, D-03-0101, D-03-0102, D-03-0103, D-03-0104,

D-03-0105, D-03-0108, D-03-0109, D-03-0110, D-03-0111, D-03-0112, D-03-0113, D-03-0114, D-03-0115, D-03-0116,
D-03-0117, D-03-0120, D-03-0121, D-03-0122, D-03-0123, D-03-0126, D-03-0127, D-03-0131, D-03-0132, D-03-0133,
D-03-0134, D-03-0135, D-03-0136, D-03-0143, D-03-0144, D-03-0145, D-03-0146, D-03-0147, D-03-0148, D-03-0149,
D-03-0150, D-03-0151, D-03-0152, D-03-0153, D-03-0154, D-03-0155, D-03-0156, D-03-0157, D-03-0158, D-03-0159,
D-03-0160, D-03-0161, D-03-0162, D-03-0163, D-03-0164, D-03-0165, D-03-0166, D-03-0167, D-03-0168, D-03-0169,
D-03-0170, D-03-0171, D-03-0172, D-03-0173, D-03-0174, D-03-0175, D-03-0176, D-03-0177, D-03-0178, D-03-0179,
D-03-0180, D-03-0181, D-03-0182, D-03-0183, D-03-0184, D-03-0185, D-03-0186, D-03-0187, D-03-0188, D-03-0189,
D-03-0190, D-03-0191, D-03-0192, D-03-0193, D-03-0194, D-03-0195, D-03-0196, D-03-0197, D-03-0198, D-03-0199,
D-03-0200, D-03-0201, D-03-0202, D-03-0203, D-03-0204, D-03-0205, D-03-0206, D-03-0207, D-03-0208, D-03-0209,
D-03-0210, D-03-0211, D-03-0212, D-03-0213, D-03-0214, D-03-0215, D-03-0233, D-03-0234, D-03-0235, D-03-0236,
D-03-0237, D-03-0238, D-03-0239, D-03-0240, D-03-0241, D-03-0242, D-03-0243, D-03-0244, D-03-0245, D-03-0246,
D-03-0247, D-03-0248, D-03-0249, D-03-0250, D-03-0251, D-03-0252, D-03-0253, D-03-0254, D-03-0255, D-03-0256,
D-03-0257, D-03-0258, D-03-0259, D-03-0260, D-03-0261, D-03-0262, D-03-0263, D-03-0264, D-03-0265, D-03-0266,
D-03-0267, D-03-0268, D-03-0269, D-03-0270, D-03-0271, D-03-0272, D-03-0273, D-03-0274, D-03-0275, D-03-0276,
D-03-0277, D-03-0278, D-03-0279, D-03-0280, D-03-0281, D-03-0282, D-03-0283, D-03-0284, D-03-0285, D-03-0286,
D-03-0287, D-03-0288, D-03-0289, D-03-0290, D-03-0291, D-03-0292, D-03-0293, D-03-0294, D-03-0295, D-03-0296,
D-03-0297, D-03-0298, D-03-0299, D-03-0300, D-03-0301, D-03-0302, D-03-0303, D-03-0304, D-03-0305, D-03-0306,
D-03-0307, D-03-0308, D-03-0309, D-03-0310, D-03-0311, D-03-0312, D-03-0313, D-03-0314, D-03-0315, D-03-0316,
D-03-0317, D-03-0318, D-03-0319, D-03-0320, D-03-0321, D-03-0322, D-03-0323, D-03-0324, D-03-0325, D-03-0326,
D-03-0327, D-03-0328, D-03-0329, D-03-0330, D-03-0331, D-03-0332, D-03-0333, D-03-0334, D-03-0335, D-03-0336,
D-03-0337, D-03-0338, D-03-0339, D-03-0340, D-03-0341, D-03-0342, D-03-0343, D-03-0344, D-03-0345, D-03-0346,
D-03-0347, D-03-0348, D-03-0349, D-03-0350, D-03-0351, D-03-0352, D-03-0353, D-03-0354, D-03-0355, D-03-0356,
D-03-0357, D-03-0358, D-03-0359, D-03-0360, D-03-0361, D-03-0362, D-03-0363, D-03-0364, D-03-0365, D-03-0366,
D-03-0367, D-03-0368, D-03-0369, D-03-0370, D-03-0371, D-03-0372, D-03-0373, D-03-0374, D-03-0375, D-03-0376,
D-03-0377, D-03-0378, D-03-0379, D-03-0380, D-03-0381, D-03-0382, D-03-0383, D-03-0384, D-03-0385, D-03-0386,
D-03-0387, D-03-0388, D-03-0389, D-03-0390, D-03-0391, D-03-0392, D-03-0393, D-03-0394, D-03-0395, D-03-0396,
D-03-0397, D-03-0398, D-03-0399, D-03-0400, D-03-0401, D-03-0402, D-03-0403, D-03-0404, D-03-0405, D-03-0406,
D-03-0407, D-03-0408, D-03-0409, D-03-0410, D-03-0411, D-03-0412, D-03-0413, D-03-0414, D-03-0415, D-03-0416,
D-03-0417, D-03-0418, D-03-0419, D-03-0420, D-03-0436, D-03-0437, D-03-0438, D-03-0439, D-03-0440, D-03-0441,
D-03-0442, D-03-0443, D-03-0444, D-03-0445, D-03-0446, D-03-0447, D-03-0448, D-03-0449, D-03-0450, D-03-0451,
D-03-0452, D-03-0453, D-03-0454, D-03-0568, D-03-0604, D-03-0605, D-03-0606, D-03-0607, D-03-0608, D-03-0609,
D-03-0611, D-03-0612, D-03-0613, D-03-0614, D-03-0615, D-03-0616, D-03-0617, D-03-0618, D-03-0619, D-03-0620,
D-03-0621, D-03-0622, D-03-0623, D-03-0624, D-03-0625, D-03-0626, D-03-0627, D-03-0628, D-03-0629, D-03-0630,
D-03-0631, D-03-0632, D-03-0633, D-03-0634, D-03-0635, D-03-0636, D-03-0637, D-03-0638, D-03-0639, D-03-0640,
D-03-0641, D-03-0642, D-03-0643, D-03-0644, D-03-0645, D-03-0646, D-03-0647, D-03-0648, D-03-0649, D-03-0650,
D-03-0651, D-03-0654, D-03-0655, D-03-0656, D-03-0657, D-03-0658, D-03-0659, D-03-0660, D-03-0661, D-03-0668,
D-03-0669, D-03-0670, D-03-0671, D-03-0672, D-03-0673, D-03-0674, D-03-0675, D-03-0676, D-03-0677, D-03-0678,
D-03-0679, D-03-0681, D-03-0682, D-03-0683, D-03-0684, D-03-0685, D-03-0686, D-03-0690, D-03-0691, D-03-0692,
D-03-0693, D-03-0694, D-03-0695, D-03-0696, D-03-0700, D-03-0701, D-03-0702, D-03-0703, D-03-0704, D-03-0705,
D-03-0709, D-03-1039, D-03-1117, D-03-1118, D-03-1119, D-03-1120, D-03-1121, D-03-1122, D-03-1124, D-03-1125,
D-03-1126, D-03-1127, D-03-1128, D-03-1129, D-03-1131, D-03-1132, D-03-1133, D-03-1134, D-03-1135, D-03-1136,
D-03-1138, D-03-1139, D-03-1140, D-03-1141, D-03-1142, D-03-1143
A22: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q23: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL 03 Plant 2 (P4)D-P4-1001, D-P4-1010
A23: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q24: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Plaza (PL)D-PL-0006, D-PL-0047, D-PL-0064, D-PL-0121, D-PL-0123, D-PL-0124, D-PL-0145, D-PL-0146, DPL-0147, D-PL-0170, D-PL-0171, D-PL-0173, D-PL-0174, D-PL-0183, D-PL-0185, D-PL-0189, D-PL-0190, D-PL-0191,
D-PL-0194, D-PL-0206, D-PL-0208, D-PL-0212, D-PL-0213, D-PL-0214, D-PL-0215, D-PL-0216, D-PL-0222, D-PL-0225,
D-PL-0227, D-PL-0230, D-PL-0232, D-PL-0233, D-PL-0235, D-PL-0236, D-PL-0237, D-PL-0238, D-PL-0239, D-PL-0240,
D-PL-0241, D-PL-0242, D-PL-0243, D-PL-0244, D-PL-0245, D-PL-0246, D-PL-0247, D-PL-0248, D-PL-0249, D-PL-0250,
D-PL-0251, D-PL-0252, D-PL-0253, D-PL-0254, D-PL-0255, D-PL-0256, D-PL-0257, D-PL-0258, D-PL-0259, D-PL-0260,
D-PL-0261, D-PL-0262, D-PL-0263, D-PL-0264, D-PL-0265, D-PL-0266, D-PL-0267, D-PL-0268, D-PL-0269, D-PL-0270,
D-PL-0271, D-PL-0272, D-PL-0273, D-PL-0274, D-PL-0275, D-PL-0276, D-PL-0282, D-PL-0297, D-PL-0302, D-PL-0303,
D-PL-0304, D-PL-0313, D-PL-0314, D-PL-0315, D-PL-0316, D-PL-0317, D-PL-0318, D-PL-0319, D-PL-0320, D-PL-0321,
D-PL-0322, D-PL-0323, D-PL-0324, D-PL-0325, D-PL-0326, D-PL-0327, D-PL-0328, D-PL-0329, D-PL-0330, D-PL-0331,
D-PL-0332, D-PL-0333, D-PL-0334, D-PL-0335, D-PL-0336, D-PL-0337, D-PL-0338, D-PL-0339, D-PL-0340, D-PL-0341,
D-PL-0342, D-PL-0343, D-PL-0344, D-PL-0345, D-PL-0346, D-PL-0347, D-PL-0348, D-PL-0349, D-PL-0350, D-PL-0351,
D-PL-0352, D-PL-0353, D-PL-0354, D-PL-0355, D-PL-0356, D-PL-0357, D-PL-0358, D-PL-0359, D-PL-0360, D-PL-0361,
D-PL-0362, D-PL-0363, D-PL-0364, D-PL-0365, D-PL-0366, D-PL-0367, D-PL-0368, D-PL-0369, D-PL-0370, D-PL-0371,
D-PL-0372, D-PL-0373, D-PL-0374, D-PL-0375, D-PL-0376, D-PL-0377, D-PL-0378, D-PL-0379, D-PL-0380, D-PL-0381,
D-PL-0382, D-PL-0383, D-PL-0384, D-PL-0385, D-PL-0386, D-PL-0387, D-PL-0388, D-PL-0389, D-PL-0390, D-PL-0391,
D-PL-0392, D-PL-0393, D-PL-0394, D-PL-0395, D-PL-0396, D-PL-0397, D-PL-0398, D-PL-0399, D-PL-0400, D-PL-0401,
D-PL-0402, D-PL-0403, D-PL-0404, D-PL-0405, D-PL-0406, D-PL-0407, D-PL-0408, D-PL-0409, D-PL-0410, D-PL-0411,
D-PL-0412, D-PL-0413, D-PL-0414, D-PL-0415, D-PL-0416, D-PL-0417, D-PL-0418, D-PL-0419, D-PL-0420, D-PL-0421,
D-PL-0422, D-PL-0423, D-PL-0424, D-PL-0425, D-PL-0426, D-PL-0427, D-PL-0428, D-PL-0429, D-PL-0430, D-PL-0431,
D-PL-0432, D-PL-0433, D-PL-0434, D-PL-0435, D-PL-0436, D-PL-0437, D-PL-0438, D-PL-0439, D-PL-0440, D-PL-0441,
D-PL-0442, D-PL-0443, D-PL-0444, D-PL-0445, D-PL-0446, D-PL-0447, D-PL-0448, D-PL-0449, D-PL-0450, D-PL-0451,
D-PL-0452, D-PL-0453, D-PL-0454, D-PL-0455, D-PL-0456, D-PL-0457, D-PL-0458, D-PL-0459, D-PL-0460, D-PL-0461,
D-PL-0462, D-PL-0463, D-PL-0464, D-PL-0465, D-PL-0466, D-PL-0467, D-PL-0468, D-PL-0469, D-PL-0470, D-PL-0471,
D-PL-0472, D-PL-0473, D-PL-0474, D-PL-0475, D-PL-0476, D-PL-0477, D-PL-0478, D-PL-0479, D-PL-0480, D-PL-0481,
D-PL-0482, D-PL-0483, D-PL-0484, D-PL-0485, D-PL-0486, D-PL-0487, D-PL-0488, D-PL-0489, D-PL-0490, D-PL-0491,
D-PL-0492, D-PL-0493, D-PL-0494, D-PL-0495, D-PL-0496, D-PL-0497, D-PL-0498, D-PL-0499, D-PL-0500, D-PL-0501,
D-PL-0502, D-PL-0503, D-PL-0504, D-PL-0505, D-PL-0506, D-PL-0507, D-PL-0508, D-PL-0509, D-PL-0510, D-PL-0511,
D-PL-0512, D-PL-0513, D-PL-0514, D-PL-0515, D-PL-0516, D-PL-0517, D-PL-0518, D-PL-0519, D-PL-0520, D-PL-0521,
D-PL-0522, D-PL-0523, D-PL-0524, D-PL-0525, D-PL-0526, D-PL-0527, D-PL-0528, D-PL-0529, D-PL-0530, D-PL-0531,
D-PL-0532, D-PL-0533, D-PL-0534, D-PL-0535, D-PL-0536, D-PL-0537, D-PL-0538, D-PL-0539, D-PL-0540, D-PL-0541,
D-PL-0542, D-PL-0543, D-PL-0544, D-PL-0545, D-PL-0546, D-PL-0547, D-PL-0548, D-PL-0549, D-PL-0550, D-PL-0551,
D-PL-0552, D-PL-0553, D-PL-0554, D-PL-0555, D-PL-0556, D-PL-0557, D-PL-0558, D-PL-0559, D-PL-0560, D-PL-0561,
D-PL-0562, D-PL-0563, D-PL-0564, D-PL-0565, D-PL-0566, D-PL-0567, D-PL-0568, D-PL-0569, D-PL-0570, D-PL-0571,
D-PL-0572, D-PL-0573, D-PL-0574, D-PL-0575, D-PL-0576, D-PL-0577, D-PL-0580, D-PL-0581, D-PL-0582, D-PL-0583,

D-PL-0584, D-PL-0585, D-PL-0586, D-PL-0587, D-PL-0588, D-PL-0589, D-PL-0590, D-PL-0591, D-PL-0601, D-PL-0602,
D-PL-0603, D-PL-0604, D-PL-0605, D-PL-0606, D-PL-0607, D-PL-0611, D-PL-0612, D-PL-0613, D-PL-0614, D-PL-0620,
D-PL-0621, D-PL-0623, D-PL-0624, D-PL-0625, D-PL-0626, D-PL-0627, D-PL-0628, D-PL-0629, D-PL-0630, D-PL-0631,
D-PL-0634, D-PL-0635, D-PL-0636, D-PL-0637, D-PL-0638, D-PL-0639, D-PL-0640, D-PL-0641, D-PL-0642, D-PL-1106,
D-PL-1108, D-PL-1111, D-PL-1112, D-PL-1116, D-PL-1133, D-PL-1134, D-PL-1135, D-PL-5043, D-PL-5135, D-PL-5240,
D-PL-5241, D-PL-5242, D-PL-5243, D-PL-5244, D-PL-5245, D-PL-5246, D-PL-5247, D-PL-5248, D-PL-5249, D-PL-5250,
D-PL-5251, D-PL-5252, D-PL-5253
A24: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q25: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Upper Tier (04)D-04-0001, D-04-0002, D-04-0003, D-04-0004, D-04-0005, D-04-0006, D-04-0007, D-04-0008,
D-04-0009, D-04-0010, D-04-0011, D-04-0012, D-04-0013, D-04-0014, D-04-0015, D-04-0016, D-04-0017, D-04-0018,
D-04-0019, D-04-0020, D-04-0021, D-04-0022, D-04-0023, D-04-0024, D-04-0025, D-04-0026, D-04-0027, D-04-0028,
D-04-0029, D-04-0030, D-04-0031, D-04-0037, D-04-0038, D-04-0039, D-04-0040, D-04-0041, D-04-0042, D-04-0043,
D-04-0044, D-04-0045, D-04-0046, D-04-0047, D-04-0048, D-04-0049, D-04-0050, D-04-0051, D-04-0052, D-04-0053,
D-04-0054, D-04-0055, D-04-0056, D-04-0057, D-04-0058, D-04-0059, D-04-0061, D-04-0062, D-04-0063, D-04-0064,
D-04-0068, D-04-0069, D-04-0071, D-04-0072, D-04-0073, D-04-0074, D-04-0075, D-04-0076, D-04-0077, D-04-0078,
D-04-0079, D-04-0080, D-04-0081, D-04-0083, D-04-0084, D-04-0086, D-04-0087, D-04-0088, D-04-0089, D-04-0090,
D-04-0091, D-04-0092, D-04-0093, D-04-0094, D-04-0095, D-04-0096, D-04-0098, D-04-0099, D-04-0101, D-04-0102,
D-04-0103, D-04-0104, D-04-0105, D-04-0106, D-04-0107, D-04-0108, D-04-0109, D-04-0110, D-04-0111, D-04-0113,
D-04-0114, D-04-0126, D-04-0127, D-04-0128, D-04-0129, D-04-0133, D-04-0134, D-04-0135, D-04-0136, D-04-0137,
D-04-0138, D-04-0139, D-04-0140, D-04-0141, D-04-0142, D-04-0161, D-04-0162, D-04-0163, D-04-0164, D-04-0165,
D-04-0166, D-04-0167, D-04-0168, D-04-0169, D-04-0170, D-04-0171
A25: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q26: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL 04 Plant (P5)D-P5-0057, D-P5-0058, D-P5-1003, D-P5-1004, D-P5-1005, D-P5-1007, D-P5-1009, D-P5-1011,
D-P5-1013, D-P5-1015, D-P5-1017
A26: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q27: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Hospitality Club (01)D-01-0080, D-01-0136, D-01-0137, D-01-0162, D-01-0163, D-01-0164, D-01-0165, D-010166, D-01-0167, D-01-0168, D-01-0169, D-01-0170, D-01-0171, D-01-0172, D-01-0173, D-01-0174, D-01-0175, D-01-

0179, D-01-0180, D-01-0181, D-01-0183, D-01-0189, D-01-0190, D-01-0191, D-01-0200, D-01-0201, D-01-0203, D-010206, D-01-0207, D-01-0208, D-01-0209, D-01-0210, D-01-0211, D-01-0212, D-01-0213, D-01-0214, D-01-0215, D-010216, D-01-0219, D-01-0220, D-01-0221, D-01-0222, D-01-0223, D-01-0224, D-01-0225, D-01-0226, D-01-0227, D-010228, D-01-0229, D-01-0230, D-01-0231, D-01-0232, D-01-0235, D-01-0236, D-01-0237, D-01-0238, D-01-0239, D-010240, D-01-0241, D-01-0242, D-01-0243, D-01-0244, D-01-0245, D-01-0253, D-01-0254, D-01-0255, D-01-0256, D-010257, D-01-0258, D-01-0259, D-01-0260, D-01-0268, D-01-0269, D-01-0270, D-01-0271, D-01-0272, D-01-0273, D-010274, D-01-0275, D-01-0283, D-01-0284, D-01-0285, D-01-0286, D-01-0287, D-01-0288, D-01-0289, D-01-0290, D-010298, D-01-0299, D-01-0300, D-01-0301, D-01-0302, D-01-0303, D-01-0304, D-01-0305, D-01-0306, D-01-0307, D-010308, D-01-0309, D-01-0310, D-01-0311, D-01-0316, D-01-0317, D-01-0318, D-01-0319, D-01-0320, D-01-0321, D-010322, D-01-0323, D-01-0324, D-01-0325, D-01-0326, D-01-0327, D-01-0328, D-01-0329, D-01-0336, D-01-0338, D-010339, D-01-0340, D-01-0341, D-01-0342, D-01-0345, D-01-0347, D-01-0348, D-01-0349, D-01-0350, D-01-0351, D-010354, D-01-0355, D-01-0356, D-01-0357, D-01-0358, D-01-0359, D-01-0360, D-01-0361, D-01-0362, D-01-0363, D-010364, D-01-0366, D-01-0367, D-01-0371, D-01-0372, D-01-0373, D-01-0374, D-01-0376, D-01-0377, D-01-0381, D-010382, D-01-0383, D-01-0384, D-01-0386, D-01-0387, D-01-0391, D-01-0392, D-01-0393, D-01-0394, D-01-0395, D-010396, D-01-0397, D-01-0401, D-01-0402, D-01-0403, D-01-0404, D-01-0405, D-01-0406, D-01-0407, D-01-0408, D-010411, D-01-0415, D-01-0416, D-01-0417, D-01-0418, D-01-0419, D-01-0420, D-01-0421, D-01-0422, D-01-0423, D-011001, D-01-1003, D-01-1004, D-01-1005, D-01-1006, D-01-1007, D-01-1008, D-01-1010, D-01-1019, D-01-1029, D-011039, D-01-1040, D-01-1053, D-01-1057, D-01-1058, D-01-1059, D-01-1060, D-01-1061, D-01-1062, D-01-1082, D-011083, D-01-1104, D-01-1105
A27: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q28: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL Hospitality Sky Boxes (02)D-02-0003, D-02-0004, D-02-0006, D-02-0007, D-02-0008, D-02-0009, D-02-0012,
D-02-0015, D-02-0016, D-02-0018, D-02-0019, D-02-0020, D-02-0021, D-02-0022, D-02-0023, D-02-0024, D-02-0025,
D-02-0028, D-02-0030, D-02-0032, D-02-0041, D-02-0043, D-02-0044, D-02-0045, D-02-0046, D-02-0051, D-02-0052,
D-02-0054, D-02-0055, D-02-0058, D-02-0060, D-02-0062, D-02-0063, D-02-0066, D-02-0067, D-02-0069, D-02-0071,
D-02-0074, D-02-0075, D-02-0081, D-02-0090, D-02-0091, D-02-0191, D-02-0192, D-02-0230, D-02-0244, D-02-0245,
D-02-0246, D-02-0248, D-02-0249, D-02-0251, D-02-0252, D-02-0257, D-02-0261, D-02-0262, D-02-0263, D-02-0264,
D-02-0265, D-02-0266, D-02-0267, D-02-0268, D-02-0269, D-02-0270, D-02-0271, D-02-0272, D-02-0273, D-02-0274,
D-02-0275, D-02-0276, D-02-0277, D-02-0278, D-02-0279, D-02-0280, D-02-0281, D-02-0282, D-02-0283, D-02-0284,
D-02-0285, D-02-0286, D-02-0287, D-02-0288, D-02-0289, D-02-0292, D-02-0293, D-02-0294, D-02-0295, D-02-0296,
D-02-0297, D-02-0298, D-02-0299, D-02-0300, D-02-0301, D-02-0303, D-02-0304, D-02-0305, D-02-0306, D-02-0307,
D-02-0308, D-02-0309, D-02-0313, D-02-0339, D-02-0340, D-02-0341, D-02-0343, D-02-0344, D-02-0345, D-02-0357,
D-02-0364, D-02-0366, D-02-0367, D-02-0368, D-02-0369, D-02-0370, D-02-1014
A28: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q29: There is a large discrepancy between the number of doors in the drawing and door schedule. The doors have been
counted based on the Architectural Drawings at floor levels.When we compare the 'Door schedule' and 'Drawings',We
could not locate the doors which are listed as below.The Employer is kindly requested to confirm the number of
doors.FFL 02 Plant (P2)D-P2-0011, D-P2-0012, D-P2-0013, D-P2-0029, D-P2-0030, D-P2-0032, D-P2-0034, D-P2-0035,

D-P2-0036, D-P2-0037, D-P2-0038, D-P2-0039, D-P2-1013, D-P2-1021, D-P2-1022, D-P2-1023


A29: Tenderer to follow the drawings and base their door count accordingly. Any modifications to the Pricing
Document to be accounted for in the Tender Adjustment Schedule.

Q30: The Employer is kindly requested to confirm the ceiling type CLG-901 if this is a top and bottom panel as per shown
in dwg C01-FOS-D-STA-C-AR-AL-AZ-5508 dtl 2 & 3, and dwg C01-FOS-D-STA-C-AR-Al-AZ-5512 dtl 2 & 3. If so, the top
and bottom panel are the same material?
A30: Tenderer to refer to D2.4 Specification Section 074243 - Composite Wall Panels Part 2.1A.

Q31: The Employer is kindly requested to confirm the ceiling type CLG-901 if this is a top and bottom panel as per shown
in dwg C01-FOS-D-STA-C-AR-AL-AZ-5508 dtl 2 & 3, and dwg C01-FOS-D-STA-C-AR-Al-AZ-5512 dtl 2 & 3. If so, the top
and bottom panel are the same material?
A31: Tenderer to refer to D2.4 Specification Section 074243 - Composite Wall Panels Part 2.1A.

Q32: The Employer is kindly requested to provide FX-701_Bespoke sink counter detailed drawings.
A32: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report , Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q33: The Employer is kindly requested to provide Dressing Bench detailed drawings which are aforementioned as 'CO1FOS-D-STA-T-IN-PL-AZ-1209 & CO1-FOS-D-STA-T-IN-B3-AZ-5202 & CO1-FOS-D-STA-T-IN-B3-AZ-4202'.
A33: Drawing Reference should be C01-FOS-D-STA-T-ID-B3-AZ-1203 Changing Rooms Detailed Plan and RCP &
C01-FOS-D-STA-T-ID-B3-AZ-4202 Changing Rooms Interior Elevations. Tenderer to refer to Annexure 5 FF& E
Schedule for design intent and D2.2 Schematic Design Report , Section 4.1.7 Interior design.

Q34: The Employer is kindly requested to provide Dressing Screens detailed drawings which are aforementioned as
'CO1-FOS-D-STA-T-IN-PL-AZ-1209 & CO1-FOS-D-STA-T-IN-B3-AZ-5202 & CO1-FOS-D-STA-T-IN-B3-AZ-4202'.
A34: Drawing Reference should be C01-FOS-D-STA-T-ID-B3-AZ-1203 Changing Rooms Detailed Plan and RCP &
C01-FOS-D-STA-T-ID-B3-AZ-4202 Changing Rooms Interior Elevations. Tenderer to refer to Annexure 5 FF& E
Schedule for design intent and D2.2 Schematic Design Report , Section 4.1.7 Interior design.The Contractor will
be required to complete the Detailed Design while complying with the visual intent indicated on the design
documents and criteria stated in the Performance Specification.

Q35: The Employer is kindly requested to provide FX-703_Basin counter detailed drawings.
A35: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report , Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q36: The Employer is kindly requested to provideFX-702_Wall Joinery Unit detailed drawings which are aforementioned
as 'CO1-FOS-D-STA-T-IN-PL-AZ-1209 & CO1-FOS-D-STA-T-IN-B3-AZ-5202 & CO1-FOS-D-STA-T-IN-B3-AZ-4202'.
A36: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The Drawing References are as
follows: C01-FOS-D-STA-T-ID-B3-AZ-1203 Changing Rooms Detailed Plan and RCP C01-FOS-D-STA-T-ID-B3-AZ4202 Changing Rooms Interior ElevationsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q37: The Employer is kindly requested to provide FX-704_Bespoke sink counter detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-01-AZ-1201'.
A37: Drawing Reference should be Typical VVIP & Emir Toilet Detailed Plan & RCP, Interior Elevations and
Sections - C01-FOS-D-STA-T-ID-01-AZ-4202. Tenderer to refer to Annexure 5 FF& E Schedule for design intent
and D2.2 Schematic Design Report, Section 4.1.7 Interior design. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q38: The Employer is kindly requested to provide FX-705_Bespoke buffet counter detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-INVP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A38: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4003 Interior Emir & VVIP
Entrance Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer
Room General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q39: The Employer is kindly requested to provide FX-706_Bespoke built in banquette 1 detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-INVP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A39: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4003 Interior Emir & VVIP

Entrance Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer
Room General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q40: The Employer is kindly requested to provide FX-707_Bespoke built in banquette 2 detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-INVP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A40: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4003 Interior Emir & VVIP
Entrance Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer
Room General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q41: In the above mentioned specification, blockwork unit materials have beenreferred to ACICO block units
manufactured by QATAR ACICO or acceptableequivalent. The referred manufacturer primarily produces AACaeratedautoclaved concrete units.So, we understand that the intention is to utilize light weight block unitsrather than
standard concrete masonry although properties of standard concreteunits are given in the specification. Please confirm
that AAC-aerated autoclaved concrete units shall beutilized instead of standard concrete units.
A41: Tenderer to refer to Tender Bulletin 11 answer to questions 50, 51, 52 & 53.

Q42: As per D21A7_Master_Systems_List-Resp_Matrix document, We understood thatContractor will be responsible


only for infrastructure (cameras, cabling, cabletray, conduits, poles, power supply for cameras etc) and The backend
system(active switches, storages, servers, softwares,etc) will be provided byEngineer. Please kindly confirm that our
understanding is correct or not?
A42: Contractor is responsible for the following ICT and as required in the Employer's requirements:- Obtaining
MOI approval for the CCTV design and installations.- Camera supply and installations (SC materials approvals
are required).- Any related Infrastructure (Cabling, trays, conduits, power supply, and CCTV dedicated racks,
etc.).Rest of Backend systems (Servers, storage, software, etc.) will be provided by the Engineer as part of SC
programme wide systems.

Q43: SC-C01-CAB-FOS-SCH-AR-00028_T0_Door Schedule & C01-FOS-D-STA-T-AR-B2-01-1000 & C01-FOS-D-STAT-AR-B2-03-1000Door references for the Areas not assigned at the Lower Plaza (B2) Zone 1 and Zone 3 are not shown
in the drawing ref. C01-FOS-D-STA-T-AR-B2-01-1000 and C01-FOS-D-STA-T-AR-B2-03-1000.Please provide T-Sheets
Code, Door type, Fire Rating and Acoustic Rating for these doors.

A43: Tenderer to refer to Tender Bulletin 11 answer to question 37

Q44: The Employer is kindly requested to provide FX-708_Bespoke central round bar detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-INVP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A44: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4003 Interior Emir & VVIP
Entrance Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer
Room General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q45: The Employer is kindly requested to provide FX-709_Reception desk detailed drawings which are aforementioned
as 'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 &
CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A45: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4003 Interior Emir & VVIP
Entrance Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer
Room General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q46: The Employer is kindly requested to provide Dividing Credenca detailed drawings which are aforementioned as
'CO1-FOS-D-STA-T-IN-PL-AZ-1010 & CO1-FOS-D-STA-T-IN-PL-AZ-4002 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 &
CO1-FOS-D-STA-T-IN-VP-AZ-4001 & CO1-FOS-D-STA-T-IN-VP-AZ-5000'.
A46: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The Drawing References are as
follows: C01-FOS-D-STA-T-ID-PL-AZ-1011 - Interior Plaza Level VIP Lounge, Emir & VVIP Entrance Detailed Plan
C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ4001 VIP Lounge Interior Elevations and Sections 02 C01-FOS-D-STA-T-ID-PL-AZ-4002 VIP Lounge Entrance
Interior Elevations & Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 VIP/VVIP and Emir Lounge & Prayer Room
General DetailsTenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7
Interior design for design intent. The Contractor will be required to complete the Detailed Design while
complying with the visual intent indicated on the design documents and criteria stated in the Performance

Specification.

Q47: The Employer is kindly requested to provide FX-710_Counter detailed drawings which are aforementioned as 'CO1FOS-D-STA-T-AR-PL-AZ-1000'.
A47: The drawings referred to in the query is C01-FOS-D-STA-T-AR-PL-AZ-1000 Architectural Plaza (PL), other
related drawings are: C01-FOS-D-STA-T-AR-PL-01-1000 - Plaza (PL) Zone 1 C01-FOS-D-STA-T-AR-PL-02-1000 Plaza (PL) Zone 2 C01-FOS-D-STA-T-AR-PL-03-1000 - Plaza (PL) Zone 3 C01-FOS-D-STA-T-AR-PL-04-1000 - Plaza
(PL) Zone 4Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7
Interior design for design intent. The Contractor will be required to complete the Detailed Design while
complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q48: The Employer is kindly requested to provide FX-711_Reception Counter detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-AR-PL-AZ-1000'.
A48: The drawings referred to in the query is C01-FOS-D-STA-T-AR-PL-AZ-1000 Architectural Plaza (PL), other
related drawings are: C01-FOS-D-STA-T-AR-PL-01-1000 - Plaza (PL) Zone 1 C01-FOS-D-STA-T-AR-PL-02-1000 Plaza (PL) Zone 2 C01-FOS-D-STA-T-AR-PL-03-1000 - Plaza (PL) Zone 3 C01-FOS-D-STA-T-AR-PL-04-1000 - Plaza
(PL) Zone 4Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7
Interior design for design intent. The Contractor will be required to complete the Detailed Design while
complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q49: The Employer is kindly requested to provide FX-712_Reception Counter detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-AR-PL-AZ-1000'.
A49: The drawings referred to in the query is C01-FOS-D-STA-T-AR-PL-AZ-1000 Architectural Plaza (PL), other
related drawings are: C01-FOS-D-STA-T-AR-PL-01-1000 - Plaza (PL) Zone 1 C01-FOS-D-STA-T-AR-PL-02-1000 Plaza (PL) Zone 2 C01-FOS-D-STA-T-AR-PL-03-1000 - Plaza (PL) Zone 3 C01-FOS-D-STA-T-AR-PL-04-1000 - Plaza
(PL) Zone 4Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7
Interior design for design intent. The Contractor will be required to complete the Detailed Design while
complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q50: The Employer is kindly requested to provide FX-713_Bar detailed drawings which are aforementioned as 'CO1FOS-D-STA-T-IN-VP-AZ-1006 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001'.
A50: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The drawings referred to in the
query are: C01-FOS-D-STA-T-ID-VP-AZ-1006 - MZ VIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ-4001 - VIP Lounge Interior
Elevations and Sections 02 Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design

while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q51: The Employer is kindly requested to provide Posseur Table (6-8 people) detailed drawings which are
aforementioned as 'CO1-FOS-D-STA-T-IN-VP-AZ-1006 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 & CO1-FOS-D-STA-T-INVP-AZ-4001'.
A51: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The drawings referred to in the
query are: C01-FOS-D-STA-T-ID-VP-AZ-1006 - MZ VIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ-4001 - VIP Lounge Interior
Elevations and Sections 02 Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q52: The Employer is kindly requested to provide FX-714_Balustrade-Bar detailed drawings which are aforementioned
as 'CO1-FOS-D-STA-T-IN-VP-AZ-1006 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001'.
A52: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The drawings referred to in the
query are: C01-FOS-D-STA-T-ID-VP-AZ-1006 - MZ VIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ-4001 - VIP Lounge Interior
Elevations and Sections 02 Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q53: The Employer is kindly requested to provide Banquette seat detailed drawings which are aforementioned as 'CO1FOS-D-STA-T-IN-VP-AZ-1006 & CO1-FOS-D-STA-T-IN-VP-AZ-4000 & CO1-FOS-D-STA-T-IN-VP-AZ-4001'.
A53: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX. The drawings referred to in the
query are: C01-FOS-D-STA-T-ID-VP-AZ-1006 - MZ VIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-VP-AZ-4000 VIP Lounge Interior Elevations and Sections 01 C01-FOS-D-STA-T-ID-VP-AZ-4001 - VIP Lounge Interior
Elevations and Sections 02 Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report,
Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the Detailed Design
while complying with the visual intent indicated on the design documents and criteria stated in the Performance
Specification.

Q54: The Employer is kindly requested to provide FX-715_Bespoke vanity unit detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.

A54: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q55: The Employer is kindly requested to provide FX-716_Bespoke-alcove seats A detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A55: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002 - VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q56: The Employer is kindly requested to provide FX-717_Bespoke-alcove seats B detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A56: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q57: The Employer is kindly requested to provide FX-718_Bespoke-reception desk detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A57: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 -

Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q58: The Employer is kindly requested to provide FX-719_Reception stand detailed drawings which are aforementioned
as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-IN-EM-AZ-4002 &
C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A58: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q59: The Employer is kindly requested to provide FX-720_Screen partition A detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A59: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q60: The Employer is kindly requested to provide FX-721_Screen partition B detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-EM-AZ-1001& C01-FOS-D-STA-T-IN-EM-AZ-4001 & C01-FOS-D-STA-T-INEM-AZ-4002 & C01-FOS-D-STA-T-IN-EM-AZ-5002'.
A60: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-EM-AZ-1001 - Emir Lounge Detailed Plan & RCP C01-FOS-D-STA-T-ID-EM-AZ-4001 Emir Lounge, Emir Room, Protocol Office Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-4002 Emir Lounge, Royal Box Interior Elevations and Sections C01-FOS-D-STA-T-ID-EM-AZ-5002- -VIP/VVIP and Emir
Lounge & Prayer Room General Details Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic

Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q61: The Employer is kindly requested to provide FX-722_Banquette-seating detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-01-AZ-1003 & C01-FOS-D-STA-T-IN-01-AZ-4003'.
A61: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP
Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q62: The Employer is kindly requested to provide FX-723_Bespoke-VVIP-Raised_sofa detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-01-AZ-1003 & C01-FOS-D-STA-T-IN-01-AZ-4003'.
A62: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP
Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q63: The Employer is kindly requested to provide FX-724_Decorative screens A detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-01-AZ-1003 & C01-FOS-D-STA-T-IN-01-AZ-4003'.
A63: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP
Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report , Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q64: The Employer is kindly requested to provide FX-725_Decorative screens B detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-01-AZ-1003 & C01-FOS-D-STA-T-IN-01-AZ-4003'.
A64: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP
Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic

Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q65: The Employer is kindly requested to provide FX-726_Decorative screens C detailed drawings which are
aforementioned as 'C01-FOS-D-STA-T-IN-01-AZ-1003 & C01-FOS-D-STA-T-IN-01-AZ-4003'.
A65: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1003 - VVIP Lounge Detailed Plan C01-FOS-D-STA-T-ID-01-AZ-4003 - VVIP
Lounge Interior Elevations and Sections Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic
Design Report, Section 4.1.7 Interior design for design intent. The Contractor will be required to complete the
Detailed Design while complying with the visual intent indicated on the design documents and criteria stated in
the Performance Specification.

Q66: The Employer is kindly requested to provide FX-727_Counter detailed drawings.


A66: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q67: The Employer is kindly requested to provide FX-728_Reception Counter detailed drawings.
A67: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q68: The Employer is kindly requested to provide FX-729_Bespoke sink counter detailed drawings.
A68: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q69: The Employer is kindly requested to provide FX-730_Counter detailed drawings.


A69: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q70: The Employer is kindly requested to provide FX-731_Reception counter detailed drawings.
A70: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with

the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q71: The Employer is kindly requested to provide FX-733_Bespoke cupboard /cloakroom detailed drawings.
A71: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q72: The Employer is kindly requested to provide FX-734_Bespoke sink counter detailed drawings.
A72: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q73: The Employer is kindly requested to provide FX-735_Counter detailed drawings.


A73: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.

Q74: The Employer is kindly requested to provide FX-736_Bar detailed drawings which are aforementioned as 'CO1FOS-D-STA-T-IN-01-AZ-1005 & CO1-FOS-D-STA-T-IN-01-AZ-4000'.
A74: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1005 East Central Hospitality Lounge 1 - Detailed Plan & RCP 7 C01-FOS-DSTA-T-ID-01-AZ-4000 East Central Hospitality Lounge 1 - Interior Elevations and Sections. Tenderer to refer to
Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent.
The Contractor will be required to complete the Detailed Design while complying with the visual intent indicated
on the design documents and criteria stated in the Performance Specification.

Q75: The Employer is kindly requested to provide FX-737_Fixed seating detailed drawings which are aforementioned as
'CO1-FOS-D-STA-T-IN-01-AZ-1005 & CO1-FOS-D-STA-T-IN-01-AZ-4000'.
A75: Tenderer to refer to Tender Bulletin 3 answer to Query 7 (2). There are no IN series drawing, therefore C01FOS-D-STA-T-IN XX-XX-XXXX should be C01-FOS-D-STA-T-ID-XX-XX-XXXX.The drawings referred to in the query
are: C01-FOS-D-STA-T-ID-01-AZ-1005 East Central Hospitality Lounge 1 - Detailed Plan & RCP 7 C01-FOS-DSTA-T-ID-01-AZ-4000 East Central Hospitality Lounge 1 - Interior Elevations and Sections. Tenderer to refer to
Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior design for design intent.
The Contractor will be required to complete the Detailed Design while complying with the visual intent indicated
on the design documents and criteria stated in the Performance Specification.

Q76: The Employer is kindly requested to provide FX-501_Bespoke sink counter detailed drawings.
A76: Tenderer to refer to Annexure 5 FF& E Schedule and D2.2 Schematic Design Report, Section 4.1.7 Interior
design for design intent. The Contractor will be required to complete the Detailed Design while complying with
the visual intent indicated on the design documents and criteria stated in the Performance Specification.