Sei sulla pagina 1di 4

SIMATIC S7 S7-1200 Programmable controller

CPU 1214C wiring diagrams

CPU 1214C wiring diagrams


Table 1

CPU 1214C AC/DC/Relay (6ES7 214-1BG40-0XB0)

24 VDC Sensor Power


Out
For additional noise
immunity, connect "M" to
chassis ground even if
not using sensor supply.

For sinking inputs,


connect "-" to
"M" (shown).
For sourcing inputs,
connect "+" to "M".

Note 1: X11 connectors must


be gold. See Appendix C,
Spare Parts for order number.
Note 2: Either the L1 or N (L2)
terminal can be connected to
a voltage source up to 240
VAC. The N terminal can be
considered L2 and is not
required to be grounded. No
polarization is required for L1
and N (L2) terminals.
Table 2

Connector pin locations for CPU 1214C AC/DC/Relay (6ES7 214-1BG40-0XB0)


Pin

X10

X11 (gold)

X12

L1 / 120-240 VAC

2M

1L

N / 120-240 VAC

AI 0

DQ a.0

Functional Earth

AI 1

DQ a.1

L+ / 24 VDC Sensor Out

--

DQ a.2

M / 24 VDC Sensor Out

--

DQ a.3

1M

--

DQ a.4

DI a.0

--

2L

DI a.1

--

DQ a.5

DI a.2

--

DQ a.6

10

DI a.3

--

DQ a.7

11

DI a.4

--

DQ b.0

12

DI a.5

--

DQ b.1

Este documento es un extracto gratuito, compilado por el propio usuario, de la documentacin ofrecida por Siemens para este producto. Se declina cualquier
responsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.
La documentacin completa est disponible en
/dokumentation/default.aspx?DocVersionId=62121591435&Language=en-US&TopicId=60466702475
1/21/2016

SIMATIC S7 S7-1200 Programmable controller


CPU 1214C wiring diagrams

Pin

X10

X11 (gold)

X12

13

DI a.6

--

--

14

DI a.7

--

--

15

DI b.0

--

--

16

DI b.1

--

--

17

DI b.2

--

--

18

DI b.3

--

--

19

DI b.4

--

--

20

DI b.5

--

--

Table 3

CPU 1214C DC/DC/Relay (6ES7 214-1HG40-0XB0)

24 VDC Sensor Power


Out
For additional noise
immunity, connect "M" to
chassis ground even if
not using sensor supply.

For sinking inputs,


connect "-" to
"M" (shown).
For sourcing inputs,
connect "+" to "M".

Note: X11 connectors must be


gold. See Appendix C, Spare
Parts for order number.

Table 4

Connector pin locations for CPU 1214C DC/DC/Relay (6ES7 214-1HG40-0XB0)


Pin

X10

X11 (gold)

X12

L+ / 24 VDC

2M

1L

M / 24 VDC

AI 0

DQ a.0

Functional Earth

AI 1

DQ a.1

L+ / 24 VDC Sensor Out

--

DQ a.2

M / 24 VDC Sensor Out

--

DQ a.3

1M

--

DQ a.4

DI a.0

--

2L

DI a.1

--

DQ a.5

Este documento es un extracto gratuito, compilado por el propio usuario, de la documentacin ofrecida por Siemens para este producto. Se declina cualquier
responsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.
La documentacin completa est disponible en
/dokumentation/default.aspx?DocVersionId=62121591435&Language=en-US&TopicId=60466702475
1/21/2016

SIMATIC S7 S7-1200 Programmable controller


CPU 1214C wiring diagrams

Pin

X10

X11 (gold)

X12

DI a.2

--

DQ a.6

10

DI a.3

--

DQ a.7

11

DI a.4

--

DQ b.0

12

DI a.5

--

DQ b.1

13

DI a.6

--

--

14

DI a.7

--

--

15

DI b.0

--

--

16

DI b.1

--

--

17

DI b.2

--

--

18

DI b.3

--

--

19

DI b.4

--

--

20

DI b.5

--

--

Table 5

CPU 1214C DC/DC/DC (6ES7 214-1AG40-0XB0)

24 VDC Sensor Power


Out
For additional noise
immunity, connect "M" to
chassis ground even if
not using sensor supply.

For sinking inputs,


connect "-" to
"M" (shown).
For sourcing inputs,
connect "+" to "M".

Note: X11 connectors must be


gold. See Appendix C, Spare
Parts for order number.

Table 6

Connector pin locations for CPU 1214C DC/DC/DC (6ES7 214-1AG40-0XB0)


Pin

X10

X11 (gold)

X12

L+ / 24 VDC

2M

3L+

M / 24 VDC

AI 0

3M

Functional Earth

AI 1

DQ a.0

L+ / 24 VDC Sensor Out

--

DQ a.1

Este documento es un extracto gratuito, compilado por el propio usuario, de la documentacin ofrecida por Siemens para este producto. Se declina cualquier
responsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.
La documentacin completa est disponible en
/dokumentation/default.aspx?DocVersionId=62121591435&Language=en-US&TopicId=60466702475
1/21/2016

SIMATIC S7 S7-1200 Programmable controller


CPU 1214C wiring diagrams

Pin

X10

X11 (gold)

X12

M / 24 VDC Sensor Out

--

DQ a.2

1M

--

DQ a.3

DI a.0

--

DQ a.4

DI a.1

--

DQ a.5

DI a.2

--

DQ a.6

10

DI a.3

--

DQ a.7

11

DI a.4

--

DQ b.0

12

DI a.5

--

DQ b.1

13

DI a.6

--

--

14

DI a.7

--

15

DI b.0

--

--

16

DI b.1

--

--

17

DI b.2

--

--

18

DI b.3

--

--

19

DI b.4

--

--

20

DI b.5

--

--

Note
Unused analog inputs should be shorted.

Este documento es un extracto gratuito, compilado por el propio usuario, de la documentacin ofrecida por Siemens para este producto. Se declina cualquier
responsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.
La documentacin completa est disponible en
/dokumentation/default.aspx?DocVersionId=62121591435&Language=en-US&TopicId=60466702475
1/21/2016

Potrebbero piacerti anche