P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

CHANGE OVER OF ASAB 1 SS#1


POWER FROM ADCO TO ASAB 2
SS#220

2 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

Spare

H16

Spare
OHL

OHL

ASAB1SS111kV
3 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

Spare

H16

Spare
OHL

OHL

Spare Feeder Modification of H01 & H16

ASAB1SS111kV
4 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV H01

H00

H17

Spare

H16

Spare
OHL

OHL

Ensure Bus Coupler is Closed

ASAB1SS111kV
5 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
Isolate 33kV Supply
ADCO33kV
ASAB2SS22033kV
33kV H01

H00

H17

Spare

H16

Spare
OHL

OHL

Open Incomer 2

ASAB1SS111kV
6 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
Apply LOTO
ADCO33kV
ASAB2SS22033kV
33kV H01

H00

H17

Spare

H16

Spare
OHL

OHL

Apply LOTO

ASAB1SS111kV
7 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV H01

H00

H17

Spare

H16

Spare
OHL

Disconnect Cable
From Incomer 2

ASAB1SS111kV
8 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

Spare
33KVCable
OHL

Connect New Cable From H16 (ASAB


-2 SS220, Feeder Modification

CableDifferentialProtectionRelay

ASAB1SS111kV
9 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

Spare
33KVCable
OHL

Perform Stability Test for


Cable Differential
Protection

CableDifferentialProtectionRelay

ASAB1SS111kV
10 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

Spare
33KVCable
OHL

Perform Interlock &


Intertrip Test

Remove LOTO

CableDifferentialProtectionRelay

11 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

Spare
33KVCable
OHL

Energize the 33 KV Power


Cable

CableDifferentialProtectionRelay

ASAB1SS111kV
12 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
ASAB2SS22033kV
33kV

H00

H01

H17

H16

Spare
33KVCable
OHL

CableDifferentialProtectionRelay

Phase angle difference between ASAB 2 and ADCO


so Synchronizing is not possible
ASAB1SS111kV
13 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

Spare
33KVCable
OHL

CableDifferentialProtectionRelay

Switch Off the Incoming Supply of Incomer 1.


11kV Bus is DEAD. Plant Shut Down.
ASAB1SS111kV
14 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

Spare
33KVCable
OHL

Energize 11kV Bus Through Incomer 2


CableDifferentialProtectionRelay

ASAB1SS111kV
15 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
FOCable
ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

Spare
33KVCable
OHL

Normalize the Plant


CableDifferentialProtectionRelay

ASAB1SS111kV
16 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover
Apply LOTO

FOCable
ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

Spare
33KVCable
OHL

Apply LOTO

CableDifferentialProtectionRelay

ASAB1SS111kV
17 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

33KVCable

FOCable

Connect New Cable From H01 (ASAB


-2 SS220, Feeder Modification
FOCable
33KVCable

CableDifferentialProtectionRelay

ASAB1SS111kV
18 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

33KVCable

FOCable

FOCable
33KVCable

CableDifferentialProtectionRelay

Perform Stability Test for


Cable Differential
Protection

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB1SS111kV
19 of26

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

33KVCable

FOCable

FOCable
33KVCable

CableDifferentialProtectionRelay

Perform Interlock &


Intertrip test

ASAB1SS111kV
20 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

33KVCable

FOCable

FOCable
33KVCable

CableDifferentialProtectionRelay

Energize the 33 KV
Power Cable

ASAB1SS111kV
21 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
ASAB2SS22033kV
33kV

H01

H00

H17

H16

33KVCable

FOCable

FOCable
33KVCable

CableDifferentialProtectionRelay

Close Incomer 1 Both the supplies are from


same source Incomer Can be closed.

ASAB1SS111kV
22 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

ADCO33kV
33kV

ASAB2SS22033kV
H01

H00

H17

H16

33KVCable

FOCable

FOCable
33KVCable

CableDifferentialProtectionRelay

Intertrip Test for energized condition


ASAB1SS111kV
23 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

SCHEDULE
S No.

DESCRIPTION

Isolation of Incomer 1 and LOTO

33kV Power Cable Removal from


Existing Transformer
Glanding and Termination of New 33kV
Power Cable in Transformer
Incomer 1 Scheme Modification

3
4
5
6
7

Day2

Day3

Day4

Day5

Day6

Day7

Day8

Day9

Day10

Day11

Day12

Installation of CT in cable
compartment.
Control cable Termination in Protection
Panel and Incomer 1 Panel.
Pre-Commissioning Checks of Modified
Panels

Stability Test for Cable Differential


Protection.
Interlock and Inter Trip Test

10

Box up, Removal of LOTO

11

Energization of 33kV Cable from


ASAB 2 SS#220.

12

11kV Bus Isolation (Dead) by


Isolating Incomer 2 Supply.

Day 1

24 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)

ASAB-1 Changeover

SCHEDULE
S No.
13
14
15
16
17
18
19

DESCRIPTION

Day2

Day3

Day4

Day5

Day6

Day7

Day8

Day9

Day10

Day11

Day 12 Day13

Installation of CT in cable
compartment.
Control cable Termination in
Protection Panel and Incomer 2
Panel.
Pre-Commissioning Checks of
Modified Panels

21

Stability Test for Cable Differential


Protection.
Interlock and Inter Trip Test

22

Box up, Removal of LOTO

23

Energization of 33kV Cable from


ASAB 1SS#1, And Energization of
11kV Incomer 2.

20

Day 1

Energization of 11kV Bus Through


Incomer 1.
33kV Power Cable Removal from
Existing Transformer
Glanding and Termination of New
33kV Power Cable in Transformer
Incomer 2 Scheme Modification

25 of26

P5283 PowerGenerationUnitRetirement
AbuDhabiGasIndustriesLtd.(GASCO)