Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Boris Bastigkeit
OMICRON electronics GmbH
boris.bastigkeit@omicron.at
Introduction
Absolute selectivity and short tripping times of the line
protection in meshed networks can be achieved by
using line differential protection - or distance protection
with teleprotection schemes. As a result of the exchange of information between the protection devices at
the line ends, fault tripping is also quicker in the range
of the last 10-20% of the line, where instantaneous
tripping is not performed in conventional distance protection. Testing of such distributed protection systems
with communication features is performed according to
the state of the art using GPS synchronized end-to-end
testing. The example of "testing distance-teleprotection
systems" is used in this article to demonstrate how the
simulation of faults on the protected line by means of a
network model can substantially simplify testing. Hence,
not only the correct parameter setting and function of
the protection device are ensured but also the plausibility of the calculated parameter settings is verified.
Line data
Line type: Overhead line
Grounding: Compensated network
Nominal voltage: 110kV
X (primary): 7.175 ohms
R (primary): 3.44 ohms
CT/VT data
Side A:
Side B:
Voltage transformer: :110000/100
Current transformer: :600/1
CT starpoint towards busbar
The following test cases (1 5) are typically carried out. They describe the function of the teleprotection scheme in detail
and are the basis for designing a test plan.
(1) Fault at the middle of the line: Both ends feed into
the fault. Teleprotection communication channel active.
The protections in A and B detect the fault as a zone 1
fault and both perform instantaneous tripping.
(2) Double-end feeding, teleprotection communication
channel active.
Fault near busbar B. The protection in A detects the
fault as a zone 2 fault and issues a "Send PSIG". Upon
the PSIG receipt, the extended zone is released in A
and instantaneous tripping is performed.
(2a) Single-end feeding, teleprotection communication
channel active.
Fault near busbar B. The protection in A detects the
fault as a zone 2 fault and issues a "Send PSIG". Since
protection does not pick up in B because of single-end
feeding, B returns an echo signal upon the PSIG receipt. Upon the PSIG receipt, the extended zone is
released in A and instantaneous tripping is performed.
(2b) Double-end feeding, teleprotection communication
channel failed. Fault near busbar B. The protection in A
detects the fault as a zone 2 fault. The protection in B
detects the fault as a zone 1 fault and performs instantaneous tripping. Due to a PSIG failure, both ends have
to process the zone timers.
(3) Fault beyond busbar B. The protection in A detects
the fault as a zone 2 fault and issues a "Send PSIG".
The protection in B detects the fault in reverse direction,
trips with the time for the reverse zone, and must not
issue a "Send PSIG". Since the protection in A does not
receive a PSIG, tripping is performed in zone 2.
X sec = Xprim
Setting the sources
As the next step the sources of the network model are
configured. The described transient network model
offers the advantage that the pre-assignment of the
individual parameters of the sources has already been
done for typical cases and it is - especially for testing
distance protection - usually not necessary to make any
changes to the default settings. The only adjustment
recommended for the given example is to set the zero
sequence impedance of the sources to the maximum
impedance since the case discussed is a compensated
network which does not permit a high fault current in
case of a ground fault and causes a voltage offset.
However, since in the case described only 2-phase
faults are simulated the zero sequence impedance of
the sources is not relevant. If it is desirable that a load
current flows in the prefault condition, one can achieve
rI
rV
R sec = Rprim
rI
rV
Test sequence
In accordance with the protection concept as described
at the beginning of this article, the various test steps (for
example, one transient network model module per test
step) are now generated in the test plan by copying the
transient network model test module defined so far. The
following items are defined for each test step:
Outputs/hardware configuration
The test plan for end B needs to be configured that a
connected test set generates the simulated currents for
end B in the corresponding hardware configuration
dialog.
CMGPS
CMGPS
Test Set
End A
PC-A with
Test SW
Test Set
End B
PC-B with
Test SW
Summary
Literature
[1] Oliver Gludowatz, Prfung eines Leistungsschutzes mit Signalvergleich; OMICRON User Meeting
2000, Mnchen
[2] Boris Bastigkeit, "Neue Mglichkeiten bei der Prfung von Leitungsdifferentialschutz-Einrichtungen";
OMICRON User Meeting 2008, Lbeck
[3] Dr. Peter Meinhardt, "Zeitsynchronisierte Prfung
von Leitungsdifferentialschutz"; OMICRON User
Meeting 2006 Weimar
End-to-end
testing
verifies
the
complete
teleprotection scheme
Very realistic testing by applying transient
simulation
High degree of test automation and standardization
The test verifies proper function of the protection
for the most important operational conditions and
fault conditions
The plausibility of the calculated protection settings
is verified
Testing is independent of the type of protection
device used (black box test)
It is not required to know any relay parameters for
this kind of test - only a few network parameters
(line-data, CT, VT) and
the protection concept
need to be known
The test software calculates secondary test
quantities automatically from primary data and from
CT/VT data
Time savings when preparing the test plans as
compared to the conventional end-to-end test
method
Familiar test environment the transient network
model behaves like easy to use, state of the art
protection test tools in contrast to tools like EMTP
etc.