Medium-Voltage Equipment
Selection and Ordering Data
Catalog HG 11.04 August 2010
R-HG11-172.tif
3AH4 Vacuum
Circuit-Breakers
Medium-Voltage Equipment
Catalog HG 11.04 August 2010
Contents
Contents
Page
Description
General
10
Equipment Selection
11
12
13
15
22
23
Technical Data
25
26
Circuit diagrams
30
32
Annex
33
Inquiry form
34
Configuration instructions
35
Configuration aid
Foldout page
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General
R-HG11-174.tif
Switching medium
Pole assemblies
Operating mechanism
Trip-free mechanism
Releases
Closing
Interlocking
Standards
Maintenance
Ambient conditions
Dielectric strength
10
Basic equipment
10
Description
General
R-HG11-126.eps
Description
Construction and mode of operation
Switching medium
The vacuum switching technology, proven and fully
developed for more than 30 years, serves as arc-quenching
principle by using vacuum interrupters.
Pole assemblies
The pole assemblies consist of the vacuum interrupters (6)
and the interrupter supports. The vacuum interrupters are
air-insulated and freely accessible. This makes it possible to
clean the insulating parts easily in adverse ambient conditions. The vacuum interrupter is mounted rigidly to the upper
interrupter support (5). The lower part of the interrupter is
guided in the lower interrupter support (7), allowing axial
movement. The braces absorb the external forces resulting
from switching operations and the contact pressure.
Circuit-breaker structure
1 Pole assembly
2 Operating mechanism box
3 Post insulator
4 Operating rod
5 Upper interrupter support
6 Vacuum interrupter
7 Lower interrupter support
R-HG11-191.tif
Front view
R-HG11-192.tif
Trip-free mechanism
Description
Construction and mode of operation, standards
Releases
For delayed tripping, the undervoltage release can be combined with energy stores.
Closing
In the standard version, 3AH4 vacuum circuit-breakers can be
remote-closed electrically. They can also be closed locally by
mechanical unlatching of the closing spring via push- button.
Instead of this manual mechanical closing, manual electrical closing is also available. In this version, the closing
circuit of the circuit-breaker is controlled electrically by a
pushbutton instead of the mechanical button.
In this way, switchgear-related interlocks can also be considered for local operation in order to prevent involuntary
closing.
If constant CLOSE and OPEN commands are present at
the vacuum circuit-breaker at the same time, the vacuum
circuit-breaker will return to the open position after closing.
It remains in this position until a new CLOSE command is
given. In this manner, continuous closing and opening
(= pumping) is prevented.
Circuit-breaker tripping signal
The NO contact makes brief contact while the vacuum
circuit-breaker is opening, and this is often used to operate
a hazard-warning system which, however, is only allowed to
respond to automatic tripping of the circuit-breaker. Therefore, the signal from the NO contact must be interrupted
when the circuit-breaker is being opened intentionally. This
is accomplished under local control with the cut-out switch
that is connected in series with the NO contact.
Interlocking
Electrical interlocking
The vacuum circuit-breakers can be integrated in electromagnetic feeder or switchgear interlocks. In case of electrical
interlocking, the disconnector or its operating mechanism is
equipped with a magnetic lock-out mechanism. This mechanism is controlled by an auxiliary contact of the circuitbreaker, so that the disconnector can only be operated when
the circuit-breaker is open. On the other hand, the circuitbreaker is also controlled by the disconnector or its operating
mechanism, so that it can only be closed when the disconnector is in an end position. For this purpose, manual electrical
closing must be provided in the circuit-breaker operating
mechanism (see Closing).
Mechanical interlocking
To interlock circuit-breaker trucks, withdrawable parts or
disconnectors according to the switch position, the circuitbreakers can be equipped with a mechanical interlocking.
A sensor at the switchgear checks the position of the circuitbreaker and prevents the open circuit-breaker in a reliable
way from being closed mechanically and electrically.
Standards
3AH4 vacuum circuit-breakers conform to the following
standards:
IEC 62271-100 (former IEC 60056)
IEC 62271-1 (former IEC 60694)
VDE 0671 (former VDE 0670)
Description
Maintenance, ambient conditions, current carrying capacity and dielectric strength
Maintenance
The 3AH4 vacuum circuit-breakers are maintenance-free
up to 10,000 operating cycles under normal ambient
conditions according to IEC 62271-1 (former IEC 60694):
Relubrication after 10,000 operating cycles
Replacement of vacuum interruptors after 30,000
operating cycles.
Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH4 vacuum circuit-breakers
are suitable for use in the following climatic classes
according to IEC 60721, Part 3-3:
Class 3K4 1)
Class 3B1
Class 3M2
Class 3C2 2)
Class 3S2 3)
5000
A
4000
5
3000
4
2000
3
2
1000
10
20
30
1500
2000
HG11-2593d_en eps
HG11-2515a_en eps
-5C
40C
40
50
60 C 70
Ambient air temperature
Dielectric strength
Example
1.40
1.30
1.20
HG11-2517c_en eps
1.50
Altitude correction factor
1.10
1.00
1000
2500
Description
Product range overview and basic equipment
Rated
short-circuit
breaking current
2000
2500
3150
4000
kV
kA
12
31.5
40
31.5
40
25
40
31.5
40
15
24
36
210
275
350
210
p*
p
275
350
210
275
350
350
350
n
n
n
n
p
p
210
p
p
n
n
* 1600 A
n Available design 120,000 operating cycles
n
n
Basic equipment
Features
Minimum equipment
Alternative equipment
Remarks
Operating mechanism
None
1st release
2nd release
Electrical operating
mechanism
Closing solenoid and
manual mechanical closing
Shunt release
Without
3rd release
Without
Varistor circuit
Installed for W 60 V DC
None
Auxiliary switch
Plug connector
6 NO + 6 NC
24-pole terminal strip
Anti-pumping
Circuit-breaker
tripping signal
Operating cycle counter
Spring charged
signal and indication
Interlocking
Available
Available
12 NO + 12 NC
24-pole plug,
64-pole plug
None
None
Available
Available
None
None
Without
Mechanical interlocking
Closing
10
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example
11
12
13
14
R-HG11-126.eps
Release combination
15
16
Operating voltage,
1st shunt
Operating voltage,
2nd
release
18
Operating voltage,
3rd
release
19
release
17
20
21
22
22
23
11
Equipment Selection
Ordering data and configuration example
Special versions ()
Order codes
Individual equipment versions, marked with 9 or Z in the
9th to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.
a: alphabetical
Position:
Order No.:
1st position
n: numerical
10 11 12
13 14 15 16
3 A H 4
Order codes
n n n
Primary part
Superior group
Switching devices
2nd position
Main group
Circuit-breaker
3rd position
Subgroup
Circuit-breaker type series
Basic equipment
Design and ratings
primary part
Secondary part
Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Special versions ()
Initiated with -Z
Group of 3 after the Order No.
Format: a n n
Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a configuration example on each page of the chapter Equipment
Selection. For the selection of the secondary part, always the
last example of the primary part was taken over and continued,
so that at the end of the equipment selection (page 22) a
completely configured circuit-breaker results as an example.
12
3 A H 4
6 n n n n n n n n
Equipment Selection
Selection of basic types, circuit-breakers
10 11 12
13 14 15 16
Order codes
n n n
See page 22
See page 22
kV
See page 21
kV
See page 20
kV
12
See page 19
Rated short-circuit
making current
(at 50/60 Hz)
Ima
See page 18
Rated short-circuit
breaking current
at 36 % DC component
Isc
See page 15
Rated short-duration
power-frequency
withstand voltage
Ud
Pole-centre distance
Rated voltage
Ur
3 A H 4 n n n n n n n n n n n n
See page 17
Position:
Order No.:
See page 16
12 kV
Ir
kA
kA
mm
31.5
80/82
210
40
100/104
1250
2000
1250
2000
2500
3150
3
3
3
3
3
3
A
A
A
A
A
A
H
H
H
H
H
H
4
4
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
5
5
6
6
6
6
2
4
2
4
6
7
M
M
M
M
M
M
3
3
3
3
3
3
0
0
0
0
0
0
3
3
3
3
3
A
A
A
A
A
H
H
H
H
H
4
4
4
4
4
1
1
1
1
1
6
6
6
6
6
5
5
6
6
6
2
4
3
4
7
M
M
M
M
M
3
3
3
3
3
0
0
0
0
0
7 n n n n n n n n
15 kV
50/60 Hz, 30,000 / 60,000* operating cycles
Ur
Up
Ud
Isc
Ima
kV
kV
kV
kA
kA
mm
31.5
80/82
210
40
100/104
1250
2000
1600
2000
3150
15
Ir
Configuration example
3AH4 vacuum circuit-breaker
Rated voltage Ur = 15 kV, 50/60 Hz
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 210 mm
Rated normal current Ir = 3150 A
3 A H 4
3 A H 4
Order codes:
Siemens HG 11.04 August 2010
13
Equipment Selection
Selection of basic types, circuit-breakers
10 11 12
13 14 15 16
Order codes
n n n
See page 22
See page 22
See page 21
See page 20
See page 19
Rated short-circuit
making current
(at 50/60 Hz)
Ima
See page 18
Rated short-circuit
breaking current
at 36 % DC component
Isc
See page 15
Rated short-duration
power-frequency
withstand voltage
Ud
Pole-centre distance
Rated voltage
Ur
3 A H 4 n n n n n n n n n n n n
See page 17
Position:
Order No.:
See page 16
24 kV
Ir
kV
kV
kV
kA
kA
mm
24
125
50
25
100/104
210
1250
2500
1250
2000
3
3
3
3
4
4
4
4
2
2
2
2
5
5
6
6
4
4
4
4
2
4
2
4
2500
3 A H 4
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
0
0
0
0
0
0
0
0
5
5
5
5
5
6
6
6
2
4
6
7
8
6
7
8
275
A
A
A
A
H
H
H
H
M
M
M
M
3
3
3
3
0
0
0
0
E
+ E
Z
E
+ E
1
1
2
2
4
5
4
5
Z
E
Z + E
2
2
4
5
40
275
36 kV
50/60 Hz, 120,000 operating cycles
Ur
Up
Ud
Isc
Ima
Ir
kV
kV
kV
kA
kA
mm
36
170
70
31.5
80/82
350
40
100/104
350
1250
2000
2500
3150
4000
2500
3150
4000
A
A
A
A
A
A
A
A
H
H
H
H
H
H
H
H
4
4
4
4
4
4
4
4
Configuration example
3AH4 vacuum circuit-breaker
Rated voltage Ur = 36 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A
Increase of rated lightning impulse withstand voltage Up = 195 kV
and rated short-duration power-frequency withstand voltage Ud = 95 kV
Example for Order No.:
Order codes:
14
3 A H 4
3 A H 4
6 n n n n n n n n
Equipment Selection
Selection of secondary equipment
n
n
n
n
n
n
n
n
n
n
n
n
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
Closing solenoid, 1st shunt release, 2nd shunt release and
c.t.-operated release with a rated normal current of 0.5 A
10 11 12
13 14 15 16
Order codes
n n n
See page 22
See page 22
See page 21
See page 20
See page 19
See page 18
See page 17
See page 16
M
N
T
P
P
R
S
S
U
U
V
V
n
n
n
3 A H n n n n n n n n n n n n n
C.t.-operated release
with tripping pulse
0.1 Ws (20 c)
C.t.-operated release
with tripping pulse
0.1 Ws (10 c)
C.t.-operated release
1.0 A
C.t.-operated release
0.5 A
n
n
n
n
n
n
n
n
n
n
n
n
Position:
Order No.:
Undervoltage release
n
n
n
n
n
n
n
n
n
n
n
n
Closing solenoid
9th position
Release combinatiod
P n n n n n n n
3 A H 4
3
6
P
3 A H 4
15
Equipment Selection
Selection of secondary equipment
10 11 12
13 14 15 16
Order codes
n n n
See page 22
See page 22
See page 21
See page 20
See page 19
Special voltages
3 A H 4 n n n n n n n n n n n n
See page 17
Standard voltages
Position:
Order No.:
See page 18
10th position
Operating voltage of the closing solenoid
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
B
C
D
E
F
H
J
K
Z
Z
Z
Z
Z
Z
Z
Z
Z
K
K
K
K
K
K
K
K
K
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
M
N
P
Q
R
T
U
V
Z
Z
Z
Z
Z
Z
Z
Z
Z
K
K
K
K
K
K
K
K
K
2 A
2 B
2 C
2 D
2 E
2 F
2 K
2 L
2 M
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 30 V DC
3 A H 4
3
Order codes:
Siemens HG 11.04 August 2010
P
Z
16
3 A H 4
Z n n n n n n
Equipment Selection
Selection of secondary equipment
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC
110 V AC
230 V AC
10 11 12
1
2
3
4
5
6
7
8
9
9
9
9
9
9
9
9
9
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
Order codes
n n n
See page 22
See page 22
See page 21
See page 20
Special voltages
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
13 14 15 16
3 A H 4 n n n n n n n n n n n n
See page 18
Standard voltages
Position:
Order No.:
See page 19
11th position
Operating voltage of the 1st shunt release
L
L
L
L
L
L
L
L
L
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
Operating voltage of the 1st shunt release 48 V DC
3 A H 4
3
Z
2
3 A H 4
2 n n n n n
17
Equipment Selection
Selection of secondary equipment
10 11 12
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
Order codes
n n n
See page 22
See page 22
See page 21
Special voltages
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
13 14 15 16
See page 20
Standard voltages
3 A H 4 n n n n n n n n n n n n
See page 19
12th position
Position:
Operating voltage of the 2nd release
Order No.:
Shunt release, undervoltage release or c.t.-operated release
0
1
2
3
4
5
6
7
8
9
9
9
9
9
9
9
9
9
M
M
M
M
M
M
M
M
M
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
9
9
9
9
9
9
9
9
M
M
M
M
M
M
M
M
2 D
2 E
2 F
2 G
3 D
3 E
3 F
3 G
Special versions
To operate the 2nd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined
and whether the energy store will be provided by the customer
or included in the scope of supply.
Energy store
Type
60 V DC
110 V DC
220 V DC
100/110/230 V AC
60 V DC
110 V DC
220 V DC
100/110/230 V AC
In the scope
of supply
no
no
no
no
yes
yes
yes
yes
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
2nd release as undervoltage release with operating voltage 32 V DC
Example for Order No.:
Order codes:
18
3 A H 4
3
2
9
n n n n
3 A H 4
+ M 1
M 1
Equipment Selection
Selection of secondary equipment
10 11 12
13 14 15 16
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
n n n
See page 22
See page 22
Special voltages
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
Order codes
3 A H 4 n n n n n n n n n n n n
See page 21
Standard voltages
Position:
Order No.:
See page 20
13th position
Operating voltage of the 3rd release
Undervoltage release or c.t.-operated release
0
1
2
3
4
5
6
7
8
9
9
9
9
9
9
9
9
9
N
N
N
N
N
N
N
N
N
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
9
9
9
9
9
9
9
9
N
N
N
N
N
N
N
N
2 D
2 E
2 F
2 G
3 D
3 E
3 F
3 G
Special versions
To operate the 3rd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined
and whether the energy store will be provided by the customer
or included in the scope of supply.
Energy store
Type
60 V DC
110 V DC
220 V DC
100/110/230 V AC
60 V DC
110 V DC
220 V DC
100/110/230 V AC
In the scope
of supply
no
no
no
no
yes
yes
yes
yes
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
3rd release as c.t.-operated release
3 A H 4
3
3 A H 4
+ M 1
0 n n n
19
Equipment Selection
Selection of secondary equipment
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC
110 V AC
230 V AC
10 11 12
13 14 15 16
B
C
D
E
F
H
J
K
Z
Z
Z
Z
Z
Z
Z
Z
Z
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
Configuration example
3AH4 vacuum circuit-breaker
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
Operating voltage of the operating mechanism 230 V AC, 50 Hz
Example for Order No.:
Order codes:
20
3 A H 4
3
0
K
3 A H 4
+ M 1
K n n
n n n
See page 22
Special voltages
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
Order codes
3 A H 4 n n n n n n n n n n n n
See page 21
Standard voltages
Position:
Order No.:
See page 22
14th position
Operating voltage of the operating mechanism
P
P
P
P
P
P
P
P
P
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
Equipment Selection
Selection of secondary equipment
n
n
n
10 11 12
13 14 15 16
n n n
See page 22
See page 22
A
E
G
C
M
B
F
H
D
N
n
n
n
n
Order codes
3 A H 4 n n n n n n n n n n n n
24-pole
terminal strip 2)
24-pole plug 2)
64-pole plug 1)
Auxiliary switch
12 NO + 12 NC
Auxiliary switch
6 NO + 6 NC
Mechanical
interlocking
15th position
Position:
Auxiliary switch, secondary connection, interlocking Order No.:
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Special version
Auxiliary switch 12 NO + 12 NC and 24-pole plug (E or F)
Special versions gold-plated contacts and pins
Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H)
Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N)
Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B)
Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D)
Z
Z
Z
Z
A
A
A
A
1
1
2
2
7
8
0
1
C n
Configuration example
3AH4 vacuum circuit-breaker
3 A H 4
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm)
Operating voltage of the operating mechanism 230 V AC, 50 Hz
Auxiliary switch 12 NO + 12 NC, 64-pole plug, without mechanical interlocking
Example for Order No.:
Order codes:
0
K
C
3 A H 4
+ M 1
21
Equipment Selection
Selection of secondary equipment /Additional equipment
16th position
Position:
AC frequency of operating voltages
Order No.:
Languages of operating instructions and rating plate
n
n
50 Hz and DC
60 Hz and DC
50 Hz
60 Hz
n
n
DC
n
n
10 11 12
13 14 15 16
n n n
0
1
2
3
4
5
6
7
n
n
n
n
n
n
n
n
n
Other languages on request
Special versions
Additional information on the rating plate (only after consultation
with the order processing department of the Switchgear Factory Berlin).
Information in clear text.
Order codes
Frequency selection
Spanish
French
English
German
Language selection
3 A H 4 n n n n n n n n n n n n
Z
Z
Z
Z
A
A
A
B
1
3
3
0
0
0
1
0
Z
Z
D
F
1
2
0
0
E
+ E
2
2
4
5
M 1
A
F
3
2
0
0
Additional equipment
Options
Wiring cables, halogen-free and flame-retardant
Condensation protection, heating for 230 V AC, 50 W
Silicone-free design
Additional rating plate, loose delivery
Primary conductor bars silver-plated for external connections
and internal interconnection on both sides
Routine test certificate enclosed
Hand crank (also for motor operating mechanism)
for manual charging of the closing spring
Further, non-listed special versions (only after consultation with the
order processing department of the Switchgear Factory Berlin).
Information additionally in clear text.
Configuration example
3AH4 vacuum circuit-breaker
3 A H 4
Rated voltage Ur = 36 kV (50/60 Hz)
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A
Increase of rated lightning impulse withstand voltage Up = 195 kV
and rated short-duration power-frequency withstand voltage Ud = 95 kV
Closing solenoid, 1st shunt release, 2nd shunt release
and c.t.-operated release with a rated normal current of 0.5 A
Manual electrical closing at the circuit-breaker, operating voltage
of the closing solenoid 30 V DC
Operating voltage of the 1st release 48 V DC
2nd release as undervoltage release with operating voltage 32 V DC
3rd release as c.t.-operated release
Operating voltage of the operating mechanism 230 V AC, 50 Hz
Auxiliary switch 12 NO + 12 NC, 64-pole plug, without mechanical interlocking
Frequency 50 Hz or DC, operating instructions and rating plate in English
Condensation protection, heating for 230 V AC, 50 W
Routine test certificate enclosed
Example for Order No.:
Order codes:
22
P
Z
2
9
0
K
C
2
3 A H 4
+ M 1
Z
Z
Equipment Selection
Accessories and spare parts
Designation
Hand crank
Lubricant
Wire bundle
Remarks
Order No.
3AX15 30-2B
(for special application conditions)
180 g Klber-Isoflex Topas L32N
1 kg Klber-Isoflex Topas L32N
1 kg Shell Tellus oil 32 (special oil)
With 10 wires for connection of auxiliary switch to
64-pole plug connector
24-pole plug connector
24-pole terminal strip
(for wire cross-section 1.5 mm2)
Crimp pins for lower part of plug
24-pole
64-pole
Crimp sockets for upper part of plug
64-pole
Crimping pliers
Disassembly tool
3AX11 33-3H
3AX11 33-3E
3AX11 33-2D
3AX11 34-2D
3AX11 34-2B
3AX11 34-2C
3AX11 34-3A
3AX11 34-4B
3AX11 34-4C
3AX11 34-4D
3AX11 34-4G
23
R-HG11-205.tif
24
Technical Data
Contents
Contents
Page
Technical Data
25
28
Circuit diagrams
30
Operating times
32
32
32
R-HG11-199.eps
R-HG11-198.tif
25
Technical Data
Ud
kA
kA
kV
kV
mV
mm mm mm mm
kg
80/
82
80/
82
100/
104
100/
104
100/
104
100/
104
100/
104
75
28
2.5
113
S_325 00900
75
28
2.5
130 165
90
130
129
S_325 00901
75
28
2.5
140 195
90
120
135
S_325 00902
75
28
2.5
140 195
90
120
135
S_325 00902
75
28
2.5
140 195
90
120
135
S_325 00903
75
28
2.0
140 195
90
120
135
S_325 00904
75
28
2.0
140 195
90
120
135
S_325 00904
Ima
Up
Ud
Minimum clearance,
phase-to-phase
Weights
Up
kA
Ima
Minimum clearance,
phase-to-earth
mm
Isc
Ir
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
50/60 Hz
tk
12 kV
DC component in %
of the rated short-circuit breaking current
3AH4 115-2
1250 210
31.5
36
35.4
3AH4 115-4
2000 210
31.5
36
35.4
3AH4 116-2
1250 210
40
36
44.9
3AH4 116-3
1600 210
40
36
44.9
3AH4 116-4
2000 210
40
36
44.9
3AH4 116-6
2500 210
40
36
44.9
3AH4 116-7
3150 210
40
36
44.9
tk
Isc
kA
kA
kA
kV
kV
mV
mm mm mm mm
kg
80/
82
80/
82
100/
104
100/
104
100/
104
100/
104
100/
104
95
36
2.5
117
S_325 00900
95
36
2.5
130
S_325 00901
95
36
2.5
142
S_325 00902
95
36
2.5
142
S_325 00902
95
36
2.5
142
S_325 00903
95
36
2.0
142
S_325 00904
95
36
2.0
142
S_325 00904
15 kV
Ir
50/60 Hz
mm
3AH4 165-2
1250 210
31.5
36
35.4
3AH4 165-4
2000 210
31.5
36
35.4
3AH4 166-2
1250 210
40
36
44.9
3AH4 166-3
1600 210
40
36
44.9
3AH4 166-4
2000 210
40
36
44.9
3AH4 166-6
2500 210
40
36
44.9
3AH4 166-7
3150 210
40
36
44.9
26
Technical Data
Electrical data, dimensions and weights
Operating cycles
30 000
20 000
of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
10 000
5 000
2 000
1 000
500
200
100
20
10
HG11-2600d_en eps
50
2
1
10
20 31.5 40 50 kA 100
540
210
210
104
560
589
HG11-2770 eps
143
715
494
211
610
Dimension drawing 1
606
540
210
606
210
520
570
210
210
104
104
562
Dimension drawing 2
610
HG11-2776 eps
572
715
143
494
610
HG11-2771 eps
589
715
211
143
494
211
Dimension drawing 3
27
Technical Data
kA
kA
kV
kV
mV
mm mm mm mm
kg
63/
65
63/
65
63/
65
63/
65
100/
104
125
50
2.5
112
S_325 00905
125
50
2.5
131
S_325 00906
125
50
2.5
112
S_325 00907
125
50
2.5
133
S_325 00908
125
50
2.0
135
S_325 00007
Ima
Up
Ud
kA
kA
kV
kV
mV
mm mm mm mm
kg
80/
82
80/
82
80/
82
80/
82
80/
82
100/
104
100/
104
100/
104
170
70
2.3
170
S_325 00008
170
70
2.3
175
S_325 00008
170
70
2.3
175
S_325 00009
170
70
1.9
350
S_325 00011
10
170
70
1.9
350
S_325 00011
10
170
70
2.3
175
S_325 00009
170
70
1.9
350
S_325 00059
10
170
70
1.9
350
S_325 00059
10
1250 210
25
36
28
3AH4 254-4
2500 210
25
36
28
3AH4 264-2
1250 275
25
36
28
3AH4 264-4
2000 275
25
36
28
3AH4 266-6
2500 275
40
36
44.9
tk
Isc
kA
36 kV
Ir
50/60 Hz
mm
3AH4 305-2
1250 350
31.5
36
35.4
3AH4 305-4
2000 350
31.5
36
35.4
3AH4 305-6
2500 350
31.5
36
35.4
3AH4 305-7
3150 350
31.5
36
35.4
3AH4 305-8
4000 350
31.5
36
35.4
3AH4 306-6
2500 350
40
36
44.9
3AH4 306-7
3150 350
40
36
44.9
3AH4 306-8
4000 350
40
36
44.9
Minimum clearance,
phase-to-phase
Weights
Ud
kA
Up
Ima
3AH4 254-2
109
680
275
350
350
275
211
520
Dimension drawing 4
28
733
1000
HG11-2606b eps
70
HG11-2605a eps
494
778
954
494
104
ca.104
211
70
mm
Minimum clearance,
phase-to-earth
Isc
Ir
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
50/60 Hz
tk
24 kV
DC component in %
of the rated short-circuit breaking current
612
Dimension drawing 5
Technical Data
Electrical data, dimensions and weights
540
602
30 000
20 000
10 000
210
210
104
5 000
494
2 000
860
211
623
Operating cycles
50 000
1 000
HG11-2772 eps
198
500
200
HG11-2778b_en eps
50
275
20 25 40 50 kA 100
31.5
Breaking current (r.m.s. value)
10
211
623
750
670
275
104
679
602
494
20
10
610
Dimension drawing 6
100
HG11-2773 eps
Dimension drawing 7
679
530
210
679
210
660
602
275
275
104
104
602
211
1012
HG11-2775 eps
143
Dimension drawing 9
870
350
268.5
350
ca.105
679
580
750
494
610
Dimension drawing 8
HG11-2774 eps
143
580
750
494
211
Dimension drawing 10
920
HG11-2777_en eps
746.5
1126.5
max.70
494
211
29
Technical Data
Circuit diagrams
Circuit diagrams
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
-S10
-X0
-Y9
-S11
HE
-M1 M
-S3
-S41
-S42
-S7
-S6
OPEN release
HA
-Y1
11
13
21
23
31
33
41
43
51
53
61
63
12
14
22
24
32
34
42
44
52
54
62
64
HG11-2575_en eps
-S1
HG11-2579a eps
-S21 -S22
-X0
Contacts available for customer with basic circuitbreaker equipment and auxiliary switch 6 NO + 6 NC
-X0
-X0
21
-S10
A1
21
-M1 1M=
D2
-S11
-S22
21
22
22
-S1
-K1
-K1
-Y9
11
12
21
22
31
-S3
22
-S7
21
-S1
22
23
24
21
13
14
-S6
32
A1
-K1
A2
21
A1
A2
-X0
Motor operating mechanism with manual mechanical closing
14
-S41
13
13
14
-S42
21
22
-Y1
A1
HG11-2578d eps
22
22
HG11-2577b eps
-S21
A2
-X0
Cicuit-breaker
tripping signal
1st shunt
release
Signal closing
spring charged
Manual opening
Manual closing
Contactor (anti-pumping)
Motor operating mechanism
Energy store
Resistance
S1
S3
S6
S7
S10,
S11
30
Auxiliary switch
Position switch
(opens when closing
spring is charged)
Circuit-breaker tripping signal
Cutout switch for circuitbreaker tripping signal
Anti-pumping for
manual closing
S14,
S15
S21,
S22
S41,
S42
Anti-pumping
X0
Position switches
(to de-energize the motor
operating mechanism
after charging)
Position switches
(to indicate the charging state)
Y1
Y2
Y4
Y6
Y7
Y9
Technical Data
Circuit diagrams
-X0
-Y9
14
-S14
HE
-S21 -S22
-M1 M
-S3
-S41
13
-S1
-S42
-K1
-S6
OPENrelease
HA
-Y1
-K1
HG11-2576_en eps
-S7
14
-S15
-Y9
13
11
-S3
12
21
21
13
14
22
31
32
A1
-K1
A2
-X0
-X0
Manual
electrical closing
22
A1
A2
HG11-2580b eps
-S14
Closing and
anti-pumping
-X0
21
-S21
22
A1
-M1 1M=
-S1
D2
22
13
21
23
31
33
41
43
51
53
61 63
71
73
81
83
91
12
14
22
24
32
34
42
44
52
54
62 64
72
74
82
84
92
21
-X0
-X0
Motor operating
mechanism
HG11-2582a eps
HG11-2581b eps
-S22
11
The available possible combinations are described in the chapter Selection of secondary equipment.
-X0
-S1
-X0
-X0
33
-S1
34
-Y7
-X0
-Y4
A1
A2
-X0
C.t.-operated
release 0.5 A
or 1 A
-Y6
-X0
A1
A2
-R1
HG11-2585 eps
A2
HG11-2584 eps
A1
HG11-2583 eps
-Y2
Low-energy
c.t.-operated
release 0.1 Ws
D1
U<
D2
44
1
2
-X0
43
HG11-2586 eps
-X0
Undervoltage release
31
Technical Data
Operating times, short-circuit protection of motors, consumption data of releases
Operating times
Operating times at rated voltage
of the secondary circuit
Equipment of circuit-breaker
Closing time
Opening time
Arcing time
Break time
Dead time
CLOSE/OPEN contact time
Minimum command duration
< 75 ms 1)
< 60 ms 1)
< 55 ms
< 15 ms
< 80 ms
< 60 ms
300 ms
< 90 ms
< 70 ms
45 ms
40 ms
20 ms
> 15 ms
> 10 ms
< 15 s
w 2 ms
V
24 DC
48 DC
60 DC
110 DC
220 DC
110 AC
230 AC
Operating voltage
max. V
min. V
W (at DC)
VA (at AC)
26
53
66
121
242
121
244
20
41
51
93
187
93
187
500
500
500
500
500
650
650
16
8
6
4
2
4
2
2) The current inrush in the drive motor can be neglected due to its very short presence.
Power consumption
Tripping ranges
Operation at
DC
AC 50/60 Hz
approx. W
approx. VA
at DC
Tripping voltage
or tripping current
at AC 50/60 Hz
140
140
140
140
85 to 110 % U
70 to 110 % U
85 to 110 % U
85 to 110 % U
70
50
70 to 110 % U
85 to 110 % U
20
20
10 3)
35 to
35 to 0 % U
90 to 110 % Ia
3) Consumption at pickup current (90 % of the rated normal current) and open armature.
32
Tripping voltage
0%U
Annex
Contents
Contents
Page
Annex
33
Inquiry form
34
Configuration instructions
35
Foldout page
R-HG11-181.tif
Configuration aid
R-HG11-180.eps
33
Annex
Inquiry form
Please copy, fill in and return to your
Siemens partner or you can use our
prompted online configurator under
www.siemens.com/energy
Inquiry concerning
o 3AH4 circuit-breaker
Please
o Submit an offer
o Call us
o Visit us
Technical Data
Other values
o 12 kV
o 24 kV
o 15 kV
o 36 kV
o _ _ _ kV
o 125 kV
o 195 kV
o 170 kV
o 185 kV
o _ _ _ kV
Rated short-duration
power-frequency withstand voltage
o 50 kV
o 95 kV
o 70 kV
Rated short-circuit
breaking current
o 25 kA
o 31.5 kA
o 40 kA
o 1250 A
o 3150 A
o 2000 A
o 4000 A
o 2500 A
Pole-centre distance
o 210 mm
o 275 mm
o 350 mm
Rated voltage
o 85 kV
o _ _ _ kV
o _ _ _ kA
o ___A
Your address
Secondary equipment
Company
Dept.
Circuit-breaker equipment
Name
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
Closing solenoid
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
Phone
o 0.5 A
Fax
Undervoltage release
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
Street
Postal code/city
Siemens AG
Name
o 6 NO + 6 NC
o 12 NO + 12 NC
Low-voltage connection
o 24-pole
terminal strip
o 24-pole plug
o 64-pole plug
o English
o German
o French
Postal code/city
Fax
o W 0.1 Ws
(20 c)
o Mechanical interlocking
Street
34
o W 0.1 Ws
(10 c)
Auxiliary switch
Operating instructions
Dept.
o 1A
_ _ _ Please fill in
o Spanish
9 10 11 12
13 14 15 16
24 kV to 36 kV
125 kV to 195 kV
50 kV to 95 kV
31.5 kA to 40 kA
1250 A to 3150 A
275 mm to 350 mm
3 A H 4
Possible options:
Release combination
(position 9)
Closing solenoid
(position 10)
Operating voltage of the releases
(positions 11/12)
Type of local closing
(position 10)
Operating voltage of the motor
(position 14)
Number of auxiliary contacts
(position 15)
Design of the secondary connection
(position 15)
Language of the documentation
(position 16)
Frequency of the operating voltage of the
secondary equipment at AC (position 16)
3 A H 4
50 Hz/60 Hz
3 A H 4
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 22)
3 A H 4
Should you still need more options than the possible special equipment like halogen-free and
flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc.,
please contact your responsible sales partner.
3 A H 4
35
3 A H 4
See page 22
See page 22
See page 21
See page 20
3 A H 4
Mechanical closing,
manual electrical closing
Motor operating stored-energy mechanism
with operating voltages from 24 V DC to 240 V AC
6 NO + 6 NC, 12 NO + 12 NC
See page 19
3 A H 4
3 A H 4
See page 18
Ur:
Up:
Ud:
Isc:
Ir:
See page 17
See page 16
Possible options:
See page 15
See page 13
1st step: Definition of the primary part (see page 13 and 14)
page 14
and
3 A H 4 n n n n n n n n n n n n Z
R-HG11-182.tif