SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW

TENDER CLARIFICATION NO. 2

No reinforcement
pilecaps:
1.
2.
3.
4.

Consultants Response

Tender Query

S/N

details

for

ANNEX B

the

2E1
2F1
3D
3E

following Please
refer
to
Tender
Corrigendum No. 1, structural
drawing no.: 14.00050/PC
Rev. A. (Option I) and
14.00050/PC Rev. A. (option
II)

Please provide instrumentation plan.

Please refer to Tender


Corrigendum No. 2, structural
drawing no.: 14.00050/IP Rev
A and 14.00050/IPN Rev A.

The instrumentation plans


and notes are issued for
information and reference
only. The types, quantities
of the instruments are
indicative only. The
Contractor shall design,
install, maintain and monitor
all necessary
instrumentation and
monitoring works to the
relevant Authorities and the
Engineers requirements,
including real time
monitoring for the whole of
the Works. The Contractor
shall not be entitled to any
claim for additional cost
and/or extension of time
arising out of and in
connection to compliance
Engineers and/or to the
relevant Authorities
requirements arising for
instrumentation and
monitoring works.
3

Content of drawing C-SG-003159/SA/201 & C- Please refer to Tender


SG-003159/SA/202 are duplicate. Therefore we Corrigendum No. 1, sanitary
would like to request for the drawing C-SG- drawing no.: C-SG-003159SA-201 Rev. A and C-SGANNEX B/ 1

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

003159/SA/201.

003159-SA-202 Rev. A.

Kindly advise for PID system for all FAD, EAD,


FAD and SAD.

Essential fans shall be


monitored and controlled by
PLC.
Please refer to ACMV tender
specifications.

Please provide all the A/C level drawing for option Please refer to Tender drawing
2.
list no.: C-SG003159/ME/1100

Refer to the drawing for the Control Room at 2nd


Storey, there was a 900mm high stair
approaching to the Control Room. Kindly advise
the height of the raised floor system as it was not
indicated in the drawing or is there any platform to
be constructed in this area?

The height of the raised floor


system at Control Room is
900mm.

Kindly advise the height of the timber skirting and


the thickness of both timber flooring and timber
decking system required for this contract. Please
provide the technical specifications and detailed
drawings as well.

Timber skirting to be 100mm


high.

Please refer to the level which


indicated in the drawing C-SG003159/AD/103 & C-SG003159/AD/233.

Thickness of the timber


flooring is 18mm. Please refer
to architectural specification
SECTION 09 64 00 WOOD
FLOORING.
Thickness of the timber
decking system is 25mm.
Please refer to architectural
specification SECTION 06 40
13 EXTERIOR
ARCHITECTURAL

ANNEX B/ 2

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
WOODWORK and drawing
no.: C-SG-003159/AD/802 for
detail.

Kindly advise whether the fire rated roller shutter Yes, thermal Insulation is
requires insulation.
required on both sides to
manufacturer details.

There was a difference regarding the dimension Please refer to Tender


of the concrete wheel stopper as per clouded. Corrigendum No. 2,
Kindly advise.
architectural drawing No.: CSG-003159/AD/1001 Rev. A.

10

Kindly provide details and specification for the Supply of chairs will be by
following chairs.
others.

ANNEX B/ 3

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

11

ANNEX B

Kindly provide dimension and specification for the These round table at
round table.
Classrooms are provided by
others.
Please refer to Tender
Corrigendum No. 2,
architectural drawing No.: CSG-003159/AD/600 Rev. A.

12

Please provide elevation and detailed drawings Please refer to structural


for metal main platform.
drawing no.: 14.00050/3.
Please refer to Tender
Corrigendum No. 1,
architectural drawing No.: CSG-003159/AD/1012 Rev. A.
Please take note that
maintenance platform is to be
designed and built by
contractor and contractor's PE
including BCA ST submission.

13

Please kindly provide catladder details.

ANNEX B/ 4

Please refer to architectural


drawing No.: C-SG003159/AD/246.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

14

Please kindly provide cat ladder details.

15

Refer to 3rd storey plan, it stated at vinyl flooring, Therapist Office floor finish is
however, according to floor finishes plan, is 9mm to be homogenous tile.
thk non-slip homogenous tile.
Please refer to Tender
Corrigendum No. 2,
architectural specification
SECTION 09 06 00
SCHEDULE OF FINISHES.

ANNEX B/ 5

Please refer to Tender


Corrigendum No. 2,
architectural drawing No.: CSG-003159/AD/1012 Rev.A.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

16

We refer to the page PFP I/35 and PFP II/35 for Please refer to Tender
Option I & Option II - pricing for Preliminaries Corrigendum No. 1.
(Annex C I & C II) Item A - Security Deposit as
stated To be Priced in Final Summary".
Unfortunately, we can't find that any Final
Summary" page to price in our cost. Please
clarify?

17

See attach basement ramp, please kindly confirm


any slab below the ramp or backfill / what is
height of 300mm thk ramp wall ( please provide
cross section )

ANNEX B/ 6

There is no slab below the


ramp slab and space is to be
backfilled.
To refer to Ramp wall profiles
and extents which are clearly
shown
at
Drawings
14.00050/B and 14.00050/1
Plans. To refer to Tender
Corrigendum No. 2, structural
drawing no. 14.00050/RPD for
ramp profile.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

18

Missing basement sanitary system drawing

Please refer to Tender


Corrigendum No. 1, sanitary
drawing no.: C-SG-003159SA-201 Rev. A and C-SG003159-SA-202 Rev. A.

19

Refer to Arch Drawing No. C-SG-003159/AD/601, No furniture is required at 8th &


there is no layout plan for 8th to 9th floor, please 9th Storey.
clarify whether furniture is required for 8th to 9th
floor?

20

Please advise live load & Superimposed dead SDL=2.7kPa for all Areas
load for every single floor.
except SDL = 4.4kPa for
Landscape/Wet Area and
SDL=7.5kPa for
Roof/kitchen/laundry/outdoor
space.
All those above mentioned
loading are without inclusive of
Hollow Core Slab structural
topping 75mm thick where at
Hollow Core Slab Areas.
Live Load information is
provided at each floor plan
ANNEX B/ 7

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
inside
No. 1.

Tender

Corrigendum

21

Please advise the PC supply rate for all the tiles There will be no PC supply
as clouded.
rates for this contract.
Contractors are to price in
accordance to the drawings
and specifications.

22

Please provide PC supply rate for tiles and vinyl


finishes.

23

Kindly provide the chair detail for system furniture Supply of chairs will be by
type A, B and C.
others.

24

Kindly advise the furniture in conference room


and counselling room at 2nd storey, classroom 1-6
and staff lounge at 3rd storey are under main
contractors scope. If yes, please provide the
detail.

There will be no PC supply


rates for this contract.
Contractors are to price in
accordance to the drawings
and specifications.

Conference room furniture are


provided by main contractor.
Please refer to Tender
Corrigendum No. 2,
architectural drawing No.: CSG-003159/AD/600 Rev. A.
Counselling room (at 2nd
storey) furniture are provided
by others.
Classroom 1 to 6 and Staff
Lounge (at 3rd storey) furniture
are provided by others.
Please note that all chairs are
provided by others.

25

There is indicated system furniture type B in the


hot desk area beside the store 3-3 at 3rd storey
(refer to below). Kindly advise there is how many
type B tables inside that area, as there is no
drawing shown.

ANNEX B/ 8

2 sets of system furniture type


B are to be provided.
Please refer to Tender
Corrigendum No. 2,
architectural drawing No.: CSG-003159/AD/600 Rev. A.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

26

Kindly provide the dimension for WSB1-B5,


drainage sump, gully trap as stated in the
architectural basement floor plan (Dwg. No:
AD/101).

Please refer to Tender


Corrigendum No. 2, sanitary
drawing no.: C-SG003159/SA/201 Rev. B.

27

In 1st storey plan, the slab thickness stated as


200mm thick, but section M-M and section L-L in
1st storey section and detail (Dwg No.
14.0050/1/SD2) stated as 250mm thick. Please
advise.

Please
refer
to
Tender
Corrigendum No. 2, structural
drawing no.: 14.00050/1/SD1
REV A and 14.00050/1/SD2
REV B and 14.00050/B/SD1
REV A

28

Section J in 1st storey section & details (Dwg No.


14.00050/1/SD2 show that there is B-HB25, but
there is no indicated in basement plan (refer to
below).

Please
refer
to
Tender
Corrigendum No. 2, structural
drawing no.: 14.00050/B REV
B and 14.00050/1/SD2 REV B.

29

The reinforcement detail of lift roof slab shown in


upper roof slab top & bottom reinforcement plan (
Dwg. No.14.00050/URS1) is different with lift wall
section A-A shown in drawing No. 14.0050/LW.
Kindly advise.

Please
refer
to
Tender
Corrigendum No.2 Drawing,
structural
drawing
no.:
14.00050/URS1 REV A and
14.00050/ URB1 REV A and

ANNEX B/ 9

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
14.00050/LW REV
14.00050/UR REV B

30

and

Kindly provide the mesh detail for concrete Typical mesh details, required
topping above the hollow core slab
Hollow core type are provided
under Hollow core slab
details. Loading information
with HCS Area Extent is
clearly shown on each plan.
Hollow core slab design with
required strands reinforcement
with necessary precast topping
details with required mesh are
under tenderers specialist PE
design. The tenderer and
specialist tenderer PE are to
make sure to submit the
proposal and price in with
necessary
details
and
design to cater for structural
requirement of provided plan
and
specification.
Any
deviation /additional cost due
to design requirement will not
be accepted after tender
award. All designs that are
assumed
to
be
fully
ANNEX B/ 10

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
compliance
with
tender
requirement shall be deemed
to be included in your tender
offer.

31

Kindly provide the detail for the numbers of Typical


mesh
details,
strands reinforcement in the hollow core slab.
required Hollow core type
are provided under Hollow
core slab details. Loading
information with HCS Area
Extent is clearly shown on
each plan. Hollow core slab
design with required strands
reinforcement
with
necessary precast topping
details with required mesh
are
under
tenderers
specialist PE design. The
tenderer
and
specialist
tenderer PE are to make
sure to submit the proposal
and price in with necessary
details and design to cater
for structural requirement of
provided
plan
and
specification. Any deviation
/additional cost due to
design requirement will not
be accepted after tender
award. All designs that are
assumed
to
be
fully
compliance
with
tender
requirement
shall
be
deemed to be included in
your tender offer.

32

Kindly advise the slab top reinforcement (example To refer to slab reinforcement
refer to below) is distributed for the full length or plan for slab reinforcement
follow the typical detail (refer to below), which is extent.
only 0.2 Lx.

ANNEX B/ 11

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

33

Kindly provide the OAPU-FCU capacity.

34

Please confirm CU capcity needed 35.4 and 41.3 Yes please follow CU capacity
for activity space (L).
as per stated in Tender
Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/403 Rev. A & C-

ANNEX B/ 12

Please refer to Tender


Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/403 Rev. A & CSG-003159/AC/1403 Rev. A.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
SG-003159/AC/1403 Rev. A.

35

Please specify staircase-A, staircase-B MV fan


are serving at Basement or 1st STY. Drawing
no.202 shown as staircase MV fan are serving for
1st STY staircase.

Please refer to Tender


Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/202 Rev. A.

36

Please provide the capacity of AC unit in cloud Please refer to Tender


which are serving for 3rd STY GL:5 & 8 : A & G.
Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/204 Rev. A.

37

Please provide the Schedule/ List of PLC control.

Please refer to ACMV tender


specifications.

38

Please kindly confirm ceiling finishes for


bedrooms ( 4 7 storey ) ( SOF 9mm thk
gypsum board & paint / Ceiling schedule Skimcoat & paint )

No false ceiling required for


4th to 7th storey bedrooms.
Localized box up using 9mm
thick gypsum board & paint for
M&E services only.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural drawing No.: CSG-003159/AD/600 Rev. A.

39

Any requirements of waterproofing to rc fins &


ledge at the external wall?

40

Please confirm total sets for system furniture type We confirm that the quantity
A to 2nd sty; BQ shows 17 while dwg shows 16 for system furniture type A to
2nd storey is 17 sets as
ANNEX B/ 13

Not waterproofing required to


rc fin & ledge at the external
wall.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

only.

indicated in the Schedule of


Works and drawings.

41

Please confirm total sets for system furniture type


B to 2nd sty; BQ shows 9 while dwg shows 3 only.

We confirm that the quantity


for system furniture type B to
2nd storey is 9 sets as shown
in the Schedule of Works and
drawings.

42

Please confirm total sets for system furniture type We confirm that the quantity
B to 3rd sty; BQ shows 11 while dwg shows 2 for system furniture type B to
only.
3rd storey is 11 sets as shown
in the Schedule of Works.

43

Please advise location of brickwalls, drywalls and Brickwalls


Foldable partitions.
provided

are

not

to

be

Drywalls are not to be provided


Foldable partition is to be
provided. It located between
Lounge and Briefing/Training
at 2nd Storey.
44

Please advise thickness of rubber wall tile- 15mm Thickness of rubber wall tile is
as per detail in dwg AD 425 or 12mm thk as per to be 12mm.
wall sched dwg AD 424

45

Please advise total no of controller's cabinet at Total number of 2 controller


10th sty
cabinets to be provided at 10th
storey. These are to be priced
under
Annex
E
I/II

Breakdown Cost For Vertical


Transport Installation.

46

Please advise floor finish to smoke stop lobby- Smoke Stop lobby floor finish
smooth screed finish as per SOF or screed with to be in concrete screed with
hardener as per floor finish plan.
floor hardener.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 09 06 00
SCHEDULE OF FINISHES.

ANNEX B/ 14

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2
47

ANNEX B

Please advise CEILING finish to dining area at 1st Dining area ceiling at 1st
sty- skimcoat with paint as per SOF or mineral Storey is to be 15mm thick
fiber board as per ceiling finish plan.
mineral fibre board.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 09 06 00
SCHEDULE OF FINISHES.

48

Please advise wall finish to M&E shafts; 3mm Wall finish to M&E shafts are
skim with paint as per wall types plan or cement to be 5mm skim coat with
sand plaster as per SOF.
paint.
WT1 and finishes for M&E
shafts as showing in drawing
C-SG-003159/AD/424.

49

50

51

Kindly provide Sanitary Basement Floor Plan.


*(Issued Floor Plans w/ drawing no. SA-201 & SA- Please refer to Tender
Corrigendum No. 1, sanitary
202 were the same Sanitary 1st Storey Plan)
drawing no.: C-SG-003159SA-201 Rev. A and C-SG003159-SA-202 Rev. A.
Some Fresh Air Units do not given the CMH for
Please refer to Tender
OAPU. (refer to attachment)
Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/403 Rev. A & CSG-003159/AC/1403 Rev.A.

3rd Sty - Physiothery / gym the FCU quantity is Quantity is 3.


2 or 3. (refer to attachment)
Please refer to Tender
Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/403 Rev. A & CSG-003159/AC/1403 Rev. A.

ANNEX B/ 15

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

52

53

7th Sty Activity Space (R) A and B - Is Cooling


Capacity 12.5 for 2 FCU or each FCU? Because
of CU Cooling Capacity is 44.3. (refer to
attachment)

ANNEX B

Please refer to Tender


Corrigendum No. 2, ACMV
drawing no.: C-SG003159/AC/403 Rev. A & CSG-003159/AC/1403 Rev. A.

Basement and below graded


Please confirm the basement waterproofing structures
and
Basement
to follow typical waterproofing detail shown in Retaining walls , Basement
C&S drawing 14.00050/N3.
Ramps structures are required
to be cast with water proofing
additive concrete system. To
refer
to
specification for
waterproofing of basements
and below-grade structures.
Lift
pit,
sprinkler
tank/pump/transfer tank &
pump/rainwater detention tank
required
additional
cementitious
waterproofing
membrane.
To
refer
to
architectural
specification
SECTION 07 50 00
MEMBRANE
WATERPROOFING
AND
ROOFING.

54

Please also confirm whether there is requirement


for integral waterproofing like concrete additive for
basement wall, slab and water retention
structures.

Basement and below graded


structures
and
Basement
Retaining walls , Basement
Ramps structures are required
to be cast with water proofing
additive concrete system. To
refer
to
specification for
waterproofing of basements
and below-grade structures.
Lift
pit,
sprinkler
tank/pump/transfer tank &
pump/rainwater detention tank
required
additional
cementitious
waterproofing
membrane.
To
refer
to
architectural
specification
SECTION 07 50 00
MEMBRANE

ANNEX B/ 16

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
WATERPROOFING
ROOFING. .

55

AND

Please advise whether there is any size different There are no size different
for window type W2 and W2a.
between window type W2 and
W2a.
Please refer to architectural
drawing
no.:
C-SG003159/AD/301,
window
schedule for 2nd storey for
details.

56

Please provide door type D8 detail. Missing in Please refer to architectural


AD305.
drawing
no.:
C-SG003159/AD/306.

57

Please advise whether there is any gondola and Please


refer
to
anchorage ring provision on the roof. It is not Corrigendum No.1.
shown on the plan.

58

Please advise the door type for the clouded at This door type is D14 for fire
2nd storey.
extinguisher enclosure.

59

Please advise whether there is any W2 window at No window type W2 is located


2nd storey social worker head room as clouded.
at 2nd storey Social Worker
Head Room.

ANNEX B/ 17

Tender

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

60

Please provide detail of stainless steel shelf in the The stainless steel shelf to be
toilets.
in size of 650mm x 150mm x
1mm
(thick).
Perforated
pattern to SO/SO Reps
selection.

61

Please advise whether the door type clouded This door type is to be D2.
should be type D1 for 10th / 8th storey.

62

Please advise 10th / 8th storey window type W6b We confirm that the quantity
is 26 nos and W10a is 9 nos.
for window type W6b 28 nos
and W10a - 10 nos are correct
as per indicated in the
drawings.

63

The glazing schedule in AD/317 seems Please


refer
to
Tender
incomplete. Please provide complete schedule.
Corrigendum
No.
2,
architectural drawing No.: CSG-003159/AD/317 Rev. A.

64

Please advise the location of use for louver type


L1a, L2b, L3b, L5, L6, 6a, L6b, L7, L7a, L7b,
L7c, L7d, L7e, L8 and L8a. Shown in AD/315
but cannot find on plan schedule.

ANNEX B/ 18

Please
refer
to
Tender
Corrigendum
No.
1,
architectural drawing No.: CSG-003159/AD/311, 312, 313
& 314.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

65

Please advise the location of use for window type Please


refer
to
Tender
AL3. Cannot find on plan schedule.
Corrigendum No. 2, No.
architectural drawing no.: CSG-003159/AD300 Rev.A for
the location.

66

Please confirm female toilet 1-1 has 4 or 3 basins. Female toilet 1-1 has 3 basins
Discrepancy on plan against elevation 6 and as showing in the plan;
sanitary schedule.

67

Please advise the type of finish for external


retaining wall.

External retaining wall is to be


in plaster & paint finish.

68

Discrepancy in Sanitary wares & fittings Schedule


and Toilets plan, please advise which to follow.

Please
refer
to
Tender
Corrigendum No. 2, Sanitary
Wares, Fittings & Accessories
Schedule.

69

Please advise the type of sanitary fittings required


for 3rd storey Janitor, music & speech therapy
room. Not in the Sanitary wares & fittings
Schedule.

Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 22 42 00
SANITARY FIXTURES AND
FITTINGS.

70

Please advise whether there is any vanity


counter for 3rd storey physiothery / Gym room.
The lavatory in the schedule is under-counter
type.

Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 22 42 00
SANITARY FIXTURES AND
FITTINGS.

71

Please advise the link spacing for beams 4HB18 Please


refer
to
Tender
4HB26.
Corrigendum No. 2, structural
drawing no.: 14.00050/4B1
REV A

72

Pls. provide detail for 4-HB47.

ANNEX B/ 19

Please
refer
to
Tender
Corrigendum No. 2, structural
drawing no.: 14.00050/4B1
REV A

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

73

Refer to above part print. Please advise which Parapet height is 1200mm
parapet height to follow.
from finished floor level and
1400mm from structural level.

74

4th 9th storey (Option I) / 4th 7th storey


(Option II), please confirm the HCP toilets have
hand shower set with sliding rail + concealed
shower mixer and concealed box shower head.

Yes. 4th 9th storey (Option I)


/ 4th 7th storey (Option II),
HCP toilets have hand shower
set with sliding rail + concealed
shower mixer.
Please
refer
Corrigendum

ANNEX B/ 20

to
Tender
No.
2,

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
architectural
specification
SECTION 22 42 00
SANITARY FIXTURES AND
FITTINGS.

75

Option 2 cut off pile head for preliminary pile The correct cut off pile head
should be 1000mm diameter.
size for preliminary pile (Option
II)
should
be
1000mm
diameter. Please refer to
revised Schedule of Works
issued as part of Tender
Corrigendum No. 2.

76

Softscape works Schedule of Work indicated 18 Provision for Maintenance for


months Maintenance. Whereas Appendix to Softscape is to be 18 months.
Conditions indicated 12 months DLP. Please
clarify.

77

Please advise whether there is any phase / early No phasing completion


completion requirement for ESS, MDF or any required but all this room need
other rooms.
to be completed and furnished.
Authority approval to be
obtained and handing over to
be done 6 months prior to
energisation.

78

Please assist to provide the schedule of sanitary Please


refer
to
Tender
ware and fitting.
Corrigendum
No.
2,
architectural
specification
SECTION 22 42 00
SANITARY FIXTURES AND
FITTINGS.

79

Refer to Drawing 113 & 114 attached, please There are no screens required
assist to advise the type of finishes for the area at the clouded area.
circled in red.

ANNEX B/ 21

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

80

ANNEX B

Refer to section B-B attached below, the option II Option I is 10 storey.


show it is 10 storey. Please advise.
Option II is 8 storey.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural drawing No.: CSG-003159/AD/110 Rev. A.

81

Refer to the Drawing No: 14.00050/P. Please


kindly provide the detail drawing for ST1 to ST7
and Typical Pile Cap for 3 Pile Group.
ANNEX B/ 22

ST1 TO ST7 pile cap types


and pile caps details are
clearly shown on piling layout

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
plan and pile cap details.
3 PILE GROUP Please refer to
Tender Corrigendum No. 1,
structural drawing no.: Please
refer to Tender Corrigendum
No. 1, structural drawing no.:
14.00050/PC Rev. A. (Option
I) and 14.00050/PC Rev. A.
(option II)

82

Tile nosing on contrasting colour refers ceramic Tile nosing to be used.


tile nosing or photo luminescent nosing strips.

83

Ironmongery schedule please kindly provide 8 Please


refer
to
Tender
storey schedule ( The schedule too small to read ) Corrigendum
No.
2,
architectural drawing no.: CSG-003159/AD/318 Rev. B, CSG-003159/AD/319 Rev. B
and
C-SG-003159/AD/320
Rev. B.

84

Please provide the following Item:(a)


(b)
(c)
(d)

GFA
Scope of work (particular specifications)
Details of project team
CONQUAS score

(a) Approx. GFA breakdown


- 1st Storey: 940 sqm
- 2nd Storey: 1360 sqm
- 3rd Storey: 980 sqm
- 4th Storey: 1120 sqm
- 5th Storey: 1120 sqm
- 6th Storey: 1120 sqm
- 7th Storey: 1120 sqm
- 8th Storey: 1120 sqm
- 9th Storey: 1120 sqm
- 10 Storey: 970 sqm
- Roof: 20 sqm
(b) Please refer to the entire
tender documents &
drawings including all
corrigendum issued.
(c) Architect : Surbana Jurong
Infrastructure Pte Ltd
Structural Engineer
Consultants Pte Ltd

KTP

M&E Engineer : Surbana


Jurong Infrastructure Pte Ltd
Quantity Surveyor : Davis
Langdon KPK (Singapore) Pte
Ltd
(d) CONQUAS Minimum score
ANNEX B/ 23

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
is 84.86 for the whole
Works.

85

Please provide the following Item:(a) Schedule of Sanitary


(b) Schedule of Signages

(a) Please refer to Tender


Corrigendum No. 2,
architectural specification
SECTION 22 42 00
SANITARY FIXTURES
AND FITTINGS.
(b) Please refer to architectural
drawing no.: C-SG003159/AD/700 to 704.

86

Refer to Schedule of Finishes (page AS/361), the


floor finishes for Fire Command Centre (FCC) is
not tally with floor finishes drawings. Kindly advise
which to follow and what is the finishes for raised
floor system if based on the schedule of finishes.

Raised floor system is no


longer required for FCC.
Non-slip homogenous tiles
(600mm x 600mm) with
100mm(ht) x 600mm matching
tiles skirting all round
Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 09 06 00
SCHEDULE OF FINISHES.

87

Refer to Schedule of Finishes (page AS/365), the


floor finishes for Control Room (MPH) is not tally
with floor finishes drawings. Kindly advise which
to follow.

Sub floor to be in concrete


screed with floor hardener
finished + Raise floor system
(with sport vinyl flooring
600mm
x
600mm
and
100mm(ht) x 600mm matching
timber skirting all round) on top
Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 09 06 00
SCHEDULE OF FINISHES.

88

Refer to Schedule of Finishes (page AS/361), the Dining area ceiling at 1st
ceiling finishes for Dining Area (skim coat) is not Storey is to be 15mm thick
tally with ceiling finishes drawings (mineral fibre mineral fibre board.
board). Kindly advise which to follow.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural
specification
SECTION 09 06 00
ANNEX B/ 24

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
SCHEDULE OF FINISHES.

89

Refer to Drawing No. C-SG-003159/AD313, there


is landscape area for window grille & louver
schedule at 5th 7th storey while refer to Drawing
No. C-SG-003159/AD105, the landscape area is
located at 4th storey. Kindly advise for the window
grilles & louver schedule for 4th storey and 5th
7th storey.

The landscape area is located


at 4th Storey only.
Please
refer
to
Tender
Corrigendum
No.
2,
architectural drawing no.: CSG-003159/AD/313 Rev. A.

90

Please provide the details for operable partitions Please refer to architectural
(at 2nd storey)
drawing
no.:
C-SG003159/AD/427 and C-SG003159/AD/901.

91

There are a few items that contradict as below:(a) Lift interior Finishes:

(a) As per tender specification


stated, the material of lift
interior is hairline finished
grade S.S 316

Lift finishes should follow which drawing (Drawing


No:
C-SG-003159/EE/LF/100
&
C-SG- (b) Please refer to the Tender
003159/AD/254) Drawings shown (Hairline
Corrigendum No.2 Drawing
S.Steel) vs scope of work specification shown
No. C-SG(S.Steel 316)
003159/EE/LF/100 Rev. A
(Option 1) and C-SG003159/EE/LF/1100 Rev. A
(Option 2)
(b) Lift Car Size:
- In Drawing C-SG-003159/EE/LF/100
(Option
1)
&
C-SG003159/EE/LF/1100 (Option 2)
- The Interior Car Height is 2300mm or
2800mm
- The cabin size as per dwg is:
1550mm(W)x2400mm(D),
the
lift
schedule is: 1550mm(W)x2300mm(D)
92

Discrepancies between drawings and scope of (a) No vision panel required.


work (Vol 2_Part 4 of 5_006_Vertical Transport)
pages VTS/1 to VTS/6,etc.) Please confirm the (b) The scaffolding works shall
following item:be included in scope of
work.
(a) Archi
dwgs
(C-SG003159/AD/251,252&254) showing the lift
elevations, etc. but does not provide any
vision panel for the car/landing doors. Our
PSB endorsed vision panel is 140mm x
600mm for the 1hr Fire-rated.

(b) M&E specification - vertical transport


ANNEX B/ 25

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B

pages (VTS/6) - requests for scaffolding


to be included in the scope of work.

93

With reference to part print of drawing no Please


refer
to
Tender
14.00050/B below, please confirm the slab Corrigendum No. 2, structural
thickness at Basement.
drawing no.: 14.00050/B Rev.
B.

94

Please furnish Lift drawings

95

Please provide beam detail as shown in below 2HB41 A- Please refer to


table:
Tender Corrigendum No.2,
structural
drawing
no.:14.00050 /2B1 REV B

Please refer to the Tender


Corrigendum No.2 Drawing
No. C-SG-003159/EE/LF/100
Rev. A (Option 1) and C-SG003159/EE/LF/1100 Rev. A
(Option 2)

2VB 5,2VB6,2VB8
Please
refer to Tender Corrigendum
No.1, structural drawing no 14.00050 /2B2 REV A
3HB30,3HB31 Please refer to
Tender Corrigendum No.1,
structural
drawing
no
14.00050 /3B1 REV A
3-HB 24 Please refer to
Tender , structural drawing
14.00050 /3B1
4HB 4 Please refer to Tender ,
structural
drawing
ANNEX B/ 26

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2

ANNEX B
14.00050/4B1
4HB 47, 4HB 48 Please refer
to Tender Corrigendum No.2,
structural drawing no 1400050/4B1 REV A
T-HB 27A Please refer to
Tender Corrigendum No.2,
structural drawing no 1400050/5,6,7-B1 REV A
T-8&9 HB 28, Please refer to
Tender, structural drawing
14.00050/8-9B1.
10HB24 Please refer to
Tender Corrigendum No.2,
structural drawing no -1400050/10B1 REV A
10-HB28 Please refer to
Tender, structural drawing
14.00050/10B1
10-HB40
AND
10-HB40A
Please
refer
to
Tender
Corrigendum No.2, structural
drawing no 14-00050/10B1

96

Request for Topo plan.

Please
refer
to
Corrigendum No. 2.

97

Missing rebar links for 4 sty beam schedule 1

Please
refer
to
Tender
Corrigendum No. 2, structural
drawing no.: 14.00050/4B1
REV A

( 4-HB18 4-HB26 )

98

Kindly advise whether there is service ledge


behind the water closet in the toilet at 1st, 2nd ,4th 9th storey and accessible toilet at 10th storey, as
there is not indicated in the toilet plan, but is
indicated in the typical toilet detail (Dwg No.
AD226).

ANNEX B/ 27

Tender

Please refer to architectural


drawing
no.:
C-SG003159/AD211
to
C-SG003159/AD225.

SOCIAL COMMUNITY FACILITY AT COMPASSVALE BOW


TENDER CLARIFICATION NO. 2
99

ANNEX B

Kindly advise the material of window grille is steel, All material of window grille is
aluminium or other material.
steel with powder coated
finish.

ANNEX B/ 28