Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Fume hood
From Wikipedia, the free encyclopedia
[hide]This article has multiple issues. Please help improve it or discuss these issues on the talk pa
This article needs additional citations for verification. (February 2010)
This article possibly contains original research. (February 2010)
Fume hood
Other names
Hood
Fume cupboard
Uses
Fume removal
Blast shield
Related items
A fume hood or fume cupboard/closet is a type of local ventilation device that is designed to limit
exposure to hazardous or toxic fumes, vapors or dusts. A fume hood is typically a large piece of
equipment enclosing five sides of a work area, the bottom of which is most commonly located at a
standing work height.
Two main types exist, ducted and recirculating (ductless). The principle is the same for both types:
air is drawn in from the front (open) side of the cabinet, and either expelled outside the building or
made safe through filtration and fed back into the room. This is used to
protect the user from inhaling toxic gases (fume hoods, biosafety cabinets, glove boxes);
protect the environment (recirculating fume hoods, certain biosafety cabinets, and any other
type when fitted with appropriate filters in the exhaust airstream).
Secondary functions of these devices may include explosion protection, spill containment, and other
functions necessary to the work being done within the device.
Contents
[hide]
3Control panels
4Types
o
4.2Auxiliary air
6.4Radioisotope hood
6.5Scrubber
6.6Waterwash
7Energy consumption
10Maintenance
11See also
12References
13External links
Epoxy Resin
Cement Board
Control panels[edit]
Most fume hoods are fitted with a mains-powered control panel. Typically, they perform one or more
of the following functions:
Specific extra functions can be added, for example, a switch to turn a waterwash system on or off.
Types[edit]
Ducted fume hoods[edit]
Most fume hoods for industrial purposes are ducted. A large variety of ducted fume hoods exist. In
most designs, conditioned (i.e. heated or cooled) air is drawn from the lab space into the fume hood
and then dispersed via ducts into the atmosphere.
The fume hood is only one piece of the lab ventilation system. As the recirculation of lab air to the
rest of the facility is not permitted, air handling units serving the non-laboratory areas are kept
segregated from the laboratory units. As a means of improving indoor air quality, some laboratories
also utilize single-pass air handling systems, where air that is heated or cooled is used only once
prior to discharge. Many laboratories continue to utilize return air systems to the laboratory areas to
minimize energy and running costs, while still providing adequate ventilation rates for acceptable
working conditions. The fume hoods serve to evacuate hazardous levels of contaminant.
To reduce lab ventilation costs, variable air volume (VAV) systems are employed, which reduce the
volume of the air exhausted as the fume hood sash is closed. This product is often enhanced by an
automatic sash closing device, which will close the fume hood sash when the user leaves the fume
hood face. The result is that the hoods are operating at the minimum exhaust volume whenever no
one is actually working in front of them.
Since the typical fume hood in US climates uses 3.5-times as much energy as a home, [6] the
reduction or minimization of exhaust volume is particularly beneficial in reducing facility energy costs
as well as minimizing the impact on the facility infrastructure and the environment. Particular
attention must be paid to the discharge location, so as not to risk public safety, or to pull the exhaust
air back into the building supply air system.
Auxiliary air[edit]
This method is outdated technology. The premise was to bring non-conditioned outside air directly in
front of the hood so that this was the air exhausted to the outside. This method does not work well
when the climate changes as it pours frigid or hot and humid air over the user making it very
uncomfortable to work or affecting the procedure inside the hood. This system also uses additional
ductwork which can be costly.
"High-performance" or "low-flow" bypass CAV hoods are the newest type of bypass CAV hoods and
typically display improved containment, safety, and energy conservation features. Low-flow/high
performance CAV hoods generally have one or more of the following features: sash stops or
horizontal-sliding sashes to limit the openings; sash position and airflow sensors that can control
mechanical baffles; small fans to create an air-curtain barrier in the operators breathing zone;
refined aerodynamic designs and variable dual-baffle systems to maintain laminar (undisturbed,
nonturbulent) flow through the hood. Although the initial cost of a high-performance hood is typically
more than that of a conventional bypass hood, the improved containment and flow characteristics
allow these hoods to operate at a face velocity as low as 60 fpm, which can translate into $2,000 per
year or more in energy savings, depending on hood size and sash settings. [11]
hood will simply cause the lab room's air handler to increase from 1000 CFM to 2000 CFM, thus
resulting in no net reduction in air exhaust rates, and thus no net reduction in energy consumption. [15]
In a survey of 247 lab professionals conducted in 2010, Lab Manager Magazine found that
approximately 12% of fume hoods are VAV fume hoods.[16]
Cons
Additional ductwork.
Low maintenance.
Pre-filtration: This is the first stage of filtration, and consists of a physical barrier, typically
open cell foam, which prevents large particles from passing through. Filters of this type are
generally inexpensive, and last for approximately six months depending on usage.
Main filtration: After pre-filtration, the fumes are sucked through a layer of activated
charcoal which absorbs the majority of chemicals that pass through it. Ammonia andcarbon
monoxide will, however, pass through most carbon filters. Additional specific filtration techniques
can be added to combat chemicals that would otherwise be pumped back into the room. A main
filter will generally last for approximately two years, dependent on usage.
Ductless fume hoods are often not appropriate for research applications where the activity, and the
materials used or generated, may change or be unknown. As a result of this and other drawbacks,
some research organizations, including the University of Wisconsin, Milwaukee, [18] Columbia
University,[19] Princeton University,[20] the University of New Hampshire,[21] and the University of
Colorado, Boulder[22] either discourage or prohibit the use of ductless fume hoods.
A benefit of ductless fume hoods is that they are mobile, easy to install since they require no
ductwork, and can be plugged into a 110 volt or 220 volt outlet.
In a survey of 247 lab professionals conducted in 2010, Lab Manager Magazine found that
approximately 22% of fume hoods are ductless fume hoods.[23]
Pros
Cons
Radioisotope hood[edit]
This fume hood is made with a coved stainless steel liner and coved integral stainless steel
countertop that is reinforced to handle the weight of lead bricks or blocks.
Scrubber[edit]
This type of fume hood absorbs the fumes through a chamber filled with plastic shapes, which are
doused with water. The chemicals are washed into a sump, which is often filled with a neutralizing
liquid. The fumes are then dispersed, or disposed of, in the conventional manner.
Waterwash[edit]
These fume hoods have an internal wash system that cleans the interior of the unit, to prevent a
build-up of dangerous chemicals.
Energy consumption[edit]
Because fume hoods constantly remove very large volumes of conditioned (heated or cooled) air
from lab spaces, they are responsible for the consumption of large amounts of energy. Key statistics
laid out in a 2006 article by Evan Mills et al.:[24]
For standard two-meter (six-foot) hoods, per-hood energy costs range from $4,600/year for
moderate climates such as Los Angeles, USA to $9,300/year for extreme cooling climates such
as Singapore.
With an estimated 750,000 hoods in use in the U.S., the aggregate energy use and savings
potential is significant. Mills et al. estimate the annual operating cost of U.S. fume hoods at
approximately $4.2 billion, with a corresponding peak electrical demand of 5,100 megawatts.
As a result, fume hoods are a major factor in making typical laboratories four to five times
more energy intensive than typical commercial buildings. [25]
With emerging technologies, per-hood savings of 50 percent to 75 percent can be safely and
cost-effectively achieved while addressing the limitations of existing strategies.
The bulk of the energy that fume hoods are responsible for is the energy needed to heat and/or cool
air delivered to the lab space. Depending on the type of HVAC (heating, ventilation, and air
conditioning) system installed, this energy can be electricity, natural gas, heating oil, coal, or other
energy types. Additional electricity is consumed by fans in the HVAC system and fans in the fume
hood exhaust system.[26]
Harvard University:[27] A "Shut the sash" campaign in the Chemistry & Chemical Biology
(CCB) Department resulted in a sustained ~30 percent reduction in fume hood exhaust rates as
a result of increased attentiveness to fume hood sash height. The total pre-campaign exhaust
from the 150 VAV fume hoods monitored was 85,000 cubic feet/minute (CFM), and the postcampaign average 59,000 CFM. This translated into cost savings of approximately $180,000 per
year, and a greenhouse gas emission reduction of 300 MTCDE (metric tons carbon dioxide
equivalent). The campaign included a number of components:
Competition: A competition in which labs competed against each other to reduce their
fume hood energy use the most
Goal Setting: Monthly goals were set for each lab. These goals were re-evaluated as
research groups size changes and as their work changes to more or less hood-intensive
research.
Incentives: Labs that achieved their monthly goal were entered into a monthly raffle
in which they could win movie passes or a beer & pizza party. Labs that met their monthly
goal at least 4 of the most recent 6 months were invited to highly popular bi-annual wine &
cheese parties.
Feedback: Real time meters at the exit to most labs allow users to quickly check
whether all the hoods are closed each evening if they are the last one to leave the lab.
Feedback on performance is distributed twice a month once to let lab users know if they
are on track for their goal, and the other time to let them know who won the raffle that
month.
Air volume through all VAV hoods in the department is modulated by a Venturi-type
air valve by Phoenix Controls. A nominal face velocity of 100 ft/min is maintained. Data from
sash position sensors on each fume hood are sent to a central processor that controls
laboratory-scale and building-level exhaust. Software automatically collects and redistributes
the 15 minutes average sash position by laboratory from this central database
The rst fume hood behavior intervention in the MIT Chemistry Department occurred
mid-November 2006, when the Chemistry Departments EHS Coordinator reinforced the
importance of closing fume hood sashes at the regularly scheduled EHS laboratory
representative meeting. The presentation covered the reasons for shutting the sash (cost
savings, benet to the environment, personal safety), a description of how fume hoods work
and how energy is consumed, the dangers of improper fume hood use, and the magnitude
of the potential energy savings (up to $400/inch of hood opening per year in the widest
hoods in the Chemistry Department (and $80/in/year for the hoods in Building 18).
Representatives were encouraged to respond after the presentation and after discussion
with their labs. This message was reinforced by an e-mail from the department head to the
faculty with the goal of ensuring the entire department was familiar with the program. The
shut-the-sash message was subsequently integrated into the Chemistry Departments EHS
training sessions that are required for all new graduate students.
The second intervention was the release of fume hood use data to the faculty
principal investigator in charge of each lab. The rst datasets were distributed by the
department EHS coordinator to the Chemistry faculty in early August 2007. These data were
then distributed to other members of the lab at the faculty PIs discretion.
Findings: Average sash height was lowered by 26 percent (from 16.3 +- 0.85 percent
open to 12.1 +- 0.39 percent open) throughout the department, saving an estimated
$41,000/year. Sash position during inactive periods was lowered from 9 to 6 percent open.
Half of all department savings occurred in four (of 25) labs. Energy savings are substantially
less than original expectations because most installed fume hoods use combination sashes.
Labs with vertical sashes use the most energy, and see the most savings from the
intervention.
North Carolina State University [29] - During sash closing campaigns conducted at the
beginning of each semester, Energy Management and Environmental Health and Safety conduct
campus presentations highlighting the Universitys responsibility to conserve energy and provide
safe working conditions with the goal of educating scientists and research assistants on proper
lab protocol and ways to reduce their carbon footprints. Sash opening labels have been placed
on all fume hoods on campus to serve as constant reminders for all lab users. In addition to
these campaigns, periodic surveys are conducted to inventory which labs are practicing correct
lab safety procedures. These surveys also highlight buildings with high energy consumption
where further monitoring or outreach is needed.
University of British Columbia[30][31] UBC held their first fume hood competition in 2012.
Over the course of the six weeks competition, an 85 per cent reduction in fume hood energy
consumption was achieved. Six labs were recognized for exemplary fume hood practices at a
wrap-up event attended by 130 researchers, with first place groups receiving $500 and second
place groups receiving $250. All winning groups also received a commemorative sash (pun
intended).
University of California, Berkeley[32] UC Berkeley's Shut the Sash Fume Hood Campaign
educates lab researchers to close the sashes on fume hoods when they are not in use to reduce
energy consumption and improve air quality. As of May 2011, the program targets Tan Hall and
uses stickers, flyers, and emails to disseminate information. It also involves a competition to see
which lab can Shut the Sash most consistently.
University of California, Davis:[33] In summer 2009, about 600 vinyl stickers were installed
on the exterior sidewall of fume hoods in ten buildings at UC Davis. The sticker uses a traffic
light color scheme, with a red zone above 18 inches, and a large arrow pointing down with the
words, More Safe, Less Energy changing from yellow at the midpoint to green at the bottom
when the sash is closed completely. Visual surveys of sash-position status were conducted
before sticker deployment, about 2 months after sticker installations, and again in spring, 2011,
to assess persistence. The survey method estimated sash status by benchmarks in approximate
quartiles to streamline the survey effort. This also helped capture information on VAV-system
response. These benchmarks were incorporated into energy savings calculations. Sash
positions were averaged by floors at each sample time. Survey results showed 90-100%
compliance 22 months after installation with no additional reinforcement of closure. Given a per
hood sticker installation cost of $5 and a conditioned air cost of $7/CFM/year, the simple
payback of the project was estimated to be 15 hours, and the return on investment (ROI) was
estimated to be 599%.
University of California, Irvine:[34] In order to get the fume hoods sashes closed, UC Irvine's
PowerSave Campus Program uses a three-pronged approach. The first method is direct
education, in which teaching assistants (TAs) are asked to encourage their students to close the
hoods before leaving the labs. The second approach is placing point-of-decision reminder
stickers on the hoods themselves, explaining that a closed fume hood saves up to 50,000 lbs of
CO2 a year. The third method is an incentive-based competition among three buildings that
contain fume hoods. During the three-week competition, volunteers periodically audit the
buildings fume hoods, noting the total number of inches each fume hood has been left open.
The building with the fewest total number of inches at the end of the competition wins a catered
luncheon for its professors and lab users, and an energy-efficiency certificate provided by the
Green Campus Program. In 2007, the Fume Hood Use campaign won an award for Best
Practices in Student Energy Efficiency, at the sixth annual Sustainability Conference at UCSanta Barbara, beating all other PowerSave Campus Programs in the UC system. The
PowerSave Campus team estimates that the Fume Hood Use campaign saves over 80,000 lbs
of CO2 and $13,000 every quarter.
University of California, Los Angeles:[35][36][37] As its first initiative, UCLA EH&S's Laboratory
Energy Efficiency Program (LEEP) jointly sponsored a competition with the Alliance to Save
Energy's PowerSave Campus Program to encourage reduced fume hood sash heights in
research laboratories. The first fume hood competition took place in the Molecular Sciences
Building (MSB) during Fall 2008 and included about 230 fume hoods. Overall, the competition
saw a 40% sash height decrease from 13.4 to 8 (as shown by competition behavior and the
long-term followup). In order to identify the lasting, long-term behavior change, LEEP and UCLA
PowerSave Campus conducted follow-up audits each month after the competition. Sash heights
were measured throughout one week, using the same method for recording baseline
measurements. The follow-up data showed that MSBs new average sash height was 7.8a
5.6 decrease from baseline measurements. Ultimately, this 40% reduction translates into an
annual estimated savings of 1,415,278 lbs of CO2 emissions and $149,730. Several additional
competitions have been held following the success of this original one.
University of California, Riverside:[38] Make posters & stickers available for download on
their website.
University of California, San Diego:[39][40] The UC San Diego Annual Shut the Sash
Competition is a 5-week campaign sponsored by the PowerSave Campus Program, Facilities
Management, Environmental Health & Safety, and the Biology Department. The first competition
began in January 2009 and, as of October 2012, has happened every year since. The campaign
involves 11 labs in a challenge to reduce their energy consumption and improve air quality by
closing the sashes on fume hoods when not in use. The Shut the Sash competition helps
promote energy savings by challenging laboratories to save more energy than other laboratories
from a set baseline. The Shut the Sash Competition educated researchers, raised awareness of
lab energy efficiency and showed real savings in energy use and cost. On average, there was a
27 percent reduction in sash heights over a five-week period in 2009. The Shut the Sash
competition and awareness campaign also saves 21,734 kWh/year or $1695.25 annually,
assuming sash heights stay at a similar level.
University of California, Santa Barbara:[41] In summer 2009, about 200 vinyl were installed
on the exterior sidewall of fume hoods in seven buildings at UC Santa Barbara. The sticker uses
a traffic light color scheme, with a red zone above 18 inches, and a large arrow pointing down
with the words, More Safe, Less Energy changing from yellow at the midpoint to green at the
bottom when the sash is closed completely. Surveys were conducted by collecting real-time
sash position data provided by the campus building monitoring system (BMS). Data were
collected for 10-day periods prior to sticker installation for select fume hoods, and one, two, and
three months following sticker installation. The average sash height for each hood was
calculated for each 10-day period. In the Engineering Science Building, average sash opening
was ~15 inches prior to sticker installation, ~6.5 inches 3 months after sticker installation, and
~9.5 inches 23 months after sticker installation. In the California NansoSystems Institute
building, average sash opening was ~7.5 inches prior to sticker installation, ~6 inches 3 months
after sticker installation, and ~5 inches 23 months after sticker installation.
University of Toronto[44] The University of Toronto ran their first fume hood sash closing
campaign from October 2008 until March 2009. The campaign included workshops, posters, a
website, and individual and group competitions. Before the campaign, sashes were regularly left
in the same position whether the hoods were in use or not (around 11 inches). During the
campaign, sash heights of unused hoods dropped to just under 4 inches on average, resulting in
estimated annual savings of at least 49,000 kWh of electricity, 770 mmBTU of heating energy
and 51 tonnes of greenhouse gases and as much as 240,000 kWh, 3800 mmBTU of heating
energy and 260 tonnes of greenhouse gases. The changes also resulted in between $20,000
and $100,000 in energy cost savings annually. When the campaign organizers inspected sash
heights 7 months after the conclusion of the campaign, they found that users had largely
reverted to pre-campaign habits.
Maintenance[edit]
Fume hood maintenance can involve daily, periodic, and annual inspections.
The fume hood area is visually inspected for storage of material and other visible
blockages.
If hood function indicating devices are not a part of the fume hood, a 1-inch (25 mm)
by 6-inch (150 mm) piece of soft tissue paper should be placed at the hood opening and
observed for appropriate directional flow into the hood.
Other local exhaust devices shall be smoke tested to determine if the contaminants
they are designed to remove are being adequately captured by the hood.
Annual maintenance**
Exhaust fan maintenance, (i.e.,lubrication, belt tension, fan blade deterioration and rpm), shall be in
accordance with the manufacturers recommendation or as adjusted for appropriate hood function.
There are two basic types of laboratory fume hoods: conventional and bypass. Conventional hoods consist of a basic
enclosure with a movable sash (or window). Since the face velocity, or pull, is a function of the total volume divided
by the area of the sash opening, closing the sash on a conventional CAV hood will increase the face velocity. The
conventional hoods performance depends primarily on sash position.
However, as the sash is closed, velocities can increase to the point where they disturb instrumentation and delicate
apparatuses, cool hot plates and slow reactions, or create turbulence that can force contaminants into the room.
Bypass hoods contain openings above the sash, in addition to an airfoil sill that will redirect the airflow as the sash is
closed. The bypass openings reduce changes in face velocity to a narrow range by keeping the area for airflow equal
(within the limits of the bypass) as the sash is moved up or down. Therefore, face velocities do not reach the
detrimental levels often seen with conventional hoods. For this reason, bypass hoods hold a major share of the
market today.
Recent models of bypass hoods, called high-performance or low-flow hoods, display improved containment and
safety features as well as energysaving designs. These design features vary by manufacturer but generally have one
or more of the following: sash stops or horizontal-sliding sashes to limit the openings; sash position and airflow
sensors that can control mechanical baffles; small fans to create an air-curtain barrier in the operators breathing
zone; and refined aerodynamic designs and variable dual-baffle systems to maintain laminar (undisturbed,
nonturbulent) flow through the hood. Although the initial cost of a high-performance hood is slightly more than that of
a conventional bypass hood, the improved containment and flow characteristics allow these hoods to operate at a
face velocity as low as 60 fpm, which can translate into $2,000 per year or more in energy savings, depending on
hood size and sash settings.1
Reduced air volume (RAV)
In laboratory settings where the tasks may be very specific and unchanging, the reduced air volume hood (a variation
of the low-flow hood) is an option to consider. This design incorporates a bypass block to partially close off the
bypass, reducing the air volume and thus conserving energy. Usually, the block is combined with a sash stop to limit
the height of the sash opening, ensuring a safe face velocity during normal operation while lowering the hoods air
volume. By reducing the air volume, the RAV hood can operate with a smaller blower, which is another costsaving
advantage.
One downside to the RAV hood is that its restricted sash movement and reduced air volume also constrain its
flexibility and narrow the realm of tasks that can be performed. Another major caution to note is the potential to
override or disengage the sash stop. If this occurs, the face velocity could drop to an unsafe level. To counter this
condition, operators must be trained never to override the sash stop while in use, and only to do so when loading or
cleaning the hood. In addition, an airflow monitor is always recommended.
Variable air volume (VAV)
The newest generations of laboratory fume hoods vary the volume of room air exhausted while maintaining the face
velocity at a predetermined level. Variable air volume hoods change the exhaust volume using different methods,
such as a damper or valve in the exhaust duct that opens and closes based on sash position, or a blower that
changes speed to meet air-volume demands. Most VAV hoods integrate a modified bypass-block system that
ensures adequate airflow at all sash positions. They are connected electronically to the laboratory buildings HVAC,
so hood exhaust and room supply are balanced. In addition, VAV hoods feature monitors and/or alarms that warn the
operator of unsafe hood-airflow conditions.
Although VAV hoods are much more complex than traditional constant-volume hoods, and correspondingly have
higher initial costs, they can provide considerable energy savings by reducing the total volume of conditioned air
exhausted from the laboratory. Since most hoods are operated the entire time a laboratory is open, this can quickly
add up to significant cost savings.
1. How to Select the Right Laboratory Hood System, Labconco Corp., Kansas City, Mo., 2003.
Chemical Fume Hood Handbook, Northwestern University, Chicago, Ill. Last revision, May 2007. http://www.research.
northwestern.edu/research/ors/labsafe/hoods/index.htm
National Research Council Recommendations Concerning Chemical Hygiene in Laboratories, U.S. Department of
Labor, Occupational Safety and Health Administration, Washington, DC.
http://www.osha.gov/pls/oshaweb/owadisp.show_ document?p_table=STANDARDS&p_id=10107
Categories: Lab Health and Safety
Tags: Fume Hoods, Biological Safety Cabinets, Clean Rooms, Product Resource: Resources
Purchasing the correct fume hood for your laboratory is a very important, long-term decision and your choice in lab
ventilation systems will affect future lab planning, flexibility and safety. The Lab Manager Fume Hood Product
Finderenables you to quickly and easly compare the newest fume hood models and request information and pricing
from leading manufacturers. If you are in the market for a new fume hood, simply answer the questions below to
begin your search for the laboratory fume hood that best suits your needs.
Fume Hoods
Cole-Parmer offers a wide variety of fume hoods for every laboratory application including
general purpose hoods, vented enclosures, ducted fume hoods, biosafety and PCR enclosures,
and extractor systems. Choose from many trusted names including Labconco, Erlab, and Hemco.
Need assistance in choosing the right fume hood for your needs? Contact our Application
Specialists for further assistance.
Types of Fume Hoods
Balance Enclosures provide user protection by keeping powders, particulates and fumes
contained during weighing procedures. Balance Enclosures may be ducted to the outside or
connected to a HEPA and/or carbon filtered exhaust back into the laboratory.
Ductless Fume Hoods are enclosures that pass contaminated air through a filter(s) before
returning air to the room. Use for locations where outside ventilation can not be achieved. Can
eliminate very high percentages of particulates and biological hazards. Select airborne chemical
levels can be reduced to safe levels as verified with monitoring protocols.
Ducted Fume Hoods have ventilation to outside provides the most rigorous user protection,
particularly for chemically dangerous fumes. Many employ "by-pass" designs, which enable
consistent airflows in the enclosure for various sash positions. Low airflow designs provide user
protection while minimizing energy costs.
Biological Safety Cabinets provide effective containment for working with human pathogens.
BSC cabinets have three classes as sedignated by the National Sanitation FoundationClass I, II,
and III, with some sub class levels.
BSC Class I have an un-recirculated airflow away from the lab worker that, after going through
a HEPA filter, is vented into the room. They provide the lab worker medium protection but do
not protect the samples in the bacinet from contamination.
BCS Class II should be used if a lab worker is using microorganisms in containment levels 2,
3,bs. These cabinets are divided into two typesA and B, determined by construction, airflow
velocities, patterns, and exhaust systems. They protect the lab worker, samples, and the external
environment.
BCS Class III have both HEPA filtered supply and exhaust air and are totally gas tight and
enclosed. Tests are performed while using long sleeved gloves. The cabinet is under negative
pressure of at least 120 Pa while the exterior exhaust system maintains airflow. This protects the
lab worker, samples, and the external environment.
PCR Enclosures are designed specifically to privide a Class 5 work space for PCR experiments
by moving HEPA filtered air downward. PCR enclosures are unique in that they have a UV light
that eliminates DNA and RNA contaminates
Extractor Systems provide localized ventilation at the contaminant source. Extractor arms can
be easily positioned to remove fumes or air-borne particulates. Often used when the fume source
can not be readily moved to a conventional hood or when fumes are innocuous, e.g. bad-smelling
without being chemically dangerous. May vent to outside or recirculate into the room through a
filter.
Don't forget all our fume hood Accessories
Need
Assistance?
Get help from
our Experts!
or call 1-847-549-7600
Learn how chemical fume hoods protect lab workers, types of fume hoods, the
limitations, and UCSD's inspection and certification program.
NOTE: All chemical fume hoods must meet the requirements of Title 8, California Code of
Regulations, Section 5154.1.
Expand all
Definition
Cal/OSHA Fume Hood definition:
A device enclosed except for necessary exhaust purposes on three sides and top and
bottom, designed to draw air inward by means of mechanical ventilation, operated with
insertion of only the hands and arms of the user, and used to control exposure to hazardous
substances. These devices are also known as laboratory fume hoods.
Purpose
Chemical fume hoods, when used properly, are one of the most reliable engineering controls in the
laboratory. They protect workers by:
Containing vapors, dusts, gases, and fumes generated within the hood, and removing them
as air flows into the hood and then out via the laboratory exhaust system
Shielding the worker with a clear sliding window, called a sash, that contains aerosols and
prevents injury from splashes, fires, or minor explosions that may occur inside the hood
Follow Chemical Fume Hood Use Guidelines to ensure safe and effective fume hood operation.
Types
There are 2 kinds of fume hoods in use at UCSD:
VAV fume hoods are equipped with a monitor (see image at right) that
indicates whether the hood is in "standard operation" or "standby operation" mode. The fume hood
monitor also has an "emergency purge" button, which increases airflow through the hood to
maximum and can be used to quickly remove air contaminates from the lab.
VAV fume hoods are equipped with flow sensors that activate an audible alarm when malfunctions
occur. Contact Facilities Management, (858) 534-2930, if your fume hood alarm sounds.
Limitations
Biohazardous materials
Fume hoods are not for use with biohazardous materials.
Use a biological safety cabinet, (BSC), for work with infectious agents. BSCs are designed to protect
the worker and the environment from biological agents, and to protect the research materials from
contamination.
Certification
Check the laboratory room pressure differential (the room pressure must be negative to nonlaboratory space)
Confirm the face velocity is within the required specification of 100 linear feet per minute
(lfm)
If you suspect your fume hood is not operating properly, contact Environment, Health & Safety, (858)
534-5427.
Learn more
Learn more about basic airflow and operation of a Labconco fume hood, including proper work
procedures and detailed information on the movement of air in and around the hood in this video
from LabconcoCorporation.
operator from exposure to toxic vapors, gases, fumes, and particulate. AirClean Systems ductless solutions
incorporate a state-of-the-art microprocessor safety controller and revolutionary gas phase bonded-carbon
filtration.
AirClean Systems produces laboratory fume hoods in a wide array of sizes and configurations, allowing you
ultimate flexibility in choosing the level of protection, mobility and work area size. Narrow your hood search by
clicking on one of the categories below:
Independence Ductless Fume Hoods
o
Free-Standing Enclosures
o
Full and easy access for equipment loading, maintenance and cleaning
Designed to meet application requirements while adhering to strict regulatory guidelines for
operator safety or process integrity
Design incorporated microprocessor safety control, bonded carbon filtration and high
performance blowers and fans for user friendly operation and performance
UniFlow SE AireStream
UniFlow LE Fume
Hoods
UniFlow CE Fume
Hoods
UniFlow
H
UniFlow FM SE
48, 60, 72, 9
of 30
UniFlow FM LE Fume
Hoods
UniFlow
UniFlow Auxilia
hood available
UniFlow Perchloric
Acid
UniFlow Perchloric Acid fume hood
low flow constant in sizes 48", 60", &
72" wide
HEMCO Corporation711 S. Powell Road Independence, MO 64056816-796-2900800-7794362 Copyright 2010 HEMCO Corporation All Rights Reserved
UniFlow
UniFlow Rad
offered in , 4
One of the primary safety devices in a laboratory is a chemical fume hood. A welldesigned hood, when properly installed and maintained, can offer a substantial degree
of protection to the user, provided that it is used appropriately and its limitations are
understood.
This section covers a number of topics aimed at helping laboratory workers understand
the limitations and proper work practices for using fume hoods and other local
ventilation devices safely.
There are basically two types of fume hoods at Baylor University, they are:
Constant volume where the exhaust flowrate or quantity of air pulled through the
hood is constant. Therefore, when the sash is lowered and the cross-sectional area of the
hood opening decreases, the velocity of airflow (face velocity) through the hood
increases proportionally. Thus, higher face velocities can be obtained by lowering the
sash.
And variable air volume (VAV) - where the exhaust flowrate or quantity of air pulled
through the hood varies as the sash is adjust in order to maintain a set face velocity.
Therefore, when the sash is lowered and the cross-sectional area of the hood opening
decreases, the velocity of airflow (face velocity) through the hood stays the same while
less total air volume is exhausted.
Adequate planning and preparation are key.The hood user should know
theStandard Operating Configuration (SOC) of the hood and should design
experiments so that the SOC can be maintained whenever hazardous materials might be
released. The SOC refers to the position of the sash. A schematic drawing of the SOC is
displayed on the front of each chemical fume hood.
2.
The hood user should also check the magnehelic gauge or other hood
performance indicator and compare its reading to the reading indicated on the hood
survey sticker. If the reading differs significantly (15% or more for a magnehelic gauge)
from that on the sticker, the hood may not be operating properly.
Items contaminated with odorous or hazardous materials should be removed from the
hood only after decontamination or if placed in a closed outer container to avoid
releasing contaminants into the laboratory air.
When using cylinders containing highly toxic or extremely odorous gases, obtain only
the minimal practical quantity. Consider using a flow-restricting orifice to limit the rate
of release in the event of equipment failure. In some circumstances, exhaust system
control devices or emission monitoring in the exhaust stack may be appropriate.
To optimize the performance of the fume hood, follow the practices listed
below:
Mark a line with tape 6 inches behind the sash and keep all chemicals and
equipment behind that line during experiments. This will help to keep materials from
escaping the hood when disturbances like air currents from people walking past the
hood, etc., interfere with airflow at the face of the hood.
Good placement of
Best placement of
materials.
materials.
materials.
Provide catch basins for containers that could break or spill, to minimize the
spread of spilled liquids.
Visually inspect the baffles (openings at the top and rear of the hood) to be
sure that the slots are open and unobstructed. For optimum performance, adjust the
baffles when working with high temperature equipment and/or heavy gases or vapors.
See figure below for suggested baffle positions.
position - all slot is minimized since heated vapors gases and vapors. Upper
open.
tend to rise.
slot is minimized.
Do not block slots. If large equipment must be placed in the hood, put it on
blocks to raise it approximately 2 inches above the surface so that air may pass beneath
it. See figure below.
Do not use the hood as a storage device. Keep only the materials necessary
for the experiment inside of the hood. If chemicals must be stored in the hood for a
period of time, install shelves on the sides of the hood, away from the baffles. See Use
of Hood as a Storage Device for more information.
Keep the hood sash clean and clear.
Check area around the hood for sources of cross drafts, such as open
windows, supply air grilles, fans and doors. Cross drafts may cause turbulence that can
allow leaks from the hood into the lab.
Extend only hands and arms into the hood and avoid leaning against
it. If the hood user stands up against the face of the hood, air currents produced by
turbulent airflow may transport contaminants into the experimenter's breathing zone.
Clean all chemical residues from the hood chamber after each use.
Explosions: The hood is not capable of containing explosions, even when the
sash is fully closed. If an explosion hazard exists, the user should provide anchored
barriers, shields or enclosures of sufficient strength to deflect or contain it. Such barriers
can significantly affect the airflow in the hood.
Perchloric Acid: A conventional fume hood must not be used for perchloric
acid. Perchloric acid vapors can settle on ductwork, resulting in the deposition of
perchlorate crystals. Perchlorates can accumulate on surfaces and have been known to
Air Foil Sills: Many fume hoods are equipped with flat or rounded sills or air
foils which direct the flow of air smoothly across the work surface. Sills should not be
removed or modified by the hood user. Objects should never be placed on these sills.
Materials released from containers placed on the sills may not be adequately captured.
In addition, an object on the sill may prevent the quick and complete closure of the sash
in an emergency.
Spill Containment Lips: Most modern fume hoods have recessed work
surfaces or spill containment lips to help contain minor liquid spills. In many cases,
these lips are several inches wide. Containers of liquids should not be placed on the
hood lip.
Horizontal Sliding Sashes: The hood user should never remove sliding
sashes.Horizontal sash hoods are designed and balanced with no more than half the
face open at any time. Removal of sashes may reduce the face velocity below acceptable
levels.
Tubing for Exhaust: Tubing is frequently used to channel exhaust to the hood
from equipment located some distance away. This is not an effective control method.
Waste Disposal: A fume hood should not be used for waste disposal. It is a
violation of environmental regulations to intentionally send waste up the hood stack. As
described above, the hood is not a pollution control device.
Many of the newer hoods have constant face velocity measuring devices. An
LED readout of the face velocity is found on the device on the top corner of
the hood opening. The readout indicates the actual face velocity of the hood.
Do not use a hood that does not have a survey sticker. If a survey is needed, call EHS.
2.
An inadequate face velocity may result from obstructions to the airflow in the
hood. These may be caused by large quantities of equipment in the hood or by paper or
other material drawn into the exhaust slots. The user should first check for such
obstructions and remove or modify them.
The user may obtain initial maintenance through Facilities.
3.
The hood sash should be lowered until repairs are complete. Place a sign on the
hood reminding users not to use the hood.
4.
Snorkel
A snorkel is a flexible duct or hose connected to an exhaust system. It can only capture
contaminants that are very close to the inlet of the hose, typically less than a distance
equal to one half of the diameter of the duct.
Snorkels can be effective for capturing discharges from gas
chromatographs, pipe nipples or the end of tubing. However, the
effectiveness of the elephant trunk should be carefully evaluated
before they are used to control releases of hazardous substances.
Canopy Hoods
A canopy hood in a laboratory is constructed in a similar fashion to the overhead canopy
hoods seen in kitchens. In order for the canopy hood to be able to capture contaminants,
the hood requires a relatively large volume of air movement, making them somewhat
costly to operate. The canopy hood works best when the thermal or buoyant forces exist
to move the contaminant up to the hood capture zone.
One of the biggest problems with canopy hoods is that, in most cases,
they are designed such that the contaminated air passes through the
individual's breathing zone. The airflow is easily disrupted by cross
currents of air.
For the most part, canopy hoods should only be used for exhaust of non-hazardous
substances.
Glove Box
There are two general types of glove boxes, one operating under negative pressure, the
other operating under positive pressure. Glove boxes consist of a small chamber with
sealed openings fitted with arm-length gloves. The materials are placed inside the
chamber and manipulated using the gloves.
A glove box operating under negative pressure is used
for highly toxic gases, when a fume hood might not
offer adequate protection. A rule of thumb is that a
fume hood will offer protection for up to 10,000 times
the immediately hazardous concentration of a
chemical. The airflow through the box is relatively low,
and the exhaust usually must be filtered or scrubbed before release into the exhaust
system.
A glove box operating under positive pressure may be used for experiments that require
protection from moisture or oxygen. If this type of glove box is to be used with
hazardous chemicals, the glove box must be tested for leaks before each use. A pressure
gauge should be installed to be able to check the integrity of the system.
Biosafety Cabinets
A conventional fume hood should not be used for work with viable biological agents. A
biosafety cabinet is specially designed and constructed to offer protection to both the
worker and the biological materials.
Similarly, a biosafety cabinet should generally not be used for work with hazardous
chemicals. Most biosafety cabinets exhaust the contaminated air through high efficiency
particulate air (HEPA) filters back
into the laboratory.
This type of filter will not contain
most hazardous materials,
particularly gases, fumes or vapors.
Even when connected to the
building exhaust system, a ducted
biosafety cabinet may not achieve a face velocity of 95 - 125 feet per minute, making it
inappropriate for use with hazardous chemicals.
Clean Benches
Clean benches are similar to appearance as a fume hood;
however, they do not exhaust air from the laboratory. A clean
bench is a device that draws air from the lab through a HEPA
filter and vents the filtered air downwards onto a work surface
to keep the materials within free from particulate
contamination. These devices are not to be used with hazardous
materials as they provide no personal protection. Do not store
materials on top of this hood as this will block the filter, overload the motor, and provide
poor product protection.
maximum face opening is greater. The SOC is a fully open sash, unless the hood is alarm
equipped. Then the SOC is the point just before the alarm is engaged.
SOC for Vertical and Double Vertical Sash (numbers are measuring points)
Double-Vertical Sash - Two vertical rising sashes side-by-side. The SOC is generally
both sashes fully open. A few older installations may have an SOC of one sash closed and
the other fully open.
Horizontal Sash - Two or more horizontal sliding sashes. The height of the face
opening is approximately 30 inches and the maximum opening width is 1/3 to of the
width of the hood. This style hood is rarely equipped with an air by-pass. It is sometimes
modified as a chromatography hood, in which case the height of the face opening is
greater. The SOC is the largest opening that can be obtained without removing any
sashes from their tracks.
unless the hood is alarm equipped. Then the SOC is fully closed horizontal panels with
the vertical sash raised to just below the point at which the alarm is engaged. A few old
installations have an SOC of vertical sash down, horizontal panels open as much as
possible without removing them.
Walk-In Hood - a maximum face opening six feet or more high and extends to floor
level. At Baylor, this style is usually equipped with two vertical rising sashes mounted in
parallel tracks and each capable of closing half the face opening. The SOC is one half of
the face open.
California Hood - a free standing bench top enclosed on all sides by transparent
material for a height of four feet or more above the bench, and ventilated. Horizontal
sliding doors provide access from two opposite sides. The SOC is all doors closed.
Triple-Vertical Sash - three adjacent vertical-rising sashes, the center one of which is
18" wide, in an otherwise standard vertical sash hood. The SOC is center sash down and
sashes on both sides fully raised.
Eye Protection
Safety Glasses
Safety glasses look very much like normal glasses buy have lenses that are impact
resistant and frames that are far stronger than standard streetwear glasses. Safety
glasses with proper impact and shatter resistance will be marked "Z87" on the frame or
lens. Safety glasses must have side shields and should be worn whenever there is the
possibility of objects striking the eye, such as particles, glass, or metal shards. Many
potential eye injuries have been avoided by wearing safety glasses.
Standard streetwear eyeglasses fitted with side shields are not
sufficient. Workers who are interested in obtaining prescription
safety glasses should consult their department. Safety glasses
come in a variety of styles to provide the best fit and comfort,
including some designed to fit over prescription glasses.
Safety glasses do not provide adequate protection from significant
chemical splashes. They do not seal to the face, resulting in gaps at
the top, bottom and sides, where chemicals may seep through. Safety glasses may be
adequate when the potential splash is minimal, such as when opening eppendorf tubes.
Safety glasses are also not appropriate for dusts and powders, which can get by the
glasses in ways similar to those described above. Safety goggles are best used for this
type of potential exposure.
Chemical Splash Goggles
Chemical Splash Goggles should be worn when there is potential for splash from a
hazardous material. Like safety glasses, goggles are impact resistant. Chemical splash
goggles should have indirect ventilation so hazardous substances cannot drain into the
eye area. Some may be worn over prescription glasses.
Goggles come in a variety of styles for maximum comfort and splash
protection. Visorgogs are a hybrid of a goggle and safety glasses. They
offer more splash protection than safety glasses, but not as much as goggles. They fit
close to the face, but do not seal at the bottom as goggles do.
Face Shields
Face shields are in order when working with large volumes of hazardous
materials, either for protection from splash to the face or flying particles.
Face shields must be used in conjunction with safety glasses or goggles.
Contact Lenses
Contact lenses may be worn in the laboratory, but do not offer any protection from
chemical contact. If a contact lens becomes contaminated with a hazardous chemical,
rinse the eye(s) using an eyewash and remove the lens immediately. Contact lenses that
have been contaminated with a chemical must be discarded.
This particular recommendation runs counter to what most of us were taught
previously. However, studies have shown that contact lenses are safe to wear in the
laboratory environment. For more information, see the American Optometric
Association guidelines.
footwear (e.g., during spill cleanup). Leather shoes tend to absorb chemicals and may
have to be discarded if contaminated with a hazardous material.
Although generally not required in most laboratories, steel-toed safety shoes may be
necessary when there is a risk of heavy objects falling or rolling onto the feet, such as in
bottle-washing operations or animal care facilities.
Gloves
Choosing the appropriate hand protection can be a challenge in a laboratory setting.
Considering the fact that dermatitis or inflammation of the skin accounts for 40-45% of
all work-related diseases, selecting the right glove for the job is important.
Not only can many chemicals cause skin irritation or burns, but also absorption through
the skin can be a significant route of exposure to certain chemicals. Dimethyl sulfoxide
(DMSO), nitrobenzene, and many solvents are examples of chemicals that can be readily
absorbed through the skin into the bloodstream, where the chemical may cause harmful
effects.
When Should Gloves Be Worn
Protective gloves should be worn when handling hazardous materials, chemicals of
unknown toxicity, corrosive materials, rough or sharp-edged objects, and very hot or
very cold materials. When handling chemicals in a laboratory, disposable latex, vinyl or
nitrile examination gloves are usually appropriate for most circumstances. These gloves
will offer protection from incidental splashes or
contact.
When working with chemicals with high acute toxicity,
working with corrosives in high concentrations,
handling chemicals for extended periods of time or
immersing all or part of a hand into a chemical, the
appropriate glove material should be selected, based on chemical compatibility.
Selecting the Appropriate Glove Material
degradation rating
breakthrough time
permeation rate
Degradation is the change in one or more of the physical properties of a glove caused by
contact with a chemical. Degradation typically appears as hardening, stiffening,
swelling, shrinking or cracking of the glove. Degradation ratings indicate how well a
glove will hold up when exposed to a chemical. When looking at a chemical
compatibility chart, degradation is usually reported as E (excellent), G (good), F (fair), P
(poor), NR (not recommended) or NT (not tested).
Breakthrough time is the elapsed time between the initial contact of the test chemical
on the surface of the glove and the analytical detection of the chemical on the inside of
the glove.
Permeation rate is the rate at which the test chemical passes through the glove material
once breakthrough has occurred and equilibrium is reached. Permeation involves
absorption of the chemical on the surface of the glove, diffusion through the glove, and
desorption of the chemical on the inside of the glove. Resistance to permeation rate is
usually reported as E (excellent), G (good), F (fair), P (poor) or NR (not recommended).
If chemical breakthrough does not occur, then permeation rate is not measured and is
reported ND (none detected).
Manufacturers stress that permeation and degradation tests are done under laboratory
test conditions, which can vary significantly from actual conditions in the work
environment. Users may opt to conduct their own tests, particularly when working with
highly toxic materials.
For mixtures, it is recommended that the glove material be selected based on the
shortest breakthrough time.
The following table includes major glove types and their general uses. This list is not
exhaustive.
Glove
Material
Butyl
Neoprene
Nitrile
PVC
PVA
Viton
Silver
Shield
Natural
rubber
General Uses
Offers the highest resistance to permeation by most gases and water vapor.
Especially suitable for use with esters and ketones.
Provides moderate abrasion resistance but good tensile strength and heat resistance.
Compatible with many acids, caustics and oils.
Excellent general duty glove. Provides protection from a wide variety of solvents,
oils, petroleum products and some corrosives. Excellent resistance to cuts, snags,
punctures and abrasions.
Provides excellent abrasion resistance and protection from most fats, acids, and
petroleum hydrocarbons.
Highly impermeable to gases. Excellent protection from aromatic and chlorinated
solvents. Cannot be used in water or water-based solutions.
Exceptional resistance to chlorinated and aromatic solvents. Good resistance to cuts
and abrasions.
Resists a wide variety of toxic and hazardous chemicals. Provides the highest level
of overall chemical resistance.
Provides flexibility and resistance to a wide variety of acids, caustics, salts,
detergents and alcohols.
Where fine dexterity is needed, consider double gloving with a less compatible material,
immediately removing and replacing the outer glove if there are any signs of
contamination. In some cases, such as when wearing Silver Shield gloves, it may be
possible to wear a tight-fitting glove over the loose glove to increase dexterity.
Glove thickness, usually measured in mils or gauge, is another consideration. A 10gauge glove is equivalent to 10 mils or 0.01 inches. Thinner, lighter gloves offer better
touch sensitivity and flexibility, but may provide shorter breakthrough times. Generally,
doubling the thickness of the glove quadruples the breakthrough time.
Glove length should be chosen based on the depth to which the arm will be immersed or
where chemical splash is likely. Gloves longer than 14 inches provide extra protection
against splash or immersion.
Glove size may also be important. One size does not fit all. Gloves which are too tight
tend to cause fatigue, while gloves which are too loose will have loose finger ends which
make work more difficult. The circumference of the hand, measured in inches, is
roughly equivalent to the reported glove size. Glove color, cuff design, and lining should
also be considered for some tasks.
Glove Inspection, Use and Care
All gloves should be inspected for signs of degradation or puncture before use. Test for
pinholes by blowing or trapping air inside and rolling them out. Do not fill them with
water, as this makes the gloves uncomfortable and may make it more difficult to detect a
leak when wearing the glove.
Disposable gloves should be changed when there is any sign of contamination. Reusable
gloves should be washed frequently if used for an extended period of time.
While wearing gloves, be careful not to handle anything but the materials involved in the
procedure. Touching equipment, phones, wastebaskets or other surfaces may cause
contamination. Be aware of touching the face, hair, and clothing as well.
Before removing them, wash the outside of the glove. To avoid accidental skin exposure,
remove the first glove by grasping the cuff and peeling the glove off the hand so that the
glove is inside out. Repeat this process with the second hand, touching the inside of the
glove cuff, rather than the outside. Wash hands immediately with soap and water.
Follow the manufacturer's instructions for washing and caring for reusable gloves.
Grasp the exterior of one glove with your other gloved hand.
Carefully pull the glove off your hand, turning it inside-out. The contamination is
now on the inside.
Ball the glove up and hold in your other gloved hand.
Slide your ungloved finger into the opening of the other glove. Avoid touching the
exterior.
Carefully pull the glove off your hand, turning it inside out again. All
contamination is contained.
Discard appropriately.
Wash hands with mild soap and water after removing latex gloves.
Hearing Protection
Most laboratory equipment and operations do not produce noise levels that require the
use of hearing protection, with the exception of some wind tunnels, as described below.
Baylor University has a Hearing Conservation Program in place for individuals
who are exposed to noise levels equal to or exceeding the OSHA action level of 85
decibels (dBA) averaged over eight hours, per the OSHA Occupational Noise
Standard. This program includes workplace monitoring, personal exposure
monitoring, annual audiometric testing, use of hearing protection and annual training.
Laboratory workers who would like to use hearing protection for noise levels below the
action level may do so without enrollment in the Hearing Conservation Program. Using
hearing protection, such as earplugs, earmuffs or hearing bands, can improve
communication or provide comfort to the worker in a noisy environment.
The most common noisy equipment in the laboratories are ultrasonicators. EHS has
measured noise levels of several ultrasonicators used in the laboratories and found that
noise levels were well below 85 dBA, averaged over eight hours.
Respiratory Protection
A respirator may only be used when engineering controls, such as general
ventilation or a fume hood, are not feasible or do not reduce the exposure
of a chemical to acceptable levels. Since the use of a respirator is regulated
by the OSHA Respiratory Protection Standard, respirator use at Baylor is
subject to prior review by EHS, according to
university policy.
Any worker who believes that respiratory protection is
needed must notify EHS for evaluation of the hazard and
enrollment in the Respiratory Protection Program. This
program involves procedures for respirator selection, medical assessment of employee
health, employee training, proper fitting, respirator inspection and maintenance, and
recordkeeping.
Use of a paper or cloth dust mask (left-most in above picture) is allowed without
enrolling in the Respiratory Protection Program. However, if you believe you need
to upgrade to a tight-fitting respirator, you must contact EHS prior. Tight fitting
respirators are typically made of silicone or rubber and have filter cartridges or supplied
air for breathing.
For more information, see Section C4, Respiratory Protection, in the Baylor
University Health and Safety Guide.