Sei sulla pagina 1di 148

X20 System

Perfection in Automation
www.br - automation.com

The X20 System offers the highest degree of flexibility and modularity for all industrial applications.
Anton Meindl
Business Manager
for PLCs, Fieldbusses and I/O Systems

The X20 System is the result of extensive research


and development activities based on the most
modern technologies.
Manfred Kcher
Technical Manager
for PLCs, Fieldbusses and I/O Systems

X20 System

X20 System
Safety
Configurator
Labeling and Coding
EMC Protection
CAD and ERP Support
X20 System - Characteristics
X20 System - Product Overview
X20 System - Module Overview
X20 System - Accessories
Dimensions

4
28
323
38
44
46
48
52
56
142
144

The New Standard for Automation


The new standard for automation
There are many different I/O slice systems. According to the motto Perfection in Automation, B&R is setting
new standards with the X20 System. Born from experience gained from applications all over the world, numerous
conversations with customers, and with the aim for more simple, economical and secure usage, the X20 System is
the new universal solution for any automation task in machine and system manufacturing.

More than I/O


With well thought-out details and a sophisticated ergonomic design, the X20 System is more than a remote I/O
system; it is a complete control solution. Depending on the users demands and individual application requirements,
the X20 System family makes it possible to combine the exact components necessary.
The X20 System is the ideal addition to a standard fieldbus and expands the possibilities of standard control systems.
Simply connect it, configure it and your finished.
Together with B&R components, the X20 System achieves its full potential and allows the implementation of
applications with unimagined performance and flexibility. Seamless integration is a major advantage.

X20 System

3 x 1 = One
Three basic elements result in one module: Terminal block Electronic module Bus module
This modularity results in a system that combines the advantages of rack and I/O slice systems:
Prewiring without the system
Hot pluggable electronics
Free bus slots for options

Unmatched component density


Component density versus granularity, a seemingly impossible conflict. The X20 System offers both:
12 channels on one module with 12.5 mm spacing, 99 mm height and 75 mm depth.
Granularity down to one channel per module.
Universal 1, 2 or 3 conductor connection technology extra terminals are not needed.

I/O slice system with characteristics of a rack system


Because of the sophisticated mechanics, an entire X20 System can be installed on the mounting rail in preassembled
form. And it can be removed just as easily. Premounted and preprogrammed systems are delivered to you just-intime. This is a well-rehearsed procedure used at B&R to maximize cost-effectiveness in the entire logistics chain.

Local or remote you decide!


The X20 System is an intelligent controller and I/O system locally or remote. The user determines characteristics,
architecture and topology.
The modules communicate using a uniform X2X Link backplane - right next to each other on the mounting rail,
in the same switching cabinet, over 100 m away or when directly connected with other B&R components.
The X20 System minimizes costs by providing maximum design freedom and allowing a mixture of local and remote
topologies without requiring expensive fieldbus modules.

Optimal Design

6-pin/12-pin terminal blocks:


Two terminal types for efficient
configurations, 12-pin terminal
with high component density,
6-pin terminal for fewer channels

Push-in terminals
Tool-free handling, screwdriver
only needed for dismounting,
clear terminal assignments,
removal, labeling

Diagnostics
LED block with all status
displays, compact display without
view blocked by wiring, extended
diagnostics using software

Coding
Factory coding for system
security, custom coding to
prevent mix-ups, embedded
parameter chip for software
coding

Extensive product spectrum


All modules with varying number
of channels, optimal configuration
according to the number of
channels needed, scalable
performance

Electrically isolated
Bus and I/O electronics
completely separated, for secure
communication in adverse
conditions, diagnostics remains
possible

Simple mounting
Sophisticated mounting rail
system, system handling like a
rack system, module handling like
an I/O slice system

Stable in spite of three-part


modularity
Rack stability through bus module
connection, all cross-connections
in the bus module, long and stable
guides

X20 System

Concentration on the essentials


The complexity of automation should be limited to the application. The automation system is a means to a solution
and should not cause any additional complication to the project. The X20 System is a tool
for solving complex tasks. It is simple and intuitively built and can be used without special know-how.
The X20 System helps you to achieve your goals and provide fast and economical solutions.

Optimal design
X20 modules are divided into three parts to guarantee the simplest usability throughout their entire lifecycle.
The division into bus module, electronic module and terminal block provides many advantages.
Preconfigured for machine variations
The X20 System bus modules are the basic platform for many machine variations. The utilization of the machine
determines which electronic modules are used. The software recognizes the utilization automatically
and provides the necessary functions. Handling different variations couldnt be easier.
Industrial switching cabinet construction
The X20 System terminal blocks, which are separated from the electronic modules, make it possible to prewire
complete switching cabinets. Ideal for manufacturing series machines.
Easy service
X20 modules can be easily exchanged to simplify troubleshooting. The electronic modules
are exchanged during operation. The wiring stays the same thanks to the separate terminal blocks. Being able to
quickly exchange the automation components reduces down-time.

Prewired
Easy wiring
Industrial switching cabinet construction streamlines production cycles. Prefabricated cable trees make assembly
easier and faster directly on the machine or system. The X20 System supports efficient prewiring of the entire
switching cabinet using separate terminal blocks. The finished X20 System configuration is mounted in the switching
cabinet and connected to the prewired cable trees.
The supply for the X20 modules, and if needed, the supply for sensors and actuators using three-wire technology do
not result in additional energy distribution requirements. The X20 System reduces
manual wiring to a minimum.

Install the wires, plug it in and its ready to go


Simple, tool-free wiring for fast installation. The X20 System terminal blocks use a fully-integrated and proven
push-in connector system.
The terminals can even accept double wire sleeves with a cross section of 2 x 0.75 mm. The user saves time
wiring the system and distributing the signals.
Each wire connection can be removed with a screwdriver. Each terminal also has an access point for
a measurement probe.
A great deal of thought was given to designing the X20 System. Right down to the wire connectors.

Technical data for terminals


Connection cross sections
AWG 28 14 / 0.08 1.5 mm for stranded wires or wires with wire sleeves
Up to 2.5 mm for solid wires
Up o 2 x 0.75 mm for double wire tip sleeves
Up to 10 A, 230 VAC

X20 System

Detached
The terminals can be prewired without
requiring the actual I/O module. This
provides many advantages for
switching cabinet construction.
Separate manufacturing, just-intime logistics and the installation of
preassembled systems during start-up
become reality.

Tool-free
Simple, tool-free wiring for fast
installation. The X20 System terminals
use a fully-integrated and proven
push-in connector system. Available
with 6-pin and extremely compact
12-pin terminals.

Coding on the system


Factory coding prevents dangerous
mix-ups. The coding guarantees
that only parts which are permitted
to be combined can be combined.
Intuitively and without additional work.

Ergonomic
Component density must not
negatively effect ergonomics. With
terminal spacing of more than
5 mm, this has been handled optimally
on the X20 System. Experience gained
in the field can be used in the field.

Coded in the application


Incorrectly inserting terminals
does not necessarily damage the
electronics, but always causes
faulty functioning of the system.
Application coding prevents this
problem.

Labeling
Each terminal is clearly labeled,
directly in the plastic. Additionally,
labels that can be mounted are
available as system accessories incl.
printer with ECAD implementation.

Clarity
Distinct forms intuitively define
various functions, such as clearly
assigned latching and unlatching
functions for terminals.
This prevents errors.

Easy servicing
Attention to details provides
advantages for a system: In addition
to the terminal connector and
unlocking mechanism, each terminal
has an access point for a test probe.
You can simply measure the terminal
potential without disconnecting
the wire.

Hot Pluggable
Easy to use
3 am: Machine downtime every second counts! The X20 System supports high-speed error correction through
simple exchanging of electronic modules, without switching off the machine. Remove terminal, exchange module,
plug in terminal Thats it, and the rest of the system keeps running during this whole period.

Reduced number of components


Through the multi-functionality of electronic modules, the number of components needed is considerably reduced.
Fewer components, but still with a complete range of options, considerably reduce the costs for logistics and
component replacements.
Two concrete examples:
Configurable input filter for digital input modules: A module type can be used for various input situations and
different sensor technology. The digital input filter can be adapted optimally to every situation from hyper-fast input
signals to suppressing short disturbance pulses with standard sensor technology.
Analog modules for current and voltage measurement: It doesnt matter which signal needs to be measured,
the same module is always used. The selection of input values are made using various terminal assignments for
current and voltage, which improves clarity and therefore prevents errors.
The measurement signal is finally determined using the corresponding software configuration.

Reducing service costs


The X20 System can also be simply and quickly replaced as a complete system. Disconnect completely,
exchange and reconnect defects are corrected quickly without the need to disassemble into individual
components. This can even be done on the night shift, without any tools.

X20 System

11

Diagnostics
Only with outstanding diagnostic options can errors be quickly found. The X20 System offers several levels
of diagnostics:
Direct on the module using visual LED displays. Bus status, I/O status and channel states are displayed in direct
assignment to the channels or the function. The different states are displayed in different ways, e.g. green for OK,
red for error.
In the cyclical data image for the software. With the X20 System, status data means no additional communication
expense. This is because a considerable difference results between theoretically possible bus speeds and the
necessities in practical operation. All necessary status data is always transferred cyclically, with no exceptions.
Expanded diagnostic data in non-cyclic data traffic without loss in performance. If a problem occurs, detailed
diagnostic data can be requested from the application by the respective module using an asynchronous channel.
There is no resulting additional communication load whatsoever, and cycle times remain unchanged.

Embedded parameter chip


Information such as module type, serial number, functionality and version number is contained in the embedded
parameter chip of the X20 module. This information is automatically evaluated by the programming environment,
Automation Studio, and by the application program. This allows errors to be avoided, both with commissioning
and with service. Additionally, the system configuration can be automated and makes flexible versions possible.
Worldwide defined serial numbers of modules are today gaining increasing significance in validated systems,
as demanded for example by the FDA.

Electrically isolated
Each individual electronic module has electrical isolation to the electronics in the bus module. This helps to avoid
possible negative influences from system-dependent I/O. Stable and robust electronics originate from a well thoughtout basic design.

Options
Space for options
Depending on the users demands and individual application requirements, the X20 System family makes it possible
to combine the exact components necessary. This allows machine options to be easily implemented in different
ways. The basis is bus modules - more or less a rack replacement. Depending on the option, only the necessary
electronic modules are then inserted in the predefined slots. Address assignment is implicitly made using the slot.
Software that has been developed is valid for all versions and must not be changed. This is even possible for later
machine expansion. The I/O modules are simply inserted in the defined bus modules and assigned the corresponding
potential groups and E-stop groups.
To prevent unwanted expansion, each module can be identified and then freely enabled using the
application software.

Flexibility for options


The implementation of different machine variations using free bus modules is only one of the many features that
the X20 System offers. With the support of B&R Automation Studio, there is one optimized solution using
I/O configuration. What does this mean?
Each I/O configuration is created optimally according to the actual needs. However, the application software is
already designed for all options. Only the I/O channels that are actually available are configured for the application
program. If an expansion is required, then the additional necessary hardware is simply connected, and the
configuration of the I/Os is changed. This is done without having to compile the application software.
It doesnt matter how the I/O configuration list is created:
Manual creation in B&R Automation Studio
Tool supported creation e.g. using a database or a spreadsheet program
Direct from an ERP system, exactly like with the parts list for the machine.
Automatically in the application software, depending on the hardware used

One tool, many targets


B&R Automation Studio is more than just a programming tool for IEC programming of PLCs. It unites the
programming of PLCs, drives, and visualization projects into one comprehensive and universal tool. It also
includes extensive diagnostics and analysis services for cost-effective software creation and all service tasks.

X20 System

13

Machine variation A
The possibilities of the X20 System can be explained
using examples. This is a machine constellation with
two variations, A and B.
All of the necessary electronic modules for machine
variation A are shown in the picture to the left. The bus
modules needed for variation B are also present, but
electronic modules are not assembled.

Machine variation B
Variation B shows the necessary electronic modules but
the modules necessary for variation A are missing. The
distribution of the free bus modules for the variations is
also clear: The varying input and output modules can be
very easily connected to the necessary electrically isolated
groups and dont need to be hung up in the back. The
involved process needed to take apart the configuration
to expand existing electrically isolated groups is also
eliminated. Simply insert the electronic module and put
on the terminal block.

Machine variation A - optimized


The features included in Automation Studio can also
be used to achieve completely optimized hardware
configurations without losing the advantage of
comprehensive application software for all variations.
As described earlier, simply switching physical I/O
points to the application program makes it extremely
easy to optimize the hardware variations without even
needing compilation.

Unmatched Component Density


12 channels per module

75mm

For unequaled component density.

1 channel per module


For the highest granularity.

99mm

99mm
12,5mm

Studies have shown that an average I/O system consists of 15 modules divided into 9 digital input
modules and 6 digital output modules.
System comparison: System with a maximum of 8 channels per module and an X20 System with 12 channels per module:
8-channel system

Channels

9 x DI modules

72

6 x DO modules

48

15 x modules

X20 System
6 x DI modules
4 x DO modules
10 x modules

12 channels on 12.4 cm means 31% less space in the switching cabinet when compared to
systems with a maximum of 8 channels per module.

X20 System

15

Universal 1, 2, or 3-conductor technology


Extra terminals are not needed.

Universal 3-conductor
technology

Sensor 2

Sensor 1

Integrated supply and ground


for sensors and actuators.

DI

+24 VDC
GND

Universal 2-conductor
technology
Extra terminals are not needed.

+24 VDC
GND

DI
Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

+24 VDC
GND

Universal 1-conductor
technology
12 channels - unequaled component
density.

+24 VDC
GND

DI
Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

Sensor 7

Sensor 8

Sensor 9

Sensor 10

Sensor 11

Sensor 12

+24 VDC
GND

+24 VDC
GND

Experience from the Field for the Field

Sophisticated mechanics
The name B&R stands for many years of experience in developing and manufacturing industrial electronics.
But its also the mechanics of the X20 System that have been thought through to the last detail. Its robust design,
long guides, and strengthened housing guarantee the stability it needs in industrial environments. These are also
the features that allow the X20 System to be mounted on a rail with the same ease as a rack system. Or especially the
same ease when removing from the rail. Sophisticated mechanics are needed not just to meet this type of handling,
but also to be able to quickly and easily remove I/O slices from the entire system.

Components or complete system


Putting individual components together takes time and costs money. A lot more of both when dealing with
manufacturing series machines. If desired, the X20 System can also be delivered as a complete configuration.
Pre-configured, pre-mounted, and pre-programmed systems can be tailored to your needs and accessed with just
one model number. Just-in-time production at the factory with a fixed configuration.
The X20 System configuration is connected to the mounting rail in the switching cabinet and equipped with the
prewired terminal blocks. Plug and Play at the highest level. This avoids mistakes and unnecessary effort when
building the system while saving space, time, and money.
Of course, all parts of the X20 System can still be ordered individually, down to the smallest terminal block.

X20 System

DIN Rail Mounting


Unlocking lever with two positions
Closed for secure fit on the mounting rail.

Defined open position makes the difference


Open to remove a module or the entire system.

Removing an individual module from the system


Removed from the top or re-inserted.

Mounting the entire system in one step


Or just as easily removing the the entire system.

Delivery and handling


As a complete system or individual modules its your choice.

17

Local or Remote You Decide


Distributed backplane
All X20 modules are connected with a uniform and cost-effective backplane: X2X Link.
Modules right next to each other or up to 100 m beyond the switching cabinet. Without system division
or bus converters.
X2X Link guarantees the highest protection against disturbances as well as worldwide application
without special tools thanks to its twisted copper cables.

100 m

100 m

Distributed X2X Link backplane


The main idea behind X2X Link is the decentralization of the rack system backplane, or put another way:
The cable is the backplane. This not only provides a universal remote backplane which handles the
communication between bus modules and via the X2X Link cable, but makes it possible without converters
or any loss in performance.

X20 System

19

Structured systems
Local or remote, you decide the X20 System doesnt force the user to adhere to a particular controller philosophy.
The application determines the architecture. The possibilities of I/O data distribution using fieldbus technology are
thoroughly expanded with the remote X2X Link backplane, regardless whether CANopen, DeviceNet, or Profibus DP
is used. The entire performance, combined with the complete topology freedom, reveals the X20 System as a
2nd-generation fieldbus when using ETHERNET Powerlink: Complete synchronicity from I/O acquisition to the
data image in the controller, not to mention extreme scanning precision, distinguish this open, established
market standard.

X20, X67, XV, etc.


The X20 Systems X2X Link backplane is supported by all sorts of products. Valves, operating elements,
or visualization units can be connected anywhere directly on the X2X Link backplane.
When combined with the X67 System, automation projects enjoy a mixture of both IP20 and IP67 protection.
Depending on the environment, the right I/O module is always used.

Local or Remote You Decide


Integrated automation
The X20 System is distinguished by its flexibility and ability to be used for many different types of applications. Large
or compact controllers, machine manufacturing or process automation its use covers an extremely wide spectrum.
Central controller architectures with modular CPUs which allow for added interfaces can also be implemented with
the X20 System, much like a system with distributed intelligence.

+
IF

+
IF

CPU

I/O

I/O

Expanding existing systems


Bus controllers allow the X20 System to be connected to any existing products in the B&R world. Power Panel
devices, Automation PCs, Mobile Panel devices, System 2003, System 2005, and other product families even offer
direct interfaces to the remote X2X Link backplane.
Automation Runtime systems
Power Panel
System 2003, System 2005
PC Based Automation
Soft PLC with Windows

X20 System

One Tool for Every Task

21

B&R Automation Studio


This familiar programming environment does not have to change for the X20 System. A single tool for all automation
tasks also applies to the X20 System. Extensive applications for control, visualization and drive technology are also
created easily and intuitively for the X20 System using B&R Automation Studio.
Support for all IEC 61131-3 programming languages is a must. ANSI-C and Automation Basic offer an additional
degree of freedom.
With the concept configuring instead of programming, a large portion of applications do not require programming
code. Graphics editors and analysis tools provide the full overview needed for the quick creation of error-free
programs.
Automation Studio makes project configuration, program creation, and testing possible offline, without an
X20 System having to be connected. Economical use and flexible customization of the resources to meet the
project requirements is guaranteed.
Automation Studio is the first choice for the X20 System, especially when used together with all other
B&R product families.

Open for Everyone


For all fieldbuses, integrated through the standard
The X20 System is ideally suited for expanding existing control systems using standard fieldbus technology.
Using bus controllers, the X20 System can be used as a powerful I/O expansion unit. Standardized EDS or GSD
description files allow X20 System components to be integrated, configured, and programmed as usual in the
programming environment of a non-B&R system.

X20 System

The New Standard

23

ETHERNET Powerlink The next fieldbus generation


Since first applied to serial production in 2001, ETHERNET Powerlink has been the only real-time Ethernet
technology available on the market which is capable of precision down to the microsecond. The foundation
of ETHERNET Powerlink rests on standards such as IEEE 802.3, CANopen device profiles, IP protocols and
conventional Ethernet chips.
This protocol is distinguished by the following properties:
Optimized transfer of time-critical and non-time-critical data to the Ethernet medium
Seamless integration in office and factory networks
Additional usage of standard network components (e.g. fiber optic converters)
Different network topologies: The network is customized to the machine
Open without needing licenses or special ASICs
Conformity to international standards
Wide provider and user base
Available today and well-proven, over 40,000 nodes in the field
In addition to its real-time capabilities, ETHERNET Powerlink meets the demand of being able to easily use networks
in industrial environments. This is a substantial reason for the success of this protocol. Right now, its being used
around the world in serial production in more than 40,000 nodes on machines and systems. In addition, current areas
such as machine safety, availability, and engineering have allowed it to secure the path to the future.

ETHERNET Powerlink layer model

PC Based Automation
Powerful CPUs
Automation components from B&R have consistently been at the top of the performance scale for many years.
High-speed CPUs with very short configurable cycle times are an important factor in this. Fast Ethernet or USB are
part of the basic design. Systems can easily be expanded to include additional modular interfaces. This is the case
with the X20 System as well.
In the application, there is no difference from the existing CPUs. CNC, complex function blocks, real-time
communication, or data processing with floating point precision. All of this is possible with X20 System CPUs.

X20 System

Fieldbus Connection
X20 bus controllers
The X20 System is very open-minded. Several bus controllers for standard fieldbus technologies like ETHERNET
Powerlink, Device Net, Profibus or CANopen are available to connect X20 modules to existing control systems.
Fieldbus configurations transparently integrate the X20 System into the 3rd-party development environment.
X20 modules allow systems developed in the past to enter a higher performance class.

25

No Limits
X20, X67, XV, etc.
The X20 System is a part of a large product family that can be operated directly on the X2X Link backplane.
Valve connections, operating elements, visualization units or I/O with IP67 protection make the X20 System a
comprehensive and complete automation solution, far beyond the limits of the switching cabinet for all the needs
of machine and system manufacturing.

X67
X67

XV
Panelware

X67

XV
Compact I/O

X67

X20 System

27

X67
The remote X67 System opens up the world of automation outside the switching
cabinet. Equipped with the same communication mechanisms as the X20, it allows any
mixture of X67 and X20 components. X20 in the switching cabinet, X67 outside
the ideal combination of both system provides a wide array of excellent advantages.

XV
Connecting valve islands takes place with conventional wiring or with fieldbus
connections. With the XV connection, B&R offers a complete X2X Link connection that
is integrated in a DSUB housing for valve islands with a multi-pin DSUB connection
independent of the valve island manufacturer.

Compact I/O
Compact units in extremely stable metal housings thats B&R compact I/O for
X2X Link. Various signals are grouped together in a box directly on the machine
for efficient use.

Panelware
Small and mid-sized remote visualization units identify the Panelware series.
Equipped with various displays and operating elements, they can be easily integrated
into the remote backplane and programmed or configured using B&R
Automation Studio.

Integrated Safety
Integral system component
Nowadays, safety technology is a rigid technology completely separate from the flexible machine control.
Cost-intensive dedicated wiring, designed parallel to all established communication systems, separates safety
technology from the rest of the automation world.
There are a number of new approaches to secure fieldbus systems heavily influenced by proprietary standards
and limited cycle times. This is not the case with the X20 System. ETHERNET Powerlink safety is applied with
confidence in this system. This means that safety technology is fully integrated in the system.
The integration of an open solution based on the available real-time standard ETHERNET Powerlink allows B&R to
continue on a successful path of innovation at a high speed.

EPLsafety sets a technical standard


ETHERNET Powerlink Safety - abbreviated EPLsafety - is defined as an independent frame that can be used with
any bus. In principle EPLsafety can also be inserted in standard protocols other than Powerlink. For example it is fully
compatible with CANopen. The full performance ability of EPLsafety is brought out in combination with ETHERNET
Powerlink.
The safety category SIL 3 in accordance with IEC 61508 is first achieved at cycle times of up to 100 microseconds.
The functionality of EPLsafety (encapsulated) allows the standard ETHERNET Powerlink transport mechanisms
to be fully used. The frame structure is highly flexible, which means that EPLsafety optimally adapts to different
applications such as machines, systems or transport systems.

EPSG working group safety


ETHERNET Powerlink is supported by the EPSG (ETHERNET Powerlink Standardization Group), an open
association of leading end users, manufacturers and research institutes for automation technology. The groups
goal is to provide an open standard for industrial Ethernet with precise real-time behavior in the microsecond
range.

Safety

29

Complete system
Safety in the X20 System involves all of the required components. In addition to secure digital inputs and outputs,
there will also be secure supply modules, which securely shut off the I/O supply for normal, non-secure output
modules. As a result, the secure information is transferred via the distributed X2X Link backplane as securely as via
ETEHRNET Powerlink. Drives with integrated secure functions triggered via Powerlink are also integrated in the
concept.
The entire system is controlled using a secure CPU, the Safe Logic. This depends directly on ETHERNET Powerlink,
meaning that it has an optimal communication connection to the non-secure control for example.

PC control

Safe
Logic

ETHERNET Powerlink

X20 System

X20 System

Drives

Integrated Safety
Secure configuration and programming
All secure connections run in the Safe Logic, which is where the logical relationships for the individual secure devices
are defined with each other. Function block-based programming is also possible, in addition to pure configuration.
The programmer is supported by a number of pre-defined safety function blocks.
Routing can be set up to the Safe Logic via the normal CPU and ETHERNET Powerlink for programming.

Automation Studio
+
Safe Components

PC control

Safe
Logic

ETHERNET Powerlink

X20 System

X20 System

Drives

Safety

31

Open standard
EPLsafety, like all ETHERNET Powerlink components, is an open standard. Various manufacturers from all fields of
automation technology specify the concepts and requirements. The balance of different demands means that useful
solutions which are then certified and implemented can be found for all areas of use.
The result is EPLsafety - the first fully independent real-time Ethernet-based safety bus, which meets the safety
category IEC 61508 SIL 3 even with short cycle times of 100 s.

Configurator System Modules


X20 System configuration
There are different possibilities for connecting an X20 System: Directly to the distributed X2X Link backplane,
to fieldbus systems via bus controllers or directly to an X20 CPU. The latter allows modular expansions using
interface modules.

Bus Receiver

+
Bus
Controller

+
Interface
Module

Bus Transmitter

Power
Supply

+
Interface
Module

CPU

The right choice


A functioning system starts with the right choice of electronic module and bus
module. This also applies to system modules such as the X2X Link receiver or
X2X Link transmitter.

Bus Receiver

Configurator

33

Select bus receiver


BR
X20 BR 9300

X20 bus receiver

Bus module
Use BM 01
X20 BM 01

X20 bus module

Select bus controller


BC
X20 BC xxxx

X20 bus controller

Power supply
Use PS 3300
X20 PS 3300

X20 power supply

Bus module
Use BM 11
X20 BM 11

X20 bus module

Interface module
Select IF module
X20 IF xxxx

X20 interface module

Select CPU
CPU system
X20 CP xxxx

X20 CPU

Bus transmitter
Use BT optionally with expansion
X20 BT 9100
X20 bus transmitter

Bus module
Use BM 11
X20 BM 11

X20 bus module

The Power Supply Design


Bus module rack replacement
The bus module is the backbone of the X20 System regarding the bus supply and bus data as well as the I/O supply
for the electronic modules. Each bus module is an active bus station, even without an electronic module. There are
two variations of the bus module: I/O supply via connected device or as a supply module with separation of the I/O
supply to the left.

Bus power contacts


Bus data contacts

I/O power contacts

X20 BM 11

X20 BM 01

DC OK
Supply modules are X2X Link stations just like any other electronic module. They transfer status data to the
controller which is important for the continuous diagnostics such as the status DC OK, which signalizes that
the I/O supply is in the permissible range.

Configurator

35

X20 System infrastructure


Different potential groups can be implemented with the appropriate arrangement of supply bus modules, e.g. for
input groups or different E-stop circuits on the outputs. The I/O supply feed comes from power supply
electronic modules.

Input potential group

Output 1 potential
group

Output 2 potential
group

Configurator Supply
Bus supply
The X2X Link supply must be connected in specific locations because the distributed X2X Link backplane and the
I/O electronics are completely electrically isolated. The first module usually handles this task (e.g. the bus receiver).
Another supply must be connected after approximately 20 modules. A supply module must be used for the X2X Link.
On the same module, a separate feed for the I/O supply can also be connected.

Potential groups
The I/O supply is connected via the bus modules. The feed is connected via corresponding electronic feed modules.
This makes it possible to implement simple potential groups (e.g. for input groups or different output groups).
Additionally, the corresponding bus module necessary for the separation of the Power Bus is also required for this
separation.

Output modules with supply


Generally, a supply module is also necessary for current output modules with many channels such as the 8-channel
output module with 2 amp outputs. This is not the case with the X20 System. With this module, the supply feed is
directly on the module, thereby saving supply modules and construction width.

Configurator

37

Power supply
PS 2100 only for I/O supply
X20 PS 2100
X20 power supply

Bus module
BM 01 bus module supply
X20 BM 01
X20 bus module

Power supply
PS 3300 for X2X Link and I/O supply
X20 PS 3300
X20 power supply

Bus module
BM 01 bus module supply
X20 BM 01
X20 bus module

Digital output module


DO 8332 with own supply
X20 DO 8332
X20 8 x DO, 2 A

Bus module
Select BM xx
X20 BM 01
X20 BM 11

X20 bus module


X20 bus module

Labeling, Identification
Terminal
Each terminal is labeled with a unique terminal block name. Standard tags that have
different colors or are individually labeled can also be added. With the identification
system, a terminal label can be applied using a labeling clip.

Module
A module label can be inserted above the LED block using standard tags.

Plain text labeling


In addition to the identification system, inserts are available for
X20 modules for plain text labeling.

Additional functions of the labeling clip


The labeling clip serves several functions:
Holder for terminal labels
Holder for plain text insert
Additional terminal locking clip

Labeling and Coding

Identification System

39

Identification
Standard identification labels in various colors, blank or pre-preprinted.
The identification labels correspond exactly to the labeling requirements of the
modules.

Printer
System printer for individual printing of the standard identification labels.
Special ink with the resistance to wear necessary in an industrial environment is used.

Software support
System printers and standard identification labels are supported by the appropriate
printer software. All procedures for manual labeling are supported, whether from table
calculation or directly from an ECAD software program.
Software and printer are compatible with the Weidmller system.

Distinct Coding
Preventing mix-ups
Mistakes happen. Especially when working under stress. When a machine has to meet a delivery deadline or
when working under the constant time crunch in the area of service, these are situations in which mistakes can
easily occur. The multiple possibilities in the X20 System for distinct coding prevent the chance for mistakes.

Factory coding

Coding

Custom coding

Electronic
parameter chip

Labeling and Coding

41

Factory coding
The extensive range of X20 modules and individual components offers a great degree of freedom and
combination possibilities. However, it is important to ensure that the parts being used can indeed be combined
with each other.
All X20 System components are given a distinct mechanical code during production so that only components
with an identical voltage level, the same safety class or application environment can be combined.

Custom coding
Many applications require safety mechanisms to prevent individual terminals from being mistakenly connected
to the wrong modules.
The X20 System offers the possibility to uniquely assign terminals and electronic modules. The standard
labeling elements of the X20 System serve as mechanic coding elements. These can be placed on the terminal
blocks and electronic module in four positions. It is no longer possible to make a mistake when connecting a
terminal block.

Embedded parameter chip


Each X20 module is uniquely identified using a label on the outside and an embedded parameter chip.
This makes it possible to identify each module on distributed networks using software. Detailed comparisons
of the system configuration with the application program are also possible. Therefore, even incompatible
software versions can be recognized and displayed.

Future compatibility ensured with electronic parameter chip


The unique identification of the X20 modules via electronic parameter chip meets the necessary demands when
using systems in validated environments. It must be possible to identify each exchange of modules.
Applications with these demands (e.g. FDA, GAMP, 21CFR11) are becoming more and more common.

Multi-function in Detail
Terminal locking clip example

Label holder

Insert holder

Terminal locking clip

Protected against accidental release


Some specific areas require additional locking mechanisms to prevent accidental release of the mechanics
optimally implemented with the X20:
An additional clip locks the electronic
module to the bus module.
The terminal locking clip attaches
the terminal block securely to the
electronic module.

Labeling and Coding

43

Identification examples

Terminal

Terminal block

Module

Coding

1 part with 4 functions


The same part can be used for all of the functions listed above.
Reduces required stocks, makes work more efficient, X20!

Perfection in Automation
EMC protection
Optimal EMC protection is never an end in itself. It is always an obligation to the customer. EMC problems usually
arent detected until an automation device is in actual field operation. At that point, problems become expensive.
To prevent these problems, reliable EMC protection is a significant part of product development at B&R. All areas are
included in the EMC protection, ranging from effective electronic and electromechanical design to extensive tests that
exceed the requirements of the relevant guidelines.
The ESD test of the terminal contacts is mentioned here as an example. This specific test is not required by the
standard and is often therefore left out during design or not tested at all. This test belongs to the standard range
of tests at B&R. Tests such as the surge test are often not specified. B&R provides all of the specifications for the
extensive tests in the product documentation, including the surge test.

An example of outstanding EMC protection in B&R products: The input circuit


of the digital 12 channel input module is designed with three resistors in a row.
This means triple components and placement, but with that comes considerably higher
dielectric strength and optimal performance distribution. This lowers component temperatures
and significantly increases the lifespan.

Surge
Surge is the term for high-energy surge voltage. The surge test checks the immunity to these conducted
disturbances. Surge voltages of up to 2 kV are tested.

EMC Protection

45

Quality made by B&R


The name B&R stands for many years of experience in developing and manufacturing industrial electronics.
But its also the mechanics of the X20 System that have been thought through to the last detail. A robust
design, long guides, and strengthened housing guarantee the stability it needs in industrial environments.
The solid connection between the terminal block, electronic module and basis module guarantee the best
possible electric contact and mechanical stability. Many years of development experience go into the
mechanical design of the X20 System to enable the highest component density, greatest degree of flexibility
and easy handling.
The X20 System was developed entirely by B&R, where it is also produced. A requirement for usage in rough
industrial environments is to meet all of the main EMC standards. The high-grade input circuit in the I/O
channels with higher dielectric strength than conventional designs is just an example of the B&R experience put
into the development of the X20 System.
The close proximity between development and production has proven itself over the years. The X20 System is
not a combination of simple individual components by different manufacturers. There is just one contact person
behind the entire palette of hardware and software who carries sole responsibility.

Construction Support
Macros for ECAD systems
The electronics in a machine must be designed in a manner which optimally utilizes the materials and space available.
Graphic ECAD systems have established themselves as the right tool for the job.
Every module in the X20 System comes with pre-designed electronic descriptions of the mechanical dimensions,
electrical signals and module functions. These macros are loaded directly to the well-established ECAD systems.
The wiring plans are automatically applied by the configuration and programming system, Automation Studio.
Design and changes are immediately reflected at all levels of development. This saves time for the most important
tasks and prevents errors right from the start.
Accelerated development, programming, maintenance and documentation mean lower costs, enhanced quality
and increased sales by entering the market earlier.

CAD and ERP Support

ERP Systems for Software Configuration


ERP systems are integrated in the configuration process of machines
Streamlined production demands efficient use of the ERP and CAD systems. This also applies to the use
of control systems.
The configuration and programming of the X20 System is integrated with the ERP systems. Depending on the
structure, range and combination of the X20 components, I/O classification lists are created automatically.
These lists determine the exact position of the inputs and outputs and make optimal use of the existing number
of modules.
The application program always remains the same.

The principle of the automatic software generation in series machines:


Software on demand

47

Perfection in Automation
Remaining true to the guiding principle Perfection in Automation, the X20 System was developed using the most
modern technologies. The X20 System is the result of the uncompromising work of the development team, which
gave 100 percent and used their extensive automation experience to create an extremely versatile product for all
applications.

X20 System - Characteristics

49

Characteristics
Application Possibilities
Machine manufacturing
System manufacturing
Process automation
As a controller system
As an I/O system







Connection of I/O, Sensors and Actuators


Terminal block inserts for pre-wiring
Up to 12 I/O terminals for each module
Double wire sleeves up to 2 x 0.75 mm on a terminal
Single conductor technology supported
Two-wire technology supported
Three-wire technology supported
Digital I/O modules
Analog I/O modules
Temperature measurement modules
Modules with data preprocessing and filtering
Grounding directly on the terminal block
I/O electrically isolated
Sequential design of input and output groups possible
Tool-free wiring with push-in terminals
Wiring simple to release using screwdriver
Prefabricated cable tree supported
Plain text description for each individual terminal
Terminal blocks can be clearly coded by the user




















System Design
Base module, electronic module and terminal block separated
Flexible module distances, 0 - 100 m possible
Complete system configuration simple to mount and remove
Mounting rail installation in the switching cabinet
Power distribution without additional wiring
Electrically isolated groups possible
Uniform design of different versions
Plain text description for modules
Terminals and modules coded against erroneous combination
Supports several E-stop circuits
Complete identification for all components for FDA, GAMP conformity
Additional security for particularly raw environments possible














X20 System - Characteristics

51

System Performance
Synchronous process image
Cycle time 100s
I/O jitter < 2s





Maintenance
Tool-free exchange of individual modules possible
Exchange of complete configurations possible
Hot plugging supported





Terminals Completely Removable without Loosening Individual Wires


Extensive diagnostics via network
Diagnostic LEDs on every module
Documentation on-site through plain text description





Control Architecture
Distributed architecture supported
Central architecture supported
Direct connection to B&R controllers, automation PCs and visualization
Connection to 3rd-party controllers using a fieldbus






Fieldbus Connections
Profibus DP
CANopen
ETHERNET Powerlink
DeviceNet






Development Support
Macros for ECAD systems
Programming with Automation Studio
Only one single software tool for all tasks
IEC 61131-3, ANSI-C and Automation Basic
Automatic hardware recognition
Offline programming possible
Automatically generated dynamic I/O classification lists for optimal module usage
Direct coupling of ERP systems and development systems
Automatic detection of removed versions
Electronic identification plate for each module
Continual checking of HW/SW conformity possible













Delivery Form
All modules can be delivered separately
Completely predefined system configurations can be delivered
All individual components can be delivered separately
Just-in-time delivery






X20 Product Overview


Bus modules
Model Number

Short Description

X20BM01

X20 supply bus module with power bus separated to the left

 56

X20BM11

X20 standard bus module with power bus interconnected

 58

Terminal blocks
Model Number

Short Description

X20TB06

X20 standard 6-pin terminal

 60

X20TB12

X20 standard 12-pin terminal

 60

Bus receivers and bus transmitters


Model Number

Short Description

X20BR9300

X20 bus receiver X2X Link with feed for power bus and X2X Link bus supply

 62

X20BT9100

X20 bus transmitter X2X Link

 64

X20 System - Product Overview

53

Supply modules
Model Number

Short Description

X20PS2100

X20 supply module power bus

 66

X20PS3300

X20 supply module power bus with X2X Link bus supply

 68

Dummy modules
Model Number

Short Description

X20ZF0000

X20 dummy module without function

 140

Accessories
Model Number

Short Description
Terminal locking clip, plain text insert, locking plate, printer, etc.

 142

X20 I/O Product Overview

X20DC2396

X20DC1398

X20DC1396

X20DC1198

X20DC1196

X20AT6402

X20AT2402

X20AT4222

X20AT2222

X20AO4632

X20AO4622

X20AI4632

X20AO2632

X20AI4622

X20AO2622

X20AI2632

Function

X20AI2622

Electronic modules

Digital Input
Digital Output
Analog Input
Analog Output
Temperature
Event Counter
ABR Incremental Encoder 5 V

AB Incremental Encoder 24 V
ABR Incremental Encoder 24 V
SSI Absolute Encoder 5 V
SSI Absolute Encoder 24 V

1
1

Gate Measurement
PWM Output
Page

 100  102  104  106  108  110  112  114  116  118  120  122  124  126  128  130  132

X20 System - Product Overview

X20DO9322

12

X20DO9321

12

X20DO8332

X20DI9372

X20DO6322

X20DI9371

X20DO6321

X20DI6372

X20DO4332

X20DI6371

(2)

X20DO4322

X20DI4371

Digital Output

X20DO2322

X20DI2377

Digital Input

X20DI2371

X20DC4395

X20DC2395

Function

X20DC2398

55

12

12

Analog Input
Analog Output
Temperature
Event Counter

(4)

(8)

(2)

(4)

(2)

(4)

(2)

(4)

(2)

ABR Incremental Encoder 5 V


AB Incremental Encoder 24 V
ABR Incremental Encoder 24 V
SSI Absolute Encoder 5 V
SSI Absolute Encoder 24 V

Gate Measurement
PWM Output
Page

(1)
 134  136  138  70  72  74  76  78  80  82  84  86  88  90  92  94  96  98

Numbers in parentheses represent multiple assignment. Check the specifications in the data sheet for configuration.

Bus Module BM01


Basis for all X20 supply modules
For creating electrical potential groups
The internal I/O supply is interrupted towards the left

Short Description

X20BM01

Mechanical Characteristics

X20BM01

Bus Module

Supply bus module,


internal I/O supply
is separated on the left

Spacing

12.5 mm

General Information

X20BM01

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Operating Temperature
Horizontal Installation

Power Input
Bus
I/O Internal
1

Information based on pre-series.

Typ. 0.13 W1
-

Mounting Orientation

Horizontal or vertical

Protection

IP20
0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

X20 System - Module Overview

57

Image

Potential Control

+24 VDC
GND

Bus Module BM11


Standard bus module
The internal I/O supply is interconnected

Short Description

X20BM11

Mechanical Characteristics

X20BM11

Bus Module

Standard bus module, the internal


I/O supply is interconnected

Spacing

12.5 mm

General Information

X20BM11

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Power Input
Bus
I/O Internal
1

Information based on pre-series.

Typ. 0.13 W1
-

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

X20 System - Module Overview

59

Image

Potential Control

+24 VDC
GND

+24 VDC
GND

6/12-pin Terminal Blocks TB06 / TB12


Tool-free wiring through push-in technology
Simple wire release using lever
Identification option for each terminal
Plain text description possible
Test access for standard probes
Option for customer coding

Short Description

X20TB06 / X20TB12

Terminal Block
6-pin
12-pin

X20TB06
X20TB12

Terminal Block

X20TB06 / X20TB12

Type of Terminal

Push-in terminal

Distance Between Contacts


Left - Right
Above - Below

4.2 mm
10.96 mm

Contact Resistance

5 m

Rated Voltage

230 VAC

Rated Current1

10 A / contact

Connection Cross Section

0.08 mm - 1.5 mm
AWG 26 -14

Cable Type

Only copper wires


(no aluminum wires!)

Remark

Nominal values according to UL

1 Please take the respective limit data for the I/O modules into
consideration!

X20 System - Module Overview

61

Image

X20TB06

X20TB12

Bus Receiver BR9300


X2X Link bus receiver
Supply for X2X Link and internal I/O supply
Electrical isolation of supply
and X2X Link supply
Redundancy possible by operating several
power supply modules simultaneously

Short Description

X20BR9300

General Information

X20BR9300

Bus Receiver

X2X Link bus receiver with supply


for I/O and bus

Status Display

X2X bus function, overload,


operating status, module status

Input X2X Bus Supply

X20BR9300

Input Voltage

24 VDC (-15% / +20%)

Diagnosis
X2X Bus Function
Overload

Yes, with status LED


Yes, with status LED and software
status
Yes, with status LED
Yes, with status LED

Input Current

Max. 0.7 A

Reverse Polarity Protection

Yes

Fuse

Integrated, cannot be exchanged

Certification

Output X2X Bus Supply

X20BR9300

Nominal Output Power

7.0 W

Electrical Isolation
X2X Bus Supply
I/O Supply

Yes
No

Parallel Operation

Yes

Redundant Operation

Yes

Operating Status
Module Status

CE, C-UL-US (in development),


GOST-R (in development)

Mechanical Characteristics

X20BR9300

In parallel operation, only a 75 % rated power can be assumed. Please


ensure that all parallel operating power supplies are simultaneously
switched on or switched off.

Spacing

12.5 mm

Input I/O Supply

X20BR9300

Input Voltage

24 VDC (-15% / +20%)

Operating Temperature
Horizontal Installation

Fuse

Recommended pre-fusing max. 10 A

Output I/O Supply

X20BR9300

Output Rated Voltage

24 VDC

Reliable Contact Load

10.0 A

Mounting Orientation

Horizontal or vertical

Protection

IP20
0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order supply bus module 1 x
X20BM01 separately.

X20 System - Module Overview

63

X20 BR 9300

Pin Assignments

Connection Example

rn er
X I

BR

X2X
X2X\
X2X-

X2X

X2X\
X2XJumper

+24 VDC
DI 1 BUS

+24
DIVDC
2

+24
Geber
VDC
1 24V+
BUS

Geber
+242VDC
24V+

GND

GND

The bus receiver simultaneously takes over the


function of the supply module for the distributed
X2X Link backplane and for the I/O.

I/OSupply

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM01

X20 supply bus module


with power bus separated on the left

Bus Transmitter BT9100


X2X Link bus transmitter
For seamless expansion of the system
Up to 100 m segment lengths
Feed for I/O supply

Short Description

X20BT9100

Mechanical Characteristics

X20BT9100

Bus Transmitter

X2X Link bus transmitter

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical
IP20

General Information

X20BT9100

Protection

Status Display

X2X bus function, operating status,


module status

Operating Temperature
Horizontal Installation

Yes, with status LED


Yes, with status LED
Yes, with status LED

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

CE, C-UL-US (in development),


GOST-R (in development)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module
1 x X20BM11 separately.

Diagnosis
X2X Bus Function
Operating Status
Module Status
Certification
Power Input
Bus
I/O Internal
1

Information based on pre-series

Typ. 0.45 W
-

0C to +55C
Derating with vertical installation

X20 System - Module Overview

65

X20 BT 9100

Pin Assignments

Connection Example

rn er
X

BT

X2X\
X2X
X2X-

X2X

X2X\
X2X-

+24
DIVDC
2

I/OSupply

Geber
+242VDC
24V+
GND

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Supply Module PS2100


24 VDC supply module for internal I/O supply

Short Description

X20PS2100

Mechanical Characteristics

X20PS2100

Power Supply Module

24 VDC supply module


for internal I/O supply

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Input I/O Supply

X20PS2100

Input Voltage

24 VDC (-15% / +20%)

Fuse

Recommended pre-fusing max. 10 A


Storage Temperature

-20C to +70C

Output I/O Supply

X20PS2100

Humidity

5 to 95% (non-condensing)

Output Rated Voltage

24 VDC

Remark

Reliable Contact Load

10.0 A

General Information

X20PS2100

Order standard terminal block 1 x


X20TB12 separately.
Order supply bus module 1 x
X20BM01 separately.

Status Display

Operating status, module status

Diagnosis
Operating Status
Module Status

Yes, with status LED


Yes, with status LED

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Electrical Isolation
I/O Supply

No

Power Input
Bus
I/O Internal

Typ. 0.2 W
-

Information based on pre-series

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

X20 System - Module Overview

67

X20 PS 2100

Pin Assignments

Connection Example

rn er

PS

+24
DIVDC
2

I/OSupply

Geber
+24VDC
2 24V+
+24 VDC
GND

GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM01

X20 supply bus module


with power bus separated on the left

Supply Module PS3300


Feed for X2X Link and I/O supply
Electrical isolation of supply
and X2X Link supply
Redundancy possible by using
several power supply modules at the same time

Short Description

X20PS3300

General Information

X20PS3300

Power Supply Module

24 VDC supply module


for I/O and bus

Status Display

Overload, operating status, module


status

Input X2X Bus Supply

X20PS3300

Input Voltage

24 VDC (-15% / +20%)

Input Current

Max. 0.7 A

Reverse Polarity Protection

Yes

Fuse

Integrated, cannot be exchanged

Output X2X Bus Supply

X20PS3300

Nominal Output Power

Diagnosis
Overload
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

7.0 W

Electrical Isolation
X2X Bus Supply
I/O Supply

Yes
No

Parallel Operation

Yes1

Mechanical Characteristics

X20PS3300

Redundant Operation

Yes

Spacing

12.5 mm

In parallel operation, only a 75% rated power can be assumed. Please


ensure that all parallel operating power supplies are simultaneously
switched on or switched off.
Input I/O Supply

X20PS3300

Input Voltage

24 VDC (-15% / +20%)

Fuse

Recommended pre-fusing max. 10 A

Output I/O Supply

X20PS3300

Output Rated Voltage

24 VDC

Reliable Contact Load

10.0 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order supply bus module 1 x
X20BM01 separately.

X20 System - Module Overview

69

X20 PS 3300

Pin Assignments

+24 VDC
DI 1 BUS

Connection Example

rn er
I

PS

+24
DIVDC
2

+24
Geber
VDC
1 24V+
BUS

Geber
+24VDC
2 24V+

GND

GND

BusSupply

I/OSupply

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM01

X20 supply bus module


with power bus separated on the left

Digital Input Module DI2371


2 digital inputs
Sink connection
3-wire connection
24 VDC and GND for sensor supply
Software input filter can be configured for entire
module

Short Description

X20DI2371

Mechanical Characteristics

X20DI2371

I/O Module

2 digital inputs 24 VDC


in 3 line connections

Spacing

12.5 mm

Digital Inputs

X20DI2371

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Sink

Sensor Supply

0.5 A total current

General Information

X20DI2371

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.12 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

71

Connection Example

rn er
1 2

DI 1

DI 2

+24 VDC

+24 VDC

GND

GND

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

Sensor 2

DI

Sensor 1

X20 DI 2371

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI2377


2 digital inputs
Sink connection
3-wire connection
2 counter inputs with 50 kHz counter frequency
Gate measurement
24 VDC and GND for sensor supply
Software input filter can be configured for entire
module
Short Description

X20DI2377

Mechanical Characteristics

X20DI2377

I/O Module

2 digital inputs 24 VDC


in 3 line connections, special
functions

Spacing

12.5 mm

Digital Inputs

X20DI2377

Rated Voltage

24 VDC

Operating Temperature
Horizontal Installation

Input Filter
Hardware
Software

10 s
Default 0 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Sink

Additional Functionalities for


Inputs

Event counting, gate measurement

Sensor Supply

0.5 A total current

General Information

X20DI2377

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.2 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20
0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

73

Connection Example

rn er
1 2

DI 1

DI 2

+24 VDC

+24 VDC

GND

GND

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

Counter/Sensor

DI

Counter/Sensor

X20 DI 2377

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI4371


4 digital inputs
Sink connection
3-wire connection
24 VDC and GND for sensor supply
Software input filter can be configured
for entire module

Short Description

X20DI4371

Mechanical Characteristics

X20DI4371

I/O Module

4 digital inputs 24 VDC


in 3 line connections

Spacing

12.5 mm

Digital Inputs

X20DI4371

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Sink

Sensor Supply

0.5 A total current

General Information

X20DI4371

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.15 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

75

Connection Example

rn er
1 2
3 4

+24 VDC

+24 VDC

GND

GND

DI 3

DI 4

+24 VDC

+24 VDC

GND

GND

Sensor 2

DI 2

+24 VDC
GND

Sensor 4

DI 1

Sensor 1

DI

Sensor 3

X20 DI 4371

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI6371


6 digital inputs
Sink connection
2-wire connection
24 VDC for sensor supply
Software input filter can be configured for entire module
1-line connection version with 6x terminal block

Short Description

X20DI6371

Mechanical Characteristics

X20DI6371

I/O Module

6 digital inputs 24 VDC


in 1 or 2 line connections

Spacing

12.5 mm

Digital Inputs

X20DI6371

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Sink

General Information

X20DI6371

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.16 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

77

X20 DI 6371

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6

DI

DI 1

DI 2

DI 3

DI 4

DI 5

DI 6

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

The X20 standard terminal block 6x can be used


for uniform one-line wiring. A two-line wiring can
be implemented using the 12x terminal block.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI6372


6 digital inputs
Source connection
2 line connection
24 VDC for sensor supply
Software input filter can be configured for entire module
1-line connection version with 6x terminal block

Short Description

X20DI6372

Mechanical Characteristics

X20DI6372

I/O Module

6 digital inputs 24 VDC


in 1 or 2 line connections

Spacing

12.5 mm

Digital Inputs

X20DI6372

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Source

General Information

X20DI6372

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.16 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

79

X20 DI 6372

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6

DI

DI 1

DI 2

DI 3

DI 4

DI 5

DI 6

GND

GND

GND

GND

GND

GND

The X20 standard terminal block 6x can be used


for uniform one-line wiring. A two-line wiring can
be implemented using the 12x terminal block.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI9371


12 digital inputs
Sink connection
1-wire connection
Software input filter can be configured
for entire module

Short Description

X20DI9371

Mechanical Characteristics

X20DI9371

I/O Module

12 digital inputs 24 VDC


in 1 line connections

Spacing

12.5 mm

Digital Inputs

X20DI9371

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Sink

General Information

X20DI9371

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.2 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

81

X20 DI 9371

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6
7 8
9 10
11 12

DI

DI 1

DI 2

DI 3

DI 4

DI 5

DI 6

DI 7

DI 8

DI 9

DI 10

DI 11

DI 12

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

Sensor 7

Sensor 8

Sensor 9

Sensor 10

Sensor 11

Sensor 12

+24 VDC
GND

+24 VDC
GND
+24 VDC

+24 VDC

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Input Module DI9372


12 digital inputs
Source connection
1-wire connection
Software input filter can be configured
for entire module

Short Description

X20DI9372

Mechanical Characteristics

X20DI9372

I/O Module

12 digital inputs 24 VDC


in 1 line connections

Spacing

12.5 mm

Digital Inputs

X20DI9372

Rated Voltage

24 VDC

Input Filter
Hardware
Software

100 s
Default 1 ms, can be configured
between 0 and 25 ms in 0.2 ms
intervals

Input Circuit

Source

General Information

X20DI9372

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.2 W1
-

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

83

X20 DI 9372

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6
7 8
9 10
11 12

DI

DI 1

DI 2

DI 3

DI 4

DI 5

DI 6

DI 7

DI 8

DI 9

DI 10

DI 11

DI 12

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Sensor 5

Sensor 6

Sensor 7

Sensor 8

Sensor 9

Sensor 10

Sensor 11

Sensor 12

+24 VDC
GND

+24 VDC
GND
GND

GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Output Module DO2322


2 digital outputs
Source connection
3-wire connection
24 VDC and GND for actuator supply
Integrated output protection

Short Description

X20DO2322

Mechanical Characteristics

X20DO2322

I/O Module

2 digital outputs 24 VDC


in 3-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO2322

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

1.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current and


short circuit, integrated protection
for switching inductances

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

Actuator Supply

0.5 A in total for output-independent


actuator supply

General Information

X20DO2322

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.14 W1
Typ. 0.2 W1

Information based on pre-series.

X20 System - Module Overview

85

Connection Example

rn er
1 2

DO 1

DO 2

+24 VDC

+24 VDC

GND

GND

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

Actuator 2

DO

Actuator 1

X20 DO 2322

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Digital Output Module DO4322


4 digital outputs
Source connection
3-wire connection
24 VDC and GND for actuator supply
Integrated Output Protection

Short Description

X20DO4322

Mechanical Characteristics

X20DO4322

I/O Module

4 digital outputs 24 VDC


in 3-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO4322

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

2.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current or


short circuit, integrated protection
for switching inductances

Remark

Actuator Supply

0.5 A in total for output-independent


actuator supply

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO4322

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.15 W1
Typ. 0.31 W1

Information based on pre-series.

X20 System - Module Overview

87

Connection Example

rn er
1 2
3 4

+24 VDC

+24 VDC

GND

GND

DO
DI 13

DO
DI 24

Geber
+241VDC
24V+

Geber
+242VDC
24V+

GND

GND

Actuator 2

DO 2

Actuator 4

DO 1

Actuator 1

DO

Actuator 3

X20 DO 4322

Pin Assignments

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO4332


4 digital outputs with 2 A
Source connection
3-wire connection
24 VDC and GND for actuator supply
Integrated Output Protection

Short Description

X20DO4332

Mechanical Characteristics

X20DO4332

I/O Module

4 digital outputs 24 VDC


in 3-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO4332

Rated Voltage

24 VDC

Nom. Output Current

2.0 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

4.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current or


short circuit, integrated protection
for switching inductances

Remark

Actuator Supply

0.5 A in total for output-independent


actuator supply

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO4332

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.15 W1
Typ. 0.31 W1

Information based on pre-series.

X20 System - Module Overview

89

Connection Example

rn er
1 2
3 4

+24 VDC

+24 VDC

GND

GND

DO
DI 13

DO
DI 24

Geber
+241VDC
24V+

Geber
+242VDC
24V+

GND

GND

Actuator 4

DO 2

Actuator 1

DO 1

Actuator 2

DO

Actuator 3

X20 DO 4332

Pin Assignments

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO6321


6 digital outputs
Sink connection
2-wire connection
24 VDC for signal supply
Integrated output protection
1-wire connection version with 6x terminal block

Short Description

X20DO6321

Mechanical Characteristics

X20DO6321

I/O Module

6 digital outputs 24 VDC


in 1 or 2 wire connections

Spacing

12.5 mm

Digital Outputs

X20DO6321

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

3.0 A

Storage Temperature

-20C to +70C

Output Circuit

Sink

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current or


short circuit, integrated protection
for switching inductances

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO6321

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.16 W1
Typ. 0.5 W1

Information based on pre-series.

X20 System - Module Overview

91

X20 DO 6321

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6

DO

DO 1

DO 2

DO 3

DO 4

DO 5

DO 6

+24
DIVDC
1

+24
DIVDC
2

Geber
+241VDC
24V+

Geber
+242VDC
24V+

+24
GND
VDC

+24
GND
VDC

The X20 standard terminal block 6x can be used


for uniform one-line wiring. A two-line wiring can
be implemented using the 12x terminal block.

Actuator 1

Actuator 2

Actuator 3

Actuator 4

Actuator 5

Actuator 6

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO6322


6 digital outputs
Source connection
2-wire connection
GND for signal supply
Integrated output protection
1-line connection version with 6x terminal block

Short Description

X20DO6322

Mechanical Characteristics

X20DO6322

I/O Module

6 digital outputs 24 VDC


in 1 or 2 line connections

Spacing

12.5 mm

Digital Outputs

X20DO6322

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

3.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current and


short circuit, integrated protection
for switching inductances

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO6322

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.16 W1
Typ. 0.5 W1

Information based on pre-series.

X20 System - Module Overview

93

X20 DO 6322

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6

DO

DO 1

DO 2

DO 3

DO 4

DO 5

DO 6

GND
DI 1

GND
DI 2

Geber
GND
1 24V+

Geber
GND
2 24V+

GND

GND

The X20 standard terminal block 6x can be used


for uniform one-line wiring.
A two-line wiring can be implemented using the
12x terminal block.

Actuator 1

Actuator 2

Actuator 3

Actuator 4

Actuator 5

Actuator 6

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO8332


8 digital outputs with 2 A
Source connection
1-wire connection
Power feed integrated in the module
Integrated output protection

Short Description

X20DO8332

Mechanical Characteristics

X20DO8332

I/O Module

8 digital outputs 24 VDC


in 1-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO8332

Rated Voltage

24 VDC

Nom. Output Current

2.0 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

8.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current and


short circuit, integrated protection
for switching inductances, reverse
polarity protection of the supply
protection.

Remark

Order standard terminal block


1 x X20TB12 separately. Order
standard bus module 1 x X20BM11
separately.

General Information

X20DO8332

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.21 W1
-

Information based on pre-series.

X20 System - Module Overview

95

X20 DO 8332

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6
7 8

DO

DO 1

DO 2

DO 3

DO 4

DO 5

DO 6

DO
DI 17

DO
DI 28

Geber
+241VDC
24V+

Geber
+242VDC
24V+

GND

GND

Actuator 1

Actuator 2

Actuator 3

Actuator 4

Actuator 5

Actuator 6

Actuator 7

Actuator 8

+24V ext.

The output supply is fed directly on the module.


An additional supply module is not needed.
There is no connection between the module and
the I/O supply potential on the bus module.

_
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO9321


12 digital outputs
Sink connection
1-wire connection
Integrated output protection

Short Description

X20DO9321

Mechanical Characteristics

X20DO9321

I/O Module

12 digital outputs 24 VDC


in 1-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO9321

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

6.0 A

Storage Temperature

-20C to +70C

Output Circuit

Sink

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current or


short circuit, integrated protection
for switching inductances

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO9321

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.21 W1
Typ. 0.99 W1

Information based on pre-series.

X20 System - Module Overview

97

X20 DO 9321

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6
7 8
9 10
11 12

DO

DO 1

DO 2

DO 3

DO 4

DO 5

Actuator 1

Actuator 2

Actuator 3

Actuator 4

Actuator 5

Actuator 6

Actuator 7

Actuator 8

Actuator 9

Actuator 10

Actuator 11

Actuator 12

DO 6

DO
DI 17

DO
DI 28

Geber
DO1 924V+

Geber
DO210
24V+

DO
GND
11

DO
GND
12

+24 VDC
GND

+24 VDC
GND

+24 VDC

+24 VDC

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Digital Output Module DO9322


12 digital outputs
Source connection
1-wire connection
Integrated output protection

Short Description

X20DO9322

Mechanical Characteristics

X20DO9322

I/O Module

12 digital outputs 24 VDC


in 1-wire connections

Spacing

12.5 mm

Digital Outputs

X20DO9322

Rated Voltage

24 VDC

Nom. Output Current

0.5 A

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Total Current

6.0 A

Storage Temperature

-20C to +70C

Output Circuit

Source

Humidity

5 to 95% (non-condensing)

Output Protection

Thermal cutoff for over-current or


short circuit, integrated protection
for switching inductances

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

General Information

X20DO9322

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output error status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.21 W1
Typ. 0.99 W1

Information based on pre-series.

X20 System - Module Overview

99

X20 DO 9322

Pin Assignments

Connection Example

rn er
1 2
3 4
5 6
7 8
9 10
11 12

DO

DO 1

DO 2

DO 3

DO 4

DO 5

Actuator 1

Actuator 2

Actuator 3

Actuator 4

Actuator 5

Actuator 6

Actuator 7

Actuator 8

Actuator 9

Actuator 10

Actuator 11

Actuator 12

DO 6

DO
DI 17

DO
DI 28

Geber
DO1 924V+

Geber
DO210
24V+

DO
GND
11

DO
GND
12

+24 VDC
GND

+24 VDC
GND

GND

GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Input Module AI2622


2 analog inputs
Both current or voltage signals are possible
12-bit digital converter resolution

Short Description

X20AI2622

General Information

X20AI2622

I/O Module

2 analog inputs 10 V
or 0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Inputs

X20AI2622

Input

10 V or 0 to 20 mA, optional, using


different connection terminals

Digital Converter Resolution

12-bit

Conversion Time

200 s for all inputs

Output Format

INT

Input Impedance
in Signal Range
Voltage
Current (load)
Basic Accuracy
Voltage
Current
Input Protection

Information based on pre-series.

1 M
200
0.1% at 25C, based on the
measurement range
0.1% at 25C, based on the
measurement range
Protection against wiring with supply
voltage

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 0.5 W1

Mechanical Characteristics

X20AI2622

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

101

X20 AI 2622

Pin Assignments

Connection Example

rn er
1 2

Voltagemeasurement

AI

Currentmeasurement
+

AI + 1 I

AI + 2 I

AI + 1 U

AI + 2 U

AI - 1 U/I

AI - 2 U/I

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Input Module AI2632


2 analog inputs
Both current or voltage signals are possible
16-bit digital converter resolution
Integrated oscilloscope function

Short Description

X20AI2632

General Information

X20AI2632

I/O Module

2 analog outputs, 10 V or
0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Inputs

X20AI2632

Input

10 V or 0 to 20 mA, optional, using


different connection terminals

Digital Converter Resolution

16-bit

Conversion Time

50 s for all inputs

Output Format

INT

Input Impedance
in Signal Range
Voltage
Current (load)
Basic Accuracy
Voltage
Current
Input Protection

Information based on pre-series.

1 M
200
0.08% at 25C, based on the
measurement range
0.08% at 25C, based on the
measurement range
Protection against wiring with supply
voltage

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.0 W1

Mechanical Characteristics

X20AI2632

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

103

X20 AI 2632

Pin Assignments

Connection Example

rn er
1 2

Voltagemeasurement

AI

Currentmeasurement
+

AI + 1 I

AI + 2 I

AI + 1 U

AI + 2 U

AI - 1 U/I

AI - 2 U/I

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Input Module AI4622


4 analog inputs
Both current or voltage signals are possible
12-bit digital converter resolution

Short Description

X20AI4622

General Information

X20AI4622

I/O Module

4 analog outputs, 10 V or
0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Inputs

X20AI4622

Input

10 V or 0 to 20 mA, optional, using


different connection terminals

Digital Converter Resolution

12-bit

Conversion Time

400 s for all inputs

Output Format

INT

Input Impedance
in Signal Range
Voltage
Current (load)
Basic Accuracy
Voltage
Current
Input Protection

Information based on pre-series.

1 M
200
0.1% at 25C, based on the
measurement range
0.1% at 25C, based on the
measurement range
Protection against wiring with supply
voltage

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 0.8 W1

Mechanical Characteristics

X20AI4622

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

105

X20 AI 4622

Pin Assignments

Connection Example

rn er
1 2
3 4

Voltagemeasurement

AI

Currentmeasurement
+

AI + 1 I

AI + 2 I

AI + 1 U

AI + 2 U

AI - 1 U/I

AI - 2 U/I

AI + 3 I

AI + 4 I

AI + 3 U

AI + 4 U

AI - 3 U/I

AI - 4 U/I

+
+

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Input Module AI4632


4 analog inputs
Both current or voltage signals are possible
16-bit digital converter resolution
Integrated oscilloscope function

Short Description

X20AI4632

General Information

X20AI4632

I/O Module

4 analog outputs, 10 V or
0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Inputs

X20AI4632

Input

10 V or 0 to 20 mA, optional, using


different connection terminals

Digital Converter Resolution

16-bit

Conversion Time

50 s for all inputs

Output Format

INT

Input Impedance
in Signal Range
Voltage
Current (load)
Basic Accuracy
Voltage
Current
Input Protection

1 M
200
0.08% at 25C, based on the
measurement range
0.08% at 25C, based on the
measurement range
Protection against wiring with supply
voltage

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Information based on pre-series.

Mechanical Characteristics

X20AI4632

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

107

X20 AI 4632

Pin Assignments

Connection Example

rn er
1 2
3 4

Voltagemeasurement

AI

Currentmeasurement
+

AI + 1 I

AI + 2 I

AI + 1 U

AI + 2 U

AI - 1 U/I

AI - 2 U/I

AI + 3 I

AI + 4 I

AI + 3 U

AI + 4 U

AI - 3 U/I

AI - 4 U/I

+
+

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Output Module AO2622


2 analog outputs
Both current or voltage signals are possible
12-bit digital converter resolution

Short Description

X20AO2622

General Information

X20AO2622

I/O Module

2 analog outputs, 10 V
or 0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Outputs

X20AO2622

Output

10 V or 0 to 20 mA, optional, using


different connection terminals

Diagnosis
Channel Status
Operating Status
Module Status

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED

Digital Converter Resolution

12-bit

Conversion Time

200 s for all outputs

Power On/Off Behavior

Internal enable relay for boot


procedure and error

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

0.15% at 25C, based on the


output range
0.15% at 25C, based on the
output range

Power Input
Bus
I/O Internal

Typ. 0.01 W1
TBD

Basic Accuracy
Voltage
Current
Output Protection

Protected from short circuit

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Information based on pre-series.

Mechanical Characteristics

X20AO2622

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

109

Connection Example

rn er
1 2

AO

AO + 1 I

AO + 2 I

AO + 1 U

AO + 2 U

AO - 1 U/I

AO - 2 U/I

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

Current

Load

Voltage

Load

X20 AO 2622

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Output Module AO2632


2 analog outputs
Both current or voltage signals are possible
16-bit digital converter resolution

Short Description

X20AO2632

General Information

X20AO2632

I/O Module

2 analog outputs, 10 V
or 0 to 20 mA

Status Display

Channel status, operating status,


module status

Analog Outputs

X20AO2632

Output

10 V or 0 to 20 mA, optional, using


different connection terminals

Diagnosis
Channel Status
Operating Status
Module Status

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED

Digital Converter Resolution

16-bit

Conversion Time

50 s for all outputs

Power On/Off Behavior

Internal enable relay for boot


procedure and error

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

0.1% at 25C, based on the output


range
0.1% at 25C, based on the output
range

Power Input
Bus
I/O Internal

Typ. 0.01 W1
TBD

Basic Accuracy
Voltage
Current
Output Protection

Protected from short circuit

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Information based on pre-series.

Mechanical Characteristics

X20AO2632

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06 or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

111

Connection Example

rn er
1 2

AO

AO + 1 I

AO + 2 I

AO + 1 U

AO + 2 U

AO - 1 U/I

AO - 2 U/I

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

Current

Load

Voltage

Load

X20 AO 2632

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Analog Output Module AO4622


4 analog outputs
Both current or voltage signals are possible
12-bit digital converter resolution

Short Description

X20AO4622

Mechanical Characteristics

X20AO4622

I/O Module

4 analog outputs, 10 V
or 0 to 20 mA

Spacing

12.5 mm

Analog Outputs

X20AO4622

Output

10 V or 0 to 20 mA, optional, using


different connection terminals

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Digital Converter Resolution

12-bit

Storage Temperature

-20C to +70C

Conversion Time

400 s for all outputs

Humidity

5 to 95% (non-condensing)

Power On/Off Behavior

Internal enable relay for boot


procedure and error

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

Basic Accuracy
Voltage
Current

0.15% at 25C, based on the


output range
0.15% at 25C, based on the
output range

Output Protection

Protected from short circuit

General Information

X20AO4622

Status Display

Channel status, operating status,


module status

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
TBD

Information based on pre-series.

X20 System - Module Overview

113

Connection Example

rn er
1 2
3 4

AO

AO + 1 U

AO + 2 U

AO - 1 U/I

AO - 2 U/I

AO + 3 I

AO + 4 I

AO + 3 U

AO + 4 U

AO - 3 U/I

AO - 4 U/I

+24 VDC
GND

Load

AO + 2 I

Current

Load

AO + 1 I

Load

Voltage

Load

X20 AO 4622

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Analog Output Module AO4632


4 analog outputs
Both current or voltage signals are possible
16-bit digital converter resolution

Short Description

X20AO4632

Mechanical Characteristics

X20AO4632

I/O Module

4 analog outputs, 10 V
or 0 to 20 mA

Spacing

12.5 mm

Analog Outputs

X20AO4632

Output

10 V or 0 to 20 mA, optional, using


different connection terminals

Digital Converter Resolution

16-bit

Conversion Time

50 s for all outputs

Power On/Off Behavior

Internal enable relay for boot


procedure and error

Basic Accuracy
Voltage
Current

0.1% at 25C, based on the output


range
0.1% at 25C, based on the output
range

Output Protection

Protected from short circuit

General Information

X20AO4632

Status Display

Channel status, operating status,


module status

Diagnosis
Channel Status
Operating Status
Module Status
Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
TBD

Information based on pre-series.

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

115

Connection Example

rn er
1 2
3 4

AO

AO + 1 U

AO + 2 U

AO - 1 U/I

AO - 2 U/I

AO + 3 I

AO + 4 I

AO + 3 U

AO + 4 U

AO - 3 U/I

AO - 4 U/I

+24 VDC
GND

Load

AO + 2 I

Current

Load

AO + 1 I

Load

Voltage

Load

X20 AO 4632

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module with


power bus interconnected

Temperature Module AT2222


2 inputs for resistance temperature measurement
For PT100 and PT1000
Sensor type can be set for each channel
Direct resistance measurement as well
2 or 3 wire connection can be configured for each module
Filter time can be configured

Short Description

X20AT2222

General Information

X20AT2222

I/O Module

2 inputs for PT100 or PT1000


resistance temperature
measurement

Status Display

Channel status, operating status,


module status

Temperature Inputs
Resistance Measurement
Input

Operating Status
Module Status

X20AT2222
Resistance measurement with
constant current supply
for 2 or 3 wire connection

Digital Converter Resolution

16-bit

Filter Time

Configurable between 1 ms and


66.7 ms

Conversion Time
1 Channel
2 Channel

Diagnosis
Channel status

20 ms at 50 Hz filter
60 ms with same sensor type
and 50 Hz filter
100 ms with different sensor type
and 50 Hz filter

Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Information based on pre-series.

Mechanical Characteristics

X20AT2222

Spacing

12.5 mm

Output Format

INT or UINT for resistance


measurement

Basic Accuracy

0.1% at 25C,
based on the measurement range

Mounting Orientation

Horizontal or vertical

Protection

IP20

Sensor
PT100
PT1000

Can be set per channel


-200C to +850C
-200C to +850C

Operating Temperature
Horizontal Installation

Resistance Measurement Range

0.1 to 4500 or
0.05 to 2250

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06
or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

0C to +55C
Derating with vertical installation

X20 System - Module Overview

117

Connection Example

3-Wire
Connection

Sensor+ 1

Sensor+ 2

Sense- 1

Sense- 2

Sensor- 1

Sensor- 2

2-Wire
Connection
+
_

_
_

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

AT

Sensor 2

rn er
1 2

Sensor 1

X20 AT 2222

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Temperature Module AT4222


4 inputs for resistance temperature measurement

For PT100 and PT1000


Sensor type can be be set for each channel
Direct resistance measurement as well
2 or 3 wire connection can be configured for each module
Filter time can be configured

Short Description

X20AT4222

General Information

X20AT4222

I/O Module

4 inputs for PT100 or PT1000


resistance temperature
measurement

Status Display

Channel status, operating status,


module status

Temperature Inputs
Resistance Measurement
Input

Resistance measurement with


constant current supply
for 2 or 3 line connection
16-bit

Filter Time

Configurable between 1 ms and


66.7 ms

Different sensor types

Operating Status
Module Status

X20AT4222

Digital Converter Resolution

Conversion Time
1 channel
Same Sensor Types

Diagnosis
Channel status

20 ms at 50 Hz filter
30 ms for each channel with 50 Hz
filter
50 ms for each channel with 50 Hz
filter (maximum time)

Certification

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.3 W1

Information based on pre-series.

Mechanical Characteristics

X20AT4222

Spacing

12.5 mm

Output Format

INT or UINT for resistance


measurement

Basic Accuracy

0.1% at 25C,
based on the measurement range

Mounting Orientation

Horizontal or vertical

Protection

IP20

Sensor
PT100
PT1000

Can be set per channel


-200C to +850C
-200C to +850C

Operating Temperature
Horizontal Installation

Resistance Measurement Range

0.1 to 4500 or
0.05 to 2250

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

0C to +55C
Derating with vertical installation

X20 System - Module Overview

119

Connection Example

2-Wire
Connection
+
_

+
_

Sensor+ 1

Sensor+ 2

Sense- 1

Sense- 2

Sensor- 1

Sensor- 2

Sensor+
DI 1 3

Sensor+
DI 2 4

Geber
Sense1 24V+
3

Geber
Sense2 24V+
4

SensorGND 3

SensorGND 4

Sensor 3

AT

Sensor 2

3-Wire
Connection

Sensor 4

rn er
1 2
3 4

Sensor 1

X20 AT 4222

Pin Assignments

_
_

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Temperature Module AT2402


2 inputs for thermocouples
For sensor types J, K, S
Additional direct raw value measurement
Integrated terminal temperature compensation
Filter time can be configured

Short Description

X20AT2402

General Information

X20AT2402

I/O Module

2 inputs for thermocouples

Status Display

Channel status, operating status,


module status

Temperature Inputs
Thermocouples

X20AT2402

Diagnosis
Channel Status

Input

Thermocouple

Digital Converter Resolution

16-bit

Filter Time

Configurable between 1 ms and


66.7 ms

Certification

Conversion Time
1 channel
2 channels

40.4 ms at 50 Hz filter
60.6 ms at 50 Hz filter

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Output Format

INT

Basic Accuracy
Type J
Type K
Type S

0.1% at 25C1
0.1% at 25C1
0,14% at 25C1

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 0.5 W1

Measurement Range
Sensor Temperature
FeCuNi: Type J
NiCrNi: Type K
PtRhPt: Type S
Terminal Temperature
Raw Value

-210C to +1200C
-270C to +1372C
-50C to +1768C
0C to +85C
65,534 V

Terminal Temperature
Compensation
1

Internal

Refers to the measurement range, without consideration


of the reference junction measurement error.

Operating Status
Module Status

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Information based on pre-series.

Mechanical Characteristics

X20AT2402

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06
or X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

121

Connection Example

rn er
1 2

TC+ 1

TC+ 2

TC- 1

TC- 2

+24 VDC
GND

The module is designed for X20 standard terminal


blocks 6x. For logistical reasons, the 12x terminal
block can also be used.

TC 2

AT

TC 1

X20 AT 2402

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB06

X20 standard terminal 6x

X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Temperature Module AT6402


6 inputs for thermocouples
For sensor types J, K, S
Additional direct raw value measurement
Integrated terminal temperature compensation
Filter time can be configured

Short Description

X20AT6402

General Information

X20AT6402

I/O Module

6 inputs for thermocouples

Status Display

Channel status, operating status,


module status

Temperature Inputs
Thermocouples

X20AT6402

Diagnosis
Channel Status

Input

Thermocouple

Digital Converter Resolution

16-bit

Filter Time

Configurable between 1 ms and


66.7 ms

Certification

Conversion Time
1 channel
n channels

40.4 ms at 50 Hz filter
(n+1) x 20.2 ms for 50 Hz filter

Electrical Isolation
Channel - Bus
Channel - Channel

Yes
No

Output Format

INT

Basic Accuracy
Type J
Type K
Type S

0.1% at 25C1
0.1% at 25C1
0.14% at 25C1

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 0.8 W1

Measurement Range
Sensor Temperature
FeCuNi: Type J
NiCrNi: Type K
PtRhPt: Type S
Terminal Temperature
Raw Value

-210C to +1200C
-270C to +1372C
-50C to +1768C
0C to +85C
65,534 V

Terminal Temperature
Compensation
1

Internal

Refers to the measurement range, without consideration


of the reference junction measurement error.

Operating Status
Module Status

Yes, with status LED and software


status
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Information based on pre-series.

Mechanical Characteristics

X20AT6402

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

123

Connection Example

rn er
1 2
3 4
5 6

TC+ 3

TC+ 4

TCDI 13

TCDI 24

Geber
TC+
1 24V+
5

Geber
TC+
2 24V+
6

TCGND5

TCGND6

+24 VDC
GND

TC 4

TC- 2

TC 6

TC- 1

TC 3

TC+ 2

TC 5

TC+ 1

TC 2

AT

TC 1

X20 AT 6402

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC1196


1 ABR Incremental Encoder 5 V
2 additional inputs e.g. for reference enable switch
5 VDC, 24 VDC and GND for encoder supply

Short Description

X20DC1196

General Information

X20DC1196

I/O Module

1 ABR Incremental Encoder 5 V

Status Display

I/O function per channel, operating


state, module status

Incremental Encoders

X20DC1196

Encoder Inputs

5 V, symmetrical

Counter Size

16-bit

Diagnosis
Operating Status
Module Status

Input Frequency (max.)

250 kHz

Evaluation

4-fold

Encoder Supply
5V
24 V

Module-internal, max. 300 mA


Module-internal, max. 300 mA

Digital Inputs

X20DC1196

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

Additional Functionalities

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Electrical Isolation
Encoder - Bus
Channel - Bus
Channel - Encoder
Channel - Channel

Yes
Yes
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Reference Enable Switch

Yes, with status LED


Yes, with status LED

Information based on pre-series.

Mechanical Characteristics

X20DC1196

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

125

Connection Example

rn er
A
B
R
1 2

A\

B\

R\

DI 1

DI 2

Encoder 24V+

Encoder 5V+

GND

GND

A
A\
B
B\
R
R\

Counter 1

DC

Sensor 1

X20 DC 1196

Pin Assignments

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC1198


1 SSI absolute encoder 5 V
2 additional inputs
5 VDC, 24 VDC and GND for encoder supply

Short Description

X20DC1198

General Information

X20DC1198

I/O Module

1 SSI absolute encoder 5 V

Status Display

I/O function per channel, operating


state, module status

SSI Absolute Encoder

X20DC1198

Encoder Inputs

5 V, symmetrical

Diagnosis
Operating Status
Module Status

Counter Size

32-bit

Maximum Transfer Rate

1 MBit/s

Encoder Supply
5V
24 V

Module-internal, max. 300 mA


Module-internal, max. 300 mA

Digital Inputs

X20DC1198

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

Additional Functionalities

Reference enable switch

Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Channel - Bus
Channel - Encoder
Channel - Channel

Yes
Yes
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Information based on pre-series.

Mechanical Characteristics

X20DC1198

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

127

Connection Example

rner

DC

D1 D2
1 2

Data
Data \
Clock

Data \

Clock

Clock \

DI 1

DI 2

Encoder 24V+

Encoder 5V+

GND

GND

Clock \

Sensor 1

Data

Counter 1

X20 DC 1198

Pin Assignments

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC1396


1 ABR incremental encoder 24 V
1 additional input e.g. for reference enable switch
24 VDC and GND for encoder supply

Short Description

X20DC1396

Mechanical Characteristics

X20DC1396

I/O Module

1 ABR incremental encoder 24 V

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical
IP20

Incremental Encoders

X20DC1396

Protection

Encoder Inputs

24 V, asymmetrical

Counter Size

16-bit

Operating Temperature
Horizontal Installation

Input Frequency (max.)

100 kHz

0C to +55C
Derating with vertical installation

Evaluation

4-fold

Storage Temperature

-20C to +70C

Encoder Supply

Module-internal, max. 600 mA

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

Reference Enable Switch

X20DC1396

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

General Information

X20DC1396

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Yes
Reference Enable Switch - Bus Yes
Reference Enable Switch No
Encoder
Power Input
Bus
I/O Internal
1

Information based on pre-series.

Typ. 0.01 W1
Typ. 1.0 W1

X20 System - Module Overview

129

Connection Example

rn er
A
B
R
1

DC

Counter 1

X20 DC 1396

Pin Assignments

A1
B1
R1

R
DI 1
Encoder 24V+
GND

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC1398


1 SSI absolute encoder 24 V
1 additional input
24 VDC and GND for encoder supply

Short Description

X20DC1398

Mechanical Characteristics

X20DC1398

I/O Module

1 SSI absolute encoder 24 V

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical
IP20

SSI Absolute Encoder

X20DC1398

Protection

Encoder Inputs

24 V, asymmetrical

Counter Size

32-bit

Operating Temperature
Horizontal Installation

Maximum Transfer Rate

200 kBit/s

Encoder Supply

Module-internal, max. 600 mA

Digital Inputs

X20DC1398

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

General Information

X20DC1398

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Channel - Bus
Channel - Encoder

Yes
Yes
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Information based on pre-series.

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

131

Data

Connection Example

rner

DC

D1
1

Counter 1

X20 DC 1398

Pin Assignments

Data

Clock

Clock

DI 1
Encoder 24V+
GND

+24 VDC
GND

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC2396


2 ABR incremental encoder 24 V
2 additional inputs e.g. for reference enable switch
24 VDC and GND for encoder supply

Short Description

X20DC2396

General Information

X20DC2396

I/O Module

2 ABR incremental encoder 24 V

Status Display

I/O function per channel, operating


state, module status

Incremental Encoders

X20DC2396

Encoder Inputs

24 V, asymmetrical

Counter Size

16-bit

Diagnosis
Operating Status
Module Status

Input Frequency (max.)

100 kHz

Evaluation

4-fold

Encoder Supply

Module-internal, max. 600 mA

Reference Enable Switch

X20DC2396

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Ref. Enable Switch - Bus
Ref. Enable Switch - Encoder
Encoder - Encoder
Ref. Switch - Ref. Switch

Yes
Yes
No
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.1 W1

Information based on pre-series.

Mechanical Characteristics

X20DC2396

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

133

Connection Example

rn er

A1

A2

B1

B2

R1

R2

DI 1

DI 2

Encoder 1 24V+

Encoder 2 24V+

GND

GND

A1

A2

B1

B2

R1

R2

+24 VDC
GND

Counter 2

DC

A1A2
B1 B2
R1 R2
1 2

Counter 1

X20 DC 2396

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC2398


2 SSI absolute encoder 24 V
2 additional inputs
24 VDC and GND for encoder supply

Short Description

X20DC2398

Mechanical Characteristics

X20DC2398

I/O Module

2 SSI absolute encoder 24 V

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical
IP20

SSI Absolute Encoder

X20DC2398

Protection

Encoder Inputs

24 V, asymmetrical

Counter Size

32-bit

Operating Temperature
Horizontal Installation

Maximum Transfer Rate

200 kBit/s

Encoder Supply

Module-internal, max. 600 mA

Digital Inputs

X20DC2398

Amount

Rated Voltage

24 VDC

Input Filter
Hardware
Software

2 s
-

Input Circuit

Sink

General Information

X20DC2398

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Operating Status
Module Status
Certification

Yes, with status LED


Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Channel - Bus
Channel - Encoder
Encoder - Encoder
Channel - Channel

Yes
Yes
No
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.2 W1

Information based on pre-series.

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 System - Module Overview

135

Connection Example

rner

Data 1

Data 2

Clock 1

Clock 2

DI 1

DI 2

Encoder 1 24V+

Encoder 2 24V+

GND

GND

Data 1

Data 2

Clock 1

Clock 2

+24 VDC
GND

Counter 2

DC

D1 D2
1 2

Counter 1

X20 DC 2398

Pin Assignments

+24 VDC
GND

Required Accessories
X20TB12

X20 standard terminal 12x

X20BM11

X20 standard bus module


with power bus interconnected

Counter Module DC2395


24 VDC encoder inputs
SSI, AB or event counters for inputs
Pulse width modulation for outputs
24 VDC and GND for encoder supply

Short Description

X20DC2395

Digital Outputs

X20DC2395

I/O Module

2 SSI absolute encoders 24 V,


2 AB incremental encoders 24 V,
4 x event counters or
2 x pulse width modulation

Amount

Rated Voltage

24 VDC

Nom. Output Current

0.1 A

Total Current

0.4 A

SSI Absolute Encoder

X20DC2395

Output Circuit

Sink or source

Amount

Output Protection

Encoder Inputs

24 V, asymmetrical

Thermal cutoff for over-current and


short circuit, integrated protection
for switching inductances.

Counter Size

32-bit

Maximum Transfer Rate

200 kBit/s

Encoder Supply

Module-internal, max. 600 mA

Incremental Encoders

X20DC2395

Amount

Encoder Inputs

24 V, asymmetrical

Counter Size

16-bit

Input Frequency (max.)

100 kHz

Evaluation

4-fold

Encoder Supply

Module-internal, max. 600 mA

Event Counter

X20DC2395

Amount

Rated Voltage

24 VDC

Counter Size

16-bit

Evaluation

Each edge, cyclic counter

Signal Form

Square wave pulse

Pulse Width Modulation


Period Duration
Pulse Length
Resolution

500 s ... 500 ms


0.0% to 0.1%
0.1%

Actuator Supply

Module-internal, max. 600 mA

General Information

X20DC2395

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Output - Bus
Output - Encoder
Encoder - Encoder
Output - Output

Yes
Yes
No
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.2 W1

Iinformation based on pre-series.

X20 System - Module Overview

137

X20 DC 2395

Pin Assignments

Connection Example

rn er
1 2
3 4

DC
Data

Counter 1

Clock

Channel 1
Channel 2

A
B
R
PWM

Channel 3
Channel 4
Encoder 1 24V+

+24 VDC
GND

GND

Mechanical Characteristics

X20DC4395

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

+24 VDC
GND

0C to +55C
Derating with vertical installation

Required Accessories

Storage Temperature

-20C to +70C

X20TB12

X20 standard terminal 12x

Humidity

5 to 95% (non-condensing)

X20BM11

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 standard bus module


with power bus interconnected

Counter Module DC4395


24 VDC encoder inputs
SSI, AB or event counters for inputs
Pulse width modulation for outputs
24 VDC and GND for encoder supply

Short Description

X20DC4395

Digital Outputs

X20DC4395

I/O Module

4 SSI absolute encoders 24 V,


4 AB incremental encoders 24 V,
8 x event counters or
4 x pulse width modulation

Amount

Rated Voltage

24 VDC

Nom. Output Current

0.1 A

Total Current

0.4 A

SSI Absolute Encoder

X20DC4395

Output Circuit

Sink or source

Amount

Output Protection

Encoder Inputs

24 V, asymmetrical

Thermal cutoff for over-current and


short circuit, integrated protection
for switching inductances.

Counter Size

32-bit

Maximum Transfer Rate

200 kBit/s

Encoder Supply

Module-internal, max. 600 mA

Incremental Encoders

X20DC4395

Amount

Encoder Inputs

24 V, asymmetrical

Counter Size

16-bit

Input Frequency (max.)

100 kHz

Evaluation

4-fold

Encoder Supply

Module-internal, max. 600 mA

Event Counter

X20DC4395

Amount

Rated Voltage

24 VDC

Counter Size

16-bit

Evaluation

Each edge, cyclic counter

Signal Form

Square wave pulse

Pulse Width Modulation


Period Duration
Pulse Length
Resolution

500 s ... 500 ms


0.0% to 0.1%
0.1%

Actuator Supply

Module-internal, max. 600 mA

General Information

X20DC4395

Status Display

I/O function per channel, operating


state, module status

Diagnosis
Outputs
Operating Status
Module Status
Certification

Yes, with status LED and software


status (output status)
Yes, with status LED
Yes, with status LED
CE, C-UL-US (in development),
GOST-R (in development)

Electrical Isolation
Encoder - Bus
Output - Bus
Output - Encoder
Encoder - Encoder
Output - Output

Yes
Yes
No
No
No

Power Input
Bus
I/O Internal

Typ. 0.01 W1
Typ. 1.4 W1

Iinformation based on pre-series.

X20 System - Module Overview

139

Connection Example

rn er
1 2
3 4
5 6
7 8

Channel 1

Channel 5

Channel 2

Channel 6

Channel 3

Channel 7

Channel 4

Channel 8

Encoder 1 24V+

Encoder 2 24V+

GND

GND

Mechanical Characteristics

X20DC4395

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical

Protection

IP20

Operating Temperature
Horizontal Installation

Data

Data

Clock

Clock

A
B
R
PWM

+24 VDC
GND

A
B
R

Counter 2

DC

Counter 1

X20 DC 4395

Pin Assignments

PWM

+24 VDC
GND

0C to +55C
Derating with vertical installation

Required Accessories

Storage Temperature

-20C to +70C

X20TB12

X20 standard terminal 12x

Humidity

5 to 95% (non-condensing)

X20BM11

Remark

Order standard terminal block 1 x


X20TB12 separately.
Order standard bus module 1 x
X20BM11 separately.

X20 standard bus module


with power bus interconnected

Dummy Module ZF0000


Place holder for later system expansion
Used as a terminal holder
Module without electrical function

Short Description

X20ZF0000

Mechanical Characteristics

X20ZF0000

Accessories

Dummy module without function

Spacing

12.5 mm

Mounting Orientation

Horizontal or vertical
IP20

General Information

X20ZF0000

Protection

Certification

CE, C-UL-US (in development),


GOST-R (in development)

Operating Temperature
Horizontal Installation

0C to +55C
Derating with vertical installation

Storage Temperature

-20C to +70C

Humidity

5 to 95% (non-condensing)

Remark

Order standard terminal block 1 x


X20TB06
or X20TB12 separately.
Order standard terminal block 1 x
X20BM11 or supply bus module
1 x X20BM01 separately.

X20 System - Module Overview

141

Connection Example

X20 ZF 0000

Pin Assignments

+24 VDC
GND

+24 VDC
GND

Accessories
Accessories

X20 AC 0SC1

X20 AC 0SH1

Model Number

Insert holder, terminal locking clip

X20AC0SC1

Plain text insert

X20AC0SH1

Additional locking clip

X20AC0AX1

Insert holder, terminal locking clip - Pack of 100

X20AC0SC1.0100

Plain text insert - Pack of 100

X20AC0SH1.0100

Additional locking clip - Pack of 100

X20AC0AX1.0100

Locking plate left

X20AC0SL1

Locking plate right

X20AC0SR1

Locking plate left - Pack of 10

X20AC0SL1.0010

Locking plate right- Pack of 10

X20AC0SR1.0010

X20 AC 0AX1

X20 AC 0SC1

X20 AC 0AX1
X20 AC 0SH1

X20 System - Accessories

143

X20 AC 0PR1

X20 AC 0Mxx

Accessories

Model Number

Printer

X20AC0PR1

Identification label, blank, white, for 16 modules

X20AC0M01

Identification label, blank, red, for 16 modules

X20AC0M02

Identification label, blank, blue, for 16 modules

X20AC0M03

Identification label, blank, orange, for 16 modules

X20AC0M04

Identification label, printed, white, for 16 modules

X20AC0M11

Identification label, printed, red, for 16 modules

X20AC0M12

Identification label, printed, blue, for 16 modules

X20AC0M13

Identification label, printed, orange, for 16 modules

X20AC0M14

Identification label, blank, white, for 16 modules, pack of 10

X20AC0M01.0010

Identification label, blank, red, for 16 modules, pack of 10

X20AC0M02.0010

Identification label, blank, blue, for 16 modules, pack of 10

X20AC0M03.0010

Identification label, blank, orange, for 16 modules, pack of 10

X20AC0M04.0010

Identification label, printed, white, for 16 modules, pack of 10

X20AC0M11.0010

Identification label, printed, red, for 16 modules, pack of 10

X20AC0M12.0010

Identification label, printed, blue, for 16 modules, pack of 10

X20AC0M13.0010

Identification label, printed, orange, for 16 modules, pack of 10

X20AC0M14.0010

Dimensions, Mounting Guidelines


Dimensions
The dimensions are in 2D with the ECAD macros for CAD support. IGES data is provided for 3D representation.

75mm

99mm

99mm
12,5mm

Dimensions

145

Mounting guidelines

All measurement values are given in mm.

Your notes

X20 System

147

MM-E00443.231
2004 by B&R. All rights reserved.
All trademarks presented are the property of their respective company. We reserve the right to make technical changes.

CORPORATE HEADQUARTERS
Bernecker + Rainer Industrie-Elektronik Ges.m.b.H.
B &R Strae 1
A - 5142 Eggelsberg
Tel.: +43 (0) 77 48 / 65 86 - 0
Fax: +43 (0) 77 48 / 65 86 - 26
info@br-automation.com
www.br-automation.com

More information about the individual locations can be found at contact.br-automation.com

AUSTRALIA

EGYPT

KYRGYZSTAN

SPAIN

Brisbane, Procon Pty. Ltd.


Cairns, Procon Pty. Ltd.
Melbourne, Procon Pty. Ltd.
Perth, Procon Pty. Ltd.
Sydney, Procon Pty. Ltd.

Cairo, Sigma Engineering

Kirgisia, Nark OOsO

FINLAND

MALAYSIA

Zarautz Gipuzkoa,
Larraioz Electronica Industrial SL.

Savonlinna, Control Express OY

Kuala Lumpur, FA Controls Sdn Bhd

SWEDEN

FRANCE

THE NETHERLANDS

AUSTRIA

B&R Automation Industrielle Sarl


B&R HQ: Lyon

B&R Industrile Automatisering B.V.


B&R HQ: Breda

B&R Industriautomation AB
B&R HQ: Malm
B&R Stockholm

GERMANY

NORWAY

B&R Industrie-Elektronik GmbH


B&R HQ: Bad Homburg
B&R Essen
B&R Hannover
B&R Heilbronn
B&R Ismaning
B&R Krefeld
B&R Leipzig
B&R Balingen-Endingen
B&R Gummersbach-Kln
B&R Hagen
B&R Marktoberdorf
B&R Walzbachtal-Baden

Klepp Stasjon, Kverneland Elektriske A/S

B&R Industrie-Automation AG
B&R HQ: Frauenfeld

PAKISTAN

TAIWAN

Lahore, Intech PTE Ltd

Taipei County, Andtek Automation Co., Ltd.

POLAND

THAILAND

B&R Automatyka Przemyslowa Sp. z o. o.


B&R HQ: Poznan
Katowice, Constel Sp.zo.o

Samutsakhon,
Industrial Technology Supply Co., Ltd.

GREECE

B&R HQ: Moscow


Moscow, Apotheos Com
Moscow, Entas OOO
Moscow, Vado International GUS
Moscow, ZAO ACEA
Novosibirsk, ZAO NIIES
St. Petersburg, Azimuth Engineering
St. Petersburg, Vado International GUS
Tjumen, IPF ASU NEFT

Bernecker+Rainer
Industrie-Elektronik Ges.m.b.H.
B&R HQ: Eggelsberg
B&R Graz
B&R Lienz
B&R Rankweil
B&R Salzburg
B&R Wels
B&R Wien

BELARUS
Minsk, Entas OOO

BELGIUM
B&R HQ: Aalst

BRAZIL
B&R HQ: Campinas

CANADA

Athens, GNZ - Complete Solutions

PORTUGAL
RUSSIA

HUNGARY

CHINA

INDIA

B&R Industrial Automation


International Trade Co., Ltd.
B&R HQ: Shanghai
B&R Beijing
B&R Guangzhou
B&R Ji nan
B&R Xi an

B&R Industrial Automation Pvt. Ltd.


B&R HQ: Pune
B&R Ahmedabad
B&R Bangalore

CROATIA

ISRAEL

Zagreb, Evasys d.d.o.

Tel Aviv, Yeda Hen Ltd.

B&R HQ: Nov Mesto nad Vhom


ilina, Urap Automatizcia s.r.o.

CYPRUS

ITALY

SLOVENIA

Limassol, N.G. Pavlides Automations Ltd.

B&R Automazione Industriale S.p.A.


B&R HQ: Milano
B&R Bologna
B&R Padova

Ribnica, Motoman Robotek d.o.o.

CZECH REPUBLIC
B&R automatizace, spol. s.r.o.
B&R HQ: Brno

DENMARK
B&R Industriautomatisering
B&R HQ: Odense

INDONESIA
Jakarta Barat, Amptron PTE Ltd.

KOREA
B&R Industrial Automation Co., Ltd.
B&R HQ: Seoul / Anyang-city

TURKEY
Istanbul, YORUM Ltd. A.S

Lisboa, Tecnilab LDA

B&R Industrial Automation Inc.


B&R HQ: Mississauga, ON

Budapest, Dial-Comp Ltd.

SWITZERLAND

SINGAPORE
B&R HQ: Singapore
Singapore, Amptron PTE Ltd.

SLOVAKIA

SOUTH AFRICA
Johannesburg, CMW Automation Pty Ltd.
Ladysmith, CMW Automation Pty Ltd.
Port Elisabeth, CMW Automation Pty Ltd.

UKRAINE
Chernovchy, Skif Corporation
Kiev, Skif Control
Zaporizhzhya, Mikrotech

UNITED KINGDOM
B&R Industrial Automation Ltd.
B&R HQ: Peterborough

USA
B&R Industrial Automation Corp.
B&R HQ: Roswell, GA.
B&R Chicago, IL.
B&R Cincinnati, OH.
Atlanta, GA., Piedmont Automation, Inc.
Detroit, MI., Majority Controls LLC
Greensboro, NC., Integrated Motion Inc.
Rochester, NY., Total Automation Inc.

Potrebbero piacerti anche