Electrical Panel Selection

Prepared in collaboration with:


M/s. Power Engineering,
Plot No. 552, Industrial Area, Phase- IX, Mohali
Contact Person: Sh. B.S. Verma, 9417233527

Typical Power System

Types of Power Connections

LT
< 50KW.
HT
> 50KW.
Independent feeders 11KV.
High Voltage Transmission/ Distribution is Preferred
because of Low losses & Reduced size of Conductors
during transmission.
The power is transmitted at high voltage and low
current.
The heat generated during transmission is
proportional to current transmission.

Selection of Circuit Breaker













Power (KW/KVA/HP)
Rated Current.
System Voltage
Breaking Capacity
Making Capacity
Category A or B
Suitability to site Condition (Indian
Condition)
Maintenance Definitions
Effect of harmonics

Calculation Formulas

System for HT/ LT connection

HVPN Supply
GO Switch
HT Metering
VCB
Transformer
LT Panel ( Power control centre, Power factor panel,
AMF)
Distribution Panel
Sub Distribution panel

Selection Of GO Switch
Gang Operated Switch
Comprises of :- Lightning
Arresters, GO (gang
operated) switch, Drop off
Fuse(DO), Plate Earthings
two Nos.
for LA (lightening arrestor)
& GO switch.
Selected at 11KV Only.

Selection of CT & PT
CT (Current Transformer /5A)
Selected as per the full load
current of Transformer.
PT ( Potential Transformer) As per
the system
Voltage.(11Kv/220v/110v/24V)AC
Calculation of HT Current for CT
KVA/11KV/1.732
Example:- Transformer rating ( HT
current for CT/PT selection)
500Kva/11KV/1.732 = 26.24
Tri vector Meter selected as per
HT Current.

VCB Panel
Vacuum Circuit Breaker
For Switching carrying
Normal Current and
Breaking abnormal current
at High Voltage.
630A ( Short circuit current)
and Above.
Over Load, Short Circuit &
E/F protections.
Measurement of current,
Voltage etc.

Transformer
11KV( input)/433V ( Output)
Selection of Transformer as
per Total load.
Buckle relay and winding
temperature for safety of
Transfer. These help to trip
VCB.
Silica gel to check moisture
content. If blue- Ok, If white
or light pink- replace it.

LT Panels
PCC--- Power Control
Center.
MCC- Motor Control
Center.
AMF- Auto Mains Failure
Panel
APFC- Automatic Power
Factor Correction
Distribution Panels.

STARTER FOR THREE PHASE


INDUCTION MOTOR
Starting is a process in which a motors rotor is
brought from zero speed to rated speed.
The force to rotate in angular movement is
called Torque.
Direct On Line Starters used upto 10 HP
Star Delta Starters
o
o
o
o

Manual Star Delta Starters ( not used)


Automatic Start Delta Starters
Soft Starters
VFD

Starter Panel for Induction


Motors
1.
2.
3.
4.
5.
6.

Contactors + Over Load + MCCB / MPCB


Motor Protection Relay
On delay Timer + Capacitor Duty Contactor + Capacitors
Under Voltage & Over Voltage Relay
Hour Meter
Time Switch

Components To Be used In Starters


 DOL MPCB-1No,Contactor- 1No, Push Button 2Nos. On
Indication 1 No., single phase preventer 1 No Up to
10HP,
 Star Delta Starter MCCB 1no, Contactors 3nos,MPR1no, star-delta Timer 1No, Ammeter with CT 1 No, Push
Button 2no, on Indication 1no., single phase preventer 1
No.
 Soft Starter- MCCB 1 No, Semiconductor fuses 3 Nos.,
Line Contactor 1 No, Soft Starter 1 No. ( with built in
bye-pass contactor & soft starter selected as per duty or
application), Push Button 2 Nos.
 VFD- MCCB 1 No, Semiconductor fuses 3 Nos, VFD1 No.
Push Button 2 Nos. Input/ Out put Chokes.

REDUCTION IN KVA DEMAND DUE TO


POWER FACTOR

LOAD - 900 KW
EXISTING P.F. (COS 1)- 0.6
DESIRED P.F. (COS 2) - 0.92
COS . =
KVA

kW
kVA
kW
cos .

KVA 1 =

900 / 0.6 = 1500

KVA2 =

900 / 0.92 = 978

.
KW

Reduction in KVA
1500 - 978 = 522

REDUCTION IN LINE
CURRENT
KVA1 - 1500

KVA

KVA2 - 978

I1

Reduction in Current
2087 - 1361 = 726

I2

3 V I
1000
KVA x 1000
3 x 415
1500 x 1000
3 x 415

2087 Amp

978 x 1000
3 x 415

1361 Amp

Selection of Capacitor
Configuration of capacitors
1. Individual Compensation
2. Group Compensation
3. Central Compensation
KVAR required ( Capacitor)
= KVA X (1- PF(E)) - KVA X (1- PF(T))
Existing Power factor from HVPN= PF(E) i.e. 0.6 to 0.75
Target Power factor for system = PF(T) i.e. 0.99

Advantage of Soft Starter


It starts the motor rotor from zero to
designed speed thereby reducing initial
load on system.
The star Delta starts generally starts with
jerk i.e. 30 % of designed speed.
Soft starters are preferred at high heads.

Direct on Line
START

Line Contactor

Overload

% VOLTS
100
80
60
40
20
0

Run
Start

TIME

Run Contactor
START

Line Contactor

Resistors

Primary
Resistance

Overload

% VOLTS
100
80
60
40
20
0

Run
Start
TIME

Autotransformer

Star Point
Contactor

START

Transformer
Contactor

% VOLTS
100
80
60
40
20
0

Line Contactor

Overload

Run
Start
TIME

START

Star Point
Contactor

Star Delta

Delta
Contactor

% VOLTS
100
80
60
40
20
0

Line Contactor

Overload

Run
Start
TIME

Soft Starting

START

% VOLTS
100
80
60
40
20
0

Run
Start

TIME

EBG Electrical Standard Products

Basics of AC Drives
Frequency controls Motor
IMSspeed
2 Product Familiarisation
Supply Voltage controls Motor Torque
Supply Voltage is varied in proportion to
supply frequency so as to keep torque
constant

LARSEN & TOUBRO LIMITED.

GOOD TERMINATION PRACTICE


DOs AND DONTs

TERMINATION WITH
BUSBAR/LINK

DONT

DO

DONT
DO

DONT
DO

DONT

DO

TERMINATION WITH
LUGS

DONT

DO

DONT
DO

DONT

DO

DONT
DO

MCB (Miniature Circuit Breaker),


Rated current not more than 63 A, Thermal or
thermal-magnetic operation.

MCCB (Moulded Case Circuit Breaker)


Rated current above 32 A upto 630 A, Trip
current may be adjustable, Thermal or
thermal-magnetic operation.

Air Circuit Breaker


Rated current from 800 A upto 6,000 A,
Trip characteristics often fully adjustable including
configurable trip thresholds and delays.
Usually electronically controlledsome models are
microprocessor controlled.
Often used for main power distribution in large
industrial plant, where the breakers are arranged in
draw-out enclosures for ease of maintenance.

MCB Selection
Overload which is intended to prevent the accidental overloading of the
cable in a no fault situation. The speed of the MCB tripping will vary with
the degree of the overload. This is usually achieved by the use of a
thermal device in the MCB.
The second characteristic is the magnetic fault protection, which is
intended to operate when the fault reaches a predetermined level and to
trip the MCB within one tenth of a second. The level of this magnetic trip
gives the MCB its type characteristic as follows:
Type

Tripping Current

Operating Time

Type B ( Domestic)
Type C ( Industrial)
Type D ( Capacitor)

3 To 5 time full load current


5 To 10 times full load current
10 To 20 times full load current

0.04 To 13 Sec
0.04 To 5 Sec
0.04 To 3 Sec

Fuse and MCB characteristics


The fuse and the MCB, even though their nominal
currents are similar, have very different properties.
For example, For 32Amp MCB and 30 Amp Fuse, to
be sure of tripping in 0.1 seconds, the MCB requires
a current of 128 amps, while the fuse requires 300
amps.
The fuse clearly requires more current to blow it in
that time, but notice how much bigger both these
currents are than the 30 amps marked current
rating.
Fuse require replacement after blowing but MCB
only switched on.

ACB
ACB

Cable Selection

Armoured Cables ( For Out door, under ground)


Unarmoured Cables ( for indoor but open in cable trays)
Submersible cables
Size of Cable ( as per load)
Insulation on cable ( PVC, XLPE)
Core 3 ( where neutral not required) or 3 cable ( where
neutral required)
3 core cable in HT, Motor, capacitor
3 Core in light load,

Insulation over cable


Poly Vinyl Chloride
Cross-Linked Polyethylene (XLPE)- Less
deformation below 100C, Lower in cost,
Lower dissipation factor, Lower dielectric
constant, Higher dielectric strength Physically
tougher, More resistant to chemicals, More oil
resistant

Colour Code for Cables


Single Phase System
Live
Red
Neutral
Black
Ground
Green

Three phase System


Red, Yellow, Blue
Black
Green

EARTHING

BY EARTHING (OR GROUNDING), WE


MEAN MAKING A PHYSICAL AND
ELECTRICAL CONNECTION TO THE
GENERAL MASS OF EARTH.

TYPES OF EARTHING

SYSTEM EARTHING
EQUIPMENT EARTHING
LIGHTNING PROTECTION EARTHING
STATIC EARTHING

SYSTEM EARTHING
SYSTEM EARTHING IS THE EARTHING
ASSOCIATED WITH THE CURRENT CARRYING
CONDUCTOR (USUALLY THE NEUTRAL POINT OF
THE TRANSFORMER OR GENERATOR) AND IS
NORMALLY ESSENTIAL FOR THE SECURITY OF
THE SYSTEM.
(This is covered by IS 3043:1987
Code of Practice for Earthing)

EQUIPMENT EARTHING
EQUIPMENT EARTHING IS THE EARTHING
ASSOCIATED WITH NON CURRENT
CARRYING METAL WORK AND IS
ESSENTIAL TO THE SAFETY OF HUMAN
LIFE, ANIMALS & PROPERTY.
(This is covered by IS 3043:1987
Code of Practice for Earthing)

LIGHTNING PROTECTION EARTHING


LIGHTNING PROTECTION EARTHING IS
CONCERNED WITH THE CONDUCTION OF CURRENT
DISCHARGES IN ATMOSPHERE ORIGINATING IN
CLOUD FORMATIONS TO EARTH AND IS ESSENTIAL
FOR THE PROTECTION OF BUILDINGS,
TRANSMISSION LINES AND ELECTRICAL
EQUIPMENT.
(This is covered by IS 2309:1989
Protection of buildings and allied structures
against lightning Code of Practice)

SYSTEM EARTHING
WHY ?
 GREATER SERVICE CONTINUITY
 REDUCTION IN OCCURRENCES OF
MULTIPLE FAULTS TO GROUND
 FEWER ARCING FAULT BURNDOWNS
 EASIER LOCATION OF FAULTS
 GREATER SAFETY
 POSSIBLE SAVING IN COST

EQUIPMENT EARTHING
WHY ?
1. FREEDOM FROM DANGEROUS ELECTRIC
SHOCK HAZARDS
2. REDUCTION IN FIRE HAZARDS
3. PRESERVATION OF SYSTEM
PERFORMANCE

REDUCTION IN SHOCK HAZARDS


CASE 1 : NO EQUIPMENT EARTHING

LOAD
SOURCE

SYSTEM
EARTHING

REDUCTION IN SHOCK HAZARDS


CASE 3 : EQUIPMENT EARTHING WITH PE CONDUCTOR

LOAD
SOURCE

SYSTEM
EARTHING

EQUIPMENT
EARTHING

Difference between Pipe and Plate Earthing

Plate earthing costly but reliable.


Plate earhing is more efficient.
Less maintenance cost.
Easy to maintain resistance value.

Standard Pipe & Plate Type Earthing Design for the


11 Kv.
Kv. System Equipments, Distribution Transformer
Centers,, L.T. Distribution System Equipments
Centers
Design Details :
1. Earthing Pit : Size 1000 X 1000 X 1800 mm
Depth.M.S. / C.I. Plate : 500 X 500 X 8 mm
Thick.
2. Electrode Assembly : 40 mm GI / CI
Perforated pipe duly fitted or welded with base
plate and 50 X 6 mm flat termination taken on
top for equipment earthing as shown in drawing.

Standard Pipe & Plate Type Earthing Design for the 11


Kv. System Equipments, Distribution Transformer
Centers, L.T. Distribution System Equipments
4. Mixture - I : Homogeneous mixture of black
soft soil 0.3 CMT. approx.
5. Mixture - II : Homogeneous mixture of
common salt 25 Kgs. + wood charcoal pieces
25 Kgs. + Black soft soil 1 CMT. Approx.
6. Crushed Rock pieces Gravel Size 50 X 35 mm
0.1 CMT. Approx.
7. Arrangement for earthing lead terminations
from equipment body, and connection for
main earthing Grid.

Typical arrangement for Pipe


electrode earthing pit (Bore Type)
Design Details :
1. 75 mm thick RCC Cover.
2. 300 mm 6000 mm deep (Approx. 20 ft.)
bore in the earth.
3. 65 mm 6000 mm long (Approx 20 ft.) G.I.
pipe electrode. Forged at the top up to 75 mm
length and 12 mm hole provided for taking
earthing connection.
4. A homogeneous mixture of 50 kgs. wooden
coal pieces + 50 kgs. common salt
5. Water pouring purpose at the time of routine
maintenance

No. of earthing Required

Equipment
GO Switch
HT metering panel
Transformer
LT Panel
Electric Motor

Pipe
1
1
1

Plate
2
1
2
2
-

HP of Motor
HP of Motor= QH/4500/efficiency
Q= Discharge in LPM
H= Head of pump in meters
Efficiency varies from 65% to 85%

Motor Start Theory

ME00107A

Type of Insulation and Enclosures for electric


motors
Insulation Class of winding wire
Class Y- 90C, Class A- 105C, Class E- 120C, Class B- 130C,
Class H- 180C
To be used as application.

Enclosures
Screen Protected, screen protected drip proof, Splash proof,
Totally enclosed fan cooled, Totally enclosed and separately
air cooled, totally enclosed air circuit motor, direct ventilated
motor

Detail of TRANSFORMER and its Accessories


1
2
3

Descripition of Transformer
KVA of Transformer
KW of TR. at P.F -0.8
Full load current of TR.

Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in mm2
5 Size of cable 3 1/2 core
L.T. side(Aluminium ) in mm2
Metering panel with C.T./P.T
6 unit
Trivector meter as per TR.
7 rating
HT VCB/SF-6 panel with HT
8 metering
As per TR. Rating.
G.O.switch
with
all
9 accessories I/C D.O.fuse ,
lighting arrestor and stay wire
set, earthing etc.
HT current of TR.- on HT side
10 (Amp.)
11 Impedance %
Capocitor for TR (KVAR) only
12 for TR losses

Capacity
100
75
150

150
125
200

200
175
250

250
200
347

35

35

35

35

1x185 sqmm

1x240 sqmm

1x240 sqmm

2X185 sqmm

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

15/5 A/110 V

NA

NA

NA

NA

Required

Required

Required

Required

5.24
4

7.88
4

10.5
4.75

13.33
4.75

10

1
2
3

Descripition of Transformer
KVA of Transformer
KW of TR. at P.F -0.8
Full load current of TR.

Capacity
315
252
433

Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in mm2
35
5 Size of cable 3 1/2 core
L.T. side(Aluminium ) in mm2 2X240 sqmm
Metering panel with C.T./P.T
6 unit
20/5 A/110 V
Trivector meter as per TR.
7 rating
20/5 A/110 V
HT VCB/SF-6 panel with HT
8 metering
As per TR. Rating.
Required
G.O.switch
with
all
9 accessories I/C D.O.fuse ,
lighting arrestor and stay wire
set, earthing etc.
Required
HT current of TR.- on HT side
10 (Amp.)
16.8
11 Impedance %
4.75
Capocitor for TR (KVAR) only
12 for TR losses
12.5

400
320
530

500
400
687

630
604
866

50

50

50

2X240 sqmm

3X240 sqmm

3X240 sqmm

25/5 A/110 V

30/5 A/110 V

50/5 A/110 V

25/5 A/110 V

30/5 A/110 V

50/5 A/110 V

Required

Required

Required

Required

Required

Required

21.33
4.75

26.66
4.75

40.26
5

20

25

30

Descripition of
Transformer
1 KVA of Transformer
2 KW of TR. at P.F -0.8
3 Full load current of TR.
Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in
mm2

800
640
1100

1000
800
1375

Capacity
1250
1000
1718

1600
1280
2199

2000
1600
2740

70
70
95
125
125
Bus duct 1200 Bus duct 1600 Bus duct 2000 Bus duct 2500 Bus duct 4000
A
A
A
A
A

5 Size of cable 3 1/2 core


L.T. side(Aluminium ) in
3X400 sqmm 4X400 sqmm
N/A
N/A
N/A
mm2
Metering panel with C.T./P.T
6 unit
50/5 A/110 V 60/5 A/110 V 70/5 A/110 V 100/5 A/110 V 125/5 A/110 V
Trivector meter as per TR.
7 rating
50/5 A/110 V 60/5 A/110 V 70/5 A/110 V 100/5 A/110 V 125/5 A/110 V
HT VCB/SF-6 panel with
8 HT metering
As per TR. Rating.
Required
Required
Required
Required
Required
G.O.switch
with
all
9 accessories I/C D.O.fuse ,
lighting arrestor and stay
wire set, earthing etc.
Required
Required
Required
Required
Required
HT current of TR.- on HT
10 side (Amp.)
42.66
53.33
66.66
85.33
106.66
11 Impedance %
5
5
5
6.25
6.25
Capocitor for TR (KVAR)
12 only for TR losses
35
50
50
75
100

NOTE :a)

HT VCB / SF-6 as incomer of Transformer on HT side ( and required as per


Electricity Board norms )

b)

CT ratio 50/25/5 A ( if load vary from 25 amp. To 50 amp after expansion on HT


side of Transformer

c)

CT ratio - 30/30/5 amp. ( separate for metering and separate for protection.)

d)

Calculation of HT current of Transformer = Kva / 11 kv / 1.73.

e)

PT- 110 /220 volt AC.( as per requirement )

Detail of D.G.Sets with details

KVA

7.5

10

15

15

20

25

30

30

40

50

KW

12

12

16

20

24

24

32

40

62.5 62.5
50

50

AMPS 6.95 10.4 13.9 20.8 20.8 27.8 34.75 41.7 41.7 55.6 69.5 86.9 86.9

BHP

10

12

18.7

KVA

100

125

160

KW

80

100

128

AMPS

139

BHP

127

173.7 222.4

154

205

19

65

76

83

75

82.5

60

66

104

114.6

105

105

28

32

38

43

50.5

180

200

250

320

380

437

500

625

750

1000

144

160

200

256

304

350

400

500

600

800

250

278

348

445

528

608

614

868.8

1043

1390

231

255

306

380

450

530

614

750

890

1180

Detail of DIRECT ON LINE ( DOL ) starter with all type of possible


accessories

S.No.
1
2
3

4
5
6
7
8
9
10
11

DESCREPTION OF MOTOR
HP-3Phase 415 V AC
0.5
0.75
1
KW of Motor
0.37
0.55
0.75
Full load current of Motor
in amp.
1.2
1.6
1.8
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
MPCB as incomer. In amp.
MPCB
MPCB
MPCB
1-1.6 A
1-1.6 A
1.6-2.5 A
Contactor rating in amp.
1x9 amp
1x9 amp
1x9 amp
Single phase preventor 415 v
AC.
A/P/R
A/P/R
A/P/R
Control MCB SP.( single pole
)
6 amp SP
6 amp SP
6 amp SP
Push Botton ( START &
STOP ) 1 NO+1 NC
2-Nos
2-Nos
2-Nos
On Indication ( LED 220 V
AC )
1-Nos
1-Nos
1-Nos
Cable for supply side 3 1/2
core COPPER
1.5 sq mm
1.5 sq mm
1.5 sq mm
Cable for Motor side 3-core
COPPER.
1.5 sq mm
1.5 sq mm
1.5 sq mm

1.5
1.1
2.6
MPCB
2.5-4 A
1x9 amp
A/P/R
6 amp SP
2-Nos
1-Nos
1.5 sq mm
1.5 sq mm

Detail of DIRECT ON LINE ( DOL ) starter with all type of possible


accessories

S.No DESCREPTION OF
. MOTOR
1 HP-3Phase 415 V AC
2
3
5
7.5
2 KW of Motor
1.5
2.25
3.75
5.5
3 Full load current of
Motor in amp.
3.5
5
7.5
11
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
4 MPCB as incomer. In
amp.
MPCB
MPCB
MPCB
MPCB
2.5-4 A
4-6.3 A
6-10 A
9-15 A
5 Contactor rating in amp.
1x9 amp
1x9 amp
1x12 amp
1x18 amp
6 Single phase preventor
415 v AC.
A/P/R
A/P/R
A/P/R
A/P/R
7 Control MCB SP.( single
pole )
6 amp SP
6 amp SP
6 amp SP
6 amp SP
8 Push Botton ( START &
STOP ) 1 NO+1 NC
2-Nos
2-Nos
2-Nos
2-Nos
9 On Indication ( LED 220
V AC )
1-Nos
1-Nos
1-Nos
1-Nos
10 Cable for supply side 3
1/2 core COPPER
2.5 sq mm
2.5 sq mm
2.5 sq mm
4 sq mm
11 Cable for Motor side 3core COPPER.
2.5 sq mm
2.5 sq mm
2.5 sq mm
4 sq mm

Single phase preventor 415 v AC = A/P/R ( AS PER REQUIRMENT )

10
7.5
14

MPCB
9-15 A
1x25 amp
A/P/R
6 amp SP
2-Nos
1-Nos
4 sq mm
4 sq mm

Detail of STAR/DELTA starter with all type of possible accessories


DESCREPTION OF
S.No. MOTOR
1 HP-3Phase 415 V AC
15
20
25
2 KW of Motor
11
15
18.5
Full load Line current of
3 Motor in amp.
21
28
35
Phase current of Motor in
4 amp.
12
16
20
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
MPCB/MCCB as incomer.
5 In amp.
MPCB
MPCB
MCCB
19-25 A
24-32 A
63 A
6 Contactor rating in amp.
3x25 amp
3x32 amp
3x32 amp
7 Motor protection relay -MPR Not-req
Not-req
MPR
( 2.5-5 A )
8 Timers
0-60 sec
0-60 sec
0-60 sec
Single phase preventor 415
9 v AC.
A/P/R
A/P/R
A/P/R
10 Control MCB SP.
6 amp SP
6 amp SP
6 amp SP
11 Amp. Meter
0-50 amp
0-50 amp
0-50 amp
12 CT,s ( -/5 amp )
50/5 amp
50/5 amp
50/5 amp
Cable for supply side 3 1/2
13 core ALUMINIUM
10 sq mm
10 sq mm
16 sq mm
Cable for Motor side 3-core
14 ALUMINIUM.
2x6 sq mm 2x6 sq mm
2x10 sq mm

30
22

35
26

40

47

23

27

MCCB
100 A
3x40 amp
MPR
( 2.5-5 A )
0-60 sec

MCCB
100 A
3x40 amp
MPR
( 2.5-5 A )
0-60 sec

A/P/R
6 amp SP
0-50 amp
50/5 amp

A/P/R
6 amp SP
0-75 amp
75/5 amp

16 sq mm

25 sq mm

2x10 sq mm

2x16 sq mm

Detail of STAR/DELTA starter with all type of possible accessories


DESCREPTION OF
S.No. MOTOR
1 HP-3Phase 415 V AC
2 KW of Motor
Full load line current of
3 Motor in amp.
Phase current of Motor in
4 amp.

5
6
7
8
9
10
11
12
13
14

40
30

50
37

60
45

75
56

90
67.5

55

66

80

100

120

30

35

45

57

69

MCCB
160 A
3x80 amp
MPR
( 2.5-5 A )
0-60 sec

MCCB
200 A
3x110amp
MPR
( 2.5-5 A )
0-60 sec

A/P/R
6 amp SP
0-150 amp
150/5 amp

A/P/R
6 amp SP
0-150 amp
150/5 amp

70 sq mm

70 sq mm

2x25 sq mm

2x50 sq mm

EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR


MPCB/MCCB as incomer.
In amp.
MCCB
MCCB
MCCB
100 A
100 A
125 A
Contactor rating in amp.
3x40 amp
3x50 amp
3x70 amp
Motor protection relay -MPR
MPR
MPR
MPR
( 2.5-5 A )
( 2.5-5 A )
( 2.5-5 A )
Timers
0-60 sec
0-60 sec
0-60 sec
Single phase preventor 415
v AC.
A/P/R
A/P/R
A/P/R
Control MCB SP.
6 amp SP
6 amp SP
6 amp SP
Amp. Meter
0-75 amp 0-100 amp
0-100 amp
CT,s ( -/5 amp )
75/5 amp 100/5 amp
100/5 amp
Cable for supply side 3 1/2
core ALUMINIUM
25 sq mm
35 sq mm
50 sq mm
Cable for Motor side 3-core
ALUMINIUM.
2x16 sq mm 2x16 sq mm 2x25 sq mm

Detail of STAR/DELTA starter with all type of possible accessories


DISCREPTION OF
S.No. MOTOR
1 HP-3Phase 415 V AC
100
125
150
175
2 KW of Motor
75
90
112
132
Full load line current
3 of Motor in amp.
135
165
200
230
Phase current of Motor
4 in amp.
78
95
115
133
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
MPCB/MCCB as
5 incomer. In amp.
MCCB
MCCB
MCCB
MCCB
250 A
250 A
400 A
400 A
6 Contactor rating in amp. 3x110amp 3x140amp 3x140amp
3x200amp
Motor protection relay 7 MPR
MPR
MPR
MPR
MPR
( 2.5-5 A ) ( 2.5-5 A )
( 2.5-5 A )
( 2.5-5 A )
8 Timers
0-60 sec 0-60 sec
0-60 sec
0-60 sec
Single phase preventor
9 415 v AC.
A/P/R
A/P/R
A/P/R
A/P/R
10 Control MCB SP.
6 amp SP 6 amp SP
6 amp SP
6 amp SP
11 Amp. Meter
0-150 amp 0-250 amp 0-250 amp
0-250 amp
12 CT,s ( -/5 amp )
150/5 amp 250/5 amp 250/5 amp
250/5 amp
Cable for supply side 3
13 1/2 core ALUMINIUM
95 sq mm 120 sq mm 240 sq mm
240 sq mm
Cable for Motor side 32x50 sq
2x70 sq
14 core ALUMINIUM.
mm
mm
2x95 sq mm 2x95 sq mm

200
150

250
187

275

323

159

185

MCCB
400 A
3x200amp

MCCB
630A
3x265amp

MPR
( 2.5-5 A )
0-60 sec

MPR
( 2.5-5 A )
0-60 sec

A/P/R
6 amp SP
0-400 amp
400/5 amp
2x120 sq
mm
2x120 sq
mm

A/P/R
6 amp SP
0-400 amp
400/5 amp
2x150 sq
mm
2x185 sq
mm

IMPORTANT - ALL THE POWER CONNECTION OF STARTER IN SIDE THE PANEL WITH SOLID BUS BARS 50 HP AND ABOVE.

VIDEO ON STAR - DELTA STARTER

500

160KVA

Power of the transformer

250KVA

KVA
48.0 KA =Icc downstream
the transformer

400KVA
630KVA
Maine line (Alu or Copper)
800KVA
a=alu (cu by default)

Lenght

Cross section

800

mm

1000KVA
1250KVA
1600KVA
45.3KA
2000KVA
2500KVA
Secundary level (Alu or Copper)
a=alu (cu by default)
Lenght
Cross section

third level (Alu or Copper)


a=alu (cu by default)
Lenght
Cross section

a
10
240
33.1

m
mm
KA

20
1.5

m
mm

Icc3

0.75

KA

Icc1

0.60

KA

Thank You