< 50KW.
HT
> 50KW.
Independent feeders 11KV.
High Voltage Transmission/ Distribution is Preferred
because of Low losses & Reduced size of Conductors
during transmission.
The power is transmitted at high voltage and low
current.
The heat generated during transmission is
proportional to current transmission.
Power (KW/KVA/HP)
Rated Current.
System Voltage
Breaking Capacity
Making Capacity
Category A or B
Suitability to site Condition (Indian
Condition)
Maintenance Definitions
Effect of harmonics
Calculation Formulas
HVPN Supply
GO Switch
HT Metering
VCB
Transformer
LT Panel ( Power control centre, Power factor panel,
AMF)
Distribution Panel
Sub Distribution panel
Selection Of GO Switch
Gang Operated Switch
Comprises of :- Lightning
Arresters, GO (gang
operated) switch, Drop off
Fuse(DO), Plate Earthings
two Nos.
for LA (lightening arrestor)
& GO switch.
Selected at 11KV Only.
Selection of CT & PT
CT (Current Transformer /5A)
Selected as per the full load
current of Transformer.
PT ( Potential Transformer) As per
the system
Voltage.(11Kv/220v/110v/24V)AC
Calculation of HT Current for CT
KVA/11KV/1.732
Example:- Transformer rating ( HT
current for CT/PT selection)
500Kva/11KV/1.732 = 26.24
Tri vector Meter selected as per
HT Current.
VCB Panel
Vacuum Circuit Breaker
For Switching carrying
Normal Current and
Breaking abnormal current
at High Voltage.
630A ( Short circuit current)
and Above.
Over Load, Short Circuit &
E/F protections.
Measurement of current,
Voltage etc.
Transformer
11KV( input)/433V ( Output)
Selection of Transformer as
per Total load.
Buckle relay and winding
temperature for safety of
Transfer. These help to trip
VCB.
Silica gel to check moisture
content. If blue- Ok, If white
or light pink- replace it.
LT Panels
PCC--- Power Control
Center.
MCC- Motor Control
Center.
AMF- Auto Mains Failure
Panel
APFC- Automatic Power
Factor Correction
Distribution Panels.
LOAD - 900 KW
EXISTING P.F. (COS 1)- 0.6
DESIRED P.F. (COS 2) - 0.92
COS . =
KVA
kW
kVA
kW
cos .
KVA 1 =
KVA2 =
.
KW
Reduction in KVA
1500 - 978 = 522
REDUCTION IN LINE
CURRENT
KVA1 - 1500
KVA
KVA2 - 978
I1
Reduction in Current
2087 - 1361 = 726
I2
3 V I
1000
KVA x 1000
3 x 415
1500 x 1000
3 x 415
2087 Amp
978 x 1000
3 x 415
1361 Amp
Selection of Capacitor
Configuration of capacitors
1. Individual Compensation
2. Group Compensation
3. Central Compensation
KVAR required ( Capacitor)
= KVA X (1- PF(E)) - KVA X (1- PF(T))
Existing Power factor from HVPN= PF(E) i.e. 0.6 to 0.75
Target Power factor for system = PF(T) i.e. 0.99
Direct on Line
START
Line Contactor
Overload
% VOLTS
100
80
60
40
20
0
Run
Start
TIME
Run Contactor
START
Line Contactor
Resistors
Primary
Resistance
Overload
% VOLTS
100
80
60
40
20
0
Run
Start
TIME
Autotransformer
Star Point
Contactor
START
Transformer
Contactor
% VOLTS
100
80
60
40
20
0
Line Contactor
Overload
Run
Start
TIME
START
Star Point
Contactor
Star Delta
Delta
Contactor
% VOLTS
100
80
60
40
20
0
Line Contactor
Overload
Run
Start
TIME
Soft Starting
START
% VOLTS
100
80
60
40
20
0
Run
Start
TIME
Basics of AC Drives
Frequency controls Motor
IMSspeed
2 Product Familiarisation
Supply Voltage controls Motor Torque
Supply Voltage is varied in proportion to
supply frequency so as to keep torque
constant
TERMINATION WITH
BUSBAR/LINK
DONT
DO
DONT
DO
DONT
DO
DONT
DO
TERMINATION WITH
LUGS
DONT
DO
DONT
DO
DONT
DO
DONT
DO
MCB Selection
Overload which is intended to prevent the accidental overloading of the
cable in a no fault situation. The speed of the MCB tripping will vary with
the degree of the overload. This is usually achieved by the use of a
thermal device in the MCB.
The second characteristic is the magnetic fault protection, which is
intended to operate when the fault reaches a predetermined level and to
trip the MCB within one tenth of a second. The level of this magnetic trip
gives the MCB its type characteristic as follows:
Type
Tripping Current
Operating Time
Type B ( Domestic)
Type C ( Industrial)
Type D ( Capacitor)
0.04 To 13 Sec
0.04 To 5 Sec
0.04 To 3 Sec
ACB
ACB
Cable Selection
EARTHING
TYPES OF EARTHING
SYSTEM EARTHING
EQUIPMENT EARTHING
LIGHTNING PROTECTION EARTHING
STATIC EARTHING
SYSTEM EARTHING
SYSTEM EARTHING IS THE EARTHING
ASSOCIATED WITH THE CURRENT CARRYING
CONDUCTOR (USUALLY THE NEUTRAL POINT OF
THE TRANSFORMER OR GENERATOR) AND IS
NORMALLY ESSENTIAL FOR THE SECURITY OF
THE SYSTEM.
(This is covered by IS 3043:1987
Code of Practice for Earthing)
EQUIPMENT EARTHING
EQUIPMENT EARTHING IS THE EARTHING
ASSOCIATED WITH NON CURRENT
CARRYING METAL WORK AND IS
ESSENTIAL TO THE SAFETY OF HUMAN
LIFE, ANIMALS & PROPERTY.
(This is covered by IS 3043:1987
Code of Practice for Earthing)
SYSTEM EARTHING
WHY ?
GREATER SERVICE CONTINUITY
REDUCTION IN OCCURRENCES OF
MULTIPLE FAULTS TO GROUND
FEWER ARCING FAULT BURNDOWNS
EASIER LOCATION OF FAULTS
GREATER SAFETY
POSSIBLE SAVING IN COST
EQUIPMENT EARTHING
WHY ?
1. FREEDOM FROM DANGEROUS ELECTRIC
SHOCK HAZARDS
2. REDUCTION IN FIRE HAZARDS
3. PRESERVATION OF SYSTEM
PERFORMANCE
LOAD
SOURCE
SYSTEM
EARTHING
LOAD
SOURCE
SYSTEM
EARTHING
EQUIPMENT
EARTHING
Equipment
GO Switch
HT metering panel
Transformer
LT Panel
Electric Motor
Pipe
1
1
1
Plate
2
1
2
2
-
HP of Motor
HP of Motor= QH/4500/efficiency
Q= Discharge in LPM
H= Head of pump in meters
Efficiency varies from 65% to 85%
ME00107A
Enclosures
Screen Protected, screen protected drip proof, Splash proof,
Totally enclosed fan cooled, Totally enclosed and separately
air cooled, totally enclosed air circuit motor, direct ventilated
motor
Descripition of Transformer
KVA of Transformer
KW of TR. at P.F -0.8
Full load current of TR.
Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in mm2
5 Size of cable 3 1/2 core
L.T. side(Aluminium ) in mm2
Metering panel with C.T./P.T
6 unit
Trivector meter as per TR.
7 rating
HT VCB/SF-6 panel with HT
8 metering
As per TR. Rating.
G.O.switch
with
all
9 accessories I/C D.O.fuse ,
lighting arrestor and stay wire
set, earthing etc.
HT current of TR.- on HT side
10 (Amp.)
11 Impedance %
Capocitor for TR (KVAR) only
12 for TR losses
Capacity
100
75
150
150
125
200
200
175
250
250
200
347
35
35
35
35
1x185 sqmm
1x240 sqmm
1x240 sqmm
2X185 sqmm
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
15/5 A/110 V
NA
NA
NA
NA
Required
Required
Required
Required
5.24
4
7.88
4
10.5
4.75
13.33
4.75
10
1
2
3
Descripition of Transformer
KVA of Transformer
KW of TR. at P.F -0.8
Full load current of TR.
Capacity
315
252
433
Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in mm2
35
5 Size of cable 3 1/2 core
L.T. side(Aluminium ) in mm2 2X240 sqmm
Metering panel with C.T./P.T
6 unit
20/5 A/110 V
Trivector meter as per TR.
7 rating
20/5 A/110 V
HT VCB/SF-6 panel with HT
8 metering
As per TR. Rating.
Required
G.O.switch
with
all
9 accessories I/C D.O.fuse ,
lighting arrestor and stay wire
set, earthing etc.
Required
HT current of TR.- on HT side
10 (Amp.)
16.8
11 Impedance %
4.75
Capocitor for TR (KVAR) only
12 for TR losses
12.5
400
320
530
500
400
687
630
604
866
50
50
50
2X240 sqmm
3X240 sqmm
3X240 sqmm
25/5 A/110 V
30/5 A/110 V
50/5 A/110 V
25/5 A/110 V
30/5 A/110 V
50/5 A/110 V
Required
Required
Required
Required
Required
Required
21.33
4.75
26.66
4.75
40.26
5
20
25
30
Descripition of
Transformer
1 KVA of Transformer
2 KW of TR. at P.F -0.8
3 Full load current of TR.
Details of accessories to
run the transformer
4 Size of cable 3-core
H.T.side ( Aluminium ) in
mm2
800
640
1100
1000
800
1375
Capacity
1250
1000
1718
1600
1280
2199
2000
1600
2740
70
70
95
125
125
Bus duct 1200 Bus duct 1600 Bus duct 2000 Bus duct 2500 Bus duct 4000
A
A
A
A
A
NOTE :a)
b)
c)
CT ratio - 30/30/5 amp. ( separate for metering and separate for protection.)
d)
e)
KVA
7.5
10
15
15
20
25
30
30
40
50
KW
12
12
16
20
24
24
32
40
62.5 62.5
50
50
AMPS 6.95 10.4 13.9 20.8 20.8 27.8 34.75 41.7 41.7 55.6 69.5 86.9 86.9
BHP
10
12
18.7
KVA
100
125
160
KW
80
100
128
AMPS
139
BHP
127
173.7 222.4
154
205
19
65
76
83
75
82.5
60
66
104
114.6
105
105
28
32
38
43
50.5
180
200
250
320
380
437
500
625
750
1000
144
160
200
256
304
350
400
500
600
800
250
278
348
445
528
608
614
868.8
1043
1390
231
255
306
380
450
530
614
750
890
1180
S.No.
1
2
3
4
5
6
7
8
9
10
11
DESCREPTION OF MOTOR
HP-3Phase 415 V AC
0.5
0.75
1
KW of Motor
0.37
0.55
0.75
Full load current of Motor
in amp.
1.2
1.6
1.8
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
MPCB as incomer. In amp.
MPCB
MPCB
MPCB
1-1.6 A
1-1.6 A
1.6-2.5 A
Contactor rating in amp.
1x9 amp
1x9 amp
1x9 amp
Single phase preventor 415 v
AC.
A/P/R
A/P/R
A/P/R
Control MCB SP.( single pole
)
6 amp SP
6 amp SP
6 amp SP
Push Botton ( START &
STOP ) 1 NO+1 NC
2-Nos
2-Nos
2-Nos
On Indication ( LED 220 V
AC )
1-Nos
1-Nos
1-Nos
Cable for supply side 3 1/2
core COPPER
1.5 sq mm
1.5 sq mm
1.5 sq mm
Cable for Motor side 3-core
COPPER.
1.5 sq mm
1.5 sq mm
1.5 sq mm
1.5
1.1
2.6
MPCB
2.5-4 A
1x9 amp
A/P/R
6 amp SP
2-Nos
1-Nos
1.5 sq mm
1.5 sq mm
S.No DESCREPTION OF
. MOTOR
1 HP-3Phase 415 V AC
2
3
5
7.5
2 KW of Motor
1.5
2.25
3.75
5.5
3 Full load current of
Motor in amp.
3.5
5
7.5
11
EQUIPMENT TO START THE MOTOR BELOW FOR EACH MOTOR
4 MPCB as incomer. In
amp.
MPCB
MPCB
MPCB
MPCB
2.5-4 A
4-6.3 A
6-10 A
9-15 A
5 Contactor rating in amp.
1x9 amp
1x9 amp
1x12 amp
1x18 amp
6 Single phase preventor
415 v AC.
A/P/R
A/P/R
A/P/R
A/P/R
7 Control MCB SP.( single
pole )
6 amp SP
6 amp SP
6 amp SP
6 amp SP
8 Push Botton ( START &
STOP ) 1 NO+1 NC
2-Nos
2-Nos
2-Nos
2-Nos
9 On Indication ( LED 220
V AC )
1-Nos
1-Nos
1-Nos
1-Nos
10 Cable for supply side 3
1/2 core COPPER
2.5 sq mm
2.5 sq mm
2.5 sq mm
4 sq mm
11 Cable for Motor side 3core COPPER.
2.5 sq mm
2.5 sq mm
2.5 sq mm
4 sq mm
10
7.5
14
MPCB
9-15 A
1x25 amp
A/P/R
6 amp SP
2-Nos
1-Nos
4 sq mm
4 sq mm
30
22
35
26
40
47
23
27
MCCB
100 A
3x40 amp
MPR
( 2.5-5 A )
0-60 sec
MCCB
100 A
3x40 amp
MPR
( 2.5-5 A )
0-60 sec
A/P/R
6 amp SP
0-50 amp
50/5 amp
A/P/R
6 amp SP
0-75 amp
75/5 amp
16 sq mm
25 sq mm
2x10 sq mm
2x16 sq mm
5
6
7
8
9
10
11
12
13
14
40
30
50
37
60
45
75
56
90
67.5
55
66
80
100
120
30
35
45
57
69
MCCB
160 A
3x80 amp
MPR
( 2.5-5 A )
0-60 sec
MCCB
200 A
3x110amp
MPR
( 2.5-5 A )
0-60 sec
A/P/R
6 amp SP
0-150 amp
150/5 amp
A/P/R
6 amp SP
0-150 amp
150/5 amp
70 sq mm
70 sq mm
2x25 sq mm
2x50 sq mm
200
150
250
187
275
323
159
185
MCCB
400 A
3x200amp
MCCB
630A
3x265amp
MPR
( 2.5-5 A )
0-60 sec
MPR
( 2.5-5 A )
0-60 sec
A/P/R
6 amp SP
0-400 amp
400/5 amp
2x120 sq
mm
2x120 sq
mm
A/P/R
6 amp SP
0-400 amp
400/5 amp
2x150 sq
mm
2x185 sq
mm
IMPORTANT - ALL THE POWER CONNECTION OF STARTER IN SIDE THE PANEL WITH SOLID BUS BARS 50 HP AND ABOVE.
500
160KVA
250KVA
KVA
48.0 KA =Icc downstream
the transformer
400KVA
630KVA
Maine line (Alu or Copper)
800KVA
a=alu (cu by default)
Lenght
Cross section
800
mm
1000KVA
1250KVA
1600KVA
45.3KA
2000KVA
2500KVA
Secundary level (Alu or Copper)
a=alu (cu by default)
Lenght
Cross section
a
10
240
33.1
m
mm
KA
20
1.5
m
mm
Icc3
0.75
KA
Icc1
0.60
KA