Sei sulla pagina 1di 56

MechaTronics Co.

External static pressure Calculation


AHU-B5_G01
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

DIA.

FT.

FT.

15.0

1/26 of

Sheet
Circ:

27

MA/CAL/1

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

20.0

26.6

991

0.04

0.012

AC SUPPLY DUCT
1

4,475

1000

450

719

2.0

6.6

4,475

1000

450

719

3.0

9.8

30.0

5.0

35.0

44.8

991

0.04

0.020

3,580

900

400

643

2.2

7.2

30.0

5.0

35.0

42.2

993

0.05

0.021

3,133

900

350

597

4.0

13.1

30.0

5.0

35.0

48.1

1006

0.06

0.027

2,238

700

350

533

4.0

13.1

30.0

5.0

35.0

48.1

902

0.05

0.026

1,341

600

250

414

3.6

11.8

30.0

5.0

35.0

46.8

898

0.07

0.034

894

500

200

337

2.2

7.2

5.0

20.0

27.2

902

0.09

0.025

447

500

150

287

4.2

13.8

5.0

5.0

18.8

623

0.06

0.011

15.0

AC SUPPLY DUCTS & FITTINGS

0.176

AC RETURN DUCT
8

4,475

650

550

653

4.0

13.1

15.0

10.0

25.0

38.1

1202

AC RETURN DUCTS & FITTINGS

0.07

0.027
0.027

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.176

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.027

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.128

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.113
1.241

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-B5_F01
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

2/26 of

Sheet
Circ:

27

MA/CAL/2

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

10.0

40.0

48.5

1306

0.14

0.069

10.0

25.0

36.5

1311

0.19

0.068

AC SUPPLY DUCT
1

1,950

600

250

414

2.6

8.5

30.0

1,300

500

200

337

3.5

11.5

1,300

500

200

337

3.2

10.5

30.0

10.0

40.0

50.5

1311

0.19

0.093

650

500

150

287

6.0

19.7

30.0

10.0

40.0

59.7

905

0.11

0.069

15.0

AC SUPPLY DUCTS & FITTINGS

0.299

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.299

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.000

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.974

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.097
1.071

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-B6_G01 &AHU-B6_G02
Project
Al-Hazm Mall
Designed b

Qty.(2)

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

30.0

DIA.

FT.

3/27 of

Sheet
Circ:

27

MA/CAL/3

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

15.0

5.0

50.0

60.8

1299

0.06

0.036

15.0

5.0

20.0

30.8

1082

0.04

0.013

AC SUPPLY DUCT
1

8,000

1000

600

840

3.3

10.8

6,660

1000

600

840

3.3

10.8

6,216

1000

500

762

2.8

9.0

10.0

10.0

19.0

1228

0.06

0.012

5,772

950

500

744

2.0

6.6

5.0

5.0

11.6

1195

0.06

0.007

5,328

850

500

706

2.0

6.6

5.0

5.0

11.6

1223

0.07

0.008

4,884

800

500

687

2.0

6.6

5.0

5.0

11.6

1187

0.06

0.007

4,440

750

500

666

2.0

6.6

5.0

5.0

11.6

1147

0.06

0.007

3,996

750

450

630

2.0

6.6

5.0

5.0

11.6

1154

0.07

0.008

3,552

750

400

592

2.0

6.6

5.0

5.0

11.6

1163

0.07

0.009

10

3,108

700

400

573

1.0

3.3

5.0

5.0

8.3

1085

0.07

0.006

11

2,664

650

400

553

1.0

3.3

5.0

20.0

23.3

997

0.06

0.014

12

2,442

600

400

533

2.6

8.4

5.0

5.0

13.4

986

0.06

0.008

13

2,220

550

400

511

1.0

3.3

5.0

5.0

8.3

974

0.25

0.021

1,998

550

350

477

1.0

3.3

5.0

5.0

8.3

1008

0.08

0.006

1,554

500

350

455

1.0

3.3

5.0

5.0

8.3

858

0.06

0.005

1,332

450

350

433

1.0

3.3

5.0

5.0

8.3

814

0.06

0.005

1,110

350

350

383

1.0

3.3

5.0

5.0

8.3

869

0.07

0.006

888

350

300

354

1.0

3.3

5.0

5.0

8.3

812

0.07

0.006

666

300

300

328

1.0

3.3

5.0

5.0

8.3

710

0.06

0.005

10

444

200

300

266

1.0

3.3

5.0

5.0

8.3

717

0.08

0.007

11

222

150

300

229

1.0

3.3

5.0

20.0

23.3

487

0.05

0.011

15.0

15.0

AC SUPPLY DUCTS & FITTINGS

0.171

AC FRESH DUCT
11

250

350

350

383

1.0

3.3

5.0

5.0

8.3

196

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.171

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.097

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.110
1.206

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation


AHU-B6_F01,F02,F03 & AHU-B6_G03,G04,G05 HVAC
Project
Project No.
Al-Hazm Mall
Designed b

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

4/27 of

Sheet
Circ:

27

MA/CAL/4

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,000

700

300

490

2.3

7.5

10.0

10.0

17.5

954

0.07

0.012

1,000

550

350

477

3.4

11.0

5.0

5.0

16.0

504

0.02

0.003

AC SUPPLY DUCTS & FITTINGS

0.015

AC FRESH AIR DUCT


3

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.015

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.940

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.094
1.034

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-B6_R01 & AHU-B6_R02


Project
Al-Hazm Mall
Designed b

Qty.(2)

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

DIA.

FT.

FT.

15.0

5/27 of

Sheet
Circ:

27

MA/CAL/5

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

15.0

5.0

35.0

52.1

1998

0.09

0.046

AC SUPPLY DUCT
1

23,750

1875

650

1167

5.2

17.1

23,750

1875

650

1167

4.8

15.6

30.0

15

5.0

50.0

65.6

1998

0.09

0.057

15,830

1500

600

1011

7.0

23.0

30.0

15

5.0

50.0

73.0

1774

0.08

0.061

7,915

1000

500

762

6.4

21.0

30.0

15.0

5.0

50.0

71.0

1563

0.09

0.067

AC SUPPLY DUCTS & FITTINGS

0.231

AC RETURN DUCT
4

23,750

1875

650

1167

5.2

17.1

23,750

1875

650

1167

4.8

15.6

15,830

1500

600

1011

7.0

7,915

1000

500

762

6.4

15.0

15.0

5.0

35.0

52.1

1998

0.09

0.046

30.0

15

5.0

50.0

65.6

1998

0.09

0.057

23.0

30.0

15

5.0

50.0

73.0

1774

0.08

0.061

21.0

30.0

15.0

5.0

50.0

71.0

1563

0.09

0.067

AC RETURN DUCTS & FITTINGS

0.231

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.231

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 5 )

0.625

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.300

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.231

RETURN AIR DIFFUSER

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.787

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.179
1.966

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-B6_R03 & AHU-B6_R04


Project
Al-Hazm Mall
Designed b

Qty.(2)

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

DIA.

FT.

FT.

15.0

6/27 of

Sheet
Circ:

27

MA/CAL/6

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

20.0

39.7

1882

0.07

0.027

AC SUPPLY DUCT
1

28,500

1650

900

1317

6.0

19.7

14,250

1300

700

1031

7.0

23.0

14,250

1300

700

1031

3.0

9.8

15.0

14,250

1300

700

1031

7.8

25.6

30.0

7,125

900

500

726

5.0

3,576

500

500

547

5.0

30.0

15

5.0

50.0

73.0

1537

0.06

0.046

30.0

15

5.0

65.0

74.8

1537

0.06

0.047

5.0

35.0

60.6

1537

0.06

0.038

16.4

10.0

10.0

26.4

1551

0.10

0.026

16.4

5.0

5.0

21.4

1372

0.11

0.024

AC SUPPLY DUCTS & FITTINGS

0.208

AC RETURN DUCT
6

28,500

1650

900

1317

10.2

33.5

15.0

14,250

1300

700

1031

10.0

32.8

30.0

30.0
15.0

5.0

50.0

83.5

1882

0.07

0.057

10.0

55.0

87.8

1537

0.06

0.056

AC RETURN DUCTS & FITTINGS

0.112

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.208

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 5 )

0.625

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.300

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.112

RETURN AIR DIFFUSER

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.646

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.165
1.810

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-B6_R05
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

7/27 of

Sheet
Circ:

27

MA/CAL/7

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

10.0

40.0

46.9

1431

0.14

0.064

AC SUPPLY DUCT
1

3,000

700

300

490

2.1

6.9

30.0

1,800

550

350

477

2.0

6.6

15

5.0

20.0

26.6

908

0.06

0.017

1,200

500

200

337

2.3

7.5

15

5.0

20.0

27.5

1211

0.16

0.044

600

500

150

287

4.2

13.8

5.0

20.0

33.8

836

0.10

0.034

15.0

AC SUPPLY DUCTS & FITTINGS

0.159

AC FRESH AIR DUCT


4

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.159

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.084

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.108
1.192

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-LB_01
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

450

400

464

2.0

6.6

8/27 of

Sheet
Circ:

27

MA/CAL/8

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

10.0

25.0

31.6

1706

0.20

0.064

AC SUPPLY DUCT
1

3,200

15.0

AC SUPPLY DUCTS & FITTINGS

0.064

AC RETURN DUCT
1

3,200

450

400

464

2.0

6.6

15.0

15.0

10.0

40.0

46.6

1706

AC RETURN DUCTS & FITTINGS

0.20

0.094
0.094

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.064

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.094

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.083

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.108
1.192

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-LB_02
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

500

650

622

5.0

16.4

9/27 of

Sheet
Circ:

27

MA/CAL/9

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

10.0

25.0

41.4

593

0.02

0.009

AC SUPPLY DUCT
1

2,000

15.0

AC SUPPLY DUCTS & FITTINGS

0.009

AC RETURN DUCT
1

2,000

500

650

622

5.0

16.4

15.0

10.0

25.0

41.4

593

AC RETURN DUCTS & FITTINGS

0.02

0.009
0.009

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.009

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.009

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.942

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.094
1.036

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_01
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

10/27 of

Sheet
Circ:

27

MA/CAL/10

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

6.0

10.0

10.0

16.0

857

0.05

0.007

1,600

800

250

470

2.5

8.2

5.0

5.0

13.2

831

0.05

0.007

800

700

150

331

2.1

6.9

5.0

5.0

11.9

837

0.08

0.010

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_02
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

11/27 of

Sheet
Circ:

27

MA/CAL/11

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

6.0

10.0

10.0

16.0

857

0.05

0.007

1,600

800

250

470

2.5

8.2

5.0

5.0

13.2

831

0.05

0.007

800

700

150

331

2.1

6.9

5.0

5.0

11.9

837

0.08

0.010

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_03
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

12/27 of

Sheet
Circ:

27

MA/CAL/12

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

6.0

10.0

10.0

16.0

857

0.05

0.007

1,600

800

250

470

2.5

8.2

5.0

5.0

13.2

831

0.05

0.007

800

700

150

331

2.1

6.9

5.0

5.0

11.9

837

0.08

0.010

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_04
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

13/27

Sheet
Circ:

of

27

MA/CAL/13

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

6.0

10.0

10.0

16.0

857

0.05

0.007

1,600

800

250

470

2.5

8.2

5.0

5.0

13.2

831

0.05

0.007

800

700

150

331

2.1

6.9

5.0

5.0

11.9

837

0.08

0.010

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_05
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

14/27

Sheet
Circ:

of

27

MA/CAL/14

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

6.0

10.0

10.0

16.0

857

0.05

0.007

1,600

800

250

470

2.5

8.2

5.0

5.0

13.2

831

0.05

0.007

800

700

150

331

2.1

6.9

5.0

5.0

11.9

837

0.08

0.010

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_06
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

15/27

Sheet
Circ:

of

27

MA/CAL/15

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.8

5.7

10.0

10.0

15.7

857

0.05

0.007

1,600

800

250

470

4.5

14.8

5.0

5.0

19.8

831

0.05

0.011

800

700

150

331

4.0

13.1

5.0

5.0

18.1

837

0.08

0.015

AC SUPPLY DUCTS & FITTINGS

0.033

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.033

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.958

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.096
1.054

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_07
Qty.(2)
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

DIA.

FT.

FT.

FT.

16/27

Sheet

4 June 2014

DUCT
SECTION

Al-Hazm Mall

Circ:

of

27

MA/CAL/16

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

9,600

1200

550

872

4.5

14.8

15.0

15.0

29.8

1448

0.07

0.021

9,600

1200

550

872

11.0

36.1

15.0

15.0

51.1

1448

0.07

0.036

9,600

1200

550

872

9.4

30.8

30.0

60.8

1448

0.07

0.042

8,340

1050

500

779

0.9

3.0

5.0

35.0

38.0

1575

0.09

0.035

7,072

900

550

763

0.3

1.0

10.0

40.0

41.0

1391

0.08

0.031

5,072

800

500

687

1.3

4.1

5.0

5.0

9.1

1233

0.07

0.006

4,438

700

500

644

1.5

4.9

5.0

5.0

9.9

1224

0.07

0.007

3,804

600

400

533

1.5

4.8

5.0

5.0

9.8

1535

0.14

0.014

3,170

600

400

533

1.4

4.5

10.0

25.0

29.5

1280

0.10

0.030

10

1,902

450

350

433

1.5

4.9

5.0

5.0

9.9

1163

0.11

0.011

11

1,268

400

350

409

1.3

4.1

5.0

5.0

9.1

869

0.07

0.006

12

634

350

350

383

1.2

4.0

0.0

4.0

496

0.25

0.010

30.0
30.0
30.0

15.0

AC SUPPLY DUCTS & FITTINGS

0.249

AC RETURN DUCT
12

9,600

1200

550

872

4.5

14.8

13

9,600

1200

550

872

6.6

21.7

14

9,100

1200

550

872

4.0

13.1

15

9,100

1200

550

872

7.6

24.9

15.0
15.0

5.0

15.0
15.0

15.0

29.8

1448

0.07

0.021

20.0

41.7

1448

0.07

0.029

15.0

28.1

1372

0.06

0.018

15.0

39.9

1372

0.06

0.025

AC RETURN DUCTS & FITTINGS

0.093

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.249

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.093

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.267

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.127
1.394

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_08
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

17/27

Sheet
Circ:

of

27

MA/CAL/17

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

4,725

750

500

666

4.6

15.1

30.0

10.0

40.0

55.1

1221

0.07

0.039

3,150

550

500

573

7.7

25.3

30.0

10.0

40.0

65.3

1099

0.07

0.046

1,575

500

350

455

6.6

21.7

0.0

21.7

870

0.06

0.013

1,575

500

350

455

4.8

15.6

50.0

65.6

870

0.06

0.040

1,050

350

350

383

1.1

3.6

0.0

3.6

822

0.07

0.002

525

350

350

383

1.2

3.9

0.0

3.9

411

0.02

0.001

15.0

30.0

5.0

AC SUPPLY DUCTS & FITTINGS

0.141

AC RETURN DUCT
6

4,725

550

500

573

1.9

6.2

15.0

4,725

550

500

573

8.0

26.2

15.0

4,725

550

500

573

1.4

4.4

0.0

30.0

0.0

5.0

20.0

26.2

1649

0.15

0.039

0.0

45.0

71.2

1649

0.15

0.105

5.0

5.0

9.4

1649

0.15

0.014

AC RETURN DUCTS & FITTINGS

0.157

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.141

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.157

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.223

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.122
1.345

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_09
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

18/27

Sheet
Circ:

of

27

MA/CAL/18

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

3,200

750

400

592

1.3

4.3

10.0

10.0

14.3

1048

0.06

0.009

2,667

750

350

550

3.1

10.2

5.0

5.0

15.2

1009

0.06

0.010

2,132

750

300

506

1.7

5.6

10.0

40.0

45.6

956

0.06

0.029

1,066

500

250

381

1.7

5.6

5.0

5.0

10.6

842

0.07

0.008

533

500

150

287

3.0

9.8

5.0

5.0

14.8

742

0.08

0.012

30.0

AC SUPPLY DUCTS & FITTINGS

0.067

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.067

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.000

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.992

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.099
1.091

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_10
Qty.(2)
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

DIA.

FT.

FT.

15.0

19/27

Sheet
Circ:

of

27

MA/CAL/19

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

20.0

25.6

1294

0.08

0.022

AC SUPPLY DUCT
1

4,480

750

450

630

1.7

5.6

3,830

750

450

630

6.0

19.7

5.0

5.0

24.7

1106

0.06

0.016

3,447

650

450

589

3.5

11.5

5.0

5.0

16.5

1140

0.07

0.012

2,681

550

450

543

2.6

8.5

5.0

50.0

58.5

1041

0.07

0.040

1,532

550

350

477

4.1

13.5

10.0

10.0

23.5

773

0.05

0.011

1,149

450

350

433

3.7

12.1

10.0

10.0

22.1

702

0.04

0.010

383

350

350

383

1.1

3.6

0.0

3.6

300

0.01

0.000

30.0

15.0

AC SUPPLY DUCTS & FITTINGS

0.110

AC FRESH AIR DUCT


6

400

250

250

273

4.0

13.1

15.0

400

250

250

273

2.3

7.5

15.0

400

250

250

273

2.3

1.2

15.0

5.0

5.0

20.0

33.1

614

0.06

0.020

15.0

22.5

614

0.06

0.014

20.0

21.2

614

0.06

0.013

AC FRESH DUCTS & FITTINGS

0.046

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.110

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.046

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.081

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.108
1.189

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_11
Qty.(2)
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

20/27

Sheet
Circ:

of

27

MA/CAL/20

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

5.0

17.1

1117

0.07

0.012

10.0

55.0

68.1

1010

0.06

0.043

AC SUPPLY DUCT
1

3,200

700

400

573

3.7

12.1

2,700

650

400

553

4.0

13.1

2,550

650

350

515

4.5

14.8

5.0

5.0

19.8

1100

0.08

0.016

2,125

550

350

477

3.5

11.5

5.0

5.0

16.5

1072

0.08

0.014

1,275

450

350

433

5.9

19.4

5.0

5.0

24.4

779

0.05

0.013

425

350

350

383

1.4

4.6

0.0

4.6

333

0.01

0.001

30.0

15

AC SUPPLY DUCTS & FITTINGS

0.098

AC RETURN DUCT
6

3,200

650

400

553

2.4

7.9

3,200

650

400

553

11.5

37.7

15.0

5.0

20.0

27.9

1198

0.09

0.024

5.0

5.0

42.7

1198

0.09

0.037

AC RETURN DUCTS & FITTINGS

0.060

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.098

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.060

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.084

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.108
1.192

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_12

HVAC

Project

Project No.

Designed b

M.M

Date

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

21/27

Sheet

4 June 2014

DUCT
SECTION

Al-Hazm Mall

Circ:

of

27

MA/CAL/21

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,400

800

350

567

1.5

4.8

10.0

10.0

14.8

857

0.05

0.007

1,600

800

250

470

3.1

10.2

5.0

5.0

15.2

831

0.05

0.008

800

700

150

331

2.7

8.9

5.0

5.0

13.9

837

0.08

0.012

AC SUPPLY DUCTS & FITTINGS

0.026

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.026

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.000

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.951

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.047

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_13 & AHU-UB_14 & AHU-UB_15 Qty.(2HVAC


Project
Project No.
Al-Hazm Mall
Designed b

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

22/27

Sheet
Circ:

of

27

MA/CAL/22

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

10.0

40.0

49.2

439

0.01

0.004

5.0

20.0

45.6

468

0.01

0.004

AC SUPPLY DUCT
1

3,200

1200

600

914

2.8

9.2

30.0

2,880

1000

600

840

7.8

25.6

2,240

900

600

799

5.2

17.1

30.0

5.0

35.0

52.1

402

0.01

0.004

1,600

700

600

708

5.2

17.1

30.0

5.0

35.0

52.1

366

0.01

0.004

960

700

400

573

5.2

17.1

5.0

5.0

22.1

335

0.01

0.002

320

300

400

378

4.7

15.4

5.0

20.0

35.4

257

0.01

0.003

15

15.0

AC SUPPLY DUCTS & FITTINGS

0.020

AC FRESH AIR DUCT


6

100

350

350

383

1.0

3.3

0.0

3.3

78

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.020

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.945

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.040

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_16
Project
Al-Hazm Mall
Designed b

MP
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

600

450

567

2.8

9.0

23/27

Sheet
Circ:

of

27

MA/CAL/23

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

10.0

40.0

49.0

857

0.05

0.022

AC SUPPLY DUCT
1

2,400

30.0

AC SUPPLY DUCTS & FITTINGS

0.022

AC FRESH AIR DUCT


6

200

350

350

383

1.0

3.3

0.0

3.3

157

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.022

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.947

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.042

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_17
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

600

450

567

2.8

9.2

24/27

Sheet
Circ:

of

27

MA/CAL/24

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

10.0

40.0

49.2

857

0.05

0.022

AC SUPPLY DUCT
1

2,400

30.0

AC SUPPLY DUCTS & FITTINGS

0.022

AC FRESH AIR DUCT


6

200

350

350

383

1.0

3.3

0.0

3.3

157

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.022

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.947

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.042

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_18
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

600

450

567

4.0

13.1

25/27

Sheet
Circ:

of

27

MA/CAL/25

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

10.0

40.0

53.1

857

0.05

0.024

AC SUPPLY DUCT
1

2,400

30.0

AC SUPPLY DUCTS & FITTINGS

0.024

AC FRESH AIR DUCT


6

200

350

350

383

1.0

3.3

0.0

3.3

157

AC FRESH DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.024

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.000

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.949

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.095
1.044

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_19 & AHU-UB_20


Project
Al-Hazm Mall
Designed b

Qty.(2)

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

26/27

Sheet
Circ:

of

27

MA/CAL/26

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

Fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

2,200

500

400

488

4.3

14.1

10.0

10.0

24.1

1058

0.08

0.019

1,570

450

350

433

1.5

4.8

5.0

5.0

9.8

960

0.08

0.008

1,256

450

300

400

4.0

13.1

5.0

5.0

18.1

901

0.08

0.014

628

300

300

328

1.2

3.9

5.0

5.0

8.9

669

0.06

0.005

314

300

250

299

1.2

3.9

5.0

20.0

23.9

402

0.02

0.006

314

300

250

299

1.1

3.6

5.0

5.0

8.6

402

0.02

0.002

15.0

AC SUPPLY DUCTS & FITTINGS

0.054

AC FRESH AIR DUCT


6

600

350

350

383

1.0

3.3

0.0

3.3

470

AC FRESH DUCTS & FITTINGS

0.02

0.001
0.001

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.054

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.001

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.979

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.098
1.077

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation

AHU-UB_22
QTY.(2)
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

27/27

Sheet
Circ:

of

27

MA/CAL/27

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

10.0

40.0

57.1

823

0.04

0.025

AC SUPPLY DUCT
1

2,200

650

400

553

5.2

17.1

30.0

1,290

400

300

378

2.8

9.2

5.0

5.0

14.2

1036

0.10

0.015

860

400

200

305

2.3

7.5

5.0

5.0

12.5

1062

0.14

0.018

430

300

200

266

4.8

15.6

0.0

15.6

694

0.08

0.012

AC SUPPLY DUCTS & FITTINGS

0.070

AC FRESH AIR DUCT


4

600

400

200

305

1.9

6.2

15.0

15.0

21.2

741

0.07

0.016

600

400

200

305

11.0

36.1

15.0

15.0

51.1

741

0.07

0.038

600

400

200

305

4.0

13.1

5.0

18.1

741

0.07

0.013

5.0

AC FRESH AIR DUCTS & FITTINGS

0.067

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.070

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC FRESH DUCTS & FITTINGS

0.067

FRESH AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.812

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.081
0.893

RICTION

prepared by/ Engr.Mohamed Mosaad

MechaTronics Co.

External static pressure Calculation


AHU-B5_G01
Project
Al-Hazm Mall
Designed b

HVAC
Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

FITTINGS
Br
R

FT.

FT.

FT.

DIA.

FT.

1/26 of

Sheet
Circ:

27

MA/CAL/1

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

1,250

600

250

414

2.0

6.6

5.0

5.0

11.6

837

0.06

0.007

625

500

150

287

2.9

9.5

5.0

5.0

14.5

871

0.11

0.016

AC SUPPLY DUCTS & FITTINGS

0.023

AC RETURN DUCT
8

650

550

653

4.0

13.1

15.0

10.0

25.0

38.1

AC RETURN DUCTS & FITTINGS

0.00

0.000
0.000

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.023

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 1 )

0.125

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.000

RETURN AIR GRILLE

0.000

SOUND ATTENUATOR

0.250

SUB-TOTAL

0.548

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.055
0.603

RICTION

prepared by/ Engr.Mohamed Mosaad

Potrebbero piacerti anche