Control transformers STN...

, DTZ
Multi-winding transformer UTI
Multipurpose power supply units AING
All transformers are constructed and tested according to IEC/EN 61558 guidelines.
Depending on version, they can therefore be used in compliance with the safety norm
IEC/EN 60204.
Single-phase STN control transformers
Complete safety for electrical controls Page 15/4

Single/three-phase control, isolating, and STI, STZ, DTZ safety transformers


With increased insulation for the production of low voltages Page 15/6

Single-phase UTI multi-winding transformers


Control, isolation and safety transformers according to IEC/EN 61558-2-2 +++ simple
engineering as they are adapted to various worldwide control voltages Page 15/9

Multipurpose power supply units AING


Safety transformers to IEC/EN 61558-2-6 +++ All voltages from one device +++ allow simple
engineering and low wiring costs Page 15/9

2010 CA08103002Z-ENwww.eaton.com

Control transformers, multi-winding transformers, universal power


supply units
System overview
Transformers, universal power supply units

15/2

Ordering
Single-phase control transformers with 
STN standard voltages

15/4

Single-phase STN control transformers 

15/5

Single-phase control, isolating and 


STI safety transformers

15/6

Single-phase control, isolating and 


STZ safety transformers

15/7

Three-phase control, isolating, and 


DTZ safety transformers

15/8

Single-phase UTI multi-winding transformers 

15/9

Multipurpose power supply units AING

15/9

IP23 enclosures 

15/10

Shielding winding 

15/10

Inrush current limiters 

15/10

Additional tappings 

15/11

Additional windings 

15/11

Engineering
Size selection for control transformers 

15/12

Protection of control transformers

15/12

Technical data
Transformers

15/13

Multipurpose power supply units AING

15/13

Dimensions

g

1)

e
a

Single-phase STN control transformers 

15/15

Single-phase control, isolating, and 


STI, STZ safety transformers

15/16

Three-phase control, isolating, and


DTZ safety transformers

15/17

Multipurpose power supply units AING

15/18

Single-phase UTI multi-winding transformers 

15/18

IP23 enclosures for transformers

15/19

Further transformers can be obtained from:


Trafomodern Transformatoren Ges.m.b.H.
Industriestrae II/11
A-7053 Hornstein
E-Mail: info@trafomodern.com
Internet: www.trafomodern.com

15/2

Transformers

System overview

7
3

4
8

2010 CA08103002Z-EN

www.eaton.com

Standard transformers
Single-phase
control transformers STZ
safety transformers STZ
isolating transformers STZ

Additional tappings

2010 CA08103002Z-EN

www.eaton.com

Primary, secondary
Page 15/11

Shielding winding

Page 15/10

Sheet-steel enclosure,
degree of protection IP23
2

Primary tapping 5 %
Built and tested to
IEC/EN 61558-2-2/2-4/2-6,
VDE 0570-2-2/2-4/2-6,
UL 506, CSA 22.2 No. 66
Page 15/8

Single-phase
control transformers STI
safety transformers STI
isolating transformers STI

15/3

Transformer features

Primary tapping 5 %
Built and tested to
IEC/EN 61558-2-2/2-4/2-6,
VDE 0570-2-2/2-4/2-6,
UL 506, CSA 22.2 No. 66
Page 15/7

Three-phase
control transformers DTZ
safety transformers DTZ
isolating transformers DTZ

Transformers

Enclosure for enhanced degree of


protection
Selection of features
Ordering details of the
respective transformer
Page 15/10

Primary tapping 5 %
Built and tested to
IEC/EN 61558-2-2/2-4/2-6,
VDE 0570-2-2/2-4/2-6,
UL 506, CSA 22.2 No. 66
Page 15/6

Single-phase
control transformers STN

Primary tapping 5 %
Built and tested to
IEC/EN 61558-2-2, VDE 0570-2-2
UL 506, CSA 22.2 No. 66
Page 15/4

Single-phase multi-winding
transformers UTI

Primary tapping 208 to 600 V


Built and tested to
IEC/EN 61558-2-2/2-4/2-6,
VDE 0570-2-2/2-4/2-6,
UL 506, CSA 22.2 No. 66
Page 15/9

Universal power supply unit AING

Primary tapping 5 %
Safety transformer to
IEC/EN 61558-2-2/2-6,
VDE 0570-2-2/2-6,
For every output voltage
a fuse
an LED
a changeover contact
Page 15/9

15/4

Transformers
Single-phase control transformers with standard voltages
STN

HPL15004EN

Ordering

Single-phase control transformers with standard voltages

Rated output
kVA

Short-time rating
kVA

Preferred voltage 400/230 V

Preferred voltage 400/24 V

Preferred voltage 230/24 V

Part no.
Article no.

Part no.
Article no.

Part no.
Article no.

Price
See price
list

Price
See price
list

Price
See price
list

Std. pack

Single-phase control transformers


with standard voltages
IEC/EN 61558-2-2
VDE 0570 Part 2-2
Rated input voltage 230 5 % V ,
400 5 % V
Rated output voltage 24 V , 230 V

0.06

0.095

0.1

0.16

0.16

0.32

0.2

0.38

0.25

0.44

0.315

0.6

0.4

0.62

0.5

0.88

0.63

1.51

0.8

2.25

3.28

1.3

4.8

1.6

3.98

5.75

2.5

7.24

8.36

12.2

STN0.06(400/230)
204936
STN0.1(400/230)
204942
STN0.16(400/230)
204948
STN0.2(400/230)
204977
STN0.25(400/230)
204980
STN0.315(400/230)
204982
STN0.4(400/230)
204984
STN0.5(400/230)
204986
STN0.63(400/230)
204988
STN0.8(400/230)
204990
STN1.0(400/230)
204992
STN1.3(400/230)
221523
STN1.6(400/230)
221524
STN2.0(400/230)
221525
STN2.5(400/230)
221526
STN3.0(400/230)
221527
STN4.0(400/230)
221528

STN0.06(400/24)
204937
STN0.1(400/24)
204943
STN0.16(400/24)
204949
STN0.2(400/24)
204978
STN0.25(400/24)
221509
STN0.315(400/24)
221511
STN0.4(400/24)
221514
STN0.5(400/24)
221516
STN0.63(400/24)
221518
STN0.8(400/24)
221520
STN1.0(400/24)
221522

STN0.06(230/24)
204935
STN0.1(230/24)
204941
STN0.16(230/24)
204947
STN0.2(230/24)
204976
STN0.25(230/24)
221508
STN0.315(230/24)
221510
STN0.4(230/24)
221513
STN0.5(230/24)
221515
STN0.63(230/24)
221517
STN0.8(230/24)
221519
STN1.0(230/24)
221521

1 off

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

2010 CA08103002Z-EN

www.eaton.com

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06;
IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

Transformers

15/5

Single-phase control transformers


STN

HPL15005EN
Single-phase control transformers

Rated output

Short-time rating

kVA

kVA

Part no.
Article no.

Price
See price list

Std. pack

Notes

1 off

Ordering example
When ordering, the part number must include the
following details:
STN0, 1(*/*)
First asterisk rated input voltage
Second asterisk rated output voltage
Desired part no. STN0, 1
Desired rated input voltage 200 V
Desired rated output voltage 18.5 V
The correct part no. is
STN0. 1(200/18.5)
Transformer-protective circuit-breakers
PKZMO--T Page 7/6

Single-phase control transformers


IEC/EN 61558-2-2
VDE 0570 Part 2-2
Rated input voltage 100 690 5 % V
Rated output voltage 12 250 V

0.06

0.095

0.1

0.16

0.16

0.32

0.2

0.38

0.25

0.44

0.315

0.6

0.4

0.62

0.5

0.88

0.63

1.51

0.8

2.25

3.28

1.3

4.8

1.6

3.98

5.75

2.5

7.24

8.36

12.2

STN0.06(*/*)
204938
STN0.1(*/*)
204939
STN0.16(*/*)
204944
STN0.2(*/*)
204950
STN0.25(*/*)
204979
STN0.315(*/*)
204981
STN0.4(*/*)
204983
STN0.5(*/*)
204985
STN0.63(*/*)
204987
STN0.8(*/*)
204989
STN1.0(*/*)
204991
STN1.3(*/*)
204993
STN1.6(*/*)
204994
STN2.0(*/*)
204995
STN2.5(*/*)
204996
STN3.0(*/*)
204997
STN4.0(*/*)
204998

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06;


CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

2010 CA08103002Z-EN

www.eaton.com

15/6

Transformers
Single-phase control, isolating and safety transformers
HPL15006EN

STI
Single-phase control, isolating and safety transformers

Rated output

Short-time rating

kVA

kVA

Standard voltage
400/230 V

Standard voltage
400/24 V

Standard voltage
230/230 V

Standard voltage
230/24 V

Price
See
price list

Part no.
Article no.

Part no.
Article no.

Part no.
Article no.

Part no.
Article no.

Std. pack

STI0.06(400/230)
029975
STI0.1(400/230)
046630
STI0.16(400/230)
046633
STI0.2(400/230)
046636
STI0.25(400/230)
046638
STI0.315(400/230)
046639
STI0.4(400/230)
046640
STI0.5(400/230)
046641
STI0.63(400/230)
046883
STI0.8(400/230)
046889
STI1.0(400/230)
046895
STI1.3(400/230)
046918
STI1.6(400/230)
046952
STI2.0(400/230)
035258
STI2.5(400/230)
035259
STI3.0(400/230)
035260
STI4.0(400/230)
035261

STI0.06(400/24)
029971
STI0.1(400/24)
046631
STI0.16(400/24)
046634
STI0.2(400/24)
046637
STI0.25(400/24)
035249
STI0.315(400/24)
035250
STI0.4(400/24)
035251
STI0.5(400/24)
035252
STI0.63(400/24)
035253
STI0.8(400/24)
035254
STI1.0(400/24)
035255

STI0.06(230/230)
029968
STI0.1(230/230)
029976
STI0.16(230/230)
035247
STI0.2(230/230)
035248
STI0.25(230/230)
036400
STI0.315(230/230)
040641
STI0.4(230/230)
040642
STI0.5(230/230)
040643
STI0.63(230/230)
040644
STI0.8(230/230)
026641
STI1.0(230/230)
026642
STI1.3(230/230)
035256
STI1.6(230/230)
035257
STI2.0(230/230)
036398
STI2.5(230/230)
036399

STI0.06(230/24)
029977
STI0.1(230/24)
046629
STI0.16(230/24)
046632
STI0.2(230/24)
046635
STI0.25(230/24)
035262
STI0.315(230/24)
036392
STI0.4(230/24)
036393
STI0.5(230/24)
036394
STI0.63(230/24)
036395
STI0.8(230/24)
036396
STI1.0(230/24)
036397

1 off

Single-phase control, isolating and safety


transformers with standard voltages
IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2, Part 2-6 (safety transformers),
Part 2-4 (isolating transformers)
Rated input voltage 230 5 % V, 400 5 % V
Rated output voltage 24 , 230 V

0.06

0.13

0.1

0.24

0.16

0.36

0.2

0.44

0.25

0.6

0.315

0.75

0.4

1.1

0.5

1.6

0.63

1.7

0.8

2.8

1.3

3.7

1.6

5.5

2.5

11.5

15

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

2010 CA08103002Z-EN

www.eaton.com

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06;


CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

Transformers

15/7

Single-phase control, isolating and safety transformers


STZ

HPL15007EN
Single-phase control, isolating and safety transformers

Rated output

Short-time rating

kVA

kVA

Part no.
Article no.

Price
See price
list

Std. pack

Notes

1 off

Transformers with rated output voltages 50 V can be used as


safety transformers to IEC/EN 61558.

Single-phase control, isolating and


safety transformers
IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers)
Rated input voltage 50 950 5 % V
Rated output voltage 12 1000 V

0.06

0.13

0.1

0.24

0.16

0.36

0.2

0.44

0.25

0.6

0.315

0.75

0.4

1.1

0.5

1.6

0.63

1.7

0.8

2.8

1.3

3.7

1.6

5.5

2.5

11.5

15

5.3

13

8.3

21

13.3

34

STZ0.06(*/*)
914761
STZ0.1(*/*)
914762
STZ0.16(*/*)
914763
STZ0.2(*/*)
914764
STZ0.25(*/*)
914765
STZ0.315(*/*)
914766
STZ0.4(*/*)
914767
STZ0.5(*/*)
914768
STZ0.63(*/*)
914769
STZ0.8(*/*)
914770
STZ1.0(*/*)
914771
STZ1.3(*/*)
914772
STZ1.6(*/*)
914773
STZ2.0(*/*)
914774
STZ2.5(*/*)
914775
STZ3.0(*/*)
914776
STZ4.0(*/*)
914777
STZ5.3(*/*)
201060
STZ8.3(*/*)
201062
STZ13.3(*/*)
201064

Ordering example
When ordering, the part number must include the following
details:
STZ0.06(*/*)
First asterisk rated input voltage
Second asterisk rated output voltage
Desired part no. STZ0.06
Desired rated input voltage 230 V
Desired rated output voltage 12 V
The correct type reference is
STZ0.06(230/12)
Caution!
Standard voltages 400/230 V, 400/24 V,230/230 V, 230/24 V are only
supplied as STI Page 15/6 if other suffixes, e.g. shield winding,
are not ordered.
Accessories Page 15/10

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2
No. 66.2-06; IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

2010 CA08103002Z-EN

www.eaton.com

15/8

Transformers
Three-phase control, isolating and safety transformers
HPL15008EN

DTZ
Three-phase control, isolating and safety transformers

Rated output

Short-time rating

kVA

kVA

Part no.
Article no.

Price
See price
list

Std. pack

Notes

DTZ0.1(*/*)*
914799
DTZ0.16(*/*)*
914800
DTZ0.25(*/*)*
914801
DTZ0.4(*/*)*
914802
DTZ0.5(*/*)*
914803
DTZ0.63(*/*)*
914804
DTZ1.0(*/*)*
914805
DTZ1.6(*/*)*
914806
DTZ2.0(*/*)*
914807
DTZ2.5(*/*)*
914808
DTZ4.0(*/*)*
914809
DTZ6.3(*/*)*
914810
DTZ8.0(*/*)*
914811
DTZ10(*/*)*
914812
DTZ12.5(*/*)*
914813
DTZ16(*/*)*
914814
DTZ20(*/*)*
914815

1 off

Transformers with rated output voltages 50 V can be used as


safety transformers in accordance with IEC/EN 61558.

DTZ25(*/*)*
914816

1 off

Three-phase control, isolating and


safety transformers
IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers)
Rated input voltage 50 950 5 % V
Rated output voltage 18.5 1000 V

0.1

0.2

0.16

0.32

0.25

0.5

0.4

0.8

0.5

0.63

1.38

2.2

1.6

3.5

4.4

2.5

5.5

6.2

6.3

15.7

20

10

25

12.5

31

16

40

20

50

25

62

Ordering example
When ordering, the part number must include the following
details:
DTZ0.1(*/*)*
First asterisk rated input voltage
Second asterisk rated output voltage
Third asterisk configuration
Desired part no. DTZ0.1
Desired rated input voltage 200 V
Desired rated output voltage 18.5 V
Desired configuration Dy(n)5
The correct type reference is
DTZ0.1(200/18.5)DY(N)5)
Accessories Page 15/10

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

2010 CA08103002Z-EN

www.eaton.com

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06;


CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

Transformers

15/9

Single-phase multi-winding transformers


UTI, AING

HPL15009EN
Single-phase multi-winding transformers

Rated
output
kVA

Rated
input
voltage
V

Rated
output
voltage
V

Part no.
Article no.

Price
See
price list

Std. pack

Notes

1 off

Transformer-protective
circuit-breakers PKZM0-...-T
Page 7/6

Single-phase multi-winding transformers


(Universal) control, isolating and safety transformers
to VDE 0550,
IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2, Part 2-6 (safety transformers),
Part 2-4 (isolating transformers)
0.1
208
2 x 115
230
380
0.2
400
415
0.315
440
460
0.5
480
500
525
0.63
550
575
0.8
600
1

Rated
output
kVA

Max. output
current
A

UTI0.1-115
206923
UTI0.2-115
206924
UTI0.315-115
206925
UTI0.5-115
206926
UTI0.63-115
206927
UTI0.8-115
206928
UTI1.0-115
206929
Part no.
Article no.

Price
See
price list

Std.
pack

Notes

1 off

Circuit diagram:

Multipurpose power supply units AING


Safety transformer to IEC/EN 61558-2-2/2-6
VDE 0570 Part 2-2/2-6
For every output voltage a fuse, an LED and a
changeover contact for monitoring and annunciation.
Non-standard voltages please enquire
Rated input voltage 230 5 % V
Rated output voltage 24 AC, 10 DC, 24 DC V
0.1
4.2
1
3
0.192
8
1
3

AING4
269516
AING8
269517

+5 %
230 V

24 V AC

5 %

0
+10 V DC
_
+24 V DC

Signal contacts
Switching voltage max. 250 V AC/110 V DC
max. 1 A
Switching duty 62 VA/30 W
LED indicators
Output voltage present: LED = green
Fuse fault/missing: LED = red
Size/type FK2 fuses are used.

Notes
Information relevant for export to North America

Product Standards
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Suitable for
Max. Voltage Rating
Degree of Protection

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06;
IEC/EN 61558-2-2; CE marking
E167225
XPTQ2, XPTQ8
UL report applies to both US and Canada

UL Recognized, certified by UL for use in Canada


Branch circuits
600 V AC
IEC: IP00, UL/CSA Type: -

2010 CA08103002Z-EN

www.eaton.com

15/10

Transformers
Accessories
HPL15010EN

+IP23..., +W..., EEB..., +EEB...


Accessories

For use with

Part no. suffix


Article no. for
ordering only
with basic unit

STZ0.06 STZ0.16

+IP23/01
200618
+IP23/02
200623
+IP23/03
200624
+IP23/04
226100
+IP23/05
200648
+IP23/06
200649

Price
See price list

Std. pack

Notes

Information relevant for export to


North America

1 off

Enclosure can be used with primary


or secondary voltages >110 V.
For lower voltages, please enquire.

IP23 enclosures

STZ0.2 STZ0.5
STZ0.63 STZ1.3
STZ1.6 STZ2.0
STZ5.3 STZ8.3
STZ13.3
STZ2.5 STZ4.0
DTZ1.0 DTZ2.0
DTZ0.1 DTZ0.16
DTZ0.25 DTZ0.63
DTZ2.5 DTZ6.3
DTZ8.0 DTZ25

+IP23/32A
200763
+IP23/30
200706
+IP23/31
200753
+IP23/33
200754
+IP23/34
200755

Enclosure can be used with primary


or secondary voltages from 42 V to
max. 1000 V incl. taps.

Shielding winding
STZ0.06 STZ1.6
STZ2.0 STZ13.3
DTZ0.1 DTZ6.3
DTZ8.0 DTZ20

Primary current

For use with

IN
A

+W1.8
082270
+W4.0
082271
+W6.0
082274
+W20.0
082275

Type
Article no.
when ordered
separately

1 off

Price
See price list

Shielding winding means additional


shielding between the primary and
secondary winding.

Type suffix
Article no. for
ordering only
with basic unit

Price
See price
list

UL/CSA approval not required

Std.
pack

Notes

1 off

Primary current: from the transformer


rating plate or by calculation

Inrush current limiters


For single-phase transformers
1

STI
STZ

2
3

EEB1
226102
EEB2
226104
EEB3
226106

+EEB1
226101
+EEB2
226103
+EEB3
226105

Single-phase: IN = SN /(UNprim x )
Three-phase: IN = SN /(3 UNprim x )
SN = rated transformer output
UNprim = Transformers primary rated
voltage
= efficiency (from the technical data
table)

2010 CA08103002Z-EN

www.eaton.com

Transformers

15/11

Accessories
+ZA..., +DZA..., +ZW...

HPL15011EN
Accessories

Current
range
A

Part no. suffix


Article no. for
ordering only
with basic unit

For use
with

Price
See price
list

Std. pack

Notes

1 off

Selection of the correct tap.


Ordering example for single-phase transformers:
Selected transformer STZ0.25(400/24)
Required voltage of additional tapping 22 V
The current for selection of the tapping is calculated as follows:

Additional tappings
For deviations in the rated input or output voltage of
more than 10 %:
Ask about size of the transformer.
Also state distribution of rating in addition to the
tapping.
< 16
STZ
Primary
Single-phase
side
transformers
< 16

STZ

Secondary

Single-phase
transformers

+ZA16P(*)
931897
+ZA16S(*)
931895

I = S/U
I = current
S = apparent power
U = voltage of the tapping
I = 250/22 = 11.4 A +ZA16
For the secondary tapping, the correct suffix is:
+ZA16S(22)
A primary side additional tapping is determined in the same manner.
< 16

DTZ

Primary
side

Three-phase
transformers

+DZA16P(*)
930200

< 16

DTZ

Secondary

Three-phase
transformers

+DZA16S(*)
200406

Selection of the correct tap.


Ordering example for three-phase transformers:
Selected transformer DTZ0.25(400/24)
Required voltage of additional tapping 22 V
The current for selection of the tapping is calculated as follows:
I = S/(3 x U)
I = current
S = apparent power
U = voltage of the tapping
I = 250/( 3 x 22) = 6.6 A +DZA16
For the secondary tapping, the correct suffix is:
+DZA16S(22)
A primary side additional tapping is determined in the same manner.

Additional windings
For primary extra winding please enquire
A maximum of 5 additional windings can be ordered for
the primary and/or secondary side.
< 16
STZ
Second- Single-phase
ary
transformers

+ZW16S(*V*VA)
279276

1 off

Ordering example for single-phase transformers:


Transformer STZ...(400 V/200 V) with 1000 VA and a secondary
additional winding for 100 V and 200 VA, resulting in the required
rating of 1200 VA. The correct part no. is:
STZ1.3(400/200)
For pricing of the additional winding, the current is calculated as
follows.:
I = S/U
I = current
S = apparent power of the additional winding
U = voltage of the additional winding
I = 200/100 = 2 A +ZW16
For the secondary additional winding, the correct suffix is:
+ZW16S(100V200VA)

Notes

Information relevant for export to North America


UL/CSA approval not required

2010 CA08103002Z-EN

www.eaton.com

15/12

Transformers
Selection and protection of control transformers
ST..., DT...

Engineering

Protection of control
transformers

Selection and protection of control transformers

Size selection for control


transformers
Determination of the continuous
rating
The control transformer must be rated
in size so that the voltage drop remains
within the permissible tolerance range
even under unfavorable conditions.
The determination of the transformer
rating is performed by the addition
of all the sealing powers of all
loads which are to be connected
simultaneously as well as addition of
the inrush power of the largest load,
and multiplying the result by a factor
of 0.8.

If the ratings of the loads are very


similar, the sum of all inrush powers of
the simultaneously connected loads is
added to the sum of all the sealing
powers and the result is multiplied by
a factor of 0.8.
Determination of the short-time rating
If the primary requirement is to switch
large contactors, it is recommended
that the control transformer is
selected on the basis of the short-time
rating. In most cases, this will mean
that the transformer rating is reduced.
It is important to ensure that the
sealing power does not exceed the
continuous rating.

Operational conditions
The protective device shown in the
table below must be connected
upstream of the primary. The overload
release of the circuit-breaker must be
set to the stated current. The current
to be set must also be stated on the
rating plate of the transformer. If a
short-circuit release is present it must
be set to the maximum value.
The setting values of the circuitbreaker apply up to 1.06 times the
rated voltage. For a higher mains
voltage the +5 % terminal is to be used.
In the case of transformers > 2.0 kVA
(DT...> 4.0 kVA) the circuit-breaker

may trip under certain mains supply


conditions (Ik > 6 kA) and with
unfavorable starting torque. In such
cases we recommend the use of an
inrush current limiter.
The inrush current limiter can be
ordered as an accessory. Ordering
details Accessories

Setting range of the motor-protective circuit-breaker as a function of the STI, STZ


and DTZ transformer rated power (VA)
Part no.

ST0.06
ST0.1
ST0.16
ST0.2
ST0.25
ST0.315
ST0.4
ST0.5
ST0.63
ST0.8
ST1.0
ST1.3
ST1.6
ST2.0
ST2.5
ST3.0
ST4.0
DT0.1
DT0.16
DT0.25
DT0.4
DT0.5
DT0.63
DT1.0
DT1.6
DT2.0
DT2.5
DT4.0
DT6.3

Primary voltage
200 V
Protective Setdevice
ting
A
PKZM0-0.4 0.4
PKZM0-0.63 0.5
PKZM0-1
0.8
PKZM0-1.6 1.3
PKZM0-2.5 1.6
PKZM0-2.5 2.0
PKZM0-4
3.1
PKZM0-6.3 5.0
PKZM0-6.3 6.2
PKZM0-10 7.6
PKZM0-16 12.0
PKZ2/ZM-25 18.9

230 V
Protective
device
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZM0-10
PKZM0-10
PKZM0-16
PKZ2/ZM-16
PKZ2/ZM-25
PKZ2/ZM-25
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-4
PKZM0-6.3
PKZM0-6.3
PKZM0-10
PKZM0-16
PKZ2/ZM-25

Setting
A
0.3
0.5
0.8
1.0
1.3
1.5
2.0
2.4
3.0
3.8
4.7
6.3
7.4
10.0
11.5
16.0
18.1
0.3
0.5
0.7
1.1
1.4
1.8
2.7
4.3
5.4
6.7
10.4
16.4

400 V
Protective
device
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZM0-6.3
PKZ2/ZM-10
PKZ2/ZM-16
PKZ2/ZM-16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZ2/ZM-10

Setting
A
0.2
0.3
0.5
0.6
0.7
0.9
1.1
1.4
1.7
2.2
2.7
3.5
4.2
5.3
6.6
10.0
10.4
0.2
0.3
0.4
0.7
0.8
1.0
1.6
2.5
3.1
3.8
6.0
9.5

415 V
Protective
device
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZM0-6.3
PKZ2/ZM-10
PKZ2/ZM-16
PKZ2/ZM-16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZ2/ZM-10

For all other transformers use transformer-protective circuit-breakers PKZM0-...-T. Page 7/6

2010 CA08103002Z-EN

www.eaton.com

Setting
A
0.2
0.3
0.5
0.6
0.7
0.9
1.1
1.3
1.7
2.1
2.6
3.4
4.1
5.1
6.4
10.0
10.0
0.2
0.3
0.4
0.6
0.8
1.0
1.5
2.4
3.0
3.7
5.8
9.1

440 V
Protective
device
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZ2/ZM-10
PKZ2/ZM-10
PKZ2/ZM-10
PKZM0-0.25
PKZM0-0.4
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZ2/ZM-10

Setting
A
0.2
0.3
0.4
0.5
0.7
0.8
1.0
1.2
1.6
2.0
2.5
3.2
4.0
4.8
6.0
7.1
10.0
0.2
0.3
0.4
0.6
0.7
0.9
1.4
2.3
2.8
3.5
5.5
8.6

500 V
Protective
device
PKZM0-0.16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-4
PKZM0-6.3
PKZ2/ZM-6
PKZ2/ZM-10
PKZ2/ZM-10
PKZM0-0.16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-6.3
PKZ2/ZM-10

Setting
A
0.2
0.2
0.4
0.5
0.6
0.7
0.9
1.1
1.4
1.7
2.2
2.8
3.4
4.2
5.3
6.2
8.3
0.1
0.2
0.3
0.5
0.6
0.8
1.3
2.0
2.5
3.1
4.8
7.6

690 V
Protective
device
PKZM0-0.16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1
PKZM0-1.6
PKZM0-1.6
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZ2/ZM-4
PKZ2/ZM-6
PKZ2/ZM-6
PKZM0-0.16
PKZM0-0.25
PKZM0-0.4
PKZM0-0.63
PKZM0-0.63
PKZM0-0.63
PKZM0-1
PKZM0-1.6
PKZM0-2.5
PKZM0-2.5
PKZM0-4
PKZM0-6.3

Setting
A
0.1
0.2
0.3
0.3
0.4
0.5
0.7
0.8
1.0
1.3
1.6
2.0
2.5
3.1
4.0
4.5
6.0
0.1
0.2
0.3
0.4
0.5
0.6
0.9
1.4
1.8
2.2
3.5
5.5

Transformers

15/13

Transformers, universal power supply units


STI, STZ, DTZ, STN, UTI, AING

Technical data
Transformers, universal power supply units

Control transformers

General
Standards
Built and tested to

Suitable for use to

Ambient temperature
Characteristics
Terminals
Connection lugs
Insulation class
Rated frequency
Primary tapping
Degree of protection
Separate windings
Completely vacuum-impregnated
Reinforced insulation
Rated duty factor

Hz

% DF

Multi-winding
transformers
UTI

Universal power
supply units
AING

Safety transformer
to IEC/EN 61558-2-2/
2-6
VDE 0570 Part 2-2/
2-6

B
50 - 60
5%
IP20

100

STI, STZ

DTZ

STN

IEC/EN 61558-2-2/
2-4/2-6
VDE 0570 Part 2-2,
Part 2-6 (safety
transformers),
Part 2-4 (isolating
transformers)

IEC/EN 61558-2-2/
2-4/2-6
VDE 0570 Part 2-2,
Part 2-6 (safety
transformers),
Part 2-4 (isolating
transformers)

IEC/EN 61558-2-2
VDE 0570 Part 2-2

IEC/EN 60204-1,
VE-EN 13
VDE 0113, VDE 0100
Part 410
-25 - +40

IEC/EN 60204-1,
VE-EN 13
VDE 0113, VDE 0100
Part 410
-25 - +40

IEC/EN 60204-1,
VE-EN 13
VDE 0113, VDE 0100
Part 410
-25 - +40

(Universal)
control, isolating
and safety transformers to VDE 0550,
IEC/EN 61558-2-2/
2-4/2-6
VDE 0570 Part 2-2,
Part 2-6 (safety
transformers),
Part 2-4 (isolating
transformers)
IEC/EN 60204-1,
VE-EN 13
VDE 0113, VDE 0100
Part 410
-25 - +40

(< 115 A)
(> 115 A)
B
50 - 60
5%
IP00

100

(< 115 A)
(> 115 A)
B
50 - 60
5%
IP00

100

(< 115 A)
(> 115 A)
B
50 - 60
5%
IP00

100

B
50 - 60
20 %
IP00

100

2010 CA08103002Z-EN

IEC/EN 60204-1
VDE 0113

-25 - +40

www.eaton.com

15/14

Transformers
Transformers
STI, STZ, DTZ, UTI

Transformers

Total
weight

No-load
losses

kg

Shortcircuit
losses
W

Shortcircuit
voltage
%

Efficiency

Single-phase control, isolating, and safety transformers1)


ST0.06
ST0.1
ST0.16
ST0.2
ST0.25
ST0.315
ST0.4
ST0.5
ST0.63
ST0.8
ST1.0
ST1.3
ST1.6
ST2.0
ST2.5
ST3.0
ST4.0
STZ5.3
STZ8.3
STZ13.3

1.5
2
2.3
3
3.8
4.3
5.2
6.8
7.7
9.6
13.4
14.9
17.4
21.5
21.5
26
35
40
55
80

6
7
9
11
13
10
17
15
15
17
27
32
21
27
39
30
38
40
65
95

1)

1
1.5
2.4
2.8
2.9
3.5
4.2
5.1
7.1
9.8
12.4
14.1
14.3
19.9
20
23
27

7
7
11
9
9
11
12
15
21
24
33
46
43
56
21
32
28

No-load
losses

kg

5
8
12
17
14
18
18
24
27
25
29
35
37
33
43
55
88
165
200
265

7.8
6.9
6.6
6.6
5.1
5.5
4.4
3.9
4.1
3.2
2.9
3
2.4
2
2.4
2.1
2.2
4
4
3.5

0.85
0.87
0.88
0.88
0.9
0.92
0.92
0.93
0.94
0.95
0.95
0.95
0.96
0.97
0.97
0.97
0.97
0.96
0.97
0.97

10
15
16
19
21
21
27
27
32
24
26
33
44
42
145
94
143

11
10
6.7
6.8
6.3
5.3
5.3
4.1
3.8
2.5
2.2
2.1
2.5
2
2.4
2.4
2.4

0.79
0.84
0.87
0.88
0.9
0.91
0.92
0.93
0.93
0.94
0.94
0.94
0.95
0.95
0.95
0.96
0.96

DTZ0.1
DTZ0.16
DTZ0.25
DTZ0.4
DTZ0.5
DTZ0.63
DTZ1.0
DTZ1.6
DTZ2.0
DTZ2.5
DTZ4.0
DTZ6.3
DTZ8.0
DTZ10
DTZ12.5
DTZ16
DTZ20
DTZ25

1.9
2.5
3.6
5.1
6.1
8.9
12.9
18.5
22.4
29.3
39.6
50.2
55
70
80
95
125
160

5
8
11
15
20
25
35
55
60
80
60
66
60
80
95
100
140
180

Shortcircuit
voltage
%

Efficiency

28
20
25
40
35
50
50
60
75
85
100
170
250
280
300
420
400
350

15
9.5
8.5
8
6
5.5
4
3
3.5
2.5
2
2
4
3.5
4
4.5
3.5
3

0.75
0.85
0.88
0.88
0.9
0.9
0.92
0.93
0.94
0.94
0.96
0.96
0.96
0.97
0.97
0.97
0.98
0.98

7.5
6.5
5
3.5
3.8
2.8
2.1

0.84
0.87
0.89
0.92
0.92
0.93
0.93

Single-phase multi-winding transformers


UTI0.1
UTI0.2
UTI0.315
UTI0.5
UTI0.63
UTI0.8
UTI1.0

2
3
4.3
6.8
7.7
9.6
13.4

8
10
15
26
25
33
46

All no-load loss, short-circuit loss, short-circuit voltage and efficiency values apply at a temperature of 20 C.

2010 CA08103002Z-EN

Shortcircuit
losses
W

Three-phase control, isolating, and safety transformers1)

Single-phase control transformers1)


STN0.06
STN0.1
STN0.16
STN0.2
STN0.25
STN0.315
STN0.4
STN0.5
STN0.63
STN0.8
STN1.0
STN1.3
STN1.6
STN2.0
STN2.5
STN3.0
STN4.0

Total
weight

www.eaton.com

11
19
23
23
32
29
30

Transformers

15/15

Single-phase control transformers


STN

Dimensions
Single-phase control transformers

Single-phase control transformers


STN0.06...2.0

2) c5

Connection lugs
Maximum space requirement
With STN0,06-0.2 ground connection at bottom

c1

3)
1)

og
e

2) a

b1
2) b5

Part no.
STN0.06
STN0.1
STN0.16
STN0.2
STN0.25
STN0.315
STN0.4
STN0.5
STN0.63
STN0.8
STN1.0
STN1.3
STN1.6
STN2.0

12 V
b
79
75
97
83
103
111
108
120
121
124
150
138
183
213

a
66
85
85
106
106
106
121
121
151
151
151
175
175
175

c
78
91
91
112
121
121
133
133
157
196
196
213
170
170

24 V
b
79
75
97
83
83
91
88
120
121
138
164
148
138
168

c
78
91
91
112
112
112
124
133
157
157
157
169
216
216

42 V
b
79
75
97
83
83
91
88
100
107
124
164
148
148
178

c
78
91
91
112
112
112
124
124
145
145
157
169
169
169

110 V
b
79
75
97
83
83
91
88
100
107
124
150
138
138
168

c
78
91
91
112
112
112
124
124
145
145
145
157
157
157

230 V
b
79
75
97
83
83
91
88
100
107
124
150
138
138
168

c
78
91
91
112
112
112
124
124
145
145
145
157
157
157

e
50
64
64
80
80
80
90
90
122
122
122
135
135
135

f
56
47
70
61
61
70
68
80
82
99
125
110
110
141

g
4.8x8
4.8x8
4.8x8
5.8x9
5.8x9
5.8x9
5.8x12
5.8x12
7x15
7x15
7x15
7x15
7x15
7x15

b1
67
60
83
80
80
89
86
98
104
121
147
135
135
165

c1
60
76
76
97
97
97
106
106
132
132
132
152
152
152

STN2.5...4.0
Connection lugs
Maximum space requirement

2) b15

2) c5

c1

1)

e
b

2) a

Part no.
STN2.5
STN3.0
STN4.0

a
230
230
230

b
130
155
170

c1
250
250
250

e
190
190
190

f
200
200
200

g
11
11
11

b1
12 V
185
210
225

c
12 V
260
260
260

b1
24V
185
230
245

c
24V
250
250
250

b1
42 V
205
230
245

c
42 V
255
255
255

b1
110 V
160
185
200

c
110 V
275
275
275

2010 CA08103002Z-EN

b1
230 V
145
170
185

c
230 V
255
255
255

www.eaton.com

15/16

Transformers
Single-phase control, isolating, and safety transformers
STI, STZ

Single-phase control, isolating, and safety transformers

Single-phase control, isolating, and safety transformers


ST...0.06...2.5
Connection lugs
With STI/STZ0.06 0.16 ground connection at bottom

c1

c5

2)

1)
g

b1
b5

Part no.
ST0.06
ST0.1
ST0.16
ST0.2
ST0.25
ST0.315
ST0.4
ST0.5
ST0.63
ST0.8
ST1.0
ST1.3
ST1.6
ST2.0
ST2.5

a
85
85
85
106
106
121
121
121
151
151
151
175
195
195
195

12 V
b
75
89
97
83
111
-

c
91
91
91
112
124
-

24 V
b
75
89
97
83
91
88
100
140
121
138
164
148
142
154
154

c
91
91
91
112
112
119
119
131
157
157
157
169
240
240
240

42 V
b
75
89
97
83
91
88
100
120
107
124
164
148
149
161
154

110 V
b
75
89
97
83
91
88
100
120
107
124
150
138
142
154
161

c
91
91
91
112
112
119
119
119
145
145
157
169
186
186
240

c
91
91
91
112
112
119
119
119
145
145
145
157
174
174
186

230 V
b
75
89
97
83
91
88
100
120
107
124
150
138
142
154
154

c
91
91
91
112
112
119
119
119
145
145
145
157
174
174
174

b1
60
74
83
80
89
86
98
118
104
121
147
135
140
152
152

c1
76
76
76
97
97
106
106
106
132
132
132
152
166
166
166

e
64
64
64
80
80
90
90
90
122
122
122
135
150
150
150

ST...3.0...4.0
b

g

1)

e
a

Part no.
ST3.0
ST4.0

a
230
230

2010 CA08103002Z-EN

12 V
b
-

c
-

www.eaton.com

24 V
b
210
235

c
250
250

42 V
b
230
255

c
255
255

110 V
b
185
210

c
275
275

230 V
b
170
200

c
255
255

e
190
190

f
200
200

g
11
11

f
47
61
70
61
70
68
80
100
82
99
125
110
110
122
122

g
4.8x8
4.8x8
4.8x8
5.8x9
5.8x9
5.8x12
5.8x12
5.8x12
7x15
7x15
7x15
7x15
10x18
10x18
10x18

Transformers

15/17

Three-phase control, isolating, and safety transformers


STZ, DTZ
Three-phase control, isolating, and safety transformers

c5

STZ5.3...13.3

e
a

b5

g

12 V
Part no.
a
b
c
STZ5.3
260
200
*)
STZ8.3
260
STZ13.3
320
*) The higher rated voltage is valid

24 V
b
200
230
240

42 V
b
200
230
240

c
*)
*)
*)

c
*)
*)
*)

110 V
b
214
244
270

c
374
374
440

230 V
b
214
244
270

c
360
374
440

e
230
230
270

f
126
156
172

g
10x18
10x18
13x20

Three-phase control, isolating, and safety transformers


DTZ0.1...25
The higher rated operating voltage applies
Terminals 25 A
Connection lugs > 63 A

2)

c1

3)

og
e
a

f
b1
b

Part no.
DTZ0.1
DTZ0.16
DTZ0.25
DTZ0.4
DTZ0.5
DTZ0.63
DTZ1.0
DTZ1.6
DTZ2.0
DTZ2.5
DTZ4.0
DTZ6.3

a
125
125
155
155
190
190
210
230
240
265
300
300

18.5 V
b
65
75
77
92
82
102
137
144
117
132
166
193

DTZ8.0
DTZ10.0
DTZ12.5
DTZ16
DTZ20
DTZ25

390
390
390
450
450
450

200
-

c
134
134
154
154
180
180
210
234
279
299
317
285
1)

24 V
b
65
75
77
92
112
132
137
114
117
132
166
210
200
216
231
221
251
281

c
134
134
154
154
191
191
210
269
279
299
333
285
1)
1)
1)
1)
1)
1)

42 V
b
65
75
77
92
82
102
137
144
117
132
147
193
200
216
231
221
251
281

c
134
134
154
154
180
180
210
234
279
299
333
333
1)
1)
1)
1)
1)
1)

110 V
b
65
75
77
92
82
102
117
114
141
152
157
173
184
199
214
204
234
264

c
134
134
154
154
180
180
199
223
244
264
296
333
374
374
374
434
1)
1)

230-690 V
b
c
65
134
75
134
77
154
92
154
82
180
102
180
117
199
114
223
117
233
132
253
157
296
173
296

e
100
100
130
130
170
170
175
176
185
200
224
224

f
45
55
57
72
58
78
97
95
95
102
119
145

g
8x5
8x5
8 x 12
8 x 12
8 x 12
8 x 12
8 x 12
7 x 13
10 x 18
10 x 18
10 x 18
10 x 18

b1
61
71
77
92
82
102
117
114
117
132
147
173

c1
102
102
128
128
155
155
174
198
208
228
260
260

184
199
214
204
234
264

350
350
350
400
400
400

126
141
156
142
172
202

10 x 18
10 x 18
10 x 18
13 x 20
13 x 20
13 x 20

152
167
182
172
202
232

310
310
310
360
360
360

374
374
374
434
434
434

2010 CA08103002Z-EN

www.eaton.com

15/18

Transformers
Single-phase multi-winding transformers, universal power supply units
UTI, AING

Single-phase multi-winding transformers, universal power supply units

Universal power supply units


AING4, AING8
a
62
70

5.8

155

Part no.
AING4
AING8

14.5

80.5

110

90

Single-phase multi-winding transformers


UTI...

c1

c5

2)

og

1) a5

b1
1) b5

2010 CA08103002Z-EN

www.eaton.com

Us = 115 V
Part no.
a
b
c
UTI0.1
85
89
93
UTI0.2
106 82
112
UTI0.315 121 88
124
UTI0.5
121 120 124
UTI0.63 151 107 150
UTI0.8
151 124 150
UTI1.0
151 150 150
Us Secondary voltage
1)
2)

e
64
80
90
90
122
122
122

f
61
61
68
100
82
99
125

g
4.8x8
5.8x9
5.8x12
5.8x12
7x15
7x15
7x15

Maximum space requirement


With type UTI0,1 ground connection at bottom

b1
74
80
86
118
104
121
147

c1
76
97
106
106
132
132
132

Transformers

15/19

Enclosure for transformers


IP23
Enclosure for transformers

IP23 enclosures
+IP23/01, +IP23/02

Part no.
+IP23/01
+IP23/02
+IP23/03
+IP23/04
+IP23/30
+IP23/31
+IP23/32A

b
118
192
192
231
192
231
263

c
145
184
184
254
184
254
360

+IP23/04, +IP23/31, +IP 23/32A

+IP23/03

a
122
160
203
203
160
203
315

+IP23/30

+IP23/05, +IP23/06, +IP 23/33, +IP23/34


Part no.
+IP23/05
+IP23/06
+IP23/33
+IP23/34

a
570
690
520
620

b
390
500
410
560

c
390
480
340
440

c1
430
540
360
460

e
230
270
212
350

f
390
500
330
430

g
10
13
10
12

e
g

c1

2010 CA08103002Z-EN

www.eaton.com