inbreathing Calculation

Volume Of Tank
Pump Outlet Flow
Insulation Factor
C factor
Total inbreating air

Air Velocity
sizing of Vent

450 m3
30 m3/hr
1
6.5
497.909773 Nm3/hr

15 m/sec
0.00922055 m2
0.108351

Tank Capacity

ank Capacity

Latitude

Table 1 : C-factor for Inbreathing


Vapor Pressure
Hexane
or similar
Average Storage Temperature
< 25
>=25

Below 42o

6.5

42 to 58

2.5

Above 58o

Vin,air = Vpe + CVtk0.7 Ri


where
Vin,air = Total inbreathing in Nm3/h (Air)
Vpe = Pump-out or emptying in m3/h
Vtk = Tank capacity in m3
Ri = Insulation reduction factor

eathing
Vapor Pressure
Higher than hexane
or unknown
e Storage Temperature (oC)
< 25
>=25
6.5

6.5

Outbreathing Calculation
Volume Of Tank
Pump outlet Flow

Insulation Factor

C factor

Total Outbreathing air

450 m3
90 m3/hr

0.32

168.1702 Nm3/hr

Table 2 : Y-factor for Outbreathing


Latitude

Y-factor

Below 42o

0.32

42o to 58o

0.25

Above 58o

0.2

Vout,air = Vpf + YVtk0.9 Ri


where
Vout,air = Total Outbreathing in Nm3/h (Air)
Vpf = Pump-out or filling in m3/h
Vtk = Tank capacity in m3
Ri = Insulation reduction factor
Y = Factor subject to latitude (see Table 2)