Sei sulla pagina 1di 370

Si34 - 804_C

RXQ5-54PAY1
R-410A Cooling Only 50Hz

Si34-804_C

R-410A Cooling Only


50Hz
1. Introduction .............................................................................................v
1.1 Safety Cautions ........................................................................................v
1.2 PREFACE ............................................................................................... ix

Part 1 General Information ........................................................... 1


1. Model Names of Indoor/Outdoor Units....................................................2
1.1 Indoor Units ..............................................................................................2
1.2 Outdoor Units ...........................................................................................2
1.3 Air Treatment Equipment .........................................................................3

2. External Appearance...............................................................................4
2.1 Indoor Units ..............................................................................................4
2.2 Outdoor Units ...........................................................................................5

3. Combination of Outdoor Units.................................................................7


4. Capacity Range.......................................................................................9

Part 2 Specifications .................................................................. 12


1. Specifications ........................................................................................13
1.1 Outdoor Units .........................................................................................13
1.2 Indoor Units ............................................................................................34

Part 3 Refrigerant Circuit ........................................................... 57


1. Refrigerant Circuit .................................................................................58
1.1
1.2
1.3
1.4
1.5

RXQ5PA.................................................................................................58
RXQ8PA.................................................................................................60
RXQ10PA, 12PA ....................................................................................62
RXQ14PA, 16PA, 18PA .........................................................................64
Outdoor Air Processing Unit FXMQ125MFV1~250MFV1 ......................66

2. Functional Parts Layout ........................................................................67


2.1
2.2
2.3
2.4
2.5

RXQ5PA.................................................................................................67
RXQ8PA.................................................................................................68
RXQ10PA...............................................................................................69
RXQ12PA...............................................................................................70
RXQ14PA, 16PA, 18PA .........................................................................71

3. Refrigerant Flow for Each Operation Mode...........................................72

Part 4 Function............................................................................ 80
1. Function General...................................................................................81
1.1 Symbol ...................................................................................................81
1.2 Operation Mode......................................................................................82

2. Basic Control.........................................................................................83
2.1 Normal Operation ...................................................................................83
2.2 Compressor PI Control...........................................................................83
i

Table of Contents

Si34-804_C

2.3 Electronic Expansion Valve PI Control.................................................102


2.4 Step Control of Outdoor Unit Fans .......................................................102
2.5 Outdoor Unit Fan Control in Cooling Operation ...................................102

3. Special Control....................................................................................103
3.1
3.2
3.3
3.4
3.5

Startup Control .....................................................................................103


Oil Return Operation ............................................................................104
Pump down Residual Operation...........................................................105
Standby ................................................................................................105
Stopping Operation ..............................................................................106

4. Protection Control ...............................................................................107


4.1
4.2
4.3
4.4
4.5
4.6

High Pressure Protection Control.........................................................107


Low Pressure Protection Control..........................................................108
Discharge Pipe Protection Control .......................................................109
Inverter Protection Control ...................................................................110
STD Compressor Overload Protection.................................................111
Injection Control (only for RXQ5PA).....................................................111

5. Other Control.......................................................................................112
5.1 Outdoor Unit Rotation...........................................................................112
5.2 Emergency Operation ..........................................................................113
5.3 Demand Operation ...............................................................................118

6. Outline of Control (Indoor Unit) ...........................................................119


6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9

Drain Pump Control..............................................................................119


Louver Control for Preventing Ceiling Dirt............................................121
Using Conditions for Remote Controller Thermistor.............................122
Thermostat Control while in Normal Operation ....................................123
Thermostat Control in Dry Operation ...................................................123
Electronic Expansion Valve Control .....................................................124
Freeze-up Prevention...........................................................................124
List of Swing Flap Operations ..............................................................125
Control of Outdoor Air Processing Unit
(Unique Control for Outdoor Air Processing Unit) ................................126

Part 5 Test Operation ............................................................... 129


1. Test Operation ....................................................................................130
1.1 Installation Process ..............................................................................130
1.2 Procedure and Outline .........................................................................131
1.3 Operation when Power is Turned On ...................................................146

2. Outdoor Unit PCB Layout....................................................................147


3. Field Setting ........................................................................................148
3.1 Field Setting from Remote Controller ...................................................148
3.2 Field Setting from Outdoor Unit............................................................165

Part 6 Service Diagnosis........................................................... 185


1. Symptom-based Troubleshooting .......................................................187
2. Troubleshooting by Remote Controller ...............................................190
2.1
2.2
2.3
2.4

Table of Contents

The INSPECTION / TEST Button.........................................................190


Self-diagnosis by Wired Remote Controller .........................................191
Self-diagnosis by Wireless Remote Controller .....................................193
Operation of the Remote Controllers Inspection /
Test Operation Button ..........................................................................195
ii

Si34-804_C

2.5 Remote Controller Service Mode .........................................................196


2.6 Remote Controller Self-Diagnosis Function .........................................199
2.7 Error Code and Description..................................................................200

3. Troubleshooting by Indication on the Remote Controller ....................206


3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.27
3.28
3.29
3.30
3.31
3.32
3.33
3.34
3.35
3.36
3.37
3.38
3.39
3.40
3.41
3.42
3.43
3.44
3.45
3.46

iii

External Protection Device Abnormality ...............................................206


PCB Abnormality ..................................................................................207
Drain Level Control System (S1L) Abnormality....................................208
Fan Motor (M1F) Lock, Overload .........................................................210
Swing Flap Motor (M1S) Abnormality...................................................214
Power Supply Voltage Abnormality ......................................................216
Electronic Expansion Valve Coil (Y1E) Abnormality ............................217
Drain Level above Limit........................................................................219
Capacity Determination Device Abnormality ........................................220
Transmission Error (Between Indoor unit PCB and Fan PCB).............221
Thermistor Abnormality ........................................................................223
Combination Error (Between Indoor unit PCB and Fan PCB)..............224
Humidity Sensor System Abnormality ..................................................225
Room Temperature Thermistor in Remote Controller Abnormality ......226
PCB Abnormality ..................................................................................227
Actuation of High Pressure Switch .......................................................228
Actuation of Low Pressure Sensor .......................................................231
Inverter Compressor Motor Lock..........................................................233
STD Compressor Motor Overcurrent/Lock...........................................236
Outdoor Unit Fan Motor Abnormality....................................................237
Electronic Expansion Valve Coil (Y1E, Y2E) Abnormality....................240
Discharge Pipe Temperature Abnormality ...........................................242
Refrigerant Overcharged......................................................................244
Outdoor Fan Motor Signal Abnormality ................................................245
Thermistor Abnormality ........................................................................246
Current Sensor Abnormality .................................................................247
High Pressure Sensor Abnormality ......................................................248
Low Pressure Sensor Abnormality .......................................................250
Inverter PCB Abnormality.....................................................................253
Inverter Radiation Fin Temperature Rise Abnormality .........................255
Inverter Compressor Abnormality.........................................................258
Inverter Current Abnormality ................................................................260
Inverter Compressor Startup Abnormality ............................................262
Transmission Error between Inverter and Control PCB .......................265
Inverter Over-Ripple Protection............................................................267
Inverter Radiation Fin Temperature Abnormality .................................269
Field Setting after Replacing Main PCB Abnormality or
Combination of PCB Abnormality.........................................................270
Refrigerant Shortage ............................................................................271
Reverse Phase, Open Phase...............................................................272
Power Supply Insufficient or Instantaneous Abnormality .....................273
Check Operation is not Executed.........................................................276
Transmission Error between Indoor Units and Outdoor Units..............277
Transmission Error between Remote Controller and Indoor Unit.........279
Transmission Error between Outdoor Units .........................................280
Transmission Error between Main and Sub Remote Controllers .........282
Transmission Error between Indoor and
Outdoor Units in the Same System ......................................................283
Table of Contents

Si34-804_C

3.47 Improper Combination of Indoor and Outdoor Units, Indoor Units and
Remote Controller ................................................................................284
3.48 Address Duplication of Centralized Controller......................................286
3.49 Transmission Error between Centralized Controller and Indoor Unit ...287
3.50 System is not Set yet............................................................................290
3.51 System Abnormality, Refrigerant System Address Undefined .............291

Part 7 Appendix......................................................................... 301


1. Piping Diagrams..................................................................................302
1.1 Outdoor Unit .........................................................................................302
1.2 Indoor Unit............................................................................................306

2. Wiring Diagrams for Reference...........................................................309


2.1 Outdoor Unit .........................................................................................309
2.2 Field Wiring ..........................................................................................314
2.3 Indoor Unit............................................................................................317

3. List of Electrical and Functional Parts .................................................330


3.1 Outdoor Unit .........................................................................................330
3.2 Indoor Side ...........................................................................................333

4. Option List ...........................................................................................338


4.1 Option List of Controllers......................................................................338
4.2 Option Lists (Outdoor Unit)...................................................................340

5. Piping Installation Point.......................................................................342


5.1 Piping Installation Point ........................................................................342
5.2 The Example of a Wrong Pattern .........................................................343

6. Example of Connection (R-410A Type) ..............................................345


7. Thermistor Resistance / Temperature Characteristics........................347
8. Pressure Sensor .................................................................................349

Part 8 Precautions for New Refrigerant (R-410A) .................... 350


1. Precautions for New Refrigerant (R-410A) .........................................351
1.1 Outline ..................................................................................................351
1.2 Refrigerant Cylinders............................................................................353
1.3 Service Tools........................................................................................354

Table of Contents

iv

Introduction

Si34-804_C

1. Introduction
1.1

Safety Cautions

Cautions and
Warnings

Be sure to read the following safety cautions before conducting repair work.
Warning and
Caution. The
The caution items are classified into

Warning
items are especially important since they can lead to death or serious injury if they are not
followed closely. The
Caution items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer

1.1.1 Caution in Repair


Warning
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.

When disconnecting the suction or discharge pipe of the compressor at the


welded section, release the refrigerant gas completely at a well-ventilated
place first.
If there is a gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it can
cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The
refrigerant gas can generate toxic gases when it contacts flames.

The step-up capacitor supplies high-voltage electricity to the electrical


components of the outdoor unit.
Be sure to discharge the capacitor completely before conducting repair work.
A charged capacitor can cause an electrical shock.

Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.

Si34-804_C

Introduction

Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.

Do not clean the air conditioner by splashing water.


Washing the unit with water can cause an electrical shock.

Be sure to provide the grounding when repairing the equipment in a humid or


wet place, to avoid electrical shocks.

Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.

Do not tilt the unit when removing it.


The water inside the unit can spill and wet the furniture and floor.

Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.

1.1.2 Cautions Regarding Products after Repair


Warning
Be sure to use parts listed in the service parts list of the applicable model and
appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools can cause an electrical shock,
excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard
installation frame.
Incorrect use of the installation frame and improper installation can cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted on a
window frame.
If the unit is not securely mounted, it can fall and cause injury.

For integral units


only

For integral units


only

Be sure to use an exclusive power circuit for the equipment, and follow the
technical standards related to the electrical equipment, the internal wiring
regulations and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work can cause an
electrical shock or fire.
vi

Introduction

Si34-804_C

Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.

Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.

Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.

Be sure to install the packing and seal on the installation frame properly.
For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.

1.1.3 Inspection after Repair


Warning
Check to make sure that the power cable plug is not dirty or loose, then insert
the plug into a power outlet all the way.
If the plug has dust or loose connection, it can cause an electrical shock or fire.

If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.

Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.

vii

Si34-804_C

Introduction

Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.

Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 M or higher.
Defective insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Defective drainage can cause the water to enter the room and wet the furniture
and floor.

1.1.4 Using Icons


Icons are used to attract the attention of the reader to specific information. The meaning of each
icon is described in the table below:

1.1.5 Using Icons List


Icon

Type of
Information

Description

Note

A note provides information that is not indispensable, but may


nevertheless be valuable to the reader, such as tips and tricks.

Caution

A caution is used when there is danger that the reader, through


incorrect manipulation, may damage equipment, loose data, get
an unexpected result or has to restart (part of) a procedure.

Warning

A warning is used when there is danger of personal injury.

Reference

A reference guides the reader to other places in this binder or


in this manual, where he/she will find additional information on a
specific topic.

Note:

Caution

Warning

viii

Introduction

1.2

Si34-804_C

PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2009 VRVIII series Cooling Only System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII series R-410A
Cooling Only System.

December, 2010
After Sales Service Division

ix

Si34-804_C

Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
1.1 Indoor Units ..............................................................................................2
1.2 Outdoor Units ...........................................................................................2
1.3 Air Treatment Equipment .........................................................................3

2. External Appearance...............................................................................4
2.1 Indoor Units ..............................................................................................4
2.2 Outdoor Units ...........................................................................................5

3. Combination of Outdoor Units.................................................................7


4. Capacity Range.......................................................................................9

General Information

Model Names of Indoor/Outdoor Units

Si34-804_C

1. Model Names of Indoor/Outdoor Units


1.1

Indoor Units

Indoor Units
Capacity range
Capacity index

0.8HP
20

1HP
25

1.25HP
31.25

1.6HP
40

2HP
50

2.5HP
62.5

3.2HP
80

4HP
100

5HP
125

6HP
140

8HP
200

10HP
250

FXFQ

25P

32P

40P

50P

63P

80P

100P

125P

FXZQ

20M

25M

32M

40M

50M

FXCQ

20M

25M

32M

40M

50M

63M

80M

125M

Ceiling Mounted
Cassette Corner Type

FXKQ

25MA

32MA

40MA

63MA

20PB

25PB

32PB

Slim Ceiling Mounted


Duct Type

FXDQPBVE
FXDQPBVET
FXDQNBVE
FXDQNBVET

20PB

25PB

32PB

40NB

50NB

63NB

40NB

50NB

63NB

FXMQ

20P

25P

32P

40P

50P

63P

80P

100P

125P

140P

FXMQ

Ceiling Suspended
Type

FXHQ

32MA

63MA

100MA

Wall Mounted Type

FXAQ

20MA

25MA

32MA

40MA

50MA

63MA

Floor Standing Type

FXLQ

20MA

25MA

32MA

40MA

50MA

63MA

Concealed Floor
Standing Type

FXNQ

20MA

25MA

32MA

40MA

50MA

63MA

Ceiling Mounted
Cassette Type
(Round Flow)
Ceiling Mounted
Cassette (Compact
Multi Flow) Type
Ceiling Mounted
Cassette Type
(Double Flow)

Ceiling Mounted
Duct Type
(Middle and high static
pressure)
Ceiling Mounted
Duct Type

Power
Supply

VE

200MA 250MA

Note: FXDQ has following 2 series, as shown below.


FXDQ-PBVET, NBVET: without a Drain Pump (For General, Asia: except for EU, China and Australia)
FXDQ-PBVE, NBVE: with a Drain Pump
MA: RoHS Directive models; Specifications, dimensions and other functions are not changed compared with
M type.
Connection unit series indoor units
Capacity range
Capacity index
Ceiling Suspended
FXUQ
Cassette Type

3HP
71
71MA

4HP
100
100MA

5HP
125
125MA

Power
Supply

Connection Unit for


FXUQ

71MA

100MA

125MA

VE

BEVQ

V1

Note: BEV unit is required for FXUQ only.


MA: RoHS Directive models; Specifications, dimensions and other functions are not changed compared with
M type.

1.2

Outdoor Units

Normal Series (Space Saving Series)


Series
Cooling Only

RXQ

5PA
24PA
42PA

8PA
26PA
44PA

10PA
28PA
46PA

Model Name
12PA
14PA
30PA
32PA
48PA
50PA

16PA
34PA
52PA

18PA
36PA
54PA

20PA
38PA

22PA
40PA

Power Supply

24PAH
42PAH

Model Name
26PAH 28PAH
44PAH 46PAH

30PAH
48PAH

32PAH
50PAH

34PAH

36PAH

Y1

High COP Series (Energy Saving Series)


Series
Cooling Only

RXQ

16PAH
38PAH

18PAH
40PAH

Power Supply
Y1

VE:1 phase, 220-240/220V, 50/60Hz


V1: 1 phase, 220-240V, 50Hz
Y1: 3 phase, 380-415V, 50Hz
2

General Information

Si34-804_C

Model Names of Indoor/Outdoor Units

Combination of Outdoor Units (Normal Series (Space Saving Series))


HP
Model name

5HP
RXQ5PA

8HP
RXQ8PA

10HP
RXQ10PA

12HP
RXQ12PA

14HP
RXQ14PA

16HP
RXQ16PA

18HP
RXQ18PA

HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

20HP
RXQ20PA
RXQ8PA
RXQ12PA

22HP
RXQ22PA
RXQ10PA
RXQ12PA

24HP
RXQ24PA
RXQ8PA
RXQ16PA

26HP
RXQ26PA
RXQ8PA
RXQ18PA

28HP
RXQ28PA
RXQ10PA
RXQ18PA

30HP
RXQ30PA
RXQ12PA
RXQ18PA

32HP
RXQ32PA
RXQ16PA
RXQ16PA

HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

34HP
RXQ34PA
RXQ16PA
RXQ18PA

36HP
RXQ36PA
RXQ18PA
RXQ18PA

38HP
RXQ38PA
RXQ8PA
RXQ12PA
RXQ18PA

40HP
RXQ40PA
RXQ8PA
RXQ16PA
RXQ16PA

42HP
RXQ42PA
RXQ8PA
RXQ16PA
RXQ18PA

44HP
RXQ44PA
RXQ8PA
RXQ18PA
RXQ18PA

46HP
RXQ46PA
RXQ10PA
RXQ18PA
RXQ18PA

HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

48HP
RXQ48PA
RXQ12PA
RXQ18PA
RXQ18PA

50HP
RXQ50PA
RXQ14PA
RXQ18PA
RXQ18PA

52HP
RXQ52PA
RXQ16PA
RXQ18PA
RXQ18PA

54HP
RXQ54PA
RXQ18PA
RXQ18PA
RXQ18PA

Combination of Outdoor Units (High COP Series (Energy Saving Series))


HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

16HP
RXQ16PAH
RXQ8PA
RXQ8PA

18HP
RXQ18PAH
RXQ8PA
RXQ10PA

24HP
RXQ24PAH
RXQ8PA
RXQ8PA
RXQ8PA

26HP
RXQ26PAH
RXQ8PA
RXQ8PA
RXQ10PA

28HP
RXQ28PAH
RXQ8PA
RXQ8PA
RXQ12PA

30HP
RXQ30PAH
RXQ8PA
RXQ10PA
RXQ12PA

32HP
RXQ32PAH
RXQ8PA
RXQ12PA
RXQ12PA

HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

34HP
RXQ34PAH
RXQ10PA
RXQ12PA
RXQ12PA

36HP
RXQ36PAH
RXQ12PA
RXQ12PA
RXQ12PA

38HP
RXQ38PAH
RXQ12PA
RXQ12PA
RXQ14PA

40HP
RXQ40PAH
RXQ12PA
RXQ12PA
RXQ16PA

42HP
RXQ42PAH
RXQ12PA
RXQ12PA
RXQ18PA

44HP
RXQ44PAH
RXQ12PA
RXQ16PA
RXQ16PA

46HP
RXQ46PAH
RXQ12PA
RXQ16PA
RXQ18PA

HP
Model name
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3

48HP
RXQ48PAH
RXQ16PA
RXQ16PA
RXQ16PA

50HP
RXQ50PAH
RXQ16PA
RXQ16PA
RXQ18PA

1.3

Air Treatment Equipment

Outdoor-air processing unit


Series
FXMQ

Model name
200MF

125MF

Power supply
V1

250MF

HRV units (VKM series)


Series
HRV units with DX
coil
HRV units with DX
coil and humidifier

Model name

Power supply

50GA

80GA

100GA

50GAM

80GAM

100GAM

VKM

V1

HRV units (VAM series)


Series
HRV units

VAM

150GJ

250GJ

350GJ

500GJ

Model name
650GJ 800GJ

1000GJ

1500GJ

2000GJ

Power supply
VE

VE:1 phase, 220-240/220V, 50/60Hz


V1: 1 phase, 220-240V, 50Hz
Y1: 3 phase, 380-415V, 50Hz

General Information

External Appearance

Si34-804_C

2. External Appearance
2.1

Indoor Units

Ceiling mounted cassette (Round flow) type


FXFQ25PVE
FXFQ32PVE
FXFQ40PVE
FXFQ50PVE
FXFQ63PVE
FXFQ80PVE
FXFQ100PVE
FXFQ125PVE

FXMQ200MAVE
FXMQ250MAVE

Ceiling mounted cassette (Compact multi flow) type


FXZQ20MVE
FXZQ25MVE
FXZQ32MVE
FXZQ40MVE
FXZQ50MVE

FXCQ20MVE
FXCQ25MVE
FXCQ32MVE
FXCQ40MVE
FXCQ50MVE
FXCQ63MVE
FXCQ80MVE
FXCQ125MVE

Wall mounted type


FXAQ20MAVE
FXAQ25MAVE
FXAQ32MAVE
FXAQ40MAVE
FXAQ50MAVE
FXAQ63MAVE

Ceiling mounted cassette corner type


FXKQ25MAVE
FXKQ32MAVE
FXKQ40MAVE
FXKQ63MAVE

Floor standing type


FXLQ20MAVE
FXLQ25MAVE
FXLQ32MAVE
FXLQ40MAVE
FXLQ50MAVE
FXLQ63MAVE

Slim ceiling mounted duct type


FXDQ20PBVE/FXDQ20PBVET
FXDQ25PBVE/FXDQ25PBVET
FXDQ32PBVE/FXDQ32PBVET
FXDQ40NBVE/FXDQ40NBVET
FXDQ50NBVE/FXDQ50NBVET
FXDQ63NBVE/FXDQ63NBVET
with a Drain Pump (VE)
without a Drain Pump (VET)

Ceiling mounted duct type


(Middle and high static pressure)

Ceiling suspended type


FXHQ32MAVE
FXHQ63MAVE
FXHQ100MAVE

Ceiling mounted cassette (Double flow) type

FXMQ20PVE
FXMQ25PVE
FXMQ32PVE
FXMQ40PVE
FXMQ50PVE

Ceiling mounted duct type

FXMQ63PVE
FXMQ80PVE
FXMQ100PVE
FXMQ125PVE
FXMQ140PVE

Concealed floor standing type


FXNQ20MAVE
FXNQ25MAVE
FXNQ32MAVE
FXNQ40MAVE
FXNQ50MAVE
FXNQ63MAVE

Ceiling suspended cassette type


50Hz
FXUQ71MAV1 + BEVQ71MAVE
FXUQ100MAV1 + BEVQ100MAVE
FXUQ125MAV1 + BEVQ125MAVE
Connection unit

General Information

Si34-804_C

2.2

External Appearance

Outdoor Units

Normal Series (Space Saving Series)

RXQ5PA

RXQ8PA, 10PA

RXQ12PA, 14PA, 16PA, 18PA

5HP

8, 10HP

12, 14, 16, 18HP

RXQ20PA, 22PA, 24PA, 26PA, 28PA

RXQ30PA, 32PA, 34PA, 36PA

20, 22, 24, 26, 28HP

30, 32, 34, 36HP

RXQ38PA, 40PA, 42PA, 44PA, 46PA

RXQ48PA, 50PA, 52PA, 54PA

38, 40, 42, 44, 46HP

48, 50, 52, 54HP

General Information

External Appearance

Si34-804_C

High COP Series (Energy Saving Series)

RXQ16PAH, 18PAH

RXQ24PAH, 26PAH

16, 18HP

24, 26HP

RXQ28PAH, 30PAH

RXQ32PAH, 34PAH

28, 30HP

32, 34HP

RXQ36PAH, 38PAH, 40PAH, 42PAH, 44PAH, 46PAH, 48PAH, 50PAH

36, 38, 40, 42, 44, 46, 48, 50HP

General Information

Si34-804_C

Combination of Outdoor Units

3. Combination of Outdoor Units


Normal Series

System Number
Capacity of units
5HP
1
8HP
1
10HP
1
12HP
1
14HP
1
16HP
1
18HP
1
20HP
2
22HP
2
24HP
2
26HP
2
28HP
2
30HP
2
32HP
2
34HP
2
36HP
2
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
50HP
3
52HP
3
54HP
3
Note:

General Information

10

Module
12

14

16

18

Outdoor Unit Multi Connection


Piping Kit (Option)

Cooling Only: BHFP22P100

Cooling Only: BHFP22P151

For multiple connection of 20HP system or more, an optional Daikin Outdoor Unit Multi
Connection Piping Kit is required.

Combination of Outdoor Units

Si34-804_C

High COP Series (Energy Saving Series)

System Number
Capacity of units
16HP
2
18HP
2
24HP
3
26HP
3
28HP
3
30HP
3
32HP
3
34HP
3
36HP
3
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
50HP
3
Note:

10

Module
12
14

16

18

Outdoor Unit Multi Connection


Piping Kit (Option)

Cooling Only: BHFP22P100

Cooling Only: BHFP22P151

For multiple connection of 16HP system or more, an optional Daikin Outdoor Unit Multi
Connection Piping Kit is required.

General Information

Si34-804_C

Capacity Range

4. Capacity Range
Combination ratio
Connection capacity: 50% - 200%

Combination ratio =

Total capacity index of the indoor units


Capacity index of the outdoor units

Max. combination ratio


Types of connected indoor units
Type of connected Air Treatment Equipments
Type

Single
outdoor units
Double
outdoor units
Triple outdoor
units

Min.
combination
ratio

VKM
FXMQ-MF
Including
When
FXDQ, FXFQ25 at
Other
When VKM
When
FXMQ-P, least one indoor unit When VKM and indoor FXMQ-MF FXMQ-MF
is only
and indoor
FXAQ
models
units are
is only
unit
connected
units are
connected connected connected
200%

50%

200%

130%

160%

130%

130%

100%

100%*

130%

Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the
indoor units.
* When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units.

General Information

Capacity Range

Si34-804_C

Outdoor Unit Combinations


Normal Type (Space Saving Type)
HP
5HP
8HP
10HP
12HP
14HP
16HP
18HP
20HP
22HP
24HP
26HP
28HP
30HP
32HP
34HP
36HP
38HP
40HP
42HP
44HP
46HP
48HP
50HP
52HP
54HP

Capacity
index
125
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1,000
1,050
1,100
1,150
1,200
1,250
1,300
1,350

Model name

Combination

RXQ5PA
RXQ8PA
RXQ10PA
RXQ12PA
RXQ14PA
RXQ16PA
RXQ18PA
RXQ20PA
RXQ22PA
RXQ24PA
RXQ26PA
RXQ28PA
RXQ30PA
RXQ32PA
RXQ34PA
RXQ36PA
RXQ38PA
RXQ40PA
RXQ42PA
RXQ44PA
RXQ46PA
RXQ48PA
RXQ50PA
RXQ52PA
RXQ54PA

RXQ5PA
RXQ8PA
RXQ10PA
RXQ12PA
RXQ14PA
RXQ16PA
RXQ18PA
RXQ8PA + RXQ12PA
RXQ10PA + RXQ12PA
RXQ8PA + RXQ16PA
RXQ8PA + RXQ18PA
RXQ10PA + RXQ18PA
RXQ12PA + RXQ18PA
RXQ16PA 2
RXQ16PA + RXQ18PA
RXQ18PA 2
RXQ8PA + RXQ12PA + RXQ18PA
RXQ8PA + RXQ16PA 2
RXQ8PA + RXQ16PA + RXQ18PA
RXQ8PA + RXQ18PA 2
RXQ10PA + RXQ18PA 2
RXQ12PA + RXQ18PA 2
RXQ14PA + RXQ18PA 2
RXQ16PA + RXQ18PA 2
RXQ18PA 3

Outdoor unit multi


connection piping kit *1

BHFP22P100

BHFP22P151

Total capacity index of


connectable indoor units *2 *3
62.5 to 162.5 (250)
100 to 260 (400)
125 to 325 (500)
150 to 390 (600)
175 to 455 (700)
200 to 520 (800)
225 to 585 (900)
250 to 650 (800)
275 to 715 (880)
300 to 780 (960)
325 to 845 (1,040)
350 to 910 (1,120)
375 to 975 (1,200)
400 to 1,040 (1,280)
425 to 1,105 (1,360)
450 to 1,170 (1,440)
475 to 1,235 (1,235)
500 to 1,300 (1,300)
525 to 1,365 (1,365)
550 to 1,430 (1,430)
575 to 1,495 (1,495)
600 to 1,560 (1,560)
625 to 1,625 (1,625)
650 to 1,690 (1,690)
675 to 1,755 (1,755)

Maximum number of
connectable indoor units *2
8 (12)
13 (20)
16 (25)
19 (30)
22 (35)
26 (40)
29 (45)
32 (40)
35 (44)
39 (48)
42 (52)
45 (56)
48 (60)
52 (64)
55 (64)
58 (64)
61 (61)

64 (64)

Note: *1 For multiple connection of 20 HP systems and above, the outdoor unit multi connection
piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity,
200% for single outdoor units, 160% for double outdoor units, and 130% for triple outdoor
units.
outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
*3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units.

High COP Type (Energy Saving Type)


HP
16HP
18HP
24HP
26HP
28HP
30HP
32HP
34HP
36HP
38HP
40HP
42HP
44HP
46HP
48HP
50HP

Capacity
index
400
450
600
650
700
750
800
850
900
950
1,000
1,050
1,100
1,150
1,200
1,250

Model name

Combination

RXQ16PAH
RXQ18PAH
RXQ24PAH
RXQ26PAH
RXQ28PAH
RXQ30PAH
RXQ32PAH
RXQ34PAH
RXQ36PAH
RXQ38PAH
RXQ40PAH
RXQ42PAH
RXQ44PAH
RXQ46PAH
RXQ48PAH
RXQ50PAH

RXQ8PA 2
RXQ8PA + RXQ10PA
RXQ8PA 3
RXQ8PA 2 + RXQ10PA
RXQ8PA 2 + RXQ12PA
RXQ8PA + RXQ10PA + RXQ12PA
RXQ8PA + RXQ12PA 2
RXQ10PA + RXQ12PA 2
RXQ12PA 3
RXQ12PA 2 + RXQ14PA
RXQ12PA 2 + RXQ16PA
RXQ12PA 2 + RXQ18PA
RXQ12PA + RXQ16PA 2
RXQ12PA + RXQ16PA + RXQ18PA
RXQ16PA 3
RXQ16PA 2 + RXQ18PA

Outdoor unit multi


connection piping kit *1
BHFP22P100

BHFP22P151

Total capacity index of


connectable indoor units *2 *3
200 to 520 (640)
225 to 585 (720)
300 to 780 (780)
325 to 845 (845)
350 to 910 (910)
375 to 975 (975)
400 to 1,040 (1,040)
425 to 1,105 (1,105)
450 to 1,170 (1,170)
475 to 1,235 (1,235)
500 to 1,300 (1,300)
525 to 1,365 (1,365)
550 to 1,430 (1,430)
575 to 1,495 (1,495)
600 to 1,560 (1,560)
625 to 1,625 (1,625)

Maximum number of
connectable indoor units *2
26 (32)
29 (36)
39 (39)
42 (42)
45 (45)
48 (48)
52 (52)
55 (55)
58 (58)
61 (61)

64 (64)

Note: *1 For multiple connection of 16 HP systems and above, the outdoor unit multi connection
piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity,
200% for single outdoor units, 160% for double outdoor units, and 130% for triple outdoor
units.
*3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units.
10

General Information

Si34-804_C

Capacity Range

Indoor unit connection capacity


Normal type (Space saving type)

Type

Single
outdoor
units

Double
outdoor
units

Triple
outdoor
units

HP

5
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54

Capacity
index

Model name

125
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1,000
1,050
1,100
1,150
1,200
1,250
1,300
1,350

RXQ5PA
RXQ8PA
RXQ10PA
RXQ12PA
RXQ14PA
RXQ16PA
RXQ18PA
RXQ20PA
RXQ22PA
RXQ24PA
RXQ26PA
RXQ28PA
RXQ30PA
RXQ32PA
RXQ34PA
RXQ36PA
RXQ38PA
RXQ40PA
RXQ42PA
RXQ44PA
RXQ46PA
RXQ46PA
RXQ50PA
RXQ52PA
RXQ54PA

Min.
combination
ratio

50%

Types of connected indoor units


Including FXFQ25 at least
FXDQ, FXMQ-P, FXAQ
one unit
Max.
Max. number of
Max.
Max. number of
combination
connectable
combination
connectable
ratio
indoor units
ratio
indoor units
12
8
20
13
25
16
30
19
35
22
40
26
45
29
50
32
55
35
60
39
42
45
48
200%
130%
52
55
58
61
64

64

Other indoor unit models


Max.
combination
ratio

200%

160%

Max. number of
connectable
indoor units
12
20
25
30
35
40
45
40
44
48
52
56
60
64
61

130%

64

Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced
in all the indoor units.

High COP type (Energy saving type)

Type

Double
outdoor units

Triple
outdoor
units

HP

16
18
24
26
28
30
32
34
36
38
40
42
44
46
48
50

Capacity
index

Model name

400
450
600
650
700
750
800
850
900
950
1,000
1,050
1,100
1,150
1,200
1,250

RXQ16PAH
RXQ18PAH
RXQ24PAH
RXQ26PAH
RXQ28PAH
RXQ30PAH
RXQ32PAH
RXQ34PAH
RXQ36PAH
RXQ38PAH
RXQ40PAH
RXQ42PAH
RXQ44PAH
RXQ46PAH
RXQ46PAH
RXQ50PAH

Min.
combination
ratio

50%

Types of connected indoor units


Including FXFQ25 at least
FXDQ, FXMQ-P, FXAQ
one unit
Max.
Max. number of
Max.
Max. number of
combination
connectable
combination
connectable
ratio
indoor units
ratio
indoor units
40
26
45
29
60
39
42
45
48
52
55
200%
130%
58
64
61

64

Other indoor unit models


Max.
combination
ratio
160%

130%

Max. number of
connectable
indoor units
32
36
39
42
45
48
52
55
58
61

64

Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced
in all the indoor units.

General Information

11

Si34-804_C

Part 2
Specifications
1. Specifications ........................................................................................13
1.1 Outdoor Units .........................................................................................13
1.2 Indoor Units ............................................................................................34

12

Specifications

Si34-804_C

Specifications

1. Specifications
1.1

Outdoor Units

Cooling Only 50Hz Normal Series (Space Saving Series) <RXQ-PA>


Model Name
kcal / h

RXQ5PAY1
12,100

RXQ8PAY1
19,400

Btu / h

48,100

76,800

kW

14.1

22.5

kW

14.0

22.4

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

1680635765
Cross Fin Coil

1680930765
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


13.34

Hermetically Sealed Scroll Type


16.90

Number of Revolutions

r/min

6300

7980

Motor OutputNumber
of Units

kW

Starting Method
Type
Fan

2.21

3.61

Soft Start
Propeller Fan

Soft Start
Propeller Fan
0.751

Motor Output

kW

0.351

Airflow Rate

m/min

95

180

Direct Drive

Direct Drive

Drive

9.5 (Brazing Connection)

9.5 (Brazing Connection)

15.9 (Brazing Connection)

19.1 (Brazing Connection)

kg

160
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector

205
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector

Capacity Control
Refrigerant Name

28~100
R-410A

20~100
R-410A

Refrigerant

kg

Connecting
Pipes

Liquid Pipe
Gas Pipe

mm
mm

Product Mass (Machine weight)


Safety Devices

Charge
Control

Refrigerator Oil

6.2

7.2

Electronic Expansion Valve

Electronic Expansion Valve

Refer to the Nameplate of Compressor

Standard Accessories

Installation Manual, Operation Manual, Clamps

Drawing No.

C: 4D061669A

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D061687A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

difference : 0m.

The Reference Number


C~: Partly corrected drawings.
J~: Original drawing is Japanese
V~: Printing Convenience

Specifications

13

Specifications

Si34-804_C

Model Name

RXQ10PAY1
24,300

29,000

Btu / h

96,200

115,000

kW

28.2

33.7

kW

28.0

33.5

mm

Ivory White (5Y7.5/1)


1680930765

Ivory White (5Y7.5/1)


16801240765

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

m/h

13.34+10.53

13.34+10.53

r/min

6300, 2900

6300, 2900

Motor OutputNumber
of Units

kW

(1.4+4.5)1

(1.8+4.5)1

Type
Motor Output

kW

Airflow Rate

m/min

Soft Start

Soft Start

Propeller Fan
0.751

Propeller Fan
0.352

185

233

Direct Drive

Direct Drive

Liquid Pipe

mm

9.5 (Brazing Connection)

12.7 (Brazing Connection)

Gas Pipe

mm

22.2 (Brazing Connection)

28.6 (Brazing Connection)

kg

249

285

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant

Cross Fin Coil


Hermetically Sealed Scroll Type

Number of Revolutions

Drive
Connecting
Pipes

Cross Fin Coil


Hermetically Sealed Scroll Type

Displacement

Starting Method

Fan

RXQ12PAY1

kcal / h

Refrigerant Name
Charge
Control

Refrigerator Oil

14~100

14~100

kg

R-410A
7.9

R-410A
9.5

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Installation Manual, Operation Manual, Connection Pipes,


Clamps
C: 4D061688A

Standard Accessories
Drawing No.

Installation Manual, Operation Manual, Connection Pipes,


Clamps
C: 4D061689A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

14

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name

RXQ14PAY1
34,600

39,000

Btu / h

137,000

155,000

kW

40.2

45.3

kW

40.0

45.0

mm

Ivory White (5Y7.5/1)


16801240765

Ivory White (5Y7.5/1)


16801240765

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

m/h

13.34+10.53+10.53

13.34+10.53+10.53

r/min

6300, 2900, 2900

6300, 2900, 2900

Motor OutputNumber
of Units

kW

(1.4+4.5+4.5)1

(2.7+4.5+4.5)1

Type
Motor Output

kW

Airflow Rate

m/min

Soft Start

Soft Start

Propeller Fan
0.352

Propeller Fan
0.352

233

233

Direct Drive

Direct Drive

Liquid Pipe

mm

12.7 (Brazing Connection)

12.7 (Brazing Connection)

Gas Pipe

mm

28.6 (Brazing Connection)

28.6 (Brazing Connection)

kg

329

329

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant

Cross Fin Coil


Hermetically Sealed Scroll Type

Number of Revolutions

Drive
Connecting
Pipes

Cross Fin Coil


Hermetically Sealed Scroll Type

Displacement

Starting Method

Fan

RXQ16PAY1

kcal / h

Refrigerant Name
Charge
Control

Refrigerator Oil

10~100

10~100

kg

R-410A
11.3

R-410A
11.5

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Installation Manual, Operation Manual, Connection Pipes,


Clamps
C: 4D061690A

Standard Accessories
Drawing No.

Installation Manual, Operation Manual, Connection Pipes,


Clamps
C: 4D061691A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ18PAY1

RXQ20PAY1

Model Name (Independent Unit)

kcal / h

42,400

RXQ8PAY1+RXQ12PAY1
48,300

Btu / h

168,000

192,000

kW

49.3

56.2

kW

49.0

55.9

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

16801240765
Cross Fin Coil

(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(16.90)+(13.34+10.53)

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


16.90+10.53+10.53

Number of Revolutions

r/min

7980, 2900, 2900

(7980), (6300, 2900)

Motor OutputNumber
of Units

kW

(2.8+4.5+4.5)1

(3.61)+((1.8+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan
(0.751)+(0.352)

Starting Method
Type
Fan

Motor Output

kW

0.752

Airflow Rate

m/min

239

180+233

Liquid Pipe

mm

Direct Drive
15.9 (Brazing Connection)

Direct Drive
15.9 (Brazing Connection)

Gas Pipe

mm

28.6 (Brazing Connection)

28.6 (Brazing Connection)

kg

341

205+285

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

9~100
R-410A

8~100
R-410A

Refrigerant

kg

11.7
Electronic Expansion Valve

7.2+9.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories
Drawing No.

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

C: 4D061692A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

16

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ22PAY1

RXQ24PAY1

Model Name (Independent Unit)


kcal / h

RXQ10PAY1+RXQ12PAY1
53,200

RXQ8PAY1+RXQ16PAY1
58,300

Btu / h

211,000

231,000

kW

61.9

67.8

kW

61.5

67.4

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(16801240765)
Cross Fin Coil

(1680930765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type


(13.34+10.53)+(13.34+10.53)

Hermetically Sealed Scroll Type


(16.90)+(13.34+10.53+10.53)

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Number of Revolutions

r/min

(6300, 2900)+(6300, 2900)

(7980)+(6300, 2900, 2900)

Motor OutputNumber
of Units

kW

((1.4+4.5)1)+((1.8+4.5)1)

(3.61)+((2.7+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan
(0.751)+(0.352)

Starting Method
Type
Fan

Motor Output

kW

(0.751)+(0.352)

Airflow Rate

m/min

185+233

180+233

Liquid Pipe

mm

Direct Drive
15.9 (Brazing Connection)

Direct Drive
15.9 (Brazing Connection)

Gas Pipe

mm

28.6 (Brazing Connection)

34.9 (Brazing Connection)

kg

249+285

205+329

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

7~100
R-410A

6~100
R-410A

Refrigerant

kg

7.9+9.5
Electronic Expansion Valve

7.2+11.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

17

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ26PAY1

RXQ28PAY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ18PAY1
61,700

RXQ10PAY1+RXQ18PAY1
66,700

Btu / h

250,000

264,000

kW

71.8

77.5

kW

71.4

77.0

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(16801240765)
Cross Fin Coil

(1680930765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


(16.90)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(13.34+10.53)+(16.90+10.53+10.53)

Number of Revolutions

r/min

(7980)+(7980, 2900, 2900)

(6300, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

(3.61)+((2.8+4.5+4.5)1)

((1.4+4.5)1)+((2.8+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan
(0.751)+(0.752)

Starting Method
Type
Fan

Motor Output

kW

(0.751)+(0.752)

Airflow Rate

m/min

180+239

185+239

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

Direct Drive
19.1 (Brazing Connection)

Gas Pipe

mm

34.9 (Brazing Connection)

34.9 (Brazing Connection)

kg

205+341

249+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

6~100
R-410A

5~100
R-410A

Refrigerant

kg

7.2+11.7
Electronic Expansion Valve

7.9+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

18

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ30PAY1

RXQ32PAY1

Model Name (Independent Unit)


kcal / h

RXQ12PAY1+RXQ18PAY1
71,400

RXQ16PAY1+RXQ16PAY1
77,800

Btu / h

283,000

309,000

kW

83.0

90.5

kW

82.5

90.0

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


(13.34+10.53)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(13.34+10.53+10.53)+(13.34+10.53+10.53)

Number of Revolutions

r/min

(6300, 2900)+(7980, 2900, 2900)

(6300, 2900, 2900)+(6300, 2900, 2900)

Motor OutputNumber
of Units

kW

((1.8+4.5)1)+((2.8+4.5+4.5)1)

((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan
(0.352)+(0.352)

Starting Method
Type
Fan

Motor Output

kW

(0.352)+(0.752)

Airflow Rate

m/min

233+239

233+233

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

Direct Drive
19.1 (Brazing Connection)

Gas Pipe

mm

34.9 (Brazing Connection)

34.9 (Brazing Connection)

kg

285+341

329+329

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

5~100
R-410A

5~100
R-410A

Refrigerant

kg

9.5+11.7
Electronic Expansion Valve

11.5+11.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

19

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ34PAY1

RXQ36PAY1

Model Name (Independent Unit)


kcal / h

RXQ16PAY1+RXQ18PAY1
81,400

RXQ18PAY1+RXQ18PAY1
85,100

Btu / h

323,000

338,000

kW

94.6

99.0

kW

94.0

98.0

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


(13.34+10.53+10.53)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(16.90+10.53+10.53)+(16.90+10.53+10.53)

Number of Revolutions

r/min

(6300, 2900, 2900)+(7980, 2900, 2900)

(7980, 2900, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

((2.7+4.5+4.5)1)+((2.8+4.5+4.5)1)

((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan
(0.752)+(0.752)

Starting Method
Type
Fan

Motor Output

kW

(0.352)+(0.752)

Airflow Rate

m/min

233+239

239+239

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

Direct Drive
19.1 (Brazing Connection)

Gas Pipe

mm

34.9 (Brazing Connection)

41.3 (Brazing Connection)

kg

329+341

341+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

5~100
R-410A

4~100
R-410A

Refrigerant

kg

11.5+11.7
Electronic Expansion Valve

11.7+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor

Standard Accessories

Installation Manual, Operation Manual, Connection Pipes,


Clamps

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

20

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ38PAY1

RXQ40PAY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ12PAY1+RXQ18PAY1
91,200

RXQ8PAY1+RXQ16PAY1+RXQ16PAY1
97,200

Btu / h

362,000

386,000

kW

106

113

kW

105

112

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


(16.90)+(13.34+10.53)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(16.90)+(13.34+10.53+10.53)+(13.34+10.53+10.53)

Number of Revolutions

r/min

(7980)+(6300, 2900)+(7980, 2900, 2900)

(7980)+(6300, 2900, 2900)+(6300, 2900, 2900)

Motor OutputNumber
of Units

kW

(3.61)+((1.8+4.5)1)+((2.8+4.5+4.5)1)

(3.61)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan

Starting Method
Type
Fan

Motor Output

kW

(0.751)+(0.352)+(0.752)

(0.751)+(0.352)+(0.352)

Airflow Rate

m/min

180+233+239

180+233+233

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

205+285+341

205+329+329

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices

Direct Drive

Capacity Control
Refrigerant Name

4~100
R-410A

4~100
R-410A

Refrigerant

kg

7.2+9.5+11.7
Electronic Expansion Valve

7.2+11.5+11.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

21

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ42PAY1

RXQ44PAY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ16PAY1+RXQ18PAY1
101,000

RXQ8PAY1+RXQ18PAY1+RXQ18PAY1
104,000

Btu / h

399,000

413,000

kW

117

121

kW

116

120

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


(16.90)+(13.34+10.53+10.53)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(16.90)+(16.90+10.53+10.53)+(16.90+10.53+10.53)

Number of Revolutions

r/min

(7980)+(6300, 2900, 2900)+(7980, 2900, 2900)

(7980)+(7980, 2900, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

(3.61)+((2.7+4.5+4.5)1)+((2.8+4.5+4.5)1)

(3.61)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan

Starting Method
Type
Fan

Motor Output

kW

(0.751)+(0.352)+(0.752)

(0.751)+(0.752)+(0.752)

Airflow Rate

m/min

180+233+239

180+239+239

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

205+329+341

205+341+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices

Direct Drive

Capacity Control
Refrigerant Name

4~100
R-410A

4~100
R-410A

Refrigerant

kg

7.2+11.5+11.7
Electronic Expansion Valve

7.2+11.7+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

22

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ46PAY1

RXQ48PAY1

Model Name (Independent Unit)


kcal / h

RXQ10PAY1+RXQ18PAY1+RXQ18PAY1
109,000

RXQ12PAY1+RXQ18PAY1+RXQ18PAY1
114,000

Btu / h

433,000

454,000

kW

127

133

kW

126

132

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

Type
Displacement

m/h

Hermetically Sealed Scroll Type


Hermetically Sealed Scroll Type
(13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53) (13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)

Number of Revolutions

r/min

(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

((1.4+4.5)1)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

((1.8+4.5)1)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

Soft Start
Propeller Fan

Soft Start
Propeller Fan

Starting Method
Type
Fan

Motor Output

kW

(0.751)+(0.752)+(0.752)

(0.352)+(0.752)+(0.752)

Airflow Rate

m/min

185+239+239

233+239+239

Liquid Pipe

mm

Direct Drive
19.1 (Brazing Connection)

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

249+341+341

285+341+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Drive
Connecting
Pipes

Product Mass (Machine Weight)


Safety Devices

Direct Drive

Capacity Control
Refrigerant Name

3~100
R-410A

3~100
R-410A

Refrigerant

kg

7.9+11.7+11.7
Electronic Expansion Valve

9.5+11.7+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

23

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ50PAY1

RXQ52PAY1

Model Name (Independent Unit)


kcal / h

RXQ14PAY1+RXQ18PAY1+RXQ18PAY1
120,000

RXQ16PAY1+RXQ18PAY1+RXQ18PAY1
124,000

Btu / h

474,000

491,000

kW

139

144

kW

138

143

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

m/h

Hermetically Sealed Scroll Type


(13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)

Hermetically Sealed Scroll Type


(13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)

r/min

(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

((1.4+4.5+4.5)1)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

((2.7+4.5+4.5)1)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


Casing Color
Dimensions: (HWD)
Heat Exchanger

mm

Type
Displacement
Comp.

Number of Revolutions
Motor OutputNumber
of Units
Starting Method

Soft Start

Soft Start

Propeller Fan

Propeller Fan

kW
m/min

(0.352)+(0.752)+(0.752)
233+239+239

(0.352)+(0.752)+(0.752)
233+239+239

Drive
Liquid Pipe

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

329+341+341

329+341+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Type
Fan

Connecting
Pipes

Motor Output
Airflow Rate

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

3~100
R-410A

3~100
R-410A

Refrigerant

kg

11.3+11.7+11.7
Electronic Expansion Valve

11.5+11.7+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

difference : 0m.

24

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ54PAY1

Model Name (Independent Unit)


kcal / h

RXQ18PAY1+RXQ18PAY1+RXQ18PAY1
127,000

Btu / h

505,000

kW

148

1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

kW

Casing Color
Dimensions: (HWD)
Heat Exchanger

Comp.

mm

m/h

Hermetically Sealed Scroll Type


(16.90+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)

Number of Revolutions

r/min

(7980, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)+((2.8+4.5+4.5)1)
Soft Start
Propeller Fan

Motor Output

kW

(0.752)+(0.752)+(0.752)

Airflow Rate

m/min

239+239+239

Liquid Pipe

mm

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

Drive
Connecting
Pipes

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

Type
Displacement

Starting Method
Type
Fan

147
Ivory White (5Y7.5/1)

Direct Drive

Product Mass (Machine Weight)

kg

Safety Devices

341+341+341
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector

Capacity Control
Refrigerant Name

Refrigerant

kg

Charge
Control

3~100
R-410A
11.7+11.7+11.7
Electronic Expansion Valve

Refrigerator Oil
Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes, Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

25

Specifications

Si34-804_C

Cooling Only 50Hz High COP Series (Energy Saving Series) <RXQ-PAH>
Model Name

RXQ16PAHY1

RXQ18PAHY1

kcal / h

RXQ8PAY1+RXQ8PAY1
38,800

RXQ8PAY1+RXQ10PAY1
43,600

Btu / h

154,000

173,000

kW

45.1

50.7

kW

44.8

50.4

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(1680930765)
Cross Fin Coil

(1680930765)+(1680930765)
Cross Fin Coil

Model Name (Independent Unit)


1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger

mm

Type

Comp.

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(16.90)+(16.90)

(16.90)+(13.34+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(7980)+(7980)

(7980)+(6300, 2900)

kW

(3.61)+(3.61)

(3.61)+((1.4+4.5)1)

Starting Method
Type
Fan

Connecting
Pipes

Soft start

Propeller Fan

Propeller Fan
(0.751)+(0.751)

Motor Output

kW

(0.751)+(0.751)

Airflow Rate

m/min

180+180

180+185

Direct Drive

Direct Drive

Drive
Liquid Pipe

mm

12.7 (Brazing Connection)

15.9 (Brazing Connection)

Gas Pipe

mm

28.6 (Brazing Connection)

28.6 (Brazing Connection)

kg

205+205

205+249

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Product Mass (Machine weight)

10~100

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector
8~100

kg

R-410A
7.2+7.2

R-410A
7.2+7.9

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Electronic Expansion Valve


Refer to the Nameplate of Compressor

Safety Devices
Capacity Control
Refrigerant

Soft start

Refrigerant Name
Charge
Control

Refrigerator Oil

Installation Manual, Operation Manual, Connection Pipes,


Clamps

Standard Accessories

Installation Manual, Operation Manual, Connection Pipes,


Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

26

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ24PAHY1

RXQ26PAHY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ8PAY1+RXQ8PAY1
58,100

RXQ8PAY1+RXQ8PAY1+RXQ10PAY1
63,000

Btu / h

231,000

250,000

kW

67.6

73.2

kW

67.2

72.8

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(1680930765)+(1680930765)
Cross Fin Coil

(1680930765)+(1680930765)+(1680930765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger

mm

Type

Comp.

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(16.90)+(16.90)+(16.90)

(16.90)+(16.90)+(13.34+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(7980)+(7980)+(7980)

(7980)+(7980)+(6300, 2900)

kW

(3.61)+(3.61)+(3.61)

(3.61)+(3.61)+((1.4+4.5)1)

Starting Method
Type
Fan

Connecting
Pipes

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.751)+(0.751)+(0.751)

(0.751)+(0.751)+(0.751)

Airflow Rate

m/min

180+180+180

180+180+185

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

15.9 (Brazing Connection)

19.1 (Brazing Connection)

mm

34.9 (Brazing Connection)

34.9 (Brazing Connection)

kg

205+205+205

205+205+249

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

7~100
R-410A

6~100
R-410A

Refrigerant

kg

7.2+7.2+7.2
Electronic Expansion Valve

7.2+7.2+7.9
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

27

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ28PAHY1

RXQ30PAHY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ8PAY1+RXQ12PAY1
67,800

RXQ8PAY1+RXQ10PAY1+RXQ12PAY1
72,600

Btu / h

269,000

288,000

kW

78.8

84.4

kW

78.3

83.9

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(1680930765)+(1680930765)+(16801240765)
Cross Fin Coil

(1680930765)+(1680930765)+(16801240765)
Cross Fin Coil

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger

mm

Type

Comp.

(16.90)+(13.34+10.53)+(13.34+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(7980)+(7980)+(6300, 2900)

(7980)+(6300, 2900)+(6300, 2900)

kW

(3.61)+(3.61)+((1.8+4.5)1)

(3.61)+((1.4+4.5)1)+((1.8+4.5)1)

Type

Connecting
Pipes

Hermetically Sealed Scroll Type

(16.90)+(16.90)+(13.34+10.53)

m/h

Starting Method

Fan

Hermetically Sealed Scroll Type

Displacement

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.751)+(0.751)+(0.352)

(0.751)+(0.751)+(0.352)

Airflow Rate

m/min

180+180+233

180+185+233

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

mm

34.9 (Brazing Connection)

34.9 (Brazing Connection)

kg

205+205+285

205+249+285

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

6~100
R-410A

5~100
R-410A

Refrigerant

kg

7.2+7.2+9.5
Electronic Expansion Valve

7.2+7.9+9.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

28

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ32PAHY1

RXQ34PAHY1

Model Name (Independent Unit)


kcal / h

RXQ8PAY1+RXQ12PAY1+RXQ12PAY1
77,300

RXQ10PAY1+RXQ12PAY1+RXQ12PAY1
82,200

Btu / h

307,000

326,000

kW

89.9

95.6

kW

89.4

95.0

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

mm

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(16.90)+(13.34+10.53)+(13.34+10.53)

(13.34+10.53)+(13.34+10.53)+(13.34+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(7980)+(6300, 2900)+(6300, 2900)

(6300, 2900)+(6300, 2900)+(6300, 2900)

kW

(3.61)+((1.8+4.5)1)+((1.8+4.5)1)

((1.4+4.5)1)+((1.8+4.5)1)+((1.8+4.5)1)

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

Starting Method
Type
Fan

Connecting
Pipes

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.751)+(0.352)+(0.352)

(0.751)+(0.352)+(0.352)

Airflow Rate

m/min

180+233+233

185+233+233

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

mm

34.9 (Brazing Connection)

34.9 (Brazing Connection)

kg

205+285+285

249+285+285

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

5~100
R-410A

5~100
R-410A

Refrigerant

kg

7.2+9.5+9.5
Electronic Expansion Valve

7.9+9.5+9.5
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

29

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ36PAHY1

RXQ38PAHY1

Model Name (Independent Unit)


kcal / h

RXQ12PAY1+RXQ12PAY1+RXQ12PAY1
87,700

RXQ12PAY1+RXQ12PAY1+RXQ14PAY1
92,900

Btu / h

348,000

368,000

kW

102

108

kW

101

107

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

mm

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(13.34+10.53)+(13.34+10.53)+(13.34+10.53)

(13.34+10.53)+(13.34+10.53)+(13.34+10.53+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(6300, 2900)+(6300, 2900)+(6300, 2900)

(6300, 2900)+(6300, 2900)+(6300, 2900, 2900)

kW

((1.8+4.5)1)+((1.8+4.5)1)+((1.8+4.5)1)

((1.8+4.5)1)+((1.8+4.5)1)+((1.4+4.5+4.5)1)

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

Starting Method
Type
Fan

Connecting
Pipes

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.352)+(0.352)+(0.352)

(0.352)+(0.352)+(0.352)

Airflow Rate

m/min

233+233+233

233+233+233

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

285+285+285

285+285+329

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

5~100
R-410A

4~100
R-410A

Refrigerant

kg

9.5+9.5+9.5
Electronic Expansion Valve

9.5+9.5+11.3
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

30

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ40PAHY1

RXQ42PAHY1

Model Name (Independent Unit)


kcal / h

RXQ12PAY1+RXQ12PAY1+RXQ16PAY1
97,200

RXQ12PAY1+RXQ12PAY1+RXQ18PAY1
101,000

Btu / h

386,000

399,000

kW

113

117

kW

112

116

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

mm

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(13.34+10.53)+(13.34+10.53)+(13.34+10.53+10.53)

(13.34+10.53)+(13.34+10.53)+(16.90+10.53+10.53)

Number of Revolutions
Motor OutputNumber
of Units

r/min

(6300, 2900)+(6300, 2900)+(6300, 2900, 2900)

(6300, 2900)+(6300, 2900)+(7980, 2900, 2900)

kW

((1.8+4.5)1)+((1.8+4.5)1)+((2.7+4.5+4.5)1)

((1.8+4.5)1)+((1.8+4.5)1)+((2.8+4.5+4.5)1)

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

Starting Method
Type
Fan

Connecting
Pipes

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.352)+(0.352)+(0.352)

(0.352)+(0.352)+(0.752)

Airflow Rate

m/min

233+233+233

233+233+239

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

285+285+329

285+285+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

4~100
R-410A

4~100
R-410A

Refrigerant

kg

9.5+9.5+11.5
Electronic Expansion Valve

9.5+9.5+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

31

Specifications

Si34-804_C

Model Name (Combination Unit)

RXQ44PAHY1

RXQ46PAHY1

Model Name (Independent Unit)


kcal / h

RXQ12PAY1+RXQ16PAY1+RXQ16PAY1
108,000

RXQ12PAY1+RXQ16PAY1+RXQ18PAY1
111,000

Btu / h

427,000

440,000

kW

125

129

kW

124

128

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger

mm

Type

Comp.

Displacement

m/h

Number of Revolutions
Motor OutputNumber
of Units

r/min

(6300, 2900)+(6300, 2900, 2900)+(6300, 2900, 2900)

(6300, 2900)+(6300, 2900, 2900)+(7980, 2900, 2900)

kW

((1.8+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)

((1.8+4.5)1)+((2.7+4.5+4.5)1)+((2.8+4.5+4.5)1)

Starting Method
Type
Fan

Connecting
Pipes

(13.34+10.53)+(13.34+10.53+10.53)+(13.34+10.53+10.53) (13.34+10.53)+(13.34+10.53+10.53)+(16.90+10.53+10.53)

Soft start

Soft start

Propeller Fan

Propeller Fan

Motor Output

kW

(0.352)+(0.352)+(0.352)

(0.352)+(0.352)+(0.752)

Airflow Rate

m/min

233+233+233

233+233+239

Drive
Liquid Pipe
Gas Pipe

Product Mass (Machine Weight)

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

285+329+329

285+329+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

Safety Devices
Capacity Control
Refrigerant Name

4~100
R-410A

3~100
R-410A

Refrigerant

kg

9.5+11.5+11.5
Electronic Expansion Valve

9.5+11.5+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

32

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Model Name (Combination Unit)

RXQ48PAHY1

RXQ50PAHY1

Model Name (Independent Unit)


kcal / h

RXQ16PAY1+RXQ16PAY1+RXQ16PAY1
117,000

RXQ16PAY1+RXQ16PAY1+RXQ18PAY1
120,000

Btu / h

464,000

478,000

kW

136

140

kW

135

139

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

mm

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

Displacement

m/h

(13.34+10.53+10.53)+(13.34+10.53+10.53)+(13.34+10.53
+10.53)

(13.34+10.53+10.53)+(13.34+10.53+10.53)+(16.90+10.53
+10.53)

Number of Revolutions

r/min

(6300, 2900, 2900)+(6300, 2900, 2900)+(6300, 2900, 2900)

(6300, 2900, 2900)+(6300, 2900, 2900)+(7980, 2900, 2900)

Motor OutputNumber
of Units

kW

((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)

((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((2.8+4.5+4.5)1)

Soft start
Propeller Fan

Soft start
Propeller Fan

kW
m/min

(0.352)+(0.352)+(0.352)
233+233+233

(0.352)+(0.352)+(0.752)
233+233+239

Drive
Liquid Pipe

Direct Drive

Direct Drive

mm

19.1 (Brazing Connection)

19.1 (Brazing Connection)

Gas Pipe

mm

41.3 (Brazing Connection)

41.3 (Brazing Connection)

kg

329+329+329

329+329+341

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

High Pressure Switch, Fan Driver Overload Protector, Over


Current Relay, Inverter Overload Protector

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type

Comp.

Starting Method
Type
Fan

Connecting
Pipes

Motor Output
Airflow Rate

Product Mass (Machine Weight)


Safety Devices
Capacity Control
Refrigerant Name

3~100
R-410A

3~100
R-410A

Refrigerant

kg

11.5+11.5+11.5
Electronic Expansion Valve

11.5+11.5+11.7
Electronic Expansion Valve

Charge
Control

Refrigerator Oil

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Standard Accessories

Refer to the Nameplate of Compressor


Installation Manual, Operation Manual, Connection Pipes,
Clamps

Drawing No.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level

difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

33

Specifications

1.2

Si34-804_C

Indoor Units

Ceiling Mounted Cassette (Round Flow) Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXFQ25PVE

FXFQ32PVE

FXFQ40PVE

kcal/h

2,500

3,200

4,000

5,000

Btu/h

9,900

12,600

16,000

19,800

kW

2.9

3.7

4.7

5.8

kW

2.8

3.6

4.5

5.6

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

246840840
261.2

246840840
261.2

246840840
261.2

246840840
261.2

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (HH/H/L)

0.267

0.267

0.267

0.267

QTS48C15M

QTS48C15M

QTS48C15M

QTS48C15M

Turbo Fan

Turbo Fan

Turbo Fan

Turbo Fan

561

561

561

561

m/min
cfm

13/11.5/10
459/406/353

13/11.5/10
459/406/353

15/13/11
530/459/388

16/13.5/11
565/477/388

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Mass (Weight)

Polyurethane Form

Polyurethane Form

Polyurethane Form

6.4 (Flare Connection)

6.4 (Flare Connection)

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

VP25
External Dia. 32
Internal Dia. 25
19.5

VP25
External Dia. 32
Internal Dia. 25
19.5

VP25
External Dia. 32
Internal Dia. 25
19.5

Dia. 32
( External
Internal Dia. 25 )

dBA

VP25

30/28.5/27
Fuse

31/29/27
Fuse

32/29.5/27
Fuse

Electronic Expansion Valve


R-410A VRV PA Series

Electronic Expansion Valve


R-410A VRV PA Series

Electronic Expansion Valve


R-410A VRV PA Series

Electronic Expansion Valve


R-410A VRV PA Series

BYCP125K-W1

BYCP125K-W1

BYCP125K-W1

BYCP125K-W1

mm

Fresh White
50950950

Fresh White
50950950

Fresh White
50950950

Fresh White
50950950

kg

Resin Net
(with Mold Resistant)
5.5

Resin Net
(with Mold Resistant)
5.5

Resin Net
(with Mold Resistant)
5.5

Resin Net
(with Mold Resistant)
5.5

Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

Air Filter

C : 3D060255A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level

difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

34

19.5

30/28.5/27
Fuse

Model

Drawing No.

Direct Drive
Microprocessor Thermostat
for Cooling and Heating

6.4 (Flare Connection)

Refrigerant Control
Connectable Outdoor Unit

Standard Accessories

Direct Drive
Microprocessor Thermostat
for Cooling and Heating

Polyurethane Form

Safety Devices

Weight

Direct Drive
Microprocessor Thermostat
for Cooling and Heating

6.4 (Flare Connection)

kg

Panel Color
Dimensions: (HWD)

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
mm

mm

4 Sound Level (HH/H/L) (220-240V)

Decoration
Panels
(Option)

FXFQ50PVE

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Ceiling Mounted Cassette (Round Flow) Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXFQ63PVE

FXFQ80PVE

FXFQ100PVE

FXFQ125PVE

kcal/h

6,300

8,000

10,000

12,500

Btu/h

24,900

31,700

39,600

49,500

kW

7.3

9.3

11.6

14.5

kW

7.1

9.0

11.2

14.0

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

246840840
2101.2

246840840
2101.2

288840840
2121.2

288840840
2121.2

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (HH/H/L)

0.535

0.535

QTS48C15M

QTS48C15M

Turbo Fan

Turbo Fan

Turbo Fan

Turbo Fan

561

561

1201

1201

19/16.5/13.5

21/18/15

32/26/20

33/28/22.5

cfm

671/583/477

742/636/530

1,130/918/706

1,165/989/794

Drive

Direct Drive

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Sound Absorbing Thermal Insulation Material

Polyurethane Form

Polyurethane Form

Polyurethane Form

Polyurethane Form

Liquid Pipes

mm

9.5 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

15.9 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

mm

VP25
External Dia. 32
Internal Dia. 25

VP25
External Dia. 32
Internal Dia. 25

VP25
External Dia. 32
Internal Dia. 25

Dia. 32
( External
Internal Dia. 25 )

Drain Pipe
Mass (Weight)
4 Sound Level (HH/H/L) (220-240V)

VP25

22

22

25

25

36/33.5/31

43/37.5/32

44/39/34

Fuse
Electronic Expansion Valve

Fuse
Electronic Expansion Valve

Fuse
Electronic Expansion Valve

Fuse
Electronic Expansion Valve

R-410A VRV PA Series

R-410A VRV PA Series

R-410A VRV PA Series

R-410A VRV PA Series

BYCP125K-W1

BYCP125K-W1

BYCP125K-W1

BYCP125K-W1

Fresh White
50950950

Fresh White
50950950

Fresh White
50950950

Fresh White
50950950

Resin Net
(with Mold Resistant)

Resin Net
(with Mold Resistant)

Resin Net
(with Mold Resistant)

Resin Net
(with Mold Resistant)

5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.

mm

Air Filter
kg

Standard Accessories

34/31/28

Model

Weight

kg

Connectable Outdoor Unit


Panel Color
Dimensions: (HWD)

dBA

Safety Devices
Refrigerant Control

Decoration
Panels
(Option)

0.446
QTS48C15M

m/min

Temperature Control

Piping
Connections

0.446
QTS48C15M

Drawing No.

C : 3D060255A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level

difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level

difference : 0 m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

35

Specifications

Si34-804_C

Ceiling Mounted Cassette (Compact Multi Flow) Type


Model

FXZQ20MVE

FXZQ25MVE

FXZQ32MVE

1 phase, 220-240/220V, 50/60Hz

1 phase, 220-240/220V, 50/60Hz

1 phase, 220-240/220V, 50/60Hz

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

Power supply
1 3 Cooling capacity (19.5CWB)
2 3 Cooling capacity (19.0CWB)

Casing / Colour

Galvanized steel plate

Galvanized steel plate

Galvanized steel plate

mm

286575575

286575575

286575575

mm
m

2101.5
0.269

2101.5
0.269

2101.5
0.269

Model

QTS32C15M

QTS32C15M

QTS32C15M

Type

Turbo fan

Turbo fan

Turbo fan

Dimensions: (HWD)
Coil (Cross
fin coil)

RowsStagesFin pitch
Face area

Motor output
Number of units

551

551

551

Airflow rate (H/L)

m/min
l/s

9.0/7.0
150/116

9.0/7.0
150/116

9.5/7.5
158/125

Fan

cfm
Drive
Temperature control
Sound absorbing thermal insulation material

Piping
connections

318/247

335/265

Direct drive

Direct drive

Microprocessor thermostat for


cooling and heating

Microprocessor thermostat for


cooling and heating

Microprocessor thermostat for


cooling and heating

Foamed polystyrene/
Foamed polyethylene

Foamed polystyrene/
Foamed polyethylene

Foamed polystyrene/
Foamed polyethylene

Liquid pipes

mm

6.4 (Flare connection)

6.4 (Flare connection)

6.4 (Flare connection)

Gas pipes

mm

12.7 (Flare connection)

12.7 (Flare connection)

12.7 (Flare connection)

VP20

VP20

VP20

Drain pipe

mm

dia. 26
( External
Internal dia. 20 )

dia. 26
( External
Internal dia. 20 )

dia. 26
( External
Internal dia. 20 )

Mass (Weight)

kg

4 Sound level (H/L)

Sound power (H)

230V, 50Hz
240V, 50Hz
230V, 50Hz
240V, 50Hz

dB(A)
dB(A)

Safety devices
Refrigerant control
Model
Dimensions: (HWD)

Standard accessories

Drawing No.

18

18

30/25

32/26

32/26

32/26

34/28

47

47

49

49
PC board fuse.
Fan motor thermal protector.
Electronic expansion valve

49
PC board fuse.
Fan motor thermal protector.
Electronic expansion valve

51
PC board fuse.
Fan motor thermal protector.
Electronic expansion valve

BYFQ60B8W1

BYFQ60B8W1

BYFQ60B8W1

White (6.5Y9.5/0.5)

White (6.5Y9.5/0.5)

mm

55700700
Resin net
(with mould resistance)

55700700
Resin net
(with mould resistance)

55700700
Resin net
(with mould resistance)

kg

2.7
Operation manual. Installation manual.
Paper pattern for installation. Drain
hose. Clamp metal. Washer fixing
plate. Sealing pads. Clamps. Screws.
Washer for hanging bracket. Insulation
for fitting.

2.7
Operation manual. Installation manual.
Paper pattern for installation. Drain
hose. Clamp metal. Washer fixing
plate. Sealing pads. Clamps. Screws.
Washer for hanging bracket. Insulation
for fitting.

2.7
Operation manual. Installation manual.
Paper pattern for installation. Drain
hose. Clamp metal. Washer fixing
plate. Sealing pads. Clamps. Screws.
Washer for hanging bracket. Insulation
for fitting.

Air filter
Mass (Weight)

18
30/25

White (6.5Y9.5/0.5)

Panel colour
Decoration
panels
(Option)

318/247
Direct drive

C : 3D038929B

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

36

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Ceiling Mounted Cassette (Compact Multi Flow) Type


Model
Power supply

4,000

5,000

Btu/h

16,000

19,800

kW

4.7

5.8

kW

4.5

5.6

Galvanized steel plate

Galvanized steel plate

mm

286575575

286575575

mm
m

2101.5
0.269

2101.5
0.269

Model

QTS32C15M

QTS32C15M

Type

Turbo fan

Turbo fan

2 3 Cooling capacity (19.0CWB)

Casing / Colour
Dimensions: (HWD)
RowsStagesFin pitch
Face area

Motor output
Number of units

551

551

Airflow rate (H/L)

m/min
l/s

11.0/8.0
183/133

14.0/10.0
233/166

Fan

cfm
Drive
Temperature control
Sound absorbing thermal insulation material

Piping
connections

388/282

493/353

Direct drive

Direct drive

Microprocessor thermostat for cooling and heating


Foamed polystyrene/Foamed polyethylene

Microprocessor thermostat for cooling and heating


Foamed polystyrene/Foamed polyethylene

Liquid pipes

mm

6.4 (Flare connection)

6.4 (Flare connection)

Gas pipes

mm

12.7 (Flare connection)

12.7 (Flare connection)

VP20

VP20

Drain pipe

mm

dia. 26
( External
Internal dia. 20 )

dia. 26
( External
Internal dia. 20 )

Mass (Weight)
4 Sound level (H/L)

Sound power (H)

230V, 50Hz
240V, 50Hz
230V, 50Hz
240V, 50Hz

kg

18

18

dB(A)

36/28
37/29

41/33
42/35

53

58

54
PC board fuse.
Fan motor thermal protector.

59
PC board fuse.
Fan motor thermal protector.

Electronic expansion valve

Electronic expansion valve

dB(A)

Safety devices
Refrigerant control
Model
Decoration
panels
(Option)

FXZQ50MVE
1 phase, 220-240/220V, 50/60Hz

kcal/h
1 3 Cooling capacity (19.5CWB)

Coil (Cross
fin coil)

FXZQ40MVE
1 phase, 220-240/220V, 50/60Hz

Panel colour
Dimensions: (HWD)

mm

Air filter
Mass (Weight)

kg

Standard accessories
Drawing No.

BYFQ60B8W1

BYFQ60B8W1

White (6.5Y9.5/0.5)
55700700

White (6.5Y9.5/0.5)
55700700

Resin net
(with mould resistance)

Resin net
(with mould resistance)

2.7
2.7
Operation manual. Installation manual. Paper pattern for
Operation manual. Installation manual. Paper pattern for
installation. Drain hose. Clamp metal. Washer fixing plate. installation. Drain hose. Clamp metal. Washer fixing plate.
Sealing pads. Clamps. Screws. Washer for hanging
Sealing pads. Clamps. Screws. Washer for hanging
bracket. Insulation for fitting.
bracket. Insulation for fitting.
C : 3D038929B

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

37

Specifications

Si34-804_C

Ceiling Mounted Cassette Type (Double Flow)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXCQ20MVE

FXCQ25MVE

FXCQ32MVE

kcal/h

2,000

2,500

3,200

4,000

Btu/h

7,800

9,900

12,600

16,000

kW

2.3

2.9

3.7

4.7

kW

2.2

2.8

3.6

4.5

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

305775600
2101.5

305775600
2101.5

305775600
2101.5

305990600
2101.5

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

20.100

20.100

20.145

D17K2AB1

D17K2AB1

2D17K1AA1

Sirocco Fan

Sirocco Fan

Sirocco Fan

Sirocco Fan

101

151

151

201

7/5

9/6.5

9/6.5

12/9

cfm

247/177

318/230

318/230

424/318

Drive

Sound Absorbing Thermal Insulation Material

Direct Drive

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

VP25

VP25

VP25

VP25

Drain Pipe

mm

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Machine Weight (Mass)


4 Sound Level (H/L) (220V)

kg

26

26

26

31

dBA

32/27

34/28

34/28

34/29

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve
R-410A PA Series

Safety Devices
Refrigerant Control
Connectable outdoor unit

Decoration
Panels
(Option)

20.100
D17K2AA1

m/min

Temperature Control

Piping
Connections

FXCQ40MVE

R-410A PA Series

R-410A PA Series

R-410A PA Series

Model

BYBC32G-W1

BYBC32G-W1

BYBC32G-W1

BYBC50G-W1

Panel Color

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

mm

531,030680
Resin Net
(with Mold Resistant)

531,030680
Resin Net
(with Mold Resistant)

531,030680
Resin Net
(with Mold Resistant)

531,245680
Resin Net
(with Mold Resistant)

kg

8
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.

Dimensions: (HWD)
Air Filter
Weight

Standard Accessories

Drawing No.

8
8
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation,
Pattern for Installation,
Washer for Hanging
Washer for Hanging
Brackets, Clamp Metal,
Brackets, Clamp Metal,
Drain Hose, Insulation for
Drain Hose, Insulation for
Fitting, Washer Fixing
Fitting, Washer Fixing
Plates, Sealing Pads,
Plates, Sealing Pads,
Clamps, Screws, Washers. Clamps, Screws, Washers.
C : 3D039413

8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.

38

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Ceiling Mounted Cassette Type (Double Flow)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXCQ50MVE

FXCQ63MVE

FXCQ80MVE

FXCQ125MVE

kcal/h

5,000

6,300

8,000

12,500

Btu/h

19,800

24,900

31,700

49,500

kW

5.8

7.3

9.3

14.5

kW

5.6

7.1

9.0

14.0

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

305990600
2101.5

3051,175600
2101.5

3051,665600
2101.5

3051,665600
2101.5

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

20.287

20.287

3D17K2AA1

3D17K2AB1

Sirocco Fan

Sirocco Fan

Sirocco Fan

Sirocco Fan

201

301

501

851

12/9

16.5/13

26/21

33/25

cfm

424/318

582/459

918/741

1,165/883

Drive

Sound Absorbing Thermal Insulation Material

Direct Drive

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Glass Wool/Urethane Foam

Liquid Pipes

mm

6.4 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

VP25

VP25

VP25

VP25

Drain Pipe

mm

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Dia. 32
( External
Internal Dia. 25 )

Machine Weight (Mass)


4 Sound Level (H/L)

kg

32

35

47

48

dBA

34/29

37/32

39/34

44/38

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Fuse, Thermal Protector for


Fan Motor
Electronic Expansion Valve

Safety Devices
Refrigerant Control
Connectable outdoor unit

Decoration
Panels
(Option)

20.184
2D17K2AA1VE

m/min

Temperature Control

Piping
Connections

20.145
2D17K1AA1

R-410A PA Series

R-410A PA Series

R-410A PA Series

R-410A PA Series

Model

BYBC50G-W1

BYBC63G-W1

BYBC125G-W1

BYBC125G-W1

Panel Color

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

mm

531,245680
Resin Net
(with Mold Resistant)

531,430680
Resin Net
(with Mold Resistant)

531,920680
Resin Net
(with Mold Resistant)

531,920680
Resin Net
(with Mold Resistant)

kg

8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.

Dimensions: (HWD)
Air Filter
Weight

Standard Accessories

Drawing No.

9.5
12
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation,
Pattern for Installation,
Washer for Hanging
Washer for Hanging
Brackets, Clamp Metal,
Brackets, Clamp Metal,
Drain Hose, Insulation for
Drain Hose, Insulation for
Fitting, Washer Fixing
Fitting, Washer Fixing
Plates, Sealing Pads,
Plates, Sealing Pads,
Clamps, Screws, Washers. Clamps, Screws, Washers.
C : 3D039413

12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

39

Specifications

Si34-804_C

Ceiling Mounted Cassette Corner Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXKQ25MAVE

FXKQ32MAVE

FXKQ40MAVE

kcal/h

2,500

3,200

4,000

6,300

Btu/h

9,900

12,600

16,000

24,900

kW

2.9

3.7

4.7

7.3

kW

2.8

3.6

4.5

7.1

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

2151,110710
2111.75

2151,110710
2111.75

2151,110710
2111.75

2151,310710
3111.75

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

Machine Weight (Mass)

0.226
4D12H1AJ1V1

Sirocco Fan

Sirocco Fan

Sirocco Fan

Sirocco Fan

151

151

201

451

11/9

11/9

13/10

18/15

388/318

459/353

635/530

Direct Drive

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Microprocessor Thermostat
for Cooling and Heating

Polyethylene Foam

Polyethylene Foam

Polyethylene Foam

Polyethylene Foam

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

mm

VP25
External Dia. 32
Internal Dia. 25

VP25
External Dia. 32
Internal Dia. 25

VP25
External Dia. 32
Internal Dia. 25

Dia. 32
( External
Internal Dia. 25 )

31

31

34

38/33

40/34

42/37

Fuse,
Fuse,
Fuse,
Thermal Fuse for Fan Motor Thermal Fuse for Fan Motor Thermal Fuse for Fan Motor
Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

R-410A PA Series

R-410A PA Series

R-410A PA Series

BYK45FJW1

BYK45FJW1

BYK45FJW1

BYK71FJW1

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

mm

701,240800
Resin Net
(with Mold Resistant)

701,240800
Resin Net
(with Mold Resistant)

701,240800
Resin Net
(with Mold Resistant)

701,440800
Resin Net
(with Mold Resistant)

kg

8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.

Model
Panel Color

Air Filter

Drawing No.

VP25

31

Connectable Outdoor Units

Standard Accessories

38/33

Refrigerant Control

Weight

kg

Fuse,
Thermal Fuse for Fan Motor
Electronic Expansion Valve

Dimensions: (HWD)

dBA

Safety Devices

Decoration
Panels
(Option)

0.180
3D12H1AP1V1

388/318

Sound Absorbing Thermal Insulation Material

4 Sound Level (H/L) (220V)

0.180
3D12H1AN1V1

cfm

Drive

Gas Pipes
Piping
Connections
Drain Pipe

0.180
3D12H1AN1V1

m/min

Temperature Control

Liquid Pipes

FXKQ63MAVE

8.5
8.5
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation, Drain Pattern for Installation, Drain
Hose, Clamp Metal,
Hose, Clamp Metal,
Insulation for Fitting, Sealing Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Pads, Clamps, Screws,
Washers, Positioning Jig for Washers, Positioning Jig for
Installation, Insulation for
Installation, Insulation for
Hanger Bracket, Air Outlet
Hanger Bracket, Air Outlet
Blocking Pad.
Blocking Pad.
C : 3D038813A

R-410A PA Series

9.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

40

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET: without Drain Pump)
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXDQ20PBVE (T)

FXDQ25PBVE (T)

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

mm
mm

200700620
2121.5

200700620
2121.5

200700620
3121.5

0.126

0.126

0.126

Sirocco Fan

Sirocco Fan

Sirocco Fan

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (HH/H/L)

621

621

621

m/min

8.0/7.2/6.4

8.0/7.2/6.4

8.0/7.2/6.4

4 External Static Pressure

Pa

30-10

30-10

30-10

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXDQ32PBVE (T)

Removal / Washable / Mildew Proof

Removal / Washable / Mildew Proof

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

Drain Pipe

mm

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

Machine Weight (Mass)


5 Sound Pressure Level (HH/H/L)

kg

23

23

23

dBA

33/31/29

33/31/29

33/31/29

Safety Devices
Refrigerant Control

Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve

Standard Accessories

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

Drawing No.

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

C : 3D060921A

Note:
1 Indoor temp.: 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2

3
4
5

Specifications

difference: 0m.
Indoor temp.: 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller. This pressure means High static
pressure - Standard static pressure. (Factory setting is 10 Pa.)
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
FXDQ20 / 25 / 32PBVE only.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

41

Specifications

Si34-804_C

Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET: without Drain Pump)
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXDQ40NBVE(T)

FXDQ50NBVE(T)

kcal/h

4,000

5,000

6,300

Btu/h

16,000

19,800

24,900

kW

4.7

5.8

7.3

kW

4.5

5.6

7.1

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

mm
mm

200900620
3121.5

200900620
3121.5

2001100620
3121.5

0.176

0.176

0.227

Sirocco Fan

Sirocco Fan

Sirocco Fan

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (HH/H/L)

621

1301

1301

m/min

10.5/9.5/8.5

12.5/11.0/10.0

16.5/14.5/13.0

4 External Static Pressure

Pa

44-15

44-15

44-15

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXDQ63NBVE(T)

Removal / Washable / Mildew Proof

Removal / Washable / Mildew Proof

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

Drain Pipe

mm

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

Machine Weight (Mass)


5 Sound Pressure Level (HH/H/L)

kg

27

28

31

dBA

34/32/30

35/33/31

36/34/32

Safety Devices
Refrigerant Control

Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve

Standard Accessories

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

Drawing No.

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter,
(Product Quality Certificate 6)

C : 3D060921A

Note:
1 Indoor temp.: 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2

3
4
5

42

difference: 0m.
Indoor temp.: 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller. This pressure means High static
pressure - Standard static pressure. (Factory setting is 15 Pa.)
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
FXDQ40 / 50 / 63NBVE only.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Ceiling Mounted Duct Type


Model

FXMQ20PVE

FXMQ25PVE

FXMQ32PVE

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

kcal/h

2,200

2,800

3,400

Btu/h

8,500

10,900

13,600

Power supply
1 *6 Cooling capacity (19.5CWB)
2 *6 Cooling capacity (19.0CWB)
3 *6 Heating capacity

kW

2.5

3.2

4.0

Galvanized steel plate

Galvanized steel plate

Galvanized steel plate

mm
mm

300550700
3161.75

300550700
3161.75

300550700
3161.75

0.098

0.098

0.098

Sirocco fan

Sirocco fan

Sirocco fan

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin pitch
fin coil)
Face area
Model
Type
Motor output Number
of units
Fan

Airflow rate (HH/H/L)


External static
pressure

901

901

901

m/min

9/7.5/6.5

9/7.5/6.5

9.5/8/7

cfm

318/265/230

318/265/230

335/282/247

Pa

Standard 50 (100-30 4)

Standard 50 (100-30 4)

Standard 50 (100-30 4)

Direct drive
Microprocessor thermostat for
cooling and heating

Direct drive
Microprocessor thermostat for
cooling and heating

Direct drive
Microprocessor thermostat for
cooling and heating

Drive
Temperature control

Liquid pipes

mm

6.4 (Flare connection)

6.4 (Flare connection)

6.4 (Flare connection)

Gas pipes

mm

12.7 (Flare connection)

12.7 (Flare connection)

12.7 (Flare connection)

VP25
External dia. 32
Internal dia. 25
25

dia. 32
( External
Internal dia. 25 )

kg

VP25
External dia. 32
Internal dia. 25
25

220V
240V

33/31/29
33/31/29

33/31/29
33/31/29

34/32/30
34/32/30

Fuse.
Fan driver overload protector.

Fuse.
Fan driver overload protector.

Fuse.
Fan driver overload protector.

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Air filter

Piping
connections

Drain pipe

mm

Mass (Weight)
7 Sound level (HH/H/L)

dBA

Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.

VP25

25

C : 3D060388E

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
2
3
4

6
7

Specifications

difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
External static pressure is changeable in 7 (FXMQ20PVE / FXMQ25PVE / FXMQ32PVE),
13 (FXMQ40PVE), 14 (FXMQ50PVE / FXMQ63PVE / FXMQ80PVE / FXMQ100PVE / FXMQ125PVE),
10 (FXMQ140PVE) stages within the ( ) range by remote controller.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

43

Specifications

Si34-804_C

Ceiling Mounted Duct Type


Model
Power supply

FXMQ40PVE

FXMQ50PVE

FXMQ63PVE

FXMQ80PVE

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

kcal/h

4,000

5,000

6,300

8,000

1 *6 Cooling capacity (19.5CWB)

Btu/h

16,000

19,800

24,900

31,700

kW

4.7

5.8

7.3

9.3

2 *6 Cooling capacity (19.0CWB)

kW

4.5

5.6

7.1

9.0

3 *6 Heating capacity

kcal/h

4,300

5,400

6,900

8,600

Btu/h

17,100

21,500

27,300

34,100

kW

5.0

6.3

8.0

10.0

Galvanized steel plate

Galvanized steel plate

Galvanized steel plate

Galvanized steel plate

mm
mm

300700700
3161.75

3001,000700
3161.75

3001,000700
3161.75

3001,000700
3161.75

0.148

0.249

0.249

0.249

Sirocco fan

Sirocco fan

Sirocco fan

Sirocco fan

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin pitch
fin coil)
Face area
Model
Type
Motor output Number
of units
Fan

Airflow rate (HH/H/L)

1401

3501

3501

3501

m/min

16/13/11

18/16.5/15

19.5/17.5/16

25/22.5/20

External static
pressure

cfm

565/459/388

635/582/530

688/618/565

883/794/706

Pa

Standard 100 (160-30 4)

Standard 100 (200-50 4)

Standard 100 (200-50 4)

Standard 100 (200-50 4)

Direct drive
Microprocessor thermostat
for cooling and heating

Direct drive
Microprocessor thermostat
for cooling and heating

Direct drive
Microprocessor thermostat
for cooling and heating

Direct drive
Microprocessor thermostat
for cooling and heating

Drive
Temperature control

Liquid pipes

mm

6.4 (Flare connection)

6.4 (Flare connection)

9.5 (Flare connection)

9.5 (Flare connection)

Gas pipes

mm

12.7 (Flare connection)

12.7 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

VP25
External dia. 32
Internal dia. 25
36

VP25
External dia. 32
Internal dia. 25
36

dia. 32
( External
Internal dia. 25 )

kg

VP25
External dia. 32
Internal dia. 25
28

220V
240V

39/37/35
39/37/35

41/39/37
41/39/37

42/40/38
42/40/38

43/41/39
43/41/39

Fuse.
Fan driver overload
protector.

Fuse.
Fan driver overload
protector.

Fuse.
Fan driver overload
protector.

Fuse.
Fan driver overload
protector.

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Operation manual.
Operation manual.
Installation manual. Drain
Installation manual. Drain
hose. Sealing pads.
hose. Sealing pads.
Clamps. Washers. Screws. Clamps. Washers. Screws.
Insulation for fitting. Clamp
Insulation for fitting. Clamp
metal. Air discharge flange. metal. Air discharge flange.
Air suction flange.
Air suction flange.
C : 3D060388E

Operation manual.
Installation manual. Drain
hose. Sealing pads.
Clamps. Washers. Screws.
Insulation for fitting. Clamp
metal. Air discharge flange.
Air suction flange.

Air filter

Piping
connections

Drain pipe

mm

Mass (Weight)
7 Sound level (HH/H/L)

dBA

Safety devices
Refrigerant control
Connectable outdoor unit

Operation manual.
Installation manual. Drain
hose. Sealing pads.
Clamps. Washers. Screws.
Insulation for fitting. Clamp
metal. Air discharge flange.
Air suction flange.

Standard accessories

Drawing No.

VP25

36

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level

difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level

difference : 0 m.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :

0 m.
4 External static pressure is changeable in 7 (FXMQ20PVE / FXMQ25PVE / FXMQ32PVE),

13 (FXMQ40PVE), 14 (FXMQ50PVE / FXMQ63PVE / FXMQ80PVE / FXMQ100PVE / FXMQ125PVE),


10 (FXMQ140PVE) stages within the ( ) range by remote controller.
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

44

Specifications

Si34-804_C

Specifications

Ceiling Mounted Duct Type


Model

FXMQ100PVE

FXMQ125PVE

FXMQ140PVE

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

1 phase 50Hz 220-240V

kcal/h

10,000

12,500

14,300

Btu/h

39,600

49,500

57,000

kW

11.6

14.5

16.7

kW

11.2

14.0

16.0

kcal/h

10,800

13,800

15,500

Btu/h

42,700

54,600

61,400

kW

12.5

16.0

18.0

Galvanized steel plate

Galvanized steel plate

Galvanized steel plate

mm
mm

3001,400700
3161.75

3001,400700
3161.75

3001,400700
3161.5

0.383

0.383

0.383

Sirocco fan

Sirocco fan

Sirocco fan

Power supply
1 *6 Cooling capacity (19.5CWB)
2 *6 Cooling capacity (19.0CWB)
3 *6 Heating capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin pitch
fin coil)
Face area
Model
Type
Motor output Number
of units
Fan

Airflow rate (HH/H/L)


External static
pressure

3501

3501

3501

m/min

32/27/23

39/33/28

46/39/32

cfm

1,130/953/812

1,377/1,165/988

1,624/1,377/1,130

Pa

Standard 100 (200-50 4)

Standard 100 (200-50 4)

Standard 100 (140-50 4)

Direct drive
Microprocessor thermostat for cooling
and heating

Direct drive
Microprocessor thermostat for cooling
and heating

Direct drive
Microprocessor thermostat for cooling
and heating

Drive
Temperature control

Liquid pipes

mm

9.5 (Flare connection)

9.5 (Flare connection)

9.5 (Flare connection)

Gas pipes

mm

15.9 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

VP25
External dia. 32
Internal dia. 25
46

dia. 32
( External
Internal dia. 25 )

kg

VP25
External dia. 32
Internal dia. 25
46

220V
240V

43/41/39
43/41/39

44/42/40
44/42/40

46/45/43
46/45/43

Fuse.
Fan driver overload protector.

Fuse.
Fan driver overload protector.

Fuse.
Fan driver overload protector.

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Electronic expansion valve


R-410A P(A) series

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Operation manual. Installation manual.


Drain hose. Sealing pads. Clamps.
Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air
suction flange.

Air filter

Piping
connections

Drain pipe

mm

Mass (Weight)
7 Sound level (HH/H/L)

dBA

Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.

VP25

47

C : 3D060388E

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
2
3
4

6
7

Specifications

difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
External static pressure is changeable in 7 (FXMQ20PVE / FXMQ25PVE / FXMQ32PVE),
13 (FXMQ40PVE), 14 (FXMQ50PVE / FXMQ63PVE / FXMQ80PVE / FXMQ100PVE / FXMQ125PVE),
10 (FXMQ140PVE) stages within the ( ) range by remote controller.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

45

Specifications

Si34-804_C

Ceiling Mounted Duct Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXMQ200MAVE

FXMQ250MAVE

kcal/h

19,800

24,800

Btu/h

78,500

98,300

kW

23.0

28.8

kW

22.4

28.0

Galvanized Steel Plate

Galvanized Steel Plate

4701,3801,100
3262.0

4701,3801,100
3262.0

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model
Type
Motor Output Number
of Units
Fan

Airflow Rate (H/L)


External Static
Pressure 50Hz

0.68

0.68

D13/4G2DA12

D13/4G2DA12

Sirocco Fan

Sirocco Fan

3802

3802

m/min

58/50

72/62

cfm

2,047/1,765

2,542/2,189

Pa

221/270-132 3

270/191-147 3

Direct Drive
Microprocessor Thermostat for Cooling and Heating

Direct Drive
Microprocessor Thermostat for Cooling and Heating

Glass Fiber

Glass Fiber

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material

mm

9.5 (Flare Connection)

9.5 (Flare Connection)

mm

19.1(Brazing Connection)

22.2 (Brazing Connection)

mm
kg

PS1B
137

PS1B
137

dBA

Safety Devices

48/45
Fuse.
Thermal Protector for Fan Motor.

48/45
Fuse.
Thermal Protector for Fan Motor.

Refrigerant Control

Electronic Expansion Valve

Electronic Expansion Valve

Air Filter
Liquid Pipes
Piping
Connections Gas Pipes
Drain Pipe
Machine Weight (Mass)
6 Sound Level (H/L) (220V)

Connectable Outdoor Unit

R-410A PA Series
Operation Manual. Installation Manual. Sealing Pads.
Connection Pipes. Screws. Clamps.

Standard Accessories
Drawing No.

R-410A PA Series
Operation Manual. Installation Manual. Sealing Pads.
Connection Pipes. Screws. Clamps.

C : 3D038814B

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
2
3
4

5
6

46

difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means "High static pressure-Standard".
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Ceiling Suspended Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXHQ32MAVE

FXHQ63MAVE

FXHQ100MAVE

kcal/h

3,200

6,300

10,000

Btu/h

12,600

24,900

39,600

kW

3.7

7.3

11.6

kW

3.6

7.1

11.2

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

195960680
2121.75

1951,160680
3121.75

1951,400680
3121.75

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.233

0.293

4D12K1AA1

3D12K2AA1

Sirocco Fan

Sirocco Fan

Sirocco Fan

621

621

1301

m/min

12/10

17.5/14

25/19.5

cfm

424/353

618/494

883/688

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

0.182
3D12K1AA1

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Glass Wool

Glass Wool

Glass Wool

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Liquid Pipes

mm

6.4 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

Drain Pipe

mm

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

VP20
(External Dia. 26 Internal Dia. 20)

Machine Weight (Mass)


4 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.

kg

24

28

33

dBA

36/31

39/34

45/37

Fuse,
Thermal Protector for Fan Motor

Fuse,
Thermal Protector for Fan Motor

Fuse,
Thermal Protector for Fan Motor

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Operation Manual, Installation


Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.

Operation Manual, Installation


Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.

Operation Manual, Installation


Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.

C : 3D038815A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

47

Specifications

Si34-804_C

Wall Mounted Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXAQ20MAVE

FXAQ25MAVE

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

White (3.0Y8.5/10.5)

White (3.0Y8.5/10.5)

White (3.0Y8.5/10.5)

290795230
2141.4

290795230
2141.4

290795230
2141.4

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.161

0.161

0.161

QCL9661M

QCL9661M

QCL9661M

Cross Flow Fan

Cross Flow Fan

Cross Flow Fan

401

401

401

m/min

7.5/4.5

8/5

9/5.5

cfm

265/159

282/177

318/194

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXAQ32MAVE

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Foamed Polystyrene /
Foamed Polyethylene

Foamed Polystyrene /
Foamed Polyethylene

Foamed Polystyrene /
Foamed Polyethylene

Resin Net (Washable)

Resin Net (Washable)

Resin Net (Washable)

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

VP13
(External Dia. 18 Internal Dia. 13)
11

VP13
(External Dia. 18 Internal Dia. 13)
11

VP13
(External Dia. 18 Internal Dia. 13)
11

35/29
Fuse

36/29
Fuse

37/29
Fuse

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Drain Pipe

mm

Machine Weight (Mass)

kg

4 Sound Level (H/L)

dBA

Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.

C : 3D039370B

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.

48

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Wall Mounted Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXAQ40MAVE

FXAQ50MAVE

kcal/h

4,000

5,000

6,300

Btu/h

16,000

19,800

24,900

kW

4.7

5.8

7.3

kW

4.5

5.6

7.1

White (3.0Y8.5/10.5)

White (3.0Y8.5/10.5)

White (3.0Y8.5/10.5)

2901,050230
2141.4

2901,050230
2141.4

2901,050230
2141.4

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.213

0.213

0.213

QCL9686M

QCL9686M

QCL9686M

Cross Flow Fan

Cross Flow Fan

Cross Flow Fan

431

431

431

m/min

12/9

15/12

19/14

cfm

424/318

530/424

671/494

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXAQ63MAVE

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Foamed Polystyrene /
Foamed Polyethylene

Foamed Polystyrene /
Foamed Polyethylene

Foamed Polystyrene /
Foamed Polyethylene

Resin Net (Washable)

Resin Net (Washable)

Resin Net (Washable)

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

VP13
(External Dia. 18 Internal Dia. 13)
14

VP13
(External Dia. 18 Internal Dia. 13)
14

VP13
(External Dia. 18 Internal Dia. 13)
14

39/34
Fuse

42/36
Fuse

46/39
Fuse

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Electronic Expansion Valve


R-410A PA Series

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Operation Manual, Installation


Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.

Drain Pipe

mm

Machine Weight (Mass)

kg

4 Sound Level (H/L)

dBA

Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.

C : 3D039370B

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

49

Specifications

Si34-804_C

Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXLQ20MAVE

FXLQ25MAVE

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

6001,000222
3141.5

6001,000222
3141.5

6001,140222
3141.5

Casing Color
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

FXLQ32MAVE

0.159

0.159

0.200

D14B20

D14B20

2D14B13

Sirocco Fan

Sirocco Fan

Sirocco Fan

151

151

251

m/min

7/6

7/6

8/6

cfm

247/212

247/212

282/212

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Liquid Pipes
Piping
Connections Gas Pipes
Drain Pipe

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

mm

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

Machine Weight (Mass)

kg

25

25

30

dBA

35/32

35/32

35/32

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

4 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

Standard Accessories
Drawing No.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

C : 3D038816A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

50

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXLQ40MAVE

FXLQ50MAVE

kcal/h

4,000

5,000

6,300

Btu/h

16,000

19,800

24,900

kW

4.7

5.8

7.3

kW

4.5

5.6

7.1

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

Ivory White (5Y7.5/1)

6001,140222
3141.5

6001,420222
3141.5

6001,420222
3141.5

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.200

0.282

0.282

2D14B13

2D14B20

2D14B20

Sirocco Fan

Sirocco Fan

Sirocco Fan

251

351

351

m/min

11/8.5

14/11

16/12

cfm

388/300

494/388

565/424

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXLQ63MAVE

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

Drain Pipe

mm

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

kg

30

36

36

dBA

38/33

39/34

40/35

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Machine Weight (Mass)


4 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

Standard Accessories
Drawing No.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

C : 3D038816A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

51

Specifications

Si34-804_C

Concealed Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXNQ20MAVE

FXNQ25MAVE

kcal/h

2,000

2,500

3,200

Btu/h

7,800

9,900

12,600

kW

2.3

2.9

3.7

kW

2.2

2.8

3.6

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

610930220
3141.5

610930220
3141.5

6101,070220
3141.5

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.159

0.159

0.200

D14B20

D14B20

2D14B13

Sirocco Fan

Sirocco Fan

Sirocco Fan

151

151

251

m/min

7/6

7/6

8/6

cfm

247/212

247/212

282/212

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXNQ32MAVE

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Glass Fiber/ Urethane Foam

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

Drain Pipe

mm

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

kg

19

19

23

dBA

35/32

35/32

35/32

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Machine Weight (Mass)


4 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

Standard Accessories
Drawing No.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

C : 3D038817A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

52

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

Concealed Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)

FXNQ40MAVE

FXNQ50MAVE

kcal/h

4,000

5,000

6,300

Btu/h

16,000

19,800

24,900

kW

4.7

5.8

7.3

kW

4.5

5.6

7.1

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

6101,070220
3141.5

6101,350220
3141.5

6101,350220
3141.5

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area

mm
mm
m

Model

Fan

Type
Motor Output Number
of Units
Airflow Rate (H/L)

0.200

0.282

0.282

2D14B13

2D14B20

2D14B20

Sirocco Fan

Sirocco Fan

Sirocco Fan

251

351

351

m/min

11/8.5

14/11

16/12

cfm

388/300

494/388

565/424

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

FXNQ63MAVE

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Microprocessor Thermostat for


Cooling and Heating

Glass Fiber / Urethane Foam

Glass Fiber / Urethane Foam

Glass Fiber / Urethane Foam

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Resin Net (with Mold Resistant)

Liquid Pipes

mm

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

Gas Pipes

mm

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

Drain Pipe

mm

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

21 O.D (Vinyl Chloride)

kg

23

27

27

dBA

38/33

39/34

40/35

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve

Machine Weight (Mass)


4 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

Standard Accessories
Drawing No.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

R-410A PA Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.

C : 3D038817A

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

53

Specifications

Si34-804_C

Ceiling Suspended Cassette Type


Model

Indoor unit

FXUQ71MAV1

FXUQ100MAV1

FXUQ125MAV1

Connection unit

BEVQ71MAVE

BEVQ100MAVE

BEVQ125MAVE

Power supply
1 3 Cooling capacity (19.5CWB)

1 phase, 220-240V, 50Hz

1 phase, 220-240V, 50Hz

1 phase, 220-240V, 50Hz

kcal/h

7,100

10,000

12,500

Btu/h

28,300

39,600

49,500

kW

8.3

11.6

14.5

kW

8.0

11.2

14.0

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

165895895
361.5

230895895
381.5

230895895
381.5

2 3 Cooling capacity (19.0CWB)

Casing colour
Dimensions: (HWD)
RowsStagesFin pitch
Coil (Cross
fin coil)
Face area

mm
mm
m

Model
Type
Motor output
Number of units
Fan

0.353

0.353

QTS50B15M

QTS50B15M

Turbo fan

Turbo fan

Turbo fan

451

901

901

m/min

19/14

29/21

32/23

l/s
cfm

316/233
671/494

483/350
1,024/741

533/383
1,130/812

Airflow rate (H/L)


Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Piping
connections

0.265
QTS48A10M

Direct drive

Direct drive

Direct drive

Microprocessor thermostat for


cooling and heating

Microprocessor thermostat for


cooling and heating

Microprocessor thermostat for


cooling and heating

Heat resistant foamed polyethylene /


Regular foamed polyethylene
Resin net (with mould resistance)

Heat resistant foamed polyethylene /


Regular foamed polyethylene
Resin net (with mould resistance)

Heat resistant foamed polyethylene /


Regular foamed polyethylene
Resin net (with mould resistance)

Liquid pipes

mm

9.5 (Flare connection)

9.5 (Flare connection)

9.5 (Flare connection)

Gas pipes

mm

15.9 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

Drain pipe

mm

VP20
(External dia. 26 Internal dia. 20)

VP20
(External dia. 26 Internal dia. 20)

VP20
(External dia. 26 Internal dia. 20)

Mass (Weight)
4 Sound level (H/L)

230V

Safety devices

kg

25

31

31

dB(A)

40/35

43/38

44/39

Fan motor thermal protector


Operation manual. Installation
manual. Drain hose. Clamp metal.
Insulation for fitting. Sealing pads.
Clamps. Washers. Holding plate.

Standard accessories
Drawing No.

Fan motor thermal protector


Operation manual. Installation
manual. Drain hose. Clamp metal.
Insulation for fitting. Sealing pads.
Clamps. Washers. Holding plate.
C : 4D045395A

Fan motor thermal protector


Operation manual. Installation
manual. Drain hose. Clamp metal.
Insulation for fitting. Sealing pads.
Clamps. Washers. Holding plate.

Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level

difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.

54

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Specifications

BEV Units
Model
Power supply
Casing
Dimensions: (HWD)

mm

Sound absorbing thermal insulation material

BEVQ71MAVE

BEVQ100MAVE

BEVQ125MAVE

1 phase, 220-240/220V, 50/60Hz

1 phase, 220-240/220V, 50/60Hz

1 phase, 220-240/220V, 50/60Hz

Galvanized steel plate


100350225

Galvanized steel plate


100350225

Galvanized steel plate


100350225

Flame and heat resistant foamed


polyethylene

Flame and heat resistant foamed


polyethylene

Flame and heat resistant foamed


polyethylene

Liquid
pipes

mm

9.5 (Flare connection)

9.5 (Flare connection)

9.5 (Flare connection)

Gas pipes

mm

15.9 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

Liquid
mm
Outdoor pipes
unit
Suction gas mm
pipes
Mass (Weight)
kg

9.5 (Flare connection)

9.5 (Flare connection)

9.5 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

15.9 (Flare connection)

Indoor
unit
Piping
connection

Standard accessories
Drawing No.

Specifications

3.0

3.0

3.5

Installation manual. Gas piping


connections. Insulation for fitting.
Sealing material. Clamps.
4D045387A

Installation manual. Gas piping


connections. Insulation for fitting.
Sealing material. Clamps.
4D045387A

Installation manual. Gas piping


connections. Insulation for fitting.
Sealing material. Clamps.
4D045388A

55

Specifications

Si34-804_C

Outdoor Air Processing Unit


Model
1 Cooling Capacity

FXMQ125MFV1

FXMQ200MFV1

FXMQ250MFV1

kcal/h

12,000

19,300

24,100

Btu/h

47,800

76,400

95,500

kW

14.0

22.4

28.0

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)

mm

4707441,100

4701,3801,100

4701,3801,100

RowsStagesFin
Pitch

mm

3262.0

3262.0

3262.0

Face Area

Model
Type
Motor Output
Number of Units
Fan

Airflow Rate (H/L)


External Static
Pressure 4

0.65

0.65

D13/4G2DA1

D13/4G2DA1

Sirocco Fan

Sirocco Fan

Sirocco Fan

3801

3801

3801

m/min
cfm

18
635

28
988

35
1,236

Pa

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Connections

0.28
D13/4G2DA1

Gas Pipes

185

225

205

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for


Cooling and Heating
Glass Fiber

Microprocessor Thermostat for


Cooling and Heating
Glass Fiber

Microprocessor Thermostat for


Cooling and Heating
Glass Fiber

9.5mm
(Flare Connection)
15.9mm
(Flare Connection)

9.5mm
(Flare Connection)
19.1mm
(Brazing Connection)

9.5mm
(Flare Connection)
22.2mm
(Brazing Connection)

Drain Pipe
Machine Weight (Mass)

(mm)
kg

PS1B (female thread)


86

PS1B (female thread)


123

PS1B (female thread)


123

Sound Level (220V) 3,4

dBA

42
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve

47
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve

47
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve

Operation Manual, Installation Manual,


Sealing Pads, Screws, Clamps.

Operation Manual, Installation Manual,


Sealing Pads, Connection Pipes,
Screws, Clamps.

Operation Manual, Installation Manual,


Sealing Pads, Connection Pipes,
Screws, Clamps.

Connectable Outdoor Units 5,6

RXQ8~54PAY1

RXQ8~54PAY1

RXQ10~54PAY1

Drawing No.

C : 3D046147B

C : 3D046147B

C : 3D046147B

Safety Devices
Refrigerant Control
Standard Accessories

Note:
1. Specifications are based on the following conditions:

2.

3.

4.
5.
6.

56

Cooling: Outdoor temp. of 33CDB, 28CWB (68% RH). and discharge temp. of 18CDB
Equivalent reference piping length: 7.5m (0m Horizontal)
At 220V
Air intake filter is not supplied, so be sure to install the optional long life filter or high-efficiency filter.
Please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center.
These values (measured at 220V) are normally somewhat higher during actual operation as a result of
ambient conditions.
Valves measured at 220 V.
Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the
outdoor unit.
It is not possible to connect to the 5 HP outdoor unit. Not available for Heat Recovery type and VRV II-S
series.
This equipment cannot be incorporated into the refrigerant piping system or remote group control of the
VRV II system.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Specifications

Si34-804_C

Part 3
Refrigerant Circuit
1. Refrigerant Circuit .................................................................................58
1.1
1.2
1.3
1.4
1.5

RXQ5PA.................................................................................................58
RXQ8PA.................................................................................................60
RXQ10PA, 12PA ....................................................................................62
RXQ14PA, 16PA, 18PA .........................................................................64
Outdoor Air Processing Unit FXMQ125MFV1~250MFV1 ......................66

2. Functional Parts Layout ........................................................................67


2.1
2.2
2.3
2.4
2.5

RXQ5PA.................................................................................................67
RXQ8PA.................................................................................................68
RXQ10PA...............................................................................................69
RXQ12PA...............................................................................................70
RXQ14PA, 16PA, 18PA .........................................................................71

3. Refrigerant Flow for Each Operation Mode...........................................72

Refrigerant Circuit

57

Refrigerant Circuit

Si34-804_C

1. Refrigerant Circuit
1.1

RXQ5PA

No. in
refrigerant Symbol
system
diagram

Major Function

M1C

Inverter compressor (INV.)

Inverter compressor is operated on frequencies between 52Hz and 188Hz by using


the inverter. The number of operating steps is as follows when Inverter compressor is
operated.
RXQ5PA : 18 steps

M1F

Inverter fan

Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.

Y1E

Electronic expansion valve


(Main: EV1)

Fully open during cooling operation.

Y1S

Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.

Y2S

Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.

Y4S

to cool the compressor by injecting refrigerant when the compressor discharge


Solenoid valve (Injection: SVT) Used
pipe temperature is high.

Y3S

Four way valve

Fixed to cooling operation.

S1NPH High pressure sensor

Used to detect high pressure.

S1NPL Low pressure sensor

Used to detect low pressure.

S1PH

High pressure switch (For


INV. compressor)

In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.

Pressure regulating valve 1

This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the
compressor.

R1T

Thermistor (Outdoor air: Ta)

Used to detect outdoor temperature, correct discharge pipe temperature and others.

R2T

Thermistor (Suction pipe: Ts)

Used to detect suction pipe temperature.

R3T

Thermistor (INV. discharge


pipe: Tdi)

Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.

R4T

Thermistor (Heat exchanger


deicer: Tb)

Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation and others.

R6T

Thermistor (Liquid pipe: Tl)

Used to detect liquid pipe temperature.

R7T

Thermistor (Accumulator inlet: Used to detect gas pipe temperature at the accumulator inlet.
Ts1)

58

Name

Refrigerant Circuit

Refrigerant Circuit

S1NPL

S1PH

S1NPH

HEAT
EXCHANGER

C: 3D050782B

Si34-804_C
Refrigerant Circuit

RXQ5PA

59

Refrigerant Circuit

1.2

Si34-804_C

RXQ8PA

No. in
refrigerant
Symbol
system
diagram

60

Name

Major Function

M1C

Inverter compressor (INV.)

Inverter compressor is operated on frequencies between 52Hz and 266Hz by using


the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
RXQ8PA : 24 steps

M1F

Inverter fan

Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.

Y1E

Electronic expansion valve


(Main: EV1)

Fully open during cooling operation.

Y2E

Electronic expansion valve


(Subcooling: EV2)

PI control is applied to keep the outlet superheated degree of subcooling heat


exchanger constant.

Y1S

Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.

Y2S

Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.

S1NPH High pressure sensor

Used to detect high pressure.

S1NPL Low pressure sensor

Used to detect low pressure.

S1PH

High pressure switch (For


INV. compressor)

In order to prevent the increase of high pressure when a error occurs, this switch is
activated at high pressure of 4.0 MPa or more to stop the compressor operation.

Pressure regulating valve


(Liquid pipe)

This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.

Subcooling heat exchanger

Used to subcooling liquid refrigerant from the electronic expansion valve (cooling).

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the INV.
compressor.

R1T

Thermistor (Outdoor air: Ta)

Used to detect outdoor temperature, correct discharge pipe temperature and others.

R2T

Thermistor (Suction pipe: Ts)

Used to detect suction pipe temperature.

R3T

Thermistor (INV. discharge


pipe: Tdi)

Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.

R4T

Thermistor (Heat exchanger


deicer: Tb)

Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.

R5T

Thermistor (Subcooling heat


exchanger gas pipe: Tsh)

This detects temperature of gas pipe on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant and others.

R6T

Thermistor (Receiver outlet


liquid pipe: Tl)

Used to detect receiver outlet liquid pipe temperature.

R7T

Thermistor (Accumulator inlet: Used to detect gas pipe temperature at the accumulator inlet.
Ts1)

Refrigerant Circuit

Si34-804_C

Refrigerant Circuit

C: 3D069081

RXQ8PA

Refrigerant Circuit

61

Refrigerant Circuit

1.3

Si34-804_C

RXQ10PA, 12PA

No. in
refrigerant
Symbol
system
diagram

Major Function

M1C

Inverter compressor (INV.)

M2C

Standard compressor 1
(STD1)

M1F

Inverter fan

Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.

Y1E

Electronic expansion valve


(Main: EV1)

Fully open during cooling operation.

Y2E

Electronic expansion valve


(Subcooling: EV3)

PI control is applied to keep the outlet superheated degree of subcooling heat


exchanger constant.

Y1S

Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.

Y2S

Inverter compressor is operated on frequencies between 52Hz and 210Hz by using


the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
RXQ10, 12PA : 37 steps

Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.

S1NPH High pressure sensor

Used to detect high pressure.

S1NPL Low pressure sensor

Used to detect low pressure.

S1PH

High pressure switch (For


INV. compressor)

S2PH

High pressure switch (For


STD compressor 1)

Pressure regulating valve


(Liquid pipe)

Subcooling heat exchanger

Used to subcooling liquid refrigerant from the electronic expansion valve (cooling).

In order to prevent the increase of high pressure when a error occurs, this switch is
activated at high pressure of 4.0 MPa or more to stop the compressor operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the INV.
compressor.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.

R1T

Thermistor (Outdoor air: Ta)

Used to detect outdoor temperature, correct discharge pipe temperature and others.

R2T

Thermistor (Suction pipe: Ts)

Used to detect suction pipe temperature.

R31T

Thermistor (INV. discharge


pipe: Tdi)

R32T

Thermistor (STD1 discharge


pipe: Tds1)

R4T

Thermistor (Heat exchanger


deicer: Tb)

Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.

R5T

Thermistor (Subcooling heat


exchanger gas pipe: Tsh)

This detects temperature gas pipe on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant and others.

R6T

Thermistor (Liquid pipe: Tl)

Used to detect liquid pipe temperature.

R7T

Thermistor (Accumulator inlet: Used to detect gas pipe temperature at the accumulator inlet.
Ts1)

62

Name

Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.

Refrigerant Circuit

Si34-804_C

Refrigerant Circuit

C: 3D069082

RXQ10PA, 12PA

Refrigerant Circuit

63

Refrigerant Circuit

1.4

Si34-804_C

RXQ14PA, 16PA, 18PA

No. in
refrigerant
Symbol
system
diagram

Major Function

M1C

Inverter compressor (INV.)

M2C

Standard compressor 1
(STD1)

M3C

Standard compressor 1
(STD2)

M1F

Inverter fan

Because the system is an air heat exchange type, the fan is operated at 8-step rotation
speed by using the inverter.

Y1E

Electronic expansion valve


(Main: EV1)

Fully open during cooling operation.

Y2E

Electronic expansion valve


(Subcooling: EV3)

PI control is applied to keep the outlet superheated degree of subcooling heat


exchanger constant.

Y1S

Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.

Y2S

Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.

Inverter compressor is operated on frequencies between 52Hz and 266Hz by using


the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
RXQ14PA or 16PA : 51 steps, RXQ18PA : 55 steps

S1NPH High pressure sensor

Used to detect high pressure.

S1NPL Low pressure sensor

Used to detect low pressure.

S1PH

High pressure switch (For


INV. compressor)

S2PH

High pressure switch (For


STD compressor 1)

S3PH

High pressure switch (For


STD compressor 2)

Pressure regulating valve


(Liquid pipe)

Subcooling heat exchanger

Used to subcooling liquid refrigerant from the electronic expansion valve (cooling).

In order to prevent the increase of high pressure when a error occurs, this switch is
activated at high pressure of 4.0 MPa or more to stop the compressor operation.

This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the INV.
compressor.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.

Capillary tube

Used to return the refrigerating oil separated through the oil separator to the STD2
compressor.

R1T

Thermistor (Outdoor air: Ta)

Used to detect outdoor temperature, correct discharge pipe temperature and others.

R2T

Thermistor (Suction pipe: Ts)

Used to detect suction pipe temperature.

R31T

Thermistor (INV. discharge


pipe: Tdi)

R32T

Thermistor (STD1 discharge


pipe: Tds1)

R33T

Thermistor (STD2 discharge


pipe: Tds2)

R4T

Thermistor (Heat exchanger


deicer: Tb)

Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.

R5T

Thermistor (Subcooling heat


exchanger gas pipe: Tsh)

This detects temperature of gas pipe on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant and others.

R6T

Thermistor (Liquid pipe: Tl)

Used to detect liquid pipe temperature.

R7T

Thermistor (Accumulator inlet: Used to detect gas pipe temperature at the accumulator inlet.
Ts1)

64

Name

Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.

Refrigerant Circuit

Si34-804_C

Refrigerant Circuit

C: 3D069083

RXQ14PA, 16PA, 18PA

Refrigerant Circuit

65

Refrigerant Circuit

1.5

Si34-804_C

Outdoor Air Processing Unit FXMQ125MFV1~250MFV1

1.5.1 Refrigerant System

4D018650C

Main Control Equipment


Code

Symbol

Name

Y1E

Electronic expansion
valve

Y1S

Solenoid valve

Capillary tube

Main function
Used to control the flow rate of refrigerant, and
make the SH control while in cooling.
Used to bypass hot gas while in heating with
thermostat OFF. (close while in cooling)
Used to reduce pressure from high to low in
bypassing hot gas.

SH control: Superheated control of heat exchanger outlet

SC control: Subcooling control of heat exchanger outlet

Thermistor

66

Code

Symbol

Name
Suction air temperature
thermistor

Th1

R1T

Th2

R2T

Th3
Th4

Main function
Used to turn ON or OFF the thermostat.

R3T

Liquid pipe temperature


thermistor
Gas pipe temperature
thermistor

Used to control the opening degree of EV (Y1E)


under the SC control.
Used to control the opening degree of EV (Y1E)
under the SH control.

R4T

Discharge air
temperature thermistor

Used to control the electronic expansion valve


opening and thermostat ON/OFF so as to keep the
discharge air temperature at the set temperature.

Refrigerant Circuit

Si34-804_C

Functional Parts Layout

2. Functional Parts Layout


2.1

RXQ5PA

Plan
ACCUMULATOR

HEAT EXCHANGER
ACCUMULATOR

FOUR

THERMISTOR

Front View

THERMISTOR
R7T

FOUR WAY VALVE


(Y3S)

SOLENOID VALVE (HOT GAS BYPASS)


(Y1S)

PRESSURE SWITCH (HIGH PRESSURE PROTECTION)


(S1PH)

THERMISTOR

THERMISTOR

ELECTRONIC EXPANSION VALVE

THERMISTOR
SOLENOID VALVE (ACCUMULATOR OIL RETURN)
(Y2S)

THERMISTOR (LIQUID PIPE)


(R6T)

Refrigerant Circuit

67

Functional Parts Layout

2.2

Si34-804_C

RXQ8PA

Plan
HEAT EXCHANGER
ACCUMULATOR

HIGH PRESSURE SENSOR


(S1NPH)

THERMISTOR

Front View

THERMISTOR
THERMISTOR
ELECTRONIC

ELECTRONIC

FOUR

THERMISTOR

THERMISTOR

THERMISTOR

THERMISTOR

68

Refrigerant Circuit

Si34-804_C

2.3

Functional Parts Layout

RXQ10PA

Plan
ACCUMULATOR

HEAT EXCHANGER

THERMISTOR

THERMISTOR

Front View

THERMISTOR
THERMISTOR
ELECTRONIC

ELECTRONIC

FOUR

THERMISTOR

THERMISTOR
THERMISTOR

THERMISTOR

Refrigerant Circuit

69

Functional Parts Layout

2.4

Si34-804_C

RXQ12PA

Plan
HEAT EXCHANGER

PRESSURE SWITCH (HIGH PRESSURE PROTECTION)


(S2PH)

ACCUMULATOR

PRESSURE SWITCH (HIGH PRESSURE PROTECTION)


(S1PH)
THERMISTOR (M1C, DISCHARGE PIPE)
(R31T)

THERMISTOR (M2C, DISCHARGE PIPE)


(R32T)

Front View
FAN MOTOR
(M2F)

FAN MOTOR
(M1F)

THERMISTOR
(R5T)
THERMISTOR
(R7T)

(S1NPH)

ELECTRONIC
(Y2E)
ELECTRONIC
(Y1E)
FOUR

THERMISTOR

(Y3S)

(R1T)

(Y1S)
THERMISTOR
(R4T)

THERMISTOR
(R6T)

(M1C)

(S1NPL)
(Y2S)

(E2HC)

(E1HC)

(M2C)

THERMISTOR

(R2T)

70

(M1C)

(M2C)

Refrigerant Circuit

Si34-804_C

2.5

Functional Parts Layout

RXQ14PA, 16PA, 18PA

Plan
HEAT EXCHANGER

ACCUMULATOR

THERMISTOR

THERMISTOR
THERMISTOR

Front View

THERMISTOR
THERMISTOR

ELECTRONIC

ELECTRONIC
FOUR

THERMISTOR

THERMISTOR
THERMISTOR

THERMISTOR

Refrigerant Circuit

71

Refrigerant Flow for Each Operation Mode

Si34-804_C

3. Refrigerant Flow for Each Operation Mode


RXQ5PA
Cooling Operation
Indoor unit operation
Fan ON

Fan ON
" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

Fan OFF

" OFF "

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

EV:Normal
control
Filter

Filter

Electronic expansion valve


Indoor unit

Filter

EV:0pls

Filter

Electronic expansion valve


Indoor unit

EV:0pls

Filter

Filter

Electronic expansion valve


Indoor unit

Thermostat "ON"

Thermostat "OFF"

HEAT
EXCHANGER

S1NPH

S1PH

S1NPL

72

Refrigerant Circuit

Si34-804_C

Refrigerant Flow for Each Operation Mode

Cooling Oil Return Operation


Indoor unit operation
Fan ON

Fan OFF

Fan ON
" OFF "

" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

Filter

Electronic expansion valve


Indoor unit

Filter

EV:224pls

Filter

Electronic expansion valve

EV:Normal

Filter

Filter

Electronic expansion valve

Indoor unit

Indoor unit

Thermostat "ON"

Thermostat "OFF"

HEAT
EXCHANGER

S1NPH

S1PH

S1NPL

Refrigerant Circuit

73

Refrigerant Flow for Each Operation Mode

Si34-804_C

RXQ8PA
Cooling Operation
Indoor unit operation
Fan ON

Fan ON
Fan OFF

" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

" OFF "

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

Filter

Filter

Electronic expansion valve

EV:0pls

Filter

Filter

Electronic expansion valve


Indoor unit

Indoor unit

EV:0pls

Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

Thermostat "ON"

SUBCOOLING
HEAT
EXCHANGER

HEAT
EXCHANGER

S1NPH

S1PH

S1NPL

74

Refrigerant Circuit

Si34-804_C

Refrigerant Flow for Each Operation Mode

Cooling Oil Return Operation


Indoor unit operation
Fan OFF

Fan ON

Fan ON
" OFF "

" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

EV:224pls
Filter

Filter

Electronic expansion valve

EV:Normal
Filter

Filter

Electronic expansion valve

Indoor unit
Thermostat "ON"

Indoor unit

Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

SUBCOOLING
HEAT
EXCHANGER

HEAT
EXCHANGER

S1NPH

S1PH

S1NPL

Refrigerant Circuit

75

Refrigerant Flow for Each Operation Mode

Si34-804_C

RXQ10PA, 12PA
Cooling Operation
Indoor unit operation
Fan ON

Fan ON
" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

Fan OFF

" OFF "

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

Filter

Filter

Electronic expansion valve

EV:0pls

Filter

Filter

Electronic expansion valve


Indoor unit

Indoor unit

EV:0pls

Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

Thermostat "ON"

SUBCOOLING
HEAT
EXCHANGER

HEAT
EXCHANGER

S1NPH

S2PH

S1PH

S1NPL

76

Refrigerant Circuit

Si34-804_C

Refrigerant Flow for Each Operation Mode

Cooling Oil Return Operation


Indoor unit operation
Fan OFF

Fan ON

Fan ON
" OFF "

" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

EV:224pls
Filter

Filter

Electronic expansion valve

EV:Normal
Filter

Filter

Electronic expansion valve

Indoor unit
Thermostat "ON"

Indoor unit

Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

SUBCOOLING
HEAT
EXCHANGER

HEAT
EXCHANGER

S1NPH

S2PH

S1PH

S1NPL

Refrigerant Circuit

77

Refrigerant Flow for Each Operation Mode

Si34-804_C

RXQ14PA, 16PA, 18PA


Cooling Operation
Indoor unit operation
Fan ON

Fan ON
" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

Fan OFF

" OFF "

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

Filter

EV:Normal
control

Filter

Electronic expansion valve


Indoor unit
Thermostat "ON"

Filter

EV:0pls

Filter

Filter

EV:0pls

Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

Electronic expansion valve


Indoor unit

SUBCOOLING
HEAT
EXCHANGER

S1NPH

S1PH

S2PH

S3PH

S1NPL

78

Refrigerant Circuit

Si34-804_C

Refrigerant Flow for Each Operation Mode

Cooling Oil Return Operation


Indoor unit operation
Fan ON

Fan OFF

Fan ON

" ON "

"High temperature, high pressure gas"


"High temperature, high pressure liquid"
"Low temperature, low pressure"

" OFF "

" ON "

Heat exchanger

Heat exchanger

Heat exchanger

Fan

Fan

Fan

EV:Normal
control
Filter

EV:224pls
Filter

Filter

Filter

Electronic expansion valve

Electronic expansion valve

Indoor unit

Indoor unit

Filter

EV:Normal
Filter

Electronic expansion valve


Indoor unit
Thermostat "OFF"

Thermostat "ON"

SUBCOOLING
HEAT
EXCHANGER

S1NPH

S1PH

S2PH

S3PH

S1NPL

Refrigerant Circuit

79

Si34-804_C

Part 4
Function
1. Function General...................................................................................81
1.1 Symbol ...................................................................................................81
1.2 Operation Mode......................................................................................82

2. Basic Control.........................................................................................83
2.1
2.2
2.3
2.4
2.5

Normal Operation ...................................................................................83


Compressor PI Control...........................................................................83
Electronic Expansion Valve PI Control.................................................102
Step Control of Outdoor Unit Fans .......................................................102
Outdoor Unit Fan Control in Cooling Operation ...................................102

3. Special Control....................................................................................103
3.1
3.2
3.3
3.4
3.5

Startup Control .....................................................................................103


Oil Return Operation ............................................................................104
Pump down Residual Operation...........................................................105
Standby ................................................................................................105
Stopping Operation ..............................................................................106

4. Protection Control ...............................................................................107


4.1
4.2
4.3
4.4
4.5
4.6

High Pressure Protection Control.........................................................107


Low Pressure Protection Control..........................................................108
Discharge Pipe Protection Control .......................................................109
Inverter Protection Control ...................................................................110
STD Compressor Overload Protection.................................................111
Injection Control (only for RXQ5PA).....................................................111

5. Other Control.......................................................................................112
5.1 Outdoor Unit Rotation...........................................................................112
5.2 Emergency Operation ..........................................................................113
5.3 Demand Operation ...............................................................................118

6. Outline of Control (Indoor Unit) ...........................................................119


6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9

80

Drain Pump Control..............................................................................119


Louver Control for Preventing Ceiling Dirt............................................121
Using Conditions for Remote Controller Thermistor.............................122
Thermostat Control while in Normal Operation ....................................123
Thermostat Control in Dry Operation ...................................................123
Electronic Expansion Valve Control .....................................................124
Freeze-up Prevention...........................................................................124
List of Swing Flap Operations ..............................................................125
Control of Outdoor Air Processing Unit
(Unique Control for Outdoor Air Processing Unit) ................................126

Function

Si34-804_C

Function General

1. Function General
1.1

Symbol

Symbol

Electric symbol

Description or function

20S1

Y3S

Four way valve

DSH

Discharge pipe superheated degree

DSHi

Discharge pipe superheat of inverter compressor

DSHs

Discharge pipe superheat of standard compressor

EV

Opening of electronic expansion valve

EV1

Y1E

Electronic expansion valve for main heat exchanger

EV2

Y2E

Electronic expansion valve for subcooling heat exchanger

HTDi

Value of INV. compressor discharge pipe temperature (R31T) compensated with


outdoor air temperature

HTDs

Value of STD compressor discharge pipe temperature (R32T, R33T) compensated


with outdoor air temperature

Pc

S1NPH

Value detected by high pressure sensor

Pe

S1NPL

Value detected by low pressure sensor

SH

Evaporator outlet superheat

SHS

Target evaporator outlet superheat

SVO

Y2S

Solenoid valve for oil return

SVP

Y1S

Solenoid valve for hot gas bypass

SVT

Y4S

Solenoid valve for injection

Ta

R1T (A1P)

Outdoor air temperature

Tb

R4T

Heat exchanger outlet temperature at cooling

Ts2

R2T

Suction pipe temperature detected with the suction pipe thermistor (R2T)

Tsh

R5T ()

Temperature detected with the subcooling heat exchanger outlet thermistor (R5T)

Tc

High pressure equivalent saturation temperature

TcS

Target temperature of Tc

Te

Low pressure equivalent saturation temperature

TeS

Target temperature of Te

Tfin

R1T

Radiation fin temperature

Tl

R6T

Liquid pipe temperature detected with the liquid pipe thermistor (R6T)

Tp

Calculated value of compressor port temperature

Ts1

R7T

Suction pipe temperature detected with the accumulator inlet thermistor

Function

81

Function General

1.2

Si34-804_C

Operation Mode
Operation in
stop mode

Indoor unit stop or


thermostat OFF

Indoor unit thermostat ON


Error/Standby
Restart standby
(Compressor stop)

Pressure
equalization
prior to startup

Error/
Standby
Indoor unit stop or
thermostat OFF
Startup control
Cooling startup
control

Indoor unit thermostat ON

Pump down
residual
operation

Error/Standby

Outdoor unit
rotation

Indoor unit stop or


thermostat OFF

Normal operation
Compressor PI control
Electronic expansion
valve PI control
Protection control

Cooling operation

Error/
Standby

Oil return IN
conditions are met.

Yes

Oil return operation

No
Outdoor unit
rotation

Note:

82

In the event indoor unit stops or the thermostat turns OFF while in oil return operation pump
down residual operation is performed on completion of the oil return operation.

Function

Si34-804_C

Basic Control

2. Basic Control
2.1

Normal Operation

2.1.1 List of Functions in Normal Operation

20S1

Function of Functional Part


Normal Cooling
PI
control,
High
pressure
protection,
Low pressure protection, Td
(M1C, M2C)
protection, INV. protection,
(M1F)
Cooling fan control
(Y3S)
OFF

EV1

(Y1E)

480 pls

EV2

(Y2E)

PI control

SVP
SVO

(Y1S)
(Y2S)

OFF
ON

Part Name

Symbol

Compressor
Outdoor unit fan
Four way valve
Main electronic expansion
valve
Subcooling heat exchanger
electronic expansion valve
Hot gas bypass valve
Accumulator oil return valve

(Electric
Symbol)

Indoor unit actuator


Thermostat ON unit
Fan
Stopping unit
Thermostat OFF unit
Thermostat ON unit
Electronic
expansion
Stopping unit
valve
Thermostat OFF unit

Normal cooling
Remote controller setting
OFF
Remote controller setting
Normal opening *1
0 pls
0 pls

*1. PI control : Evaporator outlet superheated degree (SH) constant.


*2. PI control : Condenser outlet subcooled degree (SC) constant.
*1 and 2 : Refer to 6.6 Electronic expansion valve control on P.124.

2.2

Compressor PI Control

Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).

Te : Low pressure equivalent saturation


temperature (C)

Te set value (Make this setting while in Setting TeS : Target Te value
mode 2.)
(Varies depending on Te setting, operating
frequency, etc.)
Te setting
L

Function

M (Normal)
(factory
setting)
6

*On multi-outdoor-unit systems, this control is made


according to values of the first-priority unit, which is
detected with the pressure sensor.

83

Basic Control

Si34-804_C

Operating Priority and Rotation of Compressors (For multi standard connection system)
Each compressor operates in the following order of priority.
In the case of multi-outdoor-unit system, each compressor operates in any of Pattern 1
through Pattern 3 according to the rotation of outdoor units.
Pattern 1
RXQ5PA

Pattern 2
RXQ8PA

INV.: Inverter compressor


STD1: Standard compressor 1
STD2: Standard compressor 2

Pattern 3
RXQ10PA

RXQ14PA, 16PA, 18PA

RXQ12PA

No. 1

No. 1

No. 1 No. 2

No. 1 No. 2

No. 1 No. 2 No. 3

INV.

INV.

INV.

INV.

INV.

STD1

RXQ22PA

RXQ20PA

STD1

STD1 STD2

RXQ24PA, 26PA

No. 1

No. 2 No. 3

No. 1 No. 3

No. 2 No. 4

No. 1

No. 2 No. 4 No. 5

No. 2

No. 1 No. 3

No. 2 No. 4

No. 1 No. 3

No. 2

No. 1 No. 3 No. 5

INV.

INV.

INV.

INV.

INV.

STD1

STD1

STD1

No. 1 No. 3

No. 2 No. 4 No. 5

No. 1 No. 3 No. 5

No. 2 No. 4 No. 6

No. 2 No. 4

No. 1 No. 3 No. 5

No. 2 No. 4 No. 6

No. 1 No. 3 No. 5

STD1

STD1 STD2

RXQ32PA, 34PA, 36PA

RXQ28PA, 30PA

INV.

INV.

INV.

STD1 STD2

INV.

STD1 STD2

INV.

STD1 STD2

RXQ38PA

84

No. 1

No. 2

No. 4

No. 3 No. 5 No. 6

No. 3

No. 1

No. 4

No. 2 No. 5 No. 6

No. 2

No. 3

No. 5

No. 1 No. 4 No. 6

INV.

INV.

STD1

INV. STD1 STD2

Function

Si34-804_C

Basic Control

RXQ40PA, 42PA, 44PA

No. 1

No. 2 No. 4 No. 6

No. 3 No. 5 No. 7

No. 3

No. 1 No. 4 No. 6

No. 2 No. 5 No. 7

No. 2

No. 3 No. 5 No. 7

No. 1 No. 4 No. 6

INV.

INV. STD1 STD2

INV. STD1 STD2

RXQ46PA, 48PA

No. 1 No. 4

No. 2 No. 5 No. 7

No. 3 No. 6 No. 8

No. 3 No. 6

No. 1 No. 4 No. 7

No. 2 No. 5 No. 8

No. 2 No. 5

No. 3 No. 6 No. 8

No. 1 No. 4 No. 7

INV.

INV. STD1 STD2

INV. STD1 STD2

STD1

RXQ50PA, 52PA, 54PA

No. 1 No. 4 No. 7

No. 2 No. 5 No. 8

No. 3 No. 6 No. 9

No. 3 No. 6 No. 9

No. 1 No. 4 No. 7

No. 2 No. 5 No. 8

No. 2 No. 5 No. 8

No. 3 No. 6 No. 9

No. 1 No. 4 No. 7

INV.

INV.

INV. STD1 STD2

STD1 STD2

STD1 STD2

*
In the case of combination of 3 outdoor units, the above diagram shows master unit, slave unit 1, and slave unit 2
from left to right.
Compressors may operate in any pattern other than those mentioned above according to the operating status.

Function

85

Basic Control

Si34-804_C

Compressor Step Control (Multi outdoor unit connection is available on the standard connection system)

Compressor operations vary with the following steps according to information in "2.2 Compressor PI Control".
Furthermore, the operating priority of compressors is subject to information in " Operating Priority and Rotation of
Compressors".
50 Hz
Stand-alone installation
RXQ5PAY1
RXQ8PAY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

INV.
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

Note:

86

INV.
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz

RXQ10PAY1, 12PAY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37

INV.
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz

STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

RXQ14PAY1, 16PAY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51

INV.
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz

STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

RXQ18PAY1
STD2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55

INV.
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz

STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

STD2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

1. INV. : Inverter compressor


STD1 : Standard compressor 1
STD2 : Standard compressor 2
2. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

Two-unit multi system


RXQ20PAY1 (8+12HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35

(To increase Step No.)


Master Slave
unit
STD
unit
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON
88 Hz
88 Hz
ON
96 Hz
96 Hz
ON
104 Hz 104 Hz
ON
116 Hz 116 Hz
ON
124 Hz 124 Hz
ON
132 Hz 132 Hz
ON
144 Hz 144 Hz
ON
158 Hz 158 Hz
ON
176 Hz 176 Hz
ON
188 Hz 188 Hz
ON
202 Hz 202 Hz
ON
210 Hz 210 Hz
ON
218 Hz 210 Hz
ON
232 Hz 210 Hz
ON
248 Hz 210 Hz
ON
266 Hz 210 Hz
ON

Note:

Function

represents the range in which Hz is not stepped up.


RXQ22PAY1 (10+12HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

(To decrease Step No.)


Master Slave
unit
STD
unit
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
96 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON
62 Hz
62 Hz
ON
68 Hz
68 Hz
ON
74 Hz
74 Hz
ON
80 Hz
80 Hz
ON
88 Hz
88 Hz
ON
96 Hz
96 Hz
ON
104 Hz 104 Hz
ON
116 Hz 116 Hz
ON
124 Hz 124 Hz
ON
132 Hz 132 Hz
ON
144 Hz 144 Hz
ON
158 Hz 158 Hz
ON
176 Hz 176 Hz
ON
188 Hz 188 Hz
ON
202 Hz 202 Hz
ON
210 Hz 210 Hz
ON
218 Hz 210 Hz
ON
232 Hz 210 Hz
ON
248 Hz 210 Hz
ON
266 Hz 210 Hz
ON

(To increase Step No.)


Slave
STEP Master
unit
unit
STD
No.
INV.
INV.
1
52 Hz
52 Hz
OFF
2
56 Hz
56 Hz
OFF
3
62 Hz
62 Hz
OFF
4
66 Hz
66 Hz
OFF
5
70 Hz
70 Hz
OFF
6
74 Hz
74 Hz
OFF
7
80 Hz
80 Hz
OFF
8
88 Hz
88 Hz
OFF
9
96 Hz
96 Hz
OFF
10
104 Hz 104 Hz
OFF
11
110 Hz 110 Hz
OFF
12
116 Hz 116 Hz
OFF
13
124 Hz 124 Hz
OFF
14
132 Hz 132 Hz
OFF
15
144 Hz 144 Hz
OFF
16
158 Hz 158 Hz
OFF
17
166 Hz 166 Hz
OFF
18
176 Hz 176 Hz
OFF
19
80 Hz
80 Hz
ON 1
20
88 Hz
88 Hz
ON 1
21
96 Hz
96 Hz
ON 1
22
104 Hz 104 Hz ON 1
23
116 Hz 116 Hz ON 1
24
124 Hz 124 Hz ON 1
25
132 Hz 132 Hz ON 1
26
88 Hz
88 Hz
ON 2
27
96 Hz
96 Hz
ON 2
28
104 Hz 104 Hz ON 2
29
124 Hz 124 Hz ON 2
30
144 Hz 144 Hz ON 2
31
158 Hz 158 Hz ON 2
32
166 Hz 166 Hz ON 2
33
176 Hz 176 Hz ON 2
34
188 Hz 188 Hz ON 2
35
202 Hz 202 Hz ON 2
36
210 Hz 210 Hz ON 2

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46

(To decrease Step No.)


Master Slave
unit
STD
unit
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
158 Hz 158 Hz ON 2
166 Hz 166 Hz ON 2
176 Hz 176 Hz ON 2
188 Hz 188 Hz ON 2
202 Hz 202 Hz ON 2
210 Hz 210 Hz ON 2

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

87

Basic Control

Si34-804_C

represents the range in which Hz is not stepped up.


RXQ24PAY1 (8+16HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
158 Hz 158 Hz ON 2
166 Hz 166 Hz ON 2
176 Hz 176 Hz ON 2
188 Hz 188 Hz ON 2
202 Hz 202 Hz ON 2
210 Hz 210 Hz ON 2
218 Hz 210 Hz ON 2
232 Hz 210 Hz ON 2
248 Hz 210 Hz ON 2
266 Hz 210 Hz ON 2

Note:

88

RXQ26PAY1 (8+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
158 Hz 158 Hz ON 2
166 Hz 166 Hz ON 2
176 Hz 176 Hz ON 2
188 Hz 188 Hz ON 2
202 Hz 202 Hz ON 2
210 Hz 210 Hz ON 2
218 Hz 210 Hz ON 2
232 Hz 210 Hz ON 2
248 Hz 210 Hz ON 2
266 Hz 210 Hz ON 2

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
158 Hz 158 Hz ON 2
166 Hz 166 Hz ON 2
176 Hz 176 Hz ON 2
188 Hz 188 Hz ON 2
202 Hz 202 Hz ON 2
210 Hz 210 Hz ON 2
218 Hz 218 Hz ON 2
232 Hz 232 Hz ON 2
248 Hz 248 Hz ON 2
266 Hz 266 Hz ON 2

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
158 Hz 158 Hz ON 2
166 Hz 166 Hz ON 2
176 Hz 176 Hz ON 2
188 Hz 188 Hz ON 2
202 Hz 202 Hz ON 2
210 Hz 210 Hz ON 2
218 Hz 218 Hz ON 2
232 Hz 232 Hz ON 2
248 Hz 248 Hz ON 2
266 Hz 266 Hz ON 2

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

represents the range in which Hz is not stepped up.


RXQ28PAY1, 30PAY1 (10/12+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
92 Hz
92 Hz
ON 3
104 Hz 104 Hz ON 3
116 Hz 116 Hz ON 3
124 Hz 124 Hz ON 3
144 Hz 144 Hz ON 3
158 Hz 158 Hz ON 3
166 Hz 166 Hz ON 3
176 Hz 176 Hz ON 3
188 Hz 188 Hz ON 3
202 Hz 202 Hz ON 3
210 Hz 210 Hz ON 3
210 Hz 218 Hz ON 3
210 Hz 232 Hz ON 3
210 Hz 248 Hz ON 3
210 Hz 266 Hz ON 3

Note:

Function

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
52 Hz
52 Hz
ON 3
62 Hz
62 Hz
ON 3
74 Hz
74 Hz
ON 3
92 Hz
92 Hz
ON 3
104 Hz 104 Hz ON 3
116 Hz 116 Hz ON 3
124 Hz 124 Hz ON 3
144 Hz 144 Hz ON 3
158 Hz 158 Hz ON 3
166 Hz 166 Hz ON 3
176 Hz 176 Hz ON 3
188 Hz 188 Hz ON 3
202 Hz 202 Hz ON 3
210 Hz 210 Hz ON 3
210 Hz 218 Hz ON 3
210 Hz 232 Hz ON 3
210 Hz 248 Hz ON 3
210 Hz 266 Hz ON 3

RXQ32PAY1 (16+16HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
92 Hz
96 Hz
ON 3
104 Hz 104 Hz ON 3
116 Hz 116 Hz ON 3
124 Hz 124 Hz ON 3
144 Hz 144 Hz ON 3
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
52 Hz
52 Hz
ON 3
62 Hz
62 Hz
ON 3
74 Hz
74 Hz
ON 3
92 Hz
92 Hz
ON 3
104 Hz 104 Hz ON 3
52 Hz
52 Hz
ON 4
62 Hz
62 Hz
ON 4
74 Hz
74 Hz
ON 4
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

89

Basic Control

Si34-804_C

represents the range in which Hz is not stepped up.


RXQ34PAY1 (16+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
92 Hz
96 Hz
ON 3
104 Hz 104 Hz ON 3
116 Hz 116 Hz ON 3
124 Hz 124 Hz ON 3
144 Hz 144 Hz ON 3
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4
210 Hz 218 Hz ON 4
210 Hz 232 Hz ON 4
210 Hz 248 Hz ON 4
210 Hz 266 Hz ON 4

Note:

90

RXQ36PAY1 (18+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
52 Hz
52 Hz
ON 3
62 Hz
62 Hz
ON 3
74 Hz
74 Hz
ON 3
92 Hz
92 Hz
ON 3
104 Hz 104 Hz ON 3
52 Hz
52 Hz
ON 4
62 Hz
62 Hz
ON 4
74 Hz
74 Hz
ON 4
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4
210 Hz 218 Hz ON 4
210 Hz 232 Hz ON 4
210 Hz 248 Hz ON 4
210 Hz 266 Hz ON 4

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

(To increase Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
144 Hz 144 Hz
OFF
158 Hz 158 Hz
OFF
166 Hz 166 Hz
OFF
176 Hz 176 Hz
OFF
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
116 Hz 116 Hz ON 1
124 Hz 124 Hz ON 1
132 Hz 132 Hz ON 1
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
104 Hz 104 Hz ON 2
124 Hz 124 Hz ON 2
144 Hz 144 Hz ON 2
92 Hz
96 Hz
ON 3
104 Hz 104 Hz ON 3
116 Hz 116 Hz ON 3
124 Hz 124 Hz ON 3
144 Hz 144 Hz ON 3
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz
ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4
218 Hz 218 Hz ON 4
232 Hz 232 Hz ON 4
248 Hz 248 Hz ON 4
266 Hz 266 Hz ON 4

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

(To decrease Step No.)


Master Slave
unit
unit
STD
INV.
INV.
52 Hz
OFF
OFF
56 Hz
OFF
OFF
62 Hz
OFF
OFF
68 Hz
OFF
OFF
74 Hz
OFF
OFF
80 Hz
OFF
OFF
88 Hz
OFF
OFF
96 Hz
OFF
OFF
104 Hz
OFF
OFF
52 Hz
52 Hz
OFF
56 Hz
56 Hz
OFF
62 Hz
62 Hz
OFF
66 Hz
66 Hz
OFF
70 Hz
70 Hz
OFF
74 Hz
74 Hz
OFF
80 Hz
80 Hz
OFF
88 Hz
88 Hz
OFF
92 Hz
92 Hz
OFF
96 Hz
96 Hz
OFF
104 Hz 104 Hz
OFF
110 Hz 110 Hz
OFF
116 Hz 116 Hz
OFF
124 Hz 124 Hz
OFF
132 Hz 132 Hz
OFF
52 Hz
52 Hz
ON 1
62 Hz
62 Hz
ON 1
68 Hz
68 Hz
ON 1
74 Hz
74 Hz
ON 1
80 Hz
80 Hz
ON 1
88 Hz
88 Hz
ON 1
96 Hz
96 Hz
ON 1
104 Hz 104 Hz ON 1
52 Hz
52 Hz
ON 2
62 Hz
62 Hz
ON 2
74 Hz
74 Hz
ON 2
88 Hz
88 Hz
ON 2
96 Hz
96 Hz
ON 2
52 Hz
52 Hz
ON 3
62 Hz
62 Hz
ON 3
74 Hz
74 Hz
ON 3
92 Hz
92 Hz
ON 3
104 Hz 104 Hz ON 3
52 Hz
52 Hz
ON 4
62 Hz
62 Hz
ON 4
74 Hz
74 Hz
ON 4
96 Hz
96 Hz
ON 4
104 Hz 104 Hz ON 4
116 Hz 116 Hz ON 4
124 Hz 124 Hz ON 4
144 Hz 144 Hz ON 4
158 Hz 158 Hz ON 4
166 Hz 166 Hz ON 4
176 Hz 176 Hz ON 4
188 Hz 188 Hz ON 4
202 Hz 202 Hz ON 4
210 Hz 210 Hz ON 4
218 Hz 218 Hz ON 4
232 Hz 232 Hz ON 4
248 Hz 248 Hz ON 4
266 Hz 266 Hz ON 4

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

Three-unit multi system


RXQ38PAY1 (8+12+18HP)
(To increase Step No.)
Master
Slave
STEP unit Slave
unit1 unit2
No.
INV. INV. INV.
1
52 Hz 52 Hz 52 Hz
2
56 Hz 56 Hz 56 Hz
3
62 Hz 62 Hz 62 Hz
4
66 Hz 66 Hz 66 Hz
5
68 Hz 68 Hz 68 Hz
6
70 Hz 70 Hz 70 Hz
7
74 Hz 74 Hz 74 Hz
8
80 Hz 80 Hz 80 Hz
9
88 Hz 88 Hz 88 Hz
10 96 Hz 96 Hz 96 Hz
11 104 Hz 104 Hz 104 Hz
12 110 Hz 110 Hz 110 Hz
13 116 Hz 116 Hz 116 Hz
14 124 Hz 124 Hz 124 Hz
15 80 Hz 80 Hz 80 Hz
16 88 Hz 88 Hz 88 Hz
17 96 Hz 96 Hz 96 Hz
18 104 Hz 104 Hz 104 Hz
19 116 Hz 116 Hz 116 Hz
20 124 Hz 124 Hz 124 Hz
21 132 Hz 132 Hz 132 Hz
22 88 Hz 88 Hz 88 Hz
23 96 Hz 96 Hz 96 Hz
24 104 Hz 104 Hz 104 Hz
25 124 Hz 124 Hz 124 Hz
26 144 Hz 144 Hz 144 Hz
27 92 Hz 92 Hz 92 Hz
28 104 Hz 104 Hz 104 Hz
29 116 Hz 116 Hz 116 Hz
30 124 Hz 124 Hz 124 Hz
31 144 Hz 144 Hz 144 Hz
32 158 Hz 158 Hz 158 Hz
33 166 Hz 166 Hz 166 Hz
34 176 Hz 176 Hz 176 Hz
35 188 Hz 188 Hz 188 Hz
36 202 Hz 202 Hz 202 Hz
37 210 Hz 210 Hz 210 Hz
38 218 Hz 210 Hz 218 Hz
39 232 Hz 210 Hz 232 Hz
40 248 Hz 210 Hz 248 Hz
41 266 Hz 210 Hz 266 Hz

Note:

Function

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3

represents the range in which Hz is not stepped up.


RXQ40PAY1 (8+16+16HP)
(To decrease Step No.)
Master
Slave
STEP unit Slave
unit1 unit2 STD
No.
INV. INV. INV.
1
52 Hz OFF OFF OFF
2
56 Hz OFF OFF OFF
3
62 Hz OFF OFF OFF
4
68 Hz OFF OFF OFF
5
74 Hz OFF OFF OFF
6
80 Hz OFF OFF OFF
7
88 Hz OFF OFF OFF
8
96 Hz OFF OFF OFF
9 104 Hz OFF OFF OFF
10 52 Hz 52 Hz OFF OFF
11 56 Hz 56 Hz OFF OFF
12 62 Hz 62 Hz OFF OFF
13 66 Hz 66 Hz OFF OFF
14 70 Hz 70 Hz OFF OFF
15 74 Hz 74 Hz OFF OFF
16 52 Hz 52 Hz 52 Hz OFF
17 56 Hz 56 Hz 56 Hz OFF
18 62 Hz 62 Hz 62 Hz OFF
19 66 Hz 66 Hz 66 Hz OFF
20 68 Hz 68 Hz 68 Hz OFF
21 70 Hz 70 Hz 70 Hz OFF
22 74 Hz 74 Hz 74 Hz OFF
23 80 Hz 80 Hz 80 Hz OFF
24 88 Hz 88 Hz 88 Hz OFF
25 96 Hz 96 Hz 96 Hz OFF
26 52 Hz 52 Hz 52 Hz ON 1
27 62 Hz 62 Hz 62 Hz ON 1
28 68 Hz 68 Hz 68 Hz ON 1
29 74 Hz 74 Hz 74 Hz ON 1
30 80 Hz 80 Hz 80 Hz ON 1
31 88 Hz 88 Hz 88 Hz ON 1
32 96 Hz 96 Hz 96 Hz ON 1
33 104 Hz 104 Hz 104 Hz ON 1
34 52 Hz 52 Hz 52 Hz ON 2
35 62 Hz 62 Hz 62 Hz ON 2
36 74 Hz 74 Hz 74 Hz ON 2
37 88 Hz 88 Hz 88 Hz ON 2
38 96 Hz 96 Hz 96 Hz ON 2
39 52 Hz 52 Hz 52 Hz ON 3
40 62 Hz 62 Hz 62 Hz ON 3
41 74 Hz 74 Hz 74 Hz ON 3
42 92 Hz 92 Hz 92 Hz ON 3
43 104 Hz 104 Hz 104 Hz ON 3
44 116 Hz 116 Hz 116 Hz ON 3
45 124 Hz 124 Hz 124 Hz ON 3
46 144 Hz 144 Hz 144 Hz ON 3
47 158 Hz 158 Hz 158 Hz ON 3
48 166 Hz 166 Hz 166 Hz ON 3
49 176 Hz 176 Hz 176 Hz ON 3
50 188 Hz 188 Hz 188 Hz ON 3
51 202 Hz 202 Hz 202 Hz ON 3
52 210 Hz 210 Hz 210 Hz ON 3
53 218 Hz 210 Hz 218 Hz ON 3
54 232 Hz 210 Hz 232 Hz ON 3
55 248 Hz 210 Hz 248 Hz ON 3
56 266 Hz 210 Hz 266 Hz ON 3

(To increase Step No.)


Master
Slave
STEP unit Slave
unit1 unit2
No.
INV. INV. INV.
1
52 Hz 52 Hz 52 Hz
2
56 Hz 56 Hz 56 Hz
3
62 Hz 62 Hz 62 Hz
4
66 Hz 66 Hz 66 Hz
5
68 Hz 68 Hz 68 Hz
6
70 Hz 70 Hz 70 Hz
7
74 Hz 74 Hz 74 Hz
8
80 Hz 80 Hz 80 Hz
9
88 Hz 88 Hz 88 Hz
10 96 Hz 96 Hz 96 Hz
11 104 Hz 104 Hz 104 Hz
12 110 Hz 110 Hz 110 Hz
13 116 Hz 116 Hz 116 Hz
14 124 Hz 124 Hz 124 Hz
15 80 Hz 80 Hz 80 Hz
16 88 Hz 88 Hz 88 Hz
17 96 Hz 96 Hz 96 Hz
18 104 Hz 104 Hz 104 Hz
19 116 Hz 116 Hz 116 Hz
20 124 Hz 124 Hz 124 Hz
21 132 Hz 132 Hz 132 Hz
22 88 Hz 88 Hz 88 Hz
23 96 Hz 96 Hz 96 Hz
24 104 Hz 104 Hz 104 Hz
25 124 Hz 124 Hz 124 Hz
26 144 Hz 144 Hz 144 Hz
27 92 Hz 92 Hz 92 Hz
28 104 Hz 104 Hz 104 Hz
29 116 Hz 116 Hz 116 Hz
30 124 Hz 124 Hz 124 Hz
31 144 Hz 144 Hz 144 Hz
32 96 Hz 96 Hz 96 Hz
33 104 Hz 104 Hz 104 Hz
34 116 Hz 116 Hz 116 Hz
35 124 Hz 124 Hz 124 Hz
36 144 Hz 144 Hz 144 Hz
37 158 Hz 158 Hz 158 Hz
38 166 Hz 166 Hz 166 Hz
39 176 Hz 176 Hz 176 Hz
40 188 Hz 188 Hz 188 Hz
41 202 Hz 202 Hz 202 Hz
42 210 Hz 210 Hz 210 Hz
43 218 Hz 210 Hz 210 Hz
44 232 Hz 210 Hz 210 Hz
45 248 Hz 210 Hz 210 Hz
46 266 Hz 210 Hz 210 Hz

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4

(To decrease Step No.)


Master
Slave
STEP unit Slave
unit1 unit2 STD
No.
INV. INV. INV.
1
52 Hz OFF OFF OFF
2
56 Hz OFF OFF OFF
3
62 Hz OFF OFF OFF
4
68 Hz OFF OFF OFF
5
74 Hz OFF OFF OFF
6
80 Hz OFF OFF OFF
7
88 Hz OFF OFF OFF
8
96 Hz OFF OFF OFF
9 104 Hz OFF OFF OFF
10 52 Hz 52 Hz OFF OFF
11 56 Hz 56 Hz OFF OFF
12 62 Hz 62 Hz OFF OFF
13 66 Hz 66 Hz OFF OFF
14 70 Hz 70 Hz OFF OFF
15 74 Hz 74 Hz OFF OFF
16 52 Hz 52 Hz 52 Hz OFF
17 56 Hz 56 Hz 56 Hz OFF
18 62 Hz 62 Hz 62 Hz OFF
19 66 Hz 66 Hz 66 Hz OFF
20 68 Hz 68 Hz 68 Hz OFF
21 70 Hz 70 Hz 70 Hz OFF
22 74 Hz 74 Hz 74 Hz OFF
23 80 Hz 80 Hz 80 Hz OFF
24 88 Hz 88 Hz 88 Hz OFF
25 96 Hz 96 Hz 96 Hz OFF
26 52 Hz 52 Hz 52 Hz ON 1
27 62 Hz 62 Hz 62 Hz ON 1
28 68 Hz 68 Hz 68 Hz ON 1
29 74 Hz 74 Hz 74 Hz ON 1
30 80 Hz 80 Hz 80 Hz ON 1
31 88 Hz 88 Hz 88 Hz ON 1
32 96 Hz 96 Hz 96 Hz ON 1
33 104 Hz 104 Hz 104 Hz ON 1
34 52 Hz 52 Hz 52 Hz ON 2
35 62 Hz 62 Hz 62 Hz ON 2
36 74 Hz 74 Hz 74 Hz ON 2
37 88 Hz 88 Hz 88 Hz ON 2
38 96 Hz 96 Hz 96 Hz ON 2
39 52 Hz 52 Hz 52 Hz ON 3
40 62 Hz 62 Hz 62 Hz ON 3
41 74 Hz 74 Hz 74 Hz ON 3
42 92 Hz 92 Hz 92 Hz ON 3
43 104 Hz 104 Hz 104 Hz ON 3
44 52 Hz 52 Hz 52 Hz ON 4
45 62 Hz 62 Hz 62 Hz ON 4
46 74 Hz 74 Hz 74 Hz ON 4
47 96 Hz 96 Hz 96 Hz ON 4
48 104 Hz 104 Hz 104 Hz ON 4
49 116 Hz 116 Hz 116 Hz ON 4
50 124 Hz 124 Hz 124 Hz ON 4
51 144 Hz 144 Hz 144 Hz ON 4
52 158 Hz 158 Hz 158 Hz ON 4
53 166 Hz 166 Hz 166 Hz ON 4
54 176 Hz 176 Hz 176 Hz ON 4
55 188 Hz 188 Hz 188 Hz ON 4
56 202 Hz 202 Hz 202 Hz ON 4
57 210 Hz 210 Hz 210 Hz ON 4
58 218 Hz 210 Hz 210 Hz ON 4
59 232 Hz 210 Hz 210 Hz ON 4
60 248 Hz 210 Hz 210 Hz ON 4
61 266 Hz 210 Hz 210 Hz ON 4

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

91

Basic Control

Si34-804_C

represents the range in which Hz is not stepped up.


RXQ42PAY1 (8+16+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46

(To increase Step No.)


Master Slave Slave
unit unit1 unit2
INV. INV. INV.
52 Hz 52 Hz 52 Hz
56 Hz 56 Hz 56 Hz
62 Hz 62 Hz 62 Hz
66 Hz 66 Hz 66 Hz
68 Hz 68 Hz 68 Hz
70 Hz 70 Hz 70 Hz
74 Hz 74 Hz 74 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
110 Hz 110 Hz 110 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
132 Hz 132 Hz 132 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
92 Hz 92 Hz 92 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
158 Hz 158 Hz 158 Hz
166 Hz 166 Hz 166 Hz
176 Hz 176 Hz 176 Hz
188 Hz 188 Hz 188 Hz
202 Hz 202 Hz 202 Hz
210 Hz 210 Hz 210 Hz
218 Hz 210 Hz 218 Hz
232 Hz 210 Hz 232 Hz
248 Hz 210 Hz 248 Hz
266 Hz 210 Hz 266 Hz

Note:

92

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4

RXQ44PAY1 (8+18+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61

(To decrease Step No.)


Master Slave Slave
unit unit1 unit2 STD
INV. INV. INV.
52 Hz OFF OFF OFF
56 Hz OFF OFF OFF
62 Hz OFF OFF OFF
68 Hz OFF OFF OFF
74 Hz OFF OFF OFF
80 Hz OFF OFF OFF
88 Hz OFF OFF OFF
96 Hz OFF OFF OFF
104 Hz OFF OFF OFF
52 Hz 52 Hz OFF OFF
56 Hz 56 Hz OFF OFF
62 Hz 62 Hz OFF OFF
66 Hz 66 Hz OFF OFF
70 Hz 70 Hz OFF OFF
74 Hz 74 Hz OFF OFF
52 Hz 52 Hz 52 Hz OFF
56 Hz 56 Hz 56 Hz OFF
62 Hz 62 Hz 62 Hz OFF
66 Hz 66 Hz 66 Hz OFF
68 Hz 68 Hz 68 Hz OFF
70 Hz 70 Hz 70 Hz OFF
74 Hz 74 Hz 74 Hz OFF
80 Hz 80 Hz 80 Hz OFF
88 Hz 88 Hz 88 Hz OFF
96 Hz 96 Hz 96 Hz OFF
52 Hz 52 Hz 52 Hz ON 1
62 Hz 62 Hz 62 Hz ON 1
68 Hz 68 Hz 68 Hz ON 1
74 Hz 74 Hz 74 Hz ON 1
80 Hz 80 Hz 80 Hz ON 1
88 Hz 88 Hz 88 Hz ON 1
96 Hz 96 Hz 96 Hz ON 1
104 Hz 104 Hz 104 Hz ON 1
52 Hz 52 Hz 52 Hz ON 2
62 Hz 62 Hz 62 Hz ON 2
74 Hz 74 Hz 74 Hz ON 2
88 Hz 88 Hz 88 Hz ON 2
96 Hz 96 Hz 96 Hz ON 2
52 Hz 52 Hz 52 Hz ON 3
62 Hz 62 Hz 62 Hz ON 3
74 Hz 74 Hz 74 Hz ON 3
92 Hz 92 Hz 92 Hz ON 3
104 Hz 104 Hz 104 Hz ON 3
52 Hz 52 Hz 52 Hz ON 4
62 Hz 62 Hz 62 Hz ON 4
74 Hz 74 Hz 74 Hz ON 4
96 Hz 96 Hz 96 Hz ON 4
104 Hz 104 Hz 104 Hz ON 4
116 Hz 116 Hz 116 Hz ON 4
124 Hz 124 Hz 124 Hz ON 4
144 Hz 144 Hz 144 Hz ON 4
158 Hz 158 Hz 158 Hz ON 4
166 Hz 166 Hz 166 Hz ON 4
176 Hz 176 Hz 176 Hz ON 4
188 Hz 188 Hz 188 Hz ON 4
202 Hz 202 Hz 202 Hz ON 4
210 Hz 210 Hz 210 Hz ON 4
218 Hz 210 Hz 218 Hz ON 4
232 Hz 210 Hz 232 Hz ON 4
248 Hz 210 Hz 248 Hz ON 4
266 Hz 210 Hz 266 Hz ON 4

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46

(To increase Step No.)


Master Slave Slave
unit unit1 unit2
INV. INV. INV.
52 Hz 52 Hz 52 Hz
56 Hz 56 Hz 56 Hz
62 Hz 62 Hz 62 Hz
66 Hz 66 Hz 66 Hz
68 Hz 68 Hz 68 Hz
70 Hz 70 Hz 70 Hz
74 Hz 74 Hz 74 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
110 Hz 110 Hz 110 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
132 Hz 132 Hz 132 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
92 Hz 92 Hz 92 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
158 Hz 158 Hz 158 Hz
166 Hz 166 Hz 166 Hz
176 Hz 176 Hz 176 Hz
188 Hz 188 Hz 188 Hz
202 Hz 202 Hz 202 Hz
210 Hz 210 Hz 210 Hz
218 Hz 218 Hz 218 Hz
232 Hz 232 Hz 232 Hz
248 Hz 248 Hz 248 Hz
266 Hz 266 Hz 266 Hz

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61

(To decrease Step No.)


Master Slave Slave
unit unit1 unit2 STD
INV. INV. INV.
52 Hz OFF OFF OFF
56 Hz OFF OFF OFF
62 Hz OFF OFF OFF
68 Hz OFF OFF OFF
74 Hz OFF OFF OFF
80 Hz OFF OFF OFF
88 Hz OFF OFF OFF
96 Hz OFF OFF OFF
104 Hz OFF OFF OFF
52 Hz 52 Hz OFF OFF
56 Hz 56 Hz OFF OFF
62 Hz 62 Hz OFF OFF
66 Hz 66 Hz OFF OFF
70 Hz 70 Hz OFF OFF
74 Hz 74 Hz OFF OFF
52 Hz 52 Hz 52 Hz OFF
56 Hz 56 Hz 56 Hz OFF
62 Hz 62 Hz 62 Hz OFF
66 Hz 66 Hz 66 Hz OFF
68 Hz 68 Hz 68 Hz OFF
70 Hz 70 Hz 70 Hz OFF
74 Hz 74 Hz 74 Hz OFF
80 Hz 80 Hz 80 Hz OFF
88 Hz 88 Hz 88 Hz OFF
96 Hz 96 Hz 96 Hz OFF
52 Hz 52 Hz 52 Hz ON 1
62 Hz 62 Hz 62 Hz ON 1
68 Hz 68 Hz 68 Hz ON 1
74 Hz 74 Hz 74 Hz ON 1
80 Hz 80 Hz 80 Hz ON 1
88 Hz 88 Hz 88 Hz ON 1
96 Hz 96 Hz 96 Hz ON 1
104 Hz 104 Hz 104 Hz ON 1
52 Hz 52 Hz 52 Hz ON 2
62 Hz 62 Hz 62 Hz ON 2
74 Hz 74 Hz 74 Hz ON 2
88 Hz 88 Hz 88 Hz ON 2
96 Hz 96 Hz 96 Hz ON 2
52 Hz 52 Hz 52 Hz ON 3
62 Hz 62 Hz 62 Hz ON 3
74 Hz 74 Hz 74 Hz ON 3
92 Hz 92 Hz 92 Hz ON 3
104 Hz 104 Hz 104 Hz ON 3
52 Hz 52 Hz 52 Hz ON 4
62 Hz 62 Hz 62 Hz ON 4
74 Hz 74 Hz 74 Hz ON 4
96 Hz 96 Hz 96 Hz ON 4
104 Hz 104 Hz 104 Hz ON 4
116 Hz 116 Hz 116 Hz ON 4
124 Hz 124 Hz 124 Hz ON 4
144 Hz 144 Hz 144 Hz ON 4
158 Hz 158 Hz 158 Hz ON 4
166 Hz 166 Hz 166 Hz ON 4
176 Hz 176 Hz 176 Hz ON 4
188 Hz 188 Hz 188 Hz ON 4
202 Hz 202 Hz 202 Hz ON 4
210 Hz 210 Hz 210 Hz ON 4
218 Hz 218 Hz 218 Hz ON 4
232 Hz 232 Hz 232 Hz ON 4
248 Hz 248 Hz 248 Hz ON 4
266 Hz 266 Hz 266 Hz ON 4

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

represents the range in which Hz is not stepped up.


RXQ46PAY1, 48PAY1 (10/12+18+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66

(To increase Step No.)


Master Slave Slave
unit unit1 unit2
INV. INV. INV.
52 Hz 52 Hz 52 Hz
56 Hz 56 Hz 56 Hz
62 Hz 62 Hz 62 Hz
66 Hz 66 Hz 66 Hz
68 Hz 68 Hz 68 Hz
70 Hz 70 Hz 70 Hz
74 Hz 74 Hz 74 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
110 Hz 110 Hz 110 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
132 Hz 132 Hz 132 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
92 Hz 92 Hz 92 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
158 Hz 158 Hz 158 Hz
166 Hz 166 Hz 166 Hz
176 Hz 176 Hz 176 Hz
188 Hz 188 Hz 188 Hz
202 Hz 202 Hz 202 Hz
210 Hz 210 Hz 210 Hz
210 Hz 218 Hz 218 Hz
210 Hz 232 Hz 232 Hz
210 Hz 248 Hz 248 Hz
210 Hz 266 Hz 266 Hz

Note:

Function

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5
ON 5

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66

(To decrease Step No.)


Master Slave Slave
unit unit1 unit2 STD
INV. INV. INV.
52 Hz OFF OFF OFF
56 Hz OFF OFF OFF
62 Hz OFF OFF OFF
68 Hz OFF OFF OFF
74 Hz OFF OFF OFF
80 Hz OFF OFF OFF
88 Hz OFF OFF OFF
96 Hz OFF OFF OFF
104 Hz OFF OFF OFF
52 Hz 52 Hz OFF OFF
56 Hz 56 Hz OFF OFF
62 Hz 62 Hz OFF OFF
66 Hz 66 Hz OFF OFF
70 Hz 70 Hz OFF OFF
74 Hz 74 Hz OFF OFF
52 Hz 52 Hz 52 Hz OFF
56 Hz 56 Hz 56 Hz OFF
62 Hz 62 Hz 62 Hz OFF
66 Hz 66 Hz 66 Hz OFF
68 Hz 68 Hz 68 Hz OFF
70 Hz 70 Hz 70 Hz OFF
74 Hz 74 Hz 74 Hz OFF
80 Hz 80 Hz 80 Hz OFF
88 Hz 88 Hz 88 Hz OFF
96 Hz 96 Hz 96 Hz OFF
52 Hz 52 Hz 52 Hz ON 1
62 Hz 62 Hz 62 Hz ON 1
68 Hz 68 Hz 68 Hz ON 1
74 Hz 74 Hz 74 Hz ON 1
80 Hz 80 Hz 80 Hz ON 1
88 Hz 88 Hz 88 Hz ON 1
96 Hz 96 Hz 96 Hz ON 1
104 Hz 104 Hz 104 Hz ON 1
52 Hz 52 Hz 52 Hz ON 2
62 Hz 62 Hz 62 Hz ON 2
74 Hz 74 Hz 74 Hz ON 2
88 Hz 88 Hz 88 Hz ON 2
96 Hz 96 Hz 96 Hz ON 2
52 Hz 52 Hz 52 Hz ON 3
62 Hz 62 Hz 62 Hz ON 3
74 Hz 74 Hz 74 Hz ON 3
92 Hz 92 Hz 92 Hz ON 3
104 Hz 104 Hz 104 Hz ON 3
52 Hz 52 Hz 52 Hz ON 4
62 Hz 62 Hz 62 Hz ON 4
74 Hz 74 Hz 74 Hz ON 4
96 Hz 96 Hz 96 Hz ON 4
104 Hz 104 Hz 104 Hz ON 4
52 Hz 52 Hz 52 Hz ON 5
68 Hz 68 Hz 68 Hz ON 5
80 Hz 80 Hz 80 Hz ON 5
96 Hz 96 Hz 96 Hz ON 5
104 Hz 104 Hz 104 Hz ON 5
116 Hz 116 Hz 116 Hz ON 5
124 Hz 124 Hz 124 Hz ON 5
144 Hz 144 Hz 144 Hz ON 5
158 Hz 158 Hz 158 Hz ON 5
166 Hz 166 Hz 166 Hz ON 5
176 Hz 176 Hz 176 Hz ON 5
188 Hz 188 Hz 188 Hz ON 5
202 Hz 202 Hz 202 Hz ON 5
210 Hz 210 Hz 210 Hz ON 5
210 Hz 218 Hz 218 Hz ON 5
210 Hz 232 Hz 232 Hz ON 5
210 Hz 248 Hz 248 Hz ON 5
210 Hz 266 Hz 266 Hz ON 5

RXQ50PAY1, 52PAY1 (14/16+18+18HP)


STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

(To increase Step No.)


Master Slave Slave
unit unit1 unit2
INV. INV. INV.
52 Hz 52 Hz 52 Hz
56 Hz 56 Hz 56 Hz
62 Hz 62 Hz 62 Hz
66 Hz 66 Hz 66 Hz
68 Hz 68 Hz 68 Hz
70 Hz 70 Hz 70 Hz
74 Hz 74 Hz 74 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
110 Hz 110 Hz 110 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
132 Hz 132 Hz 132 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
92 Hz 92 Hz 92 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
158 Hz 158 Hz 158 Hz
166 Hz 166 Hz 166 Hz
176 Hz 176 Hz 176 Hz
188 Hz 188 Hz 188 Hz
202 Hz 202 Hz 202 Hz
210 Hz 210 Hz 210 Hz
210 Hz 218 Hz 218 Hz
210 Hz 232 Hz 232 Hz
210 Hz 248 Hz 248 Hz
210 Hz 266 Hz 266 Hz

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71

(To decrease Step No.)


Master Slave Slave
unit unit1 unit2 STD
INV. INV. INV.
52 Hz OFF OFF OFF
56 Hz OFF OFF OFF
62 Hz OFF OFF OFF
68 Hz OFF OFF OFF
74 Hz OFF OFF OFF
80 Hz OFF OFF OFF
88 Hz OFF OFF OFF
96 Hz OFF OFF OFF
104 Hz OFF OFF OFF
52 Hz 52 Hz OFF OFF
56 Hz 56 Hz OFF OFF
62 Hz 62 Hz OFF OFF
66 Hz 66 Hz OFF OFF
70 Hz 70 Hz OFF OFF
74 Hz 74 Hz OFF OFF
52 Hz 52 Hz 52 Hz OFF
56 Hz 56 Hz 56 Hz OFF
62 Hz 62 Hz 62 Hz OFF
66 Hz 66 Hz 66 Hz OFF
68 Hz 68 Hz 68 Hz OFF
70 Hz 70 Hz 70 Hz OFF
74 Hz 74 Hz 74 Hz OFF
80 Hz 80 Hz 80 Hz OFF
88 Hz 88 Hz 88 Hz OFF
96 Hz 96 Hz 96 Hz OFF
52 Hz 52 Hz 52 Hz ON 1
62 Hz 62 Hz 62 Hz ON 1
68 Hz 68 Hz 68 Hz ON 1
74 Hz 74 Hz 74 Hz ON 1
80 Hz 80 Hz 80 Hz ON 1
88 Hz 88 Hz 88 Hz ON 1
96 Hz 96 Hz 96 Hz ON 1
104 Hz 104 Hz 104 Hz ON 1
52 Hz 52 Hz 52 Hz ON 2
62 Hz 62 Hz 62 Hz ON 2
74 Hz 74 Hz 74 Hz ON 2
88 Hz 88 Hz 88 Hz ON 2
96 Hz 96 Hz 96 Hz ON 2
52 Hz 52 Hz 52 Hz ON 3
62 Hz 62 Hz 62 Hz ON 3
74 Hz 74 Hz 74 Hz ON 3
92 Hz 92 Hz 92 Hz ON 3
104 Hz 104 Hz 104 Hz ON 3
52 Hz 52 Hz 52 Hz ON 4
62 Hz 62 Hz 62 Hz ON 4
74 Hz 74 Hz 74 Hz ON 4
96 Hz 96 Hz 96 Hz ON 4
104 Hz 104 Hz 104 Hz ON 4
52 Hz 52 Hz 52 Hz ON 5
68 Hz 68 Hz 68 Hz ON 5
80 Hz 80 Hz 80 Hz ON 5
96 Hz 96 Hz 96 Hz ON 5
104 Hz 104 Hz 104 Hz ON 5
52 Hz 52 Hz 52 Hz ON 6
68 Hz 68 Hz 68 Hz ON 6
80 Hz 80 Hz 80 Hz ON 6
96 Hz 96 Hz 96 Hz ON 6
104 Hz 104 Hz 104 Hz ON 6
116 Hz 116 Hz 116 Hz ON 6
124 Hz 124 Hz 124 Hz ON 6
144 Hz 144 Hz 144 Hz ON 6
158 Hz 158 Hz 158 Hz ON 6
166 Hz 166 Hz 166 Hz ON 6
176 Hz 176 Hz 176 Hz ON 6
188 Hz 188 Hz 188 Hz ON 6
202 Hz 202 Hz 202 Hz ON 6
210 Hz 210 Hz 210 Hz ON 6
210 Hz 218 Hz 218 Hz ON 6
210 Hz 232 Hz 232 Hz ON 6
210 Hz 248 Hz 248 Hz ON 6
210 Hz 266 Hz 266 Hz ON 6

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

93

Basic Control

Si34-804_C

RXQ54PAY1 (18+18+18HP)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

(To increase Step No.)


Master Slave Slave
unit unit1 unit2
INV. INV. INV.
52 Hz 52 Hz 52 Hz
56 Hz 56 Hz 56 Hz
62 Hz 62 Hz 62 Hz
66 Hz 66 Hz 66 Hz
68 Hz 68 Hz 68 Hz
70 Hz 70 Hz 70 Hz
74 Hz 74 Hz 74 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
110 Hz 110 Hz 110 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
80 Hz 80 Hz 80 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
132 Hz 132 Hz 132 Hz
88 Hz 88 Hz 88 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
92 Hz 92 Hz 92 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
96 Hz 96 Hz 96 Hz
104 Hz 104 Hz 104 Hz
116 Hz 116 Hz 116 Hz
124 Hz 124 Hz 124 Hz
144 Hz 144 Hz 144 Hz
158 Hz 158 Hz 158 Hz
166 Hz 166 Hz 166 Hz
176 Hz 176 Hz 176 Hz
188 Hz 188 Hz 188 Hz
202 Hz 202 Hz 202 Hz
210 Hz 210 Hz 210 Hz
218 Hz 218 Hz 218 Hz
232 Hz 232 Hz 232 Hz
248 Hz 248 Hz 248 Hz
266 Hz 266 Hz 266 Hz

Note:

94

STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6

STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71

(To decrease Step No.)


Master Slave Slave
unit unit1 unit2 STD
INV. INV. INV.
52 Hz OFF OFF OFF
56 Hz OFF OFF OFF
62 Hz OFF OFF OFF
68 Hz OFF OFF OFF
74 Hz OFF OFF OFF
80 Hz OFF OFF OFF
88 Hz OFF OFF OFF
96 Hz OFF OFF OFF
104 Hz OFF OFF OFF
52 Hz 52 Hz OFF OFF
56 Hz 56 Hz OFF OFF
62 Hz 62 Hz OFF OFF
66 Hz 66 Hz OFF OFF
70 Hz 70 Hz OFF OFF
74 Hz 74 Hz OFF OFF
52 Hz 52 Hz 52 Hz OFF
56 Hz 56 Hz 56 Hz OFF
62 Hz 62 Hz 62 Hz OFF
66 Hz 66 Hz 66 Hz OFF
68 Hz 68 Hz 68 Hz OFF
70 Hz 70 Hz 70 Hz OFF
74 Hz 74 Hz 74 Hz OFF
80 Hz 80 Hz 80 Hz OFF
88 Hz 88 Hz 88 Hz OFF
96 Hz 96 Hz 96 Hz OFF
52 Hz 52 Hz 52 Hz ON 1
62 Hz 62 Hz 62 Hz ON 1
68 Hz 68 Hz 68 Hz ON 1
74 Hz 74 Hz 74 Hz ON 1
80 Hz 80 Hz 80 Hz ON 1
88 Hz 88 Hz 88 Hz ON 1
96 Hz 96 Hz 96 Hz ON 1
104 Hz 104 Hz 104 Hz ON 1
52 Hz 52 Hz 52 Hz ON 2
62 Hz 62 Hz 62 Hz ON 2
74 Hz 74 Hz 74 Hz ON 2
88 Hz 88 Hz 88 Hz ON 2
96 Hz 96 Hz 96 Hz ON 2
52 Hz 52 Hz 52 Hz ON 3
62 Hz 62 Hz 62 Hz ON 3
74 Hz 74 Hz 74 Hz ON 3
92 Hz 92 Hz 92 Hz ON 3
104 Hz 104 Hz 104 Hz ON 3
52 Hz 52 Hz 52 Hz ON 4
62 Hz 62 Hz 62 Hz ON 4
74 Hz 74 Hz 74 Hz ON 4
96 Hz 96 Hz 96 Hz ON 4
104 Hz 104 Hz 104 Hz ON 4
52 Hz 52 Hz 52 Hz ON 5
68 Hz 68 Hz 68 Hz ON 5
80 Hz 80 Hz 80 Hz ON 5
96 Hz 96 Hz 96 Hz ON 5
104 Hz 104 Hz 104 Hz ON 5
52 Hz 52 Hz 52 Hz ON 6
68 Hz 68 Hz 68 Hz ON 6
80 Hz 80 Hz 80 Hz ON 6
96 Hz 96 Hz 96 Hz ON 6
104 Hz 104 Hz 104 Hz ON 6
116 Hz 116 Hz 116 Hz ON 6
124 Hz 124 Hz 124 Hz ON 6
144 Hz 144 Hz 144 Hz ON 6
158 Hz 158 Hz 158 Hz ON 6
166 Hz 166 Hz 166 Hz ON 6
176 Hz 176 Hz 176 Hz ON 6
188 Hz 188 Hz 188 Hz ON 6
202 Hz 202 Hz 202 Hz ON 6
210 Hz 210 Hz 210 Hz ON 6
218 Hz 218 Hz 218 Hz ON 6
232 Hz 232 Hz 232 Hz ON 6
248 Hz 248 Hz 248 Hz ON 6
266 Hz 266 Hz 266 Hz ON 6

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

50Hz High COP type

Note:

Function

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

95

Basic Control

Si34-804_C

Note:

96

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

Note:

Function

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

97

Basic Control

Si34-804_C

Note:

98

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

Note:

Function

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

99

Basic Control

Si34-804_C

Note:

100

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

Function

Si34-804_C

Basic Control

Note:

Function

1. INV. : Inverter compressor


STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be
transferred according to the priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in
patterns other than those aforementioned.

101

Basic Control

2.3

Si34-804_C

Electronic Expansion Valve PI Control

Main Electronic Expansion Valve EV1 Control


Fixed to open fully.

Subcooling Electronic Expansion Valve EV2 Control


Makes PI control of the electronic expansion valve (Y2E) to keep the superheated degree of the
outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger.
SH = Tsh -Te

SH : Outlet superheated degree of evaporator (C)


Tsh : Suction pipe temperature detected with the
thermistor R5T (C)
Te : Low pressure equivalent saturation
temperature (C)

2.4

Step Control of Outdoor Unit Fans

Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
Fan revolutions (rpm)
RXQ12PA
RXQ14PA
FAN1 FAN2

RXQ16PA

RXQ18PA

STEP
No.

RXQ5PA

RXQ8PA

RXQ10PA

FAN1

FAN2

FAN1

FAN2

0
1

0
285

0
350

0
350

0
230

0
0

0
230

0
0

0
395

0
0

2
3

315
360

370
400

370
400

380
290

0
260

380
290

0
260

460
570

0
0

4
5

450
570

450
540

460
560

375
570

345
540

375
570

345
540

385
550

355
520

6
7

710
951

670
760

680
821

720
1091

690
1061

720
1091

690
1061

800
1136

770
1106

951

796

821

1136

1106

1136

1106

1166

1136

* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.

2.5

Outdoor Unit Fan Control in Cooling Operation


While in cooling operation, if the outdoor temperature is low, this mode provides high pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
circulation rate to be supplied to indoor units.
Upper limit of fan
revolutions: Step 8

Pc < 2.75 MPa

Pc > 3.24 MPa

Upper limit of outdoor unit


fan revolutions
Step 7

*For fan revolutions in each step,


refer to 2.4 Step Control of
Outdoor Unit Fans.

PI control
Lapse of 20 seconds
-1 step on
outdoor unit fan

102

PI control
Hold the
+1 step on
current step on
outdoor unit fan
outdoor unit fan
PI control
Lapse of 20 seconds

Function

Si34-804_C

Special Control

3. Special Control
3.1

Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the
startup of the compressor, thus reducing startup loads. Furthermore, the inverter is turned ON
to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the
following control is made and the position of the four way valve is also determined. To position
the four way valve, the master and slave units simultaneously start up.

3.1.1 Startup Control in Cooling Operation


Thermostat ON
Startup control

Pressure equalization
control prior to startup

STEP 1

STEP 2

Compressor

0 Hz

52 Hz
+ OFF + OFF

124 Hz + OFF + OFF


+2 steps/20 seconds
(until Pc - Pe > 0.39 MPa is achieved)

Outdoor unit fan

STEP 4

Ta < 20C: OFF


Ta 20C: STEP 4

+1 step/15 seconds (when Pc > 2.16 MPa)


-1 step/15 seconds (when Pc < 1.77 MPa)

Four way valve (Y3S)

Holds

OFF

OFF

Main electronic expansion


valve (EV1)

0 pls

480 pls

480 pls

Subcooling electronic
expansion valve (EV2)
(RXQ8~)

0 pls

0 pls

0 pls

Hot gas bypass valve


(SVP)

OFF

OFF

OFF

Accumulator oil return valve


(SVO)

OFF

OFF

OFF

Injection (SVT) (RXQ5PA


model)

OFF

OFF

OFF

Ending conditions

A lapse of one minute

A lapse of 10
seconds

OR

Function

A lapse of 130 seconds


Pc - Pe > 0.39 MPa

103

Special Control

3.2

Si34-804_C

Oil Return Operation


In order to prevent the compressor from running out of oil, the oil return operation is conducted
to recover oil flown out from the compressor to the system side.

3.2.1 Oil Return Operation in Cooling


[Start conditions]
Referring to the set conditions for the following items, start the oil return operation in cooling.
Cumulative oil feed rate
Timer setting (Make this setting so as to start the oil return operation when the initial
cumulative operating time reaches two hours after power supply is turned ON and then
every eight hours.)
Furthermore, the cumulative oil feed rate is computed from Tc, Te, and compressor loads.
Outdoor unit actuator

Oil return preparation


operation

Oil return operation

Post-oil-return operation

Compressor

5 HP: 52 Hz
( Low pressure constant
control)
Other model:
52 Hz + ON + ON
Take the current step as the
( Low pressure
upper limit.
constant control)

Maintain number of
compressors in oil
return preparation
operation ON

Outdoor unit fan

Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)

Four way valve (Y3S)

OFF

OFF

OFF

Main electronic expansion valve


(EV1)

480 pls

480 pls

480 pls

Subcooling electronic expansion


valve (EV2)

SH control

0 pls

0 pls

Hot gas bypass valve (SVP)

OFF

OFF

OFF

Accumulator oil return valve (SVO)

ON

ON

ON

Ending conditions

20 seconds

or

3 minutes
Ts - Te < 5C

Same as the oil return


operation mode.

or

3 minutes
Pe < 0.6 MPa
HTdi > 110C

* In the case of multi-outdoor-unit system,


Master unit: Performs the operations listed in the table above.
Slave units: Operating units perform the operations listed in the table above.
Non-operating units perform the operations listed in the table above from the oil return operation.
(Non-operating unit stops during oil return preparation operation.)
* Actuators are based on RXQ14~18PA.
Indoor unit actuator
Thermostat ON unit
Fan

Electronic expansion valve

104

Cooling oil return operation


Remote controller setting

Stopping unit

OFF

Thermostat OFF unit

Remote controller setting

Thermostat ON unit

Normal opening

Stopping unit

224 pls

Thermostat OFF unit

Normal opening with forced thermostat ON

Function

Si34-804_C

3.3

Special Control

Pump down Residual Operation

3.3.1 Pump down Residual Operation in Cooling


If the liquid refrigerant stays in the evaporator at the startup of a compressor, this liquid
refrigerant enters the compressor, thus resulting in diluted oil in the compressor and then
degraded lubrication performance.
Consequently, in order to recover the refrigerant in the evaporator while the compressor stops,
the pump down residual operation is conducted.
Actuator

Master unit operation

Slave unit operation

Compressor

124 Hz + OFF + OFF

OFF

Outdoor unit fan

Fan control

OFF

Four way valve (Y3S)

OFF

OFF

Main electronic expansion valve (EV1)

480 pls

0 pls

Subcooling electronic expansion valve


(EV2)

0 pls

0 pls

Hot gas bypass valve (SVP)

OFF

OFF

Accumulator oil return valve (SVO)

ON

ON

Ending conditions

or

5 minutes
Master Unit Pe < 0.49 MPa
Master Unit Td > 110C
Master Unit Pc > 2.94 MPa

* Actuators are based on RXQ14~18PA.

3.4

Standby

3.4.1 Restart Standby


Used to forcedly stop the compressor for a period of 3 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
Actuator

Operation

Compressor

OFF

Outdoor unit fan

Ta > 30C: STEP 4


Ta 30C: OFF

Four way valve (Y3S)

Holds

Main electronic expansion valve (EV1)

0 pls

Subcooling electronic expansion valve (EV2)

0 pls

Hot gas bypass valve (SVP)

OFF

Accumulator oil return valve (SVO)

OFF

Injection (SVT) (RXQ5PA model)

OFF

Ending conditions

3 minutes

* Actuators are based on RXQ14~18PA.

3.4.2 Crankcase Heater Control


In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this
mode is used to control the crankcase heater.
Discharge pipe
temperature < 70C
Crankcase heater
OFF

Function

Discharge pipe
temperature > 75C

Crankcase heater
ON

105

Special Control

3.5

Si34-804_C

Stopping Operation

3.5.1 When System is in Stop Mode (Normal operation stop)


This mode is used to define actuator operations when the system stops.
Actuator

Operation

Compressor

OFF

Outdoor unit fan


Four way valve (Y3S)

OFF
Holds

Main electronic expansion valve (EV1)


Subcooling electronic expansion valve (EV2)

0 pls
0 pls

Hot gas bypass valve (SVP)


Accumulator oil return valve (SVO)

OFF
OFF

Injection (SVT) (RXQ5PA model only)


Ending conditions

OFF
Indoor unit thermostat is turned ON.

* Actuators are based on RXQ14~18PA.

3.5.2 Stop due to Error


In order to protect compressors, if any of the following items has an abnormal value, the system
will make "stop with thermostat OFF" and the error will be determined according to the number
of retry times.
Item

Judgement Criteria

Error Code

1. Abnormal low pressure level

0.07 MPa

E4

2. Abnormal high pressure level

4.0 MPa

E3

3. Abnormal discharge pipe temperature level

135C

F3

4. Abnormal power supply voltage

Reverse phase power supply

U1

5. Abnormal inverter current level

16.1 A: 260 seconds

L8

6. Abnormal radiation fin temperature level

93C

L4

3.5.3 Stopping Operation of Slave Units During Master Unit is in Operation


with Multi-Outdoor-Unit System
While the master unit is in operation, this mode is used to set the refrigerant flow rate to a
required level using a slave unit in the stopped mode.
In cooling: The system operates in Mode A or Mode B listed in the table below.
Actuator

Mode-A operation

Mode-B operation

Compressor

OFF

OFF

Outdoor unit fan


Main electronic expansion valve
(EV1)

STEP 4

OFF

150 pls to 300 pls

0 pls

Subcooling electronic expansion


valve (EV2)
Hot gas bypass valve (SVP)

0 pls

0 pls

ON

ON

Receiver gas discharging valve


(SVG)
Non-operating unit liquid pipe stop
valve (SVSL)

OFF

OFF

OFF

ON

Mode transition conditions

To Mode B when Tc-Tl > 0.27 (Tc - Ta) + 6

To Mode A when gas shortage signal


is sent from indoor unit

Ending conditions

Slave units are required to operate.

Mode A or B operation

Operating
unit

Stopping
unit

Mode A : Operating unit collects refrigerant.

Mode B : Stopping unit storage refrigerant.

The changeover operation for mode A and B is performed for the reason that the required refrigerant amount varies
depending on the indoor unit operation capacity.
106

Function

Si34-804_C

Protection Control

4. Protection Control
4.1

High Pressure Protection Control


This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
[In cooling]
In the case of multi-outdoor-unit system, each outdoor unit performs this control

individually in the following sequence.


High pressure not limited
Pc: High pressure sensor detection
value for each outdoor unit
Pc > 3.47 MPa
INV. upper limit frequency:
3-step down from current
compressor rps
(Slave unit: 3-step down as well)

INV. upper limit rps = max

After 10 seconds
Pc > 3.47 MPa
Pc < 3.24 MPa
Current step maintained
Pc > 3.55 MPa
After 15 seconds

INV. upper limit frequency:


1-step up from current
compressor frequency
(Slave unit: Same as above)

After 10 seconds
STD compressor
standby

Pc > 3.64 MPa

High pressure standby

Function

When occurring 3 times within


30 minutes, high pressure
sensor is activated without high
pressure standby, thus
outputting the error code E3.

107

Protection Control

4.2

Si34-804_C

Low Pressure Protection Control


This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling]
In the case of multi-outdoor-unit system, the entire system performs this control in the

following sequence.
Low pressure not limited

Pe < 0.34 MPa

Pe: Low pressure sensor detection


value for master unit

Pe > 0.39 MPa

Low pressure limited


All STD compressors
stop.

Hot gas SVP = OFF

Pe < 0.15 MPa

Pe > 0.30 MPa

Pe < 0.25 MPa


Hot gas SVP = ON
Master unit: 52 Hz + OFF + OFF
Slave unit: Stop

Pe < 0.07 MPa

Low pressure standby

108

When occurring 4 times within 30 minutes,


the error code E4 is output.

Function

Si34-804_C

4.3

Protection Control

Discharge Pipe Protection Control


This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
[INV. compressor]
Normal operation

or

HTdi > 115C


Tp > 135C
&

INV. upper limit frequency:


1-step down from current
compressor rps

HTdi < 100C


Tp < 110C

HTdi : Value of INV. compressor discharge pipe


temperature (Tdi) compensated with
outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.

After 30 seconds
or

HTdi > 115C


Tp > 135C
&

HTdi > 130C


HTdi > 120C
or
for 90 seconds
or more.
Tp > 130C

HTdi < 110C


Tp < 125C

In discharge pipe temp.


protection control
After 20 seconds

RXQ5PAY1: 52 Hz
Other models:
INV. 62 Hz + OFF + OFF

or

INV. upper limit frequency: 1-step up


from current compressor frequency

HTdi > 135C


HTdi > 120C for 10 minutes or more.

Discharge pipe
temperature standby (for
a period of 10 minutes)

When occurring 3 times within 100 minutes,


the error code F3 is output.

[STD compressor]
HTds : Value of STD compressor discharge
pipe temperature ( Tds) compensated
with outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.

or

HTds > 120C continues for 5 minutes or more.


HTds > 135C
Tp > 135C continues for 10 minutes or more.
Tp > 145C

Discharge pipe temp.


protection control not limited

Applicable STD
compressor stops.
After 10 minutes

Function

109

Protection Control

4.4

Si34-804_C

Inverter Protection Control


Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an error, or transient inverter overcurrent, and fin temperature increase.

In the case of multi-outdoor-unit system, each INV. compressor performs these controls in
the following sequence.

[Inverter overcurrent protection control]


Normal operation

Inverter current > 14.7 A

INV. upper limit frequency: 1-step down


from current compressor frequency

&

Inverter current < 14.7 A


INV. upper limit frequency = max

Inverter current > 14.7 A


Inverter current < 14.7 A continues
for 20 seconds or more.
Under inverter current
protection control

INV. upper limit frequency: 1-step up from


current compressor frequency

Inverter current > 16.1 A continues for 260 seconds

When occurring 4 times within 60 minutes,


the error code L8 is output.

Inverter current standby

[Radiation fin temperature control]


Normal operation

Tfin > 84C


INV. upper limit frequency: 1-step /
1 minute down from current
compressor rps

&

Tfin < 81C


INV. upper limit rps = max

Radiation fin temp. < 81C continues


for 3 minutes or more.

Tfin > 84C


Under fin temperature
protection control

INV. upper limit frequency: 1-step / 1 minute


up from current compressor frequency Interval

Tfin > 93C

Fin temp. standby

110

When occurring 4 times within 60 minutes,


the error code L4 is output.

Function

Si34-804_C

4.5

Protection Control

STD Compressor Overload Protection


This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of STD compressor such as locking.
STD compressor ON

Demand to operate.

*If the power supply is reset while in


operation prohibition mode, the prohibition
timer will continue counting when the
power supply is turned ON.

CT detection current value > 15.0 A

STD compressor OFF for 30 minutes.*

When occurring 3 times within 90 minutes,


the error code E6 is output.

4.6

Injection Control (only for RXQ5PA)


For transitional rise in discharge pipe temperature, have the liquid refrigerant flow into the
suction side to reduce the discharge pipe temperature for the compressor protection.

SVT = OFF
HTdi: Correction value of the discharge pipe
HTdi > 112C

HTdi < 107C

temperature on the INV. compressor.


SVT: Solenoid valve for injection

SVT = ON

Function

111

Other Control

Si34-804_C

5. Other Control
5.1

Outdoor Unit Rotation


In the case of multi-outdoor-unit system, this outdoor unit rotation is used to prevent the
compressor from burning out due to unbalanced oil level between outdoor units.
[Details of outdoor unit rotation]
In the case of multi-outdoor-unit system, each outdoor unit is given an operating priority for the
control.
Outdoor unit rotation makes it possible to change the operating priority of outdoor units.
Thus, the system becomes free of compressors that stop over an extended period of time at the
time of partial loading, preventing unbalanced oil level.
[Timing of outdoor unit rotation]

or

After oil return operation


After defrosting operation
At the beginning of the starting control
There are outdoor units that stop operation (in cooling).
Low pressure of all outdoor units in operation is less than 0.25 MPa (in cooling).

Example) The following diagram shows outdoor unit rotation in combination of 3 outdoor units.

Starting
control
Normal operation

Oil return operation


or defrosting
operation

Normal operation

Master Slave 1 Slave 2


Outdoor unit
rotation

112

Priority
1

Priority
2

Priority
3

Master Slave 1 Slave 2


Outdoor unit
rotation

Priority
3

Priority
1

Priority
2

Function

Si34-804_C

Other Control

<In Cooling>

There are outdoor


or

units that stop


operation.

Low pressure of all


outdoor units in
operation < 0.25 MPa.

Normal operation

Normal operation

Master Slave 1 Slave 2


Priority
2

Priority
3

Priority
1

Master Slave 1 Slave 2


Outdoor unit
rotation

Priority
1

Priority
2

Priority
3

* Master unit, slave unit 1 and slave unit 2 in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are
different from master unit and slave unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be
designated as main unit.
Consequently, The LED display on the main PCB for master unit, slave unit 1 and slave
unit 2 do not change.

5.2

Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outdoor unit
from operating to perform emergency operation only with the operative compressor or outdoor
unit.

Caution
In order to disable the compressor operation due to a failure or else, be sure to do so
in emergency operation mode.
NEVER attempt to disconnect power supply wires from magnetic contactors or else.
(Doing so will operate compressors in combination that disables oil equalization
between the compressors, thus resulting in errors of other normal compressors.)

5.2.1 Restrictions for Emergency Operation


In the case of system with 1 outdoor unit installed, only when thermostats of indoor units
having a capacity of 50% or more of the outdoor unit capacity turn ON, the emergency
operation is functional. (If the total capacity of indoor units with thermostat ON is small, the
outdoor unit cannot operate.)
If the emergency operation is set while the outdoor unit is in operation, the outdoor unit stops
once after pump down residual operation (a maximum of 5 minutes elapsed).

Function

113

Other Control

Si34-804_C

5.2.2 In the Case of 1-Outdoor-Unit System (RXQ5PA to 18PA)


[Set the system to operation prohibition mode by compressor]
In order to set an INV. compressor to operation
LED display (k:ON h:OFF l:Blink)
prohibition mode, set No. 42 of Setting mode 2 to
H1P----H7P
"EMERGENCY OPERATION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

In order to set STD1 and STD2 compressors to


operation prohibition mode, set No. 19 of Setting
mode 2 to "STD1, 2 OPERATION PROHIBITION".
(RXQ10PA to 18PA)
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

In order to set the STD 2 compressor to operation


prohibition mode, set No. 19 of Setting mode 2 to "STD2
OPERATION PROHIBITION". (RXQ14PA, 16PA,
18PA)
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

khhhhhh
kkhkhkh
khhhhhl
khhhhlh
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
khkhhkk
khhhhhh
khhhhhl
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
khkhhkk
khhhhhh
khhhhlh
khhhhhh
hhkhhhh

(Factory setting)

For RXQ14PA, 16PA and 18PA, if the INV. compressor is set to operation prohibition mode,
only a single STD compressor will operate for the convenience of oil equalization.
For RXQ14PA, 16PA and 18PA, only the STD1 compressor cannot be put into operation
prohibition mode for the convenience of oil equalization.
For the system with a single outdoor unit (RXQ5PA to 18PA), automatic backup operation is
not functional.

5.2.3 In The Case of Multi-Outdoor-Unit System (RXQ20PA to 54PA)


[Automatic backup operation]
With multi-outdoor-unit system, if a certain outdoor unit system errors (i.e., the system stops
and indoor unit remote controller displays the error), by resetting the system with the indoor
unit remote controller, the applicable outdoor unit is inhibited from operating for 8 hours, thus
making it possible to perform emergency operation automatically.
However, in the event any of the following errors occurs, automatic backup operation can be
performed.
Errors under which automatic backup operation can be performed:
E3, E4, E5, E7
F3
H7, H9
J2, J3, J5, J6, J7, J9, JA, JC
L4, L5, L8, L9, LC
U2, UJ

114

Function

Si34-804_C

Note :

Other Control

In order to forcedly clear the automatic backup operation, reset the power
supply with the outdoor unit in the stopped state.
[Emergency operation with settings in service mode]
Inhibition of operation is set with each outdoor unit.

Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
Discriminate the operating status of the master unit / slave units through the following LED

display.
LED display (k:ON h:OFF l:Blink)
H1P----H7P H8P
Master: h h k h h h h k
Slave 1: h h h h h h h l
Slave 2: h h h h h h h h
(Factory setting)

In order to set the master unit to operation


prohibition mode, set No. 38 of Setting mode 2 to
"MASTER OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

In order to set the slave unit 1 to operation


prohibition mode, set No. 39 of Setting mode 2 to
"SLAVE 1 OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

In order to set the slave unit 2 to operation


prohibition mode, set No. 40 of Setting mode 2 to
"SLAVE 2 OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhhkkh
khhhhhl
khhhhlh
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhhkkk
khhhhhl
khhhhlh
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhkhhh
khhhhhl
khhhhlh
khhhhhh
hhkhhhh

(Factory setting)

In the case of multi-outdoor-unit system, Inhibition of operation is not set with each
compressor individually.
In the case of multi-outdoor-unit system, when the above Inhibition of operation is set,
outdoor unit rotation is not functional.
Function

115

Other Control

Si34-804_C

[Cancel of Emergency Operation]


To cancel the emergency operation, conduct the following setting. (Return to Factory setting.)
<RXQ8PA to 18PA>
Cancel to set an INV. compressor from operation
LED display (k:ON h:OFF l:Blink)
prohibition mode, set No. 42 of Setting mode 2 to
H1P----H7P
"Normal operation".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 42 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

Cancel to set STD1 and STD2 compressors from


operation prohibition mode, set No. 19 of Setting
mode 2 to "OFF". (RXQ10PA to 18PA)
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

Cancel to set the STD 2 compressor from operation


prohibition mode, set No. 19 of Setting mode 2 to "STD2
OPERATION PROHIBITION". (RXQ14PA, 16PA,
18PA)
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

116

khhhhhh
kkhkhkh
khhhhlh
khhhhhl
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
khkhhkk
khhhhhl
khhhhhh
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
khkhhkk
khhhhlh
khhhhhh
khhhhhh
hhkhhhh

(Factory setting)

Function

Si34-804_C

Other Control

<RXQ20PA to 54PA>
Cancel to set the master unit from operation
prohibition mode, set No. 38 of Setting mode 2 to
"OFF".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

Cancel to set the slave unit 1 from operation


prohibition mode, set No. 39 of Setting mode 2 to
"OFF".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

Cancel to set the slave unit 2 from operation


prohibition mode, set No. 40 of Setting mode 2 to
"OFF".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.

Function

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhhkkh
khhhhlh
khhhhhl
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhhkkk
khhhhlh
khhhhhl
khhhhhh
hhkhhhh

(Factory setting)

LED display (k:ON h:OFF l:Blink)


H1P----H7P

khhhhhh
kkhkhhh
khhhhlh
khhhhhl
khhhhhh
hhkhhhh

(Factory setting)

117

Other Control

5.3

Si34-804_C

Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using Demand 1 Setting or Demand 2 Setting.
To operate the unit with this mode, additional setting of Continuous Demand Setting or
external input by external control adaptor for outdoor unit is required.
Setting content

Set item

Condition
Mode 1

Demand 1 Mode 2
Mode 3
Demand 2
Demand 3

Setting method
Content

External control
adaptor

The compressor operates at


approx. 60% or less of rating.
The compressor operates at
approx. 70% or less of rating.
The compressor operates at
approx. 80% or less of rating.

Outdoor unit PCB


Set item No. 32 to "Demand 1", and item No.
30 to "Level 1".

Short circuit "1" and


"C" on the terminal
strip (TeS1).

The compressor operates at Short circuit "2" and "C".


approx. 40% or less of rating.
Forced thermostat OFF.
Short circuit "3" and "C".

Set item No. 32 to "Demand 1", and item No.


30 to "Level 2".
Set item No. 32 to "Demand 1", and item No.
30 to "Level 3".
Set item No. 32 to "Demand 2".

*: However the demand operation does not occur in the following operation modes.
 Startup control
 Oil return operation
 Defrosting operation
 Pump down residual operation

118

Function

Si34-804_C

Outline of Control (Indoor Unit)

6. Outline of Control (Indoor Unit)


6.1

Drain Pump Control


1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).

6.1.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
Remote controller "A3" flashing
abnormal stop

ON
Thermostat
(running) OFF
OFF
Float switch
ON

ON
Drain pump

OFF
5 minutes

5 minutes 5 seconds

*1) Normal operation

*2) Error residual

1. (Error operation):

The objective of residual operation is to completely drain any moisture adhering to the fin of the
indoor unit heat exchanger when the thermostat goes off during cooling operation.
2. (Error residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermo. is ON.

6.1.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF:
Enters error treatment if the float switch is not reset within 5 minutes.
Thermostat
(running)

Float switch

ON

Remote controller "A3" flashing abnormal stop

OFF

OFF
ON

Drain pump

ON
OFF
5 minutes 5 seconds 5 minutes 5 seconds
*3

*3. (Error residual):


The remote controller will display "A3" and the air conditioner will come to an abnormal stop if
the float switch is turned OFF and not turned ON again within 5 minutes while the cooling
thermo. is OFF.

Function

119

Outline of Control (Indoor Unit)

Si34-804_C

6.1.3 When the Float Switch is Tripped and AF is Displayed on the


Remote Controller:

Remote
controller
display
Float switch

ON

"AF" display (running)

OFF
OFF
ON

Drain pump

Enters error treatment if


the float switch is not reset
within 5 minutes.
Remote controller "A3" flashing
abnormal stop

1st time 2nd time 3rd time 4th time 5th time

ON
OFF

*1 : 5 minutes

5 seconds
*1

*1

*1

*1
*4

*1

*1

*1
*5

*4. (Error residual):


If the float switch is tripped five times in succession, a drain error is determined to have
occurred. AF is then displayed as operation continues.
*5. (Error residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop if
the float switch is OFF for more than 5 minutes in the case of *4.

120

Function

Si34-804_C

6.2

Outline of Control (Indoor Unit)

Louver Control for Preventing Ceiling Dirt


We have added a control feature that allows you to select the range of in which air direction can
be adjusted in order to prevent the ceiling surrounding the air discharge outlet of ceiling
mounted cassette type units from being soiled. (This feature is available on double flow, multiflow and corner types.)
Existing position

P0
P1
P2
P3
P4

Ceiling soiling prevention


position

Standard Setting
position

Draft prevention position

(Not for Multi flow type)

P0

P0

P1

P1

P3

P4

P4

P4'
P0

P1

P2

P2

P0'
P1'
P2'

P2

Draft
prevention
position

P0

P4

P3'
P3

P4

P0''
P1''
P2''
P4'' P3''

Same as existing position

Range of direction adjustment


Standard
position

Prohibited

P0'

P1'

P2'

P3'

P4'

Separated into 5 positions


(P1 - 4)

Range of direction adjustment


Dirt
prevention
position

Prohibited

P0''

P1''

P2''

P3''

P4''

Separated into 5 positions


(P2 - 4)

The factory setting position is standard position.

Function

121

Outline of Control (Indoor Unit)

6.3

Si34-804_C

Using Conditions for Remote Controller Thermistor


Temperature is controlled by both the room temperature thermistor in remote controller and
suction air thermistor in the indoor unit. (This is however limited to when the field setting for the
room temperature thermistor in remote controller is set to Use.)

Cooling

If there is a significant difference in the set temperature and the suction air temperature, fine
adjustment control is carried out using a suction air thermistor, or using the room temperature
thermistor in the remote controller near the position of the user when the suction air temperature
is near the set temperature.

Set temperature
(Ts)

Suction air temperature (TH1)


Range in which room
temperature thermistor in
remote controller can be used

Range in which
suction air thermistor
can be used

Differential

Ex: When cooling


Assuming the set temperature in the figure is above 24C, and the suction air
temperature has changed from 18C to 30C (A F):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18C to 23C (A C).
Room temperature thermistor in remote controller is used for temperatures from 23C to 27C
(C E).
Suction air thermistor is used for temperatures from 27C to 30C (E F).

And, assuming suction air temperature has changed from 30C to 18C (F A):
Suction air thermistor is used for temperatures from 30C to 25C (F D).
Room temperature thermistor in remote controller is used for temperatures from 25C to 21C
(D B).
Suction air thermistor is used for temperatures from 21C to 18C (B A).

122

Function

Si34-804_C

6.4

Outline of Control (Indoor Unit)

Thermostat Control while in Normal Operation


VRV multi systems are set at factory to thermostat control mode using the remote controller.
While in normal thermostat differential control mode (i.e., factory setting mode), the thermostat
turns OFF when the system reaches a temperature of -1C from the set temperature while in
cooling.

Cooling operation:

Tr < Set temperature -1C


Normal
Thermostat OFF
operation

Tr: Temperature detected with the suction air


thermistor (R1T)

While in a single remote controller group control, the body thermostat is only used for this
control.
(Through field settings, the thermostat differential setting can be changed from 1C to 0.5C.
For details on the changing procedure, refer to information on page onward.)

6.5

Thermostat Control in Dry Operation


While in dry operation, the thermostat control is conducted according to a suction air
temperature at the time of starting the dry operation.
Assuming that the suction air temperature at the time of starting the dry operation is Tro and the
suction air temperature in operation is Tr,
Tr < Tro - 1C
when Tro 24.5C:

In dry operation

when Tro > 24.5C:

In dry operation

Thermostat OFF

Tro: Suction air temperature at the


time of starting the dry operation

Tr < Tro - 1.5C


Thermostat OFF

Tr: Temperature detected with the


suction air thermistor (R1T)

Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of 6
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor humidity while in thermostat OFF mode.)

Function

123

Outline of Control (Indoor Unit)

6.6

Si34-804_C

Electronic Expansion Valve Control


In cooling, to maximize the capacity of indoor unit heat exchanger (evaporator), operate the
electronic expansion valve under PI control so that the evaporator outlet superheated degree
(SH) will become constant.
Cooling SH = TH2 - TH1

SH : Evaporator outlet superheated degree


TH1: Temperature (C) detected with the liquid thermistor
TH2: Temperature (C) detected with the gas thermistor

Furthermore, the default value of the optimal evaporator outlet superheated degree (condenser
outlet subcooled degree) is 5 deg. However, this default value varies with the operating
performance.

6.7

Freeze-up Prevention

Freeze-up
Prevention by Off
Cycle (Indoor
Unit)

When the temperature detected by liquid pipe temperature thermistor (R2T) of the indoor unit
heat exchanger drops too low, the unit enters freeze-up prevention operation in accordance with
the following conditions, and is also set in accordance with the conditions given below.
Conditions for starting freeze-up prevention: Temperature is -1C or less for total of 40 minutes,
or temperature is -5C or less for total of 10 minutes.
Conditions for stopping freeze-up prevention: Temperature is +7C or more for 10 minutes.
continuously
Ex: Case where temperature is -5C or less for total of 10 minutes.

10 minutes

Freeze-up prevention operation


10 minutes

124

Forced OFF by thermostat

Function

Si34-804_C

6.8

Outline of Control (Indoor Unit)

List of Swing Flap Operations


Swing flaps operate as shown in table below.
Flap
Fan

Thermostat ON in dry
operation using microcomputer
Thermostat OFF in dry
operation using microcomputer
Thermostat OFF in
Cooling cooling

Swing

L*1

FXCQ
FXHQ
FXKQ

FXFQ
FXZQ

FXAQ

Swing

Swing

Swing

Wind direction set L*1

Set

Set

Set

Swing

Swing

Swing

Swing

OFF or L
Wind direction set

Horizontal or Set Set

Set

Swing

Swing

Swing

Wind direction set Set

Set

Set

Set

Swing

OFF

Horizontal

Horizontal

Totally closed

Wind direction set OFF

Horizontal

Horizontal

Totally closed

Swing

Swing

Swing

Swing

Set

Set

Set

Swing

Set

Stop
Micro-computer control
(including cooling
operation)

Wind direction set L

*1. L or LL only on FXFQ models

Function

125

Outline of Control (Indoor Unit)

6.9

Si34-804_C

Control of Outdoor Air Processing Unit


(Unique Control for Outdoor Air Processing Unit)

6.9.1 Selection of Operation Mode (by suction air thermostat)


Objective

To select cooling or fan operation mode according to the suction air (outdoor air) temperature.

Details

[Outdoor air processing unit]


Suction air temperature (T1) C

5
Cooling mode

19

Fan stop

43
Cooling

Fan operation (with thermostat OFF)

"Low outdoor air protection control"

126

15

Cooling
Fan operation

18

Function

Si34-804_C

Outline of Control (Indoor Unit)

6.9.2 Discharge Air Temperature Control


Used to control the EV (electronic expansion valve) opening and thermostat ON/OFF so as to
keep the discharge air temperature at the set temperature.
(1) Cooling operations

T3

Refrigerant

Discharge
air

CPU

Ts

T1

T4
T2

Temp.
Setting

EV
Refrigerant
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
EV: Electronic expansion valve opening

SH = T3 T2

If the discharge pipe temperature


T4 is lower than the discharge
setting temperature Ts

If the discharge pipe temperature


T4 is higher than the discharge
setting temperature Ts

Yes

No

T4 > Ts?

Is EV possible
to open?

Judge if the superheat degree


is not too small when the EV is
opened.

Yes

No

Is
EV possible to
close?
Yes

If yes,
EV is opened.

EV = EV + EV

Function

Calculate superheat degree.

If yes,
EV is closed.

No

Judge if the superheat degree


is not too large when the EV is
closed.

EV = EV EV

127

Outline of Control (Indoor Unit)

Si34-804_C

(2) Thermostat OFF by discharge air temperature


<Cooling>
Target discharge air temp. Ts Discharge air temp. T4
> 5 degree continue for 5 minutes.
Thermostat stops for 1 minute. Thermostat ON

6.9.3 Low Outdoor Air Temperature Protection Control


Objective

In cooling (or fan operation), if outdoor air temperature is low, stop the fan forcibly.

Details

[Cooling and fan operation]


Turn OFF the fan for a period of 60 minutes at a suction air temperature of 5C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of 5C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.

128

Function

Si34-804_C

Part 5
Test Operation
1. Test Operation ....................................................................................130
1.1 Installation Process ..............................................................................130
1.2 Procedure and Outline .........................................................................131
1.3 Operation when Power is Turned On ...................................................146

2. Outdoor Unit PCB Layout....................................................................147


3. Field Setting ........................................................................................148
3.1 Field Setting from Remote Controller ...................................................148
3.2 Field Setting from Outdoor Unit............................................................165

Test Operation

129

Test Operation

Si34-804_C

1. Test Operation
1.1

Installation Process
Below figure shows the installation process. Install in the order of the steps shown.
Selection of Location

Inspecting and Handling the Unit

Placing the Unit

Field Wiring

Refrigerant Piping

Air Tight Test and Vacuum Drying

Pipe Insulation

Checking of Device and Installation Conditions

Additional Refrigerant Charge and Check Operation


Operations which require the
power to be turned ON.
Test Run

130

Test Operation

Si34-804_C

1.2

Test Operation

Procedure and Outline


Follow the following procedure to conduct the initial test operation after installation.

1.2.1 Check Work Prior to Turn Power Supply ON


Check the below items.
Power wiring
Control transmission wiring
between units
Earth wire
Earth leakage circuit breaker

Check on refrigerant piping /


insulation materials

Check air tight test and vacuum


drying.

Check on amount of refrigerant


charge

Check the stop valves for


conditions.

Test Operation

Is the wiring performed as specified?


Are the wiring of control transmission and earth leakage circuit
breaker correctly connected?
Is the designated wire used?
Is the wiring screw of wiring not loose?
Is the grounding work completed?
Is the insulation of the main power supply circuit deteriorated?
Use a 500 V megger tester to measure the insulation. (*1)
Do not use a megger tester for other circuits than 200 V (or
240 V) circuit.
*1:Measure to be taken against decreased insulation resistance in
the compressor
If the compressor is left to stand for
Terminal
an extended period of time after the
refrigerant charge with the stop valve
open and the power supply OFF, the
Dryer
(1000 W)
refrigerant may be mixed in the
5 cm
compressor, thus decreasing the
insulation resistance.
Heat the compressor as shown on
the right and then recheck the
insulation.
Is the pipe size proper?
Is the pipe insulation material installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes
water leak.)
Have the air tight test and the vacuum drying been conducted
according to the procedure in the Installation Manual?

Is a proper amount of refrigerant recharged?


The following two methods are available for recharge of the
refrigerant.
(1) Use the automatic refrigerant charge function.
(2) Calculate a refrigerant charging amount.

Check to be sure the stop valves are under the following


conditions.
Liquid side stop valve
Open

Gas side stop valve


Open

131

Test Operation

Si34-804_C

1.2.2 Turn Power On


Turn the outdoor unit and indoor
unit power ON.

Be sure to turn the power on 6 hours before starting operation to protect


compressors. (to power ON crankcase heater)

Check the LED display of the


outdoor unit PCB.

Check to be sure the transmission is normal.


The transmission is normal if the LEDs display conditions as shown in
table below.
LED display k: ON h: OFF l: Blinking
COOL/HEAT select
MicroLow
computer
LED display
Demand Multi
MODE
TEST
noise
(Default status before operation
MASTER
SLAVE
IND
monitor
delivery)
HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

One outdoor unit installed

When multiple Master


outdoor unit
Slave 1
installed (*)
Slave 2

(*) The master unit is the outdoor unit to which the transmission wiring for
the indoor units is connected.
The other outdoor units are slave units.
Make field settings with outdoor
unit PCB.

Conduct check operations.

Check for normal operation.

132

Make field settings if needed.


(For the setting procedure, refer to information in "3.2. Field Setting
from Outdoor Unit" on P.165 onward.)
For the outdoor-multi system, make field settings with the master unit.
(Field settings made with the slave unit will be all invalid.)
The check operations shown below will be automatically initiated.
Check for erroneous wirings
Check for failure to open stop valves
Check for excessive refrigerant charging
Automatic judgement of piping length
Before starting the normal operation after the completion of check
operations, make sure indoor and outdoor units normally operate.

Test Operation

Si34-804_C

Test Operation

1.2.3 Air Tight Test and Vacuum Drying


Note:

Always use nitrogen gas for the air tight test.


Absolutely do not open the stop valve until the main power circuit insulation measurement

has been completed. (measuring after the stop valve is opened will cause the insulation
value to drop.)

1.2.3.1

Preparations
<Needed tools>
Gauge manifold
Charge hose valve

To prevent entry of any impurities and insure sufficient


pressure resistance, always use the special tools
dedicated for R-410A.
Use charge hose that have pushing stick for connecting
to service port of stop valves or refrigerant charge port.

Vacuum pump

The vacuum pump for vacuum drying should be able to


lower the pressure to 100.7 kPa
(5 Torr 755 mm Hg).
Take care the pump oil never flow backward into the
refrigerant pipe during the pump stops.

<The system for air tight test and vacuum drying>


Referring to figure 1, connect an nitrogen tank, refrigerant tank, and a vacuum pump to the
outdoor unit.
The refrigerant tank and the charge hose connection to refrigerant charge port or the valve A,
C in figure 1 are needed in 1.2.4 Additional Refrigerant Charge and Check Operation.
The stop valve and valve A~C in figure 1 should be open or closed as shown in the table
below.
Liquid side
stop valve

Refrigerant charge port

Charge
hose

Measuring device

Gouge manifold

Nitrogen

Gas side
stop valve

Outdoor
unit

Stop valve
service port

Outdoor
unit

Valve B
Valve C
R-410A cylinder
(with siphon)

Vacuum pump

To indoor unit

Valve A
Interunit pipings
Gas flow
fig. 1

State of valve A, B and C and stop valves


Air tight test, Vacuum drying
(Close valve A and stop valves certainly. Otherwise the
refrigerant in the unit are released.)

Note:

Valve
A

Stop valve
C

Close Open Open

Liquid side

Gas side

Close

Close

The air tight test and vacuum drying should be done using the liquid side

and gas side stop valve service ports.


See the [R-410A] Label attached to the front plate of the outdoor unit for
details on the location of the service port (see figure at right).
See [Stop valve operation procedure] in 1.2.4.1 Before Working for
details on handling the stop valve. (Refer to P.134)
The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains refrigerant, so use caution when
attaching the charge hose.

Test Operation

[R-410A] Label

133

Test Operation

1.2.3.2

Si34-804_C

Air Tight Test and Vacuum Drying Method


After finished piping work, carry out air tight test and vacuum drying.
<Air tight test>
Pressurize the liquid and gas pipes to 4.0 MPa (do not pressurize more than 4.0 MPa). If the
pressure does not drop within 24 hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs, and perform the air tight test again.
<Vacuum drying>
Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2
hours and bring the system to 100.7 kPa or less. After keeping the system under that condition
for more than 1 hour, check if the vacuum gauge rises or not. If it rises, the system may either
contain moisture inside or have leaks.

Note:

If moisture might enter the piping, follow below.

(I.e., if doing work during the rainy season, if the actual work takes long enough that
condensation may form on the inside of the pipes, if rain might enter the pipes during
work, etc.)
1. After performing the vacuum drying for two hours, pressurize to 0.05 MPa (i.e., vacuum
breakdown) with nitrogen gas, then depressurize down to 100.7 kPa for an hour using the
vacuum pump (vacuum drying).
2. If the pressure does not reach 100.7 kPa even after depressurizing for at least two hours,
repeat the vacuum breakdown - vacuum drying process.
After vacuum drying, maintain the vacuum for an hour and make sure the pressure does not rise
by monitoring with a vacuum gauge.

1.2.4 Additional Refrigerant Charge and Check Operation


The outdoor unit is charged with refrigerant when shipped from the factory, but depending on
the size and length of the piping when installed, it may require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.

Note: Total amount of refrigerant should be 100 kg or less


1.2.4.1

Before Working
[About the refrigerant tank]
Check whether the tank has a siphon pipe before charging and place the tank so that the
refrigerant is charged in liquid form. (See the figure below.)
With siphon pipe
Stand the tank upright and charge.
(The siphon pipe goes all the way inside,
so the tank does not need be put
upside-down charge in liquid form.)

Other tanks
Stand the tank upside-down and charge.

Caution

Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an

improper material, it may cause an explosion or accident.


R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition

to change, which may prevent normal operation.

134

Test Operation

Si34-804_C

Test Operation

[Stop Valve Operation Procedure]


When operating the stop valve, follow the procedure instructed below.

Note:

Do not open the stop valve until 1.2.1 Check work prior to turn power supply on in P.131

are completed. If the stop valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
Be sure to use the correct tools.
The stop valve is not a back-seat type. If forced it to open, it might break the valve body.
When using a service port, use the charge hose.
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the stop valves on each model and the tightening torque for each size are listed in
the table below.
<Size of Stop Valve>
5HP type

8HP type

10HP type 12HP type 14HP type 16HP type 18HP type

Liquid side
stop valve

12.7
9.5
The 18HP type corresponds to the
The 12HP type corresponds to the 12.7-diameter 15.9-diameter onsite piping using the
onsite piping using the included piping.
accessory pipe.

Gas side
stop valve

25.4
The 10HP type corresponds to the 22.2-diameter onsite
piping using the accessory pipe.
The 12 ~ 18HP type corresponds to the 28.6-diameter onsite
piping using the accessory pipe.

15.9

19.1

<Tightening torque>
Tightening torque Nm (Turn clockwise to close)
Stop valve size

Cap
(valve lid)

Shaft (valve body)

9.5

5.4 - 6.6

12.7

8.1 - 9.9

15.9

13.5 - 16.5

Hexagonal wrench
6 mm

27.0 - 33.0

Hexagonal wrench
8 mm

19.1
25.4

Hexagonal wrench
4 mm

Service port

13.5 - 16.5
18.0 - 22.0
11.5 - 13.9
22.5 - 27.5

Service port
Cap

Seal section

Hex holes
Shaft (valve body)
fig 2

[To open]
1. Remove the cap and turn the shaft counter clockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
[To close]
1. Remove the cap and turn the shaft clockwise with the hexagon wrench (JISB4648).
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
Test Operation

135

Test Operation

Si34-804_C

[How to Check How Many Units are Connected]


It is possible to find out how many indoor or outdoor unit in the system are turned on by
operating the press button on the PCB (A1P) of outdoor unit (In case of multi system master
unit).
Follow the procedure below to check how many indoor or outdoor units are turned on.
LED display
(LED display: h ...OFF

k ...ON l ...Blinking ...Uncertain)

1. Press the MODE button (BS1) once, and set the MONITOR MODE

(H1P: Blinking).
2. Press the SET button (BS2) the number of

times until the LED display matches that at


right.

H H H H H H H
1 2 3 4 5 6 7
P P P P P P P

l hhhhhh

For checking the


number of outdoor units:
eight times

l hhkhhh

For checking the


number of indoor units:
five times

l hhhkhk

3. Press the RETURN button (BS3) and read the number of units from the

display of H2P through H7P.


[Reading Method]
The display of H2P through H7P should be read as a binary number,
with l standing for 1 and h standing for 0.

Ex: For the LED display at right, this would be 0 1 0 1 1 0 ,


which would mean 22 units are connected.

l h l h l l h
32 0 + 16 1 + 8 0 + 4 1 + 2 1 + 1 0 = 22 units
Note: 000000 indicates 64 units.

4. Press the MODE button (BS1) once. This returns to Setting Mode 1

(default).

Note:

136

hhkhhhh

Press the MODE button (BS1) if you get confused while operating.
This returns to Setting Mode 1 (default).

Test Operation

Si34-804_C

1.2.4.2

Test Operation

Procedure of Additional Refrigerant Charging and Check Operation


Warning

Electric Shock Warning


Make sure to close the EL. COMPO. BOX lid before turning on the power when performing

the refrigerant charging operation.


Perform the setting on the PCB (A1P) of the outdoor unit and check the LED display after the

power is on via the inspection door which is in the EL. COMPO. BOX lid.
Use an insulated rod to operate the push buttons via the EL. COMPO. BOXs inspection
door.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
Caution

Make sure to use the protect tool (protective groves and goggles) when charging the

refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable

maximum amount when charging the refrigerant.


Do not perform the refrigerant charging operation under working for the indoor unit.
When opening the front panel, make sure to take caution to the fan rotation during the
working.
After the outdoor unit stops operating, the fan may keep rotation for a while.
Note:

If operation is performed within 12 minutes after the indoor and outdoor units are turned on,

H2P will be lit on and the compressor will not operate.


In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the

compressor to start up after the unit starting operating. This is not an error.
<About refrigerant charging>
The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the units internal piping is already charged with
refrigerant, so be careful when connecting the charge hose.
After adding the refrigerant, make sure to close the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.
See [Stop valve operation procedure] in 1.2.4.1 for details on how to handle stop valves.
When done or when pausing the refrigerant charging operation, close the valve of the
refrigerant tank immediately. If the tank is left with the valve open, the amount of refrigerant
which is properly charged may be off the point. More refrigerant may be charged by any
remaining pressure after the machine is stopped.
<About check operation>
Make sure to perform the check operation after installation. Otherwise, the error code U3
will be displayed and normal operation cannot be performed.
And the failure of Check of wrong-wiring may also cause abnormal operation. Performance
may drop due to the failure of Judgement of piping length.
Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.
The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is completed. (Refer to
P.145)
The check operation cannot be performed in recovery or other service modes.
1. Make sure the following works are complete in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Installation work for indoor unit
2. Calculate the additional charging amount using How to calculate the additional refrigerant
to be charged in 6 Example of connection on P.345.

Test Operation

137

Test Operation

Si34-804_C

3. Open the valve C (See the figure 3. The valve A, B and the liquid pipe, suction gas pipe stop
valves must be left closed), and charge the refrigerant of the additional charging amount
from the liquid side shutout valve service port.
Charge hose

Liquid side
stop valve
Gas side
stop valve
Stop valve
service port

Outdoor unit Outdoor unit


Refrigerant
charge port

Valve B
Measuring device

Valve C
Valve A

R-410A tank
(with siphon)

To indoor unit
Field pipings
Refrigerant flow

fig 3

4. If the additional charging amount was charged fully, close the valve C and go to step 6.
If the additional charging amount was not charged fully, close the valve C and go to step 5.
5. Perform the refrigerant charging following [Automatic refrigerant charging operation
procedure] as shown next page. And charge the remaining refrigerant of the additional
charging amount.

Note:

For performing the automatic refrigerant charging operation, the push button on the PCB (A1)
of outdoor unit are used. (See figure 6.)
And the refrigerant are charged from the refrigerant charge port via the valve A. (See figure
4.) For operating the push button and opening or closing the valves, follow the procedure.
During Automatic refrigerant charging operation, the system will select charging mode by the
temperature condition as follows.
Outdoor temp. : 0C DB ~ 43C DB
Indoor temp. : 10C DB ~ 32C DB

Cooling mode

When charging in cooling mode, the system will stop operation when the required amount of
refrigerant is charged.
The refrigerant will be charged about 22kg in one hour at outdoor temp. 30C DB (about 6kg
at outdoor temp. 0C DB).
If you need to speed-up in case of multi system, connect the refrigerant tanks to each outdoor
unit as shown in the figure 5.
During Automatic refrigerant charging operation, you can stop the operation forcedly by
pressing MODE button (BS1).
Liquid side
stop valve
Gas side
stop valve
Stop valve
service port

Charge hose

Valve B
Valve C
Valve A

Measuring device
R-410A tank
(with siphon)

Measuring
device

Liquid side
stop valve
Gas side
stop valve
Stop valve
service port

To indoor unit
Field pipings
Refrigerant flow

fig 4

Refrigerant
charge port

Charge hose

Outdoor unit Outdoor unit


Refrigerant
charge port

In case of multi system if you need to speedup.


Outdoor
unit

Outdoor
unit

Outdoor
unit

valve B
valve C
valve A

valve A

Refrigerant flow

R-410A tank
(with siphon)

: Field pipings
: Refrigerant flow

fig 5

EL.COMPO.BOX lid

EL.COMPO.BOX lid
LED (H1~8P)
Inspection door
Push button
Label
(BS1-5)
Service Precaution

Lift the protruding


part to open the cover

Inspection door

Pipe intake
fig 6

138

Test Operation

Si34-804_C

Test Operation

[Automatic Refrigerant Charging Operation Procedure]


Note:

The marks of LED mean as follows.


h : OFF k : ON l : Blinking : OFF, ON or Blinking
(1) Open the liquid pipe, suction gas pipe stop valves. (The valve A~C must be closed. See
figure 4.)
(2) Close the EL. COMPO. BOX (1) lid and all front panel except on the EL. COMPO. BOX
(1) side. (*1) And turn the power to the outdoor unit and all connected indoor units. (*2)
After H2P stop blinking (about 12 minutes after turning on the power), check H2P is OFF.
If H2P is ON, check the error code in the remote controller of indoor unit and correct the
error in accordance with [Remote controller display error code] on P.143.
(3) Check the LED. And press the MODE button (BS1) once if the LED displays is not as
below.
H1P H2P H3P H4P H5P H6P H7P
h h k h h h h

(4) Press the TEST button (BS4) once. (The LED displays will change as below.)
H1P H2P H3P H4P H5P H6P H7P
k k k k k k k

(5) Hold the TEST button (BS4) down for 5 seconds or more.
(The LED displays will change as below and fan of outdoor unit will start rotation.)
H1P H2P H3P H4P H5P H6P H7P
h l h h h

(6) When the compressor start working and the LED displays change any state in below (*3),
go to In case of cooling mode in accordance with the LED displays.
H1P H2P H3P H4P H5P H6P H7P
l

Go to In case of cooling mode

In case of cooling mode


(7) Press the TEST button (BS4) once within 5 minutes after procedure (5) (*4) and close the
all front panels (*5).
After that, open the valve A immediately (See figure 4) (*6) and watch the remote controller
display of indoor unit.
(8) If the remote controller display shows PE code (*7), ready to close the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve A immediately and refer to
[Remote controller cooling mode error code]
Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.
(9) When the compressor stop working (the fan may continue rotation.), close the valve A
immediately (*8).
And check the LED displays are as below and the remote controller display shows P9
code.
H1P H2P H3P H4P H5P H6P H7P
k l l k k k k

After checking, press the MODE button (BS1) once and the charging is complete.

Test Operation

139

Test Operation

Note:

Si34-804_C

(*1)~(*8)
(*1) Lead the refrigerant charge hose etc. from the pipe intake.
All front panels must be closed at the procedure (7).
(*2) If you perform the refrigerant charging operation within the refrigerant system that have
the power off unit, the operation cannot finish properly.
Check the number of outdoor and indoor units that is powered.
For checking, see [How to check how many units are connected] in P.136.
To energize the crankcase heater, make sure to turn on for 6 hours before starting
operation.
(*3) It takes about 2~10 minutes for getting stability of refrigerant state.
If the additional refrigerant is little and operation is started before getting stability, the
system can not judge the charging amount precisely and it cause overcharge.
(*4) If the TEST button (BS4) is not pressed within 5 minutes, P2 code will displayed in the
remote controller. In this case, refer to [Remote controller cooling mode error code].
(*5) If the front panel is opened during the operation, the system cannot operate properly.
(*6) If you leave the system without connecting the refrigerant tank or opening the valve A for
30 minutes or more, the system stop operation and P2 code are displayed in remote
controller.
In this case, refer to [Remote controller cooling mode error code].
(*7) Depending on the situation of operation such as the charging amount is little, the PE code
may not be displayed and the P9 code may be displayed.
(*8) Always close the valve A and take the tank off.
The refrigerant charge port of this unit have electronic expansion valve coil and the valve
are closed when charging is finished. However, the valve will opened when after operation
(Check operation, normal operation, etc.). If you leave the tank connected, the refrigerant
will charged and it cause overcharge.
[Remote controller cooling mode error code]
Code
PE

The work contents


Charging is almost finished. Ready to close the valve A.
The refrigerant tank is empty. Close the valve A and replace the empty tank to the new
PA
tank. After changing the tank, open the valve A again.
PH
Beware the fan running. The outdoor unit does not stop operation.
P8
Close the valve A immediately, and restart the operation from procedure (3).
Operation is interrupted. Close the valve A immediately
and check the below items.
Check if suction gas pipe or liquid pipe stop valve
is opened.
P2
Check the refrigerant tank is connected and the
After correcting the abnormality,
valve A was opened.
Check if the air inlet and outlet of the indoor unit restart the operation from
procedure (3).
are not closed by an obstruction.
Operation is stopped abnormally. Close the valve A
immediately. Confirm the error code and correct the

abnormality following the [Remote controller displays


error code] in P.143.
P9
Charging is finished. Close the valve A and take the refrigerant tank off.
If the additional charging amount was not charged fully, follow the directions below to charge
additional refrigerant.

140

Test Operation

Si34-804_C

Test Operation

[Refrigerant Charging Operation Procedure]


(1) Open the liquid and gas side stop valves (The valve A~C must be closed. The valve A~C
means the valves in the figure 5.)
[Display of normal system]
SERV.
MONI- MODE TEST/
LED display
HWL
(Default status of shipped) TOR
HAP
H1P
H2P

IND MASTER SLAVE

L.N.O.P DEMA- MULTI


ND

H3P

H4P

H5P

H6P

H7P

H8P

Master unit

Sub unit 1

Sub unit 2

Single system
Multi
system
(*)

C/H SELECTOR

LED display: h...OFF, k...ON, l...Blinking


(*)How to distinguish the master unit, sub unit 1, and sub unit 2 in the multi system.
Method 1: By the H8P (MULTI) LED display

k (ON): Master unit

l (Blinking): Sub unit 1

h (OFF): Sub unit 2

Method 2: By the transmission wiring to indoor unit

Transmission wiring is connected: Master unit


Transmission wiring is not connected : Sub unit 1 or Sub unit 2

(2) If necessary, set the field setting by using the dip switch on the outdoor unit PCB (A1P).
(For how to set, refer to 1.2.5.1 Onsite Settings with the Power Off)
(3) Close the EL. COMPO. BOX lid and all front panel except on the side of the EL. COMPO.
BOX (*1) and turn the power to the outdoor unit and all connected indoor units. (*2)
After H2P stop blinking (about 12 minutes after turning on the power), check LED displays
as shown in the table [Display of normal system] and the system is normal state.
If H2P is blinking, check the error code in the remote controller, and correct the error in
accordance with [Remote controller display error code] in P.143.
(*1) Lead the refrigerant charge hose etc. from the pipe intake. All front panels must be closed at
the procedure (9).
(*2) If you perform the refrigerant charging operation within the refrigerant system that have the
power off unit, the operation cannot finish properly.
For confirming the number of the outdoor and indoor units with the power on, see [How to
check how many units are connected] in chapter 1.2.4.1. In case of a multi system, turn on
the power to all outdoor units in the refrigerant system.
To energize the crankcase heater, make sure to turn on for 6 hours before starting
operation.
(4) Start the additional refrigerant charge operation.
(About the system settings for additional refrigerant charge operation, refer to the [Service
Precaution] label attached on the EL. COMPO. BOX lid in the outdoor unit.)
Open valve A immediately after starting the compressor.
(5) Close the valve A if the additional charging amount of refrigerant was charged, and press
the RETURN button (BS3) once.
(6) Record the charging amount on the accessory REQUEST FOR THE INDICATION label
and attach it to the back side of the front panel.

Test Operation

141

Test Operation

Si34-804_C

6. After completing the additional refrigerant charging perform the check operation following
below
Note:

For check operation, the following work will be performed.


Check of stop valve opening
Check of wrong-wiring
Judgement of piping length
Check of refrigerant overcharge
It takes about 40 minutes to complete the check operation.

[Check Operation Procedure]


(1) Make the onsite setting as needed using the dip switches on the outdoor unit PCB (A1P)
with the power off (Refer to 1.2.5.1 Onsite Settings with the Power Off)
(2) Close the EL. COMPO. BOX lid and all front panels except as the side of the EL. COMPO.
BOX and turn on the power to the outdoor unit and all connected indoor units.
(Be sure to turn the power on at least 6 hours before operation in order to have power
running to the crankcase heater.)
(3) Check the LED display on the outdoor unit PCB (A1P) is as shown in the table below and
transmission is normal.
SERV.
MONI- MODE TEST/
LED display
HWL
(Default status of shipped) TOR
HAP
H1P
H2P

IND MASTER SLAVE

L.N.O.P DEMA- MULTI


ND

H3P

H4P

H5P

H6P

H7P

H8P

Master unit

Sub unit 1

Sub unit 2

Single system
Multi
system
(*)

C/H SELECTOR

LED display: h...OFF, k...ON, l...Blinking

(*)How to distinguish the master unit, sub unit 1, and sub unit 2 in the multi system.
Method 1: By the H8P (MULTI) LED display

k (ON): Master unit

l (Blinking): Sub unit 1

h (OFF): Sub unit 2

Method 2: By the transmission wiring to indoor unit

Transmission wiring is connected: Master unit


Transmission wiring is not connected : Sub unit 1 or Sub unit 2

(4) Make the onsite settings as needed using the push button (BS1-BS5) on the outdoor unit
PCB (A1P) with the power on. (Refer to 1.2.5.2 Onsite Settings with the Power On)
(5) Perform the check operation following the Check Operation Method of the [Service
Precautions] label on the EL. COMPO. BOX lid. The system operation for about 40 minutes
and automatically stops the check operation.
If the error code is not displayed in the remote controller after the system stop, check
operation is completed. Normal operation will be possible after 5 minutes. If the error code
is displayed in the remote controller, correct the error following [Remote controller displays
error code] and perform the check operation again.

142

Test Operation

Si34-804_C

Test Operation

[Remote controller displays error code]


Error code
E3, E4
F3, F6
UF
U1
U1
U4
LC
UF

Installation error

The stop valve of the outdoor unit


Open the stop valve.
is left closed.
The phases of the power to the
outdoor unit is reversed.
No power is supplied to an outdoor
or indoor unit (including phase
interruption).
There is conflict on the connection
of transmission wiring in the
system.

E3
F6
UF

Refrigerant overcharge.

E4
F3

Insufficient refrigerant.

U7, U4
UF, UH

Remedial action

If the outdoor unit terminal is


connected when there is one
outdoor unit installed.

Exchange two of the three phases (L1, L2, L3) to


make a proper connection.
Make sure the power supply wire is properly
connected to the outdoor unit and revise if
necessary.
Check if the refrigerant piping line and the
transmission wiring are consistent with each other.
Recalculate the additional amount refrigerant from
the piping length and correct the refrigerant charge
level by recovering any excessive refrigerant with
a refrigerant recovery machine.
Check if the additional refrigerant charge has
been finished correctly.
Recalculate the additional amount refrigerant
from the piping length and add the adequate
amount.
Remove the line from the outdoor multi terminals
(Q1 and Q2).

If any error codes other than the above are displayed, check the service manual for how to
respond.

Test Operation

143

Test Operation

Si34-804_C

1.2.5 Onsite Settings


Note:

1.2.5.1

In the case of a multi system, all onsite settings should be made on the master unit. Settings
made on sub units are invalid.
The outdoor unit to which the indoor unit transmission wire are connected is the master unit,
and all other units are sub units.

Onsite Settings with the Power Off


If the COOL/HEAT selector was connected to the outdoor
unit, set the dip switch (DS1) on the outdoor unit PCB (A1P)
to ON (it is set to OFF when shipped from the factory).
For the position of the dip switch (DS1), refer to the Service
Precautions label (refer to right) which is attached to the
EL. COMPO. BOX lid.

Warning

Inspection
door
EL.COMPO.
BOX lid

[Service Precautions]
label

Electric Shock Warning


Never perform with the power on.
There is a serious risk of electric shock if any live part is touched.

1.2.5.2

Onsite Settings with the Power On


Use the push button switches (BS1 through BS5) on the outdoor unit PCB (A1P) to make the
necessary onsite settings.
See the Service Precautions label on the EL. COMPO. BOX lid for details on the positions and
operating method of the push button switches and on the onsite setting.
Make sure to record the setting on the accessory REQUEST FOR THE INDICATION label.

Warning

Electric Shock Warning


Use an insulated rod to operate the push buttons via the inspection door of EL. COMPO. BOX
lid.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.

144

Test Operation

Si34-804_C

Test Operation

1.2.6 Test Run


1.2.6.1

Before Test Run


Make sure the following works are completed in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Additional refrigerant charge
Check that all work for the indoor unit are finished and there are no danger to operate.

1.2.6.2

Test Run
After check operation is completed, operate the unit normally and check the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corresponding outdoor unit is also
operating.
(3) Check to see if cold air is coming out from the indoor unit.
(4) Press the fan direction and strength buttons on the remote controller to see if they operate
properly.

Note:

1.2.6.3

Heating is not possible if the outdoor temperature is 24C or higher. Refer to the Operation
manual.
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crankcase heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote controller is pressed.
When the system operation is stopped by the remote controller, the outdoor units may
continue operating for further 5 minutes at maximum.
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not an error.

Checks after Test Run


Perform the following checks after the test run is complete.
Record the contents of field setting.
Record them on the accessory REQUEST FOR THE INDICATION label.
And attach the label on the back side of the front panel.
Record the installation date.
Record the installation date on the accessory REQUEST FOR THE INDICATION label in
accordance with the IEC60335-2-40.
And attach the label on the back side of the front panel.

Note:

Test Operation

After the test run, when handing the unit over to the customer, make sure the EL.COMPO.BOX
lid, the inspection door, and the unit casing are all attached.

145

Test Operation

1.3

Si34-804_C

Operation when Power is Turned On

1.3.1 When Turning On Power First Time


The unit cannot be run for up to 12 minutes to automatically set the master power and address
(indoor-outdoor address, etc.).
Status
Outdoor unit

Test lamp H2P .... Blinks


Can also be set during operation described above.

Indoor unit

If ON button is pressed during operation described above, the "UH" error


indicator blinks.
(Returns to normal when automatic setting is complete.)

1.3.2 When Turning On Power the Second Time and Subsequent


Tap the RESET button on the outdoor unit PCB. Operation becomes possible for about 2
minutes. If you do not press the RESET button, the unit cannot be run for up to 10 minutes to
automatically set master power.
Status
Outdoor unit

Test lamp H2P .... Blinks


Can also be set during operation described above.

Indoor unit

If ON button is pressed during operation described above, the operation lamp


lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)

1.3.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PCB has been Changed
Be sure to press and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit

Test lamp H2P .... ON


Can also be set during operation described above.

Indoor unit

If ON button is pressed during operation described above, the "UH" or "U4"


error indicator blinks. (Returns to normal when automatic setting is complete.)

Service cover
[Service Precautions] label
Switch box cover
Switch box
(the upper right)

Caution When the 400 volt power supply is applied to "N" phase by mistake,
replace the Inverter PCB (A2P) and control transformer (T1R, T2R) in
switch box together.

146

Test Operation

Si34-804_C

Outdoor Unit PCB Layout

2. Outdoor Unit PCB Layout


Outdoor unit PCB

(2) Set mode display (LED)

HAP
(3) BS button

H1P H2P H3P H4P H5P H6P H7P H8P


BS1

BS2

BS3

BS4

BS5

MODE

SET

RETURN

TEST

RESET

(1) Micro-computer normal monitor

1 2 3 4 1 2 3 4
DS1
DS2

(4) Dip switch

Connection terminal for transmission use

F1 F2 F1 F2 Q1 Q2
Indoor
Outdoor

Outdoor
Outdoor

Multi outdoor

(1) Micro-computer normal monitor


This monitor blinks while in normal operation, and turns on or off when an error occurs.
(2) Set mode display (LED)
LEDs display mode according to the setting.
(3) BS button
Used to change mode.
(4) Dip switch
Used to make field settings.

Test Operation

147

Field Setting

Si34-804_C

3. Field Setting
3.1

Field Setting from Remote Controller


Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)

3.1.1 Wired Remote Controller <BRC1E61>


<Basic screen>

1 Press and hold Cancel button for


4 seconds or more .
Field setting menu is displayed.

2 Select

Field setting list in the


field setting menu, and press
Menu/Enter button.
Field setting list screen is
displayed.

3 Highlight the mode, and select


desired Mode No. by using
(Up/Down) button.
<Field setting menu screen>

4 In the case of setting per indoor


unit during group control (When
Mode No. such as 20 , 21 ,
22 , 23 , 25 are selected),
highlight the unit No. and select
Indoor unit No. to be set by
using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE No. - means no
function.

Press Menu/Enter button.

<Field setting screen>


In the case of individual
setting per indoor unit





In the case of group total


setting




SECOND CODE No.


FIRST CODE (SW) No.

5 Highlight SECOND CODE No. of


the FIRST CODE No. to be
changed, and select desired
SECOND CODE No. by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In the case of group total
setting, all of SECOND CODE
No. which may be set are
displayed as . is
changed to SECOND CODE
No. to be set. And, SECOND
CODE No. - means no
function.

Press Menu/Enter button.

148

Test Operation

Si34-804_C

Field Setting

<Setting confirmation screen>




6 Press Menu/Enter button. Setting


confirmation screen is displayed.

7 Select

Yes and press Menu/


Enter button. Setting details are
determined and field setting list
screen returns.

8 In the case of multiple setting


changes, repeat  to  .
9 After all setting changes are completed, press Cancel button
twice.
Press Menu/Enter button.

Setting confirmation

10

Backlight goes out, and


Connection under check
Please wait for a moment is
displayed for initialization. After
the initialization, the basic screen
returns.

CAUTION
When an optional accessory is installed on the indoor unit, settings of the indoor unit may be
changed. See the manual of the optional accessory.
For field setting details of the outdoor unit, see installation manual attached to the outdoor unit.

Test Operation

149

Field Setting

Si34-804_C

3.1.2 Wireless Remote Controller - Indoor Unit


BRC7C type
BRC7E type
BRC4C type

MODE No.
FIELD SETTING MODE

SECOND CODE No.


FIRST CODE No.

1. When in the normal mode, press the


button for 4 seconds or more, and operation
then enters the field setting mode.
2. Select the desired mode No. with the
button.
3. Pressing the
button, select the first code No.
4. Pressing the
button, select the second code No.
5. Press the timer
button and check the settings.
6. Press the
button to return to the normal mode.
(Example)
When setting the filter sign time to Filter Dirtiness-High in all group unit setting, set the Mode
No. to 10, Mode setting No. to 0 and second code No. to 02.

150

Test Operation

Si34-804_C

Field Setting

3.1.3 Simplified Remote Controller


BRC2A51
BRC2C51

MODE No.

FIRST
CODE No.

UNIT No.
SECOND
CODE No.

1. Remove the upper part of remote controller.


2. When in the normal mode, press the [BS6] BUTTON () (field setting), and the FIELD
SETTING MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON () (temperature setting ) and the
[BS3] BUTTON () (temperature setting ).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
selected), press the [BS8] () BUTTON (unit No.) and select the INDOOR UNIT No. to be
set. (This operation is unnecessary when setting by group.)
5. Press the [BS9] BUTTON () (set A) and select FIRST CODE No.
6. Press the [BS10] BUTTON () (set B) and select SECOND CODE No.
7. Press the [BS7] BUTTON () (set/cancel) once and the present settings are SET.
8. Press the [BS6] BUTTON () (field setting) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
CONTAMINATION - HEAVY, SET MODE No. to 10, FIRST CODE No. to 0, and
SECOND CODE No. to 02.

Test Operation

151

Field Setting

Si34-804_C

3.1.4 Setting Contents and Code No. VRV Indoor unit


Mode First
Code
No.
Note 2 No.

0
10
(20)
1
2
3
11
(21)

12
(22)

1
3

Room temperature thermistor in


remote controller
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)

03

04

Details
No.

(1)

(2)

Long life filter


Use

No use

(3)

Display

No display

(4)

OFF

Completion of
airflow
adjustment

Start of airflow
adjustment

(5)

Indoor unit turned


ON by thermostat

Error output

(6)

Forced OFF

ON/OFF control

Operation
output
External protection
device input

(7)

1C

0.5C

(8)

LL
01:0
02:1
Not equipped
LL airflow

Set fan speed


03:2
04:3
Equipped
Preset airflow

Light

(9)
(10)
(11)
(12)

(13)

F (4 directions)

T (3 directions)

W (2 directions)

(14)

Equipped

Not equipped

(15)

Standard

Ceiling Soiling
prevention

(16)

05:4

06:5

07:6

08:7

Field setting airflow position setting

Draft prevention

Setting of the Static Pressure


Selection

External Static Pressure Settings

Thermostat OFF excess humidity


Direct duct connection
(when the indoor unit and heat
reclaim ventilation unit are
connected by duct directly.) Note 6
Drain pump humidifier interlock selection
Field setting selection for individual
ventilation setting by remote controller

High static

pressure
01:30
02:50
03:60
04:70 05:80 06:90 07:100 08:110
09:120 10:130 11:140 12:150 13:160 14:180 15:200
*7
Not equipped
Equipped

2
3
5

Note:

152

Long life filter type

02
Approx.
5,000
hrs.
Approx.
Heavy 1,250
hrs.
Approx.
100 hrs.
Ultra long life
filter

Standard
filter

Optional accessories output selection (field


selection of output for adaptor for wiring)
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Thermostat differential changeover
(Set when room temperature thermistor
in remote controller is to be used.)
OFF by thermostat fan speed
Automatic mode differential
Power failure automatic reset
Airflow When Cooling Thermostat is OFF
High air outlet velocity
(Set when installed in place with
ceiling higher than 2.7 m.)
Selection of airflow direction (Set when a
blocking pad kit has been installed.)
Airflow direction adjustment (Set at
installation of decoration panel.)

15
(25)

Long life
filter

Approx.
10,000
hrs.
Approx.
2,500
hrs.
Approx.
200 hrs.

Ultra
long life
filter

Airflow adjustment

3
4
5
6

13
(23)

Filter contamination
heavy/light (Setting for
display time to clean air
filter)
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)

01

1
VRV
system
indoor
unit
settings

Second Code No. (Note 3)


Setting Contents

Standard

(17)
(18)
(19)

Not equipped

Equipped

(20)

Not equipped

Equipped

(21)

Not equipped

Equipped

(22)

1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory setting.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. 88 may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to Equipped, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
7. The FXMQ506380100125140PVE cannot be set to 30 Pa.
The FXMQ20253240PVE cannot be set to 180 or 200 Pa.

Test Operation

Si34-804_C

Field Setting

3.1.5 Applicable Range of Field Setting


Ceiling mounted cassette type

Slim
Ceiling
ceiling
mounted
Round Compact Double Corner mounted duct type
multi flow flow
type
flow
duct type (Middle
and high
static
pressure)

Ceiling Ceiling
Wall
Floor
mounted suspended mounted standing
duct
type
type
type
type

FXMQ- FXHQ
FXDQ FXMQP
MA

FXFQ

FXZQ

FXCQ

FXKQ

Filter sign

Ultra long life


filter sign

Room
temperature
thermistor in
remote
controller

Set fan speed


when
thermostat OFF

Airflow auto
adjustment

Airflow
adjustment
ceiling height

Airflow direction

Airflow direction
adjustment
(Down flow
operation)

Concealed
floor
standing
type

Ceiling
Outdoor air Details
suspended processing No.
cassette unit
type

FXUQ FXMQMF

FXAQ

FXLQ

FXNQ

(1)

(2)

(3)

(9) (12)

(5)

(13)

(14)

(15)

Airflow direction
adjustment
range

(16)

Field setting fan


speed selection

{1

{1

(17)
(18)

Discharge air
temp. (Cooling)

3.1.72

1 Static pressure selection


2 Refer to 3.1.7 Outdoor Air Processing Unit-Field Setting (Remote Controller) on P.160.

Test Operation

153

Field Setting

Si34-804_C

3.1.6 Detailed Explanation of Setting Modes


(1) Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Filter Specs.
Setting

Standard

Long Life

Ultra Long Life Filter

Contamination Light
Contamination Heavy

200 hrs.
100 hrs.

2,500 hrs.
1,250 hrs.

10,000 hrs.
5,000 hrs.

(2) Ultra Long Life Filter Sign Setting


When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Setting Table
Mode No.

First Code No.

10 (20)

Second Code No.


01

Setting
Long Life Filter

02

Ultra Long Life Filter

(3) Selection of Thermistor


Select the thermistor to control room temperature.
Mode No.

First Code No.

Second Code No. Thermistor that controls room temperature


01

10 (20)

02
03

Room temperature thermistor in remote


controller and suction air thermistor for
indoor unit
Suction air thermistor for indoor unit
Room temperature thermistor in remote
controller

The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and room temperature thermistor in remote controller.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by room temperature
thermistor in remote controller.

(4) "Filter Cleaning" Displayed or Not Displayed


Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Mode No.
10 (20)

154

First Code No.

Second Code No.

"Filter Cleaning" display

01
02

Display
No display

Test Operation

Si34-804_C

Field Setting

(5) Airflow Adjustment (AUTO)


External Static Pressure Settings
Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated
quantity.
(b) Select External Static Pressure with Remote Controller Check that 01 (OFF) is set for the
SECOND CODE No. in MODE No. 21 for airflow adjustment on an indoor unit basis in
Table 4. The SECOND CODE No. is set to 01 (OFF) at factory setting. Change the
SECOND CODE No. as shown in Table according to the external static pressure of the
duct to be connected.
Mode No.

First Code No.

Second Code No.

01
02

OFF
Completion of airflow adjustment

03

Start of airflow adjustment

11 (21)

Airflow adjustment

(6) Optional Output Switching


Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals K1 and K2 of "customized wiring adaptor", an optional
accessory.
Mode No.

First Code No.

Second Code No.


01

12 (22)

03
04

Remarks
Indoor unit thermostat ON/OFF signal is
provided.
Output linked with "Start/Stop" of remote
controller is provided.
In case of "Error Display" appears on the
remote controller, output is provided.

(7) External ON/OFF Input


This input is used for "ON/OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block (X1A) in the electric
component box.
F2 T1 T2
Forced stop
Input A

Setting Table
Mode No.

First Code
No.

Second
Code No.
01

12 (22)

02
03

Test Operation

Operation by input of the signal A


ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
OFF ON: Permission of operation
ON OFF: Stop
ON: Operation
OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".

155

Field Setting

Si34-804_C

(8) Thermostat Switching


Differential value during thermostat ON/OFF control can be changed. (For details, refer to "6.4
Thermostat Control while in Normal Operation" on P.123.)
Mode No.

First Code No.

12(22)

Second Code No.


01

Differential value
1C

02

0.5C

(9) Airflow Setting when Heating Thermostat is OFF


This setting is used to set airflow when heating thermostat is OFF.
When thermostat OFF airflow volume up mode is used, careful consideration is required
before deciding installation location.
Mode No.

First Code No.

12 (22)

Second Code No.


01

Contents
LL airflow

02

Preset airflow

(10) Setting of Operation Mode to "AUTO"


This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
Mode No.

First Code No.

12 (22)

01

02

Second Code No.


03
04
05
06

0C

1C

2C

3C

4C

5C

07

08

6C

7C

The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.

(11) Auto Restart after Power Failure Reset


For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned off. However, for the air
conditioners with the setting (same as factory setting), the units may start automatically after
power failure reset or the main power supply turned on again (return to the same operation
condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize Auto restart function after power
failure reset, utmost care should be paid for the occurrence of the following situation.

Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).

(12) Airflow when Cooling Thermostat is OFF


This is used to set airflow to "LL airflow" when cooling thermostat is OFF.

156

Mode No.

First Code No.

12 (22)

Second Code No.


01

Contents
LL airflow

02

Preset airflow

Test Operation

Si34-804_C

Field Setting

(13) Setting of Normal Airflow


Make the following setting according to the ceiling height. The second code No. is set to 01 at
the factory.
In the Case of FXAQ
Mode No.

First Code No.

13(23)

Second Code
No.
01

02
03

Setting
Wall mounted type: Standard
Wall mounted type: Slight increase
Wall mounted type: Normal increase

In the Case of FXHQ


Mode No.

First code No.

Second code
No.

Ceiling height (m)

13(23)

01
02

2.7 or less
2.7-3.5

In the Case of FXFQ25~80 (All round outlet)


Mode
No.

First Second
code
code
No.
No.

Ceiling height (m)

02

Standard All
round outlet
High Ceiling (1)

2.7-3

03

Higher Ceiling (2)

3-3.5

01
13 (23)

Setting

2.7

In the Case of FXFQ100~125 (All round outlet)


Mode
No.

First Second
code
code
No.
No.

Ceiling height (m)

02

Standard All
round outlet
High Ceiling (1)

3.2-3.6

03

Higher Ceiling (2)

3.6-4.2

01
13 (23)

Setting

3.2

In the Case of FXFQ25~80 (*24-Way, 3-Way, 2-Way Outlets)


Mode
No.

13 (23)

First Second
code
code
Setting
No.
No.
01
Standard (N)
0

02
03

Ceiling height
4-way Outlets

3-way Outlets

2-way Outlets

Lower than 3.1 m Lower than 3.0 m Lower than 3.5 m

High Ceiling (H) Lower than 3.4 m Lower than 3.3 m Lower than 3.8 m
Higher Ceiling (S) Lower than 4.0 m Lower than 3.5 m

In the Case of FXFQ100~125 (*24-Way, 3-Way, 2-Way Outlets)


Mode
No.

13 (23)

First Second
code
code
No.
No.
0

Ceiling height
Setting

4-way Outlets

3-way Outlets

01
02

Standard (N)
High Ceiling (H)

03

Higher Ceiling (S) Lower than 4.5 m Lower than 4.2 m

2-way Outlets

Lower than 3.4 m Lower than 3.6 m Lower than 4.2 m


Lower than 3.9 m Lower than 4.0 m Lower than 4.2 m

*1 Mode No. setting is done in a batch for the group. To make or confirm settings for an
individual unit, set the internal mode number in parentheses.
*2 The figure of the ceiling height is for the all round outlet. For the settings for four-direction
(part of corner closed off), three-direction and two-direction outlets, see the installation
manual and technical guide supplied with the separately sold closure material kit.

Test Operation

157

Field Setting

Si34-804_C

In the Case of FXUQ71~125


First Second
code
code
Setting
No.
No.
01
Standard (N)

Mode
No.

13 (23)

02
03

Ceiling height
4-way Outlets

3-way Outlets

2-way Outlets

Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m

High Ceiling (H) Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m

(14) Airflow Direction Setting


Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory setting to 01.
Setting Table
Mode No.

13 (23)

First Code No.

Second Code
No.

01
02

F : 4-direction airflow
T : 3-direction airflow

03

W : 2-direction airflow

Setting

(15) Operation of Downward Flow Flap: Yes/No


Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Mode No.

First Code No.

Second Code No.

Setting

13 (23)

01
02

Down-flow operation: Yes


Down-flow operation: No

(16) Setting of Airflow Direction Adjustment Range


Make the following airflow direction setting according to the respective purpose.

Setting Table
Mode No.

13 (23)

First Code No.

Second Code No.

Setting

01

Upward (Draft
prevention)
Standard

02
03

Downward (Ceiling
soiling prevention)

Some indoor unit models are not equipped with draft prevention (upward) function.

(17) Setting of the Static Pressure Selection


In the Case of FXDQ20~32PB, FXDQ40~63NB
Model No.
13 (23)

158

First Code No.

Second Code No.

External static pressure

01
02

Standard (10Pa)
High static pressure (30Pa)

Test Operation

Si34-804_C

Field Setting

(18) External Static Pressure Settings (for FXMQ-P model)


Mode No.

13 (23)

First Code No.

Second Code No.

External Static Pressure

01
02

30 Pa (*1)
50 Pa

03
04

60 Pa
70 Pa

05
06

80 Pa
90 Pa

07
08

100 Pa
110 Pa

09
10

120 Pa
130 Pa

11
12

140 Pa
150 Pa

13
14

160 Pa
180 Pa (*2)

15

200 Pa (*2)

The SECOND CODE NO. is set to 07 (an external static pressure of 100 Pa) at factory setting.
*1 The FXMQ50 63 80 100 125 140PVE cannot be set to 30 Pa.
*2 The FXMQ20 25 32 40PVE cannot be set to 180 or 200 Pa.

(19) Humidification when Heating Thermostat is OFF


Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20C or
above and turns OFF the humidifier if suction air temperature is 18C or below when the heating
thermostat is OFF.
Mode No.

First Code No.

Second Code No.

Setting

15 (25)

01
02

Setting of humidifier

(20) Setting of Direct Duct Connection


This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries
out residual operation for one minute after the thermostat is stopped. (For the purpose of
preventing dust on the air filter from falling off.)
Mode No.

15 (25)

First Code No.

Second Code No.

Contents

01

Without direct duct


connection
With direct duct
connection equipped
with fan

2
02

(21) Interlocked Operation between Humidifier and Drain Pump


This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
Mode No.

15 (25)

First Code No.

Second Code No.

Contents

01

Individual operation of
humidifier
Interlocked operation
between humidifier and
drain pump

3
02

Test Operation

159

Field Setting

Si34-804_C

(22) Individual Setting of Ventilation


This is set to perform individual operation of heat reclaim ventilation using the remote controller/
central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
Mode No.

First Code No.

15 (25)

Second Code No.


01

Contents

02

Individual operation of
ventilation

3.1.7 Outdoor Air Processing Unit - Field Setting (Remote Controller)


: Factory setting
Mode
No.

First
Code
No.

0
10
(20)

1
12
(22)
5

14
(24)

160

Setting
contents

Second Code No.


01

Stain of filter 2500hr


Filtering
time
Display
cumulation
External
ON/OFF
input
Power
failure
automatic
reset
Discharge
temperature
(cooling)

Forced
stop

02

03

04

05

06

07

08

09

10

11

12

13

14

15

1250hr

No
display

ON-OFF
control

15

16

17

18

19

20

21

22

23

24

25

25

25

Not
equipped Equipped

13C

14

Test Operation

Si34-804_C

Field Setting

3.1.8 Centralized Control Group No. Setting


BRC1E Type

In order to conduct the centralized remote control using the centralized remote controller and
the unified ON/OFF controller, Group No. settings should be made by group using the operating
remote controller.
Make Group No. settings for centralized remote control using the operating remote controller.
(1) <Basic screen>
1. Press and hold Cancel button for 4 seconds or more.
Field setting menu in displayed.

(2) <Field setting menu screen>


2. Select Group No. settingin the field setting menu, and press
Menu/Enter button.
Group No. setting screen is displayed.

(3) <Group No. setting>


3. Select Group No. setting (Group), and press Menu/Enter
button.
Group No. setting (Group) screen is displayed.

(3) <Group No. setting (Group)>


4. Select the group No. by using ST (Up/Down) button.
Press Menu/Enter button.

Note:

For wireless remote controller, see the following.


For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the

instruction manual attached.


NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
Test Operation

161

Field Setting

Si34-804_C

Group No. setting by wireless remote controller for centralized control


1. When in the normal mode, press
button for 4 seconds or more, and operation then
enters the field setting mode.
2. Set mode No. 00 with
button.
3. Set the group No. for each group with

button (advance/backward).
4. Enter the selected group numbers by pressing
button.
5. Press
button and return to the normal mode.

BRC7C Type
BRC7E Type
BRC4C Type

MODE No.
FIELD SETTING MODE

GROUP No.

Group No. Setting


Example

Indoor/Outdoor Outdoor/Outdoor

Centralized Remote
Controller

Indoor/Outdoor Outdoor/Outdoor

F1 F2
F1 F2

F1 F2

F1 F2 P1 P2

RC
1-00

F1 F2 P1 P2
No Remote Controller
1-03

Caution

162

F1 F2

F1 F2 P1 P2

Main RC

RC Sub
1-01

F1 F2 P1 P2

F1 F2

F1 F2 P1 P2

RC
1-02

F1 F2 P1 P2

F1 F2 P1 P2

Group Control by Remote Controller


(automatic unit address)

F1 F2 P1 P2

RC
1-04

When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.

Test Operation

Si34-804_C

Field Setting

3.1.9 Setting of Operation Control Mode from Remote Controller


(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the next page.)
Centralized remote controller is normally available for operations. (Except when centralized
monitor is connected)

3.1.10 Contents of Control Modes


Twenty modes consisting of combinations of the following five operation modes with
temperature and operation mode setting by remote controller can be set and displayed by
operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn on/off by centralized remote controller only.
(Cannot be turned on/off by remote controller.)
OFF control only possible by remote controller
Used when you want to turn on by centralized remote controller only, and off by remote
controller only.
Centralized
Used when you want to turn on by centralized remote controller only, and turn on/off freely
by remote controller during set time.
Individual
Used when you want to turn on/off by both centralized remote controller and remote
controller.
Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want
to start operation by centralized remote controller when time of system start is programmed.

Test Operation

163

Field Setting

Si34-804_C

How to Select
Operation Mode

Whether operation by remote controller will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.

Example
ON by remote
controller
(Unified ON by
centralized remote
controller)

Rejection

OFF by remote
controller
(Unified OFF by
centralized remote
controller)

Rejection

OFF by
remote
controller

Rejection

Temperature
control by
remote controller

Operation mode
setting by
remote controller

Acceptance

Acceptance

Control
mode is "1."

Control by remote controller


Operation
Control mode

Unified operation,
individual operation
by centralized remote
controller, or
operation controlled
by timer

Unified OFF,
individual stop by
centralized remote
controller, or timer
stop

OFF

Temperature
Operation Control mode
control
mode setting

Rejection
ON/OFF control
impossible by
remote controller

Rejection
(Example)

Acceptance
(Example)

Rejection (Example)
Rejection

OFF control only


possible by
remote controller

Rejection (Example)
Acceptance
Rejection

Centralized
Acceptance
Acceptance

Acceptance
Rejection

Individual

Acceptance
Acceptance

Timer operation
possible by
remote controller

Acceptance
(During timer at ON
position only)

Acceptance
(During timer at ON
position only)

Rejection
Acceptance

Acceptance

Rejection

10

Acceptance
(Example)

1 (Example)

Rejection

11

Acceptance

Rejection

12

Acceptance

Rejection

13

Acceptance

Rejection

14

Acceptance

Rejection

15

Acceptance

Rejection

16

Acceptance
Rejection

7 1
17

Acceptance

Rejection

18

Acceptance

Rejection

19

Do not select timer operation possible by remote controller if not using a remote controller.
Operation by timer is impossible in this case.
1. Factory setting

164

Test Operation

Si34-804_C

3.2

Field Setting

Field Setting from Outdoor Unit

3.2.1 Field Setting from Outdoor Unit


List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1, and Setting mode 2, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on P.177 onward.
Setting item

Function setting

Content and objective of setting


Overview of setting procedure
A. Use external input to step down the upper Use the "External control adaptor for
limit of the fan (factory setting to Step 8),
outdoor unit".
providing low noise level.
Set to "External control adaptor for outdoor
(1) Mode 1: Step 6 or lower
unit" with No. 12 of "Setting mode 2" and
(2) Mode 2: Step 5 or lower
select the mode with No. 25.
(3) Mode 3: Step 4 or lower
If necessary, set the "Capacity priority
setting" to ON with No. 29.

Setting of nighttime quiet


operation (*1)

B. The night-time quiet operation


aforementioned is enabled in night-time
Make this setting while in "Setting mode 2".
automatic quiet operation mode.
Select a mode with No. 22 of "Setting mode
Start time: Possible to select in the range of
2".
20:00 to 24:00 hours.
Select the start time with No. 26 and the
End time: Possible to select in the range of
end time with No. 27.
06:00 to 08:00 hours.
If necessary, set the "Capacity priority
(Use the said time as a guide since the
setting" to ON with No. 29.
start time and the end time are estimated
according to outdoor temperatures.)
Used to place limits on the compressor
For setting with the use of "external control
operating frequency to control the upper
adaptor for outdoor unit";
limit of power consumption.
Set the system to "External control adaptor
(1) Mode 1 of Demand 1: 60% or less of
for outdoor unit" with No. 12 of Setting
Setting of demand
rating
mode 2" and select the mode with No. 30.
operation (*1)
(2) Mode 2 of Demand 1: 70% or less of
For setting only in "Setting mode 2":
rating
Set the system to Normal demand mode
(3) Mode 3 of Demand 1: 80% or less of
with No. 32 of "Setting mode 2" and select
rating
the mode with No. 30.
(4) Demand 2: 40% or less of rating
Setting of AIRNET Used to make address setting with
AIRNET connected.
address

Setting of high
static pressure

Test Operation

Set the AIRNET to an intended address


using binary numbers with No. 13 of
"Setting mode 2".

Make this setting to operate a system with


diffuser duct while in high static pressure
mode. (Use this setting mode when shields
are installed on upper floors or balconies.) Set No. 18 of "Setting mode 2" to ON.
* In order to mount the diffuser duct, remove
the cover from the outdoor unit fan.

165

Field Setting

Si34-804_C

Setting item

Overview of setting procedure

1
2

Indoor unit forced


operation

Service setting

Content and objective of setting

Indoor unit fan


Used to operate the indoor unit in the
Set No. 5 of "Setting mode 2" to indoor unit
forced H operation
stopped state in forced H operation mode.
forced fan H.
Used to operate the indoor unit in forced
operation mode.

Change of targeted In cooling operation, used to change the


evaporating
targeted evaporating temperature for
temperature
compressor capacity control.
(in cooling)
Setting of
Used to start units not in sequence but
sequential startup
simultaneously.

Emergency
operation (*1)

Additional
refrigerant
charging (*1)

Refrigerant
recovery mode (*1)

Vacuuming mode
(*1)

ENECUT test
operation
(Domestic model
only)

10

Power transistor
check mode

11

Setting of model
with spare PCB

Set No. 6 of "Setting mode 2" to indoor unit


forced operation mode.
Select high side or low side with No. 8 of
"Setting mode 2".
Set No. 11 of "Setting mode 2" to NONE.

If the compressor has a failure, used to


Make this setting while in "Setting mode 2".
prohibit the operation of compressor(s)
For system with a single outdoor unit: Set
concerned or outdoor unit(s) concerned
with No. 19 or 42.
and to conduct emergency operation of the
For system with multiple outdoor units: Set
system only with operable compressor(s)
with No. 38, 39, or 40.
or outdoor unit(s).
If a necessary amount of refrigerant cannot
be charged due to the stop of outdoor unit, Set No. 20 of "Setting mode 2" to ON and
operate the outdoor unit and then refill
then charge refrigerant.
refrigerant.
Used to recover refrigerant onsite.
With operations of indoor and outdoor units Set No. 21 of "Setting mode 2" to ON.
prohibited, fully open the expansion valve
of the indoor and outdoor units.
Used to conduct vacuuming onsite.
Fully open the expansion valves of the
indoor and outdoor units, and energize part Set No. 21 of "Setting mode 2" to ON.
of solenoid valves. Use a vacuum pump to
conduct vacuuming.
Used to forcedly turn ON the ENECUT.
(Be noted this mode is not functional with Set No. 24 of "Setting mode 2" to ON.
the indoor unit remote controller turned
ON.)
Used for the troubleshooting of DC
compressors.
Inverter waveform output makes it possible Set No. 28 of "Setting mode 2" to ON.
to judge whether a error results from the
compressor or the PCB.
In order to replace the PCB by a spare one, For this setting, set the DS2-2, -3, and-4
switches on the PCB to the model
be sure to make model setting.
concerned.

For setting items of (*1), refer to detailed information provided on P.177 onward.

166

Test Operation

Si34-804_C

Field Setting

Setting by Dip Switches

Using dip switches on the PCB enables field setting shown below. However, make no changes
of factory settings except for DS1-1.
Dip switch
No.
DS1-1

Setting
ON
OFF (Factory setting)

Setting item

Description

Cool/Heat select Used to set cool/heat select by Cool/Heat selector


equipped with outdoor unit.

ON
DS1-2
~DS1-4 OFF (Factory setting)

Not used

Do not change the factory settings.

ON
OFF (Factory setting)

Not used

Do not change the factory settings.

DS2-1
~4

Setting at replacement by spare PCB

Caution

Dip switch setting after changing the main PCB (A1P) to spare PCB
After the replacement by the spare PCB, be sure to make settings shown below.
When you change the main PCB (A1P) to spare PCB, please carry out the following setting.
Initial conditions of dip switches

ON
OFF

ON
OFF
1 2 3 4
DS1

1 2 3 4
DS2

Dip Switch Detail


DS No.

Item

DS1-1 Cool/Heat change


over setting

DS1-2 Power supply


specification

DS1-3 Cooling Only/Heat


Pump setting

DS1-4 Unit allocation


setting

DS2-1

Contents
Do not set.

ON

OFF (Factory Do not set.


setting of spare
PCB)
ON
200 V class (220 V)
OFF (Factory 400 V class (380 V)
setting of spare
PCB)
ON

Cooling Only setting

OFF (Factory Heat Pump setting


setting of spare
PCB)
ON
Make the following settings according to allocation of
unit. (All models are set to OFF at factory.)
OFF (Factory
setting of spare
PCB)

DS2-2 Model setting

Domestic
Japan

Overseas
General

Europe

DS1-4

OFF

OFF

ON

DS2-1

OFF

ON

OFF

Make the following settings according to models of outdoor units.


(All models are set to OFF at factory.)

DS2-3
DS2-4

DS2-2
DS2-3
DS2-4

RXQ5PA RXQ8PA RXQ10PA


OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF

RXQ12PA
OFF
OFF
ON

RXQ14PA
ON
OFF
ON

RXQ16PA
OFF
ON
ON

RXQ18PA
ON
ON
ON

If the DS1-1~1-4, DS2-2~2-4 setting has not been carried out, error code UA are displayed

and unit can not be operated.

Refer to DS1-1~4, DS2-1~4 setting detail on next page.

Test Operation

167

Field Setting

Si34-804_C

Detail of DS1-1~4, DS2-1~4 setting (for Overseas general)


Unit

168

Setting method (

represents the position of switches)

Cooling Only (5HP)


RXQ5PAY1

Set DS2-1 to ON.

Cooling Only (8HP)


RXQ8PAY1

Set DS2-1 and DS2-3 to ON.

Cooling Only (10HP)


RXQ10PAY1

Set DS2-1, DS2-2 and DS2-3


to ON.

Cooling Only (12HP)


RXQ12PAY1

Set DS2-1 and DS2-4 to ON.

Cooling Only (14HP)


RXQ14PAY1

Set DS2-1, DS2-2 and DS2-4


to ON.

Cooling Only (16HP)


RXQ16PAY1

Set DS2-1, DS2-3 and DS2-4


to ON.

Cooling Only (18HP)


RXQ18PAY1

Set DS2-1, DS2-2, DS2-3, and DS2-4


to ON.

Test Operation

Si34-804_C

Field Setting

Setting by push button switches

The following settings are made by push button switches on PCB.


In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED display as shown below.
LED display

Multi;

SLAVE
H5P

Low
noise
H6P

Demand

MASTER
H4P

H7P

H8P

h
h
h

k
h
h

h
h
h

h
h
h

h
h
h

h
h
h

k
l
h

TEST
H2P

Single-outdoor-unit
system

Master

h
h
h

Outdoormulti
system

Slave 1
Slave 2

COOL/HEAT select
IND
H3P

MODE
H1P

(Factory setting)
BS1

BS2

BS3

BS4

BS5

MODE

SET

RETURN

TEST

RESET

There are the following three setting modes.


c Setting mode 1 (H1P off)
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
abnormal, low noise control and demand control.
d Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
e Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing procedure 1
Using the MODE button, the modes can be changed as follows.
Press and hold the BS1
(MODE) for 5 seconds.

(Normal)

Setting mode 2
Press the BS1(MODE) one time.

MODE

Press the BS1(MODE)


one time.
Monitor mode

Setting mode 1
MODE

On

MODE
Blinking

Off

H1P

H1P

H1P

Mode changing procedure 2


(Set): Select mode with BS2 (SET) in each selection step.

Press BS1 (MODE) for more than 5 seconds

Setting mode 1
(Initial condition)

Press BS1(MODE) one time.

Setting mode 2

Monitor mode

Setting item selection


(Set)
Press BS3
(RETURN)
one time.
Setting condition
selection (Set)
Press BS3
(RETURN)
one time.
Setting condition
(Contents) display
Press BS3
(RETURN)
one time.

Check item selection


(Set)
Press BS3
(RETURN)
one time.
Contents display
Press BS3
(RETURN)
one time.

Press BS1
(MODE)
one time.

Press BS1
(MODE)
one time.

Test Operation

169

Field Setting

Si34-804_C

a. Setting mode 1
This mode is used to set and check the following items.
1. Check items The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, press the
MODE (BS1) button to set the
system to "Setting mode 1".

MODE TEST
H1P
H2P

COOL/HEAT select
Low
Demand
IND MASTER SLAVE noise
H7P
H6P
H3P
H4P
H5P

h
Current operating conditions
hNormal kAbnormal
lIn preparation or in check
operation

Check the system for each condition


through LED displays. (Refer to
information in table on the right.)

Pressing the RETURN (BS3) button


will bring the system to the initial
state of "Setting mode 1".

170

Setting of COOL/HEAT selection


khhBy individual outdoor unit
hkhIn a batch of outdoor unit
group with master unit
hhk In a batch of outdoor unit
group with slave unit
Low noise operating conditions
hIn normal operation
kIn low noise operation
Demand operating conditions
hIn normal operation
kIn demand operation

Test Operation

Si34-804_C

b. Setting mode 2
Press and hold the MODE (BS1)
button for 5 seconds and set to
Setting mode 2.

<Selection of setting items>


Press the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.

Press the RETURN (BS3) button


and decide the item. (The present
setting condition is blinked.)

Field Setting

No.

Digital pressure
gauge kit display

Sets address for cool/heat unified operation.

Cool/Heat unified
address
Low noise/demand
address

Test operation
settings

Indoor unit forced


fan H
Indoor unit forced
operation
Te setting
Sequential
operation setting
External low noise
setting / Demand
setting
AIRNET address

Used to conduct test operation without making changes


to the PCB and replacing the refrigerant, after the
completion of maintenance.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)

6
8
11

13
18

<Selection of setting conditions>

19

20
21

22
Press the RETURN (BS3) button
and set to the initial status of
Setting mode 2.

24
25

If you become unsure of how to


proceed, press the MODE (BS1)
button and return to setting mode 1.

26

27

28

29

Test Operation

Description
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)

12

Press the SET (BS2) button and set


to the setting condition you want.

Press the RETURN (BS3) button


and decide the condition.

Setting item

Address for low noise/demand operation

Allows forced operation of indoor unit.


Target evaporation temperature for cooling
Sets sequential operation
(Factory setting to ON)
Reception of external low noise or demand signal

Set address for AIRNET.


Make this setting in the case of operating in high static
High static pressure pressure mode with diffuser duct mounted.
setting
(In order to mount the diffuser duct, remove the cover
from the outdoor unit fan.)
Used to operate system only with inverter compressor
Emergency
when STD compressor error. This is a temporary
operation
operation extremely impairing comfortable environment.
(STD compressor
Therefore, prompt replacement of the compressor is
operation
required.
prohibited)
(This operation, however, is not set with RXQ5, 8PA.)
Additional
refrigerant charge
Carries out additional refrigerant charge operation.
operation setting
Refrigerant recovery/
vacuuming mode
Sets to refrigerant recovery or vacuuming mode.
setting
Sets automatic night-time low noise operation in a simple
Night-time low
way.
noise setting
The operating time is based on Starting set and Ending
set.
ENECUT test
Used to forcedly turn ON the ENECUT. (Be noted that the
operation
ENECUT is only functional with outdoor unit in the
(Domestic model
stopped state - Japanese domestic model only.)
only)
Setting of external Sets low noise level when the low noise signal is input
low noise level
from outside.
Night-time low
Sets starting time of night-time low noise operation.
noise operation
(Night-time low noise setting is also required.)
start setting
Night-time low
ending time of night-time low noise operation.
noise operation end Sets
(Night-time low noise setting is also required.)
setting
Power transistor
Used for trouble diagnosis of DC compressor. Since the
check mode
waveform of inverter is output without wiring to the
Check after
compressor, it is convenient to probe whether the trouble
disconnection of
compressor wires comes from the compressor or PCB.
If the capacity control is required, the low noise control is
Capacity
released by this setting during carrying out
precedence setting automatically
low noise operation and night-time low noise operation.

30

Demand setting 1

32

Normal demand
setting

Changes target value of power consumption when


demand control 1 is input.
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)

171

Field Setting

Si34-804_C

No.

Setting item

38

Emergency
operation
(Setting for the
master unit
operation
prohibition in multioutdoor-unit
system)

39

40

42

172

Emergency
operation
(Setting for the
slave unit 1
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 2
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(prohibition of INV.
compressor
operation)

Description

Used to temporarily prohibit the applicable outdoor unit


from operating should there be any detective part in multioutdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.

If the INV. compressor has a failure, used to run the


system only with STD compressor(s). This is a temporary
running of the system until the compressor is replaced,
thus making comfort extremely worse. Therefore, it is
recommended to replace the compressor as soon as
possible.
(Be noted this setting is not available on model RXQ5,
8PAY1.)

Test Operation

Si34-804_C

Field Setting

Setting item display


No.

Setting item

pressure
0 Digital
gauge kit display

MODE
H1P

TEST
H2P

IND
H3P

C/H selection
Master Slave
H4P
H5P

Low
noise
H6P

Setting condition display

Demand
H7P

Address

Binary number

(4 digits)
15

Cool/Heat
Unified address

Address

Binary number

(6 digits)

Low noise/demand
address

Address

Binary number

(6 digits)

Test operation
settings

Test operation: OFF

Indoor unit forced


fan H

Normal operation

Indoor unit forced


operation

Normal operation

Test operation: ON

Indoor forced fan H

Indoor forced operation


Low (Level L)
Normal (Level M)
High

Te setting

High
High

(Level H)

High
High
operation
11 Sequential
setting

External low noise


12 setting/Demand
setting

13 AIRNET address

OFF
ON
External low noise/demand:
NO

Address

Binary number

(6 digits)

High static pressure setting:


OFF

static pressure
18 High
setting

Emergency
19 operation
(STD compressor is
prohibited.)

Additional refrigerant
20 charging operation
setting

Refrigerant charging: OFF

Refrigerant
21 recovery/Vacuuming
mode setting

Refrigerant recovery / vacuuming: OFF

High static pressure setting:


ON
OFF
STD 1, 2 operation: Inhibited
STD 2 operation: Inhibited

Refrigerant charging: ON

Refrigerant recovery / vacuuming: ON

khkkkkk
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhhkk
khhhkhh
khhhkhk
khhhkkh
khhhkkk
khhhhhk
khhhhkh
khhhhhk
khhhhkh

External low noise/demand:


YES

khhhhhh
khhhhhk
~

63

Test Operation

khkkkkk
khhhhhh
khhhhhk
~

31
3

khhkkkk
khhhhhh
khhhhhk
~

31

Factory setting
khhhhhh
khhhhhk

kkkkkkk
khhhhhk
khhhhkh
khhhhhh
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhhhk
khhhhkh

173

Field Setting

Si34-804_C

Setting item display


No.

Setting item

MODE
H1P

TEST
H2P

IND
H3P

C/H selection
Master
Slave
H4P
H5P

Low
noise
H6P

Setting condition display

Demand
H7P
OFF

22

Night-time low noise


setting

Level 1 (outdoor fan with 6 step or lower)


Level 2 (outdoor fan with 5 step or lower)
Level 3 (outdoor fan with 4 step or lower)

ENECUT test
24 operation (Domestic
model only)

ENECUT output OFF


ENECUT output forced ON
Level 1 (outdoor fan with 6 step or lower)

25

Setting of external
low noise setting

Level 2 (outdoor fan with 5 step or lower)


Level 3 (outdoor fan with 4 step or lower)
About 20:00

Night-time low noise


26 operation start
setting

About 22:00 (factory setting)


About 24:00
About 6:00

Night-time low noise


27 operation end
setting

About 7:00
About 8:00 (factory setting)

28 Power transistor
check mode

OFF

29 Capacity
precedence setting

OFF

ON

ON
60 % demand

30 Demand setting 1

70 % demand
80 % demand

demand
32 Normal
setting

Emergency operation
(Setting for the master
38 unit operation
prohibition in multioutdoor-unit-system)

Emergency operation
(Setting for the slave
39 unit 1 operation
prohibition in multioutdoor-unit system)
Emergency operation
(Setting for the slave
40 unit 2 operation
prohibition in multioutdoor-unit system)
Emergency
operation
42 (prohibition of INV.
compressor
operation)

174

OFF
ON
OFF

Master unit operation: Inhibited

khhhhkh

OFF

khhhhhk

Slave unit 1 operation: Inhibited

khhhhkh

OFF

khhhhhk

Slave unit 2 operation: Inhibited

khhhhkh

Normal operation

khhhhhk

Emergency operation
(prohibition of INV. compressor
operation)

khhhhkh

Factory setting
khhhhhh
khhhhhk
khhhhkh
khhhhkk
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhkhh
khhhhhk
khhhhkh
khhhkhh
khhhhhk
khhhhkh
khhhkhh
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhhhk
khhhhkh
khhhkhh
khhhhhk
khhhhkh
khhhhhk

Test Operation

Si34-804_C

c. Monitor mode
To enter the monitor mode, press the
MODE (BS1) button when in Setting
mode 1.

<Selection of setting item>


Press the SET (BS2) button and set
the LED display to a setting item.

<Confirmation on setting contents>


Press the RETURN (BS3) button to
display different data of set items.

Press the RETURN (BS3) button


and switches to the initial status of
Monitor mode.

Field Setting

No.

Setting item

Various settings

C/H unified address

Low noise/demand address

Not used

AIRNET address

Number of connected indoor units


*1

Number of connected BS units *2

Number of connected zone units


(Fixed to "0")

Number of outdoor units *3

Number of BS units *4

10

Number of BS units *4

11

Number of zone units

12

Number of terminal units *5

13

Number of terminal units *5

14

Contents of error (the latest)

15

Contents of error (1 cycle before)

16

Contents of error (2 cycle before)

20

Contents of retry (the latest)

21

Contents of retry (1 cycle before)

22

25

LED display
H1P

H2P

H3P

H4P

H5P

H6P

H7P

l
l
l
l
l
l
l
l
l
l

h
h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
k
k

h
h
h
h
k
k
k
k
h
h

h
h
k
k
h
h
k
k
h
h

h
k
h
k
h
k
h
k
h
k

Data display
Lower 4 digits

Lower 6 digits

Lower 4 digits:
upper

l h h k h k h
l h h k h k k
l h h k k h h

Lower 4 digits:
lower

Lower 4 digits:
lower

Contents of retry (2 cycle before)

l
l
l
l
l
l
l

Number of multi connection


outdoor units

l h k k h h k

h
h
h
h
h
h
h

h
h
h
k
k
k
k

k
k
k
h
h
h
h

k
k
k
h
k
k
k

h
k
k
h
h
h
k

k
h
k
h
h
k
h

Lower 6 digits
Lower 4 digits:
upper

Error code table

Refer to
P.202.

Lower 6 digits

The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Press the MODE (BS1) button and
returns to Setting mode 1.

Test Operation

*1: Number of connected indoor units


Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)

175

Field Setting

Si34-804_C

Setting item 0 Display contents of Number of units for various settings


EMG operation /
backup operation
setting

ON

Te setting

OFF

M
H ~
Tc setting

L
M
H

l
l
l
l
l
l
l
l

h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h

k
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h

h
h
h
l
k
h
h
h

h
h
h
h
h
h
l
k

Data such as addresses and number of units is expressed as binary numbers; the two ways

of expressing are as follows:


The No. 1 cool/heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
16
32

4
8

1
2

In c the address is 010110 (binary number), which translates to


16 + 4 + 2 = 22 (base 10 number). In other words, the address is
22.

64 16
No.12 128 32

4
No.13

1
2

The number of terminal blocks for No. 12 and 13 is expressed as


an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
In d the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.

See the preceding page for a list of data, etc. for No. 0 - 25.

176

Test Operation

Si34-804_C

Field Setting

3.2.2 Setting of Night-time Quiet Operation and Demand Operation


Setting of Night-time Quiet Operation
By connecting the external contact input to the low noise input of the external control adaptor for
outdoor unit (optional), you can lower operating noise by 2-3 dB.
Setting

Content

Mode 1
Mode 2

Set the outdoor unit fan to Step 6 or lower.


Set the outdoor unit fan to Step 5 or lower.

Mode 3

Set the outdoor unit fan to Step 4 or lower.

A. When the night-time quiet operation is carried out by external contact (with the use
of the external control adaptor for outdoor unit)
1. Connect external control adaptor for outdoor unit and short-circuit terminal of low noise
(Refer below figure).
If carrying out demand or low-noise input, connect the adaptors terminals as shown below.

External control
adapter for
outdoor unit

Host computer
monitor panel
or demand
controller

F1

F2

P3

P4

2 3 C
Demand

Low
noise

Outside wiring indicated


by dotted line

2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
night-time quiet/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2",
or "Mode 3") for set item No. 25 (Setting of external low noise level).
4. If necessary, while in "Setting mode 2", set the setting condition for the set item No. 29
(Setting of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the nighttime quiet operation command will be ignored to put the system into normal operation
mode.)
B. When the low noise operation is carried out automatically at night (The external
control adaptor for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime night-time quiet operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime night-time quiet operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)

Test Operation

177

Field Setting

Si34-804_C

Image of operation in the case of A


If capacity precedence is set in
"Capacity precedence setting", the
fan speed will be increased
according to the load of air
conditioning when load is heavier.

Operation sound
Rated operation
sound
Operation sound of
mode 1
Operation sound of
mode 2
Operation sound of
mode 3

Operation sound
during low noise
mode is instructed
can be set with
"External low noise
level setting"
(Factory setting is
"Mode 2".)

Low noise mode instructing


Approx. 55 db (target)
(The power consumption may be increased by about 10%)
Approx. 50 db (target)
(The power consumption may be increased by about 20%)
Operation sound level set with "External low noise setting"
Approx. 45 db (target)
(The power consumption may be increased by about 30%)

Image of operation in the case of B

Operation sound
Rated operation
sound
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
of mode 3

Time set with "Night-time low noise


start setting"

If capacity precedence is set in


"Capacity precedence setting", the
fan speed will be increased
according to the load of air
conditioning when load is heavier.
Night-time

Operation sound level set with


"Night-time low noise setting"

Time set with "Night-time low


noise end setting"
Operation sound
during night-time low
noise mode is
instructed can be set
with "Night-time low
noise level setting".
(Factory setting is
"OFF".)

PM 8:00 PM 10:00 PM 0:00

AM 6:00 AM 7:00 AM 8:00

Set with "Night-time low noise start setting".


(Factory setting is "PM 10:00".)

Set with "Night-time low noise end setting".


(Factory setting is "AM 8:00".)

Image of operation in the case of A and B

Operation sound

If capacity precedence is set in


"Capacity precedence setting", the
fan speed will be increased
according to the load of air
conditioning when load is heavier.

Time set with "Night-time low


noise end setting"
Operation sound during low noise
mode is instructed can be set with
Rated operation
"External low noise level setting".
sound
Night-time
(Factory setting is "Mode 2".)
Operation sound
Operation sound during night-time
of mode1
low noise mode is instructed can
Low noise mode
Operation sound
be set with "Night-time low noise
instructing

Operation
sound
of mode2
level setting".
level set with
(Factory setting is "OFF".)
Operation sound Low noise mode instructing
"Night-time low Operation sound set with
of mode3
When external low noise
noise setting" "External low noise setting"
Operation sound set with
instruction is received during
"External low noise setting"
PM 8:00 PM 10:00 PM 0:00
AM 6:00 AM 7:00 AM 8:00 the operation with night-time
low noise mode,
Set with "Night-time low noise start setting".
Set with "Night-time low noise end setting". Mode 2 precedes Mode 1
and Mode 3 precedes Mode 2.
(Factory setting is "PM 10:00".)
(Factory setting is "AM 8:00".)
Time set with "Night-time low noise
start setting"

178

Test Operation

Si34-804_C

Field Setting

Setting of Demand Operation


By connecting the external contact input to the demand input of the external control adaptor for
outdoor unit (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
Setting content
Set item

Condition
Mode 1

Demand 1 Mode 2
Mode 3
Demand 2
Demand 3

Setting method
External control
adaptor

Content

Outdoor unit PCB

The compressor operates at


approx. 60% or less of rating.
The compressor operates at
approx. 70% or less of rating.
The compressor operates at
approx. 80% or less of rating.

Set item No. 32 to "Demand 1", and item No.


30 to "Level 1".
Short circuit "1" and
"C" on the terminal
strip (TeS1).

Set item No. 32 to "Demand 1", and item No.


30 to "Level 2".
Set item No. 32 to "Demand 1", and item No.
30 to "Level 3".

The compressor operates at Short circuit "2" and "C".


approx. 40% or less of rating.
Forced thermostat OFF.
Short circuit "3" and "C".

Set item No. 32 to "Demand 2".

*: However the demand operation does not occur in the following operation modes.
 Startup control
 Oil return operation
 Defrosting operation
 Pump-down residual operation
If carrying out demand or low-noise input, connect the adaptors terminals as shown below.

External control
adapter for
outdoor unit

Host computer
monitor panel
or demand
controller

F1

F2

P3

P4

2 3 C
Demand

Low
noise

Outside wiring indicated


by dotted line

A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short-circuit terminals as required
(Refer above figure).
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control
adaptor for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of alternate demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.

Test Operation

179

Field Setting

Si34-804_C

Image of operation in the case of A


Power consumption

Rated power consumption


80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption

Demand level 1 instructing

Demand level 2 instructing

Demand level 3 instructing

Power consumption set by


"Demand 1 level setting".

40 % of rated power consumption


Forced thermostat OFF
(Fan operation)

The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power
consumption" has
been set at factory.)

Image of operation in the case of B


Power consumption

Rated power consumption


80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
The power consumption set with "Demand 1 level setting".

When the "Normal


demand setting" is
set to ON ("OFF"
has been set at
factory.) , the power
consumption can be
set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)

Image of operation in the case of A and B


The power
consumption can
be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at
factory.)

Power consumption

Rated power consumption


80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption The power consumption set with "Demand 1 level setting".
Forced thermostat OFF
(Fan operation)

180

+Demand level 2 instructing +Demand level 3 instructing

+During continuous demand operation,


when the external demand instruction is
received repeatedly, the instruction with
higher demand level has the precedence.

Test Operation

Si34-804_C

Field Setting

Detailed Setting Procedure of Low Noise Operation and Demand Control


1. Setting mode 1 (H1P off)
c In setting mode 2, press the BS1 (MODE) one time. Setting mode 1 is entered and H1P

lights off.
During the setting mode 1 is displayed, In low noise operation and In demand control are
displayed.
2. Setting mode 2 (H1P on)
c In setting 1, press and hold the BS1 (MODE) for more than 5 seconds. Setting mode 2 is
entered and H1P lights.
d Press the BS2 (SET) several times and match the LED display with the Setting No. you
want.
e Press the BS3 (RETURN) one time, and the present setting content is displayed.
Press the BS2 (SET) several times and match the LED display with the setting content
(as shown next page) you want.
f Press the BS3 (RETURN) two times. Returns to c.
g Press the BS1 (MODE) one time. Returns to the setting mode 1 and turns H1P off.

Test Operation

181

Field Setting

Si34-804_C

{: ON
d

c
Setting
No.

Setting
contents
External
low noise
setting/
Demand
setting

22

Night-time
low noise
setting

25

Setting No. indication

Setting of
external low
noise
setting

Setting
contents

Night-time
low noise
operation
start setting

Night-time
low noise
operation
end setting

27

29

30

32

H1P H2P H3P H4P H5P H6P H7P

YES

OFF
(Factory
setting)

Mode 1

Mode 2
Mode 3

{
{

z
z

z
z

z
z

z
z

l
l

z
l

Mode 1

Mode 2
(Factory
setting)

{
{

z
z

z
z

z
z

l
z

z
z

z
l

PM 10:00
(Factory
setting)

PM 0:00

AM 6:00

{
{

z
z

z
z

z
z

z
z

z
l

l
z

AM 8:00
(Factory
setting)

Low noise
precedence
(Factory
setting)

Capacity
precedence

60 % of
rated power
consumption

70 % of
rated power
consumption
(Factory
setting)

80 % of
rated power
consumption

OFF
(Factory
setting)

ON

PM 8:00

AM 7:00

Capacity
precedence
setting

Demand
setting 1

Normal
demand
setting

Setting mode indication section

182

Setting No. indication section

Setting contents indication (Initial setting)

NO
(Factory
setting)

Mode 3
26

l: Blink

Setting No. indication

H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12

z: OFF

Set contents indication section

Test Operation

Si34-804_C

Field Setting

3.2.3 Setting of Refrigerant Recovery Mode


When carrying out the refrigerant collection onsite, fully open the respective electronic
expansion valve of indoor and outdoor units.
All indoor and outdoor units operation are prohibited.
[Operation procedure]
c In setting mode 2 with units in stop mode, set Refrigerant Recovery / Vacuuming mode to
ON. The respective electronic expansion valve of indoor and outdoor units are fully opened.
(H2P turns to display TEST OPERATION (blinks), TEST OPERATION and UNDER
CENTRALIZED CONTROL are displayed on the remote controller, and the all indoor /
outdoor unit operation is prohibited.
After setting, do not cancel Setting Mode 2 until completion of refrigerant recovery
operation.
d Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the

refrigerant recovery unit for more detail.)


e Press the BS1 (MODE) once and reset Setting Mode 2.

Test Operation

183

Field Setting

Si34-804_C

3.2.4 Setting of Vacuuming Mode


In order to perform vacuuming operation at site, fully open the electric expansion valves of
indoor and outdoor units and turn on some solenoid valves.
[Operating procedure]
c With Setting Mode 2 while the unit stops, set Refrigerant recovery / Vacuuming mode to
ON. The electric expansion valves of indoor and outdoor units fully open and some of
solenoid valves open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test
Operation" and "Under centralized control", thus prohibiting operation.)
After setting, do not cancel Setting Mode 2 until completion of Vacuuming operation.
d Use the vacuum pump to perform vacuuming operation.
e Press the BS1 (MODE) once and reset Setting Mode 2.

3.2.5 Check Operation Detail


CHECK OPERATION FUNCTION
(Press the BS1 (MODE) once and set to SETTING MODE 1 (H1P: OFF))
LED display (H1P~H7P) (k: ON

Unit stopping

h: OFF l: BLINK)

hhkhhhh
Press the TEST button for 5 seconds.

Step 1

hlhhhhk

Pressure equalizing
10 seconds to 10 minutes

Step 2

Cooling start control

Step 3

Stability waiting operation

hlhhhkh
20 seconds to 2 minutes

hlhhhkk
10 minutes

Step 4~8

Judgement function

Stop valve close check


Wrong wiring check
Correct Refrigerant charge check
Piping length check

hlhhkhh
hlhhkhk
hlhhkkh
hlhhkkk
hlhkhhh

Step 9

hlhkhhk

Pump down residual operation


5 minutes

Step 10

hlhkhkh

Standby for restarting


5 minutes
Completion

184

Test Operation

Si34-804_C

Part 6
Service Diagnosis
1. Symptom-based Troubleshooting .......................................................187
2. Troubleshooting by Remote Controller ...............................................190
2.1
2.2
2.3
2.4

The INSPECTION / TEST Button.........................................................190


Self-diagnosis by Wired Remote Controller .........................................191
Self-diagnosis by Wireless Remote Controller .....................................193
Operation of the Remote Controllers Inspection /
Test Operation Button ..........................................................................195
2.5 Remote Controller Service Mode .........................................................196
2.6 Remote Controller Self-Diagnosis Function .........................................199
2.7 Error Code and Description..................................................................200

3. Troubleshooting by Indication on the Remote Controller ....................206


3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.27
3.28
3.29
3.30
3.31
3.32
3.33
3.34
Service Diagnosis

External Protection Device Abnormality ...............................................206


PCB Abnormality ..................................................................................207
Drain Level Control System (S1L) Abnormality....................................208
Fan Motor (M1F) Lock, Overload .........................................................210
Swing Flap Motor (M1S) Abnormality...................................................214
Power Supply Voltage Abnormality ......................................................216
Electronic Expansion Valve Coil (Y1E) Abnormality ............................217
Drain Level above Limit........................................................................219
Capacity Determination Device Abnormality ........................................220
Transmission Error (Between Indoor unit PCB and Fan PCB).............221
Thermistor Abnormality ........................................................................223
Combination Error (Between Indoor unit PCB and Fan PCB)..............224
Humidity Sensor System Abnormality ..................................................225
Room Temperature Thermistor in Remote Controller Abnormality ......226
PCB Abnormality ..................................................................................227
Actuation of High Pressure Switch .......................................................228
Actuation of Low Pressure Sensor .......................................................231
Inverter Compressor Motor Lock..........................................................233
STD Compressor Motor Overcurrent/Lock...........................................236
Outdoor Unit Fan Motor Abnormality....................................................237
Electronic Expansion Valve Coil (Y1E, Y2E) Abnormality....................240
Discharge Pipe Temperature Abnormality ...........................................242
Refrigerant Overcharged......................................................................244
Outdoor Fan Motor Signal Abnormality ................................................245
Thermistor Abnormality ........................................................................246
Current Sensor Abnormality .................................................................247
High Pressure Sensor Abnormality ......................................................248
Low Pressure Sensor Abnormality .......................................................250
Inverter PCB Abnormality.....................................................................253
Inverter Radiation Fin Temperature Rise Abnormality .........................255
Inverter Compressor Abnormality.........................................................258
Inverter Current Abnormality ................................................................260
Inverter Compressor Startup Abnormality ............................................262
Transmission Error between Inverter and Control PCB .......................265
185

Si34-804_C

3.35 Inverter Over-Ripple Protection............................................................267


3.36 Inverter Radiation Fin Temperature Abnormality .................................269
3.37 Field Setting after Replacing Main PCB Abnormality or
Combination of PCB Abnormality.........................................................270
3.38 Refrigerant Shortage ............................................................................271
3.39 Reverse Phase, Open Phase...............................................................272
3.40 Power Supply Insufficient or Instantaneous Abnormality .....................273
3.41 Check Operation is not Executed.........................................................276
3.42 Transmission Error between Indoor Units and Outdoor Units..............277
3.43 Transmission Error between Remote Controller and Indoor Unit.........279
3.44 Transmission Error between Outdoor Units .........................................280
3.45 Transmission Error between Main and Sub Remote Controllers .........282
3.46 Transmission Error between Indoor and
Outdoor Units in the Same System ......................................................283
3.47 Improper Combination of Indoor and Outdoor Units, Indoor Units and
Remote Controller ................................................................................284
3.48 Address Duplication of Centralized Controller......................................286
3.49 Transmission Error between Centralized Controller and Indoor Unit ...287
3.50 System is not Set yet............................................................................290
3.51 System Abnormality, Refrigerant System Address Undefined .............291

186

Service Diagnosis

Si34-804_C

Symptom-based Troubleshooting

1. Symptom-based Troubleshooting
Symptom
1

Supposed Cause

The system does not start operation at all.

Blowout of fuse(s)
Cutout of breaker(s)

Countermeasure
Turn Off the power supply and
then replace the fuse(s).
If the knob of any breaker is in
its OFF position, turn ON the
power supply.
If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.

ON
Knob
Tripped

OFF
Circuit breaker

Power failure
2

The system starts operation but makes an


immediate stop.

The system does not cool air well.

After the power failure is reset,


restart the system.
Blocked air inlet or outlet of indoor Remove obstacle(s).
or outdoor unit
Clogged air filter(s)
Clean the air filter(s).
Blocked air inlet or outlet of indoor Remove obstacle(s).
or outdoor unit
Clogged air filter(s)
Enclosed outdoor unit(s)

Clean the air filter(s).


Remove the enclosure.

Improper set temperature

Set the temperature to a proper


degree.
Set it to a proper airflow rate.

Airflow rate set to "LOW"

Improper direction of air diffusion Set it to a proper direction.


Open window(s) or door(s)
Shut it tightly.

[In cooling] Direct sunlight received

Hang curtains or shades on


windows.

[In cooling] Too many persons staying in a


room
[In cooling] Too many heat sources (e.g. OA
equipment) located in a room

The model must be selected to


match the air conditioning load.

The system does The system stops and


not operate.
immediately restarts operation.
Pressing the TEMP ADJUST
button immediately resets the
system.

If the OPERATION lamp on the


remote controller turns ON, the
system will be normal. These
symptoms indicate that the
system is controlled so as not to
put unreasonable loads on the
system.
The remote controller displays The system is controlled with
"UNDER CENTRALIZED
centralized controller. Blinking
CONTROL", which blinks for a display indicates that the system
period of several seconds
cannot be operated using the
when the OPERATION button remote controller.
is depressed.

Normal operation. The system will


automatically start operation after
a lapse of five minutes.

The system stops immediately


after turning ON the power
supply.
The remote controller displays
error codes "U4" and "U5", and
the system stops but restarts
after a lapse of several
minutes.

The system is in preparation


mode of micro-computer
operation.
The system stops due to an
interruption in communication
between units caused by
electrical noises coming from
equipment other than air
conditioners.

Wait for a period of approximately


one minute.

The system is in preparation


mode of operation.

Wait for a period of approximately


10 minutes.

The system
makes
intermittent
stops.

The system
This symptom occurs
conducts fan
immediately after turning ON
operation but not the power supply.
cooling
operation.

Service Diagnosis

Operate the system using the


COOL/HEAT centralized remote
controller.

Remove causes of electrical


noises.
If these causes are removed, the
system will automatically restart
operation.

187

Symptom-based Troubleshooting

Symptom

Si34-804_C

Supposed Cause

Countermeasure

The airflow rate


is not
reproduced
according to the
setting.

Even pressing the AIRFLOW


RATE SET button makes no
changes in the airflow rate.

The fan LL operation is also


Normal operation.
enabled while in oil return mode in
cooling operation.

The airflow
direction is not
reproduced
according to the
setting.
A white mist
comes out from
the system.

The airflow direction is not


corresponding to that
displayed on the remote
controller.
The flap does not swing.
<Indoor unit>
In cooling, the ambient
humidity is high.
(This indoor unit is installed in
a place with much oil or dust.)

Automatic control

<Indoor unit>
Immediately after cooling
operation stopping, the
outdoor air temperature and
ambient humidity are low.
<Indoor unit>
Immediately after turning ON
the power supply, indoor unit
produces "ringing" sounds.

Hot gas (refrigerant) flown in the


indoor unit results to be vapor
from the unit.

<Indoor and outdoor units>


"Hissing" sounds are
continuously produced while in
cooling or defrosting operation.
<Indoor and outdoor units>
"Hissing" sounds are produced
immediately after the startup or
stop of the system, or the
startup or stop of defrosting
operation.

These sounds are produced from Normal operation.


gas (refrigerant) flowing
respectively through the indoor
and outdoor units.
These sounds are produced
Normal operation.
when the gas (refrigerant) stops
or changes flowing.

<Indoor unit>
Faint sounds are continuously
produced while in cooling
operation or after stopping the
operation.
<Indoor unit>
"Creaking" sounds are
produced after stopping the
operation.

These sounds are produced from Normal operation.


the drain discharge device in
operation.

<Indoor unit>
Sounds like "trickling" or the
like are produced from indoor
units in the stopped state.

On VRV systems, these sounds Normal operation.


are produced when other indoor
units in operation. The reason is
that the system runs in order to
prevent oil or refrigerant from
dwelling.
The reason is that the compressor Normal operation.
changes the operating frequency.

10 The system
produces
sounds.

<Outdoor unit>
Pitch of operating sounds
changes.
11 Dust comes out Dust comes out from the
from the system. system when it restarts after
the stop for an extended period
of time.
12 Odors come out In operation
from the system.
13 Outdoor unit fan
does not rotate.

In operation

14 LCD display "88" Immediately after turning ON


appears on the
the power supply
remote
controller.
15 The outdoor unit After stopping operation
compressor or
the outdoor unit
fan does not
stop.

188

Normal operation.

Uneven temperature distribution Clean the inside of the indoor unit.


due to heavy stain of the inside of
the indoor unit

Normal operation.

These are operating sounds of


Normal operation.
the electronic expansion valve of This sound becomes low after a
the indoor unit.
lapse of approximately one
minute.

These sounds are produced from Normal operation.


resin parts expanding and
contracting with temperature
changes.

Dust, which has deposited on the Normal operation.


inside of indoor unit, is blown out
from the system.
Odors of room, cigarettes or else The inside of the indoor unit
adsorbed to the inside of indoor should be cleaned.
unit are blown out.
The reason is that fan revolutions
are controlled to put the operation
to the optimum state.
The reason is that the system is
checking to be sure the remote
controller is normal.

Normal operation.

It stops in order to prevent oil or


refrigerant from dwelling.

Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.

Normal operation.
This code is displayed for a period
of approximately one minute at
maximum.

Service Diagnosis

Si34-804_C

Symptom-based Troubleshooting

Symptom
16 The outdoor gets While stopping operation
hot.

Supposed Cause

The reason is that the compressor Normal operation.


is warmed up to provide smooth
startup of the system.

17 The system does The system is in dry operation. The reason is that the dry
not cool air well.
operation serves not to reduce
the room temperature where
possible.

Service Diagnosis

Countermeasure

Change the system to cooling


operation.

189

Troubleshooting by Remote Controller

Si34-804_C

2. Troubleshooting by Remote Controller


2.1

The INSPECTION / TEST Button


The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
On power-up, the message "Connection under check. Please wait for a moment" will be
displayed on the remote controller screen. Then that message will disappear and the basic
screen will be displayed. To access a mode from the basic screen, refer to the figure below.
When any of the operation buttons is pressed, the backlight will come on and remains lit for
about 30 seconds. Be sure to press a button while the backlight is on (this does not apply to the
On/Off button.)
<Main Menu>

Main Menu screen

<Basic Screen>
Operation mode changeover
Fan speed control
Menu display
Confirmation of each setting
ON
OFF
Cancel
Operation lamp

Press
Menu/Enter
button once.

Press Cancel button


for 4 seconds or more.

Set temp. mode changeover


Airflow direction
Quick Cool/Heat ON/OFF
Ventilation
Timer setting
Service Contact/Model Info
Convenient functions
Setting status list
Clock setting
Language changeover

Press Cancel
button once.

Basic screen

Press Cancel
button once.

Press Cancel
button once.
Press Cancel button
for 4 seconds or more.

Field Setting screen

<Field Setting Menu>


Test operation ON/OFF
Register Service Contract
Field setting list
Group No. setting
Indoor unit AIRNET No. set
Outdoor unit AIRNET No. set
Error record
Indoor status display
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign OFF

190

Service Menu screen

<Service Menu>
Model name display
Operating hours display
Indoor status display
Outdoor status display
Forced defrost
Error display selection
Unit No. transfer
Sensor/address data display

Service Diagnosis

Si34-804_C

2.2

Troubleshooting by Remote Controller

Self-diagnosis by Wired Remote Controller

2.2.1 Wired Remote Controller BRC1C61/BRC1D61


If operation stops due to error, the remote controllers operation LED blinks, and error code is
displayed. (Even if stop operation is carried out, error contents are displayed when the
inspection mode is entered.) The error code enables you to tell what kind of error caused
operation to stop. Refer to P.202 for error code and error contents.
Operation LED
ON/OFF button

Display of indoor unit for


which a error has been
detected

Inspection display

Error code

Inspection/Test button

Note:

Service Diagnosis

1. Pressing the INSPECTION/TEST button will blink the check indication.


2. While in service mode, holding down the ON/OFF button for a period of 5 seconds or more
will clear the failure history indication shown above. In this case, on the codes display, the
error code will blink twice and then change to 00 (=Normal), the Unit No. will change to 0,
and the operation mode will automatically switch from service mode to normal mode
(displaying the set temperature).

191

Troubleshooting by Remote Controller

Si34-804_C

2.2.2 Wired Remote Controller BRC1E61


Explanation

The following will be displayed on the screen when an error (or a warning) occurs during
operation.
Check the error code and take the corrective action specified for the particular model.
Screen

Operation lamp

(1) Checking an error or warning


Operation Status

192

Display

Abnormal
shutdown

The system stops operating.

The operation lamp (green)


starts to blink. The message
"Error: Press Menu button"
will appear and blink at the
bottom of the screen.

Warning

The system continues its


operation.

The operation lamp (green)


remains on. The message
"Warning: Press Menu
button" will appear and blink
at the bottom of the screen.

Service Diagnosis

Si34-804_C

2.3

Troubleshooting by Remote Controller

Self-diagnosis by Wireless Remote Controller


If unit stops due to an error, the operation indicating LED on the signal receiving part of indoor unit flashes.
The error code can be determined by following the procedure described below. (The error code is displayed
when an operation error has occurred. In normal condition, the error code of the last problem is displayed.)

3
4

Press the INSPECTION/TEST button to select inspection. The equipment enters


the inspection mode. The Unit indication is displayed and the Unit No. display
shows flashing 0 indication.
Set the Unit No.
Press the UP or DOWN button and change the Unit No. display until the buzzer
(1) is generated from the indoor unit.
1 Number of beeps
3 short beeps : Conduct all of the following operations.
1 short beep : Conduct steps 3 and 4.
Continue the operation in step 4 until a buzzer remains ON. The
continuous buzzer indicates that the error code is confirmed.
Continuous beep : No abnormality.
Press the MODE selector button.
The left 0 (upper digit) indication of the error code flashes.
Error code upper digit diagnosis
Press the UP or DOWN button and change the error code upper digit until the error
code matching buzzer (2) is generated.
The upper digit of the code changes as shown below when the UP and DOWN
buttons are pressed.

2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Error code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
5
6

Press the MODE selector button.


The right 0 (lower digit) indication of the error code flashes.
Error code lower digit diagnosis
Press the UP or DOWN button and change the error code lower digit until the
continuous error code matching buzzer (2) is generated.
The lower digit of the code changes as shown below when the UP and DOWN
buttons are pressed.

Service Diagnosis

193

Troubleshooting by Remote Controller

194

Si34-804_C

Service Diagnosis

Si34-804_C

2.4

Troubleshooting by Remote Controller

Operation of the Remote Controllers Inspection / Test


Operation Button
0
Unit
L0
Malfunction code
Inspection
Error code blinks when an error tion occurs.

Normal display (No display)

Inspection/test
operation

Press the button.

0
L0

Unit
Error code
Inspection

Inspection mode

Inspection/test
operation

Example of capacity code display

0 7 1... Capacity code


F... Indoor unit system code
C... Indoor unit type code
J... Progression code

Display

Example model
FXCQ25

028

FXFQ63

071

Press the button.


Indoor unit system code
Product classification

System classification

VRV system

(VAV indoor unit)

VRV system

Outdoor air processing unit

VRV system

Standard indoor unit

VRV system

New ceiling suspended cassette

Display
071
FCJ
Indoor unit model code display

Indoor unit type code


Inspection/test
operation

Press the button.

Display

AA1
Outdoor unit model code display

Inspection/test
operation

Press the button.

Test operation
Test operation mode

Wall mounted

FXAQ

Double flow

FXCQ

Corner

FXKQ

Round flow

FXFQ-P

Ceiling suspended

FXHQ

Floor standing

FXLQ

Ceiling mounted duct

FXMQ-P, MA

Concealed floor standing type

FXNQ

Slim Ceiling mounted duct

FXDQ

Outdoor model code


Type

Display
Inspection/test
operation

Service Diagnosis

Press the button.

Model

Type

Model

AA1

VRV System Inverter K Series

RSXYP

AA3

R-407C VRV PLUS Series

RXYP

A92

VRV Heat Recovery Series

RSEYP

AA5

High COP type R-407C L Series

RSXYP-L

AAA

VRVII

RXYQ-M

AAC

VRVII M/C

RXYQ-MA

AAE

VRVIII

RX(Y)Q-P(A)

195

Troubleshooting by Remote Controller

2.5

Si34-804_C

Remote Controller Service Mode

How to Enter the


Service Mode

Service Mode
Operation
Method

1. Select the mode No.


Select the desired item from the Service menu, and then press Menu/Enter button.
2. Select the Item 2.
Select the desired Unit No. using the S/T (Up/Down) buttons. The corresponding data will be
displayed.
For details, refer to the table in next page.

196

Service Diagnosis

Si34-804_C

Troubleshooting by Remote Controller

Service Menu

Item 2

1. Model Name Display 1. Unit No.

Remarks
Select the Unit No. you want to check.

2. Indoor unit
3. Outdoor unit
2. Operating Hours
Display

1. Unit No.
2. Indoor unit operating
time

Select the Unit No. you want to check.


All of these are displayed in hours.

3. Indoor fan operation


4. Indoor unit energized
time
5. Outdoor operating
time
6. Outdoor fan 1
operation
7. Outdoor fan 2
operation
8. Outdoor comp. 1
operation
9. Outdoor comp. 2
operation
3. Indoor Status Display 1. Unit No.
1/2
2. FAN
3. FLAP

Fan speed (rpm)


Opening degree of electronic expansion valve
(pls)

6. MP
7. 52H

Drain pump ON/OFF


Electric heater ON/OFF

8. Hu
9. Anti-freezing

Humidifier ON/OFF
Anti-freezing control ON/OFF
Select the Unit No. you want to check.
VRV

2. Th1
3. Th2

Suction air thermistor


Heat exchanger liquid pipe thermistor

4. Th3
5. Th4

Heat exchanger gas pipe thermistor


Discharge air thermistor

6. Th5
7. Th6

1. Unit No.
2. FAN Tap 1

Select the Unit No. you want to check.


Fan tap

3. COMP
4. EV1

Compressor power supply frequency (Hz)


Opening degree of electronic expansion valve
(pls)

5. SV1

Solenoid valve ON/OFF


VRV

6. Th1
7. Th2
5. Error Display
Selection

Tap, speed (rpm)


Swing, fixed

4. Speed
5. EV

3. Indoor Status Display 1. Unit No.


2/2

4. Outdoor Status
Display

Select the Unit No. you want to check.

8. Th3
1. Warning display ON

Displays a warning on the screen if an error


occurs.

2. Warning display OFF No warning is displayed.


3. Error display ON
Displays the error on the screen.
6. Unit No. Transfer

4. Error display OFF


1. Current Unit No.

Displays neither errors nor warnings.


A unit No. can be transferred to another.

2. Transfer Unit No.

Service Diagnosis

197

Troubleshooting by Remote Controller

Service Menu
7. Sensor Address
Display

198

Si34-804_C

Item 2
{ Unit No.: 0 - 15
{ Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
{ Data

Remarks
Select the Unit No. you want to check.
Remote controller thermistor (C)
Suction air thermistor (C)
Heat exchanger liquid pipe thermistor (C)
Heat exchanger gas thermistor (C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/heating batch address No.
Demand/low-noise address No.
The corresponding data will be displayed, based
on the Unit No. and Code selected.

Service Diagnosis

Si34-804_C

2.6

Troubleshooting by Remote Controller

Remote Controller Self-Diagnosis Function


The following will be displayed on the screen when an error (or a warning) occurs during
operation.
Check the error code and take the corrective action specified for the particular model.
Screen

Operation lamp

(1) Checking an error or warning


Operation Status

Abnormal
shutdown

Warning

Display

The system stops operating.

The operation lamp (green)


starts to blink. The message
"Error: Press Menu button"
will appear and blink at the
bottom of the screen.

The system continues its


operation.

The operation lamp (green)


remains on. The message
"Warning: Press Menu
button" will appear and blink
at the bottom of the screen.

(2) Taking corrective action


Press the Menu/Enter button to check the error code.

Take the corrective action specific to the model.


Error code

Applicable
model names

Service Diagnosis

199

Troubleshooting by Remote Controller

2.7

Si34-804_C

Error Code and Description


k: ON

Indoor Unit

Outdoor Unit

200

h: OFF

Error contents

l: Blink
Page
Referred

Error code

Operation
lamp

A0
A1

l
l

External protection device abnormality


PCB abnormality

206
207

A3
A6

l
l

Drain level control system (S1L) abnormality


Fan motor (M1F) lock, overload

208
210,
211

A7
A8

k
l

Swing flap motor (M1S) abnormality


Power supply voltage abnormality

214
216

A9
AF

l
k

Electronic expansion valve coil (Y1E) abnormality


Drain level above limit

217
219

AJ
C1

l
l

Capacity Determination Device abnormality


Transmission error (between indoor unit PCB and fan PCB)

220
221

C4
C5

l
l

Thermistor (R2T) for heat exchange abnormality


Thermistor (R3T) for gas pipes abnormality

223
223

C6
C9

l
l

Combination error (between indoor unit PCB and fan PCB)


Thermistor (R1T) for suction air abnormality

224
223

CC
CJ

k
k

Humidity sensor system abnormality


Room temperature thermistor in remote controller abnormality

225
226

E1
E3

l
l

PCB abnormality
Actuation of high pressure switch

227
228

E4
E5

l
l

Actuation of low pressure sensor


Inverter compressor motor lock

231
233

E6
E7

l
l

STD compressor motor overcurrent/lock


Outdoor unit fan motor abnormality

236
237

E9
F3

l
l

Electronic expansion valve coil (Y1E, Y2E) abnormality


Discharge pipe temperature abnormality

240
242

F6
H7

l
l

Refrigerant overcharged
Outdoor fan motor signal abnormality

244
245

H9
J2

l
l

Thermistor (R1T) for outdoor air abnormality


Current sensor abnormality

246
247

J3
J5

l
l

Discharge pipe thermistor (R3, R31~33T) abnormality


Thermistor (R2T,R7T) for suction pipe abnormality

246
246

J6
J7

l
l

Thermistor (R4T) for outdoor unit heat exchanger abnormality


Liquid pipe thermistor (R5T or R6T) abnormality

246
246

J9
JA

l
l

Subcooling heat exchanger gas pipe thermistor (R5T) abnormality


High pressure sensor abnormality

248

JC
L0

l
l

Low pressure sensor abnormality


Inverter system abnormality

250

L4

Inverter radiation fin temperature rise abnormality

255

L5
L8

l
l

Inverter compressor abnormality


Inverter current abnormality

258
260

L9
LC

l
l

Inverter compressor startup abnormality


Transmission error between inverter and control PCB

262
265

P1
P4

l
l

Inverter over-ripple protection


Inverter radiation fin temperature abnormality

267
269

PJ

Field setting after replacing main PCB abnormality or combination of PCB


abnormality

270

Service Diagnosis

Si34-804_C

Troubleshooting by Remote Controller

k: ON
Error code
System

U0

Operation
lamp
k
Refrigerant shortage

h: OFF

Error contents

l: Blink
Page
Referred
271

U1

Reverse phase / open phase

272

U2
U3

l
l

Power supply insufficient or instantaneous abnormality


Check operation is not executed

273
276

U4
U5

l
l

Transmission error between indoor units and outdoor units


Transmission error between remote controller and indoor unit

277
279

U7
U8

l
l

Transmission error between outdoor units


Transmission error between main and sub remote controllers

280
282

U9
UA

l
l

Transmission error between indoor and outdoor units in the same system
Improper combination of indoor and outdoor units, indoor units and remote
controller

283
284

UC
UE

k
l

Address duplication of centralized controller


Transmission error between centralized controller and indoor unit

286
287

UF
UH

l
l

System is not set yet


System abnormality, refrigerant system address undefined

290
291

The system operates for error codes indicated in black squares, however, be sure to check and repair.

Service Diagnosis

201

Troubleshooting by Remote Controller

Si34-804_C

Error code indication by outdoor unit PCB


<Monitor mode>
Contents of error

To enter the monitor mode, press the


MODE (BS1) button when in
Setting mode 1.

PCB abnormality

Error code

PCB abnormality

E1

Faulty PCB

* Refer to P.175 for Monitor mode.

Abnormal high pressure switch

High pressure switch activated

E3

Abnormal low pressure switch

Low pressure switch activated

E4

Compressor lock

Detection of INV. compressor lock

E5

Activation of OC

Detection of STD1 compressor lock

E6

Detection of STD2 compressor lock

<Selection of setting item>

Over load, overcurrent,


Instantaneous overcurrent of DC fan 1 motor
abnormal lock of outdoor unit fan motor
Detection of DC fan 1 motor lock

Press the SET (BS2) button and set


the LED display to a setting item.

E7

Instantaneous overcurrent of DC fan 2 motor


Detection of DC fan 2 motor lock

* Refer to P.175 for Monitor mode.

E9

Malfunction of electronic expansion


valve

EV1

Abnormal position signal of outdoor


unit fan motor

Abnormal position signal of DC fan 1 motor

Faulty thermistor of outdoor air


temperature

Faulty Ta sensor (short)

Abnormal discharge pipe temperature

Abnormal Td

EV2
EV3

<Confirmation of error 1>


Press the RETURN (BS3) button
once to display "First digit" of error
code.

H7

Abnormal position signal of DC fan 2 motor


H9

Faulty Ta sensor (open)


F3

Abnormal heat exchanger temperature Refrigerant overcharge

F6

Faulty current sensor

J2

Faulty CT1 sensor


Faulty CT2 sensor

<Confirmation of error 2>


Press the SET (BS2) button once to
display "Second digit" of error code.

Faulty discharge pipe thermistor

Faulty Tdi sensor (short)

J3

Faulty Tds1 sensor (short)

Detail
description
on next
page.

Faulty Tds2 sensor (short)


Faulty Tdi sensor (open)
Faulty Tds1 sensor (open)
Faulty Tds2 sensor (open)
Faulty suction pipe thermistor

Faulty Ts1 sensor (short)

J5

Faulty Ts1 sensor (open)


Faulty Ts2 sensor (short)

<Confirmation of error 3>


Press the SET (BS2) button once to
display "error location".

Faulty Ts2 sensor (open)


Faulty heat exchanger thermistor

Faulty Tb sensor (short)

J6

Faulty Tb sensor (open)


Faulty liquid pipe thermistor

Faulty TI sensor (short)

J7

Faulty TI sensor (open)


Faulty subcooling heat exchanger
thermistor

<Confirmation of error 4>


Press the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "error location".

Faulty sensor of high pressure

Faulty Tsh sensor (short)

J9

Faulty Tsh sensor (open)


Faulty Pc sensor (short)

JA

Faulty Pc sensor (open)


Faulty sensor of low pressure

Faulty Pe sensor (short)

JC

Faulty Pe sensor (open)


Instantaneous power failure

NO display on remote controller


(Judge during compressor operation)

(L2)

Inverter radiation fin temperature rising Over heating of inverter radiation fin temperature

L4

DC output overcurrent

Inverter instantaneous overcurrent

L5

IGBT malfunction

L5

Electronic thermal switch 1

L8

Electronic thermal

Electronic thermal switch 2

Press the RETURN (BS3) button


and switches to the initial status of
Monitor mode.

Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)

Stall prevention (Current increasing)

L9

Stall prevention (Faulty start up)

Press the MODE (BS1) button and


returns to Setting mode 1.

Abnormal wave form in startup


Out-of-step
Transmission error between inverter
and outdoor unit

202

Inverter transmission error

LC

Service Diagnosis

Si34-804_C

Troubleshooting by Remote Controller

k: ON

h: OFF

l:Blink

Confirmation of error 1
Confirmation of error 2
Confirmation of error 3
Confirmation of error 4
Error
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P

E6

l
l
l
l
l
l

h
h
h
h
h
h

h
h
h
l
l
l

h
h
l
h
h
l

l
l
l
h
l
h

E7

E9

l
l
l

h
h
h

h
l
h

l
l
l

l
h
h

J3

J5

E1

E3
E4
E5

H7

H9
F3

F6
J2

J6

J7

J9

JA

JC

l
l

h
h

l
l

h
h

h
l

(L2)

L4
L5
L5
L8

L9

LC

Display of contents of
error (first digit)

Display of contents of
error (second digit)

l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l

h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h
l
l
h
h
h
h
l
h
l
h
h
h
h
h
h
h
l
l
l
h
l
h
l
h
l
h
l
h
l
h
l
h
l
h

l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l

h
h
h
h
h
h
h
h
h
h
h
h
h
l
h
h
h
h
h
h
h
h
h
h
l
h
h
l
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h

h
l
h
h
h
h
l
h
l
h
l
h
l
h
h
h
h
h
h
h
h
l
h
l
h
h
l
h
h
h
l
l
h
h
h
h
h
h
h
h
h
h
h

l
l
l
l
l

h
h
h
h
h

h
h
h
h
h

h
h
h
h
h

h
h
h
h
h

l
l
l
l
l

h
h
h
h
h

h
h
l
h
l

l
l
l
l
l
l

h
h
h
h
h
h

h
h
h
h
h
h

h
h
h
h
h
h

h
l
h
h
h
h

l
l
l
l
l
l

l
h
h
h
l
h

h
h
h
l
h
l

Display 1 of
error in detail

l
l

Display 2 of
error in detail
1

Service Diagnosis

l
l

h
h
l
l

h
l
h
l

Master
Slave1
Slave2
System

203

Troubleshooting by Remote Controller

Si34-804_C

<Monitor mode>
Contents of error

To enter the monitor mode, press the


MODE (BS1) button when in
Setting mode 1.

* Refer to P.175 for Monitor mode.

Error code

Inverter over-ripple protection

Imbalance of inverter power supply


voltage

P1

Faulty temperature sensor of inverter


radiation fin

Faulty thermistor of radiation fin

P4

Incorrect combination of inverter and


fan driver

Incorrect combination of inverter

PJ

Incorrect combination of fan driver 1


Incorrect combination of fan driver 2

<Selection of setting item>


Press the SET (BS2) button and set
the LED display to a setting item.

Refrigerant shortage

Refrigerant shortage alarm

U0

Reverse phase/open phase

Reverse phase error

U1

Abnormal power supply voltage

Insufficient Inverter voltage

U2

Inverter open phase (phase T)


Charging error of capacitor in inverter
main circuit

* Refer to P.175 for Monitor mode.

No implementation of check operation

<Confirmation of error 1>


Press the RETURN (BS3) button
once to display "First digit" of error
code.

U3

Transmission error between indoor


unit

I/O transmission error

Transmission error between outdoor


units, transmission error between
thermal storage units, duplication of IC
address

Sequential startup ADP alarm

U7

Sequential startup ADP malfunction

U7

U4

I/O transmission error

Malfunction of transmission between


multi units (Multi 1)
Malfunction of transmission between
multi units (Multi 2)
Abnormal multi horsepower setting

<Confirmation of error 2>


Press the SET (BS2) button once to
display "Second digit" of error code.

Abnormal multi address setting


Excessive multi connections

Detail
description
on next
page.

Multi system malfunction


Transmission error of other system

Erroneous field setting

Indoor unit system abnormal in other


system or other indoor unit system
abnormal in own system

U9

System transmission malfunction

UA

Over connection malfunction of indoor units


Malfunction of field setting

<Confirmation of error 3>

Refrigerant abnormal
Multi-ID abnormal

Press the SET (BS2) button once to


display "error location".

Alarm of TSS field setting

UA

Alarm of CT address setting


Faulty system

Wiring error (Auto-address error)

UH

Conflict in wiring and piping, no setting


for system

Conflict in wiring and piping

UF

<Confirmation of error 4>


Press the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "error location".

Press the RETURN (BS3) button


and switches to the initial status of
Monitor mode.

Press the MODE (BS1) button and


returns to Setting mode 1.

204

Service Diagnosis

Si34-804_C

Troubleshooting by Remote Controller

k: ON

h: OFF

l:Blink

Confirmation of error 1
Confirmation of error 2
Confirmation of error 3
Confirmation of error 4
Error
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1
l
l h h h l
h h h l l
h h h h l
h h
P4

PJ

h
h
h

h
h
h

h
h
l

h
l
h

h
h
h
h
h
h
h

h
h
h
h
h
h
h

h
h
h
h
h
h
h

h
h
h
h
h
h
h

l
l
l
l
l
l
l

h
h
l
h
h
h
h

h
l
h
h
h
h
l

U2

l
l
l

l
l
l
l
l
l
l

U3

U4

U7

l
l
l
l
l
l
l

h
h
h
h
h
h
h

h
h
h
h
h
h
h

h
h
h
h
h
h
h

h
h
h
h
h
h
h

l
l
l
l
l
l
l

h
h
h
h
h
h
l

h
l
h
l
l
h
h

l
l
l
l
l
l
l

l
l
l
l
l
l
l

l
l
l
l
l

h
h
h
h
h

h
h
h
h
h

h
h
h
h
h

l
l
l
l
h

l
l
l
l
l

h
h
l
l
h

h
l
h
l
h

l
l
l
l
l

l
l
l
l
l

l
l
l
l
l
l
l
l
l

h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h

h
h
h
h
h
h
h
h
h

h
h
h
l
l
l
l
h
h

l
l
l
l
l
l
l
l
l

h
h
l
h
h
l
l
h
h

h
l
h
h
l
h
l
h
h

l
l
l
l
l
l
l
l
l

l
l
l
l
l
l
l
l
l

U0

U1

U7

U9

UA

l
l

l
l

h
l

l
l

l
l

UA
UH
UF

Display of contents of
error (first digit)

Display of contents of
error (second digit)

Display 1 of
error in detail

Display 2 of
error in detail
1

Service Diagnosis

h
h
l
l

h
l
h
l

Master
Slave1
Slave2
System

205

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3. Troubleshooting by Indication on the Remote


Controller
3.1

External Protection Device Abnormality

Remote
Controller
Display

A0

Applicable
Models

All models of indoor unit

Method of Error
Detection

Detect open or short circuit between external input terminals in indoor unit.

Error Decision
Conditions

When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal"

Supposed
Causes

Actuation of external protection device


Improper field setting
Defective indoor unit PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
block.

YES

Actuation of external protection


device.

NO
Check the setting state of the
ON/OFF input from outside by
remote controller.

ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO

206

YES

Change the second code No. to


"01" or "02" .

Replace the indoor unit PCB.

Service Diagnosis

Si34-804_C

3.2

Troubleshooting by Indication on the Remote Controller

PCB Abnormality

Remote
Controller
Display

A1

Applicable
Models

All models of indoor unit

Method of Error
Detection

Check data from EPROM.

Error Decision
Conditions

When data could not be correctly received from the EPROM


EPROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.

Supposed
Causes

Defective indoor unit PCB


External factor (noise etc.)

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Turn power supply OFF, then


power ON again.

Does
the system return
to normal?
NO

YES

The indoor unit PCB is


normal.
External factor other than
error (for example, noise
etc.).
Replace the indoor unit
PCB.

Service Diagnosis

207

Troubleshooting by Indication on the Remote Controller

3.3

Si34-804_C

Drain Level Control System (S1L) Abnormality

Remote
Controller
Display

A3

Applicable
Models

FXCQ, FXZQ, FXFQ, FXKQ, FXDQ, FXMQ, FXUQ, FXHQ (Option), FXMQ200 250M
(Option), FXAQ (Option), FXMQ-MF (Option)

Method of Error
Detection

By float switch OFF detection

Error Decision
Conditions

When rise of water level is not a condition and the float switch goes OFF

Supposed
Causes

208

220~240V power supply is not provided


Defective float switch or short circuit connector
Defective drain pump
Drain clogging, upward slope, etc.
Defective indoor unit PCB
Loose connection of connector

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is power supply
220~240 V provided?

NO
Provide 220~240V power
supply.

YES
The float
switch is connected to
X8A or X15A of the indoor
unit PCB.

NO

YES
The float
switch contact is
forming a short circuit.
(continuity check
with X8A or X15A
disconnected)

YES

Connect either a short circuit


connector or float switch and
turn ON again.

Becomes
normal when X8A
or X15A of the indoor unit
PCB is short
circuited.

NO
Defective indoor unit PCB.

YES

NO

The float switch


functions normally.
YES

YES
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoor unit
PCB.

NO

YES

NO

Water builds up
in the drain pan.

A short
circuit connector is
connected to X8A
or X15A.

Loose connection of connector.


NO
Replace the float switch.
Modify the float switch's
connection and turn ON again.

NO
Connect the drain pump and
turn ON again.

YES
The drain
pump works when
the power supply is reset
for the indoor
unit.

YES
Check the drain piping for
clogging or upward slope, etc.

NO
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5 minutes of resetting
the power
supply).
YES

Service Diagnosis

NO
Replace the indoor unit PCB.

Replace the drain pump or


check for dirt, etc.

209

Troubleshooting by Indication on the Remote Controller

3.4

Si34-804_C

Fan Motor (M1F) Lock, Overload

Remote
Controller
Display

A6

Applicable
Models

All models of indoor unit (except FXMQ-P)

Method of Error
Detection

Detection by failure of signal for detecting number of turns to come from the fan motor

Error Decision
Conditions

When number of turns can not be detected even when output voltage to the fan is maximum

Supposed
Causes

Fan motor lock


Disconnected or defective wiring between fan motor and PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit
PCB?

NO

Connect the wiring and turn ON


again.

YES
Wiring
between the
indoor unit PCB and
fan motor is
disconnected.

YES

Fix the wiring and turn ON again.

NO
Does the fan motor run?
NO

210

YES

Replace the indoor unit PCB.


Replace the fan motor.

Service Diagnosis

Si34-804_C

Remote
Controller
Display

Troubleshooting by Indication on the Remote Controller

A6

Applicable
Models

FXMQ50~140P

Method of Error
Detection

Error from the current flow on the fan PCB


Error from the RPM of the fan motor in operation
Error from the position signal of the fan motor
Error from the current flow on the fan PCB when the fan motor starting operation

Error Decision
Conditions

An overcurrent flows.
The RPM is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.

Supposed
Causes

Service Diagnosis

The clogging of a foreign matter


The disconnection of the fan motor connectors (X1A and X2A)
The disconnection of the connectors between the indoor unit PCB (A1P) and fan PCB (A2P)
Defective fan PCB (A2P)
Defective fan motor

211

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.

Caution

Turn OFF the power and wait


for 10 minutes.

There is a
foreign matter around
the fan.

YES

Remove the foreign matter.

NO
The fan
motor connectors (X1A
and X2A) of the fan PCB (A2P) are
disconnected.

YES

Connect correctly.

NO

The connectors
between the indoor unit
PCB (A1P) and the fan
PCB (A2P) are
disconnected.

YES

Connect correctly.

NO

The fuse
(F3U, white) on the fan
PCB (A2P) has
no continuity.

NO

Replace the fan


PCB (A2P).

YES

The fan can be


moved lightly by hand after
the fan motor connector of the
fan PCB (A2P) is
removed.

NO

Replace the fan motor.

YES

The resistance
between the power wire
terminals of the fan motor and
motor frame (metal part) is
1 M or below.

YES

Replace the fan motor.

NO
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases (*1).
A

212

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

The resistors among


U, V, and W are unbalanced or
short circuited.

YES

Replace the fan motor.

NO
Remove the signal connector
from the fan motor and check
the resistance (*2).

Between VCC and GND


terminals, and between GND
and HW, HV, or HU terminals
are short circuited.

YES

Replace the fan motor.

NO
Turn ON the power.

The HAP
lamp of the indoor unit
PCB (A1P) blinks and the HAP
lamp of the fan PCB
(A2P) is OFF.

YES

Replace the fan PCB


(A2P).

NO
Replace the fan motor.

Note:

*1. Measurement of power wire connector.


Remove the X1A connector from the fan PCB (A2P) and measure the resistance between
the U and V, V and W, and W and U phases of the motor connector (with five conductors)
and check that each phase are balanced (within a permissible dispersion range of 20%).
*2. Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between GND and VCC, HW, HV,
or HU terminals of the motor connector (with five conductors).
Connector power wire use (X1A)
5 Red

4
3 White

2
1 Black

Service Diagnosis

Connector signal wire use (X2A)


5 Gray

GND

4 Pink

Vcc

3 Orange

Hw

2 Blue

HV

1 Yellow

HU

213

Troubleshooting by Indication on the Remote Controller

3.5

Si34-804_C

Swing Flap Motor (M1S) Abnormality

Remote
Controller
Display

A7

Applicable
Models

FXCQ, FXHQ, FXKQ, FXUQ

Method of Error
Detection

Utilize ON/OFF of the limit switch when the motor turns.

Error Decision
Conditions

When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing
flap motor is energized for a specified amount of time (about 30 seconds).

Supposed
Causes

214

Defective swing motor


Defective connection cable (power supply and limit switch)
Defective airflow direction adjusting flap-cam
Defective indoor unit PCB

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is power supply
220~240 V provided?

NO
Provide 220~240 V power
supply.

YES
Indoor unit
is a model equipped
with a swing flap
function.

NO

Replace the indoor unit PCB.

YES
The swing
motor works when
the power supply is turned
OFF and then back
ON.

YES

NO

The connector
is connected to X9A or
X14A of the indoor
unit PCB.

NO

Connect the connector to X9A


or X14A and turn ON again.

YES
The limit switch
functions normally.

NO

Replace the swing motor.

YES

After
turning
the swing flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PCB is 220 VAC
(50 Hz) when turned ON
again (within 30
seconds of
turning on
again).

The connecting
cable is short circuited
or disconnected.

YES

Replace the limit switch


connecting cable.

NO
NO

Replace the indoor unit PCB.

YES
The connecting cable
has no continuity.

YES

Replace the power supply


connecting cable.

NO
When
the airflow
direction flap-cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
ON again.
YES

Service Diagnosis

NO

Replace the swing motor.

Take the flap-cam mechanism


apart, reassemble and turn ON
again.

215

Troubleshooting by Indication on the Remote Controller

3.6

Si34-804_C

Power Supply Voltage Abnormality

Remote
Controller
Display

A8

Applicable
Models

FXMQ20~140P

Method of Error
Detection

Detect error checking the input voltage of fan motor

Error Decision
Conditions

When the input voltage of fan motor is 150 V or less, or 386V or more

Supposed
Causes

Defective power supply voltage.


Connection defect on signal line.
Defective wiring.
Instantaneous blackout, others.

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Check the condition of


the power supply.
 Check if power supply
voltage is 220 V - 240 V
10%.
 Check if there is power
open phase or defective
wiring.
 Check if power supply
voltage unbalance is
within 6 V.

There
are problems on
the condition of power
suplly described
above.

YES

Correct any fault.

NO
"A8"
error recurs.

YES

Check and correct each wiring.

NO
It is possible to have external
factor, such as brownout and
instantaneous blackout.

216

Service Diagnosis

Si34-804_C

3.7

Troubleshooting by Indication on the Remote Controller

Electronic Expansion Valve Coil (Y1E) Abnormality

Remote
Controller
Display

A9

Applicable
Models

All models of indoor unit

Method of Error
Detection

Use a micro-computer to check the electronic expansion valve for coil conditions.

Error Decision
Conditions

When the pin input of the electronic expansion valve is not normal while in the initialization of
the micro-computer

Supposed
Causes

Defective electronic expansion valve coil


Defective indoor unit PCB
Defective connecting cable

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

The
electronic
expansion valve coil is
connected to X7A of the
indoor unit
PCB.
YES
Normal
when coil check
(1) of the electronic
expansion valve coil
is checked.

NO

NO

After connecting, turn the power


supply OFF and then back ON.

Replace the electronic expansion


valve coil.

YES
The connecting
cable is short circuited or
disconnected.
NO

Service Diagnosis

YES

Replace the connecting cable.


If you turn the power supply OFF
and turn ON again, and it still does
not help, replace the indoor unit
PCB.

217

Troubleshooting by Indication on the Remote Controller

Note:

Si34-804_C

1: Coil check method for the electronic expansion valve coil

Disconnect the electronic expansion valve from the PCB and check the continuity between the
connector pins.
(Normal)
Pin No.
1. White

2. Yellow

3. Orange

4. Blue

5. Red

1. White

2. Yellow

3. Orange
{
Approx.
300

4. Blue

5. Red
{
Approx.
150

6. Brown

{
Approx.
300

{
Approx.
150

{
Approx.
150

{
Approx.
150

6. Brown

{: Continuity
: No continuity

218

Service Diagnosis

Si34-804_C

3.8

Troubleshooting by Indication on the Remote Controller

Drain Level above Limit

Remote
Controller
Display

AF

Applicable
Models

FXCQ, FXZQ, FXFQ, FXKQ, FXMQ, FXDQ, FXMQ-MF, FXUQ

Method of Error
Detection

Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.

Error Decision
Conditions

When the float switch changes from ON to OFF while the compressor is in non-operation

Supposed
Causes

Humidifier unit (optional accessory) leaking


Defective drain pipe (upward slope, etc.)
Defective indoor unit PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Field drain
piping has a defect such as
upward sloping.

YES

Modify the drain piping.

NO
A humidifier
unit (optional accessory)
is installed on the
indoor unit.

YES

Check if the humidifier unit is


leaking.

NO
Defective indoor unit PCB.

Service Diagnosis

219

Troubleshooting by Indication on the Remote Controller

3.9

Si34-804_C

Capacity Determination Device Abnormality

Remote
controller display

AJ

Applicable
Models

All models of indoor unit

Method of Error
Detection

Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.

Error Decision
Conditions

Operation and:
When the capacity code is not saved to the PCB, and the capacity setting adaptor is not
connected.
When a capacity that does not exist for that unit is set.

Supposed
Causes

The capacity setting adaptor is not mounted.


Defective indoor unit PCB

Troubleshooting

Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

The indoor
unit PCB was replaced
with a spare
PCB.

NO
Replace the indoor unit PCB.

YES
The capacity
setting adaptor need to
be mounted when
replacing the
PCB.
YES

220

NO

Replace the indoor unit PCB.

Mount a capacity setting adaptor.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.10 Transmission Error (Between Indoor unit PCB and Fan


PCB)
Remote
Controller
Display

C1

Applicable
Models

FXMQ20~140P

Method of Error
Detection

Check the condition of transmission between indoor unit PCB (A1P) and PCB for fan (A2P)
using micro-computer.

Error Decision
Conditions

When normal transmission is not conducted for certain duration

Supposed
Causes

Service Diagnosis

Connection defective connecter between indoor unit PCB (A1P) and PCB for fan (A2P)
Defective indoor unit PCB (A1P)
Defective PCB for fan (A2P)
External factor, such as instantaneous blackout

221

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the
connector between
indoor unit PCB (A1P) and
PCB for fan (A2P) accurately
connected? (*1)

NO

Connect the connector accurately.

YES
Confirm the condition
of transmission on
indoor unit PCB using
field setting mode.
(*2)

Under above
field setting mode,
setting position
is "01".

NO

Replace the indoor unit PCB


(A1P).

YES
Connect the
connecter X70A and
turn ON the power
again.

"C1"
Error recurs.

YES

Replace the PCB for fan (A2P).

NO
Connect it and operate. (It is
possible to have a cause, such
as instantaneous blackout)

Note:

1. Pull out and insert the connecter once and check it is absolutely connected.
2. Method to check transmission part of indoor unit PCB.

 Turn off the power and remove the connecter X70A of indoor unit PCB (A1P).
 Short circuit X70A.
 After turning on the power, check below numbers under local setting remote control.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No. 41)

Determination

01: Normal
Other than 01: Transmission defect on indoor unit PCB

After confirmation, turn off the power, take off the short circuit and connect X70A back to

original condition.

222

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.11 Thermistor Abnormality

C4, C5, C9

Remote
Controller
Display
Applicable
Models

All models of indoor unit

Method of Error
Detection

The error is detected by temperature detected by thermistor.

Error Decision
Conditions

When the thermistor becomes disconnected or short circuited while the unit is running.

Supposed
Causes

Defective thermistor
Defective indoor unit PCB
Defective connector connection
Broken or disconnected wire

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Remove the thermistor from


the indoor unit PCB, and then
insert it again.

Is the
thermistor normal?

YES

Normal (The error is caused by


faulty contact.)

NO
Remove the thermistor from
the indoor unit PCB, and then
make resistance
measurement of the thermistor
using a multiple meter.

5 k to 90 k

NO

Replace the thermistor.

YES
Replace the indoor unit PCB.

Note:

1 Error code and thermistor


Error Code

C4
C5
C9

Thermistor
Heat exchanger liquid pipe thermistor

Symbol
R2T

Heat exchanger gas pipe thermistor

R3T

Suction air thermistor

R1T

Refer to Thermistor Resistance / Temperature Characteristics table on P.347.

Service Diagnosis

223

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.12 Combination Error (Between Indoor unit PCB and Fan


PCB)
Remote
Controller
Display

C6

Applicable
Models

FXMQ40~140P

Method of Error
Detection

Conduct open line detection with PCB for fan (A2P) using indoor unit PCB (A1P).

Error Decision
Conditions

When the communication data of PCB for fan (A2P) is determined as incorrect

Supposed
Causes

Defective PCB for fan (A2P)


Defective connection of capacity setting adaptor
Setting mistake onsite

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the
type of PCB
for fan (A2P)
correct?

NO

Replace it with correct PCB for fan


(A2P).

YES

NO

Was
indoor unit
PCB (A1P) replaced
with a spare
PCB?
YES
Was
correct capacity
setting adaptor installed when
replacing it with a spare
PCB?

NO

Install correct capacity setting


adaptor.

YES
After establishing transmission
for indoor and outdoor,
diagnose the operation again.

224

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.13 Humidity Sensor System Abnormality

CC

Remote
Controller
Display
Applicable
Models

FXFQ

Method of Error
Detection

Even if an error occurs, operation still continues.


Error is detected according to the moisture (output voltage) detected by the moisture sensor.

Error Decision
Conditions

When the moisture sensor is disconnected or short circuited

Supposed
Causes

Defective sensor
Disconnection

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Remove the humidity sensor


from the indoor unit PCB
and insert it again.

Does it
function normally?

YES

It is normal.
(Poor connector contact)

NO
Delete the error code record
from the remote controller.
(*1)

Is "CC"
displayed on
the remote
controller? (*2)

YES

Replace the humidity sensor


PCB assy (A2P).
*3

NO
It is believed that external factors
(noise or else) other than failure
caused the error.

Note:

Service Diagnosis

*1: To delete the record, the ON/OFF button of the remote controller must be pressed and held
for 5 seconds in the check mode.
*2: To display the code, the Inspection/Test Operation button of the remote controller must be
pressed and held in the normal mode.
*3: If "CC" is displayed even after replacing the humidity sensor PCB assy (A2P) and taking the
steps *1 and 2, replace the indoor unit PCB assy (A1P).

225

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.14 Room Temperature Thermistor in Remote Controller


Abnormality

CJ

Remote
Controller
Display
Applicable
Models

All models of indoor unit

Method of Error
Detection

Error is detected by temperature detected by room temperature thermistor in remote controller.


(Note:)

Error Decision
Conditions

When the room temperature thermistor in remote controller becomes disconnected or short
circuited while the unit is running

Supposed
Causes

Defective room temperature thermistor in remote controller


Defective remote controller PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Clear the error code history.


(While in inspection mode,
press and hold the ON/OFF
button for a period of 4
seconds or more.)
Is "CJ"
displayed on the remote
controller?

YES

Replace the remote


controller.

NO
External factor other than
equipment error.
(for example, noise etc.)

Note:

In case of defective room temperature thermistor in remote controller, unit is still operable by
suction air thermistor in the indoor unit.
Refer to Thermistor Resistance / Temperature Characteristics table on P.347.

226

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.15 PCB Abnormality


Remote
Controller
Display

E1

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Check data from EPROM

Error Decision
Conditions

When data could not be correctly received from the EPROM


EPROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned OFF.

Supposed
Causes

Defective outdoor unit PCB (A1P)


Disconnection of the indoor/outdoor relay wires

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Turn OFF the power once


and turn ON again.

Return to normal?

YES

External factor other than


error (for example, noise
etc.).

NO

Check
if indoor / outdoor
relay wires of outdoor
main PCB is
disconnected.

YES

Connect the indoor/ outdoor


relay wires correctly.

NO

Replace the outdoor main


PCB (A1P).

Service Diagnosis

227

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.16 Actuation of High Pressure Switch


Remote
Controller
Display

E3

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

The error is detected by the protection device circuit that detects continuity at high pressure
switch.

Error Decision
Conditions

When the protector circuit is partially opened


(For reference) Operating pressure for the high pressure switch
Operating pressure: 4.0 MPa
Reset pressure:
3.0 MPa

Supposed
Causes

228

Actuation of outside unit high pressure switch


Defective high pressure switch
Defective main PCB
Momentary power failure
Defective high pressure sensor

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Check the following items:


 Is the stop valve open?
 Is the connector for high pressure switch
properly connected to the main PCB?
 Does the high pressure switch have
continuity?

Are the
3 points above
OK?

NO

Rectify the defective points, if any.

YES
Mount a pressure gauge on the high pressure
service port.
Reset the operation using the remote controller, and
then restart the operation.

Does the
YES
emergency stop due to
error (E3) recur?

NO

Replace the high pressure


switch.

YES

NO

Are the
characteristics of
high pressure sensor
normal?
(1)

Is the high
pressure switch
operating value
(4.0 MPa)
normal?

NO

Replace the high pressure sensor.

YES
SERVICE CHECKER
Connect the service checker to compare the "high pressure" value and the
actual measurement value by pressure sensor (Refer to 2) by using the
service checker.

Are the
"high pressure"
value and the actual
measurement value by
pressure sensor
the same?

NO

Replace the main PCB.

YES
The high pressure sensor is normal and the pressure detected with the
main PCB is also normal.
The high pressure or field piping pressure has really become high.
CHECK 3 : Remove the causes by which the high pressure or field piping
pressure has become high.

Service Diagnosis

229

Troubleshooting by Indication on the Remote Controller

Note:

Si34-804_C

1 Make a comparison between the voltage of the pressure sensor and that read by the

pressure gauge. (As to the voltage of the pressure sensor, make measurement of voltage at
the connector and then convert it pressure.)
2 Make measurement of voltage of the pressure sensor.

(4)

Red

(3)

Black

(2)
Micro-computer
A/D input

(1)

White

High pressure sensor

+5V Connector for high


pressure sensor (red)

Measure the voltage (DC) between


these 2 points.

CHECK 3 Refer to P.294.

230

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.17 Actuation of Low Pressure Sensor


Remote
Controller
Display

E4

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Judge the pressure detected by a low pressure sensor with the outside unit main PCB.

Error Decision
Conditions

When low pressure drops while the compressor is in operation


Operation pressure: 0.07 MPa

Supposed
Causes

Service Diagnosis

Abnormal drop of low pressure


Defective low pressure sensor
Defective outside unit main PCB
The stop valve is not opened.

231

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the stop
valve opened?

NO

Open the stop valve.

YES
 Mount a pressure gauge in the low pressure
service port.
 Reset the operation using the remote controller,
and then restart the operation.

Are the
characteristics
of the low pressure
sensor normal?
(1)

NO

Replace the low pressure sensor.

YES
SERVICE CHECKER
Connect the service checker to compare the "low pressure" value and the
actual measurement value by pressure sensor (Refer to 2) by using the
service checker.

Are the
"low pressure"
value and the actual
measurement valve by
pressure sensor
the same?

NO

Replace the main PCB.

YES
The low pressure sensor is normal, and the pressure detected with the
PCB is also normal.
The low pressure has really become low.

CHECK 4 : Remove the causes by which the low pressure has become low.

Note:

1: Make a comparison between the voltage of the pressure sensor and that read by the

pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it pressure,)
2: Make measurement of voltage of the pressure sensor.

Micro-computer
A/D input

(4)

Red

(3)

Black

(2)

White

(1)

Low pressure sensor

+5V Connector for low


pressure sensor (Blue)

Measure the voltage (DC) between


these 2 points.

CHECK 4 Refer to P.295.


232

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.18 Inverter Compressor Motor Lock


Remote
Controller
Display

E5

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Inverter PCB takes the position signal from UVW line connected between the inverter and
compressor, and the error is detected when any abnormality is observed in the phase-current
waveform.

Error Decision
Conditions

This error will be output when the inverter compressor motor does not start up even in forced
startup mode.

Supposed
Causes

Service Diagnosis

Inverter compressor lock


High differential pressure (0.5 MPa or more)
Incorrect UVW wiring
Defective inverter PCB
Stop valve is not opened.

233

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the stop valve open?


Power OFF

NO

Onsite causes.
Open the stop valve.

YES
Check the compressor cable
for disconnection and flaws.

The compressor cable


has a defect.

YES

Replace the cable, and


then securely connect
the connectors.

NO
Are wire
connections made to
phases U, V, and W in the
proper order and
manner?

NO

Make wire connections


without a mistake.
W

YES
Are wire
connections properly
made (according to the
Wiring Diagram)?

U
V

NO
Are the wire connections
mixed up with those for
non-inverter compressor?

Make wire connections


without a mistake.

YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.

The insulation
resistance is low (i.e., not
more than
100 k.)

YES

Replace the
compressor.

NO
Check the compressor motor
coil for any broken wire.

Some phase has a


broken wire.

YES

NO
A

234

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Restart the
compressor, and then
check whether or not
the error
recurs.
Power ON

NO

YES
Has the
compressor started
up at high differential
pressure (not less
than 0.5 MPa)?

YES

End of work
Defective pressure
equalization or else
may have occurred.
Check the refrigerant
system.
Defective pressure
equalization:
Check the refrigerant
system.

NO
CHECK 8
Is the power
transistor normal?

NO

Replace the outdoor unit


PCB .

YES
Does the
error recur when restart
operation?

NO

Continue the operation.


(Instantaneous power
failure, etc.)

YES
Replace the outdoor unit PCB.

Does the
error recur when restart
operation?
YES

NO

Continue the operation.

Replace the
compressor.

CHECK 8 Refer to P.298.

Service Diagnosis

235

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.19 STD Compressor Motor Overcurrent/Lock

E6

Remote
Controller
Display
Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Detects the overcurrent with current sensor (CT).

Error Decision
Conditions

Error is decided when the detected current value exceeds 28.8 A for 2 seconds.

Supposed
Causes

Stop valve is not opened


Obstacles at the air outlet
Improper power voltage
Defective magnetic switch
Defective compressor
Defective current sensor (A6P, A7P)

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the stop valve open?


YES
Obstacle
exists around the air
outlet.

NO

YES

Open the stop valve.

Remove the obstacle.

NO
Is the power
supply voltage
normal?
YES
Is the
magnetic switch
(K2M, K3M)
normal?
YES

NO

NO

Correct the power voltage.

Replace the magnetic


switch.

Check the wiring from power supply ~ current sensor (A6P, A7P) ~
MgS (K2M, K3M) ~ compressor
Is
above wiring
correct?

NO

Correct the wiring.

YES
Is
the current sensor
correct? 1
YES

NO

Replace the corresponding


current sensor
(A6P or A7P).
Replace the compressor.

Note:

236

1 Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0 A during STD compressor stop.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.20 Outdoor Unit Fan Motor Abnormality


Remote
Controller
Display

E7

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Detect an error based on the current value in the inverter PCB (as for motor 2, current value in
the fan PCB).
Detect an error for the fan motor circuit based on the number of rotation detected by hole IC
during the fan motor operation.

Error Decision
Conditions

Overcurrent is detected for inverter PCB (A2P) or fan inverter PCB (A3P)

(System down is caused by 4 times of detection.)


In the condition of fan motor rotation, the number of rotation is below the fixed number for

more than 6 seconds. (System down is caused by 4 times of detection.)


Supposed
Causes

Service Diagnosis

Failure of fan motor


Defect or connection error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes

237

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Check in the monitor mode


12HP ~ 18HP class models have 2 fans.
Check electric motor (electric motor 1 or 2) corresponding to
error code E7 in the monitor mode of outdoor unit PCB.

Turn OFF the power supply and wait for 10 minutes.

Check if
any foreign matters
around the fan.

YES

Remove the foreign matters.

NO
Check the connection of the connectors
Fan motor 1: X1A of PCB
Fan motor 2: X1A of PCB

Check
if any connector is
disconnected.

YES

Insert the connector.

NO
Check the color of relay connectors
Fan motor 1: Both power supply wire and signal wire are all white.
Fan motor 2: Both power supply wire and signal wire are red
in the PCB side and white in the motor side.

Relay
connectors have any
connection error.

YES

Correct the connection of


the relay connectors.

NO
5~10HP

238

12~18HP

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
A

No continuity
of fuse (F1U) on fan PCB
(A4P or A8P).

YES

Replace the PCB (A4P or A8P).

NO

Unable to
rotate the fan manually
with ease when removing
the connector of the
fan motor.

YES

Replace the corresponding fan


motor.

NO

Resistance
value between the
power supply wire
terminal of fan motor
and the motor frame
(metal) is 1M
or less.

YES

Replace the corresponding fan


motor.

NO
CHECK 1
Check fan motor connector
(power supply wire)

The
resistance
value between
UVW phases of fan
motor is out of balance,
or short circuit
between UVW
phases.

YES

Replace the corresponding fan


motor.

NO
CHECK 2
Check fan motor connector
(signal wire)

The signal
wire short circuits
between Vcc and GND
and between UVW
and GND.

YES

Replace the corresponding fan


motor.

NO

Replace the PCB (A1P).

CHECK 1 Refer to P.293.


CHECK 2 Refer to P.293.

Service Diagnosis

239

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.21 Electronic Expansion Valve Coil (Y1E, Y2E) Abnormality


Remote
Controller
Display

E9

Applicable
Models

RXQ5PA~54PAY1

Method of Error
Detection

Check disconnection of connector.


To be detected based on continuity existence of electronic expansion valve coil.

Error Decision
Conditions

No current is detected in the common (COM [+]) when the power is ON.

Supposed
Causes

Defective electronic expansion valve coil


Defective outdoor unit PCB (A1P)
Disconnection of connectors for electronic expansion valve (Y1E) or (Y2E).

240

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Turn power supply OFF, and


turn power supply ON again.

Return to normal?

YES

NO

External factor other than error


(for example, noise etc.).

Check the electronic expansion valve corresponding to the eror code E9


in the monitor mode.
When Confirmation of error 4 shows as follows:
Electronic expansion valve for main use (Y1E)
When Confirmation of error 4 shows as follows:
Electronic expansion valve for subcooling (Y3E)
Explanation of

Master unit
Slave unit 1
Slave unit 2
System

The
connector of
outdoor unit PCB
(A1P) for electronic
expansion valve is
connected.

NO

Ensure correct connection.

NO

Replace the connecting cable.

YES
The coil
resistance of
electronic expansion
valve is normal.
(1)
YES

Replace the outdoor unit PCB


(A1P).
Make measurement of resistance between the connector pins, and then make sure the
resistance falls in the range of 40 to 50.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5

Measuring points Judgement criteria


1-6
2-6
40~50
3-6
4-6

COM[+] (Gray) 6

Service Diagnosis

241

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.22 Discharge Pipe Temperature Abnormality


Remote
Controller
Display

F3

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Abnormality is detected according to the temperature detected by the discharge pipe thermistor.

Error Decision
Conditions

When the discharge pipe temperature rises to an abnormally high level (135 C or more)
When the discharge pipe temperature rises suddenly (120 C or more for 10 successive
minutes)

Supposed
Causes

Faulty discharge pipe temperature


Faulty discharge pipe thermistor
Faulty outdoor unit PCB

242

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Connect the service


checker.
Press reset and start
operation again.

Check if
discharge pipe
thermistor property is
normal.
(1)

NO

Replace the discharge pipe


thermistor.

YES

Service Checker
Connect the service checker to compare the temperature of
discharge pipe by using service checker with actual
measurement value of discharge pipe thermistor (1).

Check if
temperature of
discharge pipe by
using service checker is
the same with actual
measurement value
of discharge pipe
thermistor.

NO

Replace the main PCB (A1P).

YES

Discharge pipe thermistor is normal and the temperature


detection of the main PCB is also normal.
Actually the temperature of discharge pipe is high.
CHECK 9 Remove the factor of overheat operation.

Note:

1 Compare the resistance value of discharge pipe thermistor and the value based on the

surface thermometer.
(Refer to Thermistor Resistance / Temperature Characteristics table on P.347.
CHECK 9 Refer to P.300.

Service Diagnosis

243

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.23 Refrigerant Overcharged


Remote
Controller
Display

F6

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Excessive charging of refrigerant is detected by using the outdoor air temperature, heat
exchanger deicer temperature and liquid pipe temperature during a check operation.

Error Decision
Conditions

When the amount of refrigerant, which is calculated by using the outdoor air temperature, heat
exchanger deicer temperature and liquid pipe temperature during a check operation, exceeds
the standard.

Supposed
Causes

Refrigerant overcharge
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Disconnection of liquid pipe thermistor

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Check the mounting condition of


the temperature sensors of the
outdoor air thermistor, heat
exchanger deicer thermistor and
liquid pipe thermistor in the piping.

Are the
above thermistor
installed on pipes
correctly?

NO

Install the thermistor correctly.

YES
Remove the outdoor air thermistor,
heat exchanger deicer thermistor
and the liquid pipe thermistor from
the outdoor unit PCB and measure
resistance with a tester.

Is the
characteristic of the
above thermistor
normal?

YES

NO

Replace the thermistor.

Rectify the overcharge of the


refrigerant.

Refer to Thermistor Resistance / Temperature Characteristics table on P.347.

244

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.24 Outdoor Fan Motor Signal Abnormality

H7

Remote
Controller
Display
Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Detection of abnormal signal from fan motor

Error Decision
Conditions

In case of detection of abnormal signal at starting fan motor

Supposed
Causes

Abnormal fan motor signal (defective circuit)


Broken, short circuited or disconnection connector of fan motor connection cable
Defective fan inverter PCB

Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.

Caution
Turn power OFF.

Is the fan
motor connector
X2A connected to PCB
for fan inverter
correctly?

NO

Connect correctly.

YES
Check the connector of fan
motor. (1)
The
resistance of
fan motor lead wire
connector pins between
Vcc-UVW and
GND-UVW
balanced?

NO

Replace the fan motor.

YES

Note:

Replace the fan inverter PCB.

1: Disconnect connector (X2A) and measure the following resistance.


X2A

Service Diagnosis

5 Gray

GND

4 Pink

Vcc

3 Orange

2 Blue

1 Yellow

Measure the
resistance
between VccUVW and
GND-UVW.

245

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.25 Thermistor Abnormality

H9, J3, J5, J6, J7, J8

Remote
Controller
Display
Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected from the temperature detected by the thermistor.

Error Decision
Conditions

When the thermistor has short circuit or open circuit

Supposed
Causes

Defective thermistor
Defective outdoor unit PCB
Defective thermistor connection

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Connector is
connected to outdoor
unit PCB.

NO

Connect the connector and turn


ON again.

YES
Resistance
is normal when
measured after
disconnecting the thermistor
from the outdoor
unit PCB.
(1.8 k to
800 k)

NO

Replace the thermistor

YES

Replace the outdoor unit PCB.

Refer to Thermistor Resistance / Temperature Characteristics table on P.347.

Note:

1: Error code and thermistor


Error
code.

246

Symbol
Thermistor

RXQ5PA

RXQ8PA

RXQ1012PA

RXQ1418PA

PCB

H9
J3
J5

Outdoor air thermistor

R1T

R1T

R1T

R1T

A1P

Discharge pipe thermistor

R3T

R3T

R31-32T

R31-33T

A1P

Suction pipe thermistor

R2T

R2T, R7T R2T, R7T R2T, R7T

A1P

J6

Outdoor unit heat exchanger


thermistor

R4T

R4T

R4T

R4T

A1P

J7

Liquid pipe thermistor

R5T

R6T

R6T

R6T

A1P

J9

Subcooling heat exchanger gas


pipe thermistor

R5T

R5T

R5T

A1P

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.26 Current Sensor Abnormality


Remote
Controller
Display

J2

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected according to the current value detected by current sensor.

Error Decision
Conditions

When the current value detected by current sensor becomes 5 A or lower, or 40 A or more
during STD compressor operation

Supposed
Causes

Defective current sensor (A6P, A7P)


Defective outdoor unit PCB
Defective compressor

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the
connector for
current sensor
connected to X25A, X26A
on outdoor unit
PCB
(A1P)?

NO

Connect the connector, and


operate the unit again.

YES

Are the
current sensors inversely
connected to two STD
compressors?

YES

Correct the connections between


the current sensors and the STD
compressors.

NO
Is the
current sensor
mounted on the T-phase
(A6P) and R-phase
(A7P) wire?
YES

Service Diagnosis

NO

Mount the current sensor


correctly, and operate the unit
again.
Replace the current sensor and
outdoor unit PCB.

247

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.27 High Pressure Sensor Abnormality


Remote
Controller
Display

JA

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected from the pressure detected by the high pressure sensor.

Error Decision
Conditions

When the high pressure sensor is short circuit or open circuit.


(4.22 MPa or more, or 0.01 MPa or less)

Supposed
Causes

248

Defective high pressure sensor system


Connection of low pressure sensor with wrong connection
Defective outdoor unit PCB
Defective connection of high pressure sensor

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

1.Set the high pressure gauge


upright.
2.Connect the checker for
VRV to the gauge.

Are the
characteristics
of the high pressure
sensor normal? (Make a
comparison between the
voltage characteristics
(*1) and the gauge
pressure.)

NO

Replace the high pressure


sensor.

YES
If the
PCB pressure
detection normal?
(Make a comparison
between the checker
pressure data and the
voltage
characteristics
(*1).)

NO

Replace the main PCB.

YES
Reset the operation, and then
restart the outdoor unit.

Are the
characteristics of the
high pressure sensor
normal?

NO

Replace the high pressure


sensor.

YES

Replace the main PCB.

Note:

1: Voltage measurement point

2: Refer to Pressure Sensor, Pressure / Voltage Characteristics table on P.349.

Service Diagnosis

249

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.28 Low Pressure Sensor Abnormality


Remote
Controller
Display

JC

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected from pressure detected by low pressure sensor.

Error Decision
Conditions

When the low pressure sensor is short circuit or open circuit.

Supposed
Causes

250

Defective low pressure sensor system


Connection of high pressure sensor with wrong connection
Defective outdoor unit PCB
Defective connection of low pressure sensor

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

1.Set the low pressure gauge


upright.
2.Connect the checker for
VRV to the gauge.

Are the
characteristics
of the low pressure
sensor normal? (Make a
comparison between the
voltage characteristics
(*1) and the gauge
pressure.)

NO

Replace the low pressure


sensor.

YES

If the
PCB pressure
detection normal?
(Make a comparison
NO
between the checker pressure
data and the voltage
characteristics
(*1).)

Replace the main PCB.

YES

Reset the operation, and then


restart the outdoor unit.

Are the
characteristics of the
low pressure sensor
normal?

NO

Replace the low pressure


sensor.

YES

Replace the main PCB.

Service Diagnosis

251

Troubleshooting by Indication on the Remote Controller

Note:

Si34-804_C

1: Voltage measurement point

2: Refer to Pressure Sensor, Pressure / Voltage Characteristics table on P.349.

252

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.29 Inverter PCB Abnormality


Remote
Controller
Display

L1

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected based on the current value during waveform output before starting
compressor.
Error is detected based on the value from current sensor during synchronous operation when
starting the unit.

Error Decision
Conditions

Overcurrent (OCP) flows during waveform output


Error of current sensor during synchronous operation
IPM failure

Supposed
Causes

Main PCB (A1P)


zIPM failure
zCurrent sensor failure
zDrive circuit failure

Service Diagnosis

253

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Turn OFF the power supply


once, and then turn ON the
power supply again.

Does the
power supply normally
come back ON?

YES

It is supposed that the error


results from external causes
other than failures (e.g.
exogenous noises or thunder).

NO

CHECK 8
Check if the power
transistor is
normal.

NO

YES
Check if
insulation resistance of
the compressor is
100k or more.

NO

Replace the compressor and


the main PCB (A1P) at the
same time.

YES

Replace the main PCB (A1P).


CHECK 8
Check if the power
transistor of the fan
driver is normal.

NO

Replace the main PCB (A1P).

YES

Replace the main PCB (A1P).

CHECK 8 Refer to the information on P.298.

254

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.30 Inverter Radiation Fin Temperature Rise Abnormality


Remote
Controller
Display

L4

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Fin temperature is detected by the thermistor of the radiation fin.

Error Decision
Conditions

When the temperature of the inverter radiation fin increases above 87C

Supposed
Causes

Actuation of fin thermal (Actuates above 87C)


Defective inverter PCB
Defective radiation fin thermistor

Service Diagnosis

255

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

The radiation
fin of the main PCB
concerned exceeded a
temperature of
87C.

YES

NO

Faulty radiation from the power


unit
Blocked air suction port
Stained radiation fin
High outdoor temperature

Turn OFF the power supply,


and then make measurement
of resistance of the radiation
fin thermistor.

Is the thermistor
resistance normal?

NO

Replace the thermistor (Fin TH).

YES

Connect and disconnect the


connector (X111A) for the fin
thermistor, and then properly
connect it.

Does
the error
recur when the power
supply turns ON to start
the compressor?

YES

Replace the main PCB (A1P).

NO

Continue operation.
It is supposed that the
radiation fin temperature
became high due to some
field factors. In this
connection, check the
following points:
Stained radiation fin
Airflow obstructed with dirt
or foreign matters
Damage to fan impellers
Too high outdoor
temperature

256

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Inverter PCB for compressor


Refer to Thermistor Resistance / Temperature Characteristics table on P.347.

Service Diagnosis

257

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.31 Inverter Compressor Abnormality


Remote
Controller
Display

L5

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected from current flowing in the power transistor.

Error Decision
Conditions

When an excessive current flows in the power transistor


(Instantaneous overcurrent (59.1 A) also causes activation.)

Supposed
Causes

Defective compressor coil (disconnected, defective insulation)


Defective compressor startup (mechanical lock)
Defective inverter PCB

Troubleshooting
Compressor inspection
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the stop valve open?

NO

Open the stop valve.

YES

Power OFF

The
compressor lead wires
and normal.

NO

Replace the compressor


lead wires.

YES
The wiring and
connection to the
compressor are
normal.

NO

Correct the wiring and


connection.

YES
A

258

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
A

Power OFF

The insulation
resistance is low (i.e.,
not more than
100 k.)

YES

Replace the compressor.

NO
Compressor coils are
disconnected.

YES

Replace the compressor.

NO
CHECK 8
The power transistor has
an abnormality.

NO

Replace the inverter PCB.

YES

Power ON

Restart
the compressor, and
then check whether or
not the error
recurs.

NO

Normal
Onsite causes such as
instantaneous power
failure or open phase

YES
Power OFF

Power ON

Replace the inverter PCB.

Restart
the compressor, and
then check whether or
not the error
recurs.
YES

NO

Continue the operation.

Replace the compressor.


Conduct checks and
diagnosis of the
compressor.

CHECK 8 Refer to P.298.

Service Diagnosis

259

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.32 Inverter Current Abnormality


Remote
Controller
Display

L8

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error is detected by current flowing in the power transistor.

Error Decision
Conditions

When overload in the compressor is detected (Inverter secondary current)


(1) 33.5 A or more continues for 5 seconds
(2) 27.6 A or more continues for 260 seconds

Supposed
Causes

260

Compressor overload
Compressor coil disconnected
Defective inverter PCB
Disconnection of compressor

Service Diagnosis

Si34-804_C

Troubleshooting

Troubleshooting by Indication on the Remote Controller

Output current check

Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the stop valve open?

NO

Open the stop valve.

YES

The compressor lead wires


are normal.

NO

YES

The wiring and


connection to the compressor
are normal.

NO

Replace the
compressor lead
wires.

Correct the wiring and


connection.

YES

Power OFF

Insulation resistance
of the compressor is 100 k
or less.

YES

Replace the inverter


compressor.

NO
Compressor
coils are disconnected.

YES

Replace the inverter


compressor.

NO
CHECK 8
Check if the power transistor
is normal.

NO

Replace the main


PCB (A1P).

YES
Connect the compressor lead wires
then restart the operation.

Error code
L8 is displayed again.

NO

Continue the
operation.

YES

The pressure
difference between high
pressure and low pressure
before restarting is
0.2 MPa or less.

NO

Defective pressure
equalizing in the
refrigerant circuit.

YES

Inspection of the
compressor.

CHECK 8 Refer to P.298.

Service Diagnosis

261

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.33 Inverter Compressor Startup Abnormality


Remote
Controller
Display

L9

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Detect the failure based on the signal waveform of the compressor.

Error Decision
Conditions

Starting the compressor does not complete.

Supposed
Causes

262

Defective compressor
Stop valve is not opened.
Large pressure difference before starting the compressor
Defective compressor connection
Defective inverter PCB

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

It is the first
time to start after
installation.

NO

Continued to A (on the


following page)

YES

The proper
amount of refrigerant
is charged.

NO

Charge a proper amount of


refrigerant.

YES

Is the
stop valve open?

NO

Open the stop valve.

YES

Refrigerant
is sleeping. ( The unit is
out of power supply for
more than 6
hours.)

YES

Cancel the sleeping state of


refrigerant.

NO

The insulation
resistance of the
compressor is more
than 100k.

NO

Cancel the sleeping state of


refrigerant.

YES

The
compressor lead wires are
disconnected.

YES

Fix the compressor lead


wire.

NO

Correct the wiring, and then


supply power to restart.

Service Diagnosis

263

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
A

Refrigerant is
sleeping. ( The unit is out
of power supply for more
than 6 hours.)

NO

Cancel the sleeping state of


refrigerant.

YES

The insulation
resistance of the
compressor is 100k
or over.

NO

Replace the inverter


compressor.

YES

Is inside the
compressor broken?

YES

Replace the inverter


compressor.

NO

CHECK 8
Check if the power
transistor is normal.

NO

Replace the main PCB (A1P).

YES

Recheck the compressor/


refrigerant circuit.

CHECK 8 Refer to P.298.

264

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.34 Transmission Error between Inverter and Control PCB


Remote
Controller
Display

LC

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Check the communication state between inverter PCB and control PCB by micro-computer.

Error Decision
Conditions

When the correct communication is not conducted in certain period

Supposed
Causes

Service Diagnosis

Transmission error between the inverter PCB and outdoor control PCB
Defective outdoor control PCB (transmission section)
Defective inverter PCB
Defective noise filter
External factor (noise, etc.)
Defective compressor
Defective fan motor

265

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Are the
connectors of the
main PCB, and
inverter PCB all securely
connected?
(1)

NO

Properly connect the connectors.

YES

Is the type of
the inverter PCB
correct?

NO

Replace it with a correct PCB.

YES

The INV.
compressor has
insulation resistance of
not more than
100k.

YES

Replace the INV. compressor


(M1C).

NO
The fan
motor has insulation
resistance of not more
than 1M.

YES

Replace the fan motor.

NO
The
micro-computer
normal monitor (green)
of the main PCB (A1P)
is blinking.

NO

Not the LC error. Check the error


code again.

YES
The
micro-computer
normal monitor (green)
of the inverter PCB
(A2P)is blinking.

NO

Replace the inverter PCB (A2P).

YES
Error is displayed
again?
NO

Note:

266

YES

Replace the main PCB (A1P).

Continue the operation.


(It is supposed that the error
results from causes such as
instantaneous power failure.)

1: Disconnect the connector once, then reconnect it and check that it is securely connected.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.35 Inverter Over-Ripple Protection


Remote
Controller
Display

P1

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Imbalance in supply voltage is detected in PCB.

Error Decision
Conditions

When the amplitude of the ripple exceeding 6 V is detected.


When the resistance value of thermistor becomes a value equivalent to open or short circuited
status
Error is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.

Supposed
Causes

Service Diagnosis

Open phase
Voltage imbalance between phases
Defective main circuit capacitor
Defective inverter PCB
Defective K2M relay in inverter PCB
Improper main circuit wiring

267

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Imbalance
in supplied voltage is
in excess of 6 V.
1

YES

NO

Open phase?

YES

Open phase
Normalize field cause.

NO

Fix power supply voltage


imbalance.
Is
the voltage
imbalance applied to the
inverter in excess of
6 V?

YES

NO
<When voltage monitoring is possible:>
Using a device capable of constant
recording of power supply voltage
record power supply voltage
between 3 phases (L1 ~ L2, L2 ~ L3,
L3~L1) for about one continuous
week.

No abnormalities are
observed in the power
supply, but the imbalance in
voltage recurs.

Part or wiring defect


After turning the power
supply OFF, check and
repair the main circuit
wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2M contact
disposition, fusion or
contact is poor.
(3) Loose or disconnected
noise filter

Power supply voltage imbalance


Even if the power supply voltage is not
unbalanced when measuring it, there
are many cases where it gets
unbalanced during nighttime (around
6:00PM to 10:00PM).
measure

Replace the inverter PCB.


Explanation for users In accordance with "notification of inspection results" accompanying spare parts.
Be sure to explain to the user that
Give the user a copy of "notification of inspection results" and leave
there is a "power supply imbalance"
it up to him to improve the imbalance.
for which DAIKIN is not responsible.

1.Measure voltage at the X1M power supply terminal block.

268

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.36 Inverter Radiation Fin Temperature Abnormality


Remote
Controller
Display

P4

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Resistance of radiation fin thermistor is detected when the compressor is not operating.

Error Decision
Conditions

When the resistance value of thermistor becomes a value equivalent to open or short circuited
status
Error is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.

Supposed
Causes

Defective radiation fin temperature thermistor


Defective inverter PCB
Defective inverter compressor
Defective fan motor

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.
Measure resistance value of
the radiation fin thermistor.

Is the thermistor
resistance value
normal?
YES
The INV.
compressor's
insulation resistance
is not more than
100k.

NO

Replace the inverter


PCB.

YES
Replace the INV.
compressor (M1C).

NO
The fan motor's
insulation resistance
is not more than
1M.
NO

YES

Error is displayed
again when the power
supply turns ON?

YES

NO

Service Diagnosis

Replace the fan motor.

Replace the INV. PCB.

Continue the operation.

269

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.37 Field Setting after Replacing Main PCB Abnormality or


Combination of PCB Abnormality
Remote
Controller
Display

PJ

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

This error is detected according to communications with the INV. PCB.

Error Decision
Conditions

Make judgement according to communication data on whether or not the type of the INV. PCB
is correct.

Supposed
Causes

Mis-matching of type of PCB


Improper (or no) field setting after replacing main PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is the
type of the compressor
inverter PCB (A2P)
correct?

NO

Replace it with the


correct compressor
inverter PCB.

YES
Is the
type of the fan inverter
PCB (A2P) correct?

NO

Replace it with the


correct fan inverter
PCB.

YES
Is the
setting of dip switches
when replace the main
PCB correct?

NO

YES
Does the
preparation indication
lamp (H2P) on the main
PCB turn
OFF?
YES

NO

Set the dip switches


correctly.
(After setting: Reset the
power supply)

Rectify the connection


wiring.

Replace the outside


unit main PCB.

270

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.38 Refrigerant Shortage

U0

Remote
Controller
Display
Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Detect refrigerant shortage based on the temperature difference between low pressure or
suction pipe and heat exchanger.

Error Decision
Conditions

Error is not determined. The unit continues the operation.

Low pressure becomes 0.1 MPa or less.

Supposed
Causes

Refrigerant shortage and refrigerant clogging (wrong piping)


Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

 Mount a pressure gauge at the service port on the low


pressure side.
 Reset the operation using the remote controller then restart.

Is the
low pressure 0.1MPa
or less? (1)
YES

NO

Is the
characteristics of low
pressure sensor
normal? (2)

NO

Replace the low pressure


sensor.

YES
Replace the outside unit
main PCB (A1P).
Remove the factor of
decreasing low pressure.
CHECK 4

Note:

1: Check the low pressure value by using pressure gauge in operation.


2: Compare the actual measurement value by pressure sensor with the value by the pressure

gauge.
(To gain actual measurement value by pressure sensor, measure the voltage at the
connector [between (2)-(3)] and then convert the value into pressure referring to P.232.)
CHECK 4 Refer to P.295.

Service Diagnosis

271

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.39 Reverse Phase, Open Phase


Remote
Controller
Display

U1

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.

Error Decision
Conditions

When a power supply is reverse phase, or T phase is open phase.

Supposed
Causes

Power supply reverse phase


T phase open phase
Defective outdoor unit PCB (A1P)

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

There
is an open phase
at the power supply
(T phase) terminal section
(X1M) of the
outdoor unit.

YES

Fix the open phase. Requires


inspection of field power supply
section.

NO
Operation
is normal if one
phase of power supply
line phase is
replaced.
NO

272

YES

Reverse phase.
Countermeasure of the problem is
completed by phase replacement.
Replace the outdoor unit PCB
(A1P).

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.40 Power Supply Insufficient or Instantaneous Abnormality


Remote
Controller
Display

U2

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Error of voltage of main circuit capacitor built in the inverter PCB and power supply voltage.

Error Decision
Conditions

When the voltage aforementioned is 190 V or less.

Supposed
Causes

Service Diagnosis

Power supply insufficient


Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor service monitor PCB
Defective main circuit wiring
Defective compressor
Defective fan motor
Defective connection of signal cable

273

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.
Check for
power supply voltage.
Voltage between phases:
380 to 415 V
YES

Power ON

Unbalanced
power supply? (Not more
than 2%: Phase voltage of
not more than
approx. 5 V)

Power OFF

NO

NO

YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
The insulation
resistance is low. (i.e., not more than
100 k.)

YES

Onsite causes.
Make proper wire connections
without open phase, erroneous
connections, or erroneous order of
phases.

Onsite causes.
Correct the unbalanced loads to
eliminate the unbalanced state.
Unbalanced voltage will cause
extremely unbalanced current,
thus impairing the service life of or
resulting in the error of the
equipment.

Replace the compressor.

NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The
insulation resistance is
low (i.e., not more than
1 M.)
NO

YES

Replace the fan motor.


Replace the fan driver.

Check the inverter power


transistor.

CHECK 8
Has the power transistor
got defective?

YES

NO

Check the fan driver power


transistor.

Has the
power transistor
got defective?

YES

Replace the inverter PCB.


Observe the conditions of the
PCB.
In the case of a serious failure, a
compressor failure may cause
the failure of the PCB. Even if
the PCB is replaced, it may
cause failure again.
To avoid that, recheck the
compressor for ground and for
any broken wires. Furthermore,
even after the completion of
PCB replacement, check the
compressor.
Replace the fan driver PCB.
Observe the conditions of the
PCB.

NO
A

274

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
A

Power OFF

Check for connector connections: Remove


and insert the connectors shown below.
Furthermore, check the connectors for
terminal conditions and continuity.
RXQPAY1:
X1M power receiving terminal X400A A2P
A2P X401A X10A A3P
A1P X28A X6A A3P
A3P X61A X402A A2P
A3P X1A X403A A2P
A3P P1, P2 Reactor terminal L1R
A3P P3, N3 P1, N1 A4P
A4P P2, N2 P1, N1 A8P

Has the
inverter PCB caused
damage?

YES
A3P: Replace the inverter PCB.
If the PCB replaced is badly
damaged, the compressor is
likely to get defective. To make
sure, recheck the compressor.

NO
Has the
fan driver caused
damage?

If any wiring has damage, replace


the harness.

YES

NO

A4P/A8P: Replace the fan driver


PCB.
If the PCB replaced is badly
damaged, the fan motor is likely
to get defective. To make sure,
recheck the compressor.

Turn ON the power supply.


Stop (standby)
before the fan rotates.

YES

NO

Power ON

Stop (standby)
when the compressor
starts up.

YES

NO

The U2
error recurs.

YES

Recheck for the power supply. If


there is no problem with the power
supply, replace the A2P noise filter
PCB.
If the error recurs, replace the
inverter PCB.
Recheck for the power supply. If
there is no problem with the power
supply, replace the A3P inverter
PCB.
If the PCB replaced is badly
damaged, compressor is likely to
get defective. To make sure,
recheck the compressor.
Check the harness, and then
replace it if necessary.

NO
End of measures:
The error may temporarily result
from onsite causes.
Causes: Instantaneous power
failure (open phase), noises, or
else.

Refer to CHECK 8 P.298.

Service Diagnosis

275

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.41 Check Operation is not Executed


Remote
Controller
Display

U3

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Check operation is executed or not executed

Error Decision
Conditions

Error is decided when the unit starts operation without check operation.

Supposed
Causes

Check operation is not executed.

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Has the
check operation
performed on outdoor
unit PCB?
YES

NO

Press and hold BS4 on the main


outdoor unit PCB for 5
seconds or more, or turn ON the
field setting mode 2-3 to conduct a
check operation.
Performs the check operation
again and completes the check
operation.

276

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.42 Transmission Error between Indoor Units and Outdoor


Units
Remote
Controller
Display

U4

Applicable
Models

All models of indoor unit


RXQ5PA~54PA

Method of Error
Detection

Micro-computer checks if transmission between indoor and outdoor units is normal.

Error Decision
Conditions

When transmission is not carried out normally for a certain amount of time

Supposed
Causes

Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit

Service Diagnosis

or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor unit PCB

277

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Has
the indoor
or outdoor unit
PCB been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been
modified?

YES

Press and hold the RESET


button on the master outdoor
unit PCB for 5 seconds.
The unit will not operate for
up to 12 minutes.

NO
All
indoor unit
remote controllers of the
same refrigerant system
display
"U4."

NO

Is indoor
- outdoor and outdoor outdoor unit transmission
wiring normal?

YES

NO

YES

Fix the indoor/outdoor or


outdoor/outdoor unit
transmission wiring.

Reset the power supply.

Outdoor
unit PCB
micro-computer monitor
(HAP) blinks.

NO

YES

The
voltage between
terminals L1 and N of the
outdoor unit PCB
is 220~240 V
10%.

NO

Supply 220~240 V.

YES
The fuse on
the outdoor unit's
PCB is burnt.
NO

NO

Replace the indoor unit PCB


indicated by the error code
U4.

YES

Replace the fuse.

Replace the outdoor unit


PCB.

Operation
ready lamp (H2P) is
blinking.
YES
Lamp does
not go off for 12 minutes
or more.

YES

NO
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?

NO

Press and hold the RESET


button on the outdoor unit
PCB for 5 seconds.

Fix the indoor/outdoor or


outdoor/outdoor unit
transmission wiring.

YES
Disconnect
the outdoor-outdoor
unit transmission wiring, and
then check with a single
system whether or
not it
is normal.
YES

278

NO

Replace the outdoor unit PCB


(A1P).

Mount the DIII-NET extension


adaptor.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.43 Transmission Error between Remote Controller and


Indoor Unit
Remote
Controller
Display

U5

Applicable
Models

All models of indoor unit

Method of Error
Detection

Micro-computer checks if transmission between indoor unit and remote controller is normal.

Error Decision
Conditions

When transmission is not carried out normally for a certain amount of time

Supposed
Causes

Transmission error between indoor unit and remote controller


Connection of 2 main remote controllers (when using 2 remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Transmission error caused by noise

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Using
2-remote controllers
control.

YES

NO

All indoor
unit PCB micro-computer
monitors blink.

YES

Set one remote controller to


"SUB"; turn the power supply
OFF once and then back ON.

NO

NO

YES

Operation
returns to normal when
the power is turned OFF
momentarily.
YES

Replace the remote controller.

Normal

SS1 of
both remote controllers
is set to "MAIN."

YES

NO

Replace the indoor unit


PCB.
There is possibility of error
caused by noise. Check the
surrounding area and turn on
again.
Normal

NO
Replace the indoor unit PCB.

Normal
NO

Service Diagnosis

YES

Normal
There is possibility of error
caused by noise. Check the
surrounding area and turn on
again.

279

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.44 Transmission Error between Outdoor Units


Remote
Controller
Display

U7

Applicable
Models

RXQ5PA~54PA

Method of Error
Detection

Micro-computer checks if transmission between outdoor units is normal.

Error Decision
Conditions

When transmission is not carried out normally for a certain amount of time

Supposed
Causes

Improper connection of transmission wiring between outdoor unit and external control

280

adaptor for outdoor unit


Improper connection of transmission wiring between outdoor units.
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defective outdoor unit PCB (A1P)
Defective external control adaptor for outdoor unit

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is there any
broken wire or erroneous
wire connection in the
communication wiring of
multi outdoor unit
system?

NO

Fix the outdoor units multi


connection transmission
wiring and reset power.

YES
C/H SELECT is set to "IND".

YES

Replace the outdoor unit PCB


(A1P).

NO
Cool/Heat selection
is unified.

NO

Set C/H SELECT to "IND."

YES
C/H SELECT
is set to
"MASTER."

YES

NO
C/H SELECT
is set to
"SLAVE."
NO

YES

The cool/heat unified


address for outdoor units in
outdoor - outdoor unit
transmission is duplicated.
Set the address correctly.
Check
NO
and see if the following items
Fix the problem.
are normal.

YES
External control adaptor for outdoor unit
Is this PCB energized?
Does the cool/heat unified address match?
Outdoor unit (unified master unit)
Is this energized?
Does the cool/heat unified address match?
YES
Does an
error occur when
the cool/heat selector is
set to "IND?"
YES

Service Diagnosis

NO

Replace the external control


adaptor for outdoor unit.

Replace the outdoor unit PCB


(A1P).

281

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.45 Transmission Error between Main and Sub Remote


Controllers
Remote
Controller
Display

U8

Applicable
Models

All models of indoor unit

Method of Error
Detection

In case of controlling with 2-remote controller, check the system using micro-computer if signal
transmission between indoor unit and remote controller (main and sub) is normal.

Error Decision
Conditions

When transmission is not carried out normally for a certain amount of time.

Supposed
Causes

Transmission error between main and sub remote controller


Connection between sub remote controllers
Defective remote controller PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Using 2-remote
controllers control.

NO

YES
SS1
of both remote controllers is
set to "SUB."
YES

282

SS1
of remote controller PCB
is set to "MAIN."

NO

Set SS1 to "MAIN"; the


power supply OFF once and
then back ON.

YES
NO

Turn the power OFF and


then back ON. If an error
occurs, replace the remote
controller PCB.
Set 1 remote controller to
"MAIN"; the power supply
OFF once and then back
ON.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.46 Transmission Error between Indoor and Outdoor Units


in the Same System
Remote
Controller
Display

U9

Applicable
Models

All models of indoor unit


RXQ5~54PA

Method of Error
Detection

Detect the error signal for the other indoor unit within the circuit by outdoor unit PCB.

Error Decision
Conditions

When the error decision is made on any other indoor unit within the system concerned

Supposed
Causes

Transmission error within or outside of other system


Defective electronic expansion valve in indoor unit of other system
Defective indoor unit PCB in other system
Improper connection of transmission wiring between indoor and outdoor unit

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Turn ON all indoor units.

All the units


are display "U9".

NO

Continue the operation.

YES
"U9"
has been displayed for 2
minutes or more.
YES

Service Diagnosis

NO

Re-diagnose by display after


passage of 2 minutes or more.
The outdoor unit PCB indicated
by the error code U9 is normal.
Check for the indoor unit of other
system, and then conduct
troubleshooting by diagnosis
according to the Error Code
Flowchart.

283

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.47 Improper Combination of Indoor and Outdoor Units,


Indoor Units and Remote Controller
Remote
Controller
Display

UA

Applicable
Models

All models of indoor unit


RXQ5PA~54PA

Method of Error
Detection

A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units connected is out of the allowable range.

Error Decision
Conditions

The error decision is made as soon as either of the abnormalities aforementioned is detected.

Supposed
Causes

284

Excess of connected indoor units


Defective outdoor unit PCB (A1P)
Mismatch of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit PCB was not carried out after replacing to spare PCB.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Reset all power supplies for


indoor and outdoor units
connected to one and the
same system.

Is the
error code "UA"
displayed?

NO

Normal
(It is assumed that the code is
displayed due to temporary
external cause (e.g. noises).

YES
Is the
error code
"UA" displayed for all indoor
units connected to one and
the same
system?

YES

Is the outdoor
unit PCB replaced
to spare PCB?

NO
Is
the type of
refrigerant for the
indoor units with "UA"
displayed corresponding
to that for the
outdoor
units?
YES

NO

YES

NO

The setting after replacing spare


PCB has not been set yet. Please
set as per P.167, 168.
Correct the combination of indoor
units with "UA" displayed.

The total
of indoor units
displaying "UA" and
indoor units connected to the NO
same refrigerant system is
within connectable
number of
unit

The number of indoor units that


can be connected to a single
outdoor unit system is excess of
allowable range.

YES
Replace the indoor unit PCB.
Does the
refrigerant type of indoor
and outdoor unit
match?

NO

Matches the refrigerant type of


indoor and outdoor unit.

YES
Is it a multi
outdoor unit connection
system?

NO

Replace the outdoor unit main


PCB.

YES
Is the
combination of master
unit and slave unit
correct?

NO

Change to a correct combination.

YES
Replace the outdoor unit main
PCB.

The number of indoor units that can be connected to a single outdoor unit system depends on

the model of outdoor unit.

Service Diagnosis

285

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.48 Address Duplication of Centralized Controller


Remote
Controller
Display

UC

Applicable
Models

All models of indoor unit


Centralized controller

Method of Error
Detection

The principal indoor unit detects the same address as that of its own on any other indoor unit.

Error Decision
Conditions

The error decision is made as soon as the abnormality aforementioned is detected.

Supposed
Causes

Address duplication of centralized controller


Defective indoor unit PCB

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

The centralized address is


duplicated.

286

Make setting change so that


the centralized address will
not be duplicated.

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.49 Transmission Error between Centralized Controller and


Indoor Unit
Remote
Controller
Display

UE

Applicable
Models

All models of indoor unit


Centralized controller
Schedule timer

intelligent Touch Controller

Method of Error
Detection

Micro-computer checks if transmission between indoor unit and centralized controller is normal.

Error Decision
Conditions

When transmission is not carried out normally for a certain amount of time

Supposed
Causes

Transmission error between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.

(or disconnection of connector for independent / combined use changeover switch.)


Defective PCB for centralized remote controller
Defective indoor unit PCB

Service Diagnosis

287

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Check
the indoor
unit for which
UE is displayed.
Is the the transmission
error (UE)
caused on
all indoor
units?

YES

Continued to A
(on the following
page)

NO
Is the
power supply of
the indoor unit, on which
the UE occurred,
turned ON?

NO

Make sure there are no


hazardous situations, and
then turn ON the power
supply.

YES
Has
the setting of
central control group No.
been made with the
indoor unit on which
the UE
occurred?

NO

Can
the setting of
central control group
No be made?

YES

Make correct setting of the


central control group No.

NO

YES
For VRV
systems, can the
setting of central control group
No. be made in one and
the same refrigerant
system?
Was
the central
control group No.
for indoor unit
changed?
YES

YES
NO

NO

Check outdoor units to which


the refrigerant system is
connected.
Check whether or not there
are no problems with the
transmission wiring length,
types of cables and wires,
number of units connected,
and others. If no problems,
replace the indoor unit PCB.
Reset the power supplies of
every centralized controller.
For the intelligent Touch
controller, register the air
conditioner again while in
DIII-NET test run menu.

288

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

Troubleshooting
A

Check the
transmission wiring
between centralized
controller for any broken wire.
For details, refer to information in the
Procedure for checking broken
wires section.
CHECK 7

Abnormal

Correct the wiring.

Normal

Check the
transmission
wiring between main
centralized controller for
any broken wire. For details,
refer to information in
the Procedure for
checking
broken wires
section.

Abnormal

Correct the wiring.

Normal
Has the
master centralized
controller setting connector
been connected?

NO

Correct the connection of the


connector.

YES
Disconnect the transmission
wiring of the main centralized
controller, and then check the
voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multiple meter.
Is the
voltage between
the terminals F1 (+)
and F2 (-) in the range of
15.2 to 17.6
VDC?
YES

NO

Replace the centralized


controller.

Centralized controller: Normal

It is supposed that the error


results from external factors
(e.g. noises) from other
equipment.

Refer to CHECK 7 P.297.

Service Diagnosis

289

Troubleshooting by Indication on the Remote Controller

Si34-804_C

3.50 System is not Set yet


Remote
Controller
Display

UF

Applicable
Models

All models of indoor unit


RXQ5PA~54PA

Method of Error
Detection

On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.

Error Decision
Conditions

The error is determined as soon as the abnormality aforementioned is detected through


checking the system for any erroneous connection of units on the check operation.

Supposed
Causes

Improper connection of transmission wiring between indoor-outdoor units and outdoor-

outdoor units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Are the stop


valves opened?

NO

Open the stop valve.

YES
Is the
check operation
carried out?

NO

YES
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES

Is indoor
-outdoor and outdooroutdoor unit transmission
wiring normal?

YES
Replace the indoor unit PCB.

NO
NO

After fixing incorrect wiring,


press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
The unit will not run for up to
12 minutes.
Wiring check operation may
not have been carried out
successfully.

290

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

3.51 System Abnormality, Refrigerant System Address


Undefined
Remote
Controller
Display

UH

Applicable
Models

All models of indoor unit


RXQ5PA~54PA

Method of Error
Detection

Detect an indoor unit with no auto address setting.

Error Decision
Conditions

The error decision is made as soon as the abnormality aforementioned is detected.

Supposed
Causes

Improper connection of transmission wiring between indoor-outdoor units and outdoor-

outdoor units
Defective indoor unit PCB
Defective outdoor unit PCB (A1P)

Service Diagnosis

291

Troubleshooting by Indication on the Remote Controller

Si34-804_C

Troubleshooting
Caution

Be sure to turn off power switch before connect or disconnect connector,


or parts damage may be occurred.

Is
electricity
being introduce for
the first time after
YES
installation or after an indoor
or outdoor unit PCB
has been
replaced?
NO

Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?

NO

Normal

YES

NO

YES
Press and hold the RESET
button on the outdoor unit
PCB for 5 seconds

Does an error occur?

Does
an error
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?

NO

After fixing incorrect wiring,


press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
The unit will not run for up to
12 minutes.

Normal

YES

Disconnect
the outdoor-outdoor
unit transmission
wiring to create the onesystem status, and then
check whether or not
the system is
normal.

YES

Mount the DIII-NET extension


adaptor.

NO
Does
a "UH" error occur
for all indoor units in
the system?
YES

292

NO

Replace the indoor unit PCB.

Replace the outdoor unit PCB


(A1P).

Service Diagnosis

Si34-804_C

CHECK 1

CHECK 2

Service Diagnosis

Troubleshooting by Indication on the Remote Controller

Check on connector of fan motor (Power supply cable)


(1) Turn off the power supply.
Measure the resistance between phases of U,V,W at the motor side connectors (three-core
wire) to check that the values are balanced and there is no short circuiting, while connector
or relay connector is disconnected.

Red

White

Black

Measure the resistance


values between phases
U,V,W.

(1) Turn off the power supply.


(2) Measure the resistance between Vcc and each phase of U,V,W, and GND and each phase
at the motor side connectors (five-core wire) to check that the values are balanced within the
range of 20 %, while connector or relay connector is disconnected.
Furthermore, to use a multiple meter for measurement, connect the probe of negative pole
to Vcc and that of positive pole to GND.

5 Gray

GND

4 Pink

Vcc

3 Orange

2 Blue

1 Yellow

Measure the resistance


values between Vcc
and U,V,W, and GND
and U,V,W.

293

Troubleshooting by Indication on the Remote Controller

Si34-804_C

CHECK 3 Check for causes of rise in high pressure

Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.

Local
pressure
rise

Rise in high
pressure

[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Defective
high
pressure
control

High pipe
resistance

Stop valve closed

Check to be sure the stop valve is open.

Bent or crashed pipe

Conduct visual checks for pipe conditions.

Clogging of foreign
particles

Is there any temperature difference caused before


and after the filter or branch pipe.

Defective valve coil


Defective outdoor
unit electronic
expansion valve
Defective valve body
A temperature difference in excess of 10C
between the inlet and the outlet is deemed to be abnormal.
Defective high pressure sensor
Defective
control
Defective service moniter PCB

[In cooling]

Are the coil resistance and insulation normal?

Are the electrical characteristics normal?


Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?

Short circuit

Is the suction air temperature not more than


43C?

High outdoor air temperature

Is the outdoor temperature not more than 43C?

High suction
air
temperature
of the
condenser

High suction air


temperature
of outdoor unit

Degradation
in condensing
capacity

Dirty condenser

Is the heat exchanger clogged? (In cooling)

Mixing of non-condensable gas

Is air or else mixed in the refrigerant system?

Decreased
fan airflow
rate

Decreased
fan
output

High air
passage
resistance
Excessive refrigerant charging

Defective fan
motor
Defective service
moniter PCB
(Including
capacity setting)

Can the fan motor be rotated with hands?


Are the motor coil resistance and
insulation normal?
If a spare PCB is mounted, is the capacity
setting properly made?

Dirty filter

Is the air filter clogged?

Obstacle

Is there any obstacle in the air passage?

Refer to 2.
Is the indoor unit too small compared to
the large-sized outdoor unit?

1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
2: Refer to Refrigerant Overcharged on P.244.

294

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

CHECK 4 Check for causes of drop in low pressure

Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
[In cooling]
(See 1.)
Faulty low
pressure
control

Abnormally low
pressure
(Low evaporating
temperature)

[In both cooling


and heating]
(See 2.)
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:

Faulty
compressor
capacity
control
Faulty low
pressure
protection
control

Faulty indoor
unit electronic
expansion valve

Are the electrical characteristics normal?

Faulty service monitor PCB

Is the pressure value checked with the Service Checker


corresponding to the measurement of the pressure sensor?

Faulty low pressure sensor

Are the electrical characteristics normal?

Faulty hot gas solenoid valve

Are the coil resistance and insulation normal?

Faulty service monitor PCB

Is the pressure value checked with the Service Checker


corresponding to the measurement of the pressure sensor?

Faulty valve coil

Are the coil resistance and insulation normal?

Faulty valve body

Faulty electronic
expansion valve
control
Faulty
control

[In cooling]
Low suction
air temperature
of the
evaporator

Faulty low pressure sensor

Low suction air


temperature of
indoor unit

Faulty gas pipe


thermistor of indoor unit

Check for the thermistor resistance and connection.

Faulty liquid pipe


thermistor of indoor unit

Check for the thermistor resistance and connection.

Faulty service monitor PCB

Is the pressure value checked with the Service Checker


corresponding to the measurement of the pressure sensor?

Short circuit

Is the suction air temperature not less than 14C

Low outdoor temperature

Is the indoor temperature not more than 14C


Is the connector properly connected?
Are the thermistor resistance characteristics normal?

Faulty suction air thermistor of indoor unit

High pipe
resistance

Abnormal piping length

Does the piping length fall in the permissible range?

Bent or crashed pipe

Conduct visual checks for pipe conditions.

Clogging of foreign particles

Is there any temperature difference caused before


and after the filter or branch pipe?

Stop valve closed


Less
circulation
quantity of
refrigerant

Degradation
in condensing
capacity

Check to be sure the stop valve is open.

Inadequate refrigerant quantity


Moisture choke

Eliminate moisture by vacuum operation.

Dirty
evaporator

Is the heat exchanger clogged?

Decreased
fan airflow
rate

Decreased
fan output
High air
passage
resistance

Faulty fan motor

Can the fan motor be rotated with hands?


Are the motor coil resistance and insulation normal?

Faulty service monitor PCB


(Including capacity setting)

If a spare PCB is mounted, is the capacity


setting properly made?

Dirty filter

Is the air filter clogged?

Obstacle

Is there any obstacle in the air passage?

1: For details of the compressor capacity control while in cooling, refer to Compressor PI

Control on P.83.
2: The low pressure protection control includes low pressure protection control and hot gas

bypass control. Refer to P.108.

Service Diagnosis

295

Troubleshooting by Indication on the Remote Controller

Si34-804_C

CHECK 5 Master-Slave Unit Setting Table

Combination of intelligent Touch Controller and Centralized Remote Controller


Master

#1

Slave

#2

#3

#1
Pattern


#4

#2

1-00~4-15

Master/
Slave

CRC

CRC

intelligent
Touch
Controller

Master

CRC

#3

5-00~8-15

Master/
Slave

Master

CRC

Master

Master

#4

1-00~4-15

Master/
Slave

5-00~8-15

Master/
Slave

CRC

Slave

CRC

Slave

CRC

Slave

intelligent
Touch
Controller

Slave

Master

intelligent
Touch
Controller

Slave

intelligent
Touch
Controller

Master

CRC

Slave

CRC

Master

intelligent
Touch
Controller

Master

CRC: Centralized remote controller <DCS302C1>


intelligent Touch Controller: < DCS601C51 >
The patterns marked with have nothing to do with those described in the list of Setting of master unit central setting connector.

CHECK 6 Master Unit Central Connector Setting Table

The master unit central setting connector (CN1/X1A) is mounted at the factory.
To independently use a single unit of the intelligent Touch controller or a single unit of the
centralized remote controller, do not dismount the master unit central setting connector (i.e.,
use the connector with the factory setting unchanged).
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been mounted at the factory. Insert the
connector, which is attached to the casing of the main unit, in the PCB (CN1/X1A).
(Independent-use connector=Master unit central setting connector)
To use two or more centralized controller in combination, make settings according to the
table shown below.
Centralized controller connection pattern
Pattern intelligent Centralized Unified Schedule
remote
ON/OFF
Touch
timer
Controller controller controller


1 to 2
units

(*1)




1 unit

(*1)
1 to 8
units

1 to 2
units

1 to 4
units

1 to 16
units

(*1)

1 unit
1 unit

Unified
ON/OFF
controller

Schedule
timer

(*1)
1 unit




Setting of master unit central setting connector(*2)


Centralized
intelligent
remote
Touch
controller
Controller
Only a
single unit:
"Provided",
Others: "Not
provided"

1 to 16
units

1 unit
1 unit

Provided

Not provided

Only a
single unit:
"Provided",
Others: "Not
provided"

All "Not
provided"

Only a
single unit:
"Provided",
Others: "Not
provided"

All "Not
provided"

Not provided
Not provided

Only a
single unit:
"Provided",
Others: "Not
provided"

Not provided
Provided

(*1) The intelligent Touch Controller and the schedule timer are not available for combined use.
(*2) The intelligent Touch Controller, centralized remote controller, and the unified ON/OFF controller have been set to "Provided with the
master unit central setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit central
setting connector" at the factory, which is attached to the casing of the main unit.

296

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

CHECK 7 Procedures for Detecting Broken Wires in Transmission Wiring for Control

1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short-circuit
between the outdoor-outdoor unit terminal parts F1 and F2 in the "Outdoor Unit A" that is
farthest from the centralized remote controller, and then conduct continuity checks between
the transmission wiring terminal blocks F1 and F2 of the centralized remote controller using
a multiple meter. If there is continuity between the said terminal blocks, the outdoor-outdoor
unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the outdooroutdoor unit terminal parts of the "Outdoor Unit A" short-circuited, conduct continuity checks
between the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller.
If there is no continuity as well, conduct continuity checks between the outdoor-outdoor unit
terminal parts of the "Outdoor Unit E", between the outdoor-outdoor unit terminal parts of the
"Outdoor Unit D", between the outdoor-outdoor unit terminal parts of the "Outdoor Unit C",
in the order described, thus identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for
checking the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken
wires)
Turn OFF the power supply to all equipment, short-circuit between the indoor-outdoor unit
terminal parts F1 and F2 in the "Outdoor Unit C, and then conduct continuity checks
between the transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the
"Outdoor Unit C" using a multiple meter. If there is continuity between the said transmission
wirings, the indoor-outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indooroutdoor unit terminal parts of the "Outdoor Unit C" short-circuited, identify the place with
continuity in the transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor
Unit c", and transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.

 Short-circuit
between the
outdoor-outdoor
unit terminal
parts.

 Check the transmission


wiring for continuity.
If there is continuity, the
indoor-outdoor unit
transmission has no
broken wires in it.

Indoor-outdoor Unit
Transmission Wiring

 Short-circuit between
the indoor-outdoor unit
terminal parts.

Outdoor-outdoor Unit
Transmission Wiring

 Check the transmission


wiring for continuity.
If there is continuity, the
outdoor-outdoor unit
transmission has no broken
wires in it.

Unified ON/OFF controller

Service Diagnosis

Centralized remote controller

297

Troubleshooting by Indication on the Remote Controller

Si34-804_C

CHECK 8 Power Transistor Check

Checking failures in power semiconductors mounted on inverter PCB


Check the power semiconductors mounted on the inverter PCB by the use of a multiple tester.
<Items to be prepared>
z Multiple tester : Prepare the analog type of multiple tester.
For the digital type of multiple tester, those with diode check function are
available for the checking.
<Test points>
z Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement
of resistance.
<Preparation>
z To make measurement, disconnect all connectors and terminals.
Inverter PCB

J1
J2
J3

P1

P3

N3 U

Electronic circuit
DM

P1

P2 P3

IGBT

X10A K2
J1
L1
J2
L2
L3
J3
N3

W
X11A

According to the checking aforementioned, it is probed that the error results from the

defective inverter. The following section describes supposed causes of the defective
inverter.
z Defective compressor (ground leakage)
z Defective fan motor (ground leakage)
z Entry of conductive foreign particles
z Abnormal voltage (e.g. overvoltage, surge (thunder), or unbalanced voltage)
In order to replace the defective inverter, be sure to check for the points aforementioned.

298

Service Diagnosis

Si34-804_C

Troubleshooting by Indication on the Remote Controller

1. Power module checking


When using the analog type of multiple
tester, make measurement in resistance
measurement mode in the x1 k range.
No.

Measuring
point
+
-

1
2

P3
P3

U
V

3
4

P3
U

W
P3

5
6

V
W

P3
P3

7
8

N3
N3

U
V

9
10

N3
U

W
N3

11
12

V
W

N3
N3

Criterion

Remark

2 to 15 k

Not less
than
15 k
(including)

It may take
time to
determine the
resistance due
to capacitor
charge or else.

2 to 15 k

2. Diode module checking


When using the analog type of multiple
tester, make measurement in resistance
measurement mode in the x1 k range.
No.

Service Diagnosis

Measuring
point

+
P1

J1

2
3

P1
P1

J2
J3

4
5

J1
J2

P1
P1

6
7

J3
N3

P1
J1

8
9

N3
N3

J2
J3

10
11

J1
J2

N3
N3

12

J3

N3

Criterion

Remark

2 to 15 k

It may take
Not less time to
than
determine the
1 5 k resistance due
(including) to capacitor
charge or else.

2 to 15 k

When using the digital type of multiple


tester, make measurement in diode check
mode (
).
No.

Measuring
point
+
-

1
2

P3
P3

U
V

3
4

P3
U

W
P3

5
6

V
W

P3
P3

7
8

N3
N3

U
V

9
10

N3
U

W
N3

11
12

V
W

N3
N3

Criterion

Remark

Not less
than
1.2 V
(including)

It may take time to


determine the voltage
due to capacitor
charge or else.

0.3 to 0.7 V

Not less
than
1.2 V
(including)

It may take time to


determine the voltage
due to capacitor
charge or else.

When using the digital type of multiple


tester, make measurement in diode check
mode (
).
No.

Measuring
point

+
P1

J1

2
3

P1
P1

J2
J3

4
5

J1
J2

P1
P1

6
7

J3
N3

P1
J1

8
9

N3
N3

J2
J3

10
11

J1
J2

N3
N3

12

J3

N3

Criterion

Remark

Not less
than
1.2 V
(including)

It may take time to


determine the voltage
due to capacitor
charge or else.

0.3 to 0.7 V

Not less
than
1.2 V
(including)

It may take time to


determine the voltage
due to capacitor
charge or else.

299

Troubleshooting by Indication on the Remote Controller

Si34-804_C

CHECK 9 Check the Factors of Overheat Operation (*5)

Identify the defective points referring to the failure factor analysis (FTA) as follows.
Hot gas circuit clogging
Faulty hot
gas bypass
control
(*1)

Defective solenoid
valve coil
Defective solenoid
valve body

Check if coil resistance and insulation


are normal.

Defective control PCB

Faulty
discharge
pipe
temperature
control

[In cooling mode only]

Faulty
subcooling
electronic
expansion valve
control (EV2)

Subcooling
electronic
expansion
valve failure
Control
failure

(*2)
Temperature
increase of
discharge
pipe

[In cooling mode]


If the indoor unit
electronic
expansion valve
is excessively
throttled. (*3)

insulation are normal.

Defective valve
body
Defective low
Check if the voltage property is
pressure sensor
normal.
Defective subcooling
Check if the connector is connected properly.

heat exchanger outlet


Check if the thermistor resistance property is
thermistor
Defective control
PCB

Faulty of four
way valve
operation

Compressor
overheat

Defective valve coil Check if coil resistance and

Four way valve is in the


middle position.
Leak from hot gas bypass
valve

normal.
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.

Check if the piping temperature connected


to the four way valve is normal.

Superheat due to
shaft damage
Superheat due to
defective compressor

Indoor unit
electronic expansion
valve failure

Defective valve coil

Check if coil resistance and insulation are


normal.

Defective valve body

Faulty
superheated
degree
control.

Faulty control

Defective thermistor for


indoor unit gas pipe

Check if the connector is connected properly.


Check if the thermistor resistance property is
normal.

Defective thermistor for


indoor unit liquid pipe

Check if the connector is connected properly.


Check if the thermistor resistance property is
normal.

Defective control PCB

Refrigerant gas
shortage

Large resistance
of piping

*1.
*2.
*3.
*4.
*5.

300

Irregular piping length

Does the piping length fall in the permissible range?

Bend/collapse

Conduct visual checks.

(Including moisture choke)

Remove the moisture by vacuum break.

Stop valve is closed.

Check if the stop valve is open.

Refer to Low pressure protection control for hot gas bypass control.
Refer to Subcooling electronic expansion valve control.
Superheating temperature control in cooling mode is conducted by indoor unit electronic expansion valve.
Superheating temperature control in heating mode is conducted by outdoor unit electronic expansion valve (EVM).
Judgement criteria of superheat operation:
(1) Suction gas superheating temperature: 10 degrees and over. (2) Discharge gas superheating temperature: 45 degrees
and over, except for immediately after starting and drooping control, etc..
(Use the above stated values as a guide. Depending on the other conditions, the unit may be normal despite the values
within the above scope.)

Service Diagnosis

Si34-804_C

Part 7
Appendix
1. Piping Diagrams..................................................................................302
1.1 Outdoor Unit .........................................................................................302
1.2 Indoor Unit............................................................................................306

2. Wiring Diagrams for Reference...........................................................309


2.1 Outdoor Unit .........................................................................................309
2.2 Field Wiring ..........................................................................................314
2.3 Indoor Unit............................................................................................317

3. List of Electrical and Functional Parts .................................................330


3.1 Outdoor Unit .........................................................................................330
3.2 Indoor Side ...........................................................................................333

4. Option List ...........................................................................................338


4.1 Option List of Controllers......................................................................338
4.2 Option Lists (Outdoor Unit)...................................................................340

5. Piping Installation Point.......................................................................342


5.1 Piping Installation Point ........................................................................342
5.2 The Example of a Wrong Pattern .........................................................343

6. Example of Connection (R-410A Type) ..............................................345


7. Thermistor Resistance / Temperature Characteristics........................347
8. Pressure Sensor .................................................................................349

Appendix

301

Piping Diagrams

Si34-804_C

1. Piping Diagrams
1.1

Outdoor Unit

302

S1NPL

S1PH

S1NPH

HEAT
EXCHANGER

C: 3D050782B

RXQ5PAY1

Appendix

Si34-804_C

Piping Diagrams

3D069081

RXQ8PAY1

Appendix

303

Piping Diagrams

Si34-804_C

3D069082

RXQ10PA / 12PAY1

304

Appendix

Si34-804_C

Piping Diagrams

3D069083

RXQ14PA / 16PA / 18PAY1

Appendix

305

Piping Diagrams

1.2

Si34-804_C

Indoor Unit

FXMQ, FXHQ, FXAQ

Gas piping connection port

Heat exchanger

Flare connection : 15.9 or less


Attached piping : Above 19.1

(4)

Fan
(2)
(3)
Liquid piping connection port
(Flare connection)

Filter

(1)
Electronic
Filter
expansion valve

DU220-602K

Code

Code

Main function

(1)

Electronic expansion valve

Y1E

Used for gas superheated degree control while in


cooling operation.

(2)

Suction air temperature


thermistor

R1T

Used for thermostat control.

R2T

Used for gas superheated degree control while in


cooling operation.
Used for gas superheated degree control while in
cooling operation.

(3)
(4)

306

Name

Liquid pipe temperature


thermistor
Gas pipe temperature
thermistor

R3T

Capacity

GAS

20 / 25 / 32 / 40 / 50M(A)
63 / 80 / 100 / 125M(A)

12.7
15.9

(mm)
Liquid
6.4
9.5

Appendix

Si34-804_C

Piping Diagrams

FXDQ

Gas side
Liquid side

Electronic expansion valve


Filter

Filter

Fan

Indoor heat exchanger


4D060927

Refrigerant pipe connection port diameters


Model
FXDQ20PB / 25PB / 32PB / 40NB /
50NBVE(T)
FXDQ63NBVE(T)

Gas

(mm)
Liquid

12.7

6.4

15.9

9.5

FXMQ20P / 25P / 32P / 40P / 50P / 63P / 80P / 100P / 125P / 140PVE

4D034245D

Refrigerant pipe connection port diameters


(mm)

Appendix

Model
FXMQ20P / 25P / 32P / 40P / 50PVE

Gas
12.7

Liquid
6.4

FXMQ63P / 80P / 100P / 125P / 140PVE

15.9

9.5

307

Piping Diagrams

Si34-804_C

FXMQ125MF / 200MF / 250MFV1

4D018650C

Refrigerant pipe connection port diameters


(mm)

308

Model
FXMQ125MFV1

Gas
15.9

Liquid
9.5

FXMQ200MFV1
FXMQ250MFV1

19.1
22.2

9.5
9.5

Appendix

RED
WHT

R50 R59

C66 C63
+ +

X10A

X4A

X111A

X41A

N1

X20A

X28A

MS
3~

M1F

MS
3~

X1A

Z5C

X4A

X3A

X2A

K3R

K4R
X1A

A5P

X29A

Y2S

X8A

K5R
Y4S

X15A

R2T R4T

Y3S

X9A

K11R
X30A

HAP
K1R
K3R
K2M
K4M

R5T R6T

E1HC

X11A

PS

K3R
K4R
K5R
K7R
K11R
L1R
M1C
M1F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R3T
PILOT LAMP (SERVICE MONITOR-GREEN) R4T
R5T
MAGNETIC RELAY (A3P)
MAGNETIC RELAY (A2P)
R6T
MAGNETIC CONTACTOR (M1C) (A3P) S1NPH
MAGNETIC CONTACTOR (M1C) (A2P) S1NPL

X66A

R3T

Y1S

X7A

K7R

PRINTED CIRCUIT BOARD (MAIN)


PRINTED CIRCUIT BOARD (NOISE FILTER)
PRINTED CIRCUIT BOARD (INV.)
PRINTED CIRCUIT BOARD (FAN)
PRINTED CIRCUIT BOARD (ABC I/P)
PUSH BUTTON SWITCH
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
C63, C66 CAPACITOR
DS1
DIP SWITCH
E1HC CRANKCASE HEATER
F1U
FUSE (8A, DC650V) (A4P)
F1U, F2U FUSE (T, 3.15A, 250V) (A1P)
F400U FUSE (T, 6.3A, 250V) (A2P)
H1P~8P PILOT LAMP (SERVICE MONITOR-ORANGE)
[H2P] PREPARE, TEST ------------------- FLICKERING
MALFUNCTION DETECTION --- LIGHT UP

A1P
A2P
A3P
A4P
A5P
BS1~5

V1CP

S1PH

P<

F2U Q1RP

F1U

X2A

F1U R10
X4A
X3A +
V1R
X2A
X1A

X5A

P1

X61A Z2C
X6A

N3 Z4C BLK
RED
P3
A4P

X5A

t
R1T

X11A

V1R

R95

K1R

V2R

X1A

BLU
BLK

RED X1A

A1P

M1C

U V W

Z3C
N=5

GRN

K2M

X400A

C1

X402A
X403A

PS

BLU

F400U
K4M
K3R
X401A

+
P1
WHT
L1R
WHT
P2

A3P

WHT

Z1F

BLK

NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR
: TERMINAL
: PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE
INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION
F1 F2, OUTDOOR-OUTDOOR TRANSMISSION F1 F2, REFER TO
THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE
PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON'T SHORT CIRCUIT THE PROTECTION
DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE
PNK : PINK YLW : YELLOW BRN : BROWN GRY : GRAY
GRN : GREEN ORG : ORANGE.

BLK

X1M L1 L2 L3 N

Z1C
A2P

RED

RED
WHT

BLU

POWER SUPPLY
Y1:3N~380-415V 50Hz

RED

WHT
BLK

Appendix

BLK

1234

X37A

MAGNETIC RELAY (Y1S)


MAGNETIC RELAY (Y2S)
MAGNETIC RELAY (Y3S)
MAGNETIC RELAY (E1HC)
MAGNETIC RELAY (Y4S)
REACTOR
MOTOR (COMPRESSOR)
MOTOR (FAN)
SWITCHING POWER SUPPLY (A1P, A3P)
PHASE REVERSAL DETECT CIRCUIT
RESISTOR (CURRENT SENSOR) (A4P)
RESISTOR
RESISTOR (CURRENT LIMITING)
THERMISTOR (AIR) (A1P)
THERMISTOR (FIN) (A3P)
THERMISTOR (SUCTION)
THERMISTOR (M1C DISCHARGE)
THERMISTOR (HEAT EXC. DEICER)
THERMISTOR (LIQ. PIPE)
THERMISTOR (ACCUMULATOR)
PRESSURE SENSOR (HIGH)
PRESSURE SENSOR (LOW)

outdoor (F1) (F2)


indoor (F1) (F2)

S1PH
V1CP
V1R
V2R
X1A, X2A
X1M
X1M
Y1E
Y1S
Y2S
Y3S
Y4S
Z1C~5C
Z1F

X21A

X32A

X31A

X18A

HAP

NOTE) 4

NOTE) 5

X1M
TO IN/D UNIT TO OUT/D UNIT
F1 F2 F1 F2

OFF

ON DS1

BS1 BS2 BS3 BS4 BS5

H1P H2P H3P H4P H5P H6P H7P H8P

Y1E
M

OUTER SHELL

M1C

EL. COMPO. BOX

A4P

L1R

(BACK)

A2P

A3P

A5P

A1P
X1M

(FRONT)

X1M

X1A
X2A

EL. COMPO. BOX

M1F

3D061668

PRESSURE SWITCH (HIGH)


SAFETY DEVICES INPUT
POWER MODULE (A3P, A4P)
DIODE BRIDGE (A3P)
CONNECTOR (M1F)
TERMINAL STRIP (POWER SUPPLY)
TERMINAL STRIP (CONTROL) (A1P)
ELECTRONIC EXPANSION VALVE (MAIN)
SOLENOID VALVE (HOT GAS)
SOLENOID VALVE (OIL)
SOLENOID VALVE (FOUR WAY VALVE)
SOLENOID VALVE (INJECTION)
NOISE FILTER (FERRITE CORE)
NOISE FILTER (WITH SURGE ABSORBER)

S1NPH

S1NPL

R1T

W
V
LAYOUT OF M1C, M1F

TERMINAL OF M1C

2.1

RED
WHT
BLK

L1 L2 L3 N

Si34-804_C
Wiring Diagrams for Reference

2. Wiring Diagrams for Reference


Outdoor Unit

RXQ5PAY1

309

Wiring Diagrams for Reference

Si34-804_C

3D069664

RXQ8PAY1

310

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D069665

RXQ10PAY1

Appendix

311

Wiring Diagrams for Reference

Si34-804_C

3D069666

RXQ12PAY1

312

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D069667

RXQ14PA / 16PA / 18PAY1

Appendix

313

Wiring Diagrams for Reference

2.2

Si34-804_C

Field Wiring
3D051452N

RXQ5PA / 8PA / 10PA / 12PA / 14PA / 16PA / 18PAY1

314

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D052261J

RXQ20PA / 22PA / 24PA / 26PA / 28PA / 30PA / 32PAY1

Appendix

315

Wiring Diagrams for Reference

Si34-804_C

3D052262J

RXQ34PA / 36PA / 38PA / 40PA / 42PA / 44PA / 46PA / 48PA / 50PA / 52PA / 54PAY1

316

Appendix

X33A

A1P
X2M

A2P

CN1

KPR

R1T

X16A

X27A

F1U

X25A

Y1E

X7A

YLW

YLW

Z1F
C1

+
PS

X18A

MS
3~

N=1

X35A
NOTE) 3

HAP

X17A

R3T

M1S

MSW

X36A

X33A
NOTE) 3

X30A

X24A
NOTE) 3

X15A

S1L

BLK

BLU

ORG

YLW

WHT

PNK

X2A

A3P

X1A

X1A

A4P
H1P
H2P BS1
H3P
H4P
H5P
H6P

P1
X1M

P2

F1

MS
3~
25~80-CLASS

M1F

WHT

Z1C
N=1

TRANSMISSION WIRING
CENTRALIZED REMOTE CONTROLLER
NOTE) 2
P2
WIRED REMOTE
P1 R1T
CONTROLLER
SS1

F2

X20A

INPUT FROM
NOTE) 4
OUTSIDE

T1

T2

RECEIVER/DISPLAY UNIT

SS2

SS1

3D059890A

4. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR


ON/OFF CONTROL OPERATION CAN BE SELECTED BY THE REMOTE
CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.
5. CONFIRM THE METHOD OF SETTING THE SELECTOR SWITCH (SS1, SS2) BY
INSTALLATION MANUAL AND ENGINEERING DATA, ETC.
6. SYMBOLS SHOWS AS FOLLOWS:
RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW GRN : GREEN
ORG : ORANGE BRN : BROWN PNK : PINK GRY : GRAY BLU : BLUE

100, 125-CLASS

M1F

Z1C

X20A

V1R +

M1P

M
~

K1R

R4T

: TERMINAL
,
: CONNECTOR
: FIELD WIRING
2. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT
IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
INSTALLATION MANUAL.
3. X24A, X33A AND X35A ARE CONNECTED WHEN THE OPTIONAL
ACCESSORIES ARE BEING USED.

CONTROL BOX

X35A

A2P

WHT

GRN/YLW

RED

X2M

WHT
ORG
BRN
BLU

POWER SUPPLY
~220-240V
50Hz

A1P

R2T

RED

GRN

WHT
ORG
BRN
BLU

Appendix
RED

2.3

NOTES)
1.

INDOOR UNIT
H1P LIGHT EMITTING DIODE
(ON-RED)
A1P PRINTED CIRCUIT BOARD
A2P PRINTED CIRCUIT BOARD H2P LIGHT EMITTING DIODE
C1 CAPACITOR
(TIMER-GREEN)
F1U FUSE (F, 5A, 250V) H3P LIGHT EMITTING DIODE
(FILTER SIGN-RED)
HAP LIGHT EMITTING DIODE
(SERVICE MONITOR GREEN) H4P LIGHT EMITTING DIODE
(DEFROST-ORANGE)
K1R MAGNETIC RELAY
KPR MAGNETIC RELAY (M1P) SS1 SELECTOR SWITCH
(MAIN/SUB)
M1F MOTOR (INDOOR FAN)
M1P MOTOR (DRAIN PUMP) SS2 SELECTOR SWITCH
(WIRELESS ADDRESS SET)
M1S MOTOR (SWING FLAP)
R1T THERMISTOR (AIR) CONNECTOR FOR OPTIONAL PARTS
R2T THERMISTOR (COIL LIQUID) X24A CONNECTOR (WIRELESS
REMOTE CONTROLLER)
R3T THERMISTOR (COIL GAS)
R4T THERMISTOR PTC X33A CONNECTOR
(ADAPTOR FOR WIRING)
S1L FLOAT SWITCH
V1R DIODE BRIDGE
X35A CONNECTOR (GROUP
CONTROL ADAPTOR)
X1M TERMINAL STRIP
WIRED REMOTE CONTROLLER
X2M TERMINAL STRIP
R1T THERMISTOR (AIR)
Y1E ELECTRONIC
EXPANSION VALVE SS1 SELECTOR SWITCH (MAIN/SUB)
Z1C FERRITE CORE
Z1F NOISE FILTER
PS POWER SUPPLY CIRCUIT
RECEIVER/DISPLAY UNIT
(ATTACHED TO WIRELESS
X24A
REMOTE CONTROLLER)
A3P PRINTED CIRCUIT BOARD
X1M
A4P PRINTED CIRCUIT BOARD
BS1 PUSH BUTTON (ON/OFF)

Si34-804_C
Wiring Diagrams for Reference

Indoor Unit

FXFQ25P / 32P / 40P / 50P / 63P / 80P / 100P / 125PVE

317

Wiring Diagrams for Reference

Si34-804_C

3D064843

FXZQ20MVE / FXZQ25MVE / FXZQ32MVE / FXZQ40MVE / FXZQ50MVE

318

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D039556A

FXCQ20M / 25M / 32M / 63MVE

Appendix

319

Wiring Diagrams for Reference

Si34-804_C

3D039557A

FXCQ40M / 50M / 80M/ 125MVE

320

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D039564C

FXKQ25MA / 32MA / 40MA / 63MAVE

Appendix

321

TRANSFORMER (220V/22V)

PHASE CONTROL CIRCUIT

TERMINAL BLOCK

TERMINAL BLOCK

ELECTRONIC EXPANSION VALVE

T1R

V1TR

X1M

X2M

Y1E

SELECTOR SWITCH (MAIN/SUB)

SS1

: CONNECTOR

: TERMINAL

Z2C

Z1C

X2M

X16A

CONTROL BOX

T1R

C1

A1P

X18A

~220-240V
50Hz

POWER
SUPPLY

Y1E

GRN
/YLW

BLU

RED

S1L

X2M

X8A

X7A

X31A

F1U

X13A

R1T

X25A

KPR

X1A

X12A

R2T

M
~

M1P

T1R

X11A

R3T

HAP

X3A

X4A

X27A

X18A

X30A

V1TR

X16A

A1P

BLK

RED

GRY
PRP
BLU

Z2C
N=3

Z1C
N=3

C1

X1M
PNK T2
WHT T1
YLW F2
ORG F1
BLU P2
BLK P1

M1F

M
~
Q1M

3D060547

NOTE) 5
INPUT FROM
OUTSIDE
TRANSMISSION
WIRING CENTRALIZED
REMOTE CONTROLLER
NOTE) 3
P2 R1T
P1
SS1
WIRED REMOTE
CONTROLLER

2.
: FIELD WIRING
3. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN

NOTES)
1.

X18A

X1M

CONNECTOR (ADAPTOR FOR WIRING)

CONNECTOR (WIRING ADAPTOR


FOR ELECTRICAL APPENDICES)

X16A

CONNECTOR FOR OPTIONAL PARTS

THERMISTOR (AIR)

R1T

WIRED REMOTE CONTROLLER

Z1C Z2C NOISE FILTER (FERRITE CORE)

THERMISTOR (COIL-2)

FLOAT SWITCH

S1L

THERMISTOR (COIL-1)

R2T

R3T

THERMISTOR (AIR)

R1T

MOTOR (INDOOR FAN)

M1F

MOTOR (DRAIN PUMP)

MAGNETIC RELAY (M1P)

KPR

THERMAL PROTECTOR (M1F EMBEDDED)

LIGHT EMITTING DIODE


(SERVICE MONITOR GREEN)

HAP

Q1M

FUSE (F5A/250V)

F1U

M1P

PRINTED CIRCUIT BOARD

CAPACITOR (M1F)

YLW

C1

WHT

322

A1P

Wiring Diagrams for Reference


Si34-804_C

FXDQ20PB / 25PB / 32PB


FXDQ40NB / 50NB / 63NBVE (with Drain Pump)

Appendix

CAPACITOR (M1F)

FUSE (F5A/250V)

LIGHT EMITTING DIODE


(SERVICE MONITOR GREEN)

MOTOR (INDOOR FAN)

THERMAL PROTECTOR (M1F EMBEDDED)

THERMISTOR (AIR)

THERMISTOR (COIL-1)

THERMISTOR (COIL-2)

TRANSFORMER (220V/22V)

PHASE CONTROL CIRCUIT

TERMINAL BLOCK

TERMINAL BLOCK

ELECTRONIC EXPANSION VALVE

F1U

HAP

M1F

Q1M

R1T

R2T

R3T

T1R

V1TR

X1M

X2M

Y1E

SELECTOR SWITCH (MAIN/SUB)

SS1

: CONNECTOR

: TERMINAL

Z2C

Z1C

X2M

X16A

CONTROL BOX

T1R

C1

A1P

X18A

~220-240V
50Hz

POWER
SUPPLY

Y1E

X2M

GRN
/YLW

BLU

RED

X7A

X31A

F1U

X13A

R1T

X1A

X12A

R2T

T1R
t

X11A

R3T

X3A

HAP

X4A

X27A

X18A

X30A

V1TR

X16A

A1P

BLK

RED

GRY
PRP
BLU

Z2C
N=3

Z1C
N=3

C1

X1M
PNK T2
WHT T1
YLW F2
ORG F1
BLU P2
BLK P1

M1F

M
~
Q1M

3D060548

NOTE) 5
INPUT FROM
OUTSIDE
TRANSMISSION
WIRING CENTRALIZED
REMOTE CONTROLLER
NOTE) 3
P2 R1T
P1
SS1
WIRED REMOTE
CONTROLLER

2.
: FIELD WIRING
3. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN

NOTES)
1.

CONNECTOR (WIRING ADAPTOR


FOR ELECTRICAL APPENDICES)

X18A

X1M

CONNECTOR (ADAPTOR FOR WIRING)

X16A

CONNECTOR FOR OPTIONAL PARTS

THERMISTOR (AIR)

R1T

WIRED REMOTE CONTROLLER

Z1C Z2C NOISE FILTER (FERRITE CORE)

PRINTED CIRCUIT BOARD

YLW

C1

WHT

Appendix

A1P

Si34-804_C
Wiring Diagrams for Reference

FXDQ20PB / 25PB / 32PB


FXDQ40NB / 50NB / 63NBVET (without Drain Pump)

323

Wiring Diagrams for Reference

Si34-804_C

3D058783D

FXMQ20P / 25P / 32P / 40P / 50P / 63P / 80P / 100P / 125P / 140PVE

324

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D039621C

FXMQ200MA / 250MAVE

Appendix

325

Wiring Diagrams for Reference

Si34-804_C

3D039801D

FXHQ32MA / 63MA / 100MAVE

326

Appendix

POWER CIRCUIT

(WIRELESS ADDRESS SET)

SS2 SELECTOR SWITCH

SS1 SELECTOR SWITCH (MAIN/SUB)

(DEFROST-ORANGE)

H4P LIGHT EMITTING DIODE

(FILTER SIGN-RED)

H3P LIGHT EMITTING DIODE

(TIMER-GREEN)

H2P LIGHT EMITTING DIODE

H1P LIGHT EMITTING DIODE (ON-RED)

BS1 PUSH BUTTON (ON/OFF)

A3P PRINTED CIRCUIT BOARD

A2P PRINTED CIRCUIT BOARD

TO WIRELESS REMOTE CONTROLLER)

RECEIVER/DISPLAY UNIT (ATTACHED

PC

Y1E ELECTRONIC EXPANSION VALVE

X2M TERMINAL BLOCK (POWER)

X1M TERMINAL BLOCK (CONTROL)

R3T THERMISTOR (COIL GAS PIPE)

R2T THERMISTOR (COIL LIQUID PIPE)

R1T THERMISTOR (AIR)

M1S MOTOR (SWING FLAP)

M1F MOTOR (INDOOR FAN)

(SERVICE MONITOR GREEN)

HAP LIGHT EMITTING DIODE

F1U FUSE( B , 3A, 250V)

SIDE

FRONT

X1M

X2M

X27A

X20A

F1U

: CONNECTOR
: CONNECTOR

: FIELD WIRING

M1F

MS
3~

PC

: TERMINAL

A1P
HAP

N WHT

L RED

A1P

X2M GRN/YLW

PC

M1S

MSW

X36A

NE

GRN

HAP

Y1E

X7A

X35A

X19A

X18A

X14A

WHT

X15A

SS1 SELECTOR SWITCH (MAIN/SUB)

R1T THERMISTOR (AIR)

X35A

X15A

CONNECTOR (GROUP CONTROL ADAPTOR)

CONNECTOR (FLOAT SWITCH)

CONNECTOR FOR OPTIONAL PARTS

SHOWS SHORT CIRCUIT CONNECTOR.

WIRED REMOTE CONTROLLER

4.

X1A

A3P
H1P
BS1
H2P
H3P
H4P

CONNECTING.

ENGINEERING DATA AND CATALOGS, ETC. BEFORE

ACCORDING TO THE COMBINATION SYSTEM, CONFIRM

6. REMOTE CONTROLLER MODEL VARIES

INSTALLATION MANUAL ATTACHED THE UNIT.

CONTROLLER. IN DETAILS, REFER TO THE

OPERATION CAN BE SELECTED BY REMOTE

OUTSIDE, FORCED OFF OR ON/OFF CONTROL

REMOTE CONTROLLER KIT IS BEING USED.

8. X24A IS CONNECTED WHEN THE WIRELESS

3D034206D

ATION MANUAL AND ENGINEERING DATA, ETC.

AND WIRELESS REMOTE CONTROLLER BY INSTALL-

SWITCH (SS1, SS2) OF WIRED REMOTE CONTROLLER

PNK : PINK YLW : YELLOW BLK : BLACK ORG : ORANGE BRN : BROWN BLU : BLUE 7. CONFIRM THE METHOD OF SETTING THE SELECTOR

3. SYMBOLS SHOWS AS FOLLOWS: RED : RED WHT : WHITE GRN : GREEN

IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.

PNK
WHT
YLW
ORG
BLU
BLK

X1A

SS2

SS1

RECEIVER/DISPLAY UNIT

X2A

A2P

(WIRELESS REMOTE CONTROLLER)


NOTE) 5
T2
INPUT FROM OUTSIDE
T1
TRANSMISSION WIRING
F2
F1
CENTRALIZED REMOTE CONTROLLER
P2
NOTE) 2
P1
SS1
P2
X1M
WIRED REMOTE
P1 R1T CONTROLLER

X24A
NOTE) 8

A1P

5. WHEN CONNECTING THE INPUT WIRES FROM

X30A

NOTE) 8

X24A

R1T

R2T

R3T

2. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT

1.

X1M

X2M

CONTROL BOX
(INDOOR UNIT)

HAP

A1P

NOTES)

L
N

220~240V
~
50Hz

POWER SUPPLY

WHT
ORG
BRN
BLU

INDOOR UNIT

RED

Appendix

A1P PRINTED CIRCUIT BOARD

Si34-804_C
Wiring Diagrams for Reference

FXAQ20MA / 25MA / 32MAVE / 40MA / 50MA / 63MAVE

327

Wiring Diagrams for Reference

Si34-804_C

3D039826F

FXLQ20MA / 25MA / 32MA / 40MA / 50MA / 63MAVE


FXNQ20MA / 25MA / 32MA / 40MA / 50MA / 63MAVE

328

Appendix

Si34-804_C

Wiring Diagrams for Reference

3D044996D

FXMQ125MF / 200MF / 250MFV1

Appendix

329

List of Electrical and Functional Parts

Si34-804_C

3. List of Electrical and Functional Parts


3.1

Outdoor Unit

3.1.1 RXQ5PAY1~8PAY1
Item

Compressor

Name

Symbol

M1C

STD 1

Type
OC protection
device

M2C

STD 2

Type
OC protection
device

M3C

M1F

Electronic expansion valve (Subcooling)

Y2E

Others

330

RXQ8PAY1
JT1GCVDKYR@T

Inverter

OC protection
device
Electronic expansion valve (Main)

Temperature
protection

RXQ5PAY1
JT1GCVDKYR@SB

Type
OC protection
device

Fan motor

Pressure
protection

Model

Y1E

14.7 A

1.15 A

3A

Fully closed: 0pls

Fully open: 480 pls


Fully closed: 0 pls
Fully open: 480 pls

+0

For M1C

S1PH

High pressure
For M2C
switch

S2PH

For M3C
Low pressure sensor

S3PH
S1NPL

OFF: 0.07 MPa

R3T

OFF: 135C

R1T

OFF: 93C

For main PCB

A1P
A2P

250 V, 15 A
250 V, 3 A

For Noise filter


PCB

F1U

250 V AC 5 A Class B

Discharge gas temperature


protection
(Discharge pipe thermistor)
Radiation fin temperature
protection
(Radiation fin thermistor)

Fuse

OFF: 4.0 0.12 MPa

ON: 3.00.15 MPa

Appendix

Si34-804_C

List of Electrical and Functional Parts

3.1.2 RXQ10PAY1~12PAY1
Item

Name

Symbol

Type
Inverter

Compressor

OC protection
device
Type

M1C

STD 1

OC protection
device
Type

M2C

STD 2

OC protection
device
OC protection
device

M3C

Fan motor

Electronic expansion valve (Main)


Electronic expansion valve (Subcooling)

Pressure
protection

M1F

15.0 A

3A

1.15 A

For M1C

S1PH

OFF: 4.0 0.12 MPa

High pressure
For M2C
switch

S2PH

OFF: 4.0 0.12 MPa

Low pressure sensor


Discharge gas temperature
protection
(Discharge pipe thermistor)
Radiation fin temperature
protection
(Radiation fin thermistor)

Fuse
For Noise filter
PCB

Appendix

JT170G-KYE@T

Fully closed: 0 pls


Fully closed: 0 pls

For main PCB


Others

14.7 A

Y1E
Y2E

For M3C

Temperature
protection

Model
RXQ10PAY1
RXQ12PAY1
JT1GCVDKYR@T

Fully open: 480 pls


Fully open: 480 pls

+0
+0

ON: 3.00.15 MPa


ON: 3.00.15 MPa

S3PH

S1NPL

OFF: 0.07 MPa

R3T

OFF: 135C

R1T

OFF: 93C

A1P

250 V, 15 A

A2P

250 V, 3 A

F1U

250 V AC 5 A Class B

331

List of Electrical and Functional Parts

Item

Compressor

Name

Si34-804_C

Symbol

Inverter

Type
OC protection
device

M1C

STD 1

Type
OC protection
device

M2C

STD 2

Type
OC protection
device

M3C

Model
RXQ16PAY1

RXQ14PAY1

RXQ18PAY1

JT1GCVDKYR@T
14.7 A
JT170G-KYE@T
15.0 A
JT170G-KYE@T
15.0 A

OC protection
device
Electronic expansion valve (Main)

M1F

1.15 A

Y1E

Fully closed: 0 pls

Fully open: 480 pls

Electronic expansion valve (Subcooling)

Y2E

Fully closed: 0 pls

Fully open: 480 pls

Fan motor

Pressure
protection

Others

332

+0
OFF: 4.0 0.12 MPa
+0
OFF: 4.0 0.12 MPa

For M1C

S1PH

High pressure For M2C


switch

S2PH

For M3C

S3PH

+0
OFF: 4.0 0.12 MPa

S1NPL

OFF: 0.07 MPa

R3T

OFF: 135C

R1T

OFF: 93C

For main PCB

A1P
A2P

250 V, 15 A
250 V, 3 A

For Noise filter


PCB

F1U

250 V AC 5 A Class B

Low pressure sensor

Temperature
protection

3A

Discharge gas temperature


protection
(Discharge pipe thermistor)
Radiation fin temperature
protection
(Radiation fin thermistor)

Fuse

ON: 3.00.15 MPa


ON: 3.00.15 MPa

ON: 3.00.15 MPa

Appendix

Si34-804_C

3.2

List of Electrical and Functional Parts

Indoor Side

3.2.1 Indoor Unit


Parts Name
Remote
Controller

Motors

Symbol

Wired Remote
Controller
Wireless Remote
Controller
Fan Motor

M1F

Drain Pump

M1P

Swing Motor

M1S

Symbol

Capacitor, fan motor

R1T
R3T
R2T

FXZQ20
MVE

FXZQ25
MVE

Model
FXZQ32
MVE

FXZQ40
MVE

FXZQ50
MVE

Remark

Option
BRC7E530
AC 220~240V 50Hz
155W 4P
Thermal Fuse OFF : 1305 / ON : 8020
4.0 F 400VAC
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
MP35HCA [3P080801-1]
AC200~240V
ST8601A-1 4 L250
20k (25C)
ST8605-3 8 L630
20k (25C)
ST8602A-3 6 L630
20k (25C)
FS-0211
250V 5A 5.2
TR22H21R8

M1F
C1
M1P

Swing Motor

M1S

Thermistor (Suction Air)

R1T

(for Heat
Thermistors Thermistor
Exchanger High Temp.)
Thermistor (Heat
Exchanger)
Float Switch
Others
Fuse
Transformer

R3T

S1L
F1U
T1R

Parts Name

Symbol

R2T

FXCQ
20MVE

FXCQ
25MVE

FXCQ
32MVE

Wired Remote
Controller
Wireless Remote
Controller

Model
FXCQ
FXCQ
40MVE 50MVE

FXCQ
63MVE

FXCQ
80MVE

FXCQ Remark
125MVE

BRC1E61
Option
BRC7C67

M1F

1 10 W

1 15 W
Thermal Fuse 152C

Motors
Drain Pump

M1P

Swing Motor

M1S

Thermistor (Suction Air)

R1T

(for Heat
Thermistors Thermistor
Exchanger High Temp.)
Thermistor (Heat
Exchanger)
Float Switch
Others
Fuse
Transformer

R3T

Appendix

DC 320 V 120 W 8P

BRC1E61

Drain Pump

Fan Motor

FXFQ100 FXFQ125 Remark


PVE
PVE

FXFQ80
PVE

DC 280 V 56 W 8P
AC 220-240 V (50 Hz)
PLD-12230DM
Thermal Fuse 145C
MP35HCA [3P080801-1]
Stepping Motor DC 12 V
In PCB A2P or wired remote controller
ST8605-14 8 L1000
20 k (25C)
ST8602A-15 6 L1000
20 k (25C)
FS-0211B
250 V 5 A 5.2

Wired Remote
Controller
Wireless Remote
Controller
Fan Motor

Model
FXFQ50 FXFQ63
PVE
PVE

Option

Parts Name

Remote
Controller

FXFQ40
PVE

BRC7F635F

S1L
F1U
TFu
T1R

Motors

FXFQ32
PVE

BRC1E61

Thermistor (Suction Air)


Thermistor (for Heat
Thermistors Exchanger High Temp.)
Thermistor (Heat
Exchanger)
Float Switch
Fuse
Others
Thermal Fuse
Transformer

Remote
Controller

FXFQ25
PVE

R2T
S1L
F1U
T1R

AC 220~240 V 50 Hz
1 20 W
1 30 W 1 50 W 1 85 W

Thermal protector 135C

: OFF

87C : ON

AC 220-240 V (50 Hz)


PLD-12230DM
Thermal Fuse 145C
MT8-L[3PA07509-1]
AC 200~240 V
ST8601-6 4 L1250
20 k (25C)
ST8605-6 8 L1250
20 k (25C)
ST8602A-5 6 L1000
20 k (25C)
FS-0211B
250 V 5 A 5.2
TR22H21R8

333

List of Electrical and Functional Parts

Si34-804_C

Model
Parts Name

Remote
Controller

Symbol

FXKQ
25MAVE

FXKQ
32MAVE

FXKQ
40MAVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C63

Remark

FXKQ
63MAVE

Option

AC 220~240 V 50 Hz
Fan Motor

1 15 W 4P

M1F

1 20 W 4P

Thermal Fuse 146C


Motors
Drain Pump

M1P

AC 220-240 V (50 Hz)


PLD-12200DM
Thermal Fuse 145C

Swing Motor

M1S

MP35HCA [3P080801-1]
AC 200~240 V

Thermistor (Suction Air)

R1T

ST8601-13 4 L630
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-7 8 L1600
20 k (25C)

R2T

ST8602A-7 6 L1600
20 k (25C)

Thermistor (Heat
Exchanger)
Others

1 45 W 4P

Thermal protector 120C : OFF


ON

Float Switch

S1L

FS-0211B

Fuse

F1U

250 V 5 A 5.2

Transformer

T1R

TR22H21R8

105C :

Model
Parts Name

Remote
Controller

Symbol

FXDQ
20PBVE(T)

FXDQ
25PBVE(T)

FXDQ
32PBVE(T)

FXDQ
40NBVE(T)

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C66

FXDQ
50NBVE(T)

FXDQ
63NBVE(T)

Remark

Option
AC 220~240 V 50 Hz

Fan Motor

M1F

1 62 W

1 130 W

Thermal protector
130C: OFF, 83C: ON

Motors
Drain Pump

M1P

AC 220-240 V (50 Hz)


PLD-12230DM
Thermal Fuse 145C

Thermistor (Suction Air)

R1T

ST8601-1 4 L=250
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-4 8 L=800
20 k (25C)

R2T

ST8602A-4 6 L=800
20 k (25C)

Thermistor (Heat
Exchanger)
Others

Float Switch

S1L

FS-0211E

Fuse

F1U

250 V 5 A 5.2

Transformer

T1R

TR22H21R8

only for FXDQ20~32PBVE (with Drain Pump Type)

334

Appendix

Si34-804_C

List of Electrical and Functional Parts

Parts Name

Remote
Controller

Model
Symbol FXMQ FXMQ FXMQ FXMQ FXMQ FXMQ FXMQ FXMQ
FXMQ
FXMQ Remark
20PVE 25PVE 32PVE 40PVE 50PVE 63PVE 80PVE 100PVE 125PVE 140PVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C65

Fan Motor

M1F

DC 280 V 140 W 8P

Drain Pump

M1P

AC 220-240 V (50 Hz)


PLD-12230DM
Thermal protector 145C

Thermistor (Suction Air)

R1T

ST8601-3 L630
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-14 8 L1000
20 k (25C)

R2T

ST8602A-6 8 L1250
20 k (25C)

Motors

Thermistor (for Heat


Exchanger)

Others

Float Switch

S1L

FS-0211B

Fuse (A1P)

F1U

250 V 3.15 A

Fuse (A2P, A3P)

F3U
F4U

250 V 6.3 A

Fuse (A2P)

F2U

Parts Name

Remote
Controller

Motors

Symbol

250 V 5 A

Model
FXMQ200MAVE

FXMQ250MAVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C64

Fan Motor

M1F

Capacitor for Fan Motor

C1R

AC 220~240 V 50 Hz
1 380 W2
10 F 400 V

12 F 400 V

Thermistor (Suction Air)

R1T

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605A-5
8 L1000

Thermistor (Heat
Exchanger)

R2T

ST8602A-6
6 L1250

Float switch

S1L

FS-0211

Fuse

F1U

250 V 5 A 5.2

Transformer

T1R

TR22H21R8

Appendix

Remark

Option

ST8601A-13
4 L630

Others

DC 373 V 350 W 8P

335

List of Electrical and Functional Parts

Si34-804_C

Model
Parts Name

Remote
Controller

Symbol

FXHQ
32MAVE

FXHQ
63MAVE

Wired Remote
Controller

FXHQ
100MAVE

BRC1E61

Wireless Controller

Remark
Option

BRC7E66
AC 220~240 V 50 Hz

Fan Motor

1 63 W

M1F

1 130 W

Thermal protector 130C : OFF

Motors
Capacitor for Fan Motor

3.0 F-400 V

C1R

80C : ON
9.0 F-400 V

Swing Motor

M1S

MT8-L[3P058751-1]
AC 200~240 V

Thermistor (Suction Air)

R1T

ST8601A-1 4 L250
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-6 8 L = 1250
20 k (25C)

ST8605-6 8 L = 1250
20 k (25C)

R2T

ST8602A-6 6 L = 1250
20 k (25C)

ST8602A-6 6 L = 1250
20 k (25C)

Thermistor (Heat
Exchanger)
Others

Fuse

F1U

250 V 5 A 5.2

Transformer

T1R

TR22H21R8

Model
Parts Name

Remote
Controller

Symbol

FXAQ
20MAVE

FXAQ
25MAVE

FXAQ
32MAVE

FXAQ
40MAVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC7E619

FXAQ
50MAVE

FXAQ
63MAVE

Remark

Option
AC 220~240 V 50 Hz

Fan Motor

M1F

Motors

1 40 W

1 43 W

Thermal protector 130C : OFF


MP24 [3SB40333-1]
AC 200~240 V

MSFBC20C21 [3SB40550-1]
AC 200~240 V

Swing Motor

M1S

Thermistor (Suction Air)

R1T

ST8601-2 4 L400
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-2 8 L400
20 k (25C)

R2T

ST8602-2 6 L400
20 k (25C)

Thermistor (for Heat


Exchanger)
Others

336

80C : ON

Float Switch

S1L

OPTION

Fuse

F1U

250 V 5A 5.2

Appendix

Si34-804_C

List of Electrical and Functional Parts

Model
Parts Name

Remote
Controller

Symbol

FXLQ
20MAVE

FXLQ
25MAVE

FXLQ
32MAVE

FXLQ
40MAVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C64

FXLQ
50MAVE

FXLQ
63MAVE

Remark

Option
AC 220~240 V 50 Hz

Motors

Fan Motor

M1F

1 15 W

1 25 W
Thermal protector 135C : OFF

1.0 F-400 V

0.5 F-400 V 1.0 F-400 V 1.5 F-400 V 2.0 F-400 V

Capacitor for Fan Motor

C1R

Thermistor (Suction Air)

R1T

ST8601-6 4 L1250
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-9 8 L2500
20 k (25C)

R2T

ST8602A-9 6 L2500
20 k (25C)

Fuse

F1U

AC 250 V 5 A

Transformer

T1R

TR22H21R8

Thermistor (for Heat


Exchanger)
Others

1 35 W
120C : ON

Model
Parts Name

Remote
Controller

Symbol

FXNQ
20MAVE

FXNQ
25MAVE

FXNQ
32MAVE

FXNQ
40MAVE

Wired Remote
Controller

BRC1E61

Wireless Remote
Controller

BRC4C64

FXNQ
50MAVE

FXNQ
63MAVE

Remark

Option
AC 220~240 V 50 Hz

Motors

Fan Motor

M1F

1 15 W

1 25 W
Thermal protector 135C : OFF

1.0 F-400 V

0.5 F-400 V 1.0 F-400 V 1.5 F-400 V 2.0 F-400 V

Capacitor for Fan Motor

C1R

Thermistor (Suction Air)

R1T

ST8601-6 4 L1250
20 k (25C)

(for Heat
Thermistors Thermistor
Exchanger High Temp.)

R3T

ST8605-9 8 L2500
20 k (25C)

R2T

ST8602A-9 6 L2500
20 k (25C)

Fuse

F1U

AC 250 V 5 A

Transformer

T1R

TR22H21R8

Thermistor (for Heat


Exchanger)
Others

Parts Name

Remote
Controller

Symbol

1 35 W
120C : ON

Model
FXMQ125MFV1

Wired Remote
Controller

FXMQ200MFV1

FXMQ250MFV1

Remark

BRC1E61

Wireless Remote
Controller

Option

AC 200~240 V 50 Hz

Fan Motor

1 380 W

M1F

Motors

Solenoid
valve

Thermistors

Others

Appendix

Thermal protector 135C : OFF


10 F
400 V2

87C : ON

10 F
400 V

Capacitor for Fan Motor

C1R

Solenoid valve
(Hot gas)

Y1S

Body: VPV-603D
Coil: NEV-MOAJ532C1 AC 220-240 V

Thermistor (Suction Air)

R1T

ST8601-13 4 L=630
20 k (25C)

Thermistor (for Heat


Exchanger High Temp.)

R3T

ST8605-6 8 L=1250
20 k (25C)

Thermistor (Heat
Exchanger)

R2T

ST8602A-2 6 L=1250
20 k (25C)

Thermistor (for
discharge air)

R4T

ST8605-8 L=2000
20 k (25C)

Float switch

S1L

Option

Fuse

F1U

250 V 5 A 5.2

Transformer

T1R

TR22H21R8

16 F
400 V

337

Option List

Si34-804_C

4. Option List
4.1

Option List of Controllers

Operation Control System Optional Accessories


No.
1
2
3
4
5
6-1
6-2
7
8
9
9-1
10
10-1
10-2
11
12
13

Type
Item
Wireless
Wired
Wired remote controller
with weekly schedule timer
Simplified remote
controller
Remote controller for
hotel use
Adaptor for wiring
Wiring adaptor for
electrical appendices (1)
Wiring adaptor for
electrical appendices (2)
Remote sensor
Installation box for
adaptor PCB
Centralized remote
controller
Electrical box with earth
terminal (3 blocks)
Unified on/off controller
Electrical box with earth
terminal (2 blocks)
Noise filter (for
electromagnetic interface
use only)
Schedule timer
External control adaptor
for outdoor unit (Must be
installed on indoor units)
Remote
controller

FXFQ-P

FXCQ-M

FXKQ-MA

FXDQ-NB
FXDQ-PB

FXUQ-M

FXSQ-M

BRC7F635F

BRC7C67

BRC4C63

BRC4C66

BRC7C529W

BRC4C64
BRC1E61

FXMQ-MA

FXMQ-P
BRC4C66

FXHQ-MA FXAQ-MA
BRC7E66

BRC7E619

FXLQ-MA
FXNQ-MA
BRC4C64

BRC1D61

Note 8
BRC2C51

Note 8
BRC2C51

Note 8
BRC2C51

BRC3A61

KRP1C63

KRP1B61

KRP1B61

KRP1B56

KRP1B61

BRC3A61
KRP1C64

KRP1C3

KRP1B61

KRP2A62

KRP2A61

KRP2A61

KRP2A53

KRP2A62

KRP2A61

KRP2A61

KRP2A62

KRP2A61

KRP2A61

KRP4AA53

KRP4A51

KRP4A51

KRP4A54

KRP4A53

KRP4A51

KRP4AA51

KRP4A52

KRP4A51

KRP4A51

KRCS01-4B
Note 2, 3
KRP1H98

KRCS01-1
Note 2, 3
KRP1B96

Note 3
KRP1C93

KRCS01-1
Note 2, 3
KRP4A93

DTA104A61

DTA104A61

KRCS01-1

Note 4, 6
KRP1B101

KRP1B97

Note 5
KRP4A91

KRCS01-4B
Note 2, 3
KRP4A96

BRC3A61

DCS302CA61
KJB311AA
DCS301BA61
KJB212AA
KEK26-1A
DST301BA61

DTA104A62

DTA104A61

Interface adaptor for


SkyAir series

DTA104A61

DTA104A53

DTA104A61

Note 7
DTA102A52

DTA104A61 DTA104A62

Note:
1. Installation box (No.8) is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
7. This adaptor is required when connecting with optional controller for centralized control.
8. BRC2A51 is also available.
Various PCB
No.

Part name

Adaptor for wiring

DIII-NET Expander Adaptor

338

Model No.
KRP1B56
KRP1B57
KRP1B59
KRP1B61
KRP1C3
DTA109A51

Function
PCB when equipped with auxiliary electric heater in the indoor unit.
Up to 1024 units can be centrally controlled in 64 different groups.
Wiring restrictions (max. length: 1000m, total wiring length: 2000m, max. number of
branches: 16) apply to each adaptor.

Appendix

Si34-804_C

Option List

System Configuration
No.

Item

Model No.

Residential centralized remote


controller

Centralized remote controller

2-1
3

Note *2
DCS303A51
DCS302CA61

Electrical box with earth terminal (3 blocks)


Unified ON/OFF controller

KJB311AA

Up to 64 groups of indoor units (128 units) can be connected, and ON/OFF, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
to 2 controllers in one system.

DCS301BA61

3-1

Electrical box with earth terminal (2 blocks)

KJB212AA

3-2

Noise filter (for electromagnetic


interface use only)

KEK26-1A

Schedule timer

Interface adaptor for


SkyAir-series

For SkyAir,
FD(Y)M-FA,
FDY-KA
FDYB-KA,
FVY(P)J-A

*DTA102A52

Central control
adaptor kit

For UAT(Y)K(A),FD-K

*DTA107A55

DST301BA61

Wiring adaptor for other air-conditioner

*DTA103A51

DIII-NET Expander Adaptor

DTA109A51

8-1

Function
Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD
panel. ON/OFF, temperature settings and scheduling can be controlled individually for
indoor units.

Mounting plate

KRP4A92

Up to 16 groups of indoor units (128 units) can be turned, ON/OFF individually or


simultaneously, and operation and error can be displayed. Can be used in combination with
up to 8 controllers.
Programmed time weekly schedule can be controlled by unified control for up to 64 groups
of indoor units (128 units). Can turn units ON/OFF twice per day.
Adaptors required to connect products other than those of the VRV System to the highspeed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on
the product unit to be controlled.
Up to 1024 units can be centrally controlled in 64 different groups.
Wiring restrictions (max. length : 1,000m, total wiring length : 2,000m, max. number of
branches : 16) apply to each adaptor.
Fixing plate for DTA109A51

Note:
1. Installation box for * adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralized control equipment.
Building Management System

1-3
1-4

2-1
2-2

3-1
3-2
4
5
6
7
8

Basic

Hardware

128 units
256 units
Number of
512 units
units to be
connected
768 units
1024 units
P.P.D.

Model No.

Function

DCS601C51

Air Conditioning management system that can be controlled by


a compact all-in-one unit.

DCS601A52
DCS002C51
DCS004A51

Additional 64 groups (10 outdoor units) is possible.


P. P. D.: Power Proportional Distribution function
Monitors and controls the air conditioning system using the
Internet and a Web browser application on a PC.

Wall embedded switch box.


KJB411A
DAM602B52
DAM602B51
conditioner management system that can be controlled by
DAM602B512 Air
personal computers.
DAM602B513
DAM602B514
DAM002A51 Power Proportional Distribution function

Web

DAM004A51

Eco

DAM003A51
DAM101A51
DEC101A51
DEC102A51

Optional DIII Ai unit


Di unit
Dio unit
Communication line

Option

Option Software

Contact/analog
signal

2-3
2-4
2-5
2-6

Basic

Hardware intelligent Touch


Controller
Hardware DIII-NET plus adaptor
P.P.D.
Software
Web

Electrical box with earth terminal (4 blocks)

intelligent
Manager III

1
1-1
1-2

Part name

intelligent Touch
Controller

No.

Monitors and controls the air conditioning system using the


Internet and a Web browser application on a PC.
ECO (Energy saving functions.)
External temperature sensor for intelligent Manager III.
8 pairs based on a pair of On/Off input and abnormality input.
4 pairs based on a pair of On/Off input and abnormality input.

*1 Interface for use in BACnet

DMS502B51

Interface unit to allow communications between VRV and BMS.


Operation and monitoring of air conditioning systems through
BACnet communication.

Optional DIII board

DAM411B51

Expansion kit, installed on DMS502B51, to provide 2 more DIIINET communication ports. Not usable independently.

Optional Di board

DAM412B51

Expansion kit, installed on DMS502B51, to provide 16 more


wattmeter pulse input points. Not usable independently.

*2 Interface for use in LONWORKS

DMS504B51

Interface unit to allow communications between VRV and BMS.


Operation and monitoring of air conditioning systems through
LONWORKS communication.

Parallel interface
Basic unit
Temperature
measurement units
Temperature
setting units
Unification adaptor for
computerized control

DPF201A51

Enables ON/OFF command, operation and display of error; can


be used in combination with up to 4 units.

DPF201A52

Enables temperature measurement output for 4 groups; 05VDC.

DPF201A53

Enables temperature setting input for 16 groups; 0-5VDC.

* DCS302A52

Interface between the central monitoring board and central


control units.

Note:
*1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE).
*2. LONWORKS is a registered trade mark of Echelon Corporation.
*3. Installation box for * adaptor must be procured on site.
Appendix

339

Option List

4.2

Si34-804_C

Option Lists (Outdoor Unit)

RXQ5 ~ 18PAY1(S)

Distributive
Piping

Optional accessories

REFNET header

REFNET joint

RXQ8PAY1(S)
RXQ10PAY1(S)

KHRP26M22H
(Max. 4 branch)

KHRP26M22H,
(Max. 4 branch)
KHRP26M33H
(Max. 8 branch)

KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch)
KHRP26M72H
(Max. 8 branch)

KHRP26A22T

KHRP26A22T,
KHRP26A33T

KHRP26A22T, KHRP26A33T,
KHRP26A72T

KWC26C160

KWC26C280

Outdoor unit multi connection piping kit


Central drain pan kit

RXQ12PAY1(S)
RXQ14PAY1(S)
RXQ16PAY1(S)
RXQ18PAY1(S)

RXQ5PAY1

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F

KWC26C450

C : 3D056901C

RXQ20 ~ 36PAY1(S)

Distributive
Piping

Optional accessories

REFNET header

KHRP26M22H
(Max. 4 branch),
KHRP26M33H
(Max. 8 branch),
KHRP26M72H
(Max. 8 branch)

REFNET joint

KHRP26A22T,
KHRP26A33T,
KHRP26A72T

KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H


(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)

KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T


BHFP22P100

Outdoor unit multi connection piping kit


Pipe size reducer
Central drain pan kit

RXQ30PAY1(S)
RXQ32PAY1(S)
RXQ34PAY1(S)
RXQ36PAY1(S)

RXQ24PAY1(S)
RXQ26PAY1(S)
RXQ28PAY1(S)

RXQ20PAY1(S)
RXQ22PAY1(S)

KHRP26M73TP, KHRP26M73HP
KWC26C280
KWC26C450

KWC26C4502

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F
C : 3D056901C

RXQ38 ~ 54PAY1(S)

Distributive
Piping

Optional accessories

RXQ38PAY1(S)
RXQ40PAY1(S)
RXQ42PAY1(S)
RXQ44PAY1(S)
RXQ46PAY1(S)

RXQ48PAY1(S)
RXQ50PAY1(S)
RXQ52PAY1(S)
RXQ54PAY1(S)

REFNET header

KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H


(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)

REFNET joint

KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T


BHFP22P151

Outdoor unit multi connection piping kit

KHRP26M73TP, KHRP26M73HP

Pipe size reducer


Central drain pan kit

KWC26C280
KWC26C4502

KWC26C4503

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F
C : 3D056901C

340

Appendix

Si34-804_C

Option List

RXQ16 ~ 18PAHY1(S)
RXQ16PAHY1(S)
RXQ18PAHY1(S)

Distributive
Piping

Optional accessories

KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch)
KHRP26M72H
(Max. 8 branch)

REFNET header
REFNET joint

KHRP26A22T, KHRP26A33T, KHRP26A72T


BHFP22P100

Outdoor unit multi connection piping kit


Central drain pan kit

KWC26C2802

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F
C : 3D053053A

RXQ24 ~ 30PAHY1(S)
Distributive
Piping

Optional accessories
REFNET header
REFNET joint

RXQ24PAHY1(S)

KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T


BHFP22P151

Outdoor unit multi connection piping kit

KHRP26M73TP, KHRP26M73HP

Pipe size reducer


Central drain pan kit

RXQ28PAHY1(S)

KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H


(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)

KWC26C2802
KWC26C450

KWC26C2803

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F
C : 3D053053A

RXQ32 ~ 50PAHY1(S)

Distributive
Piping

Optional accessories

RXQ36PAHY1(S)
RXQ38PAHY1(S)
RXQ40PAHY1(S)
RXQ42PAHY1(S)
RXQ44PAHY1(S)
RXQ46PAHY1(S)
RXQ48PAHY1(S)
RXQ50PAHY1(S)

RXQ32PAHY1(S)

REFNET header

KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H


(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)

REFNET joint

KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T


BHFP22P151

Outdoor unit multi connection piping kit

KHRP26M73TP, KHRP26M73HP

Pipe size reducer


Central drain pan kit

KWC26C280
KWC26C4502

KWC26C4503

Digital Pressure Gauge Kit

BHGP26A1(E)

Filter kit

BHF26A450F
C : 3D053053A

Appendix

341

Piping Installation Point

Si34-804_C

5. Piping Installation Point


5.1

Piping Installation Point

5 m or less
than 5 m
Maximum length from a connection
kit. 10 m or less from first branch.
(Equivalent Piping Length 13 m)

Connection
Kit B

Connection
Kit A

Since there is a possibility that oil may be collected on a stop machine side, install piping
between outdoor units to go to level or go up to an outdoor unit, and to make a slope.

The projection part between multi connection piping kits


When the piping length between the multi connection kits or between multi connection kit and
outdoor unit is 2 m or more, prepare a vertical projection part (200 mm or more as shown below) only
on the gas pipe line location less than 2 m from multi connection kit.
In the case of 2 m or less

Less than 2 m

In the case of 2 m or more

Vertical
Projection
200 mm
or more
Less than 2 m
2 m or more

Vertical
Projection

Less than 2 m

342

Vertical
Projection

Less than 2 m

Appendix

Si34-804_C

5.2

Piping Installation Point

The Example of a Wrong Pattern


Wrong

Oil is collected to the outdoor


unit at the time of a stop,
because of bottom omission of
piping.

Wrong

Oil is collected to the low level outdoor


unit at the time of a stop, because of
downward slope of piping.

The example of installation on which oil is not collected.

Good

Good

Vertical
Projection

Outdoor Unit - Multi Connection Piping Kit Actual piping length 10 m or less, equivalent length 13 m or less
Max. allowable Multi Connection Piping Kit - Indoor Unit
Piping Length
REFNET Joint - Indoor Unit
Outdoor Unit - Outdoor Unit
Allowable
Level
Difference

Outdoor Unit - Indoor Unit


Indoor Unit - Indoor Unit

Actual piping length 165 m or less, equivalent length 190 m or


less, the total extension 1000 m or less
Actual piping length 40 m or less
(Refer to Note 2 on P.346 in case of up to 90 m)
5 m or less
50 m or less
90 m or less
(when an outdoor unit is lower than indoor units: 40 m or less in
case of RXQ5PA)
15 m or less

Note): Available on request if the outdoor unit is above.

Appendix

343

Piping Installation Point

344

Si34-804_C

Appendix

Si34-804_C

Example of Connection (R-410A Type)

6. Example of Connection (R-410A Type)


Example refrigerant branch using REFNET joint

Example of connection
(Connection of 8 indoor units)

(2)In case of multi outdoor system, re-read to the first


Outdoor unit multi connection piping kit as seen
from the indoor unit.

Single outdoor
system

Outdoor unit

REFNET joint (A-G)

Outdoor unit

(1)
indicate the Outdoor unit multi
connection piping kit

Example refrigerant branch using REFNET joint and REFNET header

b
A

c
B

d
C

i
1

j
2

k
3

l
4

H1

H1

m
5

d
1

Indoor units ( 1 - 8 )

e
2

First Outdoor
unit multi connection
piping kit
Actual pipe length
Maximum
allowable
length

Allowable
height
length

Between outdoor unit and Outdoor unit multi


connection piping kit (Only for multi system)
Between outdoor and indoor units
Between indoor and indoor units
Between outdoor and outdoor units

Equivalent length
Total extension length
Actual pipe length
Equivalent length
Difference in height
Difference in height
Difference in height
Actual pipe length

Allowable length after the branch

Refrigerant branch kit selection

Example for indoor units connected downstream

Pipe size selection


Caution
The thickness of the pipes in the table shows the requirements of Japanese
High Pressure Gas Control low. (As of Jan. 2003)
The thickness and material shall be selected in accordance with local code.
For the multi outdoor unit system, select in accordance with the following figure.

Appendix

Part B

i
1

d
k
3

f
E

j
2

l
4

H1

m
6

Part C

f
3

h
7 H2

i
8

REFNET header
a

j
g

H3

e
2

e
3

Indoor units ( 1 - 8 )
Outdoor unit

REFNET header

7 H2

REFNET joint (A B)

Indoor units ( 1 - 8 )

H1

k
7

H1

H2

b
1

d
2

e
4

h
7 H2

Indoor units ( 1 - 8 )

Indoor units ( 1 - 8 )

i
8

Pipe length between outdoor (2) and indoor units 165m


Example unit 8 : a + b + c + d + e + f + g + p 165m
Example unit 8 : a + i 165m
Example unit 6 : a + b + h 165m, unit 8 : a + i + k 165m
Equivalent pipe length between outdoor (2) and indoor units 190m (assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, calculation purposes) (See Note 1 - Next page)
Total pipe length from outdoor unit (2) to all indoor units 1000m
Pipe length between outdoor unit and Outdoor unit multi connection piping kit 10m, Equivalent length between outdoor unit and Outdoor unit multi connection piping kit 13m

Outdoor unit

Difference in height between outdoor and indoor units (H1) 50m


Difference in height between indoor units (H2) 15m

( 90m if the outdoor unit is below)


s

Difference in height between outdoor unit (H3) 5m


Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit 40m (See Note 2 - Next page)
Example unit 8 : b + c + d + e + f + g + p 40m
Example unit 6 : b + h 40m, unit 8 :i + k 40m

Temper grade and wall thickness for pipes.


(Temper grade, O type and 1/2H type indicate the material types specified in JIS
H 3300.)
(Unit:mm)
Copper tube O.D.

6.4
9.5
12.7
15.9
19.1
22.2
25.4
28.6
31.8
34.9
38.1
41.3

Copper tube W.T.


(Minimum requirement)

0.80
0.80
0.80
0.99
0.80
0.80
0.88
0.99
1.10
1.21
1.32
1.43

Temper grade

O type

Indoor unit total capacity index


< 200
200 x< 290
290 x< 640
640

5HP type
8HP type
10HP type
12~16HP type
18~22HP type
24HP type
26~34HP type
36~54HP type
(See Note 1 - Next page)

Refrigerant branch kit name


KHRP26M22H (Max. 4 branch)
KHRP26M33H (Max. 8 branch)
KHRP26M72H (Max. 8 branch) (See Note 3 - Next page)
KHRP26M73H (Max. 8 branch) + KHRP26M73HP

How to select the Outdoor unit multi connection piping kit (This is required when the system is multi outdoor unit system.)
Choose from the following table in accordance with the number of outdoor units.
Number of outdoor units
2 units
3 units

Piping size (O.D.)


Gas pipe
15.9
19.1
22.2
28.6

Liquid pipe
9.5
12.7
15.9

34.9
41.3

Connection piping kit name


BHFP22P100
BHFP22P151

Example REFNET header: indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8

Piping between Outdoor unit and first refrigerant branch kit.


Piping between first Outdoor unit multi connection piping kit and first refrigerant
branch kit. (Part A)
Choose from the following table in accordance with the outdoor unit capacity type.
Piping between Outdoor unit multi connection piping kits. (Part B)
Piping between outdoor unit and Outdoor unit multi connection piping kit. (Part C)
Choose from the following table in accordance with the total capacity type of all
the outdoor units connected above Outdoor unit multi connection piping kit.
(Unit:mm)
Outdoor unit capacity type

1/2H type

r 10m (Equivalent length: 13m)


s 10m (Equivalent length: 13m)
t 10m (Equivalent length: 13m)

Example unit 8 : i 40m

Example REFNET joint B: indoor units 7 + 8


Example REFNET header: indoor units 1 + 2 + 3 + 4 + 5 + 6

Example REFNET joint C: indoor units 3 + 4 + 5 + 6 + 7 + 8

How to select the REFNET header


Choose from the following table in accordance with the total capacity index of all the indoor units connected below the REFNET header.
Note: 250 type indoor unit cannot be connected below the REFNET header.

Outdoor unit capacity type


Refrigerant branch kit name
5HP type
KHRP26A22T
8, 10HP type
KHRP26A33T
12~22HP type
KHRP26A72T
24HP type~
KHRP26A73T + KHRP26M73TP
Choose the REFNET joints other than that for the first branch from the following table in accordance with the total
capacity index of all the indoor units connected below the REFNET joint.
Indoor unit total capacity index
Refrigerant branch kit name
< 200
KHRP26A22T
200 x< 290
KHRP26A33T
290 x< 640
KHRP26A72T
640
KHRP26A73T + KHRP26M73TP

When multi outdoor system are installed, be sure to


use the special separately sold Outdoor unit multi
connection piping kit.
The table at right shows how to select the proper kit.

H3

How to select the REFNET joint


When using REFNET joint at the first branch counted from the outdoor unit side.
Choose from the following table in accordance with the outdoor unit capacity type.
(Example: REFNET joint A)

Refrigerant branch kits can only be


used with R-410A.

Part A

H2

Indoor units ( 1 - 8 )
Outdoor unit

REFNET joint (A-G)

H1

a
a
A

Between outdoor (2)


and indoor units

H3

Multi outdoor
system

j
7

7 H2

REFNET header

Outdoor unit
a

REFNET header

n
6

Outdoor unit

REFNET joint (A B)
i

a
a

Example refrigerant branch using REFNET header

Piping between refrigerant branch kits


Choose from the following table in accordance with the total capacity index of
all the indoor units connected below this.
Do not let the connection piping exceed the main refrigerant piping size. (Unit:mm)
Indoor unit total capacity index
< 150
150 x< 200
200 x< 290
290 x< 420
420 x< 640
640 x< 920
920

Liquid pipe
9.5

28.6

12.7
15.9

34.9
41.3

19.1

Piping between refrigerant branch kit and indoor unit


Match to the size of the connection piping on the indoor unit.
Indoor unit capacity type

19.1

Piping size (O.D.)


Gas pipe
15.9
19.1
22.2

20 25 32 40 50 type
63 80 100 125 type
200 type
250 type

(Unit:mm)

Piping size (O.D.)


Gas pipe
12.7
15.9
19.1
22.2

Liquid pipe
6.4
9.5

345

Example of Connection (R-410A Type)

Si34-804_C

How to calculate the additional


refrigerant to be charged
Additional refrigerant to be charged : R (kg)
(R should be rounded off in units of 0.1 kg.)

Total length(m) of liquid


piping size at 22.2

R=

Total length(m) of liquid


piping size at 19.1

0.37

0.26

Total length(m) of liquid


piping size at 15.9

0.18

Total length(m) of liquid


piping size at 12.7

0.12

Total length(m) of liquid


piping size at 9.5

0.059

Total length(m) of liquid


piping size at 6.4

0.022

REFRIGERANT
AMOUNT FOR
HEAT PUMP SYSTEM

REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT

TABLE A

TABLE B

TABLE A
MODEL NAME
RXQ5P
RXQ8 ~ 12P
RXQ14 ~ 22P
RXQ24 ~ 30P
RXQ32 ~ 38P
RXQ40 ~ 48P
RXQ50 ~ 54P

TABLE B

THE AMOUNT OF
REFRIGERANT
0kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg

INDOOR CONNECTION
CAPACITY [X]
X 100%
100% < X 120%
120% < X 130%
130% < X 140%
140% < X 150%
150% < X 160%
160% < X 170%
170% < X 180%
180% < X 190%
190% < X 200%

MODEL NAME [RXQ ~ P]


10P 12P~14P 16P 18P~22P 24P~28P 30P~32P 34P 36P 38P 40P 42P~44P 46P~48P 50P 52P~54P
0kg
0.5kg
0.5kg
1.0kg
0.5kg
1.0kg
1.5kg
1.0kg
1.5kg
2.0kg
0.5kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
1.5kg
2.0kg
0.5kg
1.0kg
2.5kg
3.0kg
1.5kg
2.0kg
2.5kg
3.0kg
0.5kg
1.0kg
3.5kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
3.5kg
4.0kg
0.5kg

5P~8P

Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : RXQ34P~
R = ( 30 0.26 + 10 0.18 + 10 0.12 + 40 0.059 + 49 0.022 )+ 2.0 + 0.5
Total capacity of indoor unit : 116%
a
b
i
c+d+e+f
g+h+i+j+k
RXQ34P~ 116%
a : 19.1 30m d : 9.5 10m g : 6.4 10m j : 6.4 10m
= 16.738
16.7kg
b : 15.9 10m e : 9.5 10m h : 6.4 20m k : 6.4 9m
c : 9.5 10m f : 9.5 10m i : 12.7 10m
Round off units of 0.1 kg.

Note 1
When the equivalent pipe length between outdoor and indoor
units is 90m or more, the size of main pipes (both gas side and
liquid side) must be increased.
Depending on the length of the piping, the capacity may drop, but
even in such case it is able to increase the size of main pipes.
The first refrigerant branch kit
Outdoor unit
Main pipes

Indoor unit

Increase

Diameter of above case


Model

Gas

Liquid

Model

RXQ5 Type

19.1

Not Increased

RXQ20 Type

Gas

Liquid

31.8*

19.1

Model

Gas

Liquid

RXQ34 Type

38.1*

22.2

Model

Gas

Liquid

RXQ48 Type

Not Increased

22.2

RXQ8 Type

22.2

12.7

RXQ22 Type

31.8*

19.1

RXQ36 Type

Not Increased

22.2

RXQ50 Type

Not Increased

22.2

RXQ10 Type

25.4*

12.7

RXQ24 Type

Not Increased

19.1

RXQ38 Type

Not Increased

22.2

RXQ52 Type

Not Increased

22.2

RXQ12 Type

Not Increased

15.9

RXQ26 Type

38.1*

22.2

RXQ40 Type

Not Increased

22.2

RXQ54 Type

Not Increased

22.2

RXQ14 Type

Not Increased

15.9

RXQ28 Type

38.1*

22.2

RXQ42 Type

Not Increased

22.2

RXQ16 Type

31.8*

15.9

RXQ30 Type

38.1*

22.2

RXQ44 Type

Not Increased

22.2

*If available on the site, use this size.


Otherwise, it can not be increased.

RXQ18 Type

31.8*

19.1

RXQ32 Type

38.1*

22.2

RXQ46 Type

Not Increased

22.2

Note 2

Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of Branch with REFNET joint )
Required Conditions

Example Drawings

1.It is necessary to increase the pipe size if the pipe length between the first branch
kit and the final branch kit is over 40m. (Reducers must be procured onsite)
If the increased pipe size is larger than main pipe size, then increase the main pipe
size to the same pipe size.

8 b + c + d + e + f + g + p 90 m
increase the pipe size of b, c, d, e, f, g

2.For calculation of Total extension length, the actual length of above pipes must be
doubled. (except main pipe and the pipes that are not increased)

a+b2+c2+d2+e2+f2+g2
+ h + i + j + k + l + m + n + p 1000 m

3.Indoor unit to the nearest branch kit 40 m

h, i, j....... p 40 m

Increase the pipe size as follows


9.5 12.7
15.9 19.1
12.7 15.9
19.1 22.2

The farthest indoor unit 8


The nearest indoor unit 1
( a + b + c + d + e + f + g + p ) - ( a + h ) 40 m

h
1

j
2

e
D

l
4

m
5

H1

f
E

k
3

34.9 38.1*

REFNET joint (A-G)

Outdoor unit

4.The difference between


[Outdoor unit to the farthest indoor unit] and [Outdoor unit to the nearest indoor unit]
40 m

22.2 25.4*
28.6 31.8*

*If available on the site, use


this size.
Otherwise it can not be
increased.

n
6

Indoor units ( 1 - 8 )

7
8

Note 3

If the pipe size above the REFNET header is 34.9 or more, KHRP26M73HP is required.

346

Appendix

Si34-804_C

Thermistor Resistance / Temperature Characteristics

7. Thermistor Resistance / Temperature


Characteristics
Indoor unit

Outdoor unit for radiation fin thermistor R1T

Appendix

TC
-10
-8
-6
-4
-2

k
88.0
79.1
71.1

0
2
4
6
8

64.1
57.8
52.3
47.3
42.9

10
12
14
16
18

38.9
35.3
32.1
29.2
26.6

20
22
24
26
28

24.3
22.2
20.3
18.5
17.0

30
32
34
36
38

15.6
14.2
13.1
12.0
11.1

40
42
44
46
48

10.3
9.5
8.8
8.2
7.6

50
52
54
56
58

7.0
6.7
6.0
5.5
5.2

60
62
64
66
68

4.79
4.46
4.15
3.87
3.61

70
72
74
76
78

3.37
3.15
2.94
2.75
2.51

80
82
84
86
88

2.41
2.26
2.12
1.99
1.87

90
92
94
96
98

1.76
1.65
1.55
1.46
1.38

For air suction


For liquid pipe
For gas pipe

R1T
R2T
R3T

Outdoor unit For outdoor air


For coil
For suction pipe
For Receiver gas pipe
For Receiver outlet liquid pipe
TC
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

k
197.81
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
111.99
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
65.84
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
39.96
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
25.01
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
16.10

TC
-19.5
-18.5
-17.5
-16.5
-15.5
-14.5
-13.5
-12.5
-11.5
-10.5
-9.5
-8.5
-7.5
-6.5
-5.5
-4.5
-3.5
-2.5
-1.5
-0.5
0.5
1.5
2.5
3.5
4.5
5.5
6.5
7.5
8.5
9.5
10.5
11.5
12.5
13.5
14.5
15.5
16.5
17.5
18.5
19.5
20.5
21.5
22.5
23.5
24.5
25.5
26.5
27.5
28.5
29.5
30.5

k
192.08
181.16
170.94
161.36
152.38
143.96
136.05
128.63
121.66
115.12
108.96
103.18
97.73
92.61
87.79
83.25
78.97
74.94
71.14
67.56
64.17
60.96
57.94
55.08
52.38
49.83
47.42
45.14
42.98
40.94
39.01
37.18
35.45
33.81
32.25
30.77
29.37
28.05
26.78
25.59
24.45
23.37
22.35
21.37
20.45
19.56
18.73
17.93
17.17
16.45
15.76

TC
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80

R1T
R2T
R4T
R5T
R6T
k
16.10
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
10.63
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
7.18
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
4.96
4.79
4.62
4.46
4.30
4.16
4.01
3.88
3.75
3.62
3.50
3.38
3.27
3.16
3.06
2.96
2.86
2.77
2.68
2.60
2.51

TC
30.5
31.5
32.5
33.5
34.5
35.5
36.5
37.5
38.5
39.5
40.5
41.5
42.5
43.5
44.5
45.5
46.5
47.5
48.5
49.5
50.5
51.5
52.5
53.5
54.5
55.5
56.5
57.5
58.5
59.5
60.5
61.5
62.5
63.5
64.5
65.5
66.5
67.5
68.5
69.5
70.5
71.5
72.5
73.5
74.5
75.5
76.5
77.5
78.5
79.5
80.5

k
15.76
15.10
14.48
13.88
13.31
12.77
12.25
11.76
11.29
10.84
10.41
10.00
9.61
9.24
8.88
8.54
8.21
7.90
7.60
7.31
7.04
6.78
6.53
6.53
6.53
6.53
6.06
5.84
5.43
5.05
4.87
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
3.44
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
2.47

347

Thermistor Resistance / Temperature Characteristics

Si34-804_C

Outdoor Unit
Thermistors for
Discharge Pipe
(R3T, R3133T)
TC

TC

TC

TC

TC

TC

640.44

0.5

624.65

50

72.32

50.5

70.96

100

13.35

100.5

13.15

609.31

1.5

594.43

51

69.64

51.5

68.34

101

12.95

101.5

12.76

579.96

2.5

565.78

52

67.06

52.5

65.82

102

12.57

102.5

12.38

552.00

3.5

538.63

53

64.60

53.5

63.41

103

12.20

103.5

12.01

525.63

4.5

512.97

54

62.24

54.5

61.09

104

11.84

104.5

11.66

500.66

5.5

488.67

55

59.97

55.5

58.87

105

11.49

105.5

11.32

477.01

6.5

465.65

56

57.80

56.5

56.75

106

11.15

106.5

10.99

454.60

7.5

443.84

57

55.72

57.5

54.70

107

10.83

107.5

10.67

433.37

8.5

423.17

58

53.72

58.5

52.84

108

10.52

108.5

10.36

413.24

9.5

403.57

59

51.98

59.5

50.96

109

10.21

109.5

10.06

10

394.16

10.5

384.98

60

49.96

60.5

49.06

110

9.92

110.5

9.78

11

376.05

11.5

367.35

61

48.19

61.5

47.33

111

9.64

111.5

9.50

12

358.88

12.5

350.62

62

46.49

62.5

45.67

112

9.36

112.5

9.23

13

342.58

13.5

334.74

63

44.86

63.5

44.07

113

9.10

113.5

8.97

14

327.10

14.5

319.66

64

43.30

64.5

42.54

114

8.84

114.5

8.71

15

312.41

15.5

305.33

65

41.79

65.5

41.06

115

8.59

115.5

8.47

16

298.45

16.5

291.73

66

40.35

66.5

39.65

116

8.35

116.5

8.23

17

285.18

17.5

278.80

67

38.96

67.5

38.29

117

8.12

117.5

8.01

18

272.58

18.5

266.51

68

37.63

68.5

36.98

118

7.89

118.5

7.78

19

260.60

19.5

254.72

69

36.34

69.5

35.72

119

7.68

119.5

7.57

20

249.00

20.5

243.61

70

35.11

70.5

34.51

120

7.47

120.5

7.36

21

238.36

21.5

233.14

71

33.92

71.5

33.35

121

7.26

121.5

7.16

22

228.05

22.5

223.08

72

32.78

72.5

32.23

122

7.06

122.5

6.97

23

218.24

23.5

213.51

73

31.69

73.5

31.15

123

6.87

123.5

6.78

24

208.90

24.5

204.39

74

30.63

74.5

30.12

124

6.69

124.5

6.59

25

200.00

25.5

195.71

75

29.61

75.5

29.12

125

6.51

125.5

6.42

26

191.53

26.5

187.44

76

28.64

76.5

28.16

126

6.33

126.5

6.25

27

183.46

27.5

179.57

77

27.69

77.5

27.24

127

6.16

127.5

6.08

28

175.77

28.5

172.06

78

26.79

78.5

26.35

128

6.00

128.5

5.92

29

168.44

29.5

164.90

79

25.91

79.5

25.49

129

5.84

129.5

5.76

30

161.45

30.5

158.08

80

25.07

80.5

24.66

130

5.69

130.5

5.61

31

154.79

31.5

151.57

81

24.26

81.5

23.87

131

5.54

131.5

5.46

32

148.43

32.5

145.37

82

23.48

82.5

23.10

132

5.39

132.5

5.32

33

142.37

33.5

139.44

83

22.73

83.5

22.36

133

5.25

133.5

5.18

34

136.59

34.5

133.79

84

22.01

84.5

21.65

134

5.12

134.5

5.05

35

131.06

35.5

128.39

85

21.31

85.5

20.97

135

4.98

135.5

4.92

36

125.79

36.5

123.24

86

20.63

86.5

20.31

136

4.86

136.5

4.79

37

120.76

37.5

118.32

87

19.98

87.5

19.67

137

4.73

137.5

4.67

38

115.95

38.5

113.62

88

19.36

88.5

19.05

138

4.61

138.5

4.55

39

111.35

39.5

109.13

89

18.75

89.5

18.46

139

4.49

139.5

4.44

40

106.96

40.5

104.84

90

18.17

90.5

17.89

140

4.38

140.5

4.32

41

102.76

41.5

100.73

91

17.61

91.5

17.34

141

4.27

141.5

4.22

42

98.75

42.5

96.81

92

17.07

92.5

16.80

142

4.16

142.5

4.11

43

94.92

43.5

93.06

93

16.54

93.5

16.29

143

4.06

143.5

4.01

44

91.25

44.5

89.47

94

16.04

94.5

15.79

144

3.96

144.5

3.91

45

87.74

45.5

86.04

95

15.55

95.5

15.31

145

3.86

145.5

3.81

46

84.38

46.5

82.75

96

15.08

96.5

14.85

146

3.76

146.5

3.72

47

81.16

47.5

79.61

97

14.62

97.5

14.40

147

3.67

147.5

3.62

48

78.09

48.5

76.60

98

14.18

98.5

13.97

148

3.58

148.5

3.54

49

75.14

49.5

73.71

99

13.76

99.5

13.55

149

3.49

149.5

3.45

50

72.32

50.5

70.96

100

13.35

100.5

13.15

150

3.41

150.5

3.37

348

Appendix

Si34-804_C

Pressure Sensor

8. Pressure Sensor

Detected Pressure

PH = 1.38VH-0.69
PL = 0.57VL-0.28
PH : High pressure (MPa)
PL : Low pressure (MPa)

VH : Output Voltage [High Side] VDC


VL : Output Voltage [Low Side] VDC

High Pressure (PH)

Low Pressure (PL)

Output Voltage (VH, VL)

Appendix

349

Si34-804_C

Part 8
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................351
1.1 Outline ..................................................................................................351
1.2 Refrigerant Cylinders............................................................................353
1.3 Service Tools........................................................................................354

350

Precautions for New Refrigerant (R-410A)

Si34-804_C

Precautions for New Refrigerant (R-410A)

1. Precautions for New Refrigerant (R-410A)


1.1

Outline

1.1.1 About Refrigerant R-410A


Characteristics of new refrigerant, R-410A
1. Performance
Almost the same performance as R-22 and R-407C
2. Pressure
Working pressure is approx. 1.4 times more than R-22 and R-407C.
3. Refrigerant composition
Few problems in composition control, since it is a Quasi-azeotropic mixture refrigerant.
HFC units (Units using new refrigerants)
R-407C
R-410A

Refrigerant name
Composing
substances
Design pressure

Non-azeotropic mixture
of HFC32, HFC125 and
HFC134a (*1)
3.2 MPa (gauge pressure)
= 32.6 kgf/cm2

Quasi-azeotropic mixture
of HFC32 and HFC125
(*1)
4.0 MPa (gauge pressure)
= 40.8 kgf/cm2

HCFC units
R-22
Single-component
refrigerant
2.75 MPa (gauge pressure)
= 28.0 kgf/cm2

Refrigerant oil
Ozone destruction
factor (ODP)

Synthetic oil (Ether)

Mineral oil (Suniso)

0.05

Combustibility
Toxicity

None
None

None
None

None
None

1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different

boiling points.
2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar

boiling points.
3. The design pressure is different at each product. Please refer to the installation manual for

each product.
(Reference) 1 MPa

10.19716 kgf/cm2

Pressure-Enthalpy curves of HFC-32/125 (50/50wt%)

Precautions for New Refrigerant (R-410A)

351

Precautions for New Refrigerant (R-410A)

Si34-804_C

Thermodynamic characteristic of R-410A


Temperature
( )

352

Steam pressure
(kPa)
Liquid
Vapor

Density
(kg/m3 )
Liquid
Vapor

Specific heat at constant


pressure (kJ/kgK)
Liquid
Vapor

Specific enthalpy
(kJ/kg)
Liquid
Vapor

Specific entropy
(kJ/KgK)
Liquid
Vapor

Precautions for New Refrigerant (R-410A)

Si34-804_C

1.2

Precautions for New Refrigerant (R-410A)

Refrigerant Cylinders
Cylinder specifications

The cylinder is painted refrigerant color (pink).


The cylinder valve is equipped with a siphon tube.

Siphon tube

Cylinder

Refrigerant can be charged in liquid state with cylinder in


upright position.
Caution: Do not lay cylinder on its side during charging, since
it cause refrigerant in gas state to enter the system.

Handling of cylinders

(1) Laws and regulations


R-410A is liquefied gas, and the High Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high pressure gases. Be sure to follow the regulations.
(2) Handing of vessels
Since R-410A is high pressure gas, it is contained in high pressure vessels.
Although those vessels are durable and strong, careless handling can cause damage that
can lead to unexpected accidents. Do not drop vessels, let them fall, apply impact or roll
them on the ground.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high pressure gases.
It should also be noted that high pressure vessels are equipped with safety devices that
releases gas when the outdoor air temperature reaches more than a certain level (fusible
plug melts) and when the pressure exceeds a certain level (spring-type safety valve
operates).

Precautions for New Refrigerant (R-410A)

353

Precautions for New Refrigerant (R-410A)

1.3

Si34-804_C

Service Tools
R-410A is used under higher working pressure, compared to previous refrigerants
(R-22, R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to
Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other
problems. Therefore, gauge manifolds and charge hoses that are used with a previous
refrigerant (R-22, R-407C) can not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
Tool compatibility
Compatibility
HFC
HCFC

Tool

R-410A

R-407C

Gauge manifold
Charge hose

Do not use the same tools for R-22


and R-410A.
Thread specification differs for
R-410A and R-407C.

Charging cylinder
Gas detector

Vacuum pump
(pump with reverse flow
preventive function)
Weighting instrument

Weighting instrument used for HFCs.


The same tool can be used for HFCs.
To use existing pump for HFCs,
vacuum pump adaptor must be
installed.

Charge mouthpiece

Flaring tool (Clutch type)

Torque wrench
Pipe cutter

{
{

Pipe expander
Pipe bender

{
{

Pipe assembling oil

Refrigerant recovery
device

Check your recovery device.

Refrigerant piping

Reasons for change

R-22

See the chart below.

Seal material is different between


R-22 and HFCs.
Thread specification is different
between R-410A and others.
For R-410A, flare gauge is necessary.
Torque-up for 1/2 and 5/8

Due to refrigerating machine oil


change. (No Suniso oil can be used.)

Only 19.1 is changed to 1/2H material


while the previous material is "O".

As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
Copper tube material and thickness
Pipe size
6.4
9.5
12.7
15.9
19.1
22.2
25.4
28.6
31.8
38.1
44.5

Material
O
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H

R-407C
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.2
1.4
1.6

Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H

R-410A
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.1
1.4
1.6

* O: Soft (Annealed)
H: Hard (Drawn)

354

Precautions for New Refrigerant (R-410A)

Si34-804_C

Precautions for New Refrigerant (R-410A)

1. Flaring tool

Flare gauge

Specifications
Dimension A

Unit:mm
Nominal size

A +00.4

Tube O.D.
Do

Class-2 (R-410A)

Class-1 (Conventional)

1/4

6.35

9.1

9.0

3/8

9.52

13.2

13.0

1/2

12.70

16.6

16.2

5/8

15.88

19.7

19.4

3/4

19.05

24.0

23.3

Differences
Change of dimension A
Dimension A

For class-1: R-407C


For class-2: R-410A

Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5 mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5 mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.

Precautions for New Refrigerant (R-410A)

355

Precautions for New Refrigerant (R-410A)

Si34-804_C

2. Torque wrench

Specifications
Dimension B

Unit:mm

Nominal size

Class-1

Class-2

Previous

1/2
5/8

24
27

26
29

24
27

No change in tightening torque


No change in pipes of other sizes
Differences
Change of dimension B
Only 1/2", 5/8" are extended

For class-1: R-407C


For class-2: R-410A

Dimension B

3. Vacuum pump with check valve


Vacuum pump adaptor
Reverse flow preventive
vacuum adaptor

Specifications
Discharge speed
50 l/min (50 Hz)
Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adaptor

z Maximum degree of vacuum

Select a vacuum pump which is able to keep


the vacuum degree of the system in excess of
100.7 kPa (5 torr 755 mmHg).

Differences
Equipped with function to prevent reverse oil flow
Previous vacuum pump can be used by installing adaptor.

356

Precautions for New Refrigerant (R-410A)

Si34-804_C

Precautions for New Refrigerant (R-410A)

4. Leak tester

Specifications
Hydrogen detecting type, etc.
Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.

5. Refrigerant oil (Air compal)

Specifications
Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
Offers high rust resistance and stability over long period of time.
Differences
Can be used for R-410A and R-22 units.

6. Gauge manifold for R-410A

Specifications
High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
1/4" 5/16" (2 minutes 2.5 minutes)
No oil is used in pressure test of gauges.
For prevention of contamination
Precautions for New Refrigerant (R-410A)

357

Precautions for New Refrigerant (R-410A)

Si34-804_C

Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.

Differences
Change in pressure
Change in service port diameter

7. Charge hose for R-410A

(Hose with ball valve)

Specifications
Working pressure 5.08 MPa (51.8 kg/cm2)
Rupture pressure 25.4 MPa (259 kg/cm2)
Available with and without hand-operate valve that prevents refrigerant from outflow.

Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance

8. Charging cylinder

Can not be used

Specifications
Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.

When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.

358

Precautions for New Refrigerant (R-410A)

Si34-804_C

Precautions for New Refrigerant (R-410A)

9. Weigher for refrigerant charge

Specifications
High accuracy
TA101A (for 10-kg cylinder) = 2g
TA101B (for 20-kg cylinder) = 5g
Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
Measurement is based on weight to prevent change of mixing ratio during charging.

10.Charge mouthpiece

Specifications
For R-410A, 1/4" 5/16" (2 minutes 2.5 minutes)
Material is changed from CR to H-NBR.
Differences
Change of thread specification on hose connection side (For the R-410A use)
Change of sealer material for the HFCs use.

Precautions for New Refrigerant (R-410A)

359

Warning

Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING DIVISION

JMI-0107

Scope of Registration:
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF
COMMERCIAL AIR CONDITIONING, HEATING, COOLING,
REFRIGERATING EQUIPMENT, COMMERCIAL HEATING
EQUIPMENT, RESIDENTIAL AIR CONDITIONING
EQUIPMENT, HEAT RECLAIM VENTILATION, AIR
CLEANING EQUIPMENT, MARINE TYPE CONTAINER
REFRIGERATION UNITS, COMPRESSORS AND VALVES.

Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.

JQA-1452

Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR THEM

All of the Daikin Groups business


facilities and subsidiaries in Japan
are certified under the ISO 14001
international standard for
environment management.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of December 2010 but subject to change without notice.

Si34-804_C
12/2010 AK

Potrebbero piacerti anche