Sei sulla pagina 1di 8

S/No.

Characteristics

GIS Type A

GIS Type B

Project reference SLD


1
2
3
4
5

General
Rated system voltage, kV
Highest system voltage, kV
Rated voltage of switchgear, kV
Rated frequency, Hz
Number of phases

Switching arrangement

7
8
9
10

Rated normal current for main circuits, A


a)
busbars
b)
feeder circuits
Rated short time withstand current for main and earthing circuits, kA
(rms value)
Rated peak withstand current for main and earthing circuits, kA (peak
value)
Rated duration of short-circuits

GIS Type C

HIS 132kV

HIS 132kV

FWEL-I & II

Metro Wind farm

FFCL Windfram,

AIS 132kV

AIS 220kV
UCH Project

220
245
245
50
3

132
145
145
50
3

132
145
145
50
3

132
145
145
50
3

132
145
145
50
3

132
145
145
50
3

220kV
245
245
50
3

Double bus or one and


a half breaker scheme

Double bus bar

Single bus bar

Double bus bar scheme

Single bus bar scheme

Double bus bar

One & a Half Breaker


Scheme

2000
2000

3150
2000

2000
1600

2500
2500

2500
2500

2500
2500

40

40

25

100

100

63

1050

650

650

650

650

650

1050

460

275

275

275

275

275

460

40

40

31.5

40

40

Rated insulation levels at minimum operation SF6 gas pressure:


11

12

a) lightning impulse withstand voltage, kV (peak value)


b) Power-frequency (one-min) withstand
voltage, kV (rms
value)
Circuit Breakers
Rated short-circuit breakings current (symmetrical value), KA (r.m.s.
value)

50

Notes:
1

At 220kV busbar Scheme is generally Double bus bar or one and a half breaker scheme whichever is applicable. Refer P.191; 1.3.6

At 132kV: The exact types and ranges of the relays and/or scheme to be used shall be subject to approval by NTDC / DISCO.

S/No.
1
2
3
4

S/No.

Characteristics
Voltage Transformers
Rated primary voltage (phase-to-neutral, kV
Rated secondary voltage (phase-to-neutral, kV
Number of secondary windings
Rated output per phase, VA
a) for measuring
b) for protection
Accuracy class:
a) for measuring
b) for protection

GIS Type A
220/1.732
0.110/1.732
2

220/1.732
0.110/1.732
1

220/1.732
0.110/1.732
1

HIS 132kV
Metro Wind farm
220/1.733
220/1.734
2

75
200

75
200

75
200

75
200

75
200

100

0.5
6P

0.5
6P

0.5
6P

0.2
3P

0.2
3P

0.5
3P

Characteristics
Current Transformers

GIS Type B

GIS Type C

GIS Type A
Line bay

HIS 132kV
FFCL Windfram,
220/1.733
220/1.734
2

GIS Type B

Trans. Bay

Line bay

Trans. Bay

Rated primary current, A

2
3

Rated secondary current, A


No. of secondary cores
R/secondary output, VA
a) measuring core 1
b) protective core 2
c) protective core 3
d) protective core 4

Line bay

HIS 132kV

Trans. Bay
FWEL-I & II

6
7
8

a) measuring
b) protective
Accuracy limit factor (for protective cores)
Instrument security factor (for measuring core)
Power frequency (one min) withstand voltage for secondary circuits,
kV

Line bay

Trans. Bay

Metro Wind farm

2400-1200-600

2400-1200-600

1600-800-400

1600-800-400 or 200-100
appropriate

1200-600-300

200-100

1
4

1
4

1
4

1
4

5
4

5
3

15
60
30
30

15
60
30
30

15
60
30
30

15
60
30
30

15
60
30
30

15
60
30
-

0.5
5P
20
5

0.5
5P
20
5

0.5
10P
20
5

0.5
10P
20
5

0.5
10P
20
5

0.5
10P
20
5

Accuracy class (for all specified ratios):


5

AIS 220kV
UCH Project
220/1.732
0.110/1.732

100

GIS Type C

Reference Projects
1

AIS 132kV

S/No.

Characteristics

GIS Type A

Reference Projects
Current Transformers
21

Rated primary current, A

22
23

Rated secondary current, A


No. of secondary cores
R/secondary output, VA
a) measuring core 1
b) protective core 2
c) protective core 3
d) protective core 4

24

Line bay
2400-1200-600

1
4
15
60
30
30

Accuracy class (for all specified ratios):


25

a) measuring
b) protective

0.5
5P

26

Accuracy limit factor (for protective cores)

20

27

Instrument security factor (for measuring core)

28

Power frequency (one min) withstand voltage for


secondary circuits, kV

GIS Type A

GIS Type B

GIS Type C
FWEL-I & II

Trans. Bay

Line bay

Trans. Bay

Line bay

Trans. Bay

2400-1200-600

1600-800-400

1600-800-400 or 200100 appropriate

1200-600-300

200-100

1
4

1
4

1
4

5
4

5
3

15
60
30
30

15
60
30
30

15
60
30
30

15
60
30
30

15
60
30
-

0.5
5P

0.5
10P

0.5
10P

0.5
10P

0.5
10P

20

20

20

20

20

HIS 132kV

HIS 132kV

Metro Wind farm

FFCL Windfram,

Line bay

Trans. Bay

Line bay

Trans. Bay

AIS 132kV

Line bay

AIS 132kV

AIS 220kV
UCH Project

Trans. Bay

Line bay

Trans. Bay

S/No. Characteristics
Voltage Transformers
1
Rated primary voltage (phase-to-neutral, kV

GIS Type A
220/1.732

Rated secondary voltage (phase-to-neutral, kV

Number of secondary windings


2
Rated output per phase, VA
a) for measuring
75
b) for protection
200
Accuracy class:
a) for measuring
0.5
b) for protection
6P
Rated voltage factor:
a) for continuous duty
1.2
b) for 30 seconds
1.5
Rated thermal burden, VA
1000
Maximum short-circuit impedance referred to secondary,
0.25
Ohm

6
7
8
9

0.110/1.732

Power frequency (one-min) withstand voltage for secondary


2
circuits, kV

GIS Type B

GIS Type C

220/1.732

220/1.732

0.110/1.732

0.110/1.732

75
200

75
200

0.5
6P

0.5
6P

1.2
1.5
1000

1.2
1.5
1000

HIS 132kV
Metro Wind farm

HIS 132kV
FFCL Windfram,

AIS 132kV

AIS 220kV
UCH Project