Sei sulla pagina 1di 63

04/000

Moeller HPL0211-2001/2002

Relays
Contactor Relays

Control Relays, Contactor Relays, Electronic Timing Relays, Electronic Safety Relays, Measuring and Monitoring Relays

04/001

Moeller HPL0211-2001/2002

Control relays

Contactor relays

AC and DC operated

AC and DC operated

System overview

Page
04/002

Easy control relays


Basic units

04/006
04/006

Accessories
Expansion units

04/008
04/007

Technical data

04/037

Dimensions

04/064

Electronic timing relays

System overview

Page
04/004

DILER mini contactor relays


Basic units
Auxiliary contact modules

04/010
04/010
04/010

DILR contactor relays


Basic units
Auxiliary contact modules
Complete units

04/012
04/012
04/012
04/014

Accessories

04/027

Contact travel diagrams

04/029

Actuating voltages

04/030

Tripping characteristics

04/032

Technical data

04/046

Dimensions

04/065

Electronic safety relays

Relays
Contactor Relays

Control Relays, Contactor Relays, Electronic Timing Relays, Electronic Safety Relays, Measuring and Monitoring Relays
Overview

Measuring and monitoring relays

AC and DC operated

Page
DILET

Engineering
DILET11 on-delayed
timing relay
DILET70 multi-function relay

Page
04/022

EMR4-I current monitoring relays

Page
04/024

EMR4-F phase sequence relays

04/024

EMR4-W phase monitoring relays

04/024

EMR4-A phase imbalance


monitoring relays

04/024

EMR4-N level monitoring relays

04/025

04/016
04/016

ETR4
ETR4-51 star-delta
timing relay
ETR4-69 multi-function relay

04/018

ETR4-70 multi-function relay

04/020

04/018

ESR safety relays


For Emergency-Stop
monitoring
For protective door monitoring
For contact/safety mat monitoring
For monitoring of two-hand
controls
Contact expansion modules

04/023
04/023

Technical data

04/054

EMR4-R insulation monitoring


relays

04/025

Dimensions

04/067

EMR4-PH sealable shroud

04/025

04/023
04/023
04/023
04/023

Accessories

04/027

Tripping characteristics

04/033

Tripping characteristics

04/034

Technical data

04/053

Technical data

04/058

Dimensions

04/066

Dimensions

04/067

04/002

Moeller HPL0211-2001/2002

Easy Control Relays


System Overview

Relays
Contactor Relays

3
2

5
7

5
8

6
7

Moeller HPL0211-2001/2002

04/003

Basic units
AC or DC operated
Power supply
AC 100 (115) 240 V, 50/60 Hz
DC 24 V DC
DA 12 V DC
8 or 12 digital inputs
(2 inputs usable as analog inputs
[DC/DA variants only])
4 or 6 relay outputs (max. 10 A)
4 or 8 transistor outputs
LCD display, X variants without LCD
Screw fixing and snap fitting
Screw terminals

a Page 04/006

Fixing brackets
For optional screw fixing,
3 brackets per relay for EASY4...
minimum of 3 brackets per relay for
EASY6...

Basic units,
expandable EASY619/621
AC or DC operated
Power supply
AC 100 240 V, 50/60 Hz
DC 24 V DC
12 digital inputs
(2 inputs usable as analog inputs
[DC variants only])
6 relay outputs (max. 10 A)
8 transistor outputs
LCD display, X variants without LCD
Screw fixing and snap fitting
Screw terminals

a Page 04/008

EASY-LINK-DS data plug


For connecting the basic unit with
the expansion unit

a Page 04/006

a Page 04/008

External memory card


For safe storage of the circuit
configuration and all parameters

a Page 04/008

Connection cable
Safe isolation between easy and PC
a Page 04/008

Expansion unit
I/O expansion
AC or DC operated
Power supply:
AC 100 240 V, 50/60 Hz
DC 24 V DC
12 digital inputs
6 relay outputs (max. 10 A)
8 transistor outputs
Screw fixing and snap fitting
Screw terminals

a Page 04/006

Networking / Bus interfaces


EASY204-DP
PROFIBUS-DP slave connection
EASY205-ASI
AS-Interface slave connection
a Page 04/008

Coupling unit

a Page 04/007

Connection cable
e.g. NYM 3 x 1.5 mm2
a Page 04/008

Distinguishing features of the EASY control


relay
Wide operational temperature range
25 C to +55 C
Standard front dimension for fitting into service
distribution boards, 18 mm standard slot
Electronic wiring by keystroke,
LCD (4 lines of 12 characters) and keypad or
via software from the PC
Zero-voltage safe internal and external circuit
configuration storage in EEPROM memory
3 contacts (make or break contacts) in series
plus one coil in each current path
Series and parallel connection
41 current paths / lines of logic EASY412
121 current paths / lines of logic EASY600
Integral password protection for circuit
configuration and relay value presets
Current flow display for circuit configuration
testing (LCD Types)
Selection option from ten different menu
languages (EASY600)
and five different menu languages (EASY412)
D, GB, F, I, E, (P, NL, S, PL, TR)
Functions
8 timing relays 0.01 s to 99 h 59 min
On-delay
On-delay with random switching
Off-delay
Off-delay with random switching
Pulse shaping
Flashing
8 up- and down-counter relays,
0000 to 9999
4 weekly timers
(4 channels per timer, one On/Off point per
channel, optional on Types with clock)
8 analog value comparators, range 0 10 V
(EASY...-D...-... Types only)
8 lines of text, can be freely edited
(EASY600 with display)
16 auxiliary relays (EASY412), up to
32 auxiliary relays (EASY600)
Retentive actual values EASY412-D...
4 markers
1 timing relay
1 counter
Retentive actual values EASY600
12 markers
2 timing relays
4 counters, e.g. as hours-run meters

Relays
Contactor Relays

Easy Control Relays


System Overview

04/004
Contactor Relays, Electronic Timing Relays
System Overview

Relays
Contactor Relays

DILER

DILR

Moeller HPL0211-2001/2002

Moeller HPL0211-2001/2002

04/005

Contactor Relays, Electronic Timing Relays


System Overview
DILER mini contactor relays
1

Suppressors
All contactor relays with DC operated
coils have an integral suppressor circuit
Suppressors for contactor relays with
AC operated coils

Relays
Contactor Relays

Basic units
AC or DC operated
Magnet systems
AC 12 480 V, 50, 60, 50/60 Hz
0.8 1.1 Uc
25 VA/4.6 VA
DC 12 220 V DC
0.85 1.1 Uc
2.6 W/2.6 W
Maximum of eight contacts
Interlocked opposing contacts
Modular system
Screw fixing and snap fitting
Finger proof
Screw terminals

a Page 04/026

Sealable shroud with clip


As cover in IVS enclosures

3, 4

a Page 04/027

a Page 04/010

Auxiliary contact modules


2- or 4-pole
Overlapping contacts
Interlocked opposing contacts

a Page 04/010

DILR contactor relays


Basic units
AC or DC operated
Magnet systems
AC 12 600 V, 50, 60, 50/60 Hz
0.8 1.1 Uc
60 VA/8.5 VA
DC 12 250 V DC
0.85 1.1 Uc
9.5 W/9.5 W
Coils for non-standard voltages
Maximum of eight contacts
Interlocked opposing contacts
Modular system/complete units
Screw fixing and snap fitting
Finger proof
Screw terminals

Suppressors
RC suppressor
Varistor suppressor
Free-wheel diode suppressor

a Page 04/026

Amplifier modules
With and without integral
suppressor circuits
Plug-in type
Separate mounting

Auxiliary contact modules


4-pole
Plug-in type
Interlocked opposing contacts

a Page 04/012

a Page 04/026

Pneumatic timer modules


On- and Off-delayed
With or without TV* approval to
VDE 0116
*TV = German Technical Supervisory
Association

a Page 04/012

a Page 04/010
Auxiliary contact modules
2-pole
Plug-in type
Interlocked opposing contacts
a Page 04/012

Mechanical latching module


Latches the contactor relay in the
event of loss of control voltage
a Page 04/012

04/006

Moeller HPL0211-2001/2002

Easy Control Relays


Basic Units

Relays
Contactor Relays

Description

Type
Article no.

Price
See Price List

Std. pack

Basic units
24 V DC,
retentive

DEL

ESC

8 digital inputs (2 inputs usable as analog inputs)


4 relay outputs
LCD display
Operating buttons
Screw terminals

EASY412-DC-R
202403

Features same as EASY 412-DC-R plus built-in timer/time switch

EASY412-DC-RC
202404
EASY412-DC-RCX
221596
EASY412-DC-TC
207808

Features same as EASY412-DC-RC, without keypad and


LCD display
8 digital inputs (2 inputs usable as analog inputs)
4 transistor outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer
Features same as EASY412-DC-TC, without keypad and LCD display

ALT

OK

12 digital inputs (2 inputs usable as analog inputs)


6 relay outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer

12 V DC,
retentive

EASY412-DC-TCX
212307
EASY618-DC-RC
224472

12 digital inputs (2 inputs usable as analog inputs)


6 relay outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer
Can be expanded using EASY expansion units

EASY619-DC-RC
224473

Features same as EASY412-DC-RC, without keypad and


LCD display
12 digital inputs (2 inputs usable as analog inputs)
8 transistor outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer

EASY619-DC-RCX
224474
EASY620-DC-TC
212309

12 digital inputs (2 inputs usable as analog inputs)


8 transistor outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer
Can be expanded using EASY expansion units

EASY621-DC-TC
218719

Features same as EASY412-DC-TC, without keypad and


LCD display
8 digital inputs (2 inputs usable as analog inputs)
4 relay outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer

EASY621-DC-TCX
212311
EASY412-DA-RC
224471

1 off

04/007

Moeller HPL0211-2001/2002

Easy Control Relays


Basic Units, Expansion Units, Accessories
Type
Article no.

Price
See Price List

Std. pack

Basic units
115/230 V AC

8 digital inputs, 115/230 V AC


4 relay outputs
LCD display
Operating buttons
Screw terminals
Features same as EASY 412-AC-R, plus timer
Features same as EASY412-AC-RC, without keypad and LCD display

115/230 V AC,
retentive

12 digital inputs, 115/230 V AC


6 relay outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer
12 digital inputs, 115/230 V AC
6 relay outputs
LCD display
Operating buttons
Screw terminals
Time switch/Timer
Can be expanded using EASY expansion units

EASY412-AC-R
202405

1 off

EASY412-AC-RC
202406
EASY412-AC-RCX
212308
EASY618-AC-RC
212310

EASY619-AC-RC
218721

Features same as EASY619-AC-RC, without keypad and LCD display

EASY619-AC-RCX
212312

12 digital inputs
8 transistor outputs
With connector
12 digital inputs, 115/230 V AC
6 relay outputs
With connector
Coupling unit for connecting to an EASY619/621 basic unit
Terminals for remote expansion, up to 30 m to/from the expansion
unit
With connector

EASY620-DC-TE
212313

Linked directly to EASY619/621


AS-Interface connection
Slave
4 inputs, 4 outputs, 4 parameter bits
Addresses available: 0 to 31
With connector
Linked directly to EASY619/621
PROFIBUS-DP slave
Addresses available: 0 to 126
With connector

EASY205-ASI
221598

1 off

EASY204-DP
212316

1 off

9-pole (pins), comes as a kit without cable, for connection of the data
cable
Metallised insulated housing
Maximum transfer rate 12 MBit/s
Built-in switch (accessible from the outside) for the bus termination
resistances
Terminal block for two cables, optionally with straight
or 90 angled cable entry
Suitable for EASY204-DP
Twisted pair cable, 2 X 0.64 mm2, length: 100 m

ZB4-209-DS2
206982
ZB4-209-DS3
217820

1 off

Expansion units
24 V DC

115/230 V AC

Coupling unit

Expansion units for networking


AS-Interface

PROFIBUS DP

Accessories for DP
PROFIBUS DP
bus connector plug
PROFIBUS DP
bus connector plug

PROFIBUS DP
data cable

1 off

EASY618-AC-RE
212314
EASY200-EASY
212315

ZB4-900-KB1
206983

Relays
Contactor Relays

Description

04/008

Moeller HPL0211-2001/2002

Easy Control Relays


Networking, Accessories

Relays
Contactor Relays

Description

Accessories
Software
Memory card

CD, menu selection from 6 languages


Installation under WIN 95, 98, WIN NT 4.0 Service Pack 3 and above
8K memory card for storing the entire circuit configuration for EASY412
16K memory card for storing the entire circuit configuration for EASY6..

Connection cable
Input-/output simulator

Fixing bracket

Coupling piece

Length: 2 m, for connection to 9-pole serial PC interface


with interface electronics
Simulator with power supply unit, 115/230 V AC/output 24 V DC,
suitable/ designed for EASY412-DC...
Same as EASY412-DC-SIM, with 120 V AC plug-in power supply unit/ 24 V
DC output, plug suitable for North America

For screw fixing onto mounting plate:


3 brackets per EASY4...,
3 brackets per EASY6...,
2 brackets per EASY2...
Spare link between basic unit and expansion units

Telescopic adapter

With 45 mm EN 50 022 top-hat rail, for equalization of the mounting depth


of rear mounted devices in CI-K... enclosures and cabinets. Steplessly
adjustable via scales, from 75 115 mm. For screw and snap fixing (also
suitable for PKZM0, FAZ, FIP, ETR, EMR4 etc.)

Switched-mode power supply unit

Primary-switched mode, regulated


Rated input voltage 50/60 HZ: 115/230 V AC
Rated output voltage: 24 V DC
Rated output current: 1.25 A

Type
Article no.

Price
See Price List

Std. pack

EASY-SOFT
202407
EASY-M-8K
202408
EASY-M-16K
212317
EASY-PC-CAB
202409
EASY412-DC-SIM
212318
EASY412-DC-SIM-NA
222566

1 off

ZB4-101-GF1
061360

9 off

EASY-LINK-DS
221607
M22-TA
226161

1 off

EASY400-POW
212319

1 off

10 off

04/009

Moeller HPL0211-2001/2002

Easy Control Relays


Documentation
Type
Article no.

Price
See Price List

Std. pack

Documentation
Manual for the Easy control relay
German
English
French
Italian
Spanish
Brief introduction to the Easy control relay
German
English
French
Italian
Spanish

AWB2528-1304-D
205375
AWB2528-1304-GB
205481
AWB2528-1304-F
205482
AWB2528-1304-I
205483
AWB2528-1304-E
205484

1 off

AWB2528-1316-D
205376
AWB2528-1316-GB
205485
AWB2528-1316-F
205486
AWB2528-1316-I
205487
AWB2528-1316-E
205488

1 off

Relays
Contactor Relays

Description

04/010

Moeller HPL0211-2001/2002

DILER Mini Contactor Relays


Basic Units, Modules

DILER Mini Contactor Relays


Basic Units, Modules

Relays
Contactor Relays

M = Make
B = Break

Rated operational
current Ie
AC-15
220 V
380 V
230 V
400 V
240 V
415 V

Conv.
therm.
current
Ith

Basic units with interlocked opposing contacts


4M

6
3

10

Type
Article no.

Circuit symbol

A1 13 23 33 43

DC operation
Price
See Price
List

Distinctive number and


version of combination

Circuit symbol

40E

DILER-40(230V50HZ)
051759

31E

DILER-31(230V50HZ)
051768

5 off

A2 14 24 34 44

3M

1B

A1 13 21 33 43

2B

A1 13 21 31 43

61

1B

2M

22E

DILER-22(230V50HZ)
051777

42E

33

24

02DILE
010240

51E

42

33

11DILE
010224

60E

51

42

20DILE
010208

5 off

4B

53 63

10

51

42

33

51 61 71 81

3B

53 61 71 81

2M

2B

53 61 71

44E

35

26

04DILE
010256

83

54 62 72

84

53E

44

35

13DILE
002397

62E

53

44

22DILE
010288

62

53

54 62 74 84
53 63 73 83

80E

71

62

54 64 74 84

2 M 2)

Notes

2 B 2)

1)
2)

02DILE
010240

51E

42

11DILE
010224

53 63

60E

51

20DILE
010208

57 65

51

42

11DDILE
049824

57 65 71

83

58 66 72

84

5 off

51 61 71 81

44E

35

04DILE
010256

53 61 71 81

53E

44

13DILE
002397

62E

53

22DILE
010288

71E

62

31DILE
048912

80E

71

40DILE
010304

62

53

22DDILE
049823

54 62 72 82

71E

53 61 73 83

33

52 62 72 82

54 62 72 82

4M

42E

5 off

58 66

1M

1B

DILER-22-G(24VDC)
010042

54 62

11DDILE
049824

52 62 72 82

3M

22E

54 64

57 65

51 61

53 61

58 66

5 off

DILER-31-G(24VDC)
010157

31E

21 33 43

A1 13 21 31 43

54 64

4-pole

DILER-40-G(24VDC)
010223

40E

52 62

53 61

1 B 2)

Distinctive number and


version of combination

A2 14 22 32 44

54 62

1 M 2)

Notes
Std. pack

A2 14 22 34 44

52 62

1M

Price
See Price
List

A2 14 24 34 44

A2 14 22 32 44

Auxiliary contact modules with interlocked opposing contacts1)


51
2-pole

2B
4
2
10

A1 13 23 33 43

A1 13

A2 14 22 34 44

2M

Type
Article no.

Std. pack

62

Not with early-make contacts or late-break contacts


1 early-make contact
1 late-break contact

53

44

31DILE
048912
40DILE
010304
22DDILE
049823

53 61 71

83

54 62 72

84

53 61 73 83

54 62 74 84
53 63 73 83

54 64 74 84
57 65 71

83

58 66 72

84

Relays
Contactor Relays

AC operation
Contacts

04/011

Moeller HPL0211-2001/2002

5 off

Other actuating voltages


a Page 04/030
Contact numbers to EN 50 011
Coil terminal markings to
EN 50 005
With DC operation:
integral resistor/diode
combination
Coil rating: 2.6 W

Version E combinations
correspond to EN 50 011 and
are to be preferred;
other combinations correspond
to EN 50 005.

Accessories

Page

1 Suppressor
Other accessories

04/026
04/026

04/012

Moeller HPL0211-2001/2002

DILR Contactor Relays


Basic Units, Modules

DILR Contactor Relays


Basic Units, Modules

Relays
Contactor Relays

M = Make
B = Break

Rated operational
current Ie
AC-15
220 V
380 V
230 V
400 V
240 V
415 V

Conv.
therm.
current
Ith

Basic units with interlocked opposing contacts


4M

6
4

16

Type
Article no.

Circuit symbol

A1 13 23 33 43

DC operation
Price
See Price
List

Std. pack

Type
Article no.

Price
See Price
List

Distinctive number and


version of combination
40 E

DILR40(230V50HZ)
043756

31 E

DILR31(230V50HZ)
043768

DILR31-G(24VDC)
048532

22 E

DILR22(230V50HZ)
043780

DILR22-G(24VDC)
048526

42 E

33

24

02DIL
098145

51 E

42

33

11DIL
010345

11DIL
010345

60 E

51

42

20DIL
012718

20DIL
012718

1 off

DILR40-G(24VDC)
048537

1 off

A2 14 24 34 44

3M

1B

2M

2B

A1 13 21 33 43

Other actuating voltages a Page 04/030


Contact numbers to EN 50 011
Coil terminal markings to EN 50 005

DILR40: supplied without front plate


Front plate a Page 05/047

A2 14 22 34 44
A1 13 21 31 43

Notes

Std. pack

Relays
Contactor Relays

AC operation
Contacts

04/013

Moeller HPL0211-2001/2002

A2 14 22 32 44

Auxiliary contact modules with interlocked opposing contacts


2-pole

2B
6
4
16

51 61

5 off

02DIL
098145

5 off

52 62

1M

1B

2M

53 61

Version E combinations correspond to


EN 50 011 and are to be preferred;
other combinations correspond to EN 50 005

54 62

53 63

54 64

4-pole

4B

16

51 61 71 81

44 E

35

26

04DIL
015091

53 E

44

35

13DIL
017464

13DIL
017464

62 E

53

44

22DIL
019837

22DIL
019837

71 E

62

53

31DIL
010752

31DIL
010752

80 E

71

62

40DIL
022210

40DIL
022210

51

42

33

TPE11DIL
002279

51

42

33

TPD11DIL
002280

TPD11DIL
002280

51

42

33

TPEH11DIL
046924

TPEH11DIL
046924

51

42

33

TPDH11DIL
046925

TPDH11DIL
046925

40 E

31 E

22 E

VDIL(230V50HZ)
043825

5 off

04DIL
015091

5 off

52 62 72 82

1M

3B

2M

2B

53 61 71

83

54 62 72

84

3M

1B

53 61 73 83

4M

53 61 71 81

54 62 72 82

54 62 74 84

53 63 73 83

54 64 74 84

Pneumatic timer modules, time ranges of 0.2 30 s and 20 180 s


On-delayed
1M
1B
4
4
10

55 67

1 off

TPE11DIL
002279

1 off

56 68

Off-delayed

1M

1B

10

65 57

66 58

With TV1) approval to VDE 0116, for furnaces


On-delayed
1M
1B
4

10

55 67

56 68

Off-delayed

1M

1B

10

65 57

66 58

Mechanical latching module


E1

E2

Note

1)

TV = German Technical Supervisory Association

1 off

V-GDIL(24VDC)
048562

1 off

Version E combinations correspond to EN 50 011 and are


to be preferred; other combinations correspond to
EN 50 005

Accessories

Page

1 Amplifier module
Other accessories

04/026
04/026

04/014

Moeller HPL0211-2001/2002

DILR Contactor Relays


Complete Units

DILR Contactor Relays


Complete Units

Relays
Contactor Relays

M = Make
B = Break

Rated operational
current Ie
AC-15
220 V
380 V
230 V
400 V
240 V
415 V

Conv.
therm.
current
Ith

Type
Article no.

Circuit symbol

Complete units, with 1 early-make contact, 1 late-break contact


2M
2B
6
4
16
A1

13 21 35 47

DC operation
Price
See Price
List

Std. pack

Type
Article no.

4B

A1 13 23 33 47 51 61 71 85

Notes
Std. pack

Distinctive number
22

DILR22D(230V50HZ)
043792

1 off

DILR22D-G(24VDC)
048542

A2 14 22 36 48

4M

Price
See Price
List

Relays
Contactor Relays

AC operation
Contacts

04/015

Moeller HPL0211-2001/2002

44

DILR44D(230V50HZ)
043803

DILR44D-G(24VDC)
048547

53

DILR53D(230V50HZ)
043814

DILR53D-G(24VDC)
048552

1 off

Coil terminal markings to EN 50 005


Other actuating voltages a Page 04/030

DILR22D: supplied with front plate

A2 14 24 34 48 52 62 72 86

5M

3B

A1 13 23 33 47 53 61 71 85

A2 14 24 34 48 54 62 72 86

Accessories

Page

1 Amplifier module
Other accessories

04/026
04/026

04/016

Moeller HPL0211-2001/2002

Conv.
therm.
current
Ith

Timing relays, On-delayed


3
3

DILET Electronic Timing Relays

Time range

24 240 V, 50/60 Hz, AC


24 240 V, DC
Type
Price
Article no.
See Price
List

346 440V, 50/60 Hz, AC


Type
Article no.

Price
See Price
List

Available functions1)

Notes

Terminal markings to EN 50 042

Std.

Potential-free contact
Do not apply voltage!
1.5 30 s
0.05 1 s
0.15 3 s
0.5 10 s
3 60 s
0.15 3 min
0.5 10 min
3 60 min
0.15 3 h
0.5 10 h
3 60 h

Multi-function relay with connection for remote potentiometer


3
3
6
0.05 1 s
0.15 3 s
0.5 10 s
3 60 s
0.15 3 min
0.5 10 min
3 60 min
0.15 3 h
0.5 10 h
3 60 h

DILET11-30-A
048878
DILET11-M-A
048886

DILET11-30-W
048904
DILET11-M-W
048891

1 off

11

1 off

Type suffix

15

A1

11
16

A2

-A

18

-W

-A
-W
DILET70-A
048893

DILET70-W
048899

1 off

Z1

Z2
15

A1

A2

Z1

Notes

60 min
42 min
7

16

18

Z2

Y1

A1

Y2

A2

1)

15

16

Admissible cable length:


Cable, unscreened
Cable cross-section
0.5 1.5 mm2
Two-core cable
Two-core cable in same
cable duct as mains cable
50/60 Hz

Connection to
Y1/Y2
Z1/Z2
250 m
50 m

Accessories:
Sealable shroud
Remote potentiometer

Page
04/027
04/028

18

DILET11 supplied with stated function as standard

Flow diagrams
LED display

11 On-delayed
Time t not running
Contact 15 18 closed

12 Off-delayed

16 On- and Off-delayed

Y1-Y2

Y1-Y2

15-18

15-18

Time t running
Contact 15 18 closed
Time t running
Contact 15 18 open

A1-A2

A1-A2

A1-A2
15-18

LED

Calculated as follows:
Time requiredx10
--------------------------------------------------------------------- = Setting on time scale
Time range of timing relay

Actuating voltage
printed on unit
V DC
V AC
24 240
24 240,
50/60 Hz

346 440
50/60 Hz
Voltage tolerance:
V DC
V AC
16.8 288
20.4 264

294.1 484

11, 21, 42, 81

12, 16, 22, 82

Setting example
Time range of timing relay
Time required
Setting required on time scale

LED

21 Fleeting contact on energization

22 Fleeting contact on
de-energization

LED

42 Flashing
A1-A2

A1-A2

42 minx10
------------------------------ = 7
60 min

Relays
Contactor Relays

Relays
Contactor Relays

DILET Electronic Timing Relays

Rated operational
current Ie
AC-11
220V
380V
230V
400V
240V
440V

04/017

Moeller HPL0211-2001/2002

15-18

A1-A2

15-18
t

Y1-Y2

15-18

LED

LED

LED

81 Pulse generating

ON-OFF function
82 Pulse shaping
A1-A2

A1-A2
A1-A2

15-18
t

0.5 s

Y1-Y2
15-18
LED

t
LED

15-18
OFF

ON

OFF
LED

04/018

Moeller HPL0211-2001/2002

ETR4 Electronic Timing Relays

Conv.
therm.
current
Ith

220V
230V
240V

380V
400V
440V

Timing relays, On-delayed


3

Star-delta timing relays


3

ETR4 Electronic Timing Relays

Time range

24 240 V, 50/60 Hz, AC


24 240 V, DC
Type
Price

346 440 V, 50/60 Hz


Type

Price

Article no.

Article no.

See Price
List

0.05 1 s
0.15 3 s
0.5 10 s
1.5 30 s
5 100 s
15 300 s
1.5 30 min
15 300 min
1.5 30 h
5 100 h

ETR4-11-A
031882

3 60 s

ETR4-51-A
031884

See Price
List

ETR4-11-W
031883

Available functions1)

Available functions 1)

Terminal markings
to EN 50 042

Terminal markings
to EN 50 042

Std.
pack

1 off

11

Type suffix

Actuating voltage
printed on unit
V DC
V AC
24 240
24 240,
50/60 Hz

346 440
50/60 Hz
Voltage tolerance:
V DC
V AC
16.8 288
20.4 264

294.1 484

15

A1

-A
16

A2

18

-W

ETR4-51-W
031885

1 off

-A
-W

51
17
A1

18

A2

Multi-function relay
3

0.05 1 s
0.15 3 s
0.5 10 s
1.5 30 s
5 100 s
15 300 s
1.5 30 min
15 300 min
1.5 30 h
5 100 h

ETR4-69-A
031891

ETR4-69-W
031887

1 off

11, 21, 42, 81

16

A2

1)

Notes

Flow diagrams
11 On-delayed

28

12, 16, 22, 82

15

A1

Admissible cable length:


Cable, unscreened
Cable cross-section
0.5 1.5 mm2
Two-core cable
Two-core cable in same
cable duct as mains cable
50/60 Hz

B1 A1

18

A2

15

16

Connection to
B1
250 m
50 m

Accessories:
Screw adapter

18

Page
04/028

ETR4-11 and ETR4-51 supplied with stated function as standard

12 Off-delayed

16 On- and Off-delayed


A1-A2

A1-A2

21 Fleeting contact on energization


A1-A2

A1-A2
B1

15-18

B1

15-18

15-18

t
Power LED

Power LED

Power LED

15-18

Power LED

Rel LED

Rel LED

Rel LED

Rel LED

22 Fleeting contact on
de-energization

42 Flashing

81 Pulse generating

A1-A2

A1-A2

A1-A2
15-18

A1-A2

B1
t

82 Pulse shaping

15-18
Power LED

0.5 s

B1

15-18

15-18
Power LED

LED

t
Power LED

Rel LED

Rel LED

Rel LED

ON-OFF function
51 Star-delta
A1-A2

A1-A2
17-18
17-28
t

tu

15-18
OFF

ON

OFF
Power LED
Rel LED

Power LED
LED
LED

Relays
Contactor Relays

Relays
Contactor Relays

Rated operational
current Ie
AC-15

04/019

Moeller HPL0211-2001/2002

04/020

Moeller HPL0211-2001/2002

Relays
Contactor Relays

ETR4 Electronic Timing Relays

Rated operational
current Ie
AC-11
220 V
380 V
230 V
400 V
240 V
440 V

Conv.
therm.
current
Ith

Time range

24 240 V, 50/60 Hz, AC


24 240 V, DC
Type
Price
Article no.
See Price
List

Notes
Std. pack

Multi-function relay
With two changeover contacts and connection for remote potentiometer.
Can be converted to two timed contacts or one non-delayed contact and
one timed contact.
ETR4-70-A
3
3
6
0.05 1 s
031888
0.15 3 s
0.5 10 s
1.5 30 s
5 100 s
15 300 s
1.5 30 min
15 300 min
1.5 30 h
5 100 h

1 off

Type suffix

-A

Actuating voltage
printed on unit
V DC
V AC
24 240
24 240,
50/60 Hz
Voltage tolerance:
V DC
V AC
16.8 288
20.4 264

Admissible cable length:


Cable, unscreened
Cable cross-section
0.5 1.5 mm 2
Two-core cable
Two-core cable in same
cable duct as mains cable
50/60 Hz

Connection to
B1
Z1/Z2
250 m
50 m

Accessories
Screw adapter
Remote potentiometer

Page
04/027
04/028

04/021

Moeller HPL0211-2001/2002

ETR4 Electronic Timing Relays


ETR4-70 Flow Diagrams

Terminal markings
to EN 50 042

11, 21, 42, 81


ON OFF

Z1

15

X1

A2

16

25

18

26

28

21 Fleeting contact on energization


A1-A2
15-18
(25-28)

Terminal markings
to EN 50 042

12, 16, 22, 82


ON OFF

Z2
A1

11 On-delayed

Available functions

12 Off-delayed

Z2

B1

A1

X1

A2

15

16

25

18

26

28

16 On- and Off-delayed

A1-A2

A1-A2

A1-A2

15-18
(25-28)

B1

B1

15-18
(25-28)

Power LED
Power LED

Z1

Rel 1,2 LED

15-18
(25-28)

Power LED

Power LED

Rel 1,2 LED

Rel 1,2 LED

Rel 1,2 LED

42 Flashing

81 Pulse generating

22 Fleeting contact on de-energization

82 Pulse shaping

A1-A2

A1-A2

A1-A2

A1-A2

15-18
(25-28)

15-18
(25-28)

B1

B1

0,5 s

15-18
(25-28)

15-18
(25-28)

Power LED
Power LED

Power LED

Power LED
Rel 1,2 LED

Rel 1,2 LED

Rel 1,2 LED


Rel 1,2 LED

ON-OFF function
A1-A2
15-18
(25-28)
OFF

ON

OFF
Power LED
Rel 1,2 LED

A2/X1 not linked


a One non-delayed contact and one timed contact
Available functions
Terminal markings
to EN 50 042
11, 21, 42, 81
ON OFF

Z1

Z2
A1

X1

11 On-delayed

A2

Available functions

16

12, 16, 22, 82


ON - OFF

21

15

18

22

A1-A2
t

Z1

Z2

B1

A1

X1

24

21 Fleeting contact on energization


15-18

Terminal markings
to EN 50 042

12 Off-delayed

A2

21

15

16

18

22

24

16 On- and Off-delayed

A1-A2

A1-A2

A1-A2

15-18

B1

B1

15-18
21-24

15-18
t

21-24
Power LED
21-24
Power LED

Rel 1 LED
Rel 2 LED

Rel 1 LED
Rel 2 LED

42 Flashing

81 Pulse generating
15-18

Power LED

Rel 1 LED

Rel 1 LED

Rel 2 LED

Rel 2 LED

22 Fleeting contact on de-energization

A1-A2

21-24

Power LED

82 Pulse shaping

A1-A2

A1-A2

A1-A2

15-18

B1

B1

0.5 s

15-18
t

Power LED

15-18
t

21-24

21-24

Power LED

21-24

Rel 1 LED
Rel 2 LED

Power LED

Rel 1 LED

21-24
Power LED

Rel 2 LED

Rel 1 LED
Rel 1 LED
Rel 2 LED

ON-OFF function
A1-A2
15-18
(25-28)
OFF

ON

OFF
Power LED
Rel 1,2 LED

Rel 2 LED

Relays
Contactor Relays

A2/X1 linked
a Two timed contacts
Available functions

04/022

Moeller HPL0211-2001/2002

Relays
Contactor Relays

ESR Electronic Safety Relays


Engineering
Applications

Safety category

Function

Electronic safety relays are used for monitoring safetyrelated control systems. The requirements for the
electrical equipment of machines are specified in
IEC/EN 60 204. EN 954-1 stipulates that machine
users must carry out a risk assessment of machines
and implement a control system that meets the
requirements of safety categories 1, 2, 3, or 4.

The ESR electronic safety relays are approved by


employers' liability associations and meet the
requirements of safety category 3 or 4. The safety
category of the control system is determined by the
combination with the external circuitry, for which the
machine operator is responsible.
The electronic safety relays are single-fault proof,
i.e. one fault in the safety circuit does not cause
hazardous conditions. EN 954-1 excludes the
possibility of two independent faults occurring at the
same time.

In fault-free operation, following the starting


command, the safety circuits are monitored by the
electronics, and the enabling paths are activated via
the relay. Following the switch Off command, and also
in the event of a fault (earth fault, faulty insulation,
wire breakage etc.), the enabling paths are blocked
immediately (stop category 0) or with a time delay
(stop category 1), and the motor is disconnected from
the power supply. Since a short circuit in the
redundant safety circuit does not cause a hazardous
condition, the fault is not detected until the system is
reset, when switching On is prevented.

Construction
The electronic safety relays consist of a power section,
the electronics and two redundant relays with
interlocked opposing contacts for the enabling- and
signalling paths.

Stop category

Single/dual-channel construction
IEC/EN 60 204-1 stipulates two relevant stop
categories for stopping in the event of an emergency:
Stop category 0: stopping by means of immediate
removal of the power supply to the machine
actuators.
Stop category 1: controlled stopping with power
available to the machine actuators to achieve the
stop. Power is not removed until the stop is
achieved.

Product range overview


The range includes relays for:

Emergency-Stop
circuits

Monitoring of contact
mats/safety mats, and
safety bumpers

Protective guard
monitoring

Monitoring of
two-hand controls

Contact expansion modules with and


without time delay are also available.

The safety relays for Emergency-Stop applications and


the non-delayed expansion modules are suitable for
Stop category 0. Delayed contact expansion modules
meet the requirements of Stop category 1.

Safety relays for stopping in the event of an


emergency and for monitoring of protective guards
are available for single-channel and dual-channel
applications. The single-channel construction enables
earth-fault monitoring to be implemented for the
safety circuit. The dual-channel application provides a
redundant Emergency-Stop or protective guard
monitoring circuit. This allows monitoring for short
circuits and cable insulation faults to be implemented
additionally. The device can also be used with or
without reset monitoring. In this way, the device is not
started and enabling paths switched until the falling
edge of the On push-button has been detected. An
application for the device without reset monitoring is
for example, for monitoring protective doors for an
automatic restart.

04/023

Moeller HPL0211-2001/2002

ESR Electronic Safety Relays


Basic Units, Contact Expansion Modules
Actuating voltage
Uc

Safety
category to
EN 954-1

Enabling path
to
IEC/EN 60 204

Type
Article no.

Price
See Price List

Std. pack

Safety relays for Emergency-Stop and protective door monitoring1)


230 V 50/60 Hz
Dual-channel
4

ESR3-NO-31(230V)
214615

24 V DC 50/60 Hz

Single-channel

ESR4-NO-31
214612

24 V DC 50/60 Hz

Dual-channel

SR4-NO-21
214613

24 V DC

Dual-channel Offdelayed 0.15 3 s

34)/4 5)

ESR4-NV3-30
214616

24 V DC

Dual-channel Offdelayed 1.5 30 s

34)/4 5)

ESR4-NV30-306)
214617

24 V DC

Dual-channel
delayed 1.5 30 s8)

34)/4 5)

ESR4-NT30-307)
225011

Dual-channel

ESR4-NM-21
214619

1 off

24 V DC 50/60 Hz

Dual-channel

ESR4-NZ-21
214620

1 off

Contact expansion modules1)


24 V DC 50/60 Hz

Non-delayed

42)

43)

ESR4-NE-42
214614

1 off

Off-delayed
tA = 3 s

42)

ESR4-VE3-42
214618

1 off

Safety relay for contact mat monitoring 1)


24 V DC

1 off

Two-hand relay1) 9)

24 V DC

Notes

1)
2)
3)
4)
5)
6)
7)
8)
9)

For more information and examples of circuits a Safety Manual: TB0-009


The basic unit determines the maximum safety category.
The basic unit determines the maximum stop category.
Delayed contacts
Non-delayed contacts
Suitable for AT0-...MT-ZBZ safety position switches with mechanical securing action
Suitable for AT0-...FT-ZBZ safety position switches with mechanical securing action
Contact closes following Emergency-Stop actuation, On-delayed
Suitable for applications to EN 574 Type III C

Relays
Contactor Relays

Stop category
0
1

04/024

Moeller HPL0211-2001/2002

EMR4 Measuring and Monitoring Relays


Current Monitoring Relays, Phase Sequence Relays, Phase Monitoring Relays, Phase Imbalance Monitoring Relays

Relays
Contactor Relays

Description

EMR4-I... current monitoring relays


Switching hysteresis
adjustable from 5 30 %
Response delay
0.05 30 s
Supply voltage LED: green
Status indication via LEDs
EMR4...-A: monitors one
upper or lower limit
EMR4...-B: monitors
one upper limit

Description

EMR4-F... phase sequence relays


Monitors three-phase
systems for phase sequence
and
phase failure (< 0.6 X Ue)
Status indication via LEDs
Supply voltage
= voltage being monitored
Description

EMR4-W... phase monitoring relays


Monitors three-phase
systems for phase sequence,
over- and undervoltage and
phase failure (< 0.6 X Ue)
3-phase voltage monitoring
within a range
Status indication via LEDs
Selectable On-delay or
Off-delay
between 0.1 10 s

Description

Adjustable current
measuring range
I~/I=

3 30 mA
10 100 mA
0.1 1 A
0.3 1.5 A
15A
3 15 A

Monitoring
voltage

200 500 V AC

Circuit symbol

Supply
voltage

Type

Price

Article no.

See Price
List

Std.
pack

24 240 V AC/DC

EMR4-I1-2-A
221781

24 240 V AC/DC

EMR4-I15-2-A
221782

220 240 V AC

EMR4-I15-2-B
221783

Supply
voltage

Type
Article no.

Std.
pack

200 500 V AC

EMR4-F500-2
221784

1 off

Supply
voltage

Type
Article no.

160 300 V AC

EMR4-W500-2-C
221785

300 500 V AC

EMR4-W500-2-D
221786

300 500 V AC

EMR4-W580-2-D
221787

Circuit symbol

Supply
voltage

Type
Article no.

L1 L2 L3

380 415 V 50 Hz

EMR4-A400-1
221788

B1 B2 B3

15

25

1 off

C
A1

A2 16 18 26 28

Circuit symbol

L1 L2 L3

1115

2125

1216 1418 2226 2428

Monitoring
voltage
Adjustable by

Umin 300 380 V AC


Umax 420 500 V AC

Circuit symbol

L1 L2 L3

A1

15

A2 16 18 26 28

Umin 350 430 V AC


Umax 500 580 V AC

Monitoring
voltage

EMR4-A... phase imbalance monitoring relays


380 415 V 50 Hz
Monitors three-phase
systems for phase imbalance
Detects phase failure even
at 95 % regeneration of the
failed phase
Response delay: 0.5 s
Switching threshold
adjustable from 5 15 %
imbalance
Status indication via LEDs
Phase sequence detection
Supply voltage = voltage
being monitored

25

15

16 18

Price
See Price
List

Std.
pack

1 off

Price
See Price
List

Std.
pack

1 off

04/025

Moeller HPL0211-2001/2002

EMR4 Measuring and Monitoring Relays


Level Monitoring Relays, Insulation Monitoring Relays, Sealable Shrouds

EMR4-N... liquid level monitoring relays


Monitors the level of
conductive liquids
Monitors the ratio of mixtures of
conductive liquids
Status indication via LEDs
Dual-voltage protection against
running dry or overflow

Response
sensitivity range

5 100 kO

Circuit symbol

C Max.Min.

A1

Supply
voltage

11

See Price
List

EMR4-N500-2-B
221790
EMR4-N500-2-A
221791

Std.
pack

1 off

A2 12 14

220 240 V AC

250 O 500 k O

24 240 V AC/DC

Description

Insulation
resistance range

Monitors the insulation resistance


between non-earthed AC supply
systems and protective conductor/
earth
Tripping function memory
Insulation monitoring in 1- and
3-phase AC supply systems
Test via local test button or
remote test/operation
Status indication via LEDs to
VDE 0413 Part 2

Article no.

EMR4-N100-1-B
221789

250 O 500 k O

10 110 kO

Price

220 240 V AC

Monitors the level of


conductive liquids
Monitors the ratio of mixtures of
conductive liquids
Status indication via LEDs
Selectable On-delay or
Off-delay
between 0.5 10 s

EMR4-R... insulation monitoring relays


Monitors the insulation resistance
in non-earthed DC supply systems
Selector switch between opencircuit or closed-circuit principle
With test and reset facilities
Status indication via LEDs

Type

Circuit symbol

L+ L

15

Supply
voltage

Type
Article no.

Price
See Price
List

24 240 V AC/DC

EMR4-RDC-1-A
221792

1 off

24 240 V AC/DC

EMR4-RAC-1-A
221793

1 off

Std.
pack

R<

10 110 kO

A1

A2 16 18

15

R<

A1

B2

A2 16 18

Mounting width

Type
Article no.

Price
See Price
List

22.5 mm

EMR4-PH22
221795

1 off

45 mm

EMR4-PH45
221794

1 off

Std.
pack

EMR4-PH... sealable shroud

Relays
Contactor Relays

Description

04/026

Moeller HPL0211-2001/2002

Mini Contactor Relays, Contactor Relays


Accessories
Rated operational
current Ie

Actuating voltage Us/


actuating current I

AC-15
DC1)
240/415 V 220 V

Relays
Contactor Relays

1.5/1

Type
Article no.

Price
See Price
List

DILR..

VS1DIL
055480

1 off

DILR..

VS2DIL
057853

1 off

As
required

ETS4-VS3
083094

1 off

DILE...

TDDILE24
090200

1 off

For use with DILER(M)


with DC operated coil
only. Off-delay: with
auxiliary contact
approx. 100 ms,
without auxiliary
contact approx. 130 ms.

DILE...

VGDILE48
010320
VGDILE250
010336
VGDILE415
010463

10 off

For use with AC


operated 5060 Hz
contactor relays only.
The suppressor is fitted
as standard in DC
operated contactor
relays

DILR...

VGBDIL24
076837
VGBDIL48
071609
VGBDIL250
071610
VGBDIL415
071611

10 off

For AC operated
5060 Hz and DC
operated contactor
relays

DILE...

RCDILE48
044264
RCDILE250
046320
RCBDIL48
067345
RCBDIL250
069718
RCBDIL415
072091

1 off

For AC operated
5060 Hz contactor
relays Note drop-out
delay

FDBDIL
074464

10 off

For DC operated
contactor relays
Note drop-out delay

Std. pack

V DC/mA

Amplifier modules, plug-in type


1.5/1
0.2

With integral
suppressor circuit

For use
with
contactor
relays

0.2

24/11

24/11

Amplifier module for separate mounting


3/3
0.03
24/25

A0

A2

A1

A2

A0

A2

A1

A2

21

13

22

14

VS1DIL and VS2DIL


amplifier modules can
be mounted directly.
Contactor coils with
rated operational
currents > 2 A must be
energized via the
DILER-G mini contactor
relay.
Overvoltage limitation:
The output on VS2DIL
and the input on ETS4VS3 are equipped with
an integral suppressor
circuit.

Off-delay mechanism
24/

Suppressors
Varistor suppressor

24 48 V
110 250 V

A1

A2

380 415 V

12 24 V
24 48 V
110 250 V
380 415 V
RC suppressors

24 48 V
110 250 V

A1

A2

24 48 V

DILE...
DILR...

110 250 V
380 415 V
Free-wheel diode suppressors

12 250 V

A1

DILR...

A2

Notes

1)

Making and breaking conditions:


VS1DIL, VS2DIL and ETS4-VS3 to DC-13, L/R 300 ms.

Moeller HPL0211-2001/2002

04/027

Mini Contactor Relays, Contactor Relays, Electronic Timing Relays


Accessories
For use with
contactor relays or
timing relays

Type
Article no.

DILE...
DILET...

V0DILE
026634

50 off

0 mm distance between relays

DILR...
ETR4

V0DIL
010772

20 off

0 mm distance between relays

DILR...
ETR4

V5/15DIL
013145

10 off

5 mm distance between relays


15 mm distance between relays for mechanical
interlock between both relays

DILE...

MVDILE
010113

5 off

For two AC or DC operated contactor relays,


mounted vertically or horizontally. Distance
between contactor relays 0 mm, mechanical
lifespan 2.5 x 106 operations. Additional
auxiliary contact modules can be fitted.
a Page 04/012

DILE...
...DILE
DILR
...DIL

BT480
052785

100 off

Not proof against accidental contact to IEC 536

DILE...
DILET...
DILR...

BT483
059904

100 off

Use insulated ferrules

DILE...
DILET...

HDILE
010482

1 off

Snap fitting on contactor relay. For use with


open-type contactor relays or in service
distribution boards.
IP40 degree of protection from front.
Can be drilled for the setting dials of the timing
relay.

TPE(H)
TPD(H)

PL-DILT
036073

5 off

For screw fixing on timer module, and


subsequent sealing

Std. pack

Spacers
For arranging contactor
relays and timing relays in
combinations

Mechanical interlock

Paralleling link
For auxiliary contacts

Blade terminal DIN 46 244


For auxiliary contact and
coil connections

Sealable shrouds
Transparent

Relays
Contactor Relays

Price
See Price
List

04/028

Moeller HPL0211-2001/2002

Relays
Contactor Relays

Mini Contactor Relays, Contactor Relays, Electronic Timing Relays


Accessories
For use with
contactor relays
or timing relays

Type
Article no.

DILET...
ETR4-70

RR-10
031344

1 off

ETR4

CS-TE
095853

1 off

For screw fixing of ETR4 timing


relays

...DIL

KG10
022256

500 off

Clips into 2-pole auxiliary contact modules

8 x 20 mm

...DILE, DILER
...DIL, DILR

KG20
091075

500 off

Clips into 4-pole auxiliary contact modules


and basic units

Label plate with


fixing stud

8 x 17.5 mm
Colour: white

DIL...

XGKS-Z
207508

500 off

For use with Moeller equipment


with the corresponding mounting hole

Sheet of labels

7.5 x 17 mm

XGKS, XGKS-Z
KG20

XGKE-GE
207517

25 off

1 off = 1 sheet
240 labels per sheet

Colour: yellow HKS 3


(QRAL 1018)

For inscription
using laser
printer, plotter,
transparencyprinter,
photocopier

Colour: RAL 7035,


light grey

DIL...

XGKA-Z
207513

250 off

To secure XGKS on Moeller equipment with


the corresponding mounting hole

AC

DILR

1 off

Other actuating voltages


a Page 04/031

DC

DILR

J-DIL00M(230V50HZ)
043833
G-DIL00M(24VDC)
048557

Remote potentiometer, IP54


10 kO linear
0.25 W max.

Price
See Price
List

Std. pack

Screw adapter

Component labelling system


Label
8 x 10 mm

Adapter with
fixing stud

1 sheet = DIN A4,


can be split into two DIN A5 sheets

Individual coils

1 off

04/029

Moeller HPL0211-2001/2002

Mini Contactor Relays, Contactor relays


Contact Travel Diagrams
The diagrams show the closing and opening travel of the contacts of the contactor relays and auxiliary contacts at no load.
Tolerances are not taken into consideration.
DILER-AC

DILR
Make contact
0

1,9

2,78 mm

Break contact

4,3 5,7 mm

Break contact
0 0,95

2,78 mm

DILER-DC

Early-make contact
Make contact
0

1,9

2,85 mm

Late-break contact

2,5

5,7 mm

2,4

5,7 mm

5,6

5,7 mm

Break contact
0 0,95

2,85 mm

...DIL
Make contact

...DILE
Make contact

7 mm

Break contact
0

1,9

Break contact
0 0,89

2,78 mm
2,78 mm

3,9

7 mm

TP...11DIL
Make contact

...DDILE

Early-make contact
0

1,06

2,88 mm

Late-break contact
Make contact
Break contact

4,1

5,7 mm

Break contact

1,86

2,88 mm

1,9

2,78 mm

0 0,89

2,78 mm

0 1,7

5,7 mm

Relays
Contactor Relays

Make contact

04/030

Moeller HPL0211-2001/2002

DILER Mini Contactor Relays, DILR Contactor Relays


Actuating Voltages

Relays
Contactor Relays

AC

DILER-40(...)

DILER-31(...)

DILER-22(...)

DILR40(...)

DILR31(...)

DILR22(...)

Article no. 1)

Article no. 1)

Article no. 1)

Article no.1)

Article no. 1)

Article no.1)

Standard voltages

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

12V50Hz
24V50Hz
48V50Hz
240V50Hz
24V60Hz
110V60Hz
115V60Hz
42V50Hz,
48V60Hz
110V50Hz,
120V60Hz
190V50Hz,
220V60Hz
220V50Hz,
240V60Hz
230V50Hz,
240V60Hz
380V50Hz,
440V60Hz
400V50Hz,
440V60Hz
415V50Hz,
480V60Hz
24V50/60Hz
42V50/60Hz
110V50/60Hz
230V50/60Hz

066169
010094
010190
010478
010110
010254
010270
051755

066170
010251
010044
010300
010267
010172
010204
051764

066171
010344
010201
010138
010497
010265
010211
051773

025066
055915
017947
027439

096255
043752

029810
058286
022691
032183

010826
043764

077267
091505
017943
084386

093878
043776

051756

051765

051774

043753

043765

043777

051757

051766

051775

043754

043766

043778

051758

051767

051776

043755

043767

043779

051759

051768

051777

043756

043768

043780

051760

051769

051778

043757

043769

043781

051761

051770

051779

043758

043770

043782

051762

051771

051780

043759

043771

043783

021924
033459
021961
052725

021594
029869
021624
052509

021704
029433
021871
052508

022693
039304
091509
052762

027437
044048
096253
052761

058284
060657
065403
052726

Non-standard voltages
(i.e. voltages other than the
standard voltages listed above)2)
...V50Hz(12600V)
...V60Hz(12600V)

Price
See Price List

Price
See Price List

Price
See Price List

986763
989136

991507
993880

934554
936927

DC

DILER-40-G(...)

DILER-31-G(...)

DILER-22-G(...)

DILR40-G(...)

DILR31-G(...)

DILR22-G(...)

Standard voltages

Article no. 1)
Price
See Price List

Article no. 1)
Price
See Price List

Article no. 1)
Price
See Price List

Article no.1)
Price
See Price List

Article no. 1)
Price
See Price List

Article no.1)
Price
See Price List

12V DC
24V DC
48V DC
60V DC
110V DC
220V DC

079711
010223
010255
010271
010287
010303

079761
010157
010205
010221
010253
010269

080728
010042
010346
010499
010043
010091

048537
048538
048539
048535
048536

048532
048533
048534
048530
048531

048526
048527
048528
048529
048525

Non-standard voltages
(i.e. voltages other than the
standard voltages listed above)2)
...VDC(12250V)

Price
See Price List

Price
See Price List

Price
See Price List

915590

915591

915592

Notes

1)
2)

To obtain the article number for ordering, read under selected type and actuating voltage from the table above.
For non-standard voltages, state the actuating voltage selected from the range (......V) shown.

04/031

Moeller HPL0211-2001/2002

AC

DILR22D(...)

DILR44D(...)

DILR53D(...)

VDIL(...)

J-DIL00M(...)
Individual coil

Article no.1)

Article no. 1)

Article no.1)

Article no.1)

Article no.1)

Standard voltages

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

24V50Hz
48V50Hz
240V50Hz
24V60Hz
115V60Hz
42V50Hz,
48V60Hz
110V50Hz,
120V60Hz
190V50Hz,
220V60Hz
220V50Hz,
240V60Hz
230V50Hz,
240V60Hz
380V50Hz,
440V60Hz
400V50Hz,
440V60Hz
415V50Hz,
480V60Hz
24V50/60Hz
42V50/60Hz
110V50/60Hz
230V50/60Hz

013207
041683
096261
015580
084396
043788

072533
010836
065414
074906
053549
043799

055923
084399
044058
058296
032193
043810

053536
055493
053115
053659
052241
043821

000079
023809
066693
099744
043837
043829

043789

043800

043811

043822

043830

043790

043801

043812

043823

043831

043791

043802

043813

043824

043832

043792

043803

043814

043825

043833

043793

043804

043815

043834

043794

043805

043816

043835

043795

043806

043817

043836

010834
027445
079650
052760

070160
086771
048803
052838

048804
070161
027447
052961

053217
055218
051165
054487

002452
011944
085506
051352

Non-standard voltages
(i.e. voltages other than the
standard voltages listed above)2)
...V50Hz(12415V)
...V50Hz(12600V)
...V60Hz(12415V)
...V60Hz(12600V)

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

974904

977277

944057

946430

922701

925074

903184

903183

910098

910099

DC

DILR22D-G(...)

DILR44D-G(...)

DILR53D-G(...)

V-GDIL(...)

G-DIL00M(...)

Standard voltages

Article no.1)
Price
See Price List

Article no. 1)
Price
See Price List

Article no.1)
Price
See Price List

Article no.1)
Price
See Price List

Article no.1)
Price
See Price List

24VDC
48VDC
60VDC
110VDC
220VDC

048542
048543
048544
048540
048541

048547
048548
048549
048545
048546

048552
048553
048554
048550
048551

048562
048563
048564
048560
048561

048557
048558
048559
048555
048556

Non-standard voltages
(i.e. voltages other than the
standard voltages listed above)2)
...VDC(12250V)

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

Price
See Price List

915578

915579

915580

915545

910110

Notes

1)
2)

To obtain the article number for ordering, read under selected type and actuating voltage from the table above.
For non-standard voltages, state the actuating voltage selected from the range (......V) shown.

Relays
Contactor Relays

DILR Complete Units, VDIL Mechanical Latching Module, J-DIL Individual Coil
Actuating Voltages

04/032

Moeller HPL0211-2001/2002

DIL Contactor Relays, DILET Electronic Timing Relays


Tripping Characteristics
DILR (AC-15)

DILR(AC-15)
a = Make contact
b = Break contact

Component lifespan (operations)


Ie = Rated operational current

Max. operating frequency (approx.)


Ie = Rated operational current
Ops./h 5000

Relays
Contactor Relays

X 106
2000
20
10
b
1000

5
a
2

500
1
0.5
0.2

200
AC-15

AC-15

240 V

240 V

0.1
0.01

0.02

0.05

0.1

0.2

0.5

100

10 A

9 10 A

Ie

Ie

DILR(DC-131))

DILR(DC-131))

Component lifespan (operations)


Ie = Rated operational current

Max. operating frequency (approx.)


Ie = Rated operational current
Ops./h 5000

X 106
2000
20
10
1000
5
2

500

1
DC-13

DC-13
0.5

200

220 V

220 V
L

0.2

L
Q 50 ms
R

Q 50 ms

R
100

0.1
0.01 0.02

0.05

0.1

0.2

0.5

10 A

10 A

Ie

Ie
DILR(DC-131))

DILR(DC-131))

Component lifespan (operations)


Ie = Rated operational current

Max. operating frequency (approx.)


Ie = Rated operational current
ops./h

5000

106
2000
20
10
1000

500

1
DC-13
0.5
0.2

200

24 V
L
R

L
Q 50 ms
R

50 ms

0.1
0.01 0.02

24 V

100
0.05

0.1

0.2

0.5

10 A

le

Notes

1)

Making and breaking conditions to DC-13, time constant as stated.

10 A

Ie

Moeller HPL0211-2001/2002

04/033

DIL Contactor Relays, DILET Electronic Timing Relays


Tripping Characteristics
DILER(AC-15)
Component lifespan (operations)
Ie = Rated operational current

Relays
Contactor Relays

x 106

20
10
5

2
1
0.5
AC-15
0.2

240 V

0.1
0.01 0.02

0.05

0.1

0.2

0.5

10 A

Ie

DILET(AC-11)
Component lifespan (operations)
Ie = Rated operational current

x 10 6

20
10
5

2
1
0.5
AC-11
0.2

240 V

0.1
0.01

0.02

0.05

0.1

0.2

0.5

10 A
e

04/034

Moeller HPL0211-2001/2002

EMR4 Measuring and Monitoring Relays


Tripping Characteristics
EMR4-I... current monitoring relays
Function at overcurrent, OC
a Supply voltage on A1-A2
b Hysteresis (reset value) undercurrent, UC
c Response threshold for measuring the current
d Hysteresis (reset value) overcurrent, OC
e Timed contact 1: 15-18, 15-16
f Timed contact 2: 25-28, 25-26

a
b

Relays
Contactor Relays

c
d
e

tm = 80 ms, measuring cycle


t = (0.05 1 s; 1.5 30 s)
On-delay

f
tm

<t
Function at undercurrent, UC
a Supply voltage on A1-A2
b Hysteresis (reset value) undercurrent, UC
c Response threshold for measuring the current
d Timed contact 1: 15-18, 15-16
e Timed contact 2: 25-28, 25-26

a
b
c

tm = 80 ms, measuring cycle


t = (0.05 1 s; 1.5 30 s)
On-delay

e
tm

<t

EMR4-F... phase sequence relay

L1, L2, L3

L1, L3, L2

L1, L2, L3

a
b

L2, L3
L1 d

a Voltage being monitored, three-phase system, L1, L2, L3


b Timed contact 1: 11-14, 11-12
c Timed contact 2: 21-24, 21-22
d Phase failure 100 %

c
EMR4-W... phase monitoring relay
On-delayed fault indication: function
a Supply voltage on A1-A2
b>U
c Hysteresis + 5 %
d Monitored voltage (rated voltage) L1, L2, L3
e Hysteresis 5 %
f<U
e Timed contact 1: 15-18, 15-16
h Timed contact 2: 25-28, 25-26

a
b
c
d
e
f

h
t

t = Delay time applies only to overvoltage/undervoltage monitoring

<t
Off-delayed fault indication: function
a Supply voltage on A1-A2
b>U
c Hysteresis + 5 %
d Monitored voltage (rated voltage) L1, L2, L3
e Hysteresis 5 %
f<U
e Timed contact 1: 15-18, 15-16
h Timed contact 2: 25-28, 25-26

a
b
c
d
e
f

h
t

t = Delay time applies only to overvoltage/undervoltage monitoring

t
<t

Moeller HPL0211-2001/2002

04/035

EMR4 Measuring and Monitoring Relays


Tripping Characteristics
a
L1, L2, L3

L1, L3, L2

L1, L2
L3

L1
L2
L3

L1, L2

L3
d L1/L3 > I Asym. I

a Adjustable imbalance threshold 5 15 %


b Monitoring voltage L1, L2, L3 and supply
voltage Urated
c Adjustable imbalance threshold 5 15 %
d Level L1, L2, L3
e Monitoring contact/Timed contact 1: 15-18, 15-16
t = Delay time applies only with phase imbalance,
500 ms fixed setting

e
t

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

EMR4-N100... liquid level monitoring relay

a
b
c
d
e

a Maximum filling level


b Minimum filling level
c Reference sensor C
a Supply voltage on A1-A2
e Relay contact function: Drain
DOWN: 11-14, 11-12
f Relay contact function: Fill
UP: 11-14, 11-12

a
b
c
d
e

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

EMR4-N500... liquid level monitoring relay


a Maximum filling level
b Minimum filling level
c Reference sensor C
a Supply voltage on A1-A2
e On-delay function
15-18, 25-28, 15-16, 25-26
f Off-delay function
15-18, 25-28, 15-16, 25-26

f
t

EMR4-RDC... insulation monitoring relay

a
b
c
d
e
f

1.6 Rx
Rx

g
h
tT

a Supply voltage on A1-A2


b Front actuator reset L+ and
L/test L+, reset test L+
c Front actuator test LRemote connection test L, test L, S3-S4
d Remote connection test L+, S3-S1
e Remote connection save, reset, S3/S2
f Insulation resistance R of the supply system,
Set response value Rx, L+(L)/
g Front switch function:
: Open circuit arrangement/make circuit,
: Closed-circuit arrangement/break circuit
h Timed contact: 15-18, 15-16
tT = Test duration approx. 1 s

EMR4-RAC... insulation monitoring relay


a Supply voltage on A1-A2
b Remote connection save, reset, S1/S2
c Front actuator, Test/Reset reset, test
Remote connection S1/ reset, test
d Insulation resistance of the supply system
Set response value Rx
e Timed contact: 15-18, 15-16

a
b
c

1.6 Rx
Rx

tT = Test duration > approx. 300 ms

e
tT

Relays
Contactor Relays

EMR4-A... phase imbalance monitoring relay

04/036

Moeller HPL0211-2001/2002

EMR4 Measuring and Monitoring Relays


Tripping Characteristics
Load limit curves, range 22.5 mm
AC load (resistive)

Relays
Contactor Relays

U
[V]

DC load (resistive)
U
[V]

300

300

200

200

100
80
60
50
40
30

100
80
60

20

20

10

40
30

0.1

0.2

0.5

10

10

0.1

0.2

0.5

10

[A]

[A]

Derating factor at inductive AC load


F

Contact life

1.0

Ops.

0.9

106
8
6

0.8
4
0.7

0.6

Contact life
Switching operations Ops.
220 V 50 Hz AC-1
360 contact sequences/h

Derating factor F
at inductive load

0.5
0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

105

1.0

cos v

[A]

Load limit curves, range 45 mm


AC load (resistive)
U
[V]

DC load (resistive)
U
[V]

400
300

400
300

200

200

100
80
60

100
80
60

40
30

40
30

20

20

10

0.1

0.2

0.5

10

10

0.1

0.2

0.5

[A]

Derating factor at inductive AC load


F

Contact life
Ops.

1.0
0.9

10
8
6

0.8

0.7

0.6

Derating factor F
at inductive load

0.5
0.1

10
[A]

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0
cos v

10 5

Contact life
Switching operations Ops.
220 V 50 Hz AC-1
360 contact sequences/h
1

8
[A]

04/037

Moeller HPL0211-2001/2002

Easy Control Relays


Technical Data
EASY200-EASY

Weight
Mounting
Terminal capacity
Solid
Min./Max.
Flexible with ferrule
Min./Max.
Width of standard screwdriver
Tightening torque
Ambient climatic conditions
Operational ambient temperature: horizontal / vertical installation
Condensation
LCD display (clearly legible)
Storage/transport temperature
Relative humidity, non-condensing (IEC 60 068-2-30)
Air pressure (operation)
Corrosion resistance
IEC 60 068-2-42
4 days SO2
IEC 60 068-2-43
4 days H2S
Ambient conditions, mechanical
Pollution degree
Degree of protection (EN 50 178, IEC 60 529, VBG 4)
Vibration resistance to IEC 60 068-2-6
Constant amplitude 0.15 mm
Constant acceleration, 2 g
Mechanical shock resistance (half-sinusoidal shock 15 g/11 ms)
to IEC 60 068-2-32
Drop to IEC 60 068-2-31
drop height
Free fall, packaged (IEC 60 068-2-32)
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61 000-4-2, severity level 3, ESD)
Air discharge
Contact discharge
Electromagnetic fields (IEC/EN 61 000-4-3, RFI)
Radio interference suppression
Burst pulses (IEC/EN 61 000-4-4, Level 3)
Supply cables
Signal lines
High-energy pulses (surge) EASY-AC (IEC/EN 61 000-4-5)
High-energy pulses (surge) EASY-DC (IEC/EN 61 000-4-5,
severity level 2)
Immunity to line-conducted interference to IEC EN 61 000-4-6
Dielectric strength
Clearance in air and creepage distances dimensioned to
Dielectric strength
Back-up/accuracy of real-time clock (only on EASY-...C)
Clock battery back-up
at 25 C
at 40 C
Accuracy of the real-time clock
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
Resolution
Range s
Range M:S
Range H:M
Retentive memory
Write cycles of the retentive memory

EASY6...-...

EN 55 011, EN 55 022, IEC/EN 61 000-4, IEC 60 068-2-6, IEC 60 068-2-27

kg

35.5  90  53
71.5  90  53
107.5  90  53
(2 space units)
(4 space units)
(6 space units)
0.07
0.2
0.3
On EN 50 022 top-hat rail, 35 mm, or
screw fixing, using ZB4-101-GF1 fixing brackets (accessories)

mm
mm
mm
Nm

0.2/4
0.2/2.5
3.5  0.8
0.6

25/+55, low temperatures to IEC 60 068-2-1, high temperatures to IEC 60 068-2-2

C
C
%
hPa

Prevent condensation by suitable measures


0/+55
0/+55
40/+70
40/+70
5 95
5 95
795 1080
795 1080

0/+55
40/+70
5 95
795 1080

cm/m
cm/m

10
1

10
1

10
1

2
IP20

2
IP20

2
IP20

Hz
Hz
Impacts

10 57
57 150
18

10 57
57 150
18

10 57
57 150
18

mm
m

50
1

50
1

50
1

kV
kV
V/m

8
8
6
6
10
10
EN 55 011 Class B, EN 55 022 Class B

8
6
10

kV
kV
kV

2
2
2 (supply cable, balanced)

2
2

2
2

kV

0.5 (supply cable, balanced)

10

10

10

mm

(AWG 22 12)
(AWG 22 12)
3.5  0.8
0.6

EN 50 178, UL 508, CSA C22.2, No 142


EN 50 178
EN 50 178

3.5  0.8
0.6

EN 50 178

h
h
s/day

Normally 64
Normally 24
Normally g 5
(~ g 0.5 h/year)

Normally 64
Normally 24
Normally g5
(g 0.5 h/year)

g1

g1

ms
s
min

10
1
1

10
1
1

f 100 000

f 100 000

Relays
Contactor Relays

General technical data


Standards
Dimensions
WHD

EASY412-...

04/038

Moeller HPL0211-2001/2002

Relays
Contactor Relays

Easy Control Relays


Technical Data

Power supply
Rated operational voltage
Admissible range
Frequency, rated value, tolerance
Input current
at 115/120 V AC 60 Hz
at 230/240 V AC 50 Hz
Voltage dips (IEC/EN 61 131-2)
Heat dissipation
at 115/120 V AC
at 230/240 V AC

Power supply
Rated operational voltage
Admissible range
Residual ripple
Input current at 24 VDC
Voltage dips (IEC/EN 61 131-2)
Heat dissipation at 24 V DC

Digital inputs 115/230 V AC


Number
Status display
Potential isolation
From power supply
Between digital inputs
From the outputs
Rated voltage L (sinusoidal)
at signal 0
at signal 1
Rated frequency
Input current at signal 1
R1 to R12, I1 to I6
(EASY6... also I9 to I12)
Input current at signal 1
I7, I8
Delay time I1 to I6/I9 to I12
From 0 to 1 and from 1 to 0
Debounce ON
50/60 Hz
Debounce OFF
50/60 Hz
Delay time I7, I8 from 1 to 0
Debounce ON
50/60 Hz
Debounce OFF
50/60 Hz
Delay time I7, I8 from 0 to 1
Debounce ON
50/60 Hz
Debounce OFF
50/60 Hz
Max. admissible cable length (per input)
R1 to R12, I1 to I6
(with EASY 6... also I9 to I12)
I7, I8

EASY412-AC-...

EASY61...-AC-R...

V AC
V AC
Hz

110/115/120/230/240 (+10/15 %)
90 264
50/60 (g 5 %)

100/110/115/120/230/240 (+10/15 %)
85 264
50/60 (g 5 %)

mA
mA
ms

Normally 40
Normally 20
20

Normally 70
Normally 35
20

VA
VA

Normally 5
Normally 5

Normally 10
Normally 10

V DC
V DC
%
mA
ms
W

EASY412-DC-...

EASY412-DA-RC

EASY6...-DC-...

24 (15/+20 %)
20.4 28.8
F5
Normally 80
10
Normally 2

12 (15/+30 %)
10.2 15.6
G5
Normally 140
10
Normally 2

24 (15/+20 %)
20.4 28.8
F5
Normally 140
10
Normally 5

EASY412-AC-...

EASY618/619-AC-R...

8
LCD display (if provided)

12
LCD display (if provided)

No
No
Yes

No
No
Yes

V AC
V AC
Hz
mA

0 40
79 264
50/60
6 x 0.5 (at 230 V AC 50 Hz)
6 x 0.25 (at 115 V AC 60 Hz)

0 40
79 264
50/60
10 (12) x 0.5 (at 230 V AC 50 Hz)
10 (12) x 0.25 (at 115 V AC 60 Hz)

mA

2 x 6 (at 230 V AC 50 Hz)


2 x 4 (at 115 V AC 60 Hz)

2 x 6 (at 230 V AC 50 Hz)


2 x 4 (at 115 V AC 60 Hz)

ms
ms

80/66 n
20/16 n

80/66 n
20/16 n

ms
ms

160/150
100/100

80/66 n
20/16 n

ms
ms

80/66 n
20/16 n

80/66 n
20/16 n

Normally 40

Normally 40

Normally 100

Normally 100

Moeller HPL0211-2001/2002

04/039

EASY412-DC-...

EASY412-DA-RC

EASY6...-DC...

12 (on basic unit)

LCD display (if provided)

LCD display (if provided)

LCD display (if provided)

No
No
Yes
12
< 4.0 (I1 I8)
> 8.0 (I1 I8)

mA

No
No
Yes
24
< 5.0 (I1 I8)
> 15.0 (I1 I6)
> 8.0 (I7 I8)
3.3 (at 24 V DC)

3.3 (at 12 V DC)

No
No
Yes
24
< 5.0 (I1 I12, R1 R12)
> 15.0 (I1 I6, I9 I12, R1 R12)
> 8.0 (I7 I8)
3.3 (at 24 V DC)

mA

2.2 (at 24 V DC)

1.1 (at 12 V DC)

2.2 (at 24 V DC)

ms

20

20

20

Debounce Off

ms

Normally 0.25 (I1 I6)

Normally 0.30 (I1 I6)


Normally 0.35 (I7, I8)

Normally 0.25 (I1 I6, I9 I12)

Delay time from 1 to 0


Debounce On

ms

20

20

20

Debounce Off

ms

Normally 0.4 (I1 I6)


Normally 0.2 (I7, I8)
100

Normally 0.30 (I1 I6)


Normally 0.15 (I7, I8)
100

Normally 0.4 (I1 I6, I9 I12)


Normally 0.2 (I7, I8)
100

Digital inputs 24 V DC
Quantity, of which 2 inputs (I7, I8)
can be used as analog inputs
Status display
Potential isolation
From power supply
Between digital inputs
From the outputs
Rated operational voltage
at signal 0
at signal 1
Input current at signal 1
R1 to R12, I1 to I6
(EASY620/621 also I9 to I12)
Input current at signal 1
(I7, I8)
Delay time from 0 to 1
Debounce On

Cable length (unscreened)

Analog inputs
Number
Potential isolation
From power supply
From the digital inputs
From the outputs
Input type
Signal range
Resolution, analog
Resolution, digital

V DC
V DC
V DC

V DC
V

EASY412-D...

EASY6...-DC-...

No
No
Yes
DC voltage
0 10
0.1
0.1

No
No
Yes
DC voltage
0 10
0.1
0.1

U[V]
9.9

5.0

5.0

9.9

Input impedance
Accuracy of actual value

kO

11.2

11.2

Two EASY devices


Within a single device
Conversion time, analog/digital

%
%
ms

Input current
Cable length (unscreened)

mA
m

g3
g 2 (I7, I8) g 0.12 V
Input delay On: 20
Debounce Off: every cycle
<1
30

g3
g 2 (I7, I8) g 0.12 V
Input delay ON: 20
Debounce OFF: every cycle
<1
30

Relays
Contactor Relays

Easy Control Relays


Technical Data

04/040

Moeller HPL0211-2001/2002

Easy Control Relays


Technical Data

Relays
Contactor Relays

EASY412-...-R...
Relay outputs
Number
in groups of
Parallel connection of outputs to increase performance
Protection for one output relay
Potential isolation from mains supply, inputs
Safe isolation
Basic insulation
Lifespan, mechanical operations
Relay contacts
Conventional thermal current (10 A UL)
Recommended for load: 12 V AC/DC
Protection against short circuit, cos v = 1,
characteristic B16 at 600 A
Protection against short circuit, cos v = 0.5 0.7,
characteristic B16 at 900 A
Rated impulse withstand voltage Uimp contact to coil
Rated insulation voltage Ui
Rated operational voltage Ue
Safe isolation to EN 50 178 between coil and contact
Safe isolation to EN 50 178 between two contacts
Making capacity
AC-15 250 V AC, 3 A (600 Ops/h)
DC-13 L/R F150 ms 24 V DC, 1 A (500 Ops/h)
Breaking capacity
AC-15 250 V AC, 3 A (600 Ops/h)
DC-13 L/R F150 ms 24 V DC, 1 A (500 Ops/h)
Filament lamp load
1000 W at 230/240 V AC
500 W at 115/120 V AC
Fluorescent tubes
10 x 58 W at 230/240 V AC
With upstream electrical device
Uncompensated
1 x 58 W at 230/240 V AC
Conventional, compensated
Operating frequency, relays
Mechanical operations
Mechanical switching frequency
Resistive load/ lamp load
Inductive load
UL/CSA
Uninterrupted current at 240 V AC/24 V DC
AC
Control Circuit Rating Codes (utilization category)
Max. rated operational voltage
Max. thermal uninterrupted current at B 300
Max. Make/Break at B 300

EASY618/619-...-R...

V AC
V AC
x 106

4
6
1
1
Not admissible
Not admissible
Miniature circuit-breaker B16 or 8 A fuse (slow)
Yes
Yes
300
300
600
600
10
10

A
mA
A

8
> 500
16

8
> 500
16

16

16

kV
V AC
V AC
V AC
V AC

6
250
250
300
300

6
250
250
300
300

Operations
Operations

300 000
200 000

300 000
200 000

Operations
Operations

300 000
200 000

300 000
200 000

Operations
Operations

25 000
25 000

25 000
25 000

Operations
Operations

25 000
25 000

25 000
25 000

Operations

25 000

25 000

x 106
Hz
Hz
Hz

10
10
2
0.5

10
10
2
0.5

10/8

10/8

V AC
A
VA

B 300 Light Pilot Duty


300
5
3600/360

B 300 Light Pilot Duty


300
5
3600/360

V DC
A
VA

R 300 Light Pilot Duty


300
1
28/28

R 300 Light Pilot Duty


300
1
28/28

DC
Control Circuit Rating Codes (utilization category)
Max. rated operational voltage
Max. thermal uninterrupted current at B 300
Max. Make/Break at R 300

Moeller HPL0211-2001/2002

04/041

Transistor outputs
Number
Rated operational voltage Ue
Admissible range
Residual ripple
Supply current
at 0 signal
at 1 signal
Protection against polarity reversal
Potential isolation from power supply, inputs

EASY6...-DC-T...

4
24
20.4 28.8
F5

8
24
20.4 28.8
F5

mA
mA

9/16
12/22
Yes
Yes

18/32
24/44
Yes
Yes

A
W
mA

0.5
5
< 1.0

0.5
5
< 1.0

V DC
V DC

2.5
2.5
U = Ue 1 V
U = Ue 1 V
Yes (detected via diagnostics input I16, I15; R15, R16)
0.7 F Ie F 2
0.7 F Ie F 2
8
16
16
32
Yes
Yes
40 000
40 000

V DC
V DC
%
Normally/max.
Normally/max.

max.
Rated current Ie at 1 signal, DC
Lamp load without Rv
Residual current at signal 0, per channel
Max. output voltage
at signal 0 with external load < 10 MO
at signal 1, Ie = 0.5 A
Short-circuit protection
Short-circuit tripping current for Ra F 10 mO
Max. total short-circuit current
Peak short-circuit current
Thermal cutout
Max. operating frequency at constant resistive load (depending on
circuit configuration and load), RL < 100 kO
Parallel connection of outputs with resistive load;
inductive load with external suppression circuit, combination
within a group
Quantity of outputs
max.
Total maximum current
Status display of the outputs

Approvals
Currently UL/CSA approved; others in preparation:

Oscillation test to EN 61 373 for railway applications, passed

Notes

EASY412-DC-T...

A
A
A
Ops./h

Group 1: Q1 to Q4

Group 1: Q1 to Q4, S1 to S4
Group 2: Q5 to Q8, S5 to S8

4
2.0
LCD display (if provided)

4
2.0
LCD display (if provided)

EASY200-EASY
EASY412-DC-R
EASY412-DC-RC
EASY412-DC-TC
EASY412-DC-TCX
EASY412-AC-R
EASY412-AC-RC
EASY412-AC-RCX
EASY618-DC-RC
EASY618-AC-RC
EASY618-AC-RE
EASY619-DC-RC
EASY619-DC-RCX
EASY619-AC-RC
EASY619-AC-RCX
EASY620-DC-TC
EASY620-DC-TE
EASY621-DC-TC
EASY621-DC-TCX
EASY412-DC-RC
EASY412-DC-TC
EASY618-DC-RC
EASY620-DC-TC

For more detailed Technical Data a AWB2528-1304-GB

Relays
Contactor Relays

Easy Control Relays


Technical Data

04/042

Moeller HPL0211-2001/2002

Easy Control Relays


Technical Data
EASY205-ASI

Relays
Contactor Relays

General technical data


Standards
Dimensions
Weight
Mounting
Ambient climatic conditions
Operational ambient temperature: horizontal/
vertical installation
Cold to IEC 60 068-2-1
Heat to IEC 60 068-2-2
Condensation
Storage/transport temperature
Relative humidity
IEC 60 068-2-30, non-condensing
Air pressure (operation)
Corrosion resistance
IEC 60 068-2-42
4 days SO2
IEC 60 068-2-43
4 days H 2S
Ambient conditions, mechanical
Pollution degree
Degree of protection
EN 50 178, IEC 60 529 VBG 4
Vibration resistance to IEC 60 068-2-6
Constant amplitude 0.15 mm
Constant acceleration, 2 g
Mechanical shock resistance
(half-sinusoidal shock 15 g/11 ms)
to IEC 60 068-2-27
Drop
to IEC 60 068-2-31
drop height
Free fall, packaged
to IEC 60 068-2-32
Electromagnetic compatibility (EMC)
Electrostatic discharge
to IEC/EN 61 000-4-2, severity level 3
Air discharge
Contact discharge
Electromagnetic fields
to IEC/EN 61 000-4-3
field strength
Radio interference suppression
to EN 55011, EN 55022
Burst pulses
to IEC/EN 61 000-4-4, severity level 3
High-energy pulses (surge) EASY...-DC...
to IEC/EN 61 000-4-5, severity level 2
Immunity to line-conducted interference
to IEC/EN 61 000-4-6
Dielectric strength
Clearance in air and creepage distances
dimensioned to
Dielectric strength
Terminal capacity
Solid
Min./Max.
Flexible with ferrule
Min./Max.
Width of standard screwdriver
Tightening torque

mm
kg

EASY204-DP

EN 55 011, EN 55 022, IEC/EN 61 000-4...,


EN 55 011, EN 55 022, IEC/EN 61 000-4,
IEC 60 068-2-27, EN 50 295
IEC 60 068-2-27, IEC 61 158
35.5 x 90 x 53
35.5 x 90 x 53
0.12
0.15
On EN 50 022 top-hat rail, 35 mm, or screw fixing, using ZB4-101-GF1 fixing brackets (accessories)

25/+55

25/+55

Prevent condensation by suitable measures

Prevent condensation by suitable measures

40/+70

40/+70

5 95

5 95

hPa

795 1080

795 1080

cm3 /m3
cm3 /m3

10
1

10
1

IP20

IP20

Hz
Hz

10 57
57 150

10 57
57 150

Impacts

18

18

mm

50

50

kV
kV

8
6

8
6

V/m

10

10

Limit value Class B

Limit value Class B

kV

2 (AS-Interface cables)

2 (power supply-, signal cables)

kV

0.5 (supply cable, balanced)

10

10

EN 50 178, UL 508, CSA C22.2 No 142

EN 50 178, UL 508, CSA C22.2 No 142

EN 50 178

EN 50 178

0.2/4
(AWG 22 12)
0.2/2.5 (AWG 22 12)
3.5  0.8
0.6

0.2/4
(AWG 22 12)
0.2/4
(AWG 22 12)
3.5  0.8
0.6

mm
mm
mm
Nm

Moeller HPL0211-2001/2002

04/043

Power supply
Rated operational voltage
Total power consumption
(from yellow AS-Interface cable)
Admissible range
Residual ripple
Input current at 24 VDC
Voltage dips (IEC/EN 61 131-2)
Heat dissipation at 24 V DC
Protection against polarity reversal
AS-Interface protected against polarity reversal
AS-Interface profile cable
Slave addresses
Addressing unit interface
Power supply
LED displays

Logic links
EASY600 contact/coil t AS-Interface

EASY205-ASI

EASY204-DP

V DC
mA

26.5 31.6
30

24 (15/+20 %)

V DC
%
mA
ms
W

20.4 28.8
<5
Normally 200
10
Normally 4.8

Yes

7F (hex)
0. 1 31
3.5 mm socket

Yes

Power: green
Com-Error: red

Power LED (POW): green


PROFIBUS-DP LED (BUS): red

S1 l Input 0
S2 l Input 1
S3 l Input 2
S4 l Input 3
R1 m Output 0
R2 m Output 1
R3 m Output 2
R4 m Output 3
R5 m PARAMETEROUTPUT 0
R6 m PARAMETEROUTPUT 1
R7 m PARAMETEROUTPUT 2
R8 m PARAMETEROUTPUT 3

PROFIBUS-DP
Connection device
Potential isolation

Function
Interface
Bus protocol
Baud rates
Bus termination resistors

Bus addresses

1 126, can be addressed via EASY basic unit


with display or via EASY-SOFT

Services
Cyclical
Acyclical

All data R1 R12, S1 S8


Read/write, real-time, day, summer
time/winter time. All parameters of the Easy
function relay

SUB-D 9-pole, socket


Bus to power supply
Bus and power supply to EASY basic unit
(safe isolation)
PROFIBUS-DP slave
RS 485
PROFIBUS-DP
Automatic search up to 12 MBd
Can be connected via plug

Relays
Contactor Relays

Easy Control Relays


Technical Data

04/044

Moeller HPL0211-2001/2002

Easy Control Relays


Technical Data

Relays
Contactor Relays

EASY400-POW
General technical data
Standards
Dimensions
Weight
Mounting position
Mounting
Ambient climatic conditions
Operational ambient temperature: horizontal/vertical installation
Cold to IEC 60 068-2-1
Heat to IEC 60 068-2-2
Condensation
Storage/transport temperature
Relative humidity
IEC 60 068-2-30, non-condensing
Air pressure (operation)
Corrosion resistance
IEC 60 068-2-42
4 days SO2
IEC 60 068-2-43
4 days H 2S
Max. altitude above sea level; above this, note derating
Ambient conditions, mechanical
Pollution degree
Degree of protection
EN 50 178, IEC 60 529, VBG 4
Vibration resistance to IEC 60 068-2-6
Constant amplitude 0.15 mm
Constant acceleration, 2 g
Mechanical shock resistance (half-sinusoidal shock 15 g/11 ms)
to IEC 60 068-2-27
Drop
to IEC 60 068-2-31
drop height
Free fall, packaged
to IEC 60 068-2-32
Electromagnetic compatibility (EMC)
Radio interference suppression
EN 55011, EN 55022, EN 50 081-2
Electrostatic discharge (IEC/EN 61 000-4-2, severity level 3, ESD)
Air discharge
Contact discharge
Electromagnetic fields (RFI)
to IEC/EN 61 000-4-3
field strength
Burst pulses
to IEC/EN 61 000-4-4, severity level 3
High-energy pulses (surge)
to IEC/EN 61 000-4-5, supply cable balanced
High-energy pulses (surge)
to IEC/EN 61 000-4-5, severity level 2,
output cable balanced
Immunity to line-conducted interference
to IEC/EN 61 000-4-6
Surge voltage
to IEC/EN 60 947

kg

EN 55 011, EN 55 022, IEC/EN 61 000-4, IEC 60 068-2-27,


71.5 x 90 x 53
0.25
Horizontal and vertical on top-hat rail or fixing brackets
On EN 50 022 top-hat rail, 35 mm, or
screw fixing, using ZB4-101-GF1 fixing brackets (accessories)

25/+55

Prevent condensation by suitable measures


40/+70

%
hPa

5 95
795 1080

cm3 /m3
cm3 /m3
m

10
1
2000

2
IP20
Hz
Hz

10 57
57 150

Impacts

18

mm

50

Limit value Class B


kV
kV

8
6

V/m

10

kV

kV

kV

0.5

10

kV

4.9

Moeller HPL0211-2001/2002

04/045

Easy Control Relays


Technical Data

Dielectric strength, potential isolation


Clearance in air and creepage distances dimensioned to
Dielectric strength
Protection class Uout against Uin
Potential isolation primary/secondary
Terminal capacity
Solid
Min./Max.
Flexible with ferrule
Min./Max.
Width of standard screwdriver
Tightening torque
Input voltage
Rated input voltage
Voltage range
Frequency range
Input current nominal value
115/230 V
Inrush current at 25C
230 V
Power failure bridging
115/230 V
Fuse
115/230 V
Protective switch, min.
Rating data
Efficiency
Power consumption
Heat dissipation
Input current
Input current
115/230 V AC
Output voltage
Rated value
Tolerance range
Switching peaks (peak to peak)
Influence of input voltage
115 230 V
Influence at 25 100 % load fluctuation
Output current
Output current
Effectiveness of current limitation
Reduction of output voltage after current limitation
Overload proof
Proof against sustained short circuit
Special load conditions
Lamp load, cold
24 V DC
Base load present
Behaviour at Emergency-Stop in 24 V DC circuit, disconnection by contactor
(contactor load, no damage)
Displays
Indication of output voltage (LED, continuous green light = OK)

to EN 50 178
to EN 50 178
Class II to IEC 60 536
Yes, SELV to VDE 0100 Part 410, IEC 60 364-4-41, HD 384.4.41 S2
mm
mm
mm
Nm

0.2/4
(AWG 22 12)
0.2/2.5 (AWG 22 12)
3.5  0.8
0.6

V AC
V AC
Hz
Approx. A
A
ms
A

100/120/230/240 (15/+10 %)
85 264
47 63
0.3/0.15
<5
>10/>20
2/1 slow
FAZ-C1 or FAZ-B6

%
W
W

F 87
Normally 35
Normally 5

0.3/0.15

V DC
%
mV
%
%

24
g2
< 240
g1
g2

A
A
V

0 1.25
> 1.25
< 18
Yes, by current limitation
Yes, hiccup mode, approx. 10 Hz

W
W
W

10
5
30

V DC

24

Relays
Contactor Relays

EASY400-POW

04/046

Moeller HPL0211-2001/2002

DILER, DILR Contactor Relays


Technical Data

Relays
Contactor Relays

DILER
...DILE
General technical data
Standards
Lifespan, mechanical
AC operated
Operations
DC operated
Operations
Maximum operating frequency, mechanical
Climatic proofing
Ambient temperature
Open
Min./Max.
Enclosed
Min./Max.
Mounting position
Mechanical shock resistance
Half-sinusoidal shock, 10 ms
Basic unit
Make/break contact
Basic unit with auxiliary contact module Make/break contact
Half-sinusoidal shock, 20 ms
Basic unit
Make/break contact
Basic unit with auxiliary contact module Make/break contact
Degree of protection
Protection against direct contact from the front when actuated
by a perpendicular test finger (IEC 536)
Dimensions
Weight
AC operated
DC operated
Terminal capacity
Solid
Flexible with ferrule to DIN 46 228
Solid or stranded
Min.
Max.
Terminal screw
Pozidriv screwdriver
Size
Standard screwdriver
Tightening torque
Max.

DILR
...DIL

IEC/EN 60 947, VDE 0660, UL, CSA

106

10

106
Ops./h

20
20
9000
7000
Damp heat, constant, to IEC 60 068-2-3
Damp heat, cyclical, to IEC 60 068-2-30

25/+50

25/+50

25/+40
As required, except vertical
with A1/A2 at bottom

25/+40
As required,
except suspended

g
g

10/8
10/8

g
g

10/6

10/6
IP20
IP20 (DILR) IP00 (...DIL)
Finger and back-of-hand proof

20

a Page 04/065

a Page 04/066

kg
kg

0.17
0.2

a Page 15/022
a Page 15/022

mm2
mm2
mm2
mm2

1  (0.75 2.5)
2  (0.75 2.5)
1  (0.75 1.5)
2  (0.75 1.5)

1  (0.75 4)
2  (0.75 4)
1  (0.75 2.5)
2  (0.75 2.5)

AWG
AWG

18
14
M3.5

18
10
M3.5

mm
mm

2
0.8  5.5
16

2
0.8  5.5
16

Nm

1.2

1.2

Moeller HPL0211-2001/2002

04/047

Contacts
Interlocked opposing contacts to ZH 1/457, including auxiliary contact
module
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Rated operational voltage Ue
Safe isolation to IEC 536 between coil and auxiliary contacts, and
between the auxiliary contacts
Rated operational current Ie
AC-15

220/240 V
380/415 V
500 V

DC-132)
Above 110 V and at L/R > 15 ms:
it is essential that an arc-quenching device
(RC suppressor) be used in parallel with the contacts.
C: 1 F, R: 0.5  in series
L/R 15 ms: e.g. contactor coils, solenoid valves,
DC motors
Contacts in series:
1
24 V
2 (1)
60 V
3 (1)
110 V
3 (1)
220 V
L/R  50 ms: e.g. magnetic clutches, solenoid brakes
Contacts in series:
2
24 V
2
60 V
3 (1)
110 V
3 (1)
220 V
Control circuit reliability at Ue = 24 V
Umin = 17 V, Imin = 5.4 mA
Fault probability
Conventional thermal current Ith
Component lifespan at Ue  240 V
AC-15
DC-13
L/R  50 ms:
Operations
2 contacts in series
at Ie  0.5 A
Short-circuit rating without welding when supplied directly from mains
or transformer > 1000 VA
Maximum overcurrent protective 220/240 V
device
380/415 V
220/230 V
Maximum fuse3)
500 V
500 V
Current heat loss at Ith
Per contact
AC operated
DC operated
Notes

1) Auxiliary

DILER
...DILE

DILR
...DIL

Yes

Yes

V AC
V AC
V AC

6000
III/3
690
600
300

6000
III/3
690
500
440

A
A
A

6 (4)1)
3 (2)1)
1.5

6
4
1.5

A
A
A
A

2.5
2.5
1.5
0.5

10
10 (6)
6 (3)
5 (1)

A
A
A
A

6
6
3 (1.5)
2 (1)

HF
A

< 108, < 1 failure in 100 million operations


10
16

a Page 04/032

a Page 04/032

 106

0.15

a Page 04/032

PKZM0
PKZM0
FAZ-C
gG/gL A
A fast

4
4

6
10

4
2.4
4
16

W
W

0.2
0.3

0.8
0.8

contact module
Making and breaking conditions to DC-13, time constant as stated
3) See transparent overlay Fuses for time/current characteristics (please enquire)
2)

Relays
Contactor Relays

DILER, DILR Contactor Relays


Technical Data

04/048

Moeller HPL0211-2001/2002

Relays
Contactor Relays

DILER, DILR Contactor Relays


Technical Data

Magnet systems
Voltage tolerance
AC operated
Single-voltage coil 50 Hz and
dual-voltage coil 50 Hz, 60 Hz
Pick-up
Dual-frequency coil ... V, 50/60 Hz
Pick-up
DC operated1)
Pick-up
Without auxiliary contact module
Pick-up
Power consumption
AC operated
Single-voltage coil 50 Hz and
dual-voltage coil 50 Hz, 60 Hz
Pick-up
Sealing
Dual-frequency coil
... V, 50/60 Hz at 50 Hz
Pick-up
Sealing
... V, 50/60 Hz at 60 Hz
Pick-up
Sealing
DC operated
Pull-in  sealing
Duty factor
Switching times at 100 % U (approximate values)
AC operated
Closing delay
Make contact
Opening delay
With auxiliary contact module
Max. closing delay
DC operated
Closing delay
Make contact
Opening delay
With auxiliary contact module
Max. closing delay
Notes

1)

DILER
...DILE

DILR
...DIL

 Uc

0.8  1.1

0.8  1.1

 Uc

0.85  1.1

0.85  1.1

 Uc

0.85  1.3

0.85  1.1

 Uc

0.7  1.3

VA/W
VA/W

25/22
4.6/1.3

67/52
8.5/2.5

VA/W
VA/W

30/26
5.4/1.6

VA/W
VA/W

29/24
3.9/1.1

W
% DF

2.6
100

9.5
100

ms

14 21

22

ms

8 18

14

ms

45

ms

26 35

38

ms

15 25

ms

70

Smoothed DC or three-phase bridge rectifier

04/049

Moeller HPL0211-2001/2002

TP Timer Modules, V Latching Module, VS Amplifier modules


Technical Data
TPE(H)11DIL
TPD(H)11DIL

Ambient temperature
Open
Min./Max.
Min./Max.
Enclosed
Min./Max.
Min./Max.
Mounting position
Mechanical shock resistance
(half-sinusoidal shock, 20 ms)
Make/break contact
Mechanical latching
Degree of protection
Protection against direct contact from the front when
actuated by a perpendicular test finger (IEC 536)
Dimensions
Weight
Terminal capacity
Solid
Flexible with ferrule to DIN 46 228
Solid or stranded
Min.
Max.
Terminal screw
Pozidriv screwdriver
Standard screwdriver
Tightening torque
Max.
Notes

1)

ETS4-VS3

IEC/EN 60 947, VDE 0660, UL, CSA

 106

 106

10

30

Ops./h
Ops./h

3600 (100)1)
1500
3600 (100)1)
1500
Damp heat, constant, to IEC 60 068-2-3
Damp heat, cyclical, to IEC 60 068-2-30

9000

72000

C
C

25/+50
(10/+50)1)

25/+50

25/+50

25/+60

C
C

25/+40
(10/+40)1)
As required, except
suspended2)

25/+40

25/+40

25/+45

As required

As required

As required

10/6

IP00
Finger and back-of-hand
proof

20
IP00
Finger and
back-of-hand proof

10/

IP00
Finger and
back-of-hand proof

10/

IP20
Finger and
back-of-hand proof

kg

a Page 04/066
0.08

a Page 04/066
0.1

a Page 04/066
0.04 (VS1)
0.05 (VS2)

a Page 04/066
0.09

mm2
mm2
mm2
mm2

1  (0.5 2.5)
2  (0.5 2.5)
1  (0.5 1.5)
2  (0.5 0.75)

1  (0.5 2.5)
2  (0.5 2.5)
1  (0.5 1.5)
2  (0.5 0.75)

1  (0.75 4)
2  (0.75 4)
1  (0.75 2.5)
2  (0.75 2.5)

1  (0.75 2.5)
2  (0.75 1.5)3)
1  (0.75 2.5)
2  (0.75 1.5)3)

AWG
AWG
Size
mm
mm

18
14
M3
2
0.8  5.5
16

18
14
M3
2
0.8  5.5
16

18
12
M3.5
2
0.8  5.5
16

16
14
M3.5
2
0.8  5.5
16

Nm

1.2

1.2

1.2

1.2

g
g

TPEH11DIL, TPDH11DIL
DILR ... -G + TPD(H)11DIL: do not mount vertically
3) Use equal cross-sections only
2)

VS1DIL
VS2DIL

Relays
Contactor Relays

General technical data


Standards
Lifespan, mechanical
AC operated
Operations
DC operated
Operations
Maximum operating frequency, mechanical
AC operated
DC operated
Climatic proofing

VDIL

04/050

Moeller HPL0211-2001/2002

Relays
Contactor Relays

TP Timer Modules, V Latching Module, VS Amplifier modules


Technical Data

Contacts
Interlocked opposing contacts to ZH 1/457, including auxiliary contact
module
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Rated operational voltage Ue
Rated operational current Ie
AC-15
220/240 V
380/415 V
DC-13 1)
Above 110 V and at L/R > 15 ms:
it is essential that an arc-quenching device
(RC suppressor) be used in parallel with the contacts.
C: 1 F, R: 0.5 in series
L/R  15 ms: e.g. contactor coils, solenoid valves, DC motors
Contacts in series:
1
24 V
1
60 V
1
110 V
1
220 V
L/R  50 ms: e.g. magnetic clutches, solenoid brakes
Contacts in series:
1
24 V
1
60 V
1
110 V
1
220 V
L/R  300 ms
1
24 V
1
60 V
1
110 V
1
220 V
Control circuit reliability at Ue = 24 V, Umin = 17 V, Imin = 5.4 mA
Fault probability
Conventional thermal current Ith
Component lifespan at Ie  0.1 A/1.2 A
AC-15
230 V
Operations
DC-13
230 V
Operations
Short-circuit rating without welding when supplied directly
from mains or transformer > 1000 VA
Maximum overcurrent protective device
220/240 V
380/415 V
Maximum fuse2)
500 V
Current heat loss at Ith
Per contact, max.
Notes

1)
2)

TPE(H)11DIL
TPD(H)11DIL

VDIL

VS1DIL
VS2DIL

ETS4-VS3

Yes

V AC
V AC

6000
III/3
690
500

8000
III/3
690
415

4000
III/2
440
415

6000
III/3
440
440

A
A

4
4

1.5
1

2
2

A
A
A
A

10
6
3
1

1
1
1
1

2.6
1.0
0.6
0.2

A
A
A
A

4
4
1
0.5

0.5
0.5
0.5
0.5

2.0
0.6
0.08
0.08

A
A
A
A

0.2
0.2
0.2
0.2

0.6
0.2
0.08
0.03

HF
A

< 108, < 1 failure in 100 million operations


10

 106

8/

7/1

 106

0.85/

PKZM0
PKZM0

2.5
1.6

A gG/gL
A fast

0.3

Making and breaking conditions to DC-13, time constant as stated


See transparent overlay 'Fuses' for time/current characteristics (please enquire)

04/051

Moeller HPL0211-2001/2002

Magnet systems
Voltage tolerance
AC operated
Single-voltage coil 50 Hz and
dual-voltage coil 50 Hz, 60 Hz
Dual-frequency coil ... V, 50/60 Hz
DC operated1)
Power consumption
AC operated
Single-voltage coil 50 Hz and
dual-voltage coil 50 Hz, 60 Hz
DC operated

Minimum command time


AC operated 50 Hz
DC operated

Notes

2)

ETS4-VS3

0.8 1.1

Unlatching
Pick-up
Unlatching

 Uc
 Uc
 Uc

0.85 1.1

0.8 1.1
0.75 1.25

0.85 1.2

Pick-up
Sealing
Pull-in  sealing

VA/W
VA/W
W

13/12
5/2
26

0.27

0.6

% DF

100

100 at AC
200 ms at DC

100

100

Closing delay
Opening delay

ms
ms

6
2.5

7
3

Latching
Unlatching
Latching
Unlatching

ms
ms
ms
ms
%
%/K

< 3 (5)2)
0.2

35
25
45
25

%
ms

15
20

Coil 50/60 Hz
1)

VS1DIL
VS2DIL

 Uc

Repetition accuracy
Time deviation in relation to ambient
temperature based on 20 C
Long-time deviation
Recovery time (after 100% time delay)
Lifespan, mechanical

VDIL

Unlatching

Duty factor
Switching times at 100 % U (approximate values)
DC operated

TPE(H)11DIL
TPD(H)11DIL

Smoothed DC or three-phase bridge rectifier


TPEH11DIL, TPDH11DIL

At 50 Hz, approximately 30% less than shown under General technical data

Relays
Contactor Relays

TP Timer Modules, V Latching Module, VS Amplifier modules


Technical Data

04/052

Moeller HPL0211-2001/2002

DILET, ETR4 Electronic Timing Relays


Technical Data

Relays
Contactor Relays

DILET-A
General technical data
Standards
Lifespan, mechanical
AC operated
DC operated
Climatic proofing

ETR4-A

ETR4-W

IEC/EN 60 255, VDE 0435, IEC/EN 60 947, UL , CSA


Operations
Operations

Ambient temperature
Open
Min./Max.
Enclosed
Min./Max.
Mounting position
Mechanical shock resistance (half-sinusoidal Make contact
shock, 20 ms)
Degree of protection
Terminals
Dimensions
Weight
Terminal capacity
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Rated operational voltage Ue
Safe isolation to IEC 536 between coil and auxiliary contacts,
and between the auxiliary contacts
Making capacity
AC-14
cos
= 0.3
440 V
AC-15
cos
= 0.3
220 V
DC-11
L/R  40 ms
Breaking capacity
AC-14
cos
= 0.3
440 V
AC-15
cos
= 0.3
220 V
DC-11
L/R  40 ms
Rated operational current Ie
AC-14
440 V
AC-15
220 V
DC-11 1)
Above 110 V and at L/R > 15 ms:
it is essential that an arc-quenching device
(RC suppressor) be used in parallel with the contacts.
C: 1 F, R: 0.5  in series
L/R  15 ms: e.g. contactor coils, solenoid valves,
DC motors
24 V
L/R  50 ms:
Conventional thermal current Ith
Short-circuit rating 2) without welding
Maximum fuse
Notes

DILET-W

1)
2)

 106
 106

30
30
30
30
Damp heat, constant, to IEC 60 068-2-3
Damp heat, cyclical, to IEC 60 068-2-30

30
30

30
30

C
C

20/+60
20/+45
As required
4

25/+60
20/+45
As required
4

25/+60
20/+45
As required
4

20/+60
20/+45
As required
4

IP20
IP20
a Page 04/066
a Page 04/066
0.09
0.09
a Page 04/046 (as DILER)

IP20
IP20
a Page 04/066
a Page 04/066
0.1
0.1
a Page 04/049 (as ETS4VS3)

V AC
V AC
V AC

6000
III/2
600
440
250

6000
III/2
600
440
250

6000
III/3
600
440
250

6000
III/3
600
440
250

A
A
 Ie

48
50
1.1

48
50
1.1

48
50
1.1

48
50
1.1

A
A
 Ie

3
3
1.1

3
3
1.1

3
3
1.1

3
3
1.1

A
A

3
3

3
3

3
3

3
3

A
A
A

1.5
1.2
6

1.5
1.2
6

1.5
1.2
6

1.5
1.2
6

A gG/gL

kg

V AC

Making and breaking conditions to DC-13, time constant as stated


When supplied directly from mains or transformer > 1000 VA

04/053

Moeller HPL0211-2001/2002

DILET-A

DILET-W

ETR4-A

ETR4-W

a Page 04/017

a Page 04/017

a Page 04/019

a Page 04/019

a Page 04/017

a Page 04/017

a Page 04/019

a Page 04/019

VA/W
VA/W

2/
2/

0.5/
0.5/

2/
2/

0.5/
0.5/

W
W
% DF
Ops./h

1.8
1.8
100
4000

100
4000

1.8
1.8
100
4000

100
4000

Magnet systems
Voltage tolerance
AC operated 50/60 Hz
Pick-up
DC operated1) when supplied directly from
mains or transformer > 1000 VA
Pick-up
Power consumption
AC operated 50/60 Hz
Pick-up
Sealing
DC operated
Pick-up
Sealing
Duty factor
Maximum operating frequency
Minimum command time
AC/DC
Voltage variation
Variation due to temperature fluctuation based on
20 C
Repetition accuracy (deviation)
Recovery time (after 100% time delay)

ms
%U

50/30
0.01
0.025

50/
0.01
0.025

50/30
0.01
0.025

50/
0.01
0.025

%
ms

0.1
70

0.1
70

0.1
70

0.1
70

Contact changeover time tu

ms

4 (50)2)

4 (50)2)

Notes

1)
2)

Not DILET-W
ETR4-51

Relays
Contactor Relays

DILET, ETR4 Electronic Timing Relays


Technical Data

04/054

Moeller HPL0211-2001/2002

ESR Electronic Safety Relays


Technical Data

Relays
Contactor Relays

ESR3-NO-31
General technical data
Standards
Lifespan, mechanical
Maximum operating frequency
Climatic proofing
Ambient temperature
Storage temperature
Mounting position
Vibration resistance
Degree of protection
Enclosure
Terminals
Protection against direct contact from the
front when actuated by a perpendicular
test finger (IEC 536)
Dimensions
Weight
Terminal capacity
Flexible with ferrule

Operations

x106
Ops./h

Min./Max.
Min./Max.

C
C
g

ESR4-NO-31

ESR4-NO-21

IEC/EN 60 947, VDE 0660, IEC/EN 60 255, UL, CSA


10
10
10
3600
3600
3600
Damp heat to DIN 50 016: 24 hour cycle,
23 C, 83% relative humidity, 40 C, 92% relative humidity
25/+55
25/+55
25/+55
25/+70
25/+70
25/+70
As required
As required
As required
5, to IEC/EN 60 068-2-6, frequency: 10 55 Hz, amplitude: 0.35 mm
IP40
IP40
IP20
IP20
Finger and back-of-hand proof

IP40
IP20

a Page 04/067
0.36

a Page 04/067
0.2

a Page 04/067
0.2

1 x (0.5 1.5)
2 x (0.5 1.5)
1 x (0.75 2.5)
2 x (0.75 2.5)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

Size
mm

0.6 x3.5

0.6 x3.5

Nm

0.6

0.6

V AC

4000

4000

4000

V AC
V AC/DC

III/3
III/2
300
230

III/3
III/2
300
230

III/3
III/2
300
230

Max. summation current of all poles

A
A
A
A

6
6
3
18

6
6
3
12

6
6
3
12

Short-circuit protection
Fuse

gG/gL A

kg
mm

Solid

mm

Terminal screw
Pozidriv screwdriver
Standard screwdriver
Tightening torque
Main contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
outside
inside
Rated insulation voltage Ui
Rated operational voltage Ue
Rated operational current Ie
AC-15
DC-13

230 V
24 V (360 Ops./h)
24 V (3600 Ops./h)

Moeller HPL0211-2001/2002

04/055

ESR4-NV3(30)-30
ESR4-NT30-30

ESR4-NM-21

ESR4-NZ-21

IEC/EN 60 947, VDE 0660, IEC/EN 60 255, UL, CSA


10
10
10
3600
3600
3600
Damp heat to DIN 50 016: 24 hour cycle,
23 C, 83% relative humidity, 40 C, 92% relative humidity
25/+55
25/+55
25/+55
25/+70
25/+70
25/+70
As required
As required
As required
5, to IEC/EN 60 068-2-6, frequency: 10 55 Hz, amplitude: 0.35 mm

ESR4-NE-42

ESR4-VE3-42

10
3600

10
3600

25/+55
25/+70
As required

25/+55
25/+70
As required

IP40
IP40
IP20
IP20
Finger and back-of-hand proof

IP40
IP20

IP40
IP20

IP40
IP20

a Page 04/067
0.2

a Page 04/067
0.2

a Page 04/067
0.2

a Page 04/067
0.2

a Page 04/067
0.2

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

1 x (0.25 2.5)
2 x (0.25 0.5)
1 x (0.14 2.5)
2 x (0.14 0.75)

0.6 x3.5

0.6 x3.5

0.6 x3.5

0.6 x3.5

0.6 x3.5

0.6

0.6

0.6

0.6

0.6

4000

4000

4000

4000

4000

III/3
III/2
300
230

III/3
III/2
300
230

III/3
III/2
300
230

III/3
III/2
300
230

III/3
III/2
300
230

6
6
3
12

6
6
3
12

6
6
3
12

6
6
3
12

6
6
3
12

Relays
Contactor Relays

ESR Electronic Safety Relays


Technical Data

04/056

Moeller HPL0211-2001/2002

ESR Electronic Safety Relays


Technical Data

Relays
Contactor Relays

Magnet system
Actuating voltage Uc
Voltage tolerance
Power consumption
AC operated 50/60 Hz
DC operated
Control circuit
Rated output voltage
No-load voltage
Rated current
Short-circuit current
Protection
Response time
Recovery time
Inputs
Rated current
Response time tA1
(with reset monitoring)
Response time tA1
(without reset monitoring)
Reset time tR /tR1
Minimum contact closing time tM
Recovery time tW
Synchronous monitoring time tS
EMC
Emitted interference
Noise immunity

Pick-up

ESR3-NO-31

ESR4-NO-31

ESR4-NO-21

V AC
V DC
xUc

230

0.85 1.1

24
24
0.85 1.1

24
24
0.85 1.1

VA/W
W

3.2/2.5

2.4/1.4
1.3

3.5/2.1
1.5

V DC
V DC
mA
A

F24
F40
40
1
Short-circuit proof
transformer

F24

40
1.4
PTC resistor

F24

50
2.2
PTC resistor

2000
3000

2000
3000

Y2: 40

ms

Y13, Y14: 40
Y12, Y31: 15
80

S12: 30, S31


S22: 20
80

ms

500

50

60

ms
ms
ms
ms

50/100
50
500

40
50
< 50

40/100
50
500

ms
ms
mA

To EN 50 081-1 and EN 50 081-2


To EN 50 082-2

Moeller HPL0211-2001/2002

04/057

ESR4-NV3(30)-30
ESR4-NT30-30

ESR4-NM-21

ESR4-NZ-21

ESR4-NE-42

ESR4-VE3-42

24
0.85 1.1

24
0.85 1.1

24
24
0.85 1.1

24
24
0.85 1.1

24
0.85 1.1

2.5

2.7

2.7/1.6
1.5

2.7/1.5
1.0

1.0

F24

50
2.2
PTC resistor

F24

50
0.1
Electronic protection

F24

60
1
PTC resistor

2000
3000

5
5

2000
3000

S12, S22, S31: 25


S34, S35: 40
30

S12: 30
S31, S22: 20
80

Y2: 60
Y11, Y21: 60

200

60

40

25

25

25/adjustable
200
500

40/100
50
500

< 50

< 250
< 500

15

To EN 50 081-1 and EN 50 081-2


To EN 50 082-2

Relays
Contactor Relays

ESR Electronic Safety Relays


Technical Data

04/058

Moeller HPL0211-2001/2002

EMR4-I Current Monitoring


Technical Data
EMR4-I1-2-A

Relays
Contactor Relays

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Timing cycle
Response delay time
Time error within supply voltage
Time error within temperature range
Measuring circuits
Input

Hysteresis
Max. measuring cycle
Temperature error
Error within supply voltage
Status indication
Supply voltage
Output relay energized
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
Rated operational current Ie AC-15
Rated operational current Ie DC-12
Rated operational current Ie DC-13
Maximum electrical lifespan (AC-12/230 V/5 A)
Short-circuit rating, max. fuse
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

kg

EMR4-I15-2-A

IEC/EN 60 255-6, EN 61 557, UL , CSA, GL


30
30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
25/+65
25/+65
40/+85
40/+85
As required
As required
10
10
IP20
IP20
A Page 04/067
A Page 04/067
0.3
0.3

EMR4-I15-2-B

30

25/+65
40/+85
As required
10
IP20
A Page 04/067
0.3

mm
mm
mm
Nm

2 x 2.5
2 x 2.5
2 x 2.5
2 x 2.5
5.5 x 0.8
5.5 x 0.8
0.5 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8

V AC
V AC

4000
III/3
400

4000
III/3
400

4000
III/3
400

V AC/DC
V AC
x Uc
VA
Hz
% DF

24 240

0.85 1.1
2
50 60
100

24 240

0.85 1.1
2
50 60
100

220 240
0.85 1.1
2
50 60
100

Adjustable

s
%
%/C

0.05 1 and 1.5 30


F 0.5
F 0.06

0.05 1 and 1.5 30


F 0.5
F 0.06

0.05 1 and 1.5 30


F 0.5
F 0.06

B1-C
B2-C
B3-C

A
A
A
%
ms
%/C
%

0.003 0.03
0.01 0.1
0.1 1
5 30
80
F 0.06
F 0.5

0.3 1.5
15
3 15
5 30
80
F 0.06
F 0.5

0.3 1.5
15
3 15
5 30
80
F 0.06
F 0.5

Green
Yellow

Green
Yellow

Green
Yellow

400
5
3
5
2.5
0.1
5

400
5
3
5
2.5
0.1
5

400
5
3
5
2.5
0.1
5

a Page 04/036

a Page 04/036

a Page 04/036

LED
LED

At 230 V
At 230 V
At 24 V
At 24 V
Operations
Fast/gL

V AC
A
A
A
A
x 106
A

IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

Moeller HPL0211-2001/2002

04/059

EMR4-F Phase Sequence Relays


Technical Data

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Measuring circuits
Voltage to be monitored UN
Frequency
Max. measuring cycle
Temperature error
Error within the supply voltage tolerance
Status indication
Output relay energized
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
Rated operational current Ie AC-15
Rated operational current Ie DC-12
Rated operational current Ie DC-13
Maximum lifespan, electrical (AC-12/230 V/4 A)
Short-circuit rating, max. fuse
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

kg

IEC/EN 60 255-6, EN 61 557, UL , CSA, GL


30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
20/+60
40/+80
As required
10
IP20
a Page 04/067
0.15

mm
mm
mm
Nm

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

V AC
V AC

4000
III/3
400

L1, L2, L3

V AC
x Uc
VA
Hz
%

200 500
0.85 1.1
15
50 60
100

L1, L2, L3

V AC
Hz
ms
%/C
%

200 500
50 60
500
F 0.06
F 0.5

LED

At 230 V
At 230 V
At 24 V
At 24 V
Operations
Fast/gL

Yellow
V AC
A
A
A
A
x 106
A

500
4
3
4
2
0.3
10
a Page 04/036
IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

Relays
Contactor Relays

EMR4-F500-2

04/060

Moeller HPL0211-2001/2002

EMR4-W Phase Monitoring Relays


Technical Data
EMR4-W500-2-C

Relays
Contactor Relays

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Timing cycle
Response delay time
Off delay time
Time error within supply voltage
Time error within temperature range
Measuring circuits
Response range adjustable for over and
undervoltage
Hysteresis
Max. measuring cycle
Temperature error
Error within supply voltage
Status indication
Supply voltage
Output relay energized
Overvoltage
>U
Undervoltage
<U
Phase failure, phase sequence error
P
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
Rated operational current Ie AC-15
Rated operational current Ie DC-12
Rated operational current Ie DC-13
Maximum electrical lifespan (AC-12/230 V/5 A)
Short-circuit rating, max. fuse
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

kg

EMR4-W500-2-D

IEC/EN 60 255-6, EN 61 557, UL , CSA, GL


30
30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
25/+65
25/+65
40/+85
40/+85
As required
As required
10
10
IP20
IP20
a Page 04/067
a Page 04/067
0.3
0.3

EMR4-W580-2-D

30

25/+65
40/+85
As required
10
IP20
a Page 04/067
0.3

mm
mm
mm
Nm

2 x 2.5
2 x 2.5
2 x 2.5
2 x 2.5
5.5 x 0.8
5.5 x 0.8
0.5 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8

V AC
V AC

4000
III/3
400

4000
III/3
400

4000
III/3
400

V AC
x Uc
VA
Hz
%

160 300
0.85 1.1
3
50 60
100

300 500
0.85 1.1
3
50 60
100

300 500
0.85 1.1
3
50 60
100

Adjustable
Adjustable

s
s
%
%/C

0.1 10
0.1 10
F 0.5
F 0.06

0.1 10
0.1 10
F 0.5
F 0.06

0.1 10
0.1 10
F 0.5
F 0.06

Umin/Umax

V AC

300 380/420 500

300 380/420 500

350 430/500 580

%
ms
%/C
%

5
80
F 0.06
F 0.5

5
80
F 0.06
F 0.5

5
80
F 0.06
F 0.5

Green
Yellow
Red
Red
Red

Green
Yellow
Red
Red
Red

Green
Yellow
Red
Red
Red

500
5
3
5
2.5
0.1
5
a Page 04/036

500
5
3
5
2.5
0.1
5
a Page 04/036

500
5
3
5
2.5
0.1
5
a Page 04/036

LED
LED
LED
LED
LED

At 230 V
At 230 V
At 24 V
At 24 V
Operations
Fast/gL

V AC
A
A
A
A
x 106
A

IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

Moeller HPL0211-2001/2002

04/061

EMR4-A Phase Imbalance Monitoring Relay


Technical Data

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Timing cycle
Response delay, indication of phase imbalance
Time error within supply voltage
Time error within temperature range
Measuring circuits
Monitoring voltage/Voltage to be monitored UN
Frequency
Phase imbalance level adjustable
Switching hysteresis
Temperature error
Error/Deviation within the supply voltage tolerance
Status indication
Output relay energized
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
Rated operational current Ie AC-15
Rated operational current Ie DC-12
Rated operational current Ie DC-13
Maximum lifespan, electrical (AC-12/230 V/4 A)
Short-circuit rating, max. fuse
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

50 Hz

L1, L2, L3

kg
mm
mm
mm
Nm

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

V AC
V AC

4000
III/3
400

V AC
x Uc
VA
Hz
%

380 415
0.8 1.2
15
50
100

ms
%
%/C

500
F 0.5
F 0.06

V AC
Hz
%
%
%/C
%

380 415
50
5 15
20
F 0.06
F 0.5

LED

At 230 V
At 230 V
At 24 V
At 24 V
Operations
Fast/gL

IEC/EN 60 255-6, EN 61 557, UL, CSA, GL


30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
20/+60
40/+80
As required
10
IP20
a Page 04/067
0.3

Yellow
V AC
A
A
A
A
x 106
A

500
4
3
4
2
0.3
10
a Page 04/036
IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

Relays
Contactor Relays

EMR4-A400-1

04/062

Moeller HPL0211-2001/2002

EMR4-N Liquid Level Monitoring Relays


Technical Data
EMR4-N100-1-B

Relays
Contactor Relays

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Timing cycle
On or Off delay time
Measuring circuit
Sensor inputs

Response sensitivity range


Maximum sensor voltage
Reset range
Maximum sensor current
Maximum cable capacity
Maximum cable length
Response delay
Status indication
Supply voltage
Output relay energized
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
Rated operational current Ie AC-15
Rated operational current Ie DC-12
Rated operational current Ie DC-13
Maximum lifespan, electrical (AC-12/230 V/5 A)
Short-circuit rating, max. fuse
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

kg

EMR4-N500-2-B

IEC/EN 60 255-6, EN 61 557, UL , CSA, GL


30
30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
20/+60
25/+65
40/+80
40/+85
As required
As required
10
10
IP20
IP20
a Page 04/067
a Page 04/067
0.15
0.3

EMR4-N500-2-A

30

25/+65
40/+85
As required
10
IP20
a Page 04/067
0.3

mm
mm
mm
Nm

2 x 2.5
2 x 2.5
2 x 2.5
2 x 2.5
5.5 x 0.8
5.5 x 0.8
0.5 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8

V AC
V AC

4000
III/3
400

4000
III/3
400

4000
III/3
400

V AC
V AC/DC
x Uc
VA/W
Hz
%

220 240

0.85 1.1
2.5
50 60
100

220 240

0.85 1.1
3
50 60
100

24 240
0.85 1.1
2
50 60 DC
100

0.1 10

0.1 10

B1

Earth reference sensor

Earth reference sensor

Earth reference sensor

B2
B3

Maximum level
Minimum level
5 100
30
1.5 2.3
1
10
100
250

Maximum level
Minimum level
0.25 500
20

Maximum level
Minimum level
0.25 500
20

Green
Yellow

Green
Yellow

Green
Yellow

250
4
3
4
2
0.3
10
a Page 04/036

400
5
3
5
2.5
0.1
5
a Page 04/036

400
5
3
5
2.5
0.1
5
a Page 04/036

Adjustable

approx.

kO
V AC
kO
mA
nF
m
ms

LED
LED

At 230 V
At 230 V
At 24 V
At 24 V
Operations
Fast/gL

V AC
A
A
A
A
x 106
A

IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

Moeller HPL0211-2001/2002

04/063

EMR4-R Insulation Monitoring Relays


Technical Data

General technical data


Standards
Lifespan, mechanical
Climatic proofing
Ambient temperature range
Storage temperature
Mounting position
Mechanical shock resistance
Degree of protection
Dimensions
Weight
Terminal capacity
Flexible with ferrule
Solid
Standard screwdriver
Tightening torque
Fixing
Contacts
Rated impulse withstand voltage Uimp
Overvoltage category/pollution degree
Rated insulation voltage Ui
Power supply
Supply voltage
Voltage tolerance
Power consumption
Rated frequency
Duty factor
Timing cycle
Delay time

Operations

x 106

Min./Max.
Min./Max.

C
C
g

Terminals
Approx.

AC

At Rinsulation
x response value

Measuring circuits
Input
Response range
Minimum internal resistance of alternating current
Minimum internal resistance of direct current
Minimum internal resistance
Test resistance
Maximum insulation voltage
Maximum voltage being monitored/test voltage (EMR4-RAC-1-A = DC
voltage being monitored/test voltage)
Cable length for cancellation- and test button, maximum
Status indication
Supply voltage
LED
Faults
LED
Fault at L+
LED
Fault at L
LED
Relay output contacts
Rated operational voltage Ue
Rated operational current Ie AC-12
At 230 V
Rated operational current Ie AC-15
At 230 V
Rated operational current Ie DC-12
At 24 V
Rated operational current Ie DC-13
At 24 V
Maximum lifespan, electrical (AC-12/230 V/5 A)
Operations
Short-circuit rating, max. fuse
Fast/gL
Load limit curves
EMC
Electromagnetic compatibility
ESD
HF immunity to radiation
Burst
Surge
HF immunity to line-conducted interference

kg

EMR4-RAC-1-A

IEC/EN 60 255-6, EN 61 557, UL , CSA, GL


30
30
Damp heat cyclical to IEC 60 068-2-30:
24 h cycle, 55 C, 93 % relative humidity 96 h
25/+65
25/+65
40/+85
40/+85
As required
As required
10
10
IP20
IP20
a Page 04/067
a Page 04/067
0.3
0.3

mm
mm
mm
Nm

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8
Snap fitting on top-hat rail to EN 50 022

2 x 2.5
2 x 2.5
5.5 x 0.8
0.5 0.8

V AC
V AC

4000
III/3
400

4000
III/3
400

V AC/DC
x Uc
VA
Hz
%

24 240
0.85 1.1
5.5
50 60
100

24 240
0.85 1.1
4.5
50 60
100

s
s

<1
< 0.9

<1
< 0.9

kO
kO
kO
kO
kO
V
V DC

L+, L, PE
10 110

57

300 DC
24 240

L, PE
1 11, 10 110
100
100

0.82
415 AC
F 30

10

10

Green
Yellow
Red
Red

Green
Red
Red
Red

400
5
3
5
2.5
0.1
5
a Page 04/036

320
5
3
3
2.5
0.1
5
a Page 04/036

IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

IEC/EN 61 000-6-2
IEC/EN 61 000-4-2 Level 3
IEC/EN 61 000-4-3 Level 3
IEC/EN 61 000-4-4 Level 3
IEC/EN 61 000-4-5 Level 4
IEC/EN 61 000-4-6 Level 3

V AC
A
A
A
A
x 106
A

Relays
Contactor Relays

EMR4-RDC-1-A

04/064

Moeller HPL0211-2001/2002

Easy Control Relays


Dimensions
Control relay

EASY2...

EASY4...
10.75

Relays
Contactor Relays

7.5

50

45

110

90

102

M4

4.5

M4
7.5

47.5

35.75

56.5

35.5

71.5

58

EASY6...
75

16.25

45

110

90

M4

102

16.25

4.5
107.5

47.5
56.5
58

04/065

Moeller HPL0211-2001/2002

DILER Mini Contactor Relays


Dimensions
Mini contactor relays
DILER-...
DILER-...-G

DILER-... + ...DILE
DILER-...-G + ...DILE
5,5

2DILER-... + MVDILE
2DILER-...-G + MVDILE

58

45

58

43

45

90

65,3

2DILER-... + MVDILE + ...DILE


2DILER-...-G + MVDILE + ...DILE

58

62,5

DILER-... + RCDILE
DILER-...-G + VGDILE

63

45

52

94

90

75

~125

DILER-... + TDDILE24

45

4,7

67

Suppressors, amplifier modules


RCBDIL,
FDBDIL
VGBDIL
VS1(2)DIL
a
b

a
b
c

RCBDIL
33
15
30

FDBDIL
33
15
30

VGBDIL
33
15
30

VS1DIL
45
26
55

VS2DIL
45
26
55

Relays
Contactor Relays

DILER-... + HDILE
DILER-...-G + HDILE

35

83

45

52

45

50

58

58

M4

04/066

Moeller HPL0211-2001/2002

DILR Contactor Relays, DILET, ETR4 Electronic Timing- and Special-Purpose Relays
Dimensions
Contactor relays

Relays
Contactor Relays

DILR22(-G)
DILR22D(-G)
DILR31(-G)
DILR40(-G)

DILR22(-G) + ...DIL
DILR31(-G) + ...DIL
DILR40(-G) + ...DIL
DILR44D(-G)
DILR53D(-G)

DILR22(-G) + TPE(TPD)11DIL
DILR31(-G) + TPE(TPD)11DIL
DILR40(-G) + TPE(TPD)11DIL

DILR22(-G) + V(-G) DIL


DILR31(-G) + V(-G) DIL
DILR40(-G) + V(-G) DIL

c2
c1
4.7

35

77

60

38.5

45

2 M4

DILR22
DILR31
DILR40
DILR22D

(-G)
(-G)
(-G)
(-G)

DILR22+...DIL
DILR31+...DIL
DILR40+...DIL
DILR44D
DILR53D

c (with HDIL)
76.5
(101.5)
c (without
74
(99)

HDIL)

107
c1

c1 = With ...DIL auxiliary contact module


or DILR...D(-G) complete unit
c2 = With V(-G)DIL mechanical latching module
or with TP...11DIL pneumatic timer module

(-G)
(-G)
(-G)
(-G)
(-G)

(132)

DILR22+TPE11DIL
DILR22+TPD11DIL
DILR31+TPE11DIL
DILR31+TPD11DIL
DILR40+TPE11DIL
DILR40+TPD11DIL

136

16

(-G)
(-G)
(-G)
(-G)
(-G)
(-G)

161

DILR22+VDIL
DILR31+VDIL
DILR40+VDIL

(-G)
(-G)
(-G)

137

162

Electronic timing relays


DILET... + HDILE
43

52

45

M4

45

58

58

5,5

45

Electronic timing relays

Remote potentiometer

ETR4-11...
ETR4-51...
ETR4-69...
ETR4-70...

RR-10

50

DILET...

65,3

35

2...8

103
98

22,5

12,5

78

82,5

3,2

22,5

29
17
29
48

04/067

Moeller HPL0211-2001/2002

ESR Electronic Safety Relays, EMR4 Measuring and Monitoring Relays


Dimensions

3.8

Relays
Contactor Relays

75

52.5

Electronic safety relays


ESR3-NO-31(230 V)

107

45

120.5

ESR4-NO-31
ESR4-NO-21
ESR4-NM-21
ESR4-NZ-21
ESR4-NV3(30)-30
ESR4-NT30-30
ESR4-NE-42
ESR4-VE3-42

99

111.5

22.5

114

Measuring and monitoring relays


EMR4-...
109.5

102
b

78

EMR4-I1-2-A
EMR4-I15-2-A
EMR4-I15-2-B
EMR4-F500-2
EMR4-W500-2-C
EMR4-W500-2-D
EMR4-W580-2-C
EMR4-A400-1
EMR4-N100-1-B
EMR4-N500-2-B
EMR4-N500-1-A
EMR4-RDC-1-A
EMR4-RAC-1-A

22.5

45

5.5

1
100

68.5

68.5

Sealable shroud
EMR4-PH...

22.5

45

b
K
K
K

K
K
K
K
K
K

K
K
K
K

Potrebbero piacerti anche